This file contains 100% design submittal drawings for electrical renovations to Hangar 9 at the Federal Aviation Administration's Mike Monroney Aeronautical Center in Oklahoma City. The comprehensive electrical design package includes six sheets covering high bay lighting demolition, new lighting installation, control details, and equipment mounting specifications. Key design elements include replacing existing metal halide high bay lighting with new LED fixtures, installing a 5kW lighting inverter, implementing new lighting control systems with relay panels and zone controls, and specifying detailed mounting methods using steel channel strut raceways and suspension systems. The drawings specify using #10 AWG wiring, provide detailed installation notes about bird netting replacement, and include requirements for coordinating power outages and work phases around active aircraft maintenance schedules.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Drawing No. AMP - 400 -lead or pm designed
WORK REQUEST NO.
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
MIKE MONRONEY AERONAUTICAL CENTER − OKLAHOMA CITY, OKLAHOMA
drawn approved by
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520. No part of this record may be disclosed to persons without a "need to know", as defined in 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR parts 15 and 1520.
ISSUED BY
OFFICE OF
facility management amp − 400 drawn d r a w in g N a m e d r a w in g N a m e
100% DESIGN SUBMITTAL - FOR CONSTRUCTION
SEAL:SEAL:
/1 /2
:2 :1 A
M A u t o d e s k D o c s /1 F A A H a n g a r
R e n o v a t io n s R /1 1_
E L E C H C F .r v t
/1 /2
:2 :1 A
M A u t o d e s k D o c s /1 F A A H a n g a r R e n o v a t io n s R /1 1_
E L E C H C F .r v t
Z. RUSH
Z. RUSH
HANGAR 9
COVER SHEET
1550021
MATTCV
07/24/23
E-001
PROJECT LOCATION
PROJECT LOCATION
VICINITY MAP LOCATION MAP
BENHAM PROJECT NO.:
WORK ORDER NO.:
WWW.BENHAM.COM
2018-021538
FEDERAL AVIATION ADMINISTRATION
HANGAR 9
1550021
FINAL SUBMITTAL
03.14.2025
SHT No SHEET NAME REV DATE
E-001 COVER SHEET 0 03/14/25
E-002 LEGEND AND ABBREVIATIONS 0 03/14/25
ED110 HIGH BAY LIGHTING DEMOLITION LIGHTING PLAN 0 03/14/25
EL110 HIGH BAY LIGHTING PLAN 0 03/14/25
E-501 LIGHTING CONTROL DETAILS 0 03/14/25
E-601 ELEVATIONS & INVERTER PANEL SCHEDULE 0 03/14/25
Grand total: 6
HANGAR 8
HANGAR 9
No. Date Description Issued by Issued to
0 03/14/25 100% DESIGN SUBMITTAL TV FAA
ABBREVIATIONS
POWER AND CONTROL PLAN SYMBOLS
ABBREVIATION DESCRIPTION
A AMPERE
ACB AIR CIRCUIT BREAKER
AF AMPERE FRAME
AFC AVAILABLE FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AIC AMPERES INTERRUPTING CAPACITY
AT AMPERE TRIP
A.T.S. AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
BKR BREAKER
C CONDUIT
CAB CABINET
CB CIRCUIT BREAKER
CCT CIRCUIT
CNTL CONTROL
COMM COMMUNICATIONS
ABBREVIATION DESCRIPTION
CONT'D CONTINUED
COR CONTRACTING OFFICER'S REPRESENTATIVE
CP CONTROL PANEL
CR CONTROL RELAY
CFL COMPACT FLUORESCE LAMP
CT CURRENT TRANSFORMER\ CERAMIC TILE\
COOLING TOWER
CU COPPER
D DIMMER\ DEEP\ DEPTH
DIST DISTRIBUTION
DT DUAL TECHNOLOGY
DWG DRAWING
ELEC ELECTRIC, ELECTRICAL
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
EO ELECTRICALLY OPERATED
EPO EMERGENCY POWER OFF
FA FIRE ALARM
ABBREVIATION DESCRIPTION
GEN GENERATOR\ GENERAL
GF GROUND FAULT
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
HID HIGH INTENSITY DISCHARGE
H-O-A HAND-OFF-AUTOMATIC SWITCH
HP HORSEPOWER
HPS HIGH PRESSURE SODIUM
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
INST INSTANTANEOUS
JB JUNCTION BOX\ JOIST BEARING
KA KILOAMPERE
KCMIL THOUSAND CIRCULAR MILLS
kV KILOVOLT kVA KILOVOLT-AMPERE kW KILOWATT
LED LIGHT-EMITTING DIODE
ABBREVIATION DESCRIPTION
LTG LIGHTING
M METER
MAINT MAINTENANCE
MAX MAXIMUM
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCS MOLDED CASE SWITCH
MH MANHOLE, METAL HALIDE
MLO MAIN LUGS ONLY
MIN MINIMUM
MOCPD MAXIMUM OVERCURRENT
PROTECTIVE DEVICE
MMS MANUAL MOTOR STARTER
MTD MOUNTED
MTR MOTOR
MTS MANUAL TRANSFER SWITCH
NF NON-FUSED, NON-FUSABLE
NEU NEUTRAL
ABBREVIATION DESCRIPTION
OH OVERHEAD\ OPPOSITE HAND
OPER OPERATOR
PB PUSHBUTTON\ PULL BOX
PC PHOTOELECTRIC CELL
PIR PASSIVE INFRARED
PNL PANEL
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE
RF RADIO FREQUENCY
PWR POWER
REM REMOTE
RGS/RMC RIGID GALVANIZED STEEL
CONDUIT
RM ROOM
SA SURGE ARRESTER
SC SPLIT CIRCUIT
SW SWITCH
SPD SURGE PROTECTION DEVICE
ABBREVIATION DESCRIPTION
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TC TERMINAL CABINET/ TIME CLOCK/
TRIP COIL
TD TIME DELAY
TGB TELECOMMUNICATIONS GROUND
BUSBAR
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLT
VFD VARIABLE FREQUENCY DRIVE
W WIRE/ WATT/ WIDTH/ WEST
W/ WITH
WP WEATHERPROOF/ WORKING POINT
XFMR TRANSFORMER
SURFACE MOUNTED PANELBOARD, MOUNT SUCH THAT TOP CIRCUIT BREAKER IS NO
MORE THAN 72" A.F.F.
FLUSH MOUNTED PANELBOARD, MOUNT SUCH THAT TOP CIRCUIT BREAKER IS NO MORE
THAN 72" A.F.F.
CONTROL CABINET
DISCONNECT SWITCH NF = NON FUSED
DENOTES SWITCH RATING
DENOTES FUSE
RATING
DRY TYPE TRANSFORMER
LIGHTING FIXTURE SYMBOLS
CEILING MOUNTED SURFACE OR
RECESSED LIGHTING FIXTURE.
LIGHTING FIXTURE, WITH INTEGRAL
EMERGENCY BATTERY PACK.
LIGHTING FIXTURE.
LIGHTING FIXTURE, WITH INTEGRAL
EMERGENCY BATTERY PACK.
EXIT LIGHTING, DARKENED SECTION(S) DENOTE FACE(S).
USE DIRECTIONAL ARROWS WHERE INDICATED.
EMERGENCY LIGHTING FIXTURE
A
A
A
A
A
A
A
A A
A
NOTES: UPPER CASE LETTER DENOTES FIXTURE TYPE. REFER TO LIGHTING FIXTURE SCHEDULE.
LOWERCASE LETTERS DENOTES LIGHTING ZONE.
CEILING WALL
A
A A
A
LIGHTING FIXTURE
A a
PANEL - CIRCUIT
LOWERCASE LETTERS DENOTED LIGHTING ZONE CONTROLS FOR ROOMS
UPPER CASE LETTER DENOTES FIXTURE TYPE
PANEL & CIRCUIT DESIGNATION
Drawing No. AMP - 400 -lead or pm designed drawn approved by
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520. No part of this record may be disclosed to persons without a "need to know", as defined in 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR parts 15 and 1520.
ISSUED BY
OFFICE OF
facility management amp − 400 drawn d r a w in g N a m e d r a w in g N a m e
100% DESIGN SUBMITTAL - FOR CONSTRUCTION
SEAL:SEAL:
/1 /2
:2 :1 A
M A u t o d e s k D o c s /1 F A A H a n g a r
R e n o v a t io n s R /1 1_
E L E C H C F .r v t
/1 /2
:2 :1 A
M A u t o d e s k D o c s /1 F A A H a n g a r R e n o v a t io n s R /1 1_
E L E C H C F .r v t
Z. RUSH
Z. RUSH
HANGAR 9
LEGEND AND ABBREVIATIONS
1550021
MATTCV
05/10/23
E-002
GENERAL NOTES
A. NOT ALL SYMBOLS USED IN THIS LEGEND ARE USED IN THIS SET OF DRAWINGS.
B. ALL ELECTRICAL WORK TO BE PER NEC AND ALL LOCAL APPLICABLE CODES AND ORDINANCES.
C. ALL CIRCUITS SHALL HAVE NEUTRAL (EXCEPT 3W, 3PH.) AND GROUNDING CONDUCTORS.
GROUNDING CONDUCTORS MAY SHARED IN ACCORDANCE WITH THE NEC. ALL SINGLE PHASE
BRANCH CIRCUITS SHALL HAVE A SEPARATE NEUTRAL. NEUTRALS SHALL NOT BE SHARED AS IN
MULTI-WIRE CIRCUITS. ALL GROUNDED CONDUCTORS SHALL BE INSULATED AND COLOR CODED
GREEN.
D. OPENINGS AROUND ELECTRICAL PENETRATIONS THROUGH FIRE RESISTANT RATED WALLS,
PARTITIONS, FLOOR OR CEILING SHALL BE FIRE STOPPED TO MAINTAIN THE FIRE RESISTANCE
RATING.
E. CONTRACTOR IS RESPONSIBLE FOR MANAGING DISPOSAL OF REMOVED LIGHTING FIXTURES. ALL
FLUORESCENT LIGHTING MUST BE RECYCLED AS UNIVERSAL WASTE THROUGH WASTE RECYCLING
BY CONTRACTOR. ALL OTHER LIGHTING AND ASSOCIATED E-WASTE MUST BE MANAGED IN
ACCORDANCE WITH CONTRACTOR'S WASTE MANAGEMENT PLAN. ANY RECOVERED PCB BALLAST
MUST BE DELIVERED TO AMP-100 FOR DISPOSAL AS HAZARDOUS WASTE.
F. UPDATE PANEL SCHEDULES (TYPED).
G. REGARDING LEAD-BASED PAINT IN THE HANGAR 9 HIGH BAY AREA, THE ROOF DECKING AND PURLIN
HAVE NOT BEEN TESTED FOR LEAD-BASED PAINT. CONTRACTOR MUST PRESUME LEAD-BASED
PAINT IS POSITIVE UNTIL TESTED. WHEN THE CONTRACTOR REMOVES BIRD NETTING, THEN THE
CONTRACTOR CAN REQUEST FAA TO TEST THE ROOF DECKING AND PURLIN FOR LEAD-BASED
PAINT. ADDITIONAL AREAS CAN BE TESTED BY FAA UPON CONTRACTOR'S REQUEST. CONTRACTOR
MUST REMOVE AND REPAIR BIRD NETTING FOR TESTING AS APPLICABLE.
H. CONTRACTOR TO PROVIDE CONEX BOX FOR STORING EQUIPMENT IF NECESSARY. CONEX BOX
COULD BE LOCATED NORTH OF H8.
PROJECT PHASING NOTES:
A. WORK IS ANTICIPATED TO BE DIVIDED UP INTO PHASES. THIS WILL BE DEPENDENT ON FAA HANGAR
AVAILABILITY. BELOW IS AN ESTIMATE FOR PLANNING PURPOSES. ACTUAL SCHEDULE WILL BE
DETERMINED BETWEEN INSTALLER AND FAA AFTER CONTRACT AWARD.
a. OBTAIN ALL MATERIALS NEEDED FOR CONSTRUCTION PHASE BEFORE STARTING THAT
WORK PHASE.
b. MOST WORK TO BE PERFORMED DURING NORMAL WORK HOURS MONDAY THROUGH
FRIDAY.
c. POWER PANEL OUTAGES MUST BE COORDINATED WITH FAA 24 HOURS IN ADVANCE.
HANGAR SCHEDULE WILL TYPICALLY ALLOW POWER PANEL OUTAGES DURING WEEKDAYS
BETWEEN 12:30AM TO 5:30AM AND ON WEEKENDS BETWEEN 3:30PM TO 5:30AM AND ON
FEDERAL HOLIDAYS. AVAILABILITY FOR POWER OUTAGES MAY VARY BASED ON HANGAR
SCHEDULE NEEDS.
d. IN THE EVENT OF SIGNIFICANT WEATHER, FAA MAY NEED TO BRING AIRCRAFT INTO HANGAR
FOR PROTECTION FROM THE WEATHER. THIS COULD INTERRUPT CONTRACTOR WORK
SCHEDULE AND AVAILABILITY OF HANGAR WORKSPACE.
e. LEAD TIME AND COORDINATION IS VERY IMPORTANT BECAUSE OF AIRCRAFT MAINTENANCE
REQUIREMENTS. SOME AIRCRAFT CANNOT BE MOVED FOR WEEKS AT A TIME.
f. PHASE 1: EIGHT WEEKS FOR INSTALLER TO PERFORM ALL WORK IN HANGAR 9 NORTH.
g. EXPECTED GAP OF 1 TO 4 WEEKS.
h. PHASE 2: EIGHT WEEKS FOR INSTALLER TO PERFORM ALL WORK IN HANGAR 9 SOUTH.
i. FOUR WEEKS FOR CLOSEOUT.
B. THIS IS FOR PLANNING PURPOSES ONLY. GAPS MAY BE LONGER AND ORDER OF HANGAR WORK
MAY BE DIFFERENT.
C. HANGAR SIDE NOT UNDER CONSTRUCTION, MUST HAVE OPERATIONAL LIGHTING DURING FAA
HANGAR WORK HOURS.
T
LIGHTING CONTROL SCHEDULE
"X" DESCRIPTION BASIS OF DESIGN (nLIGHT)
SENSOR
TYPE ROOM TYPES
05 ON/OFF SWITCH w/ DIMMING nPODMA-2P-DX-WH-BAA-SSW-1 GNG N/A HIGH BAY
LIGHT FIXTURE SCHEDULE (BASIS OF DESIGN)
TYPE
MARK DESCRIPTION MANUFACTURER MODEL #
LAMPS CCT
VOLTAGE
COLOR
TEMPERATURE VA REMARKS AND MOUNTINGLUMENS TYPE
H HIGH BAY LED METALUX BAA-BMK-70-WCL-UNV-L850-CD-SHK C3(1) 70000 LED 277 5000K 500 MATCH EX. MOUNTING APPROX. 38 FT. PROVIDE
SAFETY LOOP CABLE AND NEMA L7-20P
HE HIGH BAY LED ON INVERTER METALUX SAME AS TYPE H 70000 LED 277 5000K 500 MATCH EX. MOUNTING APPROX. 38 FT. PROVIDE
SAFETY LOOP CABLE AND NEMA L7-20P
No. Date Description Issued by Issued
BCDEFGHL J
TYPICAL TANDEM FIXTURE
HIGH BAY
LIGHTS SOURCE
1N4FA-1
1N4FA-2
TYPICAL TANDEM EMERGENCY FIXTURE
W110
W108
1N2FA-1
1N2FA-2
1N2FA-3
FAN CONTROLS
1E4A
DEMOLISH EXISTING
CONTROL DEVICE
MECHANICAL
109AW
Drawing No. AMP - 400 -lead or pm designed drawn approved by
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520. No part of this record may be disclosed to persons without a "need to know", as defined in 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR parts 15 and 1520.
ISSUED BY
OFFICE OF
facility management amp − 400 drawn d r a w in g N a m e d r a w in g N a m e
100% DESIGN SUBMITTAL - FOR CONSTRUCTION
SEAL:SEAL:
/1 /2
:2 :1 A
M A u t o d e s k D o c s /1 F A A H a n g a r
R e n o v a t io n s R /1 1_
E L E C H C F .r v t
/1 /2
:2 :1 A
M A u t o d e s k D o c s /1 F A A H a n g a r R e n o v a t io n s R /1 1_
E L E C H C F .r v t
Z. RUSH
Z. RUSH
HANGAR 9
HIGH BAY LIGHTING DEMOLITION LIGHTING PLAN
1550021
MATTCV
05/10/23
ED110
SCALE IN FEET - 1/16" = 1'-0"
16' 8' 0' 16' 48'32'
1/16" = 1'-0"1
HIGH BAY LIGHTING DEMOLITION PLAN - COMPOSITE
GENERAL NOTES
A. DEMOLISH ALL HIGH BAY LIGHT FIXTURES UNLESS OTHERWISE NOTED. DEMOLISH
CORRESPONDING CONDUITS, LIGHTING CONTROL DEVICES, AND BRANCH CIRCUIT CONDUCTORS
BACK TO SOURCE.
B. HIGH BAY FIXTURES ARE METAL HALIDE AND LOCATED AT APPROX. 38' AFF.
BIRD NETTING NOTES:
A. DEMOLISH ALL BIRD NETTING (APPROX. 38' AFF) FOR DEMOLITION AND INSTALLATION OF NEW
EQUIPMENT. DO NOT REUSE BIRD NETTING. CONTRACTOR TO INSTALL NEW BIRD NETTING.
B. UPON COMPLETION OF THIS PROJECT THE BIRD NETTING INSTALLATION MUST BE OF EQUAL OR
BETTER QUALITY AS EXISTING.
C. FAA TO INSPECT BIRD NETTING PRIOR TO ACCEPTANCE.
D. EACH LIGHT FIXTURE MUST HAVE BIRD ZIPPER INSTALLED BENEATH IT. UNLESS NOTED
OTHERWISE.
a. PLACEMENT: CENTER ZIPPER BELOW LIGHT FIXTURE INSTALLED BENEATH EACH LIGHT
FIXTURE.
b. DO NOT REUSE EXISTING BIRD NET ZIPPERS. CONTRACTOR TO INSTALL NEW BIRD NET
ZIPPERS.
c. BIRD NET ZIPPERS TO BE ATTACHED DIRECTLY TO THE NETTING WITH HOG RINGS USING A
HOG RING TOOL.
d. MATERIAL TO USE:
a. NIXALITE K-NET HT BIRD NETTING 3/4 INCH SQUARE MESH.
b. NIXALITE BIRD NET ZIPPER BLACK, 6 FEET LONG.
e. INSTALL ZIPPER IN ACCORDANCE WITH MANUFACTURER INSTRUCTIONS AND
SPECIFICATIONS.
000 KEYED NOTES:
1. DEMOLISH EMERGENCY HIGH BAY LIGHTING DISCONNECT. FED FROM
PANEL 1E4A, FIELD VERIFY CIRCUITS.
2. DEMOLISH ELECTRICAL BUSWAY AND ASSOCIATED CONDUITS, WIRING,
AND SUPPORTS.
N
SECTOR 2
SECTOR 1 SECTOR 3
SECTOR 4
HIGH BAY
No. Date Description Issued by Issued
BCDEFGHL J
H H H H
H
HE HE
H
H H H H
H H H
H
H H H H
H HE HE
H
H H H H
H H H H
H HE HE H
H H H H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
1N4FA-2
1N4FA-1
a b c d
1E4A
MECHANICAL
109AW
1N2FA-1
1N2FA-2
1N2FA-3
1N2F
110W
108W
E-601
1INVA- 3 1INVA- 3
1INVA- 4 1INVA- 4
1INVA- 5 1INVA- 5
1INVA
"d" CONTROL ZONE"c" CONTROL ZONE
"a" CONTROL ZONE "b" CONTROL ZONE a b c d a b c d a b c d
1N4FA-1- 2 1N4FA-1- 2 1N4FA-1- 2 1N4FA-1- 1 1N4FA-1- 1 1N4FA-1- 1
1N4FA-1- 2 1N4FA-1- 4 1N4FA-1- 1 1N4FA-1- 3
1N4FA-1- 4 1N4FA-1- 4 1N4FA-1- 4 1N4FA-1- 3 1N4FA-1- 3 1N4FA-1- 3
1N4FA-1- 6 1N4FA-1- 6 1N4FA-1- 6 1N4FA-1- 5 1N4FA-1- 5 1N4FA-1- 5
1N4FA-1- 7 1N4FA-1- 7 1N4FA-1- 9 1N4FA-1- 9
1N4FA-2- 8 1N4FA-2- 8 1N4FA-2- 8 1N4FA-2- 7 1N4FA-2- 7 1N4FA-2- 7
1N4FA-2- 6 1N4FA-2- 6 1N4FA-2- 6 1N4FA-2- 5 1N4FA-2- 5 1N4FA-2- 5
1N4FA-2- 4 1N4FA-2- 4 1N4FA-2- 4 1N4FA-2- 3 1N4FA-2- 3 1N4FA-2- 3
1N4FA-2- 2 1N4FA-2- 4 1N4FA-2- 1 1N4FA-2- 3
1N4FA-2- 2 1N4FA-2- 2 1N4FA-2- 2 1N4FA-2- 1 1N4FA-2- 1 1N4FA-2- 1
147E
141E
101E
105W
119W
111W
113W
INSTALL RELAY
PANEL WITHIN
THIS SPACE
10' - 0" 6' - 0" 10' - 0"
1' - 4"
12' - 0" 12' - 0" 6' - 0" 12' - 0" 12' - 0" 6' - 0" 12' - 0" 12' - 0" 6' - 0" 12' - 0" 6' - 0" 12' - 0" 12' - 0" 6' - 0"12' - 0"
1' - 4"
FIELD
VERIFY
7'
8'
7'
5'
4'
8'
2'
6'
2'
7'
7'
(17-SPACES)
(17-SPACES)
(17-SPACES)
(17-SPACES)
(17-SPACES)
(17-SPACES)
(17-SPACES)
(17-SPACES)
(17-SPACES)
(17-SPACES)
Drawing No. AMP - 400 -lead or pm designed drawn approved by
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520. No part of this record may be disclosed to persons without a "need to know", as defined in 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR parts 15 and 1520.
ISSUED BY
OFFICE OF
facility management amp − 400 drawn d r a w in g N a m e d r a w in g N a m e
100% DESIGN SUBMITTAL - FOR CONSTRUCTION
SEAL:SEAL:
/1 /2
:2 :2
A
M A u t o d e s k D o c s /1 F A A H a n g a r
R e n o v a t io n s R /1 1_
E L E C H C F .r v t
/1 /2
:2 :2
A
M A u t o d e s k D o c s /1 F A A H a n g a r R e n o v a t io n s R /1 1_
E L E C H C F .r v t
Z. RUSH
Z. RUSH
HANGAR 9
HIGH BAY LIGHTING PLAN
1550021
MATTCV
05/10/23
EL110
SCALE IN FEET - 1/16" = 1'-0"
16' 8' 0' 16' 48'32'
1/16" = 1'-0"1
HIGH BAY LIGHTING PLAN
N
SECTOR 2
SECTOR 1 SECTOR 3
SECTOR 4
HIGH BAY
GENERAL NOTES
A. USE #10AWG WIRE FOR HIGH BAY LIGHTING CIRCUITS. RUN WIRING IN
CHANNEL STRUT RACEWAY. PROVIDE NEW CONDUITS AS NECESSARY.
B. CIRCUITING SHOWN IS FOR REFERENCE ONLY. FIELD VERIFY EXACT
CIRCUITING. INSTALL OF NEW CIRCUITING MAY DIFFER, MAX OF 4 LIGHTS ON A
SINGLE CIRCUIT.
C. CIRCUIT HIGH BAY FIXTURES TO EXISTING BREAKERS FROM SAME SOURCE AS
DEMOLISHED LIGHTS.
D. PROVIDE NEW CONDUIT FOR DIMMING CONTROLS. 0-10V CONTROL WIRING
SHALL BE MINIMUM 12 AWG, SHIELDED CABLE THHN.
E. CONTRACTOR SHALL SUBMIT STEEL FRAMING SUPPORT SHOP DRAWINGS FOR
REVIEW. ALL SHOP DRAWINGS SHALL BE REVIEWED AND STAMPED BY THE
CONTRACTOR AND STEEL FRAMING CHANNEL STRUT MANUFACTURER PRIOR
TO SUBMITTING FOR REVIEW.
KEYED NOTES:
1. 5KW LIGHTING INVERTER. CIRCUIT TO NEW 1P30A BREAKER IN EXISTING PANEL
1E4A. REFER TYPICAL EQUIPMENT PAD DETAIL SHEET E-601 FOR MOUNTING
DETAIL.
2. EXISTING METASYS PANEL IS IN THIS ROOM.
3. PROVIDE ONE "05" CONTROL DEVICE PER 2 ZONES. INSTALL STARTING 6" FROM
DOOR AND 48" AFF. EITHER SIDE OF SPECIFIED DOOR IS ACCEPTABLE.
4. PROVIDE CONTINUOUS HORIZONTAL STEEL FRAMING CHANNEL STRUT LISTED
FOR USE AS ELECTRICAL RACEWAY, (UNITSTRUT P1000 OR EQUAL) INSTALL
CHANNEL STRUT AT THE SAME ELEVATION AS REMOVED BUSWAY.
A. PROVIDE SNAP-IN COVER (GREY) FOR THE ENTIRE LENGTH OF THE
CHANNEL STRUT RACEWAY.
B. PROVIDE ALL ACCESSORIES REQUIRED FOR A COMPLETE LIGHT
SUPPORT SYSTEM, REFER TO DETAIL 5 ON SHEET E-601 FOR ADDITIONAL
INFORMATION AND REQUIREMENTS.
5. PROVIDE 3/8" DIAMETER HANGER RODS (ASTM A36) AND LOCATE AS SHOWN ON
PLAN AND DETAIL 5 ON SHEET E-601. HANGAR RODS SHALL BE LOCATED
HORIZONTALLY WITHIN 4 INCHES OF A STEEL JOIST PANEL POINT. ROOF
ELEVATION OF HANGAR BAY VARIES, PEAK ELEVATION OF HANGAR BAY IS
APPOX. 67'-0" ABOVE FINISH FLOOR.
LIGHTING CONTROL NOTES:
A. SIX EMERGENCY LIGHTS EXCLUDED FROM ZONE CONTROLS AND ARE AT
100% BRIGHTNESS, 24/7.
No. Date Description Issued by Issued
Drawing No. AMP - 400 -lead or pm designed drawn approved by
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520. No part of this record may be disclosed to persons without a "need to know", as defined in 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR parts 15 and 1520.
ISSUED BY
OFFICE OF
facility management amp − 400 drawn d r a w in g N a m e d r a w in g N a m e
100% DESIGN SUBMITTAL - FOR CONSTRUCTION
SEAL:SEAL:
/1 /2
:2 :1 A
M A u t o d e s k D o c s /1 F A A H a n g a r
R e n o v a t io n s R /1 1_
E L E C H C F .r v t
/1 /2
:2 :1 A
M A u t o d e s k D o c s /1 F A A H a n g a r R e n o v a t io n s R /1 1_
E L E C H C F .r v t
Z. RUSH
Z. RUSH
HANGAR 9
LIGHTING CONTROL DETAILS
1550021
MATTCV
11/14/23
E-501
NTS
LIGHTING CONTROL DIAGRAM - RELAY PANEL
NTS
TYPICAL LIGHTING CONTROL DIAGRAM - SWITCHES
#10 AWG
#12 AWG MINIMUM
NOTES:
1. RELAY PANEL B.O.D. - ACUITY BRANDS
A. MODEL # ARP INTENC16 NLT 16FCR MVOLT SM
2. USE FOUR RELAYS PER ZONE.
3. CONNECT ONE CIRCUIT TO ONE RELAY.
4. MAX OF FOUR LIGHTS CONNECTED TO ONE CIRCUIT.
5. CIRCUIT RELAY PANEL TO EXISTING 1P20A BREAKER IN PANEL "1E4A".
NOTES:
A. PROVIDE ADHESIVE TEXT LABEL FOR WHICH ZONE IT
CONTROLS. NE, NW, ETC.
No. Date Description Issued by Issued
PANEL 1E4A
480Y/277V
1INVA
5 KW
277V
2#10, 1#10G., 3/4"C
NEW 1P30A BREAKER
IN EXISTING EATON
POW-R-LINE PANEL
1ST FLOOR
EXISTING WATER PIPES
PROVIDE HOSE TO NEARBY
DRAIN
DRIP PAN SIZED 2" LARGER
THAN INVERTER ON EACH SIDE
ADDITIONAL NOTE:
CONTRACTOR TO ATTACH DRIP PAN TO THE WALL IN A MANNER THAT THE ATTACHMENT
POINT DOES NOT FAIL IN THE EVENT THE DRAIN CLOGS AND THE PAN FILLS WITH WATER.
INSTALL TENSION WIRE OR SIMILAR FROM THE CANTILEVERED END OF THE DRIP PAN
BACK TO THE WALL AT AN ANGLE TO PROVIDE ADDITIONAL SUPPORT.
1INVA
EQUIPMENT
PAD
SAFETY CABLE
PENDANT MOUNTED HIGH
BAY LIGHT FIXTURE.
MOUNTING HEIGHT AS
SHOWN ON FIXTURE
MOUNTING SCHEDULE.
NOTES:
CONTROL WIRING CONDUIT MAY BE
SUPPORTED BY THE STEEL FRAMING
CHANNEL OR BY THE STRUCTURE.
HOLES ARE NOT PERMITTED IN STEEL
FRAMING CHANNEL UNLESS APPROVED
BY OWNER.
2 TO 6" (TYP.)
BIRD NETTING
CONTINUOUS CHANNEL
STRUT RACEWAY, SEE PLAN
FIXTURE HANGER WITH
SWIVEL (UNISTRUT
P2755, M2350 OR EQ.)
3/8" DIAMETER THREADED ROD
BAR JOIST HANGER (CADDY
ROD LOCK BAR JOIST HANGER
BY NVENT OR EQUAL), TYP.
CHANNEL MOUNTED
OUTLET BOX (UNI. P2567)
PROVIDE NEMA L7-20R.
1/2" FMC FOR
DIMMING WIRES
EXIST. STEEL
ROOF DECK
3/4" EMT FOR
DIMMING WIRES
FACTORY-ASSEMBLED
CORD. PROVIDE NEMA
L7-20P.
EXIST. STEEL
ROOF JOIST, TYP.
SUPPORT STEEL FRAMING CHANNEL FROM THE ROOF
PURLINS DIRECTLY ADJACENT TO LIGHT FIXTURES, TYP.
6'-0"± MAX SPAN FOR CHANNEL
STRUT RACEWAY AT LIGHT
FIXTURE LOCATIONS, SEE PLAN
SWIVEL HANGER
(UNISTRUT M2037 OR
EQUAL) WITH 600 LBS LOAD
RATING AND REQUIRED
HARDWARE TYP.
3/8" DIA, HANGER
ROD, TYP.
PROVIDE PLATE WASHER
(UNISTRUT P1063 OR EQUAL),
LOCKING NUT AND HEX NUT
ABOVE AND BELOW, TYP.
12'-0"± MAX SPAN FOR CHANNEL
STRUT RACEWAY BETWEEN LIGHT
FIXTURE LOCATIONS, SEE PLAN
ELEVATION VIEW
CHANNEL HANGER (UNISTRUT
P2855 OR EQUAL)
END CAP (UNISTRUT
P#2860 OR EQUAL)
Drawing No. AMP - 400 -lead or pm designed drawn approved by
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520. No part of this record may be disclosed to persons without a "need to know", as defined in 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR parts 15 and 1520.
ISSUED BY
OFFICE OF
facility management amp − 400 drawn d r a w in g N a m e d r a w in g N a m e
100% DESIGN SUBMITTAL - FOR CONSTRUCTION
SEAL:SEAL:
/1 /2
:2 :1 A
M A u t o d e s k D o c s /1 F A A H a n g a r
R e n o v a t io n s R /1 1_
E L E C H C F .r v t
/1 /2
:2 :1 A
M A u t o d e s k D o c s /1 F A A H a n g a r R e n o v a t io n s R /1 1_
E L E C H C F .r v t
Z. RUSH
Z. RUSH
HANGAR 9
ELEVATIONS & INVERTER PANEL SCHEDULE
1550021
MATTCV
05/02/23
E-601
INVERTER NOTES:
A. INVERTER 5KW SPECIFICATIONS AS FOLLOWS:
a. 277V, 1-PHASE
b. MINIMUM 90-MINUTE RUNTIME
c. MINIMUM 8 CIRCUIT OUTPUT BREAKERS. NORMALLY ON.
d. MYERS ILLUMINATOR SERIES, ISOLITE OR EQUAL
e. INTEGRATED SELF DIAGNOSTICS 2-EA STATUS MONITORING DRY FORM C
CONTACTS
B. CONNECT INVERTER TO NEAREST METASYS PANEL IN MECH ROOM 109AW,
WIRING IN 3/4" CONDUIT. PROVIDE ALARM FUNCTION TO CCMS IF THE INVERTER
HAS ANY ACTIVE ALARM. THIS CAN BE A SINGULAR ALARM ON CCMS TO
REPRESENT ANY ACTIVE ALARM FROM THE INVERTER 1INVA-H9-WEST. PROVIDE
UPDATE TO METASYS SCREEN GRAPHICS TO ILLUSTRATE INVERTER STATUS. IN
THE OTHER DRAWING PACKAGE, MORE INVERTERS WILL BE ADDED FOR
DIFFERENT HANGAR FLOORS. MAKE THE SCREEN GRAPHICS COMPATIBLE FOR
INVERTER ADDITIONS. THE ALARM SHOULD INDICATE WHICH INVERTER IS IN
ALARM, BUT IT DOES NOT NEED TO DISTINGUISH WHAT THE SPECIFIC ALARM IS
SAYING. THE ALARM STATUS FOR EACH INVERTER CAN BE NORMAL OR ALARM
ON THE METASYS SCREEN GRAPHICS. CONTRACT WITH JCI FOR METASYS WORK.
C. EMERGENCY LIGHTS SHALL COME ON AT 100% BRIGHTNESS IF NORMAL POWER
FAILS, REGARDLESS OF SWITCH POSITION.
NTS2
INVERTER ELEVATION RM 109AW
NTS3
HIGH BAY MOUNTING DETAIL
No. Date Description Issued by Issued to
0 03/14/25 100% DESIGN SUBMITTAL TV FAA
NTS4
TYPICAL EQUIPMENT PAD DETAIL
| Sheets |
| E-001 - COVER SHEET |
| E-002 - LEGEND AND ABBREVIATIONS |
| ED110 - HIGH BAY LIGHTING DEMOLITION LIGHTING PLAN |
| EL110 - HIGH BAY LIGHTING PLAN |
| E-501 - LIGHTING CONTROL DETAILS |
| E-601 - ELEVATIONS & INVERTER PANEL SCHEDULE |