Attachment 12 - MECH BINDER-2.pdf
PDF 10 MB Posted
- Solicitation number
- 36C77623B0037
About this file
This document provides details for a federal contract opportunity to construct an integrated health center in Murfreesboro, Tennessee. The solicitation number is 36C77623B0037 and is being issued by the Department of Veterans Affairs Technology Acquisition Center in Austin, Texas. The project involves the construction of an integrated health center for Veterans Affairs facility number 626-309. No other details are provided on the required construction products or services, the response deadline, or anticipated award date. The attached file is labeled as an appendix but does not appear to include any further salient information on the requirements.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
107-EF-5 107-EF-6
107-RH-2 107-RH-1
CONTRACTOR TO REINSTALL EXISTING
LIGHTNING PROTECTION ON NEW HOODS
CURB CAP WITH INSULATION
CURB CAP WITH INSULATION
CURB CAP WITH INSULATION
CURB CAP WITH INSULATION
107-EF-3
107-EF-4
107-EF-1
NEW STEAM VENT FROM PRV
IN BASEMENT
107-IL-1
107-IL-2
107-RL-4
MOUNTED
ABOVE DOOR
LADDER UP TO ROOF
LADDER UP TO ROOF
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2020
TLC No.:
www.tlc-engineers.com
121388
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldhfr.com
WOLD | HFR DESIGN
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
KEYPLAN
AREA B
B
IM
/T V
H S
A lv in
C Y o rk
V A
I n te g ra te d H e a lt h /1
-M
E C
H -T
V H
S A
C Y
V A
M C
I n te g ra te d H e a lt h C e n te r- R
.r v t
/1
/2
:1
:4
A
M
M-MH-03B
ROOF PLAN AREA B - DUCTWORK TVHS - ALVIN C. YORK VAMC -
INTEGRATED HEALTH CENTER
SHK5-20-2022 JBE
0 4' 8' 12'
1/8" = 1'-0"
1 ROOF PLAN AREA B - DUCTWORK
Revisions: Date:
ET-1
107-HEX-2
107-APT-3
107-RH-2
107-RH-1
107-AHU-58
107-AHU-59
107-RAF-60
107-AHU-60
72x24
16x16
20x20
30x20
40x18 x2
48x24 x1
107-HWP-1
& 2
107-RH-1
107-RH-2
107-AHU-58
107-AHU-59
30x20 x1
62x24
40x24
ET-1
107-HEX-1
107-HWP-1
& 2
20x20
THE AREA AT EACH END OF THE MECHANICAL ROOM WILL NOT BE
EASILY ACCESSABLE, DO NOT LOCATE EQUIPMENT SUCH AS
DAMPERS OR SENSORS WHICH WILL REQUIRE SERVICE IN THIS
AREA. LOCATE EQUIPMENT IN THE MECHANICAL ROOM WHERE IT
WILL BE EASILY ACCESSABLE.
IT ROOM
GROUND FLOOR
MECH EQUIP PLATFORM 2
ROOF
DDC
VFD
107-RH-1
107-AHU-58
107-EF-6
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2020
TLC No.:
www.tlc-engineers.com
121388
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldhfr.com
WOLD | HFR DESIGN
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
B
IM
/T V
H S
A lv in
C Y o rk
V A
I n te g ra te d H e a lt h /1
-M
E C
H -T
V H
S A
C Y
V A
M C
I n te g ra te d H e a lt h C e n te r- R
.r v t
/1
/2
:1
:5
A
M
M-MH-04
SECTIONS TVHS - ALVIN C. YORK VAMC -
INTEGRATED HEALTH CENTER
SHK5-20-2022 JBE
NOT TO SCALE
MECH EQUIP PLATFORM 2 - VIEW 1
NOT TO SCALE
MECH EQUIP PLATFORM 2 - VIEW 2
NOT TO SCALE
MECH EQUIP PLATFORM 2 - VIEW 3
NOT TO SCALE
MECH EQUIP PLATFORUM 2 - VIEW 4
J
II
H
G
F
E
D
C
B
A
10987
4321 11 12
5.1
10.2
5.2
H1
F3
F2
E1
I2
H3
G1
12.511.5
9.57.5
15 16 17 18 19 22
K
L
15.1 15.2 17.1 17.2
00 01 02 03
7.1
9.1
4.5
5.5
20 21
EXISTING
PRV-1
EXISTING
PRV-2
EXISTING
PRV-4
107-PRV-3
EXISTING PRV SERVING
HUMIDIFIERS ON
AHU-34, 35, AND HEAT
EXCHANGERS IN
EXISTING MECH RM
G11
5" CHWS & R UP TO 2ND
FLR MECH RM SERVING
107-AHU-35 & 36
6" CHWS & R DN
FROM EXISTING MECH
RM
NEW 2" LPR DOWN TO
DRIP RETURN IN TUNNEL
4"ø
EXISTING
FLASH TANK
3" MPS UP TO 107-PRV-1
NEW 3" MPS UP TO
107-PRV-2
2-1/2" CHWS & R UP TO AHU-37 SERVING
CANTEEN AREA, FLOW TO THIS UNIT WAS
NOT KNOWN AND WAS ASSUMED TO BE
ABOUT 90 GPM OF CHILLED WATER.
AHU-37 IS THE ONLY UNIT ASSUMED TO BE
ON THIS CHILLED WATER PIPE.
PROVIDE NEW END OF MAIN DRIP AND NEW 8"
STEAM SHUTOFF VALVE FOR BUILDING 107.
COORDINATE LOCATION IN TUNNEL WITH VA
8" MEDIUM PRESSURE STEAM
2-1/2" DRIP RETURN
EXISTING 3" VAC RETURN
3/4" LPR FROM 107-PRV-1
1-1/4" PUMPED
CONDENSATE FROM
107-CRU-1
LPS
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2020
TLC No.:
www.tlc-engineers.com
121388
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldhfr.com
WOLD | HFR DESIGN
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
KEYPLAN
AREA A
AREA B
B
IM
/T V
H S
A lv in
C Y o rk
V A
I n te g ra te d H e a lt h /1
-M
E C
H -T
V H
S A
C Y
V A
M C
I n te g ra te d H e a lt h C e n te r- R
.r v t
/1
/2
:1
:2
A
M
M-MP-00
BASEMENT OVERALL - PIPING TVHS - ALVIN C. YORK VAMC -
INTEGRATED HEALTH CENTER
SHK5-20-2022 JBE
0 8' 16' 32'4'
1/16" = 1'-0"
1 BASEMENT OVERALL - PIPING
ORIGINAL 1958 PIPE TUNNEL PLAN FOR REFERENCE
NOT TO SCALE
H
G
F
E
D
C
B
A
10987
11 12
5.1
10.2
5.2
H1
F3
F2
E1
I2
H3
G1
12.511.5
9.57.5
7.1
9.1
3" MPS LINE UP TO 107-PRV-1 IN
MECHANICAL ROOM
NEW 3" MPS UP TO 107-PRV-2 AND
107-AHU-36 HUMIDIFIER ON
SECOND FLOOR
EXISTING 5" CHWS & R UP TO 107-
AHU-35 & 36 ON SECOND FLOOR
EXISTING 6" CHWS & R DOWN
FROM MECHANICAL ROOM, VERIFY
DIRECTION OF FLOW AND LABLE
PIPES CORRECTLY
1-1/4" PUMPED CONDENSATE
FROM WATER HEATERS IN MECH
ROOM
3/4" LPR CONDENSATE FROM 107-
PRV-1 IN MECH ROOM
NEW 2" LPR CONDENSATE FROM
WATER HEATER, 107-PRV-2, AND
107-AHU-36 HUMIDIFIER ON
SECOND FLOOR, CONNECT TO
EXISTING DRIP RETURN
2-1/2" CHWS & R UP TO 107-AHU-37
SERVING CANTEEN AREA, FLOW
TO THIS UNIT WAS NOT KNOWN
AND WAS ASSUMED TO BE ABOUT
90 TO 100 GPM OF CHILLED
WATER. AHU-37 IS THE ONLY UNIT
ASSUMED TO BE ON THIS CHILLED
WATER PIPE.
EXISTING 2-1/2" DRIP
RETURN
EXISTING PRV-4
EXISTING 8" MED
PRESS STEAM
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2020
TLC No.:
www.tlc-engineers.com
121388
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldhfr.com
WOLD | HFR DESIGN
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
KEYPLAN
AREA A
B
IM
/T V
H S
A lv in
C Y o rk
V A
I n te g ra te d H e a lt h /1
-M
E C
H -T
V H
S A
C Y
V A
M C
I n te g ra te d H e a lt h C e n te r- R
.r v t
/1
/2
:1
:2
A
M
M-MP-00A
BASEMENT AREA A - PIPING TVHS - ALVIN C. YORK VAMC -
INTEGRATED HEALTH CENTER
SHK5-20-2022 JBE
0 4' 8' 12'
1/8" = 1'-0"
1 BASEMENT AREA A - PIPING
H
G
F
G1
17 18 19 22
K
L
15.1 15.2 17.1 17.2
20 21
CONNECT NEW STEAM VENT
TO EXISTING AND ROUTE AS
SHOWN, MATCH EXISTING
SIZE
ROUTE 3" STEAM VENT UP
TO ROOF
107-PRV-3
ROUTE 4" STEAM LINE UP TO
FLOOR ABOVE, 15 PSI
3/4" LPR FROM
ABOVE
1.5" LPR FROM 2ND
FLOOR MECH ROOM
CONNECT 3/4" LPR TO
EXISTING CONDENSATE AT
FLASH TANK
CONNECT 1.5" PCR TO
EXISTING CONDENSATE IN
TUNNEL
TRAP
4"ø LPS
EXISTING PRV SERVING
HUMIDIFIERS ON AHU-34 &
35, AND EXISTING HEAT
EXCHANGERS IN MECH RM
G11
EOM DRIP
2-1/2" STEAM VENT
1" LPR
3" MPS
2" STEAM TO MECH ROOM G11
5" STEAM MAIN
2-1/2" DRIP RETURN
5" STEAM MAIN
T
PROVIDE TEMP SENSOR IN
BASEMENT AREA FOR
MONITORING BY BAS
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2020
TLC No.:
www.tlc-engineers.com
121388
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldhfr.com
WOLD | HFR DESIGN
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
KEYPLAN
AREA B
B
IM
/T V
H S
A lv in
C Y o rk
V A
I n te g ra te d H e a lt h /1
-M
E C
H -T
V H
S A
C Y
V A
M C
I n te g ra te d H e a lt h C e n te r- R
.r v t
/1
/2
:1
:2
A
M
M-MP-00B
BASEMENT AREA B - PIPING TVHS - ALVIN C. YORK VAMC -
INTEGRATED HEALTH CENTER
SHK5-20-2022 JBE
0 4' 8' 12'
1/8" = 1'-0"
1 BASEMENT AREA B - PIPING
UP
UP
J
I I
G
F
E
D
C
B
A
10987
4321 11 12
5.1 10.25.2
H1
F3
F2
E1
I2
H3
G1
12.511.5
9.5 7.5
15 16 17 18 19 22
F4
F1
E2
D1
C1
B1
H2
I1
I3
K
L
15.1 15.2 17.1 17.2
00 01 02 03
7.1 9.1
ELECTRICAL
G41
SIM MAINTENANCE
G30G
PROCEDURE SIM LAB
G30FCONTROL ROOM
G30E
WAITING
G39
MULTI-PURPOSE
G20J
MULTI-PURPOSE
G20F
MULTI-PURPOSE
G20D
MULTI-PURPOSE
G20B
MULTI-PURPOSE
G20
MULTI-PURPOSE
G20H
STOR.
G20C
MED/SURG SIM LAB
G30D KITCHEN/SERVING
G21
EDUC CHIEF
G17A
MUSIC THERAPY CLINIC
G13
WC STORAGE
G12B
REC. THERAPY CLINIC
G08
COMPUTER LAB
G16
STOR.
G20A
STOR.
G20E
STOR
G20G
STOR.
G20I
BARBER CART
G02FOOD SERVICE CHIEF
G03
FOOD SERVICE VEND SUPPLY
G04
CORRIDOR
G54
CORRIDOR
G52
MUSIC THER. 1
G43
MUSIC THER. 2
G42
CORRIDOR
G45
WORK AREA
G15
ENTRY
G01
CORRIDOR
G46
COURTYARD
G10
CORRIDOR
G48
CORRIDOR
G48A
CORRIDOR
G49
CORRIDOR
G50
CORRIDOR
G51
STORAGE
G20K
4.5
5.5
PRACTICE ROOM
G13B
MUSIC STORAGE
G13A
ALS CLASSROOM
G30J
TRNG EQUIP STOR
G30C
STAFF LOUNGE
G33
CREATIVE ARTS GROUP
G34
LOBBY
G36
PMRS STORAGE
G31
ACCESS STAIR
G26
FEMALE
G24
MALE
G25
LACTATION
G27
HAC
G30I
MALE
G37
FEMALE
G38
MEDIA COORD.
G17B
WORK
G17
PAT. RESOURCE
G40
RT SPVR.
G15A
PMRS CONSULT
G14
HAC
G07
RECREATION
STORAGE
G08B
MALE
G09A
FEMALE
G09C
COPIER
COPIER
VENDING
G32
KINESIO GROUP THERAPY
G12
COPIERSAFE
WORK
G12A
KITCHENETTE
G08A
VESTIBULE
G35
SECURITY
G35A
STORAGE
G34A
CORRIDOR
G55
STORAGE
G30K
STORAGE
G30H
DE-BRIEF
G30A
CORRIDOR
G30 CORRIDOR
G30
CONNECTOR
G47
FEMALE SHOWER
G09D
MALE SHOWER
G09B
ENTRY
G44
CORRIDOR
G53
CHARGING CART STOR.
G19WHOLE HEALTH
STORAGE
G18
IT
G23
20 21
CHASE
G26A
CLO.
G30B
COMM/MEDIA CONTROL
G22
RISER
G13D
MECH.
G11
ELEC.
G28
ELEC.
G29
MECH.
G11A
STAIRS
G09
CORRIDOR
G46
V59-7
V59-6
V59-1
V59-8
V59-9
V59-10
V59-11
V59-12
V59-13
V59-5
V59-4
V59-3
V59-2
V58-2
V58-1
V58-3
V58-4 V58-5
V58-8 V58-11
V58-10
V58-7
V58-6
V58-9
V58-18
V58-19
V58-17
V58-12
V58-14
V58-15
V35-6
V35-7V35-5
V35-2
V35-8
V35-12
V35-9 V35-11
V35-10 V35-4
V35-3
V35-1
V58-20
V58-21
V58-16
V36-1
V36-2
V36-4
V36-3 V36-5
V36-6
V36-7
V36-9
V36-10
CAP OFF EXISTING 4"
UNDERGROUND CHILLED
WATER PIPES
COORDINATE DEPTH OF
UNDERGROUND PIPING
WITH NEW GRADE BEAMS
UNDER CONNECTOR.
107-CAC-1
ROUTE CONNECTION SIZE
DRAIN LINE FROM AIR
COMPRESSOR ON MEZZANINE
LEVEL DOWN TO SINK ON
MACHINE FLOOR LEVEL, SEE
PHOTO # 2.
107-EH-1
LOCATE AIR COMPRESSOR ON
MEZZANINE LEVEL, SEE PHOTO
# 3.
V36-8
V60-2 V60-1
V34-1
V34-3
V34-5
V34-2 V34-4
V58-13
107-CHWP-1
& 2
NEW 6" CHWS & CHWR
UNDERGROUND CHILLED
WATER PIPES, ADJUST
ROUTING AS NEEDED FOR
EXISTING CONDITIONS
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2020
TLC No.:
www.tlc-engineers.com
121388
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldhfr.com
WOLD | HFR DESIGN
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
KEYPLAN
AREA A
AREA B
B
IM
/T V
H S
A lv in
C Y o rk
V A
I n te g ra te d H e a lt h /1
-M
E C
H -T
V H
S A
C Y
V A
M C
I n te g ra te d H e a lt h C e n te r- R
.r v t
/1
/2
:1
:3
A
M
M-MP-01
GROUND FLOOR OVERALL -
PIPING
TVHS - ALVIN C. YORK VAMC -
INTEGRATED HEALTH CENTER
SHK5-20-2022 JBE
1. CONNECT NEW 6" CHWS AND CHWR TO EXISTING UNDERGROUND MAINS, SEE
PHOTO # 1 ON THIS SHEET.
2. ROUTE NEW PNEUMATIC LINE OVER TO KITCHEN AREA AND CONNECT INTO
EXISTING PNEUMATIC SYSTEM SERVING KITCHEN, GIFTSHOP, AND CANTEEN AREA.
FIELD VERIFY LOCATION. VERIFY ALL PENUMATIC CONTROLS SERVED BY THE NEW
COMPRESSOR FUNCTION PROPERLY AFTER CONNECTING TO NEW COMPRESSOR.
KEY NOTES:#
0 8' 16' 32'4'
1/16" = 1'-0"
1 GROUND FLOOR OVERALL - PIPING
PHOTO # 1
PHOTO # 2
ROUTE DRAIN LINE FROM NEW AIR
COMPRESSOR ON MEZZANINE TO
THIS SINK
PHOTO # 3 LOCATE AIR COMPRESSOR IN THIS
GENERAL AREA ON MEZZANINE
STAIRS UP TO MEZZANINE LEVEL SHOWN IN PHOTO # 2
(THIS SHEET ONLY)
J
I
F
E
D
C
B
A
11 12
5.1 10.25.2
F3
F2
E1
I2
H3
G1
12.511.5
9.57.5
F4
F1
E2
D1
C1
B1
7.1 9.1
AREA BAREA A
A R
E A
B
A R
E A
A
STAIRS
REC. THERAPY CLINIC
G08
BARBER CART
G02
FOOD SERVICE CHIEF
G03
CORRIDOR
G45
ENTRY
G01
CORRIDOR
G46
FOOD SERVICE VEND SUPPLY
G04
612 SF
CONNECTOR
G47
KITCHENETTE
G08A
MUSIC THERAPY CLINIC
G13
MUSIC STORAGE
G13A
WORK
G12A
EDUC CHIEF
G17A
RECREATION
STORAGE
G08B
HAC
G07
KINESIO GROUP THERAPY
G12
WC STORAGE
G12B
MALE
G09A
FEMALE
G09C
COURTYARD
G10
WORK AREA
G15
PRACTICE ROOM
G13B
PMRS CONSULT
G14
CHASE
G-104A
MALE SHOWER
G09B
FEMALE SHOWER
G09D
CLEAN
G12C
SOILED
G12D
MECH.
G11A
MECH.
G11
ELEC.
G28
ELEC.
G29
V35-3
V35-4
V35-10
V35-11
V35-9
V35-12
V35-8
V35-2
V35-7
V35-6
V35-1
V35-5
V36-1
V36-2
V36-3
V36-5
V36-4
V36-6
V36-7
V36-8 V36-9
V36-10
2"ø HWR
2"ø HWS
2"ø HWR 2"ø HWS
1 1/4"ø HWR 1 1/4"ø HWS
1"ø HWR
1"ø HWS
1"ø HWS 1"ø HWR
1 1/2"ø HWR 1 1/2"ø HWS 1 1/4"ø HWR
1 1/4"ø HWS
1 1/4"ø HWS
1 1/4"ø HWR
1"ø HWS
1"ø HWR
EXISTING 5" CHWS & R UP
FROM TUNNEL, CONNECT
NEW 4" TO EXISTING 5"
AND ROUTE AS SHOWN
4"CHWS & R UP
CONNECT NEW 1-1/2"
HWS & R TO EXISTING 3"
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
107-BAF-1
107-BAF-2
107-BAF-4107-BAF-3
107-BAF-6107-BAF-5
T
T
T
3-WAY VALVE
"ø
4"ø 4"ø
DOMESTIC WATER
HEATERS, SEE
PLUMBING
STEAM PIPING IS SIZED SO
WATER HEATERS CAN HEAT
40°F WATER UP TO 180°F
DURING CLEAN OUT
PROCEDURE BUT RECOMMEND
ONLY PEFORMING PROCEDURE
ON ONE HEATER AT A TIME.
1-1/4" PUMPED
CONDENSATE DOWN TO
EXISTING DRIP RETURN
IN TUNNEL
3" MPS UP & 2" LPR DN
FROM 107-PRV-2, WATER
HEATER, & HUMIDIFIER
ON AHU-36 ABOVE
1 1/4"ø HWR 1 1/4"ø HWS
S S
S S
S S
TO 107-BAF-1 & 2
TO 107-BAF-3 & 4
TO 107-BAF-5 & 6
107-EH-1
T
107-PRV-1
3" MPS FROM
MAIN IN TUNNEL
T
T
T
CEILING FAN CONTROLLERS
KINESIO ROOM TEMPERATURE CONTROL
3/4" CONDENSATE DOWN TO
EXISTING DRIP RETURN IN TUNNEL
1 1/4"ø
SEE CHILLED WATER PUMP
VIEW ON THIS SHEET.
107-CHWP-1
& 2
CAP EXISTING PIPING OFF
UNDERGROUND.
EOM DRIP
4"ø CHWR
4"ø CHWS
EOM
DRIP
107-AHU-34
EXISTING 4" STEAM
VENT FROM TUNNEL
UP TO ROOF.
NEW 3" MPS UP
FROM TUNNEL
2" LPR CONDENSATE
DOWN TO EXISTING DRIP
RETURN IN TUNNEL
VFD'S FOR CHWP-1 & 2
107-CRU-1
3-WAY VALVE
2"ø CHWS
6"ø CHWS
6"ø CHWR
6"ø CHWS
V34-1
EXISTING STEAM,
CONDENSTAT, HWS & HWR UP
TO FLOOR ABOVE.
1 1/4"ø HWS
1 1/4"ø HWR
2"ø CHWR
NEW 6" CHWS AND 6" CHWR
PIPING UNDERGROUND
107-CHWP-1
& 26"ø CHWS
6"ø CHWR
6" VERTICAL CHECK VALVE
6" FLANGED CIRCUIT SETTER
SEE PUMP DETAIL FOR VALVES
AND FITTINGS REQUIRED AT
PUMP INLET AND OUTLET
SHUTOFF VALVES
6" CROSS CONNECTION WITH
SHUTOFF, KEEP CLOSED NORMALLY
6"ø CHWR
6"ø CHWS
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2020
TLC No.:
www.tlc-engineers.com
121388
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldhfr.com
WOLD | HFR DESIGN
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
KEYPLAN
AREA A
B
IM
/T V
H S
A lv in
C Y o rk
V A
I n te g ra te d H e a lt h /1
-M
E C
H -T
V H
S A
C Y
V A
M C
I n te g ra te d H e a lt h C e n te r- R
.r v t
/1
/2
:2
:1
A
M
M-MP-01A
GROUND FLOOR AREA A - PIPING TVHS - ALVIN C. YORK VAMC -
INTEGRATED HEALTH CENTER
SHK5-20-2022 JBE
0 4' 8' 12'
1/8" = 1'-0"
1 GROUND FLOOR AREA A - PIPING
VAV BOXES V36-4, V36-6, AND V36-7 CONTROL THE ROOM TEMPERATURE FOR THE
KINESIO GROUP THERAPY ROOM. THESE 3 VAV BOXES SHALL HAVE
TEMPERATURE SENSORS IN THE KINESIO ROOM WHERE SHOWN ON FLOOR PLAN
AT RIGHT BUT THE TEMPERATURE CONTROLLERS SHALL BE LOCATED IN THE
WORK ROOM G12A. LABEL THE CONTROLLERS IN THE WORK ROOM "A", "B", AND
"C" AND PROVIDE A DIAGRAM SIMILAR TO PHOTO SHOWN ABOVE INDICATING ZONE
LOCATIONS. BOX V36-6 CONTROLS ZONE "A", BOX V36-4 CONTROLS ZONE "B", AND
BOX V36-7 CONTROLS ZONE "C"
KINESIO GROUP THERAPY ZONE MAP
KEY NOTES: (APPLIES TO THIS SHEET ONLY)
1. VERIFY THE REQUIRED DIRECTION OF CHILLED WATER FLOW IN EXISTING PIPES
BEFORE CONNECTING NEW PIPES TO MAKE SURE THE FLOW DIRECTION IS
CORRECT. REPLACE FLOW ARROWS ON PIPING WHEN PROPER DIRECTION IS
DETERMINED.
2. FULL SIZE VENT FROM CONDENSATE PUMP UP THRU ROOF.
3. 2-1/2" STEAM VENT FROM 107-PRV-1 UP THRU ROOF.
4. CONTRACTOR TO REFIL EXISTING HOT WATER SYSTEM AFTER CONNECTING NEW
PIPING. SYSTEM IS NOTED ON EXISTING PLANS TO CONTAIN 30% GLYCOL.
NOT TO SCALE
CHILLED WATER PUMP VIEW
CHILLED WATER PIPING SYSTEM NOTES:
• PROVIDE SHUTOFF VALVES AND 6" CROSS CONNECTION AS SHOWN IN VIEW ABOVE FOR BUILDING
107 SYSTEM FLUSHING.
• CONTRACTOR SHALL BE RESPONSIBILE FOR REFILLING CAMPUS CHILLED WATER SYSTEM TO
ACCOUNT FOR THE VOLUME OF NEW AND EXISTING PIPING IN BUILDING 107 WHEN NEW PIPING IS
CONNECTED TO EXISTING CAMPUS CHILLED WATER SYSTEM.
• CONTRACTOR TO ENSURE ALL AIR IS VENTING OUT OF THE CHILLED WATER SYSTEM WHEN
COMPLETE.
• CONTRACTOR SHALL BE RESPONSIBILE FOR ADDING ANY CHEMICALS AS NEEDED TO OVERALL
SYSTEM TO BALANCE PH LEVELS AND ENSURE PROPER CORROSION PROTECTION AND COMPLY
WITH ANY VA STANDARDS FOR CHILLED WATER SYSTEMS.
• CONTRACTOR TO REPLACE ANY EXISTING PIPE LABELS ON ANY EXISTING TO REMAIN CHILLED WATER PIPE IN THE SCOPE OF WORK AREA AND ENSURE THE FLOW ARROWS ARE POINTING IN THE
PROPER DIRECTION OF FLOW.
• CONTRACTOR TO REPLACE ANY DAMAGED PIPE INSULATION WITH NEW INSULATION ON EXISTING
TO REMAIN PIPE IN SCOPE OF WORK AREA.
• CONTRACTOR TO REPLACE ANY RUSTED OUT PIPE HANGERS AND SUPPORTS SERVING EXISTING
TO REMAIN PIPES WITH NEW HANGERS AND SUPPORTS IN THE TUNNEL AND ELSEWHERE IN THE
SCOPE OF WORK AREA.
I
H
F
G1
17 18 19 22
F4
F1
E2
D1
C1
B1
H2
I1
I3
K
L
15.1 15.2 17.1 17.2
MEDIA COORD.
G17B
LOBBY
G36
MALE
G37
FEMALE
G38
VESTIBULE
G35
SECURITY
G35A
58 SF
HAC
G30I
PAT. RESOURCE
G40
STORAGE
G34A
SIM MAINTENANCE
G30G
PROCEDURE SIM LAB
G30F
CONTROL ROOM
G30E
TRNG EQUIP STOR
G30C
499 SF
ALS CLASSROOM
G30J
MALE
G25
WAITING
G39
LACTATION
G27
MULTI-PURPOSE
G20J
MULTI-PURPOSE
G20F
MULTI-PURPOSE
G20D
MULTI-PURPOSE
G20B
MULTI-PURPOSE
G20
MULTI-PURPOSE
G20H
STOR.
G20A
STOR.
G20E STOR
G20G
STOR.
G20I
STOR.
G20C
MED/SURG SIM LAB
G30D
VENDING
G32
STAFF LOUNGE
G33
KITCHEN/SERVING
G21
EDUC CHIEF
G17A
WORK
G17
RT SPVR.
G15A
COMPUTER LAB
G16
CREATIVE ARTS GROUP
G34
CORRIDOR
G48
CORRIDOR
G48A
CORRIDOR
G49
CORRIDOR
G50
CORRIDOR
G51
STORAGE
G20K
FEMALE
G24
MUSIC THER. 1
G43 MUSIC THER. 2
G42
CORRIDOR
G54
CORRIDOR
G52
ACCESS STAIR
G26
PMRS STORAGE
G31
C O
P
IE
R
327 SF
DE-BRIEF
G30A
361 SF
CORRIDOR
G30
177 SF
STORAGE
G30H
65 SF
STORAGE
G30K
AREA BAREA A
A R
E A
B
A R
E A
A
C O
R R
ID
O
R T
O B
LD
G
217 SF
CORRIDOR
G30
WHOLE HEALTH
STORAGE
G18 m a n e q u in s to ra g e r a c k
CHARGING CART STOR.
G19
CORRIDOR
G53
IT
G23
20 21
CONNECTOR
G47
CHASE
G26A
CLO.
G30B
COMM/MEDIA CONTROL
G22
ELECTRICAL
G41
CORRIDOR
G45
S S
STEAM VENT UP
THRU ROOF, SIZE
TO MATCH EXISTING
V59-5
V59-4
V59-3
V59-2
V59-1
V58-15
V58-14
V58-12
V58-11 V58-8
V58-10
V58-16
V58-18
V58-19 V58-17
V58-20V58-21
V58-9
V58-6
V58-7
V58-2
V58-1
V58-3
V58-4
V58-5
V59-12
V59-13
V35-6
T
T
2"ø HWS
2"ø HWR
3"ø HWR
3"ø HWS
1 1/4"ø HWR 1 1/4"ø HWS
1"ø HWR 1"ø HWS
1 1/4"ø HWR
1 1/4"ø HWS
T
TT T
T
T
T
V59-6
V59-7
V59-8 V59-9
V59-10
V59-11
T
T
T T
T
T
T
T T
T
T
T
T
T
T
T
T
T
TT
T
T
T T T T
2"ø HWR
2"ø HWS
2"ø HWS
2"ø HWR
1 1/2"ø HWS
1 1/2"ø HWR
1 1/4"ø HWR 1 1/4"ø HWS
1 1/4"ø HWS
1 1/4"ø HWR
2"ø HWR
2"ø HWS
3/4"ø HWS
3/4"ø HWR
3/4"ø HWS 3/4"ø HWR
2"ø HWR
2"ø HWS
2"ø HWR
2"ø HWS 1 1/2"ø HWS
1 1/2"ø HWR
1 1/4"ø HWS
1 1/4"ø HWR 1"ø HWR
1"ø HWS
1 1/4"ø HWS
1 1/4"ø HWR
4" STM UP,
15 PSI
EOM DRIP
3/4" LPR
DOWN
4" STM DN,
15 PSI
1.5" LPR
DOWN
1.5" LPR
3-WAY VALVE
3-WAY VALVE
3-WAY VALVE
V60-2
V60-1
T T
1 1/4"ø HWS 1 1/4"ø HWR
1"ø HWS1"ø HWR
V34-2
V34-3
V34-1
V34-5
V34-4
T
T
T
T
T
3-WAY VALVE
V58-13 T
1 1/2"ø HWS
1 1/2"ø HWREXISTING STEAM &
CONDENSATE PIPING UP
FROM TUNNEL TO
REMAIN
COORDINATE THERMOSTAT
LOCATIONS WITH WALL
SWITCHES (TYP.)
COORDINATE T'STAT LOCATION WITH
FURNITURE LAYOUT
4"ø CHWR 4"ø CHWS
SEE SHEET M-MP-02B FOR
CONTINUATION
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2020
TLC No.:
www.tlc-engineers.com
121388
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldhfr.com
WOLD | HFR DESIGN
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
KEYPLAN
AREA B
B
IM
/T V
H S
A lv in
C Y o rk
V A
I n te g ra te d H e a lt h /1
-M
E C
H -T
V H
S A
C Y
V A
M C
I n te g ra te d H e a lt h C e n te r- R
.r v t
/1
/2
:2
:1
A
M
M-MP-01B
GROUND FLOOR AREA B - PIPING TVHS - ALVIN C. YORK VAMC -
INTEGRATED HEALTH CENTER
SHK5-20-2022 JBE
0 4' 8' 12'
1/8" = 1'-0"
1 GROUND FLOOR AREA B - PIPING
H
G
F
E
D
C
B
A
10987
4321 11 12
5.1
10.2
5.2
H1
F3
F2
E1
I2
H3
G1
12.511.5
9.57.5
15 16 17 18 19 22
F4
F1
E2
D1
C1
B1
H2
I1
I3
K
L
15.1 15.2 17.1 17.2
00 01 02 03
7.1
9.1
4.5
5.5
ROOF
ROOF
ROOF
REC THERAPY BELOW
AHU - 3
20 21
STAIR
G10
MECH EQUIP PLATFORM 1
100A
MECH EQUIP PLATFORM 1
100B
107-AHU-60
CONTROL AIR
COMPRESSOR 107-CC-1
ON MEZZANINE LEVEL
ROUTE CONNECTION SIZE CONDENSATE
LINE DOWN UNDER STAIRS AND OVER
TO SINK ON GROUND FLOOR
T
T
V35-14
V35-13
107-EF-4
107-EF-3 107-EF-5
107-EF-6
107-EF-2
107-EF-1
107-AHU-36
107-PRV-2
107-AHU-59
107-AHU-58
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2020
TLC No.:
www.tlc-engineers.com
121388
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldhfr.com
WOLD | HFR DESIGN
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
KEYPLAN
AREA A
AREA B
B
IM
/T V
H S
A lv in
C Y o rk
V A
I n te g ra te d H e a lt h /1
-M
E C
H -T
V H
S A
C Y
V A
M C
I n te g ra te d H e a lt h C e n te r- R
.r v t
/1
/2
:2
:1
A
M
M-MP-02
SECOND FLOOR OVERALL -
PIPING
TVHS - ALVIN C. YORK VAMC -
INTEGRATED HEALTH CENTER
SHK5-20-2022 JBE
1/16" = 1'-0"
1 SECOND FLOOR OVERALL - PIPING
0 8' 16' 32'4'
SCUPPER SCUPPER SCUPPERSCUPPER
I
H
G
F
E
D
C
B
A
10987
11 12
5.1
10.2
5.2
H1
F3
F2
E1
I2
H3
G1
12.511.5
9.57.5
F4
F1
E2
D1
C1
B1
7.1
9.1
STAIR
G10
MECH EQUIP PLATFORM 1
100A
MECH EQUIP PLATFORM 1
100B
T
T
3"ø CHWS
2 1/2"ø CHWS
107-P-3
V35-14
V35-13
1"ø
DDC
107-PRV-2
5" LPS TO WATER HEATER
1 1/4"ø LPS
2"ø LPR
3" MPS UP
FROM BELOW
3"ø CHWR
1-1/4" HWS & R
107-AHU-36
EXISTING PIPING UP TO
107-AHU-35 ON ROOF
3/4"ø LPR
2" LPR CONDENSATE
FROM AUTO TRAP PUMP,
KEEP LOW.
4" CHWS & CHWR
UP FROM BELOW
CONNECTION SIZE CONDENSATE
FROM WATER HEATER TO TRAP
PUMP.
107-APT-1
3/4" STEAM TO TRAP PUMP.3" STEAM VENT
CONNECT 3" VENT FROM
107-PRV-2 TO EXISTING 4"
UP THRU ROOF OR ROUTE
3" UP SEPARATELY
EXISTING PIPING UP FROM
BELOW
E.O.M.
DRIP
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2020
TLC No.:
www.tlc-engineers.com
121388
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldhfr.com
WOLD | HFR DESIGN
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
KEYPLAN
AREA A
B
IM
/T V
H S
A lv in
C Y o rk
V A
I n te g ra te d H e a lt h /1
-M
E C
H -T
V H
S A
C Y
V A
M C
I n te g ra te d H e a lt h C e n te r- R
.r v t
/1
/2
:2
:2
A
M
M-MP-02A
SECOND FLOOR AREA A - PIPING TVHS - ALVIN C. YORK VAMC -
INTEGRATED HEALTH CENTER
SHK5-20-2022 JBE
0 4' 8' 12'
1/8" = 1'-0"
1 MECH EQUIP PLATFORM 1 AREA A - PIPING
H
G
F
G1
15 16 17 18 19 22
F4
F1
E2
D1
C1
B1
H2
I1
I3
K
L
15.1 15.2 17.1 17.2
20 21
MECH EQUIP PLATFORM 2
107-AHU-60
107-HWP-1
& 2
107-AS-1
107-HEX-1
107-HEX-2
107-RH-2
107-RH-1
107-APT-3
107-EF-4
107-EF-3
107-EF-5
107-EF-6
107-EF-1
FLOW METER (DIGITAL FLOW DF868)
ET-1
DDC PANEL
DDC PANEL
VFD'S
4" STEAM, 15 PSI, UP FROM BELOW
3/4"LPR
1" LPR
3"ø CHWR3"ø CHWS
3"ø CHWR 3"ø CHWS
1 1/2"ø HWS
1 1/2"ø HWR
1-1/2" LPR CONDENSATE DOWN
3-WAY VALVE107-P-2
107-P-1
3/4"LPR
1"LPR
2"ø LPS
107-APT-2
4"ø HWS
4"ø HWR
2"ø HWS
2"ø HWR
107-UH-1
107-AHU-59
107-AHU-58
T
4"ø CHWR
3"ø HWS
3"ø HWR
4"ø CHWS
2"ø HWR2"ø HWS
3/4"ø LPR
1 1/4"ø LPS
E.O.M. DRIP
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2020
TLC No.:
www.tlc-engineers.com
121388
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldhfr.com
WOLD | HFR DESIGN
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
KEYPLAN
AREA B
B
IM
/T V
H S
A lv in
C Y o rk
V A
I n te g ra te d H e a lt h /1
-M
E C
H -T
V H
S A
C Y
V A
M C
I n te g ra te d H e a lt h C e n te r- R
.r v t
/1
/2
:2
:2
A
M
M-MP-02B
SECOND FLOOR AREA B - PIPING TVHS - ALVIN C. YORK VAMC -
INTEGRATED HEALTH CENTER
SHK5-20-2022 JBE
0 4' 8' 12'
1/8" = 1'-0"
1 MECH EQUIP PLATFORM 2 AREA B - PIPING
107-AHU-58 DATA & DIMENSIONS
(BASIS OF DESIGN)
Revisions: Date:
107-AHU-60 DATA
(BASIS OF DESIGN)
NOTE:
1.
2.
3.
4.
ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.
WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE
REGARDLESS OF W DIMENSION.
ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2" [40mm] MAXIMUM
SPACE BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE.
WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL BE DOUBLE
VANE TYPE.
W1
W
VANE
VANE
NOTE:
1.
2.
THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.
ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS ELBOWS. ALL
SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE CONSTRUCTED,
SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.
R SHALL
EQUAL
OR BE
GREATER
THAN W.
R SHALL
EQUAL
OR BE
GREATER
THAN
1/3W.R
R SHALL
EQUAL
OR BE
GREATER
THAN
1/6W.
STANDARD RADIUS OR
LONG RADIUS ELBOW
SHORT RADIUS ELBOW
WITH ONE VANE
SHORT RADIUS ELBOW
WITH TWO VANES
W
R
2/3W
/3
W
W W
1/6W
1/2W 1 /3
W
R
NOTE:
UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.
MAX.
MAX.
E Q
U
IP
M E
N T
AIR
FLOW
AIR
FLOW
TYPICAL DUCTWORK TRANSITION
PLAN OR SIDE VIEWTYPICAL DUCTWORK TRANSITION WITH
EQUIPMENT MOUNTED IN DUCT
PLAN OR SIDE VIEW
MAX.
MAX.
MAX.
MAX.
15° 30°
15°
30°
15°
15°
AIR SPLIT DUCT TAKE-OFF PLAN
VIEW
BRANCH DUCT TAKE-OFF PLAN VIEW
SUPPLY REGISTER TAKE-OFF
PLAN VIEW
AIR
FLOW
AIR
FLOW
A
IR
F L
O W
SUPPLY REGISTER
OR BRANCH DUCT
TURNING VANES
MAIN
SUPPLY
DUCT
SEE FLOOR PLAN FOR
SPLIT DIMENSION
PROVIDE VOLUME
DAMPER
PROVIDE VOLUME
DAMPER
ADJUSTABLE
METAL ROD
OR LINKAGE
TOP REGISTER
MAIN
SUPPLY
DUCT
VOLUME EXTRACTOR; ADJUSTABLE FROM
FULLY CLOSED POSITION TO CFM NOTED
ON FLOOR PLANS
AIR
FLOW
AIR
FLOW
1/4 W OR 4" [100mm] MIN.
AIR
FLOW
MAIN SUPPLY
DUCT
A
IR
F L
O W
W
RIGID DUCT TO AIR TERMINAL
UNIT.
ROUND SHEET METAL DUCT.
MAIN SUPPLY
PLAN VIEW
45°M A X
"D
SMACNA FIGURE 4-6
45° LEED IN
RIGID DUCT TO AIR TERMINAL
UNIT.
MAIN SUPPLY
PLAN VIEW
FLOW
F L O
W
MAIN EXHAUST OR RETURN
PLAN VIEW
AIR
FLOW AIR
FLOW
W
PROVIDE VOLUME DAMPER
AT EACH BRANCH DUCT
1/4W OR 4" [100mm]
MIN.
BRANCH DUCT
VD
NOTE:
1.
2.
DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR
MULTI-BLADE DAMPERS & ROUND DAMPERS.
INSULATION SEE
SPECIFICATION
DAMPER BLADE
1/8" [6mm]
CLEARANCE
ALL AROUND
OUTSIDE END BEARING
INSIDE END BEARING
HANDLE WITH
LOCKING
QUADRANT
INSULATION STAND-OFF
1/2" [15mm] ROUND
ROD PIN
DUCT
STIFFEN BLADE
AS REQUIRED
SIDE ELEVATION SECTION
SECTION "A-A"
"B" "B"
NOTES:
1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS TIGHTLY.
2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS.
3. SEE SMACNA 2005, FIGURE 9-15
ACCESS PANEL
ACCESS DOOR
CASING
GASKET
HANDLE INSIDE
FLEXIBLE
WASHER
FACTORY
FABRICATED
LATCH
SECTION "B-B"
INSULATION
DUCT
GASKET
INSULATION
INSULATION
"A"
"A"
ROUND FLEXIBLE CONNECTION
RECTANGULAR FLEXIBLE CONNECTION
FLANGED
CONNECTION ON FAN
SIDE
WASHER 1-1/2" [40mm] MIN. TO 3" [75mm] MAX.
INSTALLED. 6" [150mm] NOMINAL WITH
MATERIAL TAUT
FLEXIBLE
MATERIAL AS
SPECIFIED
1"x1/8" [25x3mm] DRAW BAND
1"x1/8" [25x3mm] BAND IRON
BOLT ON 4" [100mm] CENTERS
5/16" [8mm] FLANGE
DUCT
SHEET METAL SCREWS ON
12" [300mm] CENTERS
RIVET ON 4"
[100mm] CENTERS
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
1"x1/8" [25x3mm] BAND IRON
BOLT ON 4" [100mm] CENTERS
1" [25mm] FLANGE & HEMALTERNATE
POSITION
OF BOLT 1 1/2" [40mm]
POCKET SLIP
DUCT
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
[15mm] [15mm] [40mm]
1 1/2" [40mm] MIN. TO 3" [75mm] MAX.
INSTALLED. 6" [150mm] NOMINAL WITH
MATERIAL TAUT
FLANGED
CONNECTION
ON FAN SIDE
WASHER
FLEXIBLE MATERIAL
AS SPECIFIED
1/2" 1/2" 1 1/2"
NOTE:
1.
2.
3.
4.
5.
6.
A VERTICAL DAMPER IS SHOWN. HORIZONTAL DAMPER INSTALLATION, 1S SIMILAR. FOLLOW
DAMPER MANUFACTURER'S INSTRUCTIONS, INCLUDING FASTENER OPTIONS AND GAGES FOR
SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST BE INSTALLED IN THE PARTITION OR
FLOOR AND NOT OUTSIDE THE PENETRATION.
GALVANIZED SLEEVE: GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO DAMPER
FRAME AND TO PERIMETER ANGLES.
PERIMETER ANGELS: GALVANIZED STEEL, NOT LESS THAN 1 1/2"x1 1/2" [40x40mm], 14 GAGE, TO
PROVIDE 1" [25mm] MINIMUM OVERLAP OF OPENING ON ALL 4 SIDES.
BREAKAWAY DUCT CONNECTION: CONTRACTOR'S OPTION OF TYPES SHOWN IN SMACNA.
ACCESS PANELS: SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE LINK OR LINKS.
PROVIDE 1/4" TO 1/2" [6 TO 15mm] CLEARANCE ON HEIGHT AND WIDTH. FILL OPEN SPACE WITH
ROCK WOOL FIRESTOP FIBER.
ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS AND
MECHANICAL ROOM FLOORS, SHALL BE PROVIDED WITH 3" [75mm] HIGH CONCRETE CURB
AROUND OPENING FOR DUCT.
SLEEVE, NOTE 2
DUCT
CONNECTION
NOTE 4
DAMPER,
NOTE 1
DAMPER COLLAR
EXTENSION INTEGRAL
PART OF SLEEVE
SLEEVE, NOTE 2
NOTE 6FIRE BARRIER
PARTITION OR CHASE
TYPICAL DUCT
INSULATION
PERIMETER ANGLE, NOTE 3 (NOTE
FASTENED TO PARTITION)
ACCESS
PANEL
NOTE 5
[2 m m
NOTE:
ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS AND FAN
ROOM FLOORS SHALL BE PROVIDED WITH A 3" [75mm] HIGH CONCRETE CURB AROUND
OPENING FOR DUCT.
SEAL HOLE WITH FIREPROOFING
MATERIAL AFTER DUCT INSTALLATION
2"x2"x1/4" [50x50x6mm] ANGLE
INSTALL ON BOTH LONG
DIMENSION SIDES OF DUCT.
DUCT RISER - SEE FLOOR PLANS
FOR DETAILS
SEAL HOLE WITH FIREPROOFING
MATERIAL AFTER DUCT INSTALLATION
FLOOR
EXTEND ANGLE 3" [75mm]
BEYOND DUCT
DUCT RISER - SEE FLOOR PLANS
FOR SIZES SHEET METAL SCREWS 4" [100mm]
ON CENTER
1 1/2"x1 1/2"x1/8" [40x40x3mm] ANGLE
INSTALL ON BOTH LONG DIMENSION
SIDES OF DUCT. FOR DUCTS OVER 60"
[1500mm] USE 2"x2"x1/8" [50x50x3mm]
ANGLE.
HOLE IN STRUCTURAL FLOOR
DUCT RISER
0.5 INCH WG [125Pa] TO 2 INCHES WG [500Pa] DUCT RISER SUPPORT
ARRANGE RISER SO REINFORCER
TRANSVERSE JOINT IS AT RISER
SUPPORT POINT
FLOOR
2 INCHES WG [500Pa] TO 4 INCHES WG [1000Pa] DUCT RISER SUPPORT
HOLE IN STRUCTURAL FLOOR
DUCT RISER
NOTE:
1.
2.
3.
4.
5.
6.
RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A
MINIMUM OF 3 TIMES THE DIAMETER OF INLET
A FLEXIBLE AIR DUCT CONNECTOR IS NOT MANDATORY FOR INLET TO THIS
BOX, BUT ALLOWED TO ACCOMMODATE MINOR OFFSETS. MAXIMUM LENGTH
3'-0" [900mm].
A BRANCH DUCT SERVING AN INDIVIDUAL BOX MAY BE THE SAME SIZE AS THE
BOX INLET, PROVIDED THE EQUIVALENT LENGTH OF THE BRANCH DUCT, AS
SHOWN, DOES NOT EXCEED 10 FEET (3 METERS). FOR LONGER LENGTHS,
INCREASE THE DUCT SIZE AND PROVIDE A DUCT TRANSITION TO MAINTAIN
THE DUCT STATIC PRESSURE DROP AT OR BELOW 0.2"/100' [1.64Pa/m].
FLEXIBLE AIR DUCT CONNECTORS, WHEN USED FROM TERMINAL UNIT SUPPLY
AIR DUCT TO DIFFUSER, SHALL NOT EXCEED 5'-0" [1500mm]. USE RIGID
ELBOWS FOR CHANGE OF DIRECTION GREATER THAN 45°.
COMPONENT ARRANGEMENT MAY VARY BY MANUFACTURER. PROVIDE
INSULATION W/VAPOR BARRIER FOR CONNECTING DUCT SECTIONS.
USE OF THE FLEXIBLE AIR DUCT CONNECTORS ARE NOT PERMITTED FOR THE
DEDICATED AHU SERVING THE SURGICAL SUITE.
AIR TERMINAL UNIT
(CV OR VAV)
REHEAT COIL
SOUND
ATTENUATOR SEE
EQUIPMENT
SCHEDULE
FLEXIBLE AIR DUCT
CONNECTOR. SEE DETAIL
DIFFUSER (TYP.)
SEE SPECIFICATIONS FOR
CLAMPS AND SEALANT (TYP.)
SEE NOTE 5
SEE NOTE 1
SEE NOTE 2
SEE NOTE 3
S E
E N
O T
E
SECTION A-A (BASE NOT POURED WITH SLAB)
SECTION A-A (BASE POURED WITH FLOOR SLAB)
PLAN
TYPICAL ANCHOR
BOLT NUT & WASHER
SECTION B-B
EQUIPMENT BASE PLATE
PROVIDE #3 BARS 12" [300mm] O.C.
EACH WAY IN THE BASE & DOWEL
BASE TO FLOOR
EQUIPMENT BASE PLATE
PROVIDE DOUBLE SLAB
REINFORCING IN BASE AREA
WELD HEAD TO PLATE OR
BEND OVER END 5D
FLOOR
PIPE SLEEVE (5D, 3"
[75mm] MIN.)
ANCHOR
BOLT (TYP)
CONCRETE BASE
NOTE:
L & W DIMENSIONS SHALL
BE 6" [150mm] GREATER
THAN THE EQUIPMENT
BASE PLATE.
A
A
[400mm]
M
IN
[1 m m
M
IN
[1 m m
TYPICAL ANCHOR
BOLT NUT & WASHER
[2 m m
L /1
L
/1
L
W
D
D
5D
16"
BB
2D
SECTION A-A (ADD ON TO EXISTING CONCRETE PAD)
ADDED ON CONCRETE PAD
PROVIDE #3 BARS 12" [300mm] O.C.
EACH WAY IN THE BASE & DOWEL
BASE TO FLOOR
M
IN
[1 m m
L /1
EXISTING
CONCRETE
PAD
PROVIDE WELDED WIRE REMESH
SECURE CURB CAP TO WOOD NAILING STRIP WITH 3/8" [10mm] CADMIUM PLATED LAG BOLTS
NOT OVER 12" [300mm] ON CENTER.
SECURE ROOF CURB, DUCTWORK AND DAMPER TO ROOF WITH EXPANSION BOLTS
(CONCRETE ROOF) OR RUST RESISTANT BOLTS (METAL DECK AND BAR JOIST ROOF).
RUN ELECTRICAL LINES THROUGH CLEARANCE HOLE PROVIDED IN GRAVITY DAMPER, THEN
THROUGH VENTILATOR ELECTRICAL CONDUIT GUIDE.
GRAVITY BACKDRAFT
DAMPER
RIGID CONDUIT TO
ACCOMMODATE
ELECTRICAL WIRES
SEE NOTE 2
PREFABRICATED
ROOF CURB, 12"
HIGH
WOOD NAILING
STRIP
ELECTRICAL
CONDUIT GUIDE
MOTOR HOUSING
DUCT
TRANSITION DUCT TO FULL
SIZE OF DAMPER SUPPLIED
WITH ROOF VENTILATOR
ROOF
SEE NOTE 2
SEE NOTE 1
CURB CAP
NOTE:
1.
2.
3.
PIPE HANGERS - PROVIDE KINETICS KSIP
SUSPENDED INLINE PUMP SUPPORT OR
APPROVED EQUIVALENT ON EACH SIDE
OF PUMP (SEE NOTE NO. 1)
PRESSURE GAGE
1/2" [15mm]
STRAINERFLEXIBLE
CONNECTION
BALL OR
BUTTERFLY TYP.
NOTES:
1. SUPPORT PUMP FROM PIPING ONLY. DO NOT SUPPORT PUMP FROM MOTOR.
2. ELIMINATE BALANCING VALVE WHEN PUMP IS CONTROLLED BY VARIABLE SPEED
DRIVE
BALANCING DEVICE
HEAVY GAUGE HOT
DIPPED GALVANIZED
STEEL TOP WITH RUST
PROOF COATING
FASTEN AS REQUIRED
SEAL AIR & WATER TIGHT
WITH CAULK
EXISTING CURB
FLASHING
ROOF
BLOCK OR SPRAY
FOAM INSULATION, SEE
ARCHITECTURAL FOR
TYPE (MIN. 12" THICK
W/VAPOR BARRIER)
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2020
TLC No.:
www.tlc-engineers.com
121388
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldhfr.com
WOLD | HFR DESIGN
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
B
IM
/T V
H S
A lv in
C Y o rk
V A
I n te g ra te d H e a lt h /1
-M
E C
H -T
V H
S A
C Y
V A
M C
I n te g ra te d H e a lt h C e n te r- R
.r v t
/1
/2
:1
:0
A
M
M-MJ-01
MECHANICAL DETAILS TVHS - ALVIN C. YORK VAMC -
INTEGRATED HEALTH CENTER
SHK5-20-2022 JE
NOT TO SCALE
1 DUCTWORK SQUARE VANE ELBOWS
NOT TO SCALE
2 DUCTWORK RAIDUS ELBOWS
NOT TO SCALE
DUCTWORK TRANSITIONS (WITH
EQUIPMENT MOUNTED IN DUCT)
NOT TO SCALE
4 SUPPLY DUCTWORK TAKEOFFS
NOT TO SCALE
SUPPLY DUCT TAKEOFF - AIR TERMINAL
UNITS
NOT TO SCALE
ALTERNATE SUPPLY DUCT TAKEOFF -
AIR TERMINAL UNITS
NOT TO SCALE
EXHAUST OR RETURN BRANCH
DUCTWORK
NOT TO SCALE
8 VOLUME DAMPER DETAIL
NOT TO SCALE
9 ACCESS PANEL AND DOOR DETAIL
NOT TO SCALE
10 FLEXIBLE DUCT CONNECTIONS
NOT TO SCALE
SECTION THRU FIRE DAMPER
INSTALLATION
NOT TO SCALE
12 DUCT RISER SUPPORTS
NOT TO SCALE
DUCT CONNECTIONS - AIR TERMINAL
UNITS
NOT TO SCALE
14 CONCRETE EQUIPMENT BASES
NOT TO SCALE
15 POWER ROOF VENTILATOR
NOT TO SCALE
16 INLINE PUMP DETAIL
NOT TO SCALE
17 CURB CAP DETAIL
SIDE VIEW TRAPEZE HANGER FOR UP TO
453KG [1000 LB.] UNIFORM LOAD
ADJUSTABLE CLEVIS HANGER TYPE 1 - SEE
SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER TYPE 43 - SEE
SPECIFICATIONS
PROVIDE INSULATION SHIELD
& INSERT FOR ALL PIPING
(200mm [8"] MIN.)
BAND
43mm [1-5/8"] 12 GAUGE CHANNEL OR 50x50x6.4mm
[2"X2"X1/4"] ANGLE
15mm [1/2"] DIA.
HANGER RODS WITH
900mm [36"] MAX.
SPACING ON EACH
CHANNEL
WELD
SADDLE
INSULATION SHIELD
AT HANGER
PROVIDE HIGH COMPRESSIVE
STRENGTH INSULATION (9 PSF MIN.
DENSITY) UNDER INSULATION SHIELD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
HANGER ROD
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
NOM. SIZE
PIPE
TUBING
m m
1" M
A X mm
[IN]
mm
[FT]
mm
[FT]
THRU 20
[THRU 3/4]
[7]
[5]
[1]
[7]
[6]
[11/4]
[7]
[7]
[11/2]
[9]
[8]
[2]
[10]
[8]
[21/2]
[11]
[9]
[3]
[12]
[10]
[4]
[14]
[12]
[5]
[16]
[13]
[6]
[17]
[14]
[8]
[19]
[16]
[10]
[22]
[12]
[23]
[14]
[25]
[16]
[27]
[18]
[28]
[20]
[30]
[24]
[32]
P
D
C
D+[1"]
D+25mm INSULATE AS INDICATED FOR ALL CHILLED WATER.
INSULATE PIPE ONLY FOR STEAM, CONDENSATE
& HEATING WATER.
NOTE:
WHERE USED FOR COPPER TUBE OR PIPE, BRAZE TO FABRICATED STEEL ANCHOR
D+[21/2"]
D+[43/4"]
D+121mm
D+64mm
D+[11/2"]
D+38mm
D+[33/4"]
D+95mm
8mm
[5/16"]
ANCHOR BOLTS N=NUMBER
S=SIZE
DRILL ∅ = S+2mm
DRILL ∅ = S+[ 1/16"]
STL PIPE OR
COPPER TUBE
D=PIPE O.D.
NOTE A
PIPE ANCHOR SCHEDULE
D P C N S BOLT PATTERN
mm in mm in mm in mm in mm in
13 1/2"
102 4
19 3/4
21/2
11/2
5/8
1/2
3/8
3/8
3/8
1/2
3/8
3/8
1/4
3/4
5/8
5/8
5/8
NOTES:
1. PROVIDE ANCHORS ONLY WHERE SHOWN ON
DRAWINGS.
2. EXTEND SLEEVE ABOVE FLOOR WHERE
SPECIFIED.
INSULATION BOLT (TYPICAL)
FLOOR SLAB
FIRE-STOPPING
MATERIAL
BOLT
PIPE
PIPE SLEEVE
WHERE SPECIFIED
RISER
CLAMP
PIPE
PIPE SLEEVE WHERE
SPECIFIED
RISER CLAMP. BOTTOM
CLAMP REQUIRED AT
ANCHOR POINTS ONLY.
ELEVATION
PLAN
RISER CLAMP
STEEL EXPANSION SHIELD FOR EXISTING
CONSTRUCTION AND INSERTS FOR NEW
CONSTRICTION THIS TYPE SHALL BE USED
ONLY IN SLABS OR BEAMS OF 4" [100mm]
MIN DEPTH
3/8" [10mm] MIN DIA EXPANSION BOLTS FOR
EXISTING CONSTRUCTION AND INSERTS
FOR NEW CONSTRUCTION
CONCRETE
FLOOR SLAB
CLIP
ANGLE
NUTS & WASHERS
3/8" [10mm] MIN DIA
HANGER RODS
FOR PIPES UNDER 2" [50mm] IN SIZE USE 1 1/2"x1 1/2"x1/4" [40x40x6.4mm] ANGLE. ALL PIPES 2" [50mm] & LARGER USE 3"x3"x1/4" [75x75x6.4mm]
ANGLE
TURNBUCKLE
3/8" [10mm] MIN DIA
HANGER RODS
3/8" [10mm] MIN DIA
INSERTS NEW
CONSTRUCTION ONLY.
GREATER THAN 50mm [2"] DIA. PIPE 50mm [2"] DIA. & SMALLER
VERTICAL
GREATER THAN 50mm [2"] DIA. PIPE 50mm [2"] DIA. & SMALLER
HORIZONTAL
65mm [2 1/2"] DIA.
NOTE:
PROVIDE THE APPROPRIATE WELL DEPTH TO HAVE THE NECESSARY
INSULATION STAND-OFF DISTANCE.
65mm [2 1/2"] DIA.
TYPICAL MANUAL AIR VENT
TYPICAL CHILLED AND HOT WATER PIPING DRAIN
VALVE CONNECTIONS
ELEVATION THREADED
PIPING
ELEVATION
WELDED PIPING
TYPICAL WATER PIPING
REDUCER, IF REQUIRED
3/4" [20mm] BALL VALVE
ADAPTER TO 3/4" [20mm] HOSE
THREAD-PROVIDE HOSE CAP NUT
NOTES:
1. DRAIN ALL LOW POINTS AS INDICATED ABOVE.
2. WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS AND/OR PLANS LOCATE DRAIN
AT BOTTOM OF SCALE POCKET.
AIR VENT
1/2" [15mm]
BALL VALVE
1/4" [8mm]
COPPER TUBING
1/2" [15mm] x 4" [100mm]
NIPPLE
CIRCULATING WATER PIPING
ELEVATION
NOTES:
1. VENT ALL HIGH POINTS INDICATED ABOVE.
2. IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE TO DRAIN.
MV
OR
AV
COIL
TEST PLUG (TYP.)
REDUCER, IF REQUIRED
WATER RETURN
MANUAL AIR VENT
UNION CONNECTIONS
(TYP.)
WATER SUPPLY
SHUT OFF VALVE
DRAIN WITH HOSE
CONNECTION
MV
MODULATION CONTROL VALVE
NOTE:
1.
2.
PROVIDE IN CHILLED WATER MAIN AND IN CONDENSER WATER MAIN.
LOCATE PILOT TUBE TAPS 20 PIPE DIAMETERS DOWNSTREAM AND 10 PIPE
DIAMETERS UPSTREAM FROM THE NEAREST PIPE FITTING.
EITHER TOP OR SIDE LOCATION. BOTH ARE NOT REQUIRED AT SAME LOCATION.
PLUG
1 1/2" [40mm] FULL
PORT BALL VALVE
1 1/2"∅x2" LONG [40x50mm] PIPE
1 1/2" [40mm] FULL PORT
BALL VALVE
PLUG
WELD (TYP)
COMBINATION BALANCING
AND FLOW MEASURING VALVE,
SEE SPECS FOR TYPE.
SERVICE VALVES
SEE SPECS FOR TYPE
REQUIRED (TYP.)
SUPPLY
RETURN
SUPPLY
RETURN
PROVIDE MINIMUM 5
PIPE DIAMETERS OF
STRAIGHT PIPE
UPSTREAM OF VALVE,
COORDINATE W/ VALVE
MANUFACTURER
SINGLE COIL
WATER COIL
AIR VENT WHEN
COIL IS NOT
SELF-VENTING
DRAIN WHEN COIL IS
NOT SELF-DRAINING
TEST PLUG (TYP.)
PIPE HANGER SHALL SUPPORT
PIPING INDEPENDENT OF COIL
REDUCER, IF REQUIRED
DRAIN
WATER COIL
AIR VENT WHEN
COIL IS NOT
SELF-VENTING
TEST PLUG
(TYP.)
PIPE HANGER SHALL SUPPORT
PIPING INDEPENDENT OF COIL
WATER COIL
REDUCER, IF REQUIRED
FLOW ELEMENT
DRAIN WHEN COIL
IS NOT SELF-DRAINING
DRAIN
DOUBLE COIL
NOTES:
1. WHEN COIL IS INCLUDED IN CASING MOUNTED ON VIBRATION ISOLATORS THE FIRST 2 HANGERS FOR EACH PIPE SHALL BE SPRING &
NEOPRENE TYPE. TYPE "H" FOR 100mm [4"]∅ PIPE & SMALLER. TYPE "H-P" FOR 125mm [5"]∅ PIPE & LARGER.
2. PIPING SHALL BE INSTALLED IN SUCH MANNER THAT IT WILL NOT BLOCK THE SWING OR USE OF ACCESS DOORS OR PANELS; NEITHER
SHALL IT BLOCK THE SERVICING OF FILTERS, VALES, OR EQUIPMENT.
3. THE FLOW ELEMENT MAY BE INSTALLED IN THE SUPPLY PIPING IF THE REQUIRED MINIMUM UPSTREAM AND DOWNSTREAM DIMENSIONS
CANNOT BE OBTAINED IN THE RETURN PIPING.
FE
MV
MV
MV
MV
MV
MV
FE
TI
TI
TEMPERATURE
INDICATION TO ECC
SEE CONTROL
DIAGRAM
MV
CALIBRATED BALANCING
VALVE (TYP.)
NOTE:
1. ALL DRIP POINTS ON STEAM MAINS SHALL BE PROVIDED WITH A 300mm [12"] MINIMUM HIGH DRIP LEG FROM BOTTOM OF
STEAM MAIN TO TRAP INLET. DRIP LEG SHALL HAVE 150mm [6"] SCALE POCKET BELOW TRAP INLET.
TO RETURN MAIN
PIPE SIZE SHALL BE SAME SIZE AS TRAP
THERMOSTATIC TRAP. SEE OTHER
STEAM DETAILS, PLANS, AND
SCHEDULES
DIELECTRIC FITTING WHERE
RETURN IS COPPER PIPE
FLOW
SCHEDULE 80
STEEL PIPE
0m m
0m m
DRIP LEG OR EQUIPMENT CONNECTION. MAKE
THE SAME SIZE AS THE SUPPLY MAIN OR
EQUIPMENT CONNECTION. SEE NOTE 1
[1 2"
M
IN
[6
" M
IN
SCHEDULE 80 STEEL PIPE
SEE DRAWINGS FOR PIPE SIZES
25mm [1"]
GATE VALVE
USE 4-BOLT RAISED FACE FLANGES
STEAM TRAP ASSEMBLY
m m
[6
M
IN
m m
[1 2" m m [6
M
IN
[1
2"
M
IN
m m
DRIP LEG (TYP.)
20mm [3/4"] DRAIN (ALTERNATE
LOCATIONS) (TYPICAL)
STEAM LINE
(TYPICAL)
CAP (TYPICAL)
PIPE T0 STEAM
TRAP (TYPICAL)
NOTE:
DRIP POCKET PIPE SIZE SAME AS
STEAM MAIN UNLESS OTHERWISE
NOTED.
STEAM LINE DRIP POCKET
20mm [3/4"] MIN.
FROM DRIP
CONNECTION DRIP RETURN
10mm [3/8"] TEST CONNECTION
D U
C T
H E
IG
H
T
H
1/
H 1/
H
1/
H
STEAM
CONDENSATE
RETURN
TEMPERATURE
SWITCH
SCALE POCKET
HUMIDIFIER CONTROL
VALVE
TO HUMIDISTAT
MANIFOLD PIPE ADAPTERS
STEAM SUPPLY
ON-OFF CONTROL VALVE DUCT CROSS SECTION
[1 m m
INVERTED BUCKET
TRAP ASSEMBLY
NOTE:
SEE MANUFACTURER'S PIPING RECOMMENDATIONS FOR FINAL LAYOUT
6" M
IN
NOTES:
1. WHEN COIL IS INCLUDED IN CASING MOUNTED ON VIBRATION ISOLATOR
UNITS, THE RUNOUT PIPING FOR CONNECTIONS TO COIL SHALL BE
INSTALLED WITH SWING JOINTS TO ALLOW FOR THE VIBRATION.
2. PIPING SHALL BE INSTALLED IN SUCH MANNER THAT IT WILL NOT BLOCK
THE SWING OR USE OF ACCESS DOORS OR PANELS; NEITHER SHALL IT
BLOCK THE SERVICING OF FILTERS, VALVES, OR EQUIPMENT.
3. TRAP EACH COIL SEPARATELY WHEN INSTALLED IN A BANK OF TWO OR
MORE HIGH. ALSO PROVIDE SEPARATE VACUUM BREAKER FOR EACH COIL.
4. TWO TRAP ASSEMBLIES IN PARALLEL ARE SHOWN. TWO TRAPS REQUIRED
WHEN CONDENSATE LOAD IS 2400 KG/HR [5,000 LBS/HR] OR GREATER.
5. SUPPLY & RETURN PIPES ARE SHOWN FROM SAME END. REHEAT COIL MAY
HAVE SUPPLY & RETURN PIPES FROM OPPOSITE ENDS.
PIPE HANGER SHALL
SUPPORT PIPING
INDEPENDENT OF
COIL (TYP.)
PITCH COIL DOWN 8mm
[1/4"] PER FOOT TO
CONDENSATE OUTLET
FULL SIZE
TAPPING
PRESSURE GAGE
SCALE POCKET
SEE NOTE
NO. 4
STEAM CONDENSATE
RETURN
15mm [1/2"] C
HECK
VALVE VACUUM
BREAKER
INCREASER,
IF REQUIRED
REDUCER,
IF REQUIRED
0m m
[6 " M
IN
0m m
[1 2"
M
IN
STEAM SUPPLY
CONDENSATE
TO DRAIN
MV
MANUAL
AIR VENT
TO BUILDING
LOAD
INVERTED BUCKET
TRAP ASSEMBLY
STEAM PIPE
WELDED TEE
300mm[12"]
150mm[6"]WELDED
TEE
SCHEDULE 80 STEEL PIPE
25mm [1"] GATE VALVE
NOTES:
1. ALL DRIP POINTS ON STEAM MAINS SHALL BE PROVIDED WITH A 300mm [12"] MINIMUM HIGH DRIP LEG FROM BOTTOM OF STEAM MAIN TO
TRAP INLET. DRIP LEG SHALL HAVE 150mm [6"] SCALE POCKET BELOW TRAP INLET.
2. PROVIDE BYPASS PIPING.
SEE DRAWINGS FOR PIPE SIZES
TO RETURN MAIN
SCHEDULE 80 STEEL PIPE
PIPE SIZE SHALL BE SAME SIZE AS TRAP
INVERTED BUCKET TRAP. SEE
PLANS, AND SCHEDULES
DIELECTRIC FITTING WHERE
RETURN IS COPPER PIPE
FLOW
SCHEDULE 80
STEEL PIPE
BYPASS-INSTALL IN HORIZONTAL PLANE LEVEL WITH
TRAP OR IN VERTICAL PLANE & BELOW TRAP
0m m
0m m
DRIP LEG OR EQUIPMENT CONNECTION. MAKE
THE SAME SIZE AS THE SUPPLY MAIN OR
EQUIPMENT CONNECTION. SEE NOTE 1
[1 2"
M
IN
[6
" M
IN
1" GATE VALVE
USE 4-BOLT RAISED FACE FLANGES
NOTE:
ALL DRIP POINTS ON STEAM MAINS SHALL BE PROVIDED WITH A 300mm [12"] MINIMUM HIGH DRIP LEG FROM BOTTOM OF STEAM MAIN TO
TRAP INLET. DRIP LEG SHALL HAVE 150mm [6"] SCALE POCKET BELOW TRAP INLET.
TO RETURN MAIN
PIPE SIZE SHALL BE SAME SIZE AS TRAP
FLOAT AND THERMOSTATIC TRAP.
SEE PLANS, AND SCHEDULES
DIELECTRIC FITTING WHERE
RETURN IS COPPER PIPE
FLOW
SCHEDULE 80
STEEL PIPE
BYPASS-INSTALL IN HORIZONTAL PLANE LEVEL WITH
TRAP OR IN VERTICAL PLANE & BELOW TRAP PROVIDE
BYPASS PIPING FOR ALL TRAPS 25mm [1"] AND
LARGER. 3
m m m m
DRIP LEG OR EQUIPMENT CONNECTION. MAKE
THE SAME SIZE AS THE SUPPLY MAIN OR
EQUIPMENT CONNECTION. SEE NOTE 1
[1 2"
M
IN
[6
" M
IN
SCHEDULE 80 STEEL PIPE
SEE DRAWINGS FOR PIPE SIZES
25mm [1"]
GATE VALVE
USE 4-BOLT RAISED FACE FLANGES
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2020
TLC No.:
www.tlc-engineers.com
121388
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldhfr.com
WOLD | HFR DESIGN
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
B
IM
/T V
H S
A lv in
C Y o rk
V A
I n te g ra te d H e a lt h /1
-M
E C
H -T
V H
S A
C Y
V A
M C
I n te g ra te d H e a lt h C e n te r- R
.r v t
/1
/2
:1
:1
A
M
M-MJ-02
MECHANICAL DETAILS TVHS - ALVIN C. YORK VAMC -
INTEGRATED HEALTH CENTER
SHK5-20-2022 JE
NOT TO SCALE
1 PIPE HANGERS
NOT TO SCALE
2 SMALL PIPE ANCHOR
NOT TO SCALE
3 SUPPORT/ANCHOR FOR PIPE RISERS
NOT TO SCALE
4 SECURING HANGER RODS IN CONCRETE
NOT TO SCALE
INSTALLATION OF THERMOMETER
WELLS
NOT TO SCALE
DRAIN VALVE AND AIR VENT
CONNECTIONS (HYDRONIC SYSTEMS)
NOT TO SCALE
TERMINAL UNIT WATER COILS - PIPING
CONNECTIONS
NOT TO SCALE
17 PITOT TEST CONNECTIONS
NOT TO SCALE
9 FLOW MEASURING STATION
NOT TO SCALE
10 WATER COILS - PIPING CONNECTIONS
NOT TO SCALE
11 THERMOSTATIC STEAM TRAP ASSEMBLY
NOT TO SCALE
STEAM TRAP ASSEMBLY AND STEAM
LINE DRIP POCKET
NOT TO SCALE
STEAM HUMIDIFIER - PIPING
CONNECTIONS
NOT TO SCALE
14 STEAM COIL - PIPING CONNECTIONS
NOT TO SCALE
15 END OF STEAM LINE DRIP TRAP
NOT TO SCALE
INVERTED BUCKET STEAM TRAP
ASSEMBLY
NOT TO SCALE
FLOAT AND THERMOSTATIC STEAM
TRAP ASSEMBLY
DRAW THRU
BLOW THRU
2" [50mm]
PLUS X
1" [25mm]
MINIMUM
X
2X
UNIT TYPE A B
WHERE X = STATIC PRESSURE IN PAN
DRAIN LINE SHALL BE AT LEAST THE SAME SIZE AS
THE NIPPLE ON THE DRAIN PAN
PIPING SHALL BE RIGID COPPER TYPE L OR TYPE M
UNLESS NOTE BELOW IS MET
PITCH DOWN TOWARD
DRAIN
CLEAN OUT
FLOOR SINK
DRAIN PAN
NOTE: 1. CPVC PIPE MAY BE USED ONLY IF APPROVED BY LOCAL VA AND IS
INDOORS AND DOES NOT PASS THROUGH RATED BARRIERS.
2. DIELECTRIC FITTING TO BE USED WHEN TWO DISSIMILAR METALS ARE TO BE
CONNECTED.
A B
[2 m m
DIELECTRIC
FITTING
DIFFUSER CONE (INSUL. PER SPEC.)
DIFFUSER NECK (INSUL. PER SPEC.)
(2438.4 mm)
MAX. 8'-0" IN LENGTH
DRAW BAND
HIGH EFFICIENCY TAP W/ VOLUME
CONTROL DAMPER (INSUL. PER SPEC.)
FLEXIBLE DUCT
DRAW BAND
LIGHT
CEILING TEE
FULLY EXTENDED.
3/8" SOLID ROD
DAMPER WITH 2"
STANDOFF
NOTES:
4. VERTICAL POSITION SHOWN. HORIZONTAL INSTALLATION SIMILAR.
3. ALL ATTACHMENTS PER MANUFACTURER'S APPROVED INSTALLATION INSTRUCTION.
1. PROVIDE ACCESS DOOR & LABEL ON SIDE OR BOTTOM OF DUCT AS FOLLOWS:
12" x 12"
8" x 8"
22" AND ABOVE
14" THRU 20"
10" THRU 12"
DOOR SIZEDUCT WIDTH
18" x 18"
165°F FUSIBLE LINK
NOTE #5
WRAPPED SHEET METAL DUCT
NOTE #1
METAL STUD CONSTRUCTION
CLOSURE TAPE
6" MAX.
CAULKING (TYP. OF 2)
CLEARANCE 1/8" PER
LINEAR FOOT, BOTH
DIMENSIONS
FIRE RESISTIVE
MATERIAL (TYP.)
DUCT WRAP W/VAPOR
BARRIER (TYP.)
DUCT MOUNTED SMOKE DETECTOR
TO BE INSTALLED WITHIN
5'-0" OF DAMPER PER
MANUFACTURER'S RECOMMENDATIONS,
WITH NO AIR INLETS OR OUTLETS
BETWEEN THE DETECTOR AND THE
DAMPER.
MOUNTING ANGLE 1" MIN.
OVERLAP ALL SIDES
PLAIN "S" SLIP (TYP.)
BREAK-AWAY CONNECTION
U.L. (555S) LABELED
FIRE/SMOKE DAMPER,
SECURE TO SLEEVE
MANUFACTURER OR
FIELD FABRICATED
STEEL SLEEVE 16 GA.
MIN.
RETAINING ANGLES 1-1/2"x 1-1/2"x 1/8"
MIN. ALL SIDES. (SEE NOTE #2)
2. 1-1/2" x 1-1/2" x 1/8" RETAINING ANGLES SHALL LAP STRUCTURAL OPENING 1" MIN. & COVER
CORNERS OF OPENINGS. ANGLES ATTACH TO SLEEVE ONLY AND MUST NOT BE ATTACHED TO
EACH OTHER AT CORNERS OR TO WALL.
5. ACTUATOR TO BE MOUNTED ON OUTSIDE OF DAMPER SLEEVE ON
ACCESIBLE SIDE. ACTUATOR SHALL NOT INTERFERE WITH "S" JOINT.
ACTUATOR ASSEMBLY TO BE U.L. LABELED.
6. VERIFY THAT ACCESS IS PROVIDED ON THE ACTUATOR SIDE OF THE WALL/FLOOR SO
THAT THE LINK MAY BE SERVICED WITH THE DAMPER IN CLOSED POSITION.
NOTES:
4. VERTICAL POSITION SHOWN. HORIZONTAL INSTALLATION SIMILAR. DAMPER TO BE
SPRING LOADED WHEN HORIZONTAL.
3. ALL ATTACHMENTS PER MANUFACTURER'S APPROVED INSTALLATION INSTRUCTION.
2. 1-1/2"x1-1/2"x1/8" RETAINING ANGLES SHALL LAP STRUCTURAL OPENING 1" MIN. &
COVER CORNERS OF OPENINGS. ANGLES ATTACH TO SLEEVE ONLY AND MUST NOT
BE ATTACHED TO EACH OTHER AT CORNERS OR TO WALL.
1. PROVIDE ACCESS DOOR & LABEL ON SIDE OR BOTTOM OF DUCT AS FOLLOWS:
LINK
FUSIBLE
165°F
4" MIN.
1" MIN.
SLEEVE 16 GA. MIN.
FABRICATED STEEL
MANUF. OR FIELD
NOTE# 2
EACH SIDE
6" MAXIMUM
METAL STUD CONSTRUCTION
MATERIAL (TYP.)
FIRE RESISTIVE
NOTE # 1
DUCT SIZE
FASTENER W/WASHER
DUCT
SHEET METAL
NOTE # 2)
MIN. ALL SIDES (SEE
1-1/2"x1-1/2"x1/8"
RETAINING ANGLES
CLOSURE TAPE (TYP.)
BARRIER (TYP.)
DUCT WRAP W/VAPOR
METAL DUCT
WRAPPED SHEET
PLAIN "S" SLIP
(555) SECURE TO SLEEVE
U.L. LABELED FIRE DAMPER,
DIMENSIONS.
LINEAR FOOT BOTH
CLEARANCE 1/8" PER
CONSTRUCTION
CONCRETE OR MASONRY
18" x 18"
10" THRU 12"
14" THRU 20"
22" AND ABOVE
8" x 8"
12" x 12"
DOOR SIZEDUCT WIDTH
Notes:
A SECTION A-A
Floor or Wall Assembly-Min 4-1/2 in. thick lightweight (100-150 pcf) concrete. Wall assembly may also be constructed of any UL Classified Concrete Blocks*. Max dia.
of circular through-opening is 12-1/4 in.
*See Concrete Block (Cazt) category in fire resistance Directory for names of manufacturers.
Steel Pipe or Conduit-Nom 10 in. dia.
This is the start of the file's text. The full file is on GovTribe.