This document appears to be design plans for installing patient lift systems at a Veterans Affairs medical center. It provides detailed drawings and specifications for installing Liko brand lifts, rails, carriers and other components throughout patient rooms and hallways. Key details include requirements for certified Liko installation by a contractor, reference to Liko load tables and installation instructions, and multiple revisions to the plans dated between November 2011 and April 2012. Dimensions and locations are provided for all lift system elements. Elevation drawings include height details for rails, carriers and wall mounts. The related federal contract opportunity is for renovating and expanding a community living center at the Spokane VAMC, suggesting these lift installation plans may be part of that larger construction project.

View the file

Other files

File Type Posted
Wage Determination WDWA20230017 MOD4.pdf PDF
36C77623B0071 0006.docx DOCX document
EP612 12.11.2023.pdf PDF
36C77623B0071 0005.docx DOCX document
MP103 12.12.2023.pdf PDF
CLC Technical Response Tracking Spreadsheet - 12.13.2023.pdf PDF
MH701 12.12.2023.pdf PDF
MH603 12.12.2023.pdf PDF
36C77623B0071 0004.docx DOCX document
Question 97 - formatrac-bendable-track_specifications-ipc.1196-rev9.pdf PDF
CLC Technical Response Tracking Spreadsheet - 12.4.2023.pdf PDF
Question 82 - CO-Series-Product-Sheet-PS-CO8 (1).pdf PDF
36C77623B0071 0003.docx DOCX document
Question 5 and 64 - 09 29 00 - Gyp Board.pdf PDF
CLC Technical Response Tracking Spreadsheet - FINAL.pdf PDF
Question 67 - Spokane Design Requirements - Design Amendments May 2021.pdf PDF
CLC - Master Submittal Register (Responding to item 4 on VA email from 11.15.2023.pdf PDF
Question 44 - Links word and excel Statement of SI Temp.pdf PDF
Lift count - CLC Spokane - 100_ CD Drawings_.pdf PDF
Amendment 0002 Technical Question Tracker.pdf PDF
36C77623B0071 0002.docx DOCX document
LQ-610380-07 NEW LIFT INFO.pdf PDF
SF1442 Page 2 - Signature Page.pdf PDF
CLC Technical Response Tracking Spreadsheet - 10-26-2023.pdf PDF
Wage Determination WDWA20230017 MOD2.pdf PDF
Completed Site Visit Sign-In Sheet 10-17-23.pdf PDF
36C77623B0071 0001.docx DOCX document
ATTACHMENT 7 - DAVIS-BACON ACT WAGE DETERMINATION WDWA20230017 MOD1.pdf PDF
ATTACHMENT 1 - FINAL SPECIFICATIONS - CLC RENO SPOKANE - PART 1 of 2.pdf PDF
ATTACHMENT 5 - FINAL DRAWINGS - CLC RENO SPOKANE - PART 3 of 3.pdf PDF
ATTACHMENT 2 - FINAL SPECIFICATIONS - CLC RENO SPOKANE - PART 2 of 2.pdf PDF
ATTACHMENT 4 - FINAL DRAWINGS - CLC RENO SPOKANE - PART 2 of 3.pdf PDF
ATTACHMENT 3 - FINAL DRAWINGS - CLC RENO SPOKANE - PART 1 of 3.pdf PDF
ATTACHMENT 6 - LIMITATIONS ON SUBCONTRACTING.docx DOCX document
ATTACHMENT 8 - SITE VISIT INSTRUCTIONS.pdf PDF
36C77623B0071.docx DOCX document
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LI-WVA-019-04

Brian McGuirk 3/16" = 1' 1 7

Notes:

A. Reference Liko Point Load Tables regarding the loading applied to the building structure.

B. Refer to Liko installation instructions for proper installation procedures.

C. Liko patient lift systems must be installed by a Liko certified installer(s).

D. Refer to Liko bracing details for proper installation.

8'-11"

(Approx.)

1'-6"

9'-2"

1'-4"

3"

18'-1"

Liko

Traverse Switch

Liko H70 Rail

(Cut in sections)

20'-8"

Approx.

8'-8"

Approx.

2'-11"

(Approx.)

Liko

Turntable

4'-5"

(Approx.)

9'-10"

(Max Span 9'-10")

11'-1

18'-4"6'-2"

Likorall 250ES

Lift Motor 550lb Capacity

Liko Traverse Rail

Carrier Multi Standard

Liko 3.4M H70 Rail with

2.4M Reinforcement Rail 100

Liko 5.6M

H160 Rail

Liko H160 Rail

(Cut to fit)

24'-6"

Approx.

Liko Slimline

Upright Support

3'-6"

(Approx.)

3'-10"

(Approx.)

Liko H70 Rail

90° Curve

Liko H70 Rail

90° Curve

Version Revision Description Date Initials

1 Changed bathroom support 11/28/11 BM

2 Added rooms 129, 144 & 145 1/10/12 BM

3 Revised per mark ups 1/19/12 BM

4 Revised per mark ups 1/26/12 BM

5 Revised room 129 to room 138 1/30/12 BM

6 Revised per mark ups 2/16/12 BM

7 Revised door swings 3/26/12 BM

Liko Support

Pendants (16 total)

2'-1"

Liko H70 Rail

45° Curve

BM4/16/12Revised per mark ups8

Brian McGuirk 1/4" = 1' 2 7

Notes:

A. Reference Liko Point Load Tables regarding the loading applied to the building structure.

B. Refer to Liko installation instructions for proper installation procedures.

C. Liko patient lift systems must be installed by a Liko certified installer(s).

D. Refer to Liko bracing details for proper installation.

5'-9

4'-6

" Primary rail to wall

11"

1'-6"

1'-6"

1'-3"

9'-6"

3'-0

3'-6"

" Primary rail to wall

1'-4"

3"

3"

1'-4"

Likorall 250ES

Lift Motor 550lb Capacity

Liko Traverse Rail

Carrier Multi Standard

Liko 3.4M H70 Rail with

1.9M Reinforcement Rail 50

Liko

H140 Rail

Liko Slimline

Upright Support

Liko Traverse Switch

Liko H70 Rail

90 degree Curve

Liko Support Pendant

(See page 2 for height variance)

Liko H100 Rail

Cut to size

Liko Traverse Rail

Carrier Multi Standard

Liko 2.0M H70 Rail

Liko Support

Pendant

2 Added rooms 129, 144 & 145 1/10/12 BM

3 Revised per mark ups 1/19/12 BM

4 Revised per mark ups 1/26/12 BM

5 Revised room 129 to room 138 1/30/12 BM

6 Revised per mark ups 2/16/12 BM

7 Revised door swings 3/26/12 BM

BM4/16/12Revised per mark ups8

Bridging if needed typical all wall supports

Brian McGuirk 1/4" = 1' 3 7

Notes:

A. Reference Liko Point Load Tables regarding the loading applied to the building structure.

B. Refer to Liko installation instructions for proper installation procedures.

C. Liko patient lift systems must be installed by a Liko certified installer(s).

D. Refer to Liko bracing details for proper installation.

8'-6

7'-2

"8

1'-6"

1'-6"

1'-3"

8'-2"

2'-10

3'-6"

" Primary rail to wall

1'-4"

3"

3"

1'-4"

Likorall 250ES

Lift Motor 550lb Capacity

Liko Traverse Rail

Carrier Multi Standard

Liko 2.8M H70 Rail with

1.9M Reinforcement Rail 50

Liko

H140 Rail

Liko Slimline

Upright Support

Liko Traverse Switch

Liko H70 Rail

90 degree Curve

Liko Support Pendant

(See page 2 for height variance)

Liko H140 Rail

Cut to size

Liko

Support Pendant

Liko Traverse Rail

Carrier Multi Standard

Liko 2.6M H70 Rail with

1.4M Reinforcement Rail 30

2 Added rooms 129, 144 & 145 1/10/12 BM

3 Revised per mark ups 1/19/12 BM

4 Revised per mark ups 1/26/12 BM

5 Revised room 129 to room 138 1/30/12 BM

6 Revised per mark ups 2/16/12 BM

7 Revised door swings 3/26/12 BM

BM4/16/12Revised per mark ups8

Bridging if needed typical all wall supports

Brian McGuirk 1/4" = 1' 4 7

Notes:

A. Reference Liko Point Load Tables regarding the loading applied to the building structure.

B. Refer to Liko installation instructions for proper installation procedures.

C. Liko patient lift systems must be installed by a Liko certified installer(s).

D. Refer to Liko bracing details for proper installation.

9'-6

8'-3

1'-6"

1'-6"

1'-3"

8'-2"

2'-11

4'-6"

" Primary rail to wall

1'-4"

3"

3"

1'-4"

Likorall 250ES

Lift Motor 550lb Capacity

Liko Traverse Rail

Carrier Multi Standard

Liko 2.8M H70 Rail with

1.9M Reinforcement Rail 50

Liko

H140 Rail Liko Slimline

Upright Support

Liko Traverse Switch

Liko H70 Rail

90 degree Curve

Liko H100 Rail

Cut to size

Liko Traverse Rail

Carrier Multi Standard

Liko 2.6M H70 Rail with

1.9M Reinforcement Rail 50

" Primary rail to wall

Liko

Support

Pendant

1'-6"

1'-6"

2'-11

4'-6"

1'-4"

3"

3"

1'-4"

Likorall 250ES

Lift Motor 550lb Capacity

Liko Traverse Rail

Carrier Multi Standard

Liko 2.8M H70 Rail with

1.9M Reinforcement Rail 50

Liko

H140 RailLiko Slimline

Upright Support

Liko

Support

Pendant

20'-0" 20'-0"

2 Added rooms 129, 144 & 145 1/10/12 BM

3 Revised per mark ups 1/19/12 BM

4 Revised per mark ups 1/26/12 BM

5 Revised room 129 to room 138 1/30/12 BM

6 Revised per mark ups 2/16/12 BM

7 Revised door swings 3/26/12 BM

Bridging if needed - typical all wall supports

Brian McGuirk 1/4" = 1' 5 7

Notes:

A. Reference Liko Point Load Tables regarding the loading applied to the building structure.

B. Refer to Liko installation instructions for proper installation procedures.

C. Liko patient lift systems must be installed by a Liko certified installer(s).

D. Refer to Liko bracing details for proper installation.

9'-6

8'-3

1'-6"

1'-6"

1'-3"

8'-2"

2'-11

4'-6"

" Primary rail to wall

1'-4"

3"

3"

1'-4"

Likorall 250ES

Lift Motor 550lb Capacity

Liko Traverse Rail

Carrier Multi Standard

Liko 2.8M H70 Rail with

1.9M Reinforcement Rail 50

Liko

H140 Rail Liko Slimline

Upright Support

Liko Traverse Switch

Liko H70 Rail

90 degree Curve

Liko H100 Rail

Cut to size

Liko Traverse Rail

Carrier Multi Standard

Liko 2.6M H70 Rail with

1.9M Reinforcement Rail 50

" Primary rail to wall

Liko

Support

Pendant

1'-6"

1'-6"

2'-11

4'-6"

1'-4"

3"

3"

1'-4"

Likorall 250ES

Lift Motor 550lb Capacity

Liko Traverse Rail

Carrier Multi Standard

Liko 2.8M H70 Rail with

1.9M Reinforcement Rail 50

Liko

H140 RailLiko Slimline

Upright Support

Liko

Support

Pendant

20'-0" 20'-0"

2 Added rooms 129, 144 & 145 1/10/12 BM

3 Revised per mark ups 1/19/12 BM

4 Revised per mark ups 1/26/12 BM

5 Revised room 129 to room 138 1/30/12 BM

6 Revised per mark ups 2/16/12 BM

7 Revised door swings 3/26/12 BM

Bridging if needed - typical all wall supports

Bathroom Doorway

Liko Sling

X-Large

Patient Room

Elevation Detail

Notes:

A. Reference Liko Point Load Tables regarding the loading applied to the building structure.

B. Refer to Liko installation instructions for proper installation procedures.

C. Liko patient lift systems must be installed by a Liko certified installer(s).

D. Refer to Liko bracing details for proper installation.

Brian McGuirk 1/2" = 1' 6 7

1'-0

" Approx.

Top of Traverse Rail

1'-3"

Approx.

6" Approx.

Top of Primary Rail

1'-3

" Approx.

Pendant Height

" Approx.

Pendant Height

1'-3"

3'-5"

Approx.

2'-1" Approx.

Max Lifting Height

8'-0"

" Approx.

Top of Reinforcement Rail

2 Added rooms 129, 144 & 145 1/10/12 BM

3 Revised per mark ups 1/19/12 BM

4 Revised per mark ups 1/26/12 BM

5 Revised room 129 to room 138 1/30/12 BM

6 Revised per mark ups 2/16/12 BM

7 Revised door swings 3/26/12 BM

BM4/16/12Revised per mark ups8

6'-9" Approx.

Bottom of Traverse Rail

6'-8"

Door Height

Steel Substructure

Bathroom Doorway

Liko Sling

X-Large

Patient Room

Elevation Detail

Notes:

A. Reference Liko Point Load Tables regarding the loading applied to the building structure.

B. Refer to Liko installation instructions for proper installation procedures.

C. Liko patient lift systems must be installed by a Liko certified installer(s).

D. Refer to Liko bracing details for proper installation.

8" Approx.

Top of Traverse Rail

11"

Approx.

1" Approx.

Top of Primary Rail

" Approx.

Pendant Height

" Approx.

Pendant Height

1'-3"

3'-5"

Approx.

2'-5" Approx.

Max Lifting Height

8'-0"

Brian McGuirk 1/2" = 1' 7 7

2 Added rooms 129, 144 & 145 1/10/12 BM

3 Revised per mark ups 1/19/12 BM

4 Revised per mark ups 1/26/12 BM

5 Revised room 129 to room 138 1/30/12 BM

6 Revised per mark ups 2/16/12 BM

7 Revised door swings 3/26/12 BM

BM4/16/12Revised per mark ups8

" Approx.

Top of Reinforcement Rail

7'-1"

Bottom of Traverse Rail

7'-0"

Door Height

Steel Substructure