Attachment 11 - MECH BINDER-1.pdf

PDF 14 MB Posted

Attached to
Y1DA--626-309 Construct Integrated Health Center (Minor) - Murfreesboro
Solicitation number
36C77623B0037
Issued by

About this file

This document provides details for a federal contract opportunity to construct an integrated health center in Murfreesboro, Tennessee. The solicitation number is 36C77623B0037 and is being issued by the Department of Veterans Affairs Technology Acquisition Center in Austin, Texas. The project involves the construction of an integrated health center for veterans and has a description of "Project# 626-309 Construct Integrated Health Center." No other details are provided in the attached file such as response dates, award amounts, or requirements for the construction project.

View the file

Other files

File Type Posted
36C77623B0037 0008 - 8-29-23.pdf PDF
36C77623B0037 0007.pdf PDF
36C77623B0037 0006 - 8-22-23.pdf PDF
36C77623B0037 0005 - 8-18-23.pdf PDF
081710 integrated door assemblies - R2.pdf PDF
36C77623B0037 0004 - 08-15-2023.pdf PDF
Technical Questions Round 2 - 8-14-23.docx DOCX document
232113.13 FL - UNDERGROUND HYDRONIC PIPING.pdf PDF
2023-08-09 - IHC - Addendum 2.pdf PDF
IHC - Add 2 - Narrative.pdf PDF
36C77623B0037 0003 - 08-03-2023.pdf PDF
Technical Questions Tracking Spreadsheet - Murf IHC - 7-24-23.pdf PDF
VAMC - IHC - Addendum 1 - Dwgs.pdf PDF
36C77623B0037 0002.pdf PDF
Integrated Health Laydown Areas.pdf PDF
Attachment 17 - Construction Wage Rates - Rutherford County - 6-30-23.pdf PDF
Site Visit Sign In Sheet.pdf PDF
36C77623B0037 0001.docx DOCX document
Civil Binder.pdf PDF
Attachment 5 - CIVIL BINDER.pdf PDF
Attachment 19 - Site Visit Instructions.pdf PDF
36C77623B0037_1.docx DOCX document
Attachment 9 - GENERAL BINDER.pdf PDF
Attachment 3 - ARCHITECTURAL BINDER-1.pdf PDF
Attachment 2 - IHC - SPEC - VOLUME 2.pdf PDF
Attachment 8 - FP BINDER.pdf PDF
Attachment 18 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 7 - ELEC BINDER.pdf PDF
Attachment 1 - IHC - SPEC - VOLUME 1.pdf PDF
Attachment 13 - PLUMBING BINDER.pdf PDF
Attachment 15 - TECH BINDER.pdf PDF
Attachment 10 - INTERIORS BINDER.pdf PDF
Attachment 12 - MECH BINDER-2.pdf PDF
Attachment 17 - Construction Wage Rates.pdf PDF
Attachment 6 - DEMO BINDER1.pdf PDF
Attachment 4 - ARCHITECTURAL BINDER-2.pdf PDF
Attachment 14 - STRUCTURAL BINDER.pdf PDF
Attachment 16 - Limitations on Subcontracting - Construction Jan 2023 Deviation.docx DOCX document
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

U C c

GENERAL NOTES

1. ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A

FURRED CHASE OR ABOVE HARD SUSPENDED CEILING, OR ACOUSTICAL CEILING.

2. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR INDICATED.

DUCT SIZES ARE NET INSIDE DIMENSIONS.

3. ACCESS PANELS IN HARD SUSPENDED CEILINGS ARE REQUIRED FOR ALL VALVES, TRAPS,

DAMPERS, CLEANOUTS, CONTROLS, ETC. ACCESS PANELS SHALL BE FURNISHED AND

INSTALLED UNDER THE ARCHITECTURAL SPECIFICATIONS. COORDINATE LOCATION WITH

4. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES INCLUDES DUCT SYSTEM, TERMINAL

UNITS, FILTERS, COILS, ETC. LOSS FOR FILTERS SHALL BE FOR FILTERS AT 50% LOADING.

5. FOR TYPICAL STEAM AND WATER PIPING CONNECTIONS TO EQUIPMENT, SEE STANDARD

EQUIPMENT DETAILS.

6. DIFFUSER, REGISTER AND GRILLE SIZES SHOWN ON FLOOR PLANS ARE NECK SIZES.

7. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE MADE TO

PROVIDE COUNTER FLOW BETWEEN WATER AND AIR.

8. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF CEILING

DIFFUSERS, REGISTERS, AND GRILLES.

MECHANICAL INSTALLATION AND DEMONSTRATE ACCESS TO EQUIPMENT SERVED.

NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT

M

BD

P

M

TS

SYMBOL DESCRIPTIONSYMBOL DESCRIPTIONSYMBOL DESCRIPTION SYMBOL DESCRIPTION

SYMBOL DESCRIPTIONSYMBOL DESCRIPTIONSYMBOL DESCRIPTION

SYMBOL DESCRIPTION

24x12

24x12

-EXISTING FIRE DAMPER TO REMAIN

-EXISTING FIRE & SMOKE DAMPER TO REMAIN

-PACKAGED TERMINAL AIR CONDITIONER

(PTAC)

-HYDRONIC REHEAT COIL

-FLAT OVAL DUCT

(WITH ACCESS PANEL)

(WITH ACCESS PANEL)

-ELECTRIC DUCT HEATER

(W/ PANEL CLEARANCE)FM

-MANUAL BALANCING DAMPER

-AIR FLOW MEASURING STATION

-MOTOR OPERATED CONTROL DAMPER (MOD)

-FIRE & SMOKE DAMPER

-FIRE DAMPER

-FLEXIBLE CONNECTION

-ACCESS DOORS, VERTICAL OR HORIZONTAL

-INLINE CENTRIFUGAL FAN

-STAINLESS STEEL DUCTWORK

-DOOR GRILLE

-UNDERCUT DOOR

SA-1 -SOUND ATTENUATOR

-SPIN-IN TAKE-OFF

-DUCT ELBOW UP THROUGH ROOF OR SLAB ABOVE

-RECTANGLE-TO-ROUND TAKE-OFF

DNUP

-TRANSITION, SQUARE TO ROUND

UP W/IN FLOORDOWN

-CEILING EXHAUST

-CEILING RETURN

24x12

-STANDARD BRANCH TAKE-OFF

-RADIUS ELBOW

-TRANSITION, ECCENTRIC

-FLEXIBLE DUCT

-CHANGE OF ELEVATION

-DUCT ELBOW, NEGATIVE PRESSURE, RETURN

-DUCT ELBOW, EXHAUST

DIMENSION INDICATES SIDE TO WHICH ARROW IS POINTING

-DUCT ELBOW, POSITIVE PRESSURE (SUPPLY), FIRST

-NEW DUCTWORK, FIRST DIMENSION IS SIDE SHOWN -TRANSITION, CONCENTRIC

-SQUARE THROAT ELBOW

W/TURNING VANES

-RECTANGULAR/ROUND BRANCH TAKE-OFF

OR ROUND/ROUND BRANCH TAKE-OFF

-SQUARE THROAT TEE

-RADIUS TEE

-ROUND DIFFUSER

-SUPPLY REGISTER OR GRILLE

-RETURN/EXHAUST REGISTER OR GRILLE

(VERTICAL MOUNT, SIDEWALL)

(VERTICAL MOUNT, SIDEWALL)

-EXISTING DUCTWORK TO REMAIN

-EXISTING DUCTWORK TO BE REMOVED

(CEILING DIFFUSERS ARE 4-WAY THROW UNO)

-CEILING DIFFUSER, ROUND NECK

-CEILING DIFFUSER, RECTANGULAR OR

SQUARE NECK (CEILING DIFFUSERS

ARE 4-WAY THROW UNO)

M-1

-TEMPERATURE SENSOR

-MOTORIZED CONTROL DAMPER

-HUMIDISTAT/HUMIDITY SENSOR

-THERMOSTAT/TEMPERATURE SENSOR

-REVISION REFERENCE

-DETAIL REFERENCE: TOP-DETAIL#,

BOTTOM-DRAWING# SHOWN ON

-PRESSURE SENSOR

-DUCT SMOKE DETECTOR

-CONNECT TO EXISTING

-DEMOLISH TO POINT INDICATED FF -FINAL FILTERS

DDC -DIRECT DIGITAL CONTROLS

PRS -PRESSURE REDUCING STATION

SP -STATIC PRESSURE

-CFM (CUBIC FEET PER MINUTE)

P -CHANGE IN PRESSURE

CV -CONSTANT AIR VOLUME

-ROOFTOP AIR HANDLING UNITRTU

RS/L -REFRIGERANT SUCTION & LIQUID LINES

h

-OUTSIDE AIR LOUVEROAL

-VARIABLE AIR VOLUMEVAV

-SUPPLY AIRSA

-ROOFTOP HEAT PUMPRHP

-REHEAT COILRHC

-REVOLUTIONS PER MINUTERPM

-RETURN AIRRA

-POLYVINYL CHLORIDE PIPEPVC

-PSI GAUGEPSIG

-POUNDS PER SQUARE INCHPSI

-PRESSURE REDUCING VALVEPRV

-OUTSIDE AIROA

-NOT TO SCALENTS

-NORMALLY OPENNO

-NORMALLY CLOSEDNC

-LINEAR DIFFUSERLD

-LOW PRESSURE STEAMLPS

-LEAVING AIR TEMPERATURELAT

-GALLONS PER MINUTEGPM

-FEET PER MINUTE

-FIRE DAMPER

-FAN COIL UNIT

-ENTERING WATER TEMPERATURE

-ENTERING AIR TEMPERATURE

-DOWN

-CONDENSING UNIT

-CUBIC FEET PER MINUTE

-CHANGE IN TEMPERATURE

-COOLING TOWER

-CEILING DIFFUSER

-CENTER LINE

-BRITISH THERMAL UNIT

-BRAKE HORSEPOWER

-BOTTOM OF PIPE

-ACCESS PANEL

-ABOVE FINISHED FLOOR

FPM

FD

FCU

EWT

EAT

DN

CU

CFM

T

CT

CD

BTU

BOP

BHP

AP

AFF

-AIR HANDLING UNITAHU

MBH -THOUSAND BTUs PER HOUR

AFD -ADJUSTABLE FREQUENCY DRIVE

ESP -EXTERNAL STATIC PRESSURE

KW -KILOWATT

MCA -MINIMUM CIRCUIT AMPS

MOCP -MAXIMUM OVER CURRENT PROTECTION

UNO

TSP -TOTAL STATIC PRESSURE

-VOLTS/PHASEV/PH

VFD -VARIABLE FREQUENCY DRIVE

-UNLESS NOTED OTHERWISE

FLA -FULL LOAD AMPS

-CONTROL VALVE

-45° PIPE RISE (R) / DROP (D)

-CONDENSER WATER SUPPLY

-CONDENSER WATER RETURN

-CHILLED WATER SUPPLY

-CHILLED WATER RETURN

-CONDENSATE

-HOT WATER RETURN

-HOT WATER SUPPLY

-REFRIGERANT LIQUID

-REFRIGERANT SUCTION

-VALVE ON RISER

-CAP

-CONNECTION, BOTTOM

-CONNECTION, TOP

-COUPLING

-ELBOW, 90°

-ELBOW, 45°

-ELBOW, TURNED DOWN

-ELBOW, TURNED UP

-TEE, OUTLET DOWN

-TEE, OUTLET UP

CWS

CWR

CHWS

CHWR

RL

RS

-FLOW SWITCH

-CHECK VALVE

-PSI REG.

-SOLENOID VALVE

-STRAINER

-GAS COCK

-BUTTERFLY VALVE

-CALIBRATING BALANCING VALVE

-BALL VALVE

-GATE VALVE

-UNION

PC -PUMPED CONDENSATE

DD

-HIGH PRESSURE STEAM SUPPLY

-LOW PRESSURE STEAM SUPPLY

-MEDIUM PRESSURE STEAM SUPPLY

CR -CONDENSATE RETURN

-SLOPE DIRECTION (DOWN)

-FLEX CONNECTION

-O.S.&Y. GATE VALVE

-THREE-WAY MODULATING CONTROL VALVE

-THERMOMETER

- P-TRAP

-TWO-WAY CHECK VALVE

EQUIP.

-MANUAL VENT

-PRESSURE GAUGE

-RELIEF VALVE

-FLOW METER

-WATER METER

-INLINE PUMP

-INLINE PUMP

-NEGATIVE RELATIVE PRESSURE

-POSITIVE RELATIVE PRESSURE

-NEUTRAL RELATIVE PRESSURE

-HIGH PRESSURE STEAM RETURN

-LOW PRESSURE STEAM RETURN

-MEDIUM PRESSURE STEAM RETURN

-BACKDRAFT DAMPER

MOD -MOTOR OPERATED CONTROL DAMPER (MOD)

-PACKAGED TERMINAL AIR CONDITIONERPTAC

-PIPE ANCHORS

-CONCENTRIC REDUCER

-ECCENTRIC REDUCER

-STEAM TRAP

-FLOW DIRECTION

-SHEET NOTE CALLOUT

-SHEET NOTE CALLOUT

-SHEET NOTE CALLOUT

-EXHAUST DUCT UP THROUGH SLAB TO

-CENTRIFUGAL EXHAUST FAN ON ROOF

-CEILING MOUNTED ACCESS DOOR

-RECTANGULAR DUCT SECTION UP, EXHAUST

-RECTANGULAR DUCT SECTION UP,

-RECTANGULAR DUCT SECTION UP, POSITIVE PRESSURE,

-ROUND DUCT SECTION UP

-FLAT OVAL DUCT SECTION UP

SUPPLY OR OUTSIDE AIR

NEGATIVE PRESSURE, RETURN

FAN ON ROOF ABOVE

-ABOVE FINISHED ROOFAFR

-TERMINAL UNIT, VARIABLE/CONSTANT AIR

VOLUME WITH ELECTRIC HEAT

-TERMINAL UNIT, VARIABLE/CONSTANT AIR

-TERMINAL UNIT, VARIABLE/CONSTANT AIR

VOLUME, FAN POWERED

VOLUME, FAN POWERED, WITH ELECTRIC

HEAT

-TERMINAL UNIT, VARIABLE/CONSTANT AIR

12x8

HVAC GENERAL NOTESHVAC ABBREVIATIONSHVAC SYMBOL LEGEND

HVAC PIPING SYMBOL LEGEND

8Ø10x8

24x12

12x8

HPS

MPS

LPS

CD

HWR

HWS

HPR

MPR

LPR

H

VOLUME WITH ELECTRIC HEAT

S

MV

FM

M

1. CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH MANUFACTURER'S CERTIFIED

DRAWINGS. TRANSITIONS TO ALL EQUIPMENT SHALL BE VERIFIED AND PROVIDED

FOR EQUIPMENT FURNISHED.

2. DIMENSIONS SHALL BE FIELD-VERIFIED AND COORDINATED PRIOR TO PROCUREMENT OR

FABRICATION. COORDINATE THE WORK WITH OTHER TRADES INVOLVED. FIELD MODIFICATIONS

SUCH AS OFFSETS IN PIPING OR DUCTWORK (INCLUDING DIVIDED DUCTWORK) NEEDED DUE TO

OBSTRUCTIONS OR INTERFERENCES SHALL BE PROVIDED AT NO ADDITIONAL COST. FOR PROJECTS

INVOLVING RENOVATION, COORDINATE NEW WORK WITH EXISTING ELEMENTS SUCH AS THE

BUILDING STRUCTURE AND ARCHITECTURAL FEATURES, SPRINKLER PIPING, LIGHTS, PLUMBING, AND

ELECTRICAL CONDUIT.

3. DUCT CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE

SMACNA HVAC DUCT CONSTRUCTION STANDARD.

4. SEE SPECIFICATIONS FOR GAUGES, THICKNESS, BRACING, REQUIREMENTS, ETC., OF DUCTWORK.

5. PROVIDE AIR TURNING VANES IN ALL 90 DEGREE RECTANGULAR DUCT ELBOWS.

6. DUCT SIZES AND ALL OPENINGS THROUGH BUILDING CONSTRUCTION SHALL SUIT EQUIPMENT

FURNISHED.

7. COORDINATE DIFFUSER, GRILLE AND REGISTER LOCATIONS WITH ARCHITECTURAL

REFLECTED CEILING PLANS AND EQUIPMENT OF ALL TRADES.

8. LOCATE THERMOSTATS, TEMPERATURE SENSORS, HUMIDISTATS, AND HUMIDITY SENSORS AT ABOUT 48" TO 55" ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. COORDINATE LOCATIONS WITH OTHER

EQUIPMENT, LIGHT SWITCHES, FURNITURE, AND DOOR SWINGS.

9. ALL EQUIPMENT, DUCTWORK, ETC., SHALL BE SUPPORTED AS DETAILED AND/OR SPECIFIED. PROVIDE

ADDITIONAL SUPPORTS AS REQUIRED TO PROVIDE A VIBRATION-FREE, RIGID INSTALLATION.

10. ALL DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS.

11. DAMPERS AND INSIDES OF DUCTS VISIBLE THROUGH GRILLES, REGISTERS AND DIFFUSERS SHALL BE

PAINTED FLAT BLACK.

12. REFER TO TYPICAL DETAILS FOR PIPING AND INSTALLATION OF EQUIPMENT.

13. TRAPPED CONDENSATE DRAINS FROM ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED FOR

PROPER DRAINAGE TO SUIT EQUIPMENT FURNISHED.

14. ACCESS PANELS IN DUCTWORK AND CEILINGS SHALL BE PROVIDED WHERE REQUIRED FOR

OPERATION, BALANCING OR MAINTENANCE OF ALL MECHANICAL EQUIPMENT.

15. ALL DUCTWORK AND PIPING IS SHOWN SCHEMATICALLY. PROVIDE ALL TRANSITIONS, TURNING VANES, ELBOWS, FITTINGS, ETC., TO ALLOW SMOOTH FLOWS. ALL SPLIT DUCT FITTINGS SHALL

TRANSITION TO FULL SIZE OF THE SUM OF BOTH BRANCHES, UPSTREAM OF SPLIT.

16. PROVIDE CONCRETE HOUSEKEEPING PAD UNDER ALL FLOOR-MOUNTED EQUIPMENT. REFER TO

SPECIFICATIONS FOR DETAILED REQUIREMENTS.

17. VERIFY FINISH WITH ARCHITECT PRIOR TO PURCHASING GRILLES, REGISTERS, DIFFUSERS, LOUVERS

AND OTHER AIR DISTRIBUTION DEVICES.

18. PROVIDE FLEXIBLE DUCT CONNECTIONS ON ALL DUCTWORK CONNECTING TO EACH FAN, AIR

HANDLING UNITS, AND FAN COIL UNITS.

19. PROVIDE TRANSITIONS AT DIFFUSER NECKS AS REQUIRED TO MATCH SIZES OF FLEX DUCTS TO BE

CONNECTED.

20. INTERRUPTIONS TO EXISTING SERVICES SHALL BE SCHEDULED FOR TIMES OTHER THAN NORMAL OPERATING HOURS (SUCH AS NIGHTS AND WEEKENDS). SUCH INTERRUPTIONS TO SERVICES SHALL

NOT BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER'S REPRESENTATIVE AND

PROPER COORDINATION WITH OTHER TRADES. PRE-WORK SHALL BE PERFORMED TO MAKE THE

SHUTDOWN PERIOD AS BRIEF AS POSSIBLE.

21. ALL EQUIPMENT, DUCTWORK, ETC., TO BE REMOVED SHALL BE DISPOSED OF LEGALLY.

22. MAINTAIN CLEARANCE OF A MINIMUM OF 6" BETWEEN DUCTWORK, PIPING, EQUIPMENT, ETC., AND ALL FIRE RATED AND FIRE/SMOKE RATED PARTITIONS, TO ALLOW FOR INSPECTIONS OF RATED WALLS.

23. LOCATE ALL OUTSIDE AIR INTAKES A MINIMUM OF 25' CLEAR FROM ALL PLUMBING VENTS AND

EXHAUST AIR DISCHARGE LOCATIONS.

24. DUCT RUNOUTS TO DIFFUSERS SHALL MATCH THE SIZE OF THE DIFFUSER NECK.

25. WATER PRESSURE DROPS THROUGH COIL CONTROL VALVES SHALL NOT EXCEED 5 PSI.

26. UNLESS OTHERWISE NOTED, ALL EQUIPMENT AND VALVE DRAINS SHALL BE INDEPENDENTLY PIPED

FULL SIZE TO THE NEAREST PLUMBING DRAIN.

27. SLEEVE AND SEAL ALL PIPING PENETRATIONS THROUGH BUILDING PARTITIONS. PROVIDE MANUAL AIR

VENTS AT ALL HIGH POINTS IN CHILLED WATER AND HOT WATER PIPING.

28. PIPING, DUCTWORK, LEAK PROTECTION APPARATUS, OR OTHER EQUIPMENT FOREIGN TO ELECTRICAL SWITCHBOARDS, PANELBOARDS, DISTRIBUTION BOARDS, OR MOTOR CONTROL CENTERS SHALL NOT BE INSTALLED WITHIN THE REQUIRED SPACE FOR WORKING CLEARANCES OR DEDICATED SPACES OF THE ELECTRICAL EQUIPMENT, EXTENDING IN FRONT OF AND FROM FLOOR TO STRUCTURAL CEILING WITH A WIDTH AND DEPTH OF THE ELECTRICAL EQUIPMENT IN ACCORDANCE WITH NEC-110.26.

T

200A

RHC-1-1

AHU-1

VTU-1-1

CTU - CONSTANT TERMINAL UNIT

VARIABLE/CONSTANT AIR VOLUME TERMINAL UNITS

VTU - VARIABLE TERMINAL UNIT

PTU - PARALLEL TERMINAL UNIT

STU - SERIES TERMINAL UNIT

-AIR HANDLING UNIT

-REHEAT COIL

-AIR DISTRIBUTION DEVICE

HVAC EQUIPMENT TAGS

TAG

CFM

AHU NUMBER

AHU NUMBER COIL NUMBER

AHU NUMBER

TERMINAL NUMBER

TERMINAL UNIT TYPE

75 UC -UNDERCUT DOOR, 75 CFM

T/H -TEMPERATURE & HUMIDITY MONITOR

DP -DIFFERENTIAL PRESSURE SENSOR

-EXISTING PIPE TO REMAIN

-EXISTING PIPE TO BE REMOVED

VTR -VENT THRU ROOF

-LEAVING WATER TEMPERATURELWT

-MEDIUM PRESSURE STEAMMPS

• SCOPE OF WORK INDICATED HEREIN FOR THIS DISCIPLINE DOES NOT INDICATE SPECIFIC

REQUIREMENTS RELATED TO PHASING OF WORK, ALTHOUGH EVERY EFFORT HAS BEEN

MADE TO INCORPORATE SEQUENTIAL PHASES OF WORK AS REQUESTED BY THE

GOVERNMENT.

• PUBLIC AND STAFF ACCESS TO BUILDINGS 7, 107 AND 116 SHALL NOT BE INTERRUPTED AT

ANY TIME DURING CONSTRUCTION.

• CANTEEN, KITCHEN, AND GIFT SHOP NORMAL OPERATION SHALL NOT BE INTERRUPTED AT

ANY TIME DURING CONSTRUCTION.

• REFER TO SHEET GI 01.30 FOR FURTHER INFORMATION ON PROJECT PHASING

REQUIREMENTS.

CONSTRUCTION PHASING / PUBLIC AND

STAFF ACCESS, BUSINESS OPERATIONS:

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h /1

-M

E C

H -T

V H

S A

C Y

V A

M C

I n te g ra te d H e a lt h C e n te r- R

.r v t

/1

/2

:1

:1

A

M

M-MK-01

LEGENDS, NOTES, AND SYMBOLS TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5-20-2022 JE

MECHANICAL SHEET INDEX

SHEET DESCRIPTION

M-MK-01 LEGENDS, NOTES, AND SYMBOLS

M-MK-02 SCHEDULES

M-MK-03 SCHEDULES

M-MK-04 SCHEDULES

M-MK-05 SCHEDULES (EXISTING EQUIPMENT)

M-MK-06 SCHEDULES

M-MD-01 BASEMENT OVERALL - HVAC DEMO

M-MD-02 GROUND FLOOR OVERALL - HVAC DEMO

M-MD-03 SECOND FLOOR OVERALL - HVAC DEMO

M-MD-04 ROOF OVERALL - HVAC DEMO

M-MD-05 AHU-34 & 35 EXISTING PLANS

M-MH-00 BASMENT OVERALL - DUCTWORK

M-MH-01 GROUND FLOOR OVERALL - DUCTWORK

M-MH-01A GROUND FLOOR AREA A - DUCTWORK

M-MH-01B GROUND FLOOR AREA B - DUCTWORK

M-MH-02 SECOND FLOOR OVERALL - DUCTWORK

M-MH-02A SECOND FLOOR AREA A - DUCTWORK

M-MH-02B SECOND FLOOR AREA B - DUCTWORK

M-MH-03 ROOF PLAN OVERALL - DUCTWORK

M-MH-03.1 ROOF PLAN OVERALL 3D

M-MH-03A ROOF PLAN AREA A - DUCTWORK

M-MH-03B ROOF PLAN AREA B - DUCTWORK

M-MH-04 SECTIONS

M-MP-00 BASEMENT OVERALL - PIPING

M-MP-00A BASEMENT AREA A - PIPING

M-MP-00B BASEMENT AREA B - PIPING

M-MP-01 GROUND FLOOR OVERALL - PIPING

M-MP-01A GROUND FLOOR AREA A - PIPING

M-MP-01B GROUND FLOOR AREA B - PIPING

M-MP-02 SECOND FLOOR OVERALL - PIPING

M-MP-02A SECOND FLOOR AREA A - PIPING

M-MP-02B SECOND FLOOR AREA B - PIPING

M-MJ-01 MECHANICAL DETAILS

M-MJ-02 MECHANICAL DETAILS

M-MJ-03 MECHANICAL DETAILS

M-MJ-04 MECHANICAL DETAILS

M-MJ-05 MECHANICAL DETAILS

M-MI-01 MECHANICAL CONTROLS

M-MI-02 MECHANICAL CONTROLS

M-MI-03 MECHANICAL CONTROLS

M-MI-04 MECHANICAL CONTROLS

M-MI-05 MECHANICAL CONTROLS

M-MI-06 MECHANICAL CONTROLS

M-MI-07 MECHANICAL CONTROLS

M-MI-08 MECHANICAL CONTROLS

Revisions: Date:

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h /1

-M

E C

H -T

V H

S A

C Y

V A

M C

I n te g ra te d H e a lt h C e n te r- R

.r v t

/1

/2

:1

:1

A

M

M-MK-02

SCHEDULES TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5-20-2022 JERevisions: Date:

P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h /1

-M

E C

H -T

V H

S A

C Y

V A

M C

I n te g ra te d H e a lt h C e n te r- R

.r v t

/1

/2

:1

:1

A

M

M-MK-03

SCHEDULES TVHS - ALVIN C. YORK VAMC -

P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h /1

-M

E C

H -T

V H

S A

C Y

V A

M C

I n te g ra te d H e a lt h C e n te r- R

.r v t

/1

/2

:1

:4

A

M

M-MK-04

SCHEDULES TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5-20-2022 JERevisions: Date:

NOTE:

THE VA REQUIRES ALL VFD'S TO HAVE A SECONDARY BACKUP VFD SO IF THE PRIMARY VFD FAILS, AN ALARM WILL BE SENT TO THE BAS AND THE SECONDARY VFD WILL BE ENERGIZED. PROVIDE SECONDARY BACKUP VFD FOR ALL VFD'S

SCHEDULED.

P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h /1

-M

E C

H -T

V H

S A

C Y

V A

M C

I n te g ra te d H e a lt h C e n te r- R

.r v t

/1

/2

:1

:2

A

M

M-MK-05

SCHEDULES (EXISTING

EQUIPMENT)

TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5-20-2022 JE

THIS SHEET CONTAINS THE SCHEDULES FOR EXISTING AHU-34, AHU-35, AND OTHER EXISTING EQUIPMENT IN MECHANICAL ROOM G11 FOR REFERENCE ONLY

P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h /1

-M

E C

H -T

V H

S A

C Y

V A

M C

I n te g ra te d H e a lt h C e n te r- R

.r v t

/1

/2

:1

:2

A

M

M-MK-06

SCHEDULES TVHS - ALVIN C. YORK VAMC -

EXISTING PIPE TUNNEL

EXISTING PIPE TUNNEL

EXISTING PIPE TUNNEL

EXISTING POOL

REMOVE 1-1/2" LPS FROM PRV-1 TO STAGE FINTUBES, PRV-1 TO REMAIN SERVING CORRIDOR RADITORS

REMOVE 3" STEAM FROM AHU'S DOWN TO TUNNEL

PHOTO # 1 PHOTO # 2 PHOTO # 3

2-1/2" CHWS & CHWR UP TO

AHU-37 SERVING CANTEEN

AREA TO REMAIN

REMOVE ALL PIPING AND EQUIPMENT

ASSOCIATED WITH POOL FILTRATION AND

HEATING, SEE PHOTO # 1, 2, & 3 ON THIS

SHEET. REMOVE ALL PIPING AND

EQUIPMENT NO LONGER IN SERVICE.

PHOTO # 4

SURGE TANK

REMOVE EXISTING AHU AND ALL

ASSOCIATED PIPING AND DUCTWORK,

SEE PHOTO # 4 ON THIS SHEET.

REMOVE EXISTING SURGE

TANK AND ALL ASSOCIATED

PIPING, SEE PHOTO # 4 ON

THIS SHEET.

PHOTO # 5

REMOVE EXISTING

VENTILATION & EXHAUST DUCT

ALONG WITH EXH FAN AND

VENT DUCT ON ROOF, SEE

PHOTO # 5 & 6 ON THIS SHEET.

PHOTO # 6

REMOVE EXISTING STEAM PIPING UP

TO GYM.

REMOVE EXISTING DUCT UP THRU

SLAB AND BACK TO UNIT.

EXISTING STEAM AND CONDENSATE

ROUTED UPSTAIRS TO REMAIN

EXISTING STEAM PRV TO REMAIN

REMOVE 1" DRAIN FROM WATER HEATER, REMOVE WATER HEATER AND ALL ASSOCIATED PIPING

REMOVE 2" LPS FROM PRV-3 TO WATER HEATER, REMOVE PRV-3

REMOVE 1-1/4" LPR FROM AHU'S DOWN TO TUNNEL

1-1/2" DOM HOT WATER DOWN TO TUNNEL

2" DOM COLD WATER DOWN TO TUNNEL

5" CHWS UP TO AHU 35 TO REMAIN

5" CHWR UP TO AHU 35 TO REMAIN, SEE PHOTO # 2 ON SHEET M-MD-03 FOR REFERENCE

4" STM VENT THRU ROOF, REROUTE AS NEEDED

APPROXIMATE LOCATION OF

EXISTING PRV-1

APPROXIMATE LOCATION OF

EXISTING PRV-2

APPROXIMATE LOCATION OF

EXISTING PRV-3. REMOVE PRV-3

WHICH SERVES DOMESTIC WATER

HEATER ON SECOND FLOOR, SEE

PHOTO # 1 ON SHEET M-MD-03.

NEW WATER HEATERS TO BE

INSTALLED BEFORE OLD IS

REMOVED, SEE PLUMBING.

APPROXIMATE LOCATION OF

EXISTING PRV-4

REMOVE EXISTING STEAM VENT UP

THRU ROOF, VENT TO BE REROUTED

EXISTING FLASH TANK TO REMAIN

REMOVE ALL PIPING AND

EQUIPMENT IN CRAWL SPACE

ASSOCIATED WITH POOL THAT

IS NOT BEING USED, SEE

PHOTO # 7. CLEAN OUT ALL

TRASH AND DEBRIS.

SEE PHOTO # 8 ON THIS SHEET

FOR INFORMATION ON EXISTING

PRV'S FROM 1958 DRAWINGS AND

PHOTO # 10 FOR 1958 STEAM PIPE

DIAGRAM.

EXISTING PIPING IN TUNNEL TO REMAIN,

SEE PHOTO # 9

REMOVE 1-1/2" STEAM FROM

PRV-1 TO STAGE FINN TUBES

EXISTING 3" VAC RETURN

EXISTING 8" MED PRESS STEAM

EXISTING 2-1/2" DRIP RETURN

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

AREA A

AREA B

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h /1

-M

E C

H -T

V H

S A

C Y

V A

M C

I n te g ra te d H e a lt h C e n te r- R

.r v t

/1

/2

:1

:0

A

M

M-MD-01

BASEMENT OVERALL - HVAC

DEMO

TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5-20-2022 JBE

0 8' 16' 32'4'

GENERAL DEMOLITION NOTES:

1. THE DEMOLITION PLAN IS INTENDED TO PROVIDE THE CONTRACTOR WITH A GENERAL KNOWLEDGE OF THE EXISTING CONDITIONS WITHIN THE PROJECT AREA. EXISTING EQUIPMENT, STRUCTURE, DUCTWORK, ETC. LOCATED ON DRAWING MAY NOT BE ALL INCLUSIVE OF SERVICES THAT EXIST IN THE PROJECT AREA. CONTRACTOR SHALL VERIFY SERVICES AND LOCATIONS PRIOR TO ANY DEMOLITION WORK. ANY DEVIATIONS IMPACTING WORK SHOWN ON THESE DOCUMENTS SHALL BE REPORTED TO THE ARCHITECT AND ENGINEER PRIOR TO BEGINNING DEMOLITION. START UP OF DEMOLITION SHALL SIGNIFY CONTRACTORS ACCEPTANCE OF EXISTING CONDITIONS.

THE CONTRACTOR IS RESPONSIBLE FOR ALL REQUIRED DEMOLITION WHETHER SHOWN ON THE PLANS OR NOT.

2. CONTRACTOR SHALL PERFORM A PRE-BID SURVEY TO FIELD-VERIFY AND COORDINATE ALL DIMENSIONS PROIR TO PROCUREMENT OR FABRICATION. FIELD CONDITIONS SHALL GOVERN. COORDINATE THE WORK WITH OTHER TRADES INVOLVED. COORDINATE NEW WORK WITH EXISTING ELEMENTS SUCH AS THE BUILDING STRUCTURE AND ARCHITECTURAL FEATURES, SPRINKLER PIPING, LIGHTS, PLUMBING, ELECTRICAL CONDUIT, AND PNEUMATIC TUBING. THE COST OF REROUTING DUCTWORK OR PIPING DUE TO CONFLICTS WITH EXISTING CONDITIONS SHALL

BE PAID BY THE CONTRACTOR.

3. ALL MECHANICAL SYSTEMS SERVING OTHER SPACES OR FLOORS THAT RUN THROUGH THE PROJECT AREA SHALL REMAIN ACTIVE DURING CONSTRUCTION SO AS NOT TO CAUSE ANY DISRUPTION TO THE OTHER SPACES. ALL

MECHANICAL SYSTEMS IN THE RENOVATION SPACE WHICH ARE INACTIVE SHALL BE REMOVED.

4. CONTRACTOR SHALL PROVIDE MECHANICAL WORK FOR PHASING AS REQUIRED OR DIRECTED BY THE ARCHITECT, REFER TO ARCHITECTURAL PHASING PLAN, TEMPORARY MECHANICAL SERVICES SHALL BE PROVIDED WHEN NEW

WORK AFFECTS SERVICES NEEDED TO REMAIN ACTIVE.

5. ALL ITEMS REMOVED UNDER THIS PROJECT SHALL BE DISPOSED OF.

6. CONTRACTOR SHALL REMOVE EXISTING THERMOSTATS IN RENOVATION SPACE. REMOVED THERMOSTATS SHALL

BE DISPOSED OF.

7. PROPERLY REMOVE AND DISPOSE OF ALL INDICATED EXISTING TO BE REMOVED HVAC DUCTWORK, PIPING, AND AIR

DISTRIBUTION DEVICES.

8. PATCH HOLES LEFT IN WALLS AND FLOORS AFTER REMOVAL OF EXISTING DUCTWORK, CONDUIT, ETC… TO MATCH

NEW OR EXISTING CONSTRUCTION AND FIRE RATING. THIS INCLUDES ANY EXISTING OPENINGS IN RATED WALLS OR

FLOORS.

9. PROVIDE TEMPORARY CONSTRUCTION FILTERS FOR ALL AIR DISTRIBUTION DEVICES LOCATED WITHIN SCOPE OF

WORK.

10. PROVIDE TEMPORARY NEGATIVE AIR MACHINE FOR CONSTRUCTION AREA. MAINTAIN A NEGATIVE PRESSURE IN THE AREA RELATIVE TO THE ADJACENT SPACES AT A MINIMUM OF -0.03” W.C. PROVIDE TEMPORARY DUCT BARRIER PARTITIONS. FAN TO BE EQUIVALENT TO HEPA-AIRE PAS1200HC, 800 CFM, ¼ HP, 120 VOLT. PROVIDE AS MANY MACHINES AS NECESSARY TO MAINTAIN NEGATIVE PRESSURE REQUIREMENT. REFERENCE ARCHITECTURAL PLANS

FOR ADDITIONAL INFORMATION CONCERNING ICRA.

1/16" = 1'-0"

1 BASEMENT OVERALL - HVAC DEMO

PHOTO # 7

PHOTO # 8

PHOTO # 9

PHOTO # 10

FROM ORIGINAL PLANS, FOR REFERENCE ONLY

UP

J

I I

H

G

F

E

D

C

B

A

10987

11 12

135.1 10.25.2

H1

F3

F2

E1

I2

H3

G1

12.511.5

9.57.5

15 16 17 18 19 22

F4

F1

E2

D1

C1

B1

H2

I1

I3

K

L

15.1 15.2 17.1 17.2

00 01 02 03

7.1 9.1

4.5

5.5

ELECTRICAL

STAIRS

20 21

KEY NOTES: (APPLIES TO THIS SHEET ONLY)#

1. REMOVE EXISTING DX CONDENSING UNIT ON GRADE

2. REMOVE EXISTING INDOOR DX DUCTLESS WALL MOUNTED AC UNIT & PIPING

3. REMOVE 3" STEAM VENT FROM BASEMENT UP THRU ROOF

4. REMOVE EXISTING WALL LOUVER AND PATCH OPENING TO MATCH EXISTING

5. REMOVE 5" CHILLED WATER SUPPLY AND RETURN FROM THIS POINT UP TO

FLOOR ABOVE AND REROUTE AS SHOWN ON NEW WORK PLANS

6. VERIFY LOCATION OF STEAM VENT AND REROUTE AS NEEDED.

7. REMOVE PIPING DOWN TO BASEMENT

8. REMOVE AIR COMPRESSOR AFTER INSTALLING NEW AIR COMPRESSOR IN

CHILLER PLANT, SEE PHOTO # 2.

9. REMOVE FAN AND ALL ASSOCIATED DUCTWORK, CAP CURB ON ROOF WITH

INSULATED CAP

10. REMOVE RADIANT STEAM HEATING, CONDENSATE RETURN, AND ALL

ASSOCIATED PIPING

11. REMOVE REFRIGERATED AIR DRYER

12. REMOVE CHILLED WATER PIPING BACK TO SHUTOFF VALVES.

13. REMOVE ELECTRIC HEATER AND ALL ASSOCIATED HARDWARE

14. EXISTING STEAM AND CONDENSATE PIPING TO REMAIN

15. REMOVE EXISTING DUCT THRU ROOF AND CAP CURB

16. REMOVE EXISTING WALL GRILLE

17. REMOVE LOUVER AND PNEUMATIC DAMPER.

18. REMOVE EXISTING WALL LOUVER, ARCHITECT TO PATCH OPENING WITH

SPANDREL.

19. REMOVE RETURN DUCT AND PATCH FLOOR SLAB.

20. REMOVE EXISTING WALL LOUVER AND REPLACE WITH NEW.

21. REMOVE WALL DAMPER AND PATCH TO MATCH EXISTING.

22. REMOVE EXISTING CHILLED WATER PUMPS AND ASSOCIATED PIPING.

23. CAP OFF EXISTING CHILLED WATER PIPING DOWN LOW.

24. THE VA REQUESTED THE METAL FENCE BE REMOVED.

25. REMOVE STAGE VENTS, CAP CURB ON ROOF w/INSULATED CAP.

26. REMOVE ALL DUCTWORK IN AUDITORIUM.

107-AHU-34

AHU-35 ON ROOF 8

ASSUMED LOCATION OF

EXISTING UNDERGROUND 5"

CHILLED WATER SUPPLY

AND RETURN PIPING, SEE

PHOTO # 6.

EXISTING UNDERGROUND 3"

CHILLED WATER SUPPLY

AND RETURN PIPING TO

BUILDING 6

ASSUMED LOCATION OF

EXISTING UNDERGROUND 4"

CHILLED WATER PIPING TO

BUILDING 107, CONTRACTOR

TO FIELD VERIFY. REMOVE IF

POSSIBLE OR ABANDON IN

PLACE .

EXISTING UNDERGROUND

2-1/2" CHILLED WATER

SUPPLY AND RETURN PIPING

TO BUILDING 118

EXISTING UNDERGROUND

10" CHILLED WATER SUPPLY

AND RETURN PIPING TO

CAMPUS LOOP

REMOVE 1-1/2" LPS FROM PRV-1 TO STAGE FINTUBES

REMOVE 3" STEAM FROM AHU'S DOWN TO TUNNEL

REMOVE 1" DRAIN FROM WATER HEATER

REMOVE 2" LPS FROM PRV-3 TO WATER HEATER, REMOVE PRV-3

REMOVE 1-1/4" LPR FROM AHU'S DOWN TO TUNNEL

REMOVE 1-1/2" DOM HOT WATER DOWN TO TUNNEL

REMOVE 2" DOM COLD WATER DOWN TO TUNNEL

4" STM VENT FROM TUNNEL

4" STM VENT THRU

ROOF, FIELD VERIFY

LOCATION

SEE PHOTO #1

17 17

SEE PHOTO #5

SEE PHOTO #3

SEE PHOTO #4

SEE SHEET M-MD-05

FOR EXISTING LAYOUT

OF THIS AREA

REMOVE PIPING AND CAP OFF

REMOVE ALL PNEUMATIC

CONTROL TUBING IN RENOVATION

AREA AND CAP OFF

GIFT SHOP

CANTEEN

KITCHEN AREA

CHILLER PLANT

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

AREA A

AREA B

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h /1

-M

E C

H -T

V H

S A

C Y

V A

M C

I n te g ra te d H e a lt h C e n te r- R

.r v t

/1

/2

:1

:1

A

M

M-MD-02

GROUND FLOOR OVERALL - HVAC

DEMO

TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5-20-2022 JBE

0 8' 16' 32'4'

1/16" = 1'-0"

1 GROUND FLOOR OVERALL - HVAC DEMO

GENERAL DEMOLITION NOTES:

1. THE DEMOLITION PLAN IS INTENDED TO PROVIDE THE CONTRACTOR WITH A

GENERAL KNOWLEDGE OF THE EXISTING CONDITIONS WITHIN THE PROJECT

AREA. EXISTING EQUIPMENT, STRUCTURE, DUCTWORK, ETC. LOCATED ON

DRAWING MAY NOT BE ALL INCLUSIVE OF SERVICES THAT EXIST IN THE

PROJECT AREA. CONTRACTOR SHALL VERIFY SERVICES AND LOCATIONS

PRIOR TO ANY DEMOLITION WORK. ANY DEVIATIONS IMPACTING WORK SHOWN

ON THESE DOCUMENTS SHALL BE REPORTED TO THE ARCHITECT AND

ENGINEER PRIOR TO BEGINNING DEMOLITION. START UP OF DEMOLITION

SHALL SIGNIFY CONTRACTORS ACCEPTANCE OF EXISTING CONDITIONS. THE

CONTRACTOR IS RESPONSIBLE FOR ALL REQUIRED DEMOLITION WHETHER

SHOWN ON THE PLANS OR NOT.

2. CONTRACTOR SHALL PERFORM A PRE-BID SURVEY TO FIELD-VERIFY AND

COORDINATE ALL DIMENSIONS PROIR TO PROCUREMENT OR FABRICATION.

FIELD CONDITIONS SHALL GOVERN. COORDINATE THE WORK WITH OTHER

TRADES INVOLVED. COORDINATE NEW WORK WITH EXISTING ELEMENTS SUCH

AS THE BUILDING STRUCTURE AND ARCHITECTURAL FEATURES, SPRINKLER

PIPING, LIGHTS, PLUMBING, ELECTRICAL CONDUIT, AND PNEUMATIC TUBING.

THE COST OF REROUTING DUCTWORK OR PIPING DUE TO CONFLICTS WITH

EXISTING CONDITIONS SHALL BE PAID BY THE CONTRACTOR.

3. ALL MECHANICAL SYSTEMS SERVING OTHER SPACES OR FLOORS THAT RUN

THROUGH THE PROJECT AREA SHALL REMAIN ACTIVE DURING CONSTRUCTION

SO AS NOT TO CAUSE ANY DISRUPTION TO THE OTHER SPACES. ALL

MECHANICAL SYSTEMS IN THE RENOVATION SPACE WHICH ARE INACTIVE

SHALL BE REMOVED.

4. CONTRACTOR SHALL PROVIDE MECHANICAL WORK FOR PHASING AS

REQUIRED OR DIRECTED BY THE ARCHITECT, REFER TO ARCHITECTURAL

PHASING PLAN, TEMPORARY MECHANICAL SERVICES SHALL BE PROVIDED

WHEN NEW WORK AFFECTS SERVICES NEEDED TO REMAIN ACTIVE.

5. ALL ITEMS REMOVED UNDER THIS PROJECT SHALL BE DISPOSED OF.

6. CONTRACTOR SHALL REMOVE EXISTING THERMOSTATS IN RENOVATION

SPACE. REMOVED THERMOSTATS SHALL BE DISPOSED OF.

7. PROPERLY REMOVE AND DISPOSE OF ALL INDICATED EXISTING TO BE

REMOVED HVAC DUCTWORK, PIPING, AND AIR DISTRIBUTION DEVICES.

8. PATCH HOLES LEFT IN WALLS AND FLOORS AFTER REMOVAL OF EXISTING

DUCTWORK, CONDUIT, ETC… TO MATCH NEW OR EXISTING CONSTRUCTION

AND FIRE RATING. THIS INCLUDES ANY EXISTING OPENINGS IN RATED WALLS

OR FLOORS.

9. PROVIDE TEMPORARY CONSTRUCTION FILTERS FOR ALL AIR DISTRIBUTION

DEVICES LOCATED WITHIN SCOPE OF WORK.

10. PROVIDE TEMPORARY NEGATIVE AIR MACHINE FOR CONSTRUCTION AREA.

MAINTAIN A NEGATIVE PRESSURE IN THE AREA RELATIVE TO THE ADJACENT

SPACES AT A MINIMUM OF -0.03” W.C. PROVIDE TEMPORARY DUCT BARRIER

PARTITIONS. FAN TO BE EQUIVALENT TO HEPA-AIRE PAS1200HC, 800 CFM, ¼

HP, 120 VOLT. PROVIDE AS MANY MACHINES AS NECESSARY TO MAINTAIN

NEGATIVE PRESSURE REQUIREMENT. REFERENCE ARCHITECTURAL PLANS

FOR ADDITIONAL INFORMATION CONCERNING ICRA.

PHOTO # 1 PHOTO # 2 PHOTO # 3 PHOTO # 4

DAMPER

PHOTO # 5

REMOVE EXISTING AIR

COMPRESSOR, REMOVE ALL

INACTIVE PNEUMATIC PIPING

IN RENOVATED AREAS AND

CAP

REMOVE EXISTING

REFRIGERATED AIR DRYER

NEW AIR COMPRESSOR TO BE INSTALLED AND

ACTIVATED BEFORE OLD IS REMOVED.

PHOTO # 6

ROOF BELOW

ROOF BELOW

ROOF BELOW

REC THERAPY BELOW

STAIR

STUDIO

FAN ROOM

GENERATOR

RM

REWIND RM PROJECTION ROOM CONTROL RM AMP RM

C O

R R

ID

O

R

AMATEUR

RADIO ROOM

JANITOR

J

I

H

G

F

E

D

C

B

10976

54321

11 12

10.2

H1

F3

F2

E1

I2

12.511.5

9.57.5

15 16

17 18 19

F4

F1

E2

D1

C1

B1

H2

I1

I3

K

L

15.1 15.2

1400 01 02 03

THIS SECTION OF

CHILLED WATER PIPING

TO BE REMOVED AND

REROUTED, SEE NEW

WORK PLANS

REMOVE DUCTWORK DOWN

FROM ABOVE AND PATCH

FLOOR AND ROOF OPENINGS

REMOVE KITCHEN WATER HEATER AND ALL

ASSOCIATED PIPING, WAIT TILL NEW WATER

HEATER IS INSTALLED FIRST. REMOVE OLD

HEAT EXCHANGER AND ALL ASSOCIATED

PIPING. SEE PHOTO # 1

REMOVE AIR HANDLER # 36

AND ALL ASSOCIATED

DUCTWORK AND PIPING

KEY NOTES: (THIS SHEET ONLY)#

1. REMOVE ALL SUPPLY, RETURN, AND EXHAUST DUCT IN THIS SPACE

2. CONTRACTOR TO DETERMINE WHICH PNEUMATIC LINES SERVE THE

CANTEEN AND KITCHEN AREA AND KEEP THOSE LINES ACTIVE, REROUTE

AS NEEDED TO ACCOMODATE NEW FLOOR PLAN. REMOVE ALL THE

PNEUMATIC LINES SERVING EQUIPMENT TO BE DEMOLISHED.

3. EQUIPMENT TO BE REMOVED

EXISTING PIPING

SERVING AHU-35 TO

REMAIN

AHU-37 CANTEEN UNIT ON ROOF TO

REMAIN. VERIFY CHILLED WATER

FLOW BEFORE DEMOLITION AND

REBALANCE TO PRE DEMOLITION

FLOW AFTER WORK IS COMPLETE

3 3 3

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

AREA A

AREA B

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h /1

-M

E C

H -T

V H

S A

C Y

V A

M C

I n te g ra te d H e a lt h C e n te r- R

.r v t

/1

/2

:1

:1

A

M

M-MD-03

SECOND FLOOR OVERALL - HVAC

DEMO

TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5-20-2022 JBE

1/16" = 1'-0"

1 SECOND FLOOR OVERALL - HVAC DEMO

0 8' 16' 32'4'

PHOTO # 1

PHOTO # 2

CANTEEN UNIT AHU-37 AUDITORIUM UNIT

AHU-36

AUDITORIUM UNIT

AHU-36

OLD UNIT AHU-35

THIS WAS WHEN THE OLD CHILLED WATER SYSTEM HAD

A CHILLER WHERE AHU-34 IS LOCATED NOW BEFORE THE

SYSTEM WAS CONNECTED TO THE CAMPUS CHILLED

WATER LOOP

KEY NOTES: (THIS SHEET ONLY)

1. REMOVE FAN ON ROOF AND CAP CURB

2. REMOVE EXISTING DUCT DOWN THRU ROOF AND CAP CURB

3. REMOVE EXISTING STEAM VENT PIPING AND REROUTE

4. REMOVE EXISTING ROOF VENTS AND CAP CURB

5. REMOVE EXISTING LOUVER

6. REMOVE EXISTING DAMPER

7. EXISTING RTU TO REMAIN

8. EXISTING OUTSIDE AIR INTAKE TO REMAIN

1 1

107-AHU-35

RTU-M107

444444

SEE PHOTO # 1

SEE PHOTO # 2

SEE PHOTO # 6

SEE PHOTO # 7

SEE PHOTO # 4

SEE PHOTO # 5

6 6

SEE PHOTO # 3

SEE PHOTO # 8

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

AREA A

AREA B

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h /1

-M

E C

H -T

V H

S A

C Y

V A

M C

I n te g ra te d H e a lt h C e n te r- R

.r v t

/1

/2

:1

:2

A

M

M-MD-04

ROOF OVERALL - HVAC DEMO TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5-20-2022 JBE

0 8' 16' 32'4'

GENERAL DEMOLITION NOTES:

1. THE ONLY MECHANICAL HVAC WORK REQUIRED ON THIS FLOOR IS TO PROVIDE A PATH

WAY FOR THE VENTILATION DUCTWORK REQUIRED ON THE THIRD FLOOR TO CONNECT TO

FANS AND EQUIPMENT ON THE ROOF AND TO CREATE CHASES TO ENCLOSE THE NEW

DUCTWORK REQUIRED.

2. THE DEMOLITION PLAN IS INTENDED TO PROVIDE THE CONTRACTOR WITH A GENERAL

KNOWLEDGE OF THE EXISTING CONDITIONS WITHIN THE PROJECT AREA. EXISTING

EQUIPMENT, STRUCTURE, DUCTWORK, ETC. LOCATED ON DRAWING MAY NOT BE ALL

INCLUSIVE OF SERVICES THAT EXIST IN THE PROJECT AREA. CONTRACTOR SHALL VERIFY

SERVICES AND LOCATIONS PRIOR TO ANY DEMOLITION WORK. ANY DEVIATIONS IMPACTING

WORK SHOWN ON THESE DOCUMENTS SHALL BE REPORTED TO THE ARCHITECT AND

ENGINEER PRIOR TO BEGINNING DEMOLITION. START UP OF DEMOLITION SHALL SIGNIFY

CONTRACTORS ACCEPTANCE OF EXISTING CONDITIONS. THE CONTRACTOR IS

RESPONSIBLE FOR ALL REQUIRED DEMOLITION WHETHER SHOWN ON THE PLANS OR NOT.

3. CONTRACTOR SHALL PERFORM A PRE-BID SURVEY TO FIELD-VERIFY AND COORDINATE ALL

DIMENSIONS PROIR TO PROCUREMENT OR FABRICATION. FIELD CONDITIONS SHALL

GOVERN. COORDINATE THE WORK WITH OTHER TRADES INVOLVED. COORDINATE NEW

WORK WITH EXISTING ELEMENTS SUCH AS THE BUILDING STRUCTURE AND ARCHITECTURAL

FEATURES, SPRINKLER PIPING, LIGHTS, PLUMBING, ELECTRUCAL CONDUIT, AND PNEUMATIC

TUBING. THE COST OF REROUTING DUCTWORK OR PIPING DUE TO CONFLICTS WITH

EXISTING CONDITIONS SHALL BE PAID BY THE CONTRACTOR.

4. ALL MECHANICAL SYSTEMS SERVING OTHER SPACES OR FLOORS THAT RUN THROUGH THE

PROJECT AREA SHALL REMAIN ACTIVE DURING CONSTRUCTION SO AS NOT TO CAUSE ANY

DISRUPTION TO THE OTHER SPACES. ALL MECHANICAL SYSTEMS THAT RUN INTO THE

SPACE BUT DO NOT SERVE ANYTHING SHALL BE REMOVED BACK TO WHERE THEY ENTER

THE SPACE TO FREE-UP VALUABLE CLREANCE FOR NEW DUCT AND PIPING.

5. CONTRACTOR SHALL PROVIDE MECHANICAL WORK FOR PHASING AS REQUIRED OR

DIRECTED BY THE ARCHITECT, REFER TO ARCHITECTURAL PHASING PLAN, TEMPORARY

MECHANICAL SERVICES SHALL BE PROVIDED WHEN NEW WORK AFFECTS SERVICES

NEEDED TO REMAIN ACTIVE.

6. ALL ITEMS REMOVED UNDER THIS PROJECT SHALL BE DISPOSED OF.

7. PROVIDE TEMPORARY NEGATIVE AIR MACHINES FOR CONSTRUCTION AREA. MAINTAIN A

NEGATIVE PRESSURE IN THE AREA RELATIVE TO THE ADJACENT SPACES AT A MINIMUM

OF -0.03” W.C. PROVIDE SHEET ROCK TYPE WALL BARRIER PARTITIONS WITH AIR TIGHT OR

LOW LEAKAGE CONSTRUCTION ACCESS. FAN TO BE EQUIVALENT TO HEPA-AIRE PAS1200HC,

800 CFM, ¼ HP, 120 VOLT. PROVIDE AS MANY MACHINES AS NECESSARY TO MAINTAIN

NEGATIVE PRESSURE REQUIREMENT IN RENOVATION SPACE. REFERENCE ARCHITECTURAL

PLANS FOR ADDITIONAL INFORMATION CONCERNING ICRA.

PHOTO # 4 PHOTO # 5 PHOTO # 6

PHOTO # 7

1/16" = 1'-0"

1 ROOF PLAN OVERALL - HVAC DEMO

PHOTO # 1

PHOTO # 2 PHOTO # 3REMOVE LIGHTNING PROTECTION

AND REINSTALL ON NEW INTAKE

HOOD. (TYP OF 2)

PHOTO # 8

P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h /1

-M

E C

H -T

V H

S A

C Y

V A

M C

I n te g ra te d H e a lt h C e n te r- R

.r v t

/1

/2

:1

:2

A

M

M-MD-05

AHU-34 & 35 EXISTING PLANS TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5-20-2022 JBE

PARTIAL EXISTING DUCT PLAN - AHU-34

PARTIAL EXISTING PIPE PLAN - AHU-34

PARTIAL EXISTING PIPE PLAN - AHU-35

PARTIAL EXISTING DUCT PLAN - AHU-35

NOTE:

EXISTING PLANS SHOWN ON THIS SHEET SHOW THE EXISTING

DUCTWORK AND PIPING ASSOCIATED WITH AHU-34 AND AHU-35 PRIOR

TO ANY RENOVATION, AND IS FOR REFERENCE ONLY.

J

II

H

G

F

E

D

C

B

A

10987

4321 11 12

5.1

10.2

5.2

H1

F3

F2

E1

I2

H3

G1

12.511.5

9.57.5

15 16 17 18 19 22

K

L

15.1 15.2 17.1 17.2

00 01 02 03

7.1

9.1

4.5

5.5

20 21

B 150016x16 UP TO EXHAUST

FAN ON ROOF

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

AREA A

AREA B

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h /1

-M

E C

H -T

V H

S A

C Y

V A

M C

I n te g ra te d H e a lt h C e n te r- R

.r v t

/1

/2

:1

:2

A

M

M-MH-00

BASMENT OVERALL - DUCTWORK TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5-20-2022 JBE

1/16" = 1'-0"

1 BASEMENT OVERALL - DUCTWORK

0 8' 16' 32'4'

UP

J

I I

G

F

E

D

C

B

A

10987

4321 11 12

5.1 10.25.2

H1

F3

F2

E1

I2

H3

G1

12.511.5

9.5 7.5

15 16 17 18 19 22

F4

F1

E2

D1

C1

B1

H2

I1

I3

K

L

15.1 15.2 17.1 17.2

00 01 02 03

7.1 9.1

ELECTRICAL

G41

SIM MAINTENANCE

G30G

PROCEDURE SIM LAB

G30FCONTROL ROOM

G30E

WAITING

G39

MULTI-PURPOSE

G20J

MULTI-PURPOSE

G20F

MULTI-PURPOSE

G20D

MULTI-PURPOSE

G20B

MULTI-PURPOSE

G20

MULTI-PURPOSE

G20H

STOR.

G20C

MED/SURG SIM LAB

G30D KITCHEN/SERVING

G21

EDUC CHIEF

G17A

MUSIC THERAPY CLINIC

G13

WC STORAGE

G12B

REC. THERAPY CLINIC

G08

COMPUTER LAB

G16

STOR.

G20A

STOR.

G20E

STOR

G20G

STOR.

G20I

BARBER CART

G02FOOD SERVICE CHIEF

G03

FOOD SERVICE VEND SUPPLY

G04

CORRIDOR

G54

CORRIDOR

G52

MUSIC THER. 1

G43

MUSIC THER. 2

G42

CORRIDOR

G45

WORK AREA

G15

ENTRY

G01

CORRIDOR

G46

COURTYARD

G10

CORRIDOR

G48

CORRIDOR

G48A

CORRIDOR

G49

CORRIDOR

G50

CORRIDOR

G51

STORAGE

G20K

4.5

5.5

PRACTICE ROOM

G13B

MUSIC STORAGE

G13A

ALS CLASSROOM

G30J

TRNG EQUIP STOR

G30C

STAFF LOUNGE

G33

CREATIVE ARTS GROUP

G34

LOBBY

G36

PMRS STORAGE

G31

ACCESS STAIR

G26

FEMALE

G24

MALE

G25

LACTATION

G27

HAC

G30I

MALE

G37

FEMALE

G38

MEDIA COORD.

G17B

WORK

G17

PAT. RESOURCE

G40

RT SPVR.

G15A

PMRS CONSULT

G14

HAC

G07

RECREATION

STORAGE

G08B

MALE

G09A

FEMALE

G09C

COPIER

COPIER

VENDING

G32

KINESIO GROUP THERAPY

G12

COPIERSAFE

WORK

G12A

KITCHENETTE

G08A

VESTIBULE

G35

SECURITY

G35A

STORAGE

G34A

CORRIDOR

G55

STORAGE

G30K

STORAGE

G30H

DE-BRIEF

G30A

CORRIDOR

G30 CORRIDOR

G30

CONNECTOR

G47

FEMALE SHOWER

G09D

MALE SHOWER

G09B

ENTRY

G44

CORRIDOR

G53

CHARGING CART STOR.

G19WHOLE HEALTH

STORAGE

G18

IT

G23

20 21

CHASE

G26A

CLO.

G30B

COMM/MEDIA CONTROL

G22

RISER

G13D

MECH.

G11

ELEC.

G28

ELEC.

G29

MECH.

G11A

STAIRS

G09

CORRIDOR

G46

107-CAC-1

NEW CONTROL AIR

COMPRESSOR UP ON

MEZZANINE LEVEL

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

AREA A

AREA B

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h /1

-M

E C

H -T

V H

S A

C Y

V A

M C

I n te g ra te d H e a lt h C e n te r- R

.r v t

/1

/2

:1

:4

A

M

M-MH-01

GROUND FLOOR OVERALL -

DUCTWORK

TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5-20-2022 JBE

1/16" = 1'-0"

1 GROUND FLOOR OVERALL - DUCTWORK

1. ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A

FURRED CHASE OR ABOVE HARD SUSPENDED CEILING, OR ACOUSTICAL CEILING.

2. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR INDICATED.

DUCT SIZES ARE NET INSIDE DIMENSIONS.

3. ACCESS PANELS IN HARD SUSPENDED CEILINGS ARE REQUIRED FOR ALL VALVES, TRAPS,

DAMPERS, CLEANOUTS, CONTROLS, ETC. ACCESS PANELS SHALL BE FURNISHED AND

INSTALLED UNDER THE ARCHITECTURAL SPECIFICATIONS. COORDINATE LOCATION WITH

MECHANICAL INSTALLATION AND DEMONSTRATE ACCESS TO EQUIPMENT SERVED.

4. FOR TYPICAL WATER PIPING CONNECTIONS TO EQUIPMENT, SEE STANDARD EQUIPMENT

DETAILS.

5. DIFFUSER, REGISTER AND GRILLE SIZES SHOWN ON FLOOR PLANS ARE CFM's, REFER TO

AIR DISTRIBUTION DEVICE SCHEDULE FOR ADDITIONAL INFORMATION.

6. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE MADE TO

PROVIDE COUNTER FLOW BETWEEN WATER AND AIR.

7. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF

CEILING DIFFUSERS, REGISTERS, AND GRILLES.

GENERAL NOTES:

0 8' 16' 32'4'

J

I

F

E

D

C

B

A

11 12

5.1 10.25.2

F3

F2

E1

I2

H3

G1

12.511.5

9.57.5

F4

F1

E2

D1

C1

B1

7.1 9.1

E.9

10.1 12.911.9

E.4

AREA BAREA A

A R

E A

B

A R

E A

A

B.2

C.5

C.6

E.3

E.5

F.3

STAIRS

REC. THERAPY CLINIC

G08

BARBER CART

G02

FOOD SERVICE CHIEF

G03

CORRIDOR

G45

ENTRY

G01

CORRIDOR

G46

FOOD SERVICE VEND SUPPLY

G04

612 SF

CONNECTOR

G47

KITCHENETTE

G08A

MUSIC THERAPY CLINIC

G13

MUSIC STORAGE

G13A

WORK

G12A

EDUC CHIEF

G17A

RECREATION

STORAGE

G08B

HAC

G07

KINESIO GROUP THERAPY

G12

WC STORAGE

G12B

MALE

G09A

FEMALE

G09C

COURTYARD

G10

WORK AREA

G15

PRACTICE ROOM

G13B

PMRS CONSULT

G14

CHASE

G-104A

MALE SHOWER

G09B

FEMALE SHOWER

G09D

CLEAN

G12C

SOILED

G12D

MECH.

G11A

MECH.

G11

ELEC.

G28

ELEC.

G29

KEY NOTES: (THIS SHEET ONLY)

1. UNITED McGILL UNI-RIB-k27 DOUBLE WALL INSULATED DUCT (SPIRAL LOCKSEAM WITH STANDING RIB) 12" INSIDE DIAMETER WITH 1" INSULATION THICKNESS, 24 GAUGE GALVANIZED STEEL WITH END

CAP, PAINTED GLOSS WHITE OR AS INDICATED ON ARCHITECTURAL DRAWINGS. (TYP OF 2)

2. UNITED McGILL MODEL DDF-RUDDW 12x6 DOUBLE DEFLECTION REGISTER, WHITE, 215 CFM. (TYP OF

4) REGISTER TO BE MOUNTED IN SOFFIT FACE.

3. COORDINATE DUCT ROUTING WITH ROOF DRAIN PIPING & SPRINKLER PIPING IN THIS AREA. SEE PHOTO # 1 ON THIS SHEET SHOWING EXISTING ROOF DRAIN AND FIRE MAIN PIPING IN THIS AREA.

DUCT TO BE ROUTED IN SOFFIT, SEE ARCHITECTURAL DRAWINGS.

D 860 x1

12ø

12ø

12ø

A 270

A 195 A 195 A 195

A 195

A 195

A 195

A 195 A 195

A 150A 155 A 155

A 155

A 185

A 190 A 185

A 250 A 250

A 50

A 150

A 65

A 150

A 150

A 300 A 300

A 300 A 300

A 300

A 300

A 300 A 300

A 300

A 300A 300

A 300

A 300 A 300 A 300

A 110

B 100

B 400

B 400

B 100

B 250

B 100

A 260 A 260 A 260 A 260

A 110

A 75

A 300 A 300

A 250 A 250

A 250

A 250

V36-10

V36-9

V36-7

V36-6

V36-4

V36-3 V36-5

V36-2

V36-1

A 155

B 560 B 500

B 270

B 880

B 875

V35-1

V35-2

V35-3

V35-4

V35-10

V35-8

V35-9

V35-12

V35-11

V35-5

V35-7

V35-6 x1 x1

48x14

V36-8

10x38 SWR 8" A.F.F.

14x14 14x12 12x12 10ø30x818x12

107-EH-1

6" ROUND DOWN TO 12"x3" AND EXTEND THRU

SLATS, TRIM BOTTOM EDGE OF 12X3 TO BE EVEN

WITH BOTTOM OF SLATS, PAINT TO MATCH

SLATS, SEE CORRIDOR G-056 VIEW ON THIS

SHEET. BALANCE FOR 97 CFM. VERIFY WIDTH

BETWEEN SLATS BEFORE FABRICATING. (TYP.

OF 6)

x1 x1

8x

14x12

B 1000

20x14 14x14 x1 x1 x1 x1 x1

20x14 14x14 x1

UC100 UC65

U C

B 75B 110

B 110 x1

A 200

FIRE MAIN DOWN

THRU FLOOR

107-BAF-4107-BAF-3

107-BAF-5 107-BAF-6

107-BAF-1 107-BAF-2

x1 x1 x1

B 1500

B 1500

B 1500

U C

B 65

A 440

B 300 UC100

UC100

UC100

FLATTEN DUCT AS SHOWN AND ROUTE DUCT

DOWN TIGHT TO WALL IN FUR-OUT, SEE

ARCHITECTURAL PLANS FOR COORDINATION.

12x12 x1

12x8 14x6 x1

UP TO

EXHAUST FAN

ON ROOF

12x1010x10

8x10

10x12

20x10

16x10 14x10 10x10

8ø 10x10

10x10

16x12

12x12 x1

20x10 x1

14x10 8ø

16x10

14x10

10x10

8x10

18x12 12x8

8ø

B 600

B 700 x1

40x12

107-CHWP-1

& 2

VFD

107-RAF-34

107-AHU-34

107-CRU-1

EXISTING HEAT

EXCHANGERS

EXISTING HOT

WATER PUMPS

CONTRACTOR TO BE RESPONSIBLE FOR

REBALANCING EXISTING UNIT TO NEW AIR

FLOW AND STATIC PRESSURE TO MEET

NEW REQUIREMENTS. PROVIDE ALL

NECESSARY COMPONENTS TO ACOMPLISH

PROPER OPERATION

x8

12x12

6ø

8ø

14x14

18x12

12x3

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

AREA A

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h /1

-M

E C

H -T

V H

S A

C Y

V A

M C

I n te g ra te d H e a lt h C e n te r- R

.r v t

/1

/2

:1

:2

A

M

M-MH-01A

GROUND FLOOR AREA A -

DUCTWORK

TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5-20-2022 JE

0 4' 8' 12'

1/8" = 1'-0"

1 GROUND FLOOR AREA A - DUCTWORK

EXISTING ROOF DRAIN PIPE

EXISTING SPRINKLER PIPE

PHOTO # 1

NOT TO SCALE

CORRIDOR G-056 VIEW

ROUTE 6" ROUND DOWN AND TRANSITION TO 12"x3"

AND EXTEND THRU SLATS IN CEILING. TRIM BOTTOM

EDGE OF 12x3 TO MATCH PROFILE OF SLATS AND TO

BE FLUSH WITH SURFACE, PAINT VISIBLE DUCTWORK

TO MATCH COLOR OF SLATS.

I

H

F

G1

17 18 19 22

F4

F1

E2

D1

C1

B1

H2

I1

I3

K

L

15.1 15.2 17.1 17.2

MEDIA COORD.

G17B

LOBBY

G36

MALE

G37

FEMALE

G38

VESTIBULE

G35

SECURITY

G35A

58 SF

HAC

G30I

PAT. RESOURCE

G40

STORAGE

G34A

SIM MAINTENANCE

G30G

PROCEDURE SIM LAB

G30F

CONTROL ROOM

G30E

TRNG EQUIP STOR

G30C

499 SF

ALS CLASSROOM

G30J

MALE

G25

WAITING

G39

LACTATION

G27

MULTI-PURPOSE

G20J

MULTI-PURPOSE

G20F

MULTI-PURPOSE

G20D

MULTI-PURPOSE

G20B

MULTI-PURPOSE

G20

MULTI-PURPOSE

G20H

STOR.

G20A

STOR.

G20E STOR

G20G

STOR.

G20I

STOR.

G20C

MED/SURG SIM LAB

G30D

VENDING

G32

STAFF LOUNGE

G33

KITCHEN/SERVING

G21

EDUC CHIEF

G17A

WORK

G17

RT SPVR.

G15A

COMPUTER LAB

G16

CREATIVE ARTS GROUP

G34

CORRIDOR

G48

CORRIDOR

G48A

CORRIDOR

G49

CORRIDOR

G50

CORRIDOR

G51

STORAGE

G20K

FEMALE

G24

MUSIC THER. 1

G43 MUSIC THER. 2

G42

CORRIDOR

G54

CORRIDOR

G52

ACCESS STAIR

G26

PMRS STORAGE

G31

C O

P

IE

R

327 SF

DE-BRIEF

G30A

361 SF

CORRIDOR

G30

177 SF

STORAGE

G30H

65 SF

STORAGE

G30K

AREA BAREA A

A R

E A

B

A R

E A

A

C O

R R

ID

O

R T

O B

LD

G

217 SF

CORRIDOR

G30

WHOLE HEALTH

STORAGE

G18 m a n e q u in s to ra g e r a c k

CHARGING CART STOR.

G19

CORRIDOR

G53

IT

G23

20 21

CONNECTOR

G47

CHASE

G26A

CLO.

G30B

COMM/MEDIA CONTROL

G22

ELECTRICAL

G41

CORRIDOR

G45

C 190

F 155

(TYP. OF 12)

(TYP. OF 6)

A 175 A 175 A 120

A 215

C 400

A 70

A 175

A 100

A 205

A 100

A 200

A 170A 170

A 170

A 40

A 175

A 175

A 175

A 155

A 175

A 175

A 175

A 100 A 150

A 150 A 260A 260

A 75

A 150

A 140

A 75

A 190 A 190

A 175

A 100 A 200

A 100A 250

A 250

A 250

A 250

A 250 A 250

A 250

A 250

A 250A 250

A 200

A 100

D 800 C 700D 700

A 215

A 205

A 190

16x8 x6

B 400

B 200 18x20

DOWN TO

16x44 SWR 8" A.F.F.

2000 CFM

B 330

B 330

B 100

B 175

B 525

B 40

B 510

B 175

B 175

D 400

16x10

16x10

20x10

B 120

B 70

B 570

B 1685

B 260

B 260

B 300

B 350

B 75

A 100

A 240A 195A 195

A 150

A 245

A 245

A 150

A 50

A 110

A 200

A 175

A 175 A 200 A 200

A 200

A 125 A 125

A 60A 60 A 60

A 50

A 180 A 100

A 550

A 550

A 550

A 450

A 450

A 550

A 550

A 550

A 550

A…