Attachment 8 - FP BINDER.pdf

PDF 5 MB Posted

Attached to
Y1DA--626-309 Construct Integrated Health Center (Minor) - Murfreesboro
Solicitation number
36C77623B0037
Issued by

About this file

This solicitation is for the construction of an integrated health center at the Alvin C. York VA Medical Center campus in Murfreesboro, Tennessee. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center in Austin, Texas under solicitation number 36C77623B0037.

The project involves the full construction of an integrated health center building to replace and expand upon existing facilities. Scope of work includes demolition of existing structures, construction of a new approximately 80,000 square foot building, and installation of new mechanical, electrical and fire protection systems. The construction drawings provide layouts and details for demolition, new construction, and fire protection work. Notes specify requirements for phasing, maintaining existing operations, and temporary fire protection during construction.

The solicitation is for a firm-fixed-price design-bid-build contract. The contractor will be responsible for designing and constructing the project in accordance with the provided drawings and specifications, and all applicable local and federal codes and standards.

View the file

Other files

File Type Posted
36C77623B0037 0008 - 8-29-23.pdf PDF
36C77623B0037 0007.pdf PDF
36C77623B0037 0006 - 8-22-23.pdf PDF
36C77623B0037 0005 - 8-18-23.pdf PDF
081710 integrated door assemblies - R2.pdf PDF
36C77623B0037 0004 - 08-15-2023.pdf PDF
Technical Questions Round 2 - 8-14-23.docx DOCX document
232113.13 FL - UNDERGROUND HYDRONIC PIPING.pdf PDF
2023-08-09 - IHC - Addendum 2.pdf PDF
IHC - Add 2 - Narrative.pdf PDF
36C77623B0037 0003 - 08-03-2023.pdf PDF
Technical Questions Tracking Spreadsheet - Murf IHC - 7-24-23.pdf PDF
VAMC - IHC - Addendum 1 - Dwgs.pdf PDF
36C77623B0037 0002.pdf PDF
Integrated Health Laydown Areas.pdf PDF
Attachment 17 - Construction Wage Rates - Rutherford County - 6-30-23.pdf PDF
Site Visit Sign In Sheet.pdf PDF
36C77623B0037 0001.docx DOCX document
Civil Binder.pdf PDF
Attachment 5 - CIVIL BINDER.pdf PDF
Attachment 11 - MECH BINDER-1.pdf PDF
Attachment 19 - Site Visit Instructions.pdf PDF
36C77623B0037_1.docx DOCX document
Attachment 9 - GENERAL BINDER.pdf PDF
Attachment 3 - ARCHITECTURAL BINDER-1.pdf PDF
Attachment 2 - IHC - SPEC - VOLUME 2.pdf PDF
Attachment 18 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 7 - ELEC BINDER.pdf PDF
Attachment 1 - IHC - SPEC - VOLUME 1.pdf PDF
Attachment 13 - PLUMBING BINDER.pdf PDF
Attachment 15 - TECH BINDER.pdf PDF
Attachment 10 - INTERIORS BINDER.pdf PDF
Attachment 12 - MECH BINDER-2.pdf PDF
Attachment 17 - Construction Wage Rates.pdf PDF
Attachment 6 - DEMO BINDER1.pdf PDF
Attachment 4 - ARCHITECTURAL BINDER-2.pdf PDF
Attachment 14 - STRUCTURAL BINDER.pdf PDF
Attachment 16 - Limitations on Subcontracting - Construction Jan 2023 Deviation.docx DOCX document
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NOT TO SCALE

METAL PIPE THROUGH GYPSUM WALL ASSEMBLY (1-HR.)

INSTALL PER UL SYSTEM W-L-1054

USE HILTI FS-ONE MAX FIRESTOP SEALANT

METAL PIPE

TYPE MAX. DIA.

STEEL PIPE (SCH. 10

OR HEAVIER)

30"

CAST IRON PIPE 30"

COPPER PIPE 6"

STEEL CONDUIT 6"

EMT 4"

2 1/2"

2 1/2"

3-0

NOT TO SCALE

METAL PIPE THROUGH GYPSUM WALL ASSEMBLY (2-HR.)

INSTALL PER UL SYSTEM W-L-1054

USE HILTI FS-ONE MAX FIRESTOP SEALANT

METAL PIPE

TYPE MAX. DIA.

STEEL PIPE (SCH. 10

OR HEAVIER)

30"

CAST IRON PIPE 30"

COPPER PIPE 6"

STEEL CONDUIT 6"

EMT 4"

Notes:

1. Refer to the following specifications for firestopping.

a. 07 84 00 Firestopping

b. 07 84 13 Penetration Firestopping

c. 22 00 00 Plumbing

d. 23 00 00 HVAC

e. 26 00 00 Electrical

f. 27 06 37 Communication

For Quality Control requirements, refer to the Quality Control portion of the specification.

2. Details shown are typical details, containing general information only. Always refer to the full UL system detail for complete system requirements. If field conditions do not match requirements of details, approved alternate details shall be utilized. Design requirements, field conditions and dimensions need to be verified for compliance with the details, including but not limited to the following:

* Fire Rating (F-Rating)

* Temperature Rating (T-Rating)

* Leakage Rating (L-Rating)

* Water Rating (W-Rating)

* Annular Space

* Percent Fill

* Movement

* Type and thickness of fire-rated construction.

3. If alternate details matching the field conditions are not available, manufacturer's engineering judgment drawings are acceptable.

Contact Hilti Inc. for alternative systems or Engineering Judgment (800-879-8000) Drawings shall follow the International Firestop Council (IFC) Guidelines for Evaluating Firestop

Systems Engineering Judgments.

4. References:

* 2013 Underwriter's Laboratories Fire Resistance Directory, Volumes 1 & 2

* NFPA 101 Life Safety Code

* NFPA 70 - National Electric Code

* All governing local and regional building codes

5. Firestop System installation must meet requirements of ASTM

E-814 (UL 1479) tested assemblies that provide a fire rating equal to that of construction being penetrated.

6. All rated through-penetration assemblies shall be prominently labeled with a Hilti Firestop Label equipped with a QR code with the following information:

*Warning! - Do Not Disturb

*Through Penetration Firestop System

* UL System # * Product(s) used

* Hourly Rating (F-Rating)

* Installation Date

*Contractor's Name

7. For outlet boxes requiring protection, use only Wall Opening

Protective Materials, category CLIV as classified by Underwriter's

Laboratories, Fire Resistance Directory (Volume 1.)

FIRE PROTECTION DRAWING INDEX

FIRE PROTECTION LEGEND

FIRE PROTECTION DESIGN CRITERIA

FIRE PROTECTION FLOW TEST DATA

THERE IS NO FIRE PUMP AT THIS FACILITY.

NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT

SYMBOL DESCRIPTION

- CONTROL VALVE w/TAMPER SWITCH

- HYDRAULIC REFERENCE NODE

- EXISTING SPRINKLER PIPING

- FIRE VALVE CABINET

- REVISION REFERENCE

OR

- CONNECT TO

- DEMO TO

- DEMOLISHED SPRINKLER PIPING

- NEW SPRINKLER PIPING

- U/G GATE VALVE

# - KEYNOTE

- HYDRAULIC REMOTE AREA

- CONTROL VALVE W/ TAMPER SWITCH

- PIPE SIZE

- 2-1/2" FIRE DEPARTMENT VALVE W/ CAP AND CHAIN

- PIPE SIZE AND LENGTH

1. FIRE PROTECTION DESIGN SHALL COMPLY THE VA FIRE PROTECTION DESIGN MANUAL; SEVENTH

EDITION 2015.

2. V.A. IS THE ONLY AHJ. SEE V.A. FIRE PROTECTION DESIGN MANUAL AND NFPA 13, 2019 EDITION.

3. THE FIRE PROTECTION SYSTEMS SHOWN REPRESENT THE DESIGN INTENT OF THE ENGINEER, IN

ACCORDANCE WITH ALL APPLICABLE LOCAL CODES. IT IS THE RESPONSIBILITY OF THE

CONTRACTOR TO COORDINATE INSTALLATION WITH ALL OTHER TRADES. SUBMIT COMPLETE

SPRINKLER SYSTEM LAYOUT DRAWINGS WITH ANY ADDITIONAL OFFSETS, SPRINKLERS OR SYSTEM

COMPONENTS AS REQUIRED FOR A COMPLETE AND OPERABLE SYSTEM AND TO AVOID CONFLICTS

WITH OTHER TRADES.

4. SPRINKLER SHOP DRAWINGS AND MATERIAL CUT SHEETS SHALL BE SUBMITTED TO THE

ARCHITECT AND LOCAL FIRE MARSHAL FOR APPROVAL PRIOR TO ANY INSTALLATION.

5. PIPE ROUTING SHOWN IS SCHEMATIC ONLY. PROVIDE ALL ADDITIONAL OFFSETS REQUIRED FOR

PROPER INSTALLATION AND COORDINATION WITH OTHER TRADES.

6. INSTALL PIPING IN AREAS WITH EXPOSED STRUCTURE AS HIGH AS POSSIBLE TO ALLOW THE

OWNER MAXIMUM USE OF THE SPACE.

7. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR CEILING DESCRIPTIONS AND HEIGHTS.

8. COORDINATE SPRINKLERS WITH ALL DIFFUSERS, SPEAKERS, LIGHTING FIXTURES AND LISTING OF

THE SPRINKLER.

9. CENTER SPRINKLERS IN THE CENTER OF CEILING TILE. PROVIDE ARMOVER OR SWING JOINT AS

REQUIRED.

10. SPRINKLERS IN AREAS WITH EXPOSED STRUCTURE (OBSTRUCTED CONSTRUCTION) SHALL BE

INSTALLED WITH DEFLECTOR 1" BELOW THE BOTTOM OF THE BEAM (MAXIMUM 22" BELOW ROOF

DECK). EXPOSED BAR JOISTS THAT HAVE SPRAY-ON FIRE PROOFING THAT MAKES THE JOIST SOLID

SHALL BE TREATED LIKE A BEAM WITH THE SPRINKLERS 1" BELOW THE BOTTOM OF THE FIRE

PROOFING.

11. SLEEVE AND/OR FIRESTOP ALL PENETRATIONS THROUGH RATED WALLS, CEILINGS, AND FLOORS WITH U/L LISTED ASSEMBLIES. PROVIDE FIRESTOP ASSEMBLIES EQUAL TO OR EXCEEDING THE

RATING OF THE WALL, CEILING OR FLOOR. SEE ARCHITECTURAL DRAWINGS FOR RATINGS.

12. FURNISH ACCESS PANELS TO ALL VALVES ABOVE NON-ACCESSIBLE CEILINGS AND CHASES, FOR

INSTALLATION BY GENERAL CONTRACTOR.

13. PROVIDE A PERMANENTLY ATTACHED NAME TAG TO THE RISER STATING THE REQUIRED DESIGN

CRITERIA FOR EACH HYDRAULICALLY-DESIGNED SYSTEM.

14. PROVIDE SPRINKLERS UNDERNEATH ALL EXPOSED DUCTWORK WHICH IS OVER 48" WIDE AND

SPACE HEADS AROUND ALL OBSTRUCTIONS IN ACCORDANCE WITH VA FIRE PROTECTION DESIGN

MANUAL 2015 EDITION AND NFPA 13, 2019 EDITION. HEADS UNDER DUCTS ARE NOT INDICATED ON THE DRAWINGS BUT ARE REQUIRED. PROVIDE IN ACCORDANCE WITH VA FIRE PROTECTION DESIGN

MANUAL 2015 EDITION. COORDINATE SPRINKLER LOCATIONS UNDER DUCTWORK AND AROUND

OBSTRUCTIONS WITH FINAL INSTALLED LOCATIONS.

15. PROVIDE SPRINKLER GUARDS ON ALL HEADS IN ELECTRIC ROOMS, TELEPHONE ROOMS, ELEVATOR

ROOMS, ELEVATOR SHAFTS, STORAGE ROOMS, UTILITY ROOMS AND ON ANY HEADS LESS THAN

7'-0" ABOVE THE FLOOR.

16. PROVIDE HANGERS ON END HEADS IN PENDANT POSITION WITHIN 12" OF END OF LINE, IN

ACCORDANCE WITH VA FIRE PROTECTION DESIGN MANUAL 2015 EDITION, WHEN SYSTEM

PRESSURE EXCEEDS 100 PSI.

17. COORDINATE PIPING WITH ALL ELECTRICAL EQUIPMENT (PANELS, TRANSFORMERS, ETC.) PRIOR TO

ANY INSTALLATION. DO NOT ROUTE ANY PIPING OVER ANY ELECTRICAL PANELS UNDER ANY

CIRCUMSTANCES. REROUTE ANY PIPING RUN OVER ELECTRICAL EQUIPMENT.

18. ALL DRAIN SYSTEM PIPING AND FITTINGS SHALL BE GALVANIZED BOTH INSIDE AND OUTSIDE.

19. PROVIDE TAMPER SWITCHES ON ALL CONTROL VALVES.

20. SLOPE ALL PIPING TO THE SYSTEM MAIN DRAIN AS REQUIRED TO INSURE PROPER DRAINAGE.

INSTALL ADDITIONAL DRAINS AND PLUGS WHERE REQUIRED TO COMPLY WITH THE ABOVE

REFERENCED CODES.

21. SPRINKLER CONTRACTOR TO INDICATE SPRINKLER DESIGN DENSITIES FOR ALL AREAS/ROOMS ON

THEIR RESPECTIVE DRAWINGS.

22. THIS BUILDINGS STRUCTURAL SYSTEM HAS BEEN DESIGNED TO SUPPORT THE ADDITIONAL

WEIGHT ASSOCIATED WITH THE SPRINKLER SYSTEM.

23. PAINT ALL SPRINKLER PIPING INSTALLED BELOW THE CEILINGS AND IN EXPOSED LOCATIONS.

CLEAN, PRIME AND PAINT ALL EXPOSED PIPING RED, UNLESS OTHERWISE NOTED. COORDINATE

ALL COLORS WITH THE ARCHITECT.

24. COORDINATE HANGER LOCATIONS WITH THE BUILDING STRUCTURE. SUPPORT PIPING IN

ACCORDANCE WITH VA FIRE PROTECTION DESIGN MANUAL 2015 EDITION. PROVIDE ALL

MISCELLANEOUS STEEL FRAMING AS REQUIRED TO SUPPORT PIPING. PROVIDE GALVANIZED OR

COATED HANGERS AND RODS.

25. THE OWNER AND ARCHITECT/ENGINEER SHALL BE NOTIFIED IN WRITING AT LEAST 10 DAYS PRIOR

TO ANY FIRE PROTECTION SYSTEM SHUTDOWNS. FIRE PROTECTION CONTRACTOR SHALL BE

RESPONSIBLE FOR A FIRE WATCH ON THE BUILDING WHILE THE SYSTEM IS DOWN.

26. TENNESSEE SPRINKLER CONTRACTOR TO PROVIDE SPRINKLER CALCS ON THE DRAWINGS.

27. SPRINKLER CONTRACTOR TO MOUNT INFORMATION PLATES ON SPRINKLER SYSTEMS WITH CALCS

ON THE PLATES.

28. SPRINKLER CONTRACTOR SHOW LOCATION OF SPRINKLER RISER AND ALL CONTROL AND TEST

VALVES FOR THIS AREA.

29. PROVIDE DETAILED DRAWING OF THE MAIN SPRINKLER RISER AND ALARM VALVE

INCLUDINGTAMPER AND FLOW SWITCH LOCATIONS. SHOW BACKFLOW PREVENTER AND METHOD

FOR FRONT FLOW TESTING IT. SHOW ALL DRAINS DISCHARGING TO THE EXTERIOR OF THE

BUILDING.

GENERAL NOTES

HANGER - STEEL

No Scale

PIPE HANGER RING

(UL LISTED OR FM APPROVED)

ALL THREAD ROD

TOP BEAM CLAMP

(UL LISTED OR FM APPROVED)

RETURN BEND

No Scale

SPRINKLER HEAD

1" DROP

1" 90° ELL

1" 90° ELL

BRANCH LINE

1x1/2 REDUCER

CEILING

LIGHT HAZARD

WET PIPE

.10 GPM/SQ. FT.

1,500 SQ. FT.

1/2"

30 MIN.

225 SQ. FT.

100 GPM

OCCUPANCY CLASSIFICATION:

SYSTEM TYPE:

DESIGN DENSITY:

HYDRAULIC REMOTE AREA:

SPRINKLER ORIFICE SIZE:

DURATION OF SUPPLY:

MAXIMUM COVERAGE/SPRINKLER HEAD:

HOSE STREAM ALLOWANCE:

ENTIRE BUILDING (EXCEPT AS NOTED):

FIRE SPRINKLER:

WATER SUPPLY DATA:

THE CONTRACTOR SHALL PREPARE SYSTEM LAYOUT DRAWINGS PER VA FIRE PROTECTION

DESIGN MANUAL 2015 EDITION AND NFPA 13, 2019 EDITION. THE CONTRACTOR SHALL PERFORM

HYDRAULIC CALCULATIONS. CONTRACTOR'S SPRINKLER SYSTEM LAYOUT (SHOP DRAWINGS),

HYDRAULIC CALCULATIONS AND MATERIAL DATA SHALL BE SUBMITTED TO THE

ARCHITECT/ENGINEER AND AUTHORITY HAVING JURISDICTION FOR APPROVAL PRIOR TO

SYSTEM INSTALLATION.

THE CONTRACTOR SHALL PERFORM HYDRANT-FLOW TEST TO VERIFY WATER PRESSURE

REQUIRED FOR HYDRAULIC CALCULATIONS.

UNLESS OTHERWISE NOTED ALL STORAGE ROOMS:

DESIGN CRITERIA:

DESIGN OF THE FIRE SUPPRESSION SYSTEM ON THIS PROJECT. THE

FOLLOWING PUBLICATIONS SHALL BE USED AS A REFERENCE.

1. VA FIRE PROTECTION MANUAL, 2015 EDITION AND NFPA 13, 2019 EDITION.

ORDINARY HAZARD GROUP II

WET PIPE

0.2 GPM/SQ. FT.

1,500 SQ. FT.

1/2"

60-90 MIN.

130 SQ. FT.

250 GPM

OCCUPANCY CLASSIFICATION:

SYSTEM TYPE:

DESIGN DENSITY:

HYDRAULIC REMOTE AREA:

SPRINKLER ORIFICE SIZE:

DURATION OF SUPPLY:

MAXIMUM COVERAGE/SPRINKLER HEAD:

HOSE STREAM ALLOWANCE:

STANDPIPE DESIGN CRITERIA:

HYDRAULIC DESIGN CRITERIA: EXISTING

SPRINKLER LEGEND

SWING JOINT

No Scale

1" DROP

1" 90° ELL

1" NIPPLE

BRANCH LINE

1" 90° ELL

REDUCER

CEILING

SPRINKLER HEAD

UNLESS OTHERWISE NOTED ALL MECHANICAL AND ELECTRICAL ROOMS:

ORDINARY HAZARD GROUP I

WET PIPE

.15 GPM/SQ. FT.

1,500 SQ. FT.

1/2"

60-90 MIN.

130 SQ. FT.

250 GPM

OCCUPANCY CLASSIFICATION:

SYSTEM TYPE:

DESIGN DENSITY:

HYDRAULIC REMOTE AREA:

SPRINKLER ORIFICE SIZE:

DURATION OF SUPPLY:

MAXIMUM COVERAGE/SPRINKLER HEAD:

HOSE STREAM ALLOWANCE:

• SCOPE OF WORK INDICATED HEREIN FOR THIS DISCIPLINE DOES NOT INDICATE

SPECIFIC REQUIREMENTS RELATED TO PHASING OF WORK, ALTHOUGH EVERY

EFFORT HAS BEEN MADE TO INCORPORATE SEQUENTIAL PHASES OF WORK AS

REQUESTED BY THE GOVERNMENT.

• PUBLIC AND STAFF ACCESS TO BUILDINGS 7, 107 AND 116 SHALL NOT BE

INTERRUPTED AT ANY TIME DURING CONSTRUCTION.

• CANTEEN, KITCHEN, AND GIFT SHOP NORMAL OPERATION SHALL NOT BE

INTERRUPTED AT ANY TIME DURING CONSTRUCTION.

• REFER TO SHEET GI 01.30 FOR FURTHER INFORMATION ON PROJECT PHASING

REQUIREMENTS

CONSTRUCTION PHASING/ PUBLIC AND STAFF

ACCESS/BUILDING OPERATIONS

FIRE SPRINKLER LEGEND

SYMBOL ORF.

1/2"

1/2"

TEMP.

155 DEG.

155 DEG.

RESPONSE

QUICK

QUICK

K-FACTOR

5.6

5.6

FINISH

BRASS

BRASS

MODEL STYLE PLATE

WHITE

WHITE

MFG

RELIABLE

RELIABLERECESSED

UPRIGHTF1-FR

DESIGN NOTES:

1. PROVIDE F1FR SPRINKLERS WITH 175 DEG. F. TEMPERATURE RATING IN ALL MECHANICAL

AND ELECTRICAL ROOMS

2. RELIABLE IS BASIS OF DESIGN, APPROVED EQUALS ARE ALLOWED.

1/2" 155 DEG. QUICK 5.6 BRASS RELIABLESIDEWALL

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h

/1

-P

L U

M B

-T V

H S

A C

Y V

A M

C I n te g ra te d

H e a lt h

C e n te r- R

.r v t

/1

/2

:0

:0

P

M

F-FI-01

FIRE PROTECTION LEGENDS,

DETAILS & NOTES

TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5/20/22 DRT

Sheet Number Sheet Name

F-FI-01 FIRE PROTECTION LEGENDS, DETAILS & NOTES

F-FD-01 BASEMENT - DEMOLITION PLAN - FIRE PROTECTION OVERALL

F-FD-02 GROUND FLOOR - DEMOLITION PLAN - FIRE PROTECTION OVERALL

F-FD-03 SECOND FLOOR - DEMOLITION - FIRE PROTECTION

F-FX-01A GROUND FLOOR - NEW WORK - FIRE PROTECTION - AREA A

F-FX-01B GROUND FLOOR - NEW WORK - FIRE PROTECTION - AREA B

F-FX-02A SECOND FLOOR - NEW WORK PLAN - FIRE PROTECTION - AREA A

F-FX-02B SECOND FLOOR - NEW WORK PLAN - FIRE PROTECTION - AREA B

MIN.RADIUS = 7"

MAX NUMBER OF BENDS = 2

SHEET METAL SCREW

DROP CEILING TILE

CEILING COVER PLATE

SPRINKLER HEAD

END BRACKET ASSEMBLY

SQUARE BAR

CENTER BRACKET ASSEMBLYREDUCING OUTLET

NUT

COLLAR

STAINLESS STEEL FLEXIBLE

BRAIDED HOSE

COLLAR

ISOLATION RING

NUT

INLET NIPPLE

MAX LENGTH OF PIPE = 48"

FLEX PIPE TO SPRINKLER

No Scale

FLEXIBLE HOSE SHALL BE INSTALLED IN ACCORDANCE WITH REQUIREMENTS OF THE LISTING INCLUDING INSTALLATION INSTRUCTIONS SEE 9.2.1.3.3.1 OF THE 2018 NFPA-13. FLEXIBLE SPRINKLER HOSE SHALL BE FM APPROVED AND LIMITED TO HOSE WITH THREADED END FITTINGS WITH A MINIMUM INSIDE

DIAMETER OR 1-INCH AND A MAXIMUM LENGTH OF 6-FEET.

SUSPENDED CEILINGS SHALL BE CERTIFIED AS

MEETING ASTM C 635 SPECIFICATION AND ASTM

C 636 STANDARD PRACTICE FOR INSTALLATION.

SEE NFPA-13, 2019 EIDTION. ADD A NOTE THAT

THE CEILING INSTALLING CONTRACTOR SHALL

PROVIDE A SIGNED STATEMENT CONFIRMING

THE LAY-IN CEILING SYSTEMS COMPLY WITH

ASTM C 635 AND ASTM C 636 AT THE AHCA

SURVEY.

FLEXIBLE HOSE EXCEEDING 6 FEET IN

LENGTH SERVING SPRINKLERS IN

SUSPENDED CEILINGS SHALL HAVE

HANGER ATTACHED TO THE STRUCTURE

TO LIMIT THE MAXIMUM UNSUPPORTED

LENGTH TO 6 FEET. SEE NFPA-13, 2019

EDITION.

Revisions: Date:

ADDENDUM 01 06/20/2019

THE EXISTING FIRE PROTECTION SYSTEM SHALL REMAIN ACTIVE DURING THE CONSTRUCTION

AND INSTALLATION OF THE NEW FIRE SPRINKLER SYSTEM. ONCE THE NEW SYSTEM IS

INSTALLED, CONNECTED TO THE WATER SOURCE, IS TESTED AND ACCEPTED BY THE AHJ THE

EXISTING SYSTEM CAN BE DEMOLISHED. THE BUILDING SHALL NOT BE WITH OUT FIRE

SPRINKLER PROTECTION AT ANY TIME DURING CONSTRUCTION EXCEPT FOR THE TIME OF

CONNECTING THE NEW SYSTEM AND DISCONNECTING THE EXISTING SYSTEM. PROVIDE 72

HOUR NOTICE TO THE OWNER PRIOR TO SYSTEM SHUT DOWNS. COORDINATION WITH THE

OWNER PRIOR TO SHUT DOWN OF THE EXISTING FIRE SPRINKLER SYSTEM IS REQUIRED TO

IMPLEMENT OTHER MEANS OF FIRE SAFETY FOR THE BUILDING.

TEMPORARY FIRE PROTECTION:

PROVIDE TEMPORARY HEAT DETECTORS, CONNECTED TO EXISTING FIRE ALARM SYSTEM TO

NOTIFY SYSTEM IN THE EVENT OF A FIRE IN SPACES UNDER CONSTRUCTION. HEAT

DETECTORS SHALL PROVIDE COMPLETE COVERAGE OF THE AREA UNDER CONSTRUCTION.

QUANTITIES AND SPACING SHALL NOT EXCEED MANUFACTURER’S RECOMMENDATIONS FOR

THE DETECTORS USED. PROVIDE A MINIMUM OF ONE (1) HEAT DETECTOR IN EVERY SPACE IN

THE AREA OF CONSTRUCTION FOR EVERY 900 SQUARE FEET (MAXIMUM). HEAT DETECTORS

SHALL REMAIN ACTIVE AND IN PLACE UNTIL REPLACEMENT FIRE ALARM SYSTEM IS FULLY-

FUNCTIONAL AND COVERAGE IS PROVIDED.

FIRE SPRINKLER CONSTRUCTION CONSIDERATIONS

FIRE PROTECTION GENERAL NOTES

1. FIRE PROTECTION DRAWINGS ARE CONCEPTUAL, FOR

GENERAL INFORMATION ONLY AND NOT AN EXACT

INDICATOR OF PIPE AND SPRINKLER HEAD LOCATIONS.

2. REMOVE EXISTING FIRE EXTINGUISHERS AND RETURN

TO VA FOR STORAGE.

3. REMOVE EXISTING FIRE VALVE CABINETS AND PIPING.

EXISTING MECHANICAL

ROOM TO REMAIN.

EXISTING UTILITY TUNNEL

PROVIDE NEW SPRINKLER

PIPING AND VA APPROVED

SPRINKLER HEADS.

EXISTING POOL

TO BE REMOVED.

EXISTING CRAWLSPACE

EXISTING CRAWLSPACE

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

AREA A

AREA B

OUT OF

SCOPE

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h

/1

-P

L U

M B

-T V

H S

A C

Y V

A M

C I n te g ra te d

H e a lt h

C e n te r- R

.r v t

/1

/2

:0

:5

P

M

F-FD-01

BASEMENT - DEMOLITION PLAN -

FIRE PROTECTION OVERALL

TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5/20/22 DRT

1/16" = 1'-0"

1 BASEMENT OVERALL - FIRE PROTECTION DEMO

0 8' 16' 32'4'

UP

UP

J

I I

H

G

F

E

D

C

B

A

10987

11 12

135.1 10.25.2

H1

F3

F2

E1

I2

H3

G1

12.511.5

9.57.5

15 16 17 18 19 22

F4

F1

E2

D1

C1

B1

H2

I1

I3

K

L

15.1 15.2 17.1 17.2

00 01 02 03

7.1 9.1

4.5

5.5

ELECTRICAL

STAIRS

20 21

SIDEWALL

SIDEWALL

SIDEWALL

EXISTING FIRE MAIN.

TO REMAIN.

EXISTING FIRE DEPT.

CHECK VALVE.

REMOVE

EXISTING F.H.R

F.D.C.

REMOVE EXISTING FIRE

SPRINKLER PIPING IN

RENOVATED AREAS.

REMOVE EXISTING FIRE

SPRINKLER PIPING IN

RENOVATED AREAS.

REMOVE FIRE

MAIN UP TO

2ND FLOOR.

NOT IN

SCOPE

NOT IN

SCOPE

NOT IN

SCOPE

NOT IN

SCOPE

NOT IN

SCOPE

NOT IN

SCOPE

NOT IN

SCOPE

NOT IN

SCOPE

NOT IN

SCOPE

NOT IN

SCOPE

NOT IN

SCOPE

REMOVE EXISTING FIRE

SPRINKLER PIPING IN

RENOVATED AREAS.

EXISTING GYM AREA

EXISTING POOL AREA

EXISTING AUDITORIUM AREA

REMOVE

EXISTING

FDC 2ND FLR

MAIN

EXISTING FIRE MAIN

WEST DOWN BELOW

GRADE TO REMAIN.

FIRE MAIN

WEST

FIRE MAIN

EAST DOWN

TO REMAIN.

FIRE MAIN

UP FROM

BELOW TO

REMAIN. EXISTING SPRINKLER RISER

FIRE MAIN EAST AND 2ND FLR (STAGE AREA)

FIRE MAIN WEST

2ND FLR

MAIN TO

REMAIN

REMOVE EXISTING FIRE

SPRINKLER PIPING IN

RENOVATED AREAS.

REMOVE EXISTING FIRE

SPRINKLER PIPING IN

RENOVATED AREAS.

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

AREA A

AREA B

OUT OF

SCOPE

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h

/1

-P

L U

M B

-T V

H S

A C

Y V

A M

C I n te g ra te d

H e a lt h

C e n te r- R

.r v t

/1

/2

:0

:0

P

M

F-FD-02

GROUND FLOOR - DEMOLITION

PLAN - FIRE PROTECTION

OVERALL

TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5/20/22 DRT

1/16" = 1'-0"

1 GROUND FLOOR OVERALL - FIRE PROTECTION DEMO

0 4' 8' 12'

THE EXISTING FIRE PROTECTION SYSTEM SHALL REMAIN ACTIVE DURING THE CONSTRUCTION

AND INSTALLATION OF THE NEW FIRE SPRINKLER SYSTEM. ONCE THE NEW SYSTEM IS

INSTALLED, CONNECTED TO THE WATER SOURCE, IS TESTED AND ACCEPTED BY THE AHJ THE

EXISTING SYSTEM CAN BE DEMOLISHED. THE BUILDING SHALL NOT BE WITH OUT FIRE

SPRINKLER PROTECTION AT ANY TIME DURING CONSTRUCTION EXCEPT FOR THE TIME OF

CONNECTING THE NEW SYSTEM AND DISCONNECTING THE EXISTING SYSTEM. PROVIDE 72

HOUR NOTICE TO THE OWNER PRIOR TO SYSTEM SHUT DOWNS. COORDINATION WITH THE

OWNER PRIOR TO SHUT DOWN OF THE EXISTING FIRE SPRINKLER SYSTEM IS REQUIRED TO

IMPLEMENT OTHER MEANS OF FIRE SAFETY FOR THE BUILDING.

TEMPORARY FIRE PROTECTION:

PROVIDE TEMPORARY HEAT DETECTORS, CONNECTED TO EXISTING FIRE ALARM SYSTEM TO

NOTIFY SYSTEM IN THE EVENT OF A FIRE IN SPACES UNDER CONSTRUCTION. HEAT

DETECTORS SHALL PROVIDE COMPLETE COVERAGE OF THE AREA UNDER CONSTRUCTION.

QUANTITIES AND SPACING SHALL NOT EXCEED MANUFACTURER’S RECOMMENDATIONS FOR

THE DETECTORS USED. PROVIDE A MINIMUM OF ONE (1) HEAT DETECTOR IN EVERY SPACE IN

THE AREA OF CONSTRUCTION FOR EVERY 900 SQUARE FEET (MAXIMUM). HEAT DETECTORS

FIRE PROTECTION GENERAL NOTES

1. FIRE PROTECTION DRAWINGS ARE CONCEPTUAL, FOR

GENERAL INFORMATION ONLY AND NOT AN EXACT

INDICATOR OF PIPE AND SPRINKLER HEAD LOCATIONS.

2. REMOVE EXISTING FIRE EXTINGUISHERS AND RETURN

TO VA FOR STORAGE.

3. REMOVE EXISTING FIRE VALVE CABINETS AND PIPING.

ROOF BELOW

ROOF BELOW

ROOF BELOW

REC THERAPY BELOW

STAIR

STUDIO

FAN ROOM

GENERATOR

RM

REWIND RM PROJECTION ROOM CONTROL RM AMP RM

C O

R R

ID

O

R

AMATEUR

RADIO ROOM

JANITOR

02.11

02.16

02.16

02.10

02.16

02.16

02.10

02.10

02.1002.10

02.16

02.16

02.1602.16

02.16

02.10

02.10

02.10

J

I

G

F

10987

I2

H3

G1

REMOVE F.H.C.

REMOVE EXISTING FIRE

SPRINKLER PIPING IN

RENOVATED AREAS.

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

AREA A

OUT OF

SCOPE

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h

/1

-P

L U

M B

-T V

H S

A C

Y V

A M

C I n te g ra te d

H e a lt h

C e n te r- R

.r v t

/1

/2

:0

:0

P

M

F-FD-03

SECOND FLOOR - DEMOLITION -

FIRE PROTECTION

TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5/20/22 DRT

1/4" = 1'-0"

1 SECOND FLOOR OVERALL - FIRE PROTECTION DEMO

0 4' 8' 12'

FIRE PROTECTION GENERAL NOTES

1. FIRE PROTECTION DRAWINGS ARE CONCEPTUAL, FOR

GENERAL INFORMATION ONLY AND NOT AN EXACT

INDICATOR OF PIPE AND SPRINKLER HEAD LOCATIONS.

2. REMOVE EXISTING FIRE EXTINGUISHERS AND RETURN

TO VA FOR STORAGE.

3. REMOVE EXISTING FIRE VALVE CABINETS AND PIPING.

THE EXISTING FIRE PROTECTION SYSTEM SHALL REMAIN ACTIVE DURING THE CONSTRUCTION

AND INSTALLATION OF THE NEW FIRE SPRINKLER SYSTEM. ONCE THE NEW SYSTEM IS

INSTALLED, CONNECTED TO THE WATER SOURCE, IS TESTED AND ACCEPTED BY THE AHJ THE

EXISTING SYSTEM CAN BE DEMOLISHED. THE BUILDING SHALL NOT BE WITH OUT FIRE

SPRINKLER PROTECTION AT ANY TIME DURING CONSTRUCTION EXCEPT FOR THE TIME OF

CONNECTING THE NEW SYSTEM AND DISCONNECTING THE EXISTING SYSTEM. PROVIDE 72

HOUR NOTICE TO THE OWNER PRIOR TO SYSTEM SHUT DOWNS. COORDINATION WITH THE

OWNER PRIOR TO SHUT DOWN OF THE EXISTING FIRE SPRINKLER SYSTEM IS REQUIRED TO

IMPLEMENT OTHER MEANS OF FIRE SAFETY FOR THE BUILDING.

TEMPORARY FIRE PROTECTION:

PROVIDE TEMPORARY HEAT DETECTORS, CONNECTED TO EXISTING FIRE ALARM SYSTEM TO

NOTIFY SYSTEM IN THE EVENT OF A FIRE IN SPACES UNDER CONSTRUCTION. HEAT

DETECTORS SHALL PROVIDE COMPLETE COVERAGE OF THE AREA UNDER CONSTRUCTION.

QUANTITIES AND SPACING SHALL NOT EXCEED MANUFACTURER’S RECOMMENDATIONS FOR

THE DETECTORS USED. PROVIDE A MINIMUM OF ONE (1) HEAT DETECTOR IN EVERY SPACE IN

THE AREA OF CONSTRUCTION FOR EVERY 900 SQUARE FEET (MAXIMUM). HEAT DETECTORS

EXISTING

A/S ZONE

#2

EXISTING

A/S ZONE

#3

Z

J

I

H

G

F

E

D

C

B

A

10987

11 12

5.1

10.2

5.2

H1

F3

F2

E1

I2

H3

G1

12.511.5

9.57.5

F4

F1

E2

D1

C1

B1

7.1

9.1

E.9

10.1 12.911.9

E.4

STAIRS

EDUC CHIEF

G17A

MUSIC THERAPY CLINIC

G13

WC STORAGE

G12B

REC. THERAPY CLINIC

G08

BARBER CART

G02

FOOD SERVICE CHIEF

G03

FOOD SERVICE VEND SUPPLY

G04

CORRIDOR

G45

WORK AREA

G15ENTRY

G01

CORRIDOR

G46

COURTYARD

G10

PRACTICE ROOM

G13BMUSIC STORAGE

G13A

PMRS CONSULT

G14

HAC

G07

RECREATION

STORAGE

G08B

MALE

G09A

FEMALE

G09C

KINESIO GROUP THERAPY

G12

WORK

G12A

KITCHENETTE

G08A

615 SF

CONNECTOR

G47

B.2

C.5

C.6

E.3

E.5

F.3

COORDINATE WITH

CELING CLOUD FOR

SPRINKLER HEAD

LAYOUT.

COORDINATE WITH

CELING CLOUD FOR

SPRINKLER HEAD

LAYOUT.

COORDINATE WITH

CELING CLOUD FOR

SPRINKLER HEAD

LAYOUT. CONNECTOR

ATLERNATE #3

NOT IN SCOPE

NOT IN SCOPE

PROVIDE NEW VA APPROVED

SPRINKER HEADS IF REQUIRED

IN EXISTING MECH. ROOM.

NEW EQUIPMENT BEING

INSTALLED IN SPACE.

COORDINATE WITH STRUCTURAL.

EXISTING ROOF STRUCTURE IS LOW.

VERIFY SPACE BETWEEN NEW

CEILING AND STRUTURAL.

OPEN SPACE TO OUTISDE

COORDINATE WITH

CELING CLOUD FOR

SPRINKLER HEAD

LAYOUT.

OCCUPANCY:

SEE LIFE SAFETY PLAN.

NOT IN SCOPE

NOT IN SCOPE

NOT IN SCOPE

NOT IN SCOPE

NOT IN SCOPE

COORDINATE WITH

CELING CLOUD FOR

SPRINKLER HEAD

LAYOUT.

COORDINATE WITH

CELING CLOUD FOR

SPRINKLER HEAD

LAYOUT.

PROVIDE SPRINKLER COVERAGE

ABOVE AND BELOW DECORATIVE

CEILING.

NEW SPRINKLER

RISER SPACE.

EXTERIOR DOOR.

ACCESS TO NEW

SPRINKLER RISER

ROOM.

EXISTING FIRE MAIN

AND SPRINKLER RISER

COURTYARD

ATLERNATE #3

STORAGE

STORAGE

JANITOR CLOSET

STORAGE

STORAGE

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

AREA A

OUT OF

SCOPE

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h

/1

-P

L U

M B

-T V

H S

A C

Y V

A M

C I n te g ra te d

H e a lt h

C e n te r- R

.r v t

/1

/2

:0

:1

P

M

F-FX-01A

GROUND FLOOR - NEW WORK -

FIRE PROTECTION - AREA A

TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5/20/22 DRT

0 4' 8' 12'

1/8" = 1'-0"

1 GROUND FLOOR - RCP NEW WORK AREA A

THE EXISTING FIRE PROTECTION SYSTEM SHALL REMAIN ACTIVE DURING THE CONSTRUCTION

AND INSTALLATION OF THE NEW FIRE SPRINKLER SYSTEM. ONCE THE NEW SYSTEM IS

INSTALLED, CONNECTED TO THE WATER SOURCE, IS TESTED AND ACCEPTED BY THE AHJ THE

EXISTING SYSTEM CAN BE DEMOLISHED. THE BUILDING SHALL NOT BE WITH OUT FIRE

SPRINKLER PROTECTION AT ANY TIME DURING CONSTRUCTION EXCEPT FOR THE TIME OF

CONNECTING THE NEW SYSTEM AND DISCONNECTING THE EXISTING SYSTEM. PROVIDE 72

HOUR NOTICE TO THE OWNER PRIOR TO SYSTEM SHUT DOWNS. COORDINATION WITH THE

OWNER PRIOR TO SHUT DOWN OF THE EXISTING FIRE SPRINKLER SYSTEM IS REQUIRED TO

IMPLEMENT OTHER MEANS OF FIRE SAFETY FOR THE BUILDING.

TEMPORARY FIRE PROTECTION:

PROVIDE TEMPORARY HEAT DETECTORS, CONNECTED TO EXISTING FIRE ALARM SYSTEM TO

NOTIFY SYSTEM IN THE EVENT OF A FIRE IN SPACES UNDER CONSTRUCTION. HEAT

DETECTORS SHALL PROVIDE COMPLETE COVERAGE OF THE AREA UNDER CONSTRUCTION.

QUANTITIES AND SPACING SHALL NOT EXCEED MANUFACTURER’S RECOMMENDATIONS FOR

THE DETECTORS USED. PROVIDE A MINIMUM OF ONE (1) HEAT DETECTOR IN EVERY SPACE IN

THE AREA OF CONSTRUCTION FOR EVERY 900 SQUARE FEET (MAXIMUM). HEAT DETECTORS

1. SPRINKLER CONTRACTOR TO INDICATE SPRINKLER DESIGN DENSITIES FOR ALL

AREAS/ROOMS ON THEIR RESPECTIVE DRAWINGS.

2. SPRINKLER CONTRACTOR TO SHOW LOCATION OF SPRINKLER RISER AND ALL

CONTROL AND TEST VALVES FOR THIS AREA.

3. PROVIDE DETAILED DRAWING OF THE MAIN SPRINKLER RISER AND ALARM

VALVE INCLUDING TAMPER AND FLOW SWITCH LOCATIONS. SHOW BACKFLOW

PREVENTER AND METHOD FOR FRONT FLOW TESTING IT. SHOW ALL DRAINS

DISCHARGING TO THE EXTERIOR OF THE BUILDING.

FIRE PROTECTION GENERAL NOTES:

S

S

S

SSSS

S

S

S

S

S

J J

J

J

J J

J

J

J

J

I

H

12.5

17 18 19 22

F4

F1

E2

D1

C1

B1

H2

I1

I3

K

L

15.1 15.2

17.1 17.2

E.9

12.9

12.9

E.4

K.8

24 26

J.5

15' - 0"

10' - 0"

10' - 0"

10' - 0"

ELECTRICAL

MEDIA COORD.

G17B

LOBBY

G36

MALE

G37

FEMALE

G38

VESTIBULE

G35

SECURITY

G35A

HAC

G30I

PAT. RESOURCE

G40

STORAGE

G34A

SIM MAINTENANCE

G30G

PROCEDURE SIM LAB

G30F

CONTROL ROOM

G30E

TRNG EQUIP STOR

G30C

ALS CLASSROOM

G30J

MALE

G25

WAITING

G39

LACTATION

G27

MULTI-PURPOSE

G20J

MULTI-PURPOSE

G20F

MULTI-PURPOSE

G20D

MULTI-PURPOSE

G20B

MULTI-PURPOSE

G20

MULTI-PURPOSE

G20H

STOR.

G20A

STOR.

G20E

STOR

G20G

STOR.

G20I

STOR.

G20C

MED/SURG SIM LAB

G30D

VENDING

G32

STAFF LOUNGE

G33

KITCHEN/SERVING

G21

EDUC CHIEF

G17A

WORK

G17

RT SPVR.

G15A

COMPUTER LAB

G16

CREATIVE ARTS GROUP

G34

CORRIDOR

G48

CORRIDOR

G48A

CORRIDOR

G49

CORRIDOR

G50

CORRIDOR

G51

STORAGE

G20K

FEMALE

G24

MUSIC THER. 1

G43

MUSIC THER. 2

G42 CORRIDOR

G54

CORRIDOR

G52

ACCESS STAIR

G26

PMRS STORAGE

G31

327 SF

DE-BRIEF

G30A

361 SF

CORRIDOR

G30

177 SF

STORAGE

G30H

8' - 5" 10' - 0"

10' - 0"

10' - 0" 10' - 0"

16' - 0"

8' - 9"8' - 9"

16' - 0"

16' - 0"

16' - 0"

15' - 0"

16' - 0"

8' - 9" 8' - 9" 16' - 0" 8' - 9"

8' - 6"

10' - 0"

10' - 0"

8' - 5"

8' - 5"

8' - 5"

8' - 5"

8' - 5"

9' - 0"

11' - 5"

8' - 5"

8' - 1"

7' - 10"

8' - 0"

7' - 10"

9' - 0"

9' - 0"

9' - 0"

23 25

15' - 0"

10' - 0"

14' - 6"

10' - 0"

10' - 0"

10' - 0"

10' - 0"

8' - 5" 10' - 0"

10' - 0"

10' - 0"

10' - 0"

8' - 5"

10' - 0"

10' - 0" 10' - 0"

16' - 0"

16' - 0"8' - 9"8' - 9"

16' - 0"

16' - 0" 16' - 0"

9' - 0"

8' - 9"

16' - 0"

16' - 0"

15' - 0"

16' - 0"

16' - 0"

8' - 9"

8' - 9"

16' - 0"

16' - 0"

8' - 9" 8' - 9" 16' - 0" 8' - 9"

8' - 6"

10' - 0"

10' - 0"

8' - 5" 8' - 8"

8' - 5"

8' - 5"

8' - 5"

8' - 5"

8' - 5"

8' - 5"

9' - 0"

11' - 5"

8' - 5"

8' - 1"

8' - 0"

8' - 0"

7' - 10"

9' - 0"

8' - 8"

9' - 0"

8' - 8"

9' - 0"

9' - 0"

9' - 0"

8' - 4"

15' - 9"

15' - 0"

14' - 10"

9' - 0"

9' - 0"

CHARGING CART STOR.

G19

WHOLE HEALTH

STORAGE

G18

IT

G23

20 21

K.1

K.9

B.2

C.5

C.6

E.3

E.5

F.3

16.5 17.4 17.5 18.8 18.9 20.1 20.2 21.321.5

+ 8'-5"

13' - 7"

STORAGE

G30K

15' - 0"15' - 0" 15' - 0"

7' - 10"

8' - 0"

COORDINATE WITH

CLOUD CEILING FOR

SPRINKLER HEAD LAYOUT.

COORDINATE WITH

CLOUD CEILING FOR

SPRINKLER HEAD LAYOUT.

COORDINATE WITH

CLOUD CEILING FOR

SPRINKLER HEAD LAYOUT.

CHASE TO

MECH. ROOM

BELOW.

OCCUPANCY:

REFER TO THE LIFE SAFETY

PLANS.

ELECTRICAL ROOM

STORAGE

STORAGE

STORAGE

STORAGE STORAGE STORAGE STORAGE

STORAGE

STORAGE

JANITOR CLOSET

STORAGE

I.T. ROOM

COMM. ROOM

STORAGE

CLOSET

RETRACTABLE WALL

RETRACTABLE WALL

RETRACTABLE WALL

RETRACTABLE WALL

RETRACTABLE WALL

STORAGE

MULTI-PURPOSE

G20J

MULTI-PURPOSE

G20F

MULTI-PURPOSE

G20D

MULTI-PURPOSE

G20B

MULTI-PURPOSE

G20

MULTI-PURPOSE

G20H

STOR.

G20A

STOR.

G20E STOR

G20G

STOR.

G20I

STOR.

G20C

CORRIDOR

G49

CORRIDOR

G50

CORRIDOR

G51

STORAGE

G20K

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

AREA B

OUT OF

SCOPE

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h

/1

-P

L U

M B

-T V

H S

A C

Y V

A M

C I n te g ra te d

H e a lt h

C e n te r- R

.r v t

/1

/2

:0

:2

P

M

F-FX-01B

GROUND FLOOR - NEW WORK -

FIRE PROTECTION - AREA B

TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5/20/22 DRT

0 4' 8' 12'

1/8" = 1'-0"

1 GROUND FLOOR - RCP NEW WORK AREA B

THE EXISTING FIRE PROTECTION SYSTEM SHALL REMAIN ACTIVE DURING THE CONSTRUCTION

AND INSTALLATION OF THE NEW FIRE SPRINKLER SYSTEM. ONCE THE NEW SYSTEM IS

INSTALLED, CONNECTED TO THE WATER SOURCE, IS TESTED AND ACCEPTED BY THE AHJ THE

EXISTING SYSTEM CAN BE DEMOLISHED. THE BUILDING SHALL NOT BE WITH OUT FIRE

SPRINKLER PROTECTION AT ANY TIME DURING CONSTRUCTION EXCEPT FOR THE TIME OF

CONNECTING THE NEW SYSTEM AND DISCONNECTING THE EXISTING SYSTEM. PROVIDE 72

HOUR NOTICE TO THE OWNER PRIOR TO SYSTEM SHUT DOWNS. COORDINATION WITH THE

OWNER PRIOR TO SHUT DOWN OF THE EXISTING FIRE SPRINKLER SYSTEM IS REQUIRED TO

IMPLEMENT OTHER MEANS OF FIRE SAFETY FOR THE BUILDING.

TEMPORARY FIRE PROTECTION:

PROVIDE TEMPORARY HEAT DETECTORS, CONNECTED TO EXISTING FIRE ALARM SYSTEM TO

NOTIFY SYSTEM IN THE EVENT OF A FIRE IN SPACES UNDER CONSTRUCTION. HEAT

DETECTORS SHALL PROVIDE COMPLETE COVERAGE OF THE AREA UNDER CONSTRUCTION.

QUANTITIES AND SPACING SHALL NOT EXCEED MANUFACTURER’S RECOMMENDATIONS FOR

THE DETECTORS USED. PROVIDE A MINIMUM OF ONE (1) HEAT DETECTOR IN EVERY SPACE IN

THE AREA OF CONSTRUCTION FOR EVERY 900 SQUARE FEET (MAXIMUM). HEAT DETECTORS

AREAS/ROOMS ON THEIR RESPECTIVE DRAWINGS.

2. SPRINKLER CONTRACTOR TO SHOW LOCATION OF SPRINKLER RISER AND ALL

CONTROL AND TEST VALVES FOR THIS AREA.

3. PROVIDE DETAILED DRAWING OF THE MAIN SPRINKLER RISER AND ALARM

VALVE INCLUDING TAMPER AND FLOW SWITCH LOCATIONS. SHOW BACKFLOW

PREVENTER AND METHOD FOR FRONT FLOW TESTING IT. SHOW ALL DRAINS

DISCHARGING TO THE EXTERIOR OF THE BUILDING.

REC THERAPY BELOW

STAIR

NEW MECHANICAL

ROOM NEW STEAM WATER HEATER

ROOM.

STORAGE

STORAGE

STAIR

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

AREA A

OUT OF

SCOPE

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h

/1

-P

L U

M B

-T V

H S

A C

Y V

A M

C I n te g ra te d

H e a lt h

C e n te r- R

.r v t

/1

/2

:0

:2

P

M

F-FX-02A

SECOND FLOOR - NEW WORK

PLAN - FIRE PROTECTION - AREA

A

TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5/20/22 DRT

1/8" = 1'-0"

1 SECOND FLOOR - RCP NEW WORK AREA A

0 4' 8' 12'

THE EXISTING FIRE PROTECTION SYSTEM SHALL REMAIN ACTIVE DURING THE CONSTRUCTION

AND INSTALLATION OF THE NEW FIRE SPRINKLER SYSTEM. ONCE THE NEW SYSTEM IS

INSTALLED, CONNECTED TO THE WATER SOURCE, IS TESTED AND ACCEPTED BY THE AHJ THE

EXISTING SYSTEM CAN BE DEMOLISHED. THE BUILDING SHALL NOT BE WITH OUT FIRE

SPRINKLER PROTECTION AT ANY TIME DURING CONSTRUCTION EXCEPT FOR THE TIME OF

CONNECTING THE NEW SYSTEM AND DISCONNECTING THE EXISTING SYSTEM. PROVIDE 72

HOUR NOTICE TO THE OWNER PRIOR TO SYSTEM SHUT DOWNS. COORDINATION WITH THE

OWNER PRIOR TO SHUT DOWN OF THE EXISTING FIRE SPRINKLER SYSTEM IS REQUIRED TO

IMPLEMENT OTHER MEANS OF FIRE SAFETY FOR THE BUILDING.

TEMPORARY FIRE PROTECTION:

PROVIDE TEMPORARY HEAT DETECTORS, CONNECTED TO EXISTING FIRE ALARM SYSTEM TO

NOTIFY SYSTEM IN THE EVENT OF A FIRE IN SPACES UNDER CONSTRUCTION. HEAT

DETECTORS SHALL PROVIDE COMPLETE COVERAGE OF THE AREA UNDER CONSTRUCTION.

QUANTITIES AND SPACING SHALL NOT EXCEED MANUFACTURER’S RECOMMENDATIONS FOR

THE DETECTORS USED. PROVIDE A MINIMUM OF ONE (1) HEAT DETECTOR IN EVERY SPACE IN

THE AREA OF CONSTRUCTION FOR EVERY 900 SQUARE FEET (MAXIMUM). HEAT DETECTORS

AREAS/ROOMS ON THEIR RESPECTIVE DRAWINGS.

2. SPRINKLER CONTRACTOR TO SHOW LOCATION OF SPRINKLER RISER AND ALL

CONTROL AND TEST VALVES FOR THIS AREA.

3. PROVIDE DETAILED DRAWING OF THE MAIN SPRINKLER RISER AND ALARM

VALVE INCLUDING TAMPER AND FLOW SWITCH LOCATIONS. SHOW BACKFLOW

PREVENTER AND METHOD FOR FRONT FLOW TESTING IT. SHOW ALL DRAINS

DISCHARGING TO THE EXTERIOR OF THE BUILDING.

NEW MECHANICAL ROOM

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

AREA B

OUT OF

SCOPE

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h

/1

-P

L U

M B

-T V

H S

A C

Y V

A M

C I n te g ra te d

H e a lt h

C e n te r- R

.r v t

/1

/2

:0

:2

P

M

F-FX-02B

SECOND FLOOR - NEW WORK

PLAN - FIRE PROTECTION - AREA

B

TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5/20/22 DRT

1/8" = 1'-0"

1 SECOND FLOOR RCP NEW WORK AREA B

0 4' 8' 12'

THE EXISTING FIRE PROTECTION SYSTEM SHALL REMAIN ACTIVE DURING THE CONSTRUCTION

AND INSTALLATION OF THE NEW FIRE SPRINKLER SYSTEM. ONCE THE NEW SYSTEM IS

INSTALLED, CONNECTED TO THE WATER SOURCE, IS TESTED AND ACCEPTED BY THE AHJ THE

EXISTING SYSTEM CAN BE DEMOLISHED. THE BUILDING SHALL NOT BE WITH OUT FIRE

SPRINKLER PROTECTION AT ANY TIME DURING CONSTRUCTION EXCEPT FOR THE TIME OF

CONNECTING THE NEW SYSTEM AND DISCONNECTING THE EXISTING SYSTEM. PROVIDE 72

HOUR NOTICE TO THE OWNER PRIOR TO SYSTEM SHUT DOWNS. COORDINATION WITH THE

OWNER PRIOR TO SHUT DOWN OF THE EXISTING FIRE SPRINKLER SYSTEM IS REQUIRED TO

IMPLEMENT OTHER MEANS OF FIRE SAFETY FOR THE BUILDING.

TEMPORARY FIRE PROTECTION:

PROVIDE TEMPORARY HEAT DETECTORS, CONNECTED TO EXISTING FIRE ALARM SYSTEM TO

NOTIFY SYSTEM IN THE EVENT OF A FIRE IN SPACES UNDER CONSTRUCTION. HEAT

DETECTORS SHALL PROVIDE COMPLETE COVERAGE OF THE AREA UNDER CONSTRUCTION.

QUANTITIES AND SPACING SHALL NOT EXCEED MANUFACTURER’S RECOMMENDATIONS FOR

THE DETECTORS USED. PROVIDE A MINIMUM OF ONE (1) HEAT DETECTOR IN EVERY SPACE IN

THE AREA OF CONSTRUCTION FOR EVERY 900 SQUARE FEET (MAXIMUM). HEAT DETECTORS

PROVIDE NEW SPRINKLER PIPING AND SPRINKLER HEADS IN NEW

MECHANICAL SPACE. COORDINATE WITH MECHANICAL EQUIPMENT

AND DUCTWORK. THIS SPACE IS REQUIRED TO SUPPLY THE NEW

I.T. ROOM BELOW.

1. SPRINKLER CONTRACTOR TO INDICATE SPRINKLER DESIGN DENSITIES FOR ALL

AREAS/ROOMS ON THEIR RESPECTIVE DRAWINGS.

2. SPRINKLER CONTRACTOR TO SHOW LOCATION OF SPRINKLER RISER AND ALL

CONTROL AND TEST VALVES FOR THIS AREA.

3. PROVIDE DETAILED DRAWING OF THE MAIN SPRINKLER RISER AND ALARM

VALVE INCLUDING TAMPER AND FLOW SWITCH LOCATIONS. SHOW BACKFLOW

PREVENTER AND METHOD FOR FRONT FLOW TESTING IT. SHOW ALL DRAINS

DISCHARGING TO THE EXTERIOR OF THE BUILDING.

F-FI-01 - FIRE PROTECTION LEGENDS, DETAILS & NOTES
F-FD-01 - BASEMENT - DEMOLITION PLAN - FIRE PROTECTION OVERALL
F-FD-02 - GROUND FLOOR - DEMOLITION PLAN - FIRE PROTECTION OVERALL
F-FD-03 - SECOND FLOOR - DEMOLITION - FIRE PROTECTION
F-FX-01A - GROUND FLOOR - NEW WORK - FIRE PROTECTION - AREA A
F-FX-01B - GROUND FLOOR - NEW WORK - FIRE PROTECTION - AREA B
F-FX-02A - SECOND FLOOR - NEW WORK PLAN - FIRE PROTECTION - AREA A
F-FX-02B - SECOND FLOOR - NEW WORK PLAN - FIRE PROTECTION - AREA B