BLDG 161 Club 56.pdf
PDF 133 KB Posted
- Solicitation number
- FA488725Q0006
About this file
This is a Hood Fire Suppression System inspection report for Building 161 Club 56 at Luke Air Force Base in Litchfield Park, AZ, conducted on April 11, 2024 by A P Fire Protection technician Cody Buckmaster. The report documents a comprehensive inspection of a Pyro-Chem wet system with PCL-460 and PCL-300 cylinders, which includes six 450ML fusible links and covers kitchen equipment including fryers, a 10-burner stove, ovens, and tilt skillet.
The inspection results indicate all components passed testing requirements per NFPA 17, 17A, and 96 standards, including proper nozzle coverage, cylinder pressure, remote pull stations, gas valve operation, and monitoring system connectivity to the Emergency Communication Center (623-856-6641). The system's cylinder hydro test date is 2027, and the activation cartridge was last replaced in September 2023. The contact person for the facility is Darryel Abraham Jr. (916-893-8045), and the optimal service time is noted as 7:30.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Results
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
N/A
Pass
Light
Pass
Hood Fire Suppression System Report
(Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)
Location Names BLDG 161 Club 56 Luke Air Force Base
Address BLDG 161 Club 56
City, State, Zip Litchfield Park, AZ
Technician Cody Buckmaster
Location Contact Darryel Abraham Jr Location Phone Number 916-893-8045 Monitoring Company Emergency Communication Center Monitoring Company Number 623-856-6641
Date 4/11/20248
C-16 ROC 251919 CR-67 ROC 251920
Account Number Password
Location of System/Cylinder(s) Right of Hood Inspection Type 6-Month
Manufacturer Pyro-Chem #3 Cylinder Slave Size
Serial Number Size of Activation Cartridge 16 Gram
System Type Wet #1 Cylinder Size PCL-460 Model Number NMCH3 #2 Cylinder Slave Size PCL-300
Last Recharge Date N/A Number of Fusible Links 6 Best Time to Service 7:30 Type of Fusible Links 450ML
Original System Install Date 2015 Date of Activation Cartridge Sep-23 Cylinder 12 Year Hydro Test Date 2027 Location of Shut Off/Valves Behind Appliances
Check If Seals Intact, Evidence of Tampering Pass
Item(s) CheckedItem(s) Checked
Duct and Plenum Nozzle Protection (List Model/Type/Position)
Appliance Line Up Left To Right (Size of Hazards/Nozzle Coverage Description)
Fryer (2H) 10 Burner (1H, 1H, 2L) OvenTilt Skillet (2H, 2H)
Oven Oven
Remote Pull 42"-48" From Floor (N.F.P.A. 17A)
All Appliances Properly Covered With Correct Nozzles Pass
Duct and Plenum Covered With Correct Nozzles Pass
Check Positioning/Condition of All Nozzles Pass
Results
Inspect Cylinder/Wall Mount Bracket(s) Pass
Remote Station(s) Have Signage (N.F.P.A. 17A)
Replace System Cover(s)
System Operational & Seals In Place
Slave Cylinder Operational
If System Has Been Discharged, Report Same N/A
Is Pressure Gauge In Proper Range (If Gauged) Pass
Check Cartridge Weight (If Applicable) Pass
Is System Installed Accordance With Manufacturer UL Listing Pass
Hood & Duct Penetrations Sealed With Weld or UL Device Pass
Operated System From Terminal Link Pass
Test for Proper Operation From Remote Pull Station Pass
12 Year Hydro Cylinder Test Date 2027
12 Year Regulator Test Date (Ansul) N/A
1/4' Gas Valve Hose Assembly Test Date Pass
Clean Cylinders/Wall Mount Brackets
Grease Filters Aluminum/Stainless Steel (N.F.P.A. 96) Pass
Replaced Fusible Link(s)
Check Travel of Cable Nut/S-Hooks
All Piping Conduit Securely Bracketed
Proper Separation/Fryer & Flames (N.F.P.A. 90A)
Proper Clearance of Flames To Filter
Exhaust Fan in Operating Order
When System Activated Did Make-Up Air Shutdown
Fuel Shut Off In Position
Wipe Grease Off Nozzles (Surface Cleaning Only) Pass
Visually Check All Fusible Links Pass
Did System Report to Fire Alarm Panel/Monitoring Pass
Check Operation of Micro-Switch(s) Pass
Date of The Last Hood/Duct/Plenum Cleaning
Accumulation of Grease In Hood
Exhaust Fan Warning Sign On Hood
Personnel Instructed In Operation Of System
K-Class Extinguisher(s) Properly Serviced
Portable Fire Extinguisher(s) Properly Serviced
Certification Tag Place On System & Remote
System Equipped With Water Mist/Water Wash
Check Operation of Gas Valve(s) Pass
Proper Nozzle Covers/Caps/Seals In Place Pass
Puff Test Completed Pass Is Suppression System Compliant
A P Fire Protection www.apfireprotection.com
7612 N 71st Ave, Glendale, AZ 85303
Phone: (623) 772-5344 Fax: (623) 772-5384
Page 1 of 2 REV 04-2020
C-16 ROC 251919 CR-67 ROC 251920
Location Contact Darryel Abraham Jr Location Phone Number 916-893-8045
Note: Breaker in Panel K-5
Notes/Deficiencies
Monitoring Company Emergency Communication Center Monitoring Company Number 623-856-6641 Account Number Password
Hood Fire Suppression System Report
(Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)
Location Names BLDG 161 Club 56 Luke Air Force Base
Address BLDG 161 Club 56
City, State, Zip Litchfield Park, AZ
Technician Cody Buckmaster
Date 4/11/2024
A P Fire Protection www.apfireprotection.com
7612 N 71st Ave, Glendale, AZ 85303
Phone: (623) 772-5344 Fax: (623) 772-5384
Page 2 of 2 REV 04-2020