Attachment 1d Amended Specifications_Am01_6.17.25.pdf

PDF 508 KB Posted

Attached to
Solicitation - Hanger 9 Renovation at the Mike Monroney Aeronautical Center (MMAC), Oklahoma City, OK
Solicitation number
6973GH-25-R-00132
Issued by

About this file

These are technical specifications for the renovation of Hangar 9 at the FAA Mike Monroney Aeronautical Center, covering multiple sections including plastic-laminate architectural cabinets, phenolic-core toilet compartments, wall and door protection, and electrical systems commissioning. The specifications provide detailed requirements for construction materials, installation methods, quality standards, and testing procedures for various building components. Key sections include guidelines for cabinets using high-pressure decorative laminate, toilet compartment construction with phenolic-core panels, metal corner guards, and comprehensive electrical system commissioning protocols. The documents represent Amendment 01, which includes modifications such as removing AWI certification requirements, clarifying stainless steel finish for brackets, changing corner guard height specifications, and adding lighting controls to commissioning activities.

View the file

Other files

File Type Posted
6973GH-25-R-00132 Amend0009.pdf PDF
6973GH-25-R-00132 Amend0008.pdf PDF
6973GH-25-R-00132 Amend0007.pdf PDF
Attachment 1f Amended Specifications_Am02_6.26.25.pdf PDF
QA Log - Answers - 25-R-00132 H9 Reno 7.7.25 Final.pdf PDF
6973GH-25-R-00132 Amend0006.pdf PDF
Attachment 1e Revised.Additional Drawings Hangar 9 Renovation_6.26.2025.pdf PDF
6973GH-25-R-00132 Amend0005.pdf PDF
QA Log.2 25-R-00132 H9 Reno 6.30.25.pdf PDF
Attachment 12 Furniture Equipment Moving Diagram Hangar 9 6.17.25.pdf PDF
6973GH-25-R-00132 Amend0004.pdf PDF
Attachment 1c Revised.Additional Drawings Hangar 9 Renovation_6.17.2025.pdf PDF
6973GH-25-R-00132 Amend0003.pdf PDF
6973GH-25-R-00132 Amend0002.pdf PDF
6973GH-25-R-00132 Amend0001.pdf PDF
Attendance List Hanger 9 May 20 Site Visit.pdf PDF
QA Log.1 25-R-00132 H9 Reno 5.16.25.pdf PDF
6973GH-25-R-00132.pdf PDF
Attachment 9 Contractor Release.pdf PDF
Attachment 1b Hangar_9_High_Bay_Lights_100_Drawings.3.14.2025.pdf PDF
Attachment 4 SF25A Payment Bond.pdf PDF
Attachment 10 AMP400-ENV-OC-2.4.3-CC.pdf PDF
Attachment 5 SF24 Bid Bond.pdf PDF
Attachment 2 Wage Determination OK20250049 03.14.2025.pdf PDF
Attachment 1 Hangar 09_Combined Specs_3.14.2025.pdf PDF
Attachment 11 Chapter 33 Construction Safety.pdf PDF
Attachment 6 Past Performance Survey 4.23.25.docx DOCX document
Attachment 1a Hangar 9_Renovation_100_Drawings_3.14.2025.pdf PDF
Attachment 8 Client Authorization Letter.docx DOCX document
Attachment 7 Past Performance Experience Form.docx DOCX document
Attachment 3 SF25 Performance Bond.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Technical Specifications 100% Design_Am01 FAA Hangar 09 (Building #10) Work Order 6973GH-22-F-01701 Building Renovations

PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS 064116 - 1

SECTION 064116 - PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS

Amendment 01 Description – Removes AWI Certification Requirements. Removes Butt Hinges from scope; Frameless Concealed Hinges to be used at all locations.

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Plastic-laminate-clad architectural cabinets.

B. Related Requirements:

1. Section 061000 "Rough Carpentry" for wood furring, blocking, shims, and hanging strips required for installing cabinets that are concealed within other construction before cabinet installation.

2. Section 123661.16 "Solid Surfacing Countertops."

1.2 COORDINATION

A. Coordinate sizes and locations of framing, blocking, furring, reinforcements, and other related units of Work specified in other Sections to support loads imposed by installed and fully loaded cabinets.

1.3 ACTION SUBMITTALS

A. Product Data:

1. Plastic-laminate-clad architectural cabinets.

B. Product Data Submittals: For each product.

1. Include data for fire-retardant treatment from chemical-treatment manufacturer and certification by treating plant that treated materials comply with requirements.

C. Shop Drawings:

1. Include plans, elevations, sections, and attachment details.

2. Show large-scale details.

3. Show locations and sizes of furring, blocking, and hanging strips, including concealed blocking and reinforcement specified in other Sections.

4. Show locations and sizes of cutouts and holes for items installed in plastic-laminate architectural cabinets.

5. Apply AWI Standards to Shop Drawings.

PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS 064116 - 2

D. Samples: For each exposed product and for each color and texture specified, in manufacturer's or manufacturer's standard size.

E. Samples for Initial Selection: For each type of exposed finish.

F. Samples for Verification: For the following:

1. Plastic Laminates: 8 by 10 inches for each type, color, pattern, and surface finish required.

a. Provide one sample applied to core material with specified edge material applied to one edge.

2. Corner Pieces:

a. Cabinet-front frame joints between stiles and rails and at exposed end pieces, 18 inches high by 18 inches wide by 6 inches deep.

b. Miter joints for standing trim.

3. Exposed Cabinet Hardware and Accessories: One full-size unit for each type and finish.

1.4 CLOSEOUT SUBMITTALS

A. Quality Standard Compliance Certificates.

1.5 QUALITY ASSURANCE

A. Manufacturer's Qualifications: Employs skilled workers who custom fabricate products similar to those required for this Project and whose products have a record of successful in-service performance.

B. Mockups: Build mockups to verify selections made under Sample submittals, to demonstrate aesthetic effects, and to set quality standards for materials and execution.

1. Build mockups of typical architectural cabinets as shown on Drawings.

2. Subject to compliance with requirements, approved mockups may become part of the completed Work if undisturbed at time of Substantial Completion.

1.6 DELIVERY, STORAGE, AND HANDLING

A. Do not deliver cabinets until painting and similar finish operations that might damage architectural cabinets have been completed in installation areas. Store cabinets in installation areas or in areas where environmental conditions comply with requirements specified in "Field Conditions" Article.

PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS 064116 - 3

1.7 FIELD CONDITIONS

A. Environmental Limitations without Humidity Control: Do not deliver or install cabinets until building is enclosed, wet-work is complete, and HVAC system is operating and maintaining temperature and relative humidity at levels planned for building occupants during the remainder of the construction period.

B. Environmental Limitations with Humidity Control: Do not deliver or install cabinets until building is enclosed, wet-work is complete, and HVAC system is operating and maintaining temperature between 60 and 90 deg F and relative humidity between 25 and 55 percent during the remainder of the construction period.

C. Field Measurements: Where cabinets are indicated to fit to other construction, verify dimensions of other construction by field measurements before fabrication, and indicate measurements on Shop Drawings. Coordinate fabrication schedule with construction progress to avoid delaying the Work.

1. Locate concealed framing, blocking, and reinforcements that support cabinets by field measurements before being enclosed/concealed by construction, and indicate measurements on Shop Drawings.

D. Established Dimensions: Where cabinets are indicated to fit to other construction, establish dimensions for areas where cabinets are to fit. Provide allowance for trimming at site, and coordinate construction to ensure that actual dimensions correspond to established dimensions.

PART 2 - PRODUCTS

2.1 PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS: HPL-1

A. Quality Standard: Unless otherwise indicated, comply with the Architectural Woodwork Standards for grades of cabinets indicated for construction, finishes, installation, and other requirements.

1. Provide labels and certificates indicating that woodwork and installation complies with requirements of grades specified.

2. The Contract Documents contain requirements that are more stringent than the referenced quality standard. Comply with requirements of Contract Documents in addition to those of the referenced quality standard.

B. Architectural Woodwork Standards Grade: Premium.

C. Type of Construction: Face frame.

D. Door and Drawer-Front Style: Reveal overlay.

1. Reveal Dimension: 1/2 inch.

PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS 064116 - 4

E. High-Pressure Decorative Laminate: ISO 4586-3, grades as indicated or if not indicated, as required by quality standard.

1. Manufacturers: Subject to compliance with requirements, provide products by the following:

a. Wilsonart LLC.

1) High Pressure Laminate: #8235K-05, Daintree

F. Exposed Surfaces:

1. Plastic-Laminate Grade: HGS.

2. Edges: Grade HGS

3. Pattern Direction: Vertically for drawer fronts, doors, and fixed panels.

G. Semiexposed Surfaces:

1. Surfaces Other Than Drawer Bodies: High-pressure decorative laminate, ISO 4586-3.

a. Edges of Plastic-Laminate Shelves: PVC tape, 0.018-inch minimum thickness, matching laminate in color, pattern, and finish.

b. Edges of Thermally Fused Laminate Panel Shelves: PVC or polyester edge banding.

c. For semiexposed backs of panels with exposed plastic-laminate surfaces, provide surface of high-pressure decorative laminate, ISO 4586-3, grade to match exposed surface.

2. Drawer Sides and Backs: Thermoset decorative panels with PVC or polyester edge banding.

3. Drawer Bottoms: Thermoset decorative panels.

H. Dust Panels: 1/4-inch plywood or tempered hardboard above compartments and drawers unless located directly under tops.

I. Concealed Backs of Panels with Exposed Plastic-Laminate Surfaces: High-pressure decorative laminate, ISO 4583-3, grade to match exposed surface.

J. Drawer Construction: Fabricate with exposed fronts fastened to subfront with mounting screws from interior of body.

1. Join subfronts, backs, and sides with glued rabbeted joints supplemented by mechanical fasteners.

K. Colors, Patterns, and Finishes: Provide materials and products that result in colors and textures of exposed laminate surfaces complying with the following requirements:

1. Match Architect's sample.

2.2 WOOD MATERIALS

A. Wood Products: Provide materials that comply with requirements of referenced quality standard for each type of architectural cabinet and quality grade specified unless otherwise indicated.

PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS 064116 - 5

1. Wood Moisture Content: 8 to 13 percent.

B. Composite Wood Products: Provide materials that comply with requirements of referenced quality standard for each type of architectural cabinet and quality grade specified unless otherwise indicated.

1. Medium-Density Fiberboard (MDF): ANSI A208.2, Grade 130.

2. Particleboard (Medium Density): ANSI A208.1, Grade M-2.

3. Softwood Plywood: DOC PS 1, medium-density overlay.

2.3 FIRE-RETARDANT-TREATED MATERIALS

A. Fire-Retardant-Treated Materials, General: Where fire-retardant-treated materials are indicated, use materials that are acceptable to authorities having jurisdiction and with fire-test-response characteristics specified as determined by testing identical products in accordance with test method indicated by a qualified testing agency.

1. Use treated materials that comply with requirements of referenced quality standard. Do not use materials that are warped, discolored, or otherwise defective.

2. Use fire-retardant-treatment formulations that do not bleed through or otherwise adversely affect finishes. Do not use colorants to distinguish treated materials from untreated materials.

3. Identify fire-retardant-treated materials with appropriate classification marking of qualified testing agency in the form of removable paper label or imprint on surfaces that will be concealed from view after installation.

B. Fire-Retardant-Treated Lumber and Plywood: Products with a flame-spread index of 25 or less when tested in accordance with ASTM E84, with no evidence of significant progressive combustion when the test is extended an additional 20 minutes, and with the flame front not extending more than 10.5 feet beyond the centerline of the burners at any time during the test.

1. Kiln-dry lumber and plywood after treatment to a maximum moisture content of 19 and 15 percent, respectively.

2. For items indicated to receive a stained or natural finish, use organic resin chemical formulation.

3. Mill lumber after treatment within limits set for wood removal that do not affect listed fire-test-response characteristics, using a woodworking shop certified by testing and inspecting agency.

4. Mill lumber before treatment and implement procedures during treatment and drying processes that prevent lumber from warping and developing discolorations from drying sticks or other causes, marring, and other defects affecting appearance of architectural cabinets.

C. Fire-Retardant Particleboard: Made from softwood particles and fire-retardant chemicals mixed together at time of panel manufacture to achieve flame-spread index of 25 or less and smoke-developed index of 25 or less in accordance with ASTM E84.

1. For panels 3/4 inch thick and less, comply with ANSI A208.1 for Grade M-2 except for the following minimum properties: modulus of rupture, 1600 psi; modulus of elasticity, PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS 064116 - 6

300,000 psi; internal bond, 80 psi; and screw-holding capacity on face and edge, 250 and 225 lbf, respectively.

2. For panels 13/16 to 1-1/4 inches thick, comply with ANSI A208.1 for Grade M-1 except for the following minimum properties: modulus of rupture, 1300 psi; modulus of elasticity, 250,000 psi; linear expansion, 0.50 percent; and screw-holding capacity on face and edge, 250 and 175 lbf, respectively.

D. Fire-Retardant Fiberboard: MDF panels complying with ANSI A208.2, made from softwood fibers, synthetic resins, and fire-retardant chemicals mixed together at time of panel manufacture to achieve flame-spread index of 25 or less and smoke-developed index of 200 or less in accordance with ASTM E84.

2.4 CABINET HARDWARE AND ACCESSORIES

A. Cabinet Hardware: Provide cabinet hardware and accessory materials associated with architectural cabinets.

B. Frameless Concealed Hinges (European Type): ANSI/BHMA A156.9, B01602, 135 degrees of opening, self-closing.

C. Wire Pulls: Back mounted, solid metal, 4 inches long, 5/16 inch in diameter.

D. Shelf Rests: ANSI/BHMA A156.9, B04013; metal.

E. Drawer Slides: ANSI/BHMA A156.9.

1. Standard Duty (Grade 1 and Grade 2): Side mount.

a. Type: Full extension.

b. Material: Epoxy-coated steel with polymer rollers.

F. Door and Drawer Silencers: ANSI/BHMA A156.16, L03011.

G. Exposed Hardware Finishes: For exposed hardware, provide finish that complies with ANSI/BHMA A156.18 for ANSI/BHMA finish number indicated.

1. Satin Chromium Plated: ANSI/BHMA 626 for brass or bronze base; ANSI/BHMA 652 for steel base.

H. For concealed hardware, provide manufacturer's standard finish that complies with product class requirements in ANSI/BHMA A156.9.

2.5 MISCELLANEOUS MATERIALS

A. Furring, Blocking, Shims, and Hanging Strips: kiln-dried to less than 15 percent moisture content.

B. Anchors: Select material, type, size, and finish required for each substrate for secure anchorage.

Provide metal expansion sleeves or expansion bolts for post-installed anchors. Use nonferrous-metal or hot-dip galvanized anchors and inserts at inside face of exterior walls and at floors.

PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS 064116 - 7

C. Adhesive for Bonding Plastic Laminate: as selected by fabricator to comply with requirements.

2.6 FABRICATION

A. Fabricate architectural cabinets to dimensions, profiles, and details indicated.

B. Complete fabrication, including assembly and hardware application, to maximum extent possible before shipment to Project site. Disassemble components only as necessary for shipment and installation. Where necessary for fitting at site, provide ample allowance for scribing, trimming, and fitting.

1. Notify Architect seven days in advance of the dates and times architectural cabinet fabrication will be complete.

2. Trial fit assemblies at manufacturer's shop that cannot be shipped completely assembled.

Install dowels, screws, bolted connectors, and other fastening devices that can be removed after trial fitting. Verify that various parts fit as intended and check measurements of assemblies against field measurements before disassembling for shipment.

C. Shop-cut openings to maximum extent possible to receive hardware, appliances, electrical work, and similar items. Locate openings accurately and use templates or roughing-in diagrams to produce accurately sized and shaped openings. Sand edges of cutouts to remove splinters and burrs.

EXECUTION

2.7 PREPARATION

A. Before installation, condition cabinets to humidity conditions in installation areas for not less than 72 hours.

2.8 INSTALLATION

A. Architectural Woodwork Standards Grade: Install cabinets to comply with quality standard grade of item to be installed.

B. Assemble cabinets and complete fabrication at Project site to extent that it was not completed in the shop.

C. Anchor cabinets to anchors or blocking built in or directly attached to substrates. Secure with wafer-head cabinet installation screws.

D. Install cabinets level, plumb, and true in line to a tolerance of 1/8 inch in 96 inches using concealed shims.

1. Scribe and cut cabinets to fit adjoining work, refinish cut surfaces, and repair damaged finish at cuts.

PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS 064116 - 8

2. Install cabinets without distortion so doors and drawers fit openings and are accurately aligned. Adjust hardware to center doors and drawers in openings and to provide unencumbered operation. Complete installation of hardware and accessory items as indicated.

3. Fasten wall cabinets through back, near top and bottom, and at ends not more than 16 inches o.c.

2.9 FIELD QUALITY CONTROL

A. Inspections: Provide inspection of installed Work certifying that woodwork, including installation, complies with requirements of the Architectural Woodwork Standards for the specified grade.

1. Inspection entity is to prepare and submit report of inspection.

2.10 ADJUSTING AND CLEANING

A. Repair damaged and defective cabinets, where possible, to eliminate functional and visual defects.

Where not possible to repair, replace architectural cabinets. Adjust joinery for uniform appearance.

B. Clean, lubricate, and adjust hardware.

C. Clean cabinets on exposed and semiexposed surfaces.

END OF SECTION 064116

PHENOLIC-CORE TOILET COMPARTMENTS 102113.17 - 1

SECTION 102113.17 - PHENOLIC-CORE TOILET COMPARTMENTS

Amendment 01 Description – Adds continuous stainless steel finish clarification for Manufacturer’s standard design brackets (fittings).

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Phenolic-core toilet compartments.

1.2 ACTION SUBMITTALS

A. Product Data: For each type of product.

B. Shop Drawings: For toilet compartments. Include plans, elevations, sections, details, and attachment details.

C. Samples for each type of toilet compartment material indicated.

1.3 INFORMATIONAL SUBMITTALS

A. Product certificates.

1.4 CLOSEOUT SUBMITTALS

A. Maintenance data.

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

A. Surface-Burning Characteristics: Comply with ASTM E84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.

1. Flame-Spread Index: 75 or less.

2. Smoke-Developed Index: 450 or less.

B. Regulatory Requirements: Comply with applicable provisions in the U.S. Architectural & Transportation Barriers Compliance Board's ADA-ABA Accessibility Guidelines for Buildings and Facilities and ICC A117.1 for toilet compartments designated as accessible.

PHENOLIC-CORE TOILET COMPARTMENTS 102113.17 - 2

2.2 PHENOLIC-CORE TOILET COMPARMENTS

A. Manufacturers: Subject to compliance with requirements, provide products by the following:

1. ASI Accurate Partitions.

B. Toilet-Enclosure Style: Floor anchored.

C. Urinal-Screen Style: Wall hung.

D. Door, Panel and Pilaster Construction: Solid phenolic-core panel material with melamine facing on both sides fused to substrate during panel manufacture (not separately laminated), and with manufacturer’s standard edges.

E. Pilaster: Formed from stainless steel sheet, not less than 0.031-inch (0.79-mm) nominal thickness and 3 inches (76 mm) high, finished to match hardware.

F. Urinal-Screen Post: Manufacturer's standard post design of material matching the thickness and construction of pilasters with shoe matching that on the pilaster.

G. Brackets (Fittings):

1. Full-Height (Continuous) Type: Manufacturer's standard design, continuous stainless steel.

H. Phenolic-Panel Finish:

1. Facing Sheet Finish: One color and pattern in each room.

2. Color and Pattern: ASI Accurate Partitions – Color-Thru Phenolic, #3450 Fog.

3. Edge Color: Through-color matching facing sheet color.

2.3 HARDWARE AND ACCESSORIES

A. Hardware and Accessories: Manufacturer's standard operating hardware and accessories.

1. Material: Clear-anodized aluminum.

2. Provide units that comply with regulatory requirements for accessibility at compartments designated as accessible.

B. Overhead Bracing: Manufacturer's standard continuous, extruded-aluminum head rail with antigrip profile and in manufacturer's standard finish.

C. Anchorages and Fasteners: Manufacturer's standard exposed fasteners of stainless steel, finished to match the items they are securing, with theft-resistant-type heads. Provide sex-type bolts for through-bolt applications. For concealed anchors, use stainless steel, hot-dip galvanized-steel, or other rust-resistant, protective-coated steel compatible with related materials.

PHENOLIC-CORE TOILET COMPARTMENTS 102113.17 - 3

2.4 FABRICATION

A. Fabrication, General: Fabricate toilet compartment components to sizes indicated. Coordinate requirements and provide cutouts for through-partition toilet accessories where required for attachment of toilet accessories.

B. Overhead-Braced Units: Provide manufacturer's standard corrosion-resistant supports, leveling mechanism, and anchors at pilasters to suit floor conditions. Provide shoes at pilasters to conceal supports and leveling mechanism.

C. Floor-Anchored Units: Provide manufacturer's standard corrosion-resistant anchoring assemblies with leveling adjustment nuts at pilasters for structural connection to floor. Provide shoes at pilasters to conceal anchorage.

D. Urinal-Screen Posts: Provide manufacturer's standard corrosion-resistant anchoring assemblies with leveling adjustment nuts. Provide shoes at posts to conceal anchorage.

E. Door Size and Swings: Unless otherwise indicated, provide 24-inch- (610-mm-) wide in-swinging doors for standard toilet compartments and 36-inch- (914-mm-) wide out-swinging doors with a minimum 32-inch- (813-mm-) wide clear opening for compartments designated as accessible.

PART 3 - EXECUTION

3.1 INSTALLATION

A. General: Comply with manufacturer's written installation instructions. Install units rigid, straight, level, and plumb. Secure units in position with manufacturer's recommended anchoring devices.

1. Maximum Clearances:

a. Pilasters and Panels: 1/2 inch (13 mm).

b. Panels and Walls: 1 inch (25 mm).

c.

2. Full-Height (Continuous) Brackets: Secure panels to walls and to pilasters with full-height brackets.

a. Locate bracket fasteners so holes for wall anchors occur in masonry or tile joints.

b. Align brackets at pilasters with brackets at walls.

3.2 ADJUSTING

A. Hardware Adjustment: Adjust and lubricate hardware according to hardware manufacturer's written instructions for proper operation. Set hinges on in-swinging doors to hold doors open approximately 30 degrees from closed position when unlatched. Set hinges on out-swinging doors to return doors to fully closed position.

PHENOLIC-CORE TOILET COMPARTMENTS 102113.17 - 4

END OF SECTION 102113.17

WALL AND DOOR PROTECTION 102600 - 1

SECTION 102600 - WALL AND DOOR PROTECTION

Amendment 01 Description – Changes corner guard height from “from top of base to bottom of ceiling system” to “8’H.”

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Corner guards.

2. Abuse-resistant wall coverings.

1.3 ACTION SUBMITTALS

A. Product Data: For each type of product.

1. Include construction details, material descriptions, impact strength, dimensions of individual components and profiles, and finishes.

2. Include fire ratings of units recessed in fire-rated walls and listings for door-protection items attached to fire-rated doors.

B. Shop Drawings: For each type of wall and door protection showing locations and extent.

1. Include plans, elevations, sections, and attachment details.

C. Samples for Initial Selection: For each type of impact-resistant wall-protection unit indicated, in each color and texture specified.

1. Include Samples of accent strips and accessories to verify color selection.

D. Samples for Verification: For each type of exposed finish on the following products, prepared on Samples indicated below:

1. Corner Guards

2. Abuse-resistant wall coverings

1.4 INFORMATIONAL SUBMITTALS

A. Sample Warranty: For special warranty.

WALL AND DOOR PROTECTION 102600 - 2

1.5 CLOSEOUT SUBMITTALS

A. Maintenance Data: For each type of wall and door protection product to include in maintenance manuals.

1. Include recommended methods and frequency of maintenance for maintaining best condition of plastic covers under anticipated traffic and use conditions. Include precautions against using cleaning materials and methods that may be detrimental to finishes and performance.

1.6 MAINTENANCE MATERIAL SUBMITTALS

A. Furnish extra materials, from the same product run, that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.

1. Corner-Guard Covers: Full-size plastic covers of maximum length equal to 5 percent of each type, color, and texture of cover installed, but no fewer than two units.

2. Mounting and Accessory Components: Amounts proportional to the quantities of extra materials. Package mounting and accessory components with each extra material.

1.7 DELIVERY, STORAGE, AND HANDLING

A. Store wall and door protection in original undamaged packages and containers inside well-ventilated area protected from weather, moisture, soiling, extreme temperatures, and humidity.

1. Maintain room temperature within storage area at not less than 70 deg F during the period plastic materials are stored.

2. Keep plastic materials out of direct sunlight.

3. Store plastic wall- and door-protection components for a minimum of 72 hours, or until plastic material attains a minimum room temperature of 70 deg F.

a. Store corner-guard covers in a vertical position.

1.8 WARRANTY

A. Special Warranty: Manufacturer agrees to repair or replace components of wall- and door-protection units that fail in materials or workmanship within specified warranty period.

1. Failures include, but are not limited to, the following:

a. Structural failures including detachment of components from each other or from the substrates, delamination, and permanent deformation beyond normal use.

b. Deterioration of metals, metal finishes, plastics, and other materials beyond normal use.

2. Warranty Period: Five years from date of Substantial Completion.

WALL AND DOOR PROTECTION 102600 - 3

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Source Limitations: Obtain wall- and door-protection products from single source from single manufacturer.

2.2 PERFORMANCE REQUIREMENTS

A. Surface Burning Characteristics: Comply with ASTM E84 or UL 723; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.

1. Flame-Spread Index: 25 or less.

2. Smoke-Developed Index: 450 or less.

B. Regulatory Requirements: Comply with applicable provisions in the U.S. Architectural & Transportation Barriers Compliance Board's ADA-ABA Accessibility Guidelines for Buildings and Facilities and ICC A117.1.

2.3 CORNER GUARDS: CG-1

A. Surface-Mounted, Metal Corner Guards: Fabricated as one piece from formed or extruded metal with formed edges; with 90- or 135-degree turn to match wall condition.

1. Manufacturers: Subject to compliance with requirements, provide products by the following:

a. Construction Specialties, Inc.

1) CS Acrovyn: CO-8 Series, #4 Stainless Steel

2. Material: Stainless-steel sheet, Type 430, 16-guage.

a. Thickness: Minimum of 0.0625 inches

b. Finish: Stainless Steel, No. 4

3. Wing Size: 2 inches by 2 inches.

4. Corner Radius: 3/16 inch.

5. Mounting: Mechanical fasteners. Flat-head, countersunk screws through factory-drilled mounting holes.

2.4 ABUSE-RESISTANT WALL COVERINGS: FRP-1

A. Impact-Resistant Wall Panels: Rigid wall panels consisting of semirigid, plastic sheet wall covering material factory laminated to high-impact-resistant core, with moisture-resistant vapor barrier factory laminated to reverse side of panel for stability.

1. Manufacturers: Subject to compliance with requirements, provide products by the following:

a. Crane Composites, Inc.

1) Glasbord: Pebbled Embossed, 85 White

WALL AND DOOR PROTECTION 102600 - 4

2) Composition: 0.09 inch thick fiberglass reinforced plastic with impact-resistant film finish.

3) Sheet Size: 48 inches by 96 inches

4) Height: Wainscot: 42 inches

5) Sheet Edge: Square

6) Color and Texture: Pebbled Embossed – 85 White

7) Trim and Joint Moldings: Extruded rigid plastic that matches wall-covering color.

8) Mounting: Adhesive.

2.5 MATERIALS

A. Plastic Materials: Chemical- and stain-resistant, high-impact-resistant plastic with integral color throughout; extruded and sheet material as required, thickness as indicated.

B. Fasteners: Aluminum, nonmagnetic stainless-steel, or other noncorrosive metal screws, bolts, and other fasteners compatible with items being fastened. Use security-type fasteners where exposed to view.

2.6 FABRICATION

A. Fabricate wall and door protection according to requirements indicated for design, performance, dimensions, and member sizes, including thicknesses of components.

B. Factory Assembly: Assemble components in factory to greatest extent possible to minimize field assembly. Disassemble only as necessary for shipping and handling.

C. Quality: Fabricate components with uniformly tight seams and joints and with exposed edges rolled. Provide surfaces free of wrinkles, chips, dents, uneven coloration, and other imperfections.

Fabricate members and fittings to produce flush, smooth, and rigid hairline joints.

2.7 FINISHES

A. Protect finishes on exposed surfaces from damage by applying a strippable, temporary protective covering before shipping.

B. Appearance of Finished Work: Noticeable variations in same piece are not acceptable. Variations in appearance of adjoining components are acceptable if they are within the range of approved Samples and are assembled or installed to minimize contrast.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine substrates and wall areas, with Installer present, for compliance with requirements for installation tolerances and other conditions affecting performance of the Work.

WALL AND DOOR PROTECTION 102600 - 5

B. Examine walls to which wall and door protection will be attached for blocking, grounds, and other solid backing that have been installed in the locations required for secure attachment of support fasteners.

C. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 PREPARATION

A. Complete finishing operations, including painting, before installing wall and door protection.

B. Before installation, clean substrate to remove dust, debris, and loose particles.

3.3 INSTALLATION

A. Installation Quality: Install wall and door protection according to manufacturer's written instructions, level, plumb, and true to line without distortions. Do not use materials with chips, cracks, voids, stains, or other defects that might be visible in the finished Work.

B. Mounting Heights: Install wall and door protection in locations and at mounting heights indicated:

1. Corner Guards: 8’H.

2. Abuse-Resistant Wall Coverings: as indicated.

C. Accessories: Provide splices, mounting hardware, anchors, trim, joint moldings, and other accessories required for a complete installation.

1. Provide anchoring devices and suitable locations to withstand imposed loads.

2. Adjust bottom and top caps as required to ensure tight seams.

3.4 CLEANING

A. Immediately after completion of installation, clean accessories using a standard ammonia-based household cleaning agent.

END OF SECTION 102600

SUPPLEMENTAL REQUIREMENTS

FOR ELECTRICAL

260010 - 1

SECTION 260010 - SUPPLEMENTAL REQUIREMENTS FOR ELECTRICAL

Amendment 01 Description – Added lighting controls to commissioning activities.

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Supplemental requirements generally applicable to the Work specified in Division 26.

This Section is also referenced by related Work specified in other Divisions.

B. Related Requirements:

1. Section 260548.16 "Seismic Controls for Electrical Systems" for seismic-load and other field conditions applicable to Work specified in this Section.

1.2 REFERENCES

A. Abbreviations and Acronyms for Electrical Terms and Units of Measure:

1. 8P8C: An 8-position 8-contact modular jack.

2. A: Ampere, unit of electrical current.

3. AC or ac: Alternating current.

4. AFCI: Arc-fault circuit interrupter.

5. AIC: Ampere interrupting capacity.

6. AL, Al, or ALUM: Aluminum.

7. ASD: Adjustable-speed drive.

8. ATS: Automatic transfer switch.

9. AWG: American wire gauge; see ASTM B258.

10. BAS: Building automation system.

11. BIL: Basic impulse insulation level.

12. BIM: Building information modeling.

13. CAD: Computer-aided design or drafting.

14. CATV: Community antenna television.

15. CB: Circuit breaker.

16. cd: Candela, the SI fundamental unit of luminous intensity.

17. CO/ALR: Copper-aluminum, revised.

18. COPS: Critical operations power system.

19. CU or Cu: Copper.

20. CU-AL or AL-CU: Copper-aluminum.

21. dB: Decibel, a unitless logarithmic ratio of two electrical, acoustical, or optical power values.

22. dB(A-weighted) or dB(A): Decibel acoustical sound pressure level with A-weighting applied in accordance with IEC 61672-1.

260010 - 2

23. dB(adjusted) or dBa: Decibel weighted absolute noise power with respect to 3.16 pW (minus 85 dBm).

24. dBm: Decibel absolute power with respect to 1 mW.

25. DC or dc: Direct current.

26. DCOA: Designated critical operations area.

27. DDC: Direct digital control (HVAC).

28. EGC: Equipment grounding conductor.

29. ELV: Extra-low voltage.

30. EMF: Electromotive force.

31. EMI: Electromagnetic interference.

32. EPM: Electrical preventive maintenance.

33. EPS: Emergency power supply.

34. EPSS: Emergency power supply system.

35. ESS: Energy storage system.

36. EV: Electric vehicle.

37. EVPE: Electric vehicle power export equipment.

38. EVSE: Electric vehicle supply equipment.

39. fc: Footcandle, an internationally recognized unit of illuminance equal to one lumen per square foot or 10.76 lx. The simplified conversion 1 fc = 10 lx in the Specifications is common practice and considered adequate precision for building construction activities.

When there are conflicts, lux is the primary unit; footcandle is specified for convenience.

40. FLC: Full-load current.

41. ft: Foot.

42. ft-cd: Foot-candle, the antiquated U.S. Standard unit of illuminance, equal to one international candle measured at a distance of one foot, that was superseded in 1948 by the unit "footcandle" after the SI unit candela (cd) replaced the international candle; see "fc,"

43. GEC: Grounding electrode conductor.

44. GFCI: Ground-fault circuit interrupter.

45. GFPE: Ground-fault protection of equipment.

46. GND: Ground.

47. HACR: Heating, air conditioning, and refrigeration.

48. HDPE: High-density polyethylene.

49. HID: High-intensity discharge.

50. HP or hp: Horsepower.

51. HVAC: Heating, ventilating, and air conditioning.

52. Hz: Hertz.

53. IBT: Intersystem bonding termination.

54. inch: Inch. To avoid confusion, the abbreviation "in." is not used.

55. IP: Ingress protection rating (enclosures); Internet protocol (communications).

56. IR: Infrared.

57. IS: Intrinsically safe.

58. IT&R: Inspecting, testing, and repair.

59. ITE: Information technology equipment.

60. kAIC: Kiloampere interrupting capacity.

61. kcmil or MCM: One thousand circular mils.

62. kV: Kilovolt.

63. kVA: Kilovolt-ampere.

64. kVAr or kVAR: Kilovolt-ampere reactive.

65. kW: Kilowatt.

66. kWh: Kilowatt-hour.

260010 - 3

67. LAN: Local area network.

68. lb: Pound (weight).

69. lbf: Pound (force).

70. LCD: Liquid-crystal display.

71. LCDI: Leakage-current detector-interrupter.

72. LED: Light-emitting diode.

73. Li-ion: Lithium-ion.

74. lm: Lumen, the SI derived unit of luminous flux.

75. LNG: Liquefied natural gas.

76. LP-Gas: Liquefied petroleum gas.

77. LRC: Locked-rotor current.

78. LV: Low voltage.

79. lx: Lux, the SI derived unit of illuminance equal to one lumen per square meter.

80. m: Meter.

81. MCC: Motor-control center.

82. MDC: Modular data center.

83. MG set: Motor-generator set.

84. MIDI: Musical instrument digital interface.

85. MLO: Main lugs only.

86. MV: Medium voltage.

87. MVA: Megavolt-ampere.

88. mW: Milliwatt.

89. MW: Megawatt.

90. MWh: Megawatt-hour.

91. NC: Normally closed.

92. Ni-Cd: Nickel-cadmium.

93. Ni-MH: Nickel-metal hydride.

94. NIU: Network interface unit.

95. NO: Normally open.

96. NPT: National (American) standard pipe taper.

97. OCPD: Overcurrent protective device.

98. ONT: Optical network terminal.

99. PC: Personal computer.

100. PCS: Power conversion system.

101. PCU: Power-conditioning unit.

102. PF or pf: Power factor.

103. PHEV: Plug-in hybrid electric vehicle.

104. PLC: Programmable logic controller.

105. PLFA: Power-limited fire alarm.

106. PoE: Power over Ethernet.

107. PV: Photovoltaic.

108. PVC: Polyvinyl chloride.

109. pW: Picowatt.

110. RFI: (electrical) Radio-frequency interference; (contract) Request for interpretation.

111. RMS or rms: Root-mean-square.

112. RPM or rpm: Revolutions per minute.

113. SCADA: Supervisory control and data acquisition.

114. SCR: Silicon-controlled rectifier.

115. SPD: Surge protective device.

116. sq.: Square.

117. SWD: Switching duty.

260010 - 4

118. TCP/IP: Transmission control protocol/Internet protocol.

119. TEFC: Totally enclosed fan-cooled.

120. TR: Tamper resistant.

121. TVSS: Transient voltage surge suppressor.

122. UL: (standards) Underwriters Laboratories, Inc.; (product categories) UL, LLC.

123. UL CCN: UL Category Control Number.

124. UPS: Uninterruptible power supply.

125. USB: Universal serial bus.

126. UV: Ultraviolet.

127. V: Volt, unit of electromotive force.

128. V(ac): Volt, alternating current.

129. V(dc): Volt, direct current.

130. VA: Volt-ampere, unit of complex electrical power.

131. VAR: Volt-ampere reactive, unit of reactive electrical power.

132. VFC: Variable-frequency controller.

133. VOM: Volt-ohm-multimeter.

134. VPN: Virtual private network.

135. VRLA: Valve regulated lead acid; also called "sealed lead acid (SLA)" or "valve regulated sealed lead acid."

136. W: Watt, unit of real electrical power.

137. Wh: Watt-hour, unit of electrical energy usage.

138. WPT: Wireless power transfer.

139. WPTE: Wireless power transfer equipment.

140. WR: Weather resistant.

B. Abbreviations and Acronyms for Electrical Raceway Types:

1. EMT: Electrical metallic tubing.

2. EMT-A: Aluminum electrical metallic tubing.

3. EMT-S: Steel electrical metallic tubing.

4. EMT-SS: Stainless steel electrical metallic tubing.

5. ENT: Electrical nonmetallic tubing.

6. EPEC: Electrical HDPE underground conduit.

7. EPEC-40: Schedule 40 electrical HDPE underground conduit.

8. EPEC-80: Schedule 80 electrical HDPE underground conduit.

9. EPEC-A: Type A electrical HDPE underground conduit.

10. EPEC-B: Type B electrical HDPE underground conduit.

11. ERMC: Electrical rigid metal conduit.

12. ERMC-A: Aluminum electrical rigid metal conduit.

13. ERMC-S: Steel electrical rigid metal conduit.

14. ERMC-S-G: Galvanized-steel electrical rigid metal conduit.

15. ERMC-S-PVC: PVC-coated-steel electrical rigid metal conduit.

16. ERMC-SS: Stainless steel electrical rigid metal conduit.

17. FMC: Flexible metal conduit.

18. FMC-A: Aluminum flexible metal conduit.

19. FMC-S: Steel flexible metal conduit.

20. FMT: Steel flexible metallic tubing.

21. FNMC: Flexible nonmetallic conduit. See "LFNC."

22. HDPE: See EPEC.

23. IMC: Steel electrical intermediate metal conduit.

24. LFMC: Liquidtight flexible metal conduit.

260010 - 5

25. LFMC-A: Aluminum liquidtight flexible metal conduit.

26. LFMC-S: Steel liquidtight flexible metal conduit.

27. LFMC-SS: Stainless steel liquidtight flexible metal conduit.

28. LFNC: Liquidtight flexible nonmetallic conduit.

29. LFNC-A: Layered (Type A) liquidtight flexible nonmetallic conduit.

30. LFNC-B: Integral (Type B) liquidtight flexible nonmetallic conduit.

31. LFNC-C: Corrugated (Type C) liquidtight flexible nonmetallic conduit.

32. PVC: Rigid PVC conduit.

33. PVC-40: Schedule 40 rigid PVC conduit.

34. PVC-80: Schedule 80 rigid PVC Conduit.

35. PVC-A: Type A rigid PVC concrete-encased conduit.

36. PVC-EB: Type EB rigid PVC concrete-encased underground conduit.

37. RGS: See ERMC-S-G.

38. RMC: See ERMC.

39. RTRC: Reinforced thermosetting resin conduit.

40. RTRC-AG: Low-halogen, aboveground reinforced thermosetting resin conduit.

41. RTRC-AG-HW: Heavy wall, low-halogen, aboveground reinforced thermosetting resin conduit.

42. RTRC-AG-SW: Standard wall, low-halogen, aboveground reinforced thermosetting resin conduit.

43. RTRC-AG-XW: Extra heavy wall, low-halogen, aboveground reinforced thermosetting resin conduit.

44. RTRC-BG: Low-halogen, belowground reinforced thermosetting resin conduit.

C. Abbreviations and Acronyms for Electrical Single-Conductor and Multiple-Conductor Cable Types:

1. AC: Armored cable.

2. CATV: Coaxial general-purpose cable.

3. CATVP: Coaxial plenum cable.

4. CATVR: Coaxial riser cable.

5. CI: Circuit integrity cable.

6. CL2: Class 2 cable.

7. CL2P: Class 2 plenum cable.

8. CL2R: Class 2 riser cable.

9. CL2X: Class 2 cable, limited use.

10. CL3: Class 3 cable.

11. CL3P: Class 3 plenum cable.

12. CL3R: Class 3 riser cable.

13. CL3X: Class 3 cable, limited use.

14. CM: Communications general-purpose cable.

15. CMG: Communications general-purpose cable.

16. CMP: Communications plenum cable.

17. CMR: Communications riser cable.

18. CMUC: Under-carpet communications wire and cable.

19. CMX: Communications cable, limited use.

20. DG: Distributed generation cable.

21. FC: Flat cable.

22. FCC: Flat conductor cable.

23. FPL: Power-limited fire-alarm cable.

24. FPLP: Power-limited fire-alarm plenum cable.

260010 - 6

25. FPLR: Power-limited fire-alarm riser cable.

26. IGS: Integrated gas spacer cable.

27. ITC: Instrumentation tray cable.

28. ITC-ER: Instrumentation tray cable, exposed run.

29. MC: Metal-clad cable.

30. MC-HL: Metal-clad cable, hazardous location.

31. MI: Mineral-insulated, metal-sheathed cable.

32. MTW: (machine tool wiring) Moisture-, heat-, and oil-resistant thermoplastic cable.

33. MV: Medium-voltage cable.

34. NM: Nonmetallic sheathed cable.

35. NMC: Nonmetallic sheathed cable with corrosion-resistant nonmetallic jacket.

36. NMS: Nonmetallic sheathed cable with signaling, data, and communications conductors, plus power or control conductors.

37. NPLF: Non-power-limited fire-alarm circuit cable.

38. NPLFP: Non-power-limited fire-alarm circuit cable for environmental air spaces.

39. NPLFR: Non-power-limited fire-alarm circuit riser cable.

40. NUCC: Nonmetallic underground conduit with conductors.

41. OFC: Conductive optical fiber general-purpose cable.

42. OFCG: Conductive optical fiber general-purpose cable.

43. OFCP: Conductive optical fiber plenum cable.

44. OFCR: Conductive optical fiber riser cable.

45. OFN: Nonconductive optical fiber general-purpose cable.

46. OFNG: Nonconductive optical fiber general-purpose cable.

47. OFNP: Nonconductive optical fiber plenum cable.

48. OFNR: Nonconductive optical fiber riser cable.

49. P: Marine shipboard cable.

50. PLTC: Power-limited tray cable.

51. PLTC-ER: Power-limited tray cable, exposed run.

52. PV: Photovoltaic cable.

53. RHH: (high heat) Thermoset rubber, heat-resistant cable.

54. RHW: Thermoset rubber, moisture-resistant cable.

55. SA: Silicone rubber cable.

56. SE: Service-entrance cable.

57. SER: Service-entrance cable, round.

58. SEU: Service-entrance cable, flat.

59. SIS: Thermoset cable for switchboard and switchgear wiring.

60. TBS: Thermoplastic cable with outer braid.

61. TC: Tray cable.

62. TC-ER: Tray cable, exposed run.

63. TC-ER-HL: Tray cable, exposed run, hazardous location.

64. THW: Thermoplastic, heat- and moisture-resistant cable.

65. THHN: Thermoplastic, heat-resistant cable with nylon jacket outer sheath.

66. THHW: Thermoplastic, heat- and moisture-resistant cable.

67. THWN: Thermoplastic, moisture- and heat-resistant cable with nylon jacket outer sheath.

68. TW: Thermoplastic, moisture-resistant cable.

69. UF: Underground feeder and branch-circuit cable.

70. USE: Underground service-entrance cable.

71. XHH: Cross-linked polyethylene, heat-resistant cable.

72. XHHW: Cross-linked polyethylene, heat- and moisture-resistant cable.

D. Definitions:

260010 - 7

1. Basic Impulse Insulation Level (BIL): Reference insulation level expressed in impulse crest voltage with a standard wave not longer than 1.5 times 50 microseconds and 1.5 times 40 microseconds.

2. Cable: In accordance with NIST NBS Circular 37 and IEEE standards, in the United States for the purpose of interstate commerce, the definition of "cable" is (1) a conductor with insulation, or a stranded conductor with or without insulation (single-conductor cable); or (2) a combination of conductors insulated from one another (multiple-conductor cable).

3. Communications Jack: A fixed connecting device designed for insertion of a communications cable plug.

4. Communications Outlet: One or more communications jacks, or cables and plugs, mounted in a box or ring, with a suitable protective cover.

5. Conductor: In accordance with NIST NBS Circular 37 and IEEE standards, in the United States for the purpose of interstate commerce, the definition of "conductor" is (1) a wire or combination of wires not insulated from one another, suitable for carrying an electric current; (2) (National Electrical Safety Code) a material, usually in the form of wire, cable, or bar, suitable for carrying an electric current; or (3) (general) a substance or body that allows a current of electricity to pass continuously along it.

6. Designated Seismic System: A system component that requires design in accordance with Chapter 13 of ASCE/SEI 7 and for which the Component Importance Factor is greater than 1.0.

7. Direct Buried: Installed underground without encasement in concrete or other protective material.

8. Enclosure: The case or housing of an apparatus, or the fence or wall(s) surrounding an installation, to prevent personnel from accidentally contacting energized parts or to protect the equipment from physical damage. Types of enclosures and enclosure covers include the following:

a. Cabinet: An enclosure that is designed for either surface mounting or flush mounting and is provided with a frame, mat, or trim in which a swinging door or doors are or can be hung.

b. Concrete Box: A box intended for use in poured concrete.

c. Conduit Body: A means for providing access to the interior of a conduit or tubing system through one or more removable covers at a junction or terminal point. In the United States, conduit bodies are listed in accordance with outlet box requirements.

d. Conduit Box: A box having threaded openings or knockouts for conduit, EMT, or fittings.

e. Cutout Box: An enclosure designed for surface mounting that has swinging doors or covers secured directly to and telescoping with the walls of the enclosure.

f. Device Box: A box with provisions for mounting a wiring device directly to the box.

g. Extension Ring: A ring intended to extend the sides of an outlet box or device box to increase the box depth, volume, or both.

h. Floor Box: A box mounted in the floor intended for use with a floor box cover and other components to complete the floor box enclosure.

i. Floor-Mounted Enclosure: A floor box and floor box cover assembly with means to mount in the floor that is sealed against the entrance of scrub water at the floor level.

j. Floor Nozzle: An enclosure used on a wiring system, intended primarily as a housing for a receptacle, provided with a means, such as a collar, for surface-

260010 - 8 mounting on a floor, which may or may not include a stem to support it above the floor level, and is sealed against the entrance of scrub water at the floor level.

k. Junction Box: A box with a blank cover that joins different runs of raceway or cable and provides space for connection and branching of the enclosed conductors.

l. Outlet Box: A box that provides access to a wiring system having pryout openings, knockouts, threaded entries, or hubs in either the sides or the back, or both, for the entrance of conduit, conduit or cable fittings, or cables, with provisions for mounting an outlet box cover, but without provisions for mounting a wiring device directly to the box.

m. Pedestal Floor Box Cover: A floor box cover that, when installed as intended, provides a means for typically vertical or near-vertical mounting of receptacle outlets above the floor's finished surface.

n. Pull Box: A box with a blank cover that joins different runs of raceway and provides access for pulling or replacing the enclosed cables or conductors.

o. Raised-Floor Box: A floor box intended for use in raised floors.

p. Recessed Access Floor Box: A floor box with provisions for mounting wiring devices below the floor surface.

q. Recessed Access Floor Box Cover: A floor box cover with provisions for passage of cords to recessed wiring devices mounted within a recessed floor box.

r. Ring: A sleeve, which is not necessarily round, used for positioning a recessed wiring device flush with the plaster, concrete, drywall, or other wall surface.

s. Ring Cover: A box cover, with raised center portion to accommodate a specific wall or ceiling thickness, for mounting wiring devices or luminaires flush with the surface.

t. Termination Box: An enclosure designed for installation of termination base assemblies consisting of bus bars, terminal strips, or terminal blocks with provision for wire connectors to accommodate incoming or outgoing conductors, or both.

9. Emergency Systems: Those systems legally required and classed as emergency by municipal, state, federal, or other codes, or by any governmental agency having jurisdiction that are designed to ensure continuity of lighting, electrical power, or both, to designated areas and equipment in the event of failure of the normal supply for safety to human life.

10. The term "fault limited" is being proposed to replace "low voltage" or "extra-low voltage" for description of communications and PoE circuits because the safety issue is not solely related to voltage. Instead of limiting these circuits to a voltage less than 30 V(ac) or 60 V(dc), now 120 V, 0.5 A power supplies may be considered fault limited.

While the voltage may be high enough to be painful, the available power in a fault condition is not great enough to cause physical harm or start a fire.

11. The definition of "High-Performance Building" in first subparagraph below is from the Energy Independence and Security Act (EISA) of 2007.

12. High-Performance Building: A building that integrates and optimizes on a life-cycle basis all major high-performance attributes, including energy conservation, environment, safety, security, durability, accessibility, cost-benefit, productivity, sustainability, functionality, and operational considerations.

13. Jacket: A continuous nonmetallic outer covering for conductors or cables.

14. Luminaire: A complete lighting unit consisting of a light source such as a lamp, together with the parts designed to position the light source and connect it to the power supply. It may also include parts to protect the light source or the ballast or to distribute the light.

15. Mode: The terms "Active Mode," "Off Mode," and "Standby Mode" are used as defined in the Energy Independence and Security Act (EISA) of 2007.

260010 - 9

16. Multi-Outlet Assembly: A type of surface, flush, or freestanding raceway designed to hold conductors, receptacles, and switches, assembled in the field or at the factory.

17. Plenum: A compartment or chamber to which one or more air ducts are connected and that forms part of the air distribution system.

18. Receptacle: A fixed connecting device arranged for insertion of a power cord plug. Also called a power jack.

19. Receptacle Outlet: One or more receptacles mounted in a box with a suitable protective cover.

20. Sheath: A…

This is the start of the file's text. The full file is on GovTribe.