Attachment 1c Revised.Additional Drawings Hangar 9 Renovation_6.17.2025.pdf

PDF 6 MB Posted

Attached to
Solicitation - Hanger 9 Renovation at the Mike Monroney Aeronautical Center (MMAC), Oklahoma City, OK
Solicitation number
6973GH-25-R-00132
Issued by

About this file

The provided file is a set of architectural and engineering drawings for the Hangar 9 Renovation project at the Mike Monroney Aeronautical Center in Oklahoma City. The comprehensive drawing set includes detailed mechanical, electrical, fire alarm, plumbing, and architectural plans across three levels (Level 1, Level 2, and Level 3), covering four distinct sectors within the hangar. The drawings provide extensive technical specifications for renovating the facility, including floor plans, mechanical system layouts, fire alarm device placements, diffuser relocations, and interior finish details.

Key technical aspects include relocating HVAC diffusers, updating fire alarm systems, implementing new ceiling and floor finishes, and modifying mechanical and electrical infrastructure across office spaces, industrial areas, and the hangar bay. The drawings are part of a federal renovation project with an estimated budget between $5-10 million, prepared by Benham and dated for construction in 2025. The project involves comprehensive systems upgrades while maintaining the facility's existing structural framework, with careful attention to details such as fire separation, air terminal placement, and interior space configuration.

View the file

Other files

File Type Posted
6973GH-25-R-00132 Amend0009.pdf PDF
6973GH-25-R-00132 Amend0008.pdf PDF
6973GH-25-R-00132 Amend0007.pdf PDF
Attachment 1f Amended Specifications_Am02_6.26.25.pdf PDF
QA Log - Answers - 25-R-00132 H9 Reno 7.7.25 Final.pdf PDF
6973GH-25-R-00132 Amend0006.pdf PDF
Attachment 1e Revised.Additional Drawings Hangar 9 Renovation_6.26.2025.pdf PDF
6973GH-25-R-00132 Amend0005.pdf PDF
QA Log.2 25-R-00132 H9 Reno 6.30.25.pdf PDF
Attachment 12 Furniture Equipment Moving Diagram Hangar 9 6.17.25.pdf PDF
6973GH-25-R-00132 Amend0004.pdf PDF
Attachment 1d Amended Specifications_Am01_6.17.25.pdf PDF
6973GH-25-R-00132 Amend0003.pdf PDF
6973GH-25-R-00132 Amend0002.pdf PDF
6973GH-25-R-00132 Amend0001.pdf PDF
Attendance List Hanger 9 May 20 Site Visit.pdf PDF
QA Log.1 25-R-00132 H9 Reno 5.16.25.pdf PDF
6973GH-25-R-00132.pdf PDF
Attachment 9 Contractor Release.pdf PDF
Attachment 1b Hangar_9_High_Bay_Lights_100_Drawings.3.14.2025.pdf PDF
Attachment 4 SF25A Payment Bond.pdf PDF
Attachment 10 AMP400-ENV-OC-2.4.3-CC.pdf PDF
Attachment 5 SF24 Bid Bond.pdf PDF
Attachment 2 Wage Determination OK20250049 03.14.2025.pdf PDF
Attachment 1 Hangar 09_Combined Specs_3.14.2025.pdf PDF
Attachment 11 Chapter 33 Construction Safety.pdf PDF
Attachment 6 Past Performance Survey 4.23.25.docx DOCX document
Attachment 1a Hangar 9_Renovation_100_Drawings_3.14.2025.pdf PDF
Attachment 8 Client Authorization Letter.docx DOCX document
Attachment 7 Past Performance Experience Form.docx DOCX document
Attachment 3 SF25 Performance Bond.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Drawing No. AMP - 400 -lead or pm designed

WORK REQUEST NO.

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

MIKE MONRONEY AERONAUTICAL CENTER − OKLAHOMA CITY, OKLAHOMA

drawn approved by

SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520. No part of this record may be disclosed to persons without a "need to know", as defined in 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR parts 15 and 1520.

ISSUED BY

OFFICE OF

facility management amp − 400 drawn d r a w in g N a m e d r a w in g N a m e

AMENDMENT 1

SEAL:

/1 /2

:2

1:

P

M A u t o d e s k D o c s /1 F A A H a n g a r

R e n o v a t io n s R /1 1_

A R C H H C F .r v t

/1 /2

:2

1:

P

M A u t o d e s k D o c s /1 F A A H a n g a r R e n o v a t io n s R /1 1_

A R C H H C F .r v t

B. BRADDICK

T. AUFRANC

HANGAR 9

INDEX OF DRAWINGS

1550021

MATTCV

11.10.2023

G-004

SHT No SHEET NAME REV DATE

0000 - GENERAL

G-001 COVER SHEET 0 01.24.25

G-002 GENERAL PROJECT INFORMATION 0 01.24.25

G-003 GENERAL PROJECT INFORMATION 0 01.24.25

G-004 INDEX OF DRAWINGS 1 06.17.25

G-005 CONTRACTOR HAUL ROUTE AND LAY DOWN AREA 0 01.24.25

G-006 PHASING PLAN 0 01.24.25

0000 - GENERAL: 6

02 - GENERAL

G001 LIFE SAFETY CODE ANALYSIS 0 01.24.25

GI002 LIFE SAFETY OCCUPANT LOAD CALCULATIONS 0 01.24.25

GI110 LIFE SAFETY PLAN LEVEL 1 - COMPOSITE 0 01.24.25

GI120 LIFE SAFETY PLAN LEVEL 2 - COMPOSITE 0 01.24.25

GI130 LIFE SAFETY PLAN LEVEL 3 - COMPOSITE 0 01.24.25

02 - GENERAL: 5

04 - ARCHITECTURAL

AD101 LEVEL 1 COMPOSITE DEMOLITION PLAN - FLOORING 0 01.24.25

AD102 LEVEL 2 COMPOSITE DEMOLITION PLAN - FLOORING 0 01.24.25

AD103 LEVEL 3 COMPOSITE DEMOLITION PLAN - FLOORING 0 01.24.25

AD104 LEVEL 1 COMPOSITE DEMOLITION PLAN - CEILINGS 0 01.24.25

AD105 LEVEL 2 COMPOSITE DEMOLITION PLAN - CEILINGS 0 01.24.25

AD106 LEVEL 3 COMPOSITE DEMOLITION PLAN - CEILINGS 0 01.24.25

A-110 LEVEL 1 - COMPOSITE FLOOR PLAN 0 01.24.25

A-110a LEVEL 1 - SLAB THICKNESS PLAN 1 06.17.25

A-111 LEVEL 1 - SECTORS 1 & 2 0 01.24.25

A-112 LEVEL 1 - SECTORS 3 & 4 0 01.24.25

A-120 LEVEL 2 - COMPOSITE FLOOR PLAN 0 01.24.25

A-121 LEVEL 2 - SECTORS 1 & 2 0 01.24.25

A-122 LEVEL 2 - SECTORS 3 & 4 0 01.24.25

A-130 LEVEL 3 - COMPOSITE FLOOR PLAN 0 01.24.25

A-131 LEVEL 3 - SECTORS 1 & 2 0 01.24.25

A-132 LEVEL 3 - SECTORS 3 & 4 0 01.24.25

A-210 LEVEL 1 - COMPOSITE RCP 0 01.24.25

A-211 LEVEL 1 - SECTORS 1 & 2 RCP 0 01.24.25

A-212 LEVEL 1 - SECTORS 3 & 4 RCP 0 01.24.25

A-220 LEVEL 2 - COMPOSITE RCP 0 01.24.25

A-221 LEVEL 2 - SECTORS 1 & 2 RCP 0 01.24.25

A-222 LEVEL 2 - SECTORS 3 & 4 RCP 0 01.24.25

A-230 LEVEL 3 - COMPOSITE RCP 0 01.24.25

A-231 LEVEL 3 - SECTORS 1 & 2 RCP 0 01.24.25

SHT No SHEET NAME REV DATE

05 - INTERIORS: 19

06 - FIRE PROTECTION

FA001 FIRE ALARM LEGEND AND GENERAL NOTES 1 06.17.25

FA110 FIRE ALARM PLAN LEVEL 1 - HANGAR BAY 0 01.24.25

FA111 FIRE ALARM PLAN LEVEL 1 - SECTORS 1 & 2 1 06.17.25

FA112 FIRE ALARM PLAN LEVEL 1 - SECTORS 3 & 4 0 01.24.25

FA121 FIRE ALARM PLAN LEVEL 2 - SECTORS 1 & 2 0 01.24.25

FA122 FIRE ALARM PLAN LEVEL 2 - SECTORS 3 & 4 0 01.24.25

FA131 FIRE ALARM PLAN LEVEL 3 - SECTORS 1 & 2 0 01.24.25

FA132 FIRE ALARM PLAN LEVEL 3 - SECTORS 3 & 4 0 01.24.25

FA600 TYPICAL FIRE ALARM RISER DIAGRAM 0 01.24.25

FA601 TYPICAL FIRE ALARM INPUT / OUTPUT MATRIX 0 01.24.25

FX001 FIRE SUPPRESSION GENERAL NOTES AND LEGEND 0 01.24.25

FX110 FIRE SUPPRESSION PLAN LEVEL 1 - COMPOSITE 0 01.24.25

FX120 FIRE SUPPRESSION PLAN LEVEL 2 - COMPOSITE 0 01.24.25

FX130 FIRE SUPPRESSION PLAN LEVEL 3 - COMPOSITE 0 01.24.25

06 - FIRE PROTECTION: 14

07 - PLUMBING

P-001 LEGEND AND ABBREVATIONS 0 01.24.24

PD110 PLUMBING DEMO 0 01.24.24

PD120 PLUMBING DEMO 0 01.24.24

PD130 PLUMBING DEMO 0 01.24.24

PD411 ENLARGED PLUMBING DEMOLITION - SECTOR 1 AND 2 0 01.24.24

PD412 ENLARGED PLUMBING DEMOLITION - SECTOR 3 AND 4 0 01.24.24

PD421 ENLARGED PLUMBING DEMOLITION - SECTOR 2 0 01.24.24

PD422 ENLARGED PLUMBING DEMOLITION - SECTOR 3 AND 4 0 01.24.24

PD431 ENLARGED PLUMBING DEMOLITION - SECTOR 1 AND 2 0 01.24.24

PD432 ENLARGED PLUMBING DEMOLITION - SECTOR 3 AND 4 0 01.24.24

P-110 PLUMBING OVERALL 0 01.24.24

P-120 PLUMBING OVERALL 0 01.24.24

P-130 PLUMBING OVERALL 0 01.24.24

P-411 LEVEL 1 - ENLARGED PLUMBING DRAWINGS - SECTOR 1 AND 2 0 01.24.24

P-412 LEVEL 1 - ENLARGED PLUMBING DRAWINGS - SECTOR 3 AND 4 0 01.24.24

P-421 LEVEL 2 - ENLARGED PLUMBING DRAWINGS - SECTOR 1 AND 2 0 01.24.24

P-422 LEVEL 2 - ENLARGED PLUMBING DRAWINGS - SECTOR 3 AND 4 0 01.24.24

P-431 LEVEL 3 - ENLARGED PLUMBING DRAWINGS - SECTOR 1 AND 2 0 01.24.24

P-432 LEVEL 3 - ENLARGED PLUMBING DRAWINGS - SECTOR 3 AND 4 0 01.24.24

P-501 PLUMBING DETAILS 0 01.24.24

P-601 PLUMBING SCHEDULES 0 01.24.24

P-901 DOMESTIC WATER ISOMETRICS - SECTOR 1 AND 2 0 01.24.24

P-902 DOMESTIC WATER ISOMETRICS - SECTOR 3 AND 4 0 01.24.24

SHT No SHEET NAME REV DATE

P-903 SANITARY AND VENT ISOMETRICS - SECTOR 1 AND 2 0 01.24.24

P-904 SANITARY AND VENT ISOMETRICS - SECTOR 3 AND 4 0 01.24.24

07 - PLUMBING: 25

10 - MECHANICAL

M-001 LEGEND AND ABBREVIATIONS 0 01.24.24

M-110 MECHANICAL OVERALL 0 01.24.24

M-111 LEVEL 1 - MECHANICAL PLAN - SECTORS 1 AND 2 1 06.17.25

M-112 LEVEL 1 - MECHANICAL PLAN - SECTORS 3 AND 4 1 06.17.25

M-120 MECHANICAL OVERALL 0 01.24.24

M-121 LEVEL 2 - MECHANICAL PLAN - SECTORS 1 AND 2 1 06.17.25

M-122 LEVEL 2 - MECHANICAL PLAN - SECTORS 3 AND 4 1 06.17.25

M-130 MECHANICAL OVERALL 0 01.24.24

M-131 LEVEL 3 - MECHANICAL PLAN - SECTORS 1 AND 2 1 06.17.25

M-132 LEVEL 3 - MECHANICAL PLAN - SECTORS 3 AND 4 1 06.17.25

M-401 LEVEL 3 - MECHANICAL ENLARGED SECTOR 3 AND 4 0 01.24.24

M-601 MECHANICAL SCHEDULES 0 01.24.24

10 - MECHANICAL: 12

1500 - ELECTRICAL

E-001x LEGEND AND ABBREVIATIONS 0 03/14/25

ED111 LEVEL 1 - LIGHTING DEMOLITION PLANS 0 03/14/25

ED112 LEVEL 1 - LIGHTING DEMOLITION PLANS 0 03/14/25

ED211 LEVEL 2 - LIGHTING DEMOLITION PLANS 0 03/14/25

ED212 LEVEL 2 - LIGHTING DEMOLITION PLANS 0 03/14/25

ED311 LEVEL 3 - LIGHTING DEMOLITION PLANS 0 03/14/25

ED312 LEVEL 3 - LIGHTING DEMOLITION PLANS 0 03/14/25

ED313 LEVEL 3 - DEMOLITION POWER PLAN 0 03/14/25

EL111 LEVEL 1 - LIGHTING PLAN 0 03/14/25

EL112 LEVEL 1 - LIGHTING PLAN 0 03/14/25

EL211 LEVEL 2 - LIGHTING PLAN 0 03/14/25

EL212 LEVEL 2 - LIGHTING PLAN 0 03/14/25

EL311 LEVEL 3 - LIGHTING PLAN 0 03/14/25

EL312 LEVEL 3 - LIGHTING PLAN 0 03/14/25

EP110 ENLARGED POWER PLANS LEVEL 1 0 03/14/25

EP210 ENLARGED POWER PLANS LEVEL 2 0 03/14/25

EP310 ENLARGED POWER PLANS LEVEL 3 0 03/14/25

E-601x ELECTRICAL PARTIAL ONE-LINE & LIGHTING CONTROLS 0 03/14/25

E-602 INVERTER PANEL SCHEDULES 0 03/14/25

E-001 COVER SHEET 0 03/14/25

E-002 LEGEND AND ABBREVIATIONS 0 03/14/25

ED110 HIGH BAY LIGHTING DEMOLITION LIGHTING PLAN 0 03/14/25

EL110 HIGH BAY LIGHTING PLAN 0 03/14/25

E-501 LIGHTING CONTROL DETAILS 0 03/14/25

E-601 ELEVATIONS & INVERTER PANEL SCHEDULE 0 03/14/25

1500 - ELECTRICAL: 25

Grand total: 158

SHT No SHEET NAME REV DATE

A-232 LEVEL 3 - SECTORS 3 & 4 RCP 0 01.24.25

A-301 BUILDING SECTIONS 1 06.17.25

A-302 BUILDING SECTIONS 0 01.24.25

A-303 BUILDING SECTIONS 0 01.24.25

A-401 ENLARGED PLANS - 104E, 224E 0 01.24.25

A-402 ENLARGED PLANS - 143E 0 01.24.25

A-403 ENLARGED PLANS - 107W, 106W, 115W 0 01.24.25

A-404 ENLARGED PLANS - 215E, 218E 0 01.24.25

A-405 ENLARGED PLANS - 215E, 218E 0 01.24.25

A-406 ENLARGED PLANS - 214W, 215W 0 01.24.25

A-407 ENLARGED PLANS - 305E, 311E, 313E 0 01.24.25

A-408 ENLARGED PLANS - 305E, 311E, 313E 0 01.24.25

A-409 ENLARGED PLANS - 328E 0 01.24.25

A-410 ENLARGED PLANS - 303W, 304W 0 01.24.25

A-411 ENLARGED PLANS - 313W, 315W 0 01.24.25

A-412 ENLARGED PLANS 0 01.24.25

A-413 ENLARGED PLANS 0 01.24.25

A-420 INTERIOR ELEVATIONS 0 01.24.25

A-421 INTERIOR ELEVATIONS 0 01.24.25

A-422 INTERIOR ELEVATIONS 0 01.24.25

A-423 INTERIOR ELEVATIONS 0 01.24.25

A-424 INTERIOR ELEVATIONS 0 01.24.25

A-425 INTERIOR ELEVATIONS 0 01.24.25

A-501 DETAILS 0 01.24.25

A-502 DETAILS 1 06.17.25

A-601 PARTITION TYPES 0 01.24.25

A-602 PARTITION TYPES 0 01.24.25

A-603 DOOR SCHEDULE/DETAILS 0 01.24.25

04 - ARCHITECTURAL: 52

05 - INTERIORS

I-111 LEVEL 1 FINISH PLAN - SECTORS 1 & 2 1 06.17.25

I-112 LEVEL 1 FINISH PLAN - SECTORS 3 & 4 1 06.17.25

I-121 LEVEL 2 FINISH PLAN - SECTORS 1 & 2 1 06.17.25

I-122 LEVEL 2 FINISH PLAN - SECTORS 3 & 4 1 06.17.25

I-131 LEVEL 3 FINISH PLAN - SECTORS 1 & 2 1 06.17.25

I-132 LEVEL 3 FINISH PLAN - SECTORS 3 & 4 1 06.17.25

IG531 SIGNAGE DETAILS 0 01.24.25

I-400 ENLARGED PLANS & ELEVATIONS 0 01.24.25

I-401 ENLARGED PLANS & ELEVATIONS 0 01.24.25

I-402 ENLARGED PLANS & ELEVATIONS 0 01.24.25

I-403 ENLARGED PLANS & ELEVATIONS 0 01.24.25

I-404 ENLARGED PLANS & ELEVATIONS 0 01.24.25

I-405 ENLARGED PLANS & ELEVATIONS 0 01.24.25

I-406 ENLARGED PLANS & ELEVATIONS 0 01.24.25

I-407 ENLARGED PLANS & ELEVATIONS 0 01.24.25

I-408 MILLWORK DETAILS 0 01.24.25

IN601 ROOM FINISH SCHEDULE - LEVELS 1 & 2 0 01.24.25

IN602 ROOM FINISH SCHEDULE - LEVEL 3 0 01.24.25

IN603 MATERIALS & FINISH LEGEND 1 06.17.25

No. Date Description Issued by

Issued to

0 01.24.25 100% DESIGN SUBMITTAL TV FAA

1 06.17.25 AMENDMENT 1 TV FAA

L

L

J

J

G

G

F

F

E

E

D

D

C

C

B

B

1 1

2 2

3 3

4 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

P A

R K

IN

G

S

ID

E

T A

R M

A C

S

ID

E

4" CONCRETE REINFORCED

WITH 6X6 10/10 WIRE MESH

B.

A.

6" CONCRETE REINFORCED

WITH 6X6 6/6 WIRE MESH

V .I.

F

12" SLAB

80' - 0"

8" SLAB

49' - 4"

8" SLAB

49' - 4"

V .I.

F

NOTE:

INFORMATION ON THIS SHEET WAS TAKEN

FROM ORIGINAL CONSTRUCTION DOCUMENTS,

AND IS ASSUMED TO BE CORRECT. THE CONTRACTOR

SHALL VERIFY IN FIELD ALL INFORMATION FOUND ON

THIS SHEET.

Drawing No. AMP - 400 -lead or pm designed drawn approved by

SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520. No part of this record may be disclosed to persons without a "need to know", as defined in 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR parts 15 and 1520.

ISSUED BY

OFFICE OF

facility management amp − 400 drawn d r a w in g N a m e d r a w in g N a m e

AMENDMENT 1

SEAL:

/1 /2

:2

:1 P

M A u t o d e s k D o c s /1 F A A H a n g a r

R e n o v a t io n s R /1 1_

A R C H H C F .r v t

/1 /2

:2

:1 P

M A u t o d e s k D o c s /1 F A A H a n g a r R e n o v a t io n s R /1 1_

A R C H H C F .r v t

B. BRADDICK

T. AUFRANC

HANGAR 9

LEVEL 1 - SLAB THICKNESS PLAN

1550021

MATTCV

06/10/25

A-110a

1" = 20'-0"1

LEVEL 1 - SLAB THICKNESS PLAN

0 10' 20' 40'

N

SECTOR 2

SECTOR 1 SECTOR 3

SECTOR 4

HIGH BAY

8 ALL HANGAR BAY WALLS TO RECEIVE NEW PAINT FINISH FULL HEIGHT TO BOTTOM OF ROOF

DECK.

7 DIMENSIONS IN PLANS ARE TYPICALLY SHOWN TO:

A. COLUMN CENTERLINES.

B. FACE OF UNIT MASONRY OR CONCRETE.

C. FACE OF FRAMING WALLS.

D. FACE OF INTERIOR PARTITIONS (FACE OF CMU, IMP, MTL PANEL)

NOTE: WALL WITH APPLIED FINISHES ARE DIMENSIONED TO FACE OF FINISH U.O.N.

6 COORDINATE PLACEMENT OF FIRE ALARM HORN STROBES WITH FIRE PROTECTION...

5 EQUIPMENT SHOWN IN DRAWINGS IS NOT IN CONTRACT AND FURNISHED BY THE OWNER

U.O.N. REFER TO OWNER FURNISHED EQUIPMENT BOOK FOR SOME EQUIPMENT THAT

REQUIRES UTILITY CONNECTIONS IN CONTRACT

4 PROVIDE PROPER SEPARATION BETWEEN ALL DISSIMILAR MATERIALS

3 VERIFY EQUIPMENT REQUIREMENTS FOR ROUGH-IN AND UTILITY CONNECTIONS PRIOR TO

CONSTRUCTION TO ASSURE THAT PROPER BLOCKING, OPENINGS, AND UTILITY

CONNECTIONS ARE PROVIDED

2 THESE DRAWINGS ARE NOT TO BE SCALED. REFER TO DIMENSIONS INDICATED ON

DIMENSION PLANS, SHOP DRAWINGS, OR ESTABLISHED FIELD DIMENSIONS. WHERE NO

DIMENSIONS OR METHOD OF DETERMINING A LOCATION IS GIVEN, VERIFY WITH ARCHITECT

PRIOR TO PROCEEDING.

1 CONTRACTOR SHALL REFER TO THE OKLAHOMA DEPARTMENT OF LABOR (ODOL)

REGULATIONS AND ALL APPLICABLE FAA ORDERS, NOTICES, PROTOCOLS AND OTHER

REQUIREMENTS.

GENERAL NOTES

No. Date Description Issued by

Issued to

1 06.17.25 AMENDMENT 1 TV FAA

LEVEL 1

100' - 0"

LEVEL 3

128' - 0"

LEVEL 2

114' - 0"

L J H G F E D C B

REMOVE BIRD NETTING

TO THE EXTENT

NEEDED TO PAINT WALL

ABOVE NETTING

SYSTEM - REPAIR AND

REPLACE NETTING IF

REQUIRED.

FIRE RATED SEALANT

REQUIRED AT ALL

PENETRATIONS TO SEPERATE

ADMIN FROM HANGAR BAY. SEE

DETAILS ON SHEET A-502

FIRE RATED SEALANT

REQUIRED AT ALL

PENETRATIONS TO SEPERATE

ADMIN FROM HANGAR BAY. SEE

DETAILS ON SHEET A-502.

A-303

A-302

BOTTOM CHORD

OF TRUSS

Drawing No. AMP - 400 -lead or pm designed drawn approved by

SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520. No part of this record may be disclosed to persons without a "need to know", as defined in 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR parts 15 and 1520.

ISSUED BY

OFFICE OF

facility management amp − 400 drawn d r a w in g N a m e d r a w in g N a m e

AMENDMENT 1

SEAL:

/1 /2

:2

:3

P

M A u t o d e s k D o c s /1 F A A H a n g a r

R e n o v a t io n s R /1 1_

A R C H H C F .r v t

/1 /2

:2

:3

P

M A u t o d e s k D o c s /1 F A A H a n g a r R e n o v a t io n s R /1 1_

A R C H H C F .r v t

B. BRADDICK

T. AUFRANC

HANGAR 9

BUILDING SECTIONS

1550021

MATTCV

11.10.2023

A-301

3/32" = 1'-0"1

TRANSVERSE SECTION

No. Date Description Issued by

Issued to

0 01.24.25 100% DESIGN SUBMITTAL TV FAA

M A

S O

N R

Y O

P E

N

IN

G

MASONRY OPENING

2' - 0"

0' - 6" 1' - 0" 0' - 6"

SOLID CONCRETE

MASONRY UNIT INFILL.

A MINIMUM 1/2" THICKNESS OF

ELASTOMERIC FIRESTOP SEALANT

OVER MINERAL WOOL INSULATION

FIRMLY PACKED INTO OPENING AS A

PERMANENT FORM AND RECESSED

FROM THE SURFACE TO ACCOMMODATE

THE REQUIRED THICKNESS OF THE

SEALANT.

PIPE.

M A

S O

N R

Y O

P E

N

IN

G

"1

CONCRETE MASONRY UNIT.

SOLID CONCRETE

MASONRY UNIT INFILL.

CONCRETE MASONRY UNIT.

A MINIMUM 1/2" THICKNESS OF

ELASTOMERIC FIRESTOP

SEALANT.

MINERAL WOOL INSULATION

FIRMLY PACKED INTO OPENING AS

A PERMANENT FORM AND

RECESSED FROM THE SURFACE

TO ACCOMMODATE THE REQUIRED

THICKNESS OF THE SEALANT.

A MINIMUM 1/2" THICKNESS

OF ELASTOMERIC FIRESTOP

SEALANT.

PIPE.

Drawing No. AMP - 400 -lead or pm designed drawn approved by

SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520. No part of this record may be disclosed to persons without a "need to know", as defined in 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR parts 15 and 1520.

ISSUED BY

OFFICE OF

facility management amp − 400 drawn d r a w in g N a m e d r a w in g N a m e

AMENDMENT 1

SEAL:

/1 /2

:2

:4

P

M A u t o d e s k D o c s /1 F A A H a n g a r

R e n o v a t io n s R /1 1_

A R C H H C F .r v t

/1 /2

:2

:4

P

M A u t o d e s k D o c s /1 F A A H a n g a r R e n o v a t io n s R /1 1_

A R C H H C F .r v t

Designer

Author

HANGAR 9

DETAILS

1550021

ApproverTCV

06/17/25

A-502

No. Date Description Issued by

Issued to

1 06.17.25 AMENDMENT 1 TV FAA

1 1/2" = 1'-0"1

PIPE PENETRATION DETAIL

1 1/2" = 1'-0"2

PIPE PENETRATION DETAIL

0 0.25' 0.5' 1' 1.5' 0 0.25' 0.5' 1' 1.5'

ELEV.

100DW

ELECTRIC

108GW

TELE.

108FW

SHEET METAL SHOP

108W

MECHANICAL

109AW

ENTRY

109BW

PLASMA SHOP

109W

OFFICE

108EW

OFFICE

108CW

UNISEX

107W

WOMEN

106W

ELEV. EQUIP.

108AW

ENTRY

100BW

CLOS.

100CW

VEST.

100AW

STAIR

100JW

TS-2 TS-2

I-400

CG-1

CG-1

CG-1

TS-5

B

HIGH BAY

/2 I-111

/1 I-112

/2 I-112

TS-4

TS-4

TS-4

STAIR

109BW

PLASMA SHOP

109W

PAINT SHOP

110W

SHOP

111W

OFFICE

119DW

ENGINEERING LAB

119W

CLOSET

119CW

MECHANICAL

119BW

ELEV. EQUIP.

119AW

ELEV.

100GW

ENTRY

100FW

MEN

115W

STAIR

100HW

VEST

100EW TS-2

PAINT SHOP BACK

110BW

I-400

TS-4

A

A

B

B

B

B

HIGH BAY

/1 I-112

/2 I-112

/1 I-111

GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

REFER TO ROOM FINISH SCHEDULES ON SHEETS IN601 AND IN602 FOR MATERIAL AND FINISH

LOCATIONS.

REFER TO IN603 FOR ABBREVIATIONS LEGEND.

REFER TO IG531 FOR SIGNAGE DETAILS AND SIGNAGE SCHEDULE.

REFERENCE INTERIOR ELEVATIONS FOR TYPICAL WALL TILE PATTERNS.

FIELD VERIFY DIMENSIONS. MODIFY LAYOUT AS REQUIRED TO ACCOMMODATE FIELD CONDITIONS AND

ACHIEVE DESIRED PATTERN AND DESIGN INTENT.

ALL INTERIOR SUPPLY AND DIFFUSERS SHALL BE FINISHED TO MATCH ADJACENT SURFACE.

COLUMNS AND GALVANIZED BREAK METAL TRIM TO BE PAINTED TO MATCH ADJACENT WALL SURFACE, UNO.

SPEAKERS, SMOKE DETECTORS, GRILLS, ETC TO BE PAINTED TO MATCH CEILING COLOR, UNO.

ALL ELECTRICAL PANELS, ELECTRICAL OUTLET STRIPS, FIRE EXTINGUISHER CABINETS,

VENTS/ACCESS PANELS SHALL BE FACTORY FINISHED AND FIELD PAINTED TO MATCH ADJACENT

WALL.

ALL FLOORING TO BE INSTALLED FLUSH WITH ADJACENT FLOORING FINISH, UNO.

ALL FURNITURE AND EQUIPMENT IS NIC, UNO.

UNLESS NOTED OTHERWISE, WHERE ADJOINING ROOMS HAVE DIFFERENT TYPES AND/OR

THICKNESSES OF FLOORING, INSTALL TRANSITION STRIP, CENTERED AND PER MANUFACTURERS INSTRUCTIONS. TAPER FLOOR TO A REDUCTION IN THICKENSS FROM 1/2 TO 1/4 INCH ACROSS NOMINAL 4 INCH DIMENSION IN ORDER TO ENSURE A SMOOTH AND LEVEL TRANSITION BETWEEN

FLOOR SURFACES. ALL TRANSITIONS SHALL BE IN ACCORDANCE WITH ABA STANDARDS.

ALL FLOORING CHANGES TO OCCUR AT CENTER OF DOOR LEAF. IF NO DOOR, MATERIAL CHANGE TO

OCCUR AT MIDPOINT OF JAMB, UNO.

FINISH PLAN LEGEND

CG-1

CG-1 CORNER GUARD

TRANSITION STRIP LEGEND

NOTES:

1. NOT ALL TRANSITION STRIPS ARE SHOWN ON THIS SHEET.

2. REFER TO IN603 FOR ABBREVIATIONS LEGEND.

PORCELAIN FLOOR TILE TO VINYL TILE /

CARPET TILE TO VINYL TILE

VINYL TILE TO VINYL TILE

RUBBER TILE TO CONCRETE / VINYL TILE TO CONCRETE

RUBBER TILE TO VINYL TILE

TS-2

TS-3

TS-4

TS-5

FLOOR PATTERN LEGEND

REFER TO SHEET IN603 FOR ABBREVIATIONS LIST.

PFT-1

RSL-1 / RST-1

CPT-1

LVT-1

LVT-2

TO MATCH EXISTING VCT COLOR (TME)

EXISTING TO REMAIN

SIGNAGE PLAN LEGEND

KEYNOTE INDICATES

SIGN TYPEX

A NO EXIT SIGN

B FIRE EXTINGUISHER SIGN

SIGN TYPES

COLUMN NUMBER INDICATES

SIGN PLACEMENT1

AMENDMENT 1

HANGAR 9

LEVEL 1 FINISH PLAN - SECTORS 1 & 2

1550021

MATTCV

I-1110 4' 8' 16' 1/8" = 1'-0"1 LEVEL 1 FINISH PLAN - SECTOR 1

1/8" = 1'-0"2 LEVEL 1 FINISH PLAN - SECTOR 2

0 4' 8' 16'

N

SECTOR 2

SECTOR 1 SECTOR 3

SECTOR 4

HIGH BAY

No. Date Description Issued by

Issued to

0 01.24.25 100% DESIGN SUBMITTAL TV FAA

OFFICE

119AE

OFFICE

118E

CIRC INT

120E

CONF SHARE

120BE

OFFICE

120CE

CONFERENCE

121AE

OFFICE

115E

OFFICE

116E

OFFICE

114E

OFFICE

112E

OFFICE

122AE

OPEN OFFICE

122E

OFFICE

122BE

OFFICE

110E

OFFICE

111E

MECHANICAL

108E

WOMEN

106E

ELEC.

123E

TELE.

123AE

CORRIDOR

101E

EQUIP

127AE

MEN

102E

JAN.

103E

UNISEX

104E

ELEV.

100QE

STOR.

105E

STORAGE

124AE

SUPPLY INVENTORY

ROOM

128E

AJF SHIP/RCV

128AE

VEST

100ME

TS-2

STAIR

100PE

BREAK

120AE

VEST

100RE

I-401

CG-1 CG-1

CG-1

CG-1

CG-1CG-1 CG-1

CG-1

CG-1

CG-1

CG-1

CG-1 CG-1

CG-1

CG-1

CG-1CG-1

CG-1CG-1

CG-1

CG-1

CG-1

CG-1 CG-1

CG-1CG-1

TS-5

B

B

HIGH BAY

/2 I-112

/1 I-111

/2 I-111

OFFICE

130AE

OFFICE

130E

SUPPLY INVENTORY

ROOM

128E

CORRIDOR

147E

STAIR

100KE

STOR.

145E

ELEV.

100JE

ELEV. EQUIP.

146E

UPHOLSTERY SHOP

135E

MEN

143E

ELEC.

144E

TELE.

134E

VESTIBULE

143AE

CL.

143BE

FITNESS

141AE

OPEN OFFICE

141E

CORRIDOR

137E

ENTRY

138E

OFFICE

139E

OFFICE

139AE

VEST

100LE

JANITOR

133E

TS-2

I-401

CG-1

CG-1CG-1CG-1

CG-1

CG-1CG-1

TS-5

B

B

HIGH BAY

CG-1

CG-1

/1 I-111

/2 I-111

/1 I-112

FLOORING

TO ALIGN

WITH WALLTS-3

CG-1

I-406

GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

REFER TO ROOM FINISH SCHEDULES ON SHEETS IN601 AND IN602 FOR MATERIAL AND FINISH

LOCATIONS.

REFER TO IN603 FOR ABBREVIATIONS LEGEND.

REFER TO IG531 FOR SIGNAGE DETAILS AND SIGNAGE SCHEDULE.

REFERENCE INTERIOR ELEVATIONS FOR TYPICAL WALL TILE PATTERNS.

FIELD VERIFY DIMENSIONS. MODIFY LAYOUT AS REQUIRED TO ACCOMMODATE FIELD CONDITIONS AND

ACHIEVE DESIRED PATTERN AND DESIGN INTENT.

ALL INTERIOR SUPPLY AND DIFFUSERS SHALL BE FINISHED TO MATCH ADJACENT SURFACE.

COLUMNS AND GALVANIZED BREAK METAL TRIM TO BE PAINTED TO MATCH ADJACENT WALL SURFACE, UNO.

SPEAKERS, SMOKE DETECTORS, GRILLS, ETC TO BE PAINTED TO MATCH CEILING COLOR, UNO.

ALL ELECTRICAL PANELS, ELECTRICAL OUTLET STRIPS, FIRE EXTINGUISHER CABINETS,

VENTS/ACCESS PANELS SHALL BE FACTORY FINISHED AND FIELD PAINTED TO MATCH ADJACENT

WALL.

ALL FLOORING TO BE INSTALLED FLUSH WITH ADJACENT FLOORING FINISH, UNO.

ALL FURNITURE AND EQUIPMENT IS NIC, UNO.

UNLESS NOTED OTHERWISE, WHERE ADJOINING ROOMS HAVE DIFFERENT TYPES AND/OR

THICKNESSES OF FLOORING, INSTALL TRANSITION STRIP, CENTERED AND PER MANUFACTURERS INSTRUCTIONS. TAPER FLOOR TO A REDUCTION IN THICKENSS FROM 1/2 TO 1/4 INCH ACROSS NOMINAL 4 INCH DIMENSION IN ORDER TO ENSURE A SMOOTH AND LEVEL TRANSITION BETWEEN

FLOOR SURFACES. ALL TRANSITIONS SHALL BE IN ACCORDANCE WITH ABA STANDARDS.

ALL FLOORING CHANGES TO OCCUR AT CENTER OF DOOR LEAF. IF NO DOOR, MATERIAL CHANGE TO

OCCUR AT MIDPOINT OF JAMB, UNO.

FINISH PLAN LEGEND

CG-1

CG-1 CORNER GUARD

TRANSITION STRIP LEGEND

NOTES:

1. NOT ALL TRANSITION STRIPS ARE SHOWN ON THIS SHEET.

2. REFER TO IN603 FOR ABBREVIATIONS LEGEND.

PORCELAIN FLOOR TILE TO VINYL TILE /

CARPET TILE TO VINYL TILE

VINYL TILE TO VINYL TILE

RUBBER TILE TO CONCRETE / VINYL TILE TO CONCRETE

RUBBER TILE TO VINYL TILE

TS-2

TS-3

TS-4

TS-5

FLOOR PATTERN LEGEND

REFER TO SHEET IN603 FOR ABBREVIATIONS LIST.

PFT-1

RSL-1 / RST-1

CPT-1

LVT-1

LVT-2

TO MATCH EXISTING VCT COLOR (TME)

EXISTING TO REMAIN

SIGNAGE PLAN LEGEND

KEYNOTE INDICATES

SIGN TYPEX

A NO EXIT SIGN

B FIRE EXTINGUISHER SIGN

SIGN TYPES

COLUMN NUMBER INDICATES

LEVEL 1 FINISH PLAN - SECTORS 3 & 4

I-112 0 4' 8' 16'

N

SECTOR 2

SECTOR 1 SECTOR 3

SECTOR 4

HIGH BAY

1/8" = 1'-0"1 LEVEL 1 FINISH PLAN - SECTOR 3

1/8" = 1'-0"2 LEVEL 1 FINISH PLAN - SECTOR 4

0 4' 8' 16'

No. Date Description Issued by

Issued to

0 01.24.25 100% DESIGN SUBMITTAL TV FAA

200DW

MECHANICAL

231W

CORRIDOR

200BW

STAIR

200CW

WOMEN

202W

CORR.

201W

STORAGE

202BW

CONFERENCE

230W

MEN

203AW

OPEN OFFICE

229W

BREAK ROOM

204W

STORAGE

203BW

CORR.

216W OPEN OFFICE

205W

OFFICE

227AW

ELEC.

226W

BREAK ROOM

206W

TS-2

TS-2

TS-2

TS-2

TS-2

CG-1

CG-1CG-1

CG-1CG-1

CG-1CG-1

CG-1CG-1

CG-1CG-1

CG-1CG-1

/2 I-121

/1 I-122

/2 I-122

CG-1

TELE.

224W

OFFICE

208W

STAIR

225W

OFFICE

223W

OFFICE

209W

OFFICE

210W

OPEN OFFICE

221W

OFFICE

220W

OFFICE

211W

CONFERENCE ROOM

212W

OFFICE

213W

OFFICE

219W

ELEC.

218W

JANITOR

217W

ELEV.

200GW

STAIR

200HW

WOMEN

215W

MEN

214W

COPIER SYSTEMS

LAB

220AW

CORR.

216W

OFFICE

207W

CORRIDOR

200FW

TS-2

TS-2

TS-2

TS-2

TS-2

TS-2

TS-2

TS-2

TS-2

TS-2

TS-2

TS-2

TS-2

I-402

I-402

CG-1CG-1

CG-1CG-1

TS-2

TS-5

CG-1

CG-1

/1 I-122

/2 I-122

/1 I-121

I-407

GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

REFER TO ROOM FINISH SCHEDULES ON SHEETS IN601 AND IN602 FOR MATERIAL AND FINISH

LOCATIONS.

REFER TO IN603 FOR ABBREVIATIONS LEGEND.

REFER TO IG531 FOR SIGNAGE DETAILS AND SIGNAGE SCHEDULE.

REFERENCE INTERIOR ELEVATIONS FOR TYPICAL WALL TILE PATTERNS.

FIELD VERIFY DIMENSIONS. MODIFY LAYOUT AS REQUIRED TO ACCOMMODATE FIELD CONDITIONS AND

ACHIEVE DESIRED PATTERN AND DESIGN INTENT.

ALL INTERIOR SUPPLY AND DIFFUSERS SHALL BE FINISHED TO MATCH ADJACENT SURFACE.

COLUMNS AND GALVANIZED BREAK METAL TRIM TO BE PAINTED TO MATCH ADJACENT WALL SURFACE, UNO.

SPEAKERS, SMOKE DETECTORS, GRILLS, ETC TO BE PAINTED TO MATCH CEILING COLOR, UNO.

ALL ELECTRICAL PANELS, ELECTRICAL OUTLET STRIPS, FIRE EXTINGUISHER CABINETS,

VENTS/ACCESS PANELS SHALL BE FACTORY FINISHED AND FIELD PAINTED TO MATCH ADJACENT

WALL.

ALL FLOORING TO BE INSTALLED FLUSH WITH ADJACENT FLOORING FINISH, UNO.

ALL FURNITURE AND EQUIPMENT IS NIC, UNO.

UNLESS NOTED OTHERWISE, WHERE ADJOINING ROOMS HAVE DIFFERENT TYPES AND/OR

THICKNESSES OF FLOORING, INSTALL TRANSITION STRIP, CENTERED AND PER MANUFACTURERS INSTRUCTIONS. TAPER FLOOR TO A REDUCTION IN THICKENSS FROM 1/2 TO 1/4 INCH ACROSS NOMINAL 4 INCH DIMENSION IN ORDER TO ENSURE A SMOOTH AND LEVEL TRANSITION BETWEEN

FLOOR SURFACES. ALL TRANSITIONS SHALL BE IN ACCORDANCE WITH ABA STANDARDS.

ALL FLOORING CHANGES TO OCCUR AT CENTER OF DOOR LEAF. IF NO DOOR, MATERIAL CHANGE TO

OCCUR AT MIDPOINT OF JAMB, UNO.

FINISH PLAN LEGEND

CG-1

CG-1 CORNER GUARD

TRANSITION STRIP LEGEND

NOTES:

1. NOT ALL TRANSITION STRIPS ARE SHOWN ON THIS SHEET.

2. REFER TO IN603 FOR ABBREVIATIONS LEGEND.

PORCELAIN FLOOR TILE TO VINYL TILE /

CARPET TILE TO VINYL TILE

VINYL TILE TO VINYL TILE

RUBBER TILE TO CONCRETE / VINYL TILE TO CONCRETE

RUBBER TILE TO VINYL TILE

TS-2

TS-3

TS-4

TS-5

FLOOR PATTERN LEGEND

REFER TO SHEET IN603 FOR ABBREVIATIONS LIST.

PFT-1

RSL-1 / RST-1

CPT-1

LVT-1

LVT-2

TO MATCH EXISTING VCT COLOR (TME)

EXISTING TO REMAIN

SIGNAGE PLAN LEGEND

KEYNOTE INDICATES

SIGN TYPEX

A NO EXIT SIGN

B FIRE EXTINGUISHER SIGN

SIGN TYPES

COLUMN NUMBER INDICATES

LEVEL 2 FINISH PLAN - SECTORS 1 & 2

I-121

0 4' 8' 16' 1/8" = 1'-0"1 LEVEL 2 FINISH PLAN - SECTOR 1

1/8" = 1'-0"2 LEVEL 2 FINISH PLAN - SECTOR 2

0 4' 8' 16'

N

SECTOR 2

SECTOR 1 SECTOR 3

SECTOR 4

HIGH BAY No. Date Description Issued by

Issued to

0 01.24.25 100% DESIGN SUBMITTAL TV FAA

FILE STORAGE

230E

BREAK ROOM

229E

CONFERENCE ROOM

233EE

OFFICE

233DE

OFFICE

233CE

OFFICE

233BE

OFFICE

233AE

OPEN OFFICE

233E

CORRIDOR

231E

OFFICE

228E

MEN

223E

OPEN OFFICE

222E

UNISEX

224E

ELEV.

200QE

WOMEN

225E

MECHANICAL

227E

STAIR

201E

CORRIDOR

226E

OPEN OFFICE

203E

CORRIDOR

212E

OFFICE

205AE

OFFICE

205E

TS-2

TS-2

TS-2

TS-2

CG-1

CG-1

I-402

CG-1CG-1

CG-1CG-1

CG-1

CG-1

CG-1

CG-1CG-1

CG-1CG-1

CG-1CG-1

TS-5

CG-1

/2 I-122

/1 I-121

/2 I-121

CG-1CG-1

OFFICE

222AE

OPEN OFFICE

222E

TELE.

220E

OFFICE

205E

OFFICE

206E

OFFICE

205CE

OFFICE

205BE

OFFICE

206AE

STAIR

207E

OFFICE

209E

OFFICE

209AE

OFFICE

209BE

CORRIDOR

218AE

ELEV.

200JE

MECHANICAL

217E

MEN

218E

CORRIDOR

212E

ELEC.

216E

WOMEN

215E

VEST.

215AE

JANITOR

215BE

OPEN OFFICE

210E

CONFERENCE ROOM

213AE

OPEN OFFICE

213E

COPIER

214E

OFFICE

213BE

OFFICE

213CE

TS-2

TS-2

TS-2

TS-2

TS-2 TS-2

TS-2

TS-2

TS-2

CG-1

CG-1

CG-1

CG-1

CG-1CG-1

CG-1

I-403

I-403

CG-1

CG-1

CG-1

CG-1CG-1

CG-1

TS-5

CG-1CG-1

CG-1

CG-1

CG-1CG-1

CG-1CG-1

/1 I-121

/2 I-121

/1 I-122

FLOORING

TO ALIGN

WITH WALL

TS-3

CG-1

I-406

I-407

GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

REFER TO ROOM FINISH SCHEDULES ON SHEETS IN601 AND IN602 FOR MATERIAL AND FINISH

LOCATIONS.

REFER TO IN603 FOR ABBREVIATIONS LEGEND.

REFER TO IG531 FOR SIGNAGE DETAILS AND SIGNAGE SCHEDULE.

REFERENCE INTERIOR ELEVATIONS FOR TYPICAL WALL TILE PATTERNS.

FIELD VERIFY DIMENSIONS. MODIFY LAYOUT AS REQUIRED TO ACCOMMODATE FIELD CONDITIONS AND

ACHIEVE DESIRED PATTERN AND DESIGN INTENT.

ALL INTERIOR SUPPLY AND DIFFUSERS SHALL BE FINISHED TO MATCH ADJACENT SURFACE.

COLUMNS AND GALVANIZED BREAK METAL TRIM TO BE PAINTED TO MATCH ADJACENT WALL SURFACE, UNO.

SPEAKERS, SMOKE DETECTORS, GRILLS, ETC TO BE PAINTED TO MATCH CEILING COLOR, UNO.

ALL ELECTRICAL PANELS, ELECTRICAL OUTLET STRIPS, FIRE EXTINGUISHER CABINETS,

VENTS/ACCESS PANELS SHALL BE FACTORY FINISHED AND FIELD PAINTED TO MATCH ADJACENT

WALL.

ALL FLOORING TO BE INSTALLED FLUSH WITH ADJACENT FLOORING FINISH, UNO.

ALL FURNITURE AND EQUIPMENT IS NIC, UNO.

UNLESS NOTED OTHERWISE, WHERE ADJOINING ROOMS HAVE DIFFERENT TYPES AND/OR

THICKNESSES OF FLOORING, INSTALL TRANSITION STRIP, CENTERED AND PER MANUFACTURERS INSTRUCTIONS. TAPER FLOOR TO A REDUCTION IN THICKENSS FROM 1/2 TO 1/4 INCH ACROSS NOMINAL 4 INCH DIMENSION IN ORDER TO ENSURE A SMOOTH AND LEVEL TRANSITION BETWEEN

FLOOR SURFACES. ALL TRANSITIONS SHALL BE IN ACCORDANCE WITH ABA STANDARDS.

ALL FLOORING CHANGES TO OCCUR AT CENTER OF DOOR LEAF. IF NO DOOR, MATERIAL CHANGE TO

OCCUR AT MIDPOINT OF JAMB, UNO.

FINISH PLAN LEGEND

CG-1

CG-1 CORNER GUARD

TRANSITION STRIP LEGEND

NOTES:

1. NOT ALL TRANSITION STRIPS ARE SHOWN ON THIS SHEET.

2. REFER TO IN603 FOR ABBREVIATIONS LEGEND.

PORCELAIN FLOOR TILE TO VINYL TILE /

CARPET TILE TO VINYL TILE

VINYL TILE TO VINYL TILE

RUBBER TILE TO CONCRETE / VINYL TILE TO CONCRETE

RUBBER TILE TO VINYL TILE

TS-2

TS-3

TS-4

TS-5

FLOOR PATTERN LEGEND

REFER TO SHEET IN603 FOR ABBREVIATIONS LIST.

PFT-1

RSL-1 / RST-1

CPT-1

LVT-1

LVT-2

TO MATCH EXISTING VCT COLOR (TME)

EXISTING TO REMAIN

SIGNAGE PLAN LEGEND

KEYNOTE INDICATES

SIGN TYPEX

A NO EXIT SIGN

B FIRE EXTINGUISHER SIGN

SIGN TYPES

COLUMN NUMBER INDICATES

LEVEL 2 FINISH PLAN - SECTORS 3 & 4

I-122

0 4' 8' 16' 1/8" = 1'-0"1 LEVEL 2 FINISH PLAN - SECTOR 3

1/8" = 1'-0"2 LEVEL 2 FINISH PLAN - SECTOR 4

0 4' 8' 16'

N

SECTOR 2

SECTOR 1 SECTOR 3

SECTOR 4

HIGH BAY No. Date Description Issued by

Issued to

0 01.24.25 100% DESIGN SUBMITTAL TV FAA

300DW

CORRIDOR

300BW

ELEC.

335W

OFFICE

334W

OFFICE

333W

OFFICE

332W

OPEN OFFICE

330W

OPEN OFFICE

329W

OFFICE

328W

LIBRARY/FILE ROOM

308W

OFFICE

307W

OPEN OFFICE

306W

WOMEN

304W

MEN

303W

STAIR

301W

CORR.

302W

TS-2TS-2

TS-2

TS-2

TS-2

TS-2

TS-2

TS-2

TS-2

TS-2

TS-2

TS-2

CG-1

CG-1

CG-1

CG-1

I-404

I-404

CG-1CG-1 CG-1CG-1

CG-1CG-1 CG-1CG-1

TS-5

TS-5

/2 I-131

/1 I-132

/2 I-132

FLOOR TO ALIGN

WITH WALL

TELE.

325W

ELEC.

326W

BREAK ROOM

309W

CONFERENCE

310W

OFFICE

324W

OFFICE

323W

OFFICE

311W

OFFICE

322W

STORAGE

321W

OFFICE

320W

OPEN OFFICE

312W

OFFICE

320AW

ELEC.

319W

MECHANICAL

318W

ELEV.

300GW

CORRIDOR

300FW

MEN

313W

WOMEN

315W

STAIR

316W

JAN.

317W

STAIR

327W

TS-2

TS-2

TS-2

TS-2

TS-2

TS-2

TS-2

TS-2

TS-2

TS-2

I-404

I-405

TS-5

/1 I-132

/2 I-132

/1 I-131

GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

REFER TO ROOM FINISH SCHEDULES ON SHEETS IN601 AND IN602 FOR MATERIAL AND FINISH

LOCATIONS.

REFER TO IN603 FOR ABBREVIATIONS LEGEND.

REFER TO IG531 FOR SIGNAGE DETAILS AND SIGNAGE SCHEDULE.

REFERENCE INTERIOR ELEVATIONS FOR TYPICAL WALL TILE PATTERNS.

FIELD VERIFY DIMENSIONS. MODIFY LAYOUT AS REQUIRED TO ACCOMMODATE FIELD CONDITIONS AND

ACHIEVE DESIRED PATTERN AND DESIGN INTENT.

ALL INTERIOR SUPPLY AND DIFFUSERS SHALL BE FINISHED TO MATCH ADJACENT SURFACE.

COLUMNS AND GALVANIZED BREAK METAL TRIM TO BE PAINTED TO MATCH ADJACENT WALL SURFACE, UNO.

SPEAKERS, SMOKE DETECTORS, GRILLS, ETC TO BE PAINTED TO MATCH CEILING COLOR, UNO.

ALL ELECTRICAL PANELS, ELECTRICAL OUTLET STRIPS, FIRE EXTINGUISHER CABINETS,

VENTS/ACCESS PANELS SHALL BE FACTORY FINISHED AND FIELD PAINTED TO MATCH ADJACENT

WALL.

ALL FLOORING TO BE INSTALLED FLUSH WITH ADJACENT FLOORING FINISH, UNO.

ALL FURNITURE AND EQUIPMENT IS NIC, UNO.

UNLESS NOTED OTHERWISE, WHERE ADJOINING ROOMS HAVE DIFFERENT TYPES AND/OR

THICKNESSES OF FLOORING, INSTALL TRANSITION STRIP, CENTERED AND PER MANUFACTURERS INSTRUCTIONS. TAPER FLOOR TO A REDUCTION IN THICKENSS FROM 1/2 TO 1/4 INCH ACROSS NOMINAL 4 INCH DIMENSION IN ORDER TO ENSURE A SMOOTH AND LEVEL TRANSITION BETWEEN

FLOOR SURFACES. ALL TRANSITIONS SHALL BE IN ACCORDANCE WITH ABA STANDARDS.

ALL FLOORING CHANGES TO OCCUR AT CENTER OF DOOR LEAF. IF NO DOOR, MATERIAL CHANGE TO

OCCUR AT MIDPOINT OF JAMB, UNO.

FINISH PLAN LEGEND

CG-1

CG-1 CORNER GUARD

TRANSITION STRIP LEGEND

NOTES:

1. NOT ALL TRANSITION STRIPS ARE SHOWN ON THIS SHEET.

2. REFER TO IN603 FOR ABBREVIATIONS LEGEND.

PORCELAIN FLOOR TILE TO VINYL TILE /

CARPET TILE TO VINYL TILE

VINYL TILE TO VINYL TILE

RUBBER TILE TO CONCRETE / VINYL TILE TO CONCRETE

RUBBER TILE TO VINYL TILE

TS-2

TS-3

TS-4

TS-5

FLOOR PATTERN LEGEND

REFER TO SHEET IN603 FOR ABBREVIATIONS LIST.

PFT-1

RSL-1 / RST-1

CPT-1

LVT-1

LVT-2

TO MATCH EXISTING VCT COLOR (TME)

EXISTING TO REMAIN

SIGNAGE PLAN LEGEND

KEYNOTE INDICATES

SIGN TYPEX

A NO EXIT SIGN

B FIRE EXTINGUISHER SIGN

SIGN TYPES

COLUMN NUMBER INDICATES

LEVEL 3 FINISH PLAN - SECTORS 1 & 2

I-131 0 4' 8' 16'

1/8" = 1'-0"1 LEVEL 3 FINISH PLAN - SECTOR 1

1/8" = 1'-0"2 LEVEL 3 FINISH PLAN - SECTOR 2

0 4' 8' 16'

N

SECTOR 2

SECTOR 1 SECTOR 3

SECTOR 4

HIGH BAY No. Date Description Issued by

Issued to

0 01.24.25 100% DESIGN SUBMITTAL TV FAA

CONFERENCE

303BE

STORAGE / BREAK

303AE

OFFICE

304EE

CONFERENCE

304AE

OFFICE

304BE

OFFICE

304E

OFFICE

303DE

OFFICE

303EE

OFFICE

302AE

OFFICE

302BE

OFFICE

302CE

OPEN OFFICE

302E

CORR.

301E

BREAK ROOM

304DEOFFICE

304CE

MEN

305E

WOMEN

313E

MECHANICAL

306E

ELEV.

300QE

STAIR

307E

OFFICE

309AE

ELEC.

308E

CORR.

310E

CORRIDOR

317E

JANITOR

312E

OFFICE

310AE

OFFICE

310CE

OFFICE

310BE

OPEN OFFICE

309E

CONFERENCE ROOM

318AE

BREAK ROOM

310DE

OFFICE

310EE

OFFICE

310GE

TS-2

TS-2

TS-2

TS-2

TS-2

TS-2

UNISEX

311E

TS-2 TS-2

TS-2

CG-1

CG-1

CG-1

CG-1

I-405

I-408

TS-5

TS-3

/2 I-132

/1 I-131

/2 I-131

OFFICE

310HE

OFFICE

310FE

TELE.

314E

INDUST.

318E

EQUIP.

316E

INDUST.

315E

STAIR

333E

STOR.

332E

CORRIDOR

329E

ELEV.

300JE MECHANICAL

331E

STOR.

319E

STAIR

320E

ELEC.

330E

MEN

328E

CL.

328AE

BREAK ROOM

327CE

CIRC. INT.

321E

OFFICE

321BE

STO OFC.

322E

OFFICE

321AE

INDUSTRIAL

327E

INDUSTRIAL

323E

STO.

324E

TS-2

TS-2

TS-2

TS-2

TS-2

CORR.

325E

TS-2

TS-2

CG-1

CG-1

CG-1

CG-1

I-406

TS-5

TS-5

CG-1

TS-2

TS-3

/1 I-131

/2 I-131

/1 I-132

INDUSTRIAL OFFICE

327ABE

TS-2

TS-3

OFFICE

310GE

CG-1

CG-1 CG-1

I-406

TS-4

TS-4

TS-4

GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

REFER TO ROOM FINISH SCHEDULES ON SHEETS IN601 AND IN602 FOR MATERIAL AND FINISH

LOCATIONS.

REFER TO IN603 FOR ABBREVIATIONS LEGEND.

REFER TO IG531 FOR SIGNAGE DETAILS AND SIGNAGE SCHEDULE.

REFERENCE INTERIOR ELEVATIONS FOR TYPICAL WALL TILE PATTERNS.

FIELD VERIFY DIMENSIONS. MODIFY LAYOUT AS REQUIRED TO ACCOMMODATE FIELD CONDITIONS AND

ACHIEVE DESIRED PATTERN AND DESIGN INTENT.

ALL INTERIOR SUPPLY AND DIFFUSERS SHALL BE FINISHED TO MATCH ADJACENT SURFACE.

COLUMNS AND GALVANIZED BREAK METAL TRIM TO BE PAINTED TO MATCH ADJACENT WALL SURFACE, UNO.

SPEAKERS, SMOKE DETECTORS, GRILLS, ETC TO BE PAINTED TO MATCH CEILING COLOR, UNO.

ALL ELECTRICAL PANELS, ELECTRICAL OUTLET STRIPS, FIRE EXTINGUISHER CABINETS,

VENTS/ACCESS PANELS SHALL BE FACTORY FINISHED AND FIELD PAINTED TO MATCH ADJACENT

WALL.

ALL FLOORING TO BE INSTALLED FLUSH WITH ADJACENT FLOORING FINISH, UNO.

ALL FURNITURE AND EQUIPMENT IS NIC, UNO.

UNLESS NOTED OTHERWISE, WHERE ADJOINING ROOMS HAVE DIFFERENT TYPES AND/OR

THICKNESSES OF FLOORING, INSTALL TRANSITION STRIP, CENTERED AND PER MANUFACTURERS INSTRUCTIONS. TAPER FLOOR TO A REDUCTION IN THICKENSS FROM 1/2 TO 1/4 INCH ACROSS NOMINAL 4 INCH DIMENSION IN ORDER TO ENSURE A SMOOTH AND LEVEL TRANSITION BETWEEN

FLOOR SURFACES. ALL TRANSITIONS SHALL BE IN ACCORDANCE WITH ABA STANDARDS.

ALL FLOORING CHANGES TO OCCUR AT CENTER OF DOOR LEAF. IF NO DOOR, MATERIAL CHANGE TO

OCCUR AT MIDPOINT OF JAMB, UNO.

FINISH PLAN LEGEND

CG-1

CG-1 CORNER GUARD

TRANSITION STRIP LEGEND

NOTES:

1. NOT ALL TRANSITION STRIPS ARE SHOWN ON THIS SHEET.

2. REFER TO IN603 FOR ABBREVIATIONS LEGEND.

PORCELAIN FLOOR TILE TO VINYL TILE /

CARPET TILE TO VINYL TILE

VINYL TILE TO VINYL TILE

RUBBER TILE TO CONCRETE / VINYL TILE TO CONCRETE

RUBBER TILE TO VINYL TILE

TS-2

TS-3

TS-4

TS-5

FLOOR PATTERN LEGEND

REFER TO SHEET IN603 FOR ABBREVIATIONS LIST.

PFT-1

RSL-1 / RST-1

CPT-1

LVT-1

LVT-2

TO MATCH EXISTING VCT COLOR (TME)

EXISTING TO REMAIN

SIGNAGE PLAN LEGEND

KEYNOTE INDICATES

SIGN TYPEX

A NO EXIT SIGN

B FIRE EXTINGUISHER SIGN

SIGN TYPES

COLUMN NUMBER INDICATES

LEVEL 3 FINISH PLAN - SECTORS 3 & 4

I-132

0 4' 8' 16' 1/8" = 1'-0"1 LEVEL 3 FINISH PLAN - SECTOR 3

1/8" = 1'-0"2 LEVEL 3 FINISH PLAN - SECTOR 4

0 4' 8' 16'

N

SECTOR 2

SECTOR 1 SECTOR 3

SECTOR 4

HIGH BAY No. Date Description Issued by

Issued to

0 01.24.25 100% DESIGN SUBMITTAL TV FAA

GENERAL NOTES

1.

2.

3.

4.

5.

6.

REFER TO SHEET IN601 & IN602 FOR MATERIAL AND FINISH LOCATIONS.

TRANSITION STRIPS TO BE CENTERED UNDER DOOR AND INSTALLED

PER MANUFACTURERS INSTRUCTIONS.

UNLESS NOTED OTHERWISE, WHERE ADJOINING ROOMS HAVE DIFFERENT

TYPES AND/OR THICKNESS OF FLOORING, INSTALL METAL EDGE PROTECTIVE

STRIP AND TAPER FLOOR TO REDUCTION IN THICKNESS FROM 1/2 TO 1/4 INCH

ACROSS NOMINAL 4 INCH DIMENSION IN ORDER TO ENSURE A SMOOTH AND

LEVEL TRANSITION BETWEEN FLOOR SURFACES. ALL TRANSITIONS SHALL BE

IN ACCORDANCE WITH ANSI, ADA & ABA STANDARDS.

COLUMNS AND GALVANIZED BREAK METAL TRIM TO BE PAINTED TO MATCH

ADJACENT WALL SURFACE.

ALL VENTS/ACCESS PANELS TO BE PAINTED TO MATCH ADJACENT SURFACE.

AWC-1 - WALL PANELS MUST BE CLEANED AND PORPERLY PREPARED

BEFORE COATING IS APPLIED. REFER TO SPECIFICATION 099600.

ABBREVIATIONS LEGEND

ACP ACOUSTICAL CEILING PANEL

AWC ACRYLIC WALL COVERING

CG CORNER GUARD

CPT CARPET TILE

FRP FIBERGLASS REINFORCED PANEL

GT GROUT

HPL HIGH PRESSURE LAMINATE

LVT LUXURY VINYL TILE

NIC NOT IN CONTRACT

PFT PORCELAIN FLOOR TILE

PT PAINT

PWB PORCELAIN WALL BASE

PWT PORCELAIN WALL TILE

RB RUBBER BASE

RM ROOM

RSL RESILIENT STAIR LANDING

RST RESILIENT STAIR TREADS

SG SIGNAGE

SSM SOLID SURFACE MATERIAL

TME TO MATCH EXISTING

TP TOILET PARTITION

TS TRANSITION STRIP

UNO UNLESS NOTED OTHERWISE

VCT VINYL COMPOSITION TILE

MATERIALS & FINISH LEGEND

IN603

CEILING TYPES

TYPE DESCRIPTION MANUFACTURER PATTERN / FINISH COMMENTS

ACP-1 ACOUSTCAL CEILING PANEL USG MARS, HIGH-NRC/HIGH-CAC, ITEM 86346,

SLT EDGE, 24" X 24", GRID DONN DX/DXL,

WHITE

ACP-2 ACOUSTCAL CEILING PANEL ARMSTRONG CERAMAGUARD FINE FISSURED, ITEM 607,

SQUARE LAY-IN, 24" X 24", PRELUDE GRID,

WHITE

RESTROOMS

PT-1 PAINT SHERWIN WILLIAMS ACRYLIC ENAMEL, SATIN FINISH, SW 7005

PURE WHITE

WALL FINISHES

TYPE DESCRIPTION MANUFACTURER PATTERN / FINISH COLOR COMMENTS

AWC-1 MULTI-SURFACE ACYLIC WALL

COATING

SHERWIN WILLIAMS PRO INDUSTRIAL

MULTI-SURFACE ACYLIC,

EGGSHELL

SW1017 GARBO SILVER COLOR DISCONTINUED, CUSTOM MIX

PT-2 PAINT SHERWIN WILLIAMS EGGSHELL SW1017 GARBO SILVER FIELD PAINT - DISCONTINUED,CUSTOM MIX

PT-3 PAINT SHERWIN WILLIAMS ACRYLIC ENAMEL, SATIN SW 7019 GAUNTLET

GRAY

DOOR FRAMES, ENTRANCE FRAMES

PT-4 PAINT SHERWIN WILLIAMS EGGSHELL SW 7017 DORIAN GRAY ACCENT PAINT

PWT-1 PORCELAIN WALL TILE CROSSVILLE JAVA JOINT, 12" X 24" TWO SUGARS RESTROOM WALL TILE, INSTALL:

HORIZONTAL, STACKED

WALL BASE TYPES

TYPE DESCRIPTION MANUFACTURER PATTERN / FINISH COLOR COMMENTS

PWB-1 PORCELAIN WALL BASE CROSSVILLE JAVA JOINT, 6" X 12" COVE

BASE

TWO SUGARS

RB-1 RUBBER WALL BASE TARKETT/JOHNSONITE BASEWORKS, 4" HIGH 20 CHARCOAL

FLOOR TYPES

TYPE DESCRIPTION MANUFACTURER PATTERN / FINISH COLOR NOTES

CPT-1 CARPET TILE INTERFACE, ARCHITECTURAL

PLANS COLLECTION

TO SCALE, 50CM X 50CM,

NON-DIRECTIONAL

BLUEPRINT 7772

LVT-1 LUXURY VINYL TILE INTERFACE NATURAL STONES, 50CM X

50CM, NON-DIRECTIONAL

WARM IMPALA A00104

LVT-2 LUXURY VINYL TILE TARKETT/JOHNSONITE VICTORY CHROMA VCM, 12" X

12", NON-DIRECTIONAL

METROPOLIS 0223

PFT-1 PORCELAIN FLOOR TILE CROSSVILLE GOTHAM, 12" X 24", 3/8"

THICKNESS

MAINLINE AV324 RESTROOM FLOOR TILE, INSTALL:

HORIZONTAL, STACKED

RSL-1 RESILIENT STAIR LANDING TARKETT/JOHNSONITE SOLID COLOR RUBBER,

RAISED ROUND, 24" X 24"

20 CHARCOAL STAIRS

RST-1 RESILIENT STAIR TREAD TARKETT/JOHNSONITE ANGLE FIT RUBBER STAIR

TREAD W/ INTEGRATED

RISER, RAISED ROUND, GREY

GRIT TAPE

20 CHARCOAL STAIRS

MISC. FINISH TYPES

TYPE DESCRIPTION MANUFACTURER PATTERN / FINISH COLOR COMMENTS

CG-1 CORNER GUARD CS ACROVYN CO-8, STAINLESS, 3/16"

NOSE RADIUS, 2" LEG

#4 SATIN 8'H, PROVIDE ENDCAPS

FRP-1 FIBERGLASS REINFORCED PANELS CRANE COMPOSITES GLASBORD, PEBBLED

EMBOSSED, 0.90"

85 WHITE JANITORS CLOSETS

GT-1 GROUT MAPEI KERAPOXY 107 IRON PFT-1

GT-2 GROUT MAPEI KERAPOXY 93 WARM GRAY PWT-1

HPL-1 HIGH PRESSURE LAMINATE WILSONART 38 FINE VELVET TEXTURE 8235 DAINTREE BREAKROOMS, RESTROOMS

SG-1 SIGNAGE 2/90 SIGN SYSTEMS SLIDE MODULAR SIGN

SYSTEM

703 COOL GREY SIGN BACKGROUND AND END CAPS

SG-2 SIGNAGE 2/90 SIGN SYSTEMS SLIDE MODULAR SIGN

SYSTEM

708 SOFT WHITE SIGN LETTERING /COPY

SSM-1 SOLID SURFACE MATERIAL FORMICA GRADE 02, 1/2" THICK 758 BIANCO MINERAL BREAKROOM / RESTROOM COUNTERTOPS

TP-1 TOILET PARTITION ASI SOLID CORE

COLOR-THRU PHENOLIC

#3450C FOG ALUMINUM BRACKETS

TS-1 TRANSITION STRIP SCHLUTER QUADEC SATIN ANODIZED

ALUMINUM

VERTICAL TRANSITION STRIP

TS-2 TRANSITION STRIP SCHLUTER RENO-U SATIN ANODIZED

ALUMINUM

PORCELAIN FLOOR TILE TO VINYL TILE,

CARPET TILE TO VINYL TILE

TS-3 TRANSITION STRIP SCHLUTER SCHIENE SATIN ANODIZED

ALUMINUM

VINYL TILE TO VINYL TILE

TS-4 TRANSITION STRIP TARKETT/JOHNSONITE SSR-XXX-B 20 CHARCOAL RUBBER TILE TO CONCRETE, VINYL TILE TO

CONCRETE

TS-5 TRANSITION STRIP TARKETT/JOHNSONITE SLT-XX-B 20 CHARCOAL RUBBER TILE TO VINYL TILE

INTERIOR MATERIALS & FINISH LEGEND

No. Date Description Issued by

Issued to

0 01.24.25 100% DESIGN SUBMITTAL TV FAA

SYMBOL DESCRIPTION SYMBOL DESCRIPTION

C

CEILING MOUNTED HORN/STROBE, XX

INDICATES CANDELA RATING

C

CEILING MOUNTED STROBE, XX INDICATES

CANDELA RATING

SPD SURGE PROTECTION DEVICE

FIRE ALARM SYMBOLS LEGEND

XX

END OF LINE RESISTOR

APPLICABLE CODES AND STANDARDS:

• IEBC - INTERNATIONAL EXISTING BUILDING CODE, 2015 EDITION

• IBC - INTERNATIONAL BUILDING CODE, 2015 EDITION

• NFPA 72 - NATIONAL FIRE ALARM AND SIGNALING CODE, 2022 EDITION

MANUAL PULL STATIONF

FACU EXISTING FIRE ALARM CONTROL UNIT

XX

S/R DUCT SMOKE DETECTOR, S/R = SUPPLY /

RETURN SIDE

WALL/CEILING MOUNTED HEAT DETECTOR

P

WALL/CEILING MOUNTED SMOKE

DETECTOR, EL = FOR ELEVATOR CONTROL

P

WALL/CEILING MOUNTED SMOKE

DETECTOR

EL

LCP EXISTING LIGHTING CONTROL PANEL

FIRE ALARM GENERAL NOTES:

1. PROJECT SCOPE INCLUDES DELEGATED DESIGN AND INSTALLATION OF A FIRE ALARM SYSTEM FOR HANGAR 9 AT MIKE MONRONEY AERONAUTICAL

CENTER. EXISTING NOTIFICATION AND INITIATION DEVICES SHALL BE DEMOLISHED AND REPLACED WITH NEW DEVICES THROUGHOUT THE FACILITY.

CONDUIT TO BE REUSED WHERE POSSIBLE. NEW DEVICES TO BE ADDRESSABLE AND COMPATIBLE WITH THE EXISTING FIRE ALARM PANEL SIMPLEX 4100 U

FIRE CONTROL.

2. CONTRACTOR TO BE JCI. ANY REFERENCE TO CONTRACTOR WITHIN FA SERIES DRAWINGS SHALL BE REFERENCING JCI.

3. CONTRACTOR TO PROVIDE ALL MATERIALS AND LABOR FOR THE DETAILED DESIGN AND INSTALLATION REQUIRED FOR A COMPLETE AND FUNCTIONAL FIRE

ALARM SYSTEM. CONTRACTOR IS RESPONSIBLE FOR ALL APPLICABLE FEES, TAXES AND PERMIT COSTS. ALL FIRE ALARM SYSTEM MATERIALS AND DESIGN SHALL COMPLY WITH CONTRACT DRAWINGS, CONTRACT SCOPE OF WORK, AND THE APPLICABLE CODES AND STANDARDS INDICATED ON THIS SHEET.

4. CONTRACTOR SHALL FIELD VERIFY ALL SITE CONDITIONS AND INFORMATION CONTAINED IN CONTRACT DRAWINGS. CONTRACT DRAWINGS MAY NOT SHOW ALL INFORMATION NECESSARY FOR INSTALLATION OF THE SYSTEM BUT ARE INTENDED TO ASSIST THE CONTRACTOR IN PROVIDING A VISUAL

REPRESENTATION OF THE PROPOSED SCOPE OF WORK.

5. THE CONTRACTOR SHALL SUBMIT ALL REQUIRED DOCUMENTS AND MATERIALS TO CREATE A COMPLETE SHOP DRAWING PACKAGE IN ACCORDANCE WITH NFPA 72 CHAPTER 7 WHICH INCLUDES, BUT IS NOT LIMITED, TO SHOP DRAWINGS, BATTERY CALCULATIONS, VOLTAGE DROP CALCULATIONS, AND MATERIAL DATA SHEETS. THE SHOP DRAWING PACKAGE SHALL BE SUBMITTED FOR REVIEW BY BENHAM FIRE PROTECTION ENGINEER AND MUST BE APPROVED BEFORE THE PACKAGE CAN BE SUBMITTED TO THE AUTHORITY HAVING JURISDICTION FOR PERMIT. INSTALLATION OF THE FIRE ALARM SYSTEM IS NOT PERMITTED UNTIL THE PACKAGE IS APPROVED BY THE BENHAM FIRE PROTECTION ENGINEER AND A PERMIT HAS BEEN ISSUED.

6. ALL WIRING SHALL BE CLASS "B" AND INSTALLED IN METALLIC CONDUIT IN ACCORDANCE WITH NFPA 70 AND NFPA 72. ALL CONDUITS SHALL BE SECURELY

ATTACHED TO THE BUILDING STRUCTURE.

7. WIRING SHALL NOT EXCEED 80% OF ITS RATED OUTPUT. ALL SLC SHALL BE SOLID OR STRANDED COPPER. ALL SLC CIRCUITS SHALL BE MINIMUM 16 GAUGE.

8. PULL ALL CONDUCTORS SPLICE FREE; CONDUCTORS MUST BE CONTINUOUS FROM DEVICE TO DEVICE. THE USE OF WIRE NUTS, CRIMPED CONNECTORS, OR TWISTING OF CONDUCTORS IS PROHIBITED.

9. RUN ALL WIRING TO AND WITHIN CONTROL PANELS IN THE VERTICAL OR HORIZONTAL PLANE, MAKE ALL TURNS AT 90-DEGREE ANGLES, AND TIGHTLY

BUNDLE, WRAP, AND IDENTIFY ALL CONDUCTORS INDIVIDUALLY WITH PERMANENT MARKINGS. CONDUCTOR MARKINGS MUST BE PRINTED LABELS, PERMANENTLY AFFIXED TO THE CONDUCTOR VIA SHRINK WRAP.

10. ALL DEVICES MUST HAVE SCREW TERMINALS. WHERE DEVICES ARE ONLY PROVIDED WITH PIGTAILS FROM THE MANUFACTURER, PIGTAILS MUST BE

LANDED ON TERMINAL STRIPS MOUNTED WITHIN THE JUNCTION BOX.

11. ALL TERMINATIONS MUST BE AT A TERMINAL STRIP OR THE DEVICE SCREW TERMINALS. TERMINAL STRIPS ARE ONLY PERMITTED WHERE DIRECT CONNECTION TO A DEVICE IS NOT POSSIBLE. (E.G., PIGTAILS OFF A RATE-COMPENSATING HEAT DETECTOR).

12. THE LOCATION OF NOTIFICATION DEVICES SHOWN IS SUGGESTED. ACTUAL LOCATIONS TO BE DETERMINED BY CONTRACTOR IN ACCORDANCE WITH THE REQUIREMENTS OF THE APPLICABLE CODES. NOTIFICATION APPLIANCES SHALL BE COORDINATED WITH ARCHITECTURAL, STRUCTURAL, PROCESS, MECHANICAL, AND ELECTRICAL FIXTURES AND FEATURES.

13. HORN / STROBES SHALL BE RED WITH A CLEAR LENS AND MARKED "FIRE" IN WHITE LETTERS. MINIMUM STROBE CANDELA SHOWN FOR REFERENCE ONLY.

ACTUAL CANDELA SHALL BE DETERMINED BY CONTRACTOR BASED ON LAYOUT. ENSURE STROBES IN THE SAME FIELD OF VIEW FLASH IN

SYNCHRONIZATION.

14. MANUAL PULL STATIONS SHALL BE PROVIDED THROUGHOUT THE FACILITY IN ACCORDANCE WITH NFPA 72. MANUAL PULL STATIONS SHALL BE ADDRESSABLE DOUBLE ACTION TYPE WITH MECHANICAL KEY RESET. THE KEY REQUIRED SHALL BE THE SAME KEY AS REQUIRED FOR THE MAIN FIRE

ALARM CONTROL PANEL.

15. A SINGLE MANUAL PULL STATION ON A SEPARATE CIRCUIT SHALL ALSO BE PROVIDED IN THE VICINITY OF THE SPRINKLER RISER. THE MANUAL PULL STATION SHALL BE CONNECTED TO A SEPARATE CIRCUIT THAT IS NOT PLACED “ON TEST” WHEN THE DETECTION DEVICES OR SPRINKLER SYSTEM IS PLACED “ON TEST”. THE MANUAL PULL STATION REQUIRED BY NFPA 72 SECTION 23.8.5.1.2 IS INTENDED TO PROVIDE A BACKUP MEANS TO MANUALLY ACTIVATE THE FIRE ALARM SYSTEM WHEN THE AUTOMATIC FIRE DETECTION SYSTEM OR WATER-FLOW DEVICES ARE OUT OF SERVICE DUE TO

MAINTENANCE OR TESTING.

16. SMOKE DETECTORS SHALL BE LOCATED A MINIMUM OF THREE FEET FROM ANY HVAC DIFFUSER OR RETURN GRILLE.

17. DUCT SMOKE DETECTORS SHALL BE PROVIDED IN ALL HVAC DUCTS WHERE REQUIRED BY THE INTERNATIONAL MECHANICAL CODE AND SHALL HAVE

AUXILIARY CONTACTS TO PROVIDE CONTROL, INTERLOCK, AND SHUTDOWN FUNCTIONS OF THE HVAC SYSTEMS. DETECTORS SHALL BE POWERED BY THE

FIRE ALARM CONTROL UNIT.

18. THE FIRE ALARM SYSTEM SHALL MONITOR THE SPRINKLER SYSTEM WATERFLOW AND TAMPER SWITCHES.

19. SURGE PROTECTION DEVICES (SPD) SHALL BE PROVIDED ON ALL 120 VAC CIRCUITS TO CONTROL PANELS, SUBPANELS, TRANSMITTERS, AMPLIFIER

PANELS, AND BOOSTER PANELS. SPD SHALL HAVE BOTH A UL 1449 AND UL 1283 LISTING AND SHALL BE LOCATED IN AN ADJACENT HINGED TERMINAL BOX.

20. IN UNFINISHED AREAS PAINT ALL FIRE ALARM CONDUITS, JUNCTION BOXES AND COVERS WITH ONE COAT OF RED ALKYD GLOSS ENAMEL PAINT. IN

FINISHED AREAS WITH EXPOSED CONDUIT PAINT ALL FIRE ALARM CONDUIT, JUNCTION BOXES AND COVERS TO MATCH THE ROOM FINISH, IDENTIFY “FIRE ALARM” ON THE INSIDE COVER OF ALL JUNCTION BOXES AND THE CONDUIT SHALL HAVE PAINTED RED BANDS ¾-INCH WIDE AT 10 FOOT INTERVALS AND AT EACH SIDE OF A FLOOR, WALL AND CEILING PENETRATION. ANODIZED RED CONDUIT IS ALSO ACCEPTABLE.

Drawing No. AMP - 400 -lead or pm designed drawn approved by

SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520. No part of this record may be disclosed to persons without a "need to know", as defined in 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR parts 15 and 1520.

ISSUED BY

OFFICE OF

facility management amp − 400 drawn d r a w in g N a m e d r a w in g N a m e

100% DESIGN SUBMITTAL - FOR CONSTRUCTION

SEAL:

10/25/23

/1 /2

:5 :4

A

M A u t o d e s k D o c s /1 F A A H a n g a r

R e n o v a t io n s R /1 1_

F

IR

E H R V T .r v t

/1 /2

:5 :4

A

M A u t o d e s k D o c s /1 F A A H a n g a r R e n o v a t io n s R /1 1_

F

IR

E H R V T .r v t

KDC

CME

HANGAR 9

FIRE ALARM LEGEND AND GENERAL NOTES

1550021

TCVTCV

FA001

No. Date Description Issued by

Issued to

0 01.24.25 100% DESIGN SUBMITTAL TV FAA

1 06.17.25 AMMENDMENT 01 TV FAA

F

F

F

C

C

C

C

P

C C

C

C

C

F A

C U

P

140°

F

F

F

F

C

C

C

C

C

C C

P

C

F

140°

F

F

L J H G F

1 1

2 2

3 3

4 4

5 5

6 6

7 7

8 8

9 9

ELEV.

100DW

CLOS.

100CW

UNISEX

107W

WOMEN

106W

ELEV. EQUIP.

108AW

ELECTRIC

108GW

ENTRY

100BW

TELE.

108FW

SHEET METAL SHOP

108W

OFFICE

108CW

OFFICE

108EW

MECHANICAL

109AW

PLASMA SHOP

109W

15 15

S

R

EL

ELEVATOR

SHAFT HEAT

DETECTOR

LCP

AOM

HEAT DETECTOR

TO BE LESS THAN

SPRINKLER HEAD

ACTIVATION

TEMPERATURE

HEAT DETECTOR

TO BE LESS THAN

SPRINKLER HEAD

ACTIVATION

TEMPERATURE

SIMPLEX 4100 U

FIRE CONTROL

L J H G F

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

STAIR

109BW

PAINT SHOP

110W

SHOP

111W

OFFICE

119DW

ENGINEERING LAB

119W

ELEV. EQUIP.

119AW

CLOSET

119CW

MECHANICAL

119BW

ENTRY

100FW

MEN

115W

STAIR

100HW

S

R

WF

WF

VSAIM AIM

ELEV.

100GW

PULL STATION FOR

TESTING, REFER

TO GENERAL NOTE

14 ON SHEET FA001

PLASMA SHOP

109W

EL

ELEVATOR

SHAFT HEAT

DETECTOR

Drawing No. AMP - 400 -lead or pm designed drawn approved by

SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520. No part of this record may be disclosed to persons without a "need to know", as defined in 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR parts 15 and 1520.

ISSUED BY

OFFICE OF

facility management amp − 400 drawn d r a w in g N a m e d r a w in g N a m e

100% DESIGN SUBMITTAL - FOR CONSTRUCTION

SEAL:

10/25/23

/1 /2

:5 :4

A

M A u t o d e s k D o c s /1 F A A H a n g a r

R e n o v a t io n s R /1 1_

F

IR

E H R V T .r v t

/1 /2

:5 :4

A

M A u t o d e s k D o c s /1 F A A H a n g a r R e n o v a t io n s R /1 1_

F

IR

E H R V T .r v t

KDC

CME

HANGAR 9

FIRE ALARM PLAN LEVEL 1 - SECTORS 1 & 2

1550021

TCVTCV

FA111

N

SECTOR 2

SECTOR 1 SECTOR 3

SECTOR 4

HIGH BAY

0 4' 8' 16'1/8" = 1'-0"

FIRE ALARM PLAN LEVEL 1 - SECTOR 1

1/8" = 1'-0"

FIRE ALARM PLAN LEVEL 1 - SECTOR 2

0 4' 8' 16'

HEAT DETECTOR TO BE

LESS THAN SPRINKLER

HEAD ACTIVATION

TEMPERATURE

HEAT DETECTOR TO BE

LESS THAN SPRINKLER

HEAD ACTIVATION

TEMPERATURE

No. Date Description Issued by

Issued to

0 01.24.25 100% DESIGN SUBMITTAL TV FAA

1 06.17.25 AMMENDMENT 01 TV FAA

L J H G F

M-111

ELEV.

100DW

MECHANICAL

109AW

PLASMA SHOP

109W

OFFICE

108CW

OFFICE

108EW

TELE.

108FW

ELEV. EQUIP.

108AW

SHEET METAL SHOP

108W

V E

S T

A

W

ENTRY

109BW

ELECTRIC

108GW

CLOS.

100CW

STAIR

100JW

UNISEX

107W

WOMEN

106W

R1

R1

R1

L J H G F

V E

S T

E

W

MECHANICAL

119BW

ELEV. EQUIP.

119AW

CLOSET

119CW

OFFICE

119DW

SHOP

111W

P A

IN

T

S H

O P

B A

C K

B

W PAINT SHOP

110W

PLASMA SHOP

109W

STAIR

100HW

ENTRY

109BW

ENGINEERING LAB

119W

MEN

115W

ELEV.

100GW

Drawing No. AMP - 400 -lead or pm designed drawn approved by

SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520. No part of this record may be disclosed to persons without a "need to know", as defined in 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR parts 15 and 1520.

ISSUED BY

OFFICE OF

facility management amp − 400 drawn d r a w in g N a m e d r a w in g N a m e

100% DESIGN SUBMITTAL - FOR CONSTRUCTION

/1 /2

:4 :5

P

M A u t o d e s k D o c s /1 F A A H a n g a r

R e n o v a t io n s R /1 1_

H V A C R H .r v t

/1 /2

:4 :5

P

M A u t o d e s k D o c s /1 F A A H a n g a r R e n o v a t io n s R /1 1_

H V A C R H .r v t

J. WILSON

R. MELTON

HANGAR 9

LEVEL 1 - MECHANICAL PLAN - SECTORS 1 AND 2

1550021

MATTCV

11.10.2023

M-1111/8" = 1'-0"

LEVEL 1 - MECHANICAL PLAN - SECTOR 1

1/8" = 1'-0"

LEVEL 1 - MECHANICAL PLAN - SECTOR 2

1/4" = 1'-0"

LEVEL 1 - WEST SECTOR TYPICAL DIFFUSER RELOCATION

N

SECTOR 2

SECTOR 1 SECTOR 3

SECTOR 4

HIGH BAY

1. DEMOLISH EXISTING DUCT BACK AS REQUIRED

FOR INSULATION OF NEW WALL. NEW WALL WILL

BE FIRE RATED AND CANNOT BE PENETRATED BY

THIS DUCT SYSTEM.

GENERAL NOTES:

KEYED NOTES:

No. Date Description Issued by

Issued to

0 01.24.24 100% DESIGN SUBMITTAL TV FAA

1 06.17.25 AMENDMENT 1 TV FAA

1. AIR TERMINAL SHALL BE RELOCATED IN SPACES

WITH NEW CEILINGS WITH SIMILAR CONNECTION

TYPES. SUPPLY DIFFUSERS ARE EXPECTED TO

BE CONNECTED TO FLEX DUCT AND EXHAUST

DIFFUSERS ARE EXPECTED TO HAVE RIGID DUCT

CONNECTIONS. RETURN GRILLS SHALL BE

LAYIN/PLENUM RETURN.