This document is a mechanical equipment power schedule for a renovation and expansion project of a Community Living Center located in Spokane, Washington. The schedule lists over thirty mechanical units including fan coil units, exhaust fans, air handling units, and variable air volume boxes. It specifies details such as the voltage, phase, manufacturer, full load amps, circuit breaker size, conductor and conduit sizes, and overload protection for each unit. The schedule also includes notes that instruct electrical contractors on installation requirements such as providing a separate power supply circuit for each system, verifying equipment electrical load characteristics, and mounting transformers above panels with labels indicating the load served. This document is related to the federal contract opportunity to renovate and expand the Community Living Center at the Spokane VA Medical Center, with a solicitation number of 36C77623B0071, issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MECHANICAL EQUIPMENT POWER SCHEDULE
MARK STATUS LOCATION
FCU-S101
FCU-S104
NEW RESIDENT BEDROOM S101
VOLTAGE/
PHASE
208/1
MANUFACTURER
HP
FLA
MCA
1.75
BREAKER
SIZE
20A
CONDUCTOR
SIZE
2#12
GROUNDING
CONDUCTOR
1#12
SHORT CKT & GROUND
PROTECTION-
INVERSE TIME BREAKER
FUSE SIZE OVERLOAD PROTECTION
NEW
NEW
NEW
FCU-S105
FCU-S106
FCU-S107
FCU-S108
FCU-S109
FCU-S110
FCU-S111
FCU-S113
FCU-S116
FCU-S117
FCU-S118
FCU-S119
FCU-S120
FCU-S121
FCU-S122
FCU-W101
FCU-W104
FCU-W105
FCU-W106
FCU-W107
FCU-W108
FCU-W109
FCU-W110
FCU-W113
FCU-W114
FCU-W116
FCU-W117
FCU-W118
FCU-W115
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
RESIDENT BEDROOM S104
RESIDENT BEDROOM S105
RESIDENT BEDROOM S106
RESIDENT BEDROOM S107
RESIDENT BEDROOM S108
RESIDENT BEDROOM S109
RESIDENT BEDROOM S110
RESIDENT BEDROOM S111
TELECOM
RESIDENT BEDROOM S116
RESIDENT BEDROOM S117
RESIDENT BEDROOM S118
RESIDENT BEDROOM S119
RESIDENT BEDROOM S120
DINING ROOM
RESIDENT BEDROOM S122
RESIDENT BEDROOM W101
RESIDENT BEDROOM W104
RESIDENT BEDROOM W105
RESIDENT BEDROOM W106
RESIDENT BEDROOM W107
FAMILY
RESIDENT BEDROOM W118
RESIDENT BEDROOM W117
RESIDENT BEDROOM W116
TELECOM
RESIDENT BEDROOM W114
RESIDENT BEDROOM W113
RESIDENT BEDROOM W110
RESIDENT BEDROOM W109
TOGGLE MOTOR DISCONNET SWITCH
208/1
208/1
208/1
208/1
208/1
208/1
208/1
208/1
208/1
208/1
208/1
208/1
208/1
208/1
208/1
208/1
208/1
208/1
208/1
208/1
208/1
208/1
208/1
208/1
208/1
208/1
208/1
208/1
208/1
208/1
1.75
1.75
1.75
1.75
1.75
1.75
1.75
1.75
1.75
1.75
1.75
1.75
1.75
1.75
1.75
1.75
1.75
1.75
1.75
1.75
1.75
1.75
1.75
1.75
1.75
1.75
1.75
1.75
1.75
1.75
12-CWP-1
12-CWP-2
12-HWP-1
12-HWP-2
NEW
NEW
NEW
NEW
MECHANICAL PENTHOUSE
MECHANICAL PENTHOUSE
MECHANICAL RM 110
MECHANICAL RM 110
208/3
208/3
208/3
208/3
VFD
VFD
VFD
VFD
12-EF-1W NEW ROOF
12-EF-1S NEW ROOF
208/3
208/3
4.8
4.8
12-ACC-1 NEW ROOF/PENTHOUSE 208/3 441
12-DOAS-1 NEW MECHANICAL RM S112 208/3 42 52.5
500A
20A 15A
CONDUIT
SIZE
3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
20A 2#12 1#12 20A 15A3/4"
35A 3#10 1#10 60A 40A1"
35A 3#10 1#10 60A 40A1"
20A 3#12 1#12 20A 15A3/4"
20A 3#12 1#12 20A 15A3/4"
20A 3#12 1#12 20A 15A3/4"
20A 3#12 1#12 20A 15A3/4"
90A 3#4 1#8 90A 90A1 1/4"
VFD
VFD
2 SETS OF
3#350
2 SETS OF
1#1 600A 600A2 SETS
OF 3"
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
TOGGLE MOTOR DISCONNET SWITCH
SHEET NOTES:
INSTALL CONTROL WIRING AND CONNECT TO EQUIPMENT
TO PERFORM THE REQUIRED FUNCTIONS. INSTALL A
SEPARATE POWER SUPPLY CIRCUIT FOR EACH SYSTEM.
PROVIDE ALL EQUIPMENT IN SCHEDULE UNLESS
OTHERWISE NOTED.
VERIFY EXACT EQUIPMENT ELECTRICAL LOAD
CHARACTERISTICS WITH FINAL APPROVED PRODUCT
DATA SHEET SUBMITTALS PRIOR TO ELECTRICAL ROUGH-
IN.
PROVIDE LINE VOLTAGE INTERLOCK WIRING ALONG WITH
MANUAL MOTOR STARTER TO CONNECT
INTEGRAL MOTOR OPERATED DAMPER.
PROVIDE NEMA TYPE 3R NON-FUSIBLE SAFETY SWITCH
LOCATED AT MECHANICAL UNIT AND WIRING
TO REMOTE COMBINATION MAGNETIC MOTOR STARTER
AND FUSIBLE SAFETY SWITCH AS NOTED ON
PLANS.
REFER TO POWER DISTRIBUTION ONE LINE DIAGRAMS
FOR ADDITIONAL INFORMATION.
PROVIDE LINE VOLTAGE INTERLOCK WIRING BETWEEN
EXHAUST FAN, MOTOR OPERATED DAMPER
AND ROOM T-STAT.
PROVIDE NEMA TYPE 3R NON-FUSIBLE SAFETY SWITCH
LOCATED AT MECHANICAL UNIT AND WIRING
TO REMOTE VARIABLE FREQUENCY DRIVE UNIT
CONTROLLER AS NOTED ON PLANS.
MECHANICAL UNIT FURNISHED WITH FACTORY WIRED,
VARIABLE FREQUENCY DRIVE FOR SINGLE
POINT POWER CONNECTION.
MECHANICAL UNIT FURNISHED WITH FACTORY WIRED,
COMBINATION MAGNETIC MOTOR STARTER AND
FUSIBLE SAFETY SWITCH FOR SINGLE POINT POWER
CONNECTION.
MECHANICAL UNIT FURNISHED WITH FACTORY WIRED,
QUICK DISCONNECT SWITCH FOR SINGLE POINT
POWER CONNECTION.
CIRCUIT SERVING VAVS THROUGH 500 VA 277V - 120V
STEP-DOWN TRANSFORMER WITH INTEGRAL
PRIMARY AND SECONDARY OVERLOAD PROTECTION.
MOUNT TRANSFORMER ABOVE PANEL AND
PROVIDE LABEL TO INDICATE LOAD SERVED.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
PROJECT NUMBER
BUILDING
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASEARCHITECT/ENGINEER OF RECORD SEALCONSULTANTS
321 4 5 6 7 8 9 10
DWG. OF
NAME:
FULLY SPRINKLERED
CONTRACTING OFFICER'S REPRESENTATIVE
FULL SIZE DWG: 30x42
PHONE:
EMAIL:11031 S. PIKES PEAK DRIVE #102 PARKER, COLORADO 80138 PH. 303.841-3922
RENOVATE AND EXPAND
COMMUNITY LIVING
CENTER (CLC)
SPOKANE, WA
668-318
100% SUBMITTAL
CONSTRUCTION
DOCUMENTS (CD)
/1
1/
1:
:5
AM
EP621
MECHANICAL EQUIPMENT POWER
SCHEDULE
APRIL 2023 JOL DKC
169 183
David Arment 509-964-1889 David.Arment@va.govREVISIONS DATE