Attachment 15 - TECH BINDER.pdf

PDF 10 MB Posted

Attached to
Y1DA--626-309 Construct Integrated Health Center (Minor) - Murfreesboro
Solicitation number
36C77623B0037
Issued by

About this file

This document provides details for a federal solicitation to construct an integrated health center in Murfreesboro, Tennessee. The solicitation number is 36C77623B0037 and is being issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas. The project involves the construction of an integrated health center identified as project number 626-309. No further details are provided on the required construction products or services, the response deadline, or information on the potential award. The attached file is referenced as the "TECH BINDER" but its specific contents are not described.

View the file

Other files

File Type Posted
36C77623B0037 0008 - 8-29-23.pdf PDF
36C77623B0037 0007.pdf PDF
36C77623B0037 0006 - 8-22-23.pdf PDF
36C77623B0037 0005 - 8-18-23.pdf PDF
081710 integrated door assemblies - R2.pdf PDF
36C77623B0037 0004 - 08-15-2023.pdf PDF
Technical Questions Round 2 - 8-14-23.docx DOCX document
232113.13 FL - UNDERGROUND HYDRONIC PIPING.pdf PDF
2023-08-09 - IHC - Addendum 2.pdf PDF
IHC - Add 2 - Narrative.pdf PDF
36C77623B0037 0003 - 08-03-2023.pdf PDF
Technical Questions Tracking Spreadsheet - Murf IHC - 7-24-23.pdf PDF
VAMC - IHC - Addendum 1 - Dwgs.pdf PDF
36C77623B0037 0002.pdf PDF
Integrated Health Laydown Areas.pdf PDF
Attachment 17 - Construction Wage Rates - Rutherford County - 6-30-23.pdf PDF
Site Visit Sign In Sheet.pdf PDF
36C77623B0037 0001.docx DOCX document
Civil Binder.pdf PDF
Attachment 5 - CIVIL BINDER.pdf PDF
Attachment 11 - MECH BINDER-1.pdf PDF
Attachment 19 - Site Visit Instructions.pdf PDF
36C77623B0037_1.docx DOCX document
Attachment 9 - GENERAL BINDER.pdf PDF
Attachment 3 - ARCHITECTURAL BINDER-1.pdf PDF
Attachment 2 - IHC - SPEC - VOLUME 2.pdf PDF
Attachment 8 - FP BINDER.pdf PDF
Attachment 18 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 7 - ELEC BINDER.pdf PDF
Attachment 1 - IHC - SPEC - VOLUME 1.pdf PDF
Attachment 13 - PLUMBING BINDER.pdf PDF
Attachment 10 - INTERIORS BINDER.pdf PDF
Attachment 12 - MECH BINDER-2.pdf PDF
Attachment 17 - Construction Wage Rates.pdf PDF
Attachment 6 - DEMO BINDER1.pdf PDF
Attachment 4 - ARCHITECTURAL BINDER-2.pdf PDF
Attachment 14 - STRUCTURAL BINDER.pdf PDF
Attachment 16 - Limitations on Subcontracting - Construction Jan 2023 Deviation.docx DOCX document
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

B

IM

/T

V H

S

A lv in C

Y o rk

V A

I n te g ra te d

H e a lt h

/1

-T E

C H

-T V

H S

A C

Y V

A M

C I n te g ra te d

H e a lt h

C e n te r- R

.r v t

/1

/2

:0

:5

P

M

T-TJ-00

GENERAL TECHNOLOGY

INFORMATION

MURFREESBORO INTEGRATED

HEALTH

TH5-20-2022

626-20-102

JAK

DESCRIPTIONSYMBOLDESCRIPTIONSYMBOLDESCRIPTIONSYMBOL DESCRIPTIONSYMBOL

NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT.

DESCRIPTIONSYMBOL

X

T

2.5

DELAYED EGRESSDE

AUDIO/VIDEO SYSTEM

REQUEST TO EXIT MOTION SENSOR

GLASS BREAK SENSOR

360° MOTION DETECTOR

PAN/TILT/ZOOM CCTV CAMERA,,

PROVIDE CAT6A CABLE,

FACEPLATE, AND DOUBLE GANG

JUNCTION BOX AND CONDUIT

SECURITY PANEL

DOOR POSITION SWITCH

BALANCED MAGNETIC SWITCH

ELECTRIC LATCH

ELECTRIC MORTISE/TRIM LOCK

ELECTRIC STRIKE

MAGNETIC LOCK

POWER OVER ETHERNET

CARDREADER/LOCK COMBO

REMOTE DOOR RELEASE BUTTON

ASSISTANCE STATION

DURESS BUTTON MOUNTED

UNDERSIDE OF

COUNTER

CCTV MONITOR

PHOTO ELECTRIC BEAM

INTERCOM MASTER STATION

DIRECTIONAL MOTION DETECTOR

FIXED CCTV CAMERA, PROVIDE

CAT6A CABLE, FACEPLATE, AND

DOUBLE GANG JUNCTION BOX AND

CONDUIT

P

BASIC MATERIALS

J

J

TECHNOLOGY SYSTEMS SYMBOL LEGEND

J

SECURITY SYSTEM

LADDER TRAY FOR HORIZONTAL

CABLING.

PENETRATION CONDUIT

SLEEVE WITH

BUSHINGS.

GENERAL NOTES

EXISTING TO BE REMOVED

EXISTING TO REMAIN

EXISTING AFFECTED BY THIS

PROJECT

FUTURE

SLEEVE TURNING DOWN

SLEEVE TURNING UP

GROUND OR GROUND ROD AS

NOTED

FLEXIBLE CONDUIT

CONDUIT CONTINUED

CONDUIT STUB

CONDUIT TURNING DOWN

CONDUIT TURNING UP

CONDUIT CONCEALED IN SLAB,

UNDERGROUND OR UNDER

FLOOR

CONDUIT EXPOSED

CONDUIT CONCEALED

PEDESTAL MOUNTED JUNCTION BOX

FLOOR MOUNTED JUNCTION BOX

JUNCTION BOX

VOICE & DATA SYSTEM

BROADBAND TELEVISION SYSTEM

6 PORT TAP

8 PORT TAP

TERMINATION TAP

4 PORT TAP

2 PORT TAP

3 WAY SPLITTER

2 WAY SPLITTER

4 WAY SPLITTER

AMPLIFIER

DIRECTIONAL COUPLER

BIOMETRIC READER

INTRUSION ALARM KEYPAD

HIRSH SCRAMBLE KEYPAD

KEYPAD

CARD READER

LOCAL HORN STROBE ALARMSA

COMBINED CARD READER/KEYPAD

GENERAL SYSTEM NOTES

1. PRODUCTS SHALL BE OF MATERIALS THAT ARE SUITABLE FOR THE

ENVIRONMENT IN WHICH THEY ARE TO BE INSTALLED.

2. WORKING CLEARANCES AROUND ELECTRICAL EQUIPMENT SHALL BE

MAINTAINED IN COMPLIANCE WITH THE NATIONAL ELECTRICAL CODE ARTICLE

110, COORDINATE EQUIPMENT INSTALLATION TO MAINTAIN REQUIRED

CLEARANCES.

3. IF AN OUTLET BOX IS REQUIRED TO BE LOCATED IN AN ASSEMBLY OR PARTITION

RATED AS "FIRE/SMOKE" OR "SMOKE" OR IDENTIFIED AS EITHER "FIRE/SMOKE"

OR "SMOKE", THEN ALL OF THE FOLLOWING CONDITIONS SHALL BE MET:

THE OUTLET BOX OPENINGS SHALL OCCUR ONLY ON ONE SIDE OF THE

FRAMING SPACE.

THE OUTLET BOX SHALL BE METALLIC.

THE OUTLET BOX OPENINGS SHALL NOT EXCEED 16 SQUARE INCHES.

ALL CLEARANCES BETWEEN THE OUTLET BOX AND THE WALL BOARD

MATERIAL SHALL BE COMPLETELY SEALED WITH APPROVED MATERIALS IN

ACCORDANCE WITH THE APPLICABLE CODES AND STANDARDS FOR THE

PROJECT.

PROVIDE A SUPPLEMENTAL BARRIER AROUND OUTLETS LARGER THAN 16

INCHES SO THAT THE ORIGINAL RATING OF THE PENETRATION IS

MAINTAINED.

THE TOTAL AGGREGATE SURFACE AREA OF THE OUTLET BOX SHALL

NOT EXCEED 100 SQUARE INCHES PER 100 SQUARE FEET.

THE OUTLET BOX SHALL BE SEPARATED FROM OPENINGS ON THE

OPPOSITE SIDE OF THE RATED PARTITION BY A MINIMUM

HORIZONTAL DISTANCE OF 24 INCHES.

THE OUTLET BOX SHALL BE SECURELY FASTENED TO A PARTITION

FRAMING MEMBER BY MEANS OF AN APPROVED ATTACHMENT

METHOD.

OPENINGS CUT INTO THE WALL BOARD MATERIAL SHALL NOT

EXCEED 1/8 INCH BETWEEN THE EDGES OF THE OUTLET BOX

AND THE EDGES OF THE OPENING.

A.

B.

C.

D.

E.

F.

G.

H.

I.

LOCATIONS OF EQUIPMENT SHOWN ON THE DRAWINGS ARE

APPROXIMATE, COORDINATE EXACT EQUIPMENT LOCATION AND

CONNECTION REQUIREMENTS WITH THE APPROPRIATE TRADE PRIOR TO

INSTALLATION.

FOR EXACT LOCATION OF CEILING MOUNTED EQUIPMENT REFER TO THE

ARCHITECTURAL REFLECTED CEILING PLAN. LOCATIONS OF EQUIPMENT

NOT INCLUDED ON THE REFLECTED CEILING PLAN SHALL BE COORDINATED

WITH THOSE ITEMS SHOWN. COORDINATION OF CEILING MOUNTED

EQUIPMENT SHALL BE PRIOR TO ANY ROUGH-IN. NOTIFY ENGINEER OF ANY

DISCREPANCY.

PROVIDE FINAL CONNECTIONS TO VA PROVIDED EQUIPMENT WHERE

INDICATED ON THE PLAN DRAWINGS.

PRIOR TO ROUGH-IN AND INSTALLATION OF ANY FLOOR MOUNTED

DEVICE, VERIFY LOCATION WITH THE COR.

VERIFY AND COORDINATE THE LOCATION OF REQUIRED OUTLETS

WITH OTHER TRADE DRAWINGS AND VA PROVIDED EQUIPMENT.

EACH TELEVISION OUTLET LOCATION SHOWN, SHALL HAVE A DOUBLE GANG

OUTLET BOX WITH A SINGLE GANG PLASTER RING AND (1) 1" CONDUIT

STUBBED UP TO AN ACCESSIBLE LOCATION ABOVE THE FINISHED CEILING OR

TO AN ACCESSIBLE CABLE TRAY WHERE PROVIDED.

THE DESIGNATION ''N.I.C.'' SHALL DENOTE ITEMS, WHICH ARE ''NOT IN CONTRACT''.

THE DESIGNATION ''U.S.C.'' SHALL DENOTE ITEMS, WHICH ARE ''UNDER SEPARATE

CONTRACT''.

THE DESIGNATION ''F.B.O.'' SHALL DENOTE ITEMS, WHICH ARE ''FURNISHED BY

OTHERS''.

THE DESIGNATION ''O.F.E.'' SHALL DENOTE ITEMS, WHICH ARE ''OWNER

FURNISHED EQUIPMENT''.

ALL RACEWAY SYSTEMS SHOWN TO SUPPORT THE INSTALLATION OF THE

DIVISION 27 EQUIPMENT SHALL BE PROVIDED BY THE ELECTRICAL INSTALLER.

PROVIDE COORDINATION FOR THE INSTALLATION OF THIS BE PROVIDED BY THE

ELECTRICAL INSTALLER.

THE SYMBOL LEGENDS SHOWN ON THIS SHEET ARE ALL INCLUSIVE,

SYMBOLS INCLUDED IN THE LEGENDS MAY OR MAY NOT BE USED IN

THESE PROJECT DRAWINGS.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

EACH VOICE/DATA OUTLET LOCATION SHOWN, SHALL HAVE A DOUBLE GANG

OUTLET BOX WITH A SINGLE GANG PLASTER RING AND (1) 1" CONDUIT STUBBED UP

TO AN ACCESSIBLE LOCATION ABOVE THE FINISHED CEILING, TO AN ACCESSIBLE

CABLE TRAY WHERE PROVIDED OR HOMERUN IN SLAB TO NEAREST

COMMUNICATIONS ROOM. WORK BY ELECTRICAL INSTALLER PER

SPECIFICATIONS.

EACH FLOOR MOUNTED VOICE/DATA OUTLET SHALL HAVE A SINGLE GANG SPACE

WITHIN THE FLOOR BOX AND (1) 1" CONDUIT CONCEALED IN SLAB STUBBED UP TO

AN ACCESSIBLE LOCATION ABOVE THE FINISHED CEILING OR TO AN ACCESSIBLE

CABLE TRAY WHERE PROVIDED. WORK BY ELECTRICAL INSTALLER PER

SPECIFICATIONS.

ALL BONDING AND GROUNDING ELEMENTS UTILIZED FOR STRUCTURED CABLING

SYSTEM SHALL BE IN COMPLIANCE WITH SPECIFICATIONS.

PROVIDE ALL SLEEVES AS REQUIRED FOR ALL LOW VOLTAGE CABLE

PATHWAYS. RESTORE THE FIRE RATING OF THE SURFACE.

AUDIO VISUAL INPUT/OUTPUT - WALL MOUNTED

WITH ADJACENT DEDICATED DUPLEX

RECEPTACLE BY

X = TYPE (A, B, C, ETC.) SEE DETAILS FOR

ADDITIONAL INFORMATION

PODIUM

X x

Y

X x Y x

SX

SX

OVERHEAD PROJECTOR WITH

SCREEN, SCREEN SIZE SHOWN ON

PLANS

OVERHEAD PROJECTOR -

CEILING MOUNTED

X - DENOTES TYPE

PULLDOWN PROJECTION SCREEN, SIZE

SPECIFIED ON PLANS

OVERHEAD PROJECTION SCREEN MOTOR

WALL SWITCH FOR MOTORIZED SCREEN

CEILING MOUNTED SPEAKER

x DENOTES TYPE y DENOTES ZONE

TELECOMMUNICATIONS EQUIPMENT ROOMTER:

TR: TELECOMMUNICATIONS ROOM

TELECOMMUNICATIONS ENTRANCE FACILITYTEF:

NOTES:

INSTALLER TO REMOVE ALL EXISTING LOW VOLTAGE CABLES NOT TO BE

REUSED. E.G. ALL EXISTING UTP 4 PAIR CABLES. NO ABANDONED CABLES

SHALL BE LEFT IN THE BUILDING.

MOUNTING 2" ABOVE COUNTER OR BACK SPLASH

C

1. VOICE/DATA JACKS:

EACH RJ45 JACK FOR VOICE/DATA SHALL BE

CONNECTED TO A DEDICATED UTP 4 PR CABLE.

COMMUNICATIONS "INFORMATION OUTLET" MOUNTED AT

RECEPTACLE HEIGHT UNLESS OTHERWISE NOTED. MODULE

AND FACEPLATE DESCRIPTIONS ON DETAIL SHEETS

NNX

X = MOUNTING (F)LUSH, (S)URFACE, (M)ODULAR FURNITURE

ADAPTER (P)OLE, (R)ACEWAY, (D)OUBLE GANG FLUSH, (PD)

PEDESTAL

N = # OF VOICE/DATA JACKS

WALL TELEPHONE OUTLET FOR HOUSE PHONE.

MOUNTED AT 52" ABOVE FINISHED FLOOR TO TOP.

WIRELESS ACCESS POINT OUTLET. ACCESS POINT BY

OWNER.

X = MOUNTING (F)LUSH, (S)URFACE, (C)EILING.

N = # OF DATA JACKS. MAXIMUM CABLE LENGTH 262 FT

N

N = # OF COAX CONNECTORS "F" TYPE CONNECTOR

N = # OF FIBER OPTIC CONNECTORS. SC, ST, LC

REX OR ADA DOOR OPEN BUTTON

AUDIO/VIDEO CAMERAAV

ASSOCIATED DOOR DETAIL REFERENCE

INGROUND PULL BOX

MON

PERSONAL COMPUTER WORKSTATION

SPECIAL NOTES:

W F1

WALL MOUNTED OUTLET FOR ADA ACCESSABLE PAY

PHONE. MOUNTED AT 44" ABOVE FINISHED FLOOR

WAP

XON

WALL TELEPHONE OUTLET FOR TELEPHONE IN ELEVATOR

MACHINE ROOM. (S)URFACE MOUNTED AT 52" ABOVE

FINISHED FLOOR.

W

ADA

S1

ELV

COMBINED VOICE/DATA, AUDIO/VIDEO AND POWER OUTLETS IN

FLOOR BOX. POWER RECEPTACLE IS SHOWN FOR

REFERENCE ONLY. CONDUIT, BOX AND POWER RECEPTACLE

PROVIDED BY

X = A, B, C... FLOOR BOX TYPE. N'S ARE DESCRIBED ABOVE.

TB

TABLE TOP POP-UP WITH VOICE/DATA, AUDIO/VIDEO AND

POWER INTERFACE.

X = A, B, C... FLOOR BOX TYPE. N'S ARE DESCRIBED ABOVE.

POKE THRU WITH COMBINED VOICE/DATA,

AUDIO/VIDEO AND POWER.

X = A, B, C... FLOOR BOX TYPE. N'S ARE DESCRIBED

ABOVE.

P

3/4" PLYWOOD BACKBOARD. BY

IDF - 2 POST RACK

IDF - 4 POST RACK

TELECOMM PANEL

1.

ALL CABLE TRAY, CONDUITS AND BOXES SHOWN ARE IN CONTRACT BY THE

ELECTRICAL INSTALLER. J-HOOKS AND LADDER RACKS BY SCS INSTALLER.

2.

STRUCTURED CABLING SYSTEM BYDIVISION 17CABLING INSTALLER.

3.

ALL DOUBLE DOORS ARE TO RECEIVE (1)

DOOR POSITION SWITCH ON EACH

DOOR LEAF AND SHALL REPORT AS ONE

ALARM POINT.

1.

2.

FIBER CCTV LOCATION WHICH EXCEEDS 3000 FEET SHALL BE EQUIPPED WITH 2

FIBER CONNECTIONS 1 VIDEO, 1 DATA

3.

A. THE MAXIMUM PULLING TENSION SHALL NOT EXCEED 25 POUNDS TO

AVOID STRETCHING THE CONDUCTORS.

THE MINIMUM BENDING RADIUS OF THE CABLE SHALL NOT BE

LESS THAN 4X THE OUTSIDE DIAMETER OF THE CABLE.

B.

THE CABLE SHALL BE INSTALLED WITHOUT KINKS OR TWISTS AND THE

APPLICATION OF CABLE TIES SHALL NOT DEFORM THE CABLE BUNDLE.

C.

D. STRIP BACK ONLY AS MUCH CABLE JACKET AS IS REQUIRED TO

TERMINATE THE CABLE. CABLE PAIRS SHALL NOT BE UNTWISTED

MORE THAN 1/2 INCH.

4.

5.

6.

7.

ALL 120V POWER WIRING SHALL BE INSTALLED IN A SEPARATE CONDUIT.

ALL POWER CIRCUITS, 120VAC AND 24VAC, SHALL INCLUDE AN EQUIPMENT

GROUNDING CONDUCTOR WHICH IS EQUAL IN SIZE TO THE PHASE AND

NEUTRAL CONDUCTORS.

ALL CONDUIT ABOVE GRADE SHALL BE METALLIC, ALL CONDUIT BELOW GRADE

SHALL BE PVC UNLESS OTHERWISE NOTED ON DRAWINGS.

ALL CARD READERS AND KEYPADS DEDICATED FOR ELEVATOR FLOOR

SELECTION CONTROL ARE SHOWN INSIDE THE ELEVATOR CAB ON THE

LOWEST LEVEL FLOOR PLAN TO WHICH THE ELEVATOR

TRAVELS.

ALL CONDUIT, WIRING, AND ASSOCIATED BACK BOXES SHALL BE FULLY

CONCEALED WITHIN WALLS, FLOORS, AND CEILINGS.

INSTALLATION OF UTP CABLE SHALL BE IN ACCORDANCE WITH

EIA/TIA GUIDELINES. CABLE INSTALLATION AND TERMINATIONS THAT

DO NOT COMPLY SHALL BE REPLACED BY THE INSTALLER.

8.

INSTALLATION OF FIBER OPTIC CABLES SHALL BE IN ACCORDANCE

WITH EIA/TIA GUIDELINES. CABLE INSTALLATION AND TERMINATIONS

THAT DO NOT COMPLY SHALL BE REPLACED BY THE INSTALLER.

9.

A. THE BEND RADIUS FOR INTRABUILDING 2 AND 4-FIBER

HORIZONTAL OPTICAL FIBER CABLE SHALL NOT BE LESS THAN 1

INCH UNDER NO-LOAD CONDITIONS. WHEN UNDER A MAXIMUM

TENSILE LOAD OF 50 LBF, THE BEND RADIUS SHALL NOT BE LESS

THAN 2 INCHES.

B. THE BEND RADIUS FOR INTRABUILDING OPTICAL FIBER BACKBONE

SHALL NOT BE LESS THAN THAT RECOMMENDED BY THE

MANUFACTURER IF NO RECOMMENDATION IS KNOWN, THEN THE

APPLIED BEND RADIUS SHALL NOT BE LESS THAN 10 TIMES THE

CABLE OUTSIDE DIAMETER

UNDER NO-LOAD CONDITIONS AND NOT LESS THAN 15 TIMES THE

CABLE OUTSIDE DIAMETER WHEN THE CABLE IS UNDER TENSILE

LOAD.THE BEND RADIUS FOR INTER BUILDING (OSP) OPTICAL FIBER BACKBONE

SHALL NOT BE LESS THAN THAT RECOMMENDED BY THE MANUFACTURER

IF NO RECOMMENDATION IS KNOWN, THEN THE APPLIED BEND RADIUS

SHALL NOT BE LESS THAN 10 TIMES THE CABLE OUTSIDE DIAMETER NO-

LOAD CONDITIONS AND NOT LESS THAN 20 TIMES THE CABLE OUTSIDE

DIAMETER WHEN THE CABLE IS UNDER A TENSILE LOAD UP TO THE RATING

OF THE CABLE, USUALLY 600 LBF.

C.

10. COORDINATE LOCATION OF ALL FIRE RATED PENETRATIONS PRIOR TO

PROCEEDING WITH INSTALLATION. ALL PENETRATIONS THROUGH FIRE

RATED BARRIERS SHALL BE COMPLETELY SEALED WITH APPROPRIATE

FIRE STOP MATERIAL IN ACCORDANCE WITH NFPA AND FIRE AUTHORITY

HAVING

JURISDICTION.

ALL CABLES SHALL BE SUITABLE TO THE ENVIRONMENT TO WHERE THEY WILL

BE INSTALLED.

NOTES:

ALL RACEWAYS AND BOXES SHOWN ARE IN CONTRACT

BY THE ELECTRICAL INSTALLER.

1.

AUDIO/VIDEO DEVICES AND EQUIPMENT BY THE

AUDIO/VIDEO INSTALLER.

2.

NOTES:

INSTALLER TO REMOVE ALL EXISTING SECURITY

CABLES AND EQUIPMENT NOT TO BE REUSED.

ALL EXISTING EQUIPMENT WILL BE RETURNED

TO THE OWNER.

1. ALL RACEWAYS AND BOXES SHOWN ARE IN

CONTRACT BY THE ELECTRICAL INSTALLER.

2. SECURITY DEVICES AND EQUIPMENT BY

SECURITY INSTALLER.

3.

CEILING MOUNTED DOCUMENT CAMERA

X = A, B, C... INTERFACE TYPE.

X

ASSISTED LISTENING TRANSMITTER

TOUCH SCREEN AUDIO/VIDEO CONTROL

WALL MOUNTED TOUCH SCREEN AUDIO/VIDEO

CONTROL

Y

WALL MOUNTED SPEAKER

x DENOTES TYPE y DENOTES ZONE

NO ZONE DENOTES LOCAL AUDIO/VIDEO SYSTEM

Y

SPEAKER - DEMOLITION PLAN

VOLUME CONTROL. PROVIDE 3/4" CONDUIT

STUB-UP ABOVE CEILING AND SINGLE

STANDARD ELECTRICAL BOX

AT 52" ABOVE FINISHED FLOOR

CEILING MOUNTED MICROPHONE OUTLET

x DENOTES TYPE y DENOTES ZONE

MX

Y

MX WALL MOUNTED MICROPHONE

x DENOTES TYPE y DENOTES ZONE

NO ZONE DENOTES LOCAL AUDIO/VIDEO SYSTEM

Y

MICROPHONE - DEMOLITION PLAN

SATELLITE DISHSD

CALL STATION

SEE PODIUM DETAILS

CS

IK

AS

DURESS BUTTON WALL MOUNTED

X x Y MOTORIZED PROJECTION SCREEN, SIZE

SPECIFIED ON PLANS

XNNN

XNNN

XNNN

D

MX SURFACE MOUNTED MICROPHONE

x DENOTES TYPE y DENOTES ZONE

NO ZONE DENOTES LOCAL AUDIO/VIDEO SYSTEM

Y

ALL INDOOR CONDUITS N0 LARGER THAN 1" SHOWN ON THE GROUND FLOOR

SHALL BE INSTALLED EMBEDDED IN THE SLAB. CONDUITS SHALL BE KEPT DRY

AND CLEAN PRIOR TO PULLING CABLES.

ANYTHING NOT DESIGNATED AS ROUGH-IN AND SUPPORT RESPONSIBILITY

ON THESE DRAWINGS IS IN THE SYSTEM INSTALLER SCOPE OF WORK.

INTERCOM & PAGING SYSTEM

SX

SX

CEILING MOUNTED SPEAKER

x DENOTES TYPE y DENOTES ZONE

Y

WALL MOUNTED SPEAKER

x DENOTES TYPE y DENOTES ZONE

NO ZONE DENOTES LOCAL AUDIO/VIDEO SYSTEM

Y

ADMINISTRATIVE PHONEAP

HANDSETHS

11. ALL DELAYED EGRESS LOCKS AND MAGNETIC LOCKS, SHALL

RECEIVE A FIRE ALARM RELAY TO RELEASE THE DOOR UPON ALARM

AS REQUIRED BY CODE.

SEE DETAIL SHEETS FOR DEVICE MOUNTING REQUIREMENTS AND ADDITIONAL

INFORMATION.

THE DESIGNATION "D.H.C." SHALL DENOTE "DOOR HARDWARE INSTALLER".14.

IN ELECTRICAL AND MECHANICAL ROOMS, CONDUIT FOR LOW VOLTAGE

OUTLETS SHALL BE EXTENDED TO ACCESSIBLE CEILING OUTSIDE OF THE ROOM.

X

DETENTION LOCKDL

DOOR INTERLOCKDI

INTERCOM SUBSTATION

SPEAKER PHONE

16.

17.

18.

19.

20.

21.

22.

23.

24.

25.

26.

THE DESIGNATION "O.F.C.I." SHALL DENOTE ITEMS WHICH ARE FURNISHED

BY THE OWNER AND INSTALLED BY THE CONTRACTOR.

15.

M

S

DPS

BMS

CR

KP

CK

HS

BR

EL

EM

ES

ML

PE

IS

SP

D

MI

M

G

R

PC

S

AV

ALT

TS

TS

VC

DIVISION 17

DIVISION 16.

DETENTION DOOR INTERLOCKI

CABLE TRAY FOR HORIZONTAL

CABLING.

DIVISION 16

DIVISION 17

DIVISION 17

DIVISION 17

DIVISION 16

N

XX"

N = FACEPLATE CONNECTIVITY AND MOUNTING

TYPE, SEE DETAILS FOR INFORMATION

(TYPE 1,2,3, ETC.)

MONITOR SIZE IF APPLICABLE, SEE DETAILS

FOR INFORMATION

TV

AUDIO VISUAL INPUT/OUTPUT -SURFACE OR

FLOOR BOX MOUNTED WITH ADJACENT

DEDICATED DUPLEX RECEPTACLE BY

X = TYPE (A, B, C, ETC.) SEE DETAILS FOR

ADDITIONAL INFORMATION

X

AV

DIVISION 16

TELEVISION/MONITOR OUTLET, SEE DETAILS

FOR MOUNTING HEIGHT

SECURITY CAMERA EXTERIOR POLECP

PRESS CONNECTION PANEL, SEE DETAILS FOR

ADDITIONAL INFORMATION

PR

SECURITY SYSTEM NOTES

INDICATES WALL MOUNT

INDICATES WALL MOUNT

SECURITY CAMERA NETWORK OUTLET. COORDINATE

EXACT LOCATION OF OUTLET WITH OWNER PRIOR TO

ROUGH IN.

N = # OF DATA JACKS. MAXIMUM CABLE LENGTH 262 FT

CN

360 DEGREE CAMERA

MON

CMON

PAITENT MONITORING OUTLET - (1) CAT6A

CENTRAL MONITOR OUTLET - (4) CAT6A

F1T TEMPERATURE MONITORING CABLE. MOUNT ADJACTENT

TO TAP, 6" BELOW CEILING.

TAP

TEMPERATURE PROBE ACCESS POINT WALL MOUNTED 6"

BELOW CEILING. (1) CAT6A DATA OUTLET MOUNTED ADJACENT

TO DEVICE WITH CENTER OF OUTLET 6" BELOW CEILING.

CONSTRUCTION PHASING / PUBLIC & STAFF ACCESS /

BUILDING OPERATIONS

SCOPE OF WORK INDICATED HEREIN FOR THIS DICIPLINE DOES NOT INDICATE

SPECIFIC REQUIREMENTS RELATED TO PHASING OF WORK, ALTHOUGH EVERY

EFFORT HAS BEEN MADE TO INCORPORATE SEQUENTIAL PHASES OF WORK AS

REQUESTED BY THE GOVERNMENT.

1.

PUBLIC AND STAFF ACCESS TO BUILDINGS 7, 107, AND 116 SHALL NOT BE

INTERUPTED AT ANY TIME DURING CONSTRUCTION.

2.

CANTEEN, KITCHEN, AND GIFT SHOP NORMAL OPERATION SHALL NOT BE

INTERUPTED AT ANY TIME DURING CONSTRUCTION.

3.

REFER TO SHEET GI 01.30 FOR FURTHER INFORMATION ON PROJECT PHASING

REQUIREMENTS.

4.

CAT6

CAT6

CAT6

TECHNOLOGY DRAWING INDEX

SHEET DESCRIPTION ISSUED

T-TJ-00 GENERAL TECHNOLOGY INFORMATION Yes

T-TD-00 BASEMENT - DEMOLITION PLAN - OVERALL Yes

T-TD-01 GROUND FLOOR - DEMOLITION PLAN - OVERALL Yes

T-TJ-01 GROUND FLOOR - NEW WORK PLAN - TECHNOLOGY - OVERALL Yes

T-TJ-01A GROUND FLOOR - NEW WORK PLAN - TECHNOLOGY - AREA A Yes

T-TJ-01B GROUND FLOOR - NEW WORK PLAN - TECHNOLOGY - AREA B Yes

T-TJ-04 TECHNOLOGY - ENLARGED ROOMS Yes

T-TJ-05 TECHNOLOGY - ENLARGED ROOMS Yes

T-TJ-06 TECHNOLOGY - ENLARGED ROOMS Yes

T-TJ-07 TECHNOLOGY - DETAILS Yes

T-TJ-08 TECHNOLOGY - DETAILS Yes

T-TJ-09 TECHNOLOGY - RISER Yes

T-TJ-10 TECHNOLOGY - A/V SCHEMATIC FUNCTIONAL DIAGRAM Yes

Revisions: Date:

EXISTING PIPE TUNNEL

EXISTING PIPE TUNNEL

EXISTING PIPE TUNNEL

EXISTING POOL

EXISTING JUNCTION

BOX TO REMAIN

(2) EXISTING 4" CONDUITS

TO BLDG 106 TO REMAIN

EXISTING FIBER TO REMAIN

EXISTING FIBER ROUTED DOWN

FROM COMM ROOM TO BE REMOVED

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

B

IM

/T

V H

S

A lv in C

Y o rk

V A

I n te g ra te d

H e a lt h

/1

-T E

C H

-T V

H S

A C

Y V

A M

C I n te g ra te d

H e a lt h

C e n te r- R

.r v t

/1

/2

:0

:5

P

M

T-TD-00

BASEMENT - DEMOLITION PLAN -

OVERALL

MURFREESBORO INTEGRATED

HEALTH

TH5-20-2022

626-20-102

JAK

3/32" = 1'-0"

1 BASEMENT OVERALL - TECHNOLOGY DEMO

UP

J

I I

H

G

F

E

D

C

B

A

10987

11 12

135.1 10.25.2

H1

F3

F2

E1

I2

H3

G1

12.511.5

9.57.5

17 18 19 22

F4

F1

E2

D1

C1

B1

H2

I1

I3

K

L

15.1 15.2 17.1 17.2

00 01 02 03

7.1 9.1

4.5

5.5

BASEMENT ACCESS

ELECTRICAL

STAIRS

WORK ROOM

DRESS ROOM DRESS ROOM

JAN

STAGE

AUDITORIUM

WOMENLOBBYMENSTORAGE

TRANSFORMER

ENTRANCE

OFFICE SHOWER

THERAPEUTIC POOL/STORAGE

LOCKER

TOILET

TOILET

CORRIDOR

HACLOCKER

STAIR

OFFICESTORAGEOFFICE

EXERCISE/GYMRECREATION HALL

KITCHEN

TLT

AS PART OF BASE BID,

TRANSFORMER IS TO BE

REMOVED AND RELOCATED.

REFERENCE ELECTRICAL

DRAWINGS FOR MORE

INFORMATION.

20 21

C O

R R

ID

O

R T

O B

LD

G

DN

UP

EXISTING

IT/COMM ROOM

EXISTING CATV HEADEND CONNECTION

TO BLDG 7 & BLDG 116 TO BE REMOVED

INACTIVE NEXTEL DAS TO BE REMOVED.

EXISTING FIRE ALARM FIBER

ROUTING UP CHASE WITH OTHER

UTILITIES TO BE REMOVED

EXISTING FIBER ROUTING

DOWN TO TUNNEL

REMOVE EXISTING FIBER TO BLDG 5 & BLDG 106

REMOVE EXISTING COPPER & FIBER

TO NURSING HOME (ROOM 156)

EXISTING PUBLIC ADDRESS

FIBER TO BE REMOVED

EXISTING IT ROOM

TO REMAIN

EXISTING FIBER ROUTED

TO TUNNEL TO REMAIN

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

AREA A

AREA B

OUT OF

SCOPE

B

IM

/T

V H

S

A lv in C

Y o rk

V A

I n te g ra te d

H e a lt h

/1

-T E

C H

-T V

H S

A C

Y V

A M

C I n te g ra te d

H e a lt h

C e n te r- R

.r v t

/1

/2

:0

:5

P

M

T-TD-01

GROUND FLOOR - DEMOLITION

PLAN - OVERALL

MURFREESBORO INTEGRATED

HEALTH

TH5-20-2022

626-20-102

JAK

3/32" = 1'-0"

1 GROUND FLOOR OVERALL - TECHNOLOGY DEMO

UP

J

I I

G

F

E

D

C

B

A

10987

4321 11 12

5.1 10.25.2

H1

F3

F2

E1

I2

H3

G1

12.511.5

9.5

7.5

17 18 19 22

F4

F1

E2

D1

C1

B1

H2

I1

I3

K

L

15.1 15.2 17.1 17.2

00 01 02 03

7.1 9.1

ELECTRICAL

G41

SIM MAINTENANCE

G30G

PROCEDURE SIM LAB

G30F

CONTROL ROOM

G30E

WAITING

G39

MULTI-PURPOSE

G20J

MULTI-PURPOSE

G20F

MULTI-PURPOSE

G20D

MULTI-PURPOSE

G20B

MULTI-PURPOSE

G20

MULTI-PURPOSE

G20H

STOR.

G20C

MED/SURG SIM LAB

G30D

KITCHEN/SERVING

G21

EDUC CHIEF

G17A

MUSIC THERAPY CLINIC

G13

WC STORAGE

G12B

REC. THERAPY CLINIC

G08

COMPUTER LAB

G16

STOR.

G20A

STOR.

G20E

STOR

G20G

STOR.

G20I

BARBER CART

G02FOOD SERVICE CHIEF

G03

FOOD SERVICE VEND SUPPLY

G04

CORRIDOR

G54

CORRIDOR

G52

MUSIC THER. 1

G43

MUSIC THER. 2

G42

CORRIDOR

G45

WORK AREA

G15

ENTRY

G01

CORRIDOR

G46

COURTYARD

G10

CORRIDOR

G48

CORRIDOR

G48A

CORRIDOR

G49

CORRIDOR

G50

CORRIDOR

G51

STORAGE

G20K

4.5

5.5

PRACTICE ROOM

G13B

MUSIC STORAGE

G13A

ALS CLASSROOM

G30J

TRNG EQUIP STOR

G30C

STAFF LOUNGE

G33

CREATIVE ARTS GROUP

G34

LOBBY

G36

PMRS STORAGE

G31

ACCESS STAIR

G26

FEMALE

G24

MALE

G25

LACTATION

G27

HAC

G30I

MALE

G37

FEMALE

G38

MEDIA COORD.

G17B

WORK

G17

PAT. RESOURCE

G40

RT SPVR.

G15APMRS CONSULT

G14

HAC

G07

RECREATION

STORAGE

G08B

MALE

G09A

FEMALE

G09C

VENDING

G32

KINESIO GROUP THERAPY

G12

WORK

G12A

KITCHENETTE

G08A

VESTIBULE

G35

SECURITY

G35A

STORAGE

G34A

CORRIDOR

G55

STORAGE

G30K

STORAGE

G30H

DE-BRIEF

G30A

CORRIDOR

G30 CORRIDOR

G30

CONNECTOR

G47

FEMALE SHOWER

G09D

MALE SHOWER

G09B

ENTRY

G44

CORRIDOR

G53

CHARGING CART STOR.

G19

WHOLE HEALTH

STORAGE

G18

IT

G23

20 21

CHASE

G26A

CLO.

G30B

COMM/MEDIA CONTROL

G22

RISER

G13D

MECH.

G11

ELEC.

G28

ELEC.

G29

MECH.

G11A

STAIRS

G09

CORRIDOR

G46

T-TJ-05

T-TJ-06

IT ROOM & COMM ROOM TO BE COMPLETED

BEFORE DEMO BEGINS. SEE ARCHITECTURAL

PHASING PLANS FOR ADDITIONAL REQUIREMENTS.

T-TJ-04

T-TJ-05

PRIMARY J-HOOK PATHWAY

ALTERNATE PRIMARY J-HOOK

PATHWAY IF CONNECTOR IS

NOT INCLUDED. PROVIDE 4"

SLEEVES AS REQUIRED.

ALTERNATE PRIMARY

J-HOOK PATHWAY IF

CONNECTOR IS NOT

INCLUDED. PROVIDE

4" SLEEVES AS

REQUIRED.

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

AREA A

AREA B

OUT OF

SCOPE

B

IM

/T

V H

S

A lv in C

Y o rk

V A

I n te g ra te d

H e a lt h

/1

-T E

C H

-T V

H S

A C

Y V

A M

C I n te g ra te d

H e a lt h

C e n te r- R

.r v t

/1

/2

:0

:0

P

M

T-TJ-01

GROUND FLOOR - NEW WORK

PLAN - TECHNOLOGY - OVERALL

MURFREESBORO INTEGRATED

HEALTH

TH5-20-2022

626-20-102

JAK

GENERAL NOTES

0 5' 10'

3/32" = 1'-0"

1 GROUND FLOOR OVERALL - TECHNOLOGY

1. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL CONSTRUCTION PHASING REQUIREMENTS.

UP

UP

S2 S2 S2

S1

S1 S1

S1

S1

S1

S1

S1

S1

S1

S1

S1

S1S1 S1

S1

S1 S1

A V

AV

A V

I

AV 1

ES

DPS

C R

R E

X

TV

TV

TV

TV

T V

CR

D P

S

D P

S

EL

REX

D D

D D

S1S1

TAP

D P

S

DPS

S1

S1

S1

S1

S1

J

I

G

F

E

D

C

B

A

5.1 10.25.2

F3

F2

E1

I2

H3

G1

12.511.5

9.57.5

F4

C1

B1

STAIRS

7.1 9.1

REC. THERAPY CLINIC

G08

BARBER CART

G02

FOOD SERVICE CHIEF

G03

CORRIDOR

G45

ENTRY

G01

CORRIDOR

G46

FOOD SERVICE VEND SUPPLY

G04

615 SF

CONNECTOR

G47

KITCHENETTE

G08A

MUSIC THERAPY CLINIC

G13

MUSIC STORAGE

G13A

WORK

G12A

RECREATION

STORAGE

G08B

HAC

G07

KINESIO GROUP THERAPY

G12

WC STORAGE

G12B

MALE

G09A

FEMALE

G09C

COURTYARD

G10

WORK AREA

G15

PRACTICE ROOM

G13B

PMRS CONSULT

G14

COPIER

COPIER

CHASE

G-104A

MALE SHOWER

G09B

FEMALE SHOWER

G09D

COPIER

REFRIG. I. MAKERREFRIG.

SOILED

G12D

CLEAN

G12C

MECH.

G11

MECH.

G11A

STAIRS

G09

ELEC.

G28

ELEC.

G29

RISER

G13D

F 2

F 2

F 2

F 2 F 2 F 2 F 2

TEMPERATURE

MONITORING PROBE

F 2 F 2

F 2F 2F 2F 2F 2F 2F 2F 2F 2

F 2

F 2

F 1

F 1

AV INPUT PLATE

VTEL CAMERA

360°

WAP

S 2

WAP

S 2

WAP

S 2

WAP

S 2

WAP

S 2

WAP

S 2

F 1

F 1

F 1

F 1

F 2

F 2

F 2

F 2

F 2 F 2F 2

F 1

CORRIDOR

G45

CORRIDOR

G55

COURTYARD

G10

F1T 7' - 6 1/16"

9' - 0"

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

AREA A

OUT OF

SCOPE

B

IM

/T

V H

S

A lv in C

Y o rk

V A

I n te g ra te d

H e a lt h

/1

-T E

C H

-T V

H S

A C

Y V

A M

C I n te g ra te d

H e a lt h

C e n te r- R

.r v t

/1

/2

:0

:1

P

M

T-TJ-01A

GROUND FLOOR - NEW WORK

PLAN - TECHNOLOGY - AREA A

MURFREESBORO INTEGRATED

HEALTH

Checker5-20-2022

626-20-102

Author

0 4' 8' 12'

1/8" = 1'-0"

1 GROUND FLOOR AREA A - TECHNOLOGY

D P

S

DPS

D P

S D

P S

C R

CR

REX

R E

X

EL

E S

C R

ES

R E

X

CR CR

D P

S

D P

S

S1 S1 S1 S1 S1 S1

S1

S1

S1

S1

S1

S1

S1 S1

S1

S1

S1

S1

S1

S1

S1

S1

S1

S1 S1

S1

S1

S1

S1

S1

S1

S1

S1 S1

S1

S1

S1

S1

S1

S1

S1

D P

S D

P S

CR

CR

E S

E S

E S

E S

REXREX

REX

REX

C R

C R

DPS

DPS

DPS

ES

E L

R E

X R

E X

T V

CR

D P

S

E S

REX

A V

S1

AV

S1

J

I

H

F

G1

17 18 19 22

F4

F1

E2

D1

C1

B1

H2

I1

I3

K

L

15.1 15.2 17.1 17.2

MEDIA COORD.

G17B

LOBBY

G36

MALE

G37

FEMALE

G38

VESTIBULE

G35

SECURITY

G35A

58 SF

HAC

G30I

PAT. RESOURCE

G40

STORAGE

G34A

SIM MAINTENANCE

G30G

PROCEDURE SIM LAB

G30F

CONTROL ROOM

G30E

TRNG EQUIP STOR

G30C

499 SF

ALS CLASSROOM

G30J

MALE

G25

WAITING

G39

LACTATION

G27

MULTI-PURPOSE

G20J

MULTI-PURPOSE

G20F

MULTI-PURPOSE

G20D

MULTI-PURPOSE

G20B

MULTI-PURPOSE

G20

MULTI-PURPOSE

G20H

STOR.

G20A

STOR.

G20E STOR

G20G

STOR.

G20I

STOR.

G20C

MED/SURG SIM LAB

G30D

VENDING

G32

STAFF LOUNGE

G33

KITCHEN/SERVING

G21

EDUC CHIEF

G17A

WORK

G17

RT SPVR.

G15A

COMPUTER LAB

G16

CREATIVE ARTS GROUP

G34

CORRIDOR

G48

CORRIDOR

G48A

CORRIDOR

G49

CORRIDOR

G50

CORRIDOR

G51

STORAGE

G20K

FEMALE

G24

MUSIC THER. 1

G43 MUSIC THER. 2

G42

CORRIDOR

G54

CORRIDOR

G52

ACCESS STAIR

G26

PMRS STORAGE

G31

C O

P

IE

R

327 SF

DE-BRIEF

G30A

361 SF

CORRIDOR

G30

177 SF

STORAGE

G30H

65 SF

STORAGE

G30K

AREA BAREA A

A R

E A

B

A R

E A

A

C O

R R

ID

O

R T

O B

LD

G

217 SF

CORRIDOR

G30

WHOLE HEALTH

STORAGE

G18 m a n e q u in s to ra g e r a c k

CHARGING CART STOR.

G19

CORRIDOR

G53

IT

G23

20 21

CHASE

G26A

CLO.

G30B

COMM/MEDIA CONTROL

G22

ELECTRICAL

G41

CORRIDOR

G45

T-TJ-06

Sim

T-TJ-04

Sim

T-TJ-04

Sim

T-TJ-04

Sim T-TJ-04

Sim

F 2

F 2

F 2

F 2

F 2

F 2

F 2F 2F 2

F 2

F 2F 2

F 2 F 2

F 2 F 2

F 1

F 1

F 1

F 2

F 2F 2

WAP

S 2

WAP

S 2

WAP

S 2

WAP

S 2

WAP

S 2

WAP

S 2

WAP

S 2

F 1

F 2

360°

360°

360°

360°

F 2

F 2

F 2

F 2

F 2

F 2

F 2

F 2

F 2

360°

F 2

F 2

T-TJ-05

Sim

11' - 0"

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

KEYPLAN

AREA B

OUT OF

SCOPE

B

IM

/T

V H

S

A lv in C

Y o rk

V A

I n te g ra te d

H e a lt h

/1

-T E

C H

-T V

H S

A C

Y V

A M

C I n te g ra te d

H e a lt h

C e n te r- R

.r v t

/1

/2

:0

:1

P

M

T-TJ-01B

GROUND FLOOR - NEW WORK

PLAN - TECHNOLOGY - AREA B

MURFREESBORO INTEGRATED

HEALTH

Checker5-20-2022

626-20-102

Author

0 2' 4' 6'

1/8" = 1'-0"

1 GROUND FLOOR AREA B - TECHNOLOGY

HOLDOPEN

A V

AV

P

S2 S2 S2

S2 S2 S2

S2 S2 S2

S2 S2 S2

S2 S2

S2S2

S2 S2

S2 S2

A V

A V

TS

TS

T S

TS

T S

TS

TS

AV 1

AV AV

AV 1

P

P

D P

S

DPS

CR

REX

E S

C R

ES

R E

X

CR CR

D P

S

D P

S

S1

S1

S1

S1

S1

S1

S1 S1

S1

S1

S1

S1

S1

S1

E S

E S

REXREX

M X

M X

M X

A V

MED/SURG SIM

LAB

G30D

239 SF

CONTROL ROOM

G30E

151 SF

PROCEDURE SIM

LAB

G30F

275 SF

SIM

MAINTENANCE

G30G

117 SF

CORRIDOR

G30

217 SF

CORRIDOR

G30

361 SF

STORAGE

G30H

177 SF

HAC

G30I

58 SF

ALS CLASSROOM

G30J

499 SFSTORAGE

G30K

65 SF

DE-BRIEF

G30A

327 SF

LACTATION

G27

105 SF

TRNG EQUIP

STOR

G30C

161 SF

FEMALE

G24

235 SF

MALE

G25

245 SF

CORRIDOR

G48

429 SF

ACCESS STAIR

G26

109 SF

F 2

F 1

F 1 F 2

F 1

F 1

F 1 F 1

10" TOUCHSCREEN

CONTROL PANEL

7" TOUCHSCREEN

SCHEDULING PANEL

7" TOUCHSCREEN

SCHEDULING PANEL

10" TOUCHSCREEN

CONTROL PANEL

IT

G23

188 SF

F 1

F 2

F 1

F 2

10" TOUCHSCREEN

CONTROL PANEL

7" TOUCHSCREEN

SCHEDULING PANEL

7" TOUCHSCREEN

SCHEDULING PANEL F 1

AVAVAV

AV AV AV

AV AV AV

AV AV AV

AV AV

AV

AV

AV AV

AV AV

SIM CAMERA WITH

VIEW OF BED

SIM LAB CAMERA

WITH VIEW OF BED

SIM LAB CAMERA

WITH VIEW OF SINK

SIM LAB CAMERA WITH

VIEW OF DOOR G-30F

SIM LAB CAMERA WITH VIEW OF

DOOR G-30D AND CORRIDOR

F 2

F 2

F 2

F 2

F 2

F 2

SIM EQUIPMENT RACK

UNDER COUNTER

WAP

S 2WAP

S 2

WAP

S 2

F 2F 2

L 4

L 4

L 4

F 2

COMM/MEDIA

CONTROL

G22

109 SF

G30F

G30E G30GG30D

F 2

AV WALL BOX

TS

F 1

F 2AV WALL BOX

TS

F 1MX

P1

F 2 F 2 F 2 F 2

F 1 F 1

AV WALL BOX

F 2 F 2

F 2F 2

AV WALL BOX

AV WALL BOXF 1

TS

MX

P1

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

B

IM

/T

V H

S

A lv in C

Y o rk

V A

I n te g ra te d

H e a lt h

/1

-T E

C H

-T V

H S

A C

Y V

A M

C I n te g ra te d

H e a lt h

C e n te r- R

.r v t

/1

/2

:0

:3

P

M

T-TJ-04

TECHNOLOGY - ENLARGED

ROOMS

MURFREESBORO INTEGRATED

HEALTH

Checker5-20-2022

626-20-102

Author

1/4" = 1'-0"

1 SIM LAB

1/4" = 1'-0"

4 ALS CLASSROOM G-022 EAST

1/4" = 1'-0"

5 DE-BRIEF G-024 SOUTH

1/4" = 1'-0"

9 MED/SURG SIM LAB HEADWALL

1/4" = 1'-0"

10 PROCEDURE SIM LAB HEADWALL

1/4" = 1'-0"

11 CONTROL ROOM NORTH

1/4" = 1'-0"

12 CONTROL ROOM EAST

1/4" = 1'-0"

13 CONTROL ROOM WEST

1/4" = 1'-0"

3 COMPUTER LAB G-048 EAST

CR CR

P

S

D P

S

CR CR

D P

S

D P

S

IT

G23

COMM/MEDIA CONTROL

G22

4" HILTI

SLEEVES

4" HILTI

SLEEVES

4" HILTI

SLEEVES

4" HILTI

SLEEVES

S E

C U

R

IT

Y

IN

T E

R C

O M

P U

B

LI

C

A

D R

E S

S

R A

D

IO

/D A

S

DDC

E

LE

C P

A N

E L

T E

LE

V

IS

IO

N

TELCO TERM. FIBER &

COPPER TERMINATIONS.

GROUND

BUS BAR

GROUND

BUS BAR

PLYWOOD

BACKBOARD

PLYWOOD BACKBOARDIT

G23

188 SF

COMM/MEDIA

CONTROL

G22

109 SF

GROUND

BUS BAR

TELCO TERM. FIBER &

COPPER TERMINATIONS.

DDC

TELEVISION

ELEC

GROUND

BUS BAR

SECURITY

INTERCOM PUBLIC

ADDRESS

RADIO

OR DASSECURITY

IT

G23

188 SF

COMM/MEDIA

CONTROL

G22

109 SF

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

B

IM

/T

V H

S

A lv in C

Y o rk

V A

I n te g ra te d

H e a lt h

/1

-T E

C H

-T V

H S

A C

Y V

A M

C I n te g ra te d

H e a lt h

C e n te r- R

.r v t

/1

/2

:0

:4

P

M

T-TJ-05

TECHNOLOGY - ENLARGED

ROOMS

MURFREESBORO INTEGRATED

HEALTH

TH5-20-2022

626-20-102

JAK

KEYNOTES

PROVIDE 3/4" A/C GRADE PLYWOOD, PAINTED TO MATCH WALLS WITH FIRE INTUMESCENT PAINT. LINE ALL WALLS WITH PLYWOOD AND MOUNT ALL EQUIPMENT DIRECTLY TO PLYWOOD. TYPICAL BOARD HEIGHT IS 84".

PROVIDE 12" LADDER RACK WITH APPROPRIATE FITTINGS AND GROUNDING. PROVIDE WATERFALL DROP-

OUTS ABOVE ALL WIRE MANAGERS.

PROVIDE (1) 84"X19" 2-POST RACK WITH 6" WIRE MANAGERS ON EITHER SIDE. MAINTAIN 3' MINIMUM

CLEARANCES ON FRONT AND BACK.

PROVIDE 4" FIRESTOP SLEEVES. BASIS OF DESIGN: HILTI SPEED SLEEVE.

PROVIDE GROUND BUS-BAR, TIE INTO ELECTRICAL SERVICE GROUNDING SYSTEM. ENSURE ALL LADDER

RACK AND TELECOMM RACKS ARE GROUNDED TO BUS-BAR USING 2-LUG CONNECTIONS.

1/4" = 1'-0"

1 IT G-044 & COMM/MEDIA CONTROL G-043

1/4" = 1'-0"

2 IT G-044 NORTH

1/4" = 1'-0"

3 IT G-044 EAST

1/4" = 1'-0"

4 IT G-044 SOUTH

1/4" = 1'-0"

5 IT G-044 WEST

1/4" = 1'-0"

6 COMM/MEDIA CONTROL NORTH

1/4" = 1'-0"

7 COMM/MEDIA CONTROL EAST

1/4" = 1'-0"

8 COMM/MEDIA CONTROL SOUTH

1/4" = 1'-0"

9 COMM/MEDIA CONTROL WEST

1/4" = 1'-0"

10 IT G-044 & COMM/MEDIA CONTROL G-043 CABLE TRAY

FEC

F E

C

FEC FEC

192" x 120" 192" x 120" 104" x 65"104" x 65"

S2

S2

S2 S2

S2 S2

S2 S2

S2 S2

S2 S2

S2 S2

S2 S2

S2 S2

S2 S2

S2 S2

S2 S2

S2 S2

S2 S2

S2 S2

P1 P1

P1P1

P

P

TS TSTS TS

TS TS

MX

MXMX

MX

A V

A V

TS TS TS TS

T S

T S

T S

T S

AV AV AVAV

AV AV

AVAVAVAV

AV AV

A V

A V

A V

AV 1AV 1

A

V

M X

M X

MULTI-PURPOSE

G20B

393 SF

MULTI-PURPOSE

G20

472 SF

CORRIDOR

G49

420 SF

STOR.

G20A

54 SF

CORRIDOR

G50

1,100 SF

STOR.

G20E

59 SF

MULTI-PURPOSE

G20D

1,202 SF

MULTI-PURPOSE

G20F

1,225 SF

MULTI-PURPOSE

G20J

495 SF

STORAGE

G20K

104 SF

CORRIDOR

G51

348 SF

MULTI-PURPOSE

G20H

509 SF

STOR.

G20I

76 SF

STOR

G20G

66 SF

DRAPER ULTIMATE ACCESS XL V

PART # 145008

DRAPER ULTIMATE ACCESS XL V

PART # 145008

90"

DISPLAY

90"

DISPLAY

WAP

S 2

WAP

S 2

WAP

S 2

WAP

S 2

WAP

S 2

WAP

S 2

L 4

L 4

L 4

L 4

F 2 F 2

7" TOUCHSCREEN

SCHEDULING PANEL

7" TOUCHSCREEN

SCHEDULING PANEL

7" TOUCHSCREEN

SCHEDULING PANEL

7" TOUCHSCREEN

SCHEDULING PANEL

7" TOUCHSCREEN

SCHEDULING PANEL

7" TOUCHSCREEN

SCHEDULING PANEL

7" TOUCHSCREEN

SCHEDULING PANEL

7" TOUCHSCREEN

SCHEDULING PANEL

10" TOUCHSCREEN

CONTROL PANEL 10" TOUCHSCREEN

CONTROL PANEL

10" TOUCHSCREEN

CONTROL PANEL

10" TOUCHSCREEN

CONTROL PANEL

10" TOUCHSCREEN

CONTROL PANEL

EVENT MONITOR /

DIGITAL SIGNAGE

EVENT MONITOR /

DIGITAL SIGNAGE

S 2S 2S 2S 2

F 1

F 1

F 1

F 1 F 1 F 1 F 1 F 1 F 1

F 1

F 1

F 1F 1 F 1F 1

AV PARTITION

SENSORS

AV PARTITION

SENSORS

AV PARTITION

SENSORS

AV PARTITION

SENSORS

AV PARTITION

SENSORS

F 1

AV INPUT PLATE AV INPUT PLATE AV INPUT PLATE AV INPUT PLATE

AV INPUT PLATE

AV INPUT PLATE

STOR.

G20C

90 SF

WALL MOUNTED

TOUCH SCREEN

CONTROLS

PODIUM PODIUM PODIUM PODIUM

WALL MOUNTED

TOUCH SCREEN

CONTROLS

WALL MOUNTED

TOUCH SCREEN

CONTROLS

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

B

IM

/T

V H

S

A lv in C

Y o rk

V A

I n te g ra te d

H e a lt h

/1

-T E

C H

-T V

H S

A C

Y V

A M

C I n te g ra te d

H e a lt h

C e n te r- R

.r v t

/1

/2

:0

:4

P

M

T-TJ-06

TECHNOLOGY - ENLARGED

ROOMS

MURFREESBORO INTEGRATED

HEALTH

Checker5-20-2022

626-20-102

Author

1/4" = 1'-0"

1 MULTI-PURPOSE ROOMS

1/4" = 1'-0"

2 MULTIPURPOSE ROOMS NORTH

1. CAMERA SHALL BE SUPPORTED FROM THE

CEILING GRID SYSTEM, NOT THE CEILING TILE.

PROVIDE MOUNTING HARDWARE AS REQUIRED.

NOTES:

SUPPORT BOX

WALL MOUNTED BOX

WITH CAT6

CONNECTION

MODULE.

DATA

CABLE

LAY IN CEILING TILE

CEILING TEE'S

GRID SUPPORT PROVIDED

BY SCS CONTRACTOR

CEILING TILE WIRE

CONCRETE

DECK ABOVE

WIRE SHALL BE SUPPORTED

FROM LOOP SUPPORTS

SECURE SECONDARY

SUPPORT CABLE FROM

BUILDING STRUCTURE

SECONDARY SUPPORT TAB

3/4" CONDUIT

2 GANG BACK BOX

FIN. FL.

MOUNT IN TV

BACKBOX. SEE

DETAILS ON

SHEET T-TJ-08

RG6 COAX

CAT 6A F-TYPE ADAPTER

SINGLE GANG FACE PLATE FOR (2) MODULES

TV

NOTE: ALL DATA AT TV LOCATIONS TO TERMINATE IN BIOMED RACK IN IT ROOM G23.

2) RANDOMLY INSTALL J-HOOKS AT 3', 4' AND 5'

APART.

TREE SYSTEM IS FOR MAIN CORRIDOR PATHWAYS.

DOUBLE AND SINGLE TREES MAYBE USED IN

ROOMS. CABLE J-HOOK SYSTEM CAN BE SECURED

TO METAL STUDS, WHERE PERMISSIBLE.

NOTES:

CADDY CABLE J-HOOKS

CONCRETE ANCHOR ROOF DECK

BAR JOIST CLAMP

1)

CEILING

M

IN

M

A X

STRUCTURED CABLING

SECURITY,

CCTV, MISC.

NURSE CALL, PUBLIC

ADDRESS, CATV

PROVIDE DOUBLE-GANG BOX

WITH SINGLE GANG MUD RING

FOR READER. SEE FLOOR PLAN

FOR SPECIFIC TYPE AND PLACEMENT.

PROVIDE DOUBLE-GANG BOX

WITH SINGLE GANG MUD RING

FOR READER. SEE FLOOR PLAN

FOR SPECIFIC TYPE AND

PLACEMENT.

44" A.F.F.

6"

44" A.F.F.

6"

ELECTRIC STRIKE AND

ACCOMMODATING

HARDWARE

FINISHED CEILING FINISHED CEILING

MAGNETIC DOOR CONTACT

SWITCH EMBEDDED IN

DOOR & DOOR FRAME

FINISHED FLOOR

DOOR HARDWARE SHOWN FOR GRAPHICAL ILLISTRATION ONLY, REFERENCE DIVISION 8 HARDWARE

SCHEDULE AS NEEDED FOR ACTUAL HARDWARE SET.

3.

ALL CONDUIT SHALL BE 3/4" UNLESS OTHERWISE NOTED.2.

1.NOTES: CABLE TYPE AND SIZE MUST COMPLY WITH ALL ESTABLISHED REQUIREMENTS AND APPLICABLE CODES.

4" x 4" SQUARE J-BOX.

CABLE FOR COMMUNICATION

AND LOW VOLTAGE POWER

1" CONDUIT TO ACCESSIBLE CEILING

SPACE

UNSECURE SIDE SECURE SIDE

POWER

SUPPLY

PROVIDE

DOUBLE-GANG BOX

WITH SINGLE GANG

MUD RING

FOR READER. SEE

FLOOR PLAN

FOR SPECIFIC TYPE

AND PLACEMENT.

44" A.F.F.

6"

4" x 4" SQUARE J-BOX.

MAGNETIC DOOR

CONTACT

SWITCH EMBEDDED IN

DOOR & DOOR FRAME

ELECTRIC STRIKE

AND

ACCOMMODATING

HARDWARE

FINISHED FLOOR

FINISHED CEILING

DOOR HARDWARE SHOWN FOR GRAPHICAL ILLISTRATION ONLY, REFERENCE DIVISION 8 HARDWARE

SCHEDULE AS NEEDED FOR ACTUAL HARDWARE SET.

3.

ALL CONDUIT SHALL BE 3/4" UNLESS OTHERWISE NOTED.2.

1.NOTES: CABLE TYPE AND SIZE MUST COMPLY WITH ALL ESTABLISHED REQUIREMENTS AND APPLICABLE CODES.

CABLE FOR COMMUNICATION

AND LOW VOLTAGE POWER

1" CONDUIT TO ACCESSIBLE CEILING

SPACE

ELECTRIFIED HINGE

(PROVIDED BY DOOR

HARDWARE

INSTALLER)

2" x 4" J-BOX FLUSH MOUNTED

FOR EGRESS MOTION SENSOR.

ROOM #

PORT #

TR # - PP #

TELEPHONE WALL PLATE

CABLE TO TR.

W F1

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

B

IM

/T

V H

S

A lv in C

Y o rk

V A

I n te g ra te d

H e a lt h

/1

-T E

C H

-T V

H S

A C

Y V

A M

C I n te g ra te d

H e a lt h

C e n te r- R

.r v t

/1

/2

:0

:4

P

M

T-TJ-07

TECHNOLOGY - DETAILS MURFREESBORO INTEGRATED

HEALTH

TH5-20-2022

626-20-102

JAK

NOT TO SCALE

1 CCTV CAMERA INSTALLATION1

NOT TO SCALE

2 TV OUTLET

NOT TO SCALE

3 CABLE HANGER (MULTI J-HOOK)

NOT TO SCALE

SECURITY SINGLE DOOR - ELECTRIC

STRIKE WITH CARD READERS

NOT TO SCALE

SECURITY DOUBLE DOOR - ELECTRIC

STRIKE WITH CARD READER AND REX

NOT TO SCALE

4 WALL PHONE OUTLET - W/FI

LABEL

1 1/2" EMT CONDUIT

STUBBED TO THE

NEAREST J-HOOK

AND GROMMET

BLDG # - SECTION # - FLOOR # - JACKID #

F3

CAT6A DATA CABLE

CAT6A DATA CABLE

CAT6A VOICE CABLE

CAT6A DATA CABLE

BLUE FOR DATA

BLUE FOR DATA

BLUE FOR DATA

BLUE FOR PHONE/FAX

BLANK

DATA CABLE WITH BLUE KEYSTONE

VOICE CABLE WITH RED KEYSTONE

DATA CABLE WITH WHITE KEYSTONE

MAX

5'

TO COMM/DATA ROOM

NOTE:

WIRELESS ACCESS POINT AND

ANTENNA NOT IN CONTRACT.

WAP

S2

J-HOOK

ACCESSIBLE CEILING

COIL 15' SERVICE LOOP IN CEILING.

DETAIL NOTE:

COIL CABLE IN CEILING

GROUND BUS BAR

STANDOFF

RACKET

CPI 10622-000

INSULATOR

CPI 10622-012 OR EQUAL

ISOMETRIC ELEVATION

PROVIDE # 6 COPPER CABLE 2-HOLE

LUG CLAMP FOR CABLE

CONNECTION. (TYP)

PROVIDE GROUNDING

CONDUCTOR TO

BUILDINGS

STEEL PER NEC 250.66

PROVIDE GROUNDING CONDUCTOR TO

MAIN SERVICE GROUND POINT PER NEC

250.66

4"

FRONT VIEW

INSULATOR (TYPICAL)

CPI 10622-012 OR EQUAL

12"

PROVIDED BY ELECTRICAL INSTALLER.

2-HOLE LUG (TYP.)

INSULATOR MOUNTING BRACKET

(TYP.) CPI 10622-000

PROVIDE WHITE CORE BAKELITE NAMEPLATE

FASTENED TO A WALL/SURFACE BELOW

BUSBAR AT EACH FLOOR, WITH DESIGNATION

ENGRAVED THEREON IN 1/2" HIGH LETTERS.

TGB-XXX

GENERAL NOTES:

ALL HARDWARE (BOLTS, NUTS,

WASHERS, ETC.) SHALL BE SOLID

COPPER OR BRONZE. COPPER

PLATING SHALL NOT BE ACCEPTABLE.

BUSBAR SHALL BE 1/4" THICK

(MINIMUM).

INCREASE LENGTH OF BUSBAR, FOR

NUMBER OF CONNECTIONS, AS

REQUIRED

TO MAINTAIN CORRECT SPACING

BETWEEN LUGS.

1.

2.

3.

LABEL

1 1/2" EMT CONDUIT

STUBBED TO THE

NEAREST J-HOOK

AND GROMMET

BLDG # - SECTION # - FLOOR # - JACKID #

MON

CAT6A DATA CABLE

CAT6A DATA CABLE

CAT6A DATA CABLE

CAT6A DATA CABLE

ORANGE FOR DATA

ORANGE FOR DATA

ORANGE FOR DATA

ORANGE FOR DATA

DATA CABLE WITH ORANGE KEYSTONE

DATA CABLE WITH ORANGE KEYSTONE

VOICE CABLE WITH ORANGE KEYSTONE

DATA CABLE WITH ORANGE KEYSTONE

CMON

AV

FSR PWB-100

BOX (OR EQUAL)

SHOWN WITH ACCESSORY

LOW-VOLTAGE CONDUIT

ENTRY BOX

120VAC POWER PROVIDED BY

ELECTRICAL CONTRACTOR

COVER TO BE

FLUSH WITH WALL

CENTER COVER TO BE

FLUSH WITH WALL

PROVIDE CATV CABLE AND FSR

CONNECTOR PLATES FOR

CONNECTION TO WALL MOUNTED

DISPLAY: PLATE #'S INCLUDE -

(3) IPS-B010D

AV INPUT CABLES AS REQUIRED COORDINATE EXACT

HEIGHT WITH

ARCHITECTURAL PLANS

AND SECTIONS PRIOR

TO ROUGH-IN

ACCESSIBLE CEILING

FINISHED FLOOR

COORDINATE WITH

TV / MONITOR

MOUNTING BRACKET

AV / TV WALL

BOX

(1) 1-1/2" CONDUIT IN WALL

FOR LOW VOLTAGE CABLES

CONDUIT STUBBED ABOVE CEILING

WITH CONDUIT BUSHING

TO ELECTRICAL PANEL

(1) 3/4" CONDUIT FOR POWER

(1) 1-1/2" CONDUIT TO FLOOR BOX IF APPLICABLE. SEE TECHNOLOGY

DRAWINGS FOR LOCATION AND ADDITIONAL INFORMATION

TV / MONITOR

TV

FSR PWB-100

BOX (OR EQUAL)

SHOWN WITH ACCESSORY

LOW-VOLTAGE CONDUIT

ENTRY BOX

120VAC POWER PROVIDED BY

ELECTRICAL CONTRACTOR

COVER TO BE

FLUSH WITH WALL

CENTER COVER TO BE

FLUSH WITH WALL

PROVIDE CATV CABLE AND FSR

CONNECTOR PLATES FOR

CONNECTION TO WALL MOUNTED

DISPLAY: PLATE #'S INCLUDE -

(3) IPS-B010D

TV OUTLET AS SHOWN IN

DETAIL #2 ON SHEET T-TJ-07

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

B

IM

/T

V H

S

A lv in C

Y o rk

V A

I n te g ra te d

H e a lt h

/1

-T E

C H

-T V

H S

A C

Y V

A M

C I n te g ra te d

H e a lt h

C e n te r- R

.r v t

/1

/2

:0

:4

P

M

T-TJ-08

TECHNOLOGY - DETAILS MURFREESBORO INTEGRATED

HEALTH

TH5-20-2022

626-20-102

JAK

NOT TO SCALE

WALL MOUNTED OUTLET - FOUR PORT

FACEPLATE

NOT TO SCALE

WIRELESS ACCESS POINT (COILED IN

CEILING)

NOT TO SCALE

GROUND BUSBAR (TYPICAL FOR ALL

TR'S)

NOT TO SCALE

5 WALL MOUNTED OUTLET - MON / CMON

NOT TO SCALE

6 AV WALL BOX

NOT TO SCALE

FLAT PANELWALL BOX

INFRASTRUCTURE

NOT TO SCALE

7 TV WALL BOX

FIRST FLOOR

SECOND FLOOR

IT G-145 COMM / MEDIA

CONTROL G-144

RG9 TO BLDG 7 (CATV HEADEND)

RG9 TO BLDG 116 (CATV HEADEND)

12 STRANDS MM (HC)

24 STRAND SM TO BLDG 2 (CROSS CONNECTING TO BLDG 7 WHERE PUBLIC ADDRESS HEADEND IS LOCATED)

24 STRANDS SM TO EXISTING SERVER ROOM

100 PAIR COPPER TO EXISTING PBX

100 PAIR COPPER TO EXISTING PBX

24 STRANDS SM TO CONTROL ROOM(SIM LAB)

24 STRANDS SM TO BLDG 105 (NETWORK)

24 STRANDS SM TO BLDG 106 (NETWORK)

24 STRANDS SM TO NURSING HOME (NETWORK/TELEPHONY)

100 PAIR COPPER TO NURSING HOME

24 STRANDS SM TO NURSING HOME (FIRE ALARM)

24 STRANDS SM TO BLDG 7 (FIRE ALARM)

24 STRANDS MM (SIM)

12 STRANDS SM (HC)EXISTING

IT ROOM

EXISTING FIBER TO DATA CENTER TO REMAIN

12 STRANDS MM (HC)

12 STRANDS SM (HC)

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2020

TLC No.:

www.tlc-engineers.com

121388

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldhfr.com

WOLD | HFR DESIGN

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

B

IM

/T

V H

S

A lv in C

Y o rk

V A

I n te g ra te d

H e a lt h

/1

-T E

C H

-T V

H S

A C

Y V

A M

C I n te g ra te d

H e a lt h

C e n te r- R

.r v t

/1

/2

:0

:5

P

M

T-TJ-09

TECHNOLOGY - RISER MURFREESBORO INTEGRATED

HEALTH

TH5-20-2022

626-20-102

JAK

1 RISER

90" MONITOR

INPUT OUTPUT

90" MONITOR

INPUT OUTPUT

CAT6

CAT6

LECTURN

INPUT OUTPUT

CAT6

CAT6

CAT6

HDMI

CAT6

CAT6

HDMI

HDMI

AUD

PROJECTOR

INPUT OUTPUT

CAT6

CAT6

CAT6

CAT6

LECTURN

INPUT OUTPUT

CAT6

eBUS

PROJECTION

SCREEN

INPUT OUTPUT

RS232

RS232

HDMI

AUD

HDMI

HDMI

90" MONITOR

INPUT OUTPUT

CAT6

CAT6

CAT6

CAT6 LECTURN

INPUT OUTPUT

CAT6

HDMI

AUD

HDMI

HDMI

PROJECTOR

INPUT OUTPUT

CAT6

CAT6

CAT6

CAT6

LECTURN

INPUT OUTPUT

CAT6

eBUS

PROJECTION

SCREEN

INPUT OUTPUT

RS232

RS232

HDMI

AUD

HDMI

HDMI

PROJECTOR

INPUTOUTPUT

CAT6

CAT6

CAT6

CAT6

LECTURN

INPUTOUTPUT

CAT6

eBUS

PROJECTION

SCREEN

INPUTOUTPUT

RS232

RS232

HDMI

AUD

HDMI

HDMI

PROJECTOR

INPUTOUTPUT

CAT6

CAT6

HDMI

HDMI

LECTURN

INPUTOUTPUT

CAT6

eBUS

PROJECTION

SCREEN

INPUTOUTPUT

RS232

RS232

HDMI

AUD

HDMI

HDMI

90" MONITOR

INPUT OUTPUT

CAT6

CAT6

CAT6

CAT6 LECTURN

INPUT OUTPUT

CAT6

HDMI

AUD

HDMI

HDMI

PROJECTOR

INPUT OUTPUT

CAT6

CAT6

CAT6

CAT6

LECTURN

INPUT OUTPUT

CAT6

eBUS

PROJECTION

SCREEN

INPUT OUTPUT

RS232

RS232

HDMI

AUD

HDMI

HDMI

PROJECTOR

INPUTOUTPUT

CAT6

CAT6

CAT6

CAT6

LECTURN

INPUTOUTPUT

CAT6

eBUS

PROJECTION

SCREEN

INPUTOUTPUT

RS232

RS232

HDMI

AUD

HDMI

HDMI

55" MONITOR

INPUT OUTPUT

55" MONITOR

INPUT OUTPUT

CAT6 CAT6

MULTI-PURPOSE G-36

MULTI-PURPOSE G-41

MULTI-PURPOSE G-40

MULTI-PURPOSE G-39 MULTI-PURPOSE G-38 MULTI-PURPOSE G-37

COMM / MEDIA

CONTROL G-144

COMPUTER LAB G-48 DE-BRIEF G-24 ALS CLASSROOM G-22

TOUCHSCREEN

CONTROL PANEL

HDMI INPUT

PLATE IN

LECTURN

VTEL

CAM

TCOM

CAM

MIC'S

PARTITION

SENSOR

TOUCHSCREEN

CONTROL PANEL

PARTITION

SENSOR

HDMI INPUT

PLATE IN

LECTURN

HDMI INPUT PLATE IN

LECTURN

PC FOR EACH ROOM

LOCATED IN RACK

PARTITION

SENSOR

PARTITION

SENSOR

PARTITION

SENSOR

VTEL

CAM

TCOM

CAM

MIC'S

TOUCHSCREEN

SCHEDULING PANEL

TOUCHSCREEN

SCHEDULING PANEL

TOUCHSCREEN

CONTROL PANEL

HDMI INPUT

PLATE IN

LECTURN

VTEL

CAM

TCOM

CAM

MIC'S

TOUCHSCREEN

SCHEDULING PANEL

TOUCHSCREEN

CONTROL PANEL

HDMI INPUT

PLATE IN

LECTURN

VTEL

CAM

TCOM

CAM

MIC'S

TOUCHSCREEN

SCHEDULING PANEL

TOUCHSCREEN

CONTROL PANEL

HDMI INPUT

PLATE IN

LECTURN

VTEL

CAM

TCOM

CAM

MIC'S

TOUCHSCREEN

SCHEDULING PANEL

AV CONTROLLER HEADEND

IN COMM / MEDIA CONTROL

TOUCHSCREEN

CONTROL PANEL

TOUCHSCREEN

SCHEDULING PANEL

VTEL

CAM

TCOM

CAM

MIC'S

HDMI INPUT PLATE IN

LECTURN

TOUCHSCREEN

CONTROL PANEL

TOUCHSCREEN

SCHEDULING PANEL

VTEL

CAM

TCOM

CAM

MIC'S

TOUCHSCREEN

CONTROL PANEL

HDMI INPUT

PLATE IN

LECTURN

VTEL

CAM

TCOM

CAM

MIC'S

TOUCHSCREEN

SCHEDULING PANEL

TOUCHSCREEN

CONTROL PANEL

HDMI INPUT

PLATE IN

LECTURN

VTEL

CAM

TCOM

CAM

MIC'S

TOUCHSCREEN

SCHEDULING PANEL

CONTROL ROOM G-27MED/SURG SIM LAB G-26 PROCEDURE SIM LAB G-30

UNDER COUNTER RACK

CAM CAMMIC MIC MIC MICCAM CAMCAM MICMICMICMIC CAM

AUDIO VISUAL FUNCTIONAL NARRATIVE

A/V SYSTEM TO BE VENDOR FURNISHED / VENDOR INSTALLED OTHER THAN PROJECTION SCREENS WHICH ARE TO BE CONTRACTOR FURNISHED / CONTRACTOR INSTALLED. SYSTEM BASIS OF DESIGN AS NOTED BELOW. CONTRACTOR TO PROVIDE ALL CONDUIT ROUGH IN, BACKING/SUPPORTS, AND POWER. CONTRACTOR TO PROVIDE AND INSTALL ELECTRIC PROJECTION SCREENS AND ELECTRIC PROJECTOR LIFTS. AV VENDOR TO PROVIDE ALL REMAINING EQUIPMENT, A/V INFRASTRUCTURE, SETUP, AND PROGRAMMING. AV NARRATIVE AND EQUIPMENT LISTED BELOW ARE INTENDED TO ESTABLISH DESIGN REQUIREMENTS BUT ARE NOT INTENDED TO BE COMPREHENSIVE LIST OF EQUIPMENT. AV VENDOR TO PROVIDE ALL NECESSARY EQUIPMENT AND A/V INFRASTRUCTURE TO PROVIDE FULLY FUNCTIONAL SYSTEM. AS PART OF SYSTEM SOLUTION, VENDOR TO INCLUDE SITE SPECIFIC SHOP DRAWINGS/PRODUCT SUBMITTALS FOR DESIGN TEAM APPROVAL, AND LAMINATED INSTRUCTIONAL USER CARDS FOR SYSTEM UTILIZATION.

AUDIO VISUAL SYSTEM - MULTI-PURPOSE ROOMS G-036, G-037, G-038, G-039, G-040, G-041 A/V SYSTEM TO PROVIDE FLEXIBILITY TO CONTROL ANY CONFIGURATION OF CONFERENCE ROOM SET UP WITH SPEAKERS, MICROPHONE, AND ASSOCIATED PROJECTION SCREENS OR DISPLAYS. EACH ROOM TO HAVE AV OUTLET WALL PLATES WHICH INCLUDE HDMI INPUT AND A DISPLAY PORT INPUT AND WOULD AUTO-SWITCH BETWEEN THE TWO WHEN THE WALL PLATE INPUT WAS SELECTED. EACH ROOM IS CONTROLLED BY A 10” TOUCHSCREEN CONTROL PANEL MOUNTED ON THE WALL BY THE LECTERN. ROOM COMBINE/SEPARATE TO BE HANDLED BY PARTITION SENSORS AND CONTROL LOGIC WOULD COMBINE THE ROOMS BASED OFF OF FOLDABLE WALL POSITION. IN THE COMBINED STATE THE INDIVIDUAL TOUCHSCREEN CONTROL PANEL FOR THE ROOM WOULD CONTROL ONLY THE VOLUME OF THE ROOM AND PROVIDE THE MEANS TO SELECT THE INPUT AND

ROUTE THE VIDEO TO ALL PROJECTORS IN THE COMBINED STATE.

AUDIO VISUAL SYSTEM - MULTI-PURPOSE G-036

AT THE ENTRY OF THIS ROOM THERE WILL BE A 7” TOUCHSCREEN SCHEDULING PANEL ALLOWING INDIVIDUALS TO SEE IF AND WHEN THE ROOM IS AVAILABLE. THIS SCHEDULE IS MANAGED AT A DEDICATED SCHEDULING PC IN WORK G-152. ONE 90” DISPLAY IS LOCATED ON THE PLAN EAST WALL AS SHOWN ON DRAWINGS. ONE 10” TOUCHSCREEN CONTROL PANEL IS LOCATED ON THE WALL BY THE LECTERN AS SHOWN ON DRAWINGS FOR ROUTING OF INPUTS FROM RACK MOUNTED PC IN COMM/MEDIA CONTROL G-144. A PORTABLE FLOOR LECTERN WITH BUILT-IN PUBLIC ADDRESS SYSTEM SHOULD BE LOCATED NEAR DISPLAY WITH A WIRELESS KEYBOARD & MOUSE. THE LECTERN WILL HOUSE AV EQUIPMENT FOR TRANSMITTING TO AND FROM COMM/MEDIA CONTROL G-144. A CAMERA ABOVE THE DISPLAY WITH VIEW OF THE ROOM AND CEILING MOUNTED MICROPHONES WILL PROVIDE LIVE TELECONFERENCING CAPABILITIES TO LOCAL AND DISPERSED GEOGRAPHIC SITES. AUDIO WILL BE ROUTED TO (4) CEILING MOUNTED SPEAKERS NOTED AS “S2” ON THE DRAWINGS. THERE WILL BE ONE CEILING MOUNTED VTEL CAMERA WITH A VIEW OF THE LECTERN TO

PROVIDE THE ABILITY TO BROADCAST TO LOCAL AND DISPERSED GEOGRAPHIC SITES.

AUDIO VISUAL SYSTEM - MULTI-PURPOSE G-037

AT THE ENTRY OF THIS ROOM THERE WILL BE A 7” TOUCHSCREEN SCHEDULING PANEL ALLOWING INDIVIDUALS TO SEE IF AND WHEN THE ROOM IS AVAILABLE. THIS SCHEDULE IS MANAGED AT A DEDICATED SCHEDULING PC IN WORK G-152. ONE CEILING MOUNTED ROLL-UP TYPE SCREEN WITH BLACK BOARDERS IS LOCATED AT THE PLAN NORTH WALL. THE PRIMARY CONTROL WILL BE THE 10” TOUCHSCREEN CONTROL PANEL LOCATED ON THE WALL BY THE LECTERN WITH THE SECONDARY BEING A WIRELESS REMOTE CONTROL. THE TOUCH SCREEN CONTROL PANEL WILL CONTROL INPUTS FROM RACK MOUNTED PC IN COMM/MEDIA CONTROL G-144.

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .