Q and A Attachment 1 233113 Metal Ducts - Rectangular Double Wall.pdf

PDF 45 KB Posted

Attached to
Repair Maintenance Hanger, Bldg 700 Federal contract opportunity
Solicitation number
FA441821R0015
Issued by
Department of the Air Force Air Mobility Command

About this file

This document provides specifications for double-wall rectangular metal ducts and fittings. It outlines acceptable manufacturers, requirements for the outer and inner ducts to meet SMACNA standards for various pressure classes and joint types, and specifies flexible elastomeric duct liner with a maximum thermal conductivity of 0.25 Btu x in./h x sq. ft. x deg F at 75 deg F mean temperature and a minimum 0.028-inch solid sheet steel for the inner duct. Transverse and longitudinal joints must be fabricated according to SMACNA standards for the applicable pressure class, sealing requirements, materials, and support intervals.

The related federal contract opportunity is a solicitation for repair and maintenance services at Hanger Building 700 for the Department of the Air Force Air Mobility Command.

View the file

Other files for this federal contract opportunity

Other files attached to Repair Maintenance Hanger, Bldg 700, newest first.
File Type Posted
23 of 56 - A101 - FLOOR PLANS - 1 STORY AREA Rev 01 2021-07-13 (Q10).pdf PDF
17 of 56 - AD100 - DEMOLITION PLAN Rev 01 2021-07-13 (Q10).pdf PDF
8 of 056 - S201 - Typical Foundation Details Rev 01 2021-07-13.pdf PDF
5 of 056 - S000 - General Notes Rev 01 2021-07-13 (Q13).pdf PDF
B700 Pre-Proposal Questions and Answers 27 Jul 2021.xlsx XLSX spreadsheet
Solicitation Amendment FA441821R00150002 SF 30.pdf PDF
22 of 056 - A100 - FIRST FLOOR PLAN Rev 01 2021-07-13.pdf PDF
18 of 56 - AD120 - DEMOLITION CEILING PLAN Rev 01 2021-07-13.pdf PDF
01 30 00 Rev01 2021-07-15.pdf PDF
Roofing Q19.pdf PDF
6 of 056 - S101 - Foundation Plan Rev 01 2021-07-13 (Q7 and Q10).pdf PDF
Q and A Attachment 2 Answer to Question 16.png PNG image
B700 Pre-Proposal Questions and Answers.xlsx XLSX spreadsheet
Solicitation Amendment FA441821R00150001 SF 30.pdf PDF
JB Charleston - Offeror Inquiry Form FA44182R0015.xlsx XLSX spreadsheet
Attachment 9 Past Performance Questionnaire.pdf PDF
Attachment 1 Specs Repair Aircraft Maint Hangar B700.pdf PDF
Solicitation - FA441821R0015 FINAL.pdf PDF
Attachment 7 WD SC20210023.pdf PDF
Attachment 6 Asbestos and Lead Based Paint Survey Report.pdf PDF
Attachment 5 Repair Aircraft Maint Hangar Fire Systems B700 Drawing Set.pdf PDF
Attachment 4 Design Narrative Repair Aircraft Maint Hangar Fire Systems B700.pdf PDF
Attachment 3 Repair Aircraft Maint Hanger Drawing Set.pdf PDF
Attachment 2 Design Narrative Maintenance Hangar B700.pdf PDF
Attachment 8 Green Procurement Form.pdf PDF
Show all 25

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

233113 METAL DUCTS – DOUBLE WALL DUCT SUPPLEMENT

1.1 DOUBLE-WALL RECTANGULAR DUCTS AND FITTINGS

A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

1. McGill AirFlow LLC.

2. Sheet Metal Connectors, Inc.

B. Rectangular Ducts: Fabricate ducts with indicated dimensions for the inner duct.

C. Outer Duct: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and

Flexible" based on indicated static-pressure class unless otherwise indicated.

D. Transverse Joints: Select joint types and fabricate according to SMACNA's "HVAC Duct

Construction Standards - Metal and Flexible," Figure 2-1, "Rectangular Duct/Transverse Joints," for static-pressure class, applicable sealing requirements, materials involved, duct-support intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards - Metal and

Flexible."

E. Longitudinal Seams: Select seam types and fabricate according to SMACNA's "HVAC Duct

Construction Standards - Metal and Flexible," Figure 2-2, "Rectangular Duct/Longitudinal

Seams," for static-pressure class, applicable sealing requirements, materials involved, duct-support intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards -

Metal and Flexible."

F. Interstitial Insulation: Flexible elastomeric duct liner complying with ASTM C 534, Type II for sheet materials, and with NFPA 90A or NFPA 90B.

1. Maximum Thermal Conductivity: 0.25 Btu x in./h x sq. ft. x deg F at 75 deg F mean temperature.

G. Inner Duct: Minimum 0.028-inch solid sheet steel.

H. Formed-on Transverse Joints (Flanges): Select joint types and fabricate according to SMACNA's

"HVAC Duct Construction Standards - Metal and Flexible," Figure 2-1, "Rectangular

Duct/Traverse Joints," for static-pressure class, applicable sealing requirements, materials involved, duct-support intervals, and other provisions in SMACNA's "HVAC Duct Construction

Standards - Metal and Flexible."

I. Longitudinal Seams: Select seam types and fabricate according to SMACNA's "HVAC Duct

Construction Standards - Metal and Flexible," Figure 2-2, "Rectangular Duct/Longitudinal

Seams," for static-pressure class, applicable sealing requirements, materials involved, duct-support intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards -

Metal and Flexible."

http://www.specagent.com/LookUp/?ulid=3425&mf=04&mf=95&src=wd&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456812636&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456812637&mf=04&src=wd