Attachment 13 - Fire Protection.pdf
PDF 2 MB Posted
- Solicitation number
- 36C77624R0087
About this file
This document is an attachment related to the fire protection requirements for a federal contract opportunity to Construct Replacement Outpatient Clinic at US Coast Guard Air Station. The key details are:
The project involves the design and installation of a fully automatic wet-pipe fire sprinkler system for a new one-story, 16,373 sq ft outpatient clinic building. The fire protection system must comply with NFPA 13 (2022 edition) and VA fire protection design standards. The building will have a combination of light hazard, ordinary hazard group 1, and ordinary hazard group 2 occupancy areas, each with specific sprinkler density and area of operation requirements. The contractor must provide hydraulically calculated sprinkler designs, integrate the system with the fire alarm, and conduct acceptance testing per NFPA standards. Required materials must be UL listed or FM approved. The project also includes a new 4-inch fire service entrance, backflow preventer, and fire department connection.
View the file
Other files
Show all 46
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIRE PROTECTION LEGEND
NOTE: SOME ABBREVIATIONS AND SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT
GENERAL LEGEND
SYMBOL DESCRIPTION
OS&Y VALVE
FIRE DEPARTMENT CONNECTION
FIRE PROTECTION RISER
GATE VALVE
ALARM CHECK VALVE
BALL VALVE
PRESSURE REGULATING VALVE
BUTTERFLY VALVE
FLOW SWITCH
SYMBOL DESCRIPTION
PIPE TURNING DOWN
PIPE TURNING UP
FS FLOW SWITCH
TS TAMPER SWITCH
HOSE HOSE LINE CABINET
LH LIGHT HAZARD
OH-1 ORDINATY HAZARD - GROUP 1
OH-2 ORDINATY HAZARD - GROUP 2
FLUSHING CONNECTION OR CAP
A
B
SIM
FP
SECTION SYMBOL:
A = IDENTIFYING LETTER
B = SHEET WHERE SECTION IS SHOWN
SIM = SIMILAR
(ONLY NOTED IF IT APPLIES)
FIRE PROTECTION RISER DESIGNATION:
A = RISER IDENTIFYING SYSTEM TYPE
1 =
REVISION CLOUD AND
REVISION NUMBER
A TITLE SYMBOL ON SHEET WHERE SHOWN
A = IDENTIFYING NUMBER/LETTER
RISER IDENTIFYING SYSTEM NUMBER
SYMBOL DESCRIPTION
FIRE PROTECTION ABBREVIATIONS
AS ABOVE SLAB
AHJ AUTHORITY HAVING JURISDICTION
AFF ABOVE FINISHED FLOOR
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
ASTM AMERICAN STANDARDS TESTING MATERIALS
BFP BACKFLOW PREVENTER
BLDG BUILDING
BOR BOTTON OF RISER
BS BELOW SLAB
CAP CAPACITY
CONN CONNECTION
CONT CONTINUOUS
CV CHECK VALVE
DIA DIAMETER
DN DOWN
DP DRY PENDENT
DS DRY SIDE WALL
DWG DRAWING
ELEV ELEVATION
ºF DEGREES FAHRENHEIT
FDC FIRE DEPARTMENT CONNECTION
FDV FIRE DEPARTMENT VALVE
FM FACTORY MUTUAL
FP FIRE PROTECTION
FS FLOW SWITCH
FT FEET
GA GAUGE
GAL GALLON(S)
GALV GALVANIZED
GPM GALLONS PER MINUTE
HD HEAD
HP HORSEPOWER
HR HOUR
HYD HYDRANT
HZ HERTZ
IE INVERT ELEVATION
ID INTERNAL DIAMETER
IN INCHES
IPS INTERNATIONAL PIPE STANDARD
ABBR. DESCRIPTION ABBR. DESCRIPTION
KW KILOWATT
LF LINEAR FEET
MAX MAXIMUM
MIN MINIMUM
NA NOT APPLICABLE
NC NORMALLY CLOSED
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NG NITROGEN GENERATOR
NTS NOT TO SCALE
OD OUTSIDE DIAMETER
OS&Y OUTSIDE SCREW AND YOLK
P PUMP
PH PHASE
PIV POST INDICATING VALVE
POC POINT OF CONNECTION
PSI POUNDS PER SQUARE INCH
PS PRESSURE SWITCH
QR QUICK RESPONSE
RM ROOM
RPM REVOLUTIONS PER MINUTE
SF SQUARE FEET
SPEC SPECIFICATIONS
SR STANDARD RESPONSE
STD STANDARD
TEMP TEMPERATURE
TDH TOTAL DYNAMIC HEAD
TOR TOP OF RISER
TS TAMPER SWITCH
TYP TYPICAL
UG UNDERGROUND
UL UNDERWRITER'S LABORATORY
UNO UNLESS NOTED OTHERWISE
V VOLTS
VA DEPARTMENT OF VETERANS AFFAIRS
VIV VALVE IN VERTICAL
VLV VALVE
VOL VOLUME
W/ WITH
SHEET NOTE CALLOUT1
FIRE PROTECTION COMPLIANCE NOTES FIRE PROTECTION GENERAL NOTES
BUILDING DESIGN:
THE REPLACEMENT OUTPATIENT CLINIC DESIGN AT COAST GUARD CAPE COD IS A
NEW ONE STORY 16,373 SQFT BUSINESS OCCUPANCY BUILDING.
SCOPE OF WORK:
THE FIRE PROTECTION SPRINKLER CONTRACTOR SHALL HAVE THE DELEGATED
ENGINEER DESIGN AND HYDRAULICALLY CALCULATE THE NEW FIRE SPRINKLER
SYSTEM FOR THE NEW BUILDING SPACES AS INDICATED ON THE FIRE PROTECTION
DRAWINGS AND IN THE FIRE PROTECTION SPECIFICATIONS.
THE BUILDING SHALL BE FULLY PROTECTED BY A FULLY AUTOMATIC WET SYSTEM IN
ACCORDANCE WITH NFPA 13 2022 EDITION. ALL SPRINKLER HEADS SHALL BE QUICK
RESPONSIVE TYPE AND INSTALLED IN CENTER OF CEILING TILES. THE OCCUPIED
SPACES WILL BE SERVED BY A WET FIRE PROTECTION SYSTEM. SPRINKLER
CONTRACTOR SHALL USE FLOW TEST DATA WHEN PERFORMING HYDRAULIC
CALCULATIONS.
FIRE PROTECTION SPRINKLER CONTRACTOR SHALL COORDINATE THE DESIGN AND
INSTALLATION OF THE FIRE PROTECTION SPRINKLER SYSTEM AND DELIVER A
COMPLETE, FULLY FUNCTIONAL, AND TESTED FIRE PROTECTION SYSTEM THAT
MEETS THE REQUIREMENTS OF THE FIRE PROTECTION DRAWINGS, FIRE PROTECTION
SPECIFICATIONS, LISTED CODES AND STANDARDS, AND THE REQUIREMENTS OF THE
VA. THE FIRE PROTECTION SPRINKLER CONTRACTOR SHALL PROVIDE AND INSTALL
NEW MATERIALS THAT ARE UL LISTED AND\OR FM APPROVED AS REQUIRED BY THE
FIRE PROTECTION DRAWINGS AND THE FIRE PROTECTION SPECIFICATIONS. THE FIRE
PROTECTION SPRINKLER CONTRACTOR SHALL INTEGRATE THE NEW FIRE SPRINKLER
SYSTEM WITH THE NEW FIRE ALARM SYSTEM.
FLOW TEST DATA:
48 PSI STATIC; 787 GPM AT 25 PSI RESIDUAL; 1,032 GPM AT 10 PSI FOR SPRINKLER
SYSTEM; FLOW TEST RESULTS HAVE BEEN COMPLETED ON FIRE HYDRANT #68 ON
EAST HOSPTIAL ROAD BY JBCC FIRE DEPARTMENT FROM THE CITY OF CAPE COD ON
06/23/2022 AT 08:30 AM.
THE HYDRANT TESTED IS 19 FT. ABOVE THE FINISHED BUILDING ELEVATION AND THE
WATER TOWER WAS DRAINED TO MINIMUM WATER LEVELS DURING THE TEST DUE
TO MAINTENANCE. THEREFORE, THE AVAILABLE FLOW FOR THE BUILDING FIRE
PROTECTION SYSTEM WILL BE GREATER THAN THE CURRENT FLOW TEST DATA.
FLOW TEST INFORMATION NOT BASED ON ANY VARIATIONS WITH SYSTEM PRESSURE
OVER A 24 HOUR PERIOD.
BACKFLOW PREVENTION AND METERING SPECIFICATIONS:
THE BACKFLOW PREVENTION DEVICE ASSEMBLY AND METERING EQUIPMENT WILL
MEET THE REQUIREMENTS OF THE LOCAL WATER PURVEYOR. ALL NEW INTERIOR
FIRE PROTECTION EQUIPMENT SHALL BE UL LISTED OR FM APPROVED.
QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL INTERIOR FIRE PROTECTION
COMPONENTS:
ALL NEW INTERIOR FIRE PROTECTION EQUIPMENT EQUIPMENT SHALL BE UL LISTED
OR FM APPROVED.
VALVING AND ALARM REQUIREMENTS TO MINIMIZE POTENTIAL FOR IMPAIRMENTS AND
UNRECOGNIZED FLOW OF WATER:
THE FIRE SPRINKLER RISER FOR THIS BUILDING AND ALL CONTROL VALVE, POST
INDICATOR AND BACKFLOW PREVENTER WILL BE EQUIPPED WITH AN ALARM CHECK
VALVE AND WATER FLOW SWITCH, WITH A LOCAL ALARM BELL AND FIRE ALARM PANEL.
ACCEPTANCE TEST CRITERIA:
FIRE SPRINKLER SYSTEM SHALL BE DESIGNED PER NFPA 13, 2022 EDITION AND SHALL
COMPLY WITH THE VA AS THE SOLE AUTHORITY HAVING JURISDICTION (AHJ). THE
ACCEPTANCE TESTING OF THE FIRE SPRINKLER SYSTEM AND IT'S COMPONENTS SHALL
CONSIST OF ALL APPLICABLE ITEMS SHOWN ON THESE TWO FORMS, NFPA 13, 2022
EDITION, ANNEX A (FIG. A.29.1) CONTRACTOR'S MATERIAL AND TEST CERTIFICATE FOR
ABOVE GROUND PIPING. SEE NFPA 13, 2022 EDITION CHAPTER 29 FOR SYSTEM
ACCEPTANCE AND NFPA 25, 2020 INSPECTION TESTING AND MAINTENANCE.
A. CHAPTER 29, SYSTEM ACCEPTANCE
B. 29.1 APPROVAL OF SPRINKLER SYSTEM
C. 29.2 ACCEPTANCE REQUIREMENTS
D. 29.3 INSTRUCTIONS
E. 29.4 HYDRAULIC DESIGN INFORMATION SIGNS
APPLICABLE NFPA AND VA STANDARDS TO BE APPLIED:
A. U.S. DEPARTMENT OF VETERAN AFFAIRS FIRE PROTECTION DESIGN MANUAL -
EIGHTH EDITION, JUNE 2021
B. INTERNATIONAL BUILDING CODE 2018 EDITION
C. NFPA 13, 2022 EDITION, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS
D. NFPA 25, 2020 EDITION, INSPECTION, TESTING AND MAINTENANCE OF WATER BASED
FIRE PROTECTION SYSTEM.
E. NFPA 55, 2020 EDITION, COMPRESSED GASES AND CRYOGENIC FLUIDS
F. NFPA 101, 2021 EDITION, LIFE SAFETY CODE
CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR AREA:
LIGHT HAZARD:
SPACES WITH LOW QUANTITY AND COMBUSTIBILITY OF CONTENTS
I.E. OFFICES, EXAM ROOMS, CORRIDORS, MEETING ROOMS, BREAK ROOMS,
AND RESTROOMS.
ORDINARY HAZARD GROUP 1:
SPACES WITH MODERATE QUANTITY AND LOW COMBUSTIBILITY OF CONTENTS
I.E. LABORATORIES, MECHANICAL ROOMS, ELECTRICAL ROOMS, JANITOR
CLOSETS, AND AUTOPSY.
ORDINARY HAZARD GROUP 2:
SPACES WITH MODERATE TO HIGH QUANTITY AND COMBUSTIBILITY OF CONTENTS
I.E. NITROGEN STORAGE, CLEAN AND SOILED UTILITY ROOMS, MODERATE
QUANTITY AND MODERATE COMBUSTIBILITY STORAGE (UP TO 12 FT IN
HEIGHT),CLEAN AND SOILED LINEN ROOMS, AND LAUNDRY.
DESIGN APPROACH:
SPRINKLER SYSTEM TO EXTEND INTO ALL AREAS IN ACCORDANCE WITH NFPA 13 LIGHT
HAZARD OR AS NOTED. LISTED AND APPROVED SIDEWALL (5.60 K-FACTOR) AND
PENDENT (5.60 K-FACTOR) SPRINKLER HEADS TO BE PROVIDED. UPRIGHT (5.60 K-
FACTOR) HEADS TO BE PROVIDED WHERE NOTED ON DRAWINGS.
1. FIRE PROTECTION SYSTEM SHALL COMPLY WITH NFPA 13 (2022 EDITION) AND VA FIRE
PROTECTION DESIGN MANUAL (2021 EDITION) FOR INSTALLATION OF SPRINKLER
SYSTEMS. INSPECTION, TESTING, AND MAINTENANCE SHALL COMPLY TO NFPA 25 (2020
EDITION). FINAL INSPECTION AND APPROVAL BY THE VA (AHJ).
2. SPRINKLER SHOP DRAWINGS AND MATERIAL SUBMITTALS SHALL BE SUBMITTED TO
THE ARCHITECT/ENGINEER AND STATE FIRE MARSHALL AND SHALL BE APPROVED
PRIOR TO ANY INSTALLATION. THE ENGINEER OF RECORD SHALL HAVE THE RIGHT TO
REJECT ANY SUBMITTALS.
3. CUTTING OF STRUCTURAL AND/OR ARCHITECTURAL MEMBERS TO BE DONE ONLY WITH
THE WRITTEN APPROVAL OF THE ARCHITECT AND STRUCTURAL ENGINEER.
4. FITTINGS REQUIRED FOR PROPER INSTALLATION, COORDINATION WITH OTHER
EXISTING TRADES, AND/OR TO MAINTAIN PROPER CLEARANCES SHALL BE PROVIDED.
VERIFY STRUCTURAL, MECHANICAL, ELECTRICAL INSTALLATIONS AND AVOID AN/ALL
OBSTRUCTIONS OR INTERFERENCES WITH FIRE PROTECTION PIPE ROUTING.
5. CONTRACTOR SHALL MAKE A FIELD VISIT TO VERIFY ARCHITECTURAL REFLECTED
CEILING CONDITIONS AND ELECTRICAL LIGHTING, CEILING CONFIGURATIONS AND
HEIGHTS.
6. FIRE STOP ALL PENETRATIONS OF SMOKE/FIRE WALLS, CEILINGS, FLOORS, ROOFS,
ETC., FLASH AND COUNTERFLASH ROOF PENETRATIONS.
7. PROVIDE ACCESS PANELS TO ALL VALVES ABOVE NON-ACCESSIBLE CEILINGS AND
CHASES.
8. SPRINKLER HEADS ARE TO BE COORDINATED WITH ALL LOCATIONS OF DIFFUSERS,
SPEAKERS, LIGHTING FIXTURES, CEILING SYSTEMS AND STRUCTURAL SYSTEM.
9. INDICATE CENTER TO CENTER DIMENSIONS AND/OR PIPE CUT LENGTHS AND NOMINAL
PIPE DIAMETERS ON ALL PIPING. INDICATE PIPE TYPE, SCHEDULE OF WALL THICKNESS
AND METHOD OF JOINING ON SHOP DRAWING.
10. PROVIDE STOCK OF EXTRA SPRINKLERS IN ACCORDANCE WITH NFPA 13.
11. PROVIDE DETAIL AND INDICATE TYPE OF HANGERS TO BE INSTALLED FOR SPRINKLER
PIPING. METHODS OF HANGING PIPES, HEADERS AND BRANCHES SHALL BE IN
ACCORDANCE WITH NFPA 13. ALL HANGERS ON 4" PIPE AND LARGER SHALL BE CLEVIS-
TYPE HANGERS. HANGERS SHALL NOT INTERFERE WITH ANY OTHER TRADE. POWDER
DRIVEN STUDS SHALL NOT BE USED.
12. ALL GROOVED & SCREWED FITTINGS SHALL BE UL/FM APPROVED AND SUBMITTED TO
THE ENGINEER OF RECORD FOR APPROVAL PRIOR TO ANY INSTALLATION. THE
ENGINEER OF RECORD RESERVES THE RIGHT TO DISAPPROVE ANY FITTING. ALL
SCREWED PIPING SHALL BE SCHEDULE 40 BLACK STEEL PIPE IN ACCORDANCE WITH
SPECIFICATIONS ASTM A120 AND SHALL BE JOINED BY SCREWED JOINTS IN
ACCORDANCE WITH SPECIFICATION ANSI B2.1. ALL GROOVED PIPING 2-1/2" OR LARGER
SHALL BE SCHEDULE 10 BLACK STEEL.
13. WELD-O-LETS SHALL BE TWO SIZES SMALLER THAN CROSS MAIN, NO LENGTH OF
CROSS MAIN SHALL BE GREATER THAN 10'-0". ALL SPRINKLER PIPING & FITTINGS SHALL
BE INSTALLED ABSOLUTELY RUST-FREE.
14. AUTOMATIC SPRINKLER TEMPERATURE RATINGS OF FUSIBLE ELEMENTS TO BE IN
ACCORDANCE WITH NFPA 13.
15. ALL VALVES FOR FIRE SERVICE SHALL BE LISTED BY THE UNDERWRITER'S
LABORATORIES, INC. AND THE FACTORY MUTUAL LABORATORIES. VALVES SHALL BE
FACTORY MARKED "UL" OR "FM", AND RATED FOR 175 WORKING PRESSURE.
16. SPRINKLER COVERAGE SHALL COMPLY WITH NFPA 13. SPRINKLER LOCATIONS WITH
RESPECT TO OBSTRUCTIONS SHALL COMPLY WITH NFPA 13-2022, CHAPTER 9, OR THE
APPROPRIATE CHAPTER BASED ON SPRINKLER TYPE.
17. IMMEDIATELY NOTIFY THE ARCHITECT/ENGINEER OF ANY DISCREPANCIES FOUND
BETWEEN THESE PLANS, OTHER ENGINEERING PLANS, THE ARCHITECTURAL PLANS
AND/OR FIELD CONDITIONS PRIOR TO FINAL BID PRICE OR FINAL PERMITTING.
18. IN CASE OF DISPUTE OR DOUBT AS TO INTENT OF DRAWINGS OR SPECIFICATIONS,
OBTAIN ARCHITECT/ENGINEER'S WRITTEN DECISION BEFORE PROCEEDING WITH BID
OR WORK INVOLVED.
19. BEFORE SUBMITTING PROPOSAL OR BID, EXAMINE ALL DRAWINGS AND SPECIFICATIONS
RELATING TO THIS PROJECT, THE AMOUNT OF SPACE AVAILABLE FOR PIPING, EQUIPMENT
AND CONNECTING SERVICES, THE SCOPE OF SITE OF THE WORK, THE REQUIREMENTS TO
CORRELATE THE FIRE PROTECTION WORK WITH THAT OF OTHER TRADES AND THE TIME
SCHEDULE NECESSARY TO PERFORM THAT WORK.
20. PIPE SHALL BE REAMED AND CLEANED BEFORE ASSEMBLY, AND AFTER ASSEMBLY THE
ENTIRE PIPING SYSTEM SHALL BE FLUSHED CLEAN.
21. ADJUST NEW SPRINKLER PIPING AND SPRINKLER HEAD PLACEMENT TO ACCOMMODATE
EXISTING CEILING HEIGHTS AND STRUCTURAL CONFIGURATIONS.
22. PROVIDE SPRINKLERS ABOVE AND BELOW EXPOSED DUCTWORK 4 FEET OR WIDER.
23. PROVIDE HAZARD COVERAGE FOR THE FUNCTIONS FOR EACH AREA.
24. INDICATE THE LOCATION AND SIZE OF BLIND SPACES AND CLOSETS.
25. INDICATE THE TOTAL SQUARE FOOT AREA PROTECTED BY SYSTEM(S).
26. INDICATE THE NUMBER OF SPRINKLERS ON EACH RISER.
27. ALL PENDENT SPRINKLERS SHALL BE CENTER OF TILE, UNLESS MAXIMUM DISTANCES FROM
WALLS OR BETWEEN HEADS IS EXCEEDED OR UNLESS SHOWN DIFFERENTLY ON
DRAWINGS. IF NOT POSSIBLE ALL SPRINKLER HEADS MOUNTED IN CEILING SHALL BE
LOCATED A MINIMUM OF 4" AWAY FROM ANY WALLS, CEILING GRID MEMBERS, CEILING
HEIGHT CHANGES OR ANY OTHER VERTICAL INTERSECTING STRUCTURAL SURFACE.
28. FIRE PROTECTION CONTRACTOR SHALL ASSIST IN PREPARATION OF COORDINATION
DRAWINGS FOR ALL LEVELS WHICH INDICATE ALL THE ENGINEERING DISCIPLINES & FIRE
PROTECTION PIPING. THESE DRAWINGS SHALL BE PREPARED & APPROVED BY THE
ENGINEER OF RECORD PRIOR TO ANY INSTALLATION.
29. FIRE SPRINKLER PIPING SHALL NOT TRAVEL OVER THE TOPS OF ELECTRICAL
PANELBOARDS.
30. PROVIDE TEFLON COATING FOR ALL SPRINKLERS IN ANY CORROSIVE AREA.
31. REFER TO ARCHITECTURAL DRAWINGS FOR CEILING HEIGHTS IN EACH AREA.
32. ALL MATERIALS, WHERE APPLICABLE, SHALL BE U.L. LISTED OR FACTORY MUTUAL
APPROVED FOR USE IN AUTOMATIC SPRINKLER SYSTEMS. ALL NEW PIPING SHALL BE
HYDROSTATICALLY TESTED FOR TWO HOURS IN ACCORDANCE WITH NFPA 13. MINIMUM
HYDROSTATIC TEST PRESSURE SHALL BE 200 PSI.
33. FLEXIBLE SPRINKLER CONNECTIONS SHALL ONLY BE PERMITTED UPON VA APPROVAL. IF
FLEXIBLE SPRINKLER CONNECTIONS ARE PERMITTED AND USED, HYDRAULIC
CALCULATIONS MUST BE PERFORMED AND SUBMITTED TO THE ENGINEER OF RECORD.
34. THE SMALL ROOM RULE SHALL BE ACCEPTABLE FOR PLACEMENT OF SPRINKLERS PER
NFPA 13-2022, 10.2.5.2.3.
LIGHT HAZARD:
SYSTEM TYPE: WET PIPE AUTOMATIC SPRINKLER SYSTEM, USING STEEL SUPPLY
PIPING TO NEW QUICK RESPONSE, PENDENT OR UPRIGHT HEADS.
K-FACTOR: 5.6.
DENSITY: 0.10 GPM/SQ.FT.
AREA OF OPERATION: 900 SQ FT MIN AND 1500 SQ FT MAX (DESIGN AREA
REDUCTION MAY ONLY BE USED IF CEILING HEIGHT AND AREA CLASSIFICATION
PERMITS PER NFPA 13 2022 EDITION.
HEAD TEMPERATURE RATING: 155 DEGREES F.
SPACING: 225 SQ. FT. MAX. PER SPRINKLER HEAD OR BY MANUFACTURER
LITERATURE.
HOSE ALLOWANCE: 100 GPM
ORDINARY HAZARD GROUP 1:
SYSTEM TYPE: WET PIPE AUTOMATIC SPRINKLER SYSTEM, USING STEEL SUPPLY
PIPING TO NEW QUICK RESPONSE, PENDENT OR UPRIGHT HEADS.
K-FACTOR: 5.6, 8.0, 11.2, OR 14.0.
DENSITY: 0.15 GPM/SQ.FT.
AREA OF OPERATION: 900 SQ FT MIN AND 1500 SQ FT MAX (DESIGN AREA
REDUCTION MAY ONLY BE USED IF CEILING HEIGHT AND AREA CLASSIFICATION
PERMITS PER NFPA 13 2022 EDITION.
HEAD TEMPERATURE RATING: 155 DEGREES F.
SPACING: 130 SQ. FT. MAX. PER SPRINKLER HEAD OR BY MANUFACTURER
LITERATURE.
HOSE ALLOWANCE: 250 GPM
ORDINARY HAZARD GROUP 2:
SYSTEM TYPE: WET PIPE AUTOMATIC SPRINKLER SYSTEM, USING STEEL SUPPLY
PIPING TO NEW QUICK RESPONSE, OR STANDARD SPRAY UPRIGHT, SEMI-
RECESSED PENDENT, OR SIDEWALL HEADS.
K-FACTOR: 5.6, 8.0, 11.2, OR 14.0.
DENSITY: 0.20 GPM/SQ.FT.
AREA OF OPERATION: 900 SQ FT MIN AND 1500 SQ FT MAX (DESIGN AREA
REDUCTION MAY ONLY BE USED IF CEILING HEIGHT AND AREA CLASSIFICATION
PERMITS PER NFPA 13 2022 EDITION).
HEAD TEMPERATURE RATING: 155 DEGREES F.
SPACING: 130 SQ. FT. MAX. PER SPRINKLER HEAD OR BY MANUFACTURER
LITERATURE.
HOSE ALLOWANCE: 250 GPM
HAZARD CLASSIFICATION
LIGHT HAZARD
NOTES:
PROVIDE A HYDRAULICALLY CALCULATED AUTOMATIC SPRINKLER SYSTEM FOR A LIGHT HAZARD OCCUPANCY WITH A MINIMUM DENSITY/AREA OF 0.10 GPM/SF OVER 1500 SF PER NFPA 13. SPRINKLER CONTRACTOR SHALL AQUIRE ANY FLOW TEST OR FIRE PUMP DATA FOR HYDRAULIC CALCULATIONS. THE LATEST FLOW TEST OR FIRE PUMP DATA MUST BE WITHIN THE PAST 12 MONTHS. PER THE VA FIRE PROTECTION DESIGN MANUAL 6.1.D, CONTRACTOR MAY USE PIPE SCHEDULE METHOD FOR EXTENSION OF EXISTING
PIPE SCHEDULE SYSTEMS WHERE WATER SUPPLY IS ADEQUATE (2022 NFPA 13 19.2.2).
ORDINARY HAZARD GROUP 1
PROVIDE A HYDRAULICALLY CALCULATED AUTOMATIC SPRINKLER SYSTEM FOR AN ORDINARY HAZARD GROUP 1 OCCUPANCY WITH A MINIMUM DENSITY/AREA OF 0.15 GPM/SF OVER 1500 SF PER NFPA 13. SPRINKLER CONTRACTOR SHALL AQUIRE ANY FLOW TEST OR FIRE PUMP DATA FOR HYDRAULIC CALCULATIONS. THE LATEST FLOW TEST OR FIRE PUMP DATA MUST BE WITHIN THE PAST 12 MONTHS. PER THE VA FIRE PROTECTION DESIGN MANUAL 6.1.D, CONTRACTOR MAY USE PIPE SCHEDULE METHOD FOR EXTENSION OF EXISTING PIPE SCHEDULE SYSTEMS WHERE WATER SUPPLY IS ADEQUATE (2022 NFPA 13 19.2.2).
ORDINARY HAZARD GROUP 2
PROVIDE A HYDRAULICALLY CALCULATED AUTOMATIC SPRINKLER SYSTEM FOR AN ORDINARY HAZARD GROUP 2 OCCUPANCY WITH A MINIMUM DENSITY/AREA OF 0.20 GPM/SF OVER 1500 SF PER NFPA 13. SPRINKLER CONTRACTOR SHALL AQUIRE ANY FLOW TEST OR FIRE PUMP DATA FOR HYDRAULIC CALCULATIONS. THE LATEST FLOW TEST OR FIRE PUMP DATA MUST BE WITHIN THE PAST 12 MONTHS. PER THE VA FIRE PROTECTION DESIGN MANUAL 6.1.D, CONTRACTOR MAY USE PIPE SCHEDULE METHOD FOR EXTENSION OF EXISTING PIPE SCHEDULE SYSTEMS WHERE WATER SUPPLY IS ADEQUATE (2022 NFPA 13 19.2.2).
KEY
N/A SPRINKLERS AND FIRE PROTECTION ARE NOT REQUIRED.
HAZARD CLASSIFICATION LEGEND
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
BI
M
- C on st ru ct
R ep la ce m en t O ut pa tie nt C lin ic
/0
C on st . R ep la ce . O ut pa tie nt
C lin ic
R
.rv t
2/ 9/
0:
:4
AM
FP001
FIRE PROTECTION LEGENDS &
SYMBOLS
REPLACEMENT OUTPATIENT
CLINIC DESIGN AT COAST
GUARD CAPE COD
JOINT BASE CAPE COD, BARNSTABLE MA
650-318
BUILDING 1
02/10/2023 JFR WRH
100% CONSTRUCTION
DOCUMENTS
SHEET LIST
Sheet Number Sheet Name
FP001 FIRE PROTECTION LEGENDS & SYMBOLS
FP111 FIRE PROTECTION HAZARD CLASSIFICATIONS
FP112 PARTIAL FIRST FLOOR PLAN - FIRE PROTECTION - WEST
FP113 PARTIAL FIRST FLOOR PLAN - FIRE PROTECTION - EAST
FP501 FIRE PROTECTION DETAILS
Revisions Date
HAZARD CLASSIFICATION
LIGHT HAZARD
ORDINARY HAZARD GROUP 1
ORDINARY HAZARD GROUP 2
KEY
N/A
H G F E D C B A
I
VESTIBULE
WAITING
CORRIDOR
WAITING
RECEPTION
RECEPTION
WORKROOM
NURSE MANAGER
TOILET PUBLIC
TOILET PUBLIC
VOLUNTEER
CORRIDOR
SOCIAL WORKER
ELEC
SPECIMEN
COLLECTION
TOILET WMN'S
TOILET PATIENT
EXAM RM WOMEN'S
HEALTH
ULTRASOUND
TREATMENT
EXERCISE AREA
EXAM / PT/OT
EXAM / TRIAGE
PROCEDURE
ROOM, GENERAL
TOILET PROC.
TOILET STAFF
EXAM /
TELE-HEALTH
EXAM
CLOSET
CORRIDOR
MED ROOM
TOILET STAFF
TEAM WORK AREA
EXAM/TRIAGE
EXAM / MENTAL
HEALTH
EXAM /
TELE-HEALTH
EXAM / AUDIOLOGY
124 EXAM / EYE TEST
123EXAM
MULTI-PURPOSE
ROOM
MULTI-PURPOSE
ROOM
GROUP THERAPY
ROOM, MENTAL
HEALTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
OFFICE
CORRIDOR
UTILITY SOILED
ELECTRICAL ROOM
MECHANICAL
JANITOR CLOSET
WORKSTATIONS,
MENTAL HEALTH
STAFF LOUNGE &
LOCKERS
STORAGE MEDICAL
& GENERAL
COMMUNICATIONS
UTILITY CLEAN
OFFICE
CLOSET
H.2 H.1 F.7 F.5 F.3 E.5 D.9 D.7 D.6 D.5 D.3 C.6 C.5 C.3 B.7 A.4
5.5
3.7
3.6
3.3
3.1
2.7
2.5
2.4
1.9
1.5
1.3
CLOSET
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
BI
M
- C on st ru ct
R ep la ce m en t O ut pa tie nt C lin ic
/0
C on st . R ep la ce . O ut pa tie nt
C lin ic
R
.rv t
2/ 9/
0:
:5
AM
FP111
FIRE PROTECTION HAZARD
CLASSIFICATIONS
REPLACEMENT OUTPATIENT
CLINIC DESIGN AT COAST
GUARD CAPE COD
JOINT BASE CAPE COD, BARNSTABLE MA
650-318
BUILDING 1
02/10/2023 JFR WRH
100% CONSTRUCTION
DOCUMENTS
CODED NOTES:
SPRINKLERS ARE NOT REQUIRED IN THIS AREA. AREA IS CLASSIFIED AS A CEILING POCKET AND
MEETS ALL THE REQUIREMENTS OF NFPA13 2022 10.2.9.2.
DRAWING NOTES:
1. REFER TO FP112 AND FP113 FOR SPRINKLER PIPING AND NOTES ON FIRE PROTECTION SYSTEM
DESIGN.
2. PROVIDE A HYDRAULICALLY CALCULATED AUTOMATIC SPRINKLER SYSTEM FOR THE HAZARD
CLASSIFICATIONS SHOWN ON PLANS PER NFPA 13 AND VA GUIDELINES. REFER TO FIRE PROTECTION
COMPLIANCE NOTES ON SHEET FP001.
1/8" = 1'-0"FP111
1 FIRST FLOOR PLAN - HAZARD CLASSIFICATIONS - FIRE PROTECTION
0 4' 8' 16' 24'
1/8" = 1'-0"
N
H G F E D
I
4" FM
VESTIBULE
WAITING
CORRIDOR
WAITING
RECEPTION
RECEPTION
WORKROOM
NURSE MANAGER
TOILET PUBLIC
TOILET PUBLIC
VOLUNTEER
CORRIDOR
SOCIAL WORKER
ELEC
SPECIMEN
COLLECTION
TOILET WMN'S
TOILET PATIENT
EXAM RM WOMEN'S
HEALTH
ULTRASOUND
TREATMENT
EXERCISE AREA
EXAM / PT/OT
EXAM / TRIAGE
PROCEDURE
ROOM, GENERAL
TOILET PROC.
TOILET STAFF
EXAM /
TELE-HEALTH
EXAM
CLOSET
CORRIDOR
MED ROOM
TOILET STAFF
TEAM WORK AREA
EXAM/TRIAGE
EXAM / MENTAL
HEALTH
EXAM /
TELE-HEALTH
EXAM / AUDIOLOGY
EXAM / EYE TEST
123EXAM
114MULTI-PURPOSE
ROOM
MULTI-PURPOSE
ROOM
113 GROUP THERAPY
ROOM, MENTAL
HEALTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
H.2 H.1 F.7 F.5 F.3 E.5 D.9 D.7 D.6 D.5 D.3 C.6 C.5 C.3
5.5
3.7
3.6
3.3
3.1
2.7
2.5
2.4
1.9
1.5
1.3
TOILET PATIENT
125 EXAM / AUDIOLOGY
M
AT
C H
LI
N
E -C
O N
TI
N
U
ED
O N
D W
G
/F P1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
BI
M
- C on st ru ct
R ep la ce m en t O ut pa tie nt C lin ic
/0
C on st . R ep la ce . O ut pa tie nt
C lin ic
R
.rv t
2/ 9/
0:
:5
AM
FP112
PARTIAL FIRST FLOOR PLAN -
FIRE PROTECTION - WEST
REPLACEMENT OUTPATIENT
CLINIC DESIGN AT COAST
GUARD CAPE COD
JOINT BASE CAPE COD, BARNSTABLE MA
650-318
BUILDING 1
02/10/2023 JFR WRH
100% CONSTRUCTION
DOCUMENTS
CODED NOTES:
WALL MOUNTED FIRE DEPARTMENT SIAMESE CONNECTION. PROVIDE AUTOMATIC BALL DRIP. REFER
TO DETAIL 7/FP501.
FOLDING PARTITION WALL. ENSURE SPRINKLER COVERAGE IS ADEQUATE WHEN THE WALL IS OPEN
AND CLOSED.
FDC CHECK VALVE ABOVE ACCESSIBLE CEILING.
DRAWING NOTES:
1. REFER TO FP111 FOR FIRE PROTECTION SPRINKLER HAZARD CLASSIFICATIONS.
2. PROVIDE A HYDRAULICALLY CALCULATED AUTOMATIC SPRINKLER SYSTEM FOR THE HAZARD
CLASSIFICATIONS SHOWN ON PLANS PER NFPA 13 AND VA GUIDELINES. REFER TO FIRE PROTECTION
COMPLIANCE NOTES ON SHEET FP001.
0 4' 8' 12' 16'
3/16" = 1'-0"
N
3/16" = 1'-0"FP112
1 PARTIAL FIRST FLOOR PLAN - FIRE PROTECTION - WEST
C B A
4" FM CONT. TO
SPRINKLERS
OFFICE
CORRIDOR
UTILITY SOILED
ELECTRICAL ROOM
MECHANICAL
JANITOR CLOSET
WORKSTATIONS,
MENTAL HEALTH
STAFF LOUNGE &
LOCKERS
STORAGE MEDICAL
& GENERAL
COMMUNICATIONS
UTILITY CLEAN
OFFICE
B.7 A.4
5.5
3.7
3.6
3.3
3.1
2.7
2.5
2.4
1.9
1.5
1.3
M
AT
C H
LI
N
E -C
O N
TI
N
U
ED
O N
D W
G
/F P1
4" FM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
BI
M
- C on st ru ct
R ep la ce m en t O ut pa tie nt C lin ic
/0
C on st . R ep la ce . O ut pa tie nt
C lin ic
R
.rv t
5/ 4/
:4
2:
A M
FP113
PARTIAL FIRST FLOOR PLAN -
FIRE PROTECTION - EAST
REPLACEMENT OUTPATIENT
CLINIC DESIGN AT COAST
GUARD CAPE COD
JOINT BASE CAPE COD, BARNSTABLE MA
650-318
BUILDING 1
02/10/2023 JFR WRH
100% CONSTRUCTION
DOCUMENTS
CODED NOTES:
SPRINKLERS WITHIN THIS REGION SHALL BE UPRIGHT TYPE. THE DISTANCE BETWEEN SPRINKLER
DEFLECTOR AND STRUCTURE ABOVE SHALL BE A MINIMUM OF 1" AND A MAXIMUM OF 12".
PROVIDE SPRINKLER HEADS UNDER ALL DUCTS AND OBSTRUCTIONS GREATER THAN 48" IN WIDTH
PER NFPA 13 IN THIS ROOM.
4" FIRE RISER LOCATION. PROVIDE A REDUCED PRESSURE DETECTOR ASSEMBLY BACKFLOW
PREVENTER ON FIRE MAIN. PROVIDE A WET RISER, ALARM RISER VALVE BASIS OF DESIGN VIKING J-1
WITH TRIM, AFTER BACKFLOW PREVENTER.
4" FIRE MAIN. REFER TO CIVIL PLANS FOR CONTINUATION.
FLUSH MOUNT FORWARD FLOW TEST HEADER CONNECTION. REFER TO DETAIL 5/FP501.
ROUTE DRAINS FROM RISER VALVES TO SPLASH BLOCK AT EXTERIOR OF BUILDING. TIE DRAIN FROM
FIRE PROTECTION BACKFLOW WITH DOMESTIC WATER BACKFLOW AND ROUTE TO EXTERIOR OF
BUILDING. COORDINATE WITH PLUMBING CONTRACTOR. REFER TO DETAIL 5/FP501.
DRAWING NOTES:
1. REFER TO FP111 FOR FIRE PROTECTION SPRINKLER HAZARD CLASSIFICATIONS.
2. PROVIDE A HYDRAULICALLY CALCULATED AUTOMATIC SPRINKLER SYSTEM FOR THE HAZARD
CLASSIFICATIONS SHOWN ON PLANS PER NFPA 13 AND VA GUIDELINES. REFER TO FIRE PROTECTION
COMPLIANCE NOTES ON SHEET FP001.
3/16" = 1'-0"FP113
1 PARTIAL FIRST FLOOR PLAN - FIRE PROTECTION - EAST 0 4' 8' 12' 16'
3/16" = 1'-0"
N
RECESSED CEILING
ESCUTCHEON
FINISH
CEILING
1" SUPPLY LINE
1"x1/2" REDUCING
COUPLING
PENDANT TYPE SPRINKLER HEAD
CEILING
1/2"REDUCER
BRANCH LINE
1" 90° ELL1" 90° ELL
1" DROP
NOTE:
1. THE CUMULATIVE HORIZONTAL LENGTH OF AN UNSUPPORTED ARM OVER TO A SPRINKLER, SPRINKLER DROP, OR SPRIG SHALL NOT EXCEED 24 IN FOR STEEL PIPE OR 12 IN FOR COPPER PIPE PER NFPA 13 17.4.3.5.
1. WALL ASSEMBLY--THE 1, 2, 3 OR 4 HR FIRE-RATED GYPSUM
WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE
MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR
U400 SERIES WALL OR PARTITION DESIGNS IN THE UL FIRE RESISTANCE
DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION
FEATURES:
A. STUDS--WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS
(MAX 2 H FIRE RATED ASSEMBLIES OR STEEL CHANNEL STUDS.
WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. LUMBER SPACED 16
IN. OC WITH NOM 2 BY 4 IN. LUMBER END PLATES AND CROSS
BRACES. STEEL STUDS TO BE MIN 3-5/8 IN. WIDE BY 1-3/8 IN. DEEP
CHANNELS SPACED MAX 24 IN. OC.
B. WALLBOARD, GYPSUM *--NOM 1/2 OR 5/8 IN. THICK, 4 FT. WIDE WITH
SQUARE OR TAPERED EDGES. THE GYPSUM WALLBOARD TYPE,
THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET
ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR
U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX
DIAM OF OPENING IS 13-1/2 IN.
2. PIPE OR CONDUIT--NOM 12 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR
HEAVIER) STEEL PIPE, NOM 12 IN. DIAM (OR SMALLER) SERVICE WEIGHT (OR
HEAVIER) CAST IRON SOIL PIPE, NOM 12 IN. DIAM (OR SMALLER) CLASS 50
(OR HEAVIER) DUCTILE IRON PRESSURE PIPE, NOM 6 IN. DIAM (OR SMALLER)
STEEL CONDUIT, NOM 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL
METALLIC TUBING, NOM 6 IN. DIAM (OR SMALLER) TYPE L OR (OR
HEAVIER) COPPER TUBING OR NOM 1 IN. DIAM (OR SMALLER) FLEXIBLE
STEEL CONDUIT. WHEN COPPER PIPE IS USED, MAX F RATING OF FIRESTOP
SYSTEM (ITEM 3) IS 2 H. STEEL PIPES OR CONDUITS LARGER THAN NOM 4 IN.
DIAM MAY ONLY BE USED IN WALLS CONSTRUCTED USING STEEL CHANNEL
STUDS. A MAX OF ONE PIPE OR CONDUIT IS PERMITTED IN THE FIRESTOP
SYSTEM. PIPE OR CONDUIT TO BE INSTALLED NEAR CENTER OF STUD
CAVITY WIDTH AND TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL
ASSEMBLY.
3. FILL, VOID OR CAVITY MATERIAL*--CAULK--CAULK FILL MATERIAL INSTALLED
TO COMPLETELY FILL ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND
GYPSUM WALLBOARD AND WITH A MIN 1/4 IN. DIAM BEAD OF CAULK APPLIED
TO PERIMETER OF PIPE OR CONDUIT AT ITS EGRESS FROM THE WALL.
CAULK INSTALLED SYMMETRICALLY ON BOTH SIDES OF WALL ASSEMBLY.
THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON
THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS
INSTALLED, AS SHOWN IN THE FOLLOWING TABLE. THE HOURLY T RATING
OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE OF THE
PIPE OR CONDUIT AND THE HOURLY FIRE RATING OF THE WALL ASSEMBLY
IN WHICH IT IS INSTALLED, AS TABULATED BELOW:
Max pipe or Conduit Diam
In.
+When copper is used, T Rating is 0h.
SECTION A-A
12 3/16 to 3/8
1/4 to 1/2 0 to 1-1/2 1/4 to 1/2 3 to 3/16
3 or 4 1 or 2
1 or 2 3 or 4 1 or 2 0
0+, 1 or 2 3 or 4
Minnesota Mining & Mfg. Co .--Types FB-2000, FB-2000+.
*Bearing the UL Classification Marking
System No. W-L-1001 (Formerly System No. 147)
F Rating--1, 2, 3 and 4 Hr (See Items 2 and 3) T Ratings--0, 1, 2, 3, and 4 Hr (See Items 2 and 3)
L Rating at Ambient--less than 1 CFM/sq ft L Rating At 400 F--less than 1 CFM/sq ft
Annular Space In. F Rating Hr. T Rating Hr.
A
A
1B
1A
1. FLOOR OR WALL ASSEMBLY - LIGHTWEIGHT OR NORMAL WEIGHT (100-150PCF) CONCRETE. EXCEPT AS NOTED IN TABLE UNDER ITEM 4, MIN THICKNESS OF SOLID CONCRETE FLOOR OR WALL ASSEMBLY IS 4-1/2". FLOOR MAY ALSO BE CONSTRUCTED OF A MIN. 6" THICK. UL CLASSIFIED HOLLOW CORE PRECAST CONCRETE UNITS*. WHEN FLOOR IS CONSTRUCTED OF HOLLOW CORE PRECAST CONCRETE UNITS, PACKING MATERIAL (ITEM 3) AND CAULK FILL MATERIAL (ITEM 4) TO BE INSTALLED SYMMETRICALLY ON BOTH SIDES OF FLOOR, FLUSH WITH FLOOR SURFACE. WALL ASSEMBLY MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*.
MAX. DIA. OF OPENING IS IN SOLID LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE. FLOOR IS 32" MAX. DIA. OF
OPENING IN FLOOR CONSTRUCTED OF HOLLOW-CORE PRECAST CONCRETE UNITS IS 7".
SEE CONCRETE BLOCKS (CAT) AND PRECAST CONCRETE UNITS (CT) CATEGORIES IN THE FIRE RESISTANCE
DIRECTORY FOR NAMES OF MANUFACTURERS.
1A. STEEL SLEEVE - (OPTIONAL, NOT SHOWN) - MAX. 15" ID (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL SLEEVE CAST OR GROUTED INTO FLOOR OR WALL ASSEMBLY. SLEEVE MAY EXTEND A MAX. OF 2" ABOVE TOP OF FLOOR OR BEYOND EITHER SURFACE OF WALL. MAX. 16" ID (OR SMALLER) MIN. 0.028 WALL THICKNESS (OR HEAVIER) GALVANIZED STEEL SLEEVE CAST OR GROUTED INTO FLOOR OR WALL ASSEMBLY. SLEEVE MAY
EXTEND A MAX. OF 1/2" BEYOND EITHER SURFACE OF FLOOR OR WALL.
2. THROUGH ENTRANTS - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED EITHER CONCENTRIC ALLY OR ECCENTRIC ALLY WITHIN THE FIRESTOP SYSTEM. MAX. ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND EDGE OF THROUGH OPENING OR SLEEVE IS DEPENDENT ON THE PARAMETERS SHOWN IN ITEM 4.
MIN. ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND EDGE OF THROUGH OPENING IS 0". (POINT CONTACT).
PIPE CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE
FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED
A. STEEL PIPE - NOM. 30" DIA. (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE
B. IRON PIPE - NOM. 30" DIA. (OR SMALLER) CAST OR DUCTILE IRON PIPE
C. CONDUIT - NOM. 6" DIA. (OR SMALLER) RIGID STEEL CONDUIT
D. CONDUIT - NOM. 4" DIA. (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING
E. COPPER TUBING - NOM. 8" DIA. (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBE
F. COPPER PIPE - NOM. 6" DIA. (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE
3. PACKING MATERIAL - POLYETHYLENE BACKER ROD OR NOM. 1" THICKNESS OF TIGHTLY PACKED MINERAL WOOL BATT OR GLASS FIBER INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO
ACCOMMODATE THE REQUIRED THICKNESS OF CAULK FILL MATERIAL (ITEM 4).
4. FILL, VOID OR CAVITY MATERIAL* - CAULK - APPLIED TO FILL THE ANNULAR SPACE FLUSH WITH TOP SURFACE OF FLOOR. IN WALL ASSEMBLIES, REQUIRED CAULK THICKNESS TO BE INSTALLED SYMMETRICALLY ON BOTH SIDES OF WALL, FLUSH WITH WALL SURFACE, AT POINT CONTACT LOCATION BETWEEN PENETRANT AND SLEEVE OR BETWEEN PENETRANT AND CONCRETE, A MIN. 1/4" DIA. BEAD OF CAULK SHALL BE APPLIED AT TOP SURFACE PIPE CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL OF FLOOR AND AT BOTH SURFACES OF WALL. THE HOURLY F RATINGS AND THE MIN. REQUIRED CAULK THICKNESS' ARE
DEPENDENT UPON A NUMBER OF PARAMETERS, AS SHOWN IN THE FOLLOWING TABLE:
A
4A
4 1 min. floor or wall nom. pipe tube or conduit thickness, in. dia.., in.
max. annular space, in. thickness, in.
min. caulk f rating, hr.
21/21-3/81/2-122-1/2 22-1/2 1/2-12 3-1/4 1 24-1/2 1/2-6 1-3/8 1/4 (A) 34-1/2 1/2-12 1-1/4 1/2
4-1/2 1/2-20 2 1 3 4-1/2
1/2-6
2 1 34-1/2 1/2-12 3-1/4 1 44-1/2
1/2-20
1-3/8 1 (B)
(A) min. 2" thickness of mineral wool batt insulation required in annular space.
(B) min. 1" thickness of mineral wool batt insulation required in annular space. on both sides of floor or wall assembly. min 1" thickness of caulk to be installed flush with each surface of floor or wall assembly.
minnesota mining and manufacturing co. - cp 25wb+.
*bearing the ul classification marking
SECTION A-A
System No. C-AJ-1044 (formerly system no. 319)
F Rating - 2, 3 and 4 Hr (see items 2A and 4) T Rating - 0 Hr
L Rating At Ambient - 2 CFM/sq ft L Rating At 400 F - less than 1 CFM/sq ft
PIPE DRAIN TO EXTERIOR AT
APPROXIMATELY 2'-0" ABOVE
GRADE. PROVIDE CONCRETE
SPLASH BLOCK
4" FIRE SERVICE
2"
BACKFLOW PREVENTER RATED
FOR VERTICAL INSTALLATION.
BASIS OF WATTS 4" 757DCDA-OSY
WITH CONTROL VALVES AND
TAMPER SWITCHES.
4" SUPPLY TO WET
SPRINKLER SYSTEM
FINISHED
FLOOR
PRESSURE GAUGE
MAIN DRAIN
(TYP)
RESTRICTION CHECK AND
BYPASS CONNECTION
PRESSURE
GAUGE
FLOW SWITCH (TYP)
ANGLE VALVE
(TYP)
WET ALARM CHECK
VALVE WITH ALARM
PRESSURE SWITCH
4" TO FDC
CHECK VALVE. SEE SHEET
FP112 FOR LOCATION.
GRADE
2" DRAIN
6" x 4" TAG. SPRINKLER
CONTRACTOR TO IDENTIFY
SYSTEM NUMBER (TYP)
CONCRETE THRUST BLOCK.
REFER TO CIVIL DRAWING
C016 FOR DETAILS
2 1/2" x 2 1/2" FLUSH MOUNT
FORWARD FLOW TEST HEADER
CONNECTION WITH CHAINED
CAPS. INSTALL 3'-0" ABOVE
GRADE - VERIFY THREAD WITH
LOCAL FIRE DEPARTMENT.
ESCUTCHEON (TYPICAL)
CONCRETE SPLASH BLOCK
SEAL WALL PENETRATION
WATER TIGHT (TYP)
4" X 2 1/2" x 2 1/2" INLET
O.S.&Y. VALVE WITH
TAMPER SWITCH (TYP)
SEAL FLOOR PENETRATION
4"
NORMALLY CLOSED VALVE
FOR FORWARD FLOW TEST
SHUTOFF GATE VALVE
2" DRAIN TO DOMESTIC
WATER BACKFLOW
PREVENTER. REFER TO
DETAIL 8/P-502.
AUTOMATIC
BALL DRIP
FINISHED GRADE
FINISHED FLOOR
SEAL WALL PENETRATION
WATER TIGHT
EXTERIOR WALL
4"
REFER TO PLANS FOR
CONTINUATION
2 1/2" NIPPLE
4" x 2 1/2" x 2 1/2" FIRE DEPARTMENT
CONNECTION. INSTALL 3' ABOVE GRADE -
VERIFY THREAD WITH LOCAL
FIREDEPARTMENT.
WALL SIGN AS REQUIRED
BY LOCAL AUTHORITY
45 DEG ELBOW WITH ESCUTCHEON.
MATCH FINISH OF FIRE
DEPARTMENT CONNECTION.
PIPE
UNIVERSAL TOP/BOTTOM
BEAM CLAMP EQUAL TO B-
LINE TYPE 19-SP69
ADJUSTABLE CLEVIS HANGER
EQUAL TO B-LINE TYPE 10-SP-69
COUPLING
3/8"∅ MIN. HANGER ROD
NOTES:
1. SIZE HANGER AND CLAMP TO ADEQUATELY SUPPORT LOAD (REFER TO B-
LINE HANGER CATALOG).
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
BI
M
- C on st ru ct
R ep la ce m en t O ut pa tie nt C lin ic
/0
C on st . R ep la ce . O ut pa tie nt
C lin ic
R
.rv t
2/ 9/
0:
:0
AM
FP501
FIRE PROTECTION DETAILS REPLACEMENT OUTPATIENT
CLINIC DESIGN AT COAST
GUARD CAPE COD
JOINT BASE CAPE COD, BARNSTABLE MA
650-318
BUILDING 1
02/10/2023 JFR WRH
100% CONSTRUCTION
DOCUMENTS
N.T.S.
PENDENT SPRINKLER HEAD DETAIL7 N.T.S.
RETURN BEND DETAIL2
N.T.S.
WALL - DRYWALL - PIPE - 1/2/3/4 HR3 N.T.S.
WALL/FLR - CONC - PIPE - 2/3/4 HR1N.T.S.
FIRE SERVICE ENTRANCE DETAIL5
N.T.S.
FIRE DEPARTMENT CONNECTION DETAIL4N.T.S.
PIPE SUPPORT DETAIL6
File details come from the government source that posted it. Updated .