This document is a comprehensive environmental sampling and testing report for Building 1407 at Elmendorf Air Force Base, conducted by XENCO Laboratories in March 2012. The report details a hazardous materials survey that included testing paint chips and concrete surfaces for lead, PCBs, and asbestos. Key findings include lead concentrations ranging from 16.8 mg/kg to 172,000 mg/kg in various paint samples, with some samples significantly exceeding regulatory limits. The survey also identified potentially hazardous materials such as 13 mercury vapor lamps, 13 ballasts for mercury vapor lamps, 8 fluorescent light bulbs, and 4 ballasts for fluorescent lights. Asbestos testing from 2008 and 2012 showed mostly negative results, with one 2008 sample indicating 6% chrysotile asbestos in a roofing material. The building, constructed in 1972, was noted to have significant structural deterioration, including concrete spalling, missing drip edges, and major roof leaks that pose safety hazards to personnel and equipment.
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2021 Wake Island HTRW Survey
Facility: 1407 Condition: Damaged Vehicle Ops Parking Shed Utilization: In use Size: 8400 Square Feet Year Built: 1972
Construction: Cast-in-place concrete exterior. Flat rolled roofing and tar-coat. Major leaks exist.
There is deterioration of counterflashing. Drip edges are missing. Interior concrete walls and the underside of the roof is badly spalling and poses safety hazards to personnel and equipment. Rebar is exposed and corroding. The light fixtures in the bays are broken. Exterior paint is flaking and peeling. Concrete spalling inside facility is posing safety hazards to personnel and equipment. A map of the building location can be seen in Appendix 1.
Building 1407
Number of Stories: 1 Heat System Type: None Fuel Tanks: N/A PCB Painted Concrete: N/A Concrete in Foundation/Walls: 490 Cubic Yards Other Debris: 1,621 Cubic Yards
Attachment 8
Asbestos Found in Building 1407 (estimated quantities)
Expansion Joints: 90 Square Feet
The one sample of roofing that was positive for asbestos containing material was re-sampled in the same area and additional areas around the false positive. Resampled results came back negative.
Asbestos samples were not collected in 2021. Results from 2008 and 2012 are provided in Appendix 4.
Lead and PCB Paint Found in Building 1407
Lead based paint or coatings were identified in the following:
Paint on Concrete Columns 400 Square Feet Floor Stripping 130 Square Feet
The following Table shows paint samples collected in 2021 and analyzed for lead, toxicity characteristic leaching procedure (TCLP) lead, and polychlorinated biphenyls (PCBs). Complete 2021 results are provided in Appendix 3.
Sample # Location Lead
(total, mg/kg) TCLP Lead
(mg/L) PCBs
(mg/kg) Regulatory value: 5,000 5 50
W1407-100LP red jacket beam paint 1,010 NA ND W1407-101LP yellow/black stripe paint 19,500 NA ND W1407-001T red jacket beam paint NA ND NA
ND - Non-Detect NA - Not Analyzed mg – milligrams kg - kilograms L – liter Highlighted cells exceed corresponding regulatory value
One TCLP sample was collected from the red jacket beam paint and results were not detected above the regulatory limit of 5 milligrams per liter. Toxicity characteristic for lead is defined in
40 CFR 261.24.
Overall, PCBs in paint do not appear to be an environmental concern. Paint on metal does not constitute a leachability hazard and therefore all metal materials with PCB amended paint can be readily landfilled in an EPA permitted landfill per 40 CFR 761.62(b). PCBs were not detected in paint samples collected in 2021.
The yellow paint on pillars and floor stripping needs to be removed so the concrete can be recycled.
Paint results from 2012 are provided in Appendix 4.
Other Potentially Hazardous Materials found in Building 1407 (estimated quantities)
Mercury Vapor Lamps: 13 each Ballasts for Mercury Vapor Lamps: 13 each Fluorescent Light Bulbs: 8 each Ballasts for Fluorescent Lights: 4 each
Photo 1: Lead-based paint on concrete column paint. Photo 2: Yellow stripping on concrete floor.
Photo 3: Crack in exterior wall. Photo 4: Cracks and damage in exterior structure.
Photo 5: Mercury vapor lamps and ballasts. Photo 6: Concrete spalling on ceiling.
Appendix 1: Maps and Site Figures
From 2021
Figure 1:
Site Locations and
Vicinity Building Location
See Inset A
Inset A
Building 1407
Figure 2:
Building 1407 Dimensions
Building 1407 Dimensions
Appendix 2: Asbestos Sample Results
Asbestos Sample Report B1407-A
Asbestos samples were not collected in 2021.
Appendix 3: Lead and PCB Sample Results
DOD-QSM Cover Sheet
Wake Island HTRW
March 15, 2021
GEL Laboratories, LLC 2040 Savage Road Charleston, South Carolina 29407
(843) 556-8171
Project Manager: Valerie Davis Phone Extension: 4485 Email: Valerie.Davis@gel.com
Contract Purchase Order: New
Work Order: 536296 SDG: 536296
Client Contact:
Sean Benjamin U.S. Army Engineer District, AK (W911KB17A0011) PO Box 6898 Elmendorf Afb, Alaska 99506
Project Identification: Wake Island HTRW
Sample analyses were conducted using methodology as outlined in GEL Laboratories, LLC (GEL) Standard Operating Procedures. Test results for NELAP or ISO 17025 accredited tests are verified to meet the requirements of those standards, with any exceptions noted. The results reported relate only to the items tested and to the sample as received by the laboratory. These results may not be reproduced except as full reports without approval by the laboratory. Copies of GEL’s accreditations and certifications can be found on our website at www.gel.com.
GEL appreciates the opportunity to provide the enclosed analytical results for the sample(s) we received on March 01, 2021. This original data report has been prepared and reviewed in accordance with GEL’s standard operating procedures. If you have any questions, please do not hesitate to contact me at the phone number or e-mail address listed above.
Sincerely, PM_SIGN_HERE
Valerie Davis Project Manager
Meredith Boddiford for
Page 2 of 1049 SDG: 536296
Case Narrative
Page 3 of 1049 SDG: 536296
DODQSM Case Narrative for
U.S. Army Engineer District, AK (W911KB17A0011)
SDG: 536296
March 15, 2021
Laboratory Identification:
GEL Laboratories LLC 2040 Savage Road Charleston, South Carolina 29407
(843) 556-8171
Summary
Sample Receipt The samples arrived at GEL Laboratories LLC, Charleston, South Carolina on March 01, 2021 for analysis. The samples were delivered with proper chain of custody documentation and signatures. All sample containers arrived without any visible signs of tampering or breakage. There are no additional comments concerning sample receipt.
Sample Identification The laboratory received the following samples:
Laboratory ID Client ID
536296001 W1306-002LP
536296002 W1306-003LP
536296003 W1306-004LP
536296004 W1306-005LP
536296005 W1306-006LP
536296006 W1306-009LP
536296007 W1307-015LP
536296008 W1307-016LP
536296009 W1307-017LP
536296010 W1307-020L 536296011 W1307-021T 536296012 W1310-001T
536296013 W1310-003LP
536296014 W1310-004L
536296015 W1406-001LP
536296016 W1406-002LP
536296017 W1406-003T
536296018 W1407-100LP
536296019 W1407-101LP
536296020 W1407-001T
Page 4 of 1049 SDG: 536296
The enclosed data package contains the following sections: General Narrative, Chain of Custody and Supporting Documentation, and data from the following fractions: GC Semivolatile PCB and Metals.
PM_SIGN_HERE
Valerie Davis Project Manager
Meredith Boddiford for
Page 5 of 1049 SDG: 536296
Chain of Custody and Supporting
Documentation
Page 6 of 1049 SDG: 536296
Page 7 of 1049 SD G
: 536296
Page 8 of 1049 SDG: 536296
State Certification Alabama Alaska
Alaska Drinking Water Arkansas
CLIA
California Colorado
Connecticut DoD ELAP/ ISO17025 A2LA
Florida NELAP Foreign Soils Permit
Georgia Georgia SDWA
Hawaii Idaho
Illinois NELAP Indiana
Kansas NELAP Kentucky SDWA
Kentucky Wastewater Louisiana Drinking Water
Louisiana NELAP Maine
Maryland Massachusetts
Massachusetts PFAS Approv Michigan
Mississippi Nebraska Nevada
New Hampshire NELAP New Jersey NELAP
New Mexico New York NELAP
North Carolina North Carolina SDWA
North Dakota Oklahoma
Pennsylvania NELAP Puerto Rico
S. Carolina Radiochem Sanitation Districts of L
South Carolina Chemistry Tennessee
Texas NELAP Utah NELAP
Vermont Virginia NELAP
Washington
42200 17−018
SC00012
88−0651
42D0904046
SC00012
PH−0169
2567.01 E87156
P330−15−00283, P330−15−00253
SC00012
SC00012
SC00012
200029
C−SC−01
E−10332
90129 90129
LA024
03046 (AI33904)
2019020
M−SC012
Letter
SC00012
NE−OS−26−13
SC000122021−1
SC002
SC00012
11501
45709 R−158
2019−165 68−00485
SC00012
10120002 9255651 10120001
TN 02934
T104704235−21−19
SC000122020−34
VT87156
460202 C780
List of current GEL Certifications as of 15 March 2021
Page 9 of 1049 SDG: 536296
PCB Analysis
Page 10 of 1049 SDG: 536296
Page 11 of 1049 SDG: 536296
GC Semivolatile PCB Technical Case Narrative
U.S. Army Engineer District, AK
SDG #: 536296
Product: Analysis of The Analysis of Polychlorinated Biphenyls by GC/ECD by ECD Analytical Method: SW846 3541/8082A Analytical Procedure: GL-OA-E-040 REV# 25 Analytical Batch: 2100377
Preparation Method: SW846 3541 Preparation Procedure: GL-OA-E-066 REV# 9 Preparation Batch: 2100375
The following samples were analyzed using the above methods and analytical procedure(s).
GEL Sample ID# Client Sample Identification
536296007 W1307-015LP
536296008 W1307-016LP
536296009 W1307-017LP
1204768615 Method Blank (MB) 1204768616 Laboratory Control Sample (LCS) 1204768619 536828001(NonSDG) Matrix Spike (MS) 1204768620 536828001(NonSDG) Matrix Spike Duplicate (MSD)
The samples in this SDG were analyzed on an "as received" basis.
Data Summary:
All sample data provided in this report met the acceptance criteria specified in the analytical methods and procedures for initial calibration, continuing calibration, instrument controls and process controls where applicable, with the following exceptions.
Quality Control (QC) Information
Surrogate Recoveries Samples (See Below) did not meet acceptance criteria for surrogate recovery due to sample matrix interference.
Sample Analyte Value
536296007 (W1307-015LP)Decachlorobiphenyl175* (24%-138%)
536296008 (W1307-016LP)4cmx 149* (44%-130%)
Decachlorobiphenyl229* (24%-138%)
Decachlorobiphenyl708* (24%-138%)
Technical Information
Preparation/Analytical Method Verification All samples and QC in this batch were cleaned using alumina in order to remove oil and other high molecular weight interferences. All samples and QC in this batch were cleaned with activated copper in order to remove
Page 12 of 1049 SDG: 536296 sulfur. All reported analyte detections in client and quality control samples were within the established retention time windows. Reported analyte concentrations were confirmed on dissimilar columns.
Sample Dilutions Sample 536296008 (W1307-016LP) was diluted due to high level of non-target analytes within the retention time window of interest.
Sample Re-extraction/Re-analysis Sample 536296013 (W1310-003LP) was re-extracted due to surrogate failure.
Miscellaneous Information
Manual integrations Samples 1204768615 (MB), 1204768616 (LCS), 1204768619 (Non SDG 536828001MS), 1204768620 (Non SDG 536828001MSD), 536296007 (W1307-015LP), 536296008 (W1307-016LP), 536296009 (W1307-017LP) and 536296013 (W1310-003LP) required manual integration to correctly position the baseline as set in the calibration standard injections.
Additional Comments The column 1 has been chosen as the primary column. The data are reported from the column 1 for all samples in this batch.
Analytical Procedure: GL-OA-E-040 REV# 25 Analytical Batch: 2100382
Preparation Method: SW846 3541 Preparation Procedure: GL-OA-E-066 REV# 9 Preparation Batch: 2100380
The following samples were analyzed using the above methods and analytical procedure(s).
GEL Sample ID# Client Sample Identification
536296001 W1306-002LP
536296002 W1306-003LP
536296003 W1306-004LP
1204768630 Method Blank (MB) 1204768631 Laboratory Control Sample (LCS) 1204768632 Laboratory Control Sample Duplicate (LCSD)
The samples in this SDG were analyzed on an "as received" basis.
Data Summary:
All sample data provided in this report met the acceptance criteria specified in the analytical methods and procedures for initial calibration, continuing calibration, instrument controls and process controls where applicable, with the following exceptions.
Quality Control (QC) Information
Surrogate Recoveries Sample (See Below) recovered above the acceptance limits for the surrogate. The sample results were not adversely affected as the sample was not detected with Aroclors above the PQL.
Page 13 of 1049 SDG: 536296
Sample Analyte Value
536296002 (W1306-003LP)Decachlorobiphenyl1310* (24%-138%)
Laboratory Control Sample (LCSD) An LCSD was used in place of matrix QC due to limited sample volume.
Technical Information
Preparation/Analytical Method Verification All samples and QC in this batch were cleaned using alumina in order to remove oil and other high molecular weight interferences. All samples and QC in this batch were cleaned with activated copper in order to remove sulfur. All reported analyte detections in client and quality control samples were within the established retention time windows. Reported analyte concentrations were confirmed on dissimilar columns.
Sample Dilutions Samples 536296001 (W1306-002LP) and 536296002 (W1306-003LP) were diluted due to high level of non-target analytes within the retention time window of interest.
Miscellaneous Information
Manual integrations Samples 1204768631 (LCS), 1204768632 (LCSD), 536296001 (W1306-002LP), 536296002 (W1306-003LP), 536296003 (W1306-004LP) and All required manual integration to correctly position the baseline as set in the calibration standard injections.
Additional Comments The lower results from either column have been chosen and reported in the data package for the client samples, MB and LCS. The data reported for the MS/MSD are from the same analytical column as the parent sample.
Analytical Procedure: GL-OA-E-040 REV# 25 Analytical Batch: 2100591
Preparation Method: SW846 3541 Preparation Procedure: GL-OA-E-066 REV# 9 Preparation Batch: 2100588
The following samples were analyzed using the above methods and analytical procedure(s).
GEL Sample ID# Client Sample Identification
536296004 W1306-005LP
536296005 W1306-006LP
536296006 W1306-009LP
536296015 W1406-001LP
536296016 W1406-002LP
536296018 W1407-100LP
536296019 W1407-101LP
1204769083 Method Blank (MB) 1204769084 Laboratory Control Sample (LCS) 1204769085 Laboratory Control Sample Duplicate (LCSD)
Page 14 of 1049 SDG: 536296
The samples in this SDG were analyzed on an "as received" basis.
Data Summary:
All sample data provided in this report met the acceptance criteria specified in the analytical methods and procedures for initial calibration, continuing calibration, instrument controls and process controls where applicable, with the following exceptions.
Quality Control (QC) Information
Laboratory Control Sample (LCSD) An LCSD was used in place of matrix QC due to limited sample volume.
Technical Information
Preparation/Analytical Method Verification All samples and QC in this batch were cleaned using alumina in order to remove oil and other high molecular weight interferences. All samples and QC in this batch were cleaned with activated copper in order to remove sulfur. All reported analyte detections in client and quality control samples were within the established retention time windows. Reported analyte concentrations were confirmed on dissimilar columns.
Sample Dilutions Samples 536296004 (W1306-005LP), 536296005 (W1306-006LP), 536296006 (W1306-009LP), 536296015 (W1406-001LP), 536296016 (W1406-002LP) and 536296018 (W1407-100LP) were diluted due to high level of non-target analytes within the retention time window of interest.
Miscellaneous Information
Manual integrations Samples 1204769084 (LCS), 1204769085 (LCSD), 536296004 (W1306-005LP), 536296005 (W1306-006LP), 536296006 (W1306-009LP), 536296015 (W1406-001LP), 536296016 (W1406-002LP) and 536296018 (W1407-100LP) required manual integration to correctly position the baseline as set in the calibration standard injections and to properly identify one or more peaks.
Analytical Procedure: GL-OA-E-040 REV# 25 Analytical Batch: 2101722
Preparation Method: SW846 3541 Preparation Procedure: GL-OA-E-066 REV# 9 Preparation Batch: 2101721
The following samples were analyzed using the above methods and analytical procedure(s).
GEL Sample ID# Client Sample Identification
536296013 W1310-003LP
1204771176 Method Blank (MB) 1204771177 Laboratory Control Sample (LCS) 1204771594 537268001(NonSDG) Matrix Spike (MS) 1204771595 537268001(NonSDG) Matrix Spike Duplicate (MSD)
The samples in this SDG were analyzed on an "as received" basis.
Page 15 of 1049 SDG: 536296
Data Summary:
All sample data provided in this report met the acceptance criteria specified in the analytical methods and procedures for initial calibration, continuing calibration, instrument controls and process controls where applicable, with the following exceptions.
Technical Information
Preparation/Analytical Method Verification All samples and QC in this batch were cleaned using alumina in order to remove oil and other high molecular weight interferences. All samples and QC in this batch were cleaned with activated copper in order to remove sulfur. All reported analyte detections in client and quality control samples were within the established retention time windows. Reported analyte concentrations were confirmed on dissimilar columns.
Sample Dilutions The samples were diluted due to dark and thick sample extracts. 536296013 (W1310-003LP).
Miscellaneous Information
Additional Comments The column 1 has been chosen as the primary column. The data are reported from the column 1 for all samples in this batch.
Certification Statement
Where the analytical method has been performed under NELAP certification, the analysis has met all of the requirements of the NELAC standard unless otherwise noted in the analytical case narrative.
Page 16 of 1049 SDG: 536296
GEL LABORATORIES LLC
2040 Savage Road Charleston SC 29407 - (843) 556-8171 - www.gel.com
ACAK005 U.S. Army Engineer District, AK (W911KB17A0011)
Client SDG: 536296 GEL Work Order: 536296
GEL requires all analytical data to be verified by a qualified data reviewer. In addition, all CLP-like deliverables receive a third level review of the fractional data package.
The following data validator verified the information presented in this data report:
The Qualifiers in this report are defined as follows:
* Indicates that a quality control analyte recovery is outside of specified acceptance criteria.
** Indicates the analyte is a surrogate compound.
J Indicates an estimated value. The result was greater than the detection limit, but less than the reporting limit or indicates that the analyte recovery in the MS or MSD is outside of specified acceptance criteria or the response between the confirmation column and the primary column is >40%D.
Q LCS recovery not within control limits U Indicates the target analyte was analyzed for but not detected above the detection limit.
for
DL Indicates that sample is diluted.
RA Indicates that sample is re-analyzed without re-extraction.
RE Indicates that sample is re-extracted.
Qualifier Definition Report
Signature: Name:
Date: Title:15 MAR 2021
Cameron Bearden
Group Leader
Review/Validation
Page 17 of 1049 SDG: 536296
Sample Data Summary
Page 18 of 1049 SDG: 536296
GEL Laboratories LLC
PCB
Certificate of Analysis
Sample Summary
March 15, 2021Report Date:
SDG Number: 536296
Lab Sample ID: 536296018 Matrix: P
Date Received: 03/01/2021 09:15
Date Collected: 02/16/2021 09:20
12674-11-2
11104-28-2
11141-16-5
53469-21-9
12672-29-6
11097-69-1
11096-82-5
Aroclor-1016
Aroclor-1221
Aroclor-1232
Aroclor-1242
Aroclor-1248
Aroclor-1254
Aroclor-1260
0.622
0.622
0.622
0.622
0.622
0.622
0.622
U
U
U
U
U
U
U
0.311
0.311
0.311
0.311
0.311
0.311
0.311
0.935
0.935
0.935
0.935
0.935
0.935
0.935
Client: ACAK005 Project: ACAK00500
CAS No. Parmname ResultQualifier MDL LOQ
Method: SW846 3541/8082A GL-OA-E-040
Batch ID: 2100591 Inst: ECD8A.I Dilution: 10 SOP Ref:
Run Date: 03/12/2021 14:41 Analyst: JXM 1 uLInj. Vol:
Units mg/kg mg/kg mg/kg mg/kg mg/kg mg/kg mg/kg
W1407-100LPClient ID:
Prep Date: Aliquot: Final Volume:03/11/2021 07:34 1.07 g 1 mL
Column
Column:031221.b\e8c1237.D
031221.b\e8c1237.D
Data File: 1 Description: RTX-CLP
2 PEST2
LOD
0.622
0.622
0.622
0.622
0.622
0.622
0.622
Page 31 of 1049 SDG: 536296
GEL Laboratories LLC
PCB
Certificate of Analysis
Sample Summary
March 15, 2021Report Date:
SDG Number: 536296
Lab Sample ID: 536296019 Matrix: P
Date Received: 03/01/2021 09:15
Date Collected: 02/16/2021 09:25
12674-11-2
11104-28-2
11141-16-5
53469-21-9
12672-29-6
11097-69-1
11096-82-5
Aroclor-1016
Aroclor-1221
Aroclor-1232
Aroclor-1242
Aroclor-1248
Aroclor-1254
Aroclor-1260
0.888
0.888
0.888
0.888
0.888
0.888
0.888
U
U
U
U
U
U
U
0.444
0.444
0.444
0.444
0.444
0.444
0.444
1.33
1.33
1.33
1.33
1.33
1.33
1.33
Client: ACAK005 Project: ACAK00500
CAS No. Parmname ResultQualifier MDL LOQ
Method: SW846 3541/8082A GL-OA-E-040
Batch ID: 2100591 Inst: ECD8A.I Dilution: 10 SOP Ref:
Run Date: 03/12/2021 15:01 Analyst: JXM 1 uLInj. Vol:
Units mg/kg mg/kg mg/kg mg/kg mg/kg mg/kg mg/kg
W1407-101LPClient ID:
Prep Date: Aliquot: Final Volume:03/11/2021 07:34 .75 g 1 mL
Column
Column:031221.b\e8c1238.D
031221.b\e8c1238.D
Data File: 1 Description: RTX-CLP
2 PEST2
LOD
0.888
0.888
0.888
0.888
0.888
0.888
0.888
Page 32 of 1049 SDG: 536296
Metals Analysis
Page 782 of 1049 SDG: 536296
Page 783 of 1049 SDG: 536296
Metals Technical Case Narrative
U.S. Army Engineer District, AK
SDG #: 536296
Product: Determination of Metals by ICP-MS Analytical Method: SW846 3050B/6020B Analytical Procedure: GL-MA-E-014 REV# 34 Analytical Batch: 2098264
Product: Determination of Metals by ICP-MS Analytical Method: SW846 3010/6020 Analytical Procedure: GL-MA-E-014 REV# 34 Analytical Batch: 2099636
TCLP Preparation Method: SW846 1311 TCLP Preparation Procedure: GL-LB-E-006 REV# 22 TCLP Preparation Batch: 2099080
Composite Preparation Method: GEL Prep Method Composite Preparation Procedure: GL-RAD-A-026 REV# 18 Composite Preparation Batch: 2098198
Preparation Method: SW846 3050B Preparation Procedure: GL-MA-E-009 REV# 29 Preparation Batch: 2098263
Preparation Method: SW846 3010A Preparation Procedure: GL-MA-E-008 REV# 19 Preparation Batch: 2099635
The following samples were analyzed using the above methods and analytical procedure(s).
GEL Sample ID# Client Sample Identification
536296001 W1306-002LP
536296002 W1306-003LP
536296003 W1306-004LP
536296004 W1306-005LP
536296005 W1306-006LP
536296006 W1306-009LP
536296007 W1307-015LP
536296008 W1307-016LP
536296009 W1307-017LP
536296010 W1307-020L 536296012 W1310-001T
536296013 W1310-003LP
536296014 W1310-004L
536296015 W1406-001LP
536296016 W1406-002LP
536296017 W1406-003T
Page 784 of 1049 SDG: 536296
536296018 W1407-100LP
536296019 W1407-101LP
536296020 W1407-001T 1204765842 Tumble Blank (TB) 1204765843 536292008(W1504-006TS) Matrix Spike (MS) 1204764231 Method Blank (MB)ICP-MS 1204767016 Method Blank (MB)ICP-MS 1204764232 Laboratory Control Sample (LCS) 1204767017 Laboratory Control Sample (LCS) 1204764235 536296001(W1306-002LPL) Serial Dilution (SD) 1204767019 536292008(W1504-006TL) Serial Dilution (SD) 1204767018 536292008(W1504-006TD) Sample Duplicate (DUP) 1204764233 536296001(W1306-002LPS) Matrix Spike (MS) 1204765843 536292008(W1504-006TS) Matrix Spike (MS) 1204764234 536296001(W1306-002LPSD) Matrix Spike Duplicate (MSD)
The samples in this SDG were analyzed on an "as received" basis.
Data Summary:
All sample data provided in this report met the acceptance criteria specified in the analytical methods and procedures for initial calibration, continuing calibration, instrument controls and process controls where applicable, with the following exceptions.
Calibration Information
ICSA/ICSAB Statement For the ICP-MS analysis, the ICSA solution contains analyte concentrations which are verified trace impurities indigenous to the purchased standard.
Quality Control (QC) Information
MS/MSD Relative Percent Difference (RPD) Statement The RPD values between qualifying analyte results in the MS and MSD were not within the acceptance limits. Sample non-homogeneity and/or possible matrix interferences may be suspected.
Sample Analyte Value
1204764233MS and 1204764234MSD (W1306-002LP) Lead RPD 20.1* (0%-20%)
Technical Information
Preparation/Analytical Method Verification Method SW-846 3050B is not a total digestion technique for most samples. It is a very strong acid digestion that will dissolve almost all elements that could become environmentally available. By design, elements bound in silicate structures are not normally dissolved by this procedure as they are not usually mobile in the environment.
Sample Dilutions Dilutions may be required for many reasons, including to minimize matrix interferences or to bring over range target analyte concentrations into the linear calibration range. Samples 536296001 (W1306-002LP), 536296002 (W1306-003LP), 536296003 (W1306-004LP), 536296005 (W1306-006LP), 536296006 (W1306-009LP), 536296007
Page 785 of 1049 SDG: 536296
(W1307-015LP), 536296008 (W1307-016LP), 536296010 (W1307-020L), 536296013 (W1310-003LP), 536296014 (W1310-004L), 536296015 (W1406-001LP), 536296016 (W1406-002LP), 536296018 (W1407-100LP) and 536296019 (W1407-101LP)-ICP-MS were diluted to ensure that the analyte concentrations were within the linear calibration range of the instrument. The ICPMS solid samples in this SDG were diluted the standard two times.
ICP-MS.
Analyte 536296
001 002 003 004 005 006 007 008 009 010
Lead 40X 40X 10X 2X 1000X 200X 200X 100X 2X 20X
Analyte 536296
013 014 015 016 018 019
Lead 100X 10X 10000X 500X 10X 100X
Preparation Information The extracted samples and associated matrix QC were prepared at a ten times or greater dilution factor to minimize potential interferences from leached or filtered extracts. ICP-MS.
Certification Statement
Where the analytical method has been performed under NELAP certification, the analysis has met all of the requirements of the NELAC standard unless otherwise noted in the analytical case narrative.
Page 786 of 1049 SDG: 536296
GEL LABORATORIES LLC
2040 Savage Road Charleston SC 29407 - (843) 556-8171 - www.gel.com
ACAK005 U.S. Army Engineer District, AK (W911KB17A0011)
Client SDG: 536296 GEL Work Order: 536296
GEL requires all analytical data to be verified by a qualified data reviewer. In addition, all CLP-like deliverables receive a third level review of the fractional data package.
The following data validator verified the information presented in this data report:
The Qualifiers in this report are defined as follows:
J Indicates an estimated value. The result was greater than the detection limit, but less than the reporting limit or indicates that the analyte recovery in the MS or MSD is outside of specified acceptance criteria.
U Indicates the target analyte was analyzed for but not detected above the detection limit.
for Qualifier Definition Report
Signature: Name:
Date: Title:15 MAR 2021
Jamie Johnson
Group Leader
Review/Validation
Page 787 of 1049 SDG: 536296
Sample Data Summary
Page 788 of 1049 SDG: 536296
METALS
−1−
INORGANICS ANALYSIS DATA PACKAGE
GEL Laboratories LLC
SW846
SDG No: METHOD TYPE:
SAMPLE ID: CLIENT ID:
CONTRACT:
MATRIX: DATE RECEIVED LEVEL: %SOLIDS:
CAS No. Analyte Result Units C Qual M* Instrument
ID
Analytical
Run
Low
536296
536296018 W1407−100LP
ACAK00500
MISC SOLID 01−MAR−21
7439−92−1 Lead 1010 mg/kg 0.496 ICPMS14J MS 210312−3
SW846
MDL DF
100.992
LOD
1.98
LOQ
*Analytical Methods:
MS SW846 3050B/6020B
Page 805 of 1049 SDG: 536296
INORGANICS ANALYSIS DATA PACKAGE
GEL Laboratories LLC
SW846
SDG No: METHOD TYPE:
SAMPLE ID: CLIENT ID:
CONTRACT:
MATRIX: DATE RECEIVED LEVEL: %SOLIDS:
CAS No. Analyte Result Units C Qual M* Instrument
ID
Analytical
Run
Low
536296
536296019 W1407−101LP
ACAK00500
MISC SOLID 01−MAR−21
7439−92−1 Lead 19500 mg/kg 4.65 ICPMS14J MS 210312−3
SW846
MDL DF
1009.29
LOD
18.6
LOQ
*Analytical Methods:
MS SW846 3050B/6020B
Page 806 of 1049 SDG: 536296
INORGANICS ANALYSIS DATA PACKAGE
GEL Laboratories LLC
SW846
SDG No: METHOD TYPE:
SAMPLE ID: CLIENT ID:
CONTRACT:
MATRIX: DATE RECEIVED LEVEL: %SOLIDS:
CAS No. Analyte Result Units C Qual M* Instrument
ID
Analytical
Run
Low
536296
536296020 W1407−001T
ACAK00500
TCLP 01−MAR−21
7439−92−1 Lead 0.0100 mg/L 0.00500 ICPMS11U MS 210309−1
SW846
MDL DF
10.0100
LOD
0.0200
LOQ
*Analytical Methods:
MS SW846 3010/6020
Page 807 of 1049 SDG: 536296
Appendix 4: Older Sampling Locations
2008 Sampling Asbestos Results
BUILDING
NUMBER BUILDING LOCATION
WEC ID
NUMBER
SAMPLE
DATE SAMPLE LOCATION SAMPLE MATERIAL COLOR
ASBESTOS
IDENTIFICAT
ION % ASBESTOS
% OTHER FIBROUS
MATERIALS
% NON-
FIBROUS
MATERIALS
1407 HE Storage 1407R-01,02,03 7/30/2008 IH - Roofing Materials Trace <1% Asbestos IH - Silver Paint Yes 6% Chrysotile
2012 Sampling Asbestos Quick Sample Results Log Asbestos Lab Results, Feb 2012 Asbestos Lab Results, March 2012 Lead Paint Quick Sample Results Log Lead Lab Results
23-Mar-12
23-Mar-12
1-Feb-12
1-Feb-12
1-Feb-12
1-Feb-12
1-Feb-12
1-Feb-12
1-Feb-12
1-Feb-12
1-Feb-12
1-Feb-12
Date Sampled
Bldg.
ABWIA1407019
ABWIA1407018
ABWIA1407017
ABWIA1407016
ABWIA1407015
ABWIA1407014
ABWIA1407013
ABWIA1407012
ABWIA1407011
ABWIA1407010
ABWIA1407009
ABWIA1407008
ABWIA1407007
Sample Number
Roof C-side edge-Flashing End
Roof C-side edge-Flashing End
Roof C-side edge-Flashing End
Office B-side Wall
Office A-side Wall
Office B-side Wall
Office B-side Wall
C-side Ext. Wall
B-side High Bay Ext. Wall
B-side Low Bay Ext.Wall
Roof C-side far left corner
Roof A-side far left corner
Roof C-side edge
Sample Location
Mastic and Sealent
Flashing Mastic
Lap Sealent
Sheetrock
Sheetrock
Joint Compound
Joint Compound
Paint
Paint
Paint
Roofing
Roofing
Roofing
Sample Description
Black and Tan
Tan
Black
White
White
White
White
Tan
Tan
Tan
Black
Black
Black
Color
No
No
No
No
No
No
No
No
No
No
No
No
No
Asbestos
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
<1% Chrys
Asbestos Type
2012 Asbestos Quick Sample Results Log
23-Mar-12
23-Mar-12
23-Mar-12
23-Mar-12
23-Mar-12
Date Sampled
Bldg. 1407
Sample Number
ABWIA1407020
ABWIA1407021
ABWIA1407022
ABWIA1407023
ABWIA1407024
ABWIA1407025
ABWIA1407026
Sample Location
Roof C-side edge-Flashing End
Roof C-side edge-Flashing
Roof C-side edge-Flashing
Roof C-side edge-Flashing
Roof C-side edge-Flashing
Roof C-side edge-Flashing
Roof C-side edge-Flashing
Sample Description
Lap Sealent
Flashing Mastic
Mastic and Sealent
Lap Sealent
Mastic and Sealent
Flashing Mastic
Lap Sealent
Black
Tan
Black and Tan
Black
Black and Tan
Tan
Black
Color
No
No
No
No
No
No
No
Asbestos
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Asbestos Type
2012 Asbestos Quick Sample Results Log
LBPWIA1407013
LBPWIA1407012
LBPWIA1407011
LBPWIA1407010
LBPWIA1407009
LBPWIA1407008
LBPWIA1407007
LBPWIA1407006
LBPWIA1407005
LBPWIA1407004
LBPWIA1407003
LBPWIA1407002
LBPWIA1407001
Sample Number
Bldg.
2/1/2012 0:00
2/1/2012 0:00
2/1/2012 0:00
2/1/2012 0:00
2/1/2012 0:00
2/1/2012 0:00
2/1/2012 0:00
2/1/2012 0:00
2/1/2012 0:00
2/1/2012 0:00
2/1/2012 0:00
2/1/2012 0:00
2/1/2012 0:00
Date & Time
Lead Paint
Lead Paint
Lead Paint
Lead Paint
Lead Paint
Lead Paint
Lead Paint
Lead Paint
Lead Paint
Lead Paint
Lead Paint
Lead Paint
Lead Paint
Type
Dura
High Bay 2 B-side floor
High Bay 1 B-side floor
Low Bay 4 Left Pillar
Low Bay 4 Left Pillar
Low Bay 4 Left Pillar
High Bay 2 Right Pillar
High Bay 2 Right Pillar
High Bay 2 Right Pillar
High Bay 1 Left Pillar
High Bay 1 Left Pillar
High Bay 1 Left Pillar
Roof A-side Far Right Wall
Roof Far Right Corner
Component
Concrete
Concrete
Concrete
Concrete
Concrete
Concrete
Concrete
Concrete
Concrete
Concrete
Concrete
Concrete
Concrete
Substrate
Side
Poor
Poor
Poor
Poor
Poor
Poor
Poor
Poor
Poor
Poor
Poor
Poor
Poor
Cond.
Yellow
Green
Black
Yellow
Red
Black
Yellow
Red
Black
Yellow
Red
Tan
Brown
Color
Room
Negative
Negative
Negative
Positive
Negative
Negative
Positive
Negative
Negative
Positive
Negative
Negative
Negative
Results
39.1mg/kg/39.1ppm
16.8mg/kg/16.8ppm
660mg/kg/1660ppm
10000mg/kg/10000ppm
1340mg/kg/1340ppm
2390mg/kg/2390ppm
12100mg/kg/12100ppm
2350mg/kg/2350ppm
472mg/kg/472ppm
84400mg/kg/84400ppm
3470mg/kg/3470ppm
15.7mg/kg/15.7ppm
25.1mg/kg/25.1ppm
Pbl
2012 Lead Paint Quick Sample Results Log
Bldg.
Sample Number
LBPWIA1407015
LBPWIA1407017
LBPWIA1407018
2/1/2012 0:00
2/1/2012 0:00
2/1/2012 0:00
Date & Time
Lead Paint
Lead Paint
Lead Paint
Type
Dura Component
Low Bay D-side Ext. Wall
Low Bay 4 Floor
Office B-side Wall Concrete
Concrete
Concrete
Substrate
Side
Poor
Poor
Poor
Cond.
Tan
Yellow
Tan
Color
Room
Negative
Positive
Negative
Results Pbl
51.1mg/kg/51.1ppm
172000mg/kg/172000ppm
1630mg/kg/1630ppm
2012 Lead Paint Quick Sample Results Log
Analytical Report 437738 for
611 CES/CEOFE
Project Manager: George Alvarez
05-MAR-12
WO#60112
6017 Financial Dr., Norcross, GA 30071 Ph:(770) 449-8800 Fax:(770) 449-5477
Xenco-Houston (EPA Lab code: TX00122):
Texas (T104704215-10-6-TX), Arizona (AZ0765), Arkansas (08-039-0), Connecticut (PH-0102), Florida (E871002)
Illinois (002082), Indiana (C-TX-02), Iowa (392), Kansas (E-10380), Kentucky (45), Louisiana (03054) New Hampshire (297408), New Jersey (TX007), New York (11763), Oklahoma (9218), Pennsylvania (68-03610)
Rhode Island (LAO00312), USDA (S-44102)
Xenco-Atlanta (EPA Lab Code: GA00046):
Florida (E87429), North Carolina (483), South Carolina (98015), Utah (AALI1), West Virginia (362), Kentucky (85)
Louisiana (04176), USDA (P330-07-00105)
Xenco-Miami (EPA Lab code: FL01152): Florida (E86678), Maryland (330) Xenco-Tampa Mobile (EPA Lab code: FL01212): Florida (E84900) Xenco-Odessa (EPA Lab code: TX00158): Texas (T104704400-TX) Xenco-Dallas (EPA Lab code: TX01468): Texas (T104704295-TX)
Xenco Phoenix (EPA Lab Code: AZ00901): Arizona(AZ0757) Xenco-Phoenix Mobile (EPA Lab code: AZ00901): Arizona (AZM757)
Xenco Tucson (EPA Lab code:AZ000989): Arizona (AZ0758)
Celebrating 20 Years of commitment to excellence in Environmental Testing Services
Collected By: Client
Page 1 of 29 Final 1.000
Page 2 of 29 Final 1.000
Table of Contents
Cover Page 1 Cover Letter 3 Sample ID Cross Reference 4 Case Narrative 5 Explanation of Qualifiers (Flags) 6 Certificate of Analysis (Detailed Report) 7 Summary of Quality control 25
Chain of Custody 27
Sample Receipt Conformance Report 29
Houston - Dallas - San Antonio - Austin - Tampa - Miami - Atlanta - Corpus Christi - Latin America
Recipient of the Prestigious Small Business Administration Award of Excellence in 1994.
Certified and approved by numerous States and Agencies.
A Small Business and Minority Status Company that delivers SERVICE and QUALITY
Project Manager: George Alvarez
611 CES/CEOFE
6260 Artic Warrier Dr.
Elmendorf AFB, AK 99506
Reference: XENCO Report No: 437738 Project Address: AK
George Alvarez:
We are reporting to you the results of the analyses performed on the samples received under the project name referenced above and identified with the XENCO Report Number 437738. All results being reported under this Report Number apply to the samples analyzed and properly identified with a Laboratory ID number.
Subcontracted analyses are identified in this report with either the NELAC certification number of the subcontract lab in the analyst ID field, or the complete subcontracted report attached to this report.
Unless otherwise noted in a Case Narrative, all data reported in this Analytical Report are in compliance with NELAC standards. Estimation of data uncertainty for this report is found in the quality control section of this report unless otherwise noted. Should insufficient sample be provided to the laboratory to meet the method and NELAC Matrix Duplicate and Matrix Spike requirements, then the data will be analyzed, evaluated and reported using all other available quality control measures.
The validity and integrity of this report will remain intact as long as it is accompanied by this letter and reproduced in full, unless written approval is granted by XENCO Laboratories. This report will be filed for at least 5 years in our archives after which time it will be destroyed without further notice, unless otherwise arranged with you. The samples received, and described as recorded in Report No. 437738 will be filed for 60 days, and after that time they will be properly disposed without further notice, unless otherwise arranged with you. We reserve the right to return to you any unused samples, extracts or solutions related to them if we consider so necessary (e.g., samples identified as hazardous waste, sample sizes exceeding analytical standard practices, controlled substances under regulated protocols, etc).
We thank you for selecting XENCO Laboratories to serve your analytical needs. If you have any questions concerning this report, please feel free to contact us at any time.
Respectfully, 05-MAR-12
Client Services Director
David C. Fuller
Page 3 of 29 Final 1.000
Sample Cross Reference 437738 611 CES/CEOFE, Elmendorf AFB, AK
Sample Id
LBPWIA1407001
LBPWIA1407002
LBPWIA1407003
LBPWIA1407004
LBPWIA1407005
LBPWIA1407006
LBPWIA1407007
LBPWIA1407008
LBPWIA1407009
LBPWIA1407010
LBPWIA1407011
LBPWIA1407012
LBPWIA1407013
LBPWIA1407014
LBPWIA1407015
LBPWIA1407016
LBPWIA1407017
LBPWIA1407018
02-01-12 00:00 02-01-12 00:00 02-01-12 00:00 02-01-12 00:00 02-01-12 00:00 02-01-12 00:00 02-01-12 00:00 02-01-12 00:00 02-01-12 00:00 02-01-12 00:00 02-01-12 00:00 02-01-12 00:00 02-01-12 00:00 02-01-12 00:00 02-01-12 00:00 02-01-12 00:00 02-01-12 00:00 02-01-12 00:00
Date Collected Lab Sample Id
437738-001 437738-002 437738-003 437738-004 437738-005 437738-006 437738-007 437738-008 437738-009 437738-010 437738-011 437738-012 437738-013 437738-014 437738-015 437738-016 437738-017 437738-018
Sample DepthMatrix
S S S S S S S S S S S S S S S S S S
Page 4 of 29 Final 1.000
CASE NARRATIVE
437738Work Order Number:
05-MAR-12Report Date: WO#60112Project ID:
Project Name: 1407
Date Received:
Client Name: 611 CES/CEOFE
02/27/2012
None
LBA-882664
LBA-882671
Batch:
Batch:
SW6010C
Batch 882664, Lead recovered below QC limits in the Matrix Spike Duplicate.
Samples affected are: 437738-003, -004, -002, -005, -001.
The Laboratory Control Sample for Lead is within laboratory Control Limits
SW6010C
Batch 882671, Lead recovered below QC limits in the Matrix Spike Duplicate.
Samples affected are: 437738-011, -012, -016, -017, -007, -010, -006, -018, -009, -013, -014, - 008, -015.
The Laboratory Control Sample for Lead is within laboratory Control Limits
Metals, Total by SW846 6010C
Metals, Total by SW846 6010C
Sample receipt non conformances and comments:
Sample receipt non conformances and comments per sample:
Analytical non nonformances and comments:
Page 5 of 29 Final 1.000
Houston - Dallas - San Antonio - Atlanta - Midland/Odessa - Tampa/Lakeland - Phoenix - Latin America
4143 Greenbriar Dr, Stafford, TX 77477 9701 Harry Hines Blvd , Dallas, TX 75220 5332 Blackberry Drive, San Antonio TX 78238 2505 North Falkenburg Rd, Tampa, FL 33619 12600 West I-20 East, Odessa, TX 79765 6017 Financial Drive, Norcross, GA 30071 3725 E. Atlanta Ave, Phoenix, AZ 85040
Phone Fax
(281) 240-4200 (281) 240-4280
(214) 902 0300 (214) 351-9139
(210) 509-3334 (210) 509-3335
(813) 620-2000 (813) 620-2033
(432) 563-1800 (432) 563-1713
(770) 449-8800 (770) 449-5477
(602) 437-0330
Recipient of the Prestigious Small Business Administration Award of Excellence in 1994.
Certified and approved by numerous States and Agencies.
A Small Business and Minority Status Company that delivers SERVICE and QUALITY
Flagging Criteria
X In our quality control review of the data a QC deficiency was observed and flagged as noted. MS/MSD recoveries were found to be outside of the laboratory control limits due to possible matrix /chemical interference, or a concentration of target analyte high enough to affect the recovery of the spike concentration. This condition could also affect the relative percent difference in the MS/MSD.
B A target analyte or common laboratory contaminant was identified in the method blank. Its presence indicates possible field or laboratory contamination.
D The sample(s) were diluted due to targets detected over the highest point of the calibration curve, or due to matrix interference.
Dilution factors are included in the final results. The result is from a diluted sample.
E The data exceeds the upper calibration limit; therefore, the concentration is reported as estimated.
F RPD exceeded lab control limits.
J The target analyte was positively identified below the quantiation limit and above the detection limit.
U Analyte was not detected.
L The LCS data for this analytical batch was reported below the laboratory control limits for this analyte. The department supervisor and QA Director reviewed data. The samples were either reanalyzed or flagged as estimated concentrations.
H The LCS data for this analytical batch was reported above the laboratory control limits. Supporting QC Data were reviewed by the Department Supervisor and QA Director. Data were determined to be valid for reporting.
K Sample analyzed outside of recommended hold time.
JN A combination of the "N" and the "J" qualifier. The analysis indicates that the analyte is "tentatively identified" and the associated numerical value may not be consistent with the amount actually present in the environmental sample.
* Surrogate recovered outside laboratory control limit.
BRL Below Reporting Limit.
RL Reporting Limit
MDL Method Detection Limit SDL Sample Detection Limit LOD Limit of Detection
PQL Practical Quantitation Limit MQL Method Quantitation Limit LOQ Limit of Quantitation
DL Method Detection Limit
NC Non-Calculable
+ NELAC certification not offered for this compound.
* (Next to analyte name or method description) = Outside XENCO's scope of NELAC accreditation
Page 6 of 29 Final 1.000
Certificate of Analytical Results 437738
Project: WO#60112
611 CES/CEOFE, Elmendorf AFB, AK
Feb-27-12 09:50 Date Received:
Feb-01-12 00:00 Date Collected: 437738-001Lab Sample Id:
Paint ChipsMatrix: LBPWIA1407001 Sample Id:
Metals, Total by SW846 6010C Analytical Method:
4150Analyst:
SW3050BPrep Method:
Feb-29-12 10:46 Date Prep:
ABATech:
Lead
Parameter
1.16
Result
20.8
Flag mg/kg
Units
DilCas Number
7439-92-1 25.1
882664Seq Number:
RL
Wet WeightBasis:
MDL
03/01/12 14:52
Analysis Date
% Moisture:
Page 7 of 29 Final 1.000
611 CES/CEOFE, Elmendorf AFB, AK
Feb-27-12 09:50 Date Received:
Feb-01-12 00:00 Date Collected: 437738-002Lab Sample Id:
Paint ChipsMatrix: LBPWIA1407002 Sample Id:
Metals, Total by SW846 6010C Analytical Method:
4150Analyst:
SW3050BPrep Method:
Feb-29-12 10:46 Date Prep:
ABATech:
Lead
Parameter
0.607
Result
10.9
Flag mg/kg
Units
DilCas Number
7439-92-1 15.7
882664Seq Number:
RL
Wet WeightBasis:
MDL
03/01/12 14:54
Analysis Date
Page 8 of 29 Final 1.000
611 CES/CEOFE, Elmendorf AFB, AK
Feb-27-12 09:50 Date Received:
Feb-01-12 00:00 Date Collected: 437738-003Lab Sample Id:
Paint ChipsMatrix: LBPWIA1407003 Sample Id:
Metals, Total by SW846 6010C Analytical Method:
4150Analyst:
SW3050BPrep Method:
Feb-29-12 10:46 Date Prep:
ABATech:
Lead
Parameter
1.27
Result
22.7
Flag mg/kg
Units
DilCas Number
7439-92-1 3470
882664Seq Number:
RL
Wet WeightBasis:
MDL
03/01/12 15:00
Analysis Date
Page 9 of 29 Final 1.000
611 CES/CEOFE, Elmendorf AFB, AK
Feb-27-12 09:50 Date Received:
Feb-01-12 00:00 Date Collected: 437738-004Lab Sample Id:
Paint ChipsMatrix: LBPWIA1407004 Sample Id:
Metals, Total by SW846 6010C Analytical Method:
4150Analyst:
SW3050BPrep Method:
Feb-29-12 10:46 Date Prep:
ABATech:
Lead
Parameter
13.3
Result
D238
Flag mg/kg
Units
DilCas Number
7439-92-1 84400
882664Seq Number:
RL
Wet WeightBasis:
MDL
03/02/12 10:37
Analysis Date
Page 10 of 29 Final 1.000
611 CES/CEOFE, Elmendorf AFB, AK
Feb-27-12 09:50 Date Received:
Feb-01-12 00:00 Date Collected: 437738-005Lab Sample Id:
Paint ChipsMatrix: LBPWIA1407005 Sample Id:
Metals, Total by SW846 6010C Analytical Method:
4150Analyst:
SW3050BPrep Method:
Feb-29-12 10:46 Date Prep:
ABATech:
Lead
Parameter
1.16
Result
20.8
Flag mg/kg
Units
DilCas Number
7439-92-1 472
882664Seq Number:
RL
Wet WeightBasis:
MDL
03/01/12 15:03
Analysis Date
Page 11 of 29 Final 1.000
611 CES/CEOFE, Elmendorf AFB, AK
Feb-27-12 09:50 Date Received:
Feb-01-12 00:00 Date Collected: 437738-006Lab Sample Id:
Paint ChipsMatrix: LBPWIA1407006 Sample Id:
Metals, Total by SW846 6010C Analytical Method:
4150Analyst:
SW3050BPrep Method:
Feb-29-12 10:46 Date Prep:
ABATech:
Lead
Parameter
1.27
Result
22.7
Flag mg/kg
Units
DilCas Number
7439-92-1 2350
882671Seq Number:
RL
Wet WeightBasis:
MDL
03/01/12 15:16
Analysis Date
Page 12 of 29 Final 1.000
611 CES/CEOFE, Elmendorf AFB, AK
Feb-27-12 09:50 Date Received:
Feb-01-12 00:00 Date Collected: 437738-007Lab Sample Id:
Paint ChipsMatrix: LBPWIA1407007 Sample Id:
Metals, Total by SW846 6010C Analytical Method:
4150Analyst:
SW3050BPrep Method:
Feb-29-12 10:46 Date Prep:
ABATech:
Lead
Parameter
1.27
Result
22.7
Flag mg/kg
Units
DilCas Number
7439-92-1 12100
882671Seq Number:
RL
Wet WeightBasis:
MDL
03/01/12 15:28
Analysis Date
Page 13 of 29 Final 1.000
611 CES/CEOFE, Elmendorf AFB, AK
Feb-27-12 09:50 Date Received:
Feb-01-12 00:00 Date Collected: 437738-008Lab Sample Id:
Paint ChipsMatrix: LBPWIA1407008 Sample Id:
Metals, Total by SW846 6010C Analytical Method:
4150Analyst:
SW3050BPrep Method:
Feb-29-12 10:46 Date Prep:
ABATech:
Lead
Parameter
3.10
Result
55.6
Flag mg/kg
Units
DilCas Number
7439-92-1 2390
882671Seq Number:
RL
Wet WeightBasis:
MDL
03/01/12 15:30
Analysis Date
Page 14 of 29 Final 1.000
611 CES/CEOFE, Elmendorf AFB, AK
Feb-27-12 09:50 Date Received:
Feb-01-12 00:00 Date Collected: 437738-009Lab Sample Id:
Paint ChipsMatrix: LBPWIA1407009 Sample Id:
Metals, Total by SW846 6010C Analytical Method:
4150Analyst:
SW3050BPrep Method:
Feb-29-12 10:46 Date Prep:
ABATech:
Lead
Parameter
0.872
Result
15.6
Flag mg/kg
Units
DilCas Number
7439-92-1 1340
882671Seq Number:
RL
Wet WeightBasis:
MDL
03/01/12 15:32
Analysis Date
Page 15 of 29 Final 1.000
611 CES/CEOFE, Elmendorf AFB, AK
Feb-27-12 09:50 Date Received:
Feb-01-12 00:00 Date Collected: 437738-010Lab Sample Id:
Paint ChipsMatrix: LBPWIA1407010 Sample Id:
Metals, Total by SW846 6010C Analytical Method:
4150Analyst:
SW3050BPrep Method:
Feb-29-12 10:46 Date Prep:
ABATech:
Lead
Parameter
1.33
Result
23.8
Flag mg/kg
Units
DilCas Number
7439-92-1 10000
882671Seq Number:
RL
Wet WeightBasis:
MDL
03/01/12 15:39
Analysis Date
Page 16 of 29 Final 1.000
611 CES/CEOFE, Elmendorf AFB, AK
Feb-27-12 09:50 Date Received:
Feb-01-12 00:00 Date Collected: 437738-011Lab Sample Id:
Paint ChipsMatrix: LBPWIA1407011 Sample Id:
Metals, Total by SW846 6010C Analytical Method:
4150Analyst:
SW3050BPrep Method:
Feb-29-12 10:46 Date Prep:
ABATech:
Lead
Parameter
1.64
Result
29.4
Flag mg/kg
Units
DilCas Number
7439-92-1 1660
882671Seq Number:
RL
Wet WeightBasis:
MDL
03/01/12 15:41
Analysis Date
Page 17 of 29 Final 1.000
611 CES/CEOFE, Elmendorf AFB, AK
Feb-27-12 09:50 Date Received:
Feb-01-12 00:00 Date Collected: 437738-012Lab Sample Id:
Paint ChipsMatrix: LBPWIA1407012 Sample Id:
Metals, Total by SW846 6010C Analytical Method:
4150Analyst:
SW3050BPrep Method:
Feb-29-12 10:46 Date Prep:
ABATech:
Lead
Parameter
1.21
Result
J21.7
Flag mg/kg
Units
DilCas Number
7439-92-1 16.8
882671Seq Number:
RL
Wet WeightBasis:
MDL
03/01/12 15:43
Analysis Date
Page 18 of 29 Final 1.000
611 CES/CEOFE, Elmendorf AFB, AK
Feb-27-12 09:50 Date Received:
Feb-01-12 00:00 Date Collected: 437738-013Lab Sample Id:
Paint ChipsMatrix: LBPWIA1407013 Sample Id:
Metals, Total by SW846 6010C Analytical Method:
4150Analyst:
SW3050BPrep Method:
Feb-29-12 10:46 Date Prep:
ABATech:
Lead
Parameter
1.27
Result
22.7
Flag mg/kg
Units
DilCas Number
7439-92-1 39.1
882671Seq Number:
RL
Wet WeightBasis:
MDL
03/01/12 15:45
Analysis Date
Page 19 of 29 Final 1.000
611 CES/CEOFE, Elmendorf AFB, AK
Feb-27-12 09:50 Date Received:
Feb-01-12 00:00 Date Collected: 437738-014Lab Sample Id:
Paint ChipsMatrix: LBPWIA1407014 Sample Id:
Metals, Total by SW846 6010C Analytical Method:
4150Analyst:
SW3050BPrep Method:
Feb-29-12 10:46 Date Prep:
ABATech:
Lead
Parameter
1.33
Result
23.8
Flag mg/kg
Units
DilCas Number
7439-92-1 35.1
882671Seq Number:
RL
Wet WeightBasis:
MDL
03/01/12 15:47
Analysis Date
Page 20 of 29 Final 1.000
611 CES/CEOFE, Elmendorf AFB, AK
Feb-27-12 09:50 Date Received:
Feb-01-12 00:00 Date Collected: 437738-015Lab Sample Id:
Paint ChipsMatrix: LBPWIA1407015 Sample Id:
Metals, Total by SW846 6010C Analytical Method:
4150Analyst:
SW3050BPrep Method:
Feb-29-12 10:46 Date Prep:
ABATech:
Lead
Parameter
0.900
Result
16.1
Flag mg/kg
Units
DilCas Number
7439-92-1 51.1
882671Seq Number:
RL
Wet WeightBasis:
MDL
03/01/12 15:49
Analysis Date
Page 21 of 29 Final 1.000
611 CES/CEOFE, Elmendorf AFB, AK
Feb-27-12 09:50 Date Received:
Feb-01-12 00:00 Date Collected: 437738-016Lab Sample Id:
Paint ChipsMatrix: LBPWIA1407016 Sample Id:
Metals, Total by SW846 6010C Analytical Method:
4150Analyst:
SW3050BPrep Method:
Feb-29-12 10:46 Date Prep:
ABATech:
Lead
Parameter
1.33
Result
23.8
Flag mg/kg
Units
DilCas Number
7439-92-1 120
882671Seq Number:
RL
Wet WeightBasis:
MDL
03/01/12 15:52
Analysis Date
Page 22 of 29 Final 1.000
611 CES/CEOFE, Elmendorf AFB, AK
Feb-27-12 09:50 Date Received:
Feb-01-12 00:00 Date Collected: 437738-017Lab Sample Id:
Paint ChipsMatrix: LBPWIA1407017 Sample Id:
Metals, Total by SW846 6010C Analytical Method:
4150Analyst:
SW3050BPrep Method:
Feb-29-12 10:46 Date Prep:
ABATech:
Lead
Parameter
12.1
Result
D217
Flag mg/kg
Units
DilCas Number
7439-92-1 172000
882671Seq Number:
RL
Wet WeightBasis:
MDL
03/01/12 18:04
Analysis Date
Page 23 of 29 Final 1.000
611 CES/CEOFE, Elmendorf AFB, AK
Feb-27-12 09:50 Date Received:
Feb-01-12 00:00 Date Collected: 437738-018Lab Sample Id:
Paint ChipsMatrix: LBPWIA1407018 Sample Id:
Metals, Total by SW846 6010C Analytical Method:
4150Analyst:
SW3050BPrep Method:
Feb-29-12 10:46 Date Prep:
ABATech:
Lead
Parameter
1.33
Result
23.8
Flag mg/kg
Units
DilCas Number
7439-92-1 1630
882671Seq Number:
RL
Wet WeightBasis:
MDL
03/01/12 15:56
Analysis Date
Page 24 of 29 Final 1.000
QC Summary 437738
611 CES/CEOFE, Elmendorf AFB, AK
618502-1-BLK
618503-1-BLK
437725-001
437738-006
437725-001
MB Sample Id:
MB Sample Id:
Parent Sample Id:
Parent Sample Id:
Parent Sample Id:
Solid
Solid
Paint Chips
Paint Chips
Paint Chips
Matrix:
Matrix:
Matrix:
Matrix:
Matrix:
Metals, Total by SW846 6010C
Metals, Total by SW846 6010C
Metals, Total by SW846 6010C
Metals, Total by SW846 6010C
Metals, Total by SW846 6010C
Analytical Method:
Analytical Method:
Analytical Method:
Analytical Method:
Analytical Method:
SW3050B
SW3050B
SW3050B
SW3050B
SW3050B
Prep Method:
Prep Method:
Prep Method:
Prep Method:
Prep Method:
02/29/2012
02/29/2012
02/29/2012
02/29/2012
02/29/2012
Date Prep:
Date Prep:
Date Prep:
Date Prep:
Date Prep:
Lead
Lead
Lead
Lead
Lead
Parameter
Parameter
Parameter
Parameter
Parameter
%RPD
%RPD
%RPD
%RPD
%RPD
F
X
Flag
Flag
Flag
Flag
Flag
RPD
Limit
RPD
Limit
RPD
Limit
RPD
Limit
RPD
Limit
882664
882671
882664
882671
882664
Seq Number:
Seq Number:
Seq Number:
Seq Number:
Seq Number:
03/01/12 13:57
03/01/12 15:07
03/01/12 14:03
03/01/12 15:18
03/01/12 14:05
Analysis Date
Analysis Date
Analysis Date
Analysis Date
Analysis Date
Limits
Limits
Limits
Limits
Limits
80-120
80-120
80-120
80-120
80-120
LCSD
%Rec
LCSD
%Rec
MD
%Rec
MD
%Rec
MSD
%Rec
LCSD
Result
LCSD
Result
MD
Result
MD
Result
MSD
Result
94.7
92.9
LCS
%Rec
LCS
%Rec
MD
%Rec
MD
%Rec
MS
%Rec
93.5
94.1
Spike Amount
Spike Amount
Spike Amount
Spike Amount
Spike Amount
MB
Result
MB
Result
Parent Result
Parent Result
Parent Result
<0.279
<0.279
618502-1-BKS
618503-1-BKS
437725-001 D
437738-006 D
437725-001 S
LCS Sample Id:
LCS Sample Id:
MD Sample Id:
MD Sample Id:
MS Sample Id:
618502-1-BSD
618503-1-BSD
437725-001 D
437738-006 D
437725-001 SD
LCSD Sample Id:
LCSD Sample Id:
MD Sample Id:
MD Sample Id:
MSD Sample Id:
mg/kg mg/kg mg/kg mg/kg mg/kg
Units
Units
Units
Units
Units
LCS
Result
LCS
Result
MD
Result
MD
Result
MS
Result
Page 25 of 29 Final 1.000
QC Summary 437738
611 CES/CEOFE, Elmendorf AFB, AK
437738-006Parent Sample Id:
Paint ChipsMatrix:
Metals, Total by SW846 6010CAnalytical Method: SW3050BPrep Method:
02/29/2012Date Prep:
Lead
Parameter %RPD
X
Flag
RPD
Limit
882671Seq Number:
03/01/12 15:20
Analysis Date
Limits
80-120
MSD
%Rec
MSD
Result
MS
%Rec
1342990
Spike Amount
Parent Result
437738-006 SMS Sample Id: 437738-006 SDMSD Sample Id:
mg/kg
UnitsMS Result
Page 26 of 29 Final 1.000
Page…