MH603 12.12.2023.pdf

PDF 219 KB Posted

Attached to
Y1DZ--668-318 Renovate and Expand Community Living Center Minor Construction - Spokane VAMC
Solicitation number
36C77623B0071
Issued by

About this file

This document contains mechanical drawings and schedules for the renovation and expansion of a Community Living Center at the Spokane VA Medical Center. Key details include specifications for over 50 fan coil units to be installed throughout resident bedrooms, common areas, telecom rooms and a nurse station. The units will be horizontal concealed models manufactured by Trane with cooling capacities ranging from 5.18 to 5.29 tons and heating capacities from 5.18 to 5.29 MBH. Associated controls drawings and specifications are also included on additional sheets.

The related federal contract opportunity is solicitation number 36C77623B0071 to renovate and expand the Community Living Center at the Spokane VAMC, issued by the Department of Veterans Affairs Technology Acquisition Center in Austin, Texas.

View the file

Other files

File Type Posted
Wage Determination WDWA20230017 MOD4.pdf PDF
36C77623B0071 0006.docx DOCX document
EP612 12.11.2023.pdf PDF
36C77623B0071 0005.docx DOCX document
MP103 12.12.2023.pdf PDF
CLC Technical Response Tracking Spreadsheet - 12.13.2023.pdf PDF
MH701 12.12.2023.pdf PDF
36C77623B0071 0004.docx DOCX document
Question 97 - formatrac-bendable-track_specifications-ipc.1196-rev9.pdf PDF
CLC Technical Response Tracking Spreadsheet - 12.4.2023.pdf PDF
Question 82 - CO-Series-Product-Sheet-PS-CO8 (1).pdf PDF
36C77623B0071 0003.docx DOCX document
Question 5 and 64 - 09 29 00 - Gyp Board.pdf PDF
CLC Technical Response Tracking Spreadsheet - FINAL.pdf PDF
Question 67 - Spokane Design Requirements - Design Amendments May 2021.pdf PDF
CLC - Master Submittal Register (Responding to item 4 on VA email from 11.15.2023.pdf PDF
Question 44 - Links word and excel Statement of SI Temp.pdf PDF
Lift count - CLC Spokane - 100_ CD Drawings_.pdf PDF
LIFT INFORMATION - LI-WVA-019-04- Existing Lifts .pdf PDF
Amendment 0002 Technical Question Tracker.pdf PDF
36C77623B0071 0002.docx DOCX document
LQ-610380-07 NEW LIFT INFO.pdf PDF
SF1442 Page 2 - Signature Page.pdf PDF
CLC Technical Response Tracking Spreadsheet - 10-26-2023.pdf PDF
Wage Determination WDWA20230017 MOD2.pdf PDF
Completed Site Visit Sign-In Sheet 10-17-23.pdf PDF
36C77623B0071 0001.docx DOCX document
ATTACHMENT 7 - DAVIS-BACON ACT WAGE DETERMINATION WDWA20230017 MOD1.pdf PDF
ATTACHMENT 1 - FINAL SPECIFICATIONS - CLC RENO SPOKANE - PART 1 of 2.pdf PDF
ATTACHMENT 5 - FINAL DRAWINGS - CLC RENO SPOKANE - PART 3 of 3.pdf PDF
ATTACHMENT 2 - FINAL SPECIFICATIONS - CLC RENO SPOKANE - PART 2 of 2.pdf PDF
ATTACHMENT 4 - FINAL DRAWINGS - CLC RENO SPOKANE - PART 2 of 3.pdf PDF
ATTACHMENT 3 - FINAL DRAWINGS - CLC RENO SPOKANE - PART 1 of 3.pdf PDF
ATTACHMENT 6 - LIMITATIONS ON SUBCONTRACTING.docx DOCX document
ATTACHMENT 8 - SITE VISIT INSTRUCTIONS.pdf PDF
36C77623B0071.docx DOCX document
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT NUMBER

BUILDING

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD SEALCONSULTANTS

321 4 5 6 7 8 9 10

DWG. OF

NAME:

FULLY SPRINKLERED

CONTRACTING OFFICER'S REPRESENTATIVE

FULL SIZE DWG: 30x42

PHONE:

EMAIL:11031 S. PIKES PEAK DRIVE #102 PARKER, COLORADO 80138 PH. 303.841-3922

RENOVATE AND EXPAND

COMMUNITY LIVING

CENTER (CLC)

SPOKANE, WA

668-318

100% SUBMITTAL

CONSTRUCTION

DOCUMENTS (CD)

/1

2/

:2 5:

P

M

MH603

MECHANICAL SCHEDULES

APRIL 2023 CDL TJH

116 183

David Arment 509-964-1889 David.Arment@va.gov

PHASE 1 - FAN COIL UNIT SCHEDULE

MARK

LOCATION SERVED BASIS OF DESIGN

TYPE

MAX.

FAN AIR

FLOW

ESP

COOLING REQUIREMENTS HEATING REQUIREMENTS FILTER FAN MOTOR

SENSIBLE

CAPACITY

TOTAL

CAPACITY

EAT

FLOW EWT LWT WPD MIN

CAPACITY EAT Db FLOW EWT WPD MERV

RATING

POWER MCA

PHASE VOLT SPEED

CONTROL NOTESDb Wb

WING ROOM NO. ROOM NAME MAKE MODEL CFM IN. WG. MBH MBH °F °F GPM °F °F FT MBH °F GPM °F FT W A

FCU-S101 SOUTH S101 RESIDENT BEDROOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 CONSTANT 1

FCU-S104 SOUTH S104 RESIDENT BEDROOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 1

FCU-S105 SOUTH S105 RESIDENT BEDROOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 1

FCU-S106 SOUTH S106 RESIDENT BEDROOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 1

FCU-S107 SOUTH S107 RESIDENT BEDROOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 1

FCU-S108 SOUTH S108 RESIDENT BEDROOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 1

FCU-S109 SOUTH S109 RESIDENT BEDROOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 1

FCU-S110 SOUTH S110 RESIDENT BEDROOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 1

FCU-S111 SOUTH S111 RESIDENT BEDROOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 1

FCU-S113 SOUTH S113 TELECOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 --- --- --- --- --- 8 52 1 1 208 1, 2

FCU-S116 SOUTH S116 NURSE STATION TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 1

FCU-S117 SOUTH S117 RESIDENT BEDROOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 1

FCU-S118 SOUTH S118 RESIDENT BEDROOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 1

FCU-S119 SOUTH S119 RESIDENT BEDROOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 1

FCU-S120 SOUTH S120 RESIDENT BEDROOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 1

FCU-S121 SOUTH S121 DINING ROOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 1

FCU-S122 SOUTH S122 RESIDENT BEDROOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 1

FCU-W101 WEST W101 RESIDENT BEDROOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 1

FCU-W104 WEST W104 RESIDENT BEDROOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 1

FCU-W105 WEST W105 RESIDENT BEDROOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 1

FCU-W106 WEST W106 RESIDENT BEDROOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 1

FCU-W107 WEST W107 RESIDENT BEDROOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 1

FCU-W108 WEST W108 FAMILY TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 1

FCU-W109 WEST W109 RESIDENT BEDROOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 1

FCU-W110 WEST W110 RESIDENT BEDROOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 1

FCU-W113 WEST W113 RESIDENT BEDROOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 1

FCU-W114 WEST W114 RESIDENT BEDROOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 1

FCU-W115 WEST W115 TELECOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 --- --- --- --- --- 8 52 1 1 208 1, 2

FCU-W116 WEST W116 RESIDENT BEDROOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 1

FCU-W117 WEST W117 RESIDENT BEDROOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 1

FCU-W118 WEST W118 RESIDENT BEDROOM TRANE FCCB020 HORIZONTAL CONCEALED 200 0.20 5.18 5.29 80.0 62.0 1.05 45 55 1.78 8.86 60 1.05 160 2.42 8 52 1 1 208 1

NOTES:

1.) EQUIVALENT SUBSTITUTION PERMITTED UPON COR APPROVAL.

2.) COOLING ONLY FAN COIL UNIT.

REVISIONS DATE 3 APRIL 2023

CONSTANT

CONSTANT

CONSTANT

CONSTANT

CONSTANT

CONSTANT

CONSTANT

CONSTANT

CONSTANT

CONSTANT

CONSTANT

CONSTANT

CONSTANT

CONSTANT

CONSTANT

CONSTANT

CONSTANT

CONSTANT

CONSTANT

CONSTANT

CONSTANT

CONSTANT

CONSTANT

CONSTANT

CONSTANT

CONSTANT

CONSTANT

CONSTANT

CONSTANT

CONSTANT