Attachment H 1659896dwgVOL1_2of3.pdf

PDF 21 MB Posted

Attached to
P-002 EDI: Rapid Airfield Damage Recovery Storage Facilities, Aviano Air Base, Italy
Solicitation number
N6247022R3000
Issued by

About this file

This document provides details on a federal solicitation for construction services. Solicitation Number N6247022R3000 from the Department of the Navy Naval Facilities Engineering Command seeks proposals for Rapid Airfield Damage Recovery Storage Facilities to be located at Aviano Air Base in Italy. Offerors are invited to bid on constructing storage facilities to support rapid repair of airfield infrastructure damaged during combat or natural disaster operations. The solicitation does not specify pricing terms, response deadlines, or anticipated award dates. No incumbent is identified. The attached file appears to contain design drawings for the project scope but its specific contents are not disclosed.

View the file

Other files

File Type Posted
Amendment 0009.pdf PDF
Amendment 0008.pdf PDF
Amendment 0007.pdf PDF
Attachment S - Revised Drawing CU101A.pdf PDF
Attachment O - Site Visit Sign In.pdf PDF
Attachment T - Revised Drawing CU101B.pdf PDF
Attachment R - Revised Drawing CS102B.pdf PDF
Attachment U - Revised Specification 01 50 00.pdf PDF
Amendment 0006.pdf PDF
Attachment P - Site 2 Access Road Aerial.pdf PDF
Attachment Q - Revised Drawing CD101A.pdf PDF
Amendment 0005.pdf PDF
Amendment 0004.pdf PDF
Amendment 0003.pdf PDF
Attachment N - Gas Line Trench Detail.pdf PDF
Amendment 0002.pdf PDF
Attachment M - Installation Access Request Form.pdf PDF
Amendment 0001.pdf PDF
Attachment L - Installation Access Request Checklist.pdf PDF
Attachment E - Price Proposal Form.pdf PDF
Attachment F - LRA Commercial Vehicle Inspection Procedures.pdf PDF
Attachment K - Italian Safety Plan_Combined.pdf PDF
Attachment H 1659896dwgVOL1_3of3.pdf PDF
Attachment H 1659896dwgVOL1_1of3.pdf PDF
Attachment C - Construction Experience Project Data Sheet.pdf PDF
Attachment G - Specifications.pdf PDF
Attachment D - Past Performance Questionnaire (PPQ).pdf PDF
Attachment B - SEC-NAV_5512_1_11787 Form.pdf PDF
Attachment H 1659896dwgVOL2_1of4.pdf PDF
Attachment H 1659896dwgVOL2_3of4.pdf PDF
Attachment A - Pre-Proposal Inquiry Form.xls XLS spreadsheet
Attachment H 1659896dwgVOL2_2of4.pdf PDF
Attachment I - HAZMAT Report Summary.pdf PDF
Attachment J - Host Nation Code Compliance Certification.pdf PDF
N62470-22-R-3000.pdf PDF
Attachment H 1659896dwgVOL2_4of4.pdf PDF
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

0 5 10 15 20 30

1:300

SEAL

A/E INFO

2 3 4 5

1 2 3 4 5

S Y

M D

E S

C R

I P

T I O

N D

A T

E A

P P

R

D E

P A

R T

M E

N T

O

F

H E

A V

Y N

A V

A L

F

A C

I L I T

I E

S

E

N G

I N

E E

R I N

G

S

Y S

T E

M S

C

M

M A

N D

N O

R F

O L K

V

A

DES DRW CHK

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

A

B

C

D

A

B

C

D

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

1659896

A T

L A

N T

I

D

S

I G

N

A

N

S T

R U

C T

I O

N

N6247022R3000

CP GC AA

E X

I S

T I N

G

C

O N

D I T

I O

M

O L

I T

I O

N

S

I T

E

P

L A

N

LD101A

1:300

1:300

EXIST. CONDIT. AND DEMOLITIONS SITE PLAN

14121455

SEAL

A/E INFO

2 3 4 5

1 2 3 4 5

S Y

M D

E S

C R

I P

T I O

N D

A T

E A

P P

R

D E

P A

R T

M E

V

Y N

A V

A L

F

A C

I L I T

I E

S

E

N G

I N

E E

R I N

G

S

Y S

T E

M

M A

N D

N O

R F

O L K

V

A

DES DRW CHK

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

A

B

C

D

A

B

C

D

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

1659896

A T

L A

N T

S

I G

N

A

N

S T

R U

C T

I O

N

N6247022R3000

CP GC AA

0 5 10 15 20 30

1:300

D E

S I G

N

S

I T

E

A

P

L A

N T

I N

G

P

L A

N

LS102A

1:300

15700

1:300

DESIGN SITE AND PLANTING PLAN

110800

R=5000

24200

32000

63600

65000

19100

14121456

SEAL

A/E INFO

2 3 4 5

1 2 3 4 5

S Y

M D

E S

C R

I P

T I O

N D

A T

E A

P P

R

D E

P A

R T

M E

V

Y N

A V

A L

F

A C

I L I T

I E

S

E

N G

I N

E E

R I N

G

S

Y S

T E

M

M A

N D

N O

R F

O L K

V

A

DES DRW CHK

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

A

B

C

D

A

B

C

D

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

1659896

A T

L A

N T

S

I G

N

A

N

S T

R U

C T

I O

N

N6247022R3000

CP GC AA

P L

A N

T

M

A T

E R

I A

L

H

E D

U L

E

A

T

A I L

S

LK501A

NTS

NTS

TREE PLANTING DETAIL (TYP.)

NTS

GROUND COVER PLANTING WITH CURB DETAIL

35grams/sm

NTS

DRAINAGE DEPRESSION WITH GRASS COVER DETAIL

14121457

1. STRUCTURAL DESIGN IS IN ACCORDANCE WITH THE

FOLLOWING US CODES:

a. UFC 1-200-01 - DOD BUILDING CODE, OCTOBER 2019

b. UFC 3-301-01 - STRUCTURAL ENGINEERING, 2019

c. IBC2018 - INTERNATIONAL BUILDING CODE, 2018

d. ASCE7-16 - MINIMUM DESIGN LOADS FOR BUILDINGS

AND OTHER STRUCTURES, 2016

e. ACI318-14 - BUILDING CODE REQUIREMENTS FOR

REINFORCED CONCRETE, 2014

f. ANSI-AISC 341-16 - SEISMIC PROVISIONS FOR

STRUCTURAL STEEL BUILDINGS, 2016

g. ANSI-AISC 360-16 - SPECIFICATIONS FOR

STRUCTURAL STEEL BUILDINGS, 2016

2. STRUCTURAL DESIGN IS IN ACCORDANCE WITH THE

FOLLOWING ITALIAN CODES:

a. TECHNICAL NORMS FOR THE CALCULATION, EXECUTION AND TESTING OF NORMAL AND

PRESTRESSED REINFORCED CONCRETE

STRUCTURES AND STEEL STRUCTURES (LAW 1086 -

5/11/1971)

b. TECHNICAL NORMS FOR SEISMIC DESIGN (LAW 64 - 2/2/1974)

c. TECHNICAL CONSTRUCTION CRITERIA (DM 17/01/2018)

d. INSTRUCTIONS FOR THE APPLICATION OF THE

CONSTRUCTION CRITERIA (CIRC.7 - 21/02/2019)

3. DESIGN LOADS

A. SUPERIMPOSED DEAD LOADS

• 1.0 kPa

B. LIVE LOADS (ITALIAN CODE)

• ROOF - CAT. H

0.50 kPa

• GROUND FLOOR - CAT. G

12.00 kPa

C. LIVE LOADS (US CODE)

• ROOF

1.00 kPa

• GROUND FLOOR

12.00 kPa

D. SEISMIC LOADS (ITALIAN CODE)

• SITE CATEGORY

B

• SERVICEABILITY LIFE

Vn=50 years

• OCCUPANCY CLASS

II

• OCCUPANCY FACTOR

Cu=1.0

• REFERENCE LIFE

50 years

• SOIL ACCELERATION FACTOR SLV

ag/g=0.2386

• RETURN PERIOD SLV

475 years

E. SEISMIC LOADS (US CODE)

• SHORT PERIOD SPECTRAL ACCELERATION

Ss=1.25

• ONE SECOND PERIOD SPECTRAL

ACCELERATION S1=0.50

• RISK FACTOR

II

• IMPORTANCE FACTOR IE

IE=1.00

• STRUCTURAL SYSTEM: MOMENT RESISTING

FRAME SYSTEM W/STEEL ORDINARY MOMENT

FRAME

• SITE CLASS

C

• SEISMIC DESIGN CATEGORY:

D

• RESPONSE MODIFICATION AND DEFLECTION

AMPLIFICATION FACTORS: R=3.5, Cd=3.0 (X-

DIR)

F. SNOW LOADS (ITALIAN CODE)

• GROUND SNOW LOAD qk qk=1.50 kPa

• ROOF SHAPE FACTOR µ µ=0.8 (ANGLE<17°)

• ROOF SNOW LOAD qs=1.20 kPa

G. SNOW LOAD (US CODE)

• GROUND SNOW LOAD pg=1.68 kPa

• SNOW LOAD ON ROOF ps=1.06 kPa

H. WIND LOAD (ITALIAN CODE)

• REFERENCE WIND SPEED vb=25 m/s

• SITE CLASS II

• DYNAMIC COEFFICIENT cd=1.0

• WIND LOAD ON WINDWARD FACE

p=0.90 kPa

• WIND LOAD ON LEEWARD FACE

p=0.63 kPa

• WIND LOAD ON SIDES

p=0.54 kPa

DESIGN DATA

1. IL PROGETTO STRUTTURALE E' STATO REALIZZATO IN

CONFORMITA' ALLE SEGUENTI NORMATIVE

AMERICANE:

a. UFC 1-200-01 - REQUISITI GENERALI DELLE

STRUTTURE, GIUGNO 2019

b. UFC 3-301-01 - INGEGNERIA STRUTTURALE, 2019

c. IBC2018 - NORME INTERNAZIONALI DELLE

COSTRUZIONI, 2018

d. ASCE7-16 - CARICHI MINIMI DI PROGETTO PER

EDIFICI ED ALTRE STRUTTURE, 2016

e. ACI318-14 - REQUISITI DI PROGETTO PER

CALCESTRUZZO ARMATO, 2014

f. ANSI-AISC 341-16 - PROVVEDIMENTI ANTISISMICI

PER GLI EDIFICI IN ACCIAIO, 2016

g. AISC360-16 - SPECIFICHE PER EDIFICI IN ACCIAIO

STRUTTURALE, 2016

2. IL PROGETTO E' STATO ESEGUITO IN CONFORMITA'

ALLE SEGUENTI NORMATIVE ITALIANE

a. NORME TECNICHE PER IL CALCOLO, L'ESECUZIONE E IL COLLAUDO DI STRUTTURE IN

CALCESTRUZZO ARMATO NORMALE E

PRECOMPRESSO E DI STRUTTURE IN ACCIAIIO

(LEGGE 1086 - 5/11/1971)

b. NORME TECNICHE PER LE COSTRUZIONI IN ZONA

SISMICA (LEGGE 64 - 2/2/1974)

c. AGGIORNAMENTO ALLE NORME TECNICHE PER

LE COSTRUZIONI (DM 17/01/2018)

d. ISTRUZIONI PER L'APPLICAZIONE DELLE NUOVE

NORME TECNICHE PER LE COSTRUZIONI

(CIRC.7 - 21/02/2019)

3. CARICHI DI PROGETTO:

A. CARICHI PERMANENTI NON STRUTTURALI:

• 1.00 kPa

B. CARICHI VARIABILI (NORMATIVA ITALIANA):

• COPERTURA - CAT. H

0.50 kPa

• PIANO TERRA CAT. G

12.00 kPa

C. CARICHI VARIABILI (NORMATIVA US):

• COPERTURA

1.00 kPa

• PIANO TERRA

12.00 kPa

D. SISMA (NORMATIVA ITALIANA)

• CATEGORIA DI SUOLO

B

• VITA NOMINALE

Vn=50 ANNI

• CLASSE D'USO

II

• FATTORE D'USO

Cu=1.0

• VITA DI RIFERIMENTO

50 ANNI

• COEFFICIENTE DI ACELERAZIONE AL SUOLO

IN SLV ag/g=0.2386

• PERIODO DI RITORNO IN SLV

475 ANNI

E. SISMA (NORMATIVA US)

• ACCELERAZIONE SPETTRALE DI BREVE

PERIODO Ss=1.25

• ACCELERAZIONE AL PERIODO 1 SEC

S1=0.50

• CATEGORIA DI RISCHIO

II

• COEFFICIENTE DI IMPORTANZA

IE=1.00

• SISTEMA STRUTTURALE: TELAIO ORDINARIO

RESISTENTE A MOMENTO

• CATEGORIA TERRENO

C

• CATEGORIA SISMICA DI PROGETTO :

D

• COEFFICIENTE DI RISPOSTA E AMPLIF.

DEFORMAZIONI: R=3.5 , Cd=3.0

F. CARICO DA NEVE (NORMATIVA ITALIANA)

• CARICO AL SUOLO qk qk=1.50 kPa

• COEF.FORMA COPERTURA µ µ=0.8 (ANGOLO<17°)

• CARICO DA NEVE IN COPERTURA

qs=1.20 kPa

G. CARICO DA NEVE (NORMATIVA US)

• CARICO AL SUOLO

pg=1.68 kPa

• CARICO IN COPERTURA

ps=1.06 kPa

H. CARICO DA VENTO (NORMATIVA ITALIANA)

• VELOCITA' DI RIFERIMENTO

vb=25 m/s

• CATEGORIA DI SITO

II

• COEFFICIENTE DINAMICO

cd=1.0

• PRESSIONE PARETI SOPRAVENTO

p=0.90 kPa

• PRESSIONE PARETI SOTTOVENTO

p=0.63 kPa

• PRESSIONE PARETI LATERALI

p=0.54 kPa

• PRESSIONE MASSIMA COPERTURA

(SOLLEVAMENTO) p=1.00 kPa

• PRESSIONE MASSIMA COPERTURA

(COMPRESSIONE) p=0.36 kPa

DOTT. ING.

DI STEFANO PIETRO

ISCRITTO ALL'ALBO

PROFESSIONALE

COL N. 13921

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

DRAWFORM REVISION: 10 MARCH 2009

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

T

V

Y

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M C

O M

M A

N D

A

T L A

N T

IC

N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M C

O M

M A

N D

N O

R F

O L

K V

A

A V

IA

N

O A

IR

B

A S

E A

V

IA

N O

IT

A L Y

P -0

E D

I- R

A D

R S

T O

R A

G E

F A

C

IL

IT

Y

DESIGN DIRECTOR

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE: 04 AUGUST 2022

RICHARD STEPHENS, PE

NO SCALE

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

FIRE PROTECTION

LET/LRP

A T

L A

N T

IC

D

E S

IG

N

A N

D C

O N

S T

R U

C T

IO

N

UNCLASSIFIED

UNCLASSIFIED

U N

C L

A S

S

IF

IE

D

P

LO

T T

E D

N6247022R3000

DPS

A

B

C

D

Approved by Allan Lucht, via Email.

JTV

/1

/2

:2

:3

E

L a v o ri \2

\0

-R

A D

R A v ia n o \F in a l p e r fi rm e \B

L D

G C

R -1

-S

.r v t

G E

N E

R A

L N

O T

E S

/2

S-001A

PD AA ES

S -0

A

G E

N E

R A

L N

O T

E S

/2

14121458 44 429

DATI DI PROGETTO

1. CONCRETE AND STEEL STRUCTURE

DIMENSIONS ARE EXPRESSED IN MM.

2. VERTICAL ALTIMETRIC ELEVATIONS ARE

EXPRESSED IN M.

3. SPOT ELEVATION 0.00 AS INDICATED IN CIVIL

DRAWINGS

1. LE QUOTE DELLE STRUTTURE IN CALCESTRUZZO E

IN ACCIAIO SONO ESPRESSE IN MM

2. LE QUOTE ALTIMETRICHE SONO ESPRESSE IN M.

3. LA QUOTA RELATIVA 0.00 E' INDICATA NEI GRAFICI

CIVILI

UNIT OF MEASURE DIMENSION NOTE

NOTA SULLE UNITA' DI MISURA

• MAX WIND LOAD ON ROOF (UPWDS)

p=1.00 kPa

• MIN WIND LOAD ON ROOF (DWNWDS)

p=0.36 kPa

H. WIND LOAD (US CODE)

• BASIC WIND SPEED

148 Km/h

• RISK CATEGORY

II

• VELOCITY PRESSURE EXP. COEFF.

Kz=1.0

• TOPOGRAPHIC FACTOR

Kzt=1.0

• DIRECTIONALITY FACTOR

Kd=0.85

• BUILDING IS PARTIALLY ENCLOSED

• WIND LOAD ON MWFRS

• WIND LOAD ON WINDWARD FACE

p=1.38 kPa

• WIND LOAD ON LEEWARD FACE

p=0.86 kPa

• WIND LOAD ON SIDES

p=1.27 kPa

• MAX WIND LOAD ON ROOF (UPWDS)

p=1.48 kPa

• MIN WIND LOAD ON ROOF (DWNWDS)

p=0.10 kPa

4. FOUNDATIONS

FOUNDATIONS MUST BE SHALLOW TYPE, 50 CM

THICK PLUS 10 CM THICK LEAN CONCRETE LAYER

LAID DOWN AT 1.50 M BELOW GROUND FLOOR

LEVEL. THEY MUST BE CONTINUOUS BEAMS ALONG

THE EDGE, ALONG THE CENTRAL PERPENDICULAR

ALIGNMENT AND UNDERNEATH THE COLUMNS OF

THE RIDGE ALIGNMENT (1600 MM WIDE, 2500 MM

WIDE FOR EDGE MEAMS IN Y-DIR), AND ISOLATED

PADS 2500X2500 SQ.MM, CONNECTED BY TIE BEAMS

300X500 MM

DESIGN BEARING PRESSURES ARE LIMITED TO 200

KN/SQM TO CONTAIN THE SETTLEMENT.

BURIED CONCRETE STRUCTURES MUST BE

PROTECTED THROUGH WATERPROOFING

MEMBRANE.

FROST DEPTH PENETRATION IS 600 MM BELOW

GROUND.

PERMANENT GROUND WATER TABLE IS NOT

EXPECTED.

5. FALL PROTECTION SYSTEM

a. DESIGN IN ACCORDANCE WITH THE FOLLOWING

DOCUMENTS:

• OSHA 1926 S.PART M - 1926:502 - FALL

PROTECTION SYSTEMS CRITERIA AND

PRACTICE

• EM 3851-1,2008 SAFETY AND HEALTH

REQUIREMENTS MANUAL

• UNI-EN 795:2012 PERSONAL FALL

PROTECTION EQUIPMENT - ANCHOR

DEVICES

• DL 81-08SAFEGUARDING HEALTH AND

SAFETY WITHIN WORKPLACES

b. MINIMUM DESIGN LOADS FOR ANCHOR POINTS

(OSHA REQUIREMENTS):

• 13.3 KN SELF RETS. LL AND LANYARD

LIMITING FREE FALL DISTANCE TO 2 FT;

• 22 KN SELF RETS. LL AND LANYARD NOT

LIMITING FREE FALL DISTANCE TO 2 FT;

• 4.0 KN MAX ARREST FORCE FOR EMPLOYEE

USING BODY BELT;

• 8.0 KN MAX ARREST FORCE FOR EMPLOYEE

USING BODY HARNESS;

• 22.0 KN MINIMUM LANYARD BREAKING

STRENGTH

c. MINIMUM DESIGN LOADS FOR ANCHOR POINTS

(UNI EN 795 REQUIREMENTS):

• 12.0 KN CLASS A AND C ANCHOR DEVICES

H. CARICO DA VENTO (NORMATIVA US)

• VELOCITA' BASE DEL VENTO

148 Km/h

• CATEGORIA DI RISCHIO

II

• COEFFICIENTE DI ESPOSIZIONE

Kz=1.0

• COEFFICIENTE TOPOGRAFICO

Kzt=1.0

• COEFFICIENTE DIREZIONALE

Kd=0.85

• PRESSIONE PARETI SOPRAVENTO

p=1.38 kPa

• PRESSIONE PARETI SOTTOVENTO

p=0.86 kPa

• PRESSIONE PARETI LATERALI

p=1.27 kPa

• PRESSIONE MASSIMA COPERTURA

(SOLLEVAMENTO) p=1.48 kPa

• PRESSIONE MASSIMA COPERTURA

(COMPRESSIONE) p=0.10 kPa

4. FONDAZIONI

LE FONDAZIONI SONO DI TIPO DIRETTO, CON

SPESSORE 50 CM E 10 CM DI CALCESTRUZZO

MAGRO, CON INTRADOSSO A -1,5 M DAL PIANO

TERRA. CONSISTERANNO IN TRAVI CONTINUE

LUNGO IL PERIMETRO ED IN CORRISPONDENZA

DEL COLMO E DELLA LINEA MEDIANA DELL'ASSE X

(CON LARGHEZZA 1600 MM IN DIREZIONE X, 2500

MM IN DIREZIONE Y), E PLINTI ISOLATI DI

DIMENSIONE 2500X2500 MMQ COLLEGATI DA

TIRANTI IN C.A. DI SEZIONE 300X500 MM.

I CARICHI DI PROGETTO SONO LIMITATI A 200

KN/MQ PER CONTENERE IL CEDIMENTO.

TUTTE LE STRUTTURE IN CALCESTRUZZO

INTERRATE SARANNO PROTETTE DA UNA

MEMBRANA BITUMINOSA RESISTENTE ALL'ACQUA.

LA PROFONDITA' DI PENETRAZIONE DEL GHIACCIO

E' 600 MM AL DI SOTTO DEL P.C.

NON E' STATA RILEVATA ALCUNA FALDA IDRICA

PERMANENTE

5. LINEA VITA

a. PROGETTARE IN ACCORDO AI SEGUENTI

DOCUMENTI:

• OSHA 1926 S.PART M - 1926:502 - CRITERI

E PRATICA DEI SISTEMI ANTICADUTA

• EM 3851-1,2008 MANUALE PER REQUISITI

DI SICUREZZA E SALUTE

• UNI-EN 795:2012 DISPOSITIVI

ANTICADUTA - DISPOSITIVI DI

ANCORAGGIO

• DL 81-08 SICUREZZA NEI LUOGHI DI

LAVORO

b. CARICHI MINIMI PER I DISPOSITIVI DI

ANCORAGGIO (REQUISITI OSHA):

• 13.3 KN FUNI E CORDINI RETRATTILI CHE

LIMITANO AUTOMATICAMENTE LA CADUTA

LIBERA A 60 cm ;

• 22 KN FUNI E CORDINI RETRATTILI CHE

NON LIMITANO AUTOMATICAMENTE LA

CADUTA LIBERA A 60 cm;

• 4.0 KN FORZA MASSIMA DI ARRESTO PER

ADDETTO CHE UTILIZZA LA CINTURA;

• 8.0 KN FORZA MASSIMA DI ARRESTO PER

ADDETTO CHE UTILIZZA IMBRAGATURA

• 22.0 KN CARICO MINIMO DI ROTTURA DEL

CORDINO

c. CARICHI MINIMI PER I DISPOSITIVI DI

ANCORAGGIO (REQUISITI UNI EN 795 ):

• 12.0 KN DISPOSITIVI DI ANCORAGGIO

CLASSE A E C

N O

T E

G E

N E

R A

LI

/2

DOTT. ING.

DI STEFANO PIETRO

ISCRITTO ALL'ALBO

PROFESSIONALE

COL N. 13921

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

DRAWFORM REVISION: 10 MARCH 2009

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

T

V

Y

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M C

O M

M A

N D

A

T L A

N T

IC

N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M C

O M

M A

N D

N O

R F

O L

K V

A

A V

IA

N

O A

IR

B

A S

E A

V

IA

N O

IT

A L Y

P -0

E D

I- R

A D

R S

T O

R A

G E

F A

C

IL

IT

Y

DESIGN DIRECTOR

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE: 04 AUGUST 2022

RICHARD STEPHENS, PE

NO SCALE

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

FIRE PROTECTION

LET/LRP

A T

L A

N T

IC

D

E S

IG

N

A N

D C

O N

S T

R U

C T

IO

N

UNCLASSIFIED

UNCLASSIFIED

U N

C L

A S

S

IF

IE

D

P

LO

T T

E D

N6247022R3000

DPS

A

B

C

D

Approved by Allan Lucht, via Email.

JTV

/1

/2

:2

:3

E

L a v o ri \2

\0

-R

A D

R A v ia n o \F in a l p e r fi rm e \B

L D

G C

R -1

-S

.r v t

G E

N E

R A

L N

O T

E S

/2

S-002A

PD AA ES

S -0

A

G E

N E

R A

L N

O T

E S

/2

14121459 45 429

1. CONCRETE:

A. NON STRUCTURAL CONCRETE

C12/15 - f'c=12 MPa (CYLINDRICAL)

B. STRUCTURAL CAST-IN-PLACE CONCRETE

C35/45 - f'c=35 MPa (CYLINDRICAL)

EXPOSURE CLASS XC2

MAX SIZE AGGREGATE 20 MM

CONSISTENCY S4

MAX w/c = 0,5

C. CAST-IN- PLACE CONCRETE FOR SLAB ON GRADE

C30/35 - f'c=30 MPa (CYLINDRICAL)

EXPOSURE CLASS XC2

MAX SIZE AGGREGATE 20 MM

CONSISTENCY S4

MAX w/c = 0,5

2. STEEL FOR REINFORCEMENT:

A. B450C, YIELD STRENGTH

fy=450 MPa

3. CONCRETE COVER

A. CONCRETE THICKNESS COVERING

REINFORCEMENT MUST NOT BE LESS THAN ONE

BAR DIAMETER AND NOT LESS THAN SPECIFIED

IN THE EXAMPLES LISTED BELOW.

a. CONCRETE CAST AGAINST EARTH

75 MM

b. CONCRETE CAST AGAINST FORMS AND

EXPOSED TO WEATHER 50 MM

c. CONCRETE CAST AGAINST FORMS AND NOT

EXPOSED TO WEATHER:

• SLABS, JOISTS,

25 M

• WALLS (COVER ON HORIZ. EXT. BARS)

25 MM

• BEAMS AND COLUMNS (PRIMARY

REINFORCEMENT, STIRRUPS) 40 MM

4. MINIMUM CLEAR SPACING BETWEEN PARALLEL

REINFORCING BARS MUST BE GREATER THAN RE-BAR

DIAMETER BUT NOT LESS THAN 25MM.

5. EXPOSED CONCRETE EDGES MUST BE CHAMFERED

15 MILLIMETERS UNLESS OTHERWISE SHOWN.

6. NO CONCRETE MAY BE PLACED UNTIL EMBEDDED

WORK AND EXCAVATION HAVE BEEN INSPECTED BY

THE QUALITY CONTROL ORGANIZATION. THE

CONTRACTING OFFICER MUST BE NOTIFIED 24 HOURS

IN ADVANCE OF THE INSPECTION.

7. REINFORCING STEEL MUST BE HELD SECURELY IN

PLACE TO PREVENT DISLOCATION DURING

CONCRETE POURING OPERATIONS.

8. USE STRUCTURAL DRAWINGS IN CONJUNCTION WITH

CIVIL, ARCHITECTURAL, MECHANICAL, PLUMBING,

FIRE PROTECTION AND ELECTRICAL DRAWINGS IN

ORDER TO PREPARE SHOP DRAWINGS. COORDINATE

THE REQUIREMENTS OF THE WORK OF OTHER

TRADES AS TO SLEEVES, INSERTS, HOLES, HANGERS,

CHASES, ANCHORS, ETC. SHOP DRAWINGS MUST

INCLUDE ALL HOLES FOR MECHANICAL, FP,

ELECTRICAL AND TELECOMM SERVICE

PENETRATIONS SO THAT NO HOLES MAY BE ADDED

AFTER THE CONSTRUCTION OF THE CONCRETE

STRUCTURES.

9. ELECTRICAL CONDUIT, INSERTS, BOXES AND OTHER

ITEMS THAT ARE BEING EMBEDDED IN CONCRETE

WORK MUST BE COORDINATED AND PLACED BEFORE

CONCRETE IS PLACED. MAINTAIN THREE DIAMETERS

CLEARANCE BETWEEN CONDUITS. SEE MECHANICAL

AND ELECTRICAL DWGS.

CONCRETE CONSTRUCTION NOTES

1. STRUCTURAL SHAPES, BARS, PLATES AND RODS

MUST CORRESPOND TO UNI STANDARD EN 10025, EN

10210, EN 10219-1 ALL HAVING CE MARKING. SHAPES

MUST CORRESPOND TO THE FOLLOWING:

• STEEL TYPE S355, YIELDING fyk=355 MPa

• ULTIMATE TENSILE STRENGTH ftk=530 MPa.

2. FASTENERS FOR STRUCTURAL CONNECTIONS (UNI EN

898-1 AND UNI 5592:1968 AND EN ISO 4016:2002) MUST

CORRESPOND TO THE FOLLOWING:

• CLASS 8.8, YIELDING fyb=640 MPa

• TENSILE STRENGTH ftk=800 MPa

3. ANCHOR BOLTS MUST BE CONFORMING TO UNI EN

10025 CLASS S355.

4. WELDINGS TYPE E70XX IF NOT DIFFERENTLY

INDICATED. WELDS MUST DEVELOP THE FULL

STRENGTH OF THE WEAKER CONNECTED MEMBER.

5. BOLT HOLES MAY NOT BE CUT OR ENLARGED BY

FLAME CUTTING IN THE FIELD.

6. STEEL MEMBERS MUST BE HOT-DIP GALVANIZED

7. IF FLASH RUSTING OCCURS, APPLY PRIMER TO A

MINIMUM DRY FILM THICKNESS OF 0.05 MM, IN

ACCORDANCE WITH SPEC 05 12 00.

8. GROUT USED UNDER BEARING PLATES MUST BE NON

SHRINK, NON METALLIC, PRE-MIXED GROUT AND HAVE

A MINIMUM 55 MPa COMPRESSIVE STRENGTH

STEEL CONSTRUCTION NOTES

1. TUTTI I PROFILI STRUTTURALI, BARRE, PIASTRE E

TIRANTI SARANNO CONFORMI ALLA UNI EN 10025, EN

10210, EN 10219-1, E AVRANNO TUTTI LA

MARCHIATURA CE. TUTTI I SOPRA CITATI ELEMENTI

AVRANNO LE SEGUENTI CARATTERISTICHE:

• ACCIAIO TIPO S 355, SNERVAMENTO fyk=355 MPa

• RESISTENZA ULTIMA ftk=530 MPa.

2. TUTTI I BULLONI PER LE UNIONI STRUTTURALI (UNI EN

898-1, UNI 5592:1968 E EN ISO 4016:2002) SARANNO DI

CLASSE 8.8, E AVRANNO PERTANTO LE SEGUENTI

PROPRIETA':

• SNERVAMENTO fyb=640 MPa

• RESISTENZA ULTIMA ftk=800 MPa

3. I TIRAFONDI SARANNO REALIZZATI IN CONFORMITA'

CON UNI EN 10025 CLASSE S355.

4. LE SALDATURE SARANNO DEL TIPO E70XX SE NON

DIVERSAMENTE INDICATO, E DOVRANO RIPRISTINARE

LA RESISTENZA COMPLETA DELL'ELEMENTO

COLLEGATO PIU' DEBOLE.

5. I FORI PER I BULLONI NON POTRANNO ESSERE

TAGLIATI O ALLARGATI IN SITU CON CANNELLO.

6. TUTTI GLI ELEMENTI IN ACCIAIO STRUTTURALE

DEVONO ESSERE ZINCATI A CALDO.

7. IN CASO DI FORMAZIONE DI RUGGINE, APPLICARE

UNO SPESSORE MINIMO DI VERNICE PROTETTIVA

PARI A 0.05 MM COME DA SPECIFICA 05 12 00

8. LA MALTA DA UTILIZZARE COME RIEMPIMENTO AL DI

SOTTO DELLE PIASTRE METALLICHE DOVRA' ESSERE

A RITIRO COMPENSATO, NON METALLICA,

PREMISCELATA, E DOVRà AVERE UNA RESISTENZA MINIMA A COMPRESSIONE DI 55 MPa.

NOTE DI COSTRUZIONE DEL CALCESTRUZZO

1. CALCESTRUZZO:

A. CALCESTRUZZO NON STRUTTURALE

C12/15 - f'c=12 MPa (CILINDRICO)

B. CALCESTRUZZO STRUTTURALE IN OPERA

C35/45 - f'c=35 MPa (CILINDRICO)

CLASSE DI ESPOSIZIONE XC2

MASSIMA DIMENSIONE AGGREGATO 20 MM

CONSISTENZA S4

MASSIMO a/c = 0,5

C. CALCESTRUZZO IN OPERA PER SOLETTA CONTRO

TERRA

C30/35 - f'c=30 MPa (CILINDRICO)

CLASSE DI ESPOSIZIONE XC2

MASSIMA DIMENSIONE AGGREGATO 20 MM

CONSISTENZA S4

MASSIMO a/c = 0,5

2. ACCIAIO PER ARMATURE:

A. B450C, SNERVAMENTO fy=450 MPa

3. COPRIFERRI

I COPRIFERRI MINIMI DOVRANNO ESSERE NON

MINORI DI UN DIAMETRO, E COMUNQUE NON MINORI

DI QUANTO DI SEGUITO SPECIFICATO:

A. CALCESTRUZZO IN OPERA (NON

PRECOMPRESSO)

a. GETTATO CONTRO TERRA 75 MM

b. GETTATO CONTRO CASSERO ED ESPOSTO AGLI

AGENTI ATMOSFERICI 50 MM

c. GETTATO CONTRO CASSERO E NON ESPOSTO

AGLI AGENTI ATMOSFERICI:

• SOLETTE, TRAVETTI 25 MM

• PARETI (COPR. SULLA BARRA ORIZZ, EST.)

25 MM

• TRAVI E PILASTRI (ARMATURE

LONGITUDINALI, STAFFE) 40 MM

4. GLI INTERFERRI MINIMI SARANNO PARI AL DIAMETRO

DELLA BARRA MA IN NESSUN CASO INFERIORI A 25

MM.

5. TUTTI GLI SPIGOLI ESPOSTI DI CALCESTRUZZO

SARANNO SMUSSATI DI 15 MM SE NON

DIVERSAMENTE INDICATO.

6. NON SI ESEGUIRANNO GETTI DI CALCESTRUZZO

FINCHE' TUTTI GLI ELEMENTI E GLI SCAVI NON

SARANNO ISPEZIONATI DAL RESPONSABILE DEL

CONTROLLO DI QUALITA'. L'UFFICIALE CONTRAENTE

DOVRA' ESSERE AVVISATO DEL GETTO 24 ORE PRIMA

DELL'ISPEZIONE.

7. TUTTE LE ARMATURE SARANNO SALDAMENTE

BLOCCATE PER EVITARNE LO SPOSTAMENTO

DURANTE LE OPERAZIONI DI GETTO.

8. L'APPALTATORE DOVRA' UTILIZZARE I DISEGNI

STRUTTURALI INSIEME AI CIVILI, ARCHITETTONICI,

MECCANICI, IDRAULICI, ELETTRICI,

TELECOMUNICAZIONI E PROTEZIONE INCENDIO PER

PREPARARE I DISEGNI DI CANTIERE. DOVRA' INOLTRE

COORDINARE IL LAVORO DEI SUBAPPALTATORI PER

ATTRAVERSAMENTI, INSERTI, FORI, ANCORAGGI ETC.

I DISEGNI DI CANTIERE DOVRANNO INCLUDERE LE

FOROMETRIE MECCANICHE, ANTIINCENDIO,

ELETTRIHE, E TELECOMUNICAZIONI, PER EVITARE LA

REALIZZAZIONE DI FOROMETRIE NELLE STRUTTURE

IN CALCESTRUZZO DOPO LA LORO COSTRUZIONE.

9. LE CANALINE ELETTRICHE, GLI INSERTI, LE CASSETTE

ED ALTRI ELEMENTI DA ANNEGARE NEL

CALCESTRUZZO DOVRANNO ESSERE COORDINATI E

COLLOCATI PRIMA CHE IL CALCESTRUZZO SIA POSTO

IN OPERA. MANTENERE TRE DIAMETRI DI SPAZIO TRA

LE CANALINE. FARE RIFERIMENTO AI GRAFICI

MECCANICI ED ELETTRICI..

NOTE DI COSTRUZIONE DEL'ACCIAIO

1. STEEL DECK MUST COMPLY WITH REQUIREMENTS

OF APPLICABLE ITALIAN NORMS AND CODES.

2. PROVIDE HEAVY DUTY STEEL DECK TO RESIST THE

FOLLOWING WIND LOADING CONDITIONS:

DOWNWARDS: 0.30 kPa UPWARDS: 2.16 kPa (ZONE 3)

1.92 kPa (ZONE 2)

1.44 kPa (ZONE 1)

1.00 kPa (ZONE 1')

3. ROOF DECK MUST BE INSTALLED SO THAT FLUTES

RUN PERPENDICULAR TO FRAMING MEMBERS. DECK

MUST SPAN ON THREE SUPPORTS MIN. WHERE

POSSIBLE.

4. LIGHTWEIGHT ITEMS: LW CEILINGS, DUCTS, LIGHT

FIXTURES ETC., MAY BE HUNG FROM DECK. DO NOT

HANG OTHER ITEMS FROM ROOF DECK WITHOUT

APPROVAL.

5. OPENINGS IN DECK ARE NOT ALLOWED IF NOT

SPECIFICALLY INDICATED ON DRAWINGS OR

APPROVED BY THE CONTRACTING OFFICER.

6. FASTEN STEEL DECK TO THE MAIN FRAMING IN

ACCORDANCE TO MANUFACTURER'S

INSTRUCTIONS.

STEEL DECK NOTES NOTE LAMIERA GRECATA IN ACCIAIO

1. LA LAMIERA DI COPERTURA DOVRA' RISPETTARE

TUTTE LE LEGGI E NORMATIVE APPLICABILI IN ITALIA

2. FORNIRE UNA LAMIERA GRECATA IN ACCIAIO PER

CARICHI PESANTI CAPACE DI RESISTERE ALLE

SEGUENTI SOLLECITAZIONI DEL VENTO:

VERSO IL BASSO: 0.3 kPa VERSO L'ALTO: 2.16 kPa (ZONA 3)

1.92 kPa (ZONA 2)

1.44 kPa (ZONA 1)

1.00 kPa (ZONA 1')

3. INSTALLARE LA LAMIERA GRECATA IN MANIERA

TALE CHE I SOLCHI SIANO PERPENDICOLARI AGLI

ELEMENTI STRUTTURALI DI SUPPORTO. LA LAMIERA

DEVE POGGIARE ALMENO SU TRE SUPPORTI

LADDOVE POSSIBILE.

4. ELEMENTI LEGGERI COME CONTROSOFFITTI

LEGGERI, LAMPADE, CANALI POTRANNO ESSERE

COLLEGATE DIRETTAMENTE ALLA LAMIERA. NON

APPENDERE ALTRI ELEMENTI SENZA ESPLICITA

APPROVAZIONE.

5. LE APERTURE NELLA LAMIERA NON SONO

CONSENTITE SE NON SPECIFICAMENTE INDICATE

NEI GRAFICI O APPROVATE DALL'UFFICIALE

CONTRAENTE.

6. COLLEGARE LA LAMIERA ALLA STRUTTURA

PORTANTE SEGUENDO LE INDICAZIONI DEL

PRODUTTORE.

N O

T E

G E

N E

R A

LI

/2

1. FALL PROTECTION SYSTEM MUST BE DESIGNED BY

A REGISTERED ENGINEER. CONTRACTOR MUST

SUBMIT DRAWINGS AND CALCULATIONS TO USG

AND DOR SIGNED AND SEALED FOR APPROVAL.

2. CONTRACTOR MUST SUBMIT TECHNICAL DATA

SHEET THAT CERTIFIES COMPLIANCE TO UNI EN 795,

OR OSHA REQUIREMENTS, WHICHEVER IS MORE

STRINGENT.

3. ALL DIMENSIONS INDICATED IN CONSTRUCTIONS

DETAILS MUST BE VERIFIED WITH THE ACTUAL

GEOMETRY PRIOR TO PROVIDE FPS DESIGN.

4. THE ANALYSIS IS REFERRED TO A SPECIFIC

GEOMETRY OF THE FALL PROTECTION SYSTEM

DEVICE SUPPORT SYSTEM, AND MAY VARY

ACCORDING TO THE SPECIFIC PRODUCT SELECTED

BY THE CONTRACTOR.

5. EACH UNI EN 795 CLASS C DEVICE MUST BE

PROVIDED WITH AN ENERGY DISSIPATING DEVICE

AS FORESEEN BY MANUFACTURER'S TECHNICAL

DATA SHEET, UNLESS OTHERWISE DISPOSED IN THE

SAME DOCUMENT.

6. AFTER COMPLETION OF FPS INSTALLATION,

PROVIDE A COMPLETE TECHNICAL BROCHURE

INCLUDING MAINTENANCE MANUAL TO THE

CONTRACTING OFFICER. AN ACCESS SIGN MUST BE

POSITIONED IN PROXIMITY OF ROOF ACCESS.

7. ANCHORAGE EFFICIENCY OF THE FPS MUST BE

TESTED PRIOR TO PUT IN SERVICE THE SYSTEM.

FALL PROTECTION SYSTEM NOTES

1. LE LINEE VITA DEVONO ESSERE PROGETTATE DA

UN INGEGNERE ABILITATO. L'APPALTATORE DOVRA'

SOTTOMETTERE PER APPROVAZIONE AD USG E DOR

DISEGNI ESECUTIVI E RELAZIONE DI CALCOLO.

2. L'APPALTATORE DOVRA' SOTTOMETTERE I DATI

TECNICI CHE CERTIFICHINO IL RISPETTO ALLA UNI

795, O AI REQUISITI OSHA LADDOVE PIU'

RESTRITTIVI.

3. TUTTE LE DIMENSIONI INDICATE NEI PARTICOLARI

COSTRUTTIVI DOVRANNO ESSERE VERIFICATE ED

ADEGUATE ALLA GEOMETRIA EFFETTIVA PRIMA DI

PROVEDERE AL PROGETTO DELLA LINEA VITA.

4. L'ANALISI E' RIFERITA AD UNA SPECIFICA

GEOMETRIA DEL SISTEMA ANTICADUTA, E POTRA'

VARIARE IN DIPENDENZA DELLO SPECIFICO

PRODOTTO SELEZIONATO DALL'APPALTATORE.

5. OGNI DISPOSITIVO UNI EN 795 CLASSE C DOVRA'

ESSERE EQUIPAGGIATO CON UN DISPOSITIVO DI

DISSIPAZIONE DELL'ENERGIA COME PREVISTO FAL

MANUALE TECNICO DEL PRODUTTORE, A MENO CHE

NON SIA DIVERSAMENTE DISPOSTO NELLO STESSO

DOCUMENTO.

6. DOPO AVER INSTALLATO LA LINEA VITA FORNIRE

ALL'UFFICIALE CONTRAENTE DOCUMENTAZIONE

TECNICA COMPLETA, INCLUSO IL MANUALE DI

MANUTENZIONE. UN CARTELLO DI ACCESSO DOVRA'

ESSERE POSIZIONATO IN PROSSIMITA'

DELL'ACCESSO AL TETTO.

7. L'EFFICIENZA DEI DISPOSITIVI DI ANCORAGGIO

DOVRA' ESSERE VERIFICATA PRIMA DI METTERE IN

FUNZIONE IL SISTEMA.

NOTE PER LE LINEE VITA

B1

SB201A

C1

SB202A

B1

SB202A

A1

SB201A

1 2 3 4 5 6 7 8 9

SB102A

A1

SB103A

A1

A

B

C

D

E

8500 8000 8000 8000 8000 8500

65000

SF401A

C3

67500

8000 8000

5 0 5 10 15

1:200

KEY PLAN

PIANTA DI RIFERIMENTO

BA

NORD DELLA PIANTA

PLAN NORTH

1 : 200

OVERALL FOUNDATION PLAN

C1 PIANTA GENERALE DELLE FONDAZIONI

1. FOR SPECIFICATION AND MATERIAL'S PROPERTIES SEE SHEET S001A AND

S002A.

PER LE SPECIFICHE E LE PROPRIETA' DEI MATERIALI, FARE RIFERIMENTO

ALLE TAVOLE S001A E S002A.

2. FOR CONCRETE WALLS AND BOLLARDS LOCATION REFER TO

ARCHITECTURAL AND CIVIL DRAWINGS.

PER IL POSIZIONAMENTO DEI MURI IN C.A. E DEI DISSUASORI, FARE

RIFERIMENTO AI DISEGNI ARCHITETTONICI E CIVILI.

DOTT. ING.

DI STEFANO PIETRO

ISCRITTO ALL'ALBO

PROFESSIONALE

COL N. 13921

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

DRAWFORM REVISION: 10 MARCH 2009

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

T

V

Y

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M C

O M

M A

N D

A

T L A

N T

IC

N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M C

O M

M A

N D

N O

R F

O L

K V

A

A V

IA

N

O A

IR

B

A S

E A

V

IA

N O

IT

A L Y

P -0

E D

I- R

A D

R S

T O

R A

G E

F A

C

IL

IT

Y

DESIGN DIRECTOR

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE: 04 AUGUST 2022

RICHARD STEPHENS, PE

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

FIRE PROTECTION

LET/LRP

A T

L A

N T

IC

D

E S

IG

N

A N

D C

O N

S T

R U

C T

IO

N

UNCLASSIFIED

UNCLASSIFIED

U N

C L

A S

S

IF

IE

D

P

LO

T T

E D

N6247022R3000

DPS

A

B

C

D

Approved by Allan Lucht, via Email.

JTV

1 : 200

/1

/2

:2

:3

E

L a v o ri \2

\0

-R

A D

R A v ia n o \F in a l p e r fi rm e \B

L D

G C

R -1

-S

.r v t

O V

E R

A

LL

F O

U N

D A

T

IO

N P

LA

N

SB101A

PD AA ES

S B

1A

O V

E R

A

LL

F O

U N

D A

T

IO

N P

LA

N

14121460 46 429

GENERAL SHEET NOTES:

NOTE GENERALI DEL DISEGNO :

P

IA

N T

A G

E N

E R

A L

E D

E L

L E

F O

N D

A Z

IO

1 2 3 4 5

8500 8000 8000 8000

A

B

C

D

E

2500 7100 300 7700 300 7700 300

B1

SF301A

B1

SF301A

C1

SF301A

C1

SF301A

7050 1600

6 74

-1000

-1000

-1000

-1000

SK554

A1

-1000

-1000

M A

T C

H

LI

N E

S

E E

A

O N

S H

E E

T S

B

3A

2180 6000 2000 6000 2000 6000 2000 6000 2000

2500 5500 2500

SK555

C1

SK552

C3

SK551

B1

B4

SK551

B4

SK551

C1

SR301A

C1

SR301A

B3

SK551

B3

SK551

6100 100

B1

SK567

B1

SK567

LI

N

E A

D I C

O

LL

E G

A M

E N

T O

V

E D

I A

S U

T A

V . S

B

3A

1 : 100SB101A

FOUNDATION PLAN - AREA A

A1 PIANTA FONDAZIONI - AREA A KEY PLAN

PIANTA DI RIFERIMENTO

BA

1 0 1 2 3 4 5 6 7 8 9

1:100

NORD DELLA PIANTA

PLAN NORTH

DOTT. ING.

DI STEFANO PIETRO

ISCRITTO ALL'ALBO

PROFESSIONALE

COL N. 13921

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

DRAWFORM REVISION: 10 MARCH 2009

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

T

V

Y

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M C

O M

M A

N D

A

T L A

N T

IC

N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M C

O M

M A

N D

N O

R F

O L

K V

A

A V

IA

N

O A

IR

B

A S

E A

V

IA

N O

IT

A L Y

P -0

E D

I- R

A D

R S

T O

R A

G E

F A

C

IL

IT

Y

DESIGN DIRECTOR

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE: 04 AUGUST 2022

RICHARD STEPHENS, PE

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

FIRE PROTECTION

LET/LRP

A T

L A

N T

IC

D

E S

IG

N

A N

D C

O N

S T

R U

C T

IO

N

UNCLASSIFIED

UNCLASSIFIED

U N

C L

A S

S

IF

IE

D

P

LO

T T

E D

N6247022R3000

DPS

A

B

C

D

Approved by Allan Lucht, via Email.

JTV

1 : 100

/1

/2

:2

:4

E

L a v o ri \2

\0

-R

A D

R A v ia n o \F in a l p e r fi rm e \B

L D

G C

R -1

-S

.r v t

F O

U N

D A

T

IO

N P

LA

N

A

R E

A A

SB102A

PD AA ES

S B

2A

F O

U N

D A

T

IO

N P

LA

N

A

R E

A A

14121461 47 429

KEY #

KEYED NOTES / NOTE CHIAVE

ENGLISH NOTE NOTA ITALIANA

1 COLUMN HEB320 COLONNA HEB320

2 R.C. FOOTING 2500x2500x500 PLINTO IN C.A. 2500x2500x500

3 R.C. TIE BEAM 300x500 TRAVE DI COLLEGAMENTO IN C.A. 300x500

4 R.C. FOUNDATION BEAM 1600x500 TRAVE DI FONDAZIONE IN C.A. 1600x500

5 R.C. FOUNDATION BEAM 2500x500 TRAVE DI FONDAZIONE IN C.A. 2500x500

6 R.C. INTERNAL WALL (h=2200 mm) MURO INTERNO IN C.A. (h=2200 mm)

7 R.C. EXTERNAL WALL (h=1220 mm) MURO ESTERNO IN C.A. (h=1220 mm)

8 SERVICE AREA AREA SERVIZI

9 PROVIDE STEEL COLUMN BASE

PLATE PRIOR TO CASTING THE

CORNER WALL

INSTALLARE IL PILASTRO IN ACCIAIO

PRIMA DI GETTARE IL MURO D'ANGOLO

10 BOLLARD DISSUASORE

11 REMOVABLE BOLLARD DISSUASORE RIMOVIBILE

1. FOR SPECIFICATION AND MATERIAL'S PROPERTIES SEE SHEET S001A AND

S002A.

PER LE SPECIFICHE E LE PROPRIETA' DEI MATERIALI, FARE RIFERIMENTO

ALLE TAVOLE S001A E S002A.

2. FOR CONCRETE WALLS AND BOLLARDS LOCATION REFER TO

ARCHITECTURAL AND CIVIL DRAWINGS.

PER IL POSIZIONAMENTO DEI MURI IN C.A. E DEI DISSUASORI, FARE

RIFERIMENTO AI DISEGNI ARCHITETTONICI E CIVILI.

3. COORDINATE OPENING IN CONCRETE WALL FOR UTILITY PENETRATIONS

REFER TO MECHANICAL, ELECTRICAL AND FIRE DRAWINGS PRIOR TO

SUBMITTAL OF REBAR SHOP DRAWINGS.

COORDINARE LE APERTURE NEI MURI IN C.A. PER ATTRAVERSAMENTI DI

LINEE DI SERVIZIO. FARE RIFERIMENTO AI DISEGNI MECCANICI, ELETTRICI E

ANTINCENDIO PRIMA DI SOTTOMETTERE I DISEGNI ESECUTIVI DELLE BARRE

DI ARMATURA.

GENERAL SHEET NOTES:

NOTE GENERALI DEL DISEGNO :

P

IA

N T

A F

O N

D A

Z

IO

N I -

A R

E

5 6 7 8 9

A1

SF301A

A1

SF301A

8000 8000 8500

A

B

C

D

E

300 7700 300 7700 300

7100 2500

C1

SF301A

C1

SF301A

1600 7050

6 7

34 5

6 7

-1000

-1000

-1000

-1000

-1000

-1000

-1000

M A

T C

H

LIN

E

S E

E A

1 O N

S H

E E

T S

B 102A

2000 6000 2000 6000 2000 6000 2000 6000 2180

B4

SK551

B4

SK551

2500 5500 2500

LIN

E

A D

I C O

LLE

G

A M

E N

T O

V

E D

I A 1 S

U T

A V

. S B

102A

1 : 100SB101A

FOUNDATION PLAN - AREA B

A1 PIANTA FONDAZIONI - AREA B

1 0 1 2 3 4 5 6 7 8 9

1:100

KEY PLAN

PIANTA DI RIFERIMENTO

BA

NORD DELLA PIANTA

PLAN NORTH

DOTT. ING.

DI STEFANO PIETRO

ISCRITTO ALL'ALBO

PROFESSIONALE

COL N. 13921

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

DRAWFORM REVISION: 10 MARCH 2009

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

T

V

Y

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M C

O M

M A

N D

A

T L A

N T

IC

N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M C

O M

M A

N D

N O

R F

O L

K V

A

A V

IA

N

O A

IR

B

A S

E A

V

IA

N O

IT

A L Y

P -0

E D

I- R

A D

R S

T O

R A

G E

F A

C

IL

IT

Y

DESIGN DIRECTOR

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE: 04 AUGUST 2022

RICHARD STEPHENS, PE

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

FIRE PROTECTION

LET/LRP

A T

L A

N T

IC

D

E S

IG

N

A N

D C

O N

S T

R U

C T

IO

N

UNCLASSIFIED

UNCLASSIFIED

U N

C L

A S

S

IF

IE

D

P

LO

T T

E D

N6247022R3000

DPS

A

B

C

D

Approved by Allan Lucht, via Email.

JTV

1 : 100

/1

/2

:2

:4

E

L a v o ri \2

\0

-R

A D

R A v ia n o \F in a l p e r fi rm e \B

L D

G C

R -1

-S

.r v t

F O

U N

D A

T

IO

N P

LA

N

A

R E

A B

SB103A

PD AA ES

S B

3A

F O

U N

D A

T

IO

N P

LA

N

A

R E

A B

14121462 48 429

KEY #

KEYED NOTES / NOTE CHIAVE

ENGLISH NOTE NOTA ITALIANA

1 COLUMN HEB320 COLONNA HEB320

2 R.C. FOOTING 2500x2500x500 PLINTO IN C.A. 2500x2500x500

3 R.C. TIE BEAM 300x500 TRAVE DI COLLEGAMENTO IN C.A. 300x500

4 R.C. FOUNDATION BEAM 1600x500 TRAVE DI FONDAZIONE IN C.A. 1600x500

5 R.C. FOUNDATION BEAM 2500x500 TRAVE DI FONDAZIONE IN C.A. 2500x500

6 R.C. INTERNAL WALL (h=2200 mm) MURO INTERNO IN C.A. (h=2200 mm)

7 R.C. EXTERNAL WALL (h=1220 mm) MURO ESTERNO IN C.A. (h=1220 mm)

8 SERVICE AREA AREA SERVIZI

9 PROVIDE STEEL COLUMN BASE

PLATE PRIOR TO CASTING THE

CORNER WALL

INSTALLARE IL PILASTRO IN ACCIAIO

PRIMA DI GETTARE IL MURO D'ANGOLO

10 BOLLARD DISSUASORE

11 REMOVABLE BOLLARD DISSUASORE RIMOVIBILE

1. FOR SPECIFICATION AND MATERIAL'S PROPERTIES SEE SHEET S001A AND

S002A.

PER LE SPECIFICHE E LE PROPRIETA' DEI MATERIALI, FARE RIFERIMENTO

ALLE TAVOLE S001A E S002A.

2. FOR CONCRETE WALLS AND BOLLARDS LOCATION REFER TO

ARCHITECTURAL AND CIVIL DRAWINGS.

PER IL POSIZIONAMENTO DEI MURI IN C.A. E DEI DISSUASORI, FARE

RIFERIMENTO AI DISEGNI ARCHITETTONICI E CIVILI.

3. COORDINATE OPENING IN CONCRETE WALL FOR UTILITY PENETRATIONS

REFER TO MECHANICAL, ELECTRICAL AND FIRE DRAWINGS PRIOR TO

SUBMITTAL OF REBAR SHOP DRAWINGS.

COORDINARE LE APERTURE NEI MURI IN C.A. PER ATTRAVERSAMENTI DI

LINEE DI SERVIZIO. FARE RIFERIMENTO AI DISEGNI MECCANICI, ELETTRICI E

ANTINCENDIO PRIMA DI SOTTOMETTERE I DISEGNI ESECUTIVI DELLE BARRE

DI ARMATURA.

GENERAL SHEET NOTES:

NOTE GENERALI DEL DISEGNO :

P

IA

N T

A F

O N

D A

Z

IO

N I -

A R

E

B

C1

SB202A

B1

SB202A

A1

SB201A

1 2 3 4 5 6 7 8 9

A

B

C

D

E

1650016500

4390 4390 4000 4000 4000 4000 4000 4000 4000 4000 4000 4000 4390 4390

4000 4000

16000 16000

SK552

B4

SK552

B5SR304A

C1

CTJCTJ CTJ CTJ CTJ CTJ CTJ CTJ

CTJ CTJ CTJ CTJ CTJ CTJ CTJ

CTJ CTJ CTJ CTJ CTJ CTJ CTJ

CTJ CTJ CTJ CTJ CTJ CTJ CTJCTJ

CJCJCJ

CJCJCJ

CJCJCJ

CJCJCJ

CTJ CTJ CTJ CTJCTJCTJCTJ

CTJ CTJ CTJCTJCTJCTJ

CTJ CTJ CTJCTJCTJCTJ

CTJ CTJ CTJCTJCTJ

CTJ

CTJ CTJ

CTJ

CTJ

CJ CJ CJ

CTJ CTJ CTJ CTJ

CTJ CTJ CTJ CTJ

CJCJCJ

1580 2000

1900 1900 1900 1300

DOTT. ING.

DI STEFANO PIETRO

ISCRITTO ALL'ALBO

PROFESSIONALE

COL N. 13921

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

DRAWFORM REVISION: 10 MARCH 2009

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

T

V

Y

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M C

O M

M A

N D

A

T L A

N T

IC

N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M C

O M

M A

N D

N O

R F

O L

K V

A

A V

IA

N

O A

IR

B

A S

E A

V

IA

N O

IT

A L Y

P -0

E D

I- R

A D

R S

T O

R A

G E

F A

C

IL

IT

Y

DESIGN DIRECTOR

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE: 04 AUGUST 2022

RICHARD STEPHENS, PE

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

FIRE PROTECTION

LET/LRP

A T

L A

N T

IC

D

E S

IG

N

A N

D C

O N

S T

R U

C T

IO

N

UNCLASSIFIED

UNCLASSIFIED

U N

C L

A S

S

IF

IE

D

P

LO

T T

E D

N6247022R3000

DPS

A

B

C

D

Approved by Allan Lucht, via Email.

JTV

1 : 200

/1

/2

:2

:4

E

L a v o ri \2

\0

-R

A D

R A v ia n o \F in a l p e r fi rm e \B

L D

G C

R -1

-S

.r v t

S

LA

B O

N G

R A

D E

P

LA

N

SB104A

PD AA ES

S B

4A

S

LA

B O

N G

R A

D E

P

LA

N

14121463 49 429

1 : 200

SLAB ON GRADE PLAN

C1 PIANTA SOLETTA A TERRA

3 3 3

4 2

5 0 5 10 15

1:200

NORD DELLA PIANTA

PLAN NORTH

1. FOR SPECIFICATION AND MATERIAL'S PROPERTIES SEE SHEET S001A AND

S002A.

PER LE SPECIFICHE E LE PROPRIETA' DEI MATERIALI, FARE RIFERIMENTO

ALLE TAVOLE S001A E S002A.

2. FOR CONCRETE WALLS AND BOLLARDS LOCATION REFER TO

ARCHITECTURAL DRAWINGS.

PER IL POSIZIONAMENTO DEI MURI IN C.A. E DEI DISSUASORI, FARE

RIFERIMENTO AI DISEGNI ARCHITETTONICI.

GENERAL SHEET NOTES:

NOTE GENERALI DEL DISEGNO :

5 6

P

IA

N T

A D

E

LL

A S

O

LE

T T

A A

T E

R R

A

KEY PLAN

PIANTA DI RIFERIMENTO

BA

KEY #

KEYED NOTES / NOTE CHIAVE

ENGLISH NOTE NOTA ITALIANA

1 R.C. SLAB ON GRADE THICK. 220 mm SOLETTA IN C.A. SPESSORE 220 mm

2 CONSTRUCTION JOINT (CJ). SEE

DETAIL A2 ON SHEET SK552

GIUNTO DI COSTRUZIONE. VEDERE

DETTAGLIO A2 ALLA TAVOLA SK552

3 CONTROL JOINT (CTJ). SEE DETAIL

A1 ON SHEET SK552

GIUNTO DI CONTROLLO. VEDERE

DETTAGLIO A1 ALLA TAVOLA SK552

4 EXPANSION JOINT (CEJ) BETWEEN

MAT SLAB AND R.C. WALL FOR FULL

HEIGHT OF SLAB. SEE DETAIL A3 ON

SHEET SK552

GIUNTO DI ESPANSIONE TRA LA SOLETTA

ED I MURI IN C.A. PER TUTTO LO SPESSORE

DELLA SOLETTA. VEDERE DETTAGLIO A3

ALLA TAVOLA SK552

5 COLUMN EXPANSION/ISOLATION

JOINT. SEE DETAIL A3 ON SHEET

SK552

GIUNTO DI ESPANSIONE/ISOLAMENTO

DELLA COLONNA. VEDERE DETTAGLIO A3

ALLA TAVOLA SK552

6 THICKENED EDGE. SEE SECTION C1

ON SHEET SK552

BORDO RINGROSSATO. VEDERE SEZIONE

C1 ALLA TAVOLA SK552

7 R.C. APRON AT PEDESTRIAN DOOR.

SEE DETAIL B1 ON SHEET SK567

PIAZZOLA IN C.A. AGLI INGRESSI PEDONALI.

VEDERE DETTAGLIO B1 ALLA TAVOLA SK567

8 R.C. APRON AT ROLL UP DOOR. SEE

DETAIL C1 ON SHEET SK567

PIAZZOLA IN C.A. AI VARCHI CARRABILI.

VEDERE DETTAGLIO C1 ALLA TAVOLA SK567

9 STANDARD BOLLARD - INTERNAL.

SEE DETAL A2 ON SHEET SK567

DISSUASORE STANDARD - INTERNO.

VEDERE DETTAGLIO A2 ALLA TAVOLA SK567

10 STANDARD BOLLARD - EXTERNAL.

SEE DETAL A1 ON SHEET SK567

DISSUASORE STANDARD - ESTERNO.

VEDERE DETTAGLIO A1 ALLA TAVOLA SK567

11 REMOVABLE BOLLARD - SEE DETAL

A3 ON SHEET SK567

DISSUASORE RIMOVIBILE - VEDERE

DETTAGLIO A3 ALLA TAVOLA SK567

FOUND

-1000

EAVE TOS

123456789

FIRST FLOOR

DOOR

L.C.

-1500

85008000800080008000800080008500

SK561

A1

1170 6240 1760 6240 1760 6240

SK562

A1

SK565

A1

SK563

A4

GRONDA TOS

LIV. PORTE

PRIMO PIANO

FOND.

MAGRONE

FOUND

-1000

EAVE TOS

1 2 3 4 5 6 7 8 9

FIRST FLOOR

DOOR

L.C.

-1500

8500 8000 8000 8000 8000 8000 8000 8500

1170 6240 1760 6240

SK565

D1

GRONDA TOS

LIV. PORTE

PRIMO PIANO

FOND.

MAGRONE

DOTT. ING.

DI STEFANO PIETRO

ISCRITTO ALL'ALBO

PROFESSIONALE

COL N. 13921

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

DRAWFORM REVISION: 10 MARCH 2009

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

T

V

Y

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M C

O M

M A

N D

A

T L A

N T

IC

N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M C

O M

M A

N D

N O

R F

O L

K V

A

A V

IA

N

O A

IR

B

A S

E A

V

IA

N O

IT

A L Y

P -0

E D

I- R

A D

R S

T O

R A

G E

F A

C

IL

IT

Y

DESIGN DIRECTOR

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE: 04 AUGUST 2022

RICHARD STEPHENS, PE

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

FIRE PROTECTION

LET/LRP

A T

L A

N T

IC

D

E S

IG

N

A N

D C

O N

S T

R U

C T

IO

N

UNCLASSIFIED

UNCLASSIFIED

U N

C L

A S

S

IF

IE

D

P

LO

T T

E D

N6247022R3000

DPS

A

B

C

D

Approved by Allan Lucht, via Email.

JTV

1 : 100

/1

/2

:2

:5

E

L a v o ri \2

\0

-R

A D

R A v ia n o \F in a l p e r fi rm e \B

L D

G C

R -1

-S

.r v t

E

LE

V A

T

IO

N O

N A

X

IS

SB201A

PD AA ES

S B

1A

E

LE

V A

T

IO

N O

N A

X

IS

14121464 50 429

1 : 100SB101A

ELEVATION ON AXIS

B1 PROSPETTO SU ASSE

1 : 100SB101A

ELEVATION ON AXIS

A1 PROSPETTO SU ASSE

KEY #

KEYED NOTES / NOTE CHIAVE

ENGLISH NOTE NOTA ITALIANA

1 COLUMN HEB320 COLONNA HEB320

2 BEAM HEB220 TRAVE HEB220

3 COLUMN IPE160 COLONNA IPE160

4 GIRT UPN 200 ARCARECCIO UPN200

5 SHS 150x16 TRAVE TUBOLARE 150x16

6 OVERHEAD DOOR. SEE

ARCHITECTURAL DRAWINGS

PORTA BASCULANTE. VEDERE I

DISEGNI ARCHITETTONICI

1 0 1 2 3 4 5 6 7 8 9

1:100

3 4

3 4

1. FOR SPECIFICATION AND MATERIAL'S PROPERTIES SEE SHEET S001A AND

S002A.

PER LE SPECIFICHE E LE PROPRIETA' DEI MATERIALI, FARE RIFERIMENTO

ALLE TAVOLE S001A E S002A.

2. FOR CONCRETE WALLS AND BOLLARDS LOCATION REFER TO

ARCHITECTURAL DRAWINGS.

PER IL POSIZIONAMENTO DEI MURI IN C.A. E DEI DISSUASORI, FARE

RIFERIMENTO AI DISEGNI ARCHITETTONICI.

GENERAL SHEET NOTES:

NOTE GENERALI DEL DISEGNO :

4 4

54 4

A A

E E

P R

O S

P E

T T

I S U

A S

S I A

E D

E

A A

N

EAVE TOS

FIRST FLOOR

RIDGE TOS

ABCDE

DOOR

L.C.

-1500

8660 8660 8660 8660

1340 2650 2650 2650 2650 134026502650 2650 2650

V A

R

SK563

A1

2600 26002650

SK565

B1

350 350

GRONDA TOS

LIV. PORTE

PRIMO PIANO

FOND.

MAGRONE

COLMO TOS

FOUND

-1000

EAVE TOS

FIRST FLOOR

RIDGE TOS

A B C D E

DOOR

L.C.

-1500

8660 8660 8660 8660

1340 1400

2620 2620 2620

2140 1110 2140 1985 1985 2140

2200 2200 2200

2140 13402200

V A

R

350350

GRONDA TOS

LIV. PORTE

PRIMO PIANO

FOND.

MAGRONE

COLMO TOS

DOTT. ING.

DI STEFANO PIETRO

ISCRITTO ALL'ALBO

PROFESSIONALE

COL N. 13921

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

DRAWFORM REVISION: 10 MARCH 2009

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

T

V

Y

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M C

O M

M A

N D

A

T L A

N T

IC

N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M C

O M

M A

N D

N O

R F

O L

K V

A

A V

IA

N

O A

IR

B

A S

E A

V

IA

N O

IT

A L Y

P -0

E D

I- R

A D

R S

T O

R A

G E

F A

C

IL

IT

Y

DESIGN DIRECTOR

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE: 04 AUGUST 2022

RICHARD STEPHENS, PE

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

FIRE PROTECTION

LET/LRP

A T

L A

N T

IC

D

E S

IG

N

A N

D C

O N

S T

R U

C T

IO

N

UNCLASSIFIED

UNCLASSIFIED

U N

C L

A S

S

IF

IE

D

P

LO

T T

E D

N6247022R3000

DPS

A

B

C

D

Approved by Allan Lucht, via Email.

JTV

1 : 100

/1

/2

:2

:1

E

L a v o ri \2

\0

-R

A D

R A v ia n o \F in a l p e r fi rm e \B

L D

G C

R -1

-S

.r v t

E

LE

V A

T

IO

N O

N A

X

IS

SB202A

PD AA ES

S B

2A

E

LE

V A

T

IO

N O

N A

X

IS

14121465 51 429

1 : 100SB101A

ELEVATION ON AXIS

C1 PROSPETTO SU ASSE

1 : 100SB101A

ELEVATION ON AXIS

B1 PROSPETTO SU ASSE

KEY #

KEYED NOTES / NOTE CHIAVE

ENGLISH NOTE NOTA ITALIANA

1 COLUMN HEB320 COLONNA HEB320

2 BEAM IPE400 TRAVE IPE400

3 COLUMN IPE160 COLONNA IPE160

4 GIRT UPN 200 ARCARECCIO UPN200

5 SHS 150x16 TRAVE TUBOLARE 150x16

1 0 1 2 3 4 5 6 7 8 9

1:100

3 54

1. FOR SPECIFICATION AND MATERIAL'S PROPERTIES SEE SHEET S001A AND

S002A.

PER LE SPECIFICHE E LE PROPRIETA' DEI MATERIALI, FARE RIFERIMENTO

ALLE TAVOLE S001A E S002A.

2. FOR CONCRETE WALLS AND BOLLARDS LOCATION REFER TO

ARCHITECTURAL DRAWINGS.

PER IL POSIZIONAMENTO DEI MURI IN C.A. E DEI DISSUASORI, FARE

RIFERIMENTO AI DISEGNI ARCHITETTONICI.

GENERAL SHEET NOTES:

NOTE GENERALI DEL DISEGNO :

P R

O S

P E

T T

I S U

A S

S I 1

E

A

N

C1

SB202A

B1

SB202A

A1

SB201A

1 2 3 4 5 6 7 8 9

A

B

C

D

E

8500 8000 8000 8000 8000 8000 8000 8500

65000

SF401A

C1

SF102A

A1

SF103A

A1

5 0 5 10 15

1:200

KEY PLAN

PIANTA DI RIFERIMENTO

BA

NORD DELLA PIANTA

PLAN NORTH

1 : 200

OVERALL ROOF FRAMING PLAN

C1 CARPENTERIA GENERALE DELLA COPERTURA

DOTT. ING.

DI STEFANO PIETRO

ISCRITTO ALL'ALBO

PROFESSIONALE

COL N. 13921

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

DRAWFORM REVISION: 10 MARCH 2009

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

T

V

Y

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M C

O M

M A

N D

A

T L A

N T

IC

N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M C

O M

M A

N D

N O

R F

O L

K V

A

A V

IA

N

O A

IR

B

A S

E A

V

IA

N O

IT

A L Y

P -0

E D

I- R

A D

R S

T O

R A

G E

F A

C

IL

IT

Y

DESIGN DIRECTOR

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE: 04 AUGUST 2022

RICHARD STEPHENS, PE

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

FIRE PROTECTION

LET/LRP

A T

L A

N T

IC

D

E S

IG

N

A N

D C

O N

S T

R U

C T

IO

N

UNCLASSIFIED

UNCLASSIFIED

U N

C L

A S

S

IF

IE

D

P

LO

T T

E D

N6247022R3000

DPS

A

B

C

D

Approved by Allan Lucht, via Email.

JTV

1 : 200

/1

/2

:2

:2

E

L a v o ri \2

\0

-R

A D

R A v ia n o \F in a l p e r fi rm e \B

L D

G C

R -1

-S

.r v t

O V

E R

A

LL

R O

O F

F R

A M

IN

G

P

LA

N

SF101A

PD AA ES

S F

1A

O V

E R

A

LL

R O

O F

F R

A M

IN

G

P

LA

N

14121466 52 429

1. FOR SPECIFICATION AND MATERIAL'S PROPERTIES SEE SHEET S001A AND S002A.

PER LE SPECIFICHE E LE PROPRIETA' DEI MATERIALI, FARE RIFERIMENTO ALLE

TAVOLE S001A E S002A.

2. COORDINATE ROOF PENETRATIONS WITH ARCHITECTURAL DRAWINGS AND

DETAIL D3 ON SHEET SK556.

COORDINARE LE FOROMETRIE IN COPERTURA CON I GRAFICI ARCHITETTONICI E

IL PARTICOLARE D3 SUL DISEGNO SK556.

GENERAL SHEET NOTES:

NOTE GENERALI DEL DISEGNO :

C A

R P

E N

T E

R

IA

G E

N E

R A

L E

D E

L L

A C

O P

E R

T U

R

1 2 3 4 5

B

C

D

E

8500 8000 8000 8000

3 3

M

A T

C H

LI

N

E

S E

E A

O

N S

H E

E T

S F

3A

SK558

A3

SK558

C3

SK558

A1

SK558

C1

SK558

A4

LI

N

E A

D I C

O

LL

E G

A M

E N

T O

V

E D

I A

U

T A

V . S

F

3A

SK568

D3

D3

SK556

KEY PLAN

PIANTA DI RIFERIMENTO

BA

1 0 1 2 3 4 5 6 7 8 9

1:100

NORD DELLA PIANTA

PLAN NORTH

DOTT. ING.

DI STEFANO PIETRO

ISCRITTO ALL'ALBO

PROFESSIONALE

COL N. 13921

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

DRAWFORM REVISION: 10 MARCH 2009

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

T

V

Y

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M C

O M

M A

N D

A

T L A

N T

IC

N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M C

O M

M A

N D

N O

R F

O L

K V

A

A V

IA

N

O A

IR

B

A S

E A

V

IA

N O

IT

A L Y

P -0

E D

I- R

A D

R S

T O

R A

G E

F A

C

IL

IT

Y

DESIGN DIRECTOR

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE: 04 AUGUST 2022

RICHARD STEPHENS, PE

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

FIRE PROTECTION

LET/LRP

A T

L A

N T

IC

D

E S

IG

N

A N

D C

O N

S T

R U

C T

IO

N

UNCLASSIFIED

UNCLASSIFIED

U N

C L

A S

S

IF

IE

D

P

LO

T T

E D

N6247022R3000

DPS

A

B

C

D

Approved by Allan Lucht, via Email.

JTV

1 : 100

/1

/2

:2

:2

E

L a v o ri \2

\0

-R

A D

R A v ia n o \F in a l p e r fi rm e \B

L D

G C

R -1

-S

.r v t

R O

O F

F R

A M

IN

G

P

LA

N

A R

E A

A

SF102A

PD AA ES

S F

2A

R O

O F

F R

A M

IN

G

P

LA

N

A R

E A

A

14121467 53 429

1 : 100SF101A

ROOF FRAMING PLAN - AREA A

A1 CARPENTERIA COPERTURA - AREA A

KEY #

KEYED NOTES / NOTE CHIAVE

ENGLISH NOTE NOTA ITALIANA

1 COLUMN HEB320 COLONNA HEB320

2 BEAM IPE400 TRAVE IPE400

3 BEAM HEB220 TRAVE HEB220

4 ANGLE L 150x12 CONTROVENTO L 150x12

5 ANGLE L 100x10 CONTROVENTO L 100x10

C A

R P

E N

T E

R

IA

C O

P E

R T

U R

A

A R

E A

A

1. FOR SPECIFICATION AND MATERIAL'S PROPERTIES SEE SHEET S001A AND S002A.

PER LE SPECIFICHE E LE PROPRIETA' DEI MATERIALI, FARE RIFERIMENTO ALLE

TAVOLE S001A E S002A.

2. COORDINATE ROOF PENETRATIONS WITH ARCHITECTURAL DRAWINGS AND

DETAIL D3 ON SHEET SK556.

COORDINARE LE FOROMETRIE IN COPERTURA CON I GRAFICI ARCHITETTONICI E

IL PARTICOLARE D3 SUL DISEGNO SK556.

GENERAL SHEET NOTES:

NOTE GENERALI DEL DISEGNO :

5 6 7 8 9

A1

SF301A

A1

SF301A

A

B

C

D

E

8000 8000 8000 8500

M A

T C

H

LIN

E

S E

E A

1 O N

S H

E E

T S

F 102A

SK556

A1 SK557

C1

SK556

C1

LIN

E

A D

I C O

LLE

G

A M

E N

T O

V

E D

I A

S U

T A

V . S

F 102A

1 0 1 2 3 4 5 6 7 8 9

1:100

KEY PLAN

PIANTA DI RIFERIMENTO

BA

NORD DELLA PIANTA

PLAN NORTH

DOTT. ING.

DI STEFANO PIETRO

ISCRITTO ALL'ALBO

PROFESSIONALE

COL N. 13921

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

DRAWFORM REVISION: 10 MARCH 2009

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

T

V

Y

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M C

O M

M A

N D

A

T L A

N T

IC

N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M C

O M

M A

N D

N O

R F

O L

K V

A

A V

IA

N

O A

IR

B

A S

E A

V

IA

N O

IT

A L Y

P -0

E D

I- R

A D

R S

T O

R A

G E

F A

C

IL

IT

Y

DESIGN DIRECTOR

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE: 04 AUGUST 2022

RICHARD STEPHENS, PE

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

FIRE PROTECTION

LET/LRP

A T

L A

N T

IC

D

E S

IG

N

A N

D C

O N

S T

R U

C T

IO

N

UNCLASSIFIED

UNCLASSIFIED

U N

C L

A S

S

IF

IE

D

P

LO

T T

E D

N6247022R3000

DPS

A

B

C

D

Approved by Allan Lucht, via Email.

JTV

1 : 100

/1

/2

:2

:3

E

L a v o ri \2

\0

-R

A D

R A v ia n o \F in a l p e r fi rm e \B

L D

G C

R -1

-S

.r v t

R O

O F

F R

A M

IN

G

P

LA

N

A R

E A

B

SF103A

PD AA ES

S F

3A

R O

O F

F R

A M

IN

G

P

LA

N

A R

E A

B

14121468 54 429

1 : 100SF101A

ROOF FRAMING PLAN - AREA B

A1 CARPENTERIA COPERTURA - AREA B

KEY #

KEYED NOTES / NOTE CHIAVE

ENGLISH NOTE NOTA ITALIANA

1 COLUMN HEB320 COLONNA HEB320

2 BEAM IPE400 TRAVE IPE400

3 BEAM HEB220 TRAVE HEB220

4 ANGLE L 150x12 CONTROVENTO L 150x12

5 ANGLE L 100x10 CONTROVENTO L 100x10

C A

R P

E N

T E

R

IA

C O

P E

R T

U R

A

A R

E A

B

1. FOR SPECIFICATION AND MATERIAL'S PROPERTIES SEE SHEET S001A AND S002A.

PER LE SPECIFICHE E LE PROPRIETA' DEI MATERIALI, FARE RIFERIMENTO ALLE

TAVOLE S001A E S002A.

2. COORDINATE ROOF PENETRATIONS WITH ARCHITECTURAL DRAWINGS AND

DETAIL D3 ON SHEET SK556.

COORDINARE LE FOROMETRIE IN COPERTURA CON I GRAFICI ARCHITETTONICI E

IL PARTICOLARE D3 SUL DISEGNO SK556.

D

C

A

B

3 4 5 9876

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

B B B B B B D D B B B B B BD D

B B B B B B D D B B B B B BD D

A

A

A

A

A

A

A

A

D D

D D

D D

B B B B B BD B B B B B B D

E E E E E ED E E E E E E D

E E E E E ED E E E E E E D

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

1 2 3 4 5 6 7 8 9

8500 8000 8000 8000 8000 8000 8000 8500

DOTT. ING.

DI STEFANO PIETRO

ISCRITTO ALL'ALBO

PROFESSIONALE

COL N. 13921

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

DRAWFORM REVISION: 10 MARCH 2009

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

T

V

Y

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M C

O M

M A

N D

A

T L A

N T

IC

N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M C

O M

M A

N D

N O

R F

O L

K V

A

A V

IA

N

O A

IR

B

A S

E A

V

IA

N O

IT

A L Y

P -0

E D

I- R

A D

R S

T O

R A

G E

F A

C

IL

IT

Y

DESIGN DIRECTOR

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE: 04 AUGUST 2022

RICHARD STEPHENS, PE

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

FIRE PROTECTION

LET/LRP

A T

L A

N T

IC

D

E S

IG

N

A N

D C

O N

S T

R U

C T

IO

N

UNCLASSIFIED

UNCLASSIFIED

U N

C L

A S

S

IF

IE

D

P

LO

T T

E D

N6247022R3000

DPS

A

B

C

D

Approved by Allan Lucht, via Email.

JTV

1 : 200

/1

/2

:2

:3

E

L a v o ri \2

\0

-R

A D

R A v ia n o \F in a l p e r fi rm e \B

L D

G C

R -1

-S

.r v t

S T

R U

C T

U R

A L

S C

H E

M E

SF104A

PD AA ES

S F

4A

S T

R U

C T

U R

A L

S C

H E

M E

14121469 55 429

5 0 5 10 15

1:200

NORD DELLA PIANTA

PLAN NORTH

1 : 200

STRUCTURAL SCHEME

C1 SCHEMA STRUTTURALE

1. FOR SPECIFICATION AND MATERIAL'S PROPERTIES SEE SHEET S001A AND

S002A.

PER LE SPECIFICHE E LE PROPRIETA' DEI MATERIALI, FARE RIFERIMENTO

ALLE TAVOLE S001A E S002A.

STRUCTURAL CONNECTIONS / CONNESSIONI STRUTTURALI

JOINT / NODO TYPE / TIPOLOGIA

CONNECTED MEMBERS / ELEMENTI

COLLEGATI

N. BOLTS SUPPORTING PROFILE / N. BULLONI

PORTANTE

N. BOLTS SUPPORTED PROFILE / N. BULLONI

PORTATO

A FIXED / INCASTRO BEAM IPE 400 / COL HEB320 14

B FIXED / INCASTRO BEAM HEB220 / COL HEB 320 8

C PINNED / CERNIERA BEAM IPE 400 / COL HEB320 8 4

D PINNED / CERNIERA BEAM HEB220 / COL HEB 320 6 3

E PINNED / CERNIERA BEAM HEB220 / COL HEB 320 6 3

KEY #

KEYED NOTES / NOTE CHIAVE

ENGLISH NOTE NOTA ITALIANA

1 CONNECTION JOINT A. SEE

DETAIL C1 ON SHEET SK559

CONNESSIONE NODO A. VEDI

DETTAGLIO C1 ALLA TAVOLA SK559

2 CONNECTION JOINT B. SEE

DETAIL A1 ON SHEET SK559

CONNESSIONE NODO B. VEDI

DETTAGLIO A1 ALLA TAVOLA SK559

3 CONNECTION JOINT C. SEE

DETAIL C1 ON SHEET SK560

CONNESSIONE NODO C. VEDI

DETTAGLIO C1 ALLA TAVOLA SK560

4 CONNECTION JOINT D. SEE

DETAIL D3 ON SHEET SK560

CONNESSIONE NODO D. VEDI

DETTAGLIO D3 ALLA TAVOLA SK560

5 CONNECTION JOINT E. SEE

DETAIL B1 ON SHEET SK560

CONNESSIONE NODO E. VEDI

DETTAGLIO B1 ALLA TAVOLA SK560

S C

H E

M A

S T

R U

T T

U R

A L

E

1 : 200

B1 SCHEMA STATICO LAMIERA COPERTURA

ROOF DECK SPAN SCHEME

KEY PLAN

PIANTA DI RIFERIMENTO

BA

EAVE TOS

FIRST FLOOR

RIDGE TOS

A B C D E

16001600

8660866086608660

DOOR

7710 300 300

7710 7710 7710 1600

1 9

6 7 8

L.C.

-1500

GRONDA TOS

LIV. PORTE

PRIMO PIANO

FOND.

MAGRONE

COLMO TOS

FOUND

-1000

EAVE TOS

FIRST FLOOR

RIDGE TOS

ABCDE

DOOR

8660 8660 8660 8660

34640

C1

SF301A

C1

SF301A

1 9

6 7 8

1600 7710 1600

L.C.

-1500

300 1500 900 1900 900 2510 1600 2270 900 3100 900

300 7710

GRONDA TOS

LIV. PORTE

PRIMO PIANO

FOND.

MAGRONE

COLMO TOS

FOUND

-1000

EAVE TOS

1 2 3 4 5 6 7 8 9

FIRST FLOOR

RIDGE TOS

A1

SF301A

A1

SF301A

B1

SF301A

B1

SF301A

DOOR

300 7700 300 7700 300 7050 1600 7050 300 7700 300 7700 300 7100 250014002500

8500 8000 8000 8000 8000 8000 8000 8500

10 11

6 7 8

21 5

L.C.

-1500

900 3800 900

GRONDA TOS

LIV. PORTE

PRIMO PIANO

FOND.

MAGRONE

COLMO TOS

SEZIONE

1 : 100SB103A A1

SECTION

SEZIONE

1 : 100SB102A B1

SECTION

DOTT. ING.

DI STEFANO PIETRO

ISCRITTO ALL'ALBO

PROFESSIONALE

COL N. 13921

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

DRAWFORM REVISION: 10 MARCH 2009

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

T

V

Y

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M C

O M

M A

N D

A

T L A

N T

IC

N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M C

O M

M A

N D

N O

R F

O L

K V

A

A V

IA

N

O A

IR

B

A S

E A

V

IA

N O

IT

A L Y

P -0

E D

I- R

A D

R S

T O

R A

G E

F A

C

IL

IT

Y

DESIGN DIRECTOR

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE: 04 AUGUST 2022

RICHARD STEPHENS, PE

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

FIRE PROTECTION

LET/LRP

A T

L A

N T

IC

D

E S

IG

N

A N

D C

O N

S T

R U

C T

IO

N

UNCLASSIFIED

UNCLASSIFIED

U N

C L

A S

S

IF

IE

D

P

LO

T T

E D

N6247022R3000

DPS

A

B

C

D

Approved by Allan Lucht, via Email.

JTV

1 : 100

/1

/2

:2

:4

E

L a v o ri \2

\0

-R

A D

R A v ia n o \F in a l p e r fi rm e \B

L D

G C

R -1

-S

.r v t

S E

C T

IO

N

S

SF301A

PD AA ES

S F

1A

S E

C T

IO

N

S

14121470 56 429

SEZIONE

1 : 100SB102A C1

SECTION

1 0 1 2 3 4 5 6 7 8 9

1:100

KEY #

KEYED NOTES / NOTE CHIAVE

ENGLISH NOTE NOTA ITALIANA

1 COLUMN HEB320 COLONNA HEB320

2 BEAM HEB220 TRAVE HEB220

3 BEAM IPE400 TRAVE IPE400

4 ANGLE L 150x12 CONTROVENTO L 150x12

5 ANGLE L 100x10 CONTROVENTO L 100x10

6 R.C. SLAB THICK. 220 mm SOLETTA IN C.A. SPESSORE 220 mm

7 R.C. FOOTING FONDAZIONE IN C.A.

8 STEEL PLATE PIASTRA IN ACCIAIO

9 R.C. INTERNAL WALL (h=2200 mm) MURO INTERNO IN C.A. (h=2200 mm)

10 R.C. EXTERNAL WALL (h=1220 mm) MURO ESTERNO IN C.A. (h=1220 mm)

11 BOLLARD DISSUASORE

12 R.C. WALLS THICK. 200 mm MURO IN C.A. SPESSORE 200 mm

13 REMOVABLE BOLLARD DISSUASORE RIMOVIBILE

1. FOR SPECIFICATION AND MATERIAL'S PROPERTIES SEE SHEET S001A AND

S002A.

PER LE SPECIFICHE E LE PROPRIETA' DEI MATERIALI, FARE RIFERIMENTO

ALLE TAVOLE S001A E S002A.

2. FOR CONCRETE WALLS AND BOLLARDS LOCATION REFER TO

ARCHITECTURAL DRAWINGS.

PER IL POSIZIONAMENTO DEI MURI IN C.A. E DEI DISSUASORI, FARE

RIFERIMENTO AI DISEGNI ARCHITETTONICI.

GENERAL SHEET NOTES:

NOTE GENERALI DEL DISEGNO :

S E

Z

IO

C

A1

SF401A

A1

SF401A

A3

SF401A

A3

SF401A

C3

SK551

C3

SK551

b.1 b.2 b.A b.B b.C b.D b.E

3800 900

1100 1900 1100 400

FOUND

-1000

EAVE TOS

FIRST FLOOR

C

DOOR

4000 4080 3200

L.C.

-1500 b.A b.B b.C b.D b.E

900 3100 900 2270 1600 2510 900 1900 900

GRONDA TOS

LIV. PORTE

PRIMO PIANO

FOND.

MAGRONE

FOUND

-1000

EAVE TOS

FIRST FLOOR

DOOR

2500 1400 900

L.C.

-1500 b.1 b.2

9003800

GRONDA TOS

LIV. PORTE

PRIMO PIANO

FOND.

MAGRONE

C 14

C1

SR303A

C1

SR303A

A1

SR303A

A1

SR303A

C2

SR303A

C2

SR303A

A2

SR303A

A2

SR303A

SK553

A3

SK553

A4

A4

SR303A

A4

SR303A

C4

SR303A

C4

SR303A

b.1 b.2 b.A b.B b.C b.D b.E

3100 4700280

1900 400

1100 1100

SERVICE BUILDING FOUNDATION PLAN

1 : 100SB101A C3 PIANTA FONDAZIONI LOCALI DI SERVIZIO

SEZIONE

1 : 100SF401A A1

SECTION

SEZIONE

1 : 100SF401A A3

SECTION

DOTT. ING.

DI STEFANO PIETRO

ISCRITTO ALL'ALBO

PROFESSIONALE

COL N. 13921

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

S…

This is the start of the file's text. The full file is on GovTribe.