SOW_Attachment_2_-_JBCGS_28_31_76_Interior_Fire_Alarm_System_ _Mass_Noti....pdf

PDF 141 KB Posted

Attached to
SABER IDIQ - Joint Base Charleston, SC Federal contract opportunity
Solicitation number
FA4418-16-R-0001
Issued by
Department of the Air Force Air Mobility Command

About this file

SOW ATCH 2

View the file

Other files for this federal contract opportunity

Other files attached to SABER IDIQ - Joint Base Charleston, SC, newest first.
File Type Posted
_4_Qs_ _As _FA4418-16-R-0001 _SABER_IDIQ.pdf PDF
Amendment_0003 _FA4418-16-R-0001 _SABER_IDIQ.pdf PDF
Atch_7__1_Sample_Project_-_SOW_Atch_14_-_Bldg_84 _Roof__Summary_Rpt_2.pdf PDF
Atch_8 __2_Sample_Project__-_SOW_Atch_6_-_Bldg_1 _Addendum__1 _7_Dec_15.pdf PDF
SOW__Attachment_12_-_Addendum__1 _7_Dec_15.pdf PDF
Atch_7 __1_Sample_Project_-_SOW_Atch_12_-_Bldg_84 _Roof_Survey.pdf PDF
Atch_7 __1_Sample_Project_-_SOW_Atch_11-_Bldg_84 _Addendum__1 _7_Dec_15.pdf PDF
Atch_7 __1_Sample_Project_-_SOW_Atch_13_-_Bldg_84 _Roof_Summary_Rpt_1.pdf PDF
Amendment_0002 _FA4418-16-R-0001 _SABER_IDIQ.pdf PDF
_2_Qs_ __As_FA4418-16-R-0001_SABER_IDIQ.pdf PDF
Ansi_E-34x44-Border.dwg DWG drawing
Arch_E-36x48-Border.dwg DWG drawing
_3_Qs_ _As_FA4418-16-R-0001_SABER_IDIQ.pdf PDF
Atch_7 __1_Sample_Project_-_SOW_Atch_7_Bldg_84_-_As-builts_Pt_5.pdf PDF
Atch_7 __1_Sample_Project_-_SOW_Atch_4_-_Bldg_84_-_As-builts_Pt_2.pdf PDF
Atch_7 ___1_Sample_Project_-_SOW_Atch_9_-_Bldg_84_-_As-builts_Pt_7.pdf PDF
Atch_7 __1_Sample_Project_-_SOW_Atch_10_Bldg_84_-_As-builts_Pt_8.pdf PDF
Atch_8 __2_Sample_Project_-_SOW_Atch_4_-_Bldg_1_-_As-builts-Current.pdf PDF
Atch_8 __2_SampleProject_-_SOW_Atch_5_-_Bldg_1_-_As-builts-Original.pdf PDF
Atch_7 __1_Sample_Project_-_SOW_Atch_5_-_Bldg_84_-_As-builts_Pt_3.pdf PDF
Atch_7 __1_Sample_Project_-_SOW_Atch_8_Bldg_84_-_As-builts_Pt_6.pdf PDF
_1_Qs_ _As _FA4418-16-R-0001 _SABER_IDIQ.pdf PDF
Atch_7 __1_Sample_Project_-_SOW_Atch_3_-_Bldg_84_-_As-builts_Pt_1.pdf PDF
Amendment_0001 _FA4418-16-R-0001 _SABER_IDIQ.pdf PDF
Atch_7 __1_Sample_Project_-_SOW_Atch_6_-_Bldg_84_-_As-builts_Pt_4.pdf PDF
Site_Visit_Min _Attendees-SABER.pdf PDF
Atch_9 _Past_Performance_Projects_List.docx DOCX document
Atch_3 _WD_SC29_Berkeley_5-22-15.pdf PDF
SOW_Attachment_3_-_JBC_Cable_Management_Policy.pdf PDF
Atch_8 __2_Sample_Project_-_SOW_Atch_2_-_Bldg_1_Conceptual_Floor_Plan.pdf PDF
Atch_7 __1_Sample_Project_-_SOW_Atch_1_-_Bldg_84_Floorplan.pdf PDF
SOW_Attachment_11_-_UFGS_Contractor_Special_Conditions_Safety_Requirements.pdf PDF
Atch_2 _WD_SC23_Orangeburg_1-02-15.pdf PDF
SOW_Attachment_9_-_NPTU_Contractor_Special_Conditions.pdf PDF
Atch_7 __1_Sample_Project_-_SOW_Atch_2_-_Bldg_84_Asbestos_Survey.pdf PDF
SOW_Attachment_8_-_Brig_Security_Requirements.pdf PDF
Atch_1 _SOW__Tech_Specs _16_Jul_15 _FA4418-16-R-0001 _SABER.pdf PDF
FA4418-16-R-0001 _SABER_IDIQ.pdf PDF
Atch_4 _WD_SC30_Charleston_5-22-15.pdf PDF
SOW_Attachment_6_-_JBCGS_01572_-_Waste_Management.pdf PDF
SOW_Attachment_1_-_JBC_ACP.PDF PDF
Atch_7 __1_Sample_Project_-_SOW_-_Bldg_84 _1_Aug_15.pdf PDF
SOW_Attachment_4_-_JBCGS_01501_-_Environmental.pdf PDF
Atch_8 __2_Sample_Project_-_SOW_-_Bldg_1 _17_Aug_15.pdf PDF
SOW_Attachment_5_-_JBCGS_01540_-_Green_Procurement.pdf PDF
Atch_6 _Green_Procument_Form.pdf PDF
Atch_5 _WD_SC31_Dorchester_5-22-15.pdf PDF
SOW_Attachment_10_-_UFGS_01_45_00_-_Quality_Control.pdf PDF
SOW_Attachment_7_-_JBCGS_01575_-_Temporary_Environmental_Controls.pdf PDF
Atch_8 __2_Sample_Project_-_SOW_Atch_1_-_Bldg_1_Existing_Floor_Plan.pdf PDF
Show all 50

SABER IDIQ - Joint Base Charleston, SC has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

JBC UFGS-28-31-76 (November 2013) Preparing Activity: Joint Base Charleston Superseding (JBC) UFGS-28 31 76 (February 2011) Charleston, SC

SECTION 28 31 76 (Modified specifically for use at JBC)

INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM

11/13

PART 1 GENERAL-LIFE SAFETY SYSTEM

This section establishes the requirements for an integrated fire detection, fire alarm system and mass notification system (FAS/MNS). Each FAS/MNS shall include only new components meeting the requirements of NFPA, FM, UL, and ADA standards, all applicable local, state and federal regulations, manufacturer’s recommendations, and specifications identified in this section.

Each FAS/MNS shall be a complete, supervised, non-coded, analog-addressable system, installed in a class A configuration per NFPA 72. The FAS/MNS shall provide point reporting to the FACP. The FACP shall in turn provide point reporting to the Monaco D-21 Central Receiving Station at the CAFB Fire Department. Point reporting, also known as point to point reporting, is the capability to relay the status of each addressable device and certain system components such as SLC’s to the D-21 in real time. The FAS/MNS shall be tested and perform as a critical life-safety system. The FAS/MNS shall be compatible with and shall communicate seamlessly with the D-21 without impairing operational function or reliability of any existing FAS or MNS.

1.1 RELATED SECTIONS

Section 07 84 00 FIRESTOPPING Section 08 71 00 DOOR HARDWARE for door release/door unlocking Section 14 24 00 HYDRAULIC ELEVATORS Section 23 00 00 AIR SUPPLY, DIST, VENTILATION, AND EXHAUST SYSTEMS Section 26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS

1.2 REFERENCES

The publications listed below form a part of this section to the extent referenced within the text. Unless otherwise noted the latest edition/revision of each publication available at the time of contract award shall apply.

SECTION 28 31 76 (JBC) Page 1

AIR FORCE

UFC 3-600-01 Fire Protection Engineering for Facilities

UFC 4-021-01 Design and O&M for Individual Building Mass Notification System

UFC 03-601-01 Facility Planning and Design Guide

UFC 04-010-01 DoD Minimum Antiterrorism Standards for Buildings

ACOUSTICAL SOCIETY OF AMERICA (ASA)

ASA S3.2 Method for Measuring the Intelligibility of Speech Over Communication Systems (ASA 85)

AMERICANS WITH DISABILITIES ACT (ADA)

AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)

ASME INTERNATIONAL (ASME)

ASME A17.1 Safety Code for Elevators and Escalators

FM GLOBAL (Factory Mutual)

FM P7825a Approval Guide Fire Protection

INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

IEEE C62.41.1 IEEE Guide on the Surges Environment in Low-Voltage (1000 V and Less) AC Power Circuits

IEEE C62.41.2 IEEE Recommended Practice on Characterization of Surges in Low-Voltage (1000 V and Less) AC Power Circuits

INTERNATIONAL ELECTROTECHNICAL COMMISSION (IEC)

IEC 60268-16 Sound System Equipment-Part 16: Objective Rating Of Speech Intelligibility by Speech Transmission Index

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 70 National Electrical Code

NFPA 72 National Fire Alarm Code

NFPA 90A STD for the Installation of AC and Ventilating Systems

NFPA 101 Life Safety Code, 2006 Edition

NFPA 170 Fire Safety Symbols

NFPA 241 Safeguarding Construction, Alt, & Demolition Operations

U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)

47 CFR 15 Radio Frequency Devices

SECTION 28 31 76 (JBC) Page 2

UNDERWRITERS LABORATORIES (UL)

UL 6 Rigid Metal Conduit

UL 228 Door Closers-Holders, With or W/O Integral Smoke Detectors

UL 268 Standard for Smoke Det for Fire Alarm Signaling Systems

UL 268A Smoke Detectors for Duct Application

UL 464 Standard for Audible Signal Appliances

UL 521 Heat Detectors for Fire Protective Signaling Systems

UL 797 Electrical Metallic Tubing-Steel

UL 864 Control Units and Accessories for Fire Alarm Systems

UL 1242 Electrical Intermediate Metal Conduit

UL 1480 Standard for Safety Speakers for Fire Alarm, Emergency, and Commercial and Professional Use

UL 1638 Visual Signaling Appliances Private Mode Emergency and General Utility Signaling

UL 1971 Signaling Devices for the Hearing Impaired

UL 2017 STD for Safety for Gen-Purpose Signaling Devices & Systems

UL Elect Construction Equipment Directory

UL Fire Protection Equipment Directory

OTHER ORGANIZATIONS

Central Intelligence Directive (DCID 6/9), Manual for Physical Security Standards for Sensitive Compartmented Information Facilities

1.3 DEFINITIONS

Equipment, devices and functions mentioned in this specification or on the drawings, as well as commonly used FAS equipment, are defined as follows:

a. Authority Having Jurisdiction (AHJ): The AHJ responsible for enforcing the requirements of applicable codes, standards, and for approving equipment, materials, installations, and procedures is the 628 Civil Engineer Squadron (628 CES).

b. Central Receiving Station: The central receiving station is an existing Factory Mutual approved Monaco Enterprises Inc. model D-21 Incident Management System transceiver located in the CAFB Fire Department, transmitting and receiving encoded radio signals in the 138 to 174 MHz VHF band at 138.925 MHz for JBC, communicating with the FAS/MNS

SECTION 28 31 76 (JBC) Page 3 transceiver at each CAFB building. Hereafter the central receiving station will be identified merely as “D-21.”

c. Analog/Addressable System: A system where multiple signals are transmitted via the same conduction path to a remote fire alarm control unit and fire alarm control panel, decoded and separated so that each signal will initiate the specified response.

d. Hard Wired System: A system where alarm and supervisory initiating devices are directly connected, through individual dedicated conductors, to a central control panel without the use of analog/addressable circuits or devices.

e. Interface Unit (Monitor Module): An addressable device which is connected to a non-addressable device for the purpose of relaying the status/condition of the non-addressable device to the analog/addressable

FACP.

f. Class A addressable system with point reporting: A Class A system as defined in NFPA 72 with each FAS device reporting individually to the FACP and the FACP continuously relaying that information to the D-21.

This system is also referred to as “device point reporting” or “point-to-point”. In device point reporting systems the status of each device is reported back to the D-21 through the FACP. This is in contrast to a zone reporting system wherein devices are lumped into zones. In a Class A system, devices are connected by circuits configured such that an open circuit on one or both of the incoming or outgoing conductors at the same location does not prevent reporting of all devices on the circuit.

g. Class B non-addressable system: Class B non-addressable circuits are 2 wire circuits which terminate in an end-of-line device as defined in NFPA 72. In Class B circuits, a single open (or break) in either conductor will disable all devices located between the open/break and the end of line device.

h. Notification Appliance Circuits (NACs): The FACP provides Class A NAC circuits to supply power to each notification appliance. Each NAC is monitored and controlled by the FACP for fire events and by the MNS panel for MNS events.

i. Signal Line Circuit (SLC): A SLC is one of up to 8 circuits reporting to the FACP, configured for Class A operation, with each circuit having the capacity to support up to 99 addressable sensors (smoke or heat) and up to 99 addressable modules (control, monitor, NAC, and interface). Alarm, supervisory or trouble conditions are transmitted by the FACP radio transmitter to the D-21 reporting the status of each individual device. Equipment and/or device faults, including command faults, missing device, early warning, maintenance alert, communications loss, IDC, NAC, SLC, power and battery faults are also transmitted by the FACP to the D-21 instantaneously.

j. Notification Appliance Circuit (NAC) Extenders: In the event the quantity of notification appliances exceeds the capacity of the FAS/MNS, NAC extenders must be provided to power those extra appliances. NAC extenders are controlled from the FACP/NAC circuits by means of a synchronization module. Each NAC extender has the capacity to provide power for up to 4 Class A NACs. Each NAC extender has its own 120 Volt AC

SECTION 28 31 76 (JBC) Page 4 primary power, backed up with batteries and a battery charger. NAC extenders are enclosed in a steel panel, red in color, keyed the same as the FACP. Each NAC extender is monitored by the FACP for trouble conditions. All NACs, IDCs, and SLCs remain functional if the conductors between them are severed at any common point.

k. Initiating Device Circuits (IDCs): The FACP provides two Class A or four Class B initiating device circuits. Each IDC system has an interconnected riser loop or network with Class A supervision for connection to FACP/MNS panels.

l. Remote Fire Alarm and Mass Notification Control Unit: A control panel, electronically remote from the fire alarm and mass notification control panel, that receives inputs from automatic and manual fire alarm devices;

may supply power to detection devices and interface devices; may provide transfer of power to the notification appliances; may provide transfer of condition to relays or devices connected to the control unit; and reports to and receives signals from the fire alarm control panel.

m. Fire Alarm and Mass Notification Control Panel (FACP/FMCP): A master control panel having the features of a fire alarm and mass notification control unit and fire alarm and mass notification control units are interconnected. The panel has central processing, memory, input and output terminals.

n. Riser Diagram: A riser diagram is a drawing showing the circuit connections to each of the FAS/MNS devices installed through-out each floor of the building, each sheet not less than 30” X 42,” including terminal cabinets, and junction boxes. A color code schedule shall be included for the wiring and a device legend listing the drawing symbols used for each device (per NFPA 170, Fire Safety Symbols). A table shall be included, listing the voltage, model number, catalog number, and manufacturer's name for each FAS/MNS component.

1.4 FIRE ALARM SYSTEM/MASS NOTIFICATION SYSTEM (FAS/MNS) DESCRIPTION

1.4.1 Scope

a. This work includes completion of design and providing a new, complete, analog/addressable fire alarm and mass notification system (FAS/MNS) as described herein and on the contract drawings for [building name]. Include in the system wiring, raceways, pull boxes, terminal cabinets, outlet and mounting boxes, control equipment, alarm, supervisory signal initiating devices, alarm notification appliances, supervising station fire alarm system transmitter, other accessories and miscellaneous items required for a complete operating system. Provide equipment, materials, installation, workmanship, inspection, and testing in strict accordance with the required and advisory provisions of NFPA 72, ISO 7240-16, IEC 60268-16, except as modified herein. The system layouts on the construction drawings show the intent of coverage and are shown in suggested locations. Final quantity, system layout, and coordination are the responsibility of the contractor.

b. The FAS/MNS shall be a Class A addressable system with point device point reporting. The CAFB Fire Department will observe the final inspection/test. After having passed the Fire Department inspection the

SECTION 28 31 76 (JBC) Page 5 system will be officially accepted and placed in service. To minimize the effect of lightning or electrical surges from damaging the equipment, all FAS/MNS equipment connected to building 120 VAC power shall be provided with surge protection. UL and FM listing/approval of each FAS/MNS device/component verifies that surge testing has been successfully performed on each individual component.

c. Provide equipment, materials, installation, workmanship, inspection, and testing in accordance with the required and advisory provisions of NFPA 72, ISO 7240-16, and IEC 60268-16, except as modified herein. The Contractor is responsible to coordinate with the CAFB Fire Department to determine final system design and quantities/locations of each FAS/MNS device.

1.4.2 Technical Data and Computer Software-For Training Course

Technical data specifically identified in this section shall be provided to the government on a CD-ROM. Drawings shall be in AutoCAD (2009) and portable document file (PDF) format. Contractor shall identify the data provided by reference to the particular paragraph of this section against which it is furnished. Data submitted shall include the complete FAS/MNS and all related devices and equipment. Technical data/descriptions shall verify how the equipment can operate as a system to meet the performance requirements of this section. The data package (as a minimum) shall include:

a. Programmable Features: Identification of all programmable portions of system equipment and capabilities.

b. Software Data for FAS/MNS: Provide software for all modes of programmable portions of the FAS and MNS system.

c. Description of Operation of FACP/MNS: Description of the operation of FAS/FACP and MNS.

d. Description of Operation of NACs/RDUs: Description of operation of notification appliance circuits (NACs) and remote display units (RDUs).

e. Operation and Maintenance (O&M) manual: An operating manual outlining step-by-step procedures required for system startup, operation, and shutdown shall be provided. The manual shall include the manufacturer's name, model number, service manual, parts list, and a complete description of each type of installed equipment and its operating features. The manual shall include a complete procedure for system revision and expansion, detailing both equipment and software requirements.

f. Database for FAS: A database shall be provided for the FAS, to handle not only current points installed, but to handle an additional 144 points without addition of hardware or modification to the software. In the event additional points must be added, the system topology and hardware configuration shall be such that it shall not require changes of computers, hard drives or any other electronic equipment.

g. Testing Reports/Drawings: The contractor shall provide (to the CAFB Fire Department) the NFPA Record of Completion and Inspection and Testing Reports, as-built drawings, including floor plans, wiring diagrams, point to point connection diagrams, programming information, and installation, instructions.

SECTION 28 31 76 (JBC) Page 6

1.4.3 Keys

Keys and locks for all FAS/MNS equipment panels shall be identical. Upon final acceptance of the FAS/MNS, contractor is to provide not less than six keys to the CAFB Fire Department. The JBC key code will be provided by the government.

1.5 SUBMITTALS

Provide three (3) copies of each submittal document. Government approval is required for submittals with a "G" designation.

SD-02 (SD-02 is to be provided to the government as a package not to exceed 45 days after final acceptance of the system):----------G

Shop Drawings: Include with shop data, annotated catalog, in table format, of the drawings, showing manufacturer's name, model, voltage, and catalog number for each installed device/equipment and all components.

Wiring Diagrams: Point-to-point wiring diagrams showing the points of connection and terminals used for electrical field connections of each FAS/MNS device in the system, including interconnections between the equipment and FAS/MNS systems that are supervised or controlled by each system. Diagrams shall show connections from speaker control panel, strobe panel, addressable devices, etc., to the FACP, RDU, IDC, MNS, switches, relays and terminals. The drawings shall include complete wiring diagrams, showing connections between devices and equipment, both factory and field wired. The drawings shall show the system as installed, including the location (room number, floor number, location within room, etc., of each device installed), battery calculations and voltage drop calculations, and any deviations from both the project drawings and the approved shop drawings.

System Layout: Plan view drawing of each floor of the building, showing floor number, room number, location within each room, terminal cabinet locations, junction boxes, other related equipment, conduit routing, wire counts, circuit identification in each conduit, and circuit layouts. Drawings shall comply with the requirements of NFPA 170, Fire Safety Symbols.

System Operation: List each device address and corresponding status message to appear on the FACP, MNS and the D-21.

Notification Appliances: Data from each Notification Appliance Circuit (NAC) Extender. Annotate data for each circuit on the drawings.

Riser Diagrams: Drawings showing the circuit connections of each of the FAS/MNS devices installed on each floor of the building, each sheet not smaller than 30” X 42,” including terminal cabinets, junction boxes, conduit routing, wire counts, circuit identification in each conduit, circuit layout, type and location of each device identified by floor number, room number, location within each room. A color code schedule shall be included for the wiring and a device legend listing the drawing symbols used for each device (per NFPA 170, Fire Safety

SECTION 28 31 76 (JBC) Page 7

Symbols). A table shall be included, listing the voltage, model number, manufacturer's name and catalog number for each component.

Amplifiers: Annotate amplifier data for each circuit on the drawings.

Full size drawings: Provide one set of full size paper as-built detailed drawings and schematics for the FAS and the MNS to the government. The drawings shall be prepared on uniform sized sheets not less than 30 inches by 42 inches with 8 inch by 4 inch title block.

Furnish three sets of CD-ROM discs containing software back-up in AutoCAD (2009) and PDF format of as-built drawings and schematics. All final FAS/MNS drawings shall be signed and stamped by a licensed Fire Protection Engineer with documented experience in fire alarm system design and codes.

Final as built drawings: At least one set of as-built (marked-up) drawings shall be provided prior to the final acceptance test.

Operation and Maintenance (O&M) Data/Instructions: Provide three (3) copies of O&M manuals, indexed and in spiral ring booklet form and on

CD/DVD.

SD-03 Product Data----------------------------------------------------G Provide copy of UL, FM or other nationally recognized testing laboratory approval for each of the following:

FAS and MNS firmware identification and/or revision;

Fire Alarm Control Panel (FACP); FM certification;

Mass Notification System (MNS) Panel;

Transmitters (including housing);

Battery chargers;

Smoke detectors/sensors;

Thermal (heat) detectors/sensors;

Wiring and cable;

Notification Appliance Circuit (NAC) Extenders;

Addressable Monitor, Relay Control & Mini-Modules;

Water flow detectors;

Tamper switches;

Electromagnetic door holders;

SD-05 Design Data-----------------------------------------------------G

Provide a complete description of the FAS and MNS system operation in matrix format on the drawings.

Battery power and load calculations

SD-06 Test Reports----------------------------------------------------G

Field Quality Control Testing Procedures

Smoke sensor testing procedures

SD-07 Certifications--------------------------------------------------G

Installer, Electrician, and Test personnel

SECTION 28 31 76 (JBC) Page 8

SD-09 Manufacturer's Field Reports------------------------------------G

Mass Notification System (MNS)

Include the MNS panel, initiating devices, indicating devices, a unique identifier for each device, with a report of test results with signature of the factory trained technician for the FACP as well as the equipment installer. The contractor shall complete the NFPA 72 “Record of Completion” and “Inspection and Testing” form, along with the appropriate test reports/signatures.

SD-10 Operation and Maintenance (O&M) Data/Instructions;--------------G

(Included in the “as built” package.)

1.6 QUALITY ASSURANCE

Compatibility with Existing Systems: All installed equipment and devices shall be compatible and operable with all existing FASs/MNSs and shall not impair reliability or operational function of the D-21.

a. Advisory provisions mandatory: In NFPA publications referred to herein, consider advisory provisions to be mandatory, as though the word “shall” had been substituted for “should” wherever it appears.

b. Manufacturer’s recommended practices mandatory: The recommended practices stated in the manufacturer’s literature or documentation for each device shall be considered as mandatory requirements.

c. Devices must be UL or FM listed: Unless otherwise noted, devices and equipment for FAS and MNS service shall be listed by UL Fire Prot Dir or approved by FM P7825a. Devices and equipment connected together shall be UL or FM listed as acceptable to be connected together.

1.6.1 Qualifications

1.6.1.1 Design Services

Installation drawings/specifications/modifications of fire detection, FAS, MNS, and fire suppression systems require certification/approval by a registered professional engineer having a Degree in Fire Protection Engineering (FPE) from an accredited university engineering program, plus a minimum of four years work experience in fire protection engineering.

1.6.1.2 Supervisor

On site supervision of FAS/MNS equipment installation shall be by a technician who has been factory trained by the manufacturer of the FACP/MNS panels in the installation, programming, adjustment, testing and operation of FAS/MNS, with a minimum of eight years experience installing FAS/MNS.

Verification of each Fire Alarm Supervisor’s qualifications shall include submission of a valid certification by the National Institute for Certification in Engineering Technologies (NICET-minimum Level III), in the subfield of Fire Protection Engineering Technology.

SECTION 28 31 76 (JBC) Page 9

1.6.1.3 Technician/Installer/Test Personnel

All FAS and MNS components and systems shall be installed by Fire Alarm Technicians who have a minimum of two years of experience to assist in the installation of FAS and MNS devices, cabinets and panels, and have been factory trained in the installation, programming, adjustment, testing and operation of FAS and MNS. Verification of each Fire Alarm Technician/ Installer/Test Personnel’s experience in performing this type of work shall include submission of a valid certification by the National Institute for Certification in Engineering Technologies (NICET-minimum Level II), in the subfield of Fire Protection Engineering Technology. A licensed electrician shall be used to install FAS/MNS conduit, wire and cable.

1.6.1.3.1 Technician-in-training

A Fire Alarm Technician who has not yet completed the NICET II certification shall be allowed to assist in the installation under the direct supervision of a NICET II certified technician.

1.6.1.4 Manufacturer’s Representative

The FACP and MNS equipment manufacturer’s representative (an employee of the manufacturer with technical training on the system being installed) shall be present for the connection of wiring to the FACP.

1.6.1.5 Manufacturer

MNS and FAS components shall be of current design and shall be in regular and current production at the time of installation. Provide design, materials, and devices for a protected premises fire alarm system and mass notification system, complete, conforming to NFPA 72, and as additionally specified herein.

1.6.2 Regulatory Requirements

All FAS and MNS equipment shall be listed for use under the applicable reference standards. If the software programming features cannot provide a listed interface control, interfacing of equipment listed by UL 864 or other listing with MNS panels listed by UL 2017 shall be done in a laboratory listed configuration. For field modifications, such as adding equipment like relays, the contractor shall provide details of the modification for review and confirmation to the government.

1.6.2.1 Requirements for Fire Protection Service/Equipment

Equipment and material shall be UL listed in UL Fire Prot Dir or approved by FM. The FACP must be listed in FM P7825a. Where the terms “listed” or “approved” appear in this specification, they shall mean listed in UL Fire Prot Dir or FM P7825a. The omission of these terms under the description of any item of equipment described shall not be construed as waiving this requirement. Note that, while a particular fire alarm system device may be individually UL or FM approved, it must be UL or FM approved to be connected to the FACP. While connecting one manufacturer’s FAS device to another manufacturer’s FAS device may be a “field accepted practice,” that is not sufficient: connecting any FAS device to the FACP must be certified by UL or FM as approved for that use.

SECTION 28 31 76 (JBC) Page 10

1.6.2.2 Mass Notification System (MNS)

The MNS equipment shall be compatible with the FACP, be UL listed, FM approved, or approved or listed by a nationally recognized testing laboratory for its intended use.

1.6.2.3 Testing Services or laboratories

FAS, MNS and fire detection equipment shall be constructed in accordance with UL Fire Protection Directory, UL Electrical Construction, or FM P7825a, and tested in accordance with NFPA 70 & 72, Class A Systems.

1.7 DELIVERY, STORAGE, AND HANDLING

While awaiting installation, all FAS and MNS equipment shall be protected from the weather, humidity, and temperature variation, dirt and dust, and other contaminants.

1.8 OPERATION AND MAINTENANCE (O&M) FAS/MNS INSTRUCTIONS

Fire Alarm System and Mass Notification System Operation and Maintenance (O&M) Instructions provided to the CAFB Fire Department shall include:

a. Manufacturer Data Package as specified in Section 01 78 23 OPERATION

AND MAINTENANCE DATA.

b. Operating manual outlining step-by-step procedures required for system startup, operation, and shutdown. The manual shall include the manufacturer's name, model number, service manual, parts list, and a complete description of each type of installed equipment and its operating features. The manual shall include a complete procedure for system revision and expansion, detailing both equipment and software requirements.

c. Maintenance Manual including a list of routine maintenance procedures, list of possible breakdown situations and repair for each, and a troubleshooting guide for each type of installed FAS/MNS component. The manual shall include conduit layout, equipment location/layout and simplified wiring, control and riser diagrams for the entire FAS/MNS as installed.

d. Software delivered for this project shall be provided on a CD/DVD.

e. Printouts of configuration settings for all devices.

f. Routine maintenance checklist. The routine maintenance checklist shall be arranged in a columnar format. The first column shall list all installed devices, the second column shall detail the type of maintenance required, the third column shall state the frequency of the maintenance activity, and the fourth column shall be provided for additional comments.

1.9 EXTRA MATERIALS

1.9.1 Repair Service/Replacement Parts

SECTION 28 31 76 (JBC) Page 11

Repair services and replacement parts for the system shall be available for a period of 10 years after the date of final acceptance of this work. The contractor shall provide a warranty of the installed FAS/MNS (all components, wiring, etc.,) for one year after date of acceptance. In the event of a FAS/MNS component failure during the warranty period, government technicians will evaluate and determine the cause of failure. If the failure is caused by an act of nature or damaged by others, government technicians will make the repair. If, however, it is discovered that the failure is as a result of a defect, or is the cause of the contractor, the contractor shall be notified of the problem, and shall have a technician on-site within 48 hours after notification, and, during the one year warranty period, all warranty service (trouble shooting, parts, labor, travel, etc.) shall be provided by the contractor at no charge to the government.

1.9.2 Interchangeable Parts

Spare parts furnished by the contractor shall be directly interchangeable and compatible with the corresponding components of the installed system. Spare parts shall be appropriately packaged and identified by tagging, or stamping.

Spare parts shall be delivered to the government on or before system acceptance. (If a listed spare part is of a type that is not being used in the specific installation, it may be omitted.)

1.9.3 Spare Parts

a. Three (3) manual stations

b. Three (3) smoke detectors

c. Three (3) heat detectors

d. Three (3) speaker/strobes

e. Three (3) strobes

f. Three (3) tamper switches

g. Three (3) horn/strobes

h. Three (3) sets of fuses

1.9.4 Special Tools

Contractor shall provide all software, tools, laptop computer, special connecting cables and any other proprietary equipment to the government necessary for the maintenance, testing, programming and reprogramming of the FAS/MNS equipment by government technicians after the warranty period.

SECTION 28 31 76 (JBC) Page 12

PART 2 PRODUCTS

2.1 MATERIALS AND EQUIPMENT

2.1.1 Standard Products

Provide materials, equipment, and devices that have been tested by a nationally recognized testing laboratory, such as UL or FM, and listed or approved for fire protection service by NFPA 72 or this SECTION. Select material/devices for a particular classification of devices from one manufacturer and not a combination of manufacturers. Material and equipment shall be the standard products of a manufacturer regularly engaged in the manufacture of the products for at least five (5) years prior to bid opening.

Installation methods chosen for each component of the FAS/MNS shall be in accordance with the applicable requirements of the National Electrical Code (NEC), chapter 5. Each FAS/MNS component shall have passed voltage/surge tests. Each MNS & FACP control panel shall be sufficiently large to accommodate all components arranged in a precise and orderly fashion, allowing ample gutter space for interconnection of panels and field wiring.

2.1.2 Nameplates

Each panel shall be permanently identified. Nameplates shall be etched metal or plastic, permanently attached by screws to panels. Lettering, not less than one inch, high, "Fire Alarm Control Panel” or “Mass Notification Control Panel," shall be installed on the front of each panel. Each nameplate shall include the contractor’s name and address and the contract number. Lamps, circuits, meters, fuses, and switches in each panel shall be permanently identified.

2.2 GENERAL PRODUCT REQUIREMENT

All fire alarm and mass notification equipment shall be listed for use under the applicable reference standards. Interfacing of Listed UL 864 or similar approved industry listing with MNS Panels listed to UL 2017 or equal shall be done in a laboratory listed configuration, if the software programming features cannot provide a listed interface control. If a field modification is needed, such as adding equipment like relays, the manufacturer of the panels shall provide the installing contractor the modification for review and confirmation. The installing contractor shall, as part of the submittal documents, provide this information to the CAFB Fire Department.

2.3 FIRE ALARM DETECTION SYSTEM

2.3.1 ADDRESSABLE FIRE ALARM CONTROL PANEL (FACP)

The FACP shall be modular, red in color, installed in a surface mounted corrosion-resistant metal cabinet with hinged door and cylinder lock. Knock-outs shall be provided for conduit (minimum 3/4 inch I.D.) entry and attachment at no less than eight places on the housing top, sides and bottom.

All indicators and switches shall be clearly identified. LED indicators shall be provided for AC POWER, BATTERY, FAULT, TRANSMIT, RECEIVE, CARRIER DETECT, TRANSMITTER DISCONNECT, ALARM AND TROUBLE. In addition, a minimum 40 character two (2) line LCD display shall be provided to display system messages in a plain English format. Switches shall be provided for ALARM

SECTION 28 31 76 (JBC) Page 13

SILENCE, RESET, TROUBLE SILENCE, DRILL TEST, LAMP TEST and TRANSMITTER RESET.

The control unit shall contain an integral keyboard capable of performing all maintenance, history and other control functions of the system. All control panel switches shall be within the locked cabinet. Above indicators and LCD display shall be plainly visible when the cabinet door is closed. Each initiating device circuit (IDC) and signaling line circuit (SLC) shall be powered and supervised so that a signal on one IDC, SLC or addressable device point does not prevent the receipt of signals from another IDC or SLC or addressable device point.

The transmission method shall provide for identification by zone of any alarm, supervisory, or trouble condition on an IDC/SLC and by both zone and/or addressable device point alarm, supervisory, or trouble condition for any addressable initiating device point on the system by means of panel programming in the panel’s software. The control unit shall be capable of transmitting a minimum of 48 user defined zones and each addressable initiating device point individually. Use of interfacing relays between the FACP and communication transceiver to provide point or zonal alarm and trouble status shall not be permitted. The number of zones and points to be transmitted and their identification shall be coordinated with the base fire department. Loss of power, including any or all batteries, shall not require the reloading of a program from any source. Upon restoration of power, startup will be immediate, automatic, and shall not require any manual operation. The loss of primary power or the sequence of applying primary or emergency power shall not affect the transmission of alarm, supervisory, or trouble signals. Panel shall be listed or approved compatible with the existing base-wide Monaco Enterprise’s D-21 Incident Management System.

The FACP shall have a minimum capacity of sixteen (16) addressable SLC with class of operation selectable by programming function. The unit shall be expandable to the maximum capacity by addition of plug-in circuit cards in existing sockets and shall be provided with all hardware to support a minimum of two (2) signaling line circuits. Aside from programming, no other FACP additions or modifications shall be required for expansion. Each plug-in card shall support up to 99 addressable sensor device points (smoke or heat) and 99 addressable modules (monitor or control). In addition, the control unit shall provide connections for up to four (4) Class B, jumper selectable to two (2) Class A, conventional initiating circuits and four (4) notification appliance circuits (NACs). A minimum of two (2) programmable on-board relays shall be provided.

2.3.2 OPERATIONAL FEATURES

The system shall have the following operational features:

a. Electrical supervision of alarm initiation device circuits, signaling line circuits and notification appliance circuits, and auxiliary output circuits for open, short, or ground fault conditions.

b. Electrical supervision of the primary power (ac) supply, presence of the battery, battery voltage, battery charger voltage, and all fusing devices.

c. Electrical supervision of expansion module connections.

d. Electrical supervision of the transmitter interrupt and disconnect circuitry.

SECTION 28 31 76 (JBC) Page 14

e. A trouble buzzer and trouble LED (light emitting diode) which activate when any supervised circuit is compromised. The trouble condition shall be further identified by a plain English LCD display. A trouble silencing switch shall be provided which will silence the trouble buzzer but not extinguish the trouble LED or remove the trouble condition from the display. After the fault is corrected, the system shall automatically return to normal operating condition.

f. An evacuation alarm silencing switch which will turn off the alarm indicating devices designated as silenceable. Operation of the alarm silencing switch will not affect the alarm indicating LED or display nor the operation of the transceiver. This switch shall be arranged so that activation of a subsequent alarm on an unalarmed zone or device shall cause the evacuation alarm signaling devices to reactivate.

g. Switches for testing the indicating LEDs and trouble buzzer and for performing drill tests.

h. A transceiver disconnect function to allow testing and maintenance of the system without activating the transmitter.

i. PC/terminal emulation programming capability which allows entry of zone identification, description, and type, device description, device address, device location, operating parameters and all other required programming to provide a complete system as described herein and on the system drawings.

j. Storage of the programmed configuration in nonvolatile memory.

Simultaneous or subsequent actuation of any individual messages (from zones or devices not initially in alarm), including those actuated during “off air” periods, shall not result in the loss of any messages.

k. An interface to the FSK fire and mass notifiaction radio transceiver via a supervised RS-422 serial data connection. This interface will support communcation between the FACP, the local building mass notificaction system and the base central fire alarm receiving and mass notification control system

l. Monitoring circuitry to detect and shut down a continuously keyed transmitter.

m. Zones for alarm initiating circuits shall be arranged as indicated on the contract drawings.

o. Supervision of intelligent detection sensors, monitor and control modules

2.3.3 ALARM FUNCTIONS

An alarm condition on an IDC or addressable device shall automatically initiate the following functions:

a. Transmission of an alarm signal to the base fire alarm receiving system identifying the Building number, name and zone and point description.

b. Lighting of an alarm indicating LED and activation of a plain English display identifying the activated IDC and/or addressable device.

c. Continuous activation of the alarm notification appliances throughout the building and activation of all associated control outputs as identified by system programming.

d. Audible alarm notification shall recorded voice message as stated in section3.10 of this sepcification.\

SECTION 28 31 76 (JBC) Page 15

2.3.4 NOTIFICATION APPLIANCE NETWORK

The notification appliance network shall comply with NFPA 72 and the requirements of UFC 4-021-01 Design and O&M: Mass Notification Systems using combined or shared audible notification appliances and separate strobe appliances for fire alarm and mass notification systems.

2.3.4.1 Audible Voice Notification

Audible notification appliances consist of audio speakers located to alert occupants and provide intelligible voice instructions. Fire and MNS messages shall be broadcast over the same shared audio speaker network. Refer to Section 3 of this specification.

2.3.4.1.1 Audible Notification Appliance Location

Speakers shall be located as shown in the shop drawings provided by the registered fire protection engineer. Locations shall provide interior coverage throughout the building and to the exterior of the building near entrances, exits, and other outdoor areas commonly used by the building occupants.

2.3.4.1.2 Speaker Type

Speakers shall listed/approved for the purpose and suitable for installation in commercial and industrial applications with consideration of electrically hazardous (NEC classified) locations and for the intended climatic and environmental conditions.

2.3.4.1.3 Intelligibility

Speaker system shall be designed and installed to provide intelligibility.

Intelligibility is defined in NFPA 72, National Fire Alarm Code. Commercially available test instrumentation shall be used to verify intelligibility as specified by: IEC 60268-16 ed3.0: Sound system equipment - Part 16:

Objective rating of speech intelligibility by speech transmission index Intelligibility shall be measured after installation using a common intelligibility scale (CIS) score that shall be greater than 0.70 in each area where building occupants normally could be found. In areas where occupants are not expected to be present, (such as close to the wall, near floor level, or near ceilings) intelligibility may have a CIS score less than 0.70.

2.3.4.1.4 Audio Intensity

The speaker system shall be designed for effective voice communication within buildings and in areas outside of building commonly used by personnel. This shall be accomplished by using a system design approach of many speakers with lower decibel intensity while meeting the minimum decibel level required by NFPA 72. The speakers shall be rated at two watts of power or less and be provided with multiple tap settings to adjust the output power for most occupied areas. For areas that are expansive such as exterior areas or have high ambient noise levels, speakers shall be rated at eight watts of power or less and provided with multiple tap settings not exceeding increments of two watts.

2.3.4.1.5 SCIF Speakers

Speakers installed within sensitive compartmented information facilities (SCIFs) shall comply with Director of Central Intelligence Directive (DCID

SECTION 28 31 76 (JBC) Page 16

6/9), Manual for Physical Security Standards for Sensitive Compartmented Information Facilities.

2.3.4.2 Visual Notification Appliances for Fire

Visual notification appliances shall satisfy all Uniform Federal Accessibility Standards (UFAS) and Americans with Disabilities Act Accessibility Guidelines (ADA). Separate strobes shall be provided for Fire and MNS activation.

2.3.4.2.1 Visual Notification Appliance Location

Visual notification appliances shall be located per the shop drawings provided by the registered fire protection engineer.

2.3.4.2.2 Visual Notification Appliance Type

Visual notification appliances shall be suitable for installation in commercial and industrial applications with consideration of electrically hazardous (classified) locations and suitable for the intended climatic and environmental conditions. Strobes shall utilize a xenon flash tube outputting white light at a flash rate of 1 flash per second.

2.3.4.2.3 Strobes

Strobes shall meet strobe visibility and synchronization requirements in accordance with NFPA 72.

2.3.4.2.4 Strobe Markings and Colors

Separate strobes shall be used for mass notification and fire.

- Mass notification strobes body shall be white with amber-colored lens and marked with the word “ALERT” to alert the hearing impaired.

- Fire strobe shall be red with white/clear strobes marked with the word

“FIRE”.

2.3.5 ELECTRIC POWER

2.3.5.1 Primary Power

Operating power shall be 120 VAC 60 HZ provided from a single dedicated branch circuit via a single pole, 20 amp lockable circuit breaker. The circuit shall be identified by a red nameplate with the words “FIRE ALARM/MNS CIRCUIT CONTROL.” Upon loss of ac power or during a brownout condition, the fire alarm control panel shall automatically and instantaneously switch to standby battery power without loss of any alarm signals and without causing transmission of a false alarm. Loss of ac power shall not prevent transmission of a signal to the D-21 fire alarm receiving system upon operation of any initiating circuit. Loss of ac power shall also activate a trouble indication and cause an ac failure message to be transmitted to the D-21 if ac power is not restored within one minute. Upon restoration of ac power, transfer back to ac operation shall be automatic. Power supply filtering shall prevent false message transmissions caused by transient or steady-state electrical disturbances.

2.3.5.2 Emergency Power

Emergency power shall be through use of rechargeable, sealed-type storage batteries requiring no addition of water. The batteries shall have ample capacity, with primary power disconnected, to operate the fire alarm system

SECTION 28 31 76 (JBC) Page 17 and transceiver for a period of 72 hours. Following this period of battery operation, the batteries shall retain sufficient capacity to operate the system in alarm mode for 15 minutes and transmit an alarm to the central system during this time. Batteries shall be located within the fire alarm enclosure or in a separate battery cabinet. Separate battery cabinets shall have a lockable, hinged cover similar to the fire alarm control panel. The cabinet shall be be red in color and painted to match the FACP and both units shall be keyed alike.

2.3.5.3 Battery Charger

The battery charger shall be integral to the fire alarm control or provided as a separate unit and shall be completely automatic, capable of recharging the batteries from full discharge (18 Volts) to full charge within 48 hours.

2.3.6 CIRCUIT CONNECTIONS

Circuit conductors entering or leaving the panel shall be connected to screw-type terminals with each terminal marked for identification. Cabinets shall be provided with ample gutter space to allow proper clearance between the cabinet and live parts of the panel equipment and to provide sufficient space for all external wiring entering the cabinet. Where more than one module is required to form a control unit, the interconnection between modules shall be supervised. Where addressable devices contain an LED for alarm indication, the control panel shall support the lighting of up to a total of 160 alarm LEDs at one time or up to 20 device LEDs on a single addressable signaling line circuit.

2.3.7 PROGRAMMING

All required programming of the system shall be capable of being accomplished from programming software operating on a portable PC (laptop). An RS-232 port shall be provided for programming via a PC or terminal. All software, interconnecting cables and instructions required for programming shall be provided to the government without additional cost under this contract. All programming information internal to the control panel shall be stored in non-volatile memory and shall not be lost in the event of a total system power failure. Programming software shall allow “Control by Event” type programming wherein specific inputs may control specific outputs for either fire alarm, MNS or other non-fire/MNS control. The programming interface shall be a graphical user type interface. Remote programming software shall be entered and confirmed prior to downloading into the control unit. The software shall also allow the off-loading of current programmed information from the control unit to the remote programming device. Capability shall be provided to create, modify, store and print program data.

2.3.8 REMOTE EQUIPMENT CONNECTIONS

The control unit shall contain an RS-232 port for connection of a local/remote printer and an RS-422 port for connection to remote graphical, programmable, annunciators. Provisions shall also be provided for connections to standard LED type annunciators where shown on the drawings. Where provided, communication connections to remote graphical type annunciators shall be supervised.

2.3.9 INTERNAL COMMUNICATIONS

The control unit firmware shall orchestrate and control all internal communications as well as all communications to the addressable devices via the signaling line circuits. All internal communications shall be in a digital format. Signaling line circuit communications shall be such that all

SECTION 28 31 76 (JBC) Page 18 addressable devices, up to the maximum allowed quantity of the system, shall be polled within four (4) seconds. Signaling line circuits shall be protected such that a short circuit on the signaling line will not damage the equipment or prevent normal operation of any other SLC. All open, short or ground faults on signaling lines shall result in a trouble indication.

2.3.10 OTHER OPERATIONAL FEATURES

In addition to those specified elsewhere, the addressable fire alarm control panel shall provide the following operational features:

2.3.10.1 Programmable Mass Notification System Actions

The addressable fire alarm control panel shall provide at least four (4) user programmable actions when the MNS system is activated. These actions shall be intiated by commands from the MNS FSK transceiver. Interface between the FACP and MNS FSK transceiver shall be by supervised a RS-422 serial port connection.

2.3.10.2 Addressable Smoke Sensors

The control panel shall support both ionization and photoelectric type smoke sensors. In addition, the control panel will provide high and low maintenance alerts, pre alarm signals, programmable sensitivity adjustment and alarm verification capability.

2.3.10.3 Lamp Test

A lamp test switch shall be provided on the control unit which will light all panel LEDs for test purposes.

2.3.10.4 Drill Test

A drill test switch shall be provided on the control panel which will activate all circuits and control modules designated as type NAC (Notification Appliance Circuit). Operation of the drill test switch shall not result in an alarm transmission to the D-21 or operation of any supplementary circuits such as air handling unit (AHU) shutdown.

2.3.10.5 Transmitter Disconnect Circuit

The connected FSK Transceiver shall provide a transmitter disconnect mechanism providing the following features: A circuit which automatically disconnects the transmitter in the event the transmitter stays in a transmit condition for a period longer than 30 seconds. A transmitter reset button which will reconnect the transmitter when operated. A transmitter disconnected LED to indicate when the transmitter has been automatically disconnected. A failure warning to the central system supervising station if the transmitter has been automatically disconnected.

2.3.10.6 Walk Test

The control panel shall contain provisions for placing the system in a walk test mode. In this mode, activation of any sensor or monitor module included in the walk test program shall activate the visual devices for a period of approximately two (2) seconds.

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .