Attachment 12 - MECH BINDER-2.pdf

PDF 10 MB Posted

Attached to
Y1DA--626-309 Construct Integrated Health Center (Minor) - Murfreesboro
Solicitation number
36C77623B0037
Issued by

About this file

This document provides details for a federal contract opportunity to construct an integrated health center in Murfreesboro, Tennessee. The solicitation number is 36C77623B0037 and is being issued by the Department of Veterans Affairs Technology Acquisition Center in Austin, Texas. The project involves the construction of an integrated health center for Veterans Affairs facility number 626-309. No other details are provided on the required construction products or services, the response deadline, or anticipated award date. The attached file is labeled as an appendix but does not appear to include any further salient information on the requirements.

View the file

Other files

File Type Posted
36C77623B0037 0008 - 8-29-23.pdf PDF
36C77623B0037 0007.pdf PDF
36C77623B0037 0006 - 8-22-23.pdf PDF
36C77623B0037 0005 - 8-18-23.pdf PDF
081710 integrated door assemblies - R2.pdf PDF
36C77623B0037 0004 - 08-15-2023.pdf PDF
Technical Questions Round 2 - 8-14-23.docx DOCX document
232113.13 FL - UNDERGROUND HYDRONIC PIPING.pdf PDF
2023-08-09 - IHC - Addendum 2.pdf PDF
IHC - Add 2 - Narrative.pdf PDF
36C77623B0037 0003 - 08-03-2023.pdf PDF
Technical Questions Tracking Spreadsheet - Murf IHC - 7-24-23.pdf PDF
VAMC - IHC - Addendum 1 - Dwgs.pdf PDF
36C77623B0037 0002.pdf PDF
Integrated Health Laydown Areas.pdf PDF
Attachment 17 - Construction Wage Rates - Rutherford County - 6-30-23.pdf PDF
Site Visit Sign In Sheet.pdf PDF
36C77623B0037 0001.docx DOCX document
Civil Binder.pdf PDF
Attachment 5 - CIVIL BINDER.pdf PDF
Attachment 11 - MECH BINDER-1.pdf PDF
Attachment 19 - Site Visit Instructions.pdf PDF
36C77623B0037_1.docx DOCX document
Attachment 9 - GENERAL BINDER.pdf PDF
Attachment 3 - ARCHITECTURAL BINDER-1.pdf PDF
Attachment 2 - IHC - SPEC - VOLUME 2.pdf PDF
Attachment 8 - FP BINDER.pdf PDF
Attachment 18 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 7 - ELEC BINDER.pdf PDF
Attachment 1 - IHC - SPEC - VOLUME 1.pdf PDF
Attachment 13 - PLUMBING BINDER.pdf PDF
Attachment 15 - TECH BINDER.pdf PDF
Attachment 10 - INTERIORS BINDER.pdf PDF
Attachment 17 - Construction Wage Rates.pdf PDF
Attachment 6 - DEMO BINDER1.pdf PDF
Attachment 4 - ARCHITECTURAL BINDER-2.pdf PDF
Attachment 14 - STRUCTURAL BINDER.pdf PDF
Attachment 16 - Limitations on Subcontracting - Construction Jan 2023 Deviation.docx DOCX document
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

107-EF-5 107-EF-6

107-RH-2 107-RH-1

CONTRACTOR TO REINSTALL EXISTING

LIGHTNING PROTECTION ON NEW HOODS

CURB CAP WITH INSULATION

CURB CAP WITH INSULATION

CURB CAP WITH INSULATION

CURB CAP WITH INSULATION

107-EF-3

107-EF-4

107-EF-1

NEW STEAM VENT FROM PRV

IN BASEMENT

107-IL-1

107-IL-2

107-RL-4

MOUNTED

ABOVE DOOR

LADDER UP TO ROOF

LADDER UP TO ROOF

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

AREA B

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h /1

-M

E C

H -T

V H

S A

C Y

V A

M C

I n te g ra te d H e a lt h C e n te r- R

.r v t

/1

/2

:1

:4

A

M

M-MH-03B

ROOF PLAN AREA B - DUCTWORK TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5-20-2022 JBE

0 4' 8' 12'

1/8" = 1'-0"

1 ROOF PLAN AREA B - DUCTWORK

Revisions: Date:

ET-1

107-HEX-2

107-APT-3

107-RH-2

107-RH-1

107-AHU-58

107-AHU-59

107-RAF-60

107-AHU-60

72x24

16x16

20x20

30x20

40x18 x2

48x24 x1

107-HWP-1

& 2

107-RH-1

107-RH-2

107-AHU-58

107-AHU-59

30x20 x1

62x24

40x24

ET-1

107-HEX-1

107-HWP-1

& 2

20x20

THE AREA AT EACH END OF THE MECHANICAL ROOM WILL NOT BE

EASILY ACCESSABLE, DO NOT LOCATE EQUIPMENT SUCH AS

DAMPERS OR SENSORS WHICH WILL REQUIRE SERVICE IN THIS

AREA. LOCATE EQUIPMENT IN THE MECHANICAL ROOM WHERE IT

WILL BE EASILY ACCESSABLE.

IT ROOM

GROUND FLOOR

MECH EQUIP PLATFORM 2

ROOF

DDC

VFD

107-RH-1

107-AHU-58

107-EF-6

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h /1

-M

E C

H -T

V H

S A

C Y

V A

M C

I n te g ra te d H e a lt h C e n te r- R

.r v t

/1

/2

:1

:5

A

M

M-MH-04

SECTIONS TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5-20-2022 JBE

NOT TO SCALE

MECH EQUIP PLATFORM 2 - VIEW 1

NOT TO SCALE

MECH EQUIP PLATFORM 2 - VIEW 2

NOT TO SCALE

MECH EQUIP PLATFORM 2 - VIEW 3

NOT TO SCALE

MECH EQUIP PLATFORUM 2 - VIEW 4

J

II

H

G

F

E

D

C

B

A

10987

4321 11 12

5.1

10.2

5.2

H1

F3

F2

E1

I2

H3

G1

12.511.5

9.57.5

15 16 17 18 19 22

K

L

15.1 15.2 17.1 17.2

00 01 02 03

7.1

9.1

4.5

5.5

20 21

EXISTING

PRV-1

EXISTING

PRV-2

EXISTING

PRV-4

107-PRV-3

EXISTING PRV SERVING

HUMIDIFIERS ON

AHU-34, 35, AND HEAT

EXCHANGERS IN

EXISTING MECH RM

G11

5" CHWS & R UP TO 2ND

FLR MECH RM SERVING

107-AHU-35 & 36

6" CHWS & R DN

FROM EXISTING MECH

RM

NEW 2" LPR DOWN TO

DRIP RETURN IN TUNNEL

4"ø

EXISTING

FLASH TANK

3" MPS UP TO 107-PRV-1

NEW 3" MPS UP TO

107-PRV-2

2-1/2" CHWS & R UP TO AHU-37 SERVING

CANTEEN AREA, FLOW TO THIS UNIT WAS

NOT KNOWN AND WAS ASSUMED TO BE

ABOUT 90 GPM OF CHILLED WATER.

AHU-37 IS THE ONLY UNIT ASSUMED TO BE

ON THIS CHILLED WATER PIPE.

PROVIDE NEW END OF MAIN DRIP AND NEW 8"

STEAM SHUTOFF VALVE FOR BUILDING 107.

COORDINATE LOCATION IN TUNNEL WITH VA

8" MEDIUM PRESSURE STEAM

2-1/2" DRIP RETURN

EXISTING 3" VAC RETURN

3/4" LPR FROM 107-PRV-1

1-1/4" PUMPED

CONDENSATE FROM

107-CRU-1

LPS

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

AREA A

AREA B

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h /1

-M

E C

H -T

V H

S A

C Y

V A

M C

I n te g ra te d H e a lt h C e n te r- R

.r v t

/1

/2

:1

:2

A

M

M-MP-00

BASEMENT OVERALL - PIPING TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5-20-2022 JBE

0 8' 16' 32'4'

1/16" = 1'-0"

1 BASEMENT OVERALL - PIPING

ORIGINAL 1958 PIPE TUNNEL PLAN FOR REFERENCE

NOT TO SCALE

H

G

F

E

D

C

B

A

10987

11 12

5.1

10.2

5.2

H1

F3

F2

E1

I2

H3

G1

12.511.5

9.57.5

7.1

9.1

3" MPS LINE UP TO 107-PRV-1 IN

MECHANICAL ROOM

NEW 3" MPS UP TO 107-PRV-2 AND

107-AHU-36 HUMIDIFIER ON

SECOND FLOOR

EXISTING 5" CHWS & R UP TO 107-

AHU-35 & 36 ON SECOND FLOOR

EXISTING 6" CHWS & R DOWN

FROM MECHANICAL ROOM, VERIFY

DIRECTION OF FLOW AND LABLE

PIPES CORRECTLY

1-1/4" PUMPED CONDENSATE

FROM WATER HEATERS IN MECH

ROOM

3/4" LPR CONDENSATE FROM 107-

PRV-1 IN MECH ROOM

NEW 2" LPR CONDENSATE FROM

WATER HEATER, 107-PRV-2, AND

107-AHU-36 HUMIDIFIER ON

SECOND FLOOR, CONNECT TO

EXISTING DRIP RETURN

2-1/2" CHWS & R UP TO 107-AHU-37

SERVING CANTEEN AREA, FLOW

TO THIS UNIT WAS NOT KNOWN

AND WAS ASSUMED TO BE ABOUT

90 TO 100 GPM OF CHILLED

WATER. AHU-37 IS THE ONLY UNIT

ASSUMED TO BE ON THIS CHILLED

WATER PIPE.

EXISTING 2-1/2" DRIP

RETURN

EXISTING PRV-4

EXISTING 8" MED

PRESS STEAM

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

AREA A

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h /1

-M

E C

H -T

V H

S A

C Y

V A

M C

I n te g ra te d H e a lt h C e n te r- R

.r v t

/1

/2

:1

:2

A

M

M-MP-00A

BASEMENT AREA A - PIPING TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5-20-2022 JBE

0 4' 8' 12'

1/8" = 1'-0"

1 BASEMENT AREA A - PIPING

H

G

F

G1

17 18 19 22

K

L

15.1 15.2 17.1 17.2

20 21

CONNECT NEW STEAM VENT

TO EXISTING AND ROUTE AS

SHOWN, MATCH EXISTING

SIZE

ROUTE 3" STEAM VENT UP

TO ROOF

107-PRV-3

ROUTE 4" STEAM LINE UP TO

FLOOR ABOVE, 15 PSI

3/4" LPR FROM

ABOVE

1.5" LPR FROM 2ND

FLOOR MECH ROOM

CONNECT 3/4" LPR TO

EXISTING CONDENSATE AT

FLASH TANK

CONNECT 1.5" PCR TO

EXISTING CONDENSATE IN

TUNNEL

TRAP

4"ø LPS

EXISTING PRV SERVING

HUMIDIFIERS ON AHU-34 &

35, AND EXISTING HEAT

EXCHANGERS IN MECH RM

G11

EOM DRIP

2-1/2" STEAM VENT

1" LPR

3" MPS

2" STEAM TO MECH ROOM G11

5" STEAM MAIN

2-1/2" DRIP RETURN

5" STEAM MAIN

T

PROVIDE TEMP SENSOR IN

BASEMENT AREA FOR

MONITORING BY BAS

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

AREA B

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h /1

-M

E C

H -T

V H

S A

C Y

V A

M C

I n te g ra te d H e a lt h C e n te r- R

.r v t

/1

/2

:1

:2

A

M

M-MP-00B

BASEMENT AREA B - PIPING TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5-20-2022 JBE

0 4' 8' 12'

1/8" = 1'-0"

1 BASEMENT AREA B - PIPING

UP

UP

J

I I

G

F

E

D

C

B

A

10987

4321 11 12

5.1 10.25.2

H1

F3

F2

E1

I2

H3

G1

12.511.5

9.5 7.5

15 16 17 18 19 22

F4

F1

E2

D1

C1

B1

H2

I1

I3

K

L

15.1 15.2 17.1 17.2

00 01 02 03

7.1 9.1

ELECTRICAL

G41

SIM MAINTENANCE

G30G

PROCEDURE SIM LAB

G30FCONTROL ROOM

G30E

WAITING

G39

MULTI-PURPOSE

G20J

MULTI-PURPOSE

G20F

MULTI-PURPOSE

G20D

MULTI-PURPOSE

G20B

MULTI-PURPOSE

G20

MULTI-PURPOSE

G20H

STOR.

G20C

MED/SURG SIM LAB

G30D KITCHEN/SERVING

G21

EDUC CHIEF

G17A

MUSIC THERAPY CLINIC

G13

WC STORAGE

G12B

REC. THERAPY CLINIC

G08

COMPUTER LAB

G16

STOR.

G20A

STOR.

G20E

STOR

G20G

STOR.

G20I

BARBER CART

G02FOOD SERVICE CHIEF

G03

FOOD SERVICE VEND SUPPLY

G04

CORRIDOR

G54

CORRIDOR

G52

MUSIC THER. 1

G43

MUSIC THER. 2

G42

CORRIDOR

G45

WORK AREA

G15

ENTRY

G01

CORRIDOR

G46

COURTYARD

G10

CORRIDOR

G48

CORRIDOR

G48A

CORRIDOR

G49

CORRIDOR

G50

CORRIDOR

G51

STORAGE

G20K

4.5

5.5

PRACTICE ROOM

G13B

MUSIC STORAGE

G13A

ALS CLASSROOM

G30J

TRNG EQUIP STOR

G30C

STAFF LOUNGE

G33

CREATIVE ARTS GROUP

G34

LOBBY

G36

PMRS STORAGE

G31

ACCESS STAIR

G26

FEMALE

G24

MALE

G25

LACTATION

G27

HAC

G30I

MALE

G37

FEMALE

G38

MEDIA COORD.

G17B

WORK

G17

PAT. RESOURCE

G40

RT SPVR.

G15A

PMRS CONSULT

G14

HAC

G07

RECREATION

STORAGE

G08B

MALE

G09A

FEMALE

G09C

COPIER

COPIER

VENDING

G32

KINESIO GROUP THERAPY

G12

COPIERSAFE

WORK

G12A

KITCHENETTE

G08A

VESTIBULE

G35

SECURITY

G35A

STORAGE

G34A

CORRIDOR

G55

STORAGE

G30K

STORAGE

G30H

DE-BRIEF

G30A

CORRIDOR

G30 CORRIDOR

G30

CONNECTOR

G47

FEMALE SHOWER

G09D

MALE SHOWER

G09B

ENTRY

G44

CORRIDOR

G53

CHARGING CART STOR.

G19WHOLE HEALTH

STORAGE

G18

IT

G23

20 21

CHASE

G26A

CLO.

G30B

COMM/MEDIA CONTROL

G22

RISER

G13D

MECH.

G11

ELEC.

G28

ELEC.

G29

MECH.

G11A

STAIRS

G09

CORRIDOR

G46

V59-7

V59-6

V59-1

V59-8

V59-9

V59-10

V59-11

V59-12

V59-13

V59-5

V59-4

V59-3

V59-2

V58-2

V58-1

V58-3

V58-4 V58-5

V58-8 V58-11

V58-10

V58-7

V58-6

V58-9

V58-18

V58-19

V58-17

V58-12

V58-14

V58-15

V35-6

V35-7V35-5

V35-2

V35-8

V35-12

V35-9 V35-11

V35-10 V35-4

V35-3

V35-1

V58-20

V58-21

V58-16

V36-1

V36-2

V36-4

V36-3 V36-5

V36-6

V36-7

V36-9

V36-10

CAP OFF EXISTING 4"

UNDERGROUND CHILLED

WATER PIPES

COORDINATE DEPTH OF

UNDERGROUND PIPING

WITH NEW GRADE BEAMS

UNDER CONNECTOR.

107-CAC-1

ROUTE CONNECTION SIZE

DRAIN LINE FROM AIR

COMPRESSOR ON MEZZANINE

LEVEL DOWN TO SINK ON

MACHINE FLOOR LEVEL, SEE

PHOTO # 2.

107-EH-1

LOCATE AIR COMPRESSOR ON

MEZZANINE LEVEL, SEE PHOTO

# 3.

V36-8

V60-2 V60-1

V34-1

V34-3

V34-5

V34-2 V34-4

V58-13

107-CHWP-1

& 2

NEW 6" CHWS & CHWR

UNDERGROUND CHILLED

WATER PIPES, ADJUST

ROUTING AS NEEDED FOR

EXISTING CONDITIONS

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

AREA A

AREA B

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h /1

-M

E C

H -T

V H

S A

C Y

V A

M C

I n te g ra te d H e a lt h C e n te r- R

.r v t

/1

/2

:1

:3

A

M

M-MP-01

GROUND FLOOR OVERALL -

PIPING

TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5-20-2022 JBE

1. CONNECT NEW 6" CHWS AND CHWR TO EXISTING UNDERGROUND MAINS, SEE

PHOTO # 1 ON THIS SHEET.

2. ROUTE NEW PNEUMATIC LINE OVER TO KITCHEN AREA AND CONNECT INTO

EXISTING PNEUMATIC SYSTEM SERVING KITCHEN, GIFTSHOP, AND CANTEEN AREA.

FIELD VERIFY LOCATION. VERIFY ALL PENUMATIC CONTROLS SERVED BY THE NEW

COMPRESSOR FUNCTION PROPERLY AFTER CONNECTING TO NEW COMPRESSOR.

KEY NOTES:#

0 8' 16' 32'4'

1/16" = 1'-0"

1 GROUND FLOOR OVERALL - PIPING

PHOTO # 1

PHOTO # 2

ROUTE DRAIN LINE FROM NEW AIR

COMPRESSOR ON MEZZANINE TO

THIS SINK

PHOTO # 3 LOCATE AIR COMPRESSOR IN THIS

GENERAL AREA ON MEZZANINE

STAIRS UP TO MEZZANINE LEVEL SHOWN IN PHOTO # 2

(THIS SHEET ONLY)

J

I

F

E

D

C

B

A

11 12

5.1 10.25.2

F3

F2

E1

I2

H3

G1

12.511.5

9.57.5

F4

F1

E2

D1

C1

B1

7.1 9.1

AREA BAREA A

A R

E A

B

A R

E A

A

STAIRS

REC. THERAPY CLINIC

G08

BARBER CART

G02

FOOD SERVICE CHIEF

G03

CORRIDOR

G45

ENTRY

G01

CORRIDOR

G46

FOOD SERVICE VEND SUPPLY

G04

612 SF

CONNECTOR

G47

KITCHENETTE

G08A

MUSIC THERAPY CLINIC

G13

MUSIC STORAGE

G13A

WORK

G12A

EDUC CHIEF

G17A

RECREATION

STORAGE

G08B

HAC

G07

KINESIO GROUP THERAPY

G12

WC STORAGE

G12B

MALE

G09A

FEMALE

G09C

COURTYARD

G10

WORK AREA

G15

PRACTICE ROOM

G13B

PMRS CONSULT

G14

CHASE

G-104A

MALE SHOWER

G09B

FEMALE SHOWER

G09D

CLEAN

G12C

SOILED

G12D

MECH.

G11A

MECH.

G11

ELEC.

G28

ELEC.

G29

V35-3

V35-4

V35-10

V35-11

V35-9

V35-12

V35-8

V35-2

V35-7

V35-6

V35-1

V35-5

V36-1

V36-2

V36-3

V36-5

V36-4

V36-6

V36-7

V36-8 V36-9

V36-10

2"ø HWR

2"ø HWS

2"ø HWR 2"ø HWS

1 1/4"ø HWR 1 1/4"ø HWS

1"ø HWR

1"ø HWS

1"ø HWS 1"ø HWR

1 1/2"ø HWR 1 1/2"ø HWS 1 1/4"ø HWR

1 1/4"ø HWS

1 1/4"ø HWS

1 1/4"ø HWR

1"ø HWS

1"ø HWR

EXISTING 5" CHWS & R UP

FROM TUNNEL, CONNECT

NEW 4" TO EXISTING 5"

AND ROUTE AS SHOWN

4"CHWS & R UP

CONNECT NEW 1-1/2"

HWS & R TO EXISTING 3"

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

107-BAF-1

107-BAF-2

107-BAF-4107-BAF-3

107-BAF-6107-BAF-5

T

T

T

3-WAY VALVE

"ø

4"ø 4"ø

DOMESTIC WATER

HEATERS, SEE

PLUMBING

STEAM PIPING IS SIZED SO

WATER HEATERS CAN HEAT

40°F WATER UP TO 180°F

DURING CLEAN OUT

PROCEDURE BUT RECOMMEND

ONLY PEFORMING PROCEDURE

ON ONE HEATER AT A TIME.

1-1/4" PUMPED

CONDENSATE DOWN TO

EXISTING DRIP RETURN

IN TUNNEL

3" MPS UP & 2" LPR DN

FROM 107-PRV-2, WATER

HEATER, & HUMIDIFIER

ON AHU-36 ABOVE

1 1/4"ø HWR 1 1/4"ø HWS

S S

S S

S S

TO 107-BAF-1 & 2

TO 107-BAF-3 & 4

TO 107-BAF-5 & 6

107-EH-1

T

107-PRV-1

3" MPS FROM

MAIN IN TUNNEL

T

T

T

CEILING FAN CONTROLLERS

KINESIO ROOM TEMPERATURE CONTROL

3/4" CONDENSATE DOWN TO

EXISTING DRIP RETURN IN TUNNEL

1 1/4"ø

SEE CHILLED WATER PUMP

VIEW ON THIS SHEET.

107-CHWP-1

& 2

CAP EXISTING PIPING OFF

UNDERGROUND.

EOM DRIP

4"ø CHWR

4"ø CHWS

EOM

DRIP

107-AHU-34

EXISTING 4" STEAM

VENT FROM TUNNEL

UP TO ROOF.

NEW 3" MPS UP

FROM TUNNEL

2" LPR CONDENSATE

DOWN TO EXISTING DRIP

RETURN IN TUNNEL

VFD'S FOR CHWP-1 & 2

107-CRU-1

3-WAY VALVE

2"ø CHWS

6"ø CHWS

6"ø CHWR

6"ø CHWS

V34-1

EXISTING STEAM,

CONDENSTAT, HWS & HWR UP

TO FLOOR ABOVE.

1 1/4"ø HWS

1 1/4"ø HWR

2"ø CHWR

NEW 6" CHWS AND 6" CHWR

PIPING UNDERGROUND

107-CHWP-1

& 26"ø CHWS

6"ø CHWR

6" VERTICAL CHECK VALVE

6" FLANGED CIRCUIT SETTER

SEE PUMP DETAIL FOR VALVES

AND FITTINGS REQUIRED AT

PUMP INLET AND OUTLET

SHUTOFF VALVES

6" CROSS CONNECTION WITH

SHUTOFF, KEEP CLOSED NORMALLY

6"ø CHWR

6"ø CHWS

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

AREA A

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h /1

-M

E C

H -T

V H

S A

C Y

V A

M C

I n te g ra te d H e a lt h C e n te r- R

.r v t

/1

/2

:2

:1

A

M

M-MP-01A

GROUND FLOOR AREA A - PIPING TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5-20-2022 JBE

0 4' 8' 12'

1/8" = 1'-0"

1 GROUND FLOOR AREA A - PIPING

VAV BOXES V36-4, V36-6, AND V36-7 CONTROL THE ROOM TEMPERATURE FOR THE

KINESIO GROUP THERAPY ROOM. THESE 3 VAV BOXES SHALL HAVE

TEMPERATURE SENSORS IN THE KINESIO ROOM WHERE SHOWN ON FLOOR PLAN

AT RIGHT BUT THE TEMPERATURE CONTROLLERS SHALL BE LOCATED IN THE

WORK ROOM G12A. LABEL THE CONTROLLERS IN THE WORK ROOM "A", "B", AND

"C" AND PROVIDE A DIAGRAM SIMILAR TO PHOTO SHOWN ABOVE INDICATING ZONE

LOCATIONS. BOX V36-6 CONTROLS ZONE "A", BOX V36-4 CONTROLS ZONE "B", AND

BOX V36-7 CONTROLS ZONE "C"

KINESIO GROUP THERAPY ZONE MAP

KEY NOTES: (APPLIES TO THIS SHEET ONLY)

1. VERIFY THE REQUIRED DIRECTION OF CHILLED WATER FLOW IN EXISTING PIPES

BEFORE CONNECTING NEW PIPES TO MAKE SURE THE FLOW DIRECTION IS

CORRECT. REPLACE FLOW ARROWS ON PIPING WHEN PROPER DIRECTION IS

DETERMINED.

2. FULL SIZE VENT FROM CONDENSATE PUMP UP THRU ROOF.

3. 2-1/2" STEAM VENT FROM 107-PRV-1 UP THRU ROOF.

4. CONTRACTOR TO REFIL EXISTING HOT WATER SYSTEM AFTER CONNECTING NEW

PIPING. SYSTEM IS NOTED ON EXISTING PLANS TO CONTAIN 30% GLYCOL.

NOT TO SCALE

CHILLED WATER PUMP VIEW

CHILLED WATER PIPING SYSTEM NOTES:

• PROVIDE SHUTOFF VALVES AND 6" CROSS CONNECTION AS SHOWN IN VIEW ABOVE FOR BUILDING

107 SYSTEM FLUSHING.

• CONTRACTOR SHALL BE RESPONSIBILE FOR REFILLING CAMPUS CHILLED WATER SYSTEM TO

ACCOUNT FOR THE VOLUME OF NEW AND EXISTING PIPING IN BUILDING 107 WHEN NEW PIPING IS

CONNECTED TO EXISTING CAMPUS CHILLED WATER SYSTEM.

• CONTRACTOR TO ENSURE ALL AIR IS VENTING OUT OF THE CHILLED WATER SYSTEM WHEN

COMPLETE.

• CONTRACTOR SHALL BE RESPONSIBILE FOR ADDING ANY CHEMICALS AS NEEDED TO OVERALL

SYSTEM TO BALANCE PH LEVELS AND ENSURE PROPER CORROSION PROTECTION AND COMPLY

WITH ANY VA STANDARDS FOR CHILLED WATER SYSTEMS.

• CONTRACTOR TO REPLACE ANY EXISTING PIPE LABELS ON ANY EXISTING TO REMAIN CHILLED WATER PIPE IN THE SCOPE OF WORK AREA AND ENSURE THE FLOW ARROWS ARE POINTING IN THE

PROPER DIRECTION OF FLOW.

• CONTRACTOR TO REPLACE ANY DAMAGED PIPE INSULATION WITH NEW INSULATION ON EXISTING

TO REMAIN PIPE IN SCOPE OF WORK AREA.

• CONTRACTOR TO REPLACE ANY RUSTED OUT PIPE HANGERS AND SUPPORTS SERVING EXISTING

TO REMAIN PIPES WITH NEW HANGERS AND SUPPORTS IN THE TUNNEL AND ELSEWHERE IN THE

SCOPE OF WORK AREA.

I

H

F

G1

17 18 19 22

F4

F1

E2

D1

C1

B1

H2

I1

I3

K

L

15.1 15.2 17.1 17.2

MEDIA COORD.

G17B

LOBBY

G36

MALE

G37

FEMALE

G38

VESTIBULE

G35

SECURITY

G35A

58 SF

HAC

G30I

PAT. RESOURCE

G40

STORAGE

G34A

SIM MAINTENANCE

G30G

PROCEDURE SIM LAB

G30F

CONTROL ROOM

G30E

TRNG EQUIP STOR

G30C

499 SF

ALS CLASSROOM

G30J

MALE

G25

WAITING

G39

LACTATION

G27

MULTI-PURPOSE

G20J

MULTI-PURPOSE

G20F

MULTI-PURPOSE

G20D

MULTI-PURPOSE

G20B

MULTI-PURPOSE

G20

MULTI-PURPOSE

G20H

STOR.

G20A

STOR.

G20E STOR

G20G

STOR.

G20I

STOR.

G20C

MED/SURG SIM LAB

G30D

VENDING

G32

STAFF LOUNGE

G33

KITCHEN/SERVING

G21

EDUC CHIEF

G17A

WORK

G17

RT SPVR.

G15A

COMPUTER LAB

G16

CREATIVE ARTS GROUP

G34

CORRIDOR

G48

CORRIDOR

G48A

CORRIDOR

G49

CORRIDOR

G50

CORRIDOR

G51

STORAGE

G20K

FEMALE

G24

MUSIC THER. 1

G43 MUSIC THER. 2

G42

CORRIDOR

G54

CORRIDOR

G52

ACCESS STAIR

G26

PMRS STORAGE

G31

C O

P

IE

R

327 SF

DE-BRIEF

G30A

361 SF

CORRIDOR

G30

177 SF

STORAGE

G30H

65 SF

STORAGE

G30K

AREA BAREA A

A R

E A

B

A R

E A

A

C O

R R

ID

O

R T

O B

LD

G

217 SF

CORRIDOR

G30

WHOLE HEALTH

STORAGE

G18 m a n e q u in s to ra g e r a c k

CHARGING CART STOR.

G19

CORRIDOR

G53

IT

G23

20 21

CONNECTOR

G47

CHASE

G26A

CLO.

G30B

COMM/MEDIA CONTROL

G22

ELECTRICAL

G41

CORRIDOR

G45

S S

STEAM VENT UP

THRU ROOF, SIZE

TO MATCH EXISTING

V59-5

V59-4

V59-3

V59-2

V59-1

V58-15

V58-14

V58-12

V58-11 V58-8

V58-10

V58-16

V58-18

V58-19 V58-17

V58-20V58-21

V58-9

V58-6

V58-7

V58-2

V58-1

V58-3

V58-4

V58-5

V59-12

V59-13

V35-6

T

T

2"ø HWS

2"ø HWR

3"ø HWR

3"ø HWS

1 1/4"ø HWR 1 1/4"ø HWS

1"ø HWR 1"ø HWS

1 1/4"ø HWR

1 1/4"ø HWS

T

TT T

T

T

T

V59-6

V59-7

V59-8 V59-9

V59-10

V59-11

T

T

T T

T

T

T

T T

T

T

T

T

T

T

T

T

T

TT

T

T

T T T T

2"ø HWR

2"ø HWS

2"ø HWS

2"ø HWR

1 1/2"ø HWS

1 1/2"ø HWR

1 1/4"ø HWR 1 1/4"ø HWS

1 1/4"ø HWS

1 1/4"ø HWR

2"ø HWR

2"ø HWS

3/4"ø HWS

3/4"ø HWR

3/4"ø HWS 3/4"ø HWR

2"ø HWR

2"ø HWS

2"ø HWR

2"ø HWS 1 1/2"ø HWS

1 1/2"ø HWR

1 1/4"ø HWS

1 1/4"ø HWR 1"ø HWR

1"ø HWS

1 1/4"ø HWS

1 1/4"ø HWR

4" STM UP,

15 PSI

EOM DRIP

3/4" LPR

DOWN

4" STM DN,

15 PSI

1.5" LPR

DOWN

1.5" LPR

3-WAY VALVE

3-WAY VALVE

3-WAY VALVE

V60-2

V60-1

T T

1 1/4"ø HWS 1 1/4"ø HWR

1"ø HWS1"ø HWR

V34-2

V34-3

V34-1

V34-5

V34-4

T

T

T

T

T

3-WAY VALVE

V58-13 T

1 1/2"ø HWS

1 1/2"ø HWREXISTING STEAM &

CONDENSATE PIPING UP

FROM TUNNEL TO

REMAIN

COORDINATE THERMOSTAT

LOCATIONS WITH WALL

SWITCHES (TYP.)

COORDINATE T'STAT LOCATION WITH

FURNITURE LAYOUT

4"ø CHWR 4"ø CHWS

SEE SHEET M-MP-02B FOR

CONTINUATION

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

AREA B

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h /1

-M

E C

H -T

V H

S A

C Y

V A

M C

I n te g ra te d H e a lt h C e n te r- R

.r v t

/1

/2

:2

:1

A

M

M-MP-01B

GROUND FLOOR AREA B - PIPING TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5-20-2022 JBE

0 4' 8' 12'

1/8" = 1'-0"

1 GROUND FLOOR AREA B - PIPING

H

G

F

E

D

C

B

A

10987

4321 11 12

5.1

10.2

5.2

H1

F3

F2

E1

I2

H3

G1

12.511.5

9.57.5

15 16 17 18 19 22

F4

F1

E2

D1

C1

B1

H2

I1

I3

K

L

15.1 15.2 17.1 17.2

00 01 02 03

7.1

9.1

4.5

5.5

ROOF

ROOF

ROOF

REC THERAPY BELOW

AHU - 3

20 21

STAIR

G10

MECH EQUIP PLATFORM 1

100A

MECH EQUIP PLATFORM 1

100B

107-AHU-60

CONTROL AIR

COMPRESSOR 107-CC-1

ON MEZZANINE LEVEL

ROUTE CONNECTION SIZE CONDENSATE

LINE DOWN UNDER STAIRS AND OVER

TO SINK ON GROUND FLOOR

T

T

V35-14

V35-13

107-EF-4

107-EF-3 107-EF-5

107-EF-6

107-EF-2

107-EF-1

107-AHU-36

107-PRV-2

107-AHU-59

107-AHU-58

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

AREA A

AREA B

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h /1

-M

E C

H -T

V H

S A

C Y

V A

M C

I n te g ra te d H e a lt h C e n te r- R

.r v t

/1

/2

:2

:1

A

M

M-MP-02

SECOND FLOOR OVERALL -

PIPING

TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5-20-2022 JBE

1/16" = 1'-0"

1 SECOND FLOOR OVERALL - PIPING

0 8' 16' 32'4'

SCUPPER SCUPPER SCUPPERSCUPPER

I

H

G

F

E

D

C

B

A

10987

11 12

5.1

10.2

5.2

H1

F3

F2

E1

I2

H3

G1

12.511.5

9.57.5

F4

F1

E2

D1

C1

B1

7.1

9.1

STAIR

G10

MECH EQUIP PLATFORM 1

100A

MECH EQUIP PLATFORM 1

100B

T

T

3"ø CHWS

2 1/2"ø CHWS

107-P-3

V35-14

V35-13

1"ø

DDC

107-PRV-2

5" LPS TO WATER HEATER

1 1/4"ø LPS

2"ø LPR

3" MPS UP

FROM BELOW

3"ø CHWR

1-1/4" HWS & R

107-AHU-36

EXISTING PIPING UP TO

107-AHU-35 ON ROOF

3/4"ø LPR

2" LPR CONDENSATE

FROM AUTO TRAP PUMP,

KEEP LOW.

4" CHWS & CHWR

UP FROM BELOW

CONNECTION SIZE CONDENSATE

FROM WATER HEATER TO TRAP

PUMP.

107-APT-1

3/4" STEAM TO TRAP PUMP.3" STEAM VENT

CONNECT 3" VENT FROM

107-PRV-2 TO EXISTING 4"

UP THRU ROOF OR ROUTE

3" UP SEPARATELY

EXISTING PIPING UP FROM

BELOW

E.O.M.

DRIP

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

AREA A

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h /1

-M

E C

H -T

V H

S A

C Y

V A

M C

I n te g ra te d H e a lt h C e n te r- R

.r v t

/1

/2

:2

:2

A

M

M-MP-02A

SECOND FLOOR AREA A - PIPING TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5-20-2022 JBE

0 4' 8' 12'

1/8" = 1'-0"

1 MECH EQUIP PLATFORM 1 AREA A - PIPING

H

G

F

G1

15 16 17 18 19 22

F4

F1

E2

D1

C1

B1

H2

I1

I3

K

L

15.1 15.2 17.1 17.2

20 21

MECH EQUIP PLATFORM 2

107-AHU-60

107-HWP-1

& 2

107-AS-1

107-HEX-1

107-HEX-2

107-RH-2

107-RH-1

107-APT-3

107-EF-4

107-EF-3

107-EF-5

107-EF-6

107-EF-1

FLOW METER (DIGITAL FLOW DF868)

ET-1

DDC PANEL

DDC PANEL

VFD'S

4" STEAM, 15 PSI, UP FROM BELOW

3/4"LPR

1" LPR

3"ø CHWR3"ø CHWS

3"ø CHWR 3"ø CHWS

1 1/2"ø HWS

1 1/2"ø HWR

1-1/2" LPR CONDENSATE DOWN

3-WAY VALVE107-P-2

107-P-1

3/4"LPR

1"LPR

2"ø LPS

107-APT-2

4"ø HWS

4"ø HWR

2"ø HWS

2"ø HWR

107-UH-1

107-AHU-59

107-AHU-58

T

4"ø CHWR

3"ø HWS

3"ø HWR

4"ø CHWS

2"ø HWR2"ø HWS

3/4"ø LPR

1 1/4"ø LPS

E.O.M. DRIP

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

AREA B

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h /1

-M

E C

H -T

V H

S A

C Y

V A

M C

I n te g ra te d H e a lt h C e n te r- R

.r v t

/1

/2

:2

:2

A

M

M-MP-02B

SECOND FLOOR AREA B - PIPING TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5-20-2022 JBE

0 4' 8' 12'

1/8" = 1'-0"

1 MECH EQUIP PLATFORM 2 AREA B - PIPING

107-AHU-58 DATA & DIMENSIONS

(BASIS OF DESIGN)

Revisions: Date:

107-AHU-60 DATA

(BASIS OF DESIGN)

NOTE:

1.

2.

3.

4.

ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.

WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE

REGARDLESS OF W DIMENSION.

ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2" [40mm] MAXIMUM

SPACE BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE.

WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL BE DOUBLE

VANE TYPE.

W1

W

VANE

VANE

NOTE:

1.

2.

THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.

ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS ELBOWS. ALL

SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE CONSTRUCTED,

SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.

R SHALL

EQUAL

OR BE

GREATER

THAN W.

R SHALL

EQUAL

OR BE

GREATER

THAN

1/3W.R

R SHALL

EQUAL

OR BE

GREATER

THAN

1/6W.

STANDARD RADIUS OR

LONG RADIUS ELBOW

SHORT RADIUS ELBOW

WITH ONE VANE

SHORT RADIUS ELBOW

WITH TWO VANES

W

R

2/3W

/3

W

W W

1/6W

1/2W 1 /3

W

R

NOTE:

UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.

MAX.

MAX.

E Q

U

IP

M E

N T

AIR

FLOW

AIR

FLOW

TYPICAL DUCTWORK TRANSITION

PLAN OR SIDE VIEWTYPICAL DUCTWORK TRANSITION WITH

EQUIPMENT MOUNTED IN DUCT

PLAN OR SIDE VIEW

MAX.

MAX.

MAX.

MAX.

15° 30°

15°

30°

15°

15°

AIR SPLIT DUCT TAKE-OFF PLAN

VIEW

BRANCH DUCT TAKE-OFF PLAN VIEW

SUPPLY REGISTER TAKE-OFF

PLAN VIEW

AIR

FLOW

AIR

FLOW

A

IR

F L

O W

SUPPLY REGISTER

OR BRANCH DUCT

TURNING VANES

MAIN

SUPPLY

DUCT

SEE FLOOR PLAN FOR

SPLIT DIMENSION

PROVIDE VOLUME

DAMPER

PROVIDE VOLUME

DAMPER

ADJUSTABLE

METAL ROD

OR LINKAGE

TOP REGISTER

MAIN

SUPPLY

DUCT

VOLUME EXTRACTOR; ADJUSTABLE FROM

FULLY CLOSED POSITION TO CFM NOTED

ON FLOOR PLANS

AIR

FLOW

AIR

FLOW

1/4 W OR 4" [100mm] MIN.

AIR

FLOW

MAIN SUPPLY

DUCT

A

IR

F L

O W

W

RIGID DUCT TO AIR TERMINAL

UNIT.

ROUND SHEET METAL DUCT.

MAIN SUPPLY

PLAN VIEW

45°M A X

"D

SMACNA FIGURE 4-6

45° LEED IN

RIGID DUCT TO AIR TERMINAL

UNIT.

MAIN SUPPLY

PLAN VIEW

FLOW

F L O

W

MAIN EXHAUST OR RETURN

PLAN VIEW

AIR

FLOW AIR

FLOW

W

PROVIDE VOLUME DAMPER

AT EACH BRANCH DUCT

1/4W OR 4" [100mm]

MIN.

BRANCH DUCT

VD

NOTE:

1.

2.

DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.

DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR

MULTI-BLADE DAMPERS & ROUND DAMPERS.

INSULATION SEE

SPECIFICATION

DAMPER BLADE

1/8" [6mm]

CLEARANCE

ALL AROUND

OUTSIDE END BEARING

INSIDE END BEARING

HANDLE WITH

LOCKING

QUADRANT

INSULATION STAND-OFF

1/2" [15mm] ROUND

ROD PIN

DUCT

STIFFEN BLADE

AS REQUIRED

SIDE ELEVATION SECTION

SECTION "A-A"

"B" "B"

NOTES:

1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS TIGHTLY.

2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS.

3. SEE SMACNA 2005, FIGURE 9-15

ACCESS PANEL

ACCESS DOOR

CASING

GASKET

HANDLE INSIDE

FLEXIBLE

WASHER

FACTORY

FABRICATED

LATCH

SECTION "B-B"

INSULATION

DUCT

GASKET

INSULATION

INSULATION

"A"

"A"

ROUND FLEXIBLE CONNECTION

RECTANGULAR FLEXIBLE CONNECTION

FLANGED

CONNECTION ON FAN

SIDE

WASHER 1-1/2" [40mm] MIN. TO 3" [75mm] MAX.

INSTALLED. 6" [150mm] NOMINAL WITH

MATERIAL TAUT

FLEXIBLE

MATERIAL AS

SPECIFIED

1"x1/8" [25x3mm] DRAW BAND

1"x1/8" [25x3mm] BAND IRON

BOLT ON 4" [100mm] CENTERS

5/16" [8mm] FLANGE

DUCT

SHEET METAL SCREWS ON

12" [300mm] CENTERS

RIVET ON 4"

[100mm] CENTERS

SHEET METAL AS

SPECIFIED FOR

DUCTWORK.

1"x1/8" [25x3mm] BAND IRON

BOLT ON 4" [100mm] CENTERS

1" [25mm] FLANGE & HEMALTERNATE

POSITION

OF BOLT 1 1/2" [40mm]

POCKET SLIP

DUCT

SHEET METAL AS

SPECIFIED FOR

DUCTWORK.

[15mm] [15mm] [40mm]

1 1/2" [40mm] MIN. TO 3" [75mm] MAX.

INSTALLED. 6" [150mm] NOMINAL WITH

MATERIAL TAUT

FLANGED

CONNECTION

ON FAN SIDE

WASHER

FLEXIBLE MATERIAL

AS SPECIFIED

1/2" 1/2" 1 1/2"

NOTE:

1.

2.

3.

4.

5.

6.

A VERTICAL DAMPER IS SHOWN. HORIZONTAL DAMPER INSTALLATION, 1S SIMILAR. FOLLOW

DAMPER MANUFACTURER'S INSTRUCTIONS, INCLUDING FASTENER OPTIONS AND GAGES FOR

SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST BE INSTALLED IN THE PARTITION OR

FLOOR AND NOT OUTSIDE THE PENETRATION.

GALVANIZED SLEEVE: GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO DAMPER

FRAME AND TO PERIMETER ANGLES.

PERIMETER ANGELS: GALVANIZED STEEL, NOT LESS THAN 1 1/2"x1 1/2" [40x40mm], 14 GAGE, TO

PROVIDE 1" [25mm] MINIMUM OVERLAP OF OPENING ON ALL 4 SIDES.

BREAKAWAY DUCT CONNECTION: CONTRACTOR'S OPTION OF TYPES SHOWN IN SMACNA.

ACCESS PANELS: SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE LINK OR LINKS.

PROVIDE 1/4" TO 1/2" [6 TO 15mm] CLEARANCE ON HEIGHT AND WIDTH. FILL OPEN SPACE WITH

ROCK WOOL FIRESTOP FIBER.

ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS AND

MECHANICAL ROOM FLOORS, SHALL BE PROVIDED WITH 3" [75mm] HIGH CONCRETE CURB

AROUND OPENING FOR DUCT.

SLEEVE, NOTE 2

DUCT

CONNECTION

NOTE 4

DAMPER,

NOTE 1

DAMPER COLLAR

EXTENSION INTEGRAL

PART OF SLEEVE

SLEEVE, NOTE 2

NOTE 6FIRE BARRIER

PARTITION OR CHASE

TYPICAL DUCT

INSULATION

PERIMETER ANGLE, NOTE 3 (NOTE

FASTENED TO PARTITION)

ACCESS

PANEL

NOTE 5

[2 m m

NOTE:

ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS AND FAN

ROOM FLOORS SHALL BE PROVIDED WITH A 3" [75mm] HIGH CONCRETE CURB AROUND

OPENING FOR DUCT.

SEAL HOLE WITH FIREPROOFING

MATERIAL AFTER DUCT INSTALLATION

2"x2"x1/4" [50x50x6mm] ANGLE

INSTALL ON BOTH LONG

DIMENSION SIDES OF DUCT.

DUCT RISER - SEE FLOOR PLANS

FOR DETAILS

SEAL HOLE WITH FIREPROOFING

MATERIAL AFTER DUCT INSTALLATION

FLOOR

EXTEND ANGLE 3" [75mm]

BEYOND DUCT

DUCT RISER - SEE FLOOR PLANS

FOR SIZES SHEET METAL SCREWS 4" [100mm]

ON CENTER

1 1/2"x1 1/2"x1/8" [40x40x3mm] ANGLE

INSTALL ON BOTH LONG DIMENSION

SIDES OF DUCT. FOR DUCTS OVER 60"

[1500mm] USE 2"x2"x1/8" [50x50x3mm]

ANGLE.

HOLE IN STRUCTURAL FLOOR

DUCT RISER

0.5 INCH WG [125Pa] TO 2 INCHES WG [500Pa] DUCT RISER SUPPORT

ARRANGE RISER SO REINFORCER

TRANSVERSE JOINT IS AT RISER

SUPPORT POINT

FLOOR

2 INCHES WG [500Pa] TO 4 INCHES WG [1000Pa] DUCT RISER SUPPORT

HOLE IN STRUCTURAL FLOOR

DUCT RISER

NOTE:

1.

2.

3.

4.

5.

6.

RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A

MINIMUM OF 3 TIMES THE DIAMETER OF INLET

A FLEXIBLE AIR DUCT CONNECTOR IS NOT MANDATORY FOR INLET TO THIS

BOX, BUT ALLOWED TO ACCOMMODATE MINOR OFFSETS. MAXIMUM LENGTH

3'-0" [900mm].

A BRANCH DUCT SERVING AN INDIVIDUAL BOX MAY BE THE SAME SIZE AS THE

BOX INLET, PROVIDED THE EQUIVALENT LENGTH OF THE BRANCH DUCT, AS

SHOWN, DOES NOT EXCEED 10 FEET (3 METERS). FOR LONGER LENGTHS,

INCREASE THE DUCT SIZE AND PROVIDE A DUCT TRANSITION TO MAINTAIN

THE DUCT STATIC PRESSURE DROP AT OR BELOW 0.2"/100' [1.64Pa/m].

FLEXIBLE AIR DUCT CONNECTORS, WHEN USED FROM TERMINAL UNIT SUPPLY

AIR DUCT TO DIFFUSER, SHALL NOT EXCEED 5'-0" [1500mm]. USE RIGID

ELBOWS FOR CHANGE OF DIRECTION GREATER THAN 45°.

COMPONENT ARRANGEMENT MAY VARY BY MANUFACTURER. PROVIDE

INSULATION W/VAPOR BARRIER FOR CONNECTING DUCT SECTIONS.

USE OF THE FLEXIBLE AIR DUCT CONNECTORS ARE NOT PERMITTED FOR THE

DEDICATED AHU SERVING THE SURGICAL SUITE.

AIR TERMINAL UNIT

(CV OR VAV)

REHEAT COIL

SOUND

ATTENUATOR SEE

EQUIPMENT

SCHEDULE

FLEXIBLE AIR DUCT

CONNECTOR. SEE DETAIL

DIFFUSER (TYP.)

SEE SPECIFICATIONS FOR

CLAMPS AND SEALANT (TYP.)

SEE NOTE 5

SEE NOTE 1

SEE NOTE 2

SEE NOTE 3

S E

E N

O T

E

SECTION A-A (BASE NOT POURED WITH SLAB)

SECTION A-A (BASE POURED WITH FLOOR SLAB)

PLAN

TYPICAL ANCHOR

BOLT NUT & WASHER

SECTION B-B

EQUIPMENT BASE PLATE

PROVIDE #3 BARS 12" [300mm] O.C.

EACH WAY IN THE BASE & DOWEL

BASE TO FLOOR

EQUIPMENT BASE PLATE

PROVIDE DOUBLE SLAB

REINFORCING IN BASE AREA

WELD HEAD TO PLATE OR

BEND OVER END 5D

FLOOR

PIPE SLEEVE (5D, 3"

[75mm] MIN.)

ANCHOR

BOLT (TYP)

CONCRETE BASE

NOTE:

L & W DIMENSIONS SHALL

BE 6" [150mm] GREATER

THAN THE EQUIPMENT

BASE PLATE.

A

A

[400mm]

M

IN

[1 m m

M

IN

[1 m m

TYPICAL ANCHOR

BOLT NUT & WASHER

[2 m m

L /1

L

/1

L

W

D

D

5D

16"

BB

2D

SECTION A-A (ADD ON TO EXISTING CONCRETE PAD)

ADDED ON CONCRETE PAD

PROVIDE #3 BARS 12" [300mm] O.C.

EACH WAY IN THE BASE & DOWEL

BASE TO FLOOR

M

IN

[1 m m

L /1

EXISTING

CONCRETE

PAD

PROVIDE WELDED WIRE REMESH

SECURE CURB CAP TO WOOD NAILING STRIP WITH 3/8" [10mm] CADMIUM PLATED LAG BOLTS

NOT OVER 12" [300mm] ON CENTER.

SECURE ROOF CURB, DUCTWORK AND DAMPER TO ROOF WITH EXPANSION BOLTS

(CONCRETE ROOF) OR RUST RESISTANT BOLTS (METAL DECK AND BAR JOIST ROOF).

RUN ELECTRICAL LINES THROUGH CLEARANCE HOLE PROVIDED IN GRAVITY DAMPER, THEN

THROUGH VENTILATOR ELECTRICAL CONDUIT GUIDE.

GRAVITY BACKDRAFT

DAMPER

RIGID CONDUIT TO

ACCOMMODATE

ELECTRICAL WIRES

SEE NOTE 2

PREFABRICATED

ROOF CURB, 12"

HIGH

WOOD NAILING

STRIP

ELECTRICAL

CONDUIT GUIDE

MOTOR HOUSING

DUCT

TRANSITION DUCT TO FULL

SIZE OF DAMPER SUPPLIED

WITH ROOF VENTILATOR

ROOF

SEE NOTE 2

SEE NOTE 1

CURB CAP

NOTE:

1.

2.

3.

PIPE HANGERS - PROVIDE KINETICS KSIP

SUSPENDED INLINE PUMP SUPPORT OR

APPROVED EQUIVALENT ON EACH SIDE

OF PUMP (SEE NOTE NO. 1)

PRESSURE GAGE

1/2" [15mm]

STRAINERFLEXIBLE

CONNECTION

BALL OR

BUTTERFLY TYP.

NOTES:

1. SUPPORT PUMP FROM PIPING ONLY. DO NOT SUPPORT PUMP FROM MOTOR.

2. ELIMINATE BALANCING VALVE WHEN PUMP IS CONTROLLED BY VARIABLE SPEED

DRIVE

BALANCING DEVICE

HEAVY GAUGE HOT

DIPPED GALVANIZED

STEEL TOP WITH RUST

PROOF COATING

FASTEN AS REQUIRED

SEAL AIR & WATER TIGHT

WITH CAULK

EXISTING CURB

FLASHING

ROOF

BLOCK OR SPRAY

FOAM INSULATION, SEE

ARCHITECTURAL FOR

TYPE (MIN. 12" THICK

W/VAPOR BARRIER)

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h /1

-M

E C

H -T

V H

S A

C Y

V A

M C

I n te g ra te d H e a lt h C e n te r- R

.r v t

/1

/2

:1

:0

A

M

M-MJ-01

MECHANICAL DETAILS TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5-20-2022 JE

NOT TO SCALE

1 DUCTWORK SQUARE VANE ELBOWS

NOT TO SCALE

2 DUCTWORK RAIDUS ELBOWS

NOT TO SCALE

DUCTWORK TRANSITIONS (WITH

EQUIPMENT MOUNTED IN DUCT)

NOT TO SCALE

4 SUPPLY DUCTWORK TAKEOFFS

NOT TO SCALE

SUPPLY DUCT TAKEOFF - AIR TERMINAL

UNITS

NOT TO SCALE

ALTERNATE SUPPLY DUCT TAKEOFF -

AIR TERMINAL UNITS

NOT TO SCALE

EXHAUST OR RETURN BRANCH

DUCTWORK

NOT TO SCALE

8 VOLUME DAMPER DETAIL

NOT TO SCALE

9 ACCESS PANEL AND DOOR DETAIL

NOT TO SCALE

10 FLEXIBLE DUCT CONNECTIONS

NOT TO SCALE

SECTION THRU FIRE DAMPER

INSTALLATION

NOT TO SCALE

12 DUCT RISER SUPPORTS

NOT TO SCALE

DUCT CONNECTIONS - AIR TERMINAL

UNITS

NOT TO SCALE

14 CONCRETE EQUIPMENT BASES

NOT TO SCALE

15 POWER ROOF VENTILATOR

NOT TO SCALE

16 INLINE PUMP DETAIL

NOT TO SCALE

17 CURB CAP DETAIL

SIDE VIEW TRAPEZE HANGER FOR UP TO

453KG [1000 LB.] UNIFORM LOAD

ADJUSTABLE CLEVIS HANGER TYPE 1 - SEE

SPECIFICATIONS

ADJUSTABLE CLEVIS HANGER TYPE 43 - SEE

SPECIFICATIONS

PROVIDE INSULATION SHIELD

& INSERT FOR ALL PIPING

(200mm [8"] MIN.)

BAND

43mm [1-5/8"] 12 GAUGE CHANNEL OR 50x50x6.4mm

[2"X2"X1/4"] ANGLE

15mm [1/2"] DIA.

HANGER RODS WITH

900mm [36"] MAX.

SPACING ON EACH

CHANNEL

WELD

SADDLE

INSULATION SHIELD

AT HANGER

PROVIDE HIGH COMPRESSIVE

STRENGTH INSULATION (9 PSF MIN.

DENSITY) UNDER INSULATION SHIELD

INSULATION (VAPOR

BARRIER TYPE IS

REQUIRED FOR LOW

TEMPERATURE PIPE)

HANGER ROD

MAXIMUM PIPE/TUBING SUPPORT SPACING

NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.

NOM. SIZE

PIPE

TUBING

m m

1" M

A X mm

[IN]

mm

[FT]

mm

[FT]

THRU 20

[THRU 3/4]

[7]

[5]

[1]

[7]

[6]

[11/4]

[7]

[7]

[11/2]

[9]

[8]

[2]

[10]

[8]

[21/2]

[11]

[9]

[3]

[12]

[10]

[4]

[14]

[12]

[5]

[16]

[13]

[6]

[17]

[14]

[8]

[19]

[16]

[10]

[22]

[12]

[23]

[14]

[25]

[16]

[27]

[18]

[28]

[20]

[30]

[24]

[32]

P

D

C

D+[1"]

D+25mm INSULATE AS INDICATED FOR ALL CHILLED WATER.

INSULATE PIPE ONLY FOR STEAM, CONDENSATE

& HEATING WATER.

NOTE:

WHERE USED FOR COPPER TUBE OR PIPE, BRAZE TO FABRICATED STEEL ANCHOR

D+[21/2"]

D+[43/4"]

D+121mm

D+64mm

D+[11/2"]

D+38mm

D+[33/4"]

D+95mm

8mm

[5/16"]

ANCHOR BOLTS N=NUMBER

S=SIZE

DRILL ∅ = S+2mm

DRILL ∅ = S+[ 1/16"]

STL PIPE OR

COPPER TUBE

D=PIPE O.D.

NOTE A

PIPE ANCHOR SCHEDULE

D P C N S BOLT PATTERN

mm in mm in mm in mm in mm in

13 1/2"

102 4

19 3/4

21/2

11/2

5/8

1/2

3/8

3/8

3/8

1/2

3/8

3/8

1/4

3/4

5/8

5/8

5/8

NOTES:

1. PROVIDE ANCHORS ONLY WHERE SHOWN ON

DRAWINGS.

2. EXTEND SLEEVE ABOVE FLOOR WHERE

SPECIFIED.

INSULATION BOLT (TYPICAL)

FLOOR SLAB

FIRE-STOPPING

MATERIAL

BOLT

PIPE

PIPE SLEEVE

WHERE SPECIFIED

RISER

CLAMP

PIPE

PIPE SLEEVE WHERE

SPECIFIED

RISER CLAMP. BOTTOM

CLAMP REQUIRED AT

ANCHOR POINTS ONLY.

ELEVATION

PLAN

RISER CLAMP

STEEL EXPANSION SHIELD FOR EXISTING

CONSTRUCTION AND INSERTS FOR NEW

CONSTRICTION THIS TYPE SHALL BE USED

ONLY IN SLABS OR BEAMS OF 4" [100mm]

MIN DEPTH

3/8" [10mm] MIN DIA EXPANSION BOLTS FOR

EXISTING CONSTRUCTION AND INSERTS

FOR NEW CONSTRUCTION

CONCRETE

FLOOR SLAB

CLIP

ANGLE

NUTS & WASHERS

3/8" [10mm] MIN DIA

HANGER RODS

FOR PIPES UNDER 2" [50mm] IN SIZE USE 1 1/2"x1 1/2"x1/4" [40x40x6.4mm] ANGLE. ALL PIPES 2" [50mm] & LARGER USE 3"x3"x1/4" [75x75x6.4mm]

ANGLE

TURNBUCKLE

3/8" [10mm] MIN DIA

HANGER RODS

3/8" [10mm] MIN DIA

INSERTS NEW

CONSTRUCTION ONLY.

GREATER THAN 50mm [2"] DIA. PIPE 50mm [2"] DIA. & SMALLER

VERTICAL

GREATER THAN 50mm [2"] DIA. PIPE 50mm [2"] DIA. & SMALLER

HORIZONTAL

65mm [2 1/2"] DIA.

NOTE:

PROVIDE THE APPROPRIATE WELL DEPTH TO HAVE THE NECESSARY

INSULATION STAND-OFF DISTANCE.

65mm [2 1/2"] DIA.

TYPICAL MANUAL AIR VENT

TYPICAL CHILLED AND HOT WATER PIPING DRAIN

VALVE CONNECTIONS

ELEVATION THREADED

PIPING

ELEVATION

WELDED PIPING

TYPICAL WATER PIPING

REDUCER, IF REQUIRED

3/4" [20mm] BALL VALVE

ADAPTER TO 3/4" [20mm] HOSE

THREAD-PROVIDE HOSE CAP NUT

NOTES:

1. DRAIN ALL LOW POINTS AS INDICATED ABOVE.

2. WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS AND/OR PLANS LOCATE DRAIN

AT BOTTOM OF SCALE POCKET.

AIR VENT

1/2" [15mm]

BALL VALVE

1/4" [8mm]

COPPER TUBING

1/2" [15mm] x 4" [100mm]

NIPPLE

CIRCULATING WATER PIPING

ELEVATION

NOTES:

1. VENT ALL HIGH POINTS INDICATED ABOVE.

2. IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE TO DRAIN.

MV

OR

AV

COIL

TEST PLUG (TYP.)

REDUCER, IF REQUIRED

WATER RETURN

MANUAL AIR VENT

UNION CONNECTIONS

(TYP.)

WATER SUPPLY

SHUT OFF VALVE

DRAIN WITH HOSE

CONNECTION

MV

MODULATION CONTROL VALVE

NOTE:

1.

2.

PROVIDE IN CHILLED WATER MAIN AND IN CONDENSER WATER MAIN.

LOCATE PILOT TUBE TAPS 20 PIPE DIAMETERS DOWNSTREAM AND 10 PIPE

DIAMETERS UPSTREAM FROM THE NEAREST PIPE FITTING.

EITHER TOP OR SIDE LOCATION. BOTH ARE NOT REQUIRED AT SAME LOCATION.

PLUG

1 1/2" [40mm] FULL

PORT BALL VALVE

1 1/2"∅x2" LONG [40x50mm] PIPE

1 1/2" [40mm] FULL PORT

BALL VALVE

PLUG

WELD (TYP)

COMBINATION BALANCING

AND FLOW MEASURING VALVE,

SEE SPECS FOR TYPE.

SERVICE VALVES

SEE SPECS FOR TYPE

REQUIRED (TYP.)

SUPPLY

RETURN

SUPPLY

RETURN

PROVIDE MINIMUM 5

PIPE DIAMETERS OF

STRAIGHT PIPE

UPSTREAM OF VALVE,

COORDINATE W/ VALVE

MANUFACTURER

SINGLE COIL

WATER COIL

AIR VENT WHEN

COIL IS NOT

SELF-VENTING

DRAIN WHEN COIL IS

NOT SELF-DRAINING

TEST PLUG (TYP.)

PIPE HANGER SHALL SUPPORT

PIPING INDEPENDENT OF COIL

REDUCER, IF REQUIRED

DRAIN

WATER COIL

AIR VENT WHEN

COIL IS NOT

SELF-VENTING

TEST PLUG

(TYP.)

PIPE HANGER SHALL SUPPORT

PIPING INDEPENDENT OF COIL

WATER COIL

REDUCER, IF REQUIRED

FLOW ELEMENT

DRAIN WHEN COIL

IS NOT SELF-DRAINING

DRAIN

DOUBLE COIL

NOTES:

1. WHEN COIL IS INCLUDED IN CASING MOUNTED ON VIBRATION ISOLATORS THE FIRST 2 HANGERS FOR EACH PIPE SHALL BE SPRING &

NEOPRENE TYPE. TYPE "H" FOR 100mm [4"]∅ PIPE & SMALLER. TYPE "H-P" FOR 125mm [5"]∅ PIPE & LARGER.

2. PIPING SHALL BE INSTALLED IN SUCH MANNER THAT IT WILL NOT BLOCK THE SWING OR USE OF ACCESS DOORS OR PANELS; NEITHER

SHALL IT BLOCK THE SERVICING OF FILTERS, VALES, OR EQUIPMENT.

3. THE FLOW ELEMENT MAY BE INSTALLED IN THE SUPPLY PIPING IF THE REQUIRED MINIMUM UPSTREAM AND DOWNSTREAM DIMENSIONS

CANNOT BE OBTAINED IN THE RETURN PIPING.

FE

MV

MV

MV

MV

MV

MV

FE

TI

TI

TEMPERATURE

INDICATION TO ECC

SEE CONTROL

DIAGRAM

MV

CALIBRATED BALANCING

VALVE (TYP.)

NOTE:

1. ALL DRIP POINTS ON STEAM MAINS SHALL BE PROVIDED WITH A 300mm [12"] MINIMUM HIGH DRIP LEG FROM BOTTOM OF

STEAM MAIN TO TRAP INLET. DRIP LEG SHALL HAVE 150mm [6"] SCALE POCKET BELOW TRAP INLET.

TO RETURN MAIN

PIPE SIZE SHALL BE SAME SIZE AS TRAP

THERMOSTATIC TRAP. SEE OTHER

STEAM DETAILS, PLANS, AND

SCHEDULES

DIELECTRIC FITTING WHERE

RETURN IS COPPER PIPE

FLOW

SCHEDULE 80

STEEL PIPE

0m m

0m m

DRIP LEG OR EQUIPMENT CONNECTION. MAKE

THE SAME SIZE AS THE SUPPLY MAIN OR

EQUIPMENT CONNECTION. SEE NOTE 1

[1 2"

M

IN

[6

" M

IN

SCHEDULE 80 STEEL PIPE

SEE DRAWINGS FOR PIPE SIZES

25mm [1"]

GATE VALVE

USE 4-BOLT RAISED FACE FLANGES

STEAM TRAP ASSEMBLY

m m

[6

M

IN

m m

[1 2" m m [6

M

IN

[1

2"

M

IN

m m

DRIP LEG (TYP.)

20mm [3/4"] DRAIN (ALTERNATE

LOCATIONS) (TYPICAL)

STEAM LINE

(TYPICAL)

CAP (TYPICAL)

PIPE T0 STEAM

TRAP (TYPICAL)

NOTE:

DRIP POCKET PIPE SIZE SAME AS

STEAM MAIN UNLESS OTHERWISE

NOTED.

STEAM LINE DRIP POCKET

20mm [3/4"] MIN.

FROM DRIP

CONNECTION DRIP RETURN

10mm [3/8"] TEST CONNECTION

D U

C T

H E

IG

H

T

H

1/

H 1/

H

1/

H

STEAM

CONDENSATE

RETURN

TEMPERATURE

SWITCH

SCALE POCKET

HUMIDIFIER CONTROL

VALVE

TO HUMIDISTAT

MANIFOLD PIPE ADAPTERS

STEAM SUPPLY

ON-OFF CONTROL VALVE DUCT CROSS SECTION

[1 m m

INVERTED BUCKET

TRAP ASSEMBLY

NOTE:

SEE MANUFACTURER'S PIPING RECOMMENDATIONS FOR FINAL LAYOUT

6" M

IN

NOTES:

1. WHEN COIL IS INCLUDED IN CASING MOUNTED ON VIBRATION ISOLATOR

UNITS, THE RUNOUT PIPING FOR CONNECTIONS TO COIL SHALL BE

INSTALLED WITH SWING JOINTS TO ALLOW FOR THE VIBRATION.

2. PIPING SHALL BE INSTALLED IN SUCH MANNER THAT IT WILL NOT BLOCK

THE SWING OR USE OF ACCESS DOORS OR PANELS; NEITHER SHALL IT

BLOCK THE SERVICING OF FILTERS, VALVES, OR EQUIPMENT.

3. TRAP EACH COIL SEPARATELY WHEN INSTALLED IN A BANK OF TWO OR

MORE HIGH. ALSO PROVIDE SEPARATE VACUUM BREAKER FOR EACH COIL.

4. TWO TRAP ASSEMBLIES IN PARALLEL ARE SHOWN. TWO TRAPS REQUIRED

WHEN CONDENSATE LOAD IS 2400 KG/HR [5,000 LBS/HR] OR GREATER.

5. SUPPLY & RETURN PIPES ARE SHOWN FROM SAME END. REHEAT COIL MAY

HAVE SUPPLY & RETURN PIPES FROM OPPOSITE ENDS.

PIPE HANGER SHALL

SUPPORT PIPING

INDEPENDENT OF

COIL (TYP.)

PITCH COIL DOWN 8mm

[1/4"] PER FOOT TO

CONDENSATE OUTLET

FULL SIZE

TAPPING

PRESSURE GAGE

SCALE POCKET

SEE NOTE

NO. 4

STEAM CONDENSATE

RETURN

15mm [1/2"] C

HECK

VALVE VACUUM

BREAKER

INCREASER,

IF REQUIRED

REDUCER,

IF REQUIRED

0m m

[6 " M

IN

0m m

[1 2"

M

IN

STEAM SUPPLY

CONDENSATE

TO DRAIN

MV

MANUAL

AIR VENT

TO BUILDING

LOAD

INVERTED BUCKET

TRAP ASSEMBLY

STEAM PIPE

WELDED TEE

300mm[12"]

150mm[6"]WELDED

TEE

SCHEDULE 80 STEEL PIPE

25mm [1"] GATE VALVE

NOTES:

1. ALL DRIP POINTS ON STEAM MAINS SHALL BE PROVIDED WITH A 300mm [12"] MINIMUM HIGH DRIP LEG FROM BOTTOM OF STEAM MAIN TO

TRAP INLET. DRIP LEG SHALL HAVE 150mm [6"] SCALE POCKET BELOW TRAP INLET.

2. PROVIDE BYPASS PIPING.

SEE DRAWINGS FOR PIPE SIZES

TO RETURN MAIN

SCHEDULE 80 STEEL PIPE

PIPE SIZE SHALL BE SAME SIZE AS TRAP

INVERTED BUCKET TRAP. SEE

PLANS, AND SCHEDULES

DIELECTRIC FITTING WHERE

RETURN IS COPPER PIPE

FLOW

SCHEDULE 80

STEEL PIPE

BYPASS-INSTALL IN HORIZONTAL PLANE LEVEL WITH

TRAP OR IN VERTICAL PLANE & BELOW TRAP

0m m

0m m

DRIP LEG OR EQUIPMENT CONNECTION. MAKE

THE SAME SIZE AS THE SUPPLY MAIN OR

EQUIPMENT CONNECTION. SEE NOTE 1

[1 2"

M

IN

[6

" M

IN

1" GATE VALVE

USE 4-BOLT RAISED FACE FLANGES

NOTE:

ALL DRIP POINTS ON STEAM MAINS SHALL BE PROVIDED WITH A 300mm [12"] MINIMUM HIGH DRIP LEG FROM BOTTOM OF STEAM MAIN TO

TRAP INLET. DRIP LEG SHALL HAVE 150mm [6"] SCALE POCKET BELOW TRAP INLET.

TO RETURN MAIN

PIPE SIZE SHALL BE SAME SIZE AS TRAP

FLOAT AND THERMOSTATIC TRAP.

SEE PLANS, AND SCHEDULES

DIELECTRIC FITTING WHERE

RETURN IS COPPER PIPE

FLOW

SCHEDULE 80

STEEL PIPE

BYPASS-INSTALL IN HORIZONTAL PLANE LEVEL WITH

TRAP OR IN VERTICAL PLANE & BELOW TRAP PROVIDE

BYPASS PIPING FOR ALL TRAPS 25mm [1"] AND

LARGER. 3

m m m m

DRIP LEG OR EQUIPMENT CONNECTION. MAKE

THE SAME SIZE AS THE SUPPLY MAIN OR

EQUIPMENT CONNECTION. SEE NOTE 1

[1 2"

M

IN

[6

" M

IN

SCHEDULE 80 STEEL PIPE

SEE DRAWINGS FOR PIPE SIZES

25mm [1"]

GATE VALVE

USE 4-BOLT RAISED FACE FLANGES

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

B

IM

/T V

H S

A lv in

C Y o rk

V A

I n te g ra te d H e a lt h /1

-M

E C

H -T

V H

S A

C Y

V A

M C

I n te g ra te d H e a lt h C e n te r- R

.r v t

/1

/2

:1

:1

A

M

M-MJ-02

MECHANICAL DETAILS TVHS - ALVIN C. YORK VAMC -

INTEGRATED HEALTH CENTER

SHK5-20-2022 JE

NOT TO SCALE

1 PIPE HANGERS

NOT TO SCALE

2 SMALL PIPE ANCHOR

NOT TO SCALE

3 SUPPORT/ANCHOR FOR PIPE RISERS

NOT TO SCALE

4 SECURING HANGER RODS IN CONCRETE

NOT TO SCALE

INSTALLATION OF THERMOMETER

WELLS

NOT TO SCALE

DRAIN VALVE AND AIR VENT

CONNECTIONS (HYDRONIC SYSTEMS)

NOT TO SCALE

TERMINAL UNIT WATER COILS - PIPING

CONNECTIONS

NOT TO SCALE

17 PITOT TEST CONNECTIONS

NOT TO SCALE

9 FLOW MEASURING STATION

NOT TO SCALE

10 WATER COILS - PIPING CONNECTIONS

NOT TO SCALE

11 THERMOSTATIC STEAM TRAP ASSEMBLY

NOT TO SCALE

STEAM TRAP ASSEMBLY AND STEAM

LINE DRIP POCKET

NOT TO SCALE

STEAM HUMIDIFIER - PIPING

CONNECTIONS

NOT TO SCALE

14 STEAM COIL - PIPING CONNECTIONS

NOT TO SCALE

15 END OF STEAM LINE DRIP TRAP

NOT TO SCALE

INVERTED BUCKET STEAM TRAP

ASSEMBLY

NOT TO SCALE

FLOAT AND THERMOSTATIC STEAM

TRAP ASSEMBLY

DRAW THRU

BLOW THRU

2" [50mm]

PLUS X

1" [25mm]

MINIMUM

X

2X

UNIT TYPE A B

WHERE X = STATIC PRESSURE IN PAN

DRAIN LINE SHALL BE AT LEAST THE SAME SIZE AS

THE NIPPLE ON THE DRAIN PAN

PIPING SHALL BE RIGID COPPER TYPE L OR TYPE M

UNLESS NOTE BELOW IS MET

PITCH DOWN TOWARD

DRAIN

CLEAN OUT

FLOOR SINK

DRAIN PAN

NOTE: 1. CPVC PIPE MAY BE USED ONLY IF APPROVED BY LOCAL VA AND IS

INDOORS AND DOES NOT PASS THROUGH RATED BARRIERS.

2. DIELECTRIC FITTING TO BE USED WHEN TWO DISSIMILAR METALS ARE TO BE

CONNECTED.

A B

[2 m m

DIELECTRIC

FITTING

DIFFUSER CONE (INSUL. PER SPEC.)

DIFFUSER NECK (INSUL. PER SPEC.)

(2438.4 mm)

MAX. 8'-0" IN LENGTH

DRAW BAND

HIGH EFFICIENCY TAP W/ VOLUME

CONTROL DAMPER (INSUL. PER SPEC.)

FLEXIBLE DUCT

DRAW BAND

LIGHT

CEILING TEE

FULLY EXTENDED.

3/8" SOLID ROD

DAMPER WITH 2"

STANDOFF

NOTES:

4. VERTICAL POSITION SHOWN. HORIZONTAL INSTALLATION SIMILAR.

3. ALL ATTACHMENTS PER MANUFACTURER'S APPROVED INSTALLATION INSTRUCTION.

1. PROVIDE ACCESS DOOR & LABEL ON SIDE OR BOTTOM OF DUCT AS FOLLOWS:

12" x 12"

8" x 8"

22" AND ABOVE

14" THRU 20"

10" THRU 12"

DOOR SIZEDUCT WIDTH

18" x 18"

165°F FUSIBLE LINK

NOTE #5

WRAPPED SHEET METAL DUCT

NOTE #1

METAL STUD CONSTRUCTION

CLOSURE TAPE

6" MAX.

CAULKING (TYP. OF 2)

CLEARANCE 1/8" PER

LINEAR FOOT, BOTH

DIMENSIONS

FIRE RESISTIVE

MATERIAL (TYP.)

DUCT WRAP W/VAPOR

BARRIER (TYP.)

DUCT MOUNTED SMOKE DETECTOR

TO BE INSTALLED WITHIN

5'-0" OF DAMPER PER

MANUFACTURER'S RECOMMENDATIONS,

WITH NO AIR INLETS OR OUTLETS

BETWEEN THE DETECTOR AND THE

DAMPER.

MOUNTING ANGLE 1" MIN.

OVERLAP ALL SIDES

PLAIN "S" SLIP (TYP.)

BREAK-AWAY CONNECTION

U.L. (555S) LABELED

FIRE/SMOKE DAMPER,

SECURE TO SLEEVE

MANUFACTURER OR

FIELD FABRICATED

STEEL SLEEVE 16 GA.

MIN.

RETAINING ANGLES 1-1/2"x 1-1/2"x 1/8"

MIN. ALL SIDES. (SEE NOTE #2)

2. 1-1/2" x 1-1/2" x 1/8" RETAINING ANGLES SHALL LAP STRUCTURAL OPENING 1" MIN. & COVER

CORNERS OF OPENINGS. ANGLES ATTACH TO SLEEVE ONLY AND MUST NOT BE ATTACHED TO

EACH OTHER AT CORNERS OR TO WALL.

5. ACTUATOR TO BE MOUNTED ON OUTSIDE OF DAMPER SLEEVE ON

ACCESIBLE SIDE. ACTUATOR SHALL NOT INTERFERE WITH "S" JOINT.

ACTUATOR ASSEMBLY TO BE U.L. LABELED.

6. VERIFY THAT ACCESS IS PROVIDED ON THE ACTUATOR SIDE OF THE WALL/FLOOR SO

THAT THE LINK MAY BE SERVICED WITH THE DAMPER IN CLOSED POSITION.

NOTES:

4. VERTICAL POSITION SHOWN. HORIZONTAL INSTALLATION SIMILAR. DAMPER TO BE

SPRING LOADED WHEN HORIZONTAL.

3. ALL ATTACHMENTS PER MANUFACTURER'S APPROVED INSTALLATION INSTRUCTION.

2. 1-1/2"x1-1/2"x1/8" RETAINING ANGLES SHALL LAP STRUCTURAL OPENING 1" MIN. &

COVER CORNERS OF OPENINGS. ANGLES ATTACH TO SLEEVE ONLY AND MUST NOT

BE ATTACHED TO EACH OTHER AT CORNERS OR TO WALL.

1. PROVIDE ACCESS DOOR & LABEL ON SIDE OR BOTTOM OF DUCT AS FOLLOWS:

LINK

FUSIBLE

165°F

4" MIN.

1" MIN.

SLEEVE 16 GA. MIN.

FABRICATED STEEL

MANUF. OR FIELD

NOTE# 2

EACH SIDE

6" MAXIMUM

METAL STUD CONSTRUCTION

MATERIAL (TYP.)

FIRE RESISTIVE

NOTE # 1

DUCT SIZE

FASTENER W/WASHER

DUCT

SHEET METAL

NOTE # 2)

MIN. ALL SIDES (SEE

1-1/2"x1-1/2"x1/8"

RETAINING ANGLES

CLOSURE TAPE (TYP.)

BARRIER (TYP.)

DUCT WRAP W/VAPOR

METAL DUCT

WRAPPED SHEET

PLAIN "S" SLIP

(555) SECURE TO SLEEVE

U.L. LABELED FIRE DAMPER,

DIMENSIONS.

LINEAR FOOT BOTH

CLEARANCE 1/8" PER

CONSTRUCTION

CONCRETE OR MASONRY

18" x 18"

10" THRU 12"

14" THRU 20"

22" AND ABOVE

8" x 8"

12" x 12"

DOOR SIZEDUCT WIDTH

Notes:

A SECTION A-A

Floor or Wall Assembly-Min 4-1/2 in. thick lightweight (100-150 pcf) concrete. Wall assembly may also be constructed of any UL Classified Concrete Blocks*. Max dia.

of circular through-opening is 12-1/4 in.

*See Concrete Block (Cazt) category in fire resistance Directory for names of manufacturers.

Steel Pipe or Conduit-Nom 10 in. dia.

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .