This document includes mechanical construction plans and specifications for the renovation and expansion of a Community Living Center at the Spokane VA Medical Center, as well as information on the associated federal contract opportunity. The plans indicate the installation of mechanical piping, valves, equipment, and other components throughout the building. Piping for heating water, chilled water, steam, and other utilities are to be routed as shown. Equipment such as pumps, heat exchangers, air handlers, and humidifiers will be provided in specified locations. Access hatches must be included where required for maintenance. The solicitation is for minor construction services under contract number 36C77623B0071, issued by the Department of Veterans Affairs Technology Acquisition Center Austin. The work involves renovating and expanding the Community Living Center in Spokane, Washington.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FM
SHEET NOTES:
INSTALL GUIDES AND ANCHORS AS NECESSARY TO
SUPPORT PIPING THROUGHOUT THE BUILDING.
PROVIDE EXPANSION LOOPS IN MECHANICAL PIPING.
PROVIDE SHUTOFF VALVES AT ALL BRANCH
CONNECTIONS.
PROVIDE CONTROL VALVES FOR FAN COIL UNITS.
PROVIDE ACCESS HATCHES IN HARD CEILING FOR ALL
EQUIPMENT AS REQUIRED TO ACCESS FOR
MAINTENANCE SEE ARCHITECTURAL FOR LOCATION AND
SIZE.
AREA NOT IN SCOPE. IT IS SHOWN FOR
INFORMATION ONLY.
LIMITED MECHANICAL WORK.
1.
2.
3.
4.
5.
6.
KEY NOTES:
PROVIDE STEAM TO HOT WATER HEAT EXCHANGER
12-SWHX-1 IN 1ST FLOOR MECHANICAL ROOM 110. SEE
DETAIL #7 ON SHEET MH504 AND MECHANICAL
SCHEDULES FOR CONTINUATION.
PROVIDE HEATING WATER PUMPS 12-HWP-1 AND 12-
HWP-2 IN 1ST FLOOR MECHANICAL ROOM. SEE DETAIL #3
ON SHEET MH502 AND MECHANICAL SCHEDULES FOR
CONTINUATION.
ROUTE 4" HWS AND 4" HWR FROM HEATING WATER
PUMPS 12-HWP-1 AND 12-HWP-2 TO RESIDENT WING FAN
COILS AND 12-DOAS-1. SEE MECHANICAL DETAILS AND
SCHEDULES FOR CONTINUATION.
PROVIDE 1" LOW PRESSURE STEAM (LPS) LINE FROM 1ST
FLOOR MECHANICAL ROOM 110 TO HUMIDIFIER SECTION
OF 12-DOAS-1. SEE DETAILS ON SHEET MH504 FOR STEAM
PIPING DETAILS.
4" CHWS AND 4" CHWR TO AIR COOLED CHILLER 12-ACC-1
IN PENTHOUSE. SEE MECHANICAL SCHEDULES AND
SHEEET MP104 FOR CONTINUATION.
CONNECT EXISTING 2" HWS & EXISTING 2" HWR WHICH
SERVE THE EXISTING EAST WING BASEBOARD HEATERS
INTO THE NEW HYDRONIC HEATING HOT WATER PIPING
MAINS AT LOCATION INDICATED. ENSURE EAST WING
BASEBOARD HEATER REMAIN OPERATIONAL UPON
CONNECTION TO NEW HYDRONIC PIPING MAINS.
1.
2.
3.
4.
5.
6.
4" ø
C H
W R
4" ø
C H
W S
4" ø
H W
R
4" ø
H W
S
4"ø HWS 4"ø HWR
4"ø CHWS 4"ø CHWR
A B C D E F
G
H
J
126A
C1-10
C1-3
C1-7
C1-11
C1-2
119B
123 122A
115C
115A
109E
109D109C109A
C1-5
C1-4
2"ø HWR
2"ø HWS
TN N
PROJECT NUMBER
BUILDING
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASEARCHITECT/ENGINEER OF RECORD SEALCONSULTANTS
321 4 5 6 7 8 9 10
DWG. OF
NAME:
FULLY SPRINKLERED
CONTRACTING OFFICER'S REPRESENTATIVE
FULL SIZE DWG: 30x42
PHONE:
EMAIL:11031 S. PIKES PEAK DRIVE #102 PARKER, COLORADO 80138 PH. 303.841-3922
RENOVATE AND EXPAND
COMMUNITY LIVING
CENTER (CLC)
SPOKANE, WA
668-318
100% SUBMITTAL
CONSTRUCTION
DOCUMENTS (CD)
NORTH
SOUTH
WEST EAST
BLDG. 1
/1
2/
:0 5:
P
M
MP103
MECHANICAL PIPING - NORTH WING
APRIL 2023 CDL TJH
101 183
David Arment 509-964-1889 David.Arment@va.gov
8'0 4' 16'
SCALE:1/8"=1'-0"
SCALE: 1/8" = 1'-0"
MECHANICAL PIPING - NORTH WING1
#2
REVISIONS DATE 3 APRIL 2023
| Sheets |
| MP103 - MECHANICAL PIPING - NORTH WING |