Attachment 15 - Mechanical 1 of 2.pdf
PDF 4 MB Posted
- Solicitation number
- 36C77624R0087
About this file
This document appears to be a set of mechanical drawings and specifications related to the construction of a replacement outpatient clinic facility for the Department of Veterans Affairs.
The key details include:
- The drawings cover HVAC, plumbing, and controls systems for the new clinic building, including floor plans, roof plans, enlarged views of the mechanical room, and various mechanical details and symbols.
- The project is solicitation 36C77624R0087 for the "Construct Replacement Outpatient Clinic at US Coast Guard Air Station" for the Providence VA Medical Center.
- The drawings indicate the new clinic will be a fully sprinklered facility with an air handling unit, boilers, chillers, and other mechanical equipment to serve the clinic spaces.
- The drawings provide specifications for ductwork, piping, and equipment installation, as well as notes on coordination with other trades and code compliance.
View the file
Other files
Show all 46
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
-SPIN-IN TAKE-OFF
-RECTANGLE-TO-ROUND TAKE-OFF
DNUP
-TRANSITION, SQUARE TO ROUND
-CEILING EXHAUST
-CEILING RETURN
-STANDARD BRANCH TAKE-OFF
-RADIUS ELBOW
-TRANSITION, ECCENTRIC
-FLEXIBLE DUCT
-CHANGE OF ELEVATION
-TRANSITION, CONCENTRIC
-SQUARE THROAT ELBOW
W/TURNING VANES
-RECTANGULAR/ROUND BRANCH TAKE-
OFF
OR ROUND/ROUND BRANCH TAKE-OFF
-SQUARE THROAT TEE
-RADIUS TEE
-SUPPLY DIFFUSER OR GRILLE
-RETURN/EXHAUST REGISTER OR GRILLE
(VERTICAL MOUNT, SIDEWALL)
(VERTICAL MOUNT, SIDEWALL)
-CEILING DIFFUSER, ROUND NECK
(CEILING DIFFUSERS ARE 4-WAY THROW UNO)
-CEILING DIFFUSER, RECTANGULAR OR
SQUARE NECK (CEILING DIFFUSERS
ARE 4-WAY THROW UNO)
-AIRFLOW SENSORAFS-X
ECC-X -ENGINEERING CONTROL CENTER
HVAC ABBREVIATIONSHVAC SYMBOL LEGEND
SYMBOL DESCRIPTIONSYMBOL DESCRIPTIONSYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION
-CONDENSATE
-CHILLED WATER RETURN
-CHILLED WATER SUPPLY
PIPING LEGEND
SYMBOL DESCRIPTIONSYMBOL DESCRIPTION
CHWS
CHWR
X
-HOT WATER RETURN
-HOT WATER SUPPLYHWS
HWR
-WATER METER
-FLOW METER
-PRESSURE GAUGE
-ELBOW, TURNED DOWN
-CONNECTION, BOTTOM
-INLINE PUMP
-CAP
-INLINE PUMP
-ELBOW, 90°
-CONNECTION, TOP
-ELBOW, TURNED UP
-TEE, OUTLET DOWN
FM
M
-ELBOW, 45°
-TEE, OUTLET UP
-45° PIPE RISE (R)/DROP (D)
-PIPE ANCHORS
-CONCENTRIC REDUCER
-ECCENTRIC REDUCER
R R
-FLANGES
-FLEXIBLE CONNECTOR
-Y-TPE STRAINER
-MALE HOSE CONNECTION
-PIPE CONNECTION
-CONTROL VALVE
-BUTTERFLY VALVE
-FLOW DIRECTION
-CALIBRATING BALANCING VALVE
-BALL VALVE
-STRAINER
-UNION
-THERMOMETER
-SLOPE DIRECTION (DOWN)
-PSI REG.
-CHECK VALVE
-THREE-WAY CONTROL VALVE
-FLEX CONNECTION (DOUBLE SPHERE FOR
PIPES 6" AND LARGER; SINGLE SPHERE FOR
PIPES 4" AND SMALLER
-RELIEF VALVE
-VALVE ON RISER
-TEST PLUG
-GLOBE VALVE
-PSI REG.
-MANUAL VENT
EQUIP. -P-TRAP
-DUCT SMOKE DETECTOR
-STARTER
-CURRENT SENSING STATUS SWITCH
-DRY CONTACT
CS
A -ALARM
S
-HARD-WIRED INTERLOCKi
-24VAC POWER
-IMMERSION TEMPERATURE
P
-FLOW SWITCH
R -REFRIGERANT SENSOR
T -THERMOSTAT
XFM -TRANSFORMER
-EMERGENCY PUSHBUTTON
-DIFF. PRESSURE SWITCH DIGITAL
TRANSMITTER W/ THERMOWELL
CO -SPACE CARBON DIOXIDE SENSOR2
DPS
-FLOW METER
-SPACE PUSH-BUTTON OVER-RIDE SWITCH
-AIR FLOW SENSOR
-DUCT MOUNTED TEMPERATURE SENSOR
-2-WAY VALVE W / 24VAC OR 120VAC
-SPACE TEMPERATURE SENSOR
-SPACE RH SENSOR
24VAC
24VAC
F
-ACTUATOR AS INDICATED
-ACTUATOR W / 24VAC OR 120VAC
ACTUATOR AS INDICATED
-INDICATES AVERAGING ELEMENT SENSOR
-VARIABLE FREQUENCY DRIVEVFD
-DIFF. PRESSURE
INDICATING TRANSMITTER
-MAGNEHELIC DIFFERENTIAL
-OPPOSED BLADE DAMPER
-PARALLEL BLADE DAMPER
DPIT
-STATIC PRESSURE SENSORSP
PRESSURE GAUGE
-PARTICULATE TRANSMITTERPT
-INDICATES PROBE SENSOR
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
CONTROLS LEGEND
-CALIBRATED BALANCING VALVE
-SOLENOID VALVE (2-POSTION W/ ACTUATOR)
-FLOW SWITCH
PRESSURE SWITCH
-AUTOMATIC AIR VENT
-CURRENT SENSORCS-X
-MANUAL BALANCING DAMPER
-MOTOR OPERATED CONTROL DAMPER
(MOD)
-FLEXIBLE CONNECTION
-ACCESS DOORS, VERTICAL OR
HORIZONTAL
-DOOR GRILLE
-UNDERCUT DOOR
-DUCT ELBOW, RETURN AIR
-DUCT ELBOW, EXHAUST AIR
-DUCT ELBOW, SUPPLY OR OUTSIDE AIR
-NEW DUCTWORK, FIRST DIMENSION IS
SIDE SHOWN
-TEMPERATURE SENSOR
-MOTORIZED CONTROL DAMPER
-HUMIDISTAT/HUMIDITY SENSOR
-THERMOSTAT/TEMPERATURE SENSOR
-STATIC PRESSURE SENSOR
-DUCT SMOKE DETECTOR
-BACKDRAFT DAMPER
-CEILING MOUNTED ACCESS DOOR
T
H
DOWN UP
UC
M
T
SP
BD
M
-HUMIDITY SENSOR (DUCT MOUNTED)H
-CARBON DIOXIDE SENSOR (DUCT MOUNTED)CO2
-CARBON DIOXIDE SENSORCO2
-FIRE DAMPER (WITH ACCESS PANEL)
-SMOKE DAMPER (WITH ACCESS PANEL)
-STATIC PRESSURE SENSOR
-DIFFERENTIAL PRESSURE SENSORDPS-X
-DAMPERD-X
T-X -ROOM THERMOSTAT/TEMPERATURE
SENSOR
FE -FLUE EXHAUST
DDC -DIRECT DIGITAL CONTROLS
PRS -PRESSURE REDUCING STATION
SP -STATIC PRESSURE
-CFM (CUBIC FEET PER MINUTE)
CV -CONSTANT AIR VOLUME
-ROOFTOP AIR HANDLING UNITRTU
RS/L -REFRIGERANT SUCTION & LIQUID LINES
C
-OUTSIDE AIR TEMPERATUREOAT
-VARIABLE AIR VOLUMEVAV
-SUPPLY AIRSA
-ROOFTOP HEAT PUMPRHP
-REHEAT COILRHC
-REVOLUTIONS PER MINUTERPM
-RETURN AIRRA
-POLYVINYL CHLORIDE PIPEPVC
-PSI GAUGEPSIG
-POUNDS PER SQUARE INCHPSI
-PRESSURE REDUCING VALVEPRV
-OUTSIDE AIROA
-NOT TO SCALENTS
-NORMALLY OPENNO
-NORMALLY CLOSEDNC
-LINEAR DIFFUSERLD
-LEAVING WATER TEMPERATURELWT
-LEAVING AIR TEMPERATURELAT
-GALLONS PER MINUTEGPM
-FEET PER MINUTE
-FIRE DAMPER
-FIRE ALARM SYSTEM
-ENTERING WATER TEMPERATURE
-ENTERING AIR TEMPERATURE
-DOWN
-CONDENSING UNIT
-CUBIC FEET PER MINUTE
-COOLING TOWER
-CONDENSATE
-CENTER LINE
-BRITISH THERMAL UNIT
-BRAKE HORSEPOWER
-BOTTOM OF PIPE
-ACCESS PANEL
-ABOVE FINISHED FLOOR
FPM
FD
FAS
EWT
EAT
DN
CU
CFM
CT
CD
BTU
BOP
BHP
AP
AFF
-AIR HANDLING UNITAHU
MBH -THOUSAND BTUs PER HOUR
ESP -EXTERNAL STATIC PRESSURE
KW -KILOWATT
MCA -MINIMUM CIRCUIT AMPS
MOCP -MAXIMUM OVER CURRENT PROTECTION
U/G
TSP -TOTAL STATIC PRESSURE
-VOLTS/PHASEV/PH
VFD -VARIABLE FREQUENCY DRIVE
-UNDERGROUND
FLA -FULL LOAD AMPS
MOD -MOTOR OPERATED CONTROL DAMPER (MOD)
-PACKAGED TERMINAL AIR CONDITIONERPTAC
-ABOVE FINISHED ROOFAFR
-BUTTERFLY VALVEBFV
c
L
VRF -VARIABLE REFRIGERANT FLOW
-EXHAUST AIREA
-CLEAN OUTCO
TS-X -TEMPERATURE SENSOR
SPS-X -STATIC PRESSURE SENSOR
H-X -HUMIDITY SENSOR
-CARBON DIOXIDE SENSORCO2-X
V-X -VALVE (CHILLED WATER/HEATING HOT
WATER)
WFM-X -WATER FLOW METER
1-AHU-1
1-TU-I-I
VIEW NUMBER
DRAWING NUMBER WHERE SHOWN
SECTION LETTER
TYPICAL UNIT NUMBER; AHU NO. 1, LOCATED IN BLDG. 1
BUILDING NO. WHERE EQUIPMENT IS LOCATED.
AHU NUMBER
EQUIPMENT ABBREVIATION.
ITEM NUMBER (TERMINAL UNIT NO. 1)
ITEM (TERMINAL UNIT SHOWN)
SERVED BY AIR HANDLER UNIT NO. 1
BUILDING NO. WHERE EQUIPMENT IS LOCATED
MH101
MH101
A
SHEET NUMBER
A 100
DEVICE MARK
DEVICE FLOW RATE (CFM)
12X10 SA
DUCT DIMENSION (INCHES)
TYPICAL AIR DISTRIBUTION DEVICE TAG
TYPICAL DUCTWORK TAG
SYSTEM TYPE (SA = SUPPLY AIR , RA = RETURN
AIR, OA = OUTSIDE AIR, EA = EXHAUST AIR,
SS EA = STAINLESS-STEEL EXHAUST)
DRAWING SYMBOLS
REVISION REFERENCE1
SHEET NOTE CALLOUT1
-EQUIPMENT WITH CLEARANCE
CLEARANCE
EQUIPMENT
1. CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH MANUFACTURER'S CERTIFIED DRAWINGS.
TRANSITIONS TO ALL EQUIPMENT SHALL BE VERIFIED AND PROVIDED FOR EQUIPMENT FURNISHED.
2. DIMENSIONS SHALL BE FIELD-VERIFIED AND COORDINATED PRIOR TO PROCUREMENT OR
FABRICATION. COORDINATE THE WORK WITH OTHER TRADES INVOLVED. FIELD MODIFICATIONS SUCH
AS OFFSETS IN PIPING OR DUCTWORK (INCLUDING DIVIDED DUCTWORK) NEEDED DUE TO
OBSTRUCTIONS OR INTERFERENCES SHALL BE PROVIDED AT NO ADDITIONAL COST.
3. DUCT CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE SMACNA HVAC
DUCT CONSTRUCTION STANDARD.
4. INSTALL ALL FIRE DAMPERS, SMOKE DAMPERS AND COMBINATION FIRE/SMOKE DAMPERS IN
ACCORDANCE WITH MANUFACTURE'S INSTALLATION DIRECTIONS. PROVIDE ACCESS DOORS TO
ALLOW COMPLETE INSPECTION AND MAINTENANCE OF ALL DEVICES.
5. PROVIDE 1.5R ELBOWS IN DUCTWORK AS INDICATED. IF 1.5R ELBOWS DO NOT FIT, PROVIDE 1.0R ELBOWS. IF 1.0R ELBOWS DO NOT FIT, PROVIDE 90 DEGREE RECTANGULAR DUCT ELBOWS WITH
TURNING VANES.
6. DUCT SIZES AND ALL OPENINGS THROUGH BUILDING CONSTRUCTION SHALL SUIT EQUIPMENT
FURNISHED.
7. COORDINATE DIFFUSER, GRILLE AND REGISTER LOCATIONS WITH ARCHITECTURAL REFLECTED
CEILING PLANS AND EQUIPMENT OF ALL TRADES.
8. LOCATE THERMOSTATS, TEMPERATURE SENSORS, HUMIDISTATS, AND HUMIDITY SENSORS AT 48"
ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. COORDINATE LOCATIONS WITH OTHER
EQUIPMENT, FURNITURE, AND DOOR SWINGS.
9. ALL EQUIPMENT, DUCTWORK, ETC., SHALL BE SUPPORTED AS DETAILED AND/OR SPECIFIED. PROVIDE
ADDITIONAL SUPPORTS AS REQUIRED TO PROVIDE A VIBRATION-FREE, RIGID INSTALLATION.
10. ALL DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS.
11. DAMPERS AND INSIDES OF DUCTS VISIBLE THROUGH GRILLES, REGISTERS AND DIFFUSERS SHALL BE
PAINTED FLAT BLACK.
12. REFER TO TYPICAL DETAILS FOR PIPING AND INSTALLATION OF EQUIPMENT.
13. TRAPPED CONDENSATE DRAINS FROM ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED FOR
PROPER DRAINAGE TO SUIT EQUIPMENT FURNISHED.
14. ACCESS PANELS IN DUCTWORK AND CEILINGS SHALL BE PROVIDED WHERE REQUIRED FOR
OPERATION, BALANCING OR MAINTENANCE OF ALL MECHANICAL EQUIPMENT.
15. ALL DUCTWORK AND PIPING IS SHOWN SCHEMATICALLY. PROVIDE ALL TRANSITIONS, TURNING VANES, ELBOWS, FITTINGS, ETC., TO ALLOW SMOOTH FLOWS. ALL SPLIT DUCT FITTINGS SHALL TRANSITION TO
FULL SIZE OF THE SUM OF BOTH BRANCHES, UPSTREAM OF SPLIT.
16. COORDINATE SIZE REQUIREMENTS OF ALL CONCRETE HOUSEKEEPING PADS UNDER ALL FLOOR-
MOUNTED EQUIPMENT. SEE STRUCTURAL DRAWINGS FOR PAD DETAILS AND SPECIFICATIONS.
17. VERIFY FINISH WITH ARCHITECT PRIOR TO PURCHASING GRILLES, REGISTERS, DIFFUSERS, LOUVERS
AND OTHER AIR DISTRIBUTION DEVICES.
18. PROVIDE FLEXIBLE DUCT CONNECTIONS ON ALL DUCTWORK CONNECTING TO FANS, AIR HANDLING
UNITS, AND FAN COIL UNITS.
19. PROVIDE TRANSITIONS AT DIFFUSER NECKS AS REQUIRED TO MATCH SIZES OF FLEX DUCTS TO BE
CONNECTED.
20. SLEEVE AND SEAL ALL PIPING PENETRATIONS THROUGH BUILDING PARTITIONS.
21. MAINTAIN CLEARANCE OF A MINIMUM OF 6" BETWEEN DUCTWORK, PIPING, EQUIPMENT, ETC., AND ALL
FIRE RATED AND FIRE/SMOKE RATED PARTITIONS, TO ALLOW FOR INSPECTIONS OF RATED WALLS.
22. LOCATE ALL OUTSIDE AIR INTAKES A MINIMUM OF 25'-0" CLEAR FROM ALL PLUMBING VENTS AND
EXHAUST AIR DISCHARGE LOCATIONS. LOWEST POINT OF EACH OUTSIDE AIR INTAKE ON ROOF SHALL
BE A MINIMUM OF 24" ABOVE ROOF.
23. DUCT RUNOUTS TO DIFFUSERS SHALL MATCH THE SIZE OF THE DIFFUSER NECK.
24. UNLESS OTHERWISE NOTED, ALL EQUIPMENT AND VALVE DRAINS SHALL BE INDEPENDENTLY PIPED
FULL SIZE TO THE NEAREST PLUMBING DRAIN.
GENERAL NOTES
-SQUARE FOOTSF
WB -WET BULB
-DRY BULBDB
WFS-X -WATER FLOW SWITCH
-AIRFLOW SENSOR/STATIONF
SD
FD
24x12
P -BUILDING PRESSURE SENSOR
TT-X -TEMPERATURE TRANSMITTER
APPLICABLE CODES
1. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), INCLUDING (BUT NOT LIMITED TO):
A. NATIONAL ELECTRICAL CODE (NEC) 2020 EDITION
B. NATIONAL FIRE ALARM CODE (NFPA 72) 2022 EDITION
C. STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATING SYSTEMS (NFPA 90A)
2021 EDITION
D. HEALTH CARE FACILITIES CODE (NFPA 99) 2021 EDITION
E. LIFE SAFETY CODE (NFPA 101) 2021 EDITION
2. VA HVAC DESIGN MANUAL 2021 EDITION
3. SHEET METAL AND AIR CONDITIONING CONTRACTORS' NATIONAL ASSOCIATION (SMACNA)
4. OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA)
5. AMERICANS WITH DISABILITIES ACT (ADA)
6. AMERICAN SOCIETY OF TESTING AND MATERIALS (ASTM)
7. AIR MOVEMENT AND CONTROL ASSOCIATION (AMCA)
UNO -UNLESS NOTED OTHERWISE
-COOLING COILCC
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
BI
M
- C on st ru ct
R ep la ce m en t O ut pa tie nt C lin ic
/0
C on st . R ep la ce . O ut pa tie nt
C lin ic
R
.rv t
2/ 9/
0:
:0
AM
M-001
MECHANICAL LEGENDS AND
SYMBOLS
REPLACEMENT OUTPATIENT
CLINIC DESIGN AT COAST
GUARD CAPE COD
JOINT BASE CAPE COD, BARNSTABLE MA
650-318
BUILDING 1
02/10/2023 JFR JJA
100% CONSTRUCTION
DOCUMENTS
SHEET LIST
Sheet Number Sheet Name
M-001 MECHANICAL LEGENDS AND SYMBOLS
MH101 PARTIAL FIRST FLOOR PLAN - MECHANICAL HVAC - WEST
MH102 PARTIAL FIRST FLOOR PLAN - MECHANICAL HVAC - EAST
MH103 FIRST FLOOR PLAN - MECHANCAL PRESSURIZATION
MH104 ROOF PLAN - MECHANICAL
MP101 PARTIAL FIRST FLOOR PLAN - MECHANICAL PIPING - WEST
MP102 PARTIAL FIRST FLOOR PLAN - MECHANICAL PIPING - EAST
M-401 MECHANICAL ENLARGED PLANS
M-402 MECHANICAL ENLARGED PLANS
M-501 MECHANICAL DETAILS
M-502 MECHANICAL DETAILS
M-503 MECHANICAL DETAILS
M-504 MECHANICAL DETAILS
M-505 MECHANICAL DETAILS
M-701 MECHANICAL CONTROLS
M-702 MECHANICAL CONTROLS
M-703 MECHANICAL CONTROLS
M-801 MECHANICAL SCHEDULES
Revisions Date
H G F E D
I
VESTIBULE
WAITING
CORRIDOR
WAITING
RECEPTION
RECEPTION
WORKROOM
NURSE MANAGER
TOILET PUBLIC
TOILET PUBLIC
110VOLUNTEER
CORRIDOR
SOCIAL WORKER
CLOSET
ELEC
SPECIMEN
COLLECTION
TOILET WMN'S
TOILET PATIENT
EXAM RM WOMEN'S
HEALTH
ULTRASOUND
TREATMENT
EXERCISE AREA
EXAM / PT/OT
EXAM / TRIAGE
PROCEDURE
ROOM, GENERAL
TOILET PROC.
TOILET STAFF
EXAM /
TELE-HEALTH
EXAM
CLOSET
CORRIDOR
MED ROOM
TOILET STAFF
TEAM WORK AREA
EXAM/TRIAGE
EXAM / MENTAL
HEALTH
EXAM /
TELE-HEALTH
EXAM / AUDIOLOGY
EXAM / EYE TEST
EXAM
MULTI-PURPOSE
ROOM
MULTI-PURPOSE
ROOM
GROUP THERAPY
ROOM, MENTAL
HEALTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
TU-111011
TU-111002
TU-111017
TU-111014TU-111020
TU-111021
TU-111019
TU-111025
TU-111005
TU-111004
TU-111008
TU-111027
TU-111028
TU-111029
TU-111026
TU-111031
A 250
A 150
B 150
B 400
A 275A 275A 250
B 400B 475B 175
A 250
C 125
A 50
A 50
C 125
A 250
B 250
B 275
A 375A 400
A 375
A 225
A 100
B 125
A 125
A 100
B 500
A 300
B 300
A 50
C 125
C 125
A 50
A 125
B 125
B 75
B 875
A 50
C 125 A 300
A 300 A 300
A 300
A 300
A 325
A 150A 175
A 50
C 125
B 175B 150
A 150A 150
B 150
A 175
B 175
B 375
A 125
A 125
A 225
B 425
A 200
A 200
B 400
A 200
A 275
B 275
B 250
A 250 A 250
B 250 B 250
A 250 A 250
B 250
A 250
B 250
A 250
B 250
A 250
B 250
B 150
A 200
A 150
B 200
B 150
B 325
A 400
A 175
B 175
C 125
C 125
A 50
A 50
E 100
E 150
E 150
E 150
E 100
E 100
E 100 x1
2 S A 10 x1 0 S
A
8x10 SA A 225
A 75
6x8 SA
24x18 EA
A 325
8x10 SA 10x10 SA 16x14 SA 18x16 SA
22x16 SA x1
0 S A
B 150
B 275
28x18 RA22x18 RA 36x18 RA
A 250
A 300
A 150
A 50
A 50
B 200
B 200
6x10 SA
10x12 SA x1
6 R A x1
0 S A
TU-111022
TU-111012
UP
x1
2 S A
TU-111003
8x8 EA x1
2 R A x1
4 S A
12x8 SA
TU-111013
TU-111030
x1
2 R A
TU-111006
8x12 SA x1
2 R A x1
2 R A x1
2 R A
24x14 RA
TU-111023
x1
6 S A
B 900
38x14 RA
30x20 SA 48x16 RA
SPS-3
M
AT
C H
LI
N
E -C
O N
TI
N
U
ED
O N
D W
G
/M H
8x 8 E
A
8x 8 E
A
24x18 EA
22x18 EA
C 575
C 550
C 575
C 575
H.2 H.1 F.7 F.5 F.3 E.5 D.9 D.7 D.6 D.5 D.3 C.6 C.5 C.3
5.5
3.7
3.6
3.3
3.1
2.7
2.5
2.4
1.9
1.5
1.3
TU-111024
E 150
E 175
E 150
UP
UP
E 150 E 150
8ø S
A
26x18 SA
TOILET PATIENT
123434
TU-111007
UP
x1
4 S A
M-402 x1
2 S A
C 375
12x12 RA 18x14 RA
14ø RA
UP
UP
UP
UP
18x16 EA
8x
S A x1
2 S A
UP
14x14 SA
12x14 SA
22x18 EA
A 125
UH-111001
E 150E 150
28x18 EA
28x14 SA
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
BI
M
- C on st ru ct
R ep la ce m en t O ut pa tie nt C lin ic
/0
C on st . R ep la ce . O ut pa tie nt
C lin ic
R
.rv t
2/ 9/
0:
:4
AM
MH101
PARTIAL FIRST FLOOR PLAN -
MECHANICAL HVAC - WEST
REPLACEMENT OUTPATIENT
CLINIC DESIGN AT COAST
GUARD CAPE COD
JOINT BASE CAPE COD, BARNSTABLE MA
650-318
BUILDING 1
02/10/2023 JFR JJA
100% CONSTRUCTION
DOCUMENTS
CODED NOTES:
18"X14" SUPPLY AIR DUCTWORK THROUGH STRUCTURAL OPENING AT COLUMN LINE 2. REFER TO
STRUCTURAL DRAWINGS.
22"X12" RETURN AIR DUCTWORK THROUGH STRUCTURAL OPENING AT COLUMN LINE 2. REFER TO
STRUCTURAL DRAWINGS.
10" ROUND SUPPLY AIR DUCTWORK THROUGH STRUCTURAL OPENING AT COLUMN LINE 2. REFER TO
STRUCTURAL DRAWINGS.
18"X12" RETURN AIR DUCTWORK THROUGH STRUCTURAL OPENING AT COLUMN LINE 2. REFER TO
STRUCTURAL DRAWINGS.
AVOID ROUTING DUCTWORK THROUGH COLLAPSIBLE WALL ASSEMBLY ON HATCHED AREA.
DRAWING NOTES:
1. DUCTWORK DIRECTLY DOWNSTREAM OF TERMINAL UNITS SHALL BE SAME DIMENSIONS AS
TERMINAL UNIT OUTLET UNLESS NOTED OTHERWISE.
2. ALL VAV CONTROL PANELS SHALL HAVE SUFFICIENT CLEARANCE IN FRONT OF THE PANEL FOR
MAINTENANCE. OFFSET DUCTWORK ELEVATION AS NECESSARY.
3. ROUND DUCTWORK 8"Ø OR LESS ALONG COLUMN LINE 2 SHALL BE INSTALLED BETWEEN
STRUCTURUAL BEAMS. REFER TO CODED NOTES THIS SHEET FOR DUCTWORK LARGER THAN 8"Ø
PASSING THROUGH COORDINATED STRUCTURAL OPENINGS.
4. DUCTWORK ROUTED IN FLAT ROOF AREA SHALL BE INSTALLED WITHIN ROOF TRUSSES.
0 4' 8' 12' 16'
3/16" = 1'-0"
N
3/16" = 1'-0"MH101
1 PARTIAL FIRST FLOOR PLAN - MECHANICAL - WEST
C B A
OFFICE
UTILITY SOILED
ELECTRICAL ROOM
MECHANICAL
JANITOR CLOSET
WORKSTATIONS,
MENTAL HEALTH
STAFF LOUNGE &
LOCKERS
STORAGE MEDICAL
& GENERAL
COMMUNICATIONS
CH-111001
TU-111015
TU-111016
A 300
A 175
B 100
C 375
B 250
A 125 A 125
C 100
A 50B 50
A 50 C 125
A 200
B 125
B 125
A 125A 125
A 125
FCSS-111003
FCSS-111002
FCSS-111001
HP-111001
HP-111002
HP-111003
UTILITY CLEAN
x1
8 R A
OFFICE
A 125
TU-111018
TU-111010
38x18 RA
8x12 SA
3 M-401
30x14 EA
10x8 EA
M
AT
C H
LI
N
E -C
O N
TI
N
U
ED
O N
D W
G
/M H
B.7 A.4
5.5
3.7 3.6
3.3
3.1
2.7
2.5
2.4
1.9
1.5
1.3
24x18 EA x1
6 S A
48x16 RA
10x12 SA x1
6 S A
58x20 SA x1
8 E A
UP
TU-111001
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
BI
M
- C on st ru ct
R ep la ce m en t O ut pa tie nt C lin ic
/0
C on st . R ep la ce . O ut pa tie nt
C lin ic
R
.rv t
2/ 9/
0:
:5
AM
MH102
PARTIAL FIRST FLOOR PLAN -
MECHANICAL HVAC - EAST
REPLACEMENT OUTPATIENT
CLINIC DESIGN AT COAST
GUARD CAPE COD
JOINT BASE CAPE COD, BARNSTABLE MA
650-318
BUILDING 1
02/10/2023 JFR JJA
100% CONSTRUCTION
DOCUMENTS
Florida
CODED NOTES:
4" CONCRETE PAD TO EXTEND A MINIMUM OF 6" BEYOND PERIMETER OF EQUIPMENT.
24"X20" EA DUCT UP TO EF-121002. TRANSITION CONNECTION TO EXHAUST FAN AS REQUIRED. SEE
SHEET MH102 FOR CONTINUATION.
8"X8" EA DUCT UP TO 1-EF-3. SEE SHEET MH102 FOR CONTINUATION.
ROUTE MAIN SA & RA DUCTWORK MINIMUM 6" ABOVE CABLE TRAY. REFER TO ELECTRICAL
DRAWINGS FOR CABLE TRAY LOCATION.
24"X18" EXHAUST AIR DUCTWORK THROUGH STRUCTURAL OPENING AT COLUMN LINE 2. REFER TO
STRUCTURAL DRAWINGS.
DRAWING NOTES:
1. DUCTWORK DIRECTLY DOWNSTREAM OF TERMINAL UNITS SHALL BE SAME DIMENSIONS AS
TERMINAL UNIT OUTLET UNLESS NOTED OTHERWISE.
2. ALL VAV CONTROL PANELS SHALL HAVE SUFFICIENT CLEARANCE IN FRONT OF THE PANEL FOR
MAINTENANCE. OFFSET DUCTWORK ELEVATION AS NECESSARY.
3/16" = 1'-0"MH102
1 PARTIAL FIRST FLOOR PLAN - MECHANICAL - EAST 0 4' 8' 12' 16'
3/16" = 1'-0"
N
H G F E D C B A
I
VESTIBULE
WAITING
CORRIDOR
WAITING
RECEPTION
RECEPTION
WORKROOM
NURSE MANAGER
TOILET PUBLIC
TOILET PUBLIC
VOLUNTEER
CORRIDOR
SOCIAL WORKER
CLOSET
ELEC
SPECIMEN
COLLECTION
TOILET WMN'S
TOILET PATIENT
EXAM RM WOMEN'S
HEALTH
ULTRASOUND
137 TREATMENT
EXERCISE AREA
EXAM / PT/OT
EXAM / TRIAGE
PROCEDURE
ROOM, GENERAL
TOILET PROC.
TOILET STAFF
EXAM /
TELE-HEALTH
EXAM
CLOSET
CORRIDOR
MED ROOM
TOILET STAFF
TEAM WORK AREA
EXAM/TRIAGE
EXAM / MENTAL
HEALTH
EXAM /
TELE-HEALTH
EXAM / AUDIOLOGY
EXAM / EYE TEST
EXAM
114MULTI-PURPOSE
ROOM
MULTI-PURPOSE
ROOM
GROUP THERAPY
ROOM, MENTAL
HEALTH
115 CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
OFFICE
CORRIDOR
UTILITY SOILED
ELECTRICAL ROOM
MECHANICAL
JANITOR CLOSET
WORKSTATIONS,
MENTAL HEALTH
STAFF LOUNGE &
LOCKERS
STORAGE MEDICAL
& GENERAL
COMMUNICATIONS
UTILITY CLEAN
OFFICE
C
FM
75 CFM
C
FM
C
FM
C
FM
C
FM
75 CFM
75 CFM
75 CFM
100 CFM
50 CFM
50 CFM
H.2H.1 F.7 F.5 F.3 E.5 D.9 D.7D.6D.5 D.3 C.6C.5 C.3 B.7 A.4
5.5
3.73.6
3.3
3.1
2.7
2.5 2.4
1.9
1.5
1.3
0 C
FM
75 CFM
C
FM
C
FM
75 CFM
75 CFM
TOILET PATIENT
75 CFM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
BI
M
- C on st ru ct
R ep la ce m en t O ut pa tie nt C lin ic
/0
C on st . R ep la ce . O ut pa tie nt
C lin ic
R
.rv t
2/ 9/
0:
:5
AM
MH103
FIRST FLOOR PLAN - MECHANCAL
PRESSURIZATION
REPLACEMENT OUTPATIENT
CLINIC DESIGN AT COAST
GUARD CAPE COD
JOINT BASE CAPE COD, BARNSTABLE MA
650-318
BUILDING 1
02/10/2023 JFR JJA
100% CONSTRUCTION
DOCUMENTS
ROOM DATA SHEET SCHEDULE
ROOM
NUMBER
ROOM
NAME
ROOM
FUNCTION
ACTUAL
ACH CFM SA CFM RA CFM EA
PRESS
URE
(+,-,o)
100 CORRIDOR CORRIDOR 4 600 0 525 +
103 VESTIBULE VESTIBULE 0 775 550 0 +
104 WATING PACT 1 WAITING ROOM 6 400 0 400 o 105 WATING PACT 1 WAITING ROOM 6 1225 0 1225 o 106 RECEPTION OFFICE 4 400 400 0 o 107 RECEPTION WORKROOM OFFICE 4 100 100 0 o 108 NURSE MANAGER OFFICE 4 75 75 0 o 109 VOLUNTEER OFFICE 4 300 300 0 o
110 TOILET PUBLIC TOILETS PUBLIC 10 50 0 125 -
111 TOILET PUBLIC TOILETS PUBLIC 10 50 0 125 -
112 MULTI-PURPOSE ROOM MULTIPURPOSE ROOM 4 375 375 0 o 113 MULTI-PURPOSE ROOM MULTIPURPOSE ROOM 4 825 825 0 o 114 EXAM / TELEHEALTH EXAM ROOM 6 150 150 0 o 115 GROUP THERAPY ROOM / MENTAL HEALTH GROUP THERAPY ROOM 6 275 275 0 o 116 CONSULT RM MENTAL HEALTH OFFICE 4 250 250 0 o 117 CONSULT RM MENTAL HEALTH OFFICE 4 250 250 0 o 118 CONSULT RM MENTAL HEALTH OFFICE 4 250 250 0 o 119 CONSULT RM MENTAL HEALTH OFFICE 4 250 250 0 o 120 CONSULT RM MENTAL HEALTH OFFICE 4 250 250 0 o 121 CONSULT RM MENTAL HEALTH OFFICE 4 250 250 0 o 122 CONSULT RM MENTAL HEALTH OFFICE 4 250 250 0 o 123 EXAM / EYE TEST EXAM ROOM 6 175 175 0 o 124 EXAM / AUDIOLOGY EXAM ROOM 6 150 150 0 o
125 TOILET PATIENT TOILETS PUBLIC 10 50 0 125 -
126 EXAM / TELE-HEALTH EXAM ROOM 6 150 150 0 o 127 EXAM / MENTAL HEALTH EXAM ROOM 6 150 150 0 o 128 EXAM / TRIAGE EXAM ROOM 6 175 175 0 o 129 SOCIAL WORKER OFFICE 4 75 75 0 o
130 CLOSET STORAGE 4 50 0 0 +
133 SPECIMEN COLLECTION BLOOD DRAW ROOM 6 250 250 0 o
134 TOILET PATIENT TOILETS PUBLIC 10 50 0 125 -
135 EXAM RM WOMEN'S HEALTH EXAM ROOM 6 250 175 0 -
136 TOILET WMN'S TOILETS PUBLIC 10 50 0 125 -
137 ULTRASOUND ULTRASOUND 8 475 475 0 o 138 TREATMENT EXERCISE AREA TREATMENT ROOM 6 800 800 0 o 139 EXAM / PT/OT EXAM ROOM 6 150 150 0 o 140 EXAM EXAM ROOM 6 200 200 0 o 141 EXAM / TELE-HEALTH EXAM ROOM 6 150 150 0 o
142 TOILET PROC. TOILETS PUBLIC 10 50 0 125 -
143 PROCEDURE ROOM, GENERAL PROCEDURE ROOM 15 400 325 0 +
144 EXAM / TRIAGE EXAM ROOM 6 175 175 0 o
145 MED ROOM MEDICATION ROOM 4 75 75 0 +
146 TOILET STAFF TOILETS PUBLIC 10 50 0 125 -
147 TEAM WORK AREA OFFICE 4 1225 1225 0 o
148 STAFF TOILET TOILETS PUBLIC 10 50 0 125 -
151 CLOSET STORAGE 4 50 0 0 +
152 COMMUNICATIONS ELECTRICAL ROOM 0 1476 1476 0 o
153 STORAGE MEDICAL AND GENERAL STORAGE 4 175 100 0 +
154 STAFF LOUNGE & LOCKERS LOUNGE 4 300 375 0 -
155 WORKSTRATIONS MENTAL HEALTH OFFICE 4 250 250 0 o
156 JANITOR CLOSET HOUSEKEEPING AID CLOSET 10 0 0 100 -
157 UTILITY CLEAN CLEAN UTILITY 4 50 50 0 o
158 UTILITY SOILED SOILED UTILITY 10 50 0 125 -
159 OFFICE OFFICE 4 125 125 0 o 160 OFFICE OFFICE 4 125 125 0 o 161 ELECTRICAL ROOM ELECTRICAL ROOM 0 580 580 0 o 162 MECHANICAL ROOM AIR HANDLING EQUIPMENT ROOM 6 1325 1250 0 o
163 CORRIDOR CORRIDOR 4 875 400 375 +
164 CORRIDOR CORRIDOR 4 1050 625 0 +
0 4' 8' 16' 24'
1/8" = 1'-0"
N
1/8" = 1'-0"MH103
1 FIRST FLOOR PLAN - MECHANICAL PRESSURIZATION
H G F E D C B A
I
RF-121001
EF-121002 EF-121001
H.2H.1 F.7 F.5 F.3 E.5 D.9 D.7D.6D.5 D.3 C.6C.5 C.3 B.7 A.4
5.5
3.73.6
3.3
3.1
2.7
2.5 2.4
1.9
1.5
1.3
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
BI
M
- C on st ru ct
R ep la ce m en t O ut pa tie nt C lin ic
/0
C on st . R ep la ce . O ut pa tie nt
C lin ic
R
.rv t
2/ 9/
0:
:0
AM
MH104
ROOF PLAN - MECHANICAL REPLACEMENT OUTPATIENT
CLINIC DESIGN AT COAST
GUARD CAPE COD
JOINT BASE CAPE COD, BARNSTABLE MA
650-318
BUILDING 1
02/10/2023 JFR JJA
100% CONSTRUCTION
DOCUMENTS
0 4' 8' 16' 24'
1/8" = 1'-0"
N
CODED NOTES:
BOILER FLUE VENT. REFER TO DETAIL 7/M-504 FOR MORE INFORMATION.
STEAM HUMIDIFIER FLUE VENT. REFER TO DETAIL 9/M-503 FOR MORE INFORMATION.
OUTSIDE AIR INTAKE LOUVER PENTHOUSE. BASIS OF DESIGN: AMCA 540 AND 550 LISTED GREENHECK ESD-635PD-70X70. PROVIDE BIRD SCREEN AND DUCTED OPTIONS. PROVIDE 12" ROOF CURB TO MOUNT 12" LOUVER FACTORY CURB CAP. INTAKE SHALL BE MINIMUM 24" ABOVE FINISHED ROOF.
EXHAUST DISCHARGE AND PLUMBING VENTS SHALL BE LOCATED A MINIMUM OF 25 FEET FROM
OUTDOOR AIR INTAKE.
FAN SHALL BE SECURED WITH HIGH WIND RATING GUY WIRE SUPPORTS. REFER TO STRUCTURAL
FOR MORE INFORMATION.
DRAWING NOTES:
1. ROOF ANCHOR POINTS SHALL BE PROVIDED FOR ALL ROOFTOP EQUIPMENT WITHIN 10'-0" FROM
ROOF. REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR DETAILS.
2. AIRSIDE ECONOMIZER RELIEF AIR STREAM OUTLET MAY BE LOCATED 10 FEET MINIMUM FROM AHU AIR INTAKES SO LONG AS THEY ARE ORIENTED IN A WAY THAT DOES NOT INHIBIT THE ECONOMIZER
OPERATION.
1/8" = 1'-0"MH104
1 ROOF PLAN - MECHANICAL
H G F E D
I
VESTIBULE
WAITING
CORRIDOR
WAITING
RECEPTION
RECEPTION
WORKROOM
NURSE MANAGER
TOILET PUBLIC
TOILET PUBLIC
VOLUNTEER
CORRIDOR
SOCIAL WORKER
CLOSET
ELEC
SPECIMEN
COLLECTION
TOILET WMN'S
TOILET PATIENT
EXAM RM WOMEN'S
HEALTH
ULTRASOUND
137 TREATMENT
EXERCISE AREA
EXAM / PT/OT
EXAM / TRIAGE
PROCEDURE
ROOM, GENERAL
TOILET PROC.
TOILET STAFF
EXAM /
TELE-HEALTH
EXAM
CLOSET
CORRIDOR
MED ROOM
TOILET STAFF
TEAM WORK AREA
EXAM/TRIAGE
EXAM / MENTAL
HEALTH
EXAM /
TELE-HEALTH
EXAM / AUDIOLOGY
EXAM / EYE TEST
EXAM
MULTI-PURPOSE
ROOM
MULTI-PURPOSE
ROOM
GROUP THERAPY
ROOM, MENTAL
HEALTH
115 CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
TU-111011
TU-111002
TU-111017
TU-111014
TU-111020
TU-111021
TU-111019TU-111025
TU-111005
TU-111004
TU-111008
TU-111027
TU-111028
TU-111029
TU-111026
TU-111031
TU-111022
T T T
T
T
TT
T T
T
T
T
T
T T
T
T T
T
T
T
T
T
T
T
T
TU-111003
TU-111012
M
AT
C H
LI
N
E -C
O N
TI
N
U
ED
O N
D W
G
/M P1
H.2H.1 F.7 F.5 F.3 E.5 D.9 D.7 D.6D.5 D.3 C.6C.5 C.3
5.5
3.7 3.6
3.3
3.1
2.7
2.5
2.4
1.9
1.5
1.3
TOILET PATIENT
EXAM / AUDIOLOGY
TU-111024
TU-111023
TU-111013
TU-111030
TU-111006
3/4" HWR
3/4" HWS
TU-111007
1" HWS
1" HWR
1 1/2" HWS
1 1/2" HWR
3/4" HWR
3/4" HWS
3/4" HWR
3/4" HWS
3/4" HWR
3/4" HWS
TU-111018
CO2
CO2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
BI
M
- C on st ru ct
R ep la ce m en t O ut pa tie nt C lin ic
/0
C on st . R ep la ce . O ut pa tie nt
C lin ic
R
.rv t
5/ 4/
1:
:4
AM
MP101
PARTIAL FIRST FLOOR PLAN -
MECHANICAL PIPING - WEST
REPLACEMENT OUTPATIENT
CLINIC DESIGN AT COAST
GUARD CAPE COD
JOINT BASE CAPE COD, BARNSTABLE MA
650-318
BUILDING 1
02/10/2023 JFR JJA
100% CONSTRUCTION
DOCUMENTS
CODED NOTES:
PROVIDE 3 WAY CONTROL VALVE.1
0 4' 8' 12' 16'
3/16" = 1'-0"
N
3/16" = 1'-0"MP101
1 PARTAL FIRST FLOOR PLAN - PIPING - WEST
DRAWING NOTES:
1. REFER TO ELECTRICAL DRAWINGS FOR THERMOSTAT ELEVATION.
C B A
OFFICE
UTILITY SOILED
ELECTRICAL ROOM
MECHANICAL
JANITOR CLOSET
WORKSTATIONS,
MENTAL HEALTH
STAFF LOUNGE &
LOCKERS
STORAGE MEDICAL
& GENERAL
COMMUNICATIONS
CH-111001
TU-111015
TU-111016
FCSS-111003
FCSS-111002
FCSS-111001
HP-111001
HP-111002
HP-111003
REFRIG. PIPING
REFRIG. PIPING
UTILITY CLEAN
TU-111010
TU-111018
OFFICE
T
T
T
T
T
T
M-401
M
AT
C H
LI
N
E -C
O N
TI
N
U
ED
O N
D W
G
/M P1
B.7 A.4
5.5
3.7 3.6
3.3
3.1
2.7
2.5
2.4
1.9
1.5
1.3
2" HWS
2" HWR
3/4" HWS
3/4" HWR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
BI
M
- C on st ru ct
R ep la ce m en t O ut pa tie nt C lin ic
/0
C on st . R ep la ce . O ut pa tie nt
C lin ic
R
.rv t
2/ 9/
0:
:1
AM
MP102
PARTIAL FIRST FLOOR PLAN -
MECHANICAL PIPING - EAST
REPLACEMENT OUTPATIENT
CLINIC DESIGN AT COAST
GUARD CAPE COD
JOINT BASE CAPE COD, BARNSTABLE MA
650-318
BUILDING 1
02/10/2023 JFR JJA
100% CONSTRUCTION
DOCUMENTS
CODED NOTES:
4" CONCRETE PAD TO EXTEND A MINIMUM OF 6" BEYOND PERIMETER OF EQUIPMENT.
HEAT TRACING ON EXPOSED CHILLED WATER PIPING. INCREASE INTERIOR INSULATION BY 1" OVER THE RECOMMENDED THICKNESS PER VA HVAC DESIGN MANUAL 4.2.5.2(b).
PROVIDE 3 WAY CONTYROL VALVE.
ROUTE REFRIGERANT PIPING INSIDE WALL CAVITY.
2" HWS&R PIPING ROUTED FROM MECHANICAL ROOM. REFER TO SHEET M-401 FOR CONTINUATION.
REFRIGERANT PIPING ROUTED TO MECHANICAL ROOM. REFER TO SHEET M-401 FOR CONTINUATION.
DRAWING NOTES:
1. REFRIGERANT PIPING SHOWN AS SCHEMATIC. REFRIGERANT PIPING SHALL BE INSTALLED PER
MANUFACTURER'S INSTALLATION INSTRUCTIONS.
2. REFER TO ELECTRICAL DRAWINGS FOR THERMOSTAT ELEVATION.
0 4' 8' 12' 16'
3/16" = 1'-0"
N
3/16" = 1'-0"MP102
1 PARTIAL FIRST FLOOR PLAN - PIPING - EAST
B A
MECHANICAL
CHWP-111001
CHWP-111002
HHWP-111001
HHWP-111002
TU-111009
AHU-111001
BT-111001
74x22 RA
D 1250
B 1325
BL-111001
38x18 RA
M-402
M-402
SH-111001
x1
4 S A
48x16 RA 58x20 SA
(TYPICAL)
(TYPICAL)
M-402
B.7 A.4
2.4
1.9
1.5
1.3
8 14
M D-2 x2
2 E A 19
B A
M-402
M-402
MECHANICAL
CHWP-111001
CHWP-111002
HHWP-111001
HHWP-111002
TU-111009
AHU-111001
AS-111001
AS-111002
BT-111001
ET-111001
ET-111002
BL-111001
REFRIG. PIPING 4" CHWR
4" CHWS
4" CHWS
4" CHWR
4" CHWR
4" HWS
4" HWR
SH-111001
3" ST
M-402
B.7 A.4
2.4
1.9
1.5
1.3
4" CHWR
T
2" HWS
2" HWR
4" HWS
3" HWR
3" HWS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
BI
M
- C on st ru ct
R ep la ce m en t O ut pa tie nt C lin ic
/0
C on st . R ep la ce . O ut pa tie nt
C lin ic
R
.rv t
2/ 9/
0:
:0
AM
M-401
MECHANICAL ENLARGED PLANS REPLACEMENT OUTPATIENT
CLINIC DESIGN AT COAST
GUARD CAPE COD
JOINT BASE CAPE COD, BARNSTABLE MA
650-318
BUILDING 1
02/10/2023 JFR JJA
100% CONSTRUCTION
DOCUMENTS
1/4" = 1'-0"1 FIRST FLOOR ENLARGED PLAN - MECHANICAL ROOM
CODED NOTES:
42"X42" OUTSIDE AIR DUCTWORK UP TO OUTSIDE AIR INTAKE LOUVER IN ROOF. PROVIDE MOTORIZED
DAMPER IN VERTICAL TAKEOFF. REFER TO VIEW 1 / M-402 FOR MORE INFORMATION.
4" CONCRETE PAD TO EXTEND A MINIMUM OF 6" BEYOND PERIMETER OF EQUIPMENT.
40"X40" EA DUCT UP TO RF-121001. SEE SHEET MH104 FOR CONTINUATION.
6" COMBUSTION AIR INTAKE FOR BOILER.
CHILLED WATER CHEMICAL SHOT FEEDER. INSTALL PER DETAIL 8 / M-501.
HEATING HOT WATER CHEMICAL SHOT FEEDER. INSTALL PER DETAIL 8 / M-501.
HEAT TRACING PANEL.
MANUFACTURER'S RECCOMENDED CLEARANCE.
4" COMBUSTION AIR INTAKE FOR STEAM HUMIDIFIER.
BOILER FLUE VENT UP TO ROOF. REFER TO SHEET MH104 FOR CONTINUATION.
STEAM HUMIDIFIER FLUE VENT UP TO ROOF. REFER TO SHEET MH104 FOR CONTINUATION.
2" HWS&R OUT TO SERVE AIR TERMINAL UNITS. REFER TO SHEET MP101 FOR CONTINUATION.
4" CHWS&R OUT TO CHILLER. REFER TO SHEET MP101 FOR CONTINUATION.
4" CONCRETE PAD TO EXTEND A MINIMUM OF 6" BEYOND FRONT AND SIDES OF EQUIPMENT PER
MANUFACTURERS RECOMMENDATIONS.
REFRIGERANT PIPING ROUTED TO HP-111001. REFER TO SHEET MP102 FOR CONTINUATION.
REFRIGERANT PIPING ROUTED TO FCSS-111001. REFER TO SHEET MP102 FOR CONTINUATION.
AHU-111001 VFD LOCATION.
RF-121001 VFD LOCATION.
BMS PANEL LOCATION.
0 2' 4' 8' 12'
1/4" = 1'-0"
N
1/4" = 1'-0"2 FIRST FLOOR ENLARGED PLAN - MECHANICAL ROOM PIPING
LEVEL 1
0' - 0"
LEVEL 2
14' - 0"
B A
D-116x48 RA
20x58 SA
AHU-111001
4" CHWR
4" CHWS22x74 RA
M
REFRIG. PIPING
2" HWR 1
A.4
2" HWS
28x12 RA
38x18 RA
MOD (D-2)
LEVEL 1
119' - 0"
1.31.51.92.4 1.31.51.92.4
LEVEL 2
14' - 0"
2 1
BT-111001
ET-111001
CHWP-111001
CHWP-111002
AHU-111001
42x42 OA 40x40 EA 4" CHWR
4" CHWR
4" CHWS
4" CHWR
4" CHWS
3" HWR
3" HWS
74x22 RA
MOD (D-1)
2.4 1.9 1.5 1.3
AS-111001
4" CHWS
74x22 RA
48x16 RA
68x22 EA
AHU-111001
GWH-111001
GWH-111002
HEAT TRACING
PANEL
SH-111001
AHU-111001 VFD
RF-121001 VFD
CHWP-111002
CHWP-111001
BL-111001
HHWP-111002
HHWP-111001
CHEM. SHOT
FEEDER
BT-111001
TU-111009
LEVEL 1
119' - 0"
SH-111001ET-111002
BL-111001
4ø EA
2" HWS
4" HWR
3" ST
AS-111002
HHWP-111001HHWP-111002
4" HWS
4" HWS
4ø OA
4ø EA6ø EA
1.51.3
6ø OA
LEVEL 1
0' - 0"
LEVEL 2
14' - 0"
21 1.91.51.3
10ø SA
TU-11100512x12 SA
8ø RA 38x14 RA
30x20 SA
DUCTS THROUGH OPENINGS IN
GIRDER TRUSS. REFER TO
STRUCTURAL DRAWINGS. (TYP.)
DUCTS THROUGH LIGHT
GAUGE ROOF TRUSS TRUSS
OPENINGS. (TYP.)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
BI
M
- C on st ru ct
R ep la ce m en t O ut pa tie nt C lin ic
/0
C on st . R ep la ce . O ut pa tie nt
C lin ic
R
.rv t
2/ 9/
0:
:0
AM
M-402
MECHANICAL ENLARGED PLANS REPLACEMENT OUTPATIENT
CLINIC DESIGN AT COAST
GUARD CAPE COD
JOINT BASE CAPE COD, BARNSTABLE MA
650-318
BUILDING 1
02/10/2023 JFR JJA
100% CONSTRUCTION
DOCUMENTS
1/4" = 1'-0"1 MECHANICAL ROOM AHU-111001 SECTION A
1/4" = 1'-0"2 MECHANICAL ROOM AHU-111001 SECTION B
N.T.S.
MECHANICAL ROOM 3D VIEW4
0 2' 4' 8' 12'
1/4" = 1'-0"
CODED NOTES:
DUCT SMOKE DETECTOR.
4" CONCRETE PAD TO EXTEND A MINIMUM OF 6" BEYOND PERIMETER OF EQUIPMENT.
120"X76" RETURN AIR PLENUM.
MOUNT EXPANSION TANK SUSPENDED FROM CEILING.
CHILLED WATER CHEMICAL SHOT FEEDER.
HEATING HOT WATER CHEMICAL SHOT FEEDER.
BOILER AND STEAM HUMIDIFIER OUTSIDE AIR INTAKES. REFER TO DETAIL 6 / M-504 FOR MORE
INFORMATION.
AHU-111001 VFD LOCATION.
RF-121001 VFD LOCATION.
BMS PANEL LOCATION.
1/4" = 1'-0"3 MECHANICAL ROOM SECTION C
1/4" = 1'-0"5 FLAT ROOF SECTION D