Bldg 2202 Falcons Dune Golf Course.pdf

PDF 117 KB Posted

Attached to
Kitchen Fire Suppression Inspection & Maintenance
Solicitation number
FA488725Q0006
Issued by

About this file

This is a Hood Fire Suppression System inspection report for Building 2202 Falcons Dune Golf Course at Luke Air Force Base in Litchfield Park, AZ, dated April 18, 2024. The report indicates a Pyro-Chem wet system (Model PCL-600) was inspected, with all critical components passing inspection including nozzle protection, cylinder conditions, pressure gauges, fusible links, and operational tests. The system was originally installed in 2010, last recharged in 2022, with a 12-year hydro test date of 2034.

The inspection details cover a kitchen fire suppression system protecting multiple appliances including fryers, griddle/flat top, and a 2-burner stove. The system includes 4 fusible links (450ML), remote pull stations, and proper gas valve operations. The inspection was performed by technician Cody Buckmaster from A P Fire Protection (ROC 251919/251920). This report appears to be documentation related to the federal contract opportunity FA488725Q0006 for Kitchen Fire Suppression Inspection & Maintenance services at Luke AFB.

View the file

Other files

Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Results

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

N/A

Pass

Pass

Pass

Pass

Pass

Pass

N/A

Pass

Light

Pass

Hood Fire Suppression System Report

(Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)

Location Names Bldg 2202 Falcons Dune Golf Course

Address LAFB

City, State, Zip Litchfield Park, AZ

Technician Cody Buckmaster

Location Contact Peter Location Phone Number

Monitoring Company Alarm Guy took care of this Monitoring Company Number

Date 4/18/20248

C-16 ROC 251919 CR-67 ROC 251920

Account Number Password

Location of System/Cylinder(s) Right of Hood Inspection Type 6-Month

Manufacturer Pyro-Chem #3 Cylinder Slave Size

Serial Number Size of Activation Cartridge 16 Gram

System Type Wet #1 Cylinder Size PCL-600 Model Number MCH #2 Cylinder Slave Size

Last Recharge Date 2022 Number of Fusible Links 4 Best Time to Service 10am Type of Fusible Links 450ML

Original System Install Date 2010 Date of Activation Cartridge Jul-22 Cylinder 12 Year Hydro Test Date 2034 Location of Shut Off/Valves Behind Appliances

Check If Seals Intact, Evidence of Tampering Pass

Item(s) CheckedItem(s) Checked

Duct and Plenum Nozzle Protection (List Model/Type/Position)

Appliance Line Up Left To Right (Size of Hazards/Nozzle Coverage Description)

Fryer Fryer GriddleFlat Top

2 Burner Stove

Remote Pull 42"-48" From Floor (N.F.P.A. 17A)

All Appliances Properly Covered With Correct Nozzles Pass

Duct and Plenum Covered With Correct Nozzles Pass

Check Positioning/Condition of All Nozzles Pass

Results

Inspect Cylinder/Wall Mount Bracket(s) Pass

Remote Station(s) Have Signage (N.F.P.A. 17A)

Replace System Cover(s)

System Operational & Seals In Place

Slave Cylinder Operational

If System Has Been Discharged, Report Same N/A

Is Pressure Gauge In Proper Range (If Gauged) Pass

Check Cartridge Weight (If Applicable) Pass

Is System Installed Accordance With Manufacturer UL Listing Pass

Hood & Duct Penetrations Sealed With Weld or UL Device Pass

Operated System From Terminal Link Pass

Test for Proper Operation From Remote Pull Station Pass

12 Year Hydro Cylinder Test Date 2034

12 Year Regulator Test Date (Ansul) N/A

1/4' Gas Valve Hose Assembly Test Date N/A

Clean Cylinders/Wall Mount Brackets

Grease Filters Aluminum/Stainless Steel (N.F.P.A. 96) Pass

Replaced Fusible Link(s)

Check Travel of Cable Nut/S-Hooks

All Piping Conduit Securely Bracketed

Proper Separation/Fryer & Flames (N.F.P.A. 90A)

Proper Clearance of Flames To Filter

Exhaust Fan in Operating Order

When System Activated Did Make-Up Air Shutdown

Fuel Shut Off In Position

Wipe Grease Off Nozzles (Surface Cleaning Only) Pass

Visually Check All Fusible Links Pass

Did System Report to Fire Alarm Panel/Monitoring Pass

Check Operation of Micro-Switch(s) Pass

Date of The Last Hood/Duct/Plenum Cleaning

Accumulation of Grease In Hood

Exhaust Fan Warning Sign On Hood

Personnel Instructed In Operation Of System

K-Class Extinguisher(s) Properly Serviced

Portable Fire Extinguisher(s) Properly Serviced

Certification Tag Place On System & Remote

System Equipped With Water Mist/Water Wash

Check Operation of Gas Valve(s) Pass

Proper Nozzle Covers/Caps/Seals In Place Pass

Puff Test Completed Pass Is Suppression System Compliant

A P Fire Protection www.apfireprotection.com

7612 N 71st Ave, Glendale, AZ 85303

Phone: (623) 772-5344 Fax: (623) 772-5384

Page 1 of 2 REV 04-2020

C-16 ROC 251919 CR-67 ROC 251920

Location Contact Location Phone Number

Notes/Deficiencies

Monitoring Company Monitoring Company Number

Account Number Password

Hood Fire Suppression System Report

(Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)

Location Names Bldg 2202 Falcons Dune Golf Course

Address LAFB

City, State, Zip Litchfield Park, AZ

Technician Cody Buckmaster

Date 4/18/2024

A P Fire Protection www.apfireprotection.com

7612 N 71st Ave, Glendale, AZ 85303

Phone: (623) 772-5344 Fax: (623) 772-5384

Page 2 of 2 REV 04-2020