B08_Attachment_1_BIBE_259631-317515_Lodge_Final_CD_Drawings_6_18_2025_Part4.pdf
PDF 46 MB Posted
- Solicitation number
- 140P2025R0039
About this file
These mechanical engineering drawings are for the final construction documents of the Big Bend National Park Lodge project, specifically detailing the mechanical systems and equipment for a multi-level lodge facility. The documents include comprehensive mechanical system specifications covering air handling units (AHU-LL-01), variable refrigerant flow (VRF) systems, fan coil units, exhaust fans, terminal units, and associated controls across three building levels (lower level, first floor, and second floor).
Key technical details include a centralized air handling system with variable air volume capabilities, VRF heat recovery systems using Daikin equipment, multiple fan coil units serving different zones like dining, kitchen, reception, and retail areas, and a sophisticated building management control system. The mechanical design incorporates energy efficiency features such as static pressure reset logic, optimized start/stop sequences, zone temperature controls, and comprehensive monitoring capabilities for energy and water usage. The system is designed to provide precise environmental control with flexibility for different occupancy modes and zones within the lodge facility.
View the file
Other files
Show all 44
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
10d (0.128" x
3") NAILS AT 8"
ON-CENTER
2x4 ONE SIDE. USE 2X6
IF JOIST SPACING IS
GREATER THAN 24" ON-
CENTER.
BEVELED 2x4 BLOCK
BEVELED WEB STIFFENERS
ON BOTH SIDES
4'- 0"
M
IN
IM
UM
2'- 0"
M
AXIM
UM
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH. REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
259631-317515
171153
BIG BEND NATIONAL PARK
SH
FE, PN
LC
12/10/24
TYPICAL WOOD DETAILS
S6.2
FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
N.T.S.S6.2
1 OVER HANG DETAIL
N.T.S.S6.2
2 SMALL OPENING IN PLYWOOD DIAPARAGM
N.T.S.S6.2
3 LARGE OPENING IN PLYWOOD DIAPARAGM
N.T.S.S6.2
4 TYP. JOIST TO BEAM CONNECTIONS
N.T.S.S6.2
5 HANGER SCHEDULE
N.T.S.S6.2
6 WEB STIFFENER DETAIL
N.T.S.S6.2
7 WEB FILLER/BACKER BLOCK DETAIL
N.T.S.S6.2
8 OPENING AT SHEAR WALL
N.T.S.S6.2
10 POST IN WALL DETAIL
N.T.S.S6.2
9 MULTI JOISTS DETAIL
251 424426253
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH. REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
259631-317515
171153
BIG BEND NATIONAL PARK
SH
FE, PN
LC
12/10/24
TYPICAL WOOD DETAILS
S6.3
FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
N.T.S.S6.3
TYPICAL SHEAR WALL
FRAMING REQUIREMENTS
N.T.S.S6.3
9 TYPICAL FRAMING DETAILS (RECTANGULAR SAWN OR ENGINEERED LUMBER)
N.T.S.S6.3
12 SHEAR WALL CONSTRUCTION - PLAN VIEW
N.T.S.S6.3
1 SHEAR WALL SCHEDULE (S.W.S.)
N.T.S.S6.3
11 SHEAR WALL & ROOF/FLOOR DIAPHRAGM EDGE NAILING DETAIL
N.T.S.S6.3
5 DIAPHRAGM PLYWOOD PLAN
252 424426254
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
259631-317515
171153
BIG BEND NATIONAL PARK
SH
FE, PN
LC
12/10/24
SECTIONS AND DETAILS
S7.0
FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
253 424426255
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
259631-317515
171153
BIG BEND NATIONAL PARK
SH
FE, PN
LC
12/10/24
SECTIONS AND DETAILS
S7.1
254 424426256
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
259631-317515
171153
BIG BEND NATIONAL PARK
SH
FE, PN
LC
12/10/24
SECTIONS AND DETAILS
S7.2
255 424426257
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
259631-317515
171153
BIG BEND NATIONAL PARK
SH
FE, PN
LC
12/10/24
SECTIONS AND DETAILS
S7.3
FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
SCALE OF
SCALE E
0 211
FEET
SCALE OF
SCALE F
0 321
FEET
256 424426258
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
259631-317515
171153
BIG BEND NATIONAL PARK
SH
FE, PN
LC
12/10/24
SECTIONS AND DETAILS
S7.4
FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
SCALE OF
SCALE F
0 321
FEET
SCALE OF
SCALE E
0 211
FEET
SCALE OF
SCALE D
0 12612
INCHES
257 424426259
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
259631-317515
171153
BIG BEND NATIONAL PARK
Designer
Author
Checker
12/10/24
SECTIONS AND DETAILS
S7.5
FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
SCALE OF
SCALE E
0 211
FEET
258 424426260
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
259631-317515
171153
BIG BEND NATIONAL PARK
SH
FE, PN
LC
12/10/24
SECTIONS AND DETAILS
S7.10
FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
SCALE OF
SCALE G
0 422
259 424426261
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
259631-317515
171153
BIG BEND NATIONAL PARK
SH
FE, PN
LC
12/10/24
SECTIONS AND DETAILS
S7.12
FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
SCALE OF
SCALE G
0 422
260 424426262
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
259631-317515
171153
BIG BEND NATIONAL PARK
SH
FE, PN
LC
12/10/24
SECTIONS AND DETAILS
S7.13
FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
SCALE OF
SCALE G
0 422
261 424426263
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
259631-317515
171153
BIG BEND NATIONAL PARK
SH
FE, PN
LC
12/10/24
SECTIONS AND DETAILS
S7.14
FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
SCALE OF
SCALE G
0 422
262 424426264
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
259631-317515
171153
BIG BEND NATIONAL PARK
SH
FE, PN
LC
12/10/24
SECTIONS AND DETAILS
S7.15
FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
SCALE OF
SCALE G
0 422
263 424426265
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
259631-317515
171153
BIG BEND NATIONAL PARK
SH
FE, PN
LC
12/10/24
SECTIONS AND DETAILS
S7.16
264 424426266
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
259631-317515
171153
BIG BEND NATIONAL PARK
SH
FE, PN
LC
12/10/24
SECTIONS AND DETAILS
S7.17
FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
SCALE OF
SCALE G
0 422
265 424426267
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
259631-317515
171153
BIG BEND NATIONAL PARK
Designer
Author
Checker
12/10/24
SECTIONS AND DETAILS
S7.18
FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
SCALE OF
SCALE G
0 422
266 424426268
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
259631-317515
171153
BIG BEND NATIONAL PARK
Designer
Author
Checker
12/10/24
SECTIONS AND DETAILS
S7.19
FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
SCALE OF
SCALE G
0 422
267 424426269
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
259631-317515
171153
BIG BEND NATIONAL PARK
SH
FE, PN
LC
12/10/24
WATERTANK - FOUNDATION MAT
& DETAILS
S7.20
FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
SCALE OF
SCALE F
0 321
FEET
SCALE OF
SCALE G
0 422
268 424426270
MISC. VALVES & COCKS
THERMOMETER
PRESSURE GAUGE
PRESSURE-TEMPERATURE TEST PLUG
MANUAL AIR VENT
AUTOMATIC AIR VENT
FLOW SWITCH
TEMPERATURE SENSOR
VACUUM BREAKER
SOLENOID VALVE
S
V
T
F
AAV
MAV
REMOVE EXISTING PIPE
REMOVE EXISTING EQUIPMENT
DEMOLITION LEGEND
MISC. FITTINGS & SYMBOLS
DIRECTION OF FLOW
DIRECTION OF SLOPE
PIPE SLEEVE
REDUCER
ANCHOR
ELBOW (90 DEGREE)
PIPING CONNECTIONS
TEE
JOINT OR COUPLING POINT
PIPE CONTINUATION
HEAT TRACE
FLEXIBLE HOSE CONNECTOR
TEE DOWN
TEE UP
ELBOW DOWN
ELBOW UP
RISER
PLUG OR BLIND FLANGE
CAP
FLANGED CONNECTION
UNION
ELBOW (45 DEGREE)
MC
MECHANICAL COUPLING
NEW, EXISTING, & FUTURE WORK
EXISTING PIPING NEW PIPING
EXISTING EQUIPMENT NEW EQUIPMENT
EXISTING
EQUIPMENT
CLEARANCES
NEW
EQUIPMENT
CLEARANCES
GENERAL NOTES:
A. THIS IS A STANDARD LEGEND SHEET, THEREFORE, SOME SYMBOLS MAY APPEAR ON THIS SHEET
THAT DO NOT APPEAR ON THE DRAWINGS.
FUTURE PIPING
FUTURE EQUIPMENT
FUTURE
EQUIPMENT
CLEARANCES
UNIT NUMBER
EQUIPMENT TYPE
XX-XXX
EQUIPMENT
XXXX-XX-XXXXX
UNIT NUMBER
FLOOR UNIT IS
LOCATED ON
EQUIPMENT TYPE EQUIPMENT PROVIDED
BY OTHERS
XXX
TAG NUMBER
TU-X-XXX
DETAIL CALLOUT
X
XX.XX
DETAIL NUMBER
SHEET NUMBER
THRUST BLOCK
REMOVE EXISTING DUCTWORK
EXISTING DUCTWORK NEW DUCTWORK FUTURE DUCTWORK
SYMBOLS
A
E
B
X
K
R
F
ACCESS PANEL
POINT OF CONNECTION
EXISTING TO REMAIN
BELOW GRADE / FLOOR
REVISION NUMBER
NUMBERED NOTE
REMOVE EXISTING
CAP EXISTING / CAP FOR FUTURE
RELOCATE EXISTING
FUTURE
WALL-MOUNTED
PENDENT-MOUNTED
TEMPERATURE
HUMIDITY
DIFFERENTIAL
PRESSURE SWITCH
T
H
DP
T
H
DP
WALL-MOUNTED
PENDENT-MOUNTED
CARBON MONOXIDE
CARBON DIOXIDE
NITROGEN OXIDE
CO
CO2
NOX
CO
CO2
NOX
SENSORS
TERMINAL UNIT NUMBER
TERMINAL UNIT
FLOOR UNIT IS LOCATED ON
AIR HANDLER NUMBER
TERMINAL UNITS
24x16
R
R=1-1/2W
RADIUS ELBOW
W
MITER ELBOWS & TEES
TURNING VANES IN ALL
ELBOWS AND TEES FLEX
CONNECTION ACOUSTICAL LINER
SIZE SHOWN IS CLEAR
AIR PASSAGE
DUCT OFFSETS
R=1-1/2W W
LESS THAN 15° 15° TO 30° GREATER THAN 30°
30° MAX 30° MAX
TRANSITIONS
RECTANGULAR TO ROUND
45°
W
4" MIN OR
1/4W OR
12" MAX
RECTANGULAR DUCT FITTING
SPIN-IN
FITTING
CONICAL SPIN-IN
FITTING
RECTANGULAR TO ROUND FITTING
R
L
D1 D2
D
FS
D
CFM
TYPE
RETURN EXHAUST SUPPLY
FLOW DIRECTION
(NONE SHOWN
IF 4-WAY)
CFM
SIZE TYPE
TYPE REFERENCE
H = 6" BELOW CEILING
L = 6" ABOVE FLOOR
F = FLOOR
S = SLOT DIFFUSER
C = CEILING
T = DOOR TRANSFER
NECK SIZE (SIDEWALL & FLOOR GRILLE)
PLENUM INLET SIZE (SLOT DIFFUSER)
CEILING DIFFUSERS & GRILLES SIDEWALL, SLOT & FLOOR GRILLES
SUPPLY
AIR
RETURN
AIR
EXHAUST
AIR
OUTSIDE
AIR
DUCT SECTIONS
COMBINATION
FIRE/SMOKE FIRE
SMOKE
VOLUME
AUTOMATIC
RETURN OR EXHAUST AIR FLOW
SUPPLY OR OUTSIDE AIR FLOW
UNDERCUT DOORUC 1/2"
SECTION
R=2D FOR FLEX
PLAN
R=1-1/2D FOR ROUNDD
R
RETURN OR EXHAUST GRILLE CONNECTION
SECTION
D
R
R=2D FOR FLEX
PLAN
R=1-1/2D FOR ROUNDD
R
SUPPLY DIFFUSER CONNECTION
SECTION PLAN
SECTION PLAN
SECTION PLAN
SUPPLY DIFFUSER SIDE FLEX CONNECTION
SECTION PLAN
RETURN OR EXHAUST GRILLE
FLEX DUCT ROUND DUCT
FLEX DUCT ROUND DUCT
RECTANGULAR DUCT SQUARE NECK
SPIN-IN
FITTING
D
R
LINED PLENUM
FLEX DUCT
SEE SPEC FOR TYPE
SEE SCHEDULE FOR SIZE
DAMPERS
SECTION PLAN SECTION PLAN
SUPPLY DIFFUSER HARD CONNECTION SIDEWALL SUPPLY GRILLE CONNECTION
CONICAL TEE LOW LOSS LATERAL TEE CONICAL LATERAL
R=1-1/2D L=D1-D2R=.2D
R
ELBOW Y-BRANCH BELL MOUTH REDUCER
BRANCH FITTINGS
DUCT LEGEND
LOW PRESSURE DUCTWORK
MEDIUM PRESSURE DUCTWORK
DUCT DETAILS (LOW VELOCITY)
FD S
D
OCCUPANCYOCC OCC
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH. REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
BIG BEND NATIONAL PARK
Designer
Author
Checker
12-10-2024
SYMBOLS, LEGENDS AND
ABBREVIATIONS - MECHANICALM0.01
100% FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENTFINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENTFINAL CONSTRUCTION DOCUMENTS - LODGE & WATER COMPONENT
DRAWING NO.
171153
PMIS/PKG NO.
259631-317515TECH. REVIEW:
RMK
RMK
DAW
269 424426271
HVAC PIPING
LPS LOW PRESSURE STEAM
LPR LOW PRESSURE RETURN
MEDIUM PRESSURE STEAM
MEDIUM PRESSURE RETURN
HIGH PRESSURE STEAM
HIGH PRESSURE RETURN
BOILER BLOWDOWN
DRAIN (CONDENSATE/INDIRECT)
PUMPED CONDENSATE
STEAM VENT
FEEDWATER SUPPLY
OVERFLOW
CHEMICAL FEED
INDUSTRIAL COLD WATER (MAKE-UP)
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
CHILLED WATER SUPPLY
CHILLED WATER RETURN
SECONDARY CHILLED WATER SUPPLY
SECONDARY CHILLED WATER RETURN
HEATING WATER SUPPLY
HEATING WATER RETURN
SECONDARY HEATING WATER SUPPLY
SECONDARY HEATING WATER RETURN
HIGH TEMP HOT WATER SUPPLY
HIGH TEMP HOT WATER RETURN
HEAT RECOVERY WATER SUPPLY
HEAT RECOVERY WATER RETURN
GLYCOL SUPPLY
GLYCOL RETURN
REFRIGERANT LIQUID
REFRIGERANT SUCTION
REFRIGERANT HOT GAS
REFRIGERANT RELIEF VENT
BRINE SUPPLY
BRINE RETURN
HUMIDIFICATION LINE
COMPRESSED AIR
VACUUM (AIR)
DUAL TEMPERATURE SUPPLY
DUAL TEMPERATURE RETURN
RADON ABOVE GRADE
RADON BELOW GRADERAD
RAD
MPS
MPR
HPS
HPR
BBD
D
PC
SV
FWS
OFL
CHF
ICW
CDS
CDR
CHWS
CHWR
SCHWS
SCHWR
HWS
HWR
SHWS
SHWR
HTWS
HTWR
HRWS
HRWR
GLS
GLR
RL
RS
RHG
RRV
BS
BR
H
A
VAC
DTS
DTR
STANDARD ABBREVIATIONS
AREA DRAINAD
AMERICANS WITH DISABILITIES ACTADA
AIRFOILAF
ABOVE FINISHED FLOORAFF
APPARATUS HOUSING PLENUMAHP
ALUMINUMAL
ALTERNATIVEALT
AIR PRSSURE DROPAPD
APPROXIMATELYAPPROX
ARCHITECT, ARCHITECTURALARCH
AUTOMATIC SPRINKLERAS
ACCESS PANELAP
AUTOMATICAUTO
BACKDRAFT DAMPERBDD
BELOW FINISHED FLOORBFF
BREAK HORESPOWERBHP
BUILDINGBLDG
BOTTOM OF PIPEBOP
BOTTOM OF STRUCTUREBOS
BASEMENTBSMT
BACKWARD INCLINEDBI
BRITISH THERMAL UNITBTU
BRITISH THERMAL UNITS PER HOURBTUH
BUTTERFLY VALVEBTV
BALANCING VALVEBV
CATCH BASINCB
CUBIC FEET PER HOURCFH
CUBIC FEET PER MINUTECFM
CUBIC FEET PER SECONDCFS
CALCULATIONCALC
CAST IRONCI
CENTERLINECL
CEILING OR COOLINGCLG
CLEANOUTCO
CONNECT, CONNECTIONCONN
CONTINUED, CONTINUATIONCONT
CIRCULATING PUMPCP
CLEANOUT TO GRADECTG
CONCRETECONC
CHECK VALVECV
DRY BULBDB
DIRECT DIGITAL CONTROLDDC
DEFLECTIONDEFL
DRAINAGE FIXTURE UNITDFU
DEIONIZEDDI
DIAMETERDIA
DUCTILE IRON PIPEDIP
DRINKING FOUNTAINDF
DOWN (PENETRATES FLOOR)DN
DEW POINTDP
DRAINDR
DRAIN VALVEDV
DOUBLE WIDTH DOUBLE INLETDWDI
DRAWINGDWG
EXISTING(E), EXIST
ENTERING AIR TEMPERATUREEAT
DROP (WITHIN FLOOR)DROP
EXTENDED COVERAGEEC
ELECTRONICALLY COMMUTATED MOTORECM
ENTERING DRY BULBEDB
EMERGENCY EYE WASHEEW
ENTERING FLUID TEMPERATUREEFT
ELECTRIC, ELECTRICALELEC
ELEVATIONELEV
ENGINEERENGR
EFFICIENCYEFF
EQUALEQ
EQUIPMENTEQUIP
EMERGENCY SHOWERES
EXTERNAL STATIC PRESSUREESP
ENTERING WET BULBEWB
ELECTRIC WATER COOLEREWC
ELECTRIC WATER HEATEREWH
ENTERING WATER TEMPERATUREEWT
EXPANSION TANKET
EXTRACTOREX
EXPANSIONEXP
EXHAUST OR EXHAUST AIREXH
DEGREES FAHRENHEITF
FLOOR CLEANOUTFCO
FIRE DAMPER (MECHANICAL)FD
FLOOR DRAIN (PLUMBING)FD
FIRE DEPARTMENT CONNECTIONFDC
FORWARD CURVEDFC
FINISHED FLOOR ELEVATIONFFE
FIGUREFIG
FLOORFL
FULL LOAD AMPACITYFLA
FIRE PUMPFP
FLUID PRESSURE DROPFPD
FEET PER MINUTEFPM
FEET PER SECONDFPS
FLEXIBLEFLEX
FLOOR SINKFS
FIRE SMOKE DAMPERFSD
FEET/FOOTFT
FINNED TUBE RADIATORFTR
FIXTURE UNITFU
FLUSH VALVEFV
FUTURE(F)
GRADEG
FLUSH TANKFLT
GAGE/GAUGEGA
GALLONGAL
GALVANIZEDGALV
GLYCOLGLY
GALLONS PER HOURGPH
GALLONS PER MINUTEGPM
GATE VALVEGV
HEIGHTH
GROUND HYDRANTGH
HOSE BIBBHB
HUB DRAINHD
HORIZONTALHORIZ
HORSEPOWERHP
HORIZONTAL SIDE WALLHSW
HEAT TRACEHT
HEATINGHTG
HOSE VALVEHV
HOURHR
HOSE VALVE CABINETHVC
INSIDE DIAMETER, INSIDE DIMENSIONID
LEAVING WET BULBLWB
LEAVING WATER TEMPERATURELWT
MAXIMUMMAX
THOUSAND BTU PER HOURMBH
LEAVINGLVG
MINIMUM CIRCUIT AMPACITYMCA
MECHANICALMECH
MINIMUM EFFICIENCY REPORTING VALUEMERV
MANUFACTURERMFR
MISCELLANEOUSMISC
MAXIMUM OVERCURRENT PROTECTIONMOCP
MOP SINKMS
MOUNTEDMTD
MINIMUMMIN
NORMALLY CLOSEDNC
NOT IN CONTRACTNIC
NORMALLY OPENNO
NOMINAL PIPE SIZENPS
NOT TO SCALENTS
OUTSIDE AIR TEMPERATUREOAT
ON CENTER DISTANCEOC
OVERFLOW DRAINOD
NON-RISING STEMNRS
OUTSIDE SCREW & YOKE GATE VALVEOS&Y
OUTSIDE AIROSA
PLANTER DRAINPD
PITCH PER FOOTP/FT
PHASEPH
POST INDICATING VALVEPIV
POLYPROPYLENEPP
PRESSURE REDUCING VALVEPRV
PRESSURE GAUGEPG
PRESSURE SWITCHPS
POUNDS PER SQUARE INCHPSI
POUNDS PER SQUARE INCH (GAUGE)PSIG
POLYVINYL CHLORIDEPVC
RADIUSR, RAD
RELIEF AIRRA
ROOF DRAINRD
RETURN AIRRET
PVC COATED STEELPVS
REVISIONREV
RELATIVE HUMIDITYRH
RISE (WITHIN FLOOR)RISE
ROOF MANIFOLDRM
REVOLUTIONS PER MINUTERPM
SINKS
SUPPLY AIRSA
SWAY BRACESB
RISER NIPPLERN
STANDARD CUBIC FEET PER MINUTESCFM
SHOWER DRAIN (PLUMBING)SD
SMOKE DAMPER (MECHANICAL)SD
SEWAGE EJECTORSE
SENSIBLESENS
SQUARE FOOT, SQUARE FEETSF
SHOWERSH
SIMILARSIM
SECTIONSECT
SHUTOFF VALVESOV
STATIC PRESSURESP
SPECIFICATIONSPEC
SQUARESQ
STAINLESS STEEL (ALL)SS
STANDARD SPRAY PENDENTSSP
STANDARD SPRAY UPRIGHTSSU
STEELSTL
SQUARE INCH, SQUARE INCHESSQ IN
STRUCTURE, STRUCTURALSTRUCT
SINGLE WALL PLENUMSWP
SINGLE WIDTH SINGLE INLETSWSI
TRENCH DRAINTD
TOTAL DEVELOPED LENGTHTDL
TEMPERATURETEMP
THERMOSTATIC MIXING VALVETMV
TOP OF PIPETOP
TOTAL DISCHARGE HEADTDH
TRAP PRIMER VALVETP
TAMPER SWITCHTS
TOTAL STATIC PRESSURETSP
TYPICALTYP
UNDERGROUNDUG
UP (PENETRATES FLOOR SLAB)UP
UNLESS OTHERWISE NOTEDUON
VOLTSV
URINALU
VACUUM BREAKERVB
VOLUME DAMPERVD
VELOCITYVEL
VERTICALVERT
VENT THROUGH ROOFVTR
WIDTHW
WET BULBWB
WATER CLOSETWC
VARIABLE FREQUENCY DRIVEVFD
WALL CLEANOUTWCO
WATER FIXTURE UNITSWFU
WATER GAUGEWG
WALL HYDRANTWH
WATER PRESSURE DROPWPD
WATER TEMPERATURE DROPWTD
WATER TEMPERATURE RISEWTR
WITHW/
WATER HAMMER ARRESTORWHA
WITHOUTW/O
LAVATORYLAV
POUNDLB
LEAVING DRY BULBLDB
LINEAR FEETLF
LEAVING AIR TEMPLAT
LEAVING FLUID TEMPERATURELFT
JOCKEY PUMPJP
KILOWATTKW
KILOWATT HOURKWH
LENGTHL
ISOLATOR, ISOLATIONISOL
ISOMETRICISO
IRON PIPE SIZEIPS
INSULATIONINSUL
INVERT ELEVATIONIE
INCH, INCHESIN
SEE ARCHITECTURAL DRAWINGSSAD
SEE CIVIL DRAWINGSSCD
SEE ELECTRICAL DRAWINGSSED
SEE MECHANICAL DRAWINGSSMD
SEE PLUMBING DRAWINGSSPD
SEE STRUCTURAL DRAWINGSSSD
STANDARD ABBREVIATIONS
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH. REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
BIG BEND NATIONAL PARK
Designer
Author
Checker
12-10-2024
SYMBOLS, LEGENDS AND
ABBREVIATIONS - MECHANICALM0.02
100% FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENTFINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENTFINAL CONSTRUCTION DOCUMENTS - LODGE & WATER COMPONENT
DRAWING NO.
171153
PMIS/PKG NO.
259631-317515TECH. REVIEW:
RMK
RMK
270 424426272
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
BIG BEND NATIONAL PARK
RMK
RMK
DAW
12-10-2024
EQUIPMENT SCHEDULES -
MECHANICAL
M0.03 171153
259631-317515
FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
A. OUTDOOR CONDITIONS BASED ON ASHRAE FUNDAMENTALS 2021 99.6% AND 0.4% DATA.
GENERAL NOTES:
INDOOR 70˚ F ± 2˚ F DB NO CONTROL 75˚ F ± 2˚ F DB 50% RH MAX, NO MINIMUM
OUTDOOR 25.5˚ F DB 9.6˚ F DP / 9.0 HR / 29.8 ˚ F MCDB 100.1˚ F DB / 73.4˚ F MCWB 63.2˚ F DP / 87.0 HR / 75.1˚ F MCDB
TEMPERATURE HUMIDITY TEMPERATURE HUMIDITY
SPACE WINTER SUMMER
DESIGN CONDITIONS - BIG BEND NATIONAL PARK, TX
AHU-LL-01 LOWER LEVEL OUTSIDE AIR 3,300 2,850 2,850 8 14 N
TAG LOCATION SERVICE (CFM) (CFM) (CFM) (MERV) (MERV) (Y/N)
OSA OSA OSA PRE FINAL CARBON
MAX MIN LOW MIN
MIXING BOX FILTERS
AIR HANDLING UNIT SCHEDULE
3,300 CENTRIFUGAL 5.60 1.50 2,790 1.22 4.4 7.5 230/3 Y 1 2,000 CENTRIFUGAL 2.14 1.00 2,376 1.20 1.27 1.5 230/3 Y 1
(CFM) TYPE (IN WG) (IN WG) (RPM) INDEX (BHP) (HP) PHASE (Y/N) QTY CFM TYPE (IN WG) (IN WG) (RPM) INDEX (BHP) (HP) PHASE (Y/N) QTY
AIRFLOW FAN TSP ESP SPEED ENERGY POWER RATING VOLT/ VFD AIRFLOW FAN TSP ESP SPEED ENERGY POWER RATING VOLT/ VFD
FAN MOTOR FAN MOTOR
SUPPLY FAN RETURN/EXHAUST FAN
AIR HANDLING UNIT SCHEDULE
2. DX COIL IS SERVED BY DAIKIN AHU KIT WITH REMOTE VRF CONDENSING UNITS.
1. ARRANGE UNIT FOR MULTIPLE POINT POWER CONNECTION W/ DISCONNECT SWITCHES. PROVIDE A SEPARATE, DEDICATED 120V CONNECTION FOR RECEPTACLE(S) AND LIGHTS.
NOTES:
G. FAN ENERGY INDEX (FEI) BASED ON MANUFACTURERS' CERTIFIED DATA, RATIO OF THE ELECTRIC INPUT POWER OF A REFERENCE FAN TO THE ELECTRIC INPUT POWER OF THE ACTUAL FAN, AS CALCULATED PER AMCA 208.
F. PROVIDE DUCT SMOKE DETECTOR. INTERLOCK DETECTOR WITH ELECTRICAL SERVICE TO DE-ENERGIZE UNIT UPON DETECTION OF SMOKE.
E. HEAT RECOVERY SECTION EFFECTIVENESS IS BASED ON AHRI 1060.
D. COOLING COILS BASED ON MAXIMUM FACE VELOCITY OF 500 FPM, 0.75 IN WG MAXIMUM AIR PRESSURE DROP AND 18 FT WG MAXIMUM WATER PRESSURE DROP.
C. HEATING COILS BASED ON MAXIMUM FACE VELOCITY OF 750 FPM, 0.15 IN WG MAXIMUM AIR PRESSURE DROP, 5 FT WG MAXIMUM WATER PRESSURE DROP.
B. MINIMUM OSA CALCULATED BASED ON CODE AND ASHRAE STANDARD 62.
A. UNIT MOUNTED ON HOUSEKEEPING PAD.
GENERAL NOTES:
3,300 2,000 WHEEL 6.4 120/1 26 48 70 86.9 100.1/73.4 84.4/67.9 70/62 85.9 81/66 69.3/60.95 48 72 R410A 208/3 N 3,700 DAIKIN CAH008GDGC 1, 2
CFM CFM TYPE FLA PHASE (°F DB) (°F DB) (°F DB) (%) (°F DB/WB) (°F DB/WB) (°F DB/WB) (%) (°F DB/WB) (°F DB/WB) (°F DB) (°F DB) TYPE PHASE (Y/N) (LBS) & MODEL NOTES
OSA EXHAUST VOLT/ OSA EAT OSA LAT EXH EAT EFF. OSA EAT OSA LAT EXH EAT EFF. EAT LAT EAT LAT VOLT/ POWER WEIGHT MANUFACTURER
WINTER SUMMER COOLING HEATING GEN. APPROX.
HEAT RECOVERY REFRIGERANT COIL REFRIGERANT ELECTRICAL
AIR HANDLING UNIT SCHEDULE
4. PROVIDE 16" STAINLESS METAL STAND. MOUNT ACCU-LL-01 UNIT 16" ABOVE GRADE ON TOP OF STAND. BOLT UNIT TO BASE, PROVIDE 3/4" MASON SUPERWAFFLE NEOPRENE PAD MOUNTS BETWEEN STAND AND UNIT BASE.
3. COOLING ONLY UNIT.
2. INDOOR UNIT RECEIVES POWER FROM OUTDOOR UNIT.
1. PROVIDE CONDENSATE PUMP: LITTLE GIANT EC-400, 120 VOLTS, 1 PHASE, 0.24 AMPS, 20 WATTS. ROUTE CONDENSATE DRAIN TO JANITOR ROOM MOP SINK.
NOTES:
B. PROVIDE WASHABLE MERV 8 FILTERS
A. MINIMUM EFFICIENCY IS AT ARI STANDARD CONDITIONS.
GENERAL NOTES:
ACCU-LL-01 / AC-LL-01 LOWER LEVEL ELEVATOR MACHINE ROOM 700 21.2 16.7 75 20 12.5 R410A 3.50 208/1 15 18.9 20 N 35 (INDOOR) DAIKIN FTX24UVJU / RXL24UMVJU 1,2,3
TAG LOCATION SERVICE (CFM) (MBH) (MBH) (°F DB/WB) SEER EER TYPE (LBS) PHASE (A) (A) (A) (Y/N) (LBS) & MODEL NOTES
AIRFLOW TOTAL SENSIBLE EAT CHARGE VOLT/ FLA MCA MOCP POWER WEIGHT MANUFACTURER
COOLING CAPACITY MIN EFFICIENCY REFRIGERANT ELECTRICAL GEN. APPROX.
SPLIT SYSTEM HEAT PUMP SCHEDULE
4. PROVIDE PRESSURE SENSOR IN KITCHEN CONNECTED TO BMS.
3. UNT TO BE LOCATED ABOVE WALK-IN COOLER. PROVIDE ACCESS.
2. UNIT SPEED IS CONTROLLED THROUGH VFD WHICH IS CONNECTED TO STREVOID DEMAINDAIRE PLATINUM CONTROL SYSTEM (REFER TO KITCHEN CONSULTANT DRAWINGS, PROVIDE ALL REQUIRED SENSORS AND CONTROL ACCESSORIES FOR A COMPLETE INSTALLATION).
1. ARRANGE UNIT FOR SINGLE POINT POWER CONNECTION W/ DISCONNECT SWITCH.
NOTES:
F. FAN ENERGY INDEX (FEI) BASED ON MANUFACTURERS' CERTIFIED DATA, RATIO OF THE ELECTRIC INPUT POWER OF A REFERENCE FAN TO THE ELECTRIC INPUT POWER OF THE ACTUAL FAN, AS CALCULATED PER AMCA 208.
E. PROVIDE FLEXIBLE EQUIPMENT CONNECTION AT DUCT CONNECTIONS.
D. PROVIDE DUCT SMOKE DETECTOR. INTERLOCK DETECTOR WITH ELECTRICAL SERVICE TO DE-ENERGIZE UNIT UPON DETECTION OF SMOKE.
C. COOLING COILS BASED ON MAXIMUM FACE VELOCITY OF 500 FPM, 0.75 IN WG MAXIMUM AIR PRESSURE DROP AND 18 FT WG MAXIMUM WATER PRESSURE DROP.
B. HEATING COILS BASED ON MAXIMUM FACE VELOCITY OF 750 FPM, 0.15 IN WG MAXIMUM AIR PRESSURE DROP, 5 FT WG MAXIMUM WATER PRESSURE DROP.
A. UNIT CEILING MOUNTED ABOVE COLD STORAGE.
GENERAL NOTES:
MAU-02-01 LEVEL 2 KITCHEN 8 13 9,000 - CENTRIFUGAL 1 4.1 1.0 2,036 1.15 9.4 15.0 230/3 Y 1 100/73.4 77.12/64.08 25 62 208/3 N 2,700 DAIKIN CAH021GDGC 1,2,3,4
TAG LOCATION SERVICE (MERV) (MERV) (CFM) (CFM) TYPE QTY (IN WG) (IN WG) (RPM) INDEX (BHP) (HP) PHASE (Y/N) QTY (°F DB/WB) (°F DB/WB) (°F DB) (°F DB) PHASE (Y/N) (LBS) & MODEL NOTES
PRE FINAL MAX MIN FAN TSP ESP SPEED ENERGY POWER RATING VOLT/ VFD EAT LAT EAT LAT VOLT/ POWER WEIGHT MANUFACTURER
AIRFLOW FAN MOTOR COOLING HEATING GEN. APPROX.
FILTERS SUPPLY FAN REFRIGERANT COIL ELECTRICAL
MAKE-UP AIR UNIT SCHEDULE
271 424426273
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
BIG BEND NATIONAL PARK
RMK
RMK
DAW
12-10-2024
EQUIPMENT SCHEDULES -
MECHANICAL
M0.04 171153
259631-317515
FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
4. OUTDOOR UNIT CONNECTED TO MAKE-UP AIR UNIT THROUGH VRF COIL KIT. REFER TO VRF EXPANSION VALVE KIT SCHEDULE AND MAKE-UP AIR UNIT SCHEDULE FOR FURTHER DETAIL.
3. OUTDOOR UNIT CONNECTED TO AIR HANDLING UNIT THROUGH VRF COIL KIT. REFER TO VRF EXPANSION VALVE KIT SCHEDULE AND AIR HANDLING UNIT SCHEDULE FOR FURTHER DETAIL.
2. PROVIDE BAFFLE PLATES ON EACH SIDE OF UNIT, LARGE CANOPY OVERHEAD, AND PEDESTALS FOR MOUNTING. REFER TO MANUFACTURERS INSTALLATION GUIDELINES FOR LOW AMBIENT AND SNOW CONDITIONS.
1. UNIT COMPRISED OF 2 MODULES WITH SEPARATE ELECTRICAL CONNECTIONS & DISCONNECTS. SEE ELECTRICAL SHEETS FOR COORDINATION.
NOTES:
D. PROVIDE 16" STAINLESS METAL STAND. MOUNT VRF UNITS 16" ABOVE GRADE ON TOP OF STAND. BOLT VRF UNITS TO BASE, PROVIDE 3/4" MASON SUPERWAFFLE NEOPRENE PAD MOUNTS BETWEEN STAND AND UNIT BASE.
C. REFRIGERANT CHARGE INDICATED IS FOR THE EQUIPMENT ONLY. PROVIDE NECESSARY REFRIGERANT QUANTITY TO MEET THE REQUIREMENTS FOR THE SPECIFIC INSTALLATION.
B. SIZE REFRIGERANT PIPING PER MANUFACTURER'S INSTRUCTIONS.
A. MINIMUM EFFICIENCY IS AT AHRI STANDARD CONDITIONS.
GENERAL NOTES:
CU-LL-03 LOWER LEVEL INDOOR VRF 31.4 358 R410A 51.6 208/3 73.7 + 73.7 80 + 80 N 2,200 DAIKIN REYQ480AATJA 1,2
CU-LL-02C LOWER LEVEL MAU-02-01 15.6 167 R410A 25.8 208/3 59.8 60 N 1,000 DAIKIN RXYQ192AATJA 2, 4
CU-LL-02B LOWER LEVEL MAU-02-01 15.6 167 R410A 25.8 208/3 59.8 60 N 1,000 DAIKIN RXYQ192AATJA 2, 4
CU-LL-02A LOWER LEVEL MAU-02-01 15.6 167 R410A 25.8 208/3 59.8 60 N 1,000 DAIKIN RXYQ192AATJA 2, 4
CU-LL-01 LOWER LEVEL AHU-LL-01 10 107 R410A 25.4 208/3 36.5 40 N 800 DAIKIN RXYQ120AATJA 2, 3
TAG LOCATION SERVICE (TON) (MBH) TYPE (LBS) PHASE (A) (A) (Y/N) (LBS) & MODEL NOTES
COOLING HEATING CHARGE VOLT/ MCA MOCP POWER WEIGHT MANUFACTURER
CAPACITY REFRIGERANT ELECTRICAL GEN. APPROX.
VRF OUTDOOR UNIT SCHEDULE
3. PROVIDE FACTORY MERV13 FILTER BOX OR CONTRACTOR TO CREATE FIELD FABRICATED FILTER BOX.
2. PROVIDE MINI ASPEN CONDENSATE PUMP (DACA-CP1-1) WHICH DRAWS POWER FROM THE INDOOR UNIT AND IS CONCEALED WITHIN CASING.
1. PROVIDE UNIT WITH A MINIMUM OF TWO STAGES OF FAN SPEED CONTROL. MINIMUM FAN SPEED CAN BE NO GREATER THAN 66% OF FULL SPEED.
NOTES:
G. WALL MOUNTED UNITS HAVE AN INTEGRAL WASHABLE FILTER.
F. FAN COIL UNITS ARE SELECTED AT HIGH SPEED.
E. MINIMUM AND MAXIMUM ALLOWABLE SUPPLY AIR TEMPERATURES ARE 55°F AND 105°F, RESPECTIVELY.
D. DUCTWORK CONNECTED TO DUCTED FAN-COIL UNITS IS LOW PRESSURE
C. ALL FAN MOTORS ARE EC TYPE
B. ALL DUCTED AND CASSETTE UNITS ARE PROVIDED WITH AN INTEGRAL CONDENSATE PUMP CAPABLE OF 27 IN WG OF LIFT.
A. MINIMUM EFFICIENCY IS AT ARI STANDARD CONDITIONS.
GENERAL NOTES:
FCU-02-04 LEVEL 2 KITCHEN CU-LL-03 BSB-02-01 DUCTED CEILING CONCEALED 1,620 45,465 35,059 59,983 208/1 3.40 N 150 DAIKIN FXMQ54MVJU 1, 3
FCU-02-03 LEVEL 2 KITCHEN CU-LL-03 BSB-02-01 DUCTED CEILING CONCEALED 1,620 45,465 35,059 59,983 208/1 3.40 N 150 DAIKIN FXMQ54MVJU 1, 3
FCU-02-02 LEVEL 2 KITCHEN CU-LL-03 BSB-02-01 DUCTED CEILING CONCEALED 1,620 45,465 35,059 59,983 208/1 3.40 N 150 DAIKIN FXMQ54MVJU 1, 3
FCU-02-01 LEVEL 2 EMPLOYEE DINING CU-LL-03 BSB-02-01 DUCTED CEILING CONCEALED 690 20,233 16,404 26,989 208/1 1.80 N 100 DAIKIN FXMQ24PBVJU 1, 3
FCU-01-10 LEVEL 1 MPOE CU-LL-03 BSB-01-01 WALL MOUNTED 635 24,000 18,000 26,500 208/1 0.60 N 50 DAIKIN FXAQ24PVJU 1, 2
FCU-01-09 LEVEL 1 DINING CU-LL-03 BSB-01-02 DUCTED CEILING CONCEALED 1,380 40,432 31,157 53,978 208/1 3.40 N 150 DAIKIN FXMQ48PBVJU 1, 3
FCU-01-08 LEVEL 1 DINING CU-LL-03 BSB-01-02 DUCTED CEILING CONCEALED 1,380 40,432 31,157 53,978 208/1 3.40 N 150 DAIKIN FXMQ48PBVJU 1, 3
FCU-01-07 LEVEL 1 DINING CU-LL-03 BSB-01-02 DUCTED CEILING CONCEALED 1,380 40,432 31,157 53,978 208/1 3.40 N 150 DAIKIN FXMQ48PBVJU 1, 3
FCU-01-06 LEVEL 1 RECEPTION CU-LL-03 BSB-01-02 DUCTED CEILING CONCEALED 1,120 30,316 24,862 39,989 208/1 2.90 N 150 DAIKIN FXMQ36PBVJU 1, 3
FCU-01-05 LEVEL 1 RECEPTION CU-LL-03 BSB-01-02 DUCTED CEILING CONCEALED 1,120 30,316 24,862 39,989 208/1 2.90 N 100 DAIKIN FXMQ36PBVJU 1, 3
FCU-01-04 LEVEL 1 RETAIL CU-LL-03 BSB-01-01 DUCTED CEILING CONCEALED 690 20,233 16,404 26,989 208/1 1.80 N 100 DAIKIN FXMQ24PBVJU 1, 3
FCU-01-03 LEVEL 1 RETAIL CU-LL-03 BSB-01-01 DUCTED CEILING CONCEALED 1,095 25,266 20,642 33,984 208/1 2.80 N 150 DAIKIN FXMQ30PBVJU 1, 3
FCU-01-02 LEVEL 1 RETAIL STORAGE CU-LL-03 BSB-01-01 DUCTED CEILING CONCEALED 320 6,312 5,652 8,496 208/1 0.60 N 100 DAIKIN FXMQ07PBVJU 1, 3
FCU-01-01 LEVEL 1 CONCESSIONER CU-LL-03 BSB-01-01 DUCTED CEILING CONCEALED 690 20,233 16,404 26,989 208/1 1.80 N 100 DAIKIN FXMQ24PBVJU 1, 3
FCU-LL-01 LOWER LEVEL RECEIVING CU-LL-03 BSB-LL-01 WALL MOUNTED 260 6,300 5,585 8,500 208/1 0.30 N 50 DAIKIN FXAQ07PVJU 1, 2
TAG LOCATION SERVICE UNIT BOX TYPE (CFM) (MBH) (MBH) (MBH) PHASE (A) (Y/N) (LBS) & MODEL NOTES
OUTDOOR SELECTOR AIRFLOW TOTAL SENSIBLE TOTAL VOLT/ MCA POWER WEIGHT MANUFACTURER
BRANCH COOLING HEATING ELECTRICAL GEN. APPROX.
VRF INDOOR UNIT SCHEDULE
1. NONE
NOTES:
B. SIZE REFRIGERANT PIPING PER MANUFACTURER'S INSTRUCTIONS.
A. PROVIDE ISOLATION BALL VALVES FOR EACH REFRIGERANT BRANCH.
GENERAL NOTES:
BSB-02-01 CU-LL-03 LEVEL 02 6 4 N 100 208/1 0.6 15 DAIKIN BSF6Q54TVJ
BSB-01-02 CU-LL-03 LEVEL 01 6 5 N 100 208/1 0.6 15 DAIKIN BSF6Q54TVJ
BSB-01-01 CU-LL-03 LEVEL 01 6 5 N 100 208/1 0.6 15 DAIKIN BSF6Q54TVJ
BSB-LL-01 CU-LL-03 LOWER LEVEL 1 1 N 50 208/1 0.1 15 DAIKIN BSQ36TVJ
TAG UNIT LOCATION PORTS FCUs (Y/N) (LBS) PHASE (A) (A) & MODEL NOTES
OUTDOOR OF CONNECTED POWER WEIGHT VOLT/ MCA MOCP MANUFACTURER
NUMBER QTY OF GEN. APPROX. ELECTRICAL
VRF HEAT RECOVERY BOX SCHEDULE
2. PROVIDE EKEQFCBAV3-US AHU KIT W-CONTROL BOX FOR EACH EXKV EXPANSION VALVE KIT.
1. MOUNT EQUIPMENT TO UNISTRUT STRUCTURE.
NOTES:
B. INSTALL AHU AIR HANDLING UNIT INTEGRATION KIT ACCORDING TO MANUFACTURER GUIDELINES AND REQUIREMENTS.
A. REFER TO 4/M5.05 FOR SYSTEM DIAGRAM.
GENERAL NOTES:
EXVK-AHU-LL-01 LOWER LEVEL AHU-LL-01 1 208/1 1 15.75 8.5 6.5 DAIKIN EKEXV400-US 1, 2
EXVK-MAU-02-01 ROOF MAU-02-01 3 208/1 3 15.75 8.5 6.5 DAIKIN EKEXV500-US 1, 2
TAG LOCATION SERVICE PHASE (#) (IN) (IN) (LBS) & MODEL NOTES
QTY VOLT/ CONN. QTY WIDTH HEIGHT WEIGHT MANUFACTURER
ELECTRICAL DIMENSIONS APPROX.
VRF EXPANSION VALVE KIT SCHEDULE
424272 426274
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
BIG BEND NATIONAL PARK
Designer
Author
Checker
12-10-2024
EQUIPMENT SCHEDULES -
MECHANICALM0.05
100% FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
3. PROVIDE MULTIPLE SEGMENT DAMPER WITH MULTIPLE ELECTRICAL CONNECTIONS TO ACTUATORS AS REQUIRED
2. PROVIDE WITH 3 POSITION BLADE OPTION. FULL OPEN, FULL CLOSED AND PARTIALLY OPEN POSITION TO BE BALANCED TO NORMAL OPERATING AIR VOLUME
1. PROVIDE WITH FRONT GRILLE ACCESS
NOTES:
C. ALL FIRE SMOKE DAMPERS ON A SINGLE SYSTEM CLOSE ON DETECTION OF SMOKE AND SHUTDOWN OF THE AIR MOVING SYSTEMS.
B. INITIATING DEVICES: DUCT SMOKE DETECTOR (DD), AREA SMOKE DETECTOR (AD) OR FIRE ALARM SYSTEM (FA)
A. PROVIDE WITH REMOTE DAMPER BLADE POSITION INDICATOR
GENERAL NOTES:
FSD-02-08 LEVEL 2 RETURN AHU-LL-01 165 AD 120/1 1 36 12 RUSKIN
FSD-02-07 LEVEL 2 SUPPLY AHU-LL-01 165 AD 120/1 1 10 24 RUSKIN
FSD-02-06 LEVEL 2 RETURN AHU-LL-01 165 AD 120/1 1 36 12 RUSKIN
FSD-02-05 LEVEL 2 SUPPLY AHU-LL-01 165 AD 120/1 1 10 24 RUSKIN
FSD-02-04 LEVEL 2 RETURN AHU-LL-01 165 AD 120/1 1 36 12 RUSKIN
FSD-02-03 LEVEL 2 SUPPLY AHU-LL-01 165 AD 120/1 1 10 24 RUSKIN
FSD-02-02 LEVEL 2 RETURN AHU-LL-01 165 AD 120/1 1 12 12 RUSKIN
FSD-02-01 LEVEL 2 SUPPLY AHU-LL-01 165 AD 120/1 1 12 12 RUSKIN
FSD-01-02 LEVEL 1 RETURN AHU-LL-01 165 AD 120/1 1 20 20 RUSKIN
FSD-01-01 LEVEL 1 SUPPLY AHU-LL-01 165 AD 120/1 1 24 20 RUSKIN
FSD-LL-02 LOWER LEVEL RETURN AHU-LL-01 165 AD 120/1 1 20 24 RUSKIN
FSD-LL-01 LOWER LEVEL SUPPLY AHU-LL-01 165 AD 120/1 1 30 16 RUSKIN
TAG LOCATION SERVICE SYSTEM (°F) DEVICE PHASE (#) (IN) (IN) & MODEL NOTES
TEMP INITIATING VOLT/ CONN. QTY WIDTH HEIGHT MANUFACTURER
STAT ELECTRICAL DIMENSIONS
FIRE SMOKE DAMPER SCHEDULE
VV = VARIABLE AIR VOLUME TERMINAL UNIT
KEY:
2. OCCUPANCY SENSOR LOCATED WITHIN SPACE.
1. CO2 SENSOR LOCATED ADJACENT TO THERMOSTAT.
NOTES:
B. AIR PRESSURE DROP THROUGH TERMINAL UNIT TO BE NO GREATER THAN 0.20 IN.WG. WITHOUT COIL OR 0.60 IN.WG. WITH COIL.
A. PRIMARY AIR TEMPERATURE 70°F (SUMMER), 70°F (WINTER).
GENERAL NOTES:
TU-02-01 LEVEL 2 VV 6 115 0 TITUS DESV 1,2
TU-01-04 LEVEL 1 VV 6 115 0 TITUS DESV 1,2
TU-01-03 LEVEL 1 VV 12 1,425 1,425 TITUS DESV 1,2
TU-01-02 LEVEL 1 VV 10 685 685 TITUS DESV 1,2
TU-01-01 LEVEL 1 VV 6 220 220 TITUS DESV 1,2
TU-LL-01 LOWER LEVEL VV 6 250 250 TITUS DESV 1,2
TAG LOCATION TYPE (IN) CFM CFM & MODEL NOTES
INLET MAX MIN MANUFACTURER
PRIMARY AIR
TERMINAL UNIT SCHEDULE
8. FAN CONTROLLED VIA LINE VOLTAGE TSTAT.
7. PROVIDE GREASE TRAP.
6. UNIT SPEED IS CONTROLLED THROUGH VFD WHICH IS CONNECTED TO STREIVOR DEMANDAIRE PLATINUM CONTROL SYSTEM (REFER TO KITCHEN CONSULTANT DRAWINGS. PROVIDE ALL REQUIRED SENSORS AND CONTROL ACCESSORIES FOR A COMPLETE INSTALLATION.
5. PROVIDE VARI-GREEN MOTOR, DRIVE AND CONTROLLER. FAN TO BE CONNECTED INTO BMS.
4. PROVIDE FACTORY SUPPLIED ROOF CURB.
3. FAN SELECTED FOR TYPE 2 VAPOR EXHAUST APPLICATION. PROVIDE CORROSION RESISTANT COMPONENTS
2. FAN SELECTED FOR TYPE 1 GREASE EXHAUST APPLICATION.
1. EC MOTOR.
NOTES:
A. NONE
GENERAL NOTES:
VEF-R-01 ROOF VAPOR EXHAUST CENTRIFUGAL DIRECT 1,300 - 1.0 1,660 208/1 0.35 0.50 N N 100 GREENHECK CUE-120-VG 1,3,4,6
KEF-R-01 ROOF GREASE EXHAUST CENTRIFUGAL DIRECT 7,700 - 2.0 1,055 208/3 4.37 7.50 Y N 500 GREENHECK CUE-300HP-B 1,2,4,6,7
EF-01-02 LEVEL 1 RESTROOM INLINE DIRECT 180 180 0.5 1,578 208/1 0.10 0.25 N N 50 GREENHECK SQ-97-VG 1, 5
EF-01-01 LEVEL 1 RESTROOM INLINE DIRECT 825 825 0.5 1,444 208/1 0.12 0.25 N N 100 GREENHECK SQ-100-VG 1, 5
EF-LL-01 LOWER LEVEL ELECTRICAL ROOM INLINE DIRECT 150 - 0.3 1,664 208/1 0.03 0.07 N N 100 GREENHECK SQ-70-VG 1,5,8
TAG LOCATION SERVICE TYPE DRIVE (CFM) (CFM) (IN WG) (RPM) PHASE (BHP) (HP) (Y/N) (Y/N) (LBS) & MODEL NOTES
MAX MIN ESP SPEED VOLT/ POWER RATING VFD POWER WEIGHT MANUFACTURER
FAN GEN. APPROX.
AIRFLOW ELECTRICAL
LODGE FAN SCHEDULE
3. THROW VALUES ARE BASED ON 45 DEGREE BLADE DEFLECTION ANGLES.
2. PROVIDE AIR SCOOP DEVICE FOR AIR BALANCING.
1. ONE 1-INCH SLOT.
NOTES:
C. ADJUST THROW DIRECTION AND QUANTITY PRIOR TO AIR BALANCING.
B. THROW VALUES GIVEN FOR TERMINAL VELOCITIES 150, 100, AND 50 FPM FOR ISOTHERMAL CONDITIONS.
A. NOISE CRITERIA (NC) BASED ON ROOM ABSORPTION OF 10 dB, MEASURED PER ANSI/ASHRAE STANDARD 70.
GENERAL NOTES:
241 360 - 60x3 60x3 22 - 1
121 240 - 48x3 48x3 20 - 1S-2
LINEAR CEILING RETURN
GRILLE
1-SLOT, CONTINUOUS SLOT
0 120 - 24x3 24x3 20 -
TITUS FL-10
261 370 10 48x3 48x3 26 10-15-23 1
0 260 8 48x3 48x3 25 7-11-19 1S-1
LINEAR CEILING SUPPLY
DIFFUSER
1-SLOT, FIXED BLADE,
INSULATED PLENUM,
ADJUSTABLE THROW
0 140 8 24x3 24x3 16 5-8-14
TITUS FL-10
H-4
DUCT MOUNTED SUPPLY AIR
GRILLE
STEEL AEROBLADE DOUBLE
DEFLECTION
0 395 12x10 21 7-8-12 TITUS S300FL 2, 3
0 2355 36x20 18 -
H-2 SIDEWALL RETURN GRILLE
STEEL AEROBLADE DOUBLE
DEFLECTION
0 1375 36x12
16 -
TITUS S300FL
0 525 12x12 17 10-13-19
H-1 SIDEWALL SUPPLY GRILLE
STEEL AEROBLADE DOUBLE
DEFLECTION
0 150 6x6
19 10-12-18
TITUS 272RL
1,671 3,000 22x46 24x48 24x48 24 -
1,129 1,670 22x22 24x24 24x24 26 -
1,129 1,670 22x22 24x24 24x24 26 -
781 1,125 18x18 24x24 20x20 24 -
341 780 15x15 24x24 17x17 22 -
C-2
CEILING RETURN/ EXHAUST
GRILLE
PERFORATED FACE, STEEL,
ROUND DUCT CONNECTION
0 340 10x10 24x24 12x12 17 -
TITUS PAR
511 780 16x16 24x24 23x23 28 4-6-11
346 510 12x12 24x24 19x19 24 3-5-9
221 345 10x10 24x24 17x17 21 3-4-8
126 220 8x8 24x24 15x15 17 2-3-6
C-1 CEILING SUPPLY DIFFUSER
PERFORATED FACE, MODULAR
CORE, ADJUSTABLE 4-WAY
THROW
0 125 6x6 24x24 13x13 12 2-2-5
TITUS PMC
TAG TYPE DESCRIPTION (CFM) (CFM) (IN) (IN) (IN) NC (FT) & MODEL NOTES
MIN MAX SIZE T-BAR HARD LID MAX THROW MANUFACTURER
AIRFLOW RANGE INLET FACE SIZE
DIFFUSERS AND GRILLES
FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
DRAWING NO.
171153
PMIS/PKG NO.
259631-317515TECH. REVIEW:
RMK
RMK
273 424426275
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
BIG BEND NATIONAL PARK
RMK
RMK
DAW
12-10-2024
EQUIPMENT SCHEDULES -
MECHANICAL
M0.06 171153
259631-317515
FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
RSC - PREFABRICATED ROOF SPRING CURB SUCH AS MASON TYPE RSC, OR EQUAL.
ISB - CONCRETE-INERTIA BASE WITH UNHOUSED SPRING MOUNTS AND SEPARATE SNUBBERS SUCH AS MASON INDUSTRIES BMK/KSL.
HS - COMBINATION SPRING AND NEOPRENE HANGER SUCH AS MASON TYPE 30N OR EQUAL.
HR - NEOPRENE HANGERS SUCH AS MASON TYPE HD OR EQUAL, 40 DUROMETER OR SOFTER.
MASON TYPE HG FOR ALL BOLTED CONNECTIONS THROUGH NEOPRENE PADS.
PR - RESILIENT PADS SUCH AS MASON INDUSTRIES TYPE SUPER W OR EQUAL. USE 50 DUROMETER OR SOFTER PADS AND SIZE TO ACHIEVE SPECIFIED DEFLECTION WITH MULTIPLE LAYERS SEPARATED BY STEEL SHIMS. INCLUDE NEOPRENE SHOULD WASHERS SUCH AS
MR - RESILIENT FLOOR MOUNTS SUCH AS MASON INDUSTRIES TYPE ND OR BR, OR EQUAL
RS - RESTRAINED-SPRING MOUNTS SUCH AS MASON INDUSTRIES TYPE SSLFH-X OR SLRSO. USE INDEPENDENT SNUBBERS SUCH AS MASON TYPE Z-1225, OR EQUAL
FS - FREE STANDING SPRINGS SUCH AS MASON INDUSTRIES TYPE SLF, OR EQUAL. USE INDEPENDENT SNUBBERS SUCH AS MASON TYPE Z-1225, OR EQUAL. DO NOT USE HOUSED OR INTERNALLY RESTRAINED SPRINGS.
LEGEND:
REFRIGERANT PIPING - - - - - - - - CLAMPS AROUND NEOPRENE FOAM INSULATION ACCEPTABLE VRF HEAT RECOVERY BOXES (DAIKIN) BSB-XX-XX VARIES - - - - HR - NEOPRENE HANGERS, 40 DUROMETER OR SOFTER
VRF OUTDOOR CONDENSING UNITS (DAIKIN) CU-R-XX LOADING DOCK UP TO 40 TONS - - - HR - NEOPRENE PAD, 3/4" MASON SUPERWAFFLE
DUCTED VRF FAN COIL UNITS (DAIKIN) FCU-XX-XX VARIES < 1.0 - - - HS 1.0 COMBINATION NEOPRENE/SPRING HANGERS
SPLIT SYSTEM CONDENSING UNITS (DAIKIN) ACCU-XX-XX LOADING DOCK 2-3 TON - - - RS 1.0 FLOOR OR PLATFORM SUPPORTED WITH RESTRAINED-SPRING MOUNTS
WALL MOUNTED SPLIT SYSTEM FAN COIL UNITS (DAIKIN) FCU-XX-XX RECEIVING < 1.0 - - - - - NONE
EF-XX-XX RESTROOMS UP TO 1/2 VARIES N -
CENTRIFUGAL EXHAUST FANS (GREENHECK USF) KEF-R-01, VEF-R-01 ROOF UP TO 7.5 1,000 - 2,000 Y - RS 2.0 RESTRAINED SPRING MOUNTS WITH INDEPENDENT SNUBBERS
MAKEUP AIR UNIT (DAIKIN) MAU-02-01 LEVEL 2 UP TO 7.5 2079 Y PR RS
2.0
ENTIRE UNIT ON NEORPENE PAD. FANS ARE INTERNALLY ISOLATED WITH RESTRAINED SPRINGS EQUAL TO RS
AIR HANDLING UNIT (DAIKIN) AHU-LL-01 LOWER LEVEL UP TO 15 2626 Y PR RS
2.0
ENTIRE UNIT ON NEORPENE PAD. FANS ARE INTERNALLY ISOLATED WITH RESTRAINED SPRINGS EQUAL TO RS
EQUIPMENT TYPE TAG LOCATION HP RPM VFD BASE ISOLATOR TYPE STATIC DEFLECTION (IN.) NOTES
VIBRATION ISOLATION SCHEDULE
210 EMPLOYEE DINING
204 KITCHEN
2,625 12 31,500 CU-LL-03 R-410A 52 A1 26 819.0 YES 1
123 TELECOM 175 14 2,450 CU-LL-03 R-410A 52 A1 26 63.7 YES 1
133 FREEZER
132 RETAIL STORAGE
130 RETAIL
121 JAN
112 MENS
113 WOMENS
103 CORRIDOR
100 RECEPTION
5,805 14 81,270 CU-LL-03 R-410A 52 A1 26 2,113.0 YES 1
000 CORRIDOR
006 STORAGE
004 MECHANICAL EQUIPMENT
002 RECEIVING
001 LOADING
1,500 9 13,500 CU-LL-03 R-410A 52 A1 26 351.0 YES 1
NUMBER NAME (SF) (FT) (CUBIC FT) SYSTEM REFRIGERANT (LBS) CLASSIFICATION CUBIC FEET (LBS) COMPLIANCE NOTES
AREA CEILING HEIGHT SPACE VOLUME CHEMICAL SYSTEM VOLUME
MAX LBS
PER 1000
MAX LBS IS SPACE IN
SPACE REFRIGERANT
1. ROOMS ARE CONSIDERED A COMBINED AIR VOLUME.
NOTES:
A. CALCULATIONS BASED ON 2021 INTERNATIONAL MECHANICAL CODE: CHAPTER 11 - REFRIGERATION.
GENERAL NOTES:
ASHRAE 15 CALCULATION
274 424426276
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
BIG BEND NATIONAL PARK
Designer
Author
Checker
12-10-2024
EQUIPMENT SCHEDULES -
MECHANICALM0.07
100% FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
3. ACTUAL EXHAUST MINIMUM WILL BE LOWER WHEN HOODS ARE OFF OR AT LOW SPEED.
2. SUPPLY AIR REPRESENTS REQUIRED VENTILATION AIR TO THE SPACES.
1. KITCHEN MAKE-UP AIR TO MAINTAIN MAXIMUM AIRFLOW RATES WHEN HOODS ARE ENERGIZED FOR PRESSURIZATION.
NOTES:
MAINTAIN PROGRAMMED AIRFLOW OFFSET TO MAINTAIN 300CFM POSITIVE PRESSURIZATION IN DINING SPACE.
C. AS DINING VAVS DECREASE DUE TO OCCUPANCY, VARIABLE RELIEF AIR FAN DECREASES EXHAUST AIRFLOW TO
MIN/MAX FAN SPEED. IN THIS SCENARIO, KITCHEN VAVS ARE ALSO AT MAXIMUM AIRFLOW.
B. IN GENERAL, KITCHEN VAVS SHOULD TRACK HOOD AIRFLOWS AS A PERCENTAGE OF VFD SPEED BETWEEN
A. IN THIS SCENARIO, KITCHEN HOODS ARE AT MAXIMUM AIRFLOW AND DINING IS AT MAXIMUM VENTILATION AIRFLOW.
GENERAL NOTES:
BUILDING TOTAL: 11,460 11,535 75
AHU-LL-01 VENTILATION AIR RELIEF 1,470 2,850 1,380 2
EF-01-01, EF-01-02 TOILETS, JANITORS ROOM 1,005 (1,005)
KITCHEN TOTAL: 8,985 8,685 (300)
MAU-02-01 KITCHEN - 2,530 2,530 1
D04 POTWASH HOOD TYPE-2 1,300 - (1,300) 3
K03 KITCHEN HOOD TYPE-1 1,695 1,360 (335) 3
K02 KITCHEN HOOD TYPE-1 3,280 2,620 (660) 3
K01 KITCHEN HOOD TYPE-1 2,710 2,175 (535) 3
EXHAUST HOOD / CEILING DIFFUSER AREA SERVED EXHAUST TYPE MAX EXHAUST CFM MIN VENTILATION AIR CFM OFFSET CFM NOTES
KITCHEN AIR BALANCE: MAX EXHAUST, MIN VENTILATION
3. ACTUAL EXHAUST MINIMUM WILL BE LOWER WHEN HOODS ARE OFF OR AT LOW SPEED.
2. SUPPLY AIR REPRESENTS REQUIRED VENTILATION AIR TO THE SPACES.
1. KITCHEN MAKE-UP AIR TO MAINTAIN MAXIMUM AIRFLOW RATES WHEN HOODS ARE ENERGIZED FOR PRESSURIZATION.
NOTES:
MAINTAIN PROGRAMMED AIRFLOW OFFSET TO MAINTAIN 300CFM POSITIVE PRESSURIZATION IN DINING SPACE.
C. AS DINING VAVS DECREASE DUE TO OCCUPANCY, VARIABLE RELIEF AIR FAN DECREASES EXHAUST AIRFLOW TO
MIN/MAX FAN SPEED. IN THIS SCENARIO, KITCHEN VAVS ARE ALSO AT MAXIMUM AIRFLOW.
B. IN GENERAL, KITCHEN VAVS SHOULD TRACK HOOD AIRFLOWS AS A PERCENTAGE OF VFD SPEED BETWEEN
A. IN THIS SCENARIO, KITCHEN HOODS ARE AT MAXIMUM AIRFLOW AND DINING IS AT MAXIMUM VENTILATION AIRFLOW.
GENERAL NOTES:
BUILDING TOTAL: 11,890 11,985 95
AHU-LL-01 VENTILATION AIR RELIEF 1,900 3,300 1,400 2
EF-01-01, EF-01-02 TOILETS, JANITORS ROOM 1,005 (1,005)
KITCHEN TOTAL: 8,985 8,685 (300)
MAU-02-01 KITCHEN - 2,530 2,530 1
D04 POTWASH HOOD TYPE-2 1,300 - (1,300) 3
K03 KITCHEN HOOD TYPE-1 1,695 1,360 (335) 3
K02 KITCHEN HOOD TYPE-1 3,280 2,620 (660) 3
K01 KITCHEN HOOD TYPE-1 2,710 2,175 (535) 3
EXHAUST HOOD / CEILING DIFFUSER AREA SERVED EXHAUST TYPE MAX EXHAUST CFM MAX VENTILATION AIR CFM OFFSET CFM NOTES
KITCHEN AIR BALANCE: MAX EXHAUST, MAX VENTILATION
1. DESIGN OCCUPANCY REPRESENTS THE ACTUAL OCCUPANCY DOCUMENTED ON THE PLANS.
NOTES:
B. REFER TO AIR HANDLING UNIT SCHEDULE FOR ACTUAL OUTDOOR AIR FLOW RATE.
A. SYSTEM OUTDOOR AIR CALCULATION IS BASED ON CHAPTER 6 OF THE ASHRAE STANDARD 62.1-2016.
GENERAL NOTES:
CODE REQUIRED OUTDOOR AIR INTAKE FLOWRATE - Vot: 2,995
UNCORRECTED OUTDOOR AIR INTAKE - Vou: 1,376
SYSTEM POPULATION: 0 OCCUPANT DIVERSITY - D: 0.00
TOTAL AIRFLOW: 3,275 SYSTEM VENTILATION EFFICIENCY - Ev: 0.46
TOTALS: 12385 3275 445 169 2583 3238 Zp max = 1.00
201 BAR 265 175 FOOD - BARS, COCKTAIL LOUNGES TU-01-03 8 0.18 100 26.5 12.0 137.7 0.8 173 1.0
006 STORAGE 205 25 OFFICE - OCCUPIABLE STORAGE FOR DRY MATERIALS TU-LL-01 5 0.06 2 0.4 1.0 17.3 0.8 22 0.9
005 PLUMBING ROOM 145 15 OFFICE - OCCUPIABLE STORAGE FOR DRY MATERIALS TU-LL-01 5 0.06 2 0.3 0.0 8.7 0.8 11 0.7
004 MECHANICAL ROOM 750 65 OFFICE - OCCUPIABLE STORAGE FOR DRY MATERIALS TU-LL-01 5 0.06 2 1.5 1.0 50.0 0.8 63 1.0
003 ELECTRICAL ROOM 270 25 OFFICE - OCCUPIABLE STORAGE FOR DRY MATERIALS TU-LL-01 5 0.06 2 0.5 0.0 16.2 0.8 21 0.8
200 DINING 2005 1250 FOOD - RESTAURANT DINING ROOMS TU-01-03 8 0.18 70 140.4 85.0 998.4 0.8 1248 1.0
210 BREAKROOM 490 115 GENERAL - BREAK ROOMS TU-02-01 5 0.06 25 12.3 12.0 89.4 0.8 112 1.0
203 CORRIDOR 130 10 GENERAL - CORRIDORS MAU-02-01 0 0.06 0 0.0 0.0 7.8 0.8 10 1.0
204 KITCHEN 1795 490 FOOD - KITCHEN (COOKING) MAU-02-01 8 0.18 20 35.9 9.0 390.6 0.8 489 1.0
100 RECEPTION 1250 100 PUBLIC -LOBBIES TU-01-04 5 0.06 150 187.5 1.0 80.0 0.8 100 1.0
102 CORRIDOR 150 15 GENERAL - CORRIDORS TU-01-04 0 0.06 0 0.0 0.0 9.0 0.8 12 0.8
130 RETAIL 2230 685 RETAIL - SALES (EXCEPT AS BELOW) TU-01-02 8 0.12 15 33.5 37.0 545.1 0.8 682 1.0
103 CORRIDOR 615 50 GENERAL - CORRIDORS TU-01-01 0 0.06 0 0.0 0.0 36.9 0.8 47 0.9
131 STORAGE 680 70 OFFICE - OCCUPIABLE STORAGE FOR DRY MATERIALS TU-01-01 5 0.06 2 1.4 3.0 55.8 0.8 70 1.0
120 OFFICE 800 100 OFFICE - OFFICE SPACE TU-01-01 5 0.06 5 4.0 6.0 78.0 0.8 98 1.0
002 RECEIVING 105 15 OFFICE - OFFICE SPACE TU-LL-01 5 0.06 5 0.5 1.0 11.3 0.8 15 1.0
001 LOADING 185 45 MISC - SHIPPING/RECEIVING TU-LL-01 10 0.12 2 0.4 1.0 32.2 0.8 41 0.9
000 CIRCULATION 315 25 GENERAL - CORRIDORS TU-LL-01 0 0.06 0 0.0 0.0 18.9 0.8 24 1.0
LOCATION (SF) (CFM) CLASSIFICATION UNIT (CFM/PERSON) (CFM/SF) (PEOPLE/1000SF) POPULATION POPULATION (CFM) Ez (CFM) Zp NOTES
AREA RATE OCCUPANCY TERMINAL Rp Ra DENSITY CODE DESIGN Vbz EFFECTIVENESS Voz AIR FRACTION
FLOOR AIRFLOW ASSOCIATED RATE RATE OCCUPANT RATE DISTRIBUTION AIR INTAKE OUTDOOR
PRIMARY AIRFLOW AIRFLOW DEFAULT AIRFLOW ZONE AIR OUTDOOR PRIMARY
OUTDOOR OUTDOOR OUTDOOR
PEOPLE AREA
AHU-LL-01
VENTILATION SCHEDULE - MULTIPLE SPACES
FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
DRAWING NO.
171153
PMIS/PKG NO.
259631-317515TECH. REVIEW:
RMK
RMK
275 424426277
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
BIG BEND NATIONAL PARK
Designer
Author
Checker
12-10-2024
EQUIPMENT SCHEDULES -
MECHANICALM0.08
100% FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
2. PROVIDE VARI-GREEN MOTOR, DRIVE AND CONTROLLER. FAN TO BE CONNECTED INTO BMS.
1. EC MOTOR.
NOTES:
A. NONE
GENERAL NOTES:
EF-VC-01 LEVEL 1 RESTROOM INLINE DIRECT 375 375 1.0 2,470 115/1 0.50 0.75 ECM N 60 GREENHECK SQ-97-VG 1,2
TAG LOCATION SERVICE TYPE DRIVE (CFM) (CFM) (IN WG) (RPM) PHASE (BHP) (HP) (Y/N) (Y/N) (LBS) & MODEL NOTES
MAX MIN ESP SPEED VOLT/ POWER RATING VFD POWER WEIGHT MANUFACTURER
FAN GEN. APPROX.
AIRFLOW ELECTRICAL
VCS FAN SCHEDULE
4.PROVIDE WITH A LINE VOLTAGE THERMOSTAT.
3.PROVIDE 2" SEMI RECESSED TRIM KIT (1500-5000W)
2. PROVIDE HEATER CABINET AND EXTERIOR WITH BRONZE FINISH
1. PROVIDE WITH 24V RELAY WITH TRANSFORMER.
NOTES:
A.NONE
GENERAL NOTES:
EUH-VC-03 WOMENS RESTROOM WOMENS RESTROOM RECESSED 4.8 120/1 1/15 13 1.5 NO 25 INDEECO 933U01500B 1, 2, 3, 4
EUH-VC-02 JANITORS JANITORS RECESSED 4.8 120/1 1/15 13 1.5 NO 25 INDEECO 933U01500B 1, 2, 3, 4
EUH-VC-01 MENS RESTROOM MENS RESTROOM RECESSED 4.8 120/1 1/15 13 1.5 NO 25 INDEECO 933U01500B 1, 2, 3, 4
TAG LOCATION SERVICE TYPE (MBH) PHASE (HP) (AMPS) (KW) (Y/N) (LBS) & MODEL NOTES
CAPACITY VOLT/ FAN POWER FLA POWER POWER WEIGHT MANUFACTURER
ELECTRICAL GEN. APPROX.
ELECTRIC UNIT HEATER SCHEDULE
FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
DRAWING NO.
171153
PMIS/PKG NO.
259631-317515TECH. REVIEW:
RMK
RMK
276 424426278
S7.16
S7.16
S7.16
S7.16
STORAGE
MECHANICAL
EQUIPMENT
RECEIVING
ELECTRICAL
ROOM
LOADING
STAIR 2
PLUMBING
EQUIPMENT
CORRIDOR
ELEVATOR 2
FCU-LL-01
H-1
H-1
8"ø 10"ø
CU-LL-03
CU-LL-02A
ACCU-LL-01
CU-LL-01
TU-LL-01
AC-LL-01
10"ø 8"ø
6"ø
AHU-LL-01
30x16
20x24
10x10
H-1
FSD-LL-01
FSD-LL-02
BSB-LL-01 12x8
8"ø 4
H-1
M9.01
6"ø
6"ø
H-1
EF-LL-01
H-1
H-1
22x26
CU-LL-02B
CU-LL-02C
EXVK-AHU-LL-01
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 10 11 AA
D.3
28x24
OA
RA
SA
A. INSTALL ALL DUCTWORK, PIPE, AND EQUIPMENT AS HIGH AS POSSIBLE (TIGHT TO
UNDERSIDE OF STRUCTURAL DECK), COORDINATE ALL MECHANICAL WORK WITH
ARCHITECTURAL WORK (INCLUDING EXPOSED STRUCTURE) AND WORK OF OTHER TRADES.
B. NOT ALL DUCT AND PIPE TRANSITIONS, UPS AND DOWNS ARE SHOWN ON THIS PLAN. THE
CONTRACTOR SHALL PROVIDE AND COORDINATE AS NECESSARY TO FIT FIELD CONDITION.
C. ALL EQUIPMENT SHALL BE INSTALLED SO AS TO BE ACCESSIBLE FOR MAINTENANCE AND
REPAIR.
D. IF REQUIRED PROVIDE CEILING/WALL ACCESS PANELS, COORDINATE EXACT LOCATION WITH
CONTRACTING OFFICER.
E. PROVIDE BALANCING DAMPERS UPSTREAM OF ALL DIFFUSERS AND GRILLES. PROVIDE
REMOTE BALANCING DAMPERS FOR DIFFUSERS AND GRILLES LOCATED ABOVE HARD LID
CEILINGS.
F. COORDINATE ALL CONTROL PANELS, THERMOSTATS, CO2 SENSORS, OCCUPANCY SENSORS
LOCATIONS AND MOUNTING HEIGHT WITH CONTRACTING OFFICER.
GENERAL NOTES:
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH. REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
BIG BEND NATIONAL PARK
Designer
Author
Checker
12-10-2024
LOWER FLOOR PLAN -
MECHANICALM2.01
100% FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
1/8" = 1'-0"
1 LOWER FLOOR PLAN - MECHANICAL
1. FLUE CONNECTION TO DIV 22 WATER HEATER. FOLLOW MANUFACTURER'S VENTING REQUIREMENTS.
2. SIDEWALL FLUE TERMINATION. FOLLOW MANUFACTURER'S VENTING REQUIREMENTS AND 2021 IFGC.
3. PROVIDE MINIMUM 1.0 SF NFA MAKE-UP AIR LOUVER FOR WATER HEATERS. LOUVER AREA SIZED 2021 IFGC.
4. PROVIDE MINIMUM OF 15' INTERNALLY LINED DUCTWORK FOR SUPPLY AIR.
5. PROVIDE MINIMUM OF 10' INTERNALLY LINED DUCTWORK FOR OUTSIDE AIR.
6. CONDENSATE CONNECTION. ROUTE TO FLOOR DRAIN.
7. PROVIDE MINIMUM 6.25 SF NFA RELIEF AIR LOUVER.
8. OSA DUCT PENETRATION THROUGH SLAB ROOM LOUVER ON LEVEL 1.
9. LOCATE FAN COIL UNIT ABOVE DOOR AND NOT ABOVE ANY ELEVATOR MACHINE ROOM EQUIPMENT.
10. RELIEF AIR BOOT. PROVIDE WIRE MESH SCREEN AT END OF DUCT.
11. CONTRACTOR TO ADDRESS CONSTRUCTION SEQUENCING NECESSARY TO INSTALL DOAS AHU WITH
BUILDING STRUCTURE.
NOTES:
SCALE OF
SCALE K
0 1688
FEET
FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
DRAWING NO.
171153
PMIS/PKG NO.
259631-317515TECH. REVIEW:
RMK
RMK
277 424426279
B11
Y01A
Y02A
Y01
Y02
B12
S02S02
S02
B13
Y02A
3-B O
X W
ID
E
R A
C K d ry s to ra g e p os t
2172 2172 2148
2148 2148 2148 2148 2148
RAMPRAMP
RAMP
B11
Y01A
Y02A
Y01
Y02
B12
S02S02
S02
B13
Y02A
3-B O
X W
ID
E
R A
C K d ry s to ra g e p os t
2172 2172 2148
2148 2148 2148 2148 2148
RAMPRAMP
RAMP
CONCESSIONER
OFFICES
RETAIL STORAGE
RETAIL
ELEVATOR 2
STAIR 2
ELEVATOR 1
FAMILY
RESTROOM
WOMENS
JAN.
EMPLOYEE
RESTROOM
MENS
PUBLIC
CORRIDOR
PUBLIC
CORRIDOR
COOLER
FREEZER
TELECOM ROOM
EMPLOYEE
CORRIDOR
RECEPTION
EF-01-01
C-2
6"ø
20x20 RA
FCU-01-01
5 345 C-1
TYP. 2
10"ø
14x12
TU-01-01
FCU-01-02
C-1
TYP.3
14x12
12"ø12"ø
TU-01-02
FCU-01-04FCU-01-03 3
C-2
TYP.4
EF-01-02
C-2
FCU-01-06
FCU-01-05
S-1
TYP.4
S-1
TYP. 4
12"ø
C-2
TYP.2
C-2
TU-01-04
C-2
TYP.4
8"ø
24x20
24x20
C-2
TYP.2
FSD-01-02
FSD-01-01
BSB-01-01
BSB-01-02
30x16
20x24
12x12
10"ø x2
C-2
C-2
14"ø x1
8"ø
C-2
20x10 32x8
36x12
C-1
TYP.2
x1
12"ø10"ø x1
24x12
10x24
24x12
24x12
18x12
18x12
18x12 x1
10x10
10x10
C-2
TYP.4
x1
2 10"ø TYP.
10"ø TYP.
12"ø12"ø
TU-01-03
20x12
10"ø
FCU-01-08
FCU-01-07
FCU-01-09
24x14 16x10
18x12
14x13
10"ø
C-1
TYP.2
C-2
H-2
12x8
C-2
FCU-01-10
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 10 11 AA
D.3
OA
RA
SA
A. INSTALL ALL DUCTWORK, PIPE, AND EQUIPMENT AS HIGH AS POSSIBLE (TIGHT TO
UNDERSIDE OF STRUCTURAL DECK), COORDINATE ALL MECHANICAL WORK WITH
ARCHITECTURAL WORK (INCLUDING EXPOSED STRUCTURE) AND WORK OF OTHER TRADES.
B. NOT ALL DUCT AND PIPE TRANSITIONS, UPS AND DOWNS ARE SHOWN ON THIS PLAN. THE
CONTRACTOR SHALL PROVIDE AND COORDINATE AS NECESSARY TO FIT FIELD CONDITION.
C. ALL EQUIPMENT SHALL BE INSTALLED SO AS TO BE ACCESSIBLE FOR MAINTENANCE AND
REPAIR.
D. IF REQUIRED PROVIDE CEILING/WALL ACCESS PANELS, COORDINATE EXACT LOCATION WITH
CONTRACTING OFFICER.
E. PROVIDE BALANCING DAMPERS UPSTREAM OF ALL DIFFUSERS AND GRILLES. PROVIDE
REMOTE BALANCING DAMPERS FOR DIFFUSERS AND GRILLES LOCATED ABOVE HARD LID
CEILINGS.
F. COORDINATE ALL CONTROL PANELS, THERMOSTATS, CO2 SENSORS, OCCUPANCY SENSORS
LOCATIONS AND MOUNTING HEIGHT WITH CONTRACTING OFFICER.
GENERAL NOTES:
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH. REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
BIG BEND NATIONAL PARK
Designer
Author
Checker
12-10-2024
FIRST FLOOR PLAN -
MECHANICALM2.02
100% FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
1/8" = 1'-0"
1 FIRST FLOOR PLAN - MECHANICAL
NOTES:
SCALE OF
SCALE K
0 1688
FEET
1. TOILET EXHAUST LOUVER, 2.25 SF NFA.
2. REFRIGERNT CHASE. 1'x1'.
3. PROVIDE MINIMUM OF 5' INTERNALLY LINED DUCT FOR SUPPLY AIR.
4. PROVIDE MINIMUM OF 10' INTERNALLY LINED DUCT FOR SUPPLY AIR.
5. OUTSIDE AIR LOUVER SERVING AHU-LL-01. 10.5 SF NFA.
6. SUPPLY AND RETURN AIR UP TO L02 DINING AREA IN ARCHITECTURAL ENCLOSURE.
FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
DRAWING NO.
171153
PMIS/PKG NO.
259631-317515TECH. REVIEW:
RMK
RMK
278 424426280
K08A6Heat lam psHatcoUG AHL-36DKEC120/6012.88 kWS helvesJ- box Interwired th rough shelves. acceptable alternates: APW
S R
-D
A
U
T
S D
TS12BLW
B B
S
B A
C K
B A
R D
O O
R
P E
R L
IC
K
TS17
TS12HSN
TS21
B B
S
B A
C K
B A
R D
O O
R
P E
R L
IC
K
D
D
D
D
D
D
D CH
C
C
D
CC
C
EMPLOYEE
DINING
STAIR 2
200A
MECH SHAFT
DINING
ELEVATOR
200B
STAIR
200A
KITCHEN
WAITING
TERRACE
OUTDOOR DINING
s s s
To fan motors/ inter connect with blowers/make-up air sys
To fan motors/ inter connect with blowers/make-up air sys & dish machine
E1
C
D
E061J uice dispenserCrathcoCS-2E-16-290KEC120/6018.5+45" AFFa cceptable a lternates: B unn-O M atic & Vollrath
E071S atellite br ewersFetcoCBS-1221KEC208/60129.6+45" AFF3 /8" cold+45" AFFp rovide dua l check va lves with interm edia te atm osph eric ventsa cceptable alternates: Bu nn & Curtis, connect thru water filte r, item E10.
C CD
W 011H and sink, w all m ount, knee valveAdvance-Tabco7-PS-82 (K-08 aerator)KEC1/2"1/2"18"1 -1/2" Direct12"1Advance Tabco7-PS-82H and Sink, W all M ountAdvance TabcoADB018P
W 091H and sink, w all m ount, knee valveAdvance-Tabco7-PS-82 (K-08 aerator)KEC1/2"1/2"18"1 -1/2" Direct12"1Advance Tabco7-PS-82H and Sink, W all M ountAdvance TabcoADB018P
D021D ishwash er, Rack Conveyo r/clean landingCham pion4 4 Pro/CCT90/RCT64 high tem p w/boosterKEC208/603111.0+19" AFF3/4"+19" AFF1 -1/2" indirect wasteT o floor Sink/pro vide dua l check v alves with inter m ediate a tm ospher ic ventsa cceptable alt ernates: Hoba rt & Jackson
DINING TERRACE
ELEVATOR 2
STAIR 2
ELEVATOR 1
MECH SHAFT
KITCHEN
EMPLOYEE
DINING
DINING
WAITING
TERRACE
GROUP DINING
BAR
KITCHEN
VESTIBULE
FCU-02-01
FCU-02-04
MUA-02-01
TU-02-01
C-1
TYP.3
14x10
44x20
8"ø
C-2
BSB-02-01
FSD-02-02
FSD-02-01
36x12
10x24
C-2 x1 x1
C-2
TYP.2
FCU-02-03 FCU-02-02
H-1
TYP. 3
16"ø
H-4
TYP. 4
C-1
TYP. 3
C-1
TYP. 3
C-1
TYP. 5
H-2
TYP. 3
18x12
C-1
EXVK-MUA-02-01
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 10 11 AA
D.3
FSD-02-04
FSD-02-03
FSD-02-06
FSD-02-05
H-1
TYP. 4
FSD-02-07
FSD-02-08
16"ø 4 5
4 5 x1 x1 x2 x2
14x14
54x1654x1654x16
RA
SA
KX
KX
7 7
A. INSTALL ALL DUCTWORK, PIPE, AND EQUIPMENT AS HIGH AS POSSIBLE (TIGHT TO
UNDERSIDE OF STRUCTURAL DECK), COORDINATE ALL MECHANICAL WORK WITH
ARCHITECTURAL WORK (INCLUDING EXPOSED STRUCTURE) AND WORK OF OTHER TRADES.
B. NOT ALL DUCT AND PIPE TRANSITIONS, UPS AND DOWNS ARE SHOWN ON THIS PLAN. THE
CONTRACTOR SHALL PROVIDE AND COORDINATE AS NECESSARY TO FIT FIELD CONDITION.
C. ALL EQUIPMENT SHALL BE INSTALLED SO AS TO BE ACCESSIBLE FOR MAINTENANCE AND
REPAIR.
D. IF REQUIRED PROVIDE CEILING/WALL ACCESS PANELS, COORDINATE EXACT LOCATION WITH
CONTRACTING OFFICER.
E. PROVIDE BALANCING DAMPERS UPSTREAM OF ALL DIFFUSERS AND GRILLES. PROVIDE
REMOTE BALANCING DAMPERS FOR DIFFUSERS AND GRILLES LOCATED ABOVE HARD LID
CEILINGS.
F. COORDINATE ALL CONTROL PANELS, THERMOSTATS, CO2 SENSORS, OCCUPANCY SENSORS
LOCATIONS AND MOUNTING HEIGHT WITH CONTRACTING OFFICER.
GENERAL NOTES:
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH. REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
BIG BEND NATIONAL PARK
Designer
Author
Checker
12-10-2024
SECOND FLOOR PLAN -
MECHANICALM2.03
100% FINAL CONSTRUCTION DOCUMENTS - LODGE COMPONENT
1/8" = 1'-0"
1 SECOND FLOOR PLAN - MECHANICAL
1. PROVIDE MINIMUM 10.2 SF NFA MAKE-UP AIR LOUVER.
2. PROVIDE PLATFORM FOR MUA-02-01. ACCESS TO BE ABOVE FREEZER.
3. PROVIDE MINIMUM OF 5' INTERNALLY LINED DUCT FOR SUPPLY AIR.
4. SLOPE GREASE EXHAUST DUCT A MINIMUM OF 1/4-INCH PER FOOT TOWARD GREASE HOOD
CONNECTION. INSTALL ACCESS DOORS AT FAN CONNECTIONS TO DUCTWORK, 12-FEET ON
CENTER AND AT EACH CHANGE IN DIRECTION OF DUCTWORK. ALL ACCESS PANEL LOCATIONS TO
BE REVIEWED AND APPROVED BY CONTRACTING OFFICER AND FACOPS. ALL TYPE-1 DUCTWORK
SHALL BE LEAK TESTED WITH A HIGH-PRESSURE WATER HOSE FOR ENTIRE DUCT RUN PER SPEC
SECTION…