Attachment H - 1656273dwg25of29.pdf

PDF 22 MB Posted

Attached to
P-91331, Phase 3 Family Housing Villaggio at Vicenza, Italy
Solicitation number
N6247022R0002
Issued by

About this file

This solicitation is for Phase 3 Family Housing at Villaggio at Vicenza, Italy. The Naval Facilities Engineering Command is seeking offers for the construction of additional family housing units at Villaggio. Offerors must submit proposals no later than February 25, 2022. The contract will be awarded to the responsible offeror whose offer conforming to the solicitation will be most advantageous to the Government, price and other factors considered. The work will include site preparation, utilities infrastructure, roads and parking areas, and the construction of 120 family housing units in 12 buildings. The period of performance is 730 calendar days from notice to proceed.

View the file

Other files

File Type Posted
Revised Attachment E - Schedule B Price Proposal Form_16JUN2022.pdf PDF
N6247022R0002 Amend 0007.pdf PDF
Revised Attachment E - Schedule B Price Proposal Form_16JUN2022.pdf PDF
N6247022R0002 Amend 0007.pdf PDF
Revised Attachment E - Schedule B Price Proposal Form_14JUN2022.pdf PDF
N6247022R0002 Amend 0006.pdf PDF
Attachment Q - Anti-Mafia Self-Certification Form for Contracts between 150000 and 5382000.pdf PDF
Attachment R - Anti-Mafia Self-Certification Form for Contracts greater than 5382000.pdf PDF
N6247022R0002 Amend 0005.pdf PDF
Attachment J - PSC Italian Revised Revised March 18 2022.pdf PDF
Attachment O - 1656273Amend0004 Revised Drawings .pdf PDF
N6247022R0002 Amend 0004.pdf PDF
Attachment P - Site Visit Attendance Log.pdf PDF
Attachment O - 1656273Amend0004 Revised Drawings.pdf PDF
Attachment J - PSC Italian Revised Revised March 24 2022.pdf PDF
Attachment N - 1656273Amend0004 Revised Specs.pdf PDF
Attachment E - Schedule B Price Proposal Form Revised March 24 2022.pdf PDF
N6247022R0002 Amend 0003.pdf PDF
ATTACHMENT M - 1656273Amend0003 Revised Drawings.pdf PDF
ATTACHMENT L - 1656273Amend0003 Revised Specs.pdf PDF
N6247022R0002 Amend 0002.pdf PDF
N6247022R0002 Amend 0001.pdf PDF
N6247022R0002.pdf PDF
Attachment H - 1656273dwg27of29.pdf PDF
Attachment D - Past Performance Questionnaire (PPQ).pdf PDF
Attachment H - 1656273dwg14of29.pdf PDF
Attachment H - 1656273dwg19of29.pdf PDF
Attachment H - 1656273dwg12of29.pdf PDF
Attachment H - 1656273dwg08of29.pdf PDF
Attachment H - 1656273dwg04of29.pdf PDF
Attachment H - 1656273dwg16of29.pdf PDF
Attachment K - DWG Index.pdf PDF
Attachment H - 1656273dwg28of29.pdf PDF
Attachment H - 1656273dwg18of29.pdf PDF
Attachment B - SEC-NAV_5512_1_11787 Form.pdf PDF
Attachment H - 1656273dwg17of29.pdf PDF
Attachment I - UXO Report.pdf PDF
Attachment H - 1656273dwg26of29.pdf PDF
Attachment H - 1656273dwg29of29.pdf PDF
Attachment H - 1656273dwg07of29.pdf PDF
Attachment C - Construction Experience Project Data Sheet.pdf PDF
Attachment H - 1656273dwg15of29.pdf PDF
Attachment H - 1656273dwg23of29.pdf PDF
Attachment E - Schedule B Price Proposal Form.pdf PDF
Attachment H - 1656273dwg20of29.pdf PDF
Attachment F - LRA Commercial Vehicle Inspection Procedures.pdf PDF
Attachment H - 1656273dwg13of29.pdf PDF
Attachment H - 1656273dwg11of29.pdf PDF
Attachment H - 1656273dwg06of29.pdf PDF
Attachment G - Specifications.pdf PDF
Show 40 more

Latest 50 of 61 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

F G

H I

D C

B A

E

ELEVATOR

STAIR

CORRIDOR

A2

MH445

A1

MH403

T

A1

MH403

A1

MH403

A1

MH403

C1 M-306

C2 M-306

A1 M-305

A3 M-305

B107

MASTER BEDROOM

B108

MASTER CLOSET

B109

MASTER BATH

B114

CIRCULATION

B110

BATHROOM

B111

LAUNDRY

B112

FAMILY

B113

STORAGE

B106

BEDROOM 3

B105

BEDROOM 2

B104

LIVING

B103

KITCHEN

B102

DINING

B109

MASTER BATH

B108

MASTER CLOSET

B107

MASTER BEDROOM

B114

CIRCULATION

B110

BATHROOM

B111

LAUNDRY

B106

BEDROOM 3

B105

BEDROOM 2

B104

LIVING

B103

KITCHEN

B102

DINING

B113

STORAGE

B112

FAMILY

B101

FOYER

B113

STORAGE

B112

FAMILY

B111

LAUNDRY B110

BATHROOM

B109

MASTER BATH

B108

MASTER CLOSET

B107

MASTER BEDROOM

B106

BEDROOM 3

B105

BEDROOM 2

B114

CIRCULATION

B104

LIVING

B102

DINING

B103

KITCHEN

MECHANICAL ROOM

MECHANICAL ROOM

B103

KITCHEN

B102

DINING

B104

LIVING

B105

BEDROOM 2 B106

BEDROOM 3

B107

MASTER BEDROOM

B108

MASTER CLOSET

B109

MASTER BATH

B110

BATHROOM

B111

LAUNDRY

B114

CIRCULATION

B112

FAMILY

B113

STORAGE

A2

MP445

KEYPLAN / PIANO STRATEGICO

NAPOLI

PADOVA

BOLOGNA

= BLDG LOCATIONS

= SIMILAR BLDGS

PLAN

NORTH

1:100

0 1 32 4 5 10

SCALE:

D A T E

GRAPHIC SCALE

SCALA GRAFICA

NORTH

NORD

A

B

C

D

A/E INFO

SEAL

DES DRW CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

D E P A R T M E N T

O F

T H E

N A V Y

N A V A L

F A C

IL

IT

IE

S

E N G

IN

E E R

IN

G

C O M M A N D

N O R

FO

LK

VA

VI

LL

AG

G

IO

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

A

T L A

N T

IC

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DRAWFORM REVISION: 25 AUGUST 2020

OF

EPROJECT NO.:

1 2 3 4 5

A

B

C

D

1 2 3 4 5

A P P R

D E S C R

IP

T

IO

N

S Y M

H

AM

P

TO

N

B

LV

D

VI

C E N Z A, IT

AL

Y

AECOM

10 S. Jefferson Street, Suite 1600

Roanoke, VA 24011

540.857.3100 tel

540.857.3180 fax

P -9

A R

M Y

F A

M

IL

Y H

O U

S

IN

G P

R O

JE

C

T

AS NOTED

CCA/MPO

DER

R. STEPHENS, PE

DPS

P L O T T E D

F

IL

E

P A T H

A U T H O R

Approved by Michele Millers, AFH-C Program Manager, USAG Italy, via email

6 OCT 2021

:1 :5

P M

B

IM

B P A M E R

V ic e n z a p h a s e

II

I_ A F H P A P M e n v e lo p e .r v t

MWM BVMWM

A P

B U

IL

D

IN

G

F

IR

S T

F L O

O R

M E

C H

A N

IC

A

L P

L A

N

IM

P

IA

N

T I M

E C

C A

N

IC

I A

P E

D

IF

IC

IO

P

IA

N

O P

R

IM

O

M-122

14106742

1656273

M W M

SCALE 1 : 100

A1

AP BUILDING 27300 FIRST FLOOR MECHANICAL PLAN /

IMPIANTI MECCANICI AP EDIFICIO 27300 PIANO PRIMO

GENERAL NOTES/

NOTE GENERALI DI QUESTO FOGLIO:

1. SEE SHEET M-001 AND M-002 FOR ABBREVIATIONS, CHARACTER IDENTIFIERS

IN LINES ON PIPING LEGEND ARE ALSO USED FOR ABBREVIATIONS. / VEDERE

TAVOLA M-001 E M-002 PER LEGENDE, NOTE GENERALI E ABBREVIAZIONI.

2. PROVIDE ACCESS PANELS THROUGHOUT FOR ALL EQUIPMENT REQUIRING

MAINTENANCE. / FORNINE BOTOLE DI ACCESSO PER TUTTE LE

APPARECCHIATURE CHE RICHIEDONO MANUTENZIONE.

3. APARTMENT BUILDING 27300 IS SHOWN HERE. BUILDING 29200 IS A

DUPLICATE EXCEPT FOR THE GROUND FLOOR. DRAWINGS ARE NOT PROVIDED

FOR THE DUPLICATE FLOORS AT 29200. SEE SHEET M-141 FOR UNIQUE

GROUND FLOOR AT 29200. SEE SHEET AS001 FOR CORRECT ORIENTATION. /

QUI VIENE MOSTRATO IL CONDOMINIO 27300. IL CONDOMINIO 29200 È UN

DUPLICATO, ECCETTO PER IL PIANO TERRA. I DISEGNI NON SONO FORNITI PER

I PIANI DUPLICATI DEL 29200. VEDERE IL FOGLIO M-141 PER IL PIANO TERRA

UNICO AL 29200. VEDERE IL FOGLIO AS001 PER L’ORIENTAMENTO CORRETTO

G

H I

D C

B A

E

A1

MH402

T

A1

MH402

A1

MH402

A1

MH402

A2

MP445

A2

MH445

A1 M-305

A3 M-305

B007

MASTER BEDROOM

B008

MASTER CLOSET

B014

CIRCULATION

B006

BEDROOM 3

B005

BEDROOM 2

B004

LIVING

B003

KITCHEN

B002

DINING

B013

STORAGE

B012

FAMILY

B011

LAUNDRY

B010

BATHROOM

B009

MASTER BATH

STAIR

B007

MASTER BEDROOM

B008

MASTER CLOSET

B009

MASTER BATH

B010

BATHROOM

B011

LAUNDRY

B012

FAMILY

B013

STORAGE

B006

BEDROOM 3

B014

CIRCULATION

B005

BEDROOM 2

B004

LIVING

B003

KITCHEN

B002

DINING

B003

KITCHEN

B002

DINING

B013

STORAGE

B014

CIRCULATION

B012

FAMILY

B011

LAUNDRY B010

BATHROOM

B009

MASTER BATH

B008

MASTER CLOSET

B007

MASTER BEDROOM

B006

BEDROOM 3

B005

BEDROOM 2

B004

LIVING

ELEVATOR

B003

KITCHEN

B002

DINING

B013

STORAGE

B012

FAMILY

B011

LAUNDRY

B004

LIVING B005

BEDROOM 2 B006

BEDROOM 3

B014

CIRCULATION

B010

BATHROOM B009

MASTER BATH

B008

MASTER CLOSET

B007

MASTER BEDROOM

CORRIDOR

MECHANICAL ROOM

MECHANICAL ROOM

KEYPLAN / PIANO STRATEGICO

NAPOLI

PADOVA

BOLOGNA

= BLDG LOCATIONS

= SIMILAR BLDGS

PLAN

NORTH

1:100

0 1 32 4 5 10

SCALE:

D A T E

GRAPHIC SCALE

SCALA GRAFICA

NORTH

NORD

A

B

C

D

A/E INFO

SEAL

DES DRW CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

D E P A R T M E N T

O F

T H E

N A V Y

N A V A L

F A C

IL

IT

IE

S

E N G

IN

E E R

IN

G

C O M M A N D

N O R

FO

LK

VA

VI

LL

AG

G

IO

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

A

T L A

N T

IC

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DRAWFORM REVISION: 25 AUGUST 2020

OF

EPROJECT NO.:

1 2 3 4 5

A

B

C

D

1 2 3 4 5

A P P R

D E S C R

IP

T

IO

N

S Y M

H

AM

P

TO

N

B

LV

D

VI

C E N Z A, IT

AL

Y

AECOM

10 S. Jefferson Street, Suite 1600

Roanoke, VA 24011

540.857.3100 tel

540.857.3180 fax

P -9

A R

M Y

F A

M

IL

Y H

O U

S

IN

G P

R O

JE

C

T

AS NOTED

CCA/MPO

DER

R. STEPHENS, PE

DPS

P L O T T E D

F

IL

E

P A T H

A U T H O R

Approved by Michele Millers, AFH-C Program Manager, USAG Italy, via email

6 OCT 2021

:1 :0

P M

B

IM

B P A M E R

V ic e n z a p h a s e

II

I_ A F H P A P M e n v e lo p e .r v t

MWM BVMWM

A P

B U

IL

D

IN

G

T

Y P

IC

A

L F

L O

O R

M E

C H

A N

IC

A

L P

L A

N

IM

P

IA

N

T I M

E C

C A

N

IC

I A

P E

D

IF

IC

IO

P

IA

N

O T

IP

IC

O

M-123

14106743

1656273

M W M

GENERAL NOTES/

NOTE GENERALI DI QUESTO FOGLIO:

1. SEE SHEET M-001 AND M-002 FOR ABBREVIATIONS, CHARACTER IDENTIFIERS

IN LINES ON PIPING LEGEND ARE ALSO USED FOR ABBREVIATIONS. / VEDERE

TAVOLA M-001 E M-002 PER LEGENDE, NOTE GENERALI E ABBREVIAZIONI.

2. PROVIDE ACCESS PANELS THROUGHOUT FOR ALL EQUIPMENT REQUIRING

MAINTENANCE. / FORNINE BOTOLE DI ACCESSO PER TUTTE LE

APPARECCHIATURE CHE RICHIEDONO MANUTENZIONE.

3. APARTMENT BUILDING 27300 IS SHOWN HERE. BUILDING 29200 IS A

DUPLICATE EXCEPT FOR THE GROUND FLOOR. DRAWINGS ARE NOT PROVIDED

FOR THE DUPLICATE FLOORS AT 29200. SEE SHEET M-141 FOR UNIQUE

GROUND FLOOR AT 29200. SEE SHEET AS001 FOR CORRECT ORIENTATION. /

QUI VIENE MOSTRATO IL CONDOMINIO 27300. IL CONDOMINIO 29200 È UN

DUPLICATO, ECCETTO PER IL PIANO TERRA. I DISEGNI NON SONO FORNITI PER

I PIANI DUPLICATI DEL 29200. VEDERE IL FOGLIO M-141 PER IL PIANO TERRA

UNICO AL 29200. VEDERE IL FOGLIO AS001 PER L’ORIENTAMENTO CORRETTO

SCALE 1 : 100

A1

AP BUILDING 27300 TYPICAL FLOOR MECHANICAL PLAN /

IMPIANTI MECCANICI AP EDIFICIO 27300 PIANO TIPICO

T

G

H I

D C

B A

E

P02

MECHANICAL ROOM

P07

STAIR

A3

MH445

A1 M-305

A3 M-305

A3 M-306

A1 M-306

A3

MP445

KEYPLAN / PIANO STRATEGICO

NAPOLI

PADOVA

BOLOGNA

= BLDG LOCATIONS

= SIMILAR BLDGS

PLAN

NORTH

1:100

0 1 32 4 5 10

SCALE:

D A T E

GRAPHIC SCALE

SCALA GRAFICA

NORTH

NORD

A

B

C

D

A/E INFO

SEAL

DES DRW CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

D E P A R T M E N T

O F

T H E

N A V Y

N A V A L

F A C

IL

IT

IE

S

E N G

IN

E E R

IN

G

C O M M A N D

N O R

FO

LK

VA

VI

LL

AG

G

IO

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

A

T L A

N T

IC

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DRAWFORM REVISION: 25 AUGUST 2020

OF

EPROJECT NO.:

1 2 3 4 5

A

B

C

D

1 2 3 4 5

A P P R

D E S C R

IP

T

IO

N

S Y M

H

AM

P

TO

N

B

LV

D

VI

C E N Z A, IT

AL

Y

AECOM

10 S. Jefferson Street, Suite 1600

Roanoke, VA 24011

540.857.3100 tel

540.857.3180 fax

P -9

A R

M Y

F A

M

IL

Y H

O U

S

IN

G P

R O

JE

C

T

AS NOTED

CCA/MPO

DER

R. STEPHENS, PE

DPS

P L O T T E D

F

IL

E

P A T H

A U T H O R

Approved by Michele Millers, AFH-C Program Manager, USAG Italy, via email

6 OCT 2021

:1 :0

P M

B

IM

B P A M E R

V ic e n z a p h a s e

II

I_ A F H P A P M e n v e lo p e .r v t

MWM BVMWM

A P

B U

IL

D

IN

G

P

E N

T H

O U

S E

M E

C H

A N

IC

A

L P

L A

N

IM

P

IA

N

T I M

E C

C A

N

IC

I A

P E

D

IF

IC

IO

P

IA

N

O A

T T

IC

O

M-124

14106744

1656273

M W M

SCALE 1 : 100

A1

AP BUILDING 27300 PENTHOUSE MECHANICAL PLAN /

IMPIANTI MECCANICI AP EDIFICIO 27300 PIANO ATTICO

GENERAL NOTES/

NOTE GENERALI DI QUESTO FOGLIO:

1. SEE SHEET M-001 AND M-002 FOR ABBREVIATIONS, CHARACTER IDENTIFIERS

IN LINES ON PIPING LEGEND ARE ALSO USED FOR ABBREVIATIONS. / VEDERE

TAVOLA M-001 E M-002 PER LEGENDE, NOTE GENERALI E ABBREVIAZIONI.

2. PROVIDE ACCESS PANELS THROUGHOUT FOR ALL EQUIPMENT REQUIRING

MAINTENANCE. / FORNINE BOTOLE DI ACCESSO PER TUTTE LE

APPARECCHIATURE CHE RICHIEDONO MANUTENZIONE.

3. APARTMENT BUILDING 27300 IS SHOWN HERE. BUILDING 29200 IS A

DUPLICATE EXCEPT FOR THE GROUND FLOOR. DRAWINGS ARE NOT PROVIDED

FOR THE DUPLICATE FLOORS AT 29200. SEE SHEET M-141 FOR UNIQUE

GROUND FLOOR AT 29200. SEE SHEET AS001 FOR CORRECT ORIENTATION. /

QUI VIENE MOSTRATO IL CONDOMINIO 27300. IL CONDOMINIO 29200 È UN

DUPLICATO, ECCETTO PER IL PIANO TERRA. I DISEGNI NON SONO FORNITI PER

I PIANI DUPLICATI DEL 29200. VEDERE IL FOGLIO M-141 PER IL PIANO TERRA

UNICO AL 29200. VEDERE IL FOGLIO AS001 PER L’ORIENTAMENTO CORRETTO

EF-1

C008

MASTER BEDROOM

C007

BEDROOM 3

C006

BEDROOM 2

C005

LIVING

C015

BALCONY

C004

KITCHEN

C003

DINING

C009

MASTER CLOSET

C010

MASTER BATH

C011

BATHROOM C012

LAUNDRY

C013

STORAGE

C001

FOYER

C002

FAMILY

STAIR

CORRIDOR

EL

EC

TR

IC

AL

COMMUNICATIONS

GARAGE

A1

MH404

23.22

A1

MH441

4321 5 6 7 8 9 12 13 14 15 16 17

L

J

K

G

H

F

D

B

A

C

E

10 11

23.51

T

T A1

MP441

EF-4 T

23.62

23.65

23.65

SPRINKLER

FCH-1

T

23.270 23.11

20 HWR

20 HWS

KEYPLAN / PIANO STRATEGICO

NAPOLI

PADOVA

BOLOGNA

= BLDG LOCATIONS

= SIMILAR BLDGS

PLAN

NORTH

1:100

0 1 32 4 5 10

SCALE:

D A T E

GRAPHIC SCALE

SCALA GRAFICA

NORTH

NORD

A

B

C

D

A/E INFO

SEAL

DES DRW CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

D E P A R T M E N T

O F

T H E

N A V Y

N A V A L

F A C

IL

IT

IE

S

E N G

IN

E E R

IN

G

C O M M A N D

N O R

FO

LK

VA

VI

LL

AG

G

IO

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

A

T L A

N T

IC

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DRAWFORM REVISION: 25 AUGUST 2020

OF

EPROJECT NO.:

1 2 3 4 5

A

B

C

D

1 2 3 4 5

A P P R

D E S C R

IP

T

IO

N

S Y M

H

AM

P

TO

N

B

LV

D

VI

C E N Z A, IT

AL

Y

AECOM

10 S. Jefferson Street, Suite 1600

Roanoke, VA 24011

540.857.3100 tel

540.857.3180 fax

P-

AR

M

Y

FA

M

IL

Y H

O U

SI

N

G P

R O

JE

C

T

AS NOTED

CCA/MPO

DER

R. STEPHENS, PE

DPS

P L O T T E D

F

IL

E

P A T H

A U T H O R

Approved by Michele Millers, AFH-C Program Manager, USAG Italy, via email

6 OCT 2021

:5 :4

P M

B

IM

B P A M E R

V ic e n z a p h a s e

II

I_ A F H P A P M e n v e lo p e .r v t

MWM BVMWM

A P

B U

IL

D

IN

G

G

R O

U N

D F

L O

O R

M E

C H

A N

IC

A

L P

L A

N

IM

P

IA

N

T I M

E C

C A

N

IC

I A

P E

D

IF

IC

IO

P

IA

N O

T E

R R

A

M-131

14106745

1656273

M W M

NOTE CHIAVE DELLA TAVOLA:

SHEET KEYNOTES /

23.11 PROVIDE FCU CABINET HEATER. SEE EQUIPMENT SCHEDULES ON SHEET

M-601. / FORNIRE VENTILCONVETTORE. VEDERE ABACO APPARECCHIATURE

TAVOLA M-601.

23.22 PROVIDE WALL MOUNTED GARAGE EXHAUST FAN. PROVIDE WITH RAIN

HOOD, BACKDRAFT DAMPER, AND INSECT SCREEN. SEE EQUIPMENT

SCHEDULE ON SHEET M-601. / FORNIRE UN ESTRATTORE GARAGE

MONTATO A PARETE. FORNIRE CAPPA ANTIPIOGGIA, VALVOLA DI NON

RITORNO E RETE ANTI INSETTI. VEDERE ABACO APPARECCHIATURE

TAVOLA M-601.

23.24 PROVIDE THERMOSTAT, TYP. / FORNIRE TERMOSTATO, TIPO.

23.51 THE CORE AREA OF THIS BUILDING IS MIRRORED COMPARED TO THE

ENLARGED VIEW INDICATED. / L’AREA CENTRALE DI QUESTO EDIFICIO È

SPECULARE RISPETTO ALLA VISTA INGRANDITA INDICATA.

23.62 PROVIDE WALL MOUNTED EXHAUST FAN FOR COMMUNICATION ROOM.

PROVIDE WITH RAIN HOOD, BACKDRAFT DAMPER, AND INSECT SCREEN.

SEE EQUIPMENT SCHEDULE ON SHEET M-601. / FORNIRE UN ESTRATTORE

MONTATO A PARETE PER LA SALA DI COMUNICAZIONE. FORNIRE CAPPA

ANTIPIOGGIA, VALVOLA DI NON RITORNO E RETE ANTINSETTI. VEDERE

ABACO ATTREZZATURE TAVOLA M-601.

23.65 PROVIDE GRILLES FOR NATURAL VENTILATION IN TECHNICAL ROOMS

(MECHANICAL, COMMUNICATIONS AND ELECTRICAL ROOMS) AND FOR THE

ELEVATOR SHAFT. SEE SHEET A-607 AND A-608 FOR DETAILS. / FORNIRE

GRIGLIE VENTILAZIONE NATURALE NEI LOCALI TECNICI (LOCALI MECCANICI,

DI COMUNICAZIONE ED ELETTRICI) E PER IL VANO ASCENSORE. VEDERE

TAVOLA A-607 A A-608 PER I DETTAGLI.

23.270 ROUTE HEATING HOT WATER PIPING INSIDE INSULATED BULKHEAD TO

SPRINKLER ROOM. / PERCORSO TUBAZIONI ACQUA CALDA ALL'INTERNO DI

ELEMENTI ISOLATI AL LOCALE DEGLI SPRINKLER.

GENERAL NOTES/

NOTE GENERALI DI QUESTO FOGLIO:

1. SEE SHEET M-001 AND M-002 FOR ABBREVIATIONS, CHARACTER IDENTIFIERS

IN LINES ON PIPING LEGEND ARE ALSO USED FOR ABBREVIATIONS. / VEDERE

TAVOLA M-001 E M-002 PER LEGENDE, NOTE GENERALI E ABBREVIAZIONI.

2. PROVIDE ACCESS PANELS THROUGHOUT FOR ALL EQUIPMENT REQUIRING

MAINTENANCE. / FORNINE BOTOLE DI ACCESSO PER TUTTE LE

APPARECCHIATURE CHE RICHIEDONO MANUTENZIONE.

3. APARTMENT BUILDING 28200 IS SHOWN HERE FOR GROUND AND FIRST

FLOORS. SEE SHEETS M-103, M-104 AND M-105 FOR MIRRORED IMAGE OF ALL

OTHER FLOORS. APARTMENT BUILDING 29300 IS A MIRROR IMAGE OF THIS

BUILDING. APARTMENT BUILDING 29100 IS A DUPLICATE OF THIS BUILDING

EXCEPT FOR THE GROUND AND THIRD FLOORS. SEE SHEET AS001 FOR

CORRECT ORIENTATION. / QUI VIENE MOSTRATO IL CONDOMINIO 28200

RELATIVAMENTE AL PIANO TERRA E AL PRIMO PIANO. VEDERE I FOGLI M-103,

M-104 E M-105 PER UN’IMMAGINE SPECULARE DI TUTTI GLI ALTRI PIANI. IL

CONDOMINIO 29300 È UN’IMMAGINE SPECULARE DI QUESTO EDIFICIO. IL

CONDOMINIO 29100 È UN DUPLICATO DI QUESTO EDIFICIO ECCETTO IL PIANO

TERRA E IL TERZO PIANO. VEDERE IL FOGLIO AS001 PER L’ORIENTAMENTO

CORRETTO

SCALE 1 : 100

A2

AP BUILDING 28200 GROUND FLOOR MECHANICAL PLAN /

IMPIANTI MECCANICI AP EDIFICIO 28200 PIANO TERRA

E008

MASTER BEDROOM

E016

BALCONY

E003

LIVING

E004

KITCHEN

E005

DINING

E006

BEDROOM 2

E007

BEDROOM 3

E009

MASTER CLOSET

E015

CIRCULATION

E002

FAMILY

E001

FOYER

E014

STORAGEE013

LAUNDRY

E012

BATHROOM

E010

MASTER BATH

E011

BEDROOM 4

STAIR

CORRIDOR

B103

KITCHEN

B102

DINING

B103

KITCHEN

B102

DINING

B113

STORAGEB113

STORAGE

MECHANICAL

B101

FOYER

B101

FOYER

B115

BALCONY

B104

LIVING

B112

FAMILY

B112

FAMILY

B104

LIVING

B115

BALCONY

B105

BEDROOM 2

B111

LAUNDRY

B111

LAUNDRY

B105

BEDROOM 2

B114

CIRCULATION

B114

CIRCULATION

B106

BEDROOM 3

B110

BATHROOM

B110

BATHROOM

B106

BEDROOM 3

B107

MASTER BEDROOM

B108

MASTER CLOSET

B109

MASTER BATH

B109

MASTER BATH

B108

MASTER CLOSET B107

MASTER BEDROOM

A1

MH411

A2

MH441

A1

MH403

4321 5 6 7 8 9 12 13 14 15 16 17

L

J

K

G

H

F

D

B

A

C

E

10 11

23.51

T

A2

MP441

A1

MH403

KEYPLAN / PIANO STRATEGICO

NAPOLI

PADOVA

BOLOGNA

= BLDG LOCATIONS

= SIMILAR BLDGS

PLAN

NORTH

1:100

0 1 32 4 5 10

SCALE:

D A T E

GRAPHIC SCALE

SCALA GRAFICA

NORTH

NORD

A

B

C

D

A/E INFO

SEAL

DES DRW CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

D E P A R T M E N T

O F

T H E

N A V Y

N A V A L

F A C

IL

IT

IE

S

E N G

IN

E E R

IN

G

C O M M A N D

N O R

FO

LK

VA

VI

LL

AG

G

IO

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

A

T L A

N T

IC

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DRAWFORM REVISION: 25 AUGUST 2020

OF

EPROJECT NO.:

1 2 3 4 5

A

B

C

D

1 2 3 4 5

A P P R

D E S C R

IP

T

IO

N

S Y M

H

AM

P

TO

N

B

LV

D

VI

C E N Z A, IT

AL

Y

AECOM

10 S. Jefferson Street, Suite 1600

Roanoke, VA 24011

540.857.3100 tel

540.857.3180 fax

P -9

A R

M Y

F A

M

IL

Y H

O U

S

IN

G P

R O

JE

C

T

AS NOTED

CCA/MPO

DER

R. STEPHENS, PE

DPS

P L O T T E D

F

IL

E

P A T H

A U T H O R

Approved by Michele Millers, AFH-C Program Manager, USAG Italy, via email

6 OCT 2021

:5 :4

P M

B

IM

B P A M E R

V ic e n z a p h a s e

II

I_ A F H P A P M e n v e lo p e .r v t

MWM BVMWM

A P

B U

IL

D

IN

G

F

IR

S T

F L O

O R

M E

C H

A N

IC

A

L P

L A

N

IM

P

IA

N

T I M

E C

C A

N

IC

I A

P E

D

IF

IC

IO

P

IA

N

O P

R

IM

O

M-132

14106746

1656273

M W M

GENERAL NOTES/

NOTE GENERALI DI QUESTO FOGLIO:

1. SEE SHEET M-001 AND M-002 FOR ABBREVIATIONS, CHARACTER IDENTIFIERS

IN LINES ON PIPING LEGEND ARE ALSO USED FOR ABBREVIATIONS. / VEDERE

TAVOLA M-001 E M-002 PER LEGENDE, NOTE GENERALI E ABBREVIAZIONI.

2. PROVIDE ACCESS PANELS THROUGHOUT FOR ALL EQUIPMENT REQUIRING

MAINTENANCE. / FORNINE BOTOLE DI ACCESSO PER TUTTE LE

APPARECCHIATURE CHE RICHIEDONO MANUTENZIONE.

3. APARTMENT BUILDING 28200 IS SHOWN HERE FOR GROUND AND FIRST

FLOORS. SEE SHEETS M-103, M-104 AND M-105 FOR MIRRORED IMAGE OF ALL

OTHER FLOORS. APARTMENT BUILDING 29300 IS A MIRROR IMAGE OF THIS

BUILDING. APARTMENT BUILDING 29100 IS A DUPLICATE OF THIS BUILDING

EXCEPT FOR THE GROUND AND THIRD FLOORS. SEE SHEET AS001 FOR

CORRECT ORIENTATION. / QUI VIENE MOSTRATO IL CONDOMINIO 28200

RELATIVAMENTE AL PIANO TERRA E AL PRIMO PIANO. VEDERE I FOGLI M-103,

M-104 E M-105 PER UN’IMMAGINE SPECULARE DI TUTTI GLI ALTRI PIANI. IL

CONDOMINIO 29300 È UN’IMMAGINE SPECULARE DI QUESTO EDIFICIO. IL

CONDOMINIO 29100 È UN DUPLICATO DI QUESTO EDIFICIO ECCETTO IL PIANO

TERRA E IL TERZO PIANO. VEDERE IL FOGLIO AS001 PER L’ORIENTAMENTO

CORRETTO

NOTE CHIAVE DELLA TAVOLA:

SHEET KEYNOTES /

23.51 THE CORE AREA OF THIS BUILDING IS MIRRORED COMPARED TO THE

ENLARGED VIEW INDICATED. / L’AREA CENTRALE DI QUESTO EDIFICIO È

SPECULARE RISPETTO ALLA VISTA INGRANDITA INDICATA.

SCALE 1 : 100

A2

AP BUILDING 28200 FIRST FLOOR MECHANICAL PLAN /

IMPIANTI MECCANICI AP EDIFICIO 28200 PIANO PRIMO

4321 5 6 7 8 9 12 13 14 15 16 17

L

J

K

G

H

F

D

B

A

C

E

10 11

A008

MASTER BEDROOM

A007

BEDROOM 3

A006

BEDROOM 2

A005

LIVING ROOM

A015

BALCONY

A004

KITCHEN

A003

DINING

A002

FAMILY

A001

FOYER

A013

STORAGE

A012

LAUNDRY

A011

BATHROOM

A010

MASTER BATHROOM

A009

MASTER CLOSET

A014

CIRCULATION

STAIR

CORRIDOR

MECHANICAL

MECHANICAL

H002

DINING

H003

LIVING

H019

BALCONY

H016

FAMILY

H015

KITCHEN

H014

BEDROOM 5

H012

MASTER BEDROOM

H013

BEDROOM 4

H017

CIRCULATION

H009

BATHROOM

H008

BATHROOM

H007

BEDROOM 3

H006

BEDROOM 2

H005

LAUNDRY

H004

PANTRY

H010

MASTER BATH

H011

MASTER CLOSET

A1

MH442

A1

MH422

A1

MH401

T

A1

MP442

KEYPLAN / PIANO STRATEGICO

NAPOLI

PADOVA

BOLOGNA

= BLDG LOCATIONS

= SIMILAR BLDGS

PLAN

NORTH

1:100

0 1 32 4 5 10

SCALE:

D A T E

GRAPHIC SCALE

SCALA GRAFICA

NORTH

NORD

A

B

C

D

A/E INFO

SEAL

DES DRW CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

D E P A R T M E N T

O F

T H E

N A V Y

N A V A L

F A C

IL

IT

IE

S

E N G

IN

E E R

IN

G

C O M M A N D

N O R

FO

LK

VA

VI

LL

AG

G

IO

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

A

T L A

N T

IC

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DRAWFORM REVISION: 25 AUGUST 2020

OF

EPROJECT NO.:

1 2 3 4 5

A

B

C

D

1 2 3 4 5

A P P R

D E S C R

IP

T

IO

N

S Y M

H

AM

P

TO

N

B

LV

D

VI

C E N Z A, IT

AL

Y

AECOM

10 S. Jefferson Street, Suite 1600

Roanoke, VA 24011

540.857.3100 tel

540.857.3180 fax

P -9

A R

M Y

F A

M

IL

Y H

O U

S

IN

G P

R O

JE

C

AS NOTED

CCA/MPO

DER

R. STEPHENS, PE

DPS

P L O T T E D

F

IL

E

P A T H

A U T H O R

Approved by Michele Millers, AFH-C Program Manager, USAG Italy, via email

6 OCT 2021

:0 :3

P M

B

IM

B P A M E R

V ic e n z a p h a s e

II

I_ A F H P A P M e n v e lo p e .r v t

MWM BVMWM

A P

B U

IL

D

IN

G

T

H

IR

D F

L O

O R

M E

C H

A N

IC

A

L P

L A

N

IM

P

IA

N

T I M

E C

C A

N

IC

I A

P E

D

IF

IC

IO

P

IA

N

O T

E R

Z O

M-135

14106747

1656273

M W M

GENERAL NOTES/

NOTE GENERALI DI QUESTO FOGLIO:

1. SEE SHEET M-001 AND M-002 FOR ABBREVIATIONS, CHARACTER IDENTIFIERS

IN LINES ON PIPING LEGEND ARE ALSO USED FOR ABBREVIATIONS. / VEDERE

TAVOLA M-001 E M-002 PER LEGENDE, NOTE GENERALI E ABBREVIAZIONI.

2. PROVIDE ACCESS PANELS THROUGHOUT FOR ALL EQUIPMENT REQUIRING

MAINTENANCE. / FORNINE BOTOLE DI ACCESSO PER TUTTE LE

APPARECCHIATURE CHE RICHIEDONO MANUTENZIONE.

3. THE GROUND FLOOR OF APARTMENT BUILDING 29100 IS SHOWN HERE. SEE

SHEET M-101 FOR MIRROR IMAGE OF GROUND FLOOR. SEE SHEET M-132 FOR

FIRST FLOOR. SEE SHEET M-103 FOR MIRROR IMAGE OF SECOND FLOOR. SEE

SHEET AS001 FOR CORRECT ORIENTATION. / QUI VIENE MOSTRATO IL TERZO

PIANO DEL CONDOMINIO 29100. VEDERE IL FOGLIO M-101 PER UN’IMMAGINE

SPECULARE DEL PIANO TERRA. VEDERE IL FOGLIO M-132 PER IL PRIMO PIANO.

VEDERE IL FOGLIO M-103 PER UN’IMMAGINE SPECULARE DEL SECONDO PIANO.

VEDERE IL FOGLIO AS001 PER L’ORIENTAMENTO CORRETTO

SCALE 1 : 100

A2

AP BUILDING 29100 THIRD FLOOR MECHANICAL PLAN /

IMPIANTI MECCANICI AP EDIFICIO 29100 PIANO TERZO

4321 5 6 7 8 9 12 13 14 15 16 17

L

J

K

G

H

F

D

B

A

C

E

10 11

A2

MH442

A2

MP442

23.256

23.256

23.256

KEYPLAN / PIANO STRATEGICO

NAPOLI

PADOVA

BOLOGNA

= BLDG LOCATIONS

= SIMILAR BLDGS

PLAN

NORTH

1:100

0 1 32 4 5 10

SCALE:

D A T E

GRAPHIC SCALE

SCALA GRAFICA

NORTH

NORD

A

B

C

D

A/E INFO

SEAL

DES DRW CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

D E P A R T M E N T

O F

T H E

N A V Y

N A V A L

F A C

IL

IT

IE

S

E N G

IN

E E R

IN

G

C O M M A N D

N O R

FO

LK

VA

VI

LL

AG

G

IO

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

A

T L A

N T

IC

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DRAWFORM REVISION: 25 AUGUST 2020

OF

EPROJECT NO.:

1 2 3 4 5

A

B

C

D

1 2 3 4 5

A P P R

D E S C R

IP

T

IO

N

S Y M

H

AM

P

TO

N

B

LV

D

VI

C E N Z A, IT

AL

Y

AECOM

10 S. Jefferson Street, Suite 1600

Roanoke, VA 24011

540.857.3100 tel

540.857.3180 fax

P -9

A R

M Y

F A

M

IL

Y H

O U

S

IN

G P

R O

JE

DER

R. STEPHENS, PE

DPS

P L O T T E D

F

IL

E

P A T H

A U T H O R

Approved by Michele Millers, AFH-C Program Manager, USAG Italy, via email

6 OCT 2021

:0 :3

P M

B

IM

B P A M E R

V ic e n z a p h a s e

II

I_ A F H P A P M e n v e lo p e .r v t

MWM BVMWM

A P

B U

IL

D

IN

G

P

E N

T H

O U

S E

M E

C H

A N

IC

A

L P

L A

N

IM

P

IA

N

T I M

E C

C A

N

IC

I A

P E

D

IF

IC

IO

P

IA

N

O A

T T

IC

O

M-136

14106748

1656273

M W M

GENERAL NOTES/

NOTE GENERALI DI QUESTO FOGLIO:

1. SEE SHEET M-001 AND M-002 FOR ABBREVIATIONS, CHARACTER IDENTIFIERS

IN LINES ON PIPING LEGEND ARE ALSO USED FOR ABBREVIATIONS. / VEDERE

TAVOLA M-001 E M-002 PER LEGENDE, NOTE GENERALI E ABBREVIAZIONI.

2. PROVIDE ACCESS PANELS THROUGHOUT FOR ALL EQUIPMENT REQUIRING

MAINTENANCE. / FORNINE BOTOLE DI ACCESSO PER TUTTE LE

APPARECCHIATURE CHE RICHIEDONO MANUTENZIONE.

3. THE GROUND FLOOR OF APARTMENT BUILDING 29100 IS SHOWN HERE. SEE

SHEET M-101 FOR MIRROR IMAGE OF GROUND FLOOR. SEE SHEET M-132 FOR

FIRST FLOOR. SEE SHEET M-103 FOR MIRROR IMAGE OF SECOND FLOOR. SEE

SHEET AS001 FOR CORRECT ORIENTATION. / QUI VIENE MOSTRATO IL TERZO

PIANO DEL CONDOMINIO 29100. VEDERE IL FOGLIO M-101 PER UN’IMMAGINE

SPECULARE DEL PIANO TERRA. VEDERE IL FOGLIO M-132 PER IL PRIMO PIANO.

VEDERE IL FOGLIO M-103 PER UN’IMMAGINE SPECULARE DEL SECONDO PIANO.

VEDERE IL FOGLIO AS001 PER L’ORIENTAMENTO CORRETTO

SCALE 1 : 100

A2

AP BUILDING 29100 PENTHOUSE MECHANICAL PLAN /

IMPIANTI MECCANICI AP EDIFICIO 29100 PIANO ATTICO

SHEET KEYNOTES

23.256 HEAT PUMP LOCATION DIFFERS FOR THIS BUILDING COMPARED TO

TYPICAL BUILDING LAYOUT TO MAINTAIN REQUIRED CLEARANCE FROM PV

PANELS. / LA POSIZIONE DELLA POMPA DI CALORE DI QUESTO EDIFICIO E'

DIVERSA RISPETTO AL LAYOUT TIPICO DELL'EDIFICIO PER MANTENERE LA

DISTANZA RICHIESTA DAI PANNELLI FV

A B

C D E

F G

H J

EF-1 EF-1

GARAGE

GARAGE

STAIR

CORRIDOR

ELEVATOR

MECHANICAL

ELECTRICAL

COMMUNICATION

23.2223.22

A1

MH445

A2

MH446

T

A1

MP445

C1

MP445

EF-4

T

23.62

23.24

23.65

23.65

T

SPRINKLER

FCH-1

20 HWR

20 HWS

23.270

23.11

T

KEYPLAN / PIANO STRATEGICO

NAPOLI

PADOVA

BOLOGNA

= BLDG LOCATIONS

= SIMILAR BLDGS

PLAN

NORTH

1:100

0 1 32 4 5 10

SCALE:

D A T E

GRAPHIC SCALE

SCALA GRAFICA

NORTH

NORD

A

B

C

D

A/E INFO

SEAL

DES DRW CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

D E P A R T M E N T

O F

T H E

N A V Y

N A V A L

F A C

IL

IT

IE

S

E N G

IN

E E R

IN

G

C O M M A N D

N O R

FO

LK

VA

VI

LL

AG

G

IO

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

A

T L A

N T

IC

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DRAWFORM REVISION: 25 AUGUST 2020

OF

EPROJECT NO.:

1 2 3 4 5

A

B

C

D

1 2 3 4 5

A P P R

D E S C R

IP

T

IO

N

S Y M

H

AM

P

TO

N

B

LV

D

VI

C E N Z A, IT

AL

Y

AECOM

10 S. Jefferson Street, Suite 1600

Roanoke, VA 24011

540.857.3100 tel

540.857.3180 fax

P -9

A R

M Y

F A

M

IL

Y H

O U

S

IN

G P

R O

JE

DER

R. STEPHENS, PE

DPS

P L O T T E D

F

IL

E

P A T H

A U T H O R

Approved by Michele Millers, AFH-C Program Manager, USAG Italy, via email

6 OCT 2021

:2 :5

P M

B

IM

B P A M E R

V ic e n z a p h a s e

II

I_ A F H P A P M e n v e lo p e .r v t

MWM BVMWM

A P

B U

IL

D

IN

G

G

R O

U N

D F

L O

O R

M E

C H

A N

IC

A

L P

L A

N

IM

P

IA

N

T I M

E C

C A

N

IC

I A

P E

D

IF

IC

IO

P

IA

N O

T E

R R

A

M-141

14106749

1656273

M W M

NOTE CHIAVE DELLA TAVOLA:

SHEET KEYNOTES /

23.11 PROVIDE FCU CABINET HEATER. SEE EQUIPMENT SCHEDULES ON SHEET

M-601. / FORNIRE VENTILCONVETTORE. VEDERE ABACO APPARECCHIATURE

TAVOLA M-601.

23.22 PROVIDE WALL MOUNTED GARAGE EXHAUST FAN. PROVIDE WITH RAIN

HOOD, BACKDRAFT DAMPER, AND INSECT SCREEN. SEE EQUIPMENT

SCHEDULE ON SHEET M-601. / FORNIRE UN ESTRATTORE GARAGE

MONTATO A PARETE. FORNIRE CAPPA ANTIPIOGGIA, VALVOLA DI NON

RITORNO E RETE ANTI INSETTI. VEDERE ABACO APPARECCHIATURE

TAVOLA M-601.

23.24 PROVIDE THERMOSTAT, TYP. / FORNIRE TERMOSTATO, TIPO.

23.62 PROVIDE WALL MOUNTED EXHAUST FAN FOR COMMUNICATION ROOM.

PROVIDE WITH RAIN HOOD, BACKDRAFT DAMPER, AND INSECT SCREEN.

SEE EQUIPMENT SCHEDULE ON SHEET M-601. / FORNIRE UN ESTRATTORE

MONTATO A PARETE PER LA SALA DI COMUNICAZIONE. FORNIRE CAPPA

ANTIPIOGGIA, VALVOLA DI NON RITORNO E RETE ANTINSETTI. VEDERE

ABACO ATTREZZATURE TAVOLA M-601.

23.65 PROVIDE GRILLES FOR NATURAL VENTILATION IN TECHNICAL ROOMS

(MECHANICAL, COMMUNICATIONS AND ELECTRICAL ROOMS) AND FOR THE

ELEVATOR SHAFT. SEE SHEET A-607 AND A-608 FOR DETAILS. / FORNIRE

GRIGLIE VENTILAZIONE NATURALE NEI LOCALI TECNICI (LOCALI MECCANICI,

DI COMUNICAZIONE ED ELETTRICI) E PER IL VANO ASCENSORE. VEDERE

TAVOLA A-607 A A-608 PER I DETTAGLI.

23.270 ROUTE HEATING HOT WATER PIPING INSIDE INSULATED BULKHEAD TO

SPRINKLER ROOM. / PERCORSO TUBAZIONI ACQUA CALDA ALL'INTERNO DI

ELEMENTI ISOLATI AL LOCALE DEGLI SPRINKLER.

GENERAL NOTES/

NOTE GENERALI DI QUESTO FOGLIO:

1. SEE SHEET M-001 AND M-002 FOR ABBREVIATIONS, CHARACTER IDENTIFIERS

IN LINES ON PIPING LEGEND ARE ALSO USED FOR ABBREVIATIONS. / VEDERE

TAVOLA M-001 E M-002 PER LEGENDE, NOTE GENERALI E ABBREVIAZIONI.

2. PROVIDE ACCESS PANELS THROUGHOUT FOR ALL EQUIPMENT REQUIRING

MAINTENANCE. / FORNINE BOTOLE DI ACCESSO PER TUTTE LE

APPARECCHIATURE CHE RICHIEDONO MANUTENZIONE.

3. THE GROUND FLOOR OF APARTMENT BUILDING 29200 IS SHOWN HERE. FOR

ALL OTHER FLOORS SEE SHEETS M-122, M-123 AND M-124. SEE SHEET AS001

FOR CORRECT ORIENTATION. / QUI VIENE MOSTRATO IL PIANO TERRA DEL

CONDOMINIO 29200. PER TUTTI GLI ALTRI PIANI VEDERE I FOGLI M-122, M-123 E

M-124. VEDERE IL FOGLIO AS001 PER L’ORIENTAMENTO CORRETTO.

SCALE 1 : 100

A1

AP BUILDING 29200 GROUND FLOOR MECHANICAL PLAN /

IMPIANTI MECCANICI AP EDIFICIO 29200 PIANO TERRA

1 2 3 4 5

6 7 8

A

B

C

D

E

F

G

H

J

K

M

N

L

P

Q

R

S

T

U V W X

Y

Z

AA

BB

CC

HP-6

HP-6

HP-6

HP-5

HP-5

HP-5

HP-7

HP-5

C1

MH431

A1

MH432

23.40

23.40

23.40

23.40

23.40

23.40

23.40

23.40

23.08

R E

FER

TO

C

M -155

23.58

23.58

23.58

23.58

A1

MP432

A1

MP431

23.268

KEYPLAN / PIANO STRATEGICO

NAPOLI

PADOVA

BOLOGNA

= BLDG LOCATIONS

= SIMILAR BLDGS

PLAN

NORTH

1:100

0 1 32 4 5 10

SCALE:

D A T E

GRAPHIC SCALE

SCALA GRAFICA

NORTH

NORD

A

B

C

D

A/E INFO

SEAL

DES DRW CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

D E P A R T M E N T

O F

T H E

N A V Y

N A V A L

F A C

IL

IT

IE

S

E N G

IN

E E R

IN

G

C O M M A N D

N O R

FO

LK

VA

VI

LL

AG

G

IO

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

A

T L A

N T

IC

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DRAWFORM REVISION: 25 AUGUST 2020

OF

EPROJECT NO.:

1 2 3 4 5

A

B

C

D

1 2 3 4 5

A P P R

D E S C R

IP

T

IO

N

S Y M

H

AM

P

TO

N

B

LV

D

VI

C E N Z A, IT

AL

Y

AECOM

10 S. Jefferson Street, Suite 1600

Roanoke, VA 24011

540.857.3100 tel

540.857.3180 fax

P -9

A R

M Y

F A

M

IL

Y H

O U

S

IN

G P

R O

JE

DER

R. STEPHENS, PE

DPS

P L O T T E D

F

IL

E

P A T H

A U T H O R

Approved by Michele Millers, AFH-C Program Manager, USAG Italy, via email

6 OCT 2021

:3 :3

P M

B

IM

B P A M E R

V ic e n z a p h a s e

II

I_ A F H P T H M e n v e lo p e .r v t

MWM BVMWM

T H

B L D

G

A

R E

A A

G R

O U

N D

F L O

O R

M E

C H

A N

IC

A

L P

L A

N

IM

P

IA

N

T I M

E C

C A

N

IC

I T

H E

D

A

R E

A A

P

IA

N O

T E

R R

A

M-151

14106750

1656273

M W M

GENERAL NOTES/

NOTE GENERALI DI QUESTO FOGLIO:

1. SEE SHEET M-001 AND M-002 FOR ABBREVIATIONS, CHARACTER IDENTIFIERS

IN LINES ON PIPING LEGEND ARE ALSO USED FOR ABBREVIATIONS. / VEDERE

TAVOLA M-001 E M-002 PER LEGENDE, NOTE GENERALI E ABBREVIAZIONI.

2. PROVIDE ACCESS PANELS THROUGHOUT FOR ALL EQUIPMENT REQUIRING

MAINTENANCE. / FORNINE BOTOLE DI ACCESSO PER TUTTE LE

APPARECCHIATURE CHE RICHIEDONO MANUTENZIONE.

SHEET KEYNOTES/

NOTE CHIAVE DELLA TAVOLA:

23.08 PROVIDE HEAT PUMP. LOCATION APPROXIMATE, TYP. / FORNIRE POMPA DI

CALORE. POSIZIONE APPROSSIMATIVA, TIPOLOGICO.

23.40 PROVIDE REFRIGERANT LIQUID AND REFRIGERANT SUCTION PIPING BACK

TO OUTDOOR HEAT PUMP SIZED PER MANUFACTURERS

RECOMMENDATIONS. ROUTE PIPING ALONG TOWNHOME PRIVACY FENCES

AS INDICATED ON LANDSCAPE DRAWINGS. / FORNIRE IL FLUIDO

REFRIGERANTE E LE TUBAZIONI DA E PER LA POMPA DI CALORE ESTERNA

DIMENSIONATI SECONDO LE RACCOMANDAZIONI DEL PRODUTTORE.

INSTALLARE LE TUBAZIONI LUNGO LA RECINZIONE DELLA TOWNHOME

COME INDICATO NEI DISEGNI PAESAGGISTICI.

23.58 PROVIDE REFRIGERANT LIQUID AND REFRIGERANT SUCTION PIPING BACK

TO OUTDOOR HEAT PUMP SIZED PER MANUFACTURERS

RECOMMENDATIONS. ROUTE PIPING ALONG THE WALL OF THE ADJOINING

TOWNHOUSE FAÇADE AS INDICATED ON LANDSCAPE DRAWINGS. / FORNIRE

IL FLUIDO REFRIGERANTE E LE TUBAZIONI DA E PER LA POMPA DI CALORE

ESTERNA DIMENSIONATI SECONDO LE RACCOMANDAZIONI DEL

PRODUTTORE. INSTALLARE LE TUBAZIONI LUNGO LA RECINZIONE DELLA

TOWNHOME COME INDICATO NEI DISEGNI PAESAGGISTICI.

23.268 PROVIDE WITH EQUIPMENT PAD. SEE DETAIL D3/M-501. TYPICAL / FORNIRE

IL BLOCCO PER LE ATTREZZATURE. VEDI DETTAGLIO D3/M-501. TIPICA

SCALE 1 : 100

A1

TH BLDG 27500 AREA A GROUND FLOOR MECHANICAL PLAN /

IMPIANTI MECCANICI TH ED. 27500 AREA A PIANO TERRA

GG HH JJ KK LL MM NN QQ RR SS TT UU VV WW XX YY

HP-7 HP-7

HP-7HP-7

HP-7HP-7

23.40

23.40

23.40

23.40

23.08

23.40

23.40

23.58

23.268

Z AA BB CC DD EE FF GG

HP-7

HP-7 HP-7

23.40

23.40

23.40

23.08

A1

MH433

R

E F

E R

T O

A

M -1

23.58

A1

MP433

23.268

KEYPLAN / PIANO STRATEGICO

NAPOLI

PADOVA

BOLOGNA

= BLDG LOCATIONS

= SIMILAR BLDGS

PLAN

NORTH

1:100

0 1 32 4 5 10

SCALE:

D A T E

GRAPHIC SCALE

SCALA GRAFICA

NORTH

NORD

A

B

C

D

A/E INFO

SEAL

DES DRW CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

D E P A R T M E N T

O F

T H E

N A V Y

N A V A L

F A C

IL

IT

IE

S

E N G

IN

E E R

IN

G

C O M M A N D

N O R

FO

LK

VA

VI

LL

AG

G

IO

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

A

T L A

N T

IC

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DRAWFORM REVISION: 25 AUGUST 2020

OF

EPROJECT NO.:

1 2 3 4 5

A

B

C

D

1 2 3 4 5

A P P R

D E S C R

IP

T

IO

N

S Y M

H

AM

P

TO

N

B

LV

D

VI

C E N Z A, IT

AL

Y

AECOM

10 S. Jefferson Street, Suite 1600

Roanoke, VA 24011

540.857.3100 tel

540.857.3180 fax

P -9

A R

M Y

F A

M

IL

Y H

O U

S

IN

G P

R O

JE

DER

R. STEPHENS, PE

DPS

P L O T T E D

F

IL

E

P A T H

A U T H O R

Approved by Michele Millers, AFH-C Program Manager, USAG Italy, via email

6 OCT 2021

:3 :4

P M

B

IM

B P A M E R

V ic e n z a p h a s e

II

I_ A F H P T H M e n v e lo p e .r v t

MWM BVMWM

T H

B L D

G

A

R E

A B

G R

O U

N D

F L O

O R

M E

C H

A N

IC

A

L P

L A

N

IM

P

IA

N

T I M

E C

C A

N

IC

I T

H E

D

A R

E A

B P

IA

N

O T

E R

R A

M-155

14106751

1656273

M W M

GENERAL NOTES/

NOTE GENERALI DI QUESTO FOGLIO:

1. SEE SHEET M-001 AND M-002 FOR ABBREVIATIONS, CHARACTER IDENTIFIERS

IN LINES ON PIPING LEGEND ARE ALSO USED FOR ABBREVIATIONS. / VEDERE

TAVOLA M-001 E M-002 PER LEGENDE, NOTE GENERALI E ABBREVIAZIONI.

2. PROVIDE ACCESS PANELS THROUGHOUT FOR ALL EQUIPMENT REQUIRING

MAINTENANCE. / FORNINE BOTOLE DI ACCESSO PER TUTTE LE

APPARECCHIATURE CHE RICHIEDONO MANUTENZIONE.

SHEET KEYNOTES/

NOTE CHIAVE DELLA TAVOLA:

23.08 PROVIDE HEAT PUMP. LOCATION APPROXIMATE, TYP. / FORNIRE POMPA DI

CALORE. POSIZIONE APPROSSIMATIVA, TIPOLOGICO.

23.40 PROVIDE REFRIGERANT LIQUID AND REFRIGERANT SUCTION PIPING BACK

TO OUTDOOR HEAT PUMP SIZED PER MANUFACTURERS

RECOMMENDATIONS. ROUTE PIPING ALONG TOWNHOME PRIVACY FENCES

AS INDICATED ON LANDSCAPE DRAWINGS. / FORNIRE IL FLUIDO

REFRIGERANTE E LE TUBAZIONI DA E PER LA POMPA DI CALORE ESTERNA

DIMENSIONATI SECONDO LE RACCOMANDAZIONI DEL PRODUTTORE.

INSTALLARE LE TUBAZIONI LUNGO LA RECINZIONE DELLA TOWNHOME

COME INDICATO NEI DISEGNI PAESAGGISTICI.

23.58 PROVIDE REFRIGERANT LIQUID AND REFRIGERANT SUCTION PIPING BACK

TO OUTDOOR HEAT PUMP SIZED PER MANUFACTURERS

RECOMMENDATIONS. ROUTE PIPING ALONG THE WALL OF THE ADJOINING

TOWNHOUSE FAÇADE AS INDICATED ON LANDSCAPE DRAWINGS. / FORNIRE

IL FLUIDO REFRIGERANTE E LE TUBAZIONI DA E PER LA POMPA DI CALORE

ESTERNA DIMENSIONATI SECONDO LE RACCOMANDAZIONI DEL

PRODUTTORE. INSTALLARE LE TUBAZIONI LUNGO LA RECINZIONE DELLA

TOWNHOME COME INDICATO NEI DISEGNI PAESAGGISTICI.

23.268 PROVIDE WITH EQUIPMENT PAD. SEE DETAIL D3/M-501. TYPICAL / FORNIRE

IL BLOCCO PER LE ATTREZZATURE. VEDI DETTAGLIO D3/M-501. TIPICA

SCALE 1 : 100

A1

TH BLDG 27500 AREA C GROUND FLOOR MECHANICAL PLAN /

IMPIANTI MECCANICI TH ED. 27500 AREA C PIANO TERRA

SCALE 1 : 100

C2

TH BLDG 27500 AREA B GROUND FLOOR MECHANICAL PLAN /

IMPIANTI MECCANICI TH ED. 27500 AREA B PIANO TERRA

2523 2421 22

Z

41A

A

181716

T

V

U

Y

X

W

M

P

N

12 S

R

Q

L

K

J

BCE

H F

D

G

AA

BB

CC

DD

19 20

HP-6

HP-6

HP-5

HP-5

HP-5

HP-6

HP-6 HP-6

23.40

23.08

23.40

23.40

23.40

23.40

23.4023.40

A1

MH432

C1

MH431

A1

MP432

A1

MP431 23.58

23.58

23.58

23.40

23.268

KEYPLAN / PIANO STRATEGICO

NAPOLI

PADOVA

BOLOGNA

= BLDG LOCATIONS

= SIMILAR BLDGS

PLAN

NORTH

1:100

0 1 32 4 5 10

SCALE:

D A T E

GRAPHIC SCALE

SCALA GRAFICA

NORTH

NORD

A

B

C

D

A/E INFO

SEAL

DES DRW CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

D E P A R T M E N T

O F

T H E

N A V Y

N A V A L

F A C

IL

IT

IE

S

E N G

IN

E E R

IN

G

C O M M A N D

N O R

FO

LK

VA

VI

LL

AG

G

IO

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

A

T L A

N T

IC

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DRAWFORM REVISION: 25 AUGUST 2020

OF

EPROJECT NO.:

1 2 3 4 5

A

B

C

D

1 2 3 4 5

A P P R

D E S C R

IP

T

IO

N

S Y M

H

AM

P

TO

N

B

LV

D

VI

C E N Z A, IT

AL

Y

AECOM

10 S. Jefferson Street, Suite 1600

Roanoke, VA 24011

540.857.3100 tel

540.857.3180 fax

P -9

A R

M Y

F A

M

IL

Y H

O U

S

IN

G P

R O

JE

DER

R. STEPHENS, PE

DPS

P L O T T E D

F

IL

E

P A T H

A U T H O R

Approved by Michele Millers, AFH-C Program Manager, USAG Italy, via email

6 OCT 2021

:4 :2

P M

B

IM

B P A M E R

V ic e n z a p h a s e

II

I_ A F H P T H M e n v e lo p e .r v t

MWM BVMWM

T H

B U

IL

D

IN

G

G R

O U

N D

F L O

O R

M E

C H

A N

IC

A

L P

L A

N

IM

P

IA

N

T I M

E C

C A

N

IC

I T

H E

D

IF

IC

IO

P

IA

N O

T E

R R

A

M-161

14106752

1656273

M W M

SHEET KEYNOTES/

NOTE CHIAVE DELLA TAVOLA:

23.08 PROVIDE HEAT PUMP. LOCATION APPROXIMATE, TYP. / FORNIRE POMPA DI

CALORE. POSIZIONE APPROSSIMATIVA, TIPOLOGICO.

23.40 PROVIDE REFRIGERANT LIQUID AND REFRIGERANT SUCTION PIPING BACK

TO OUTDOOR HEAT PUMP SIZED PER MANUFACTURERS

RECOMMENDATIONS. ROUTE PIPING ALONG TOWNHOME PRIVACY FENCES

AS INDICATED ON LANDSCAPE DRAWINGS. / FORNIRE IL FLUIDO

REFRIGERANTE E LE TUBAZIONI DA E PER LA POMPA DI CALORE ESTERNA

DIMENSIONATI SECONDO LE RACCOMANDAZIONI DEL PRODUTTORE.

INSTALLARE LE TUBAZIONI LUNGO LA RECINZIONE DELLA TOWNHOME

COME INDICATO NEI DISEGNI PAESAGGISTICI.

23.58 PROVIDE REFRIGERANT LIQUID AND REFRIGERANT SUCTION PIPING BACK

TO OUTDOOR HEAT PUMP SIZED PER MANUFACTURERS

RECOMMENDATIONS. ROUTE PIPING ALONG THE WALL OF THE ADJOINING

TOWNHOUSE FAÇADE AS INDICATED ON LANDSCAPE DRAWINGS. / FORNIRE

IL FLUIDO REFRIGERANTE E LE TUBAZIONI DA E PER LA POMPA DI CALORE

ESTERNA DIMENSIONATI SECONDO LE RACCOMANDAZIONI DEL

PRODUTTORE. INSTALLARE LE TUBAZIONI LUNGO LA RECINZIONE DELLA

TOWNHOME COME INDICATO NEI DISEGNI PAESAGGISTICI.

23.268 PROVIDE WITH EQUIPMENT PAD. SEE DETAIL D3/M-501. TYPICAL / FORNIRE

IL BLOCCO PER LE ATTREZZATURE. VEDI DETTAGLIO D3/M-501. TIPICA

GENERAL NOTES/

NOTE GENERALI DI QUESTO FOGLIO:

1. SEE SHEET M-001 AND M-002 FOR ABBREVIATIONS, CHARACTER IDENTIFIERS

IN LINES ON PIPING LEGEND ARE ALSO USED FOR ABBREVIATIONS. /

VEDERE TAVOLA M-001 E M-002 PER LE LEGENDE, NOTE GENERALI E

ABBREVIAZIONI.

2. PROVIDE ACCESS PANELS THROUGHOUT FOR ALL EQUIPMENT REQUIRING

MAINTENANCE. / FORNIRE BOTOLE DI ACCESSO PER TUTTE LE

APPARECCHIATURE CHE RICHIEDONO MANUTENZIONE.

SCALE 1 : 100

A1

TH BUILDING 28100 GROUND FLOOR MECHANICAL PLAN /

IMPIANTI MECCANICI TH EDIFICIO 28100 PIANO TERRA

D

E

C

B

765 8421

A

HP-6 HP-6

HP-6 HP-6

A1

MH432

23.4023.40

23.08

23.40 23.40

A1

MP432

23.268

KEYPLAN / PIANO STRATEGICO

NAPOLI

PADOVA

BOLOGNA

= BLDG LOCATIONS

= SIMILAR BLDGS

PLAN

NORTH

1:100

0 1 32 4 5 10

SCALE:

D A T E

GRAPHIC SCALE

SCALA GRAFICA

NORTH

NORD

A

B

C

D

A/E INFO

SEAL

DES DRW CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

D E P A R T M E N T

O F

T H E

N A V Y

N A V A L

F A C

IL

IT

IE

S

E N G

IN

E E R

IN

G

C O M M A N D

N O R

FO

LK

VA

VI

LL

AG

G

IO

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

A

T L A

N T

IC

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DRAWFORM REVISION: 25 AUGUST 2020

OF

EPROJECT NO.:

1 2 3 4 5

A

B

C

D

1 2 3 4 5

A P P R

D E S C R

IP

T

IO

N

S Y M

H

AM

P

TO

N

B

LV

D

VI

C E N Z A, IT

AL

Y

AECOM

10 S. Jefferson Street, Suite 1600

Roanoke, VA 24011

540.857.3100 tel

540.857.3180 fax

P -9

A R

M Y

F A

M

IL

Y H

O U

S

IN

G P

R O

JE

DER

R. STEPHENS, PE

DPS

P L O T T E D

F

IL

E

P A T H

A U T H O R

Approved by Michele Millers, AFH-C Program Manager, USAG Italy, via email

6 OCT 2021

:5 :1

P M

B

IM

B P A M E R

V ic e n z a p h a s e

II

I_ A F H P T H M e n v e lo p e .r v t

MWM BVMWM

T H

B U

IL

D

IN

G

G R

O U

N D

F L O

O R

M E

C H

A N

IC

A

L P

L A

N

IM

P

IA

N

T I M

E C

C A

N

IC

I T

H E

D

IF

IC

IO

P

IA

N O

T E

R R

A

M-171

14106753

1656273

M W M

SHEET KEYNOTES/

NOTE CHIAVE DELLA TAVOLA:

23.08 PROVIDE HEAT PUMP. LOCATION APPROXIMATE, TYP. / FORNIRE POMPA DI

CALORE. POSIZIONE APPROSSIMATIVA, TIPOLOGICO.

23.40 PROVIDE REFRIGERANT LIQUID AND REFRIGERANT SUCTION PIPING BACK

TO OUTDOOR HEAT PUMP SIZED PER MANUFACTURERS

RECOMMENDATIONS. ROUTE PIPING ALONG TOWNHOME PRIVACY FENCES

AS INDICATED ON LANDSCAPE DRAWINGS. / FORNIRE IL FLUIDO

REFRIGERANTE E LE TUBAZIONI DA E PER LA POMPA DI CALORE ESTERNA

DIMENSIONATI SECONDO LE RACCOMANDAZIONI DEL PRODUTTORE.

INSTALLARE LE TUBAZIONI LUNGO LA RECINZIONE DELLA TOWNHOME

COME INDICATO NEI DISEGNI PAESAGGISTICI.

23.268 PROVIDE WITH EQUIPMENT PAD. SEE DETAIL D3/M-501. TYPICAL / FORNIRE

IL BLOCCO PER LE ATTREZZATURE. VEDI DETTAGLIO D3/M-501. TIPICA

GENERAL NOTES/

NOTE GENERALI DI QUESTO FOGLIO:

1. SEE SHEET M-001 AND M-002 FOR ABBREVIATIONS, CHARACTER IDENTIFIERS

IN LINES ON PIPING LEGEND ARE ALSO USED FOR ABBREVIATIONS. / VEDERE

TAVOLA M-001 E M-002 PER LEGENDE, NOTE GENERALI E ABBREVIAZIONI.

2. PROVIDE ACCESS PANELS THROUGHOUT FOR ALL EQUIPMENT REQUIRING

MAINTENANCE. / FORNINE BOTOLE DI ACCESSO PER TUTTE LE

APPARECCHIATURE CHE RICHIEDONO MANUTENZIONE.

SCALE 1 : 100

A2

TH BUILDING 28300 GROUND FLOOR MECHANICAL PLAN /

IMPIANTI MECCANICI TH EDIFICIO 28300 PIANO TERRA

A

B

C

D

E

F

G

H

76 8

J

K

L

M

N

13 16

P

Q

R

S

T U

V W X Y Z

AA

HP-6

HP-6

HP-5

HP-5

HP-5

HP-6HP-6

A1

MH432

C1

MH431

23.40

23.40

23.40

23.58

23.40

23.40

23.08

23.40 23.40

R

E F

E R

T O

A

M -1

A1

MP431

A1

MP432

23.58

23.58

HP-6

23.268 KEYPLAN / PIANO STRATEGICO

NAPOLI

PADOVA

BOLOGNA

= BLDG LOCATIONS

= SIMILAR BLDGS

PLAN

NORTH

1:100

0 1 32 4 5 10

SCALE:

D A T E

GRAPHIC SCALE

SCALA GRAFICA

NORTH

NORD

A

B

C

D

A/E INFO

SEAL

DES DRW CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

D E P A R T M E N T

O F

T H E

N A V Y

N A V A L

F A C

IL

IT

IE

S

E N G

IN

E E R

IN

G

C O M M A N D

N O R

FO

LK

VA

VI

LL

AG

G

IO

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

A

T L A

N T

IC

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DRAWFORM REVISION: 25 AUGUST 2020

OF

EPROJECT NO.:

1 2 3 4 5

A

B

C

D

1 2 3 4 5

A P P R

D E S C R

IP

T

IO

N

S Y M

H

AM

P

TO

N

B

LV

D

VI

C E N Z A, IT

AL

Y

AECOM

10 S. Jefferson Street, Suite 1600

Roanoke, VA 24011

540.857.3100 tel

540.857.3180 fax

P -9

A R

M Y

F A

M

IL

Y H

O U

S

IN

G P

R O

JE

DER

R. STEPHENS, PE

DPS

P L O T T E D

F

IL

E

P A T H

A U T H O R

Approved by Michele Millers, AFH-C Program Manager, USAG Italy, via email

6 OCT 2021

:5 :3

P M

B

IM

B P A M E R

V ic e n z a p h a s e

II

I_ A F H P T H M e n v e lo p e .r v t

MWM BVMWM

T H

B L D

G

A

R E

A A

G R

O U

N D

F L O

O R

M E

C H

A N

IC

A

L P

L A

N

IM

P

IA

N

T I M

E C

C A

N

IC

I T

H E

D

A

R E

A A

P

IA

N O

T E

R R

A

M-181

14106754

1656273

M W M

SHEET KEYNOTES/

NOTE CHIAVE DELLA TAVOLA:

23.08 PROVIDE HEAT PUMP. LOCATION APPROXIMATE, TYP. / FORNIRE POMPA DI

CALORE. POSIZIONE APPROSSIMATIVA, TIPOLOGICO.

23.40 PROVIDE REFRIGERANT LIQUID AND REFRIGERANT SUCTION PIPING BACK

TO OUTDOOR HEAT PUMP SIZED PER MANUFACTURERS

RECOMMENDATIONS. ROUTE PIPING ALONG TOWNHOME PRIVACY FENCES

AS INDICATED ON LANDSCAPE DRAWINGS. / FORNIRE IL FLUIDO

REFRIGERANTE E LE TUBAZIONI DA E PER LA POMPA DI CALORE ESTERNA

DIMENSIONATI SECONDO LE RACCOMANDAZIONI DEL PRODUTTORE.

INSTALLARE LE TUBAZIONI LUNGO LA RECINZIONE DELLA TOWNHOME

COME INDICATO NEI DISEGNI PAESAGGISTICI.

23.58 PROVIDE REFRIGERANT LIQUID AND REFRIGERANT SUCTION PIPING BACK

TO OUTDOOR HEAT PUMP SIZED PER MANUFACTURERS

RECOMMENDATIONS. ROUTE PIPING ALONG THE WALL OF THE ADJOINING

TOWNHOUSE FAÇADE AS INDICATED ON LANDSCAPE DRAWINGS. / FORNIRE

IL FLUIDO REFRIGERANTE E LE TUBAZIONI DA E PER LA POMPA DI CALORE

ESTERNA DIMENSIONATI SECONDO LE RACCOMANDAZIONI DEL

PRODUTTORE. INSTALLARE LE TUBAZIONI LUNGO LA RECINZIONE DELLA

TOWNHOME COME INDICATO NEI DISEGNI PAESAGGISTICI.

23.268 PROVIDE WITH EQUIPMENT PAD. SEE DETAIL D3/M-501. TYPICAL / FORNIRE

IL BLOCCO PER LE ATTREZZATURE. VEDI DETTAGLIO D3/M-501. TIPICA

GENERAL NOTES/

NOTE GENERALI DI QUESTO FOGLIO:

1. SEE SHEET M-001 AND M-002 FOR ABBREVIATIONS, CHARACTER IDENTIFIERS

IN LINES ON PIPING LEGEND ARE ALSO USED FOR ABBREVIATIONS. / VEDERE

TAVOLA M-001 E M-002 PER LEGENDE, NOTE GENERALI E ABBREVIAZIONI.

2. PROVIDE ACCESS PANELS THROUGHOUT FOR ALL EQUIPMENT REQUIRING

MAINTENANCE. / FORNINE BOTOLE DI ACCESSO PER TUTTE LE

APPARECCHIATURE CHE RICHIEDONO MANUTENZIONE.

SCALE 1 : 100

A1

TH BLDG 29400 AREA A GROUND FLOOR MECHANICAL PLAN /

IMPIANTI MECCANICI TH ED. 29400 AREA A PIANO TERRA

AA BB CC DD EE FF GG HH

KK

LL

MM

NN

PP

QQ

RR

SS

TT

UU

VV

WW

HP-6HP-6

HP-6

HP-5

HP-5

HP-6

HP-6

A1

MH432

C1

MH431

23.40 23.40

23.08

23.40

23.40

23.08

23.40

23.40

23.40

R

E F

E R

T O

A

M -1

A1

MP432

A1

MP431

23.58

23.58

23.268

KEYPLAN / PIANO STRATEGICO

NAPOLI

PADOVA

BOLOGNA

= BLDG LOCATIONS

= SIMILAR BLDGS

PLAN

NORTH

1:100

0 1 32 4 5 10

SCALE:

D A T E

GRAPHIC SCALE

SCALA GRAFICA

NORTH

NORD

A

B

C

D

A/E INFO

SEAL

DES DRW CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

D E P A R T M E N T

O F

T H E

N A V Y

N A V A L

F A C

IL

IT

IE

S

E N G

IN

E E R

IN

G

C O M M A N D

N O R

FO

LK

VA

VI

LL

AG

G

IO

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

A

T L A

N T

IC

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DRAWFORM REVISION: 25 AUGUST 2020

OF

EPROJECT NO.:

1 2 3 4 5

A

B

C

D

1 2 3 4 5

A P P R

D E S C R

IP

T

IO

N

S Y M

H

AM

P

TO

N

B

LV

D

VI

C E N Z A, IT

AL

Y

AECOM

10 S. Jefferson Street, Suite 1600

Roanoke, VA 24011

540.857.3100 tel

540.857.3180 fax

P -9

A R

M Y

F A

M

IL

Y H

O U

S

IN

G P

R O

JE

DER

R. STEPHENS, PE

DPS

P L O T T E D

F

IL

E

P A T H

A U T H O R

Approved by Michele Millers, AFH-C Program Manager, USAG Italy, via email

6 OCT 2021

:5 :3

P M

B

IM

B P A M E R

V ic e n z a p h a s e

II

I_ A F H P T H M e n v e lo p e .r v t

MWM BVMWM

T H

B L D

G

A

R E

A B

G R

O U

N D

F L O

O R

M E

C H

A N

IC

A

L P

L A

N

IM

P

IA

N

T I M

E C

C A

N

IC

I T

H E

D

A R

E A

B P

IA

N

O T

E R

R A

M-185

14106755

1656273

M W M

SCALE 1 : 100

A1

TH BLDG 29400 AREA B GROUND FLOOR MECHANICAL PLAN /

IMPIANTI MECCANICI TH ED. 29400 AREA B PIANO TERRA

SHEET KEYNOTES/

NOTE CHIAVE DELLA TAVOLA:

23.08 PROVIDE HEAT PUMP. LOCATION APPROXIMATE, TYP. / FORNIRE POMPA DI

CALORE. POSIZIONE APPROSSIMATIVA, TIPOLOGICO.

23.40 PROVIDE REFRIGERANT LIQUID AND REFRIGERANT SUCTION PIPING BACK

TO OUTDOOR HEAT PUMP SIZED PER MANUFACTURERS

RECOMMENDATIONS. ROUTE PIPING ALONG TOWNHOME PRIVACY FENCES

AS INDICATED ON LANDSCAPE DRAWINGS. / FORNIRE IL FLUIDO

REFRIGERANTE E LE TUBAZIONI DA E PER LA POMPA DI CALORE ESTERNA

DIMENSIONATI SECONDO LE RACCOMANDAZIONI DEL PRODUTTORE.

INSTALLARE LE TUBAZIONI LUNGO LA RECINZIONE DELLA TOWNHOME

COME INDICATO NEI DISEGNI PAESAGGISTICI.

23.58 PROVIDE REFRIGERANT LIQUID AND REFRIGERANT SUCTION PIPING BACK

TO OUTDOOR HEAT PUMP SIZED PER MANUFACTURERS

RECOMMENDATIONS. ROUTE PIPING ALONG THE WALL OF THE ADJOINING

TOWNHOUSE FAÇADE AS INDICATED ON LANDSCAPE DRAWINGS. / FORNIRE

IL FLUIDO REFRIGERANTE E LE TUBAZIONI DA E PER LA POMPA DI CALORE

ESTERNA DIMENSIONATI SECONDO LE RACCOMANDAZIONI DEL

PRODUTTORE. INSTALLARE LE TUBAZIONI LUNGO LA RECINZIONE DELLA

TOWNHOME COME INDICATO NEI DISEGNI PAESAGGISTICI.

23.268 PROVIDE WITH EQUIPMENT PAD. SEE DETAIL D3/M-501. TYPICAL / FORNIRE

IL BLOCCO PER LE ATTREZZATURE. VEDI DETTAGLIO D3/M-501. TIPICA

GENERAL NOTES/

NOTE GENERALI DI QUESTO FOGLIO:

1. SEE SHEET M-001 AND M-002 FOR ABBREVIATIONS, CHARACTER IDENTIFIERS

IN LINES ON PIPING LEGEND ARE ALSO USED FOR ABBREVIATIONS. / VEDERE

TAVOLA M-001 E M-002 PER LEGENDE, NOTE GENERALI E ABBREVIAZIONI.

2. PROVIDE ACCESS PANELS THROUGHOUT FOR ALL EQUIPMENT REQUIRING

MAINTENANCE. / FORNINE BOTOLE DI ACCESSO PER TUTTE LE

APPARECCHIATURE CHE RICHIEDONO MANUTENZIONE.

1 2

B

A

EF-2

23.24

23.223

23.42

23.42

LV-1

LV-1

KEYPLAN / PIANO STRATEGICO

NAPOLI

PADOVA

BOLOGNA

= BLDG LOCATIONS

= SIMILAR BLDGS

PLAN

NORTH

0 421 3 5

SCALE: 1:50

D A T E

GRAPHIC SCALE

SCALA GRAFICA

NORTH

NORD

A

B

C

D

A/E INFO

SEAL

DES DRW CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

D E P A R T M E N T

O F

T H E

N A V Y

N A V A L

F A C

IL

IT

IE

S

E N G

IN

E E R

IN

G

C O M M A N D

N O R

FO

LK

VA

VI

LL

AG

G

IO

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

A

T L A

N T

IC

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DRAWFORM REVISION: 25 AUGUST 2020

OF

EPROJECT NO.:

1 2 3 4 5

A

B

C

D

1 2 3 4 5

A P P R

D E S C R

IP

T

IO

N

S Y M

H

AM

P

TO

N

B

LV

D

VI

C E N Z A, IT

AL

Y

AECOM

10 S. Jefferson Street, Suite 1600

Roanoke, VA 24011

540.857.3100 tel

540.857.3180 fax

P -9

A R

M Y

F A

M

IL

Y H

O U

S

IN

G P

R O

JE

DER

R. STEPHENS, PE

DPS

P L O T T E D

F

IL

E

P A T H

A U T H O R

Approved by Michele Millers, AFH-C Program Manager, USAG Italy, via email

6 OCT 2021

:5 :3

P M

B

IM

B P A M E R

V ic e n z a p h a s e

II

I_ A F H P V S M s u b s ta ti o n .r v t

MWM BVMWM

S U

B S

T A

T

IO

N M

E C

H A

N

IC

A L P

L A

N

IM

P

IA

N

T I M

E C

C A

N

IC

I S

O T

T O

S T

A Z

IO

N

E

M-190

14106756

1656273

M W M

NOTE CHIAVE DELLA TAVOLA:

SHEET KEYNOTES /

23.24 PROVIDE THERMOSTAT, TYP. / FORNIRE TERMOSTATO, TIPO.

23.42 PROVIDE WALL LOUVER / FORNIRE GRIGLIA A PARETE.

23.223 PROVIDE WALL MOUNTED EXHAUST FAN. PROVIDE WITH RAIN HOOD,

BACKDRAFT DAMPER, AND INSECT SCREEN. SEE EQUIPMENT SCHEDULE

ON SHEET M-601. / FORNIRE UN ESTRATTORE MONTATO A PARETE.

FORNIRE CAPPA ANTIPIOGGIA, VALVOLA DI NON RITORNO E RETE ANTI

INSETTI. VEDERE ABACO APPARECCHIATURE TAVOLA M-601.

GENERAL NOTES/

NOTE GENERALI DI QUESTO FOGLIO:

1. SEE SHEET M-001 AND M-002 FOR ABBREVIATIONS, CHARACTER IDENTIFIERS

IN LINES ON PIPING LEGEND ARE ALSO USED FOR ABBREVIATIONS. / VEDERE

TAVOLA M-001 E M-002 PER LEGENDE, NOTE GENERALI E ABBREVIAZIONI.

2. PROVIDE ACCESS PANELS THROUGHOUT FOR ALL EQUIPMENT REQUIRING

MAINTENANCE. / FORNINE BOTOLE DI ACCESSO PER TUTTE LE

APPARECCHIATURE CHE RICHIEDONO MANUTENZIONE.

SCALE 1 : 50

A1

SUBSTATION MECHANICAL PLAN /

IMPIANTI MECCANICI SOTTOSTAZIONE

M101 - GROUND FFL

0.000

M102 - FIRST FFL

3400.000

M103 - SECOND FFL

6800.000

M104 - THIRD FFL

10200.000

M105 - PENTHOUSE

13600.000

40 HWS

40 HWR

25 HWS

25 HWR

40 HWS

40 HWR

25 HWS

25 HWR

25 HWS

25 HWR

25 HWS

25 HWR

20 HWS

20 HWR

350x300

350x300

23.37

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

100ø

150ø

M101 - GROUND FFL

0.000

M102 - FIRST FFL

3400.000

M103 - SECOND FFL

6800.000

M104 - THIRD FFL

10200.000

M105 - PENTHOUSE

13600.000

GH

FCU-1

FCU-3

FCU-3

FCU-1

20 CD

20 CD

20 CD

20 CD

20 CD

20 CD

20 CD

20 CD

250ø

1050x200

1050x200

1050x200

250ø

23.60

23.60

23.60

23.60

23.26

23.13

23.13

P02

MACHINE

MECHANICAL

MECHANICAL

MECHANICAL

MECHANICAL

900x300

250x250 250x250

20 HWS

20 HWS

23.133

M102 - FIRST FFL

3400.000

8 9 10 11

FCU-3

20 CD

200x1050

350x250

300x900

350x300

HC-3

FD

23.26

23.16

23.0323.04

23.60

23.15

CORRIDOR

MECHANICAL

1:25

0 1.00.5

SCALE:

1.5 2.5

KEYPLAN / PIANO STRATEGICO

NAPOLI

PADOVA

BOLOGNA

= BLDG LOCATIONS

= SIMILAR BLDGS

0 421 3 5

SCALE: 1:50

D A T E

GRAPHIC SCALE

SCALA GRAFICA

A

B

C

D

A/E INFO

SEAL

DES DRW CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

D E P A R T M E N T

O F

T H E

N A V Y

N A V A L

F A C

IL

IT

IE

S

E N G

IN

E E R

IN

G

C O M M A N D

N O R

FO

LK

VA

VI

LL

AG

G

IO

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

A

T L A

N T

IC

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DRAWFORM REVISION: 25 AUGUST 2020

OF

EPROJECT NO.:

1 2 3 4 5

A

B

C

D

1 2 3 4 5

A P P R

D E S C R

IP

T

IO

N

S Y M

H

AM

P

TO

N

B

LV

D

VI

C E N Z A, IT

AL

Y

AECOM

10 S. Jefferson Street, Suite 1600

Roanoke, VA 24011

540.857.3100 tel

540.857.3180 fax

P -9

A R

M Y

F A

M

IL

Y H

O U

S

IN

G P

R O

JE

DER

R. STEPHENS, PE

DPS

P L O T T E D

F

IL

E

P A T H

A U T H O R

Approved by Michele Millers, AFH-C Program Manager, USAG Italy, via email

6 OCT 2021

:5 :2

A M

B

IM

B P A M E R

V ic e n z a p h a s e

II

I_ A F H P A P M e n v e lo p e .r v t

MWM BVMWM

A P

B U

IL

D

IN

G

M

E C

H A

N

IC

A L S

E C

T

IO

N S

A P

E D

IF

IC

IO

S

E Z

IO

N

I

IM

P

IA

N T

I M

E C

C A

N

IC

I

M-301

14106757

1656273

M W M

NOTE CHIAVE DELLA TAVOLA:

SHEET KEYNOTES /

23.03 PROVIDE SUPPLY AIR DUCTWORK, TYP. / FORNIRE CANALE ARIA DI

MANDATA, TIPO.

23.04 PROVIDE RETURN AIR DUCTWORK, TYP. / FORNIRE CANALE ARIA DI

RITORNO, TIPO.

23.13 PROVIDE FLUE GAS EXHAUST THROUGH ROOF FOR NATURAL GAS FIRED

BOILER. SEE DETAIL C3/M-502. PROVIDE WITH 2-HOUR FIRE RATED JACKET. /

FORNIRE LO SCARICO DEI FUMI IN COPERTURA PER LA CALDAIA A GAS

NATURALE. VEDI DETTAGLIO C3/M-502. PREVEDERE UN RIVESTIMENTO CON

RESISTENZA AL FUOCO DI 2 ORE.

23.15 PROVIDE FIRE DAMPER AT ALL FIRE RATED CONSTRUCTION. DAMPER

RATING MUST MATCH WALL OR FLOOR RATING, TYP. SEE DETAIL C3/M-503. /

FORNIRE UNA SERRANDA TAGLIAFUOCO IN TUTTI GLI ATTRAVERSI CON REI.

LA RESISTENZA AL FUOCO DELLA SERRANDA DEVE CORRISPONDERE A

QUELLA DELLA PARETE O DEL PAVIMENTO, TIPO. VEDI DETTAGLIO C3/M-503.

23.16 PROVIDE HEATING HOT WATER COIL, TYP. SEE DETAIL A1/M-503. / FORNIRE

SERPENTINA DI RISCALDAMENTO AD ACQUA CALDA, TIPO. VEDI DETTAGLIO

A1/M-503.

23.26 PROVIDE FAN COIL UNIT, TYP. SEE EQUIPMENT SCHEDULES ON SHEET

M-602 FOR DETAILS. / FORNIRE VENTILCONVETTORE, PER I DETTAGLI

VEDERE ABACO APPARECCHIATURE TAVOLA M-602.

23.37 PROVIDE HOT WATER SUPPLY AND RETURN PIPING FROM THE BOILER TO

EACH HEATING COIL. / FORNIRE ALIMENTAZIONE DI ACQUA CALDA E

TUBATURE DI RITORNO DALLA CALDAIA A CIASCUNA BATTERIA DI

RISCALDAMENTO.

23.60 PROVIDE CONDENSATE DRAIN PIPING. ROUTE TO MECHANICAL ROOM

FLOOR DRAIN. / FORNIRE TUBAZIONI PER LO SCARICO DELLA CONDENSA.

COLLEGARLE ALLOSCARICO A PAVIMENTO DEL LOCALE IMPIANTI

MECCANICI.

23.133 SEAL HOLE WITH FIREPROOFING MATERIAL AFTER DUCT INSTALLATION. /

PREVEDERE UN COLLARE PER IL RISPRISTINO REI DOPO L'INSTALLAZIONE

DEL CONDOTTO.

GENERAL NOTES/

NOTE GENERALI DI QUESTO FOGLIO:

1. SEE SHEET M-001 AND M-002 FOR ABBREVIATIONS, CHARACTER IDENTIFIERS

IN LINES ON PIPING LEGEND ARE ALSO USED FOR ABBREVIATIONS. / VEDERE

TAVOLA M-001 E M-002 PER LEGENDE, NOTE GENERALI E ABBREVIAZIONI.

2. PROVIDE ACCESS PANELS THROUGHOUT FOR ALL EQUIPMENT REQUIRING

MAINTENANCE. / FORNINE BOTOLE DI ACCESSO PER TUTTE LE

APPARECCHIATURE CHE RICHIEDONO MANUTENZIONE.

SCALE 1 : 50 (M-101)

A1

MECHANICAL SECTION /

SEZIONI IMPIANTI MECCANICI

SCALE 1 : 50 (M-101)

A2

MECHANICAL SECTION /

SEZIONI IMPIANTI MECCANICI

SCALE 1 : 25 (M-102)

A3

MECHANICAL SECTION FIRST FLOOR /

IMPIANTI MECCANICI SEZIONE PIANO PRIMO

M103 - SECOND FFL

6800.000

8 9 10 11

FCU-2 FCU-2

150ø 150ø

20 CD

20 CD 20 CD

RL

RS

RS

RL

RS

RL

RL

RS

23.26

23.60

23.206 (TYP)

23.26

MECHANICAL

M105 - PENTHOUSE

13600.000

EFG

HP-1 HP-2

RL

RS

RL

RS

RL

23.206(TYP)

23.28 23.28

DSS-1A

23.30

23.239 23.239

23.240

M105 - PENTHOUSE

13600.000

500x500

23.32

23.67

23.65

23.241

23.133

M104 - THIRD FFL

10200.000

8 9 10 11

FD

RL

RS

RL

RS RS

RL

RS

RL

20 CD

HC-4

450x300

150ø

300x400

FD

FCU-4

20 HWR

20 HWS

23.60

23.16

23.26

23.206 (TYP)

23.03 23.04

23.15

23.15

MECHANICAL

KEYPLAN / PIANO STRATEGICO

NAPOLI

PADOVA

BOLOGNA

= BLDG LOCATIONS

= SIMILAR BLDGS

1:25

0 1.00.5

SCALE:

1.5 2.5

D A T E

GRAPHIC SCALE

SCALA GRAFICA

A

B

C

D

A/E INFO

SEAL

DES DRW CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

D E P A R T M E N T

O F

T H E

N A V Y

N A V A L

F A C

IL

IT

IE

S

E N G

IN

E E R

IN

G

C O M M A N D

N O R

FO

LK

VA

VI

LL

AG

G

IO

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

A

T L A

N T

IC

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DRAWFORM REVISION: 25 AUGUST 2020

OF

EPROJECT NO.:

1 2 3 4 5

A

B

C

D

1 2 3 4 5

A P P R

D E S C R

IP

T

IO

N

S Y M

H

AM

P

TO

N

B

LV

D

VI

C E N Z A, IT

AL

Y

AECOM

10 S. Jefferson Street, Suite 1600

Roanoke, VA 24011

540.857.3100 tel

540.857.3180 fax

P-

AR

M

Y

FA

M

IL

Y H

O U

SI

N

G P

R O

JE

C

T

AS NOTED

CCA/MPO

DER

R. STEPHENS, PE

DPS

P L O T T E D

F

IL

E

P A T H

A U T H O R

Approved by Michele Millers, AFH-C Program Manager, USAG Italy, via email

6 OCT 2021

:3 :1

A M

B

IM

B P A M E R

V ic e n z a p h a s e

II

I_ A F H P A P M e n v e lo p e .r v t

MWM BVMWM

A P

B U

IL

D

IN

G

M

E C

H A

N

IC

A L S

E C

T

IO

N S

A P

E D

IF

IC

IO

S

E Z

IO

N

I

IM

P

IA

N T

I M

E C

C A

N

IC

I

M-302

14106758

1656273

M W M

NOTE CHIAVE DELLA TAVOLA:

SHEET KEYNOTES /

23.206 PROVIDE REFRIGERANT LIQUID AND REFRIGERANT SUCTION PIPING DOWN

TO INDOOR FAN COIL UNITS SIZED PER MANUFACTURERS

RECOMMENDATIONS. / FORNIRE IL LIQUIDO REFRIGERANTE E LE TUBAZIONI

DA E PER IL VENTILCONVETTORI DIMENSIONATI SECONDO LE

RACCOMANDAZIONI DEI PRODUTTORI.

23.239 PROVIDE PIPE SUPPORTS WHERE REFRIGERANT PIPING RUNS ALONG ROOF,

TYPICAL. / FORNIRE SUPPORTI PER TUBI DOVE LE TUBAZIONI DEL

REFRIGERANTE CORRONO LUNGO IL TETTO, TIPICA.

23.240 DASHED LINE REPRESENTS REQUIRED SERVICE CLEARANCE, TYPICAL. / LA

LINEA TRATTEGGIATA RAPPRESENTA L'AUTORIZZAZIONE RICHIESTA DAL

SERVIZIO, TIPICA.