Attachment 18 - Electrical 2 of 2.pdf

PDF 1 MB Posted

Attached to
Y1DZ--VHA Minor Construction - Project 650-318 - New Otis CBOC for Providence VAMC
Solicitation number
36C77624R0087
Issued by

About this file

This document appears to be a set of construction drawings and specifications for a federal contract opportunity to construct a replacement outpatient clinic for the Department of Veterans Affairs at the US Coast Guard Air Station in Barnstable, Massachusetts.

The key details include:

  • The solicitation number is 36C77624R0087 for the "Y1DZ--VHA Minor Construction - Project 650-318 - New Otis CBOC for Providence VAMC"
  • The project involves the construction of a replacement outpatient clinic facility at the US Coast Guard Air Station in Barnstable, MA
  • The drawings and specifications cover electrical systems, including power distribution, lighting, site lighting, grounding, and controls
  • Major electrical equipment and systems include an emergency generator, HVAC equipment, pumps, fans, and plumbing systems
  • The document provides detailed schedules, one-line diagrams, panel schedules, and installation details for the electrical systems
  • The project is a full construction contract with a 100% construction document package

View the file

Other files

File Type Posted
36C77624R0087 0009.docx DOCX document
36C77624R0087 0008 Request for Propsoals 9.18.2024.docx DOCX document
36C77624R0087 00008 - Wage Determination 9.18.24.pdf PDF
36C77624R0087 0008 Request for Propsoals 9.18.2024.docx DOCX document
36C77624R0087 0008.docx DOCX document
36C77624R0087 0006.docx DOCX document
Answers to RFIs - 36C77624R0087 amendment 0006 Mass..docx DOCX document
36C77624R0087 0007.docx DOCX document
36C77624R0087 0006.docx DOCX document
Rhoad Island Note regarding FAR 52.229-3.docx DOCX document
USCG Cape Cod - SNELL STATEMENT OF SPECIAL INSPECTIONS - SNELL DSS 2024-06-24.pdf PDF
Answers to RFIs - 36C77624R0087 amendment 0006.docx DOCX document
S06 - Wage Determination 6-14-24.pdf PDF
AMENDMENT 0005 PRICE COST SCHEDULE.docx DOCX document
S06 36C77624R0087 0005.docx DOCX document
Answers to RFIs - 36C77624R0087 amendment 0005.docx DOCX document
01 00 00-VA SPEC-GENERAL REQUIREMENTS_Add1.pdf PDF
S06 36C77624R0087 0004.docx DOCX document
S06 36C77624R0087 0003.docx DOCX document
S06 36C77624R0087 0002.docx DOCX document
Attachment 9 - Architectural 4 of 5.pdf PDF
36C77624R0087 0001.docx DOCX document
Attachment 9 - Architectural 4 of 5.zip ZIP file
Attachment 19 - Telecom.pdf PDF
Attachment 17 - Electrical 1 of 2.pdf PDF
Attachment 1 - Specifications_Rev_05.2024.pdf PDF
Attachment 22 - Small Business Subcontracting Plan Template.docx DOCX document
Attachment 12 - Fire Alarm.pdf PDF
36C77624R0087_1.docx DOCX document
Attachment 20 - Brand Name - Redacted.pdf PDF
Attachment 13 - Fire Protection.pdf PDF
Attachment 11 - Structural.pdf PDF
Attachment 4 - Civil.pdf PDF
Attachment 10 - Architectural 5 of 5.pdf PDF
Attachment 9 - Architectural 4 of 5.pdf PDF
Attachment 16 - Mechanical 2 of 2.pdf PDF
Attachment 7 - Architectural 2 of 4.pdf PDF
Attachment 5 - Landscape.pdf PDF
Attachment 8 - Architectural 3 of 4.pdf PDF
Attachment 21 - wage determination.pdf PDF
Attachment 2 - General.pdf PDF
Attachment 23 - Division Breakdown Pricing.xls XLS spreadsheet
Attachment 6 - Architectural 1 of 4.pdf PDF
Attachment 14 - Plumbing.pdf PDF
Attachment 3 - Existing Conditions.pdf PDF
Attachment 15 - Mechanical 1 of 2.pdf PDF
Show all 46

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P P

P

P

P

P

JJ J

J

J

VFD

P

VFD

J

C B A

OFFICE

UTILITY SOILED

ELECTRICAL ROOM

MECHANICAL

JANITOR CLOSET

WORKSTATIONS,

MENTAL HEALTH

STAFF LOUNGE &

LOCKERS

STORAGE MEDICAL

& GENERAL

HHWP-111001

HHWP-111002

CHWP-111001

CHWP-111002

CH-111001

GWH-111002

GWH-111001

DS-AHU-111001-ML

HP-111002

HP-111003

HP-111001

FCSS-111001

FCSS-111003 FCSS-111002

AHU-111001

DS-AHU-111001-UV

BL-111001

DS-BL-111001

DS-HP-111001

DS-HP-111003

DS-HP-111002

DS-GWH-111001

DS-GWH-111002

TP-111001

HWP-111001

DS-FCSS-111002

DS-FCSS-111003

OFFICE

UTILITY CLEAN

DS-FCSS-111001

DS-HWP-111001

M

AT

C H

LI

N

E -C

O N

TI

N

U

ED

O N

D W

G

/E -2

B.7 A.4

5.5

3.7 3.6

3.3

3.1

2.7

2.5

2.4

1.9

1.5

1.3

SH-111001

DS-SH-111001

DS-AHU-111001

HEAT TRACE PANEL

DS-HHWP-111001

DS-HHWP-111002

DS-CHWP-111001

DS-CHWP-111002

LOS1-5

MECHANICAL EQUIPMENT

BUILDING AUTOMATION

CONTROL PANEL

LMP1-16

LMP1-1

LMP1-18

LOS1-14

UV-111001

DS-UV-111001

HEAT TRACE PANEL

8LMP1-20

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

BI

M

- C on st ru ct

R ep la ce m en t O ut pa tie nt C lin ic

/0

C on st . R ep la ce . O ut pa tie nt

C lin ic

R

.rv t

2/ 9/

2:

:2

PM

E-206

PARTIAL FIRST FLOOR PLAN -

ELEC. EQUIPMENT - EAST

REPLACEMENT OUTPATIENT

CLINIC DESIGN AT COAST

GUARD CAPE COD

JOINT BASE CAPE COD, BARNSTABLE MA

650-318

BUILDING 1

02/10/2023 JFR KEM

100% CONSTRUCTION

DOCUMENTS

CODED NOTES:

DRAWING NOTES:

1. REFER TO ELECTRICAL EQUIPMENT CONNECTION SCHEDULE AND DISCONNECT SCHEDULE ON

SHEET E-801 FOR ADDITIONAL CONNECTION AND SIZING INFORMATION.

PROVIDE 120V POWER FOR MECHANICAL BUILDING AUTOMATION SYSTEM PANEL. COORDINATE

EXACT CONNECTION POINT WITH EQUIPMENT PRIOR TO CONSTRUCTION.

PROVIDE 120V POWER FOR TRAP PRIMER SYSTEM PANEL. COORDINATE EXACT CONNECTION POINT

WITH EQUIPMENT PRIOR TO CONSTRUCTION.

PROVIDE 120V POWER FOR HEAT TRACE SYSTEM PANEL. COORDINATE EXACT CONNECTION POINT

WITH EQUIPMENT PRIOR TO CONSTRUCTION.

PROVIDE 120V POWER FOR REVERSE OSMOSIS SYSTEM. COORDINATE EXACT CONNECTION POINT

WITH EQUIPMENT PRIOR TO CONSTRUCTION.

PROVIDE 120V POWER FOR ULTRA VIOLET SYSTEM. COORDINATE EXACT CONNECTION POINT WITH

EQUIPMENT PRIOR TO CONSTRUCTION.

VFD FOR RF-121001, PROVIDED BY MANUFACTURER, INSTALLED AND WIRED BY ELECTRICAL

CONTRACTOR. PROVIDE HOT DIPPED GALVANIZED UNISTRUT AND REQUIRED MOUNTING HARDWARE

FOR A CODE COMPLIANT INSTALLATION IN ACCORDANCE WITH MANUFACTURERS INSTALLATION

INSTRUCTIONS. COORDINATE EXACT LOCATION OF DEVICE WITH EQUIPMENT AND REQUIRED

CLEARANCES.

VFD FOR AHU-111001, PROVIDED BY MANUFACTURER, INSTALLED AND WIRED BY ELECTRICAL

CONTRACTOR. PROVIDE HOT DIPPED GALVANIZED UNISTRUT AND REQUIRED MOUNTING HARDWARE

FOR A CODE COMPLIANT INSTALLATION IN ACCORDANCE WITH MANUFACTURERS INSTALLATION

INSTRUCTIONS. COORDINATE EXACT LOCATION OF DEVICE WITH EQUIPMENT AND REQUIRED

CLEARANCES.

PROVIDE 120V JUNCTION BOX FOR VAV TERMINAL UNIT CONTROL POWER. COORDINATE EXACT

CONNECTION POINT WITH EQUIPMENT PRIOR TO CONSTRUCTION.

3/16" = 1'-0"E-206

1 PARTIAL FIRST FLOOR PLAN - ELEC. EQUIPMENT PLAN - EAST 0 4' 8' 12' 16'

3/16" = 1'-0"

N

Revisions Date

H G F E D C B A

I

2 (TYPICAL)

EF-121002 EF-121001

RF-121001

H.2H.1 F.7 F.5 F.3 E.5 D.9 D.7D.6D.5 D.3 C.6C.5 C.3 B.7 A.4

5.5

3.73.6

3.3

3.1

2.7

2.5 2.4

1.9

1.5

1.3

DS-RF-121001

G,WP

LRP1B-12

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

BI

M

- C on st ru ct

R ep la ce m en t O ut pa tie nt C lin ic

/0

C on st . R ep la ce . O ut pa tie nt

C lin ic

R

.rv t

2/ 9/

2:

:2

PM

E-207

ELECTRICAL ROOF PLAN REPLACEMENT OUTPATIENT

CLINIC DESIGN AT COAST

GUARD CAPE COD

JOINT BASE CAPE COD, BARNSTABLE MA

650-318

BUILDING 1

02/10/2023 JFR KEM

100% CONSTRUCTION

DOCUMENTS

1/8" = 1'-0"E-207

1 ROOF PLAN - ELECTRICAL

CODED NOTES:

CONTRACTOR TO PROVIDE UL LISTED AND APPROVED LIGHTNING PROTECTION SYSTEM FOR ROOF.

DEVICES AND ROUTING INDICATED ON THIS PLAN ARE FOR COST ESTIMATION PURPOSES ONLY.

CONTRACTOR TO PROVIDE SIGNED AND SEALED LIGHTNING PROTECTION DESIGN AND SUBMITTAL

FOR REVIEW BY ENGINEER OF RECORD.

CONNECT NEW LIGHTNING PROTECTION SYSTEM TO BUILDING COPPER GROUND LOOP. EXACT

CONNECTION POINTS TO BE COORDINATED IN FIELD. SEE ELECTRICAL SITE PLAN ON SHEET E-100

AND SYSTEM GROUNDING DETAIL ON SHEET E-501 FOR FURTHER DETAILS.

DRAWING NOTES:

1. SEE SPECIFICATIONS FOR ADDITIONAL LIGHTNING PROTECTION REQUIREMENTS.

2. REFER TO ELECTRICAL EQUIPMENT CONNECTION SCHEDULE AND DISCONNECT SCHEDULE ON

SHEET E-801 FOR ADDITIONAL CONNECTION AND SIZING INFORMATION.

0 4' 8' 16' 24'

1/8" = 1'-0"

N

208Y/120V, 3PH, 4W

FED FROM PANEL "XXXX"

VIA T-XXX

TYPICAL 208Y/120V PANELBOARD

PANEL "XXXX"

1/16" THICK WHITE PLASTIC WITH COLORED

FACE PER SPECIFICATIONS

1/2" HIGH LETTERING FOR

PANELBOARD NAME

1/4" HIGH LETTERING FOR

REMAINING TEXT

ADHESIVE BACKING WHEN INSTALLED IN

CONDITIONED SPACES

480Y/277V, 3PH, 4W

FED FROM PANEL "XXXX"

TYPICAL 480Y/277V PANELBOARD

PANEL "XXXX"

1/16" THICK WHITE PLASTIC WITH COLORED

FACE PER SPECIFICATIONS

1/2" HIGH LETTERING FOR

PANELBOARD NAME

1/4" HIGH LETTERING FOR

REMAINING TEXT

ADHESIVE BACKING WHEN INSTALLED IN

CONDITIONED SPACES

SEE SPECIFICATION SECTIONS

260511 AND 260573 FOR ARC FLASH

WARNING LABEL REQUIREMENTS.

PHASE A

PHASE B

PHASE C

NEUTRAL

GROUND

BLACK

RED

BLUE

WHITE

GREEN

VOLTAGE

208Y/120V

IDENTIFICATION OF GROUNDED CONDUCTORS SHALL BE PERFORMED

BASED ON NEC ARTICLE 200.

PHASE A

PHASE B

PHASE C

NEUTRAL

GROUND

BROWN

ORANGE

YELLOW

GREY

GREEN

VOLTAGE

480Y/277V

1/16" THICK WHITE PLASTIC WITH COLORED

FACE PER SPECIFICATIONS

1/2" HIGH LETTERING FOR

EQUIPMENT NAME

1/4" HIGH LETTERING FOR

REMAINING TEXT

ADHESIVE BACKING WHEN INSTALLED IN

CONDITIONED SPACES

EQUIPMENT VOLTAGE

EQUIPMENT NAME

FASTEN WITH BRASS SCREWS WHEN LOCATED

IN NON-CONDITIONED OR EXTERIOR SPACES

EQUIPMENT SOURCE

(PANEL & CIRCUIT)

120V, 1PH

FED FROM "MDP-4"

TYPICAL EQUIPMENT

AHU-X

AHU-X

480V, 3PH

FED FROM "MDP-4"

SEE SPECIFICATION SECTIONS

260511 AND 260573 FOR ARC FLASH

WARNING LABEL REQUIREMENTS.

C

80"

48"

90"

54"

18" AFF

6" AFC

36" AFF

FIRE HORN (OR CHIME) & LIGHT 80" AFF

FROM BOTTOM OF DEVICEEXIT

DUPLEX

RECEPTACLE

CENTERED BETWEEN DOOR & CEILING

(COORDINATE WITH ARCHITECT)

CENTERED OVER DOOR

(WHERE APPLICABLE)

TELE. OUTLET

SPECIAL POWER OUTLET

FINISHED FLOOR

DUPLEX RECEPTACLE

REMOTE TEST

COMPUTER

OUTLET

RT

TELE. OUTLET

42" A.F.F. W/ 36" COUNTER,

39" A.F.F. W/ 30" COUNTER,

48" A.F.F. WITHOUT COUNTER

78" MAX. TO TOP

DEVICE

OR AS NOTED ON PLANS

WALL MOUNTED LIGHT FIXTURES

AS NOTED ON PLANS

PANELBOARD

L

CL

CL

CL

CL

CL

CL

CH

SWITCH

6" 6" 6"

COMBO KEYPAD/CARD

READER

THERMOSTAT

FA PULL STATIONF

A

A

Section A-A

1A 1B

SPECIFIED TECHNOLOGIES INC - SPECSEAL LCI SEALANT

* INDICATES SUCH PRODUCTS SHALL BEAR THE UL OR CUL

CERTIFICATION MARK FOR JURISDICTIONS EMPLOYING

THE UL OR CUL CERTIFICATION (SUCH AS CANADA),

RESPECTIVELY.

SYSTEM NO. W-L-5122

1. WALL ASSEMBLY - THE 1 OR 2 HR FIRE-RATED GYPSUM BOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION DESIGN IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING

CONSTRUCTION FEATURES:

A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. LUMBER SPACED 16 IN. OC. STEEL STUDS TO BE MIN 3-5/8 IN. WIDE AND

SPACED MAX 24 IN. OC.

B. GYPSUM BOARD* - THICKNESS, TYPE, NUMBER OF LAYERS AND FASTENERS AS SPECIFIED IN THE INDIVIDUAL

WALL AND PARTITION DESIGN. MAX DIAM OF OPENING IS 7-1/2 IN.

THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS EQUAL TO THE HOURLY FIRE RATING OF THE WALL

ASSEMBLY IN WHICH IT IS INSTALLED.

2. THROUGH PENETRANT - ONE METALLIC PIPE OR TUBE TO BE INSTALLED ECCENTRICALLY OR CONCENTRICALLY WITHIN THE FIRESTOP SYSTEM. PIPE OR TUBE TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF THE WALL

ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES AND TUBES MAY BE USED:

A. STEEL PIPE - NOM 4 IN. DIAM (OR SMALLER) SCHEDULE 5 (OR HEAVIER) STEEL PIPE.

B. IRON PIPE - NOM 4 IN. DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.

C. COPPER PIPE - NOM 2 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.

D. COPPER TUBE - NOM 2 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBE.

3. TUBE INSULATION - PLASTICS# - NOM 3/4 IN. THICK ACRYLONITRILE BUTADIENE/POLYVINYL CHLORIDE (AB/PVC) FLEXIBLE FOAM FURNISHED IN THE FORM OF TUBING. ANNULAR SPACE SHALL BE MIN 0 IN. (POINT CONTACT) TO

MAX 1-1/2 IN.

SEE PLASTICS (QMFZ2) CATEGORY IN THE PLASTICS RECOGNIZED COMPONENT DIRECTORY FOR NAMES OF MANUFACTURERS. ANY RECOGNIZED COMPONENT TUBE INSULATION MEETING THE ABOVE SPECIFICATIONS

AND HAVING A UL 94 FLAMMABILITY CLASSIFICATION OF 94-5VA MAY BE USED.

4. FILL, VOID OR CAVITY MATERIAL* - SEALANT - MIN 5/8 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF WALL ASSEMBLY. AT POINT CONTACT LOCATION, MIN 1/4 IN. DIAM BEAD OF FILL MATERIAL APPLIED AT INSULATED METALLIC PIPE/GYPSUM BOARD INTERFACE ON BOTH

SURFACES OF WALL.

STUD TO STUD TELESCOPING BOX SUPPORT, B-LINE BB2 SERIES OR

EQUAL.

CONDUITS

RECEPTACLE

EQUIPMENT

GROUND

CONDUCTOR

GROUND SCREW

ON WIRING DEVICE.

PLASTER RINGNEUTRAL CONDUCTOR

HOT CONDUCTOR

METAL STUD

DRYWALL

PLASTER RING

RECEPTACLE

CONDUIT

4 SQUARE OUTLET BOX

OUTLET BOX SECURED

TO BOX SUPPORT

WIRE NUT (TYP.)

GROUND SCREW IN

OUTLET BOX

4"

10"

INSULATOR

GROUND BUS BAR

ISOMETRIC ELEVATION

CPI 10622-020 OR

EQUAL

STANDOFF BRACKET

CPI 10622-000

FRONT VIEW

CPI 10622-020 OR EQUAL

PROVIDE # 6 COPPER CABLE DOUBLE LUG CLAMP FOR CABLE CONNECTION DIV 26. (1)

TO EACH RACK PLUS ONE TO PHONE SWITCH ENTRANCE PROTECTOR.

DOUBLE LUG (TYP)

INSULATOR (TYP)

INSULATOR MOUNTING BRACKET

(TYP.)

CPI 10622-000

#3/0 AWG

COPPER TO

BUILDING STEEL

#3/0 AWG COPPER CABLE TO MAIN SERVICE

GROUND POST.

NOTE:

LEADS AS SHORT AS POSSIBLE. (18" MAX.)

MOUNT SPD DEVICE IN A LOCATION TO MAINTAIN ALL

NEUTRAL BUS

CONNECTION

NEUTRAL BUS

CONNECTION

BREAKER FEEDING

SURGE SUPPRESSOR

TYPICAL SPD LOCATIONS (TYPE

X: 1,2,3 OR 4 AS INDICATED ON

DRAWINGS)

TWIST ALL LEADS TOGETHER

(AS MANY TURNS AS

PRACTICAL) AND TIE WRAP

TYPICAL SPD LOCATIONS

(TYPE X: 1,2,3 OR 4 AS

INDICATED ON DRAWINGS)

TWIST ALL LEADS TOGETHER (AS MANY TURNS AS

PRACTICAL) AND TIE WRAP

BREAKER FEEDING

SURGE SUPPRESSOR (TYP)

SERVICE ENTRANCE OR DISTRIBUTION PANELPANELBOARD

TYPICAL SPD LOCATIONS (TYPE

X: 1,2,3 OR 4 AS INDICATED ON

DRAWINGS)

MAIN WATER SERVICE

BONDING JUMPERS TO BUILDING STEEL

AND WATER SERVICE (#3/0 AWG CU. - 1" C.)

#4 AWG CU. - 3/4" C. TO CONCRETE ENCASED

REBAR (MIN. 20' LENGTH OF REBAR).

#6 AWG CU - 3/4" C. TO MAIN TELEPHONE TERMINAL BOARD.

#3/0 CU TO GROUND RING/LIGHTNING

PROTECTION.

#6 AWG CU - 3/4" C. TO FACP.

GROUND BUS. REFER TO DETAIL.#1/0 AWG CU - 1" C.

TO GROUND BARS IN DISTRIBUTION ELECTRICAL ROOMS

AND COMM ROOMS SIZE PER NEC TABLE 250.66.

GROUNDING ELECTRODE

CONDUCTOR, #6 AWG CU, 3/4" C.

GROUND BUS

NEUTRAL BUS

PROVIDE OTHER GROUNDING CONNECTIONS

AS SPECIFIED IN NEC ARTICLE 250.50 (2011).

COORDINATE INSPECTION AT REBAR BOND BEFORE

CONCRETE POUR WITH ELECTRICAL INSPECTOR.

LABEL ALL CONDUCTORS AT TERMINATION POINTS.

LABEL PER NEC 70 - 700 OR 70 - 702.8.

WATER PIPE GROUND LOCATED ON

HOUSE SIDE OF MAIN VALVE AT POINT

SERVICE ENTERS BUILDING

STEEL COLUMN

SERVICE ENTRANCE PANELBOARD/

SWITCHBOARD MAIN DISCONNECT

NOTES:

1.

2.

3.

4.

1#1/0AWG MAIN BONDING

JUMPER

MAIN BONDING JUMPER SHALL BE LOCATED IN SERVICE ENTRANCE PANEL/SWITCHBOARD

FOR SEPARATELY DERIVED POWER SOURCE.

5.

G

G

G G

G

G

THE 50% OF EFFECTIVELY

GROUNDED BUILDING

STEEL COLUMNS TO RING

3/0 AWG BARE COPPER BUILDING

GROUND RING - 36" MINIMUM BELOW

GRADE, 3'-0" FROM EXTERIOR WALL

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

BI

M

- C on st ru ct

R ep la ce m en t O ut pa tie nt C lin ic

/0

C on st . R ep la ce . O ut pa tie nt

C lin ic

R

.rv t

2/ 9/

2:

:2

PM

E-501

ELECTRICAL DETAILS REPLACEMENT OUTPATIENT

CLINIC DESIGN AT COAST

GUARD CAPE COD

JOINT BASE CAPE COD, BARNSTABLE MA

650-318

BUILDING 1

02/10/2023 JFR KEM

100% CONSTRUCTION

DOCUMENTS

N.T.S.

PANELBOARD NAMEPLATE1

N.T.S.

WIRE COLOR TABLE2

N.T.S.

EQUIPMENT NAMEPLATE3N.T.S.

TYPICAL MOUNTING HEIGHTS6

N.T.S.

CONDUIT PENETRATION OF FIREWALL5N.T.S.

TYPICAL RECEPTACLE MOUNTING DETAIL8

N.T.S.

TYPICAL GROUND BAR DETAIL7

N.T.S.

TYPICAL SPD MOUNTING DETAIL9

N.T.S.

SYSTEM GROUNDING DETAIL4

CONDUIT CLAMP.

SIZE AS REQUIRED

INTEGRAL

GALVANIZED

LIPPED STEEL

MOUNTING

CHANNEL

REFER TO PLANS

FOR QUANTITY & SIZE

OF CONDUITS

GENERAL NOTES:

1. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING CHANNEL

LONGER THAN 915mm (36") SHALL BE INSTALLED WITH A

CENTER SUPPORT ROD.

2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED

METHOD PER SPECIFICATION 26 05 33, RACEWAY AND BOXES

FOR ELECTRICAL SYSTEMS. FIELD VERIFY EXACT CONDITIONS.

3. FOR TRAPEZE INSTALLATIONS IN SEISMIC AREAS REFER TO

SPECIFICATION SECTION 13 05 41, SEISMIC RESTRAINT

REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.

LOCKING SQUARE

WASHER & LOCKNUT

9.52mm (3/8") MIN

GALVANIZED THREADED

ROD, TYP.

INTEGRAL

GALVANIZED

LIPPED STEEL

MOUNTING

CHANNEL

WASHER & LOCKNUT

LEN GTH AS R EQU IRED

914mm

BEAM

CLAMP,

TYP.

CONDUIT

TYP.

CONDUIT FITTING

SPRING NUT

HEAD

INSULATING

BUSHING

GENERAL NOTES:

1. INSTALLATION IS ACCEPTABLE ALTERNATE TO DETAIL SD260533-01.

2. INSTALLATION IS REQUIRED FOR CONDUIT 76mm (3") AND LARGER.

JUNCTION BOX

(SIZE AS REQUIRED)

INTEGRAL

GALVANIZED LIPPED

STEEL MOUNTING

CHANNEL

PROVIDE EXTRA CABLE

TO MAKE COMPLETE LOOP

AROUND BOX PERIMETER

CONDUIT

TRAPEZE PER

SD260533-03,

TYP.

FLOOR OR ROOF

STRUCTURE. FIELD VERIFY

ACTUAL CONDITIONS, TYP.

EXPANSION FITTING

WITH BONDING JUMPER

SEISMIC OR EXPANSION

JOINT. FIELD VERIFY

ACTUAL CONDITIONS &

LOCATIONS.

STRUCTURAL MEMBER

(BEAM, JOIST, ETC.), TYP.

STEEL EXPANSION

ANCHOR

JUNCTION BOX, TYP

(SIZE AS REQUIRED)(3'-0") MAX

914mm

SPRING NUT

GENERAL NOTE:

1. DETAIL IS APPLICABLE ONLY FOR CONDUIT SMALLER THAN 76mm (3").

JUNCTION BOX

(SIZE AS REQUIRED)

CONDUIT FITTING

INTEGRAL

GALVANIZED LIPPED

STEEL MOUNTING

CHANNEL

JUNCTION BOX, TYP

(SIZE AS REQUIRED)

BEAM

CLAMP,

TYP.

PROVIDE EXTRA CABLE

TO MAKE COMPLETE LOOP

AROUND BOX PERIMETER

CONDUIT

TRAPEZE PER

SD260533-03,

TYP.

CONDUIT,

TYP.

STEEL EXPANSION

ANCHOR

STRUCTURAL MEMBER

(BEAM, JOIST,

SEISMIC OR EXPANSION

JOINT. FIELD VERIFY

ACTUAL CONDITIONS &

LOCATIONS.

PROVIDE 127mm (5") OF SLACK AT

MIDPOINT BETWEEN TWO END OF

FLEXIBLE GALVANIZED STEEL

CONDUIT. PROVIDE GREEN INSULATED

COPPER EQUIPMENT GROUNDING

CONDUCTOR WITH FLEXIBLE CONDUIT.

FLOOR OR ROOF

STRUCTURE. FIELD VERIFY

ACTUAL CONDITIONS, TYP.

ETC.), TYP.

(3'-0") MAX

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS

AND USING THE RECOMMENDED MOUNTING HARDWARE.

FIXTURE WHIP FROM

JUNCTION BOX (1829mm

(6') LONG MAX)

CEILING MAIN

BEAM

CEILING BEAM

RECESSED CAN

LUMINAIRE

RECESSED CAN

LUMINAIRE

REFER TO

SCHEDULE.

CEILING

CROSS BEAM

WIRE TIE OR SCREW

BAR HANGER TO

CROSS BEAM TYP.

CEILING HANGER

WIRE, TYP.

LUMINAIRE SUSPENSION WIRES

REFER TO SPECIFICATION SECTION 26 51 00

LUMINAIRE

BAR HANGERS

GYPSUM

BOARD (TYP)

RECESSED

CAN

LUMINAIRE

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING

INSTRUCTIONS AND USING RECOMMENDED MOUNTING HARDWARE

WIRE TIE OR SCREW

BAR HANGER TO

ARCHITECTURAL

CEILING GRID TYP.

ARCHITECTURAL

CEILING GRID

CEILING HANGER

WIRE, TYP.

LUMINAIRE SUSPENSION WIRE

REFER TO SPECIFICATION SECTION

26 51 00.

LUMINAIRE

BAR HANGERS

ACOUSTICAL

CEILING TILE (TYP)

ARCHITECTURAL

CEILING GRID

RECESSED CAN

LUMINAIREFIXTURE WHIP FROM

JUNCTION BOX (1829mm

(6') LONG MAX)

WIRE TIE THROUGH

MOUNTING CHANNEL

CROSS BEAM, TYP.

INTEGRAL GALVANIZED

LIPPED

STEEL MOUNTING CHANNEL

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS

AND USING THE RECOMMENDED MOUNTING HARDWARE.

DRYWALL CEILING

CROSS TEE, TYP.

GYPSUM

BOARD

CEILING MAIN

BEAM.

6.35mm (1/4") SCREW

LOCKING SQUARE

WASHER & NUT

JUNCTION BOX

FIXTURE WHIP FROM JUNCTION

BOX (1829mm (6') LONG MAX)

HANGER WIRE AND MOUNTING

CHANNEL ATTACHED TO STRUCTURE

REFER TO SPECIFICATION SECTION

26 51 00 DRYWALL CEILING

CROSS TEE, TYP.

CEILING HANGER WIRE

LUMINAIRE

SUSPENSION

WIRES

REFER TO

SPECIFICATION

SECTION 26 51 00

3 TWIST

MINIMUM

(TYP)

FIXTURE WHIP

FROM

JUNCTION BOX

(1829mm (6') LONG

MAX.)

LUMINAIRE.

REFER TO

SCHEDULE

LUMINAIRE MANUFACTURER'S

MOUNTING HARDWARE

REFER TO SPECIFICATION

SECTION

26 51 00

ACOUSTICAL

CEILING

TILE (TYP)

ARCHITECTURAL

CEILING GRID

LUMINAIRE.

REFER TO

SCHEDULE

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS

AND USING THE RECOMMENDED MOUNTING HARDWARE.

LUMINAIRE

SUSPENSION

WIRES

REFER TO

SPECIFICATION

SECTION 26 51 00

3 TWIST

MINIMUM

(TYP)

FIXTURE WHIP

FROM

JUNCTION BOX

(1829mm (6') LONG

MAX.)

CEILING MAIN BEAM

GYPSUM BOARD (TYP)

LUMINAIRE.

REFER TO

SCHEDULE

LUMINAIRE MANUFACTURER'S

MOUNTING HARDWARE

REFER TO SPECIFICATION

SECTION

26 51 00

CEILING CROSS BEAM

GYPSUM BOARD

CEILING CROSS BEAM

LUMINAIRE.

REFER TO

SCHEDULE

DRYWALL BORDER

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS

AND USING THE RECOMMENDED MOUNTING HARDWARE.

9.52mm

JUNCTION BOX

(SIZE AS REQUIRED)

CONDUIT FITTING

SPRING

NUT, TYP

FLOOR SLAB,

TYP.

FIRESTOP SEALANT

PER SECTION 07 84 00,

FIRESTOPPING

CONDUIT, TYP MINERAL WOOL

(FIRMLY PACKED)

INTEGRAL GALVANIZED

LIPPED STEEL MOUNTING

CHANNEL, TYP.

STEEL EXPANSION

ANCHOR, TYP

(3/8") MAX

GENERAL NOTES:

1. MAINTAIN A MINIMUM CLEARANCE OF 305mm (12") ON ALL SIDES OF ROOF PENETRATION FROM

WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING.

2. FLANGES OF ADJACENT FLASHINGS SHALL NOT BE CUT OR OVERLAPPED.

3. VERIFY ROOF & STRUCTURAL SYSTEM WITH ARCHITECT.

4. COORDINATE FLASHING INSTALLATION WITH ROOFING CONTRACTOR TO ENSURE PROPER

METHODS & MATERIALS ARE USED TO MAINTAIN ROOF WARRANTY.

PREFABRICATED RUBBER BOOT

CAP WITH GRADUATED STEPS &

WEATHER-PROOF PRESSURE

SEAL TO COLLAR

SEALANT AT PENETRATION

TO MEMBRANE JUNCTURE

BY ROOFING CONTRACTOR MULTIPLE MEMBRANE STRIPPING

PLIES FEATHERED AT FIELD OF ROOF

BY ROOFING CONTRACTOR. PRIME

FLANGE BEFORE STRIPPING.

PREFABRICATED FORMED 1.52mm

(0.06") THICK ALUMINUM FLASHING

ROUND COLLAR WITH MIN. 76mm

(3") WIDE FLANGE. ATTACH TO

ROOF PER MANUFACTURER'S

INSTRUCTIONS

CONDUIT CLAMP. SIZE AS

REQUIRED

BATT INSULATION

ROOF MEMBRANE

WATER CUT-OFF MASTIC

COMPATIBLE WITH ROOF

MEMBRANE

STAINLESS CLAMP, TYP.

9.52mm (3/8") MIN

GALVANIZED

THREADED ROD,

TYP.

SEAL-OFF

FITTING,

TYP.

ROOF

STEEL

EXPANSION

ANCHOR

INTEGRAL GALVANIZED

LIPPED STEEL

MOUNTING CHANNEL

CONDUIT,

TYP.

CONDUIT CLAMP.

SIZE AS

REQUIRED

LOCKING

SQUARE

WASHER &

LOCKNUT

CONDUIT CLAMP.

SIZE AS REQUIRED

INTEGRAL GALVANIZED

LIPPED STEEL

MOUNTING CHANNEL

REFER TO PLANS

FOR QUANTITY & SIZE

OF CONDUITS

LOCKING SQUARE

WASHER &

LOCKNUT

9.52mm (3/8") MIN

GALVANIZED THREADED

ROD, TYP.

UV-INHIBITED POLYCARBONATE

OR HIGH-DENSITY

POLYPROPYLENE PLASTIC BLOCK,

LENGTH AS REQUIRED

CAST METAL

"WHILE-IN-USE"

WP COVER(S) &

RECEPTACLE(S)

CAST METAL, 2-GANG,

NEMA 3R JUNCTION BOX

WITH THREADED HUBS.

RIGID STEEL CONDUIT

FOR WIRING

A

A

SECTION "A-A"

ELEVATION

RIGID STEEL CONDUIT

FOR SUPPORT PER N.E.C.

ART. 314

ROOF PENETRATION

AND CONDUIT SUPPORT

PER SD260533-05

" M

AX

" M

AX

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

BI

M

- C on st ru ct

R ep la ce m en t O ut pa tie nt C lin ic

/0

C on st . R ep la ce . O ut pa tie nt

C lin ic

R

.rv t

2/ 9/

2:

:3

PM

E-502

ELECTRICAL DETAILS REPLACEMENT OUTPATIENT

CLINIC DESIGN AT COAST

GUARD CAPE COD

JOINT BASE CAPE COD, BARNSTABLE MA

650-318

BUILDING 1

02/10/2023 JFR KEM

100% CONSTRUCTION

DOCUMENTS

N.T.S.

CONDUIT TRAPEZE MOUNTING DETAIL1

N.T.S.

CONDUIT EXPANSION JOINT CROSSING DETAIL - EXPANSION FITTING2

N.T.S.

CONDUIT EXPANSION JOINT CROSSING DETAIL - FLEXIBLE CONDUIT3

N.T.S.

DOWNLIGHT MOUNTING - GYPBOARD CEILING4

N.T.S.

DOWNLIGHT MOUNTING - LAY-IN CEILING5

N.T.S.

EXIT SIGN MOUNTING - GYPBOARD CEILING6

N.T.S.

LUMINAIRE MOUNTING - LAY-IN CEILING7

N.T.S.

LUMINAIRE MOUNTING -GYPBOARD CEILING8

N.T.S.

FLOOR SLAB PENETRATION9

N.T.S.

CONDUIT ROOF PENETRATION DETAIL10

N.T.S.

ROOF CONDUIT SUPPORT DETAIL11

N.T.S.

RECEPTACLE ROOF MOUNTING DETAIL12

LIGHT POLE PER LIGHT

FIXTURE SCHEDULE

76x127mm (3"x5") REINFORCED

HAND HOLE WITH TAMPER

RESISTANT SCREWS. PROVIDE IN-

LINE SCREW-TYPE FUSE HOLDER(S)

WITH FUSE(S).

POLE GROUNDING STUD

2-PIECE BOLT COVER PLATE.

PVC CONDUIT

ADAPTER

COUPLING

PVC CONDUIT

RIGID STEEL CONDUIT

UNDISTURBED SOIL OR

SELECT BACKFILL

COMPACTED, SEE

NOTE BELOW.

#4 BARE COPPER

GROUND 6069mm

(20'-0") COILED BELOW

BASE

25mm (1") EMPTY

CONDUIT WITH CAP

(WHERE SHOWN ON

PLANS)

FINISHED GRADE

ANCHOR BOLTS PER POLE

MANUFACTURER'S REQUIREMENTS

WITH LEVELING NUTS ABOVE &

BELOW BASE PLATE

3'- 0"

2'- 0"

CONCRETE BASE &

REINFORCING STEEL,

SEE NOTE BELOW.

GENERAL NOTES:

1. BACKFILL, CONCRETE, REINFORCING STEEL, AND ANCHOR BOLTS ARE SHOWN FOR

REFERENCE ONLY. STRUCTURAL DESIGN IS SHOWN ON STRUCTURAL DRAWINGS.

2. REFER TO SPECIFICATION SECTION 26 56 00 FOR MOUNTING AND LEVELING

REQUIREMENTS.

GENERAL NOTES:

1. BACKFILL, CONCRETE, REINFORCING STEEL, AND ANCHOR BOLTS ARE SHOWN FOR

REFERENCE ONLY. STRUCTURAL DESIGN IS SHOWN ON STRUCTURAL DRAWINGS.

2. REFER TO SPECIFICATION SECTION 26 56 00 FOR MOUNTING AND LEVELING

REQUIREMENTS.

3. REFER TO LANDSCAPE DETAILS FOR INSTALLATION OF PAVERS AND INTERFACE BETWEEN

PAVERS AND POLE BASE.

LIGHT POLE PER LIGHT

FIXTURE SCHEDULE

76x127mm (3"x5") REINFORCED

HAND HOLE WITH TAMPER

RESISTANT SCREWS. PROVIDE IN-

LINE SCREW-TYPE FUSE HOLDER(S)

WITH FUSE(S).

POLE GROUNDING STUD

2-PIECE BOLT COVER PLATE.

PVC CONDUIT

ADAPTER

COUPLING

PVC CONDUIT

RIGID STEEL CONDUIT

UNDISTURBED SOIL OR

SELECT BACKFILL

COMPACTED, SEE

NOTE BELOW.

#4 BARE COPPER

GROUND 6069mm

(20'-0") COILED BELOW

BASE

25mm (1") EMPTY

CONDUIT WITH CAP

(WHERE SHOWN ON

PLANS)

FINISHED PAVING

ANCHOR BOLTS PER POLE

MANUFACTURER'S REQUIREMENTS

WITH LEVELING NUTS ABOVE &

BELOW BASE PLATE

3'- 0"

2'- 0"

CONCRETE BASE &

REINFORCING STEEL,

SEE NOTE BELOW.

HANDHOLE

DIRECT BURIAL/SUBMERSIBLE UL486D RATED

REUSABLE MECHANICAL CONNECTOR. TAPPED

SPLICED NOT ACCEPTABLE, TYPICAL

CONDUIT, TYPICAL

CIRCUIT GROUND

CONDUCTOR

GROUND WIRE

SAME SIZE AS

CIRCUIT GROUND

CONDUCTOR

GROUND ROD 10' LONG,

3/4" DIAMETER COPPER

CLAD STEEL

HANDHOLE WIRING/GROUNDING

LID FLUSH WITH PAVEMENT, OTHER AREAS

SET COVER 1" ABOVE FINISHED GRADE

HANDHOLE

GROUND ROD 10' LONG,

3/4" DIAMETER COPPER

CLAD STEEL

FINISHED GRADE

OR PAVEMENT

CONDUIT

" M

IN

IM

U M

" M

IN

IM

U M

(2

0' - 2 3/4"

0'

/1 6"

0'

5/

0'

7/

OPEN BOTTOM

NOTE: (APPLICABLE TO HANDHOLE DETAIL ONLY)

1. BASIS OF DESIGN: QUAZITE PG STYLE OR APPROVED EQUAL

2. FIELD-CUT OPENING FOR SIDE-ENTRY CONDUITS ACCORDING TO ENCLOSURE

MANUFACTURER'S WRITTEN INSTRUCTIONS. SIDE ENTRY CONDUITS ONLY ALLOWED

IF CONDUIT IS MINIMUM 36" BELOW GRADE.

3. MODIFY AS REQUIRED FOR RACEWAY LAYOUTS.

4. COORDINATE DEPTH OF HANDHOLES WITH CONDITIONS IN FIELD.

PROVIDE BOX EXTENSION AS REQUIRED TO MATCH DEPTHS OF DUCTS.

5. PROVIDE GROUND ROD IN EACH HANDHOLE CONTAINING GROUND CONDUITS.

6. COLOR OF ENCLOSURE, BOX AND COVER:

LIGHT GREEN FOR APPLICATIONS IN GRASS

LIGHT GREY FOR APPLICATIONS IN CONCRETE

DARK GREY FOR APPLICATIONS IN MACADAM

RED FOR APPLICATIONS IN RED BRICK PAVERS

COORDINATE WITH ARCHITECT FOR OTHER APPLICATIONS

7. COVER LEGEND: MOLDED LETTERING AS INDICATED FOR EACH SERVICE:

"ELECTRIC"

"TELEPHONE"

"COMMUNICATION"

"SECURITY"

"GROUND"

"CATV"

"FIRE ALARM"

8. MINIMUM ANSI SCTE TIER RATING, INSTALLATION IN:

LAWN AND SIDEWALKS: 8

PARKING LOT/DRIVEWAYS: 15

LOADING DOCKS: 22

AREAS SUBJECT TO HEAVY VEHICULAR TRAFFIC: 22

INSTALLATION

SKID RESISTANT SURFACE

PULL SLOT (TYPICAL OF 2)

STAINLESS STEEL HEX BOLT

WITH WASHER

LE

GEND

COVER

BASE

12"

12"

12"

MOUSEHOLES (2) 4X4" OPENING,

TYPICAL OF 2

#57 STONE EXTEND

12" BELOW BASE

OF HANDHOLE

#5 7 S

TO

NE

F

RO

M

" B

EL

OW

G

RA

DE

TO

B

AS

E

OF

HA

ND

HO

LE

#5 7 S

TO

NE

M

IN

. 1 2"

BE

LO

W

B

AS

E

OF

HA

ND

HO

LE

" F

IN

IS

HE

D

SO

IL

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

BI

M

- C on st ru ct

R ep la ce m en t O ut pa tie nt C lin ic

/0

C on st . R ep la ce . O ut pa tie nt

C lin ic

R

.rv t

2/ 9/

2:

:3

PM

E-503

ELECTRICAL DETAILS REPLACEMENT OUTPATIENT

CLINIC DESIGN AT COAST

GUARD CAPE COD

JOINT BASE CAPE COD, BARNSTABLE MA

650-318

BUILDING 1

02/10/2023 JFR KEM

100% CONSTRUCTION

DOCUMENTS

N.T.S.

POLE BASE DETAIL - TURF AREAS1

N.T.S.

POLE BASE DETAILS - PAVED AREAS2N.T.S.

HANDHOLE INSTALLATION3

SHORT CIRCUIT CALCULATION

INFINITE BUS METHOD

TRANSFORMER SIZE = 300KVA, 3-PHASE

SECONDARY VOLTAGE = 480Y/277V, 3-PHASE

AVAILABLE SCA AMPS = 13,390 AMPS

SERVICE ENTRANCE EQUIPMENT SCA RATING = 22 KAIC

800 A

480Y/277V, 3-PHASE, 4 WIRE

PANEL MDP

100400

M

TO UTILITY

PAD MOUNTED

UTILITY XFMR

UTILITY METERBAR CT CABINET

400 A

480Y/277V, 3-PHASE, 4 WIRE

PANEL HMP1

480- 208Y/120V

TLMP1

30 kVA

LMP1

HLP1

480V- 120/208V #1/0

TLRP2

112.5 kVA

LRP2

LRP3

110 175

SPD

N G

SEE SYSTEM GROUNDING

DETAIL ON SHEET E-501

SERVICE ENTRANCE RATED

LOS1

INV

BATTERY LIGHTING INVERTER

277V,1600 VA, 90 MIN,UL 924,

(6) 20/1 OUTPUT CIRCUIT BREAKERS,

MYERS EPS #6-EM-2-S-BD2006 OR EQUAL

(MAXIMUM 26" WIDE BY 12" DEEP)

UPS

20KVA

208V, 3PH INPUT/OUTPUT

TO BE APC - EASY UPS 3S

INTERNAL BATTERY OR

EQUAL (MAXIMUM 15"

WIDE BY 42" DEEP)

2 SETS OF 4#350KCMIL + 1#1/0AWG

SUPPLY SIDE BONDING JUMPER IN (2)

3" UNDERGROUND PVC CONDUITS

2 SETS OF 4#350KCMIL IN (2) 3"

UNDERGROUND PVC CONDUITS

NEW 3#4/0AWG + 1#1/0AWG GROUND, IN (1) 4" UNDERGROUND PVC CONDUIT AND (1) 4" SPARE PVC CONDUIT, 13.8KV PRIMARY FEEDER. THE CUSTOMER/CONTRACTOR IS TO INSTALL, OWN, & MAINTAIN THE PRIMARY UG CABLE FROM THE RISER POLE TO THE PAD MOUNT XFMR (ALL PRIVATELY-OWNED OFF OF AN EXISTING PRIVATELY-OWNED OVERHEAD PRIMARY SYSTEM). SEE ELECTRICAL SITE PLAN

ON SHEET E-100 FOR DETAILS.

(2) SETS OF 4#3/0AWG + 1#3AWG GND

EACH SET IN 2" C.

3#6AWG + 1#10AWG GND IN 3/4" C.

4#1AWG + 1#6AWG GND IN 1-1/2" C.

3#2/0AWG + 1#6AWG GND IN 2" C.

2 SETS OF 4#3/0AWG +

1#1/0AWG GND IN 2-1/2" C.

4#1AWG + 1#8AWG GND IN 2" C.

2 SETS OF 4#3/0AWG + 1

#3AWG GND IN 2-1/2" C.

4#3AWG + 1#8AWG

GND IN 1-1/4" C.

100 60 60 30

SPARE SPARE

480V- 120/208V #2

TLRP1

75 kVA

LRP1

3#2AWG + 1#6AWG GND IN 2" C.

4#300KCMIL +

1#2AWG GND IN 3" C.

ATS-LIFT

70 A

G 40kW

10HP LIFT

STATION

50KVA, 40EKW, 480Y/277V, 3-PHASE

DIESEL GENERATOR WITH 60 AMPERE

OUTPUT CIRCUIT BREAKER,

WEATHER PROOF, SOUND

ATTENUATING ENCLOSURE, 209

GALLON SUB-BASE FUEL TANK - BASIS

OF DESIGN IS CAT D40-GC.

480V, 3-POLE, SOLID

NEUTRAL, OPEN TRANSITION,

NEMA 3R ENCLOSURE - BASIS

OF DESIGN IS ASCO D-03ATS-

A-3-0070-N-G0-F.

3#4AWG + 1#8AWG GND

IN 1 1/4" C.

3#6AWG + 1#10AWG

GND IN 1" C.

SPARE

SPDSPD

SPD SPD

SPD

SPD

4#4AWG + 1#10AWG

GND IN 1" C.

TO

GG

LE

SW

ITC

H(

ES

CE

ILI

NG

/ W

AL

L M

OU

NT

ED

O

CC

UP

AN

CY

S

EN

SO

R(

S)

W

AL

L B

OX

O

CC

UP

AN

CY

SE

NS

OR

(S ) W

ITH

S

IN

GL

E

OU

TP

UT

R

EL

AY

W

AL

L B

OX

O

CC

UP

AN

CY

SE

NS

OR

(S ) W

ITH

D

IM

MI

NG

LU

MI

NA

IR

E W

ITH

BU

ILT

-IN

O

CC

UP

AN

CY

SE

NS

OR

0-1 0V

D

IM

MI

NG

SW

ITC

H

DI

GI

TA

L S W

ITC

H(

ES

CE

ILI

NG

/W

AL

L M

OU

NT

ED

O

CC

UP

AN

CY

S

EN

SO

R(

S)

IN

DO

OR

PH

OT

OS

EN

SO

R( S)

OU

TD

OO

R

PH

OT

OC

EL

L(S

AS

TR

ON

OM

IC

AL

TI

ME

CL

OC

K

FR

ES

CA

SW

ITC

HI

NG

FU

LL

R

AN

GE

D

IM

MI

NG

ST

EP

D

IM

MI

NG

CE

NT

RA

LIZ

ED

C

IR

CA

DI

AN

R

HY

TH

M

CC

T C

ON

TR

OL

VA

CA

NC

Y S

EN

SO

R

TIM

EO

UT

/D

EL

AY

(IN

M

IN

UT

ES

LIG

HT

S

MA

NU

AL

O N

LIG

HT

S

AU

TO

MA

TIC

O

N

TO

0%

LI

GH

T L

EV

EL

U

PO

N

OC

CU

PA

NC

Y

LIG

HT

S

AU

TO

MA

TIC

O

N

TO

LIG

HT

LE

VE

L U

PO

N

OC

CU

PA

NC

Y, 0%

M

AN

UA

L O

N

TIM

EC

LO

CK

S

CH

ED

UL

ED

"O

N"

TI

ME

TIM

EC

LO

CK

S

CH

ED

UL

ED

"O

FF

" T

IM

E

OC

C.

SE

NS

OR

O

VE

RR

ID

E T

IM

EC

LO

CK

D

UR

IN

G

"O

FF

" H

OU

RS

LIG

HT

IN

G

PA

RT

ITI

ON

S

EN

SO

RS

- Z

ON

ES

C

OM

BIN

E W

HE

N

PA

RT

ITI

ON

IS

O

PE

N

LINE VOLTAGE CONTROL DEVICE LOW VOLTAGE CONTROL DEVICE SWITCHING/DIMMING MISCELLANEOUS

VESTIBULE 103

TYPICAL SPACE TYPE

WAITING 104, 105

RECEPTION 106

RECEPTION WORKROOM 107

NURSE MANAGER 108

VOLUNTEER 109

PUBLIC TOILETS 110, 111

MULTI-PURPOSE ROOMS 112, 113

EXAM / TELEHEALTH 114,126,141

GROUP THERAPY ROOM, MENTAL HEALTH 115

MENTAL HEALTH CONSULT ROOMS 116-122

JANITOR CLOSET/ CLOSET 130, 149, 151, 156

UTILITY SOILED 158

UTILITY CLEAN 157

MECHANICAL 162 / ELECTRICAL 132, 161

EXAM / AUDIOLOGY 123

EXAM / EYE TEST 124

PATIENT TOILET 125, 129, 134

EXAM / MENTAL HEALTH 127

EXAM / PT / OT 139

SOCIAL WORKER 129

MED ROOM 145

STAFF TOILET 146, 148

- - - - - - X X - - - - - X - - 30 X - - - - -

X

-SPECIMEN COLLECTION 133

NOTES

NO AUTOMATIC CONTROLS PER 2019 ASHRAE 90.1 S9.4.1.1(h) EXCEPTION.

-- X - - - - - - - - - - X - - - 15 - X - - - - -

- - - - - X - - - - - - - X - - - - - - - - - -

- - - - - X - - - - - - - X - - - - - - - - - -

- - - - - - X X - - - - - X - - 30 X - - - - - -

- - - - X - - - - - - - X - - - - - - - - - -

- X - - - - - - - - - - X - - - 15 - X - - - - -

- - - - - X - - - - - - - X - - - - - - - - - -

- - - - - - X X - - - - X X - - 30 - X - - - - -

- - - - - - X X - - - - - X - - 30 X - - - - - -

WOMEN'S TOILET 136 / TOILET PROC. 142

WOMEN'S HEALTH EXAM ROOM 135

ULTRASOUND 137

TREATMENT EXERCISE AREA 138

EXAM 140/ EXAM/TRIAGE 128, 144

PROC. TOILET 142

GENERAL PROCEDURE ROOM 143

TEAM WORK AREA 147

OFFICE 159, 160

-- - - - - - X X - - - - - X - - 30 - X - - - - -

MENTAL HEALTH WORKSTATIONS 155

-- - - - - - X X - - - - X - - - 30 X - - - - - -

STAFF LOUNGE AND LOCKERS 154

-- - - - - - X X - - - - X - - - 15 X - - - - - -

MEDICAL AND GENERAL STORAGE 153

-- - - - - - X - - - - - X - - - - - - - - - - -

COMMUNICATIONS 152

-- - - - - X X - - - - X - - - 30 - X - - - - -

CORRIDORS 100, 163, 164-1, 164-2

- - - - - X - - - - - - - X - - - - - - - -

- - - - - - X X - - - - - X - 30 X - - - - -

- - - X - - - - - - - - - X - 30 X - - - - -

- X - - - - - - - - - - X - - - 15 X - - - - -

- X - - - - - - - - - - X - - - 15 X - - - - -

- X - - - - - - - - - - X - - - 15 X - - - - -

X - - - - - - - - - - - X - - - - - - - - - -

- - - - - X - - - - - - - X - - - - - - - -

- - - - - X - - - - - - - X - - - - - - - -

- X - - - - - - - - - - X - - - 15 - X - - - -

- - - - - X - - - - - - - X - - - - - - - - -

- - - - - X - - - - - - - X - - - - - - - - -

- - - X - - - - - - - - - X - - 30 X - - - - -

- X - - - - - - - - - - X - - - 15 X - - - - -

- X - - - - - - - - - - X - - - 15 - X - - - -

- - - - - - - X - - - - X - - - 30 - X - - - -

- - - - - - X X - - - - X - - - 30 - X - - - -

- - - - - - X X - - - - - X - 30 X - - - - -

- - - - - - X X - - - - - X - 30 X - - - - -

- - - - - - X X - - - - - X - 30 X - - - - -

- - - - - - X X - - - - - X - 30 X - - - - -

- - - X - - - - - - - - X - - - 15 - X - - - -

- - - - - - X X - - - - - X - 30 X - - - - -

NO AUTOMATIC CONTROLS PER 2019 ASHRAE 90.1 S9.4.1.1(h) EXCEPTION.

NO AUTOMATIC CONTROLS PER 2019 ASHRAE 90.1 S9.4.1.1(h) EXCEPTION.

NO AUTOMATIC CONTROLS PER 2019 ASHRAE 90.1 S9.4.1.1(h) EXCEPTION.

NO AUTOMATIC CONTROLS PER 2019 ASHRAE 90.1 S9.4.1.1(h) EXCEPTION.

NO AUTOMATIC CONTROLS PER 2019 ASHRAE 90.1 S9.4.1.1(h) EXCEPTION.

NO AUTOMATIC CONTROLS PER 2019 ASHRAE 90.1 S9.4.1.1(h) EXCEPTION.

NO AUTOMATIC CONTROLS PER 2019 ASHRAE 90.1 S9.4.1.1(h) EXCEPTION.

NO AUTOMATIC CONTROLS PER 2019 ASHRAE 90.1 S9.4.1.1(h) EXCEPTION.

ENTRY SIGN/FLAG POLE LIGHTING

SITE AREA LIGHTING

- - - - - - - - - X - - - - - - - - - - - - - - LIGHT FIXTURES CONTROLLED BY ROOF MOUNTED PHOTOCELL.

- - - - X - - - - X - - - - - - - - - - - - - - REFER TO LIGHTING FIXTURE SCHEDULE NOTE 6 ON SHEET E-801.

EPO GENERATOR

REMOTE

ANNUNCIATOR

PANEL

ATS-LIFT

GENERATOR

CONTROL

PANEL

1-1/2" CONDUIT

START/STOP

WIRING 4#12

RS-485 CABLING

PULL BOX

G

RS-485 CABLING

EMERGENCY STOP

WIRING 2#12

EXTERIOR

INTERIOR

EMERGENCY STOP

WIRING 2#12 IN 3/4"C

RS-485 CABLING

IN 3/4" C

START/STOP

WIRING 4#12 IN 3/4"C

RS-485 CABLING

IN 3/4"C

EMERGENCY POWER

OFF BUTTON

NOTE: THIS DIAGRAM IS INTENDED TO SHOW GENERAL DESIGN INTENT. PROVIDE WIRING

AS REQUIRED BASED UPON MANUFACTURER RECOMMENDATIONS AND TO FULFILL ALL PROJECT

REQUIREMENTS.

A. REFER TO SHEET E-100 AND E-204 FOR PANEL

CIRCUIT INFORMATION, TYPICAL.

NOTES:X

P1

277V

LIGHTING FIXTURESA

P2

SIGN & FLAG POLE

PHOTO CELL

MOUNTED NORTH

FACING ON ROOF

WHITE (NEUTRAL)

BLACK (LINE)

120V

N

L

MANUAL OFFAUTO

120V COIL

C

SPARE

A

120V

NOTE: THIS DIAGRAM IS INTENDED TO SHOW GENERAL DESIGN INTENT. PROVIDE WIRING

AS REQUIRED BASED UPON MANUFACTURER RECOMMENDATIONS AND TO FULFILL ALL PROJECT

REQUIREMENTS.

GND

HUBBELL

#DT5030W

OR EQUAL

DIGITAL

TIMER SWITCH

NORMALLY

CLOSED RELAY

J J

AUTOMATIC SINK

IN PATIENT TOILET 134

FLUSH VALVE

IN PATIENT TOILET 134

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

BI

M

- C on st ru ct

R ep la ce m en t O ut pa tie nt C lin ic

/0

C on st . R ep la ce . O ut pa tie nt

C lin ic

R

.rv t

2/ 9/

2:

:3

PM

E-601

ELECTRICAL ONE-LINE DIAGRAM REPLACEMENT OUTPATIENT

CLINIC DESIGN AT COAST

GUARD CAPE COD

JOINT BASE CAPE COD, BARNSTABLE MA

650-318

BUILDING 1

02/10/2023 JFR KEM

100% CONSTRUCTION

DOCUMENTS

N.T.S1 ELECTRICAL ONE-LINE DIAGRAM

N.T.S.

LIGHTING CONTROL MATRIX3

N.T.S.

TYPICAL ARC FLASH LABEL2

N.T.S.

GENERATOR CONTROL DIAGRAM4

N.T.S.

LIGHTING CONTACTOR WIRING DIAGRAM5

N.T.S.

AUTOMATIC PLUMBING DEVICE BYPASS TIMER DIAGRAM6

50KVA

NOTES: (APPLICABLE TO LUMINAIRE SCHEDULE ONLY)

1. ALL SUPPLIED LIGHTING FIXTURES MUST BE ON THE DESIGNLIGHTS CONSORTIUM (DLC) APPROVED LIGHTING LIST IN

ORDER TO QUALIFY FOR THE NGRID REBATE PROGRAM.

2. CONTRACTOR MAY SUBMIT LIGHT FIXTURES OF EQUAL OR BETTER PERFORMANCE FROM ALTERNATE VENDORS FOR REVIEW.

3. ALL FINAL FIXTURE SELECTIONS SHALL BE BY ARCHITECT.

4. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF LIGHT FIXTURES. COORDINATE TYPE OF

CEILING FOR EACH FIXTURE WITH ARCHITECTURAL REFLECTED CEILING PLANS AND PROVIDE FIXTURE TRIM AS REQUIRED.

5. PROVIDE ALL REQUIRED HARDWARE TO MOUNT FIXTURES PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.

IF THERE IS A DISCREPANCY BETWEEN A FIXTURE DESCRIPTION AND THE CATALOG NUMBER LISTED, THE FIXTURE DESCRIPTION

SHALL DICTATE.

6. PROVIDE WIRELESS CONTROL GATEWAY (BASIS OF DESIGN IS COOPER WAVELINX PRO) WITH TIME-SWITCH CONTROL FUNCTION.

EXTERIOR LIGHTING CONTROLS SHALL MEET 2021 IECC SECTION C405.2.7 REQUIREMENTS. EXTERIOR LIGHTS SHALL AUTOMATICALLY TURN OFF WHEN DAYLIGHT IS PRESENT. EXTERIOR LIGHTS SHALL REDUCE TO 50% OUTPUT FROM MIDNIGHT TO 6AM, NOT LATER THAN ONE HOUR AFTER BUSINESS CLOSING TO NOT EARLIER THAN ONE HOUR BEFORE BUSINESS OPENING, AND DURING ANY TIME WHERE ACTIVITY HAS NOT BEEN DETECTED FOR 15 MINUTES OR MORE. ALL EXTERIOR LIGHTS SHALL BE CONTROLLED TOGETHER, WHERE NOT MORE THAN 1500 WATTS OF LIGHTING POWER SHALL BE CONTROLLED TOGETHER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

BI

M

- C on st ru ct

R ep la ce m en t O ut pa tie nt C lin ic

/0

C on st . R ep la ce . O ut pa tie nt

C lin ic

R

.rv t

2/ 9/

2:

:4

PM

E-801

ELECTRICAL SCHEDULES REPLACEMENT OUTPATIENT

CLINIC DESIGN AT COAST

GUARD CAPE COD

JOINT BASE CAPE COD, BARNSTABLE MA

650-318

BUILDING 1

02/10/2023 JFR KEM

100% CONSTRUCTION

DOCUMENTS

LIGHTING FIXTURE SCHEDULE

TYPE DESCRIPTION MANUFACTURER MODEL VOLTAGE VA LAMP TYPE

FIXTURE

LUMENS

FIXTURE COLOR

TEMP (K) DRIVER COMMENTS

A1 2x2 LED SPECIFICATION GRADE TROFFER WITH INTEGRAL 0-10V DIMMING DRIVER. METALUX 22EN-LD2-30-UNV-L835-CD1-U 277 V 25 VA LED 3076 3500 0-10V DIMMING A2 2x2 LED SPECIFICATION GRADE TROFFER WITH INTEGRAL 0-10V DIMMING DRIVER. METALUX 22EN-LD2-39-UNV-L835-CD1-U 277 V 34 VA LED 3979 3500 0-10V DIMMING

AX4 RECESSED 4' LED LINEAR FIXTURE AXIS LIGHTING CLKLED-400-80-35-SO-4-W-UNV-DP-1-AC 277 V 13 VA LED 1600 3500 0-10V DIMMING COORDINATE INSTALLATION WITH CEILING GRID AND

MANUFACTURERS INSTALLATION INSTRUCTIONS.

AX4B RECESSED 4' LED LINEAR FIXTURE AXIS LIGHTING CLKLED-900-80-35-SO-4-W-UNV-DP-1-AC 277 V 31 VA LED 3600 3500 0-10V DIMMING COORDINATE INSTALLATION WITH CEILING GRID AND

MANUFACTURERS INSTALLATION INSTRUCTIONS.

C1 19" EXAM LIGHT WITH 45 DEGREE BEAM KIRLIN (2) PRO-19045-35K / (1) PRO-WALLC / (1)

PRO-REMOT

277 V 55 VA LED - 3500 0-10V DIMMING 7000 FOOT CANDLES DELIVERED ON TASK.

D1 4" DIAMETER ROUND LED DOWNLIGHT WITH MEDIUM DISTRIBUTION, WARM HAZE FINISH AND INTEGRAL 0-10V DIMMING DRIVER. PORTFOLIO LD4B15D010 / EU4B10208035 / 4LBM1WMH 277 V 16 VA LED 1500 3500 0-10V DIMMING FLG POLE MOUNTED LED FLAG UP-LIGHT. ACUITY BRANDS SC855-L1L50-R30-277-HL 277 V 55 VA LED 4528 4000 NON-DIMMING MOUNTED AT 6' AFG ON FLAG POLE, SPACED AT 120DEG

APART. PROVIDE HEXCELL LOUVER FOR FIXTURE.

PROVIDE POLE MOUNTING HARDWARE TO MATCH POLE

DIAMETER.

L1 4' LONG LED STRIP FIXTURE WITH ROUND WIDE DISTRIBUTION FULL FROSTED ACRYLIC LENS AND INTEGRAL 0-10V DIMMING DRIVER. METALUX 4SNLED-LD5-44SL-LW-UNV-L835-CD1-U-AYC-CHAIN 277 V 38 VA LED 2300 3500 0-10V DIMMING FIXTURE IS CHAIN SUSPENDED AT 8'-0" A.F.F.

L2 4' LONG LED STRIP FIXTURE WITH ROUND WIDE DISTRIBUTION FULL FROSTED ACRYLIC LENS AND INTEGRAL 0-10V DIMMING DRIVER. METALUX 4SNLED-LD5-56SL-LW-UNV-L835-CD1-U-AYC-CHAIN 277 V 52 VA LED 5700 3500 0-10V DIMMING FIXTURE IS CHAIN SUSPENDED AT 8'-0" A.F.F.

P1 DECORATIVE PENDANT LED, DRIPPING LIGHT MARSET DIPPING LIGHT 13 277 V 72 VA LED 203 2700 0-10V DIMMING FIXTURE IS CHAIN SUSPENDED AT 7'-0" A.F.F.

SA SINGLE HEAD LED SITE LIGHTING FIXTURE WITH SPILL CONTROL, INTEGRAL PHOTO CELL, MOTION SENSOR, WIRELESS CONTROLS AND

TYPE III WITH SPILL CONTROL OPTICAL DISTRIBUTION

MCGRAW EDISON GLEON-SA1-C-740-U-SL3-FINISH-ZW-SWPD5BZ-WA

C-POE-WPOE-120

277 V 59 VA LED 7400 4000 WIRELESS

DIMMING

20' PAINTED ROUND ALUMINUM POLE WITH CONCRETE

BASE TO 3' AFG. MOUNT FIXTURE AT 23' AFG. FINISH TO

BE SELECTED BY ARC OR EQUAL. SEE SCHEDULE NOTE

6 BELOW FOR EXTERIOR CONTROL DETAILS.

SB SINGLE HEAD LED SITE LIGHTING FIXTURE WITH INTEGRAL PHOTO CELL, MOTION SENSOR, WIRELESS CONTROLS AND TYPE V SQUARE

WIDE OPTICAL DISTRIBUTION.

MCGRAW EDISON GLEON-SA2-B-740-U-5WQ-FINISH-ZW-SWPD5BZ-WA

C-POE-WPOE-120

277 V 85 VA LED 12300 4000 WIRELESS

DIMMING

20' PAINTED ROUND ALUMINUM POLE WITH CONCRETE

BASE TO 3' AFG. MOUNT FIXTURE AT 23' AFG. FINISH TO

BE SELECTED BY ARC OR EQUAL. SEE SCHEDULE NOTE

6 BELOW FOR EXTERIOR CONTROL DETAILS.

SB2 DOUBLE HEAD LED SITE LIGHTING FIXTURE WITH INTEGRAL PHOTO CELL, MOTION SENSOR, WIRELESS CONTROLS AND TYPE V SQUARE

WIDE OPTICAL DISTRIBUTION.

MCGRAW EDISON GLEON-SA2-B-740-U-5WQ-FINISH-ZW-SWPD5BZ-WA

C-POE-WPOE-120

277 V 170 VA LED 12300 4000 WIRELESS

DIMMING

20' PAINTED ROUND ALUMINUM POLE WITH CONCRETE

BASE TO 3' AFG. MOUNT FIXTURE AT 23' AFG. FINISH TO

BE SELECTED BY ARC OR EQUAL. SEE SCHEDULE NOTE

6 BELOW FOR EXTERIOR CONTROL DETAILS.

SC LED SITE LIGHTING, FULL CUTOFF LENS MODEL, WIRELESS CONTROLS AND COLD WEATHER BATTERY PACK. COOPER LIGHTING AXCS3A-FINISH-ZW-SWPD4-BZ-CBP 277 V 27 VA LED 3500 4000 WIRELESS

DIMMING

10' PAINTED ROUND ALUMINUM POLE WITH CONCRETE

BASE TO 3' AFG. MOUNT FIXTURE AT 10' AFG. FINISH TO

BE SELECTED BY ARC OR EQUAL. SEE SCHEDULE NOTE

6 BELOW FOR EXTERIOR CONTROL DETAILS.

SL WALL MOUNTED LINEAR LED SIGN LIGHT. PINNACLE MN-HE-840SO-12FT-WH 18"-U-FSD-1-W-V 277 V 70 VA LED 9000 4000 0-10V DIMMING SL1 WALL MOUNTED EXTERIOR LED SITE LIGHTING FIXTURE WITH UP/DOWN LIGHT, SQUARE PLATE, BRONZE FINISH AND WET LOCATION

LISTING.

LUMIERE

LSI

9002-W2-RW-LED3590-OPTIC1-OPTIC2-BZ-L1-UNV-

WIS

277 V 10 VA LED 1000 3500 NON-DIMMING SEE ARCHITECTURAL ELEVATIONS FOR MOUNTING

HEIGHTS AND LOCATIONS.

SL2 WALL MOUNTED LED LUMINAIRE WITH FULL CUTOFF OPTICS, GLARE REDUCING LENS AND COLOR TO BE SELECTED BY ARCHITECT. COOPER LIGHTING AXCS3A-FINISH-GRF 277 V 27 VA LED 3500 4000 INTEGRAL SQ4 4" SQUARED LED DOWNLIGHT, UL LISTED WET LOCATION. LITHONIA LDN4SQ-40/20-LS4-AR-LSS-MVOLT-GZ10 277 V 16 VA LED 2000 3500 0-10V DIMMING V1 2' LONG 4" LED WALL MOUNT VANITY FIXTURE WITH SATIN DROP DIFFUSER, 0-10V DIMMING DRIVER AND FINISH TO BE SELECTED BY

ARCHITECT.

NEO-RAY S124DW-C-795D-835-4F0-1-U-DD-D-FINISH 277 V 13 VA LED 1600 3500 0-10V DIMMING WALL MOUNT WITH BOTTOM OF FIXTURE AT 4" ABOVE

MIRROR.

WG 42" X 42" RECESSED CEILING LED GLASS ARCHITECTURAL CEILING LIGHT, WITH INTEGRAL 0-10V DIMMING DRIVER.

DIMMING DRIVER. FINISH TO BE SELECTED BY ARCHITECT.

LIGHTGLASS S-42X42-G-1-35-I-X 277 V 21 VA LED 1603 3500 0-10V DIMMING

X1 RECESSED EDGE LIT LED EXIT SIGN, WALL MOUNTED, RED LETTERS, CLEAR BACKGROUND AND SINGLE OR DOUBLE FACE, POWERED

FROM BATTERY INVERTER.

SURE-LITES ES-S6 277 V 5 VA LED - - N/A

X2 RECESSED EDGE LIT LED EXIT SIGN, CEILLING MOUNTED, RED LETTERS, CLEAR BACKGROUND AND SINGLE OR DOUBLE FACE, POWERED

FROM BATTERY INVERTER.

SURE-LITES ES-S6 277 V 5 VA LED - - N/A

EQUIPMENT SCHEDULE

EQUIPMENT

NAME IDENTIFICATION HP FLA MCA

VOLT / PH / LOAD

(VA) MOCP

CB

AMPS PANEL CKT # FEEDER SIZE CONDUIT MOTOR STARTING DISC MEANS COMMENTS

AHU-111001 AIR HANDLING UNIT - MARINE LIGHTS - 3 - 120 V/1-360 VA - 15 LMP1 2 2#12 AWG + 1#12 AWG GND 3/4" N/A DS-AHU-111001-ML AHU-111001 AIR HANDLING UNIT - SUPPLY FAN ARRAY - - 60 480 V/3-49881 VA 100 100 HMP1 2,4,6 3#2 AWG + 1#8 AWG GND 1 1/2" VFD FACTORY VFD DUCT SMOKE DETECTORS ON SUPPLY AND RETURN FURNISHED

AND CONNECTED BY E.C., MOUNTED IN DUCTWORK BY M.C.

AHU-111001 AIR HANDING UNIT - UV LIGHTS - 4 - 120 V/1-480 VA - 15 LMP1 3 2#12 AWG + 1#12 AWG GND 3/4" N/A DS-AHU-111001-UV BL-111001 HOT WATER BOILER - 20 - 120 V/1-2400 VA - 25 LMP1 8 2#10 AWG + 1#10 AWG GND 3/4" N/A DS-BL-111001 CH-111001 AIR COOLED WATER CHILLER - - 162 480 V/3-134680 VA 175 175 MDP 5 3#2/0 AWG + 1#6 AWG GND 2" VFD FACTORY VFD

CHWP-111001 CHILLED WATER PUMP 5 7.6 - 480 V/3-6318 VA - 20 HMP1 14,16,18 3#12 AWG + 1#12 AWG GND 3/4" VFD VFD FURNISHED BY M.C., MOUNTED ADJACENT TO PUMP AND

CONNECTED BY E.C.

CHWP-111002 CHILLED WATER PUMP 5 7.6 - 480 V/3-6318 VA - 20 HMP1 13,15,17 3#12 AWG + 1#12 AWG GND 3/4" VFD VFD FURNISHED BY M.C., MOUNTED ADJACENT TO PUMP AND

CONNECTED BY E.C.

E-PAR POWERED PARTITION 1 14.0 - 120 V/1-1680 VA 20 20 LRP3A 21 2#12 AWG + 1#12 AWG GND 3/4" N/A MS-EPAR EF-121001 WAITING AREA EXHAUST FAN 2 3.2 - 480 V/3-2660 VA - 20 HMP1 20,22,24 3#12 AWG + 1#12 AWG GND 3/4" NEMA 0 FACTORY DISCONNECT EF-121002 RESTROOM EXHAUST FAN 1/10 1.5 - 120 V/1-180 VA - 20 LMP1 9 2#12 AWG + 1#12 AWG GND 3/4" N/A FACTORY DISCONNECT

FCSS-111001 MINI-SPLIT DUCTLESS HEAT PUMP INDOOR UNIT - - - 208 V/1-100 VA - - PER MANUFACTURER 1" N/A DS-FCSS-111001 POWERED FROM OUTDOOR UNIT HP-111001 FCSS-111002 MINI-SPLIT DUCTLESS HEAT PUMP INDOOR UNIT - - - 208 V/1-100 VA - - PER MANUFACTURER 1" N/A DS-FCSS-111002 POWERED FROM OUTDOOR UNIT HP-111002 FCSS-111003 MINI-SPLIT DUCTLESS HEAT PUMP INDOOR UNIT - - - 208 V/1-100 VA - - PER MANUFACTURER 1" N/A DS-FCSS-111003 POWERED FROM OUTDOOR UNIT HP-111003 GWH-111001 GAS WATER HEATER - 3 - 120 V/1-50 VA - 15 LMP1 5 2#12 AWG + 1#12 AWG GND 3/4" N/A DS-GWH-111001 GWH-111002 GAS WATER HEATER - 3 - 120 V/1-50 VA - 15 LMP1 5 2#12 AWG + 1#12 AWG GND 3/4" N/A DS-GWH-111002

HHWP-111001 HEATING HOT WATER PUMP 5 7.6 - 480 V/3-6318 VA - 20 HMP1 7,9,11 3#12 AWG + 1#12 AWG GND 3/4" VFD VFD FURNISHED BY M.C., MOUNTED ADJACENT TO PUMP AND

CONNECTED BY E.C.

HHWP-111002 HEATING HOT WATER PUMP 5 7.6 - 480 V/3-6318 VA - 20 HMP1 8,10,12 3#12 AWG + 1#12 AWG GND 3/4" VFD VFD FURNISHED BY M.C., MOUNTED ADJACENT TO PUMP AND

CONNECTED BY E.C.

HP-111001 MINI-SPLIT DUCTLESS HEAT PUMP OUTDOOR UNIT - - 14 208 V/1-2330 VA 15 15 LMP1 11,13 2#12 AWG + 1#12 AWG GND 3/4" N/A DS-HP-111001 HP-111002 MINI-SPLIT DUCTLESS HEAT PUMP OUTDOOR UNIT - - 17.1 208 V/1-2683 VA 20 20 LMP1 15,17 2#12 AWG + 1#12 AWG GND 3/4" N/A DS-HP-111002 HP-111003 MINI-SPLIT DUCTLESS HEAT PUMP OUTDOOR UNIT - - 17.1 208 V/1-2683 VA 20 20 LMP1 12,14 2#12 AWG + 1#12 AWG GND 3/4" N/A DS-HP-111003

HWP-111001 HOT WATER RECIRC. PUMP 1/2 9.8 - 208 V/1-1176 VA - 15 LMP1 4,6 2#12 AWG + 1#12 AWG GND 3/4" N/A DS-HWP-111001 RF-121001 AIR HANDLING UNIT RELIEF FAN 10 14 - 480 V/3-11640 VA - 30 HMP1 19,21,23 3#10 AWG + 1#10 AWG GND 3/4" VFD DS-RF-121001 VFD CONTROL PANEL FURNISHED BY M.C., MOUNTED AND

CONNECTED BY E.C. SEE FLOOR PLANS FOR LOCATION. E.C. TO

PROVIDE INTERLOCK BETWEEN LOCAL DISCONNECT AND VFD.

SH-111001 STEAM GENERATOR - 4.0 - 120 V/1-500 VA - 20 LMP1 7 2#12 AWG + 1#12 AWG GND 3/4" N/A DS-SH-111001 UH-111001 UNIT WALL HEATER - - 12.5 120 V/1-1500 VA - 20 LMP1 19 2#12 AWG + 1#12 AWG GND 3/4" N/A FACTORY DISCONNECT UV-111001 ULTRAVIOLET WATER DISINFECTION - 2 - 120 V/1-230 VA - 20 LMP1 10 2#12 AWG + 1#12 AWG GND 3/4" N/A DS-UV-111001

DISCONNECT SCHEDULE

DISC NAME TYPE OF EQUIPMENT

VOLTAGE

RATING

ENCLOSURE

RATING DISC. AMP/POLE FUSE/BREAKER SIZE STARTER SIZE DISCONNECT NOTES

DS-AHU-111001-ML TOGGLE SWITCH WITH PILOT LIGHT 120/1Ø TYPE 3R 20A/1P N/A N/A

DS-AHU-111001-UV TOGGLE SWITCH WITH PILOT LIGHT 120/1Ø TYPE 3R 20A/1P N/A N/A

DS-BL-111001 NON-FUSIBLE DISCONNECT 120/1Ø TYPE 1 30A/1P N/A N/A

DS-FCSS-111001 NON-FUSIBLE DISCONNECT 208/1Ø TYPE 1 30A/2P N/A N/A

DS-FCSS-111002 NON-FUSIBLE DISCONNECT 208/1Ø TYPE 1 30A/2P N/A N/A

DS-FCSS-111003 NON-FUSIBLE DISCONNECT 208/1Ø TYPE 1 30A/2P N/A N/A

DS-GWH-111001 TOGGLE SWITCH WITH PILOT LIGHT 120/1Ø TYPE 1 20A/1P N/A N/A

DS-GWH-111002 TOGGLE SWITCH WITH PILOT LIGHT 120/1Ø TYPE 1 20A/1P N/A N/A

DS-HP-111001 NON-FUSIBLE DISCONNECT 208/1Ø TYPE 3R 30A/2P N/A N/A

DS-HP-111002 NON-FUSIBLE DISCONNECT 208/1Ø TYPE 3R 30A/2P N/A N/A

DS-HP-111003 NON-FUSIBLE DISCONNECT 208/1Ø TYPE 3R 30A/2P N/A N/A

DS-HWP-111001 TOGGLE SWITCH WITH PILOT LIGHT 120/1Ø TYPE 1 20A/1P N/A N/A

DS-RF-121001 NON-FUSIBLE DISCONNECT 480/3Ø TYPE 4X 30A/3P N/A N/A E.C. TO PROVIDE INTERLOCK BETWEEN DISCONNECT AND VFD.

DS-UV-111001 TOGGLE SWITCH WITH PILOT LIGHT 120/1Ø TYPE 1 20A/1P N/A N/A

MS-EPAR MOTOR RATED TOGGLE SWITCH 120/1Ø TYPE 1 20A/1P N/A N/A

TRANSFORMER SCHEDULE

TAG SERVING SIZE PRIMARY VOLTAGE SECONDARY VOLTAGE LOCATION SUPPLY FROM TYPE GROUND CONDUCTOR NOTES

TLMP1 LMP1 30 KVA 480 208Y/120 ELECTRICAL ROOM 161 HMP1 DRY TYPE #10AWG WALL MOUNTED

TLRP1 LRP1 45 KVA 208Y/120 ELECTRICAL ROOM 161 MDP #6AWG

TLRP2 LRP2 112.5 KVA 480 208Y/120 ELECTRICAL ROOM 161 MDP DRY TYPE #1/0AWG FLOOR PAD MOUNTED

ASSOCIATED OUTDOOR UNIT

ASSOCIATED OUTDOOR UNIT

ASSOCIATED OUTDOOR UNIT

1. SEE F2/E-501 FOR TYPICAL SPD MOUNTING DETAIL

Notes:

Total Est. Demand... 510 A Lighting - Exterior 1181 VA 100.00% 1181 VA Total Conn. Current: 550 A Receptacle 77540 VA 56.45% 43770 VA Total Est. Demand: 423863 VA Other 340193 VA 100.00% 340193 VA Total Conn. Load: 457633 VA Lighting 10278 VA 100.00% 10278 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

550 A

457633 VA

10 SPD (NOTE 1) 3 30 A 0.0 kVA 9 SPACE -- -- 0.0 kVA -- 8 SPACE -- -- 0.0 kVA -- 7 SPARE 3 60 A 0.0 kVA 6 SPARE 3 60 A 0.0 kVA 5 CH-111001 3 175 A 134.7 kVA 4 TLRP2 3 175 A 143.1 kVA 3 TLRP1 3 110 A 61.3 kVA 2 HMP1 3 400 A 107.1 kVA 1 HLP1 3 100 A 11.5 kVA

CKT Circuit Description # of

Poles Trip Rating Load Remarks

SERVICE ENTRANCE RATED

Neutral Rating: 100.00% Enclosure: Type 1 MCB Rating: 800 A Mounting: Surface Wires: 4 Mains Rating: 800 A

Supply From: Phases: 3 Mains Type: MCB Location: ELECTRICAL ROOM 161 Volts: 480/277 Wye A.I.C. Rating: 25000

Panelboard: MDP

Notes:

Total Est. Demand Current: 129 A

Total Conn. Current: 129 A

Total Est. Demand: 107.07 kVA

Total Conn. Load: 107.1 kVA

Other 107065 VA 100.00% 107065 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 139 A 123 A 124 A

Total Load: 38.5 kVA 34.2 kVA 34.4 kVA

41 SPARE 20 A 1 0.00 0.00 42

39 SPARE 20 A 1 0.00 0.00 40

37 SPARE 20 A 1 0.00 0.00

3 30 A SPD

35 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 36

33 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 34

31 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 32

29 0.40 0.00 1 20 A SPARE 30

27 0.40 0.00 1 20 A SPARE 28

LIFT STATION VIA ATS-LIFT 60 A 3

0.40 0.00 1 20 A SPARE 26

23 3.88 0.89 24

21 3.88 0.89 22

RF-121001 30 A 3

3.88 0.89

3 20 A EF-001

17 2.11 2.11 18

15 2.11 2.11 16

CHWP-01 20 A 3

2.11 2.11

3 20 A CHWP-02

11 2.11 2.11 12

9 2.11 2.11 10

HHWP-01 20 A 3

2.11 2.11

3 20 A HHWP-02

5 4.18 16.63 6

3 3.94 16.63 4

TLMP1 100 A 3

8.30 16.63

3 100 A AHU-111001

CKT Circuit Description No t e Trip Po l e A B C Po l e Trip No t e Circuit Description CKT

MAXIMUM DIMENSIONS 2'-8" WIDTH X 9" DEPTH

Notes:

Enclosure: Type 1 Neutral Rating: 100.00%

Mounting: Surface Wires: 4 Mains Rating: 400 A

Supply From: MDP Phases: 3 Mains Type: MCB

Location: ELECTRICAL ROOM 161/ Volts: 480/277 Wye A.I.C. Rating: 10000

Branch Panel: HMP1

Notes:

Total Est. Demand Current: 4 A

Total Conn. Current: 4 A

Total Est. Demand: 1.18 kVA

Lighting - Exterior 54 VA 100.00% 54 VA Total Conn. Load: 1.2 kVA

Lighting 1132 VA 100.00% 1132 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps:

Total Load: 1.2 kVA 0.0 kVA

1 LTG CORRIDOR-1 164-1 20 A 1 1.08 0.10 1 20 A EXTERIOR LTG 2

CKT Circuit Description No t e Trip Po l e A A Po l e Trip No t e Circuit Description CKT

BATTERY LIGHTING INVERTER 277V,1000 VA, 90 MIN,UL 924, MYERS EPS #6-EM-1-S-BD2006 OR EQUAL (MAXIMUM 26" WIDE BY 12" DEEP), MAXIMUM DIMENSIONS 2' WIDTH X 10" DEPTH

Notes:

Enclosure: Type 1 Neutral Rating: 100.00%

Mounting: Surface Wires: 2 Mains Rating: 20 A

Supply From: PANEL HLP1 Phases: 1 Mains Type: MCB

Location: ELECTRICAL ROOM 161/ Volts: 277V SINGLE A.I.C. Rating:

INVERTER: INV

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

BI

M

- C on st ru ct

R ep la ce m en t O ut pa tie nt C lin ic

/0

C on st . R ep la ce . O ut pa tie nt

C lin ic

R

.rv t

2/ 9/

2:

:4

PM

E-802

ELECTRICAL PANEL SCHEDULES REPLACEMENT OUTPATIENT

CLINIC DESIGN AT COAST

GUARD CAPE COD

JOINT BASE CAPE COD, BARNSTABLE MA

650-318

BUILDING 1

02/10/2023 JFR KEM

100% CONSTRUCTION

DOCUMENTS

BRANCH CIRCUIT NOTES:

Total Est. Demand Current: 14 A

Total Conn. Current: 14 A

Lighting - Exterior 1181 VA 100.00% 1181 VA Total Est. Demand: 11.51 kVA

Oth…