BLDG 161 Club 56.pdf

PDF 133 KB Posted

Attached to
Kitchen Fire Suppression Inspection & Maintenance
Solicitation number
FA488725Q0006
Issued by

About this file

This is a Hood Fire Suppression System inspection report for Building 161 Club 56 at Luke Air Force Base in Litchfield Park, AZ, conducted on April 11, 2024 by A P Fire Protection technician Cody Buckmaster. The report documents a comprehensive inspection of a Pyro-Chem wet system with PCL-460 and PCL-300 cylinders, which includes six 450ML fusible links and covers kitchen equipment including fryers, a 10-burner stove, ovens, and tilt skillet.

The inspection results indicate all components passed testing requirements per NFPA 17, 17A, and 96 standards, including proper nozzle coverage, cylinder pressure, remote pull stations, gas valve operation, and monitoring system connectivity to the Emergency Communication Center (623-856-6641). The system's cylinder hydro test date is 2027, and the activation cartridge was last replaced in September 2023. The contact person for the facility is Darryel Abraham Jr. (916-893-8045), and the optimal service time is noted as 7:30.

View the file

Other files

Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Results

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

N/A

Pass

Light

Pass

Hood Fire Suppression System Report

(Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)

Location Names BLDG 161 Club 56 Luke Air Force Base

Address BLDG 161 Club 56

City, State, Zip Litchfield Park, AZ

Technician Cody Buckmaster

Location Contact Darryel Abraham Jr Location Phone Number 916-893-8045 Monitoring Company Emergency Communication Center Monitoring Company Number 623-856-6641

Date 4/11/20248

C-16 ROC 251919 CR-67 ROC 251920

Account Number Password

Location of System/Cylinder(s) Right of Hood Inspection Type 6-Month

Manufacturer Pyro-Chem #3 Cylinder Slave Size

Serial Number Size of Activation Cartridge 16 Gram

System Type Wet #1 Cylinder Size PCL-460 Model Number NMCH3 #2 Cylinder Slave Size PCL-300

Last Recharge Date N/A Number of Fusible Links 6 Best Time to Service 7:30 Type of Fusible Links 450ML

Original System Install Date 2015 Date of Activation Cartridge Sep-23 Cylinder 12 Year Hydro Test Date 2027 Location of Shut Off/Valves Behind Appliances

Check If Seals Intact, Evidence of Tampering Pass

Item(s) CheckedItem(s) Checked

Duct and Plenum Nozzle Protection (List Model/Type/Position)

Appliance Line Up Left To Right (Size of Hazards/Nozzle Coverage Description)

Fryer (2H) 10 Burner (1H, 1H, 2L) OvenTilt Skillet (2H, 2H)

Oven Oven

Remote Pull 42"-48" From Floor (N.F.P.A. 17A)

All Appliances Properly Covered With Correct Nozzles Pass

Duct and Plenum Covered With Correct Nozzles Pass

Check Positioning/Condition of All Nozzles Pass

Results

Inspect Cylinder/Wall Mount Bracket(s) Pass

Remote Station(s) Have Signage (N.F.P.A. 17A)

Replace System Cover(s)

System Operational & Seals In Place

Slave Cylinder Operational

If System Has Been Discharged, Report Same N/A

Is Pressure Gauge In Proper Range (If Gauged) Pass

Check Cartridge Weight (If Applicable) Pass

Is System Installed Accordance With Manufacturer UL Listing Pass

Hood & Duct Penetrations Sealed With Weld or UL Device Pass

Operated System From Terminal Link Pass

Test for Proper Operation From Remote Pull Station Pass

12 Year Hydro Cylinder Test Date 2027

12 Year Regulator Test Date (Ansul) N/A

1/4' Gas Valve Hose Assembly Test Date Pass

Clean Cylinders/Wall Mount Brackets

Grease Filters Aluminum/Stainless Steel (N.F.P.A. 96) Pass

Replaced Fusible Link(s)

Check Travel of Cable Nut/S-Hooks

All Piping Conduit Securely Bracketed

Proper Separation/Fryer & Flames (N.F.P.A. 90A)

Proper Clearance of Flames To Filter

Exhaust Fan in Operating Order

When System Activated Did Make-Up Air Shutdown

Fuel Shut Off In Position

Wipe Grease Off Nozzles (Surface Cleaning Only) Pass

Visually Check All Fusible Links Pass

Did System Report to Fire Alarm Panel/Monitoring Pass

Check Operation of Micro-Switch(s) Pass

Date of The Last Hood/Duct/Plenum Cleaning

Accumulation of Grease In Hood

Exhaust Fan Warning Sign On Hood

Personnel Instructed In Operation Of System

K-Class Extinguisher(s) Properly Serviced

Portable Fire Extinguisher(s) Properly Serviced

Certification Tag Place On System & Remote

System Equipped With Water Mist/Water Wash

Check Operation of Gas Valve(s) Pass

Proper Nozzle Covers/Caps/Seals In Place Pass

Puff Test Completed Pass Is Suppression System Compliant

A P Fire Protection www.apfireprotection.com

7612 N 71st Ave, Glendale, AZ 85303

Phone: (623) 772-5344 Fax: (623) 772-5384

Page 1 of 2 REV 04-2020

C-16 ROC 251919 CR-67 ROC 251920

Location Contact Darryel Abraham Jr Location Phone Number 916-893-8045

Note: Breaker in Panel K-5

Notes/Deficiencies

Monitoring Company Emergency Communication Center Monitoring Company Number 623-856-6641 Account Number Password

Hood Fire Suppression System Report

(Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)

Location Names BLDG 161 Club 56 Luke Air Force Base

Address BLDG 161 Club 56

City, State, Zip Litchfield Park, AZ

Technician Cody Buckmaster

Date 4/11/2024

A P Fire Protection www.apfireprotection.com

7612 N 71st Ave, Glendale, AZ 85303

Phone: (623) 772-5344 Fax: (623) 772-5384

Page 2 of 2 REV 04-2020