Attachment 3 ICD 705 Door Criteria - Addl salient characteristics.pdf

Intelligence Community Directive PDF 114 KB Posted

Attached to
Specialized Acoustic Doors
Solicitation number
FA520520QB097
Issued by

View the file

Other versions and copies of ICD 705

File Revision Posted Attached to
ICD 705 Tech Specs Ver 1.5.1_26 Jul 2022PDF.pdf Version 1.5.1, Jul 26, 2022 Access Control System
Sources_Sought_ICD705_Osan_PDB_OTA_27Oct26_V1.pdf Oct 27, 2026 ICD-705 Controlled Spaces Modernization and Sustainment Program - (Progressive Design-build (PDB) Other Transaction Agreement (OTA)
ICD 705 v1.5.1 Tech_Specs_for_Construction_and_Management_of_SCIFs_v1.5.1_ July 26, 2021.pdf Jul 1, 2026 IDS/ACS System
ICD 705 v1.5.1 Tech_Specs_for_Construction_and_Management_of_SCIFs_v1.5.1_ July 26, 2021.pdf Jul 1, 2026 Request for Information - IDS/ACS System
(CUI) ICD 705 v1.5.1 Tech_Specs_for_Construction_and_Management_of_SCIFs_v1.5.1_ July 26, 2021.pdf Jul 1, 2026 Request for Information - IDS/ACS System
RFI_N40080RFI24RP00048_Souces Sought ICD 705 Space NSA Washington 01.24.2024.pdf Jan 24, 2024 REQUEST FOR INTEREST (RFI) N40080RFI24RP00048 - SOURCES SOUGHT ONLY
Attachment 5 - ICD-705-Technical-Specifications 1.4 Sep 2017.pdf Sep 4, 2017 MA MERS SCIF Door Replacement at the FEMA, MERS, VSAB, Bldg. B
USEB262315 - 5h. - ICD 705 Tech Specs.pdf Revision not stated USEB262315 - B302 ISRG Ops HVAC Increase
ICD 705 Manual.pdf Revision not stated Combo - FY26 Wargamming Secure (Vault) Door
ICD 705 Technical Specifications v1.5.1.pdf Revision not stated Maintenance SCIF Alarm Systems Recompete
ICD 705 Technical Specifications v1.5.1.pdf Revision not stated SCIF MAINTENANCE FOR MSC
CDRL-009_Ph2-ICD705ComplianceReport.pdf Revision not stated FA248624RB004- Mobile SAPF Trailer
Attachment 1a - ICD 705.pdf Revision not stated 3TES SCIF Door Installation
ICD 705.pdf Revision not stated 3TES SCIF Door Installation
ATTACH07_ICD705_Construction and Management_SCIF.PDF Revision not stated Robins AFB Mechanical/Electrical II IDIQ
ICD 705 Chapter 9 Acoustic Mitigation.pdf Revision not stated A032005 - RFI Acoustic Mitigation
ICD_705_SCIFs.pdf Revision not stated HNJ Lundy Conference Room A/V Upgrade
AppD6. ICD 705.pdf Revision not stated Install Beacon Lighting
Bidders Library Security - ICD 705.pdf Revision not stated TEC II Services RFP
Attachment 9_ICD_705_SCIFs.pdf Revision not stated Vindicator Intrusion Detection System Installation
Show all 20

Who attaches ICD 705

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Chapter 3 Fixed Facility SCIF Construction and ceiling of the vault. Seams where the steel plates meet horizontally and vertically are to be continuously welded together.

All vaults shall be equipped with a GSA-approved Class 5 vault door.

D. Floor and Ceiling Construction Criteria

1. Floors and ceilings shall be constructed to meet the same standards for force protection and acoustic protection as walls.

2. All floor and ceiling penetrations shall be kept to a minimum.

E. SCIF Door Criteria

1. There shall be only one primary SCIF entrance where visitor control is conducted.

a) Primary entrance doors shall be equipped with the following:

(1) A GSA-approved pedestrian door deadbolt meeting Federal Specification FF- L- 2890.

(2) A combination lock meeting Federal Specification FF-L 2740.

(3) An approved access-control device (see Chapter 8).

(4) May be equipped with a high security keyway for use in the event of an access control system failure.

b) With AO approval, additional entrance doors may be designated for use by SCIF residents provided that the doors are equipped with an approved access control system and are secured with an approved dead bolt or lock when the SCIF is not occupied. The dead-bolt shall not be accessible from the exterior.

(1) A GSA-approved pedestrian door egress device meeting Federal Specification FF-L-2890, specifically modified for secondary SCIF door use with no combination lock and a capability of deadlocking the access control feature after hours.

2. When practical, entrance doors should incorporate a vestibule to preclude visual observation and enhance acoustic protection.

3. All perimeter SCIF doors shall be equipped with an automatic, non-hold door-closer which shall be installed internal to the SCIF, if possible.

4. Emergency exit doors shall:

a) Be secured with deadlocking panic hardware on the inside.

(1) A GSA-approved pedestrian door meeting Federal Specification FF-L-2890, type III, specifically modified for emergency exit applications with no external hardware.

b) Have no exterior hardware.

1381576074A Highlight

1381576074A Highlight

Chapter 3 Fixed Facility SCIF Construction

c) Be alarmed 24/7.

d) Provide a local audible annunciation when opened.

5. Hinge pins that are accessible from outside of the SCIF door shall be modified to prevent removal of the door, e.g., welded, set screws, etc.

6. SCIF doors and frame assemblies shall meet acoustic requirements as described in Chapter 9 unless declared a non-discussion area.

7. All perimeter doors shall be alarmed in accordance with Chapter 7.

8. Perimeter doors shall comply with applicable building, safety, and accessibility codes and requirements.

9. Perimeter doors shall meet TEMPEST requirements when applicable.

10. Wood doors shall be 1 ¾ inch-thick solid wood core (wood stave).

11. Steel doors shall meet following specifications:

a) 1 ¾ inch-thick face steel equal to 18 gauge.

b) Hinges reinforced to 7 gauge.

c) Door closure reinforced to 12 gauge.

d) Lock area predrilled and/or reinforced to 10 gauge.

12. A vault door shall not be used to control day access to a facility. To mitigate both security and safety concerns, a vestibule with an access control device may be constructed.

13. Roll-up Door Specifications

a) A roll-up door cannot be treated for acoustics and shall only be located in an area of the SCIF that is designated as a non-discussion area.

b) Roll-up doors shall be 18 gauge steel or greater and shall be secured inside the SCIF using dead-bolts on both the right and left side of the door.

14. Double Door Specifications

a) One of the doors shall be secured at the top and bottom with deadbolts.

b) An astragal strip shall be attached to one door (could be either the secured or the movable door depending on the inward/outward swing of door assembly) to prevent observation of the SCIF through the cracks between the doors.

c) Each door shall have an independent high-security switch.

F. SCIF Window Criteria

1. Every effort should be made to minimize or eliminate windows in the SCIF, especially on the ground floor.

2. Windows shall be non-opening.