Attachment 17 - Electrical 1 of 2.pdf

PDF 5 MB Posted

Attached to
Y1DZ--VHA Minor Construction - Project 650-318 - New Otis CBOC for Providence VAMC
Solicitation number
36C77624R0087
Issued by

About this file

This document is an electrical attachment for a federal contract opportunity related to the construction of a replacement outpatient clinic. It includes electrical legends, symbols, general notes, site plans, lighting plans, power plans, and equipment plans for the new clinic facility.

The key details include:

  • The project is for a new outpatient clinic to be located at the US Coast Guard Air Station in Barnstable, MA.
  • The electrical work includes site work, underground utilities, lighting, power distribution, and specialized equipment connections.
  • The drawings provide detailed information on electrical fixtures, devices, raceways, panels, and other systems required for the new clinic.
  • The general notes cover applicable codes, coordination requirements, installation standards, and other electrical design and construction guidelines.
  • The solicitation number is 36C77624R0087 and the project title is "Y1DZ--VHA Minor Construction - Project 650-318 - New Otis CBOC for Providence VAMC".

View the file

Other files

File Type Posted
36C77624R0087 0009.docx DOCX document
36C77624R0087 0008 Request for Propsoals 9.18.2024.docx DOCX document
36C77624R0087 00008 - Wage Determination 9.18.24.pdf PDF
36C77624R0087 0008 Request for Propsoals 9.18.2024.docx DOCX document
36C77624R0087 0008.docx DOCX document
36C77624R0087 0006.docx DOCX document
Answers to RFIs - 36C77624R0087 amendment 0006 Mass..docx DOCX document
36C77624R0087 0007.docx DOCX document
36C77624R0087 0006.docx DOCX document
Rhoad Island Note regarding FAR 52.229-3.docx DOCX document
USCG Cape Cod - SNELL STATEMENT OF SPECIAL INSPECTIONS - SNELL DSS 2024-06-24.pdf PDF
Answers to RFIs - 36C77624R0087 amendment 0006.docx DOCX document
S06 - Wage Determination 6-14-24.pdf PDF
AMENDMENT 0005 PRICE COST SCHEDULE.docx DOCX document
S06 36C77624R0087 0005.docx DOCX document
Answers to RFIs - 36C77624R0087 amendment 0005.docx DOCX document
01 00 00-VA SPEC-GENERAL REQUIREMENTS_Add1.pdf PDF
S06 36C77624R0087 0004.docx DOCX document
S06 36C77624R0087 0003.docx DOCX document
S06 36C77624R0087 0002.docx DOCX document
Attachment 9 - Architectural 4 of 5.pdf PDF
36C77624R0087 0001.docx DOCX document
Attachment 9 - Architectural 4 of 5.zip ZIP file
Attachment 19 - Telecom.pdf PDF
Attachment 1 - Specifications_Rev_05.2024.pdf PDF
Attachment 22 - Small Business Subcontracting Plan Template.docx DOCX document
Attachment 12 - Fire Alarm.pdf PDF
36C77624R0087_1.docx DOCX document
Attachment 20 - Brand Name - Redacted.pdf PDF
Attachment 13 - Fire Protection.pdf PDF
Attachment 11 - Structural.pdf PDF
Attachment 4 - Civil.pdf PDF
Attachment 10 - Architectural 5 of 5.pdf PDF
Attachment 9 - Architectural 4 of 5.pdf PDF
Attachment 16 - Mechanical 2 of 2.pdf PDF
Attachment 7 - Architectural 2 of 4.pdf PDF
Attachment 5 - Landscape.pdf PDF
Attachment 8 - Architectural 3 of 4.pdf PDF
Attachment 21 - wage determination.pdf PDF
Attachment 2 - General.pdf PDF
Attachment 23 - Division Breakdown Pricing.xls XLS spreadsheet
Attachment 6 - Architectural 1 of 4.pdf PDF
Attachment 14 - Plumbing.pdf PDF
Attachment 18 - Electrical 2 of 2.pdf PDF
Attachment 3 - Existing Conditions.pdf PDF
Attachment 15 - Mechanical 1 of 2.pdf PDF
Show all 46

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1PH SINGLE-PHASE

3PH THREE-PHASE

4W FOUR-WIRE

A/E ARCHITECT/ENGINEER

AF AMPERE FRAME OR AMP FUSE

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

ALT ALTERNATE

AMP AMPERE

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

BLDG BUILDING

C CONDUIT

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CKT CIRCUIT

CLG CEILING

COAX COAX CABLE

COMM COMMUNICATION

CONC CONCRETE

CONT CONTINUE

COORD COORDINATE

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CU COPPER

DB DECIBEL OR DIRECT BURIAL

DC DIRECT CURRENT

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DISC DISCONNECT

DN DOWN

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DS DISCONNECT SWITCH

DWG DRAWING

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

ESMT EASEMENT

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

ETR EXISTING TO REMAIN

ELECTRICAL ABBREVIATIONS

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FLA FULL LOAD AMPS

FP FIRE PROTECTION

FT FEET OR FOOT

GND GROUND

G or GFCI GROUND FAULT CIRCUIT INTERRUPTER

GTB GROUND TERMINAL BOX

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HZ HERTZ

IESNA ILLUMINATION ENGINEERING SOCIETY OF NORTH AMERICA

IMC INTERMEDIATE METAL CONDUIT

IR INFRARED

IWH INSTANTANEOUS WATER HEATER

J-BOX JUNCTION BOX

kV KILOVOLT kVA KILOVOLT AMPERE kVAH KILOVOLT AMPERE PER HOUR kVAR KILOVOLT AMPERE REACTIVE kW KILOWATT kWH KILOWATT HOUR

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LM LUMEN

LP LIGHT POLE

LRA LOCKED ROTOR AMPS

LTG LIGHTING

LV LOW VOLTAGE

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MH MANHOLE

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

MLO MAIN LUGS ONLY

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MV MEDIUM VOLTAGE

MVA MEGAVOLT-AMPERE

MW MEGAWATT MICROWAVE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NEUT OR N NEUTRAL

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NS NO SCALE

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OL OVERLOAD

P POLE

PA PUBLIC ADDRESS

PCB POLYCHLORINATED BIPHENYL

PH PHASE

PNL PANEL

POD POWER OPERATED DAMPER

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

RCP REFLECTED CEILING PLAN

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

REQD REQUIRED

SCC SHORT CIRCUIT CAPACITY

SD SMOKE DETECTOR

SF SQUARE FOOT (FEET)

SI INTERNATIONAL SYSTEM OF UNITS

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

TEL TELEPHONE

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

V VOLT

VA VOLT AMPERE

VAR VOLT AMPERE REACTIVE

VFD VARIABLE FREQUENCY DRIVE

VOLT VOLTAGE

W WATT

WH WATER HEATER

WP WEATHERPROOF

XFER TRANSFER

XFMR TRANSFORMER

ABBR. DESCRIPTION ABBR. DESCRIPTION ABBR. DESCRIPTION

AWG AMERICAN WIRE GAUGE

KCMIL ONE-THOUSAND CIRCULAR MILS

NA NOT APPLICABLE

HD HEAT DETECTOR

MOTOR CONNECTION

TEE SPLICE

FOUR-WAY SPLICE

ABC

PANELBOARD MAIN CIRCUIT BREAKER TYPE, ONE-LINE

### - INDICATES BREAKER RATING

ABC - INDICATES PANEL DESIGNATION

ABC

PANELBOARD MAIN LUG TYPE, ONE-LINE

### - INDICATES BUS RATING

ABC - INDICATES PANEL DESIGNATION

###A CIRCUIT BREAKER

### - INDICATES BREAKER RATING

GND GROUND BUS BAR

DN

DN

THRU-ROOF CONDUCTOR

DOWN CONDUCTOR

GROUND TERMINAL

AIR TERMINAL; PROVIDE PARAPET TYPE BASE WHERE MOUNTED ON PARAPET;

PROVIDE FLAT BASE FOR MECHANICAL EQUIPMENT OR ROOF PERIMETER WITH NO

PARAPET; PROVIDE BLUNT TIP WHERE MOUNTED ON INTERIOR OF ROOF, UNLESS

OTHERWISE NOTED ON LIGHTNING PROTECTION PLANS

BONDING PLATE

LIGHTNING PROTECTION SYSTEM

DISCONNECT SWITCH, FUSED

DISCONNECT SWITCH, UNFUSED

STARTER, COMBINATION WITH DISCONNECT SWITCH

STARTER OR MOTOR CONTROLLER

JUNCTION BOX

EARTH GROUND

RECEPTACLE, DUPLEX

RECEPTACLE, DOUBLE DUPLEX (QUADRAPLEX)

RECEPTACLE, SPECIAL PURPOSE, SEE CODED NOTES ON FLOOR PLANS FOR NEMA CONFIGURATION AND WIRING

REQUIREMENTS

ELECTRICAL SYMBOLS - POWER/LIGHTING PLANS

SWITCH (# SUBSCRIPT AS INDICATED BELOW) - SEE PLANS AND SPECIFICATIONS FOR DETAILS

BLANK = SINGLE POLE P = WITH PILOT LIGHT

WP= WEATHER PROOF

OS= DUAL TECHNOLOGY OCCUPANCY SENSOR

OSD = DUAL TECHNOLOGY OCCUPANCY SENSOR WITH DIMMING

a= SUBSCRIPT DEFINES FIXTURES THAT ARE CONTROLLED BY SWITCH

3 = THREE-WAY

D = DIMMER

LV= LOW VOLTAGE - SEE BELOW FOR DETAILS

M = MOTOR SNAP WITH PILOT LIGHT

(THERMAL TYPE)

LIGHT POLE, ONE LUMINAIRE

LIGHTING, EXTERIOR BUILDING

LIGHT POLE, TWO LUMINAIRES

J

SYMBOL DESCRIPTION DESCRIPTION

ALARM, FIRE, PANEL; LETTERS INDICATE AS FOLLOWS:

FACP = CONTROL PANEL

FAAP = ANNUNCIATOR PANEL

FACP

DESCRIPTION

SUBSCRIPTS (TYPICAL FOR ALL RECEPTACLES):

G = GFCI TYPE

T = TAMPER RESISTANT

CH = MOUNTED AT COUNTER HEIGHT WITH BOTTOM OF DEVICE AT 6" ABOVE BACKSPLASH

TV = RECEPTACLE MOUNTED ADJACENT TO TV OUTLET

USB = DUPLEX RECEPTACLE WITH (1) USB TYPE 'A' AND (1) USB TYPE 'C'

WP = DEVICE PROVIDED WITH WEATHERPROOF IN-USE METAL COVER

EWC = DENOTES DEVICE FOR ELECTRIC WATER COOLER - COORDINATE WITH EWC INSTALLER FOR

MOUNTING HEIGHT

a = LOWER CASE LETTER INDICATES RELAY POWER PACK FOR RECEPTACLE CONTROL

E = RED DEVICE, FED FROM UPS-FED BRANCH CIRCUIT

TRANSFORMER, PLANT

TRANSFORMER, ONE-LINE

FUSIBLE DISCONNECT SWITCH, ONE-LINE

###AF - INDICATES FUSE RATING

###AS - INDICATED SWITCH RATING

###AF

M

ABC

BRANCH CIRCUIT PANELBOARD, OVER 250 VOLTS, SURFACE MOUNTED

BRANCH CIRCUIT PANELBOARD, UNDER 250 VOLTS, SURFACE MOUNTED

SWITCHBOARD/ SWITCHGEAR/ DISTRIBUTION PANEL - OVER 250 VOLTS LOW VOLTAGE SWITCH - SEE PLANS, SPECIFICATIONS AND WIRING DIAGRAMS FOR DETAILS LV2Dab

S

S

SUBSCRIPT(S) INDICATE FIXTURES CONTROLLED

'D' INDICATES 0-10V DIMMING

'2' INDICATES NUMBER OF LIGHTING CONTROL ZONES

'LV' INDICATES LOW VOLTAGE SWITCH

VFD VARIABLE FREQUENCY DRIVE

A

EXIT LIGHT, LED, WALL MOUNTED

EXIT LIGHT, LED, CEILING OR PENDANT MOUNTED; DIRECTIONAL ARROWS AS

INDICATED; SHADED QUADRANT INDICATES FACE(S) OF LUMINAIRE

LED, RECESSED, PENDANT OR SURFACE CEILING LUMINAIRE

LED, RECESSED, PENDANT OR SURFACE CEILING LIGHTING FIXTURE

SHADING INDICATES FIXTURE CONNECTED TO EMERGENCY

CIRCUIT. (TYPICAL FOR ALL LIGHT FIXTURE SYMBOLS)

LED FIXTURE, RECESSED, PENDANT OR SURFACE CEILING

LED STRIP LUMINAIRE

FIXTURE TYPE

LOWER CASE LETTER INDICATES CONTROLLING SWITCHa

CIRCUIT NUMBER

LED, WALL MOUNTED LUMINAIRE

DN

UP

CONDUIT CONTINUED

CONDUIT STUBBED OUT OR UP

CONDUIT TURNING DOWN

CONDUIT TURNING UP

PUSHBUTTON STATION

MULTI-SERVICE FLOOR BOX WITH DUPLEX RECEPTACLE, VOICE/DATA/AV DEVICES (REFER TO TECHNOLOGY

DRAWINGS OR OWNER'S VENDOR DRAWINGS FOR LOW VOLTAGE REQUIREMENTS)

CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOROS

GROUND BUS BAR, COPPER

SPD SURGE PROTECTIVE DEVICE

FLOOR BOX WITH DUPLEX RECEPTACLE WITH APPROPRIATE FLANGE

FLOOR BOX, TWO DUPLEX RECEPTACLES (QUAD) WITH APPROPRIATE FLANGE

SYMBOL SYMBOL

WALL MOUNTED JUNCTION BOXJ

LPP LIGHTING POWER PACK RELAY

a

SUBSCRIPT INDICATES CONTROLLING SWITCH AND FIXTURES CONTROLLED (TYPICAL)

LPD LIGHTING POWER PACK RELAY WITH 0-10V DIMMING

LPE EMERGENCY LIGHTING POWER PACK RELAY - UL924 COMPLIANT

LPDE EMERGENCY LIGHTING POWER PACK RELAY - UL924 COMPLIANT AND 0-10V DIMMING

DOUBLE TUB PANELBOARD, ONE-LINE

ABC - INDICATES PANEL DESIGNATION

###AS

METER, ONE-LINE

UNINTERRUPTIBLE POWER SUPPLY (UPS) OR LIGHTING INVERTER, ONE-LINE

ELECTRICAL ONE-LINE

###A BRANCH CIRCUIT BREAKER

### - INDICATES BREAKER RATING

WALL SCONCE, EXTERIOR BUILDING

LRP1-1 BRANCH CIRCUIT NUMBER THAT SERVES DEVICE

PANEL THAT SERVES DEVICE

HANDHOLEHH

ROOF MOUNTED PHOTO CELL FOR LIGHTING CONTROLPC

MULTI-SERVICE FLOOR BOX WITH TWO DUPLEX RECEPTACLE, TWO VOICE/DATA/AV DEVICES (REFER TO

TECHNOLOGY DRAWINGS OR OWNER'S VENDOR DRAWINGS FOR LOW VOLTAGE REQUIREMENTS)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

BI

M

- C on st ru ct

R ep la ce m en t O ut pa tie nt C lin ic

/0

C on st . R ep la ce . O ut pa tie nt

C lin ic

R

.rv t

2/ 9/

2:

:2

PM

E-001

ELECTRICAL LEGENDS &

SYMBOLS

REPLACEMENT OUTPATIENT

CLINIC DESIGN AT COAST

GUARD CAPE COD

JOINT BASE CAPE COD, BARNSTABLE MA

650-318

BUILDING 1

02/10/2023 JFR KEM

100% CONSTRUCTION

DOCUMENTS

SHEET LIST

Sheet Number Sheet Name

E-001 ELECTRICAL LEGENDS & SYMBOLS

E-002 ELECTRICAL GENERAL NOTES

E-100 ELECTRICAL SITE PLAN

E-101 UTILITY SITE PLAN

E-201 PARTIAL FIRST FLOOR PLAN - ELEC. LIGHTING - WEST

E-202 PARTIAL FIRST FLOOR PLAN - ELEC. LIGHTING - EAST

E-203 PARTIAL FIRST FLOOR PLAN - ELEC. POWER - WEST

E-204 PARTIAL FIRST FLOOR PLAN - ELEC. POWER - EAST

E-205 PARTIAL FIRST FLOOR PLAN - ELEC. EQUIPMENT - WEST

E-206 PARTIAL FIRST FLOOR PLAN - ELEC. EQUIPMENT - EAST

E-207 ELECTRICAL ROOF PLAN

E-501 ELECTRICAL DETAILS

E-502 ELECTRICAL DETAILS

E-503 ELECTRICAL DETAILS

E-601 ELECTRICAL ONE-LINE DIAGRAM

E-801 ELECTRICAL SCHEDULES

E-802 ELECTRICAL PANEL SCHEDULES

E-803 ELECTRICAL PANEL SCHEDULES

EC100 ELECTRICAL SITE CALC

Revisions Date

ELECTRICAL GENERAL NOTES

WHERE THERE IS A DISCREPANCY BETWEEN ABOVE GENERAL NOTES AND

SPECIFICATIONS, WHERE APPLICABLE, SPECIFICATIONS SHALL BE FOLLOWED

APPLICABLE CODES

1. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), INCLUDING (BUT NOT LIMITED TO):

a. NATIONAL ELECTRICAL CODE (NEC), NFPA 70 - 2020

b. NATIONAL FIRE ALARM CODE, NFPA 72 - 2022

c. LIFE SAFETY CODE, NFPA 101 – 2021

d. STANDARD FOR THE INSTALLATION OF LIGHTNING PROTECTION SYSTEMS, NFPA 780

e. HEALTH CARE FACILITIES CODE, NFPA 99 - 2021

2. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI), INCLUDING (BUT NOT LIMITED TO):

a. NATIONAL ELECTRICAL SAFETY CODE, ANSI C2

3. OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA)

4. FEDERAL COMMUNICATION COMMISSION (FCC)

5. NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

6. INSULATED CABLE ENGINEERS ASSOCIATION (ICEA)

7. INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

8. NATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)

9. AMERICAN SOCIETY OF TESTING AND MATERIALS (ASTM)

10. ILLUMINATION ENGINEERING SOCIETY (IES)

11. ANTI-FRICTION BEARING MANUFACTURERS ASSOCIATION (AFBMA)

12. BUILDING OFFICIALS AND CODE ADMINISTRATORS INTERNATIONAL, INC. (BOCA)

13. INTERNATIONAL CODE COUNCIL (ICC):

a. INTERNATIONAL BUILDING CODE (IBC)

14. UNIFORM BUILDING CODE (UBC)

15. NATIONAL ELECTRICAL CONTRACTORS ASSOCIATION INSTALLATION STANDARDS (NECA)

16. AMERICANS WITH DISABILITIES ACT (ADA)

17. APPLICABLE STATE AND LOCAL CODES, AMENDMENTS, REGULATIONS, AND PRACTICES.

18. APPLICABLE REGULATORY REQUIREMENTS AND ADVISORY PRACTICES OF APPROPRIATE

a. AUTHORITIES HAVING JURISDICTION (AHJs).

19. APPLICABLE STANDARDS, REGULATIONS, AND PRACTICES OF THE OWNER.

20. VA ELECTRICAL DESIGN MANUAL - 2019

21. VA LIGHTING DESIGN MANUAL - 2015

GENERAL:

1. THE DRAWINGS AND APPLICABLE SPECIFICATIONS SHALL BE CONSIDERED SUPPLEMENTARY,

ONE TO THE OTHER AND ARE CONSIDERED THE "CONTRACT DOCUMENTS". ALL WORKMANSHIP,

METHODS AND/OR MATERIALS DESCRIBED OR IMPLIED BY ONE AND NOT DESCRIBED OR

IMPLIED BY THE OTHER SHALL BE PROVIDED, FURNISHED OR PERFORMED AS IF IT HAD

APPEARED IN BOTH SECTIONS. THE TERM "CONTRACT DOCUMENTS" DESCRIBED HEREIN IS

NOT LIMITED SOLELY TO THE ELECTRICAL PORTION OF THE DRAWINGS AND SPECIFICATIONS,

BUT ENCOMPASSES THE DRAWINGS AND SPECIFICATIONS OF ALL DIVISIONS AS A WHOLE.

2. PROVIDE AN OPERATING AND MAINTENANCE MANUAL TO OWNER PRIOR TO THE FINAL

ACCEPTANCE. THE MANUAL SHALL INCLUDE, AS A MINIMUM, (1) SUBMITTAL DATA STATING

EQUIPMENT RATING AND SELECTED OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING

MAINTENANCE. ALSO PROVIDE TWO OPERATIONS AND MAINTENANCE MANUALS FOR EACH

PIECE OF EQUIPMENT REQUIRING MAINTENANCE. REQUIRED ROUTINE MAINTENANCE ACTIONS

AND METHOD OF OPERATION FOR EQUIPMENT SHALL BE CLEARLY IDENTIFIED, AND THE NAME,

PHONE NUMBER AND ADDRESS OF AT LEAST ONE QUALIFIED SERVICE AGENCY.

3. INCLUDE ALL COSTS FOR EXCAVATION, SAW CUTTING, DIRECTIONAL BORING, CORE DRILLING, BACKFILLING, SURFACE RESTORATION, REPAIR OF FINISHES, ETC. THAT IS REQUIRED IN ORDER

TO MEET THE PROJECT REQUIREMENTS.

4. INCLUDE IN BID ALL COSTS ASSOCIATED WITH TEMPORARY ELECTRICAL SERVICE AS REQUIRED

FOR USE BY ALL TRADES DURING CONSTRUCTION. REMOVE TEMPORARY POWER AT THE

COMPLETION OF THE PROJECT. OBTAIN AND PAY FOR ALL REQUIRED PERMITS FOR

TEMPORARY POWER. ENGINEER OF RECORD SHALL BE PROVIDED WITH ADDITIONAL

COMPENSATION FROM THE CONTRACTOR WHERE SIGNED & SEALED DRAWINGS ARE

REQUESTED BY THE CONTRACTOR TO THE ENGINEER OF RECORD IF REQUIRED BY THE AHJ

FOR THE TEMPORARY POWER.

5. PROVIDE A COMPLETE UL LISTED LIGHTNING PROTECTION SYSTEM WITH A MASTER LABEL FOR

THE ENTIRE FACILITY PER THE REQUIREMENTS OF NFPA 780, AND THE DIVISION 26

SPECIFICATIONS, UNLESS NOTED OTHERWISE. LIGHTNING PROTECTION SYSTEM SHALL

INCLUDE BURIED COUNTERPOISE, UNLESS NOTED OTHERWISE.

6. INCLUDE IN BID THE TRANSPORT AND DISPOSAL OR RECYCLING OF ALL WASTE MATERIALS

GENERATED BY THIS PROJECT IN ACCORDANCE WITH ALL LOCAL, STATE AND FEDERAL RULES,

REGULATIONS AND GUIDELINES APPLICABLE. COMPLY FULLY WITH FLORIDA STATUTES

REGARDING MERCURY-CONTAINING DEVICES, AND WITH ALL DEP AND EPA APPLICABLE

GUIDELINES AT THE TIME OF DISPOSAL. PROVIDE OWNER WITH WRITTEN CERTIFICATION OF

ACCEPTED DISPOSAL.

7. ALL POWER CIRCUITS HAVE BEEN DESIGNED IN COMPLIANCE WITH SECTION C405.7.3 OF THE

ENERGY CONSERVATION CODE, REQUIRING 2% OR LESS VOLTAGE DROP FOR FEEDERS, AND

3% OR LESS VOLTAGE DROP FOR BRANCH CIRCUITS.

ELECTRICAL SYSTEM HAS BEEN DESIGNED IN ACCORDANCE WITH THE 2020 NATIONAL

ELECTRICAL CODE (NFPA 70).

8. ALL BRANCH CIRCUITS SHALL BE FURNISHED WITH A DEDICATED NEUTRAL. SHARED NEUTRALS

ARE NOT ALLOWED UNLESS SPECIFICALLY NOTED ON THE DRAWINGS.

9. VERIFY AND COORDINATE LOCATIONS OF ANY MISCELLANEOUS EQUIPMENT REQUIRING

ELECTRICAL CONNECTIONS (I.E., COPIERS, FAX MACHINES, PRINTERS, KITCHEN APPLIANCES, LAUNDRY APPLIANCES, PROJECTION SCREENS, SHOP TOOLS, MACHINE, ELEVATORS, ETC.)

WITH APPROVED SHOP DRAWINGS, OWNER-PROVIDED CUT SHEETS, MANUFACTURER'S

INSTRUCTIONS, AND EQUIPMENT NAMEPLATE INFORMATION, PRIOR TO ROUGH IN, AND

PROVIDE ALL NECESSARY ELECTRICAL REQUIRED.

10. VERIFY AND COORDINATE LOCATIONS AND EXACT ELECTRICAL REQUIREMENTS FOR ALL

MECHANICAL, PLUMBING AND FIRE PROTECTION EQUIPMENT PRIOR TO SUBMITTAL OF SHOP

DRAWINGS OF ELECTRICAL EQUIPMENT. PROVIDE ALL NECESSARY RACEWAYS, CONDUCTORS,

BOXES, EQUIPMENT, ACCESSORIES, ASSOCIATED DISCONNECT SWITCHES, CIRCUIT BREAKERS,

CONTROL TRANSFORMERS, FIRE ALARM SHUTDOWN, ETC. REQUIRED FOR A COMPLETE AND

OPERATIONAL SYSTEM. COORDINATE WITH APPROPRIATE TRADE'S APPROVED SHOP

DRAWINGS, MANUFACTURER'S INSTRUCTIONS, AND EQUIPMENT NAMEPLATE INFORMATION,

PRIOR TO ROUGH IN, AND PROVIDE ALL NECESSARY ELECTRICAL REQUIRED, UNLESS

OTHERWISE NOTED.

11. ALL WORK ON THE ELECTRICAL SYSTEM REQUIRED BY THE CONTRACT DOCUMENTS SHALL BE

COORDINATED WITH THE WORK OF ALL OTHER DIVISIONS/TRADES PRIOR TO COMMENCEMENT

OF WORK. AVOID INTERFERENCES WITH THE PROGRESS OF OTHER DIVISIONS/TRADES.

12. WHERE STRUCTURAL WALLS ARE OF TILT-UP CONSTRUCTION, PROVIDE COORDINATION FOR

EXACT DIMENSIONS AND OPENINGS REQUIRED FOR ALL ELECTRICAL COMPONENTS INSTALLED

WITHIN TILT-UP WALLS DURING THE SHOP DRAWING REVIEW PROCESS OF THE TILT-UP WALLS, PRIOR TO MANUFACTURE OF THE TILT-UP WALLS.

13. LOCATIONS OF VFD'S, DISCONNECTS, MOTOR STARTERS, ETC. FOR HVAC EQUIPMENT ARE

DIAGRAMMATIC ON THE PLAN DRAWINGS. EXACT LOCATIONS ARE TO BE COORDINATED WITH

CONTRACTOR'S COORDINATION DRAWINGS PRIOR TO ROUGHING IN TO ENSURE PROPER NEC

CLEARANCES AND APPROPRIATE MOUNTING SURFACE.

14. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS.

PROVIDE COMPONENTS INDICATED ON RISER DIAGRAMS WHETHER OR NOT INDICATED ON

PLANS AND VICE VERSA.

15. ROUTING OF CONDUIT IS DIAGRAMMATIC AND NOT INTENDED TO SHOW REQUIRED OFFSETS

AND DETAILS. COORDINATE EXACT ROUTING WITH FIELD CONDITIONS AND OTHER TRADES.

16. COORDINATE RECEPTACLE LOCATIONS WITH TECHNOLOGY DRAWINGS OR OWNER'S VENDOR

DRAWINGS SO THAT A 120V 20A 5-20R RECEPTACLE IS LOCATED ADJACENT TO EACH

VOICE/DATA OUTLET AND TV OUTLET INDICATED ON PLANS. RECEPTACLE IS TO BE CONNECTED

TO NEAREST 120V RECEPTACLE CIRCUIT, UNLESS OTHERWISE NOTED ON PLANS.

17. REFER TO ARCHITECTURAL, MECHANICAL, PLUMBING, FIRE PROTECTION, CIVIL, LANDSCAPE, INTERIOR DESIGN, TECHNOLOGY, STRUCTURAL, AND KITCHEN EQUIPMENT DRAWINGS FOR

RELATED INFORMATION AND ADDITIONAL INSTALLATION REQUIREMENTS TO BE PERFORMED AS

PART OF THE WORK. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT MOUNTING HEIGHT

AND LOCATIONS.

18. WHERE A DISCREPANCY OR CONFLICT IS FOUND BETWEEN ONE DRAWING AND ANOTHER, OR

BETWEEN A DRAWING AND APPLICABLE SPECIFICATIONS, NOTIFY THE ARCHITECT/ENGINEER

IMMEDIATELY IN WRITTEN FORM. IN GENERAL, THE MOST STRINGENT REQUIREMENT SHALL

GOVERN UNLESS THE DISCREPANCY CONFLICTS WITH APPLICABLE CODES OR OWNER'S

DESIGN STANDARDS, WHEREIN THE CODE OR OWNER'S DESIGN STANDARDS SHALL GOVERN.

19. COORDINATE ALL PROJECT SCHEDULING AND PHASING REQUIREMENTS WITH

ARCHITECT/ENGINEER AND OWNER PRIOR TO SUBMITTING BID PRICE. THIS PROJECT MAY

REQUIRE PHASING SEQUENCES AND POTENTIAL PREMIUM TIME WORK AND ALL COSTS FOR

SUCH SHALL BE INCLUDED IN THE BID PRICE. PROVIDE ADEQUATE WORK FORCE AND

EQUIPMENT, AND INCLUDE PREMIUM TIME AS MAY BE REQUIRED IN ORDER TO ADHERE TO THE

PROJECT SCHEDULE. ADDITIONALLY, ENSURE THAT LONG LEAD ITEMS DO NOT IMPACT THE

PROJECT'S SCHEDULE OR PHASING.

20. ANY TEMPORARY INTERRUPTION ON POWER REQUIRED FOR THE SYSTEM TIE-IN OR

SWITCHOVER FOR ANY PORTION OF THE ELECTRICAL SYSTEM SHALL BE PRE-APPROVED IN

WRITING BY THE OWNER AND SCHEDULED IN ADVANCE.

21. COORDINATE EXACT REQUIREMENTS WITH THE LOCAL UTILITY COMPANIES AND PROVIDERS

(ELECTRIC, TELEPHONE, CABLE TV, ETC.) AND INCLUDE ALL COSTS FOR PROVIDING

TEMPORARY AND PERMANENT SERVICES REQUIRED FOR THIS PROJECT IN THE BID PRICE. BID

PRICE SHALL INCLUDE, BUT NOT BE LIMITED TO, EXCAVATION, RACEWAYS, BACKFILL,

EQUIPMENT, EQUIPMENT PADS, BACKBOARDS, METERS, GROUNDING, UTILITY ENGINEERING

AND IMPACT FEES.

22. CONDUCT WORK OPERATIONS AND DEBRIS REMOVAL IN A MANNER THAT ENSURES MINIMUM

INTERFERENCE WITH NORMAL BUSINESS OPERATIONS, TRAFFIC, PARKING, ETC. ONGOING IN

ADJACENT OCCUPIED SPACES OR FACILITIES. PROVIDE ALL THAT IS REQUIRED TO

EFFECTIVELY PROTECT SURROUNDING OCCUPANTS, EQUIPMENT, FINISHES, FURNITURE, ETC.

FROM DAMAGE OR EXCESSIVE NOISE THROUGHOUT THE DURATION OF THIS PROJECT.

CONTRACTOR IS RESPONSIBLE FOR ANY LOSSES OR DAMAGE. ANY DAMAGE RESULTING FROM

THE FAILURE TO ADHERE TO THIS REQUIREMENT. RESTORE DAMAGED ELEMENTS TO ORIGINAL

CONDITION BY THE CONTRACTOR TO THE SATISFACTION OF THE ARCHITECT/ENGINEER AND

OWNER, AT NO ADDITIONAL COSTS. REPORT OF ANY SUCH OCCURRENCE TO THE

ARCHITECT/ENGINEER AND OWNER IMMEDIATELY AND AWAIT WRITTEN DIRECTION PRIOR TO

PROCEEDING WITH REPAIRS.

23. COORDINATE THE LOCATION OF ALL LIGHT FIXTURES, DEVICES AND BOXES WITH WINDOWS, MIRRORS, MILLWORK, CABINETS, GLASS CURTAIN WALLS, AND GLASS WALLS PRIOR TO

INSTALLATION OF CONDUITS OR BOXES. REVIEW ALL CONTRACT DRAWINGS TO ASCERTAIN

ANY CONFLICTS PRIOR TO BIDDING. OBTAIN CLARIFICATION FROM A/E PRIOR TO BID.

CONTRACTOR SHALL NOT BE ENTITLED TO ADDITIONAL COMPENSATION FOR WORK REQUIRED

TO RELOCATE OUTLET BOXES OR RACEWAYS FOR COORDINATION WITH OTHER TRADE'S

WORK.

24. THE EXCLUSIVELY DEDICATED SPACE EXTENDING FROM FLOOR TO 6' ABOVE EQUIPMENT OR

STRUCTURAL CEILING, WHICHEVER DISTANCE IS LOWER, WITH A WIDTH AND DEPTH OF THE

PANELBOARD OR SWITCHBOARD MUST BE CLEAR OF ALL PIPING, DUCTS, EQUIPMENT FOREIGN

TO THE ELECTRICAL EQUIPMENT OR ARCHITECTURAL APPURTENANCES IN ACCORDANCE WITH

NEC.

25. PROVIDE ALL TEMPORARY NORMAL LIGHTING, EMERGENCY LIGHTING AND EXIT SIGNAGE

REQUIRED DURING THE PROJECT CONSTRUCTION PHASE.

26. THE INFRASTRUCTURE FOR THE ACCESS CONTROL/ CCTV OR SECURITY ELECTRONICS SYSTEM (CONDUITS, ELECTRICAL BOXES) SHALL BE INSTALLED BY DIVISION 26. THE ACCESS CONTROL/

CCTV OR SECURITY ELECTRONICS SYSTEM CONTRACTOR SHALL PROVIDE AND INSTALL THE

WIRE AND CABLE FOR THE SYSTEM AND ALL REQUIRED EQUIPMENT. INSTALLATION OF THE

CONDUITS AND ELECTRICAL BOXES SHALL BE UNDER THE DIRECT SUPERVISION OF THE

ACCESS CONTROL/ CCTV SYSTEM CONTRACTOR. COORDINATE EXACT LOCATIONS OF DEVICES,

RACEWAY LOCATIONS, SIZES AND QUANTITY, CONDUIT STUB-UPS PRIOR TO ROUGH IN.

27. THE INFRASTRUCTURE FOR THE VOICE/DATA TELECOMMUNICATIONS SYSTEM (CONDUITS,

ELECTRICAL BOXES) SHALL BE INSTALLED BY DIVISION 26. THE TELECOMMUNICATIONS

CONTRACTOR SHALL PROVIDE AND INSTALL THE WIRE AND CABLE FOR THE SYSTEM AND ALL

REQUIRED EQUIPMENT AND COMPONENTS. INSTALLATION OF THE CONDUITS AND ELECTRICAL

BOXES SHALL BE UNDER THE DIRECT SUPERVISION OF THE TELECOMMUNICATIONS

CONTRACTOR. COORDINATE EXACT LOCATIONS OF DEVICES, RACEWAY LOCATIONS, SIZES AND

QUANTITY, CONDUIT STUB-UPS PRIOR TO ROUGH IN.

28. PROVIDE 120V 20A 5-20R RECEPTACLE AT ALL FAN COIL UNITS FOR CONDENSATE PUMP POWER

AND HOT WATER RECIRCULATING PUMPS, WHETHER SHOWN ON PLANS OR NOT. RECEPTACLE

IS TO BE CONNECTED TO NEAREST 120V RECEPTACLE CIRCUIT.

29. PROVIDE 120V CONNECTION TO ALL MOTORORIZED DAMPERS INDICATED ON MECHANICAL

PLANS, WHETHER SHOWN ON DIVISION 26 DRAWINGS OR NOT. FIRE/SMOKE DAMPER CIRCUITS

ARE TO BE PROVIDED FROM EMERGENCY BRANCH PANEL (LEGALLY REQUIRED BRANCH IF

AVAILABLE). MOTORIZED DAMPERS WITHIN THE SAME AREA CAN BE CIRCUITED TO THE SAME

CIRCUIT (I.E., DEDICATED CIRCUIT IS NOT REQUIRED).

30. PROVIDE PHONE/DATA OUTLET WITH 1" RACEWAY, AND 120V RECEPTACLE ON DEDICATED

CIRCUIT ADJACENT TO EACH AIR HANDLING UNIT FOR CONTROL POWER.

31. PROVIDE 120V DEDICATED CIRCUIT TO EACH AIR HANDLING UNIT WITH SEPARATE

CONNECTIONS TO UNIT UV LIGHT, UNIT LIGHTS, UNIT RECEPTACLE, AND BI-POLAR IONIZATION

FILTER WHERE PROVIDED. COORDINATE WITH DIVISION 23 SHOP DRAWINGS.

32. UNLESS NOTED AS EXISTING, ALL ELECTRICAL INDICATED ON THE CONTRACT DOCUMENTS

SHALL BE NEW, SHALL BE U.L. LISTED, AND SHALL BEAR A U.L. LABEL. WHERE NO U.L. LABEL OR

LISTING IS AVAILABLE, THE MATERIAL SHALL BE LISTED WITH AN APPROVED, NATIONALLY

RECOGNIZED ELECTRICAL TESTING AGENCY.

33. PROVIDE EXPERIENCED, QUALIFIED AND RESPONSIBLE SUPERVISION FOR ALL WORK

REQUIRED BY THE CONTRACT DOCUMENTS. ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED

IN A NEAT AND WORKMANLIKE MANNER, TO THE SATISFACTION OF THE ARCHITECT/ENGINEER

AND OWNER.

34. THE ELECTRICAL PORTION OF THE CONTRACT DOCUMENTS ARE COORDINATED WITH THE

DESIGN BASIS EQUIPMENT SPECIFIED BY DIVISION 26 AND OTHER DIVISIONS. WHERE THE

CONTRACTOR ELECTS TO SUBSTITUTE A PRODUCT IN LIEU OF PROVIDING THE DESIGN BASIS,

AND SAID SUBSTITUTION IS ACCEPTED BY THE A/E AND OWNER, THE CONTRACTOR SHALL MAKE

ALL CORRECTIONS TO THE ELECTRICAL SYSTEM NECESSARY IN ORDER TO ENSURE A

COMPLETE AND OPERATIONAL INSTALLATION OF THE EQUIPMENT AT NO ADDITIONAL COSTS.

WHERE THE CONTRACTOR'S DESIGN SUBSTITUTION RESULTS IN THE NEED FOR THE ENGINEER

TO REVISE THE CONTRACT DOCUMENTS, THE ENGINEER RESERVES THE RIGHT TO REQUEST

COMPENSATION FROM THE CONTRACTOR FOR SAID SERVICES.

35. MAINTAIN A CURRENT AND ACCURATE SET OF PROJECT RECORD DOCUMENTS (AS-BUILTS) AT

THE SITE THROUGHOUT THE DURATION OF THE PROJECT. RECORD DRAWINGS SHALL BE

UPDATED EACH DAY TO REFLECT THE ACTUAL LOCATIONS, SIZES, ROUTING, ETC. OF EACH

PORTION OF THE ELECTRICAL SYSTEM AFFECTED BY THIS WORK. A FINAL SET OF RECORD

DOCUMENTS SHALL BE ISSUED TO THE A/E FOR REVIEW AND THEN SUBMITTED TO THE OWNER

WITHIN 30 DAYS AFTER THE DATE OF FINAL ACCEPTANCE. PROVIDE RECORD DRAWINGS OF

THE ACTUAL INSTALLATION INCLUDING SINGLE LINE DIAGRAM, POWER RISER DIAGRAM OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM, SITE PLANS AND ALL ELECTRICAL FLOOR PLANS, DETAILS, PANEL SCHEDULES, ETC.

36. OWNER FURNISHED EQUIPMENT: VERIFY AND COORDINATE ELECTRICAL ROUGH IN

REQUIREMENTS FOR OWNER FURNISHED EQUIPMENT PRIOR TO ROUGH IN.

37. WHERE SUBMITTED EQUIPMENT REQUIRES REVISION TO OVERCURRENT PROTECTION,

CONDUIT OR WIRING, MAKE CHANGES IN ACCORDANCE WITH APPLICABLE CODES.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

BI

M

- C on st ru ct

R ep la ce m en t O ut pa tie nt C lin ic

/0

C on st . R ep la ce . O ut pa tie nt

C lin ic

R

.rv t

2/ 9/

2:

:3

PM

E-002

ELECTRICAL GENERAL NOTES REPLACEMENT OUTPATIENT

CLINIC DESIGN AT COAST

GUARD CAPE COD

JOINT BASE CAPE COD, BARNSTABLE MA

650-318

BUILDING 1

02/10/2023 JFR KEM

100% CONSTRUCTION

DOCUMENTS

C

C

C C

C

C

C

C

C

C

C

CCCCC

C C C C CC

C C

CCCCCCC

C C

C C

CCC

UE

U E

S

PSFMFMFMFMFMFM V

GAS

LINE POST

APPROX. GAS

MAIN

APPROX. GAS

MAIN

UP #8UP #9 UP #601/7

J

J

J

J J

J J

SB

SA

SB2 SB

BAR CT CABINET

CONNERY AVENUE

PAD MOUNTED UTILITY

TRANSFORMER

PRIMARY ELECTRICAL FEED - SEE ONE-LINE

DIAGRAM ON SHEET E-601 AND

UNDERGROUND CONDUIT DETAIL #2 ON THIS

SHEET.

UNDERGROUND CONDUITS FOR CATV,

INTERNET AND TELECOMMUNICATIONS

SERVICES, REFER TO SHEET T-101 FOR

ADDITIONAL INFORMATION.

RUN COMMUNICATIONS CONDUIT UP 8' ON

UTILITY POLE AND PROVIDE METAL GUARD

TO ATTACHMENT POINT FROM UTILITY

EXISTING

UTILITY POLE

SECONDARY ELECTRICAL FEED - SEE

ELECTRICAL ONE-LINE DIAGRAM ON SHEET

E-601 AND CONCRETE ENCASED

UNDERGROUND CONDUIT DETAIL

SA

SA

SA SA

SA

SA

SA

SA

SA

SB2

ELECTRICAL UTILITY METER

(3) GROUND RODS - REFER TO

SYSTEM GROUNDING DETAIL

FOR REQUIREMENTS

FLG FLG

FLG

2TYPICAL

HH

HH

HH

HLP1

LOS1

LOS1-17

HLP1-4

HLP1-4

HLP1-4

HLP1-4

HLP1-4

HLP1-4

HLP1-9

HLP1-9 HLP1-9

HLP1-2

HLP1-2 HLP1-2

HLP1-2

HLP1-2HLP1-2

HLP1-4

HLP1-2

HMP1

HMP1-25,27,29

LOS1-12

LOS1-17

LOS1-13

LOS1-15

8 9

LRP3A-65

LRP3A-62,64

HH

12 13 14 15

12 13 14 15

CONCRETE BOLLARDS BY OTHERS

SC

HLP1-4

HH

SL

HLP1-9

PC

FLGFLG

HH

TLRP1

DIRECT BURIAL CONDUIT

24" BELOW GRADE

MARKING

TAPE

FINISHED GRADE PAVING CONSTRUCTION AS

SPECIFIED BY CIVIL ENGINEER

0'

1/

" M

IN

IM

U M

6" M

IN3" CONCRETE ABOVE

AND BELOW CONDUIT

12" MINIMUM

(4 2"

M

IN

MU

M

FO

R

EL

EC

TR

IC

S

ER

VI

CE

PR

IM

AR

Y

CO

ND

UI

TS

CO

M

PA

CT

ED

ST

ON

E

BA

CK

FI

LL

DIRECT BURIAL CONDUIT

24" BELOW GRADE

MARKING

TAPE

FINISHED GRADE PAVING CONSTRUCTION AS

SPECIFIED BY CIVIL ENGINEER

12" MINIMUM

0'

1/

" M

IN

IM

U M

6" M

IN3" SAND ABOVE AND

BELOW CONDUIT

(4 2"

M

IN

MU

M

FO

R

EL

EC

TR

IC

S

ER

VI

CE

PR

IM

AR

Y

CO

ND

UI

TS

CO

M

PA

CT

ED

ST

ON

E

BA

CK

FI

LL

6'

0"

6' - 6"

1'

3" 0'

6" 0'

4"

0'

9"

1' - 6" 3' - 6" 1' - 6"

0'

6" 0'

4"

0' - 6" 0' - 4"

0' - 3" 0' - 6"

5/8" x 8'-0" GROUND ROD - TYPICAL OF 2.

COMPRESSION GROUNDING

CONNECTOR OR CADWELD.

4" DIA. GALVANIZED SCH. 40 STEEL

CONDUIT SECONDARY SERVICE (36"

RADIOUS QUARTER-BEND).

#4/0 AWG STRANDED CU GROUND LOOP.

#4/0 AWG CU TYP.

GROUND WIRE CONNECTION, TYPICAL.

4" OR 5" DIA. GALVANIZED SCH. 40 STEEL

CONDUIT PRIMARY SERVICE.

1/2" THICK SEALANT BEAD

APPLIED ALL AROUND

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

BI

M

- C on st ru ct

R ep la ce m en t O ut pa tie nt C lin ic

/0

C on st . R ep la ce . O ut pa tie nt

C lin ic

R

.rv t

2/ 9/

2:

:3

PM

E-100

ELECTRICAL SITE PLAN REPLACEMENT OUTPATIENT

CLINIC DESIGN AT COAST

GUARD CAPE COD

JOINT BASE CAPE COD, BARNSTABLE MA

650-318

BUILDING 1

02/10/2023 JFR KEM

100% CONSTRUCTION

DOCUMENTS

1/16" = 1'-0"E-100

4 SITE PLAN - ELECTRICAL

CODED NOTES:

DRAWING NOTES:

PROVIDE BAR CT CABINET AND METER SOCKET WITH 1" CONDUIT CONNECTION. SEE ONE-LINE

DIAGRAM ON SHEET E-601 FOR FURTHER INFORMATION. PROVIDE HOT DIPPED GALVANIZED

UNISTRUT SUPPORT RACK AND REQUIRED MOUNTING HARDWARE FOR MOUNTING ADJACENT TO

TRANSFORMER. VERIFY ALL TRANSFORMER CLEARANCES ARE MAINTAINED.

COORDINATE EXACT LOCATION AND AIMING OF FIXTURE IN FIELD WITH FLAG POLE HEIGHT. REFER

TO LIGHTING CONTACTOR WIRING DIAGRAM ON SHEET E-601 FOR ADDITIONAL INFORMATION.

COORDINATE EXACT LOCATION OF LIGHT POLE AND FIXTURE WITH FENCE RAILING AND CIVIL PLAN

C001 PRIOR TO CONSTRUCTION.

EMERGENCY PHONE CONNECTION. BASIS OF DESIGN: CODE BLUE CB-1-S (POE) TO BE FED FROM NEAREST CCTV POWER SUPPLY. COORDINATE ELECTRICAL REQUIREMENTS WITH FINAL EQUIPMENT

SELECTION. REFER TO T-101 DETAIL #2 FOR FURTHER INFORMATION.

FOR CONNECTION TO MEDIA CONVERTER. SEE TELECOM SHEET T-101 FOR HANDHOLE

REQUIREMENTS AND FURTHER INFORMATION.

PROVIDE 2#12 AWG + 1#12 AWG GND IN 3/4" UNDERGROUND PVC FOR PROPOSED BRANCH CIRCUIT

RUN (TOTAL CIRCUIT LENGTH~200').

PROVIDE 2#12 AWG + 1#12 AWG GND IN 3/4" UNDERGROUND PVC FOR PROPOSED BRANCH CIRCUIT

RUN (TOTAL CIRCUIT LENGTH~70').

PROVIDE 2#10 AWG + 1#10 AWG GND IN 3/4" UNDERGROUND PVC FOR PROPOSED BRANCH CIRCUIT

RUN (TOTAL CIRCUIT LENGTH~308'). CONDUCTORS ADJUSTED FOR VOLTAGE DROP.

PROVIDE 2#10 AWG + 1#10 AWG GND IN 3/4" UNDERGROUND PVC FOR PROPOSED BRANCH CIRCUIT

RUN (TOTAL CIRCUIT LENGTH~611'). CONDUCTORS ADJUSTED FOR VOLTAGE DROP.

PROVIDE 2#12 AWG + 1#12 AWG GND IN 3/4" UNDERGROUND PVC FOR PROPOSED BRANCH CIRCUIT

RUN (TOTAL CIRCUIT LENGTH~401').

PROVIDE 2#12 AWG + 1#12 AWG GND IN 3/4" UNDERGROUND PVC FOR PROPOSED BRANCH CIRCUIT

RUN (TOTAL CIRCUIT LENGTH~96').

LIFT STATION POWER CIRCUIT. PROVIDE 3#6 AWG + 1#10 AWG GND IN 1" UNDERGROUND PVC FOR

PROPOSED BRANCH CIRCUIT RUN (TOTAL CIRCUIT LENGTH~300'). CONDUCTORS ADJUSTED FOR

VOLTAGE DROP.

GENERATOR BATTERY CHARGING CIRCUIT. PROVIDE 2#10 AWG + 1#10 AWG GND IN 1"

UNDERGROUND PVC FOR PROPOSED BRANCH CIRCUIT RUN (TOTAL CIRCUIT LENGTH~300').

CONDUCTORS ADJUSTED FOR VOLTAGE DROP.

GENERATOR JACKET HEATER CIRCUIT. PROVIDE 2#4 AWG + 1#4 AWG GND IN 1-1/2" UNDERGROUND PVC FOR PROPOSED BRANCH CIRCUIT RUN (TOTAL CIRCUIT LENGTH~300'). CONDUCTORS ADJUSTED

FOR VOLTAGE DROP.

GENERATOR CONTROL CABLING IN 1" UNDERGROUND PVC CONDUIT FROM GENERATOR REMOTE

PANEL LOCATED IN ROOM 107.

APPROXIMATE LOCATION OF NEW LIFT STATION. COORDINATE EXACT LOCATION ON SITE AND WITH

CIVIL DRAWINGS PRIOR TO CONSTRUCTION.

NEW ATS FOR LIFT STATION BACKUP POWER. COORDINATE EXACT LOCATION ON SITE AND WITH

CIVIL DRAWINGS PRIOR TO CONSTRUCTION. REFER TO SHEET E-601 FOR ADDITIONAL ATS

INFORMATION.

NEW DIESEL GENERATOR FOR LIFT STATION BACKUP POWER. COORDINATE EXACT LOCATION ON

SITE AND WITH CIVIL DRAWINGS PRIOR TO CONSTRUCTION. REFER TO SHEET E-601 FOR ADDITIONAL

GENERATOR INFORMATION.

GENERATOR REMOTE EMERGENCY POWER OFF BUTTON (NEC 445.18) LOCATED IN ELECTRICAL

ROOM 161. REFER TO SHEET E-204 FOR LOCATION. SEE GENERATOR CONTROL DIAGRAM ON SHEET

E-601 FOR DETAILS.

ILLUMINATED SIGN POWER CIRCUIT. PROVIDE 2#10 AWG + 1#10 AWG GND IN 1" UNDERGROUND PVC FOR PROPOSED BRANCH CIRCUIT RUN (TOTAL CIRCUIT LENGTH~550'). CONDUCTORS ADJUSTED FOR

VOLTAGE DROP.

WALL MOUNTED SIGN LIGHT. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT WITH CIVIL

PLANS AND ARCHITECTURAL SIGN ELEVATIONS PRIOR TO CONSTRUCTION. REFER TO LIGHTING

CONTACTOR WIRING DIAGRAM ON SHEET E-601 FOR ADDITIONAL INFORMATION.

PHOTOCELL FOR CONTROL OF SIGN AND FLAG POLE LIGHT FIXTURES MOUNTED ON NORTH FACING SIDE OF BUILDING ROOF. COORDINATE EXACT LOCATION OF SENSOR IN FIELD WITH ALL OTHER TRADES PRIOR TO CONSTRUCTION. PROVIDE CABLING AS REQUIRED FOR CONNECTION TO LIGHTING

CONTACTOR. REFER TO SHEET E-601 FOR ADDITIONAL INFORMATION.

PROVIDE 2#10 AWG + 1#10 AWG GND IN 3/4" UNDERGROUND PVC FOR PROPOSED BRANCH CIRCUIT

RUN (TOTAL CIRCUIT LENGTH~500'). CONDUCTORS ADJUSTED FOR VOLTAGE DROP.

PROVIDE 12"X12"X12" PRECAST TRAFFIC RATED PULL BOX.

1. EXACT UNDERGROUND CONDUIT ROUTING INDICATED ON THIS PLAN IS DIAGRAMMATIC. FINAL

ROUTING TO BE DETERMINED IN THE FIELD AND COORDINATED WITH ALL OTHER UTILITIES.

2. COORDINATE THE INSTALLATION OF ALL NEW LIGHT POLES AND BASES WITH SITE CIVIL CONTRACTOR.

ALL UNDERGROUND WORK SHALL BE INSTALLED PRIOR TO PAVING. NO SAWCUTTING OR PATCHING

AS A RESULT OF IMPROPER COORDINATION IS PERMITTED.

3. ALL WIRE SHALL BE 600 VOLT THHN-THWN, 90 DEGREE INSULATED AND SHALL BE COPPER.

4. ALL UNDERGROUND WIRING SHALL BE RUN IN SCHEDULE 40 PVC CONDUIT AND DIRECT BURIED AT A MINIMUM DEPTH OF 36" BELOW GRADE. SEE UNDERGROUND CONDUIT DETAIL #1 ON THIS SHEET FOR

DETAIL REQUIREMENTS. SEE UNDERGROUND CONDUIT DETAIL #2 ON THIS SHEET FOR CONDUIT

ROUTED BELOW DRIVES AND PAVEMENT.

5. ALL LIGHT POLES SHALL BE MOUNTED A MINIMUM 24" FROM THE FACE OF THE CURB.

6. SEE SHEET E-101 FOR UTILITY POLE COORDINATION AND REQUIREMENTS.

N.T.S.

UNDERGROUND CONDUIT DETAIL #22

N.T.S.

UNDERGROUND CONDUIT DETAIL #11

0 8' 16' 32' 48'

1/16" = 1'-0"

N

N.T.S.

UTILITY TRANSFORMER PAD DETAIL3

C

C C

C

C

C

C

C

C

C

CCCCC

C C C C CC

C C

CCCCCCC

C C

C C

CCC

UE

U E

S

PSFMFMFMFMFMFM V

GAS

LINE POST

APPROX. GAS

MAIN

APPROX. GAS

MAIN

UP #8UP #9

UP #10

UP #601/7

CONNERY AVENUE

EXISTING UTILITY POLE #10 - TO BE RELOCATED EXISTING UTILITY POLE #9 - TO BE RELOCATED EXISTING UTILITY POLE #8 - TO REMAIN EXISTING UTILITY POLE #7 - TO REMAIN

RELOCATED UTILITY POLE #9

RELOCATED UTILITY POLE #10 1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

BI

M

- C on st ru ct

R ep la ce m en t O ut pa tie nt C lin ic

/0

C on st . R ep la ce . O ut pa tie nt

C lin ic

R

.rv t

2/ 9/

2:

:3

PM

E-101

UTILITY SITE PLAN REPLACEMENT OUTPATIENT

CLINIC DESIGN AT COAST

GUARD CAPE COD

JOINT BASE CAPE COD, BARNSTABLE MA

650-318

BUILDING 1

02/10/2023 JFR KEM

100% CONSTRUCTION

DOCUMENTS

1" = 20'-0"E-101

1 UTILITY SITE PLAN - ELECTRICAL

CODED NOTES:

DRAWING NOTES:

CONTRACTOR TO COORDINATE RELOCATION OF UTILITY POLE WITH LOCAL UTILITY. UTILITY POLE

RELOCATION WORK TO BE PERFORMED BY LOCAL UTILITY PERSONNEL.

1. COORDINATE EXACT LOCATIONS OF EXISTING UTILITY POLES PRIOR TO CONSTRUCTION.

2. CONTRACTOR TO COORDINATE ALL UTILITY POLE WORK WITH UTILITY PRIOR TO CONSTRUCTION.

0 8' 16' 32' 48'

1/16" = 1'-0"

N

R

EF

R

EF

OS OS

OS

LPP

OS

OS

LPP

LPP

OS LPD

OS

OS OS

OS

OS

OS

LPP OS

LPD

LPD

OS

OS

OSOS

OS

OS

OS

OS

OS

OS

OS

LPD

OS OS OS

OS

OSOS

OS

LPD

OS

OS

OS

OS

OS

LPD

LPD

LPP

LPP

LPD

OS

LPE

LPP LPE

LPE

LPD

LPD

LPE

LPP LPE

OS

LPD

LPE

LPE

J

H G F E D

I

VESTIBULE

WAITING

CORRIDOR

WAITING

RECEPTION

RECEPTION

WORKROOM

NURSE MANAGER

TOILET PUBLIC

TOILET PUBLIC

VOLUNTEER

CORRIDOR

SOCIAL WORKER

CLOSET

ELEC

SPECIMEN

COLLECTION

TOILET WMN'S

TOILET PATIENT

EXAM RM WOMEN'S

HEALTH

ULTRASOUND

TREATMENT

EXERCISE AREA

138 EXAM / PT/OT

EXAM / TRIAGE

PROCEDURE

ROOM, GENERAL

TOILET PROC.

TOILET STAFF

EXAM /

TELE-HEALTH

EXAM

CLOSET

151CORRIDOR

MED ROOM

TOILET STAFF

TEAM WORK AREA

EXAM/TRIAGE

EXAM / MENTAL

HEALTH

EXAM /

TELE-HEALTH

EXAM / EYE TEST

EXAM

114MULTI-PURPOSE

ROOM

MULTI-PURPOSE

ROOM

GROUP THERAPY

ROOM, MENTAL

HEALTH

CONSULT RM,

MENTAL HLTH

CONSULT RM,

MENTAL HLTH

CONSULT RM,

MENTAL HLTH

CONSULT RM,

MENTAL HLTH

CONSULT RM,

MENTAL HLTH

CONSULT RM,

MENTAL HLTH

CONSULT RM,

MENTAL HLTH

A1 A1

A1 A1

A1A1

AX4

AX4

AX4

AX4

AX4

AX4 AX4 AX4

A2 A2

A2

A2A2

A2

AX4

A1

A1

A1

A1

A1

A1

A1

A1 A1

A1

A1 A2

A1

A2

A2A2

A1

A1 A1

A2

A2

A2 A2

A2

A2 A2 A2

A2

A2 A2

A2

A1 A1

A2 A2

A1

A1 A1

A1A1

A1 A1 A1

A1

A1 A1

A1

A1 A1

A1

A1

A1 A1 A1 A1

A2 A2

A2A2

A2A2

A2 A2

A1A1A1A1

A1

A1 A2

A2 A2

A2

A1A1A1

A2 A2

A1 A2

A2

A1

A1

AX4AX4

A1

A1

A1 A1 A1A1 A1A1

A1A1

A1 A1

A1

AX4

AX4

A1 A1 A1

A1 A1 A1

A2

A2 A2

A2

A1 A1

A1 A1

AX4

AX4

AX4

A1 A1 A1

A1 A1 A1 A1

A1A1

A1

A1

A1

A1

A1 A1

A1

A1 A1

A1 A1

A1

A1

A1

A1

A1

A1

A1 A1

A1 A1 A1

A1 A1

A1

A2A2

A2 A2

A2 A2

A2A2

A1

A1

A1 A1

A1

A1 A1

A1 A1

A1 A1

A2A2

A2 A2

A1 A1 A1 A1 A1 A1

A2 A2

A2 A2

A1 A1

A2

A2 A2

A2

A1 A1

A1

A1

A1

A1A1

A1A1

A1A1

A1

A1

A1

D1

A1

D1

D1

D1

D1

D1 D1

D1

D1

D1 D1

D1

D1

D1

D1

D1

D1

D1

L1

L1

WAITING

OS

OS

OSD OSD OSD OSD OSD OSDOSD

OS

OS

OS

D1

LV1D

LV1Dn

LV1D

LV1D

LV1D

OS OS

LV1c

LV1c

LV1c

LV1c

LV1a

LV1a

OS

OS

LV1D

X2

X1

X1

X1

X2

X1

X1

X1

X2

X1

X1

X1 c c c cc c c c c cc c c c c c c c c ccc c c c c c c c c c aa a a a a a a a a a a a a a a a a a a a a a p p p b b b b b b b b b b b b b b b b b b b b b b b b b c ad ad ad p ad p ad

SL1

SL1

SL1

X1

SL1 SL1

OS

adc

PS

PS

LV1Dm c c c c c

LPDE

a a

L1

FIXTURE TYPE 'WG', ZONE 'd' (TYPICAL FOR 27) d

LV1Dd

LIGHTING PARTITION

SENSORS

LV1Dj j j j

V1 V1

V1

V1

V1

V1

V1

D D D

D

D D

D

DD

D

D n n n n nn n m m m m m m m m m mm m m

LV1Dn

D c c

LV1p pp

OSD

OS

M

AT

C H

LI

N

E -C

O N

TI

N

U

ED

O N

D W

G

/E -2

H.2 H.1 F.7 F.5 F.3 E.5 D.9 D.7 D.6 D.5 D.3 C.6 C.5 C.3

5.5

3.7 3.6

3.3

3.1

2.7

2.5

2.4

1.9

1.5

1.3

TOILET PATIENT

125 EXAM / AUDIOLOGY

d d d d j j j

LV1Dd

AX4B AX4BAX4B

AX4B

AX4B

AX4B

AX4B

g g f f h hh

SQ4

SQ4

A1

A1

A1 a a a

A1

A1 a a

L1 c f f f

LV1Df j d f

LV1D

D

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

163c

LV1Df d j j g f g f

HLP1-23 HLP1-23

HLP1-23 HLP1-23

HLP1-23 HLP1-23

HLP1-23 HLP1-23 INV-1 HLP1-23 HLP1-23 HLP1-23 INV-1 HLP1-23 HLP1-23 INV-1

HLP1-23

HLP1-23

INV-1

INV-1

m m

INV-1

INV-1 HLP1-23

HLP1-23

HLP1-23

HLP1-23HLP1-23

HLP1-23

HLP1-23HLP1-23HLP1-23INV-1HLP1-23

INV-1

INV-1

HLP1-8

INV-1

INV-1 INV-1

INV-1

INV-1

INV-1

INV-1

INV-1

INV-1

INV-1

INV-1

INV-1

INV-1

INV-1

INV-1

INV-1

INV-1

INV-1 INV-1 INV-1 INV-1

INV-1INV-1

INV-1

HLP1-23

HLP1-7HLP1-7

HLP1-7 HLP1-7

HLP1-7HLP1-7

HLP1-7HLP1-7

HLP1-7HLP1-7

HLP1-7

HLP1-7

HLP1-7 HLP1-7 HLP1-7 HLP1-7 HLP1-7

HLP1-7HLP1-7

HLP1-7 HLP1-7

HLP1-7

HLP1-7

HLP1-7 HLP1-7

HLP1-7HLP1-7

HLP1-7 HLP1-7

HLP1-7

HLP1-7

HLP1-7

HLP1-7HLP1-7HLP1-7

HLP1-7 HLP1-7

HLP1-7HLP1-7

HLP1-21HLP1-21HLP1-21

HLP1-21

HLP1-21 HLP1-21

HLP1-21 HLP1-21

INV-1

HLP1-21

HLP1-21

HLP1-21

HLP1-21

V1

HLP1-17HLP1-17

HLP1-17 HLP1-17HLP1-17

HLP1-17HLP1-17

HLP1-17HLP1-17

HLP1-17HLP1-17

HLP1-17HLP1-17

HLP1-17HLP1-17

HLP1-17HLP1-17HLP1-17

HLP1-17 HLP1-17HLP1-17

HLP1-17HLP1-17

HLP1-17

HLP1-17

HLP1-17HLP1-17

HLP1-17HLP1-17HLP1-17

HLP1-17 HLP1-17

HLP1-17HLP1-17HLP1-17HLP1-17

HLP1-17 HLP1-17 HLP1-17

HLP1-17HLP1-17HLP1-17HLP1-17

A1

HLP1-17 HLP1-17 HLP1-17

HLP1-17HLP1-17

HLP1-17 HLP1-17

HLP1-17HLP1-17

HLP1-17 HLP1-17

HLP1-19

HLP1-19 HLP1-19

HLP1-19 HLP1-19

HLP1-19 HLP1-19

HLP1-19 HLP1-19

HLP1-19 HLP1-19

HLP1-19

HLP1-19

HLP1-19

HLP1-19

HLP1-19

HLP1-19 HLP1-19

HLP1-19 HLP1-19

HLP1-19 HLP1-19

HLP1-19

HLP1-19

HLP1-19 HLP1-19

HLP1-19

HLP1-19 HLP1-19

HLP1-19 HLP1-19

HLP1-19

HLP1-5

HLP1-5

HLP1-5

HLP1-5

HLP1-5

HLP1-5

HLP1-5

HLP1-5

HLP1-5

HLP1-5

HLP1-5

HLP1-5

HLP1-5 HLP1-5

HLP1-5

HLP1-5

HLP1-5 HLP1-5

HLP1-5

HLP1-5

HLP1-5

HLP1-5

HLP1-5

HLP1-5

HLP1-5 HLP1-5

HLP1-5 HLP1-5

HLP1-5 HLP1-5

HLP1-5

HLP1-5

HLP1-19 HLP1-19

HLP1-19HLP1-19

HLP1-5

HLP1-5

HLP1-5

HLP1-5

HLP1-5

INV-1HLP1-8INV-1

HLP1-8

HLP1-8

HLP1-8

HLP1-8

HLP1-8

HLP1-8

HLP1-8

HLP1-8

HLP1-8

HLP1-8

HLP1-8

HLP1-8 HLP1-8 HLP1-8 HLP1-8 HLP1-8 HLP1-8 HLP1-8

HLP1-8

INV-1

HLP1-8

HLP1-8

HLP1-8

HLP1-8

HLP1-8

HLP1-19

HLP1-19

HLP1-19

HLP1-19

CLOSET

HLP1-8 HLP1-8

HLP1-8

HLP1-8

HLP1-8

HLP1-8 HLP1-8 HLP1-8 HLP1-8 HLP1-8 HLP1-8

HLP1-6HLP1-6

HLP1-6HLP1-6

HLP1-6

HLP1-6

INV-2

h

P1

P1

P1

P1

P1j j j d d

AX4

b h

HLP1-8

HLP1-5 HLP1-5

HLP1-5

HLP1-5

HLP1-5

OS

SQ4

INV-2

SQ4SQ4

SQ4

SQ4

SQ4

SQ4

HLP1-6HLP1-6

HLP1-6

HLP1-6

HLP1-6

HLP1-6

3 333

X1

INV-1

1 SL HLP1-6

A1 aHLP1-23

A1 aHLP1-23 m nn c

X2

HLP1-8

X2

X2

INV-1 INV-1

INV-1

LV1b

LV1b

LV1b

LV1b

LV1h

LV1g

LV1f

C1 C1

HLP1-5HLP1-5

b

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

BI

M

- C on st ru ct

R ep la ce m en t O ut pa tie nt C lin ic

/0

C on st . R ep la ce . O ut pa tie nt

C lin ic

R

.rv t

2/ 9/

2:

:4

PM

E-201

PARTIAL FIRST FLOOR PLAN -

ELEC. LIGHTING - WEST

REPLACEMENT OUTPATIENT

CLINIC DESIGN AT COAST

GUARD CAPE COD

JOINT BASE CAPE COD, BARNSTABLE MA

650-318

BUILDING 1

02/10/2023 JFR KEM

100% CONSTRUCTION

DOCUMENTS

0 4' 8' 12' 16'

3/16" = 1'-0"

N

3/16" = 1'-0"E-201

1 FIRST FLOOR PLAN - ELEC. LIGHTING PLAN - WEST

CODED NOTES:

EXTERIOR LIGHTING FIXTURES SHALL BE CONTROLLED WITH AREA SITE LIGHTING WITH SWITCHPACK

TO BE WAVELINX PRO WSP-UV-010.

EXTERIOR LIGHTING FIXTURES SHALL BE CONTROLLED WITH AREA SITE LIGHTING WITH UL924 LIFE

SAFETY SWITCHPACK TO BE WAVELINX PRO WSP-UV-010-EM.

ALIGN FIXTURE IN CEILING PLANKS.

PROVIDE JUNCTION BOX AND 3/4" CONDUIT WITH PULLWIRE UP TO ACCESSIBLE CEILING SPACE FOR LOW VOLTAGE PROCEDURE LIGHT CONTROL. SEE FIXTURE TYPE C1 IN LIGHTING FIXTURE SCHEDULE

FOR FURTHER DETAILS.

DRAWING NOTES:

1. LIFE SAFETY LIGHTING SHALL BE CONNECTED TO A CENTRAL BATTERY INVERTER. ALL LIGHTING

FIXTURES SHALL BE CONTROLLED BY LOCAL LIGHTING CONTROLS.

REF.

OS OS

OS

OS

OS OS

OS

OS

LPD

LPD

OS

LPD

LPP

LPP

LPP

LPE

LPE

LPE LPP

LPE

C B A

OFFICE

UTILITY SOILED

MECHANICAL

162JANITOR CLOSET

WORKSTATIONS,

MENTAL HEALTH

STAFF LOUNGE &

LOCKERS

STORAGE MEDICAL

& GENERAL

TLMP1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A2

A2 A2

A2

A2

A2

A2 A2 A2

A2A2 A2

L2

L2

A1 A1

A1 A1

A1

A1

A1

A1

A1

A1

A1

A1A1

A1

A1A1

L1

L1

L1

L1

L1 L1

OS

k k k k k k k kk k

LV1D LV1D

LV1a

X2

X1 a a a a a a a a p p ad a p

SL1

SL1

SL1

OS

OFFICE

OS

UTILITY CLEAN

LV1

ELECTRICAL ROOM

L1

LV1

LV1

LV1Dk

L2

M

AT

C H

LI

N

E -C

O N

TI

N

U

ED

O N

D W

G

/E -2

B.7 A.4

5.5

3.7

3.6

3.3

3.1

2.7

2.5

2.4

1.9

1.5

1.3

SL1

SQ4

LV1

LV1

L1 L1 L1

L1 L1 L1

A1

A1 A1

INV-1

HLP1-1

INV-1

HLP1-1 HLP1-1HLP1-1HLP1-1

HLP1-23 INV-1

HLP1-1 HLP1-1

INV-1

HLP1-1

HLP1-1

HLP1-1 HLP1-1 HLP1-1

HLP1-1

HLP1-1

HLP1-1

HLP1-1

HLP1-1

HLP1-1

HLP1-23

HLP1-23

HLP1-23

HLP1-23

HLP1-23

HLP1-1

HLP1-1

HLP1-1

INV-1

HLP1-1

HLP1-1 HLP1-1

HLP1-1

HLP1-1

HLP1-1 INV-1

HLP1-1 HLP1-1

HLP1-1

HLP1-1 HLP1-1 HLP1-1 HLP1-1

HLP1-1HLP1-1HLP1-1HLP1-1

INV-1

INV-1

INV-1

INV-1

INV-1

INV-1

INV-1

INV-1

HLP1-6

HLP1-6

HLP1-6

HLP1-6

INV-2

LRP2A

LRP1A

LMP1

UPS

LOS1

TLRP1

TLRP2

HMP1

HLP1

MDP

SL2

SL2

INV-2

INV-2

COMMUNICATIONS

L2

HLP1-1

a

A1

HLP1-23

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

BI

M

- C on st ru ct

R ep la ce m en t O ut pa tie nt C lin ic

/0

C on st . R ep la ce . O ut pa tie nt

C lin ic

R

.rv t

2/ 9/

2:

:5

PM

E-202

PARTIAL FIRST FLOOR PLAN -

ELEC. LIGHTING - EAST

REPLACEMENT OUTPATIENT

CLINIC DESIGN AT COAST

GUARD CAPE COD

JOINT BASE CAPE COD, BARNSTABLE MA

650-318

BUILDING 1

02/10/2023 JFR KEM

100% CONSTRUCTION

DOCUMENTS

3/16" = 1'-0"E-202

1 FIRST FLOOR PLAN - ELEC. LIGHTING PLAN - EAST

CODED NOTES:

EXTERIOR LIGHTING FIXTURES SHALL BE CONTROLLED WITH AREA SITE LIGHTING WITH SWITCHPACK

TO BE WAVELINX PRO WSP-UV-010 OR EQUAL.

EXTERIOR LIGHTING FIXTURES SHALL BE CONTROLLED WITH AREA SITE LIGHTING WITH UL924 LIFE

SAFETY SWITCHPACK TO BE WAVELINX PRO WSP-UV-010-EM OR EQUAL.

WIRELESS CONTROL GATEWAY TO CONTROL EXTERIOR LIGHTING. SEE LUMINAIRE SCHEDULE

NOTE 6 ON SHEET E-801.

BATTERY LIGHTING INVERTER INV. REFER TO ONE-LINE DIAGRAM ON SHEET E-601 FOR FURTHER

INFORMATION.

DRAWING NOTES:

0 4' 8' 12' 16'

3/16" = 1'-0"

N

1. LIFE SAFETY LIGHTING SHALL BE CONNECTED TO A CENTRAL BATTERY INVERTER. ALL LIGHTING

FIXTURES SHALL BE CONTROLLED BY LOCAL LIGHTING CONTROLS.

R

EF

R

EF

J

J

J

J

J

J

J J

J

J

M

J

J

J

J J

J

J

J

J J

J

J

J

J

J J

J J

J

J

J

J

J

J JJ J

J J

J

J

J

J

J

J

J

J

J

J

J

J

J J

JJ

J

J J

JJ

J J

J

J

J

J J J J J J J

J

JJ

J

J

J

J

J

J

J J

J

J

J

J

J

J

J

J

J J

JJ

J

H G F E D

I

VESTIBULE

WAITING

CORRIDOR

WAITING

105 RECEPTION

RECEPTION

WORKROOM

NURSE MANAGER

TOILET PUBLIC

TOILET PUBLIC

VOLUNTEER

CORRIDOR

SOCIAL WORKER

CLOSET

ELEC

SPECIMEN

COLLECTION

TOILET WMN'S

TOILET PATIENT

EXAM RM WOMEN'S

HEALTH

ULTRASOUND

TREATMENT

EXERCISE AREA

EXAM / PT/OT

EXAM / TRIAGE

PROCEDURE

ROOM, GENERAL

TOILET PROC.

TOILET STAFF

EXAM /

TELE-HEALTH

EXAM

CLOSET

CORRIDOR

MED ROOM

TOILET STAFF

TEAM WORK AREA

EXAM/TRIAGE

EXAM / MENTAL

HEALTH

EXAM /

TELE-HEALTH

EXAM / AUDIOLOGY

EXAM / EYE TEST

EXAM

MULTI-PURPOSE

ROOM

MULTI-PURPOSE

ROOM

GROUP THERAPY

ROOM, MENTAL

HEALTH

CONSULT RM,

MENTAL HLTH

CONSULT RM,

MENTAL HLTH

CONSULT RM,

MENTAL HLTH

CONSULT RM,

MENTAL HLTH

CONSULT RM,

MENTAL HLTH

CONSULT RM,

MENTAL HLTH

CONSULT RM,

MENTAL HLTH

LRP3A

G,48"

G

G,CH

G,48" G,48"G,48"

G,+48"

TV,60"

TV,60"

G

G,CH G,CH

G

G,CH

G

G,CH

G

G,CH

G

G,CH

G

G,CH

G

FACP

G,44"

G,48"

G,48"

G,+48"

G,+48"

CH

CH

+48",G

44",G

+48",G

44",G

+36"

G

G,CH

G,+48"

CH,G

CH,G

G,36"

+48"

TV,G,60"

G,44"

+36",G

G

+48"

44",G

+36"

G,48"

7 7 7

9 9

+48"

48"

USB

USBUSB

USB

M

AT

C H

LI

N

E -C

O N

TI

N

U

ED

O N

D W

G

/E -2

H.2 H.1 F.7 F.5 F.3 E.5 D.9 D.7 D.6 D.5 D.3 C.6 C.5 C.3

5.5

3.7

3.6

3.3

3.1

2.7

2.5

2.4

1.9

1.5

1.3

USB

44",G

G,44"

TOILET PATIENT

+60"

44"

15 15

LOS1-3

LRP3A-37

LRP3B-10

LRP3B-10

LRP3B-10

LRP3A-18

LRP3A-18

LRP3A-31

LRP3A-23

LRP3A-23

LRP3A-23

LRP3A-20 LRP3A-20

LRP3A-20

LRP3A-20

LRP3A-14

LRP3A-14

LRP3A-14

LRP3A-14

LRP3A-7

LRP3A-28

LRP3B-20 LRP3B-20

LRP3A-28

LRP3A-23

LRP3A-31

LRP3B-20

LRP3A-28

LRP2B-4

LRP3B-21

LRP3A-28

LRP2B-4

LRP3B-21

LRP3A-31

LRP2B-6

LRP3B-21

LRP2B-4

LRP2B-8

LRP2B-5

LRP2B-4

LRP3B-3

LRP3B-3

LRP3A-16 LRP3A-17

LRP3A-12

LRP3A-12

LRP3A-42

LRP3A-43

LRP3A-42

LRP3A-53

LRP3A-54

LRP3A-53

LRP3A-50

LRP3A-50

LRP3A-49

LRP2B-13

LRP2B-13

LRP2B-14LRP3A-31 LRP2B-7LRP3A-34

LRP3A-32

LRP2B-10LRP3A-33

LRP3A-33

LRP3A-26

LRP3A-26

LRP3A-25

LRP3A-12

LRP3A-11

LRP3A-44

LRP3A-45

LRP3A-46 LRP3A-46

LRP3A-45 LRP3A-45

LRP3A-61,63

LRP3A-46

LRP2B-12

LRP2B-11

LRP2B-11

LRP2B-11

LRP3A-52

LRP3A-52

LRP3A-51

LRP3A-38

LRP3A-36

LRP3A-38

LRP3A-37

LRP3A-37

LRP3B-11

LRP3A-17

LRP3A-17

LRP3A-14

LRP3B-4

LRP3A-17

LRP3A-35

LRP3A-35LRP3A-35

LRP3A-17

LRP3A-37

LRP3A-47

LRP3A-47LRP3A-37LRP3A-37

LRP3A-35LRP3A-35

LRP2B-11

LRP3A-6

LRP3A-7

LRP3A-7

LOS1-1

LRP3B-2 LRP3A-44

LRP3A-18

LRP2B-6

LRP2B-8

LRP3A-46

LRP3A-44

LRP3A-44

LRP3A-45

LRP3A-44

LRP3A-43

LOS1-2

LRP3A-17

LRP3A-48

LRP3A-5

LRP3A-18

LRP3A-7

LRP3A-4

LRP3A-4

LRP3A-4

LRP3A-5

LRP3A-5

LRP3A-1

LRP3A-2

LRP3A-2

LRP3A-2 LRP3A-2

LRP3A-6

LRP3A-8 LRP3A-8

LRP3A-8

LRP3A-8

LRP3A-8

LRP3A-9

LRP3A-10 LRP3A-10

LRP3A-10

LRP3A-10

LRP3A-12

LOS1-7

LOS1-6

LOS1-6

LOS1-6

LOS1-9

LRP3A-13

LRP3A-15

LOS1-6

LOS1-7

LOS1-7

LOS1-7

LOS1-6

LOS1-7

LOS1-8

LOS1-9

LOS1-8

CORRIDOR

LOS1-6

LRP3A-13

ALCOVE, SCALE

LOS1-2

LOS1-4

LRP3A-19 LRP3A-19

LRP3A-19

LRP3A-19

LRP3A-19

LRP3A-22

LRP3A-24

TV,60"

LRP3A-22

LRP3A-24

LRP3A-26

+36"

+36" +36"

+36" +48",G

+36"

LRP3A-38

+48"

+36"

LRP3A-33

LRP3A-27

+36" +36" +36"

CH,G

CH

CH,G

LRP3A-27 LRP3A-27 LRP3A-27 LRP2B-9 LRP2B-9 LRP2B-9 LRP2B-9

LRP2B-10

LRP3A-27

LRP3A-29 LRP3A-29 LRP3A-29

LRP3A-36

LRP3A-36

LRP3A-39

LRP3A-39

LRP3A-39

LRP3A-39

LRP3A-40

LRP3A-41

+36"

+48"

LRP3A-43

LRP3A-33

LRP3A-52

LRP3A-52

LRP3A-47

LRP3A-47

LRP3A-53

LRP3A-53

LRP3A-50

LRP3A-50

LRP2B-13

LRP2B-13

LRP2B-9

LRP2B-10

LRP2B-5LRP2B-5LRP2B-3LRP2B-3

MS-EPAR

LRP3A-56

LRP3A-55

+48"

+48" +48"

LRP3A-58

+48"

LRP3A-57

LRP2B-1

LRP3A-60

LRP3A-59

LRP3A-6

LRP3A-6

+48"

+48"

LRP3B-7

+48"+48"

+48" +48"

LRP3B-8LRP3B-9

+48"

+48"

LRP2B-2

+48" +48"

+48"

LRP3B-611

+48"

+48"

LRP3B-5

LRP3B-4 LRP3B-4

LRP3B-3

LRP3B-3

LRP3B-4

LRP3B-4

LRP3B-2

+48"

LRP3B

LRP3B-12

+48"

LRP3B-12

+48"

TV,72"

LRP3A-2

LRP3A-24

TV,72"

LRP3A-1

USB

LRP3A-1

44"

LRP3A-6

G,44"

LRP3A-10

+48"

LRP3A-3

LRP3A-30

G,CH

LRP3A-12

+48"

+48"

LRP3B-1

+48"+48"

LRP3B-13

LRP3B-14

LRP3B-15 LRP3B-15

LRP3B-15 23

23 23

LRP3B-14

LRP3B-14 23

LRP3B-14

LRP3B-26

23 LRP3B-16

LRP3B-16 LRP3B-16 LRP3B-1623 23 23 LRP3B-17 LRP3B-17 LRP3B-17 LRP3B-17

LRP3B-18

LRP3B-18

LRP3B-18 23

LRP3B-19 24

LRP3B-23

LRP3B-23

LRP3B-23

LRP3B-24

20LRP3B-24

CH LRP2B-11

LRP3B-26

LRP3B-1623

23 23 23 23

LRP3B-18

LRP3B-27 23LRP3B-27 23

LRP3B-28

LRP3B-28

LRP3B-28

LRP3B-28

LRP3B-28 23

LRP3B-29

LRP3B-29

LRP3B-29

LRP3B-29 23

LRP3B-30LRP3B-30

LRP3B-30LRP3B-30

23 23

LRP1B-9,1110

LRP2A-1

LRP2A-5 LRP2A-6

LRP2A-4 LRP2A-3

LRP2A-7 LRP2A-8

LRP2A-2

G,WP

G,WP

G,WP

LRP1B-10

LRP1B-10

LRP1B-10

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

BI

M

- C on st ru ct

R ep la ce m en t O ut pa tie nt C lin ic

/0

C on st . R ep la ce . O ut pa tie nt

C lin ic

R

.rv t

2/ 9/

2:

:0

PM

E-203

PARTIAL FIRST FLOOR PLAN -

ELEC. POWER - WEST

REPLACEMENT OUTPATIENT

CLINIC DESIGN AT COAST

GUARD CAPE COD

JOINT BASE CAPE COD, BARNSTABLE MA

650-318

BUILDING 1

02/10/2023 JFR KEM

100% CONSTRUCTION

DOCUMENTS

CODED NOTES:

REFRIGERATOR - 120V, 1.0KW ASSUMED. WIRE TO 20/1 POLE GFCI BRANCH CIRCUIT BREAKER

INDICATED.

COPIER - 120V, 1.5KW ASSUMED.

NOTE REMOVED.

NOTE REMOVED.

MEDICATION DISPENSING SYSTEM AND REFRIGERATOR - 120V, 1.0KW ASSUMED.

EXAM CHAIR - 120V, 1.5KW ASSUMED.

PROVIDE RECESSED IN-GRADE 4-GANG RECTANGULAR FLOOR BOX (HUBBELL #AFB4G50), 5.5" DEEP

MINIMUM, UL514A SCRUBSHIELD COMPLIANT, BLACK POWER COATED COVER (HUBBELL #

4GAFBCVRBK), (2) DUPLEX PLATES (HUBBELL #FBMPDUP), (2) TELEDATA KEYSTONE JACK PLATES (HUBBELL #FBMP6KS) AND ALL PARTS AND ACCESSORIES FOR A COMPLETE SYSTEM. EQUALS BY FSR OR WIREMOLD. PROVIDE (1) 1" CONDUIT WITH PULLWIRE TO ACCESSIBLE CEILING SPACE FOR

DATA/AV CABLING BY OTHERS.

PROVIDE 120V POWER FOR WATER FOUNTAIN WITH BOTTLE FILLER - 120V, 1.0 AMPERE, 0.12KW.

WIRE TO 20/1 GFCI BRANCH CIRCUIT BREAKER INDICATED. COORDINATE WITH FOUNTAIN INSTALLER

FOR MOUNTING LOCATION.

PROVIDE RECESSED IN-GRADE 2-GANG RECTANGULAR FLOOR BOX (HUBBELL #AFB2G50), 5" DEEP

MINIMUM, UL514A SCRUBSHIELD COMPLIANT, BLACK POWER COATED COVER (HUBBELL #

2GAFBCVRBK), DUPLEX PLATE (HUBBELL #FBMPDUP), TELEDATA KEYSTONE JACK PLATE (HUBBELL

#FBMP6KS) AND ALL PARTS AND ACCESSORIES FOR A COMPLETE SYSTEM. EQUALS BY FSR OR

WIREMOLD. PROVIDE (1) 1" CONDUIT WITH PULLWIRE TO ACCESSIBLE CEILING SPACE FOR DATA/AV

CABLING BY OTHERS.

JUNCTION BOX FOR FUTURE X-RAY. PROVIDE (2) #12AWG CU, #12AWG CU GROUND IN 3/4" CONDUIT

TO LOCATION SHOWN. CONTRACTOR TO LABEL JUNCTION FOR FUTURE X-RAY USE.

MOTORIZED DOOR WITH PUSH PAD CONTROLS BY GENERAL CONTRACTOR. ELECTRICAL

CONTRACTOR TO INSTALL ALL POWER AND CONTROL WIRING AND MOUNT PUSH PAD CONTROL

STATIONS. ALL CONDUIT AND WIRING MUST BE CONCEALED. COORDINATE EXACT PUSH PAD

LOCATIONS WITH OWNER PRIOR TO ROUGH-IN.

ELECTRICAL CONNECTION FOR PATIENT LIFT. COORDINATE EXACT LOCATION AND MOUNTING

HEIGHT WITH PATIENT LIFT PRIOR TO CONSTRUCTION.

POWERED PARTITION CONTROLS. COORDINATE EXACT LOCATION AND INSTALLATION

REQUIREMENTS WITH POWERED PARTITION INSTALLATION INSTRUCTIONS. PROVIDE BACK BOX AND

3/4" CONDUIT WITH PULL STRING TO ABOVE ACCESSIBLE CEILING FOR POWERED PARTITION

CONTROL CABLING.

SAFETY DISCONNECT FOR POWERED PARTITION MOUNTED AT 7'-0" AFF. COORDINATE EXACT

LOCATION OF DISCONNECT WITH POWERED PARTITION CLEARANCES.

PROVIDE 120V JUNCTION BOX ABOVE ACCESSIBLE CEILING ON SECURE SIDE OF DOOR FOR ACCESS

CONTROL HARDWARE. PROVIDE LABEL STATING "ACCESS CONTROL 120V" AND CONNECT TO

BRANCH CIRCUIT BREAKER INDICATED WITH LOCK-ON ACCESSORY.

GENERATOR REMOTE ANNUNCIATOR PANEL. SEE GENERATOR CONTROL DIAGRAM ON SHEET E-601

FOR DETAILS. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT WITH VA PRIOR TO

CONSTRUCTION.

DUPLEX OUTLET FOR MINI FRIG LOCATED BELOW COUNTER. COORDINATE EXACT LOCATION AND

MOUNTING HEIGHT OF RECEPTACLE WITH MILL WORK PRIOR TO CONSTRUCTION. RECEPTACLE TO

BE CONNECTED TO GFCI TYPE BREAKER.

CONDUIT ROUTED BELOW SLAB TO NEAREST FULL HEIGHT WALL.

ULTRASOUND MACHINE OUTLET. COORDINATE EXACT LOCATION WITH ARCHITECTURAL EQUIPMENT

LAYOUT PRIOR TO CONSTRUCTION.

AED CABINET - 120V, 0.5KW ASSUMED.

SHREDDER - 120V, 0.5KW ASSUMED.

E.C. TO…