ATTACHMENT 5 - FINAL DRAWINGS - CLC RENO SPOKANE - PART 3 of 3.pdf

PDF 17 MB Posted

Attached to
Y1DZ--668-318 Renovate and Expand Community Living Center Minor Construction - Spokane VAMC
Solicitation number
36C77623B0071
Issued by

About this file

This file attachment is related to drawings for the renovation and expansion of a Community Living Center at the Spokane VA Medical Center. The solicitation seeks to renovate and expand the existing Community Living Center to address space and facility deficiencies. Key project details include renovating up to 60,000 square feet of existing space and adding approximately 30,000 square feet of new construction. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center in Austin, with responses due by January 2023 and work expected to be completed by 2025. Pricing will be fixed-price with progress payments. The opportunity is open to all contractors but includes a preference for Service-Disabled Veteran-Owned Small Businesses.

View the file

Other files

File Type Posted
Wage Determination WDWA20230017 MOD4.pdf PDF
36C77623B0071 0006.docx DOCX document
EP612 12.11.2023.pdf PDF
36C77623B0071 0005.docx DOCX document
MP103 12.12.2023.pdf PDF
CLC Technical Response Tracking Spreadsheet - 12.13.2023.pdf PDF
MH701 12.12.2023.pdf PDF
MH603 12.12.2023.pdf PDF
36C77623B0071 0004.docx DOCX document
Question 97 - formatrac-bendable-track_specifications-ipc.1196-rev9.pdf PDF
CLC Technical Response Tracking Spreadsheet - 12.4.2023.pdf PDF
Question 82 - CO-Series-Product-Sheet-PS-CO8 (1).pdf PDF
36C77623B0071 0003.docx DOCX document
Question 5 and 64 - 09 29 00 - Gyp Board.pdf PDF
CLC Technical Response Tracking Spreadsheet - FINAL.pdf PDF
Question 67 - Spokane Design Requirements - Design Amendments May 2021.pdf PDF
CLC - Master Submittal Register (Responding to item 4 on VA email from 11.15.2023.pdf PDF
Question 44 - Links word and excel Statement of SI Temp.pdf PDF
Lift count - CLC Spokane - 100_ CD Drawings_.pdf PDF
LIFT INFORMATION - LI-WVA-019-04- Existing Lifts .pdf PDF
Amendment 0002 Technical Question Tracker.pdf PDF
36C77623B0071 0002.docx DOCX document
LQ-610380-07 NEW LIFT INFO.pdf PDF
SF1442 Page 2 - Signature Page.pdf PDF
CLC Technical Response Tracking Spreadsheet - 10-26-2023.pdf PDF
Wage Determination WDWA20230017 MOD2.pdf PDF
Completed Site Visit Sign-In Sheet 10-17-23.pdf PDF
36C77623B0071 0001.docx DOCX document
ATTACHMENT 7 - DAVIS-BACON ACT WAGE DETERMINATION WDWA20230017 MOD1.pdf PDF
ATTACHMENT 1 - FINAL SPECIFICATIONS - CLC RENO SPOKANE - PART 1 of 2.pdf PDF
ATTACHMENT 2 - FINAL SPECIFICATIONS - CLC RENO SPOKANE - PART 2 of 2.pdf PDF
ATTACHMENT 4 - FINAL DRAWINGS - CLC RENO SPOKANE - PART 2 of 3.pdf PDF
ATTACHMENT 3 - FINAL DRAWINGS - CLC RENO SPOKANE - PART 1 of 3.pdf PDF
ATTACHMENT 6 - LIMITATIONS ON SUBCONTRACTING.docx DOCX document
ATTACHMENT 8 - SITE VISIT INSTRUCTIONS.pdf PDF
36C77623B0071.docx DOCX document
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TN N

PROJECT NUMBER

BUILDING

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD SEALCONSULTANT

321 4 5 6 7 8 9 10

DWG. OF

NAME:

FULLY SPRINKLERED

CONTRACTING OFFICER

FULL SIZE DWG: 30x42

PHONE:

EMAIL:11031 S. PIKES PEAK DRIVE #202 PARKER, COLORADO 80138 PH. 303.841-3922

668-318

NORTH

SOUTH

WEST EAST

DAVID ARMENT

504-964-1889 David.Arment@va.govREVISIONS DATE

32'8'

SCALE:1/16"=1'-0"

0 16'

BLDG. 1

APRIL 2023

CONTRACTING OFFICER'S REPRESENTATIVE

100% SUBMITTAL

CONSTRUCTION

DOCUMENTS (CD)

RENOVATE AND EXPAND

COMMUNITY LIVING

CENTER (CLC)

SPOKANE, WA

ARCHITECT/ENGINEER OF RECORD

11031 S. PIKES PEAK DRIVE #202 PARKER, COLORADO 80138 PH. 303.841-3922

Group, Inc.

FIRE ALARM SYSTEM PLAN OVERALL

FA100

RDL RDL

3 APRIL 2023

1 1

2 2

3 3

4 4

5 5

6 6

7 7

8 8

A B C D E F

G

H

J

K

L

M

N

W101

RESIDENT

BEDROOM

W102

CLEAN LINEN

W103

SOILED LINEN

W104

RESIDENT

BEDROOM

W105

RESIDENT

BEDROOM

W106

RESIDENT

BEDROOM

W107

RESIDENT

BARIATRIC

BEDROOM

W108

FAMILY

W109

RESIDENT

BEDROOM

W110

RESIDENT

BEDROOM

164B

W112

STOR

W113

RESIDENT

BEDROOM

W115

TELECOM

W117

RESIDENT

BEDROOM

W118

RESIDENT

BEDROOM

S101

RESIDENT

BEDROOM

S102

HAC

S103

ELECTRICAL ROOM

S104

RESIDENT

BEDROOMS105

RESIDENT

BEDROOM

S106

RESIDENT

BARIATRIC

BEDROOM

S107

RESIDENT

BEDROOM

S108

RESIDENT

BEDROOM

S109

RESIDENT

BEDROOM

S110

RESIDENT

BEDROOM

S111

RESIDENT

BEDROOM

S112

MECHANICAL ROOM

S113

TELECOM

S114

ENTRY VESTIBULE

S115

CORR

S116

NURSE STATION

S117

RESIDENT

BEDROOM

S118

RESIDENT

BEDROOM

S119

RESIDENT

BEDROOM

S120

RESIDENT

BEDROOM

S121

DINING ROOM

S122

RESIDENT

BEDROOM

S001

CORR

S002

CORRIDOR

W001

CORRIDOR

W002

CORR

C1-10

C1-11

119B

126A

C1-3

S122A

RESIDENT

BATHROOM

S101A

RESIDENT

BATHROOM

S121A

UNISEX BATHROOM

S120A

RESIDENT

BATHROOM

S119A

RESIDENT

BATHROOM

S118A

RESIDENT

BATHROOM

S117A

RESIDENT

BATHROOM

S104A

RESIDENT

BATHROOM

S106A

RESIDENT

BARIATRIC

BATHROOM

S107A

RESIDENT

BATHROOM

S108A

RESIDENT

BATHROOM

S109A

RESIDENT

BATHROOM

S110A

RESIDENT

BATHROOM

S111A

RESIDENT

BATHROOM

W105A

RESIDENT

BATHROOM

W104A

RESIDENT

BATHROOM

W101A

RESIDENT

BATHROOM

W107A

RESIDENT

BARIATRIC

BATHROOM

W106A

RESIDENT

BATHROOM

W109A

RESIDENT

BATHROOM

W110A

RESIDENT

BATHROOM

W118A

RESIDENT

BATHROOM

W117A

RESIDENT

BATHROOM

W116A

RESIDENT

BATHROOM

W114A

RESIDENT

BATHROOM

W113A

RESIDENT

BATHROOM

C1-2

108 109 110

109A

109C 109D

109E 115A

115C

115B

115D

C1-4

C1-5

C1-7

114A 114

117118

120 121 C1

123 122A

B.1 C.7 F.1

'-4

3/ 8"

1'- 4"

RESIDENT

BEDROOM

RESIDENT

BEDROOM

RESIDENT

BEDROOM

RESIDENT

BEDROOM

RESIDENT

BEDROOM

RESIDENT

BEDROOM

RESIDENT

BEDROOM

RESIDENT

BEDROOM

RESIDENT

BEDROOM

RESIDENT

BEDROOM

RESIDENT

BEDROOM

146A

144A

TOILET

E108

ELECTRICAL

142A

BATH

140A

TOILET

C1-12

C1-12

C1-13

CORRIDOR

136A

TOILET

138A

TOILET

134A

TOILET

133A

BATH

131A

TOILET

129A

164A

C1-1

C1-7

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

P

TS FS

TS

FS

TS

FS

FACP

(E)(N)

P

(E)

(E)

(E)

(E)

(E)

(E)

(E)

(E)

(E)

(E)

(E)

P

(E) P

(E) P

(E) P

(E)

(E)

(E)

(E)

(E)

ZONE 12B ZONE 12C

ZONE 12A

ZONE 12E (NEW)

(E)

DH

(E)

DH

(E)

DH

(E)

DH

DH

DH

(E)

(E)

(E)

(E)

(E)

(E)

(E)

(E)

(E)

(E)

(E)

TS FS

WP

WP

WP

1. THE FIRE ALARM SYSTEM DESIGN, ENGINEERING AND

INSTALLATION AS INDICATED ON THIS PLAN SHALL

COMPLY WITH NFPA 72 (2019 EDITION), NFPA 101 (2018

EDITION), VA FIRE PROTECTION DESIGN MANUAL (EIGHTH

EDITION) AND OTHER APPLICABLE CODES AND

STANDARDS AS REQUIRED BY THE AUTHORITY HAVING

JURISDICTION (AHJ).

2. CONTRACTOR TO CONNECT NEW DEVICES TO THE

EXISTING FIRE ALARM SYSTEM AS SHOWN ON THE

DRAWINGS AND REQUIRED BY THE PROJECT

SPECIFICATIONS. THE EXISTING FIRE ALARM SYSTEM IS

AN EDWARDS SYSTEM TECHNOLOGY FIRE ALARM

CONTROL PANEL LOCATED IN BUILDING 12 AS SHOWN ON

THE DESIGN DRAWINGS. CANDELA SETTINGS ARE SHOWN

FOR ILLUSTRATIVE PURPOSES ONLY; FINAL CHIME AND

CANDELA SETTINGS ARE THE RESPONSIBILITY OF THE

CONTRACTOR.

3. CONTRACTOR TO REMOVE, RELOCATE AND/OR REPLACE

DEVICES IN NORTH AND WEST WINGS AS NEEDED AS PART

OF TENANT IMPROVEMENT. CONTRACTOR RESPONSIBLE

FOR VERIFYING LOCATION AND TYPE OF DEVICES. ANY

NEW DEVICES SHALL BE THE SAME AS THE ORIGINAL.

REFER TO ARCHITECTURAL DRAWING GI002 FOR

CONSTRUCTION STEPS.

4. ALL MATERIALS AND DEVICES USED IN THIS PROJECT

SHALL BE UL LISTED AND/OR FM APPROVED FOR USE IN

FIRE ALARM SYSTEMS.

5. ALL ALARM CONDUIT AND WIRING PENETRATIONS

THROUGH FIRE RATED ASSEMBLIES SHALL BE SEALED

WITH A UL APPROVED THROUGH PENETRATION FIRE STOP

ASSEMBLY.

P

XX

C

XX

C

TS

FS

MANUAL PULL STATION

PHOTOELECTRIC SMOKE DETECTOR

DUCT SMOKE DETECTOR WITH REMOTE TEST

STATION

MONITOR MODULE - TAMPER SWITCH

MONITOR MODULE - FLOW SWITCH

CHIME/STROBE, CEILING MOUNT

XX=CANDELA

STROBE, CEILING MOUNT

XX=CANDELA

FIRE ALARM SYSTEM NOTES:SYMBOL LEGEND:

DH MAGNETIC DOOR HOLDER

FACP FIRE ALARM CONTROL PANEL

C CONTROL RELAY

XX CHIME/STROBE, WALL MOUNT

XX=CANDELA

(E) EXISTING

1. LOCATION OF SMOKE DAMPER REMOTE TEST

SWITCHES

2. LOCATION OF SMOKE DAMPERS AND DUCT

DETECTORS

KEY NOTES:

1. BUILDING 12 FIRE ALARM ZONE D IS FOR

THE PENTHOUSE. THERE IS NO FIRE

DETECTION AND ALARM SYSTEM WORK IN

THIS AREA.

SHEET NOTES:

1 HOUR FIRE RESISTIVE RATED

BARRIER

XX

WP

CHIME/STROBE, WALL MOUNT

XX=CANDELA

WP = WEATHERPROOF

NOT IN CONTRACT

LIMITED WORK TO UTILITIES FOR SUPPORT AND

CONNECTIONS (ALONG WITH SUSPENDED CEILING

REMOVAL AND REPLACEMENT IN NORTH WING

LOCATIONS). LIMITED WORK ON EXTERIOR WALLS

AND DOORS TO PROVIDE TWO EGRESS DOORS AT

EAST WING.

LIMITED WORK TO INCLUDE GYPSUM BOARD CEILING

AND FIXTURE REMOVAL, NEW SUSPENDED

ACOUSTIC TILE CEILING AND NEW FIXTURES.

SMOKE BARRIERSBSB

Randy Stamp

BUILDING

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD SEALCONSULTANT

321 4 5 6 7 8 9 10

DWG. OF

NAME:

FULLY SPRINKLERED

CONTRACTING OFFICER

FULL SIZE DWG: 30x42

PHONE:

EMAIL:11031 S. PIKES PEAK DRIVE #202 PARKER, COLORADO 80138 PH. 303.841-3922

668-318

DAVID ARMENT

504-964-1889 David.Arment@va.govREVISIONS DATE

CONTRACTING OFFICER'S REPRESENTATIVE

100% SUBMITTAL

CONSTRUCTION

DOCUMENTS (CD)

RENOVATE AND EXPAND

COMMUNITY LIVING

CENTER (CLC)

SPOKANE, WA

ARCHITECT/ENGINEER OF RECORD

11031 S. PIKES PEAK DRIVE #202 PARKER, COLORADO 80138 PH. 303.841-3922

Group, Inc.

RDL RDL

FA501

FIRE ALARM SYSTEM DETAILS

APRIL 2023

18387

3 APRIL 2023

System Outputs

Actu ate

Sup erv iso ry

Alar m Visu al Ind ica tor

Actu ate

Trou ble

Alar m Visu al Ind ica tor

Actu ate

Trou ble

Alar m Aud ibl e S ou nd er

Actu ate

G en era l A lar m Aud ibl e S ou nd er

Actu ate

G en era l A lar m Visu al Ind ica tor

Actu ate

Sup erv iso ry

Alar m Aud ibl e S ou nd er

System Inputs

X X

X

X

X

X

X

XX

X

X

X

X

X

XX

X

XX

Sprinkler Flow

Tamper Switch

Open Circuit

Ground Fault

All Manual Pull Stations

Low Battery

AC Power Failure

Notification Appliance Short Circuit

Actu ate

Exte rio r A ud ibl e/V isu al

Ind ica tor

Tran sm it G en era l F ire Alar m Sign al

To S up erv iso ry Stat ion

Shu t D ow n A ir H an dli ng

U nit

Actu ate al l In ter ior

C him e/S tro be s

X X X X

X X X

X

Tran sm it S up erv iso ry Sign al To S up erv isin g S tat ion

Tran sm it T rou ble Sign al To S up erv isin g S tat ion

Duct Smoke Detector X X XX

Rele as e M ag ne tic

D oo r H old ers

X

X

XCorridor Smoke Detectors X XXX

Rele as e D oo r L oc ks

X

X

X

CONNECT TO EXISTING EDWARDS

SYSTEM TECHNOLOGY PANEL IN

BUILDING 12.

P

ZONE 12E

NAC

DH

ESTIMATED QUANTITIES ARE SHOW ON FLOOR PLAN;

CONTRACTOR RESPONSIBLE FOR CODE COMPLIANT DESIGN

C

C

1 HOUR FIRE RESISTIVE RATED

BARRIER

1. THE FIRE ALARM SYSTEM DESIGN, ENGINEERING AND

INSTALLATION AS INDICATED ON THIS PLAN SHALL

COMPLY WITH NFPA 72 (2019 EDITION), NFPA 101 (2018

EDITION), VA FIRE PROTECTION DESIGN MANUAL (EIGHTH

EDITION) AND OTHER APPLICABLE CODES AND

STANDARDS AS REQUIRED BY THE AUTHORITY HAVING

JURISDICTION (AHJ).

2. CONTRACTOR TO CONNECT NEW DEVICES TO THE

EXISTING FIRE ALARM SYSTEM AS SHOWN ON THE

DRAWINGS AND REQUIRED BY THE PROJECT

SPECIFICATIONS. THE EXISTING FIRE ALARM SYSTEM IS

AN EDWARDS SYSTEM TECHNOLOGY FIRE ALARM

CONTROL PANEL LOCATED IN BUILDING 12 AS SHOWN ON

THE DESIGN DRAWINGS. CANDELA SETTINGS ARE SHOWN

FOR ILLUSTRATIVE PURPOSES ONLY; FINAL CHIME AND

CANDELA SETTINGS ARE THE RESPONSIBILITY OF THE

CONTRACTOR.

4. CONTRACTOR TO REMOVE, RELOCATE AND/OR REPLACE

DEVICES IN NORTH AND WEST WINGS AS NEEDED AS PART

OF TENANT IMPROVEMENT. CONTRACTOR RESPONSIBLE

FOR VERIFYING LOCATION AND TYPE OF DEVICES. ANY

NEW DEVICES SHALL BE THE SAME AS THE ORIGINAL.

REFER TO ARCHITECTURAL DRAWING GI002 FOR

CONSTRUCTION STEPS.

5. ALL MATERIALS AND DEVICES USED IN THIS PROJECT

SHALL BE UL LISTED AND/OR FM APPROVED FOR USE IN

FIRE ALARM SYSTEMS.

6. ALL ALARM CONDUIT AND WIRING PENETRATIONS

THROUGH FIRE RATED ASSEMBLIES SHALL BE SEALED

WITH A UL APPROVED THROUGH PENETRATION FIRE STOP

ASSEMBLY.

P

XX

C

XX

C

TS

FS

MANUAL PULL STATION

PHOTOELECTRIC SMOKE DETECTOR

DUCT SMOKE DETECTOR WITH REMOTE TEST

STATION

MONITOR MODULE - TAMPER SWITCH

MONITOR MODULE - FLOW SWITCH

CHIME/STROBE, CEILING MOUNT

XX=CANDELA

STROBE, CEILING MOUNT

XX=CANDELA

FIRE ALARM SYSTEM NOTES:SYMBOL LEGEND:

DH MAGNETIC DOOR HOLDER

FACP FIRE ALARM CONTROL PANEL

C CONTROL RELAY

XX CHIME/STROBE, WALL MOUNT

XX=CANDELA

(E) EXISTING

1. BUILDING 12 FIRE ALARM ZONE D IS FOR

THE PENTHOUSE. THERE IS NO FIRE

DETECTION AND ALARM SYSTEM WORK IN

THIS AREA.

SHEET NOTES:

XX

WP

CHIME/STROBE, WALL MOUNT

XX=CANDELA

WP = WEATHERPROOF

XX

WP

AutoCAD SHX Text

OPERATIONAL MATRIX:

AutoCAD SHX Text

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD SEALCONSULTANT

321 4 5 6 7 8 9 10

DWG. OF

NAME:

FULLY SPRINKLERED

CONTRACTING OFFICER

FULL SIZE DWG: 30x42

PHONE:

EMAIL:11031 S. PIKES PEAK DRIVE #202 PARKER, COLORADO 80138 PH. 303.841-3922

668-318

DAVID ARMENT

504-964-1889 David.Arment@va.govREVISIONS DATE

CONTRACTING OFFICER'S REPRESENTATIVE

100% SUBMITTAL

CONSTRUCTION

DOCUMENTS (CD)

RENOVATE AND EXPAND

COMMUNITY LIVING

CENTER (CLC)

SPOKANE, WA

ARCHITECT/ENGINEER OF RECORD

11031 S. PIKES PEAK DRIVE #202 PARKER, COLORADO 80138 PH. 303.841-3922

Group, Inc.

RDL RDL

FX501

FIRE SPRINKLER SYSTEM DETAILS

18389

3 APRIL 2023 APRIL 2023

SHEET NOTES:

SPRINKLER SYSTEM DESIGN DATA

SYSTEM TYPESPACE OCCUPANCY TYPE DESIGN AREADESIGN DENSITY HOSE STREAM

(GPM/SF) (SF)

WET

ALL AREAS

NOTES: 1. SEMI-RECESSED PENDENT OR SEMI-RECESSED SIDEWALL HEADS TO BE USED UNDER ALL SUSPENDED CEILINGS.

LIGHT HAZARD 0.10 2501,500

SPRINKLER TYPE

QUICK RESPONSE, K-5.6 OR 8.0

QUICK RESPONSE, K-5.6 OR 8.0

ORDINARY TEMPERATURE

155F OR 200F

(NOTE 1)

WET ORDINARY HAZARD GROUP 1 0.15 2501,500MECHANICAL

ELECTRICAL

UNLESS OTHERWISE NOTED

(GPM)

DATE OF TEST: SEPTEMBER 8, 2021

TIME OF TEST: 9:12 AM

FLOW HYDRANT: HYDRANT #2495

PRESSURE HYDRANT: HYDRANT #2492

STATIC PRESSURE: 74 PSI

RESIDUAL PRESSURE: 63 PSI

PITOT PRESSURE: 35 PSI (DIFFUSER) & 48 (PITOT)

2-1/2" HYDT BUTT

FLOW COEFFICIENT 0.90

WATERFLOW: 2,158 GALLONS PER MINUTE

*ABOVE HYDRANT TEST IS VALID 1 YEAR FROM TIME

OF TEST. CONTRACTOR TO PROVIDE UPDATED WATER TEST

INFORMATION AS PART OF SHOP DRAWING SUBMITTAL.

WATER SUPPLY TEST:SPRINKLER RISER SCHEMATIC

BLACK STEEL PIPE

FLEXIBLE

COUPLING

TO ZONE 1 NORTH

TO

D

R

AI

N

TO ZONE E SOUTH

TO ZONE 2 WEST AND ZONE 3 EAST

GR. X GR. BUTTERFLY VA.

W/ TAMPER SWITCH (TYP.)

PRESSURE GAUGE (TYP.)

FLOW SWITCH (TYP.)

CHECK VALVE (TYP.)

TEST AND DRAIN WITH

RELIEF VALVE (TYP.)

(T

YP

HATCHED AREAS - ORDINARY

HAZARD GROUP 1 AUTOMATIC

SPRINKLER DESIGN 155° F OR 200° F

QUICK RESPONSE, k-5.6 OR k-8.0

SPRINKLERS.

NON HATCHED AREAS - LIGHT

HAZARD AUTOMATIC SPRINKLER

DESIGN 155° F QUICK RESPONSE,

k-5.6 OR k-8.0 SPRINKLERS.

WET-PIPE AUTOMATIC SPRINKLER SYSTEM RISER

SYMBOL LEGEND:

1 HOUR FIRE RESISTIVE RATED

BARRIER

AUTOMATIC SPRINKLER SYSTEM NEW MAIN PIPING

AUTOMATIC SPRINKLER SYSTEM EXISTING PIPING

INSPECTOR'S TEST CONNECTIONT

EXISTING(E)

NEW(N)

HATCHED AREAS - ORDINARY

HAZARD GROUP 2 AUTOMATIC

SPRINKLER DESIGN 155° F QUICK

RESPONSE, k-5.6 OR k-8.0 HEADS.

QUICK RESPONSE, K-5.6 OR 8.0

155F OR 200F

WET ORDINARY HAZARD GROUP 2 0.20 2501,500STORAGE

AREAS

1. AUTOMATIC FIRE SPRINKLER SYSTEM DESIGN,

ENGINEERING AND INSTALLATION AS INDICATED ON THIS

PLAN SHALL COMPLY WITH NFPA 13 (2019 EDITION),

NFPA 101 (2018 EDITION), VA FIRE PROTECTION DESIGN

MANUAL (EIGHTH EDITION) AND OTHER APPLICABLE

CODES AND STANDARDS AS REQUIRED BY THE

AUTHORITY HAVING JURISDICTION (AHJ).

2. BUILDING 12 FIRE ALARM ZONE D IS FOR THE

PENTHOUSE. THERE IS NO AUTOMATIC SPRINKLER

WORK SCHEDULED IN THIS AREA.

3. CONTRACTOR TO PROVIDE WET-PIPE AUTOMATIC

SPRINKLER SYSTEMS FOR THE NEW SOUTH WING AREA

SHOWN ON THESE DESIGN DOCUMENTS. NEW SYSTEM

PIPING SHALL BE CONNECTED AS SHOWN ON THE

DRAWING AT THE EXISTING AUTOMATIC SPRINKLER

SYSTEM RISER.

4. CONTRACTOR TO RELOCATE AND REPLACE AUTOMATIC

SPRINKLERS IN NORTH AND WEST WINGS AS NEEDED AS

PART OF TENANT IMPROVEMENT. SPRINKLERS SHALL

BE THE SAME AS THOSE USED IN THE SOUTH WING.

REFER TO ARCHITECTURAL DRAWING GI002 FOR

CONSTRUCTION STEPS.

5. AUTOMATIC SPRINKLER SYSTEM PIPING SHALL BE

INSTALLED ABOVE THE SUSPENDED CEILING.

AUTOMATIC SPRINKLERS WILL NOT BE INSTALLED

ABOVE THE SUSPENDED CEILING AS ALLOWED BY NFPA

13, 9.2.1.

6. PROVIDE FM GLOBAL APPROVED AUTOMATIC

SPRINKLERS AS INDICATED IN THE TABLE ON THIS

DRAWING. REDUCTION IN DESIGN AREA IS ALLOWED

PER NFPA 13.

7. ALL MATERIALS AND DEVICES USED IN THIS PROJECT

SHALL BE UL-LISTED AND/OR FM-APPROVED FOR USE IN

AUTOMATIC SPRINKLER SYSTEMS.

8. ALL AUTOMATIC SPRINKLER PIPING INSTALLED UNDER

THIS CONTRACT SHALL BE HYDROSTATICALLY TESTED

IN ACCORDANCE WITH NFPA 13 AND OTHER APPLICABLE

NFPA STANDARDS.

9. SPRINKLER PIPE HANGERS SHALL BE UL APPROVED.

THE SPRINKLER INSTALLATION CONTRACTOR SHALL

PROVIDE PIPE HANGERS AS REQUIRED BY NFPA 13.

10. SEISMIC BRACING SHALL BE PROVIDED FOR ALL

AUTOMATIC SPRINKLER SYSTEMS IN ACCORDANCE WITH

NFPA 13, 2019 EDITION, AND PROJECT SPECIFICATIONS.

A B C D E F

G

H

J

K

L

M

N

MD102

SHEET NOTES:

DEMO MECHANICAL EQUIPMENT UNLESS NOTED

OTHERWISE.

ENSURE BUILDING SYSTEMS REMAIN IN OPERATION IN

OTHER PARTS OF THE BUILDING NOT IN THE

CONSTRUCTION PHASE.

COORDINATE WITH ARCHITECTURAL DRAWINGS FOR

PROJECT SEQUENCING PLAN.

COORDINATE WITH ELECTRICAL AND ARCHITECTURAL

DRAWINGS FOR ADDITIONAL DEMOLITION WORK.

1.

2.

3.

4.

KEY NOTES:

DEMO AND REMOVE ALL EXISTING MECHANICAL HVAC

AND MECHANICAL PIPING EQUIPMENT AND FIXTURES IN

WEST WING.

EXISTING MECHANICAL HVAC EQUIPMENT AND PIPING TO

REMAIN IN NORTH WING AND EAST WING UNLESS NOTED

OTHERWISE, TYP.

1.

2.

LEGEND:

AREA NOT IN SCOPE. IT IS SHOWN FOR INFORMATION

ONLY.

LIMITED MECHANICAL WORK.

TN N

PROJECT NUMBER

BUILDING

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD SEALCONSULTANTS

321 4 5 6 7 8 9 10

DWG. OF

NAME:

FULLY SPRINKLERED

CONTRACTING OFFICER'S REPRESENTATIVE

FULL SIZE DWG: 30x42

PHONE:

EMAIL:11031 S. PIKES PEAK DRIVE #102 PARKER, COLORADO 80138 PH. 303.841-3922

RENOVATE AND EXPAND

COMMUNITY LIVING

CENTER (CLC)

SPOKANE, WA

668-318

100% SUBMITTAL

CONSTRUCTION

DOCUMENTS (CD)

NORTH

SOUTH

WEST EAST

BLDG. 1

7/ 5/

1:

:1

AM

MD100

MECHANICAL HVAC - DEMO -

OVERALL

APRIL 2023 CDL TJH

91 183

David Arment 509-964-1889 David.Arment@va.gov

SCALE: 1/16" = 1'-0"

MECHANICAL HVAC - DEMO - OVERALL1

32'8'

SCALE:1/16"=1'-0"

0 16'

REVISIONS DATE 5 JULY 2023

SHEET NOTES:

DEMO MECHANICAL EQUIPMENT UNLESS NOTED

OTHERWISE.

ENSURE BUILDING SYSTEMS REMAIN IN OPERATION IN

OTHER PARTS OF THE BUILDING NOT IN THE

CONSTRUCTION PHASE.

1.

2.

KEY NOTES:

DEMO AND REMOVE EXISTING DIFFUSERS, REGISTERS

AND GRILLES, TYP.

1.

LEGEND:

AREA NOT IN SCOPE. IT IS SHOWN FOR INFORMATION

ONLY.

LIMITED MECHANICAL WORK.

1011121314

G

(D)CD

(D)RG(D)RG (D)EG

(D)CD

(D)CD

(D)RG

(D)CD

(D)RG(D)RG

(D)RG

(D)EG

(D)EG

(D)CD

(D)RG

(D)CD

(D)EG

(D)CD

(D)EG

(D)RG

(D)RG

(D)CD

(D)RG

(D)CD

(D)CD

(D)EG

(D)CD

(D)CD

(D)EG

(D)RG (D)CD

(D)RG (D)CD

(D)CD

(D)RG

(D)CD

(D)RG

(D)CD

(D)RG

(D)EG

TNN

PROJECT NUMBER

BUILDING

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD SEALCONSULTANTS

321 4 5 6 7 8 9 10

DWG. OF

NAME:

FULLY SPRINKLERED

CONTRACTING OFFICER'S REPRESENTATIVE

FULL SIZE DWG: 30x42

PHONE:

EMAIL:11031 S. PIKES PEAK DRIVE #102 PARKER, COLORADO 80138 PH. 303.841-3922

RENOVATE AND EXPAND

COMMUNITY LIVING

CENTER (CLC)

SPOKANE, WA

668-318

100% SUBMITTAL

CONSTRUCTION

DOCUMENTS (CD)

NORTH

SOUTH

WEST EAST

BLDG. 1

7/ 5/

1:

:1

AM

MD102

MECHANICAL HVAC - DEMO - WEST

WING

APRIL 2023 CDL TJH

92 183

David Arment 509-964-1889 David.Arment@va.gov

8'0 4' 16'

SCALE:1/8"=1'-0"

SCALE: 1/8" = 1'-0"

MECHANICAL HVAC - DEMO - WEST (HOSPICE)

WING1

A B C D E F

G

H

J

K

L

M

N

MD113

MD112

1 1/4"ø HWR 1 1/4"ø HWS

SHEET NOTES:

DEMO MECHANICAL EQUIPMENT UNLESS OTHERWISE

NOTED.

ENSURE BUILDING SYSTEMS REMAIN IN OPERATION IN

OTHER PARTS OF THE BUILDING NOT IN THE

CONSTRUCTION PHASE.

PROVIDE NEW SHUT-OFF VALVES, CAP AND SEAL LEGACY

LINES.

AREA NOT IN SCOPE. IT IS SHOWN FOR INFORMATION

ONLY.

LIMITED MECHANICAL WORK.

1.

2.

3.

LEGEND:

TN N

PROJECT NUMBER

BUILDING

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD SEALCONSULTANTS

321 4 5 6 7 8 9 10

DWG. OF

NAME:

FULLY SPRINKLERED

CONTRACTING OFFICER'S REPRESENTATIVE

FULL SIZE DWG: 30x42

PHONE:

EMAIL:11031 S. PIKES PEAK DRIVE #102 PARKER, COLORADO 80138 PH. 303.841-3922

RENOVATE AND EXPAND

COMMUNITY LIVING

CENTER (CLC)

SPOKANE, WA

668-318

100% SUBMITTAL

CONSTRUCTION

DOCUMENTS (CD)

NORTH

SOUTH

WEST EAST

BLDG. 1

7/ 5/

1:

:0

AM

MD110

MECHANICAL PIPING - DEMO -

OVERALL

APRIL 2023 CDL TJH

93 183

David Arment 509-964-1889 David.Arment@va.gov

SCALE: 1/16" = 1'-0"

MECHANICAL PIPING - DEMO - OVERALL1

32'8'

SCALE:1/16"=1'-0"

0 16'

OTHERWISE.

FOLLOW PHASING PLAN BUT ENSURE BUILDING SYSTEMS

REMAIN IN OPERATION IN OTHER PARTS OF THE BUILDING

NOT IN THE CONSTRUCTION PHASE.

PROVIDE NEW SHUT-OFF VALVES, CAP AND SEAL LEGACY

LINES.

1.

2.

3.

KEY NOTES:

1. DEMOLISH AND REMOVE EXISTING HEATING HOT

WATER FINNED TUBE BASEBOARD HEATER W/

SUPPLY & RETURN PIPING, FITTINGS, CONTROLS,

AND SUPPORTS.

2. DEMOLISH AND COMPLETELY REMOVE ALL HEATING

HOT WATER SUPPLY & RETURN PIPE MAINS W/

ZONE ISOLATION VALVES, BALANCE VALVES,

CONTROLS, FITTINGS, AND SUPPORTS.

3. SEE SHEET MD113 FOR CONTINUATION.

LEGEND:

AREA NOT IN SCOPE. IT IS SHOWN FOR INFORMATION

ONLY.

LIMITED MECHANICAL WORK.

1011121314

G 1 1/4"ø HWR 1 1/4"ø HWS

2 1/2"ø HWS 2 1/2"ø HWR

1"ø HWS

1"ø HWS

2"ø HWR 2"ø HWS

1"ø HWS

TNN

PROJECT NUMBER

BUILDING

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD SEALCONSULTANTS

321 4 5 6 7 8 9 10

DWG. OF

NAME:

FULLY SPRINKLERED

CONTRACTING OFFICER'S REPRESENTATIVE

FULL SIZE DWG: 30x42

PHONE:

EMAIL:11031 S. PIKES PEAK DRIVE #102 PARKER, COLORADO 80138 PH. 303.841-3922

RENOVATE AND EXPAND

COMMUNITY LIVING

CENTER (CLC)

SPOKANE, WA

668-318

100% SUBMITTAL

CONSTRUCTION

DOCUMENTS (CD)

NORTH

SOUTH

WEST EAST

BLDG. 1

4/ 3/

:3

3:

P M

MD112

MECHANICAL PIPING - DEMO - WEST

WING

APRIL 2023 CDL TJH

94 183

David Arment 509-964-1889 David.Arment@va.gov

8'0 4' 16'

SCALE:1/8"=1'-0"

SCALE: 1/8" = 1'-0"

MECHANICAL PIPING - DEMO - WEST (HOSPICE)

WING1

1 1 1 1 1

REVISIONS DATE 3 APRIL 2023

OTHERWISE.

ENSURE BUILDING SYSTEMS REMAIN IN OPERATION IN

OTHER PARTS OF THE BUILDING NOT IN THE

CONSTRUCTION PHASE.

PROVIDE NEW SHUT-OFF VALVES, CAP AND SEAL LEGACY

LINES.

1.

2.

3.

KEY NOTES:

1. SEE SHEET MP403 FOR DEMOLITION WORK IN THIS

AREA.

2. EXISTING ZONE ISOLATION VALVES TO REMAIN, NO

CHANGE.

3. RE-USE EAST WING EXISTING HEATING HOT WATER

FINNED TUBE BASEBOARD HEATERS AND

CONTROLS.

4. DEMOLISH AND REMOVE EXISTING CEILING

MOUNTED CABINET UNIT HEATER, CONTROLS,

FITTINGS, AND SUPPORTS.

5. DEMOLISH AND REMOVE EXISTING FINNED TUBE

BASEBOARD HEATERS W/ SUPPORTS AND

CONTROLS.

6. SEE SHEET MD112 FOR CONTINUATION.

7. SEE SHEET MD111 FOR CONTINUATION.

8. DEMOLISH AND REMOVE EXISTING HEATING HOT

WATER SUPPLY AND RETURN PIPING MAINS AS

SHOWN W/ ZONE ISOLATION VALVES, FLOW

BALANCE VALVES, CONTROLS, FITTINGS, AND

SUPPORTS.

LEGEND:

AREA NOT IN SCOPE. IT IS SHOWN FOR INFORMATION

ONLY.

LIMITED MECHANICAL WORK.

A B C D E F

H

J 2"ø HWR

2"ø HWS

2 1/2"ø HWR 2 1/2"ø HWS

1"ø HWS

1 1/4"ø HWS 1 1/4"ø HWR

1"ø HWR 1"ø HWS

3/4"ø HWR

3/4"ø HWS

2 1/2"ø HWS 2 1/2"ø HWR

TN N

PROJECT NUMBER

BUILDING

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD SEALCONSULTANTS

321 4 5 6 7 8 9 10

DWG. OF

NAME:

FULLY SPRINKLERED

CONTRACTING OFFICER'S REPRESENTATIVE

FULL SIZE DWG: 30x42

PHONE:

EMAIL:11031 S. PIKES PEAK DRIVE #102 PARKER, COLORADO 80138 PH. 303.841-3922

RENOVATE AND EXPAND

COMMUNITY LIVING

CENTER (CLC)

SPOKANE, WA

668-318

100% SUBMITTAL

CONSTRUCTION

DOCUMENTS (CD)

NORTH

SOUTH

WEST EAST

BLDG. 1

7/ 5/

1:

:2

AM

MD113

MECHANICAL PIPING - DEMO - NORTH

WING

APRIL 2023 CDL TJH

95 183

David Arment 509-964-1889 David.Arment@va.gov

8'0 4' 16'

SCALE:1/8"=1'-0"

SCALE: 1/8" = 1'-0"

MECHANICAL PIPING - DEMO - NORTH WING1

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB

SB SB

SB

SB

SB

SB

SB

SHEET NOTES:

PROVIDE A MINIMUM OF THREE TIMES THE FAN DIAMETER

OF A STRAIGHT DUCTWORK OFF THE SUPPLY AIR

DISCHARGES BEFORE ANY TAKE-OFFS OF ELBOWS.

PROVIDE ACCESS DOORS IN DUCTORK.

DUCT DIMENSIONS SHOWN ON DRAWINGS ARE NET FREE

INTERIOR, NOT INCLUDING LINING OR INSULATION.

PROVIDE ACCESS HATCHES IN HARD CEILING FOR ALL

EQUIPMENT AS REQUIRED TO ACCESS FOR

MAINTENANCE SEE ARCHITECTURAL FOR LOCATION AND

SIZE.

AREA NOT IN SCOPE. IT IS SHOWN FOR INFORMATION

ONLY.

LIMITED MECHANICAL WORK.

1.

2.

3.

4.

LEGEND:

TN N

PROJECT NUMBER

BUILDING

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD SEALCONSULTANTS

321 4 5 6 7 8 9 10

DWG. OF

NAME:

FULLY SPRINKLERED

CONTRACTING OFFICER'S REPRESENTATIVE

FULL SIZE DWG: 30x42

PHONE:

EMAIL:11031 S. PIKES PEAK DRIVE #102 PARKER, COLORADO 80138 PH. 303.841-3922

RENOVATE AND EXPAND

COMMUNITY LIVING

CENTER (CLC)

SPOKANE, WA

668-318

100% SUBMITTAL

CONSTRUCTION

DOCUMENTS (CD)

NORTH

SOUTH

WEST EAST

BLDG. 1

4/

/2

2:

:1

PM

MH100

MECHANICAL HVAC - OVERALL

APRIL 2023 CDL TJH

96 183

David Arment 509-964-1889 David.Arment@va.gov

SCALE: 1/16" = 1'-0"

MECHANICAL HVAC - NEW - OVERALL1

32'8'

SCALE:1/16"=1'-0"

0 16'

FCU-W107

FCU-W106

FCU-W108 FCU-W109

FCU-W110

FCU-W105

FCU-W104

FCU-W101

FCU-W118 FCU-W117

FCU-W116 FCU-W114 FCU-W113

W101

W104

W105

W118

W106

W117

W107

W108

W113

W114W116

W109 W110

6"ø

CD-1

6"ø

CD-1

8"x4"

WG-1

6"x6"

EG-1

6"x6"

EG-1

8"x4"

WG-1

6"ø

CD-1

6"ø

RG-1

6"ø

RG-1

6"ø

CD-1

6"ø

CD-1

6"ø

CD-1

6"ø

RG-1

6"ø

CD-1

6"ø

CD-1

6"x6"

EG-1

6"x6"

EG-1

6"ø

CD-1

6"ø

CD-1

6"ø

CD-1

6"ø

CD-1

6"ø

RG-1

8"x4"

WG-1

6"x6"

EG-1

6"x6"

EG-1

8"x4"

WG-1

6"ø

CD-1

6"ø

CD-1

6"ø

RG-1

6"x6"

EG-1

6"x6"

EG-1

6"ø

CD-1

6"ø

RG-1

6"ø

CD-1

6"ø

CD-1

6"ø

RG-1

6"x6"

EG-1

8"x4"

WG-1

6"ø

RG-1

8"x4"

WG-1

6"ø

CD-1

6"ø

CD-1

6"ø

CD-1

6"ø

CD-1

70 6"x6"

EG-1

6"ø

CD-1

6"ø

CD-1

6"x6"

EG-1

6"ø

CD-1

70 6"ø

CD-1

6"ø

RG-1

70 6"ø

RG-1

6"x6"

EG-1

115 6"ø

CD-1

6"ø

CD-1

6"ø

RG-1

6"x6"

EG-1

8"x4"

WG-1

8"x4"

WG-1

W102

W103

W115

W001

W002

W105A

W104A

W101A

W107A

W106A W109A

W110A

W118A

W117A W116A

W114A W113A x EA16"16"

12"ø OA x EA8"16" x EA18"18" x

EA

8" x

EA

8" x

EA

8" 8" x

EA

8"

8"ø

SD-1

125 8"x4"

WG-1

6"ø

CD-1

8"x4"

WG-1

8"x4"

WG-1

8"x4"

WG-1

x

EA

8" x

EA

8"

8" x O

A

8"ø

SD-1

6"ø

RG-1

8"ø

SD-1

1808"ø

SD-1

x

EA

8"

"6"ø

RG-1

6"ø OA

10"ø OA12"ø OA12"ø OA12"ø OA

6"ø OA

6" ø

O A x EA8"8"

6"ø OA

6" ø

O A

6"ø OA

"ø

O A

"ø

O A

10"ø OA 8"ø OA

8" ø

O A

8" ø

O A

8" ø

O A x EA8"10"

FCU-W115

6"ø

RG-1

6"ø

CD-1

12-EF-1W

12-EF-1W12-EF-1W12-EF-1W

W112

SHEET NOTES:

PROVIDE A MINIMUM OF THREE TIMES THE FAN DIAMETER

OF A STRAIGHT DUCTWORK OFF THE SUPPLY AIR

DISCHARGES BEFORE ANY TAKE-OFFS OF ELBOWS.

PROVIDE ACCESS DOORS IN DUCTORK.

DUCT DIMENSIONS SHOWN ON DRAWINGS ARE NET FREE

INTERIOR, NOT INCLUDING LINING OR INSULATION.

PROVIDE ACCESS HATCHES IN HARD CEILING FOR ALL

EQUIPMENT AS REQUIRED TO ACCESS FOR

MAINTENANCE SEE ARCHITECTURAL FOR LOCATION AND

SIZE.

1.

2.

3.

4.

KEY NOTES:

18"X18" EA UP TO 12-EF-W1 ON ROOF. SEE MECHANICAL

SCHEDULES FOR CONTINUATION.

PROVIDE RESTROOM EXHAUST GRILLE, TIE TO EXHAUST

DUCTWORK AND EXHAUST FAN 12-EF-W1 SERVING WING,

TYP.

PROVIDE FOUR-PIPE FAN COIL UNIT. SEE MECHANICAL

SCHEDULES FOR CONTINUDATION, TYP.

PROVIDE CEILING SUPPLY AIR DIFFUSER SERVED BY FAN

COIL UNIT, TYP.

PROVIDE CEILING RETURN AIR GRILLE NEAR DOOR

SERVING FAN COIL UNIT, TYP.

PROVIDE CEILING OUTSIDE AIR SUPPLY DIFFUSER NEAR

WINDOW, TYP.

PROVIDE WALL RECESSED EXHAUST AIR GRILLE MIN. 7"

ABOVE FINISHED FLOOR, LOCATED NEAR HEAD OF

PATIENT BED, TYP.

PHASE-3: OUTSIDE AIR DUCTWORK TIE-IN LOCATION TO

SERVE NORTH WING RESIDENT BEDROOM OUTSIDE AIR

DIFFUSERS.

PROVIDE ACCESS PANEL IN COORIDOR HARD-LID CEILING

FOR TERMINAL UNIT MAINTENANCE.

AREA NOT IN SCOPE. IT IS SHOWN FOR INFORMATION

ONLY.

LIMITED MECHANICAL WORK.

1.

2.

3.

4.

5.

6.

7.

8.

9.

LEGEND:

TNN

PROJECT NUMBER

BUILDING

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD SEALCONSULTANTS

321 4 5 6 7 8 9 10

DWG. OF

NAME:

FULLY SPRINKLERED

CONTRACTING OFFICER'S REPRESENTATIVE

FULL SIZE DWG: 30x42

PHONE:

EMAIL:11031 S. PIKES PEAK DRIVE #102 PARKER, COLORADO 80138 PH. 303.841-3922

RENOVATE AND EXPAND

COMMUNITY LIVING

CENTER (CLC)

SPOKANE, WA

668-318

100% SUBMITTAL

CONSTRUCTION

DOCUMENTS (CD)

NORTH

SOUTH

WEST EAST

BLDG. 1

4/ 3/

:3

3:

P M

MH102

MECHANICAL HVAC - WEST WING

APRIL 2023 CDL TJH

97 183

David Arment 509-964-1889 David.Arment@va.gov

SCALE: 1/8" = 1'-0"

MECHANICAL HVAC - WEST (HOSPICE) WING1

8'0 4' 16'

SCALE:1/8"=1'-0"

FCU-S122

FCU-S120

FCU-S119FCU-S118

FCU-S117

FCU-S111

FCU-S110 FCU-S109 FCU-S108 FCU-S107 FCU-S106 FCU-S105

FCU-S101

FCU-S104

FCU-S121

FCU-S116

S122

S101

S121

S104S105

S120

S106

S119

S107S108 S109S110

S117 S116

S111

S118

6"x6"

EG-1

8"x4"

WG-1

50 6"x6"

EG-1

6"ø

CD-1

8"x4"

WG-1

8"x8"

EG-1

6"x6"

EG-1

8"x4"

WG-1

8"x4"

WG-1

6"x6"

EG-1

6"ø

CD-1

6"ø

CD-1

6"ø

CD-1

6"ø

CD-1

8"x4"

WG-1

6"x6"

EG-1

8"x4"

WG-1

6"x6"

EG-1

6"ø

CD-1

6"ø

CD-1

6"ø

RG-1

6"ø

RG-1

6"x6"

EG-1

8"x4"

WG-1

8"x4"

WG-1

6"x6"

EG-1

6"ø

CD-1

6"ø

CD-1

6"ø

CD-1

6"ø

CD-1

6"x6"

EG-1

8"x4"

WG-1

6"ø

CD-1

6"x6"

EG-1

6"ø

CD-1

6"ø

RG-1

6"ø

RG-1

6"ø

CD-1

6"ø

CD-1

6"x6"

EG-1

8"x4"

WG-1

6"x6"

EG-1

6"ø

CD-1

6"ø

CD-1

8"x4"

WG-1

8"ø

CD-1

8"ø

RG-1

6"ø

RG-1

6"x6"

EG-1

6"ø

CD-1

6"ø

CD-1

8"x4"

WG-1

6"x6"

EG-1

6"ø

RG-1

6"ø

RG-1

6"ø

CD-1

6"ø

RG-1

6"ø

CD-1

756"ø

CD-1

6"ø

CD-1

6"ø

RG-1

6"ø

RG-1

6"ø

RG-1

6"ø

CD-1

6"ø

CD-1

6"ø

CD-1

6"ø

CD-1

8"x4"

WG-1

6"x6"

EG-1

6"ø

CD-1

6"ø

CD-1

8"x4"

WG-1

6"x6"

EG-1

6"ø

RG-1

70 6"ø

RG-1

6"ø

RG-1

6"ø

RG-1

S112

S113

S004

S005

S115

S114

S108AS109A S106AS107A

S110A

S111A

S104AS105A

S103

S101A

S102

S121A

S122A

S120AS119AS118AS117A

S001

S002 x

OA

12"

30" x

OA

x

OA

16"

40"

12-LV-1

12-DOAS-1

6"ø

SD-1

6"ø

RG-1

75 6"ø

CD-1

FCU-S113

8"ø

SD-1

8"ø

SD-1

6"ø

CD-1

8"ø

CD-1

8"ø

SD-1

x

EA

x

EA

8"

10" x EA20"20"x EA16"20" x

EA

8"

8"ø

SD-1

x

OA

x

EA

8" x EA8"16" x EA16"16" x

EA

8"

" x

EA

8" x

EA

8"

" x

EA

8"

8"ø

SD-1

8"ø

SD-1

x

EA

8" 8" x

EA

8"

10"

6"ø

OA

8"ø

OA

10"ø OA12"ø OA14"ø OA

"ø

OA

12"ø OA

6"ø

OA

8"ø OA10"ø OA12"ø OA

12"ø OA

"ø

OA

6"ø

OA

x OA16"24" x

OA

SHEET NOTES:

PROVIDE A MINIMUM OF THREE TIMES THE FAN DIAMETER

OF A STRAIGHT DUCTWORK OFF THE SUPPLY AIR

DISCHARGES BEFORE ANY TAKE-OFFS OF ELBOWS.

PROVIDE ACCESS DOORS IN DUCTWORK.

DUCT DIMENSIONS SHOWN ON DRAWINGS ARE NET FREE

INTERIOR, NOT INCLUDING LINING OR INSULATION.

PROVIDE ACCESS HATCHES IN HARD CEILING FOR ALL

EQUIPMENT AS REQUIRED TO ACCESS FOR

MAINTENANCE SEE ARCHITECTURAL FOR LOCATION AND

SIZE.

ORIENT FCUS TO ALLOW SERVICE ACCESS FROM THE

CORRIDOR.

1.

2.

3.

4.

5.

KEY NOTES:

20"x20" EA UP TO 12-EF-S1 ON ROOF. SEE MECHANICAL

SCHEDULES FOR CONTINUATION.

PROVIDE RESTROOM EXHAUST GRILLE, TIE TO EXHAUST

DUCTWORK AND EXHAUST FAN 12-EF-S1 SERVING WING,

TYP.

PROVIDE 1-TON FOUR-PIPE FAN COIL UNIT. SEE

MECHANICAL SCHEDULES FOR CONTINUDATION, TYP.

PROVIDE CEILING SUPPLY AIR DIFFUSER SERVED BY FAN

COIL UNIT, TYP.

PROVIDE CEILING RETURN AIR GRILLE NEAR DOOR

SERVING FAN COIL UNIT, TYP.

PROVIDE CEILING OUTSIDE AIR SUPPLY DIFFUSER NEAR

WINDOW, TYP.

PROVIDE WALL RECESSED EXHAUST AIR GRILLE MIN. 7"

ABOVE FINISHED FLOOR, LOCATED NEAR HEAD OF

PATIENT BED, TYP.

STORE ANTE ROOM DOORS AT LOCATION INDICATED.

PROVIDE SIGNAGE, CAGE AND CAGE LOCKING DEVICE AS

REQUIRED BY THE COR.

PROVIDE DEDICATED OUTDOOR AIR SYSTEM AIR

HANDLER 12-DOAS-1 AT LOCATION INDICATED. SEE

MECHANICAL SCHEDULES FOR CONTINUATION.

PROVIDE OUTDOOR AIR INTAKE LOUVER 12-LV-1 AT

LOCATION INDICATED. SEE ARCHITECTURAL AE201 DEATIL

4 FOR EXTERIOR LOCATION, AND MECHANICAL

SCHEDULES FOR CONTINUATION.

INSTALL FLEXIBLE COUPLINGS AND SEISMIC BRACING

FOR OUTSIDE AIR DUCTWORK AT LOCATION INDICATED.

ROUTE DUCTWORK OVER JOINT AND THROUGH EXTERIOR

CHASE. SEE ARCHITECTURE AND MECHANICAL DETAILS

FOR CONTINUATION.

PROVIDE 2'X2' CEILING ACCESS PANEL TO SERVICE

MECHANICAL EQUIPMENT AT LOCATION INDICATED.

AREA NOT IN SCOPE. IT IS SHOWN FOR INFORMATION

ONLY.

LIMITED MECHANICAL WORK.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

LEGEND:

TN N

PROJECT NUMBER

BUILDING

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD SEALCONSULTANTS

321 4 5 6 7 8 9 10

DWG. OF

NAME:

FULLY SPRINKLERED

CONTRACTING OFFICER'S REPRESENTATIVE

FULL SIZE DWG: 30x42

PHONE:

EMAIL:11031 S. PIKES PEAK DRIVE #102 PARKER, COLORADO 80138 PH. 303.841-3922

RENOVATE AND EXPAND

COMMUNITY LIVING

CENTER (CLC)

SPOKANE, WA

668-318

100% SUBMITTAL

CONSTRUCTION

DOCUMENTS (CD)

NORTH

SOUTH

WEST EAST

BLDG. 1

4/ 3/

:3

4:

P M

MH105

MECHANICAL HVAC- SOUTH WING

APRIL 2023 CDL TJH

98 183

David Arment 509-964-1889 David.Arment@va.gov

SCALE: 1/8" = 1'-0"

MECHANICAL HVAC - SOUTH WING1

8'0 4' 16'

SCALE:1/8"=1'-0"

SECTION "A-A"

NOTES:

LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS

TIGHTLY.

HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE

PINS.

SEE SMACNA 2005, FIGURE 9-15

ACCESS PANEL

ACCESS DOOR

CASING GASKET HANDLE

INSIDE

FLEXIBLE

WASHER

FACTORY

FABRICATED

LATCHSECTION "B-B"

INSULATION

DUCT

GASKET

INSULATION

INSULATION

1.

2.

3.

"B" "B"

"A"

"A"

UNIT TYPE A B

DRAW THRU 2" [50mm]

PLUS X X

BLOW THRU 1" [25mm]

MINIMUM 2X

WHERE X = STATIC PRESSURE IN PAN

NOTES:

CPVC PIPE MAY BE USED ONLY IF APPROVED BY LOCAL VA AND IS

INDOORS AND DOES NOT PASS THROUGH RATED BARRIERS.

DIELECTRIC FITTING TO BE USED WHEN TWO DISSIMILAR METALS

ARE TO BE CONNECTED.

DRAIN LINE SHALL BE AT LEAST THE SAME

SIZE AS THE NIPPLE ON THE DRAIN PAN

PIPING SHALL BE RIGID COPPER TYPE L OR

TYPE M UNLESS NOTE BELOW IS MET

PITCH DOWN

TOWARD DRAIN

CLEAN OUT

FLOOR SINK

1"

B A

DIELECTRIC

FITTING

DRAIN

PAN

1.

2.

TYPICAL ANCHOR BOLT

NUT & WASHER

TYPICAL ANCHOR BOLT

NUT & WASHER

PROVIDE #3 BARS 12" O.C. EACH

WAY IN THE BASE & DOWEL

BASE TO FLOOR

ANCHOR BOLT (TYP)

PIPE SLEEVE

(5D, 3" MIN.)

CONCRETE BASE WELD HEAD TO PLATE

OR BEND OVER END 5D

FLOOR

PLAN SECTION B-B

SECTION A-A (BASE POURED WITH FLOOR SLAB)

SECTION A-A (BASE NOT POURED WITH SLAB)

EQUIPMENT BASE PLATE

EQUIPMENT BASE PLATE

A

A

B B

PROVIDE DOUBLE SLAB

REINFORCING IN BASE AREA

NOTES:

1. L & W DIMENSIONS SHALL BE 6"

GREATER THAN THE EQUIPMENT BASE

PLATE.

L

W

CONCRETE BASE

5D

D

5D

2D

1" M

IN

16" MIN

5" M

IN

L/

5" M

IN

L/

CROSS BRACING

RODS ALL FOUR

SIDES

HANGER ROD

(TYP)

LOCK NUTS (TYP)

CLAMP

EQUIPMENT WEIGHT 250

LBS. OR LESS

RESILIENT PAD

FLOOR

BONDED STEEL

PLATE

NEOPRENE

WASHER &

SLEEVE

ANCHOR BOLT

EQUIPMENT

BASE

FLOOR MOUNT EQUIPMENT

RESTRAINED BY RESILIENT PADS

(TYPE DS)

SEISMIC BRACING FOR LIGHT

SUSPENDED EQUIPMENT

NOTES:

1. SEISMIC RESTRAINT

FOR PIPING SHALL BE

SUBMITTED IN

ACCORDANCE WITH

SPECIFICATION

SECTION 13 05 41.

TYPICAL STRUCTURAL

STEEL MEMBER FOR

EQUIPMENT

DRIVEN

EQUIPMENT

MOTOR

SHAFT

NUMBER OF

ISOLATION UNITS

AS REQUIRED

ANCHOR BOLT

SLEEVE

REINFORCING BARS

TYPICAL STRUCTURAL

STEEL MEMBER FOR

EQUIPMENT

NUMBER OF ISOLATION

UNITS AS REQUIRED

TYPE "1" CONCRETE INERTIA BASE

DRIVEN

EQUIPMENT

MOTOR

SHAFT

A

A

SECTION A-A

ALL WELDED STEEL

FRAMEWORK

SPRING ISOLATOR

STRUCTURAL

STEEL FRAME

TYPE "B" WELDED STEEL BASE

ROOF

BLANK

PLATE

DRAIN, 1/2"

WELDED

COUPLING

WELDED

JOINT

SECURE GUY

WIRE TO

ROOF (TYP.)

EXHAUST FAN

F.C.

TRANSITION (AS REQUIRED)

DRIP LIP

GUY WIRE (4 REQUIRED)

1" GALVANIZED STEEL

STRAP SECURED TO

EXHAUST STACK

WELDED STAINLESS STEEL

EXHAUST STACK

SIZE TO MAINTAIN 3500 FPM

OUTLET VELOCITY

SECURE STACK

TO ROOF (TYP.)

AS

R

EQ

U

IR

ED

'-0

" M

IN

15°

EXPANSION LOOP

W H

100-ELI

LOOP NO.

PLAN

1 + 25 FT. APPROXIMATE

MINIMUM

RETURN

SUPPLY

H

W

LONG RADIUS ELBOW

(TYPICAL)

PIPE ALIGNMENT

GUIDES (TYPICAL)

OUTSIDE AIR

DAMPER

OUTSIDE AIR

LOUVER

FLOOR DRAIN (TYP.)

CMU WALL

EXTERIOR

WALL

NOTES:

THE DESIGN AND SUPPORTING DOCUMENTATION FOR THE BLAST RESISTANT

CONCRETE WALL SHALL BE COORDINATED AND APPROVED BY A REGISTERED

PROFESSIONAL STRUCTURAL ENGINEER SPECIALIZING IN BLAST RESISTANT

CONSTRUCTION.

LIMIT AIR VELOCITY TO 800 FPM THRU PLENUM.

ACCESS SECTION (WALK-IN)

24"x24" BOLTED 1/2"

STEEL ACCESS

PANEL

NOTE:1

NOTE 2

1.

2.

4'

-8

PROJECT NUMBER

BUILDING

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD SEALCONSULTANTS

321 4 5 6 7 8 9 10

DWG. OF

NAME:

FULLY SPRINKLERED

CONTRACTING OFFICER'S REPRESENTATIVE

FULL SIZE DWG: 30x42

PHONE:

EMAIL:11031 S. PIKES PEAK DRIVE #102 PARKER, COLORADO 80138 PH. 303.841-3922

RENOVATE AND EXPAND

COMMUNITY LIVING

CENTER (CLC)

SPOKANE, WA

668-318

100% SUBMITTAL

CONSTRUCTION

DOCUMENTS (CD)

4/ 3/

:3

4:

P M

MH501

MECHANICAL DETAILS

APRIL 2023 CDL TJH

106 183

David Arment 509-964-1889 David.Arment@va.gov

SCALE: NTS

ACCESS PANEL AND DOOR DETAIL1

SCALE: NTS

AIR HANDLING UNIT DRAIN TRAP DETAIL4

SCALE: NTS

CONCRETE EQUIPMENT BASES3

SCALE: NTS

SEISMIC BRACING FOR EQUIPMENT5

SCALE: NTS

VIBRATION ISOLATION BASES2

SCALE: NTS

EXHAUST STACK DETAIL6

SCALE: NTS

EXPANSION LOOP DETAIL7

SCALE: NTS

OUTSIDE AIR INTAKE FOR AIR HANDLER UNIT FOR

MISSION CRITICAL FACILITY8

TYPICAL MANUAL AIR VENTTYPICAL CHILLED AND HOT WATER

PIPING DRAIN VALVE CONNECTIONS

TYPICAL WATER PIPING

REDUCER, IF REQUIRED

3/4" BALL VALVE

ADAPTER TO 3/4" HOSE

THREAD-PROVIDE HOSE

CAP NUT

ELEVATION

THREADED PIPING

ELEVATION

WELDED PIPING

NOTES:

DRAIN ALL LOW POINTS AS INDICATED ABOVE.

WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS

AND/OR PLANS LOCATE DRAIN AT BOTTOM OF SCALE POCKET.

1/4" COPPER

TUBING

1/2" [15mm] x 4" NIPPLE

AIR VENT

1/2" BALL

VALVE

CIRCULATING

WATER PIPINg

ELEVATION

NOTES:

VENT ALL HIGH POINTS INDICATED ABOVE.

IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE TO DRAIN.

1.

2.

1.

2.

PIPE HANGERS - PROVIDE DOUBLE

DEFLECTION NEOPRENE (TYPE HN)

FOR FIRST TWO ON EACH SIDE OF

PUMP (SEE NOTE NO. 1)

BALANCING

DEVICE

BALL OR

BUTTERFLY

TYP.

FLEXIBLE

CONNECITON STRAINER

1/2"

PRESSURE GAGE

NOTES:

SUPPORT PUMP FROM PIPING ONLY. DO NOT SUPPORT PUMP FROM

MOTOR.

1.

NOTES:

CONCRETE INERTIA

BASE

1" MIN. DIA. PIPE

STAND

DRAIN

SUCTION DIFFUSER WITH

BUILT IN STRAINER.

OPTIONAL: LONG RADIUS

ELBOW AND INLET

STRAINER WITH 3XDIAM

STRAIGHT INLET TO PUMP

1/2"

PRESSURE GAUGE

OPTIONAL STRAINER

BUTTERFLY OR BALL

SHUT OFF VALVE, TYP.

RIGID PIPE HANGER

FIRST 3 HANGERS FOR EACH PIPE AND

BRANCH SHALL BE SPRING &

NEOPRENE TYPE. TYPE "H" FOR "4"

DIA. PIPE & SMALLER. TYPE "H-P" FOR

5" DIA. PIPE & LARGER.

RIGID PIPE HANGER

INSTALL HANGER AS

CLOSE TO PIPE ELBOW

AS POSSIBLE (TYPICAL)

CHECK VALVE

1/2"

FLEXIBLE CONNECTOR

(TYPICAL)

PUMP

FLOOR

VIBRATIONAL ISOLATOR

(TYPICAL)

SEE SPECIFICATION SECTION "PUMPS" FOR Y STRAINER OPTION1.

FIELD APPLIED INSULATION AFTER

INSERTION OF RESPECTIVE SERVICE

FACILITY THRU REFRIGERATOR OR

FREEZER WALL

S.S. WALL PLATE SECURED

WITH S.S. SCREWS

TUBING, PIPING

OR CONDUIT

MASTIC

EXTERIOR SKIN

PREFAB. WALL PANEL

AS SPECIFIED

GASKET

INTERIOR SKIN

S.S. WALL PLATE

SECURED WITH S.S.

SCREWS

PIPE INSULATION

AS SPECIFIED

SEAL INSULATION

AGAINST SKIN OF

WALL PANEL

AIR STORAGE TANK OR

DRYER

3/8" MANUAL

VALVE

3/8" O.D. COPPER

TUBING RUN TO

NEAREST FLOOR

DRAINDRAIN TRAP FURNISHED

WITH EQUIPMENT

NOTES:

SIDE ELEVATION SECTION

STIFFEN BLADE

AS REQUIRED

OUTSIDE END

BEARING

1/8" CLEARANCE

ALL AROUND

INSIDE END BEARING

HANDLE WITH

LOCKING

QUADRANT

DAMPER BLADE

DUCT

INSULATION SEE

SPECIFICATION

INSULATION

STAND-OFF

1/2" ROUND ROD

PIN

DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.

DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR

MULTI-BLADE DAMPERS & ROUND DAMPERS.

1.

2.

PLUG

1 1/2" FULL

PORT BALL

VALVE

1 1/2"⌀x2" LONG

PIPE

1 1/2" FULL

PORT BALL

VALVE

PLUG

WELD (TYP)

NOTES:

1.

2.

PROVIDE IN CHILLED WATER MAIN AND IN CONDENSER WATER MAIN.

LOCATE PILOT TUBE TAPS 20 PIPE DIAMETERS DOWNSTREAM AND 10

PIPE DIAMETERS UPSTREAM FROM THE NEAREST PIPE FITTING.

EITHER TOP OR SIDE LOCATION. BOTH ARE NOT REQUIRED AT

SAME LOCATION.

1/2" STEEL PIPE OR

STEEL TUBING TO

SENSORS

DIFFERENTIAL PRESSURE

TRANSMITTER (FLOW, LEVEL)

PT

BLOWDOWN

ELEVATION

NOTES:

INSTALLATION OF SENSORS AND TRANSMITTERS SHALL CONFORM TO

RECOMMENDATIONS OF MANUFACTURERS OF TRANSMITTERS.

1.

GREATER THAN 2" DIA. PIPE 2" DIA. & SMALLER

VERTICAL

GREATER THAN 2" DIA. PIPE 2" DIA. & SMALLER

HORIZONTAL

2 1/2" DIA.

NOTE:

PROVIDE THE APPROPRIATE WELL DEPTH TO HAVE THE

NECESSARY INSULATION STAND-OFF DISTANCE.

2 1/2" DIA.

PROJECT NUMBER

BUILDING

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD SEALCONSULTANTS

321 4 5 6 7 8 9 10

DWG. OF

NAME:

FULLY SPRINKLERED

CONTRACTING OFFICER'S REPRESENTATIVE

FULL SIZE DWG: 30x42

PHONE:

EMAIL:11031 S. PIKES PEAK DRIVE #102 PARKER, COLORADO 80138 PH. 303.841-3922

RENOVATE AND EXPAND

COMMUNITY LIVING

CENTER (CLC)

SPOKANE, WA

668-318

100% SUBMITTAL

CONSTRUCTION

DOCUMENTS (CD)

4/ 3/

:3

4:

P M

MH502

MECHANICAL DETAILS

APRIL 2023 CDL TJH

107 183

David Arment 509-964-1889 David.Arment@va.gov

SCALE: NTS

DRAIN VALVE AND AIR VENT CONNECTIONS

(HYDRONIC SYSTEMS)6

SCALE: NTS

IN-LINE PUMPS - CONNECTIONS2

SCALE: NTS

SINGLE SUCTION FLOOR-MOUNTED

PUMPS-CONNECTIONS WITH FLEXIBLE

CONNECTORS3

SCALE: NTS

TUBING, PIPING, AND CONDUITS PASSING THROUGH

PRE-FAB INSULATED WALL PANELS4

SCALE: NTS

TYPICAL DRAIN FOR AIR COMPRESSOR AND DRYER1

SCALE: NTS

VOLUME DAMPER DETAIL7

SCALE: NTS

PILOT TEST CONNECTIONS8

SCALE: NTS

PRESSURE TRANSMITTER INSTALLATION5

SCALE: NTS

INSTALLATION OF THERMOMETER WELLS9

SHORT RADIUS ELBOW

WITH ONE VANE

SHORT RADIUS ELBOW

WITH TWO VANES

STANDARD RADIUS OR

LONG RADIUS ELBOW

R SHALL

EQUAL

OR BE

GREATER

THAN W.

R SHALL

EQUAL

OR BE

GREATER

THAN

1/3W.

R SHALL

EQUAL

OR BE

GREATER

THAN

1/6W.

R

VANE R

THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.

ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS

ELBOWS. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE

CONSTRUCTED, SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.

1.

2.

1/6W

1/ 3W1/2W2/3W

W W

W

NOTES:

W

W1

ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY

SMACNA.

WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE

REGARDLESS OF W DIMENSION.

ALL SINGLE THICKNESS VANES SHALL HAVE A 2" RADIUS, 1 1/2" MAXIMUM SPACE

BETWEEN VANES AND A 3/4" TRAILING EDGE.

WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" VANES SHALL BE DOUBLE VANE

TYPE.

1.

2.

3.

4.

NOTES:

TYPICAL DUCTWORK TRANSITION WITH

EQUIPMENT MOUNTED IN DUCT PLAN

OR SIDE VIEW

TYPICAL DUCTOWRK TRANSITION

PLAN OR SIDE VIEW

AIR

FLOW

AIR

FLOW

EQ

U

IP

M

EN

T

15° MAX 30° MAX

15° MAX 30° MAX

15° MAX

15° MAX

UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.1.

PLAN VIEW

BRANCH DUCT PROVIDE VOLUME

DAMPER AT EACH

BRANCH DUCT

MAIN EXHAUST OR RETURN

AIR

FLOW

AIR

FLOW

VD 4"

M

IN

1/

4W O

R

W

PLAN VIEW

MAIN SUPPLY

FLOW

FL

O

W

SMACNA FIGURE 4-6 45° LEED

IN RIGID DUCT TO AIR

TERMINAL UNIT.

PLAN VIEW

RIGID DUCT TO AIR

TERMINAL UNIT.

ROUND SHEET

METAL DUCT.

MAIN SUPPLY

45° MAX

"D"

BRANCH DUCT TAKE-OFF PLAN VIEW

AIR SPLIT DUCT TAKE-OFF

PLAN VIEW

SUPPLY REGISTER TAKE-OFF

PLAN VIEW

SUPPLY REGISTER OR

BRANCH DUCT

MAIN

SUPPLY

DUCT

SEE FLOOR PLAN FOR

SPLIT DIMENSION

TURNING VANES

PROVIDE

VOLUME

DAMPER

MAIN

SUPPLY

DUCT TOP REGISTER

ADJUSTABLE

METAL ROD OR

LINKAGE

VOLUME EXTRACTOR; ADJUSTABLE

FROM FULLY CLOSED POSITION TO

CFM NOTED ON FLOOR PLANS

MAIN SUPPLY

DUCT

PROVIDE VOLUME

DAMPER

AI

R

FL

O W

AI

R

FL

O W

AIR

FLOW

AIR

FLOW

AIR

FLOW

AIR

FLOW

AIR

FLOW

W

4" M

IN

1/

4W O

R

NOTES:

HANGER STRAPS OR RODS

MAX. DUCT

⌀ IN.

QUANTITY/SIZE

IN.

MAX. LOAD

LBS.

MAX.

SPACING IN.

ONE 1 x 22 GA STRAP ONE 1 x 18 GA STRAP ONE 1 x 16 GA STRAP

TWO 3/8 ⌀ RODS

TWO 1/2 ⌀ RODS

LOAD RATED

FASTENERS

BAND OF SAME

SIZE AS HANGER

STRAP

50" ⌀ & UNDER

HANGER RODS

BAND

OVER 50"⌀

TABULATED DATA FROM SMACNA ALLOWS FOR DUCT

REINFORCING AND INSULATION, BUT NO EXTERNAL LOAD.

SEISMIC RESTRAINT FOR PIPING SHALL BE SUBMITTED IN

ACCORDANCE WITH SPECIFICATION SECTION 13 05 41.

1.

2.

THE USE OF FLEXIBLE AIR DUCT CONNECTORS ARE NOT PERMITTED FOR THE

DEDICATED AHU SERVING THE SURGICAL SUITE.

VOLUME DAMPER W/

LOCKING QUAD

SHEET METAL

SADDLE

THERMAL INSULATION

SEE SPECIFICATIONS

BRANCH DUCT

CONICAL OUTLET

SEE SPECIFICATIONS FOR

CLAMPS AND SEALANT (TYP.)

SUPPORT SADDLE FROM

STRUCTURE

FLEXIBLE DUCT SIZE SAME AS

DIFFUSER INLET: 5'-0" MAX

LENGTH.

USE RIGID ELBOWS FOR

CHANGE OF DIRECTION

GREATER THAN 45°

TYPICAL DIFFUSER OR

REGISTER IN LAY-IN CLG. CEILING

12"

NOTES:

1.

ROUND FLEXIBLE CONNECTION

RECTANGULAR FLEXIBLE CONNECTION

FLANGED

CONNECTION ON

FAN SIDE

WASHER

1-1/2" MIN. TO 3" MAX. INSTALLED.

6" NOMINAL WITH MATERIAL TAUT

FLEXIBLE

MATERIAL AS

SPECIFIED

1"x1/8" DRAW BAND

1"x1/8" BAND IRON

BOLT ON 4" CENTERS

5/16" FLANGE

DUCT

SHEET METAL

SCREWS ON 12"

CENTERS

RIVET ON 4"

CENTERS

SHEET METAL AS SPECIFIED

FOR DUCTWORK.

1"x1/8" BAND IRON

BOLT ON 4" CENTERS

1" FLANGE & HEM

ALTERNATE

POSITION

OF BOLT 1 1/2" POCKET

SLIP

DUCT

SHEET METAL AS

SPECIFIED FOR

DUCTWORK.

1 1/2" MIN. TO 3" MAX. INSTALLED. 6"

NOMINAL WITH MATERIAL TAUT

FLANGED

CONNECTION

ON FAN SIDE

WASHER

FLEXIBLE MATERIAL AS

SPECIFIED

1/2"

1/2"

COVER WITH HANDLE

AND CHAIN RETAINER

GASKETED AND

PRESSURE SEALED

ROUND OR FLAT

OVAL DUCT SECTION

HOUSING WELDED TO

DUCT SECTION

PROJECT NUMBER

BUILDING

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD SEALCONSULTANTS

321 4 5 6 7 8 9 10

DWG. OF

NAME:

FULLY SPRINKLERED

CONTRACTING OFFICER'S REPRESENTATIVE

FULL SIZE DWG: 30x42

PHONE:

EMAIL:11031 S. PIKES PEAK DRIVE #102 PARKER, COLORADO 80138 PH. 303.841-3922

RENOVATE AND EXPAND

COMMUNITY LIVING

CENTER (CLC)

SPOKANE, WA

668-318

100% SUBMITTAL

CONSTRUCTION

DOCUMENTS (CD)

4/ 3/

:3

4:

P M

MH503

MECHANICAL DETAILS

APRIL 2023 CDL TJH

108 183

David Arment 509-964-1889 David.Arment@va.gov

SCALE: NTS

DUCTWORK RADIUS ELBOWS2

SCALE: NTS

DUCTWORK SQUARE VANE ELBOWS3

SCALE: NTS

DUCTWORK TRANSITIONS(WITH EQUIPMENT

MOUNTED IN DUCT)1 SCALE: NTS

EXHAUST OR RETURN BRANCH DUCTWORK4

SCALE: NTS

ALTERNATE SUPPLY DUCT TAKEOFF - AIR TERMINAL

UNITS5

SCALE: NTS

SUPPLY DUCT TAKEOFF - AIR TERMINAL UNIT6

SCALE: NTS

SUPPLY DUCTWORK TAKE-OFFS7

SCALE: NTS

ROUND DUCT HANGERS8

SCALE: NTS

FLEXIBLE AIR DUCT CONNECTOR9

SCALE: NTS

FLEXIBLE DUCT CONNECTIONS11

SCALE: NTS

ACCESS SECTION FOR ROUND/OVAL DUCT10

D

PROVIDE UNION UNLESS SAFETY

VALVE HAS FLANGED OUTLET

SAFETY VALVE

OPEN DRAIN (NOTE 3)

CONNECTION TO

PRESSURE VESSEL OR PIPE

VENT PIPE THROUGH ROOF SUPPORT

AS INDICATED ON DWGS. (NOTES 1, 2)

PIPE THREADED INTO ELBOW

(SAME SIZE AS ELBOW)

DRIP PAN ELBOW

(SECTIONAL VIEW)

3/4" DRAIN TO

FLOOR DRAIN OR OPEN

SIGHT DRAIN (NOTE 4)ELEVATIONNOTES:

UNLESS OTHERWISE SHOWN ON THE DRAWINGS, SIZE THE VENT PIPE SO THAT STEAM IS NOT

BLOWN OUT AT THE VENT PIPE ENTRANCE. UTILIZE THE CALCULATION METHOD CONTAINED IN ANSI B31.1. POWER PIPING CODE, APPENDIX II. THE VENT PIPE SHOULD GO VERTICAL THRU THE ROOF WITH NO TURNS OR ANGLES. WHERE REQUIRED THERE SHALL BE NO MORE THEN A TOTAL OR 180

DEGREES IN DIRECTIONAL CHANGES MADE WITH 45 DEG. ELBOWS.

VENT PIPE SHALL TERMINATE 1829mm [6'] MIN. ABOVE FINISHED ROOF.

DISCHARGE OF DRAIN SHALL BE DIRECTED AWAY FROM PLATFORMS OR OTHER AREAS WHERE

PERSONNEL MAY OCCUPY.

DO NOT CONNECT ANY OTHER DRAIN TO THE DRIP PAN ELBOW DRAIN PIPE.

SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

FLEXIBLE CONNECTOR

3"

1.

2.

3.

4.

5.

24" MAX

1" M

IN

4" H

O O

K

WATER STOP

EXTERIOR WALL

PIPE SLEEVE

HIGH DENSITY

POLYETHYLENE(HDPE)

SLEEVE WITH INTEGRAL

HOLLOW MOLDED

WATER STOP RING 4"

LARGER THAN OUTSIDE

DIAMETER OF PIPE

5/8" ROD

1/4" X 1 1/4" IRON

PIPE STRAP

FLANGED

CONNECTION

1/4" X 1 1/4"

IRON PIPE

CLAMP

PIPE SLEEVE WHERE

SPECIFIED

RISER CLAMP

BOLT

PIPE

INSULATION

BOLT, TYPICAL

FLOOR SLAB

RISER CLAMP. BOTTOM

CLAMP REQUIRED AT

ANCHOR POINTS ONLY

FIRE STOPPING

MATERIAL

RISER CLAMP

PIPE SLEEVE

WHERE

SPECIFIED

PLAN

ELEVATION

NOTES:

1. PROVIDE ANCHORS ONLY WHERE SHOWN ON

DRAWINGS.

2. EXTEND SLEEVE ABOVE FLOOR WHERE SPECIFIED.

ALL DRIP POINTS ON STEAM MAINS SHALL BE PROVIDED WITH A 12" MINIMUM HIGH

DRIP LEG FROM BOTTOM OF STEAM MAIN TO TRAP INLET. DRIP LEG SHALL HAVE 6"

SCALE POCKET BELOW TRAP INLET.

DIELECTRIC FITTING WHERE

RETURN IS COPPER PIPE

TO RETURN MAIN

FLOAT AND THERMOSTATIC TRAP.

SEE PLANS, AND SCHEDULES

1" GATE

VALVE

SCHEDULE 80

STEEL PIPE

DRIP LEG OR EQUIPMENT CONNECTION.

MAKE THE SAME SIZE AS THE SUPPLY MAIN

OR EQUIPMENT CONNECTION. SEE NOTE 1

BYPASS-INSTALL IN HORIZONTAL

PLANE LEVEL WITH TRAP OR IN

VERTICAL PLANE & BELOW TRAP

PROVIDE BYPASS PIPING FOR ALL

TRAPS 25mm [1"] AND LARGER.

USE 4-BOLT RAISED

FACE FLANGES

PIPE SIZE SHALL BE

SAME SIZE AS TRAP

SCHEDULE 80

STEEL PIPE

SEE

DRAWINGS

FOR PIPE

SIZES

6" M

IN

" M

IN

NOTES:

1.

FLOW

ALL DRIP POINTS ON STEAM MAINS SHALL BE PROVIDED WITH A 12" MINIMUM HIGH

DRIP LEG FROM BOTTOM OF STEAM MAIN TO TRAP INLET. DRIP LEG SHALL HAVE 6"

SCALE POCKET BELOW TRAP INLET.

PROVIDE BYPASS PIPING.

DRIP LEG OR EQUIPMENT CONNECTION.

MAKE THE SAME SIZE AS THE SUPPLY MAIN

OR EQUIPMENT CONNECTION. SEE NOTE 1

BYPASS-INSTALL IN

HORIZONTAL PLANE LEVEL

WITH TRAP OR IN VERTICAL

PLANE & BELOW TRAP

USE 4-BOLT RAISED FACE

FLANGES

PIPE SIZE SHALL BE

SAME SIZE AS TRAP

TO RETURN

MAIN

SCHEDULE 80

STEEL PIPE

SEE DRAWINGS

FOR PIPE SIZES DIELECTRIC FITTING WHERE RETURN IS

COPPER PIPE

INVERTED BUCKET TRAP. SEE

PLANS, AND SCHEDULES

1" GATE VALVE

SCHEDULE 80

STEEL PIPE

" M

IN

6" M

IN

FLOW

NOTES:

1.

2.

STEAM LINE DRIP POCKET

DRIP LEG (TYP.)

3/4" DRAIN

(ALTERNATE

LOCATIONS)

(TYPICAL)

STEAM LINE

(TYPICAL)

CAP (TYPICAL)

PIPE T0 STEAM

TRAP

(TYPICAL)

NOTE:

DRIP POCKET PIPE SIZE SAME AS STEAM

MAIN UNLESS OTHERWISE NOTED.

3/4" MIN.

FROM DRIP

CONNECTION

DRIP RETURN

3/8" TEST CONNECTION

STEAM TRAP ASSEMBLY

6" M

IN

" M

IN

6" M

IN

" M

IN

BUILDING INCOMING

MAIN STEAM

TEMPERATURE

TRANSMITTER

PRESSURE

TRANSMITTERTT

PT

FLOW METER

INTERFACE WITH

BACNET SYSTEM

TO METERING

SYSTEM

SHUTOFF VALVE

DIFFERENTIAL

PRESSURE (DP) CELL

STEAM FLOW

MEASUREMENT

NOTES:

MAINTAIN UPSTREAM AND DOWN STREAM DISTANCES RECOMMENDED BY METER

MANUFACTURERS.

1.

THERMOMETER (TYP.)

HP STEAM

SUPPLY

HPR TO FLASH TANK OR TO HPR

MAIN LINE(TYP.)

THERMOSTATIC

AIR VENT(TYP.)

IF THE SECOND HEAT

EXCHANGER IS NOT A

REDUNDANT 100% BACK UP

UNIT, THEN PROVIDE A

MOTORIZED ISOLATION VALVE

HERE.

SEE SCHEDULES FOR RELIEF

VALVE SETTING

DDC

TEMPERATURE

SENSORS(TYP.)

TT

TT

D

IF THE SECOND HEAT

EXCHANGER IS NOT A

REDUNDANT 100% BACK UP

UNIT, THEN PROVIDE A

MOTORIZED ISOLATION VALVE

HERE.

DDC PRESSURE

SENSORS(TYP.)

IF INSTALLED

LOWER THAN MAIN

HPS LINE, PROVIDE

ANOTHER SCALE

POCKET/TRAP

HERE.

PI

PI

CONTROL VALVES IN 2/3 & 1/3 SIZE

ARRANGEMENT, TYP.

RUN DRAIN LINE FROM

RELIEF VALVE TO NEAREST

FLOOR DRAIN(TYP).

1/2" CHECK VALVE

VACUUM

BREAKER(TYP).

HWR

HWS

TEST PLUG(TYP).

SCALE POCKET(TYP.)

HEAT EXCHANGER(TYP).

6" M

IN

BYPASS

NC

NOTES:

THE ABOVE DETAIL SHOWS REQUIRED PIPING FOR TWO HEAT EXCHANGERS IN PARALLEL. INDICATE IF 100%

REDUNDANT OR NOT.

PROVIDE SADDLE SUPPORTS AND LEGS OF HANGERS FOR HEAT EXCHANGER. MOUNTING HEIGHT SHALL BE

ADJUSTED TO FACILITATE GRAVITY RETURN OF STEAM CONDENSATE.

MAKE THE BYPASS THE SAME SIZE AS THE CONNECTIONS TO THE CONTROL VALVES.

CONTROL VALVES SHALL BE IN A 1/3 AND 2/3 SIZE ARRANGEMENT.

1.

2.

3.

4.

MANUAL AIR VENT

TO BUILDING LOAD

STEAM

PIPE

WELDED TEE

12"

6"

WELDED TEE

MV

TO DRAIN

INVERTED BUCKET

TRAP ASSEMBLY

CONDENSATE

SCHEDULE 80 STEEL PIPE

1" GATE VALVE

PROJECT NUMBER

BUILDING

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD SEALCONSULTANTS

321 4 5 6 7 8 9 10

DWG. OF

NAME:

FULLY SPRINKLERED

CONTRACTING OFFICER'S REPRESENTATIVE

FULL SIZE DWG: 30x42

PHONE:

EMAIL:11031 S. PIKES PEAK DRIVE #102 PARKER, COLORADO 80138 PH. 303.841-3922

RENOVATE AND EXPAND

COMMUNITY LIVING

CENTER (CLC)

SPOKANE, WA

668-318

100% SUBMITTAL

CONSTRUCTION

DOCUMENTS (CD)

4/ 3/

:3

4:

P M

MH504

MECHANICAL DETAILS

APRIL 2023 CDL TJH

109 183

David Arment 509-964-1889 David.Arment@va.gov

SCALE: NTS

STEAM SAFETY VALVE8

SCALE: NTS

SUPPORT ANCHOR(CONDENSED WATER OR

CHILLED)5

SCALE: NTS

SUPPORT/ANCHOR FOR PIPE RISERS6

SCALE: NTS

FLOAT AND THERMOSTATIC STEAM TRAP ASSEMBLY2

SCALE: NTS

INVERTED BUCKET STEAM TRAP ASSEMBLY1

SCALE: NTS

STEAM LINE DRIP POCKET & STEAM TRAP ASSEMBLY9

SCALE: NTS

STEAM METER DETAIL3

SCALE: NTS

HEAT EXCHANGER - STEAM TO HOT WATER7

SCALE: NTS

END OF STEAM LINE DRIP TRAP4

INSULATE AS INDICATED FOR ALL CHILLED WATER.

INSULATE PIPE ONLY FOR STEAM, CONDENSATE &

HEATING WATER.

D=PIPE O.D.

L+3"

L

T

P

L+4"

L+8"

D+4" D+8"

ANCHOR BOLTS

N=NUMBER S=SIZE

DRILL ⌀ = S+[1/8"]

NOTE A

NOTES:

1. INSTALL WALL PLATE FIRST THEN WELD ON REMAINING ASSEMBLY. ONE WALL PLATE FOR BOTH

CHILLED WATER S.&R. IS OPTIONAL.

2. SEISMIC RESTRAINT FOR PIPING SHALL BE SUBMITTED IN ACCORDANCE WITH SPECIFICATION

SECTION 13 05 41.

T

E

PIPE ANCHOR SCHEDULE

PLD T E N S

in in in in in in in

8 1/2

3/4

3/4

3/4

3/4

3/4

3/4

3/8

1/2

1/2

1/2

1/2

1/2

1/2

1/2

1/2

1/2

1/4

1/4

1/4

1/4

7/8

7/8

7/8

7/8

7/8

7/8

BOLT PATTERN

INSULATION (VAPOR

BARRIER TYPE IS

REQUIRED FOR LOW

TEMPERATURE PIPE)

PROVIDE HIGH COMPRESSIVE

STRENGTH INSULATION (9 PSF

MIN. DENSITY) UPPER

INSULATION SHIELD

INSULATION SHIELD

AT HANGER

HANGER ROD

NOTES:

1. SEE SPECIFIER FOR DETAILED HANGER REQUIREMENTS

2. SEISMIC RESTRAINT FOR PIPING SHALL BE SUBMITTED IN ACCORDANCE

WITH SPECIFICATION SECTION 13 05 41.

ADJUSTABLE CLEVIS HANGER TYPE 1 -

SEE SPECIFICATIONS

ADJUSTABLE CLEVIS HANGER TYPE 43 -

SEE SPECIFICATIONS

WELD

SADDLE

1/2" DIA. HANGER

RODS WITH 36" MAX.

SPACING ON EACH

CHANNEL

1-5/8" 12 GAUGE CHANNEL

OR 2"x2"x1/4" ANGLE

SIDE VIEW TRAPEZE HANGER FOR UP

TO 1000 LB. UNIFORM LOAD

BAND

PROVIDE INSULATION

SHIELD & INSERT FOR

ALL PIPING (8" MIN.)

MAXIMUM PIPE/TUBING SUPPORT SPACING

NOM. SIZE

PIPE

TUBING

NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.

IN

FT

FT

THRU 3/4 1 1 1/4 1 1/2 2 2 1/2 3 4 5 6 8 10 12 14 16 18 20 24

7 7 9 10 11 12 14 16 17 19 22 23 25 27 28 30 32

6 7 8 8 9 10 12 13 14 16 - - - - - - -

1" M

AX

PROVIDE VAPOR BARRIER

AS SPECIFIED ON PIPING

CONVEYING FLUID TO

DEGREE C [°F] OR LOWER

HIGH COMPRESSIVE STRENGTH

INSULATION INSERT UNDER

SHIELD

WELD PIPE SADDLE

SUPPORT TO PIPE. PROVIDE

WATER TIGHT CONNECTION

CLAMPING RING

PRE-MOULDED FLEXIBLE

PIPE COUNTER FLASHING

ROOF SYSTEM INSULATION

AND MEMBRANE

ROOF SURFACE

CONCRETE ROOF SLAB OR

STEEL ROOF DECK

SECURE TO ROOF SLAB WITH (4)

EXPANSION BOLTS OR WELD TO

STEEL DECK

WELD PIPE TO

PLATE

8"x8"x3/8" STEEL PLATE

SEALANT

2-1/2" STEEL

PIPE

2" STEEL PIPE

INSULATION

PROTECTION SHIELD

PIPE AND

INSULATION

PROVIDE ALUMINUM

JACKET

NOTES:

1. PROVIDE RESTRAINING CLAMPS 8'-0" O.C. MAX.

2. SEISMIC RESTRAINT FOR PIPING SHALL BE SUBMITTED IN

ACCORDANCE WITH SPECIFICATION SECTION 13 05 41.

PROJECT NUMBER

BUILDING

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD SEALCONSULTANTS

321 4 5 6 7 8 9 10

DWG. OF

NAME:

FULLY SPRINKLERED

CONTRACTING OFFICER'S REPRESENTATIVE

FULL SIZE DWG: 30x42

PHONE:

EMAIL:11031 S. PIKES PEAK DRIVE #102 PARKER, COLORADO 80138 PH. 303.841-3922

RENOVATE AND EXPAND

COMMUNITY LIVING

CENTER…