This is a Hood Fire Suppression System inspection report for Building 1540 Popeyes at Luke Air Force Base in Litchfield Park, AZ. The inspection was conducted by A P Fire Protection (ROC 251919/251920) on May 3, 2024, by technician Cody Buckmaster.
The report indicates a successful 6-month inspection of a Pyro-Chem wet system (PCL-300/460 cylinders) installed in 2015. All critical components passed inspection, including nozzle protection, fusible links, remote pull stations, gas valve operation, and system monitoring. The system includes 5 fusible links (450 ML), with cylinder hydro test dates due in 2027/2029. Emergency monitoring is provided by the Emergency Communication Center (623-856-6641). The inspection covered fryer protection, duct and plenum nozzles, and all required safety mechanisms, with all items meeting NFPA 17, 17A, and 96 standards.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Results Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass N/A Pass Light Pass
Hood Fire Suppression System Report (Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)
Location Names BLDG 1540 Popeye's # 1 Address Luke Air Force Base
City, State, Zip Litchfield Park, AZ Technician Cody Buckmaster
Location Contact Darryel Abraham Location Phone Number 916-893-8045 Monitoring Company Emergency Communication Center Monitoring Company Number 623-856-6641
Date 5/3/2024
C-16 ROC 251919 CR-67 ROC 251920
Account Number Password Location of System/Cylinder(s) In the back on the wall Inspection Type 6-Month
Manufacturer Pyro-Chem #3 Cylinder Slave Size PCL-460 Serial Number Size of Activation Cartridge 16 Gram
System Type wet #1 Cylinder Size PCL-300 Model Number MCH #2 Cylinder Slave Size PCL-300
Last Recharge Date N/A Number of Fusible Links 5 Best Time to Service 7am Type of Fusible Links 450 ML
Original System Install Date 2015 Date of Activation Cartridge 2023 Cylinder 12 Year Hydro Test Date 2027 Location of Shut Off/Valves Above Ceiling
Check If Seals Intact, Evidence of Tampering Pass
Item(s) CheckedItem(s) Checked
Duct and Plenum Nozzle Protection (List Model/Type/Position)
Appliance Line Up Left To Right (Size of Hazards/Nozzle Coverage Description)
Fryer Fryer FryerFryer
Fryer
Remote Pull 42"-48" From Floor (N.F.P.A. 17A)
All Appliances Properly Covered With Correct Nozzles Pass Duct and Plenum Covered With Correct Nozzles Pass
Check Positioning/Condition of All Nozzles Pass
Results
Inspect Cylinder/Wall Mount Bracket(s) Pass
Remote Station(s) Have Signage (N.F.P.A. 17A) Replace System Cover(s)
System Operational & Seals In Place Slave Cylinder Operational
If System Has Been Discharged, Report Same N/A Is Pressure Gauge In Proper Range (If Gauged) N/A
Check Cartridge Weight (If Applicable) Pass
Is System Installed Accordance With Manufacturer UL Listing Pass Hood & Duct Penetrations Sealed With Weld or UL Device Pass
Operated System From Terminal Link Pass Test for Proper Operation From Remote Pull Station Pass
12 Year Hydro Cylinder Test Date 2029 12 Year Regulator Test Date (Ansul) 2029
1/4' Gas Valve Hose Assembly Test Date 2029
Clean Cylinders/Wall Mount Brackets
Grease Filters Aluminum/Stainless Steel (N.F.P.A. 96) Pass
Replaced Fusible Link(s) Check Travel of Cable Nut/S-Hooks
All Piping Conduit Securely Bracketed Proper Separation/Fryer & Flames (N.F.P.A. 90A)
Proper Clearance of Flames To Filter Exhaust Fan in Operating Order
When System Activated Did Make-Up Air Shutdown Fuel Shut Off In Position
Wipe Grease Off Nozzles (Surface Cleaning Only) Pass Visually Check All Fusible Links Pass
Did System Report to Fire Alarm Panel/Monitoring Pass
Check Operation of Micro-Switch(s) Pass
Date of The Last Hood/Duct/Plenum Cleaning Accumulation of Grease In Hood
Exhaust Fan Warning Sign On Hood Personnel Instructed In Operation Of System
K-Class Extinguisher(s) Properly Serviced Portable Fire Extinguisher(s) Properly Serviced
Certification Tag Place On System & Remote System Equipped With Water Mist/Water Wash
Check Operation of Gas Valve(s) Pass Proper Nozzle Covers/Caps/Seals In Place Pass
Puff Test Completed Pass Is Suppression System Compliant
A P Fire Protection www.apfireprotection.com
7612 N 71st Ave, Glendale, AZ 85303 Phone: (623) 772-5344 Fax: (623) 772-5384
Page 1 of 2 REV 04-2020
C-16 ROC 251919 CR-67 ROC 251920
Location Contact Darryel Abraham Location Phone Number 916-893-8045
Notes/Deficiencies
Monitoring Company Emergency Communication Center Monitoring Company Number 623-856-6641 Account Number Password
Hood Fire Suppression System Report (Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)
Location Names BLDG 1540 Popeye's & Charlies Address Luke Air Force Base
City, State, Zip Litchfield Park, AZ Technician Cody Buckmaster
Date 5/3/2024
A P Fire Protection www.apfireprotection.com
7612 N 71st Ave, Glendale, AZ 85303 Phone: (623) 772-5344 Fax: (623) 772-5384
Page 2 of 2 REV 04-2020