Bldg 2202 Falcons Dune Golf Course.pdf
PDF 117 KB Posted
- Solicitation number
- FA488725Q0006
About this file
This is a Hood Fire Suppression System inspection report for Building 2202 Falcons Dune Golf Course at Luke Air Force Base in Litchfield Park, AZ, dated April 18, 2024. The report indicates a Pyro-Chem wet system (Model PCL-600) was inspected, with all critical components passing inspection including nozzle protection, cylinder conditions, pressure gauges, fusible links, and operational tests. The system was originally installed in 2010, last recharged in 2022, with a 12-year hydro test date of 2034.
The inspection details cover a kitchen fire suppression system protecting multiple appliances including fryers, griddle/flat top, and a 2-burner stove. The system includes 4 fusible links (450ML), remote pull stations, and proper gas valve operations. The inspection was performed by technician Cody Buckmaster from A P Fire Protection (ROC 251919/251920). This report appears to be documentation related to the federal contract opportunity FA488725Q0006 for Kitchen Fire Suppression Inspection & Maintenance services at Luke AFB.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Results
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
N/A
Pass
Pass
Pass
Pass
Pass
Pass
N/A
Pass
Light
Pass
Hood Fire Suppression System Report
(Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)
Location Names Bldg 2202 Falcons Dune Golf Course
Address LAFB
City, State, Zip Litchfield Park, AZ
Technician Cody Buckmaster
Location Contact Peter Location Phone Number
Monitoring Company Alarm Guy took care of this Monitoring Company Number
Date 4/18/20248
C-16 ROC 251919 CR-67 ROC 251920
Account Number Password
Location of System/Cylinder(s) Right of Hood Inspection Type 6-Month
Manufacturer Pyro-Chem #3 Cylinder Slave Size
Serial Number Size of Activation Cartridge 16 Gram
System Type Wet #1 Cylinder Size PCL-600 Model Number MCH #2 Cylinder Slave Size
Last Recharge Date 2022 Number of Fusible Links 4 Best Time to Service 10am Type of Fusible Links 450ML
Original System Install Date 2010 Date of Activation Cartridge Jul-22 Cylinder 12 Year Hydro Test Date 2034 Location of Shut Off/Valves Behind Appliances
Check If Seals Intact, Evidence of Tampering Pass
Item(s) CheckedItem(s) Checked
Duct and Plenum Nozzle Protection (List Model/Type/Position)
Appliance Line Up Left To Right (Size of Hazards/Nozzle Coverage Description)
Fryer Fryer GriddleFlat Top
2 Burner Stove
Remote Pull 42"-48" From Floor (N.F.P.A. 17A)
All Appliances Properly Covered With Correct Nozzles Pass
Duct and Plenum Covered With Correct Nozzles Pass
Check Positioning/Condition of All Nozzles Pass
Results
Inspect Cylinder/Wall Mount Bracket(s) Pass
Remote Station(s) Have Signage (N.F.P.A. 17A)
Replace System Cover(s)
System Operational & Seals In Place
Slave Cylinder Operational
If System Has Been Discharged, Report Same N/A
Is Pressure Gauge In Proper Range (If Gauged) Pass
Check Cartridge Weight (If Applicable) Pass
Is System Installed Accordance With Manufacturer UL Listing Pass
Hood & Duct Penetrations Sealed With Weld or UL Device Pass
Operated System From Terminal Link Pass
Test for Proper Operation From Remote Pull Station Pass
12 Year Hydro Cylinder Test Date 2034
12 Year Regulator Test Date (Ansul) N/A
1/4' Gas Valve Hose Assembly Test Date N/A
Clean Cylinders/Wall Mount Brackets
Grease Filters Aluminum/Stainless Steel (N.F.P.A. 96) Pass
Replaced Fusible Link(s)
Check Travel of Cable Nut/S-Hooks
All Piping Conduit Securely Bracketed
Proper Separation/Fryer & Flames (N.F.P.A. 90A)
Proper Clearance of Flames To Filter
Exhaust Fan in Operating Order
When System Activated Did Make-Up Air Shutdown
Fuel Shut Off In Position
Wipe Grease Off Nozzles (Surface Cleaning Only) Pass
Visually Check All Fusible Links Pass
Did System Report to Fire Alarm Panel/Monitoring Pass
Check Operation of Micro-Switch(s) Pass
Date of The Last Hood/Duct/Plenum Cleaning
Accumulation of Grease In Hood
Exhaust Fan Warning Sign On Hood
Personnel Instructed In Operation Of System
K-Class Extinguisher(s) Properly Serviced
Portable Fire Extinguisher(s) Properly Serviced
Certification Tag Place On System & Remote
System Equipped With Water Mist/Water Wash
Check Operation of Gas Valve(s) Pass
Proper Nozzle Covers/Caps/Seals In Place Pass
Puff Test Completed Pass Is Suppression System Compliant
A P Fire Protection www.apfireprotection.com
7612 N 71st Ave, Glendale, AZ 85303
Phone: (623) 772-5344 Fax: (623) 772-5384
Page 1 of 2 REV 04-2020
C-16 ROC 251919 CR-67 ROC 251920
Location Contact Location Phone Number
Notes/Deficiencies
Monitoring Company Monitoring Company Number
Account Number Password
Hood Fire Suppression System Report
(Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)
Location Names Bldg 2202 Falcons Dune Golf Course
Address LAFB
City, State, Zip Litchfield Park, AZ
Technician Cody Buckmaster
Date 4/18/2024
A P Fire Protection www.apfireprotection.com
7612 N 71st Ave, Glendale, AZ 85303
Phone: (623) 772-5344 Fax: (623) 772-5384
Page 2 of 2 REV 04-2020