This document provides foundation and construction details for repair and maintenance of Building 700 at Joint Base Charleston, South Carolina. The project includes typical footing, grade beam, slab edge, step footing, ladder base, column collar, bollard, new-to-existing slab joint, slab-on-grade joint, thickened slab edge, and foundation construction details. Reinforcing bar schedules and concrete specifications are also included. The related solicitation is for repair of Maintenance Hanger B-700 under Solicitation Number FA441821R0015 issued by the Department of the Air Force Air Mobility Command. Responses are due in accordance with the solicitation and any resulting contract will be awarded based on pricing and evaluation criteria specified therein.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
3"
NOTES:
1. DO NOT LOCATE CONSTRUCTION JOINTS IN COLUMN FOOTINGS OR ENLARGED SECTIONS OF
CONTINUOUS STRIP FOOTINGS.
2. EXTEND REINFORCING FROM FIRST POUR THRU BULKHEAD ADEQUATE DISTANCE TO
ENSURE A CLASS "B" SPLICE WITH REINFORCING FOR SECOND POUR.
2'-6 1/4"
CLASS "B" SPLICE
SEE GENERAL
NOTES
KEY JOINT FULL WIDTH OF FOOTING,
PROVIDE ONE KEY PER 12" OF
FOOTING THICKNESS
(1)-#5x36" SHEAR DOWEL
PER 12" OF FOOTING
WIDTH, TYP. TOP AND
BOTTOM
CONT. FOOTING REINFORCEMENT,
SEE SCHEDULES AND SECTIONS
3"
NOTES:
1. EXTEND REINFORCING FROM FIRST POUR THRU BULKHEAD ADEQUATE DISTANCE
TO ENSURE A CLASS "B" SPLICE WITH REINFORCING FOR SECOND POUR
2. BULKHEAD FOR FIRST POUR SHALL BE REMOVED AFTER INITIAL SET AND
CONCRETE ROUGHENED TO A MINIMUM 1/4" AMPLITUDE
3. LOCATE GRADE BEAM COLD JOINTS AT THIRD POINTS BETWEEN PILE CAPS
AND/OR SUPPORTING GRADE BEAMS
4. DO NOT LOCATED COLD JOINTS WITHIN REGIONS OF TOP OR BOTTOM BAR
SPLICES
5. G.C. SHALL COORDINATE LOCATION OF CONSTRUCTION JOINTS WITH REBAR
DETAILER TO ENSURE PROPER TOP AND BOTTOM BAR SPLICING, AND PROPER
NUMBER OF JOINT DOWEL BARS.
2'-1 3/8"
CLASS "B" SPLICE
SEE GENERAL
NOTES
KEY JOINT FULL WIDTH OF
GRADE/TIE BEAM
(2)-#9 x 9'-0" SHEAR DOWELS, TYP. TOP AND BOTTOM
TOP BARS, SEE SCHEDULE
SECOND
POUR
FIRST
POUR
BOTTOM BARS,
SEE SCHEDULE
EQ EQ
M
IN
COL.
CL
SEE PLAN
8"
C L R
T
Y P
3" CLR.
TYP.
ADJACENT GRADE
V A
R
IE
S
M
IN
NOTE:
SLAB SLOPES,
SEE PLAN.
4" SLAB W/ 3000 PSI
CONC.
(NORMAL WEIGHT), SEE
PLAN ALSO.
FORM WIRE MESH
DOWN
INTO FOOTING.
3/4" CHAMFER EDGE.
#4 CONT. NOSE BAR.
(2)-#5's CONT.
3000 PSI CONCRETE FOOTING.
SHEAR REINFORCING/
STIRRUPS, SEE
SCHEDULE FOR SIZE &
SPACING.
CONT. TOP
REINFORCING, SEE
SCHEDULE FOR SIZE &
QUANTITY.
TYPICAL TB1 FOOTING
SECTION DETAIL
SEE SCHEDULE FOR
SIZE & REINFORCING
S E
E S
C H
E D
CONT. BOTTOM
REINFORCING, SEE
SCHEDULE FOR SIZE &
QUANTITY.
A L L
S
ID
E
S
C
L R
T
Y P
135° HOOK
SHEAR REINF. STIRRUPS @
EA. INTERIOR BAR
NOTES:
1) PROVIDE STEP FOOTINGS AT ALL LOCATIONS INDICATED ON PLAN
2) PROVIDE STEP FOOTINGS AS REQUIRED TO AVOID PIPING AND OTHER MISC. MECHANICAL ITEMS
3) DO NOT STEP GRADE BEAM OR TIE BEAM FOOTING WITHOUT PRIOR APPROVAL FROM ENGINEER
18"
36"
#4 BENT NOSE BARS @ 6" O.C.
S E
E P
L A
N
M A
X
U .N
.O
TIE BARS, MATCH SIZE AND QUANTITY
OF MAIN FOOTING BARS
CLASS "B" SPLICE
SEE GENERAL
NOTES
CLASS "B" SPLICE
SEE GENERAL
NOTES
MAIN FOOTING
BARS,
SEE FOOTING
SCHEDULE
18"W.x12"D.xLENGTH
3000 PSI CONC.
1/4" BENT PLATE W/
1-5/8Øx6" EMBEDMENT
ANCHOR BOLT.
NEW SLAB
3/16
NEW STEEL LADDER, THE
LADDER SHALL BE
DESIGNED BY THE STEEL
SUPPLIER, AND SHALL
MEET ALL IBC AND OSHA
REQUIREMENTS.
1_
1/2" EXPANSION JOINT 1/2" EXPANSION JOINT
NEW SLAB
EDGE OF COLLAR, TYP.
M
IN
S E
E P
L A
N
M
IN
EDGE OF SLAB/ FACE OF BLOCK
STEP COLLAR INTO BRICK
SPACE BELOW GRADE AS
REQUIRED TO PROVIDE 3"
COVER ON BASE PLATE
BASE PLATE AND ANCHOR
BOLTS, SEE SPECIFIC
DETAILS
COLUMN, SEE PLAN AND
SCHEDULE FOR SIZE
NOTES:
1. TOP OF COLLAR SHALL MATCH TOP OF ADJACENT SLAB. COORDINATE WITH UPFIT SLAB REQUIREMENTS
2. PROVIDE #3 TIES (2-PIECE "U" SHAPED) @ 8" O.C. VERTICALLY IN COLLAR. MIN. NUMBER OF TIES SHALL BE (2)
3. STEP COLLAR INTO BRICK SPACE BELOW GRADE AS REQUIRED TO PROVIDE MINIMUM COVER
4. COAT COLUMN, BASE PLATE, AND ANCHOR RODS WITH ASPHALT PAINT PRIOR TO POURING CONCRETE
COLLAR.
5. DETAIL IS TYPICAL AT SLAB ON GRADE ONLY
6. COORDINATE COLLAR GEOMETRY WITH SPECIFIC PLAN DETAILS
3" MIN.3" MIN.
1'-6" Ø
6"
ROUNDED CONC.
TOP 1/2" CROWN
NOTE: BOLLARDS SHALL BE AS
REQUIRED BY OSHA
REGULATIONS. G.C. TO
COORD.
6"Ø CONC. FILLED STEEL PIPE
PAINT SAFETY YELLOW
1" CROWN
PAVING
GRANULAR FILL
STEEL PIPE SLEEVE
CONCRETE FOOTING
10x10x1/4" THICK
PLATE WELDED
ALL AROUND
NOTE: SEE ARCHITECTURAL
DRAWINGS FOR LOCATION
EXISTING SLAB NEW SLAB/FOOTING
6" 1'-0" UNO
NEW #4x1'-6" LONG DOWELS
@ 24" O.C. (DRILL & EPOXY
INTO EXISTING SLAB)
SLAB ON GRADE,
SEE PLAN
VAPOR
RETARDER
CAPILLARY BARRIER
AS INDICATED
EXISTING FILL, RECOMPACTED
PRIOR TO POURING NEW
SLAB/FOOTING
SLAB EDGES
#4x5'-0" RE-ENTRANT BAR
CONTROL JOINT, COORDINATE
WITH PLANS AND FINAL FIELD
LAYOUT OF CONTROL JOINTS
2"
2' -6
2' -6
FIRST POUR SECOND POUR
1'-0" 1'-0"
1/2"øx24" SMOOTH BARS @
24" O.C. (GREASE ONE END)
SLAB ON GRADE,
SEE PLAN
VAPOR
RETARDER
CAPILLARY BARRIER
AS INDICATED COMPACTED SUBGRADE
PLATE, THROUGH
CENTERLINE OF TUBE
STEEL
4" SLAB W/ WWM
ON COMPACTED FILL
SLIP CRITICAL CONNECTIONS DO NOT HDG,
GALVANIZE IN FIELD AFTER CONNECTION IS
FINAL. TYPICAL ALL CONNECTIONS SHOWN
HEREIN. DESIGN WELDED CONNECTIONS TO BE IN
ACCORDANCE WITH ALL CURRENT CODE
REQUIREMENTS, SEISMIC PROVISIONS AND ALL
SUBSEQUENT ADDENDUM'S TO THE CODE AND
SEISMIC PROVISIONS.
SEE TYPICAL DETAIL FOR BASE
PLATE ATTACHMENT
2" GROUT, TYPICAL
SEE PLAN
FOR
COLUMN SIZE
3000-PSI CONC. COLLAR
AROUND
COLUMNS, TYP.
TYP ALL
1'-0" M
IN
S E
E P
L A
N
S C
H E
D
T Y
P
S E
E P
L A
N
SEE PLAN/SCHED. FOR FTG. SIZE & REINF. REQUIREMENTS
1/2" EXPANSION JOINT MATERIAL
#4 DOWELS
SLAB ON GRADE W/
WWM, SEE PLAN.
#4 CONT. NOSE BAR.
8"
S E
E P
L A
N
M
IN
THICKENED SLAB EDGE W/
(2)-#4 CONT.
EXIST ASPHALT NEW CONC SLAB
COMPACTED
SUBGRADE
JOINT & WATERPROOFING
BY G.C.
EXISTING
ASPHALT
3" CLR. TYP.
SAW CUT EXISTING ASPHALT (TRUE)
PROVIDE CLEAN SMOOTH SURFACE FOR
BONDING NEW ASPHALT
4" SLAB W/ WWM
ON COMPACTED FILL
SEE TYPICAL DETAIL FOR BASE
PLATE ATTACHMENT
2" GROUT, TYPICAL
SEE PLAN
FOR
COLUMN SIZE
3000-PSI CONC. COLLAR
AROUND
COLUMNS, TYP.
S E
E P
L A
N
S C
H E
D
T Y
P
S E
E P
L A
N
SEE PLAN/SCHED. FOR FTG. SIZE & REINF. REQUIREMENTS
1/2" EXPANSION JOINT MATERIAL
#4 DOWELS
OIL PIT,
SEE PLAN
PLAN
SEE
COL.
CL
SEE PLAN
SLAB ON GRADE,
SEE PLAN
CAPILLARY BARRIER
AS INDICATED
COMPACTED SUBGRADE
EXISTING INTERIOR SLAB
EXISTING WALL BEYOND
EXISTING FOUNDATION
WALL
GC TO COORD. STEP/
ELEVATION
1/2" EXP'N JOINT
C E
R T
IF
ICATE OF AUTHOR
I Z A
T I O
NENGINEERING
ADC
NO. 00253
INC.
S O
U
T H
C A R O L
I N
A
G
E W
B
A IR AS
I N 62 8
T H
IR
A
D
MAN
CO
M
MO
IT Y
B I L
SEAL AREA
OFSHEET
D
AT
E
P R E P
B Y
A P P R 'D
RECORD DRAWING DATE
DRAWING SIZE:
PROJECT NO.
DE
PA
RT
M
EN
T O F
TH
E
AI
R
FO
RC
E
AI
R M O B
IL
IT
Y C O M M
AN
D
R E V
D A T E
D E S C R
IP
T
IO
N
D R A W
IN
G
R E V
IS
IO
N S
C H
K
BY
D
R
AW
N B
Y:
D
SG
N
B Y:
SU
PV
C H
E N
G R
G
LI
C K
/B O
E H
M
A S
S O
C
IA
TE
S
, I N
C
K
IN
G
S
TR
E E
T, S
U
IT
E
C H
A R
LE
S
TO
N
, S C
J O
IN
T
B A S E
C H A R L E S T O N
C H A R L E S T O N S C
ARCH E(30X42)
07/27/2017
R E V
IS
IO
N
C J G
C J G
S201
TY
PI
C
AL
F O U N
DA
TI
O N D
ET
AI
LS
A C P
A C P
C J G
JB
C
AB
B R
EP
AI
R A
IR
C R
AF
T
M
AI
N
TE
N
AN
C E H
AN
GE
R
ADC #17005.0
1" = 1'-0"1
TYP. FOOTING CONSTRUCTION
JOINT
1" = 1'-0"2 TYP. GB/TB SPLICE
1" = 1'-0"4 TYP. THICKENED SLAB EDGE
1" = 1'-0"3 TYP. GB/ TB FOOTING SECTION
1" = 1'-0"6 TYP. STEP FOOTING (AS NEEDED)
1" = 1'-0"12 TYP LADDER BASE DETAIL
1" = 1'-0"5
TYP. STEEL COLUMN COLLAR
(PERIMETER CONDITION)
1" = 1'-0"8 TYP. BOLLARD DETAIL
1" = 1'-0"9A
TYP. NEW-TO-EXISTING SLAB
CONSTRUCTION
3/4" = 1'-0"10ATYP. SLAB RE-ENTRANT CORNER
1" = 1'-0"9B
TYP. SLAB-ON-GRADE
CONSTRUCTION JOINT
1" = 1'-0"11 TYP. FOUNDATION DETAIL
No. 28196
S O
UTH CAROL INA
L
IC
E
N S
E D
P
R O
F E S S I ON
A
L E
N G
I N
E E
R
C H
R
IS
TOPHER J .
G
I L G
E R
1" = 1'-0"7B
SLAB - TYP. THICKENED SLAB EDGE
DETAIL FOR INTERIOR SLAB EDGES
1" = 1'-0"10BTYP. FOUNDATION @ PIT
1" = 1'-0"7A
TYPICAL SECTION @ EX. BUILDING/