This document provides details for a federal contract opportunity to construct an integrated health center in Murfreesboro, Tennessee. The solicitation number is 36C77623B0037 and is being issued by the Department of Veterans Affairs Technology Acquisition Center in Austin, Texas. The project involves the construction of an integrated health center for veterans and has a description of "Project# 626-309 Construct Integrated Health Center." No other details are provided in the attached file such as response dates, award amounts, or requirements for the construction project.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
U C c
GENERAL NOTES
1. ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A
FURRED CHASE OR ABOVE HARD SUSPENDED CEILING, OR ACOUSTICAL CEILING.
2. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR INDICATED.
DUCT SIZES ARE NET INSIDE DIMENSIONS.
3. ACCESS PANELS IN HARD SUSPENDED CEILINGS ARE REQUIRED FOR ALL VALVES, TRAPS,
DAMPERS, CLEANOUTS, CONTROLS, ETC. ACCESS PANELS SHALL BE FURNISHED AND
INSTALLED UNDER THE ARCHITECTURAL SPECIFICATIONS. COORDINATE LOCATION WITH
4. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES INCLUDES DUCT SYSTEM, TERMINAL
UNITS, FILTERS, COILS, ETC. LOSS FOR FILTERS SHALL BE FOR FILTERS AT 50% LOADING.
5. FOR TYPICAL STEAM AND WATER PIPING CONNECTIONS TO EQUIPMENT, SEE STANDARD
EQUIPMENT DETAILS.
6. DIFFUSER, REGISTER AND GRILLE SIZES SHOWN ON FLOOR PLANS ARE NECK SIZES.
7. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE MADE TO
PROVIDE COUNTER FLOW BETWEEN WATER AND AIR.
8. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF CEILING
DIFFUSERS, REGISTERS, AND GRILLES.
MECHANICAL INSTALLATION AND DEMONSTRATE ACCESS TO EQUIPMENT SERVED.
NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT
M
BD
P
M
TS
SYMBOL DESCRIPTIONSYMBOL DESCRIPTIONSYMBOL DESCRIPTION SYMBOL DESCRIPTION
SYMBOL DESCRIPTIONSYMBOL DESCRIPTIONSYMBOL DESCRIPTION
SYMBOL DESCRIPTION
24x12
24x12
-EXISTING FIRE DAMPER TO REMAIN
-EXISTING FIRE & SMOKE DAMPER TO REMAIN
-PACKAGED TERMINAL AIR CONDITIONER
(PTAC)
-HYDRONIC REHEAT COIL
-FLAT OVAL DUCT
(WITH ACCESS PANEL)
(WITH ACCESS PANEL)
-ELECTRIC DUCT HEATER
(W/ PANEL CLEARANCE)FM
-MANUAL BALANCING DAMPER
-AIR FLOW MEASURING STATION
-MOTOR OPERATED CONTROL DAMPER (MOD)
-FIRE & SMOKE DAMPER
-FIRE DAMPER
-FLEXIBLE CONNECTION
-ACCESS DOORS, VERTICAL OR HORIZONTAL
-INLINE CENTRIFUGAL FAN
-STAINLESS STEEL DUCTWORK
-DOOR GRILLE
-UNDERCUT DOOR
SA-1 -SOUND ATTENUATOR
-SPIN-IN TAKE-OFF
-DUCT ELBOW UP THROUGH ROOF OR SLAB ABOVE
-RECTANGLE-TO-ROUND TAKE-OFF
DNUP
-TRANSITION, SQUARE TO ROUND
UP W/IN FLOORDOWN
-CEILING EXHAUST
-CEILING RETURN
24x12
-STANDARD BRANCH TAKE-OFF
-RADIUS ELBOW
-TRANSITION, ECCENTRIC
-FLEXIBLE DUCT
-CHANGE OF ELEVATION
-DUCT ELBOW, NEGATIVE PRESSURE, RETURN
-DUCT ELBOW, EXHAUST
DIMENSION INDICATES SIDE TO WHICH ARROW IS POINTING
-DUCT ELBOW, POSITIVE PRESSURE (SUPPLY), FIRST
-NEW DUCTWORK, FIRST DIMENSION IS SIDE SHOWN -TRANSITION, CONCENTRIC
-SQUARE THROAT ELBOW
W/TURNING VANES
-RECTANGULAR/ROUND BRANCH TAKE-OFF
OR ROUND/ROUND BRANCH TAKE-OFF
-SQUARE THROAT TEE
-RADIUS TEE
-ROUND DIFFUSER
-SUPPLY REGISTER OR GRILLE
-RETURN/EXHAUST REGISTER OR GRILLE
(VERTICAL MOUNT, SIDEWALL)
(VERTICAL MOUNT, SIDEWALL)
-EXISTING DUCTWORK TO REMAIN
-EXISTING DUCTWORK TO BE REMOVED
(CEILING DIFFUSERS ARE 4-WAY THROW UNO)
-CEILING DIFFUSER, ROUND NECK
-CEILING DIFFUSER, RECTANGULAR OR
SQUARE NECK (CEILING DIFFUSERS
ARE 4-WAY THROW UNO)
M-1
-TEMPERATURE SENSOR
-MOTORIZED CONTROL DAMPER
-HUMIDISTAT/HUMIDITY SENSOR
-THERMOSTAT/TEMPERATURE SENSOR
-REVISION REFERENCE
-DETAIL REFERENCE: TOP-DETAIL#,
BOTTOM-DRAWING# SHOWN ON
-PRESSURE SENSOR
-DUCT SMOKE DETECTOR
-CONNECT TO EXISTING
-DEMOLISH TO POINT INDICATED FF -FINAL FILTERS
DDC -DIRECT DIGITAL CONTROLS
PRS -PRESSURE REDUCING STATION
SP -STATIC PRESSURE
-CFM (CUBIC FEET PER MINUTE)
P -CHANGE IN PRESSURE
CV -CONSTANT AIR VOLUME
-ROOFTOP AIR HANDLING UNITRTU
RS/L -REFRIGERANT SUCTION & LIQUID LINES
h
-OUTSIDE AIR LOUVEROAL
-VARIABLE AIR VOLUMEVAV
-SUPPLY AIRSA
-ROOFTOP HEAT PUMPRHP
-REHEAT COILRHC
-REVOLUTIONS PER MINUTERPM
-RETURN AIRRA
-POLYVINYL CHLORIDE PIPEPVC
-PSI GAUGEPSIG
-POUNDS PER SQUARE INCHPSI
-PRESSURE REDUCING VALVEPRV
-OUTSIDE AIROA
-NOT TO SCALENTS
-NORMALLY OPENNO
-NORMALLY CLOSEDNC
-LINEAR DIFFUSERLD
-LOW PRESSURE STEAMLPS
-LEAVING AIR TEMPERATURELAT
-GALLONS PER MINUTEGPM
-FEET PER MINUTE
-FIRE DAMPER
-FAN COIL UNIT
-ENTERING WATER TEMPERATURE
-ENTERING AIR TEMPERATURE
-DOWN
-CONDENSING UNIT
-CUBIC FEET PER MINUTE
-CHANGE IN TEMPERATURE
-COOLING TOWER
-CEILING DIFFUSER
-CENTER LINE
-BRITISH THERMAL UNIT
-BRAKE HORSEPOWER
-BOTTOM OF PIPE
-ACCESS PANEL
-ABOVE FINISHED FLOOR
FPM
FD
FCU
EWT
EAT
DN
CU
CFM
T
CT
CD
BTU
BOP
BHP
AP
AFF
-AIR HANDLING UNITAHU
MBH -THOUSAND BTUs PER HOUR
AFD -ADJUSTABLE FREQUENCY DRIVE
ESP -EXTERNAL STATIC PRESSURE
KW -KILOWATT
MCA -MINIMUM CIRCUIT AMPS
MOCP -MAXIMUM OVER CURRENT PROTECTION
UNO
TSP -TOTAL STATIC PRESSURE
-VOLTS/PHASEV/PH
VFD -VARIABLE FREQUENCY DRIVE
-UNLESS NOTED OTHERWISE
FLA -FULL LOAD AMPS
-CONTROL VALVE
-45° PIPE RISE (R) / DROP (D)
-CONDENSER WATER SUPPLY
-CONDENSER WATER RETURN
-CHILLED WATER SUPPLY
-CHILLED WATER RETURN
-CONDENSATE
-HOT WATER RETURN
-HOT WATER SUPPLY
-REFRIGERANT LIQUID
-REFRIGERANT SUCTION
-VALVE ON RISER
-CAP
-CONNECTION, BOTTOM
-CONNECTION, TOP
-COUPLING
-ELBOW, 90°
-ELBOW, 45°
-ELBOW, TURNED DOWN
-ELBOW, TURNED UP
-TEE, OUTLET DOWN
-TEE, OUTLET UP
CWS
CWR
CHWS
CHWR
RL
RS
-FLOW SWITCH
-CHECK VALVE
-PSI REG.
-SOLENOID VALVE
-STRAINER
-GAS COCK
-BUTTERFLY VALVE
-CALIBRATING BALANCING VALVE
-BALL VALVE
-GATE VALVE
-UNION
PC -PUMPED CONDENSATE
DD
-HIGH PRESSURE STEAM SUPPLY
-LOW PRESSURE STEAM SUPPLY
-MEDIUM PRESSURE STEAM SUPPLY
CR -CONDENSATE RETURN
-SLOPE DIRECTION (DOWN)
-FLEX CONNECTION
-O.S.&Y. GATE VALVE
-THREE-WAY MODULATING CONTROL VALVE
-THERMOMETER
- P-TRAP
-TWO-WAY CHECK VALVE
EQUIP.
-MANUAL VENT
-PRESSURE GAUGE
-RELIEF VALVE
-FLOW METER
-WATER METER
-INLINE PUMP
-INLINE PUMP
-NEGATIVE RELATIVE PRESSURE
-POSITIVE RELATIVE PRESSURE
-NEUTRAL RELATIVE PRESSURE
-HIGH PRESSURE STEAM RETURN
-LOW PRESSURE STEAM RETURN
-MEDIUM PRESSURE STEAM RETURN
-BACKDRAFT DAMPER
MOD -MOTOR OPERATED CONTROL DAMPER (MOD)
-PACKAGED TERMINAL AIR CONDITIONERPTAC
-PIPE ANCHORS
-CONCENTRIC REDUCER
-ECCENTRIC REDUCER
-STEAM TRAP
-FLOW DIRECTION
-SHEET NOTE CALLOUT
-SHEET NOTE CALLOUT
-SHEET NOTE CALLOUT
-EXHAUST DUCT UP THROUGH SLAB TO
-CENTRIFUGAL EXHAUST FAN ON ROOF
-CEILING MOUNTED ACCESS DOOR
-RECTANGULAR DUCT SECTION UP, EXHAUST
-RECTANGULAR DUCT SECTION UP,
-RECTANGULAR DUCT SECTION UP, POSITIVE PRESSURE,
-ROUND DUCT SECTION UP
-FLAT OVAL DUCT SECTION UP
SUPPLY OR OUTSIDE AIR
NEGATIVE PRESSURE, RETURN
FAN ON ROOF ABOVE
-ABOVE FINISHED ROOFAFR
-TERMINAL UNIT, VARIABLE/CONSTANT AIR
VOLUME WITH ELECTRIC HEAT
-TERMINAL UNIT, VARIABLE/CONSTANT AIR
-TERMINAL UNIT, VARIABLE/CONSTANT AIR
VOLUME, FAN POWERED
VOLUME, FAN POWERED, WITH ELECTRIC
HEAT
-TERMINAL UNIT, VARIABLE/CONSTANT AIR
12x8
HVAC GENERAL NOTESHVAC ABBREVIATIONSHVAC SYMBOL LEGEND
HVAC PIPING SYMBOL LEGEND
8Ø10x8
24x12
12x8
HPS
MPS
LPS
CD
HWR
HWS
HPR
MPR
LPR
H
VOLUME WITH ELECTRIC HEAT
S
MV
FM
M
1. CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH MANUFACTURER'S CERTIFIED
DRAWINGS. TRANSITIONS TO ALL EQUIPMENT SHALL BE VERIFIED AND PROVIDED
FOR EQUIPMENT FURNISHED.
2. DIMENSIONS SHALL BE FIELD-VERIFIED AND COORDINATED PRIOR TO PROCUREMENT OR
FABRICATION. COORDINATE THE WORK WITH OTHER TRADES INVOLVED. FIELD MODIFICATIONS
SUCH AS OFFSETS IN PIPING OR DUCTWORK (INCLUDING DIVIDED DUCTWORK) NEEDED DUE TO
OBSTRUCTIONS OR INTERFERENCES SHALL BE PROVIDED AT NO ADDITIONAL COST. FOR PROJECTS
INVOLVING RENOVATION, COORDINATE NEW WORK WITH EXISTING ELEMENTS SUCH AS THE
BUILDING STRUCTURE AND ARCHITECTURAL FEATURES, SPRINKLER PIPING, LIGHTS, PLUMBING, AND
ELECTRICAL CONDUIT.
3. DUCT CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE
SMACNA HVAC DUCT CONSTRUCTION STANDARD.
4. SEE SPECIFICATIONS FOR GAUGES, THICKNESS, BRACING, REQUIREMENTS, ETC., OF DUCTWORK.
5. PROVIDE AIR TURNING VANES IN ALL 90 DEGREE RECTANGULAR DUCT ELBOWS.
6. DUCT SIZES AND ALL OPENINGS THROUGH BUILDING CONSTRUCTION SHALL SUIT EQUIPMENT
FURNISHED.
7. COORDINATE DIFFUSER, GRILLE AND REGISTER LOCATIONS WITH ARCHITECTURAL
REFLECTED CEILING PLANS AND EQUIPMENT OF ALL TRADES.
8. LOCATE THERMOSTATS, TEMPERATURE SENSORS, HUMIDISTATS, AND HUMIDITY SENSORS AT ABOUT 48" TO 55" ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. COORDINATE LOCATIONS WITH OTHER
EQUIPMENT, LIGHT SWITCHES, FURNITURE, AND DOOR SWINGS.
9. ALL EQUIPMENT, DUCTWORK, ETC., SHALL BE SUPPORTED AS DETAILED AND/OR SPECIFIED. PROVIDE
ADDITIONAL SUPPORTS AS REQUIRED TO PROVIDE A VIBRATION-FREE, RIGID INSTALLATION.
10. ALL DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS.
11. DAMPERS AND INSIDES OF DUCTS VISIBLE THROUGH GRILLES, REGISTERS AND DIFFUSERS SHALL BE
PAINTED FLAT BLACK.
12. REFER TO TYPICAL DETAILS FOR PIPING AND INSTALLATION OF EQUIPMENT.
13. TRAPPED CONDENSATE DRAINS FROM ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED FOR
PROPER DRAINAGE TO SUIT EQUIPMENT FURNISHED.
14. ACCESS PANELS IN DUCTWORK AND CEILINGS SHALL BE PROVIDED WHERE REQUIRED FOR
OPERATION, BALANCING OR MAINTENANCE OF ALL MECHANICAL EQUIPMENT.
15. ALL DUCTWORK AND PIPING IS SHOWN SCHEMATICALLY. PROVIDE ALL TRANSITIONS, TURNING VANES, ELBOWS, FITTINGS, ETC., TO ALLOW SMOOTH FLOWS. ALL SPLIT DUCT FITTINGS SHALL
TRANSITION TO FULL SIZE OF THE SUM OF BOTH BRANCHES, UPSTREAM OF SPLIT.
16. PROVIDE CONCRETE HOUSEKEEPING PAD UNDER ALL FLOOR-MOUNTED EQUIPMENT. REFER TO
SPECIFICATIONS FOR DETAILED REQUIREMENTS.
17. VERIFY FINISH WITH ARCHITECT PRIOR TO PURCHASING GRILLES, REGISTERS, DIFFUSERS, LOUVERS
AND OTHER AIR DISTRIBUTION DEVICES.
18. PROVIDE FLEXIBLE DUCT CONNECTIONS ON ALL DUCTWORK CONNECTING TO EACH FAN, AIR
HANDLING UNITS, AND FAN COIL UNITS.
19. PROVIDE TRANSITIONS AT DIFFUSER NECKS AS REQUIRED TO MATCH SIZES OF FLEX DUCTS TO BE
CONNECTED.
20. INTERRUPTIONS TO EXISTING SERVICES SHALL BE SCHEDULED FOR TIMES OTHER THAN NORMAL OPERATING HOURS (SUCH AS NIGHTS AND WEEKENDS). SUCH INTERRUPTIONS TO SERVICES SHALL
NOT BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER'S REPRESENTATIVE AND
PROPER COORDINATION WITH OTHER TRADES. PRE-WORK SHALL BE PERFORMED TO MAKE THE
SHUTDOWN PERIOD AS BRIEF AS POSSIBLE.
21. ALL EQUIPMENT, DUCTWORK, ETC., TO BE REMOVED SHALL BE DISPOSED OF LEGALLY.
22. MAINTAIN CLEARANCE OF A MINIMUM OF 6" BETWEEN DUCTWORK, PIPING, EQUIPMENT, ETC., AND ALL FIRE RATED AND FIRE/SMOKE RATED PARTITIONS, TO ALLOW FOR INSPECTIONS OF RATED WALLS.
23. LOCATE ALL OUTSIDE AIR INTAKES A MINIMUM OF 25' CLEAR FROM ALL PLUMBING VENTS AND
EXHAUST AIR DISCHARGE LOCATIONS.
24. DUCT RUNOUTS TO DIFFUSERS SHALL MATCH THE SIZE OF THE DIFFUSER NECK.
25. WATER PRESSURE DROPS THROUGH COIL CONTROL VALVES SHALL NOT EXCEED 5 PSI.
26. UNLESS OTHERWISE NOTED, ALL EQUIPMENT AND VALVE DRAINS SHALL BE INDEPENDENTLY PIPED
FULL SIZE TO THE NEAREST PLUMBING DRAIN.
27. SLEEVE AND SEAL ALL PIPING PENETRATIONS THROUGH BUILDING PARTITIONS. PROVIDE MANUAL AIR
VENTS AT ALL HIGH POINTS IN CHILLED WATER AND HOT WATER PIPING.
28. PIPING, DUCTWORK, LEAK PROTECTION APPARATUS, OR OTHER EQUIPMENT FOREIGN TO ELECTRICAL SWITCHBOARDS, PANELBOARDS, DISTRIBUTION BOARDS, OR MOTOR CONTROL CENTERS SHALL NOT BE INSTALLED WITHIN THE REQUIRED SPACE FOR WORKING CLEARANCES OR DEDICATED SPACES OF THE ELECTRICAL EQUIPMENT, EXTENDING IN FRONT OF AND FROM FLOOR TO STRUCTURAL CEILING WITH A WIDTH AND DEPTH OF THE ELECTRICAL EQUIPMENT IN ACCORDANCE WITH NEC-110.26.
T
200A
RHC-1-1
AHU-1
VTU-1-1
CTU - CONSTANT TERMINAL UNIT
VARIABLE/CONSTANT AIR VOLUME TERMINAL UNITS
VTU - VARIABLE TERMINAL UNIT
PTU - PARALLEL TERMINAL UNIT
STU - SERIES TERMINAL UNIT
-AIR HANDLING UNIT
-REHEAT COIL
-AIR DISTRIBUTION DEVICE
HVAC EQUIPMENT TAGS
TAG
CFM
AHU NUMBER
AHU NUMBER COIL NUMBER
AHU NUMBER
TERMINAL NUMBER
TERMINAL UNIT TYPE
75 UC -UNDERCUT DOOR, 75 CFM
T/H -TEMPERATURE & HUMIDITY MONITOR
DP -DIFFERENTIAL PRESSURE SENSOR
-EXISTING PIPE TO REMAIN
-EXISTING PIPE TO BE REMOVED
VTR -VENT THRU ROOF
-LEAVING WATER TEMPERATURELWT
-MEDIUM PRESSURE STEAMMPS
• SCOPE OF WORK INDICATED HEREIN FOR THIS DISCIPLINE DOES NOT INDICATE SPECIFIC
REQUIREMENTS RELATED TO PHASING OF WORK, ALTHOUGH EVERY EFFORT HAS BEEN
MADE TO INCORPORATE SEQUENTIAL PHASES OF WORK AS REQUESTED BY THE
GOVERNMENT.
• PUBLIC AND STAFF ACCESS TO BUILDINGS 7, 107 AND 116 SHALL NOT BE INTERRUPTED AT
ANY TIME DURING CONSTRUCTION.
• CANTEEN, KITCHEN, AND GIFT SHOP NORMAL OPERATION SHALL NOT BE INTERRUPTED AT
ANY TIME DURING CONSTRUCTION.
• REFER TO SHEET GI 01.30 FOR FURTHER INFORMATION ON PROJECT PHASING
REQUIREMENTS.
CONSTRUCTION PHASING / PUBLIC AND
STAFF ACCESS, BUSINESS OPERATIONS:
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2020
TLC No.:
www.tlc-engineers.com
121388
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldhfr.com
WOLD | HFR DESIGN
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
B
IM
/T V
H S
A lv in
C Y o rk
V A
I n te g ra te d H e a lt h /1
-M
E C
H -T
V H
S A
C Y
V A
M C
I n te g ra te d H e a lt h C e n te r- R
.r v t
/1
/2
:1
:1
A
M
M-MK-01
LEGENDS, NOTES, AND SYMBOLS TVHS - ALVIN C. YORK VAMC -
INTEGRATED HEALTH CENTER
SHK5-20-2022 JE
MECHANICAL SHEET INDEX
SHEET DESCRIPTION
M-MK-01 LEGENDS, NOTES, AND SYMBOLS
M-MK-02 SCHEDULES
M-MK-03 SCHEDULES
M-MK-04 SCHEDULES
M-MK-05 SCHEDULES (EXISTING EQUIPMENT)
M-MK-06 SCHEDULES
M-MD-01 BASEMENT OVERALL - HVAC DEMO
M-MD-02 GROUND FLOOR OVERALL - HVAC DEMO
M-MD-03 SECOND FLOOR OVERALL - HVAC DEMO
M-MD-04 ROOF OVERALL - HVAC DEMO
M-MD-05 AHU-34 & 35 EXISTING PLANS
M-MH-00 BASMENT OVERALL - DUCTWORK
M-MH-01 GROUND FLOOR OVERALL - DUCTWORK
M-MH-01A GROUND FLOOR AREA A - DUCTWORK
M-MH-01B GROUND FLOOR AREA B - DUCTWORK
M-MH-02 SECOND FLOOR OVERALL - DUCTWORK
M-MH-02A SECOND FLOOR AREA A - DUCTWORK
M-MH-02B SECOND FLOOR AREA B - DUCTWORK
M-MH-03 ROOF PLAN OVERALL - DUCTWORK
M-MH-03.1 ROOF PLAN OVERALL 3D
M-MH-03A ROOF PLAN AREA A - DUCTWORK
M-MH-03B ROOF PLAN AREA B - DUCTWORK
M-MH-04 SECTIONS
M-MP-00 BASEMENT OVERALL - PIPING
M-MP-00A BASEMENT AREA A - PIPING
M-MP-00B BASEMENT AREA B - PIPING
M-MP-01 GROUND FLOOR OVERALL - PIPING
M-MP-01A GROUND FLOOR AREA A - PIPING
M-MP-01B GROUND FLOOR AREA B - PIPING
M-MP-02 SECOND FLOOR OVERALL - PIPING
M-MP-02A SECOND FLOOR AREA A - PIPING
M-MP-02B SECOND FLOOR AREA B - PIPING
M-MJ-01 MECHANICAL DETAILS
M-MJ-02 MECHANICAL DETAILS
M-MJ-03 MECHANICAL DETAILS
M-MJ-04 MECHANICAL DETAILS
M-MJ-05 MECHANICAL DETAILS
M-MI-01 MECHANICAL CONTROLS
M-MI-02 MECHANICAL CONTROLS
M-MI-03 MECHANICAL CONTROLS
M-MI-04 MECHANICAL CONTROLS
M-MI-05 MECHANICAL CONTROLS
M-MI-06 MECHANICAL CONTROLS
M-MI-07 MECHANICAL CONTROLS
M-MI-08 MECHANICAL CONTROLS
Revisions: Date:
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2020
TLC No.:
www.tlc-engineers.com
121388
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldhfr.com
WOLD | HFR DESIGN
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
B
IM
/T V
H S
A lv in
C Y o rk
V A
I n te g ra te d H e a lt h /1
-M
E C
H -T
V H
S A
C Y
V A
M C
I n te g ra te d H e a lt h C e n te r- R
.r v t
/1
/2
:1
:1
A
M
M-MK-02
SCHEDULES TVHS - ALVIN C. YORK VAMC -
INTEGRATED HEALTH CENTER
SHK5-20-2022 JERevisions: Date:
P 615.297.4554
©Copyright 2020
TLC No.:
www.tlc-engineers.com
121388
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldhfr.com
WOLD | HFR DESIGN
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
B
IM
/T V
H S
A lv in
C Y o rk
V A
I n te g ra te d H e a lt h /1
-M
E C
H -T
V H
S A
C Y
V A
M C
I n te g ra te d H e a lt h C e n te r- R
.r v t
/1
/2
:1
:1
A
M
M-MK-03
SCHEDULES TVHS - ALVIN C. YORK VAMC -
P 615.297.4554
©Copyright 2020
TLC No.:
www.tlc-engineers.com
121388
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldhfr.com
WOLD | HFR DESIGN
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
B
IM
/T V
H S
A lv in
C Y o rk
V A
I n te g ra te d H e a lt h /1
-M
E C
H -T
V H
S A
C Y
V A
M C
I n te g ra te d H e a lt h C e n te r- R
.r v t
/1
/2
:1
:4
A
M
M-MK-04
SCHEDULES TVHS - ALVIN C. YORK VAMC -
INTEGRATED HEALTH CENTER
SHK5-20-2022 JERevisions: Date:
NOTE:
THE VA REQUIRES ALL VFD'S TO HAVE A SECONDARY BACKUP VFD SO IF THE PRIMARY VFD FAILS, AN ALARM WILL BE SENT TO THE BAS AND THE SECONDARY VFD WILL BE ENERGIZED. PROVIDE SECONDARY BACKUP VFD FOR ALL VFD'S
SCHEDULED.
P 615.297.4554
©Copyright 2020
TLC No.:
www.tlc-engineers.com
121388
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldhfr.com
WOLD | HFR DESIGN
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
B
IM
/T V
H S
A lv in
C Y o rk
V A
I n te g ra te d H e a lt h /1
-M
E C
H -T
V H
S A
C Y
V A
M C
I n te g ra te d H e a lt h C e n te r- R
.r v t
/1
/2
:1
:2
A
M
M-MK-05
SCHEDULES (EXISTING
EQUIPMENT)
TVHS - ALVIN C. YORK VAMC -
INTEGRATED HEALTH CENTER
SHK5-20-2022 JE
THIS SHEET CONTAINS THE SCHEDULES FOR EXISTING AHU-34, AHU-35, AND OTHER EXISTING EQUIPMENT IN MECHANICAL ROOM G11 FOR REFERENCE ONLY
P 615.297.4554
©Copyright 2020
TLC No.:
www.tlc-engineers.com
121388
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldhfr.com
WOLD | HFR DESIGN
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
B
IM
/T V
H S
A lv in
C Y o rk
V A
I n te g ra te d H e a lt h /1
-M
E C
H -T
V H
S A
C Y
V A
M C
I n te g ra te d H e a lt h C e n te r- R
.r v t
/1
/2
:1
:2
A
M
M-MK-06
SCHEDULES TVHS - ALVIN C. YORK VAMC -
EXISTING PIPE TUNNEL
EXISTING PIPE TUNNEL
EXISTING PIPE TUNNEL
EXISTING POOL
REMOVE 1-1/2" LPS FROM PRV-1 TO STAGE FINTUBES, PRV-1 TO REMAIN SERVING CORRIDOR RADITORS
REMOVE 3" STEAM FROM AHU'S DOWN TO TUNNEL
PHOTO # 1 PHOTO # 2 PHOTO # 3
2-1/2" CHWS & CHWR UP TO
AHU-37 SERVING CANTEEN
AREA TO REMAIN
REMOVE ALL PIPING AND EQUIPMENT
ASSOCIATED WITH POOL FILTRATION AND
HEATING, SEE PHOTO # 1, 2, & 3 ON THIS
SHEET. REMOVE ALL PIPING AND
EQUIPMENT NO LONGER IN SERVICE.
PHOTO # 4
SURGE TANK
REMOVE EXISTING AHU AND ALL
ASSOCIATED PIPING AND DUCTWORK,
SEE PHOTO # 4 ON THIS SHEET.
REMOVE EXISTING SURGE
TANK AND ALL ASSOCIATED
PIPING, SEE PHOTO # 4 ON
THIS SHEET.
PHOTO # 5
REMOVE EXISTING
VENTILATION & EXHAUST DUCT
ALONG WITH EXH FAN AND
VENT DUCT ON ROOF, SEE
PHOTO # 5 & 6 ON THIS SHEET.
PHOTO # 6
REMOVE EXISTING STEAM PIPING UP
TO GYM.
REMOVE EXISTING DUCT UP THRU
SLAB AND BACK TO UNIT.
EXISTING STEAM AND CONDENSATE
ROUTED UPSTAIRS TO REMAIN
EXISTING STEAM PRV TO REMAIN
REMOVE 1" DRAIN FROM WATER HEATER, REMOVE WATER HEATER AND ALL ASSOCIATED PIPING
REMOVE 2" LPS FROM PRV-3 TO WATER HEATER, REMOVE PRV-3
REMOVE 1-1/4" LPR FROM AHU'S DOWN TO TUNNEL
1-1/2" DOM HOT WATER DOWN TO TUNNEL
2" DOM COLD WATER DOWN TO TUNNEL
5" CHWS UP TO AHU 35 TO REMAIN
5" CHWR UP TO AHU 35 TO REMAIN, SEE PHOTO # 2 ON SHEET M-MD-03 FOR REFERENCE
4" STM VENT THRU ROOF, REROUTE AS NEEDED
APPROXIMATE LOCATION OF
EXISTING PRV-1
APPROXIMATE LOCATION OF
EXISTING PRV-2
APPROXIMATE LOCATION OF
EXISTING PRV-3. REMOVE PRV-3
WHICH SERVES DOMESTIC WATER
HEATER ON SECOND FLOOR, SEE
PHOTO # 1 ON SHEET M-MD-03.
NEW WATER HEATERS TO BE
INSTALLED BEFORE OLD IS
REMOVED, SEE PLUMBING.
APPROXIMATE LOCATION OF
EXISTING PRV-4
REMOVE EXISTING STEAM VENT UP
THRU ROOF, VENT TO BE REROUTED
EXISTING FLASH TANK TO REMAIN
REMOVE ALL PIPING AND
EQUIPMENT IN CRAWL SPACE
ASSOCIATED WITH POOL THAT
IS NOT BEING USED, SEE
PHOTO # 7. CLEAN OUT ALL
TRASH AND DEBRIS.
SEE PHOTO # 8 ON THIS SHEET
FOR INFORMATION ON EXISTING
PRV'S FROM 1958 DRAWINGS AND
PHOTO # 10 FOR 1958 STEAM PIPE
DIAGRAM.
EXISTING PIPING IN TUNNEL TO REMAIN,
SEE PHOTO # 9
REMOVE 1-1/2" STEAM FROM
PRV-1 TO STAGE FINN TUBES
EXISTING 3" VAC RETURN
EXISTING 8" MED PRESS STEAM
EXISTING 2-1/2" DRIP RETURN
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2020
TLC No.:
www.tlc-engineers.com
121388
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldhfr.com
WOLD | HFR DESIGN
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
KEYPLAN
AREA A
AREA B
B
IM
/T V
H S
A lv in
C Y o rk
V A
I n te g ra te d H e a lt h /1
-M
E C
H -T
V H
S A
C Y
V A
M C
I n te g ra te d H e a lt h C e n te r- R
.r v t
/1
/2
:1
:0
A
M
M-MD-01
BASEMENT OVERALL - HVAC
DEMO
TVHS - ALVIN C. YORK VAMC -
INTEGRATED HEALTH CENTER
SHK5-20-2022 JBE
0 8' 16' 32'4'
GENERAL DEMOLITION NOTES:
1. THE DEMOLITION PLAN IS INTENDED TO PROVIDE THE CONTRACTOR WITH A GENERAL KNOWLEDGE OF THE EXISTING CONDITIONS WITHIN THE PROJECT AREA. EXISTING EQUIPMENT, STRUCTURE, DUCTWORK, ETC. LOCATED ON DRAWING MAY NOT BE ALL INCLUSIVE OF SERVICES THAT EXIST IN THE PROJECT AREA. CONTRACTOR SHALL VERIFY SERVICES AND LOCATIONS PRIOR TO ANY DEMOLITION WORK. ANY DEVIATIONS IMPACTING WORK SHOWN ON THESE DOCUMENTS SHALL BE REPORTED TO THE ARCHITECT AND ENGINEER PRIOR TO BEGINNING DEMOLITION. START UP OF DEMOLITION SHALL SIGNIFY CONTRACTORS ACCEPTANCE OF EXISTING CONDITIONS.
THE CONTRACTOR IS RESPONSIBLE FOR ALL REQUIRED DEMOLITION WHETHER SHOWN ON THE PLANS OR NOT.
2. CONTRACTOR SHALL PERFORM A PRE-BID SURVEY TO FIELD-VERIFY AND COORDINATE ALL DIMENSIONS PROIR TO PROCUREMENT OR FABRICATION. FIELD CONDITIONS SHALL GOVERN. COORDINATE THE WORK WITH OTHER TRADES INVOLVED. COORDINATE NEW WORK WITH EXISTING ELEMENTS SUCH AS THE BUILDING STRUCTURE AND ARCHITECTURAL FEATURES, SPRINKLER PIPING, LIGHTS, PLUMBING, ELECTRICAL CONDUIT, AND PNEUMATIC TUBING. THE COST OF REROUTING DUCTWORK OR PIPING DUE TO CONFLICTS WITH EXISTING CONDITIONS SHALL
BE PAID BY THE CONTRACTOR.
3. ALL MECHANICAL SYSTEMS SERVING OTHER SPACES OR FLOORS THAT RUN THROUGH THE PROJECT AREA SHALL REMAIN ACTIVE DURING CONSTRUCTION SO AS NOT TO CAUSE ANY DISRUPTION TO THE OTHER SPACES. ALL
MECHANICAL SYSTEMS IN THE RENOVATION SPACE WHICH ARE INACTIVE SHALL BE REMOVED.
4. CONTRACTOR SHALL PROVIDE MECHANICAL WORK FOR PHASING AS REQUIRED OR DIRECTED BY THE ARCHITECT, REFER TO ARCHITECTURAL PHASING PLAN, TEMPORARY MECHANICAL SERVICES SHALL BE PROVIDED WHEN NEW
WORK AFFECTS SERVICES NEEDED TO REMAIN ACTIVE.
5. ALL ITEMS REMOVED UNDER THIS PROJECT SHALL BE DISPOSED OF.
6. CONTRACTOR SHALL REMOVE EXISTING THERMOSTATS IN RENOVATION SPACE. REMOVED THERMOSTATS SHALL
BE DISPOSED OF.
7. PROPERLY REMOVE AND DISPOSE OF ALL INDICATED EXISTING TO BE REMOVED HVAC DUCTWORK, PIPING, AND AIR
DISTRIBUTION DEVICES.
8. PATCH HOLES LEFT IN WALLS AND FLOORS AFTER REMOVAL OF EXISTING DUCTWORK, CONDUIT, ETC… TO MATCH
NEW OR EXISTING CONSTRUCTION AND FIRE RATING. THIS INCLUDES ANY EXISTING OPENINGS IN RATED WALLS OR
FLOORS.
9. PROVIDE TEMPORARY CONSTRUCTION FILTERS FOR ALL AIR DISTRIBUTION DEVICES LOCATED WITHIN SCOPE OF
WORK.
10. PROVIDE TEMPORARY NEGATIVE AIR MACHINE FOR CONSTRUCTION AREA. MAINTAIN A NEGATIVE PRESSURE IN THE AREA RELATIVE TO THE ADJACENT SPACES AT A MINIMUM OF -0.03” W.C. PROVIDE TEMPORARY DUCT BARRIER PARTITIONS. FAN TO BE EQUIVALENT TO HEPA-AIRE PAS1200HC, 800 CFM, ¼ HP, 120 VOLT. PROVIDE AS MANY MACHINES AS NECESSARY TO MAINTAIN NEGATIVE PRESSURE REQUIREMENT. REFERENCE ARCHITECTURAL PLANS
FOR ADDITIONAL INFORMATION CONCERNING ICRA.
1/16" = 1'-0"
1 BASEMENT OVERALL - HVAC DEMO
PHOTO # 7
PHOTO # 8
PHOTO # 9
PHOTO # 10
FROM ORIGINAL PLANS, FOR REFERENCE ONLY
UP
J
I I
H
G
F
E
D
C
B
A
10987
11 12
135.1 10.25.2
H1
F3
F2
E1
I2
H3
G1
12.511.5
9.57.5
15 16 17 18 19 22
F4
F1
E2
D1
C1
B1
H2
I1
I3
K
L
15.1 15.2 17.1 17.2
00 01 02 03
7.1 9.1
4.5
5.5
ELECTRICAL
STAIRS
20 21
KEY NOTES: (APPLIES TO THIS SHEET ONLY)#
1. REMOVE EXISTING DX CONDENSING UNIT ON GRADE
2. REMOVE EXISTING INDOOR DX DUCTLESS WALL MOUNTED AC UNIT & PIPING
3. REMOVE 3" STEAM VENT FROM BASEMENT UP THRU ROOF
4. REMOVE EXISTING WALL LOUVER AND PATCH OPENING TO MATCH EXISTING
5. REMOVE 5" CHILLED WATER SUPPLY AND RETURN FROM THIS POINT UP TO
FLOOR ABOVE AND REROUTE AS SHOWN ON NEW WORK PLANS
6. VERIFY LOCATION OF STEAM VENT AND REROUTE AS NEEDED.
7. REMOVE PIPING DOWN TO BASEMENT
8. REMOVE AIR COMPRESSOR AFTER INSTALLING NEW AIR COMPRESSOR IN
CHILLER PLANT, SEE PHOTO # 2.
9. REMOVE FAN AND ALL ASSOCIATED DUCTWORK, CAP CURB ON ROOF WITH
INSULATED CAP
10. REMOVE RADIANT STEAM HEATING, CONDENSATE RETURN, AND ALL
ASSOCIATED PIPING
11. REMOVE REFRIGERATED AIR DRYER
12. REMOVE CHILLED WATER PIPING BACK TO SHUTOFF VALVES.
13. REMOVE ELECTRIC HEATER AND ALL ASSOCIATED HARDWARE
14. EXISTING STEAM AND CONDENSATE PIPING TO REMAIN
15. REMOVE EXISTING DUCT THRU ROOF AND CAP CURB
16. REMOVE EXISTING WALL GRILLE
17. REMOVE LOUVER AND PNEUMATIC DAMPER.
18. REMOVE EXISTING WALL LOUVER, ARCHITECT TO PATCH OPENING WITH
SPANDREL.
19. REMOVE RETURN DUCT AND PATCH FLOOR SLAB.
20. REMOVE EXISTING WALL LOUVER AND REPLACE WITH NEW.
21. REMOVE WALL DAMPER AND PATCH TO MATCH EXISTING.
22. REMOVE EXISTING CHILLED WATER PUMPS AND ASSOCIATED PIPING.
23. CAP OFF EXISTING CHILLED WATER PIPING DOWN LOW.
24. THE VA REQUESTED THE METAL FENCE BE REMOVED.
25. REMOVE STAGE VENTS, CAP CURB ON ROOF w/INSULATED CAP.
26. REMOVE ALL DUCTWORK IN AUDITORIUM.
107-AHU-34
AHU-35 ON ROOF 8
ASSUMED LOCATION OF
EXISTING UNDERGROUND 5"
CHILLED WATER SUPPLY
AND RETURN PIPING, SEE
PHOTO # 6.
EXISTING UNDERGROUND 3"
CHILLED WATER SUPPLY
AND RETURN PIPING TO
BUILDING 6
ASSUMED LOCATION OF
EXISTING UNDERGROUND 4"
CHILLED WATER PIPING TO
BUILDING 107, CONTRACTOR
TO FIELD VERIFY. REMOVE IF
POSSIBLE OR ABANDON IN
PLACE .
EXISTING UNDERGROUND
2-1/2" CHILLED WATER
SUPPLY AND RETURN PIPING
TO BUILDING 118
EXISTING UNDERGROUND
10" CHILLED WATER SUPPLY
AND RETURN PIPING TO
CAMPUS LOOP
REMOVE 1-1/2" LPS FROM PRV-1 TO STAGE FINTUBES
REMOVE 3" STEAM FROM AHU'S DOWN TO TUNNEL
REMOVE 1" DRAIN FROM WATER HEATER
REMOVE 2" LPS FROM PRV-3 TO WATER HEATER, REMOVE PRV-3
REMOVE 1-1/4" LPR FROM AHU'S DOWN TO TUNNEL
REMOVE 1-1/2" DOM HOT WATER DOWN TO TUNNEL
REMOVE 2" DOM COLD WATER DOWN TO TUNNEL
4" STM VENT FROM TUNNEL
4" STM VENT THRU
ROOF, FIELD VERIFY
LOCATION
SEE PHOTO #1
17 17
SEE PHOTO #5
SEE PHOTO #3
SEE PHOTO #4
SEE SHEET M-MD-05
FOR EXISTING LAYOUT
OF THIS AREA
REMOVE PIPING AND CAP OFF
REMOVE ALL PNEUMATIC
CONTROL TUBING IN RENOVATION
AREA AND CAP OFF
GIFT SHOP
CANTEEN
KITCHEN AREA
CHILLER PLANT
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2020
TLC No.:
www.tlc-engineers.com
121388
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldhfr.com
WOLD | HFR DESIGN
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
KEYPLAN
AREA A
AREA B
B
IM
/T V
H S
A lv in
C Y o rk
V A
I n te g ra te d H e a lt h /1
-M
E C
H -T
V H
S A
C Y
V A
M C
I n te g ra te d H e a lt h C e n te r- R
.r v t
/1
/2
:1
:1
A
M
M-MD-02
GROUND FLOOR OVERALL - HVAC
DEMO
TVHS - ALVIN C. YORK VAMC -
INTEGRATED HEALTH CENTER
SHK5-20-2022 JBE
0 8' 16' 32'4'
1/16" = 1'-0"
1 GROUND FLOOR OVERALL - HVAC DEMO
GENERAL DEMOLITION NOTES:
1. THE DEMOLITION PLAN IS INTENDED TO PROVIDE THE CONTRACTOR WITH A
GENERAL KNOWLEDGE OF THE EXISTING CONDITIONS WITHIN THE PROJECT
AREA. EXISTING EQUIPMENT, STRUCTURE, DUCTWORK, ETC. LOCATED ON
DRAWING MAY NOT BE ALL INCLUSIVE OF SERVICES THAT EXIST IN THE
PROJECT AREA. CONTRACTOR SHALL VERIFY SERVICES AND LOCATIONS
PRIOR TO ANY DEMOLITION WORK. ANY DEVIATIONS IMPACTING WORK SHOWN
ON THESE DOCUMENTS SHALL BE REPORTED TO THE ARCHITECT AND
ENGINEER PRIOR TO BEGINNING DEMOLITION. START UP OF DEMOLITION
SHALL SIGNIFY CONTRACTORS ACCEPTANCE OF EXISTING CONDITIONS. THE
CONTRACTOR IS RESPONSIBLE FOR ALL REQUIRED DEMOLITION WHETHER
SHOWN ON THE PLANS OR NOT.
2. CONTRACTOR SHALL PERFORM A PRE-BID SURVEY TO FIELD-VERIFY AND
COORDINATE ALL DIMENSIONS PROIR TO PROCUREMENT OR FABRICATION.
FIELD CONDITIONS SHALL GOVERN. COORDINATE THE WORK WITH OTHER
TRADES INVOLVED. COORDINATE NEW WORK WITH EXISTING ELEMENTS SUCH
AS THE BUILDING STRUCTURE AND ARCHITECTURAL FEATURES, SPRINKLER
PIPING, LIGHTS, PLUMBING, ELECTRICAL CONDUIT, AND PNEUMATIC TUBING.
THE COST OF REROUTING DUCTWORK OR PIPING DUE TO CONFLICTS WITH
EXISTING CONDITIONS SHALL BE PAID BY THE CONTRACTOR.
3. ALL MECHANICAL SYSTEMS SERVING OTHER SPACES OR FLOORS THAT RUN
THROUGH THE PROJECT AREA SHALL REMAIN ACTIVE DURING CONSTRUCTION
SO AS NOT TO CAUSE ANY DISRUPTION TO THE OTHER SPACES. ALL
MECHANICAL SYSTEMS IN THE RENOVATION SPACE WHICH ARE INACTIVE
SHALL BE REMOVED.
4. CONTRACTOR SHALL PROVIDE MECHANICAL WORK FOR PHASING AS
REQUIRED OR DIRECTED BY THE ARCHITECT, REFER TO ARCHITECTURAL
PHASING PLAN, TEMPORARY MECHANICAL SERVICES SHALL BE PROVIDED
WHEN NEW WORK AFFECTS SERVICES NEEDED TO REMAIN ACTIVE.
5. ALL ITEMS REMOVED UNDER THIS PROJECT SHALL BE DISPOSED OF.
6. CONTRACTOR SHALL REMOVE EXISTING THERMOSTATS IN RENOVATION
SPACE. REMOVED THERMOSTATS SHALL BE DISPOSED OF.
7. PROPERLY REMOVE AND DISPOSE OF ALL INDICATED EXISTING TO BE
REMOVED HVAC DUCTWORK, PIPING, AND AIR DISTRIBUTION DEVICES.
8. PATCH HOLES LEFT IN WALLS AND FLOORS AFTER REMOVAL OF EXISTING
DUCTWORK, CONDUIT, ETC… TO MATCH NEW OR EXISTING CONSTRUCTION
AND FIRE RATING. THIS INCLUDES ANY EXISTING OPENINGS IN RATED WALLS
OR FLOORS.
9. PROVIDE TEMPORARY CONSTRUCTION FILTERS FOR ALL AIR DISTRIBUTION
DEVICES LOCATED WITHIN SCOPE OF WORK.
10. PROVIDE TEMPORARY NEGATIVE AIR MACHINE FOR CONSTRUCTION AREA.
MAINTAIN A NEGATIVE PRESSURE IN THE AREA RELATIVE TO THE ADJACENT
SPACES AT A MINIMUM OF -0.03” W.C. PROVIDE TEMPORARY DUCT BARRIER
PARTITIONS. FAN TO BE EQUIVALENT TO HEPA-AIRE PAS1200HC, 800 CFM, ¼
HP, 120 VOLT. PROVIDE AS MANY MACHINES AS NECESSARY TO MAINTAIN
NEGATIVE PRESSURE REQUIREMENT. REFERENCE ARCHITECTURAL PLANS
FOR ADDITIONAL INFORMATION CONCERNING ICRA.
PHOTO # 1 PHOTO # 2 PHOTO # 3 PHOTO # 4
DAMPER
PHOTO # 5
REMOVE EXISTING AIR
COMPRESSOR, REMOVE ALL
INACTIVE PNEUMATIC PIPING
IN RENOVATED AREAS AND
CAP
REMOVE EXISTING
REFRIGERATED AIR DRYER
NEW AIR COMPRESSOR TO BE INSTALLED AND
ACTIVATED BEFORE OLD IS REMOVED.
PHOTO # 6
ROOF BELOW
ROOF BELOW
ROOF BELOW
REC THERAPY BELOW
STAIR
STUDIO
FAN ROOM
GENERATOR
RM
REWIND RM PROJECTION ROOM CONTROL RM AMP RM
C O
R R
ID
O
R
AMATEUR
RADIO ROOM
JANITOR
J
I
H
G
F
E
D
C
B
10976
54321
11 12
10.2
H1
F3
F2
E1
I2
12.511.5
9.57.5
15 16
17 18 19
F4
F1
E2
D1
C1
B1
H2
I1
I3
K
L
15.1 15.2
1400 01 02 03
THIS SECTION OF
CHILLED WATER PIPING
TO BE REMOVED AND
REROUTED, SEE NEW
WORK PLANS
REMOVE DUCTWORK DOWN
FROM ABOVE AND PATCH
FLOOR AND ROOF OPENINGS
REMOVE KITCHEN WATER HEATER AND ALL
ASSOCIATED PIPING, WAIT TILL NEW WATER
HEATER IS INSTALLED FIRST. REMOVE OLD
HEAT EXCHANGER AND ALL ASSOCIATED
PIPING. SEE PHOTO # 1
REMOVE AIR HANDLER # 36
AND ALL ASSOCIATED
DUCTWORK AND PIPING
KEY NOTES: (THIS SHEET ONLY)#
1. REMOVE ALL SUPPLY, RETURN, AND EXHAUST DUCT IN THIS SPACE
2. CONTRACTOR TO DETERMINE WHICH PNEUMATIC LINES SERVE THE
CANTEEN AND KITCHEN AREA AND KEEP THOSE LINES ACTIVE, REROUTE
AS NEEDED TO ACCOMODATE NEW FLOOR PLAN. REMOVE ALL THE
PNEUMATIC LINES SERVING EQUIPMENT TO BE DEMOLISHED.
3. EQUIPMENT TO BE REMOVED
EXISTING PIPING
SERVING AHU-35 TO
REMAIN
AHU-37 CANTEEN UNIT ON ROOF TO
REMAIN. VERIFY CHILLED WATER
FLOW BEFORE DEMOLITION AND
REBALANCE TO PRE DEMOLITION
FLOW AFTER WORK IS COMPLETE
3 3 3
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2020
TLC No.:
www.tlc-engineers.com
121388
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldhfr.com
WOLD | HFR DESIGN
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
KEYPLAN
AREA A
AREA B
B
IM
/T V
H S
A lv in
C Y o rk
V A
I n te g ra te d H e a lt h /1
-M
E C
H -T
V H
S A
C Y
V A
M C
I n te g ra te d H e a lt h C e n te r- R
.r v t
/1
/2
:1
:1
A
M
M-MD-03
SECOND FLOOR OVERALL - HVAC
DEMO
TVHS - ALVIN C. YORK VAMC -
INTEGRATED HEALTH CENTER
SHK5-20-2022 JBE
1/16" = 1'-0"
1 SECOND FLOOR OVERALL - HVAC DEMO
0 8' 16' 32'4'
PHOTO # 1
PHOTO # 2
CANTEEN UNIT AHU-37 AUDITORIUM UNIT
AHU-36
AUDITORIUM UNIT
AHU-36
OLD UNIT AHU-35
THIS WAS WHEN THE OLD CHILLED WATER SYSTEM HAD
A CHILLER WHERE AHU-34 IS LOCATED NOW BEFORE THE
SYSTEM WAS CONNECTED TO THE CAMPUS CHILLED
WATER LOOP
KEY NOTES: (THIS SHEET ONLY)
1. REMOVE FAN ON ROOF AND CAP CURB
2. REMOVE EXISTING DUCT DOWN THRU ROOF AND CAP CURB
3. REMOVE EXISTING STEAM VENT PIPING AND REROUTE
4. REMOVE EXISTING ROOF VENTS AND CAP CURB
5. REMOVE EXISTING LOUVER
6. REMOVE EXISTING DAMPER
7. EXISTING RTU TO REMAIN
8. EXISTING OUTSIDE AIR INTAKE TO REMAIN
1 1
107-AHU-35
RTU-M107
444444
SEE PHOTO # 1
SEE PHOTO # 2
SEE PHOTO # 6
SEE PHOTO # 7
SEE PHOTO # 4
SEE PHOTO # 5
6 6
SEE PHOTO # 3
SEE PHOTO # 8
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2020
TLC No.:
www.tlc-engineers.com
121388
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldhfr.com
WOLD | HFR DESIGN
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
KEYPLAN
AREA A
AREA B
B
IM
/T V
H S
A lv in
C Y o rk
V A
I n te g ra te d H e a lt h /1
-M
E C
H -T
V H
S A
C Y
V A
M C
I n te g ra te d H e a lt h C e n te r- R
.r v t
/1
/2
:1
:2
A
M
M-MD-04
ROOF OVERALL - HVAC DEMO TVHS - ALVIN C. YORK VAMC -
INTEGRATED HEALTH CENTER
SHK5-20-2022 JBE
0 8' 16' 32'4'
GENERAL DEMOLITION NOTES:
1. THE ONLY MECHANICAL HVAC WORK REQUIRED ON THIS FLOOR IS TO PROVIDE A PATH
WAY FOR THE VENTILATION DUCTWORK REQUIRED ON THE THIRD FLOOR TO CONNECT TO
FANS AND EQUIPMENT ON THE ROOF AND TO CREATE CHASES TO ENCLOSE THE NEW
DUCTWORK REQUIRED.
2. THE DEMOLITION PLAN IS INTENDED TO PROVIDE THE CONTRACTOR WITH A GENERAL
KNOWLEDGE OF THE EXISTING CONDITIONS WITHIN THE PROJECT AREA. EXISTING
EQUIPMENT, STRUCTURE, DUCTWORK, ETC. LOCATED ON DRAWING MAY NOT BE ALL
INCLUSIVE OF SERVICES THAT EXIST IN THE PROJECT AREA. CONTRACTOR SHALL VERIFY
SERVICES AND LOCATIONS PRIOR TO ANY DEMOLITION WORK. ANY DEVIATIONS IMPACTING
WORK SHOWN ON THESE DOCUMENTS SHALL BE REPORTED TO THE ARCHITECT AND
ENGINEER PRIOR TO BEGINNING DEMOLITION. START UP OF DEMOLITION SHALL SIGNIFY
CONTRACTORS ACCEPTANCE OF EXISTING CONDITIONS. THE CONTRACTOR IS
RESPONSIBLE FOR ALL REQUIRED DEMOLITION WHETHER SHOWN ON THE PLANS OR NOT.
3. CONTRACTOR SHALL PERFORM A PRE-BID SURVEY TO FIELD-VERIFY AND COORDINATE ALL
DIMENSIONS PROIR TO PROCUREMENT OR FABRICATION. FIELD CONDITIONS SHALL
GOVERN. COORDINATE THE WORK WITH OTHER TRADES INVOLVED. COORDINATE NEW
WORK WITH EXISTING ELEMENTS SUCH AS THE BUILDING STRUCTURE AND ARCHITECTURAL
FEATURES, SPRINKLER PIPING, LIGHTS, PLUMBING, ELECTRUCAL CONDUIT, AND PNEUMATIC
TUBING. THE COST OF REROUTING DUCTWORK OR PIPING DUE TO CONFLICTS WITH
EXISTING CONDITIONS SHALL BE PAID BY THE CONTRACTOR.
4. ALL MECHANICAL SYSTEMS SERVING OTHER SPACES OR FLOORS THAT RUN THROUGH THE
PROJECT AREA SHALL REMAIN ACTIVE DURING CONSTRUCTION SO AS NOT TO CAUSE ANY
DISRUPTION TO THE OTHER SPACES. ALL MECHANICAL SYSTEMS THAT RUN INTO THE
SPACE BUT DO NOT SERVE ANYTHING SHALL BE REMOVED BACK TO WHERE THEY ENTER
THE SPACE TO FREE-UP VALUABLE CLREANCE FOR NEW DUCT AND PIPING.
5. CONTRACTOR SHALL PROVIDE MECHANICAL WORK FOR PHASING AS REQUIRED OR
DIRECTED BY THE ARCHITECT, REFER TO ARCHITECTURAL PHASING PLAN, TEMPORARY
MECHANICAL SERVICES SHALL BE PROVIDED WHEN NEW WORK AFFECTS SERVICES
NEEDED TO REMAIN ACTIVE.
6. ALL ITEMS REMOVED UNDER THIS PROJECT SHALL BE DISPOSED OF.
7. PROVIDE TEMPORARY NEGATIVE AIR MACHINES FOR CONSTRUCTION AREA. MAINTAIN A
NEGATIVE PRESSURE IN THE AREA RELATIVE TO THE ADJACENT SPACES AT A MINIMUM
OF -0.03” W.C. PROVIDE SHEET ROCK TYPE WALL BARRIER PARTITIONS WITH AIR TIGHT OR
LOW LEAKAGE CONSTRUCTION ACCESS. FAN TO BE EQUIVALENT TO HEPA-AIRE PAS1200HC,
800 CFM, ¼ HP, 120 VOLT. PROVIDE AS MANY MACHINES AS NECESSARY TO MAINTAIN
NEGATIVE PRESSURE REQUIREMENT IN RENOVATION SPACE. REFERENCE ARCHITECTURAL
PLANS FOR ADDITIONAL INFORMATION CONCERNING ICRA.
PHOTO # 4 PHOTO # 5 PHOTO # 6
PHOTO # 7
1/16" = 1'-0"
1 ROOF PLAN OVERALL - HVAC DEMO
PHOTO # 1
PHOTO # 2 PHOTO # 3REMOVE LIGHTNING PROTECTION
AND REINSTALL ON NEW INTAKE
HOOD. (TYP OF 2)
PHOTO # 8
P 615.297.4554
©Copyright 2020
TLC No.:
www.tlc-engineers.com
121388
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldhfr.com
WOLD | HFR DESIGN
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
KEYPLAN
B
IM
/T V
H S
A lv in
C Y o rk
V A
I n te g ra te d H e a lt h /1
-M
E C
H -T
V H
S A
C Y
V A
M C
I n te g ra te d H e a lt h C e n te r- R
.r v t
/1
/2
:1
:2
A
M
M-MD-05
AHU-34 & 35 EXISTING PLANS TVHS - ALVIN C. YORK VAMC -
INTEGRATED HEALTH CENTER
SHK5-20-2022 JBE
PARTIAL EXISTING DUCT PLAN - AHU-34
PARTIAL EXISTING PIPE PLAN - AHU-34
PARTIAL EXISTING PIPE PLAN - AHU-35
PARTIAL EXISTING DUCT PLAN - AHU-35
NOTE:
EXISTING PLANS SHOWN ON THIS SHEET SHOW THE EXISTING
DUCTWORK AND PIPING ASSOCIATED WITH AHU-34 AND AHU-35 PRIOR
TO ANY RENOVATION, AND IS FOR REFERENCE ONLY.
J
II
H
G
F
E
D
C
B
A
10987
4321 11 12
5.1
10.2
5.2
H1
F3
F2
E1
I2
H3
G1
12.511.5
9.57.5
15 16 17 18 19 22
K
L
15.1 15.2 17.1 17.2
00 01 02 03
7.1
9.1
4.5
5.5
20 21
B 150016x16 UP TO EXHAUST
FAN ON ROOF
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2020
TLC No.:
www.tlc-engineers.com
121388
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldhfr.com
WOLD | HFR DESIGN
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
KEYPLAN
AREA A
AREA B
B
IM
/T V
H S
A lv in
C Y o rk
V A
I n te g ra te d H e a lt h /1
-M
E C
H -T
V H
S A
C Y
V A
M C
I n te g ra te d H e a lt h C e n te r- R
.r v t
/1
/2
:1
:2
A
M
M-MH-00
BASMENT OVERALL - DUCTWORK TVHS - ALVIN C. YORK VAMC -
INTEGRATED HEALTH CENTER
SHK5-20-2022 JBE
1/16" = 1'-0"
1 BASEMENT OVERALL - DUCTWORK
0 8' 16' 32'4'
UP
J
I I
G
F
E
D
C
B
A
10987
4321 11 12
5.1 10.25.2
H1
F3
F2
E1
I2
H3
G1
12.511.5
9.5 7.5
15 16 17 18 19 22
F4
F1
E2
D1
C1
B1
H2
I1
I3
K
L
15.1 15.2 17.1 17.2
00 01 02 03
7.1 9.1
ELECTRICAL
G41
SIM MAINTENANCE
G30G
PROCEDURE SIM LAB
G30FCONTROL ROOM
G30E
WAITING
G39
MULTI-PURPOSE
G20J
MULTI-PURPOSE
G20F
MULTI-PURPOSE
G20D
MULTI-PURPOSE
G20B
MULTI-PURPOSE
G20
MULTI-PURPOSE
G20H
STOR.
G20C
MED/SURG SIM LAB
G30D KITCHEN/SERVING
G21
EDUC CHIEF
G17A
MUSIC THERAPY CLINIC
G13
WC STORAGE
G12B
REC. THERAPY CLINIC
G08
COMPUTER LAB
G16
STOR.
G20A
STOR.
G20E
STOR
G20G
STOR.
G20I
BARBER CART
G02FOOD SERVICE CHIEF
G03
FOOD SERVICE VEND SUPPLY
G04
CORRIDOR
G54
CORRIDOR
G52
MUSIC THER. 1
G43
MUSIC THER. 2
G42
CORRIDOR
G45
WORK AREA
G15
ENTRY
G01
CORRIDOR
G46
COURTYARD
G10
CORRIDOR
G48
CORRIDOR
G48A
CORRIDOR
G49
CORRIDOR
G50
CORRIDOR
G51
STORAGE
G20K
4.5
5.5
PRACTICE ROOM
G13B
MUSIC STORAGE
G13A
ALS CLASSROOM
G30J
TRNG EQUIP STOR
G30C
STAFF LOUNGE
G33
CREATIVE ARTS GROUP
G34
LOBBY
G36
PMRS STORAGE
G31
ACCESS STAIR
G26
FEMALE
G24
MALE
G25
LACTATION
G27
HAC
G30I
MALE
G37
FEMALE
G38
MEDIA COORD.
G17B
WORK
G17
PAT. RESOURCE
G40
RT SPVR.
G15A
PMRS CONSULT
G14
HAC
G07
RECREATION
STORAGE
G08B
MALE
G09A
FEMALE
G09C
COPIER
COPIER
VENDING
G32
KINESIO GROUP THERAPY
G12
COPIERSAFE
WORK
G12A
KITCHENETTE
G08A
VESTIBULE
G35
SECURITY
G35A
STORAGE
G34A
CORRIDOR
G55
STORAGE
G30K
STORAGE
G30H
DE-BRIEF
G30A
CORRIDOR
G30 CORRIDOR
G30
CONNECTOR
G47
FEMALE SHOWER
G09D
MALE SHOWER
G09B
ENTRY
G44
CORRIDOR
G53
CHARGING CART STOR.
G19WHOLE HEALTH
STORAGE
G18
IT
G23
20 21
CHASE
G26A
CLO.
G30B
COMM/MEDIA CONTROL
G22
RISER
G13D
MECH.
G11
ELEC.
G28
ELEC.
G29
MECH.
G11A
STAIRS
G09
CORRIDOR
G46
107-CAC-1
NEW CONTROL AIR
COMPRESSOR UP ON
MEZZANINE LEVEL
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2020
TLC No.:
www.tlc-engineers.com
121388
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldhfr.com
WOLD | HFR DESIGN
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
KEYPLAN
AREA A
AREA B
B
IM
/T V
H S
A lv in
C Y o rk
V A
I n te g ra te d H e a lt h /1
-M
E C
H -T
V H
S A
C Y
V A
M C
I n te g ra te d H e a lt h C e n te r- R
.r v t
/1
/2
:1
:4
A
M
M-MH-01
GROUND FLOOR OVERALL -
DUCTWORK
TVHS - ALVIN C. YORK VAMC -
INTEGRATED HEALTH CENTER
SHK5-20-2022 JBE
1/16" = 1'-0"
1 GROUND FLOOR OVERALL - DUCTWORK
1. ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A
FURRED CHASE OR ABOVE HARD SUSPENDED CEILING, OR ACOUSTICAL CEILING.
2. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR INDICATED.
DUCT SIZES ARE NET INSIDE DIMENSIONS.
3. ACCESS PANELS IN HARD SUSPENDED CEILINGS ARE REQUIRED FOR ALL VALVES, TRAPS,
DAMPERS, CLEANOUTS, CONTROLS, ETC. ACCESS PANELS SHALL BE FURNISHED AND
INSTALLED UNDER THE ARCHITECTURAL SPECIFICATIONS. COORDINATE LOCATION WITH
MECHANICAL INSTALLATION AND DEMONSTRATE ACCESS TO EQUIPMENT SERVED.
4. FOR TYPICAL WATER PIPING CONNECTIONS TO EQUIPMENT, SEE STANDARD EQUIPMENT
DETAILS.
5. DIFFUSER, REGISTER AND GRILLE SIZES SHOWN ON FLOOR PLANS ARE CFM's, REFER TO
AIR DISTRIBUTION DEVICE SCHEDULE FOR ADDITIONAL INFORMATION.
6. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE MADE TO
PROVIDE COUNTER FLOW BETWEEN WATER AND AIR.
7. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF
CEILING DIFFUSERS, REGISTERS, AND GRILLES.
GENERAL NOTES:
0 8' 16' 32'4'
J
I
F
E
D
C
B
A
11 12
5.1 10.25.2
F3
F2
E1
I2
H3
G1
12.511.5
9.57.5
F4
F1
E2
D1
C1
B1
7.1 9.1
E.9
10.1 12.911.9
E.4
AREA BAREA A
A R
E A
B
A R
E A
A
B.2
C.5
C.6
E.3
E.5
F.3
STAIRS
REC. THERAPY CLINIC
G08
BARBER CART
G02
FOOD SERVICE CHIEF
G03
CORRIDOR
G45
ENTRY
G01
CORRIDOR
G46
FOOD SERVICE VEND SUPPLY
G04
612 SF
CONNECTOR
G47
KITCHENETTE
G08A
MUSIC THERAPY CLINIC
G13
MUSIC STORAGE
G13A
WORK
G12A
EDUC CHIEF
G17A
RECREATION
STORAGE
G08B
HAC
G07
KINESIO GROUP THERAPY
G12
WC STORAGE
G12B
MALE
G09A
FEMALE
G09C
COURTYARD
G10
WORK AREA
G15
PRACTICE ROOM
G13B
PMRS CONSULT
G14
CHASE
G-104A
MALE SHOWER
G09B
FEMALE SHOWER
G09D
CLEAN
G12C
SOILED
G12D
MECH.
G11A
MECH.
G11
ELEC.
G28
ELEC.
G29
KEY NOTES: (THIS SHEET ONLY)
1. UNITED McGILL UNI-RIB-k27 DOUBLE WALL INSULATED DUCT (SPIRAL LOCKSEAM WITH STANDING RIB) 12" INSIDE DIAMETER WITH 1" INSULATION THICKNESS, 24 GAUGE GALVANIZED STEEL WITH END
CAP, PAINTED GLOSS WHITE OR AS INDICATED ON ARCHITECTURAL DRAWINGS. (TYP OF 2)
2. UNITED McGILL MODEL DDF-RUDDW 12x6 DOUBLE DEFLECTION REGISTER, WHITE, 215 CFM. (TYP OF
4) REGISTER TO BE MOUNTED IN SOFFIT FACE.
3. COORDINATE DUCT ROUTING WITH ROOF DRAIN PIPING & SPRINKLER PIPING IN THIS AREA. SEE PHOTO # 1 ON THIS SHEET SHOWING EXISTING ROOF DRAIN AND FIRE MAIN PIPING IN THIS AREA.
DUCT TO BE ROUTED IN SOFFIT, SEE ARCHITECTURAL DRAWINGS.
D 860 x1
12ø
12ø
12ø
A 270
A 195 A 195 A 195
A 195
A 195
A 195
A 195 A 195
A 150A 155 A 155
A 155
A 185
A 190 A 185
A 250 A 250
A 50
A 150
A 65
A 150
A 150
A 300 A 300
A 300 A 300
A 300
A 300
A 300 A 300
A 300
A 300A 300
A 300
A 300 A 300 A 300
A 110
B 100
B 400
B 400
B 100
B 250
B 100
A 260 A 260 A 260 A 260
A 110
A 75
A 300 A 300
A 250 A 250
A 250
A 250
V36-10
V36-9
V36-7
V36-6
V36-4
V36-3 V36-5
V36-2
V36-1
A 155
B 560 B 500
B 270
B 880
B 875
V35-1
V35-2
V35-3
V35-4
V35-10
V35-8
V35-9
V35-12
V35-11
V35-5
V35-7
V35-6 x1 x1
48x14
V36-8
10x38 SWR 8" A.F.F.
14x14 14x12 12x12 10ø30x818x12
107-EH-1
6" ROUND DOWN TO 12"x3" AND EXTEND THRU
SLATS, TRIM BOTTOM EDGE OF 12X3 TO BE EVEN
WITH BOTTOM OF SLATS, PAINT TO MATCH
SLATS, SEE CORRIDOR G-056 VIEW ON THIS
SHEET. BALANCE FOR 97 CFM. VERIFY WIDTH
BETWEEN SLATS BEFORE FABRICATING. (TYP.
OF 6)
x1 x1
8x
14x12
B 1000
20x14 14x14 x1 x1 x1 x1 x1
20x14 14x14 x1
UC100 UC65
U C
B 75B 110
B 110 x1
A 200
FIRE MAIN DOWN
THRU FLOOR
107-BAF-4107-BAF-3
107-BAF-5 107-BAF-6
107-BAF-1 107-BAF-2
x1 x1 x1
B 1500
B 1500
B 1500
U C
B 65
A 440
B 300 UC100
UC100
UC100
FLATTEN DUCT AS SHOWN AND ROUTE DUCT
DOWN TIGHT TO WALL IN FUR-OUT, SEE
ARCHITECTURAL PLANS FOR COORDINATION.
12x12 x1
12x8 14x6 x1
UP TO
EXHAUST FAN
ON ROOF
12x1010x10
8x10
10x12
20x10
16x10 14x10 10x10
8ø 10x10
10x10
16x12
12x12 x1
20x10 x1
14x10 8ø
16x10
14x10
10x10
8x10
18x12 12x8
8ø
B 600
B 700 x1
40x12
107-CHWP-1
& 2
VFD
107-RAF-34
107-AHU-34
107-CRU-1
EXISTING HEAT
EXCHANGERS
EXISTING HOT
WATER PUMPS
CONTRACTOR TO BE RESPONSIBLE FOR
REBALANCING EXISTING UNIT TO NEW AIR
FLOW AND STATIC PRESSURE TO MEET
NEW REQUIREMENTS. PROVIDE ALL
NECESSARY COMPONENTS TO ACOMPLISH
PROPER OPERATION
x8
12x12
6ø
8ø
14x14
18x12
12x3
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2020
TLC No.:
www.tlc-engineers.com
121388
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldhfr.com
WOLD | HFR DESIGN
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
KEYPLAN
AREA A
B
IM
/T V
H S
A lv in
C Y o rk
V A
I n te g ra te d H e a lt h /1
-M
E C
H -T
V H
S A
C Y
V A
M C
I n te g ra te d H e a lt h C e n te r- R
.r v t
/1
/2
:1
:2
A
M
M-MH-01A
GROUND FLOOR AREA A -
DUCTWORK
TVHS - ALVIN C. YORK VAMC -
INTEGRATED HEALTH CENTER
SHK5-20-2022 JE
0 4' 8' 12'
1/8" = 1'-0"
1 GROUND FLOOR AREA A - DUCTWORK
EXISTING ROOF DRAIN PIPE
EXISTING SPRINKLER PIPE
PHOTO # 1
NOT TO SCALE
CORRIDOR G-056 VIEW
ROUTE 6" ROUND DOWN AND TRANSITION TO 12"x3"
AND EXTEND THRU SLATS IN CEILING. TRIM BOTTOM
EDGE OF 12x3 TO MATCH PROFILE OF SLATS AND TO
BE FLUSH WITH SURFACE, PAINT VISIBLE DUCTWORK
TO MATCH COLOR OF SLATS.
I
H
F
G1
17 18 19 22
F4
F1
E2
D1
C1
B1
H2
I1
I3
K
L
15.1 15.2 17.1 17.2
MEDIA COORD.
G17B
LOBBY
G36
MALE
G37
FEMALE
G38
VESTIBULE
G35
SECURITY
G35A
58 SF
HAC
G30I
PAT. RESOURCE
G40
STORAGE
G34A
SIM MAINTENANCE
G30G
PROCEDURE SIM LAB
G30F
CONTROL ROOM
G30E
TRNG EQUIP STOR
G30C
499 SF
ALS CLASSROOM
G30J
MALE
G25
WAITING
G39
LACTATION
G27
MULTI-PURPOSE
G20J
MULTI-PURPOSE
G20F
MULTI-PURPOSE
G20D
MULTI-PURPOSE
G20B
MULTI-PURPOSE
G20
MULTI-PURPOSE
G20H
STOR.
G20A
STOR.
G20E STOR
G20G
STOR.
G20I
STOR.
G20C
MED/SURG SIM LAB
G30D
VENDING
G32
STAFF LOUNGE
G33
KITCHEN/SERVING
G21
EDUC CHIEF
G17A
WORK
G17
RT SPVR.
G15A
COMPUTER LAB
G16
CREATIVE ARTS GROUP
G34
CORRIDOR
G48
CORRIDOR
G48A
CORRIDOR
G49
CORRIDOR
G50
CORRIDOR
G51
STORAGE
G20K
FEMALE
G24
MUSIC THER. 1
G43 MUSIC THER. 2
G42
CORRIDOR
G54
CORRIDOR
G52
ACCESS STAIR
G26
PMRS STORAGE
G31
C O
P
IE
R
327 SF
DE-BRIEF
G30A
361 SF
CORRIDOR
G30
177 SF
STORAGE
G30H
65 SF
STORAGE
G30K
AREA BAREA A
A R
E A
B
A R
E A
A
C O
R R
ID
O
R T
O B
LD
G
217 SF
CORRIDOR
G30
WHOLE HEALTH
STORAGE
G18 m a n e q u in s to ra g e r a c k
CHARGING CART STOR.
G19
CORRIDOR
G53
IT
G23
20 21
CONNECTOR
G47
CHASE
G26A
CLO.
G30B
COMM/MEDIA CONTROL
G22
ELECTRICAL
G41
CORRIDOR
G45
C 190
F 155
(TYP. OF 12)
(TYP. OF 6)
A 175 A 175 A 120
A 215
C 400
A 70
A 175
A 100
A 205
A 100
A 200
A 170A 170
A 170
A 40
A 175
A 175
A 175
A 155
A 175
A 175
A 175
A 100 A 150
A 150 A 260A 260
A 75
A 150
A 140
A 75
A 190 A 190
A 175
A 100 A 200
A 100A 250
A 250
A 250
A 250
A 250 A 250
A 250
A 250
A 250A 250
A 200
A 100
D 800 C 700D 700
A 215
A 205
A 190
16x8 x6
B 400
B 200 18x20
DOWN TO
16x44 SWR 8" A.F.F.
2000 CFM
B 330
B 330
B 100
B 175
B 525
B 40
B 510
B 175
B 175
D 400
16x10
16x10
20x10
B 120
B 70
B 570
B 1685
B 260
B 260
B 300
B 350
B 75
A 100
A 240A 195A 195
A 150
A 245
A 245
A 150
A 50
A 110
A 200
A 175
A 175 A 200 A 200
A 200
A 125 A 125
A 60A 60 A 60
A 50
A 180 A 100
A 550
A 550
A 550
A 450
A 450
A 550
A 550
A 550
A 550
A…