Attachment 17 - Electrical 1 of 2.pdf
PDF 5 MB Posted
- Solicitation number
- 36C77624R0087
About this file
This document is an electrical attachment for a federal contract opportunity related to the construction of a replacement outpatient clinic. It includes electrical legends, symbols, general notes, site plans, lighting plans, power plans, and equipment plans for the new clinic facility.
The key details include:
- The project is for a new outpatient clinic to be located at the US Coast Guard Air Station in Barnstable, MA.
- The electrical work includes site work, underground utilities, lighting, power distribution, and specialized equipment connections.
- The drawings provide detailed information on electrical fixtures, devices, raceways, panels, and other systems required for the new clinic.
- The general notes cover applicable codes, coordination requirements, installation standards, and other electrical design and construction guidelines.
- The solicitation number is 36C77624R0087 and the project title is "Y1DZ--VHA Minor Construction - Project 650-318 - New Otis CBOC for Providence VAMC".
View the file
Other files
Show all 46
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1PH SINGLE-PHASE
3PH THREE-PHASE
4W FOUR-WIRE
A/E ARCHITECT/ENGINEER
AF AMPERE FRAME OR AMP FUSE
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMP AMPERE
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BLDG BUILDING
C CONDUIT
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CKT CIRCUIT
CLG CEILING
COAX COAX CABLE
COMM COMMUNICATION
CONC CONCRETE
CONT CONTINUE
COORD COORDINATE
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CU COPPER
DB DECIBEL OR DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DISC DISCONNECT
DN DOWN
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DS DISCONNECT SWITCH
DWG DRAWING
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
ESMT EASEMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
ETR EXISTING TO REMAIN
ELECTRICAL ABBREVIATIONS
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FLA FULL LOAD AMPS
FP FIRE PROTECTION
FT FEET OR FOOT
GND GROUND
G or GFCI GROUND FAULT CIRCUIT INTERRUPTER
GTB GROUND TERMINAL BOX
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HZ HERTZ
IESNA ILLUMINATION ENGINEERING SOCIETY OF NORTH AMERICA
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
kV KILOVOLT kVA KILOVOLT AMPERE kVAH KILOVOLT AMPERE PER HOUR kVAR KILOVOLT AMPERE REACTIVE kW KILOWATT kWH KILOWATT HOUR
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LM LUMEN
LP LIGHT POLE
LRA LOCKED ROTOR AMPS
LTG LIGHTING
LV LOW VOLTAGE
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MH MANHOLE
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
MLO MAIN LUGS ONLY
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT MICROWAVE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NEUT OR N NEUTRAL
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OL OVERLOAD
P POLE
PA PUBLIC ADDRESS
PCB POLYCHLORINATED BIPHENYL
PH PHASE
PNL PANEL
POD POWER OPERATED DAMPER
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
RCP REFLECTED CEILING PLAN
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
REQD REQUIRED
SCC SHORT CIRCUIT CAPACITY
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
W WATT
WH WATER HEATER
WP WEATHERPROOF
XFER TRANSFER
XFMR TRANSFORMER
ABBR. DESCRIPTION ABBR. DESCRIPTION ABBR. DESCRIPTION
AWG AMERICAN WIRE GAUGE
KCMIL ONE-THOUSAND CIRCULAR MILS
NA NOT APPLICABLE
HD HEAT DETECTOR
MOTOR CONNECTION
TEE SPLICE
FOUR-WAY SPLICE
ABC
PANELBOARD MAIN CIRCUIT BREAKER TYPE, ONE-LINE
### - INDICATES BREAKER RATING
ABC - INDICATES PANEL DESIGNATION
ABC
PANELBOARD MAIN LUG TYPE, ONE-LINE
### - INDICATES BUS RATING
ABC - INDICATES PANEL DESIGNATION
###A CIRCUIT BREAKER
### - INDICATES BREAKER RATING
GND GROUND BUS BAR
DN
DN
THRU-ROOF CONDUCTOR
DOWN CONDUCTOR
GROUND TERMINAL
AIR TERMINAL; PROVIDE PARAPET TYPE BASE WHERE MOUNTED ON PARAPET;
PROVIDE FLAT BASE FOR MECHANICAL EQUIPMENT OR ROOF PERIMETER WITH NO
PARAPET; PROVIDE BLUNT TIP WHERE MOUNTED ON INTERIOR OF ROOF, UNLESS
OTHERWISE NOTED ON LIGHTNING PROTECTION PLANS
BONDING PLATE
LIGHTNING PROTECTION SYSTEM
DISCONNECT SWITCH, FUSED
DISCONNECT SWITCH, UNFUSED
STARTER, COMBINATION WITH DISCONNECT SWITCH
STARTER OR MOTOR CONTROLLER
JUNCTION BOX
EARTH GROUND
RECEPTACLE, DUPLEX
RECEPTACLE, DOUBLE DUPLEX (QUADRAPLEX)
RECEPTACLE, SPECIAL PURPOSE, SEE CODED NOTES ON FLOOR PLANS FOR NEMA CONFIGURATION AND WIRING
REQUIREMENTS
ELECTRICAL SYMBOLS - POWER/LIGHTING PLANS
SWITCH (# SUBSCRIPT AS INDICATED BELOW) - SEE PLANS AND SPECIFICATIONS FOR DETAILS
BLANK = SINGLE POLE P = WITH PILOT LIGHT
WP= WEATHER PROOF
OS= DUAL TECHNOLOGY OCCUPANCY SENSOR
OSD = DUAL TECHNOLOGY OCCUPANCY SENSOR WITH DIMMING
a= SUBSCRIPT DEFINES FIXTURES THAT ARE CONTROLLED BY SWITCH
3 = THREE-WAY
D = DIMMER
LV= LOW VOLTAGE - SEE BELOW FOR DETAILS
M = MOTOR SNAP WITH PILOT LIGHT
(THERMAL TYPE)
LIGHT POLE, ONE LUMINAIRE
LIGHTING, EXTERIOR BUILDING
LIGHT POLE, TWO LUMINAIRES
J
SYMBOL DESCRIPTION DESCRIPTION
ALARM, FIRE, PANEL; LETTERS INDICATE AS FOLLOWS:
FACP = CONTROL PANEL
FAAP = ANNUNCIATOR PANEL
FACP
DESCRIPTION
SUBSCRIPTS (TYPICAL FOR ALL RECEPTACLES):
G = GFCI TYPE
T = TAMPER RESISTANT
CH = MOUNTED AT COUNTER HEIGHT WITH BOTTOM OF DEVICE AT 6" ABOVE BACKSPLASH
TV = RECEPTACLE MOUNTED ADJACENT TO TV OUTLET
USB = DUPLEX RECEPTACLE WITH (1) USB TYPE 'A' AND (1) USB TYPE 'C'
WP = DEVICE PROVIDED WITH WEATHERPROOF IN-USE METAL COVER
EWC = DENOTES DEVICE FOR ELECTRIC WATER COOLER - COORDINATE WITH EWC INSTALLER FOR
MOUNTING HEIGHT
a = LOWER CASE LETTER INDICATES RELAY POWER PACK FOR RECEPTACLE CONTROL
E = RED DEVICE, FED FROM UPS-FED BRANCH CIRCUIT
TRANSFORMER, PLANT
TRANSFORMER, ONE-LINE
FUSIBLE DISCONNECT SWITCH, ONE-LINE
###AF - INDICATES FUSE RATING
###AS - INDICATED SWITCH RATING
###AF
M
ABC
BRANCH CIRCUIT PANELBOARD, OVER 250 VOLTS, SURFACE MOUNTED
BRANCH CIRCUIT PANELBOARD, UNDER 250 VOLTS, SURFACE MOUNTED
SWITCHBOARD/ SWITCHGEAR/ DISTRIBUTION PANEL - OVER 250 VOLTS LOW VOLTAGE SWITCH - SEE PLANS, SPECIFICATIONS AND WIRING DIAGRAMS FOR DETAILS LV2Dab
S
S
SUBSCRIPT(S) INDICATE FIXTURES CONTROLLED
'D' INDICATES 0-10V DIMMING
'2' INDICATES NUMBER OF LIGHTING CONTROL ZONES
'LV' INDICATES LOW VOLTAGE SWITCH
VFD VARIABLE FREQUENCY DRIVE
A
EXIT LIGHT, LED, WALL MOUNTED
EXIT LIGHT, LED, CEILING OR PENDANT MOUNTED; DIRECTIONAL ARROWS AS
INDICATED; SHADED QUADRANT INDICATES FACE(S) OF LUMINAIRE
LED, RECESSED, PENDANT OR SURFACE CEILING LUMINAIRE
LED, RECESSED, PENDANT OR SURFACE CEILING LIGHTING FIXTURE
SHADING INDICATES FIXTURE CONNECTED TO EMERGENCY
CIRCUIT. (TYPICAL FOR ALL LIGHT FIXTURE SYMBOLS)
LED FIXTURE, RECESSED, PENDANT OR SURFACE CEILING
LED STRIP LUMINAIRE
FIXTURE TYPE
LOWER CASE LETTER INDICATES CONTROLLING SWITCHa
CIRCUIT NUMBER
LED, WALL MOUNTED LUMINAIRE
DN
UP
CONDUIT CONTINUED
CONDUIT STUBBED OUT OR UP
CONDUIT TURNING DOWN
CONDUIT TURNING UP
PUSHBUTTON STATION
MULTI-SERVICE FLOOR BOX WITH DUPLEX RECEPTACLE, VOICE/DATA/AV DEVICES (REFER TO TECHNOLOGY
DRAWINGS OR OWNER'S VENDOR DRAWINGS FOR LOW VOLTAGE REQUIREMENTS)
CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOROS
GROUND BUS BAR, COPPER
SPD SURGE PROTECTIVE DEVICE
FLOOR BOX WITH DUPLEX RECEPTACLE WITH APPROPRIATE FLANGE
FLOOR BOX, TWO DUPLEX RECEPTACLES (QUAD) WITH APPROPRIATE FLANGE
SYMBOL SYMBOL
WALL MOUNTED JUNCTION BOXJ
LPP LIGHTING POWER PACK RELAY
a
SUBSCRIPT INDICATES CONTROLLING SWITCH AND FIXTURES CONTROLLED (TYPICAL)
LPD LIGHTING POWER PACK RELAY WITH 0-10V DIMMING
LPE EMERGENCY LIGHTING POWER PACK RELAY - UL924 COMPLIANT
LPDE EMERGENCY LIGHTING POWER PACK RELAY - UL924 COMPLIANT AND 0-10V DIMMING
DOUBLE TUB PANELBOARD, ONE-LINE
ABC - INDICATES PANEL DESIGNATION
###AS
METER, ONE-LINE
UNINTERRUPTIBLE POWER SUPPLY (UPS) OR LIGHTING INVERTER, ONE-LINE
ELECTRICAL ONE-LINE
###A BRANCH CIRCUIT BREAKER
### - INDICATES BREAKER RATING
WALL SCONCE, EXTERIOR BUILDING
LRP1-1 BRANCH CIRCUIT NUMBER THAT SERVES DEVICE
PANEL THAT SERVES DEVICE
HANDHOLEHH
ROOF MOUNTED PHOTO CELL FOR LIGHTING CONTROLPC
MULTI-SERVICE FLOOR BOX WITH TWO DUPLEX RECEPTACLE, TWO VOICE/DATA/AV DEVICES (REFER TO
TECHNOLOGY DRAWINGS OR OWNER'S VENDOR DRAWINGS FOR LOW VOLTAGE REQUIREMENTS)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
BI
M
- C on st ru ct
R ep la ce m en t O ut pa tie nt C lin ic
/0
C on st . R ep la ce . O ut pa tie nt
C lin ic
R
.rv t
2/ 9/
2:
:2
PM
E-001
ELECTRICAL LEGENDS &
SYMBOLS
REPLACEMENT OUTPATIENT
CLINIC DESIGN AT COAST
GUARD CAPE COD
JOINT BASE CAPE COD, BARNSTABLE MA
650-318
BUILDING 1
02/10/2023 JFR KEM
100% CONSTRUCTION
DOCUMENTS
SHEET LIST
Sheet Number Sheet Name
E-001 ELECTRICAL LEGENDS & SYMBOLS
E-002 ELECTRICAL GENERAL NOTES
E-100 ELECTRICAL SITE PLAN
E-101 UTILITY SITE PLAN
E-201 PARTIAL FIRST FLOOR PLAN - ELEC. LIGHTING - WEST
E-202 PARTIAL FIRST FLOOR PLAN - ELEC. LIGHTING - EAST
E-203 PARTIAL FIRST FLOOR PLAN - ELEC. POWER - WEST
E-204 PARTIAL FIRST FLOOR PLAN - ELEC. POWER - EAST
E-205 PARTIAL FIRST FLOOR PLAN - ELEC. EQUIPMENT - WEST
E-206 PARTIAL FIRST FLOOR PLAN - ELEC. EQUIPMENT - EAST
E-207 ELECTRICAL ROOF PLAN
E-501 ELECTRICAL DETAILS
E-502 ELECTRICAL DETAILS
E-503 ELECTRICAL DETAILS
E-601 ELECTRICAL ONE-LINE DIAGRAM
E-801 ELECTRICAL SCHEDULES
E-802 ELECTRICAL PANEL SCHEDULES
E-803 ELECTRICAL PANEL SCHEDULES
EC100 ELECTRICAL SITE CALC
Revisions Date
ELECTRICAL GENERAL NOTES
WHERE THERE IS A DISCREPANCY BETWEEN ABOVE GENERAL NOTES AND
SPECIFICATIONS, WHERE APPLICABLE, SPECIFICATIONS SHALL BE FOLLOWED
APPLICABLE CODES
1. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), INCLUDING (BUT NOT LIMITED TO):
a. NATIONAL ELECTRICAL CODE (NEC), NFPA 70 - 2020
b. NATIONAL FIRE ALARM CODE, NFPA 72 - 2022
c. LIFE SAFETY CODE, NFPA 101 – 2021
d. STANDARD FOR THE INSTALLATION OF LIGHTNING PROTECTION SYSTEMS, NFPA 780
e. HEALTH CARE FACILITIES CODE, NFPA 99 - 2021
2. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI), INCLUDING (BUT NOT LIMITED TO):
a. NATIONAL ELECTRICAL SAFETY CODE, ANSI C2
3. OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA)
4. FEDERAL COMMUNICATION COMMISSION (FCC)
5. NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
6. INSULATED CABLE ENGINEERS ASSOCIATION (ICEA)
7. INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
8. NATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)
9. AMERICAN SOCIETY OF TESTING AND MATERIALS (ASTM)
10. ILLUMINATION ENGINEERING SOCIETY (IES)
11. ANTI-FRICTION BEARING MANUFACTURERS ASSOCIATION (AFBMA)
12. BUILDING OFFICIALS AND CODE ADMINISTRATORS INTERNATIONAL, INC. (BOCA)
13. INTERNATIONAL CODE COUNCIL (ICC):
a. INTERNATIONAL BUILDING CODE (IBC)
14. UNIFORM BUILDING CODE (UBC)
15. NATIONAL ELECTRICAL CONTRACTORS ASSOCIATION INSTALLATION STANDARDS (NECA)
16. AMERICANS WITH DISABILITIES ACT (ADA)
17. APPLICABLE STATE AND LOCAL CODES, AMENDMENTS, REGULATIONS, AND PRACTICES.
18. APPLICABLE REGULATORY REQUIREMENTS AND ADVISORY PRACTICES OF APPROPRIATE
a. AUTHORITIES HAVING JURISDICTION (AHJs).
19. APPLICABLE STANDARDS, REGULATIONS, AND PRACTICES OF THE OWNER.
20. VA ELECTRICAL DESIGN MANUAL - 2019
21. VA LIGHTING DESIGN MANUAL - 2015
GENERAL:
1. THE DRAWINGS AND APPLICABLE SPECIFICATIONS SHALL BE CONSIDERED SUPPLEMENTARY,
ONE TO THE OTHER AND ARE CONSIDERED THE "CONTRACT DOCUMENTS". ALL WORKMANSHIP,
METHODS AND/OR MATERIALS DESCRIBED OR IMPLIED BY ONE AND NOT DESCRIBED OR
IMPLIED BY THE OTHER SHALL BE PROVIDED, FURNISHED OR PERFORMED AS IF IT HAD
APPEARED IN BOTH SECTIONS. THE TERM "CONTRACT DOCUMENTS" DESCRIBED HEREIN IS
NOT LIMITED SOLELY TO THE ELECTRICAL PORTION OF THE DRAWINGS AND SPECIFICATIONS,
BUT ENCOMPASSES THE DRAWINGS AND SPECIFICATIONS OF ALL DIVISIONS AS A WHOLE.
2. PROVIDE AN OPERATING AND MAINTENANCE MANUAL TO OWNER PRIOR TO THE FINAL
ACCEPTANCE. THE MANUAL SHALL INCLUDE, AS A MINIMUM, (1) SUBMITTAL DATA STATING
EQUIPMENT RATING AND SELECTED OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING
MAINTENANCE. ALSO PROVIDE TWO OPERATIONS AND MAINTENANCE MANUALS FOR EACH
PIECE OF EQUIPMENT REQUIRING MAINTENANCE. REQUIRED ROUTINE MAINTENANCE ACTIONS
AND METHOD OF OPERATION FOR EQUIPMENT SHALL BE CLEARLY IDENTIFIED, AND THE NAME,
PHONE NUMBER AND ADDRESS OF AT LEAST ONE QUALIFIED SERVICE AGENCY.
3. INCLUDE ALL COSTS FOR EXCAVATION, SAW CUTTING, DIRECTIONAL BORING, CORE DRILLING, BACKFILLING, SURFACE RESTORATION, REPAIR OF FINISHES, ETC. THAT IS REQUIRED IN ORDER
TO MEET THE PROJECT REQUIREMENTS.
4. INCLUDE IN BID ALL COSTS ASSOCIATED WITH TEMPORARY ELECTRICAL SERVICE AS REQUIRED
FOR USE BY ALL TRADES DURING CONSTRUCTION. REMOVE TEMPORARY POWER AT THE
COMPLETION OF THE PROJECT. OBTAIN AND PAY FOR ALL REQUIRED PERMITS FOR
TEMPORARY POWER. ENGINEER OF RECORD SHALL BE PROVIDED WITH ADDITIONAL
COMPENSATION FROM THE CONTRACTOR WHERE SIGNED & SEALED DRAWINGS ARE
REQUESTED BY THE CONTRACTOR TO THE ENGINEER OF RECORD IF REQUIRED BY THE AHJ
FOR THE TEMPORARY POWER.
5. PROVIDE A COMPLETE UL LISTED LIGHTNING PROTECTION SYSTEM WITH A MASTER LABEL FOR
THE ENTIRE FACILITY PER THE REQUIREMENTS OF NFPA 780, AND THE DIVISION 26
SPECIFICATIONS, UNLESS NOTED OTHERWISE. LIGHTNING PROTECTION SYSTEM SHALL
INCLUDE BURIED COUNTERPOISE, UNLESS NOTED OTHERWISE.
6. INCLUDE IN BID THE TRANSPORT AND DISPOSAL OR RECYCLING OF ALL WASTE MATERIALS
GENERATED BY THIS PROJECT IN ACCORDANCE WITH ALL LOCAL, STATE AND FEDERAL RULES,
REGULATIONS AND GUIDELINES APPLICABLE. COMPLY FULLY WITH FLORIDA STATUTES
REGARDING MERCURY-CONTAINING DEVICES, AND WITH ALL DEP AND EPA APPLICABLE
GUIDELINES AT THE TIME OF DISPOSAL. PROVIDE OWNER WITH WRITTEN CERTIFICATION OF
ACCEPTED DISPOSAL.
7. ALL POWER CIRCUITS HAVE BEEN DESIGNED IN COMPLIANCE WITH SECTION C405.7.3 OF THE
ENERGY CONSERVATION CODE, REQUIRING 2% OR LESS VOLTAGE DROP FOR FEEDERS, AND
3% OR LESS VOLTAGE DROP FOR BRANCH CIRCUITS.
ELECTRICAL SYSTEM HAS BEEN DESIGNED IN ACCORDANCE WITH THE 2020 NATIONAL
ELECTRICAL CODE (NFPA 70).
8. ALL BRANCH CIRCUITS SHALL BE FURNISHED WITH A DEDICATED NEUTRAL. SHARED NEUTRALS
ARE NOT ALLOWED UNLESS SPECIFICALLY NOTED ON THE DRAWINGS.
9. VERIFY AND COORDINATE LOCATIONS OF ANY MISCELLANEOUS EQUIPMENT REQUIRING
ELECTRICAL CONNECTIONS (I.E., COPIERS, FAX MACHINES, PRINTERS, KITCHEN APPLIANCES, LAUNDRY APPLIANCES, PROJECTION SCREENS, SHOP TOOLS, MACHINE, ELEVATORS, ETC.)
WITH APPROVED SHOP DRAWINGS, OWNER-PROVIDED CUT SHEETS, MANUFACTURER'S
INSTRUCTIONS, AND EQUIPMENT NAMEPLATE INFORMATION, PRIOR TO ROUGH IN, AND
PROVIDE ALL NECESSARY ELECTRICAL REQUIRED.
10. VERIFY AND COORDINATE LOCATIONS AND EXACT ELECTRICAL REQUIREMENTS FOR ALL
MECHANICAL, PLUMBING AND FIRE PROTECTION EQUIPMENT PRIOR TO SUBMITTAL OF SHOP
DRAWINGS OF ELECTRICAL EQUIPMENT. PROVIDE ALL NECESSARY RACEWAYS, CONDUCTORS,
BOXES, EQUIPMENT, ACCESSORIES, ASSOCIATED DISCONNECT SWITCHES, CIRCUIT BREAKERS,
CONTROL TRANSFORMERS, FIRE ALARM SHUTDOWN, ETC. REQUIRED FOR A COMPLETE AND
OPERATIONAL SYSTEM. COORDINATE WITH APPROPRIATE TRADE'S APPROVED SHOP
DRAWINGS, MANUFACTURER'S INSTRUCTIONS, AND EQUIPMENT NAMEPLATE INFORMATION,
PRIOR TO ROUGH IN, AND PROVIDE ALL NECESSARY ELECTRICAL REQUIRED, UNLESS
OTHERWISE NOTED.
11. ALL WORK ON THE ELECTRICAL SYSTEM REQUIRED BY THE CONTRACT DOCUMENTS SHALL BE
COORDINATED WITH THE WORK OF ALL OTHER DIVISIONS/TRADES PRIOR TO COMMENCEMENT
OF WORK. AVOID INTERFERENCES WITH THE PROGRESS OF OTHER DIVISIONS/TRADES.
12. WHERE STRUCTURAL WALLS ARE OF TILT-UP CONSTRUCTION, PROVIDE COORDINATION FOR
EXACT DIMENSIONS AND OPENINGS REQUIRED FOR ALL ELECTRICAL COMPONENTS INSTALLED
WITHIN TILT-UP WALLS DURING THE SHOP DRAWING REVIEW PROCESS OF THE TILT-UP WALLS, PRIOR TO MANUFACTURE OF THE TILT-UP WALLS.
13. LOCATIONS OF VFD'S, DISCONNECTS, MOTOR STARTERS, ETC. FOR HVAC EQUIPMENT ARE
DIAGRAMMATIC ON THE PLAN DRAWINGS. EXACT LOCATIONS ARE TO BE COORDINATED WITH
CONTRACTOR'S COORDINATION DRAWINGS PRIOR TO ROUGHING IN TO ENSURE PROPER NEC
CLEARANCES AND APPROPRIATE MOUNTING SURFACE.
14. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS.
PROVIDE COMPONENTS INDICATED ON RISER DIAGRAMS WHETHER OR NOT INDICATED ON
PLANS AND VICE VERSA.
15. ROUTING OF CONDUIT IS DIAGRAMMATIC AND NOT INTENDED TO SHOW REQUIRED OFFSETS
AND DETAILS. COORDINATE EXACT ROUTING WITH FIELD CONDITIONS AND OTHER TRADES.
16. COORDINATE RECEPTACLE LOCATIONS WITH TECHNOLOGY DRAWINGS OR OWNER'S VENDOR
DRAWINGS SO THAT A 120V 20A 5-20R RECEPTACLE IS LOCATED ADJACENT TO EACH
VOICE/DATA OUTLET AND TV OUTLET INDICATED ON PLANS. RECEPTACLE IS TO BE CONNECTED
TO NEAREST 120V RECEPTACLE CIRCUIT, UNLESS OTHERWISE NOTED ON PLANS.
17. REFER TO ARCHITECTURAL, MECHANICAL, PLUMBING, FIRE PROTECTION, CIVIL, LANDSCAPE, INTERIOR DESIGN, TECHNOLOGY, STRUCTURAL, AND KITCHEN EQUIPMENT DRAWINGS FOR
RELATED INFORMATION AND ADDITIONAL INSTALLATION REQUIREMENTS TO BE PERFORMED AS
PART OF THE WORK. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT MOUNTING HEIGHT
AND LOCATIONS.
18. WHERE A DISCREPANCY OR CONFLICT IS FOUND BETWEEN ONE DRAWING AND ANOTHER, OR
BETWEEN A DRAWING AND APPLICABLE SPECIFICATIONS, NOTIFY THE ARCHITECT/ENGINEER
IMMEDIATELY IN WRITTEN FORM. IN GENERAL, THE MOST STRINGENT REQUIREMENT SHALL
GOVERN UNLESS THE DISCREPANCY CONFLICTS WITH APPLICABLE CODES OR OWNER'S
DESIGN STANDARDS, WHEREIN THE CODE OR OWNER'S DESIGN STANDARDS SHALL GOVERN.
19. COORDINATE ALL PROJECT SCHEDULING AND PHASING REQUIREMENTS WITH
ARCHITECT/ENGINEER AND OWNER PRIOR TO SUBMITTING BID PRICE. THIS PROJECT MAY
REQUIRE PHASING SEQUENCES AND POTENTIAL PREMIUM TIME WORK AND ALL COSTS FOR
SUCH SHALL BE INCLUDED IN THE BID PRICE. PROVIDE ADEQUATE WORK FORCE AND
EQUIPMENT, AND INCLUDE PREMIUM TIME AS MAY BE REQUIRED IN ORDER TO ADHERE TO THE
PROJECT SCHEDULE. ADDITIONALLY, ENSURE THAT LONG LEAD ITEMS DO NOT IMPACT THE
PROJECT'S SCHEDULE OR PHASING.
20. ANY TEMPORARY INTERRUPTION ON POWER REQUIRED FOR THE SYSTEM TIE-IN OR
SWITCHOVER FOR ANY PORTION OF THE ELECTRICAL SYSTEM SHALL BE PRE-APPROVED IN
WRITING BY THE OWNER AND SCHEDULED IN ADVANCE.
21. COORDINATE EXACT REQUIREMENTS WITH THE LOCAL UTILITY COMPANIES AND PROVIDERS
(ELECTRIC, TELEPHONE, CABLE TV, ETC.) AND INCLUDE ALL COSTS FOR PROVIDING
TEMPORARY AND PERMANENT SERVICES REQUIRED FOR THIS PROJECT IN THE BID PRICE. BID
PRICE SHALL INCLUDE, BUT NOT BE LIMITED TO, EXCAVATION, RACEWAYS, BACKFILL,
EQUIPMENT, EQUIPMENT PADS, BACKBOARDS, METERS, GROUNDING, UTILITY ENGINEERING
AND IMPACT FEES.
22. CONDUCT WORK OPERATIONS AND DEBRIS REMOVAL IN A MANNER THAT ENSURES MINIMUM
INTERFERENCE WITH NORMAL BUSINESS OPERATIONS, TRAFFIC, PARKING, ETC. ONGOING IN
ADJACENT OCCUPIED SPACES OR FACILITIES. PROVIDE ALL THAT IS REQUIRED TO
EFFECTIVELY PROTECT SURROUNDING OCCUPANTS, EQUIPMENT, FINISHES, FURNITURE, ETC.
FROM DAMAGE OR EXCESSIVE NOISE THROUGHOUT THE DURATION OF THIS PROJECT.
CONTRACTOR IS RESPONSIBLE FOR ANY LOSSES OR DAMAGE. ANY DAMAGE RESULTING FROM
THE FAILURE TO ADHERE TO THIS REQUIREMENT. RESTORE DAMAGED ELEMENTS TO ORIGINAL
CONDITION BY THE CONTRACTOR TO THE SATISFACTION OF THE ARCHITECT/ENGINEER AND
OWNER, AT NO ADDITIONAL COSTS. REPORT OF ANY SUCH OCCURRENCE TO THE
ARCHITECT/ENGINEER AND OWNER IMMEDIATELY AND AWAIT WRITTEN DIRECTION PRIOR TO
PROCEEDING WITH REPAIRS.
23. COORDINATE THE LOCATION OF ALL LIGHT FIXTURES, DEVICES AND BOXES WITH WINDOWS, MIRRORS, MILLWORK, CABINETS, GLASS CURTAIN WALLS, AND GLASS WALLS PRIOR TO
INSTALLATION OF CONDUITS OR BOXES. REVIEW ALL CONTRACT DRAWINGS TO ASCERTAIN
ANY CONFLICTS PRIOR TO BIDDING. OBTAIN CLARIFICATION FROM A/E PRIOR TO BID.
CONTRACTOR SHALL NOT BE ENTITLED TO ADDITIONAL COMPENSATION FOR WORK REQUIRED
TO RELOCATE OUTLET BOXES OR RACEWAYS FOR COORDINATION WITH OTHER TRADE'S
WORK.
24. THE EXCLUSIVELY DEDICATED SPACE EXTENDING FROM FLOOR TO 6' ABOVE EQUIPMENT OR
STRUCTURAL CEILING, WHICHEVER DISTANCE IS LOWER, WITH A WIDTH AND DEPTH OF THE
PANELBOARD OR SWITCHBOARD MUST BE CLEAR OF ALL PIPING, DUCTS, EQUIPMENT FOREIGN
TO THE ELECTRICAL EQUIPMENT OR ARCHITECTURAL APPURTENANCES IN ACCORDANCE WITH
NEC.
25. PROVIDE ALL TEMPORARY NORMAL LIGHTING, EMERGENCY LIGHTING AND EXIT SIGNAGE
REQUIRED DURING THE PROJECT CONSTRUCTION PHASE.
26. THE INFRASTRUCTURE FOR THE ACCESS CONTROL/ CCTV OR SECURITY ELECTRONICS SYSTEM (CONDUITS, ELECTRICAL BOXES) SHALL BE INSTALLED BY DIVISION 26. THE ACCESS CONTROL/
CCTV OR SECURITY ELECTRONICS SYSTEM CONTRACTOR SHALL PROVIDE AND INSTALL THE
WIRE AND CABLE FOR THE SYSTEM AND ALL REQUIRED EQUIPMENT. INSTALLATION OF THE
CONDUITS AND ELECTRICAL BOXES SHALL BE UNDER THE DIRECT SUPERVISION OF THE
ACCESS CONTROL/ CCTV SYSTEM CONTRACTOR. COORDINATE EXACT LOCATIONS OF DEVICES,
RACEWAY LOCATIONS, SIZES AND QUANTITY, CONDUIT STUB-UPS PRIOR TO ROUGH IN.
27. THE INFRASTRUCTURE FOR THE VOICE/DATA TELECOMMUNICATIONS SYSTEM (CONDUITS,
ELECTRICAL BOXES) SHALL BE INSTALLED BY DIVISION 26. THE TELECOMMUNICATIONS
CONTRACTOR SHALL PROVIDE AND INSTALL THE WIRE AND CABLE FOR THE SYSTEM AND ALL
REQUIRED EQUIPMENT AND COMPONENTS. INSTALLATION OF THE CONDUITS AND ELECTRICAL
BOXES SHALL BE UNDER THE DIRECT SUPERVISION OF THE TELECOMMUNICATIONS
CONTRACTOR. COORDINATE EXACT LOCATIONS OF DEVICES, RACEWAY LOCATIONS, SIZES AND
QUANTITY, CONDUIT STUB-UPS PRIOR TO ROUGH IN.
28. PROVIDE 120V 20A 5-20R RECEPTACLE AT ALL FAN COIL UNITS FOR CONDENSATE PUMP POWER
AND HOT WATER RECIRCULATING PUMPS, WHETHER SHOWN ON PLANS OR NOT. RECEPTACLE
IS TO BE CONNECTED TO NEAREST 120V RECEPTACLE CIRCUIT.
29. PROVIDE 120V CONNECTION TO ALL MOTORORIZED DAMPERS INDICATED ON MECHANICAL
PLANS, WHETHER SHOWN ON DIVISION 26 DRAWINGS OR NOT. FIRE/SMOKE DAMPER CIRCUITS
ARE TO BE PROVIDED FROM EMERGENCY BRANCH PANEL (LEGALLY REQUIRED BRANCH IF
AVAILABLE). MOTORIZED DAMPERS WITHIN THE SAME AREA CAN BE CIRCUITED TO THE SAME
CIRCUIT (I.E., DEDICATED CIRCUIT IS NOT REQUIRED).
30. PROVIDE PHONE/DATA OUTLET WITH 1" RACEWAY, AND 120V RECEPTACLE ON DEDICATED
CIRCUIT ADJACENT TO EACH AIR HANDLING UNIT FOR CONTROL POWER.
31. PROVIDE 120V DEDICATED CIRCUIT TO EACH AIR HANDLING UNIT WITH SEPARATE
CONNECTIONS TO UNIT UV LIGHT, UNIT LIGHTS, UNIT RECEPTACLE, AND BI-POLAR IONIZATION
FILTER WHERE PROVIDED. COORDINATE WITH DIVISION 23 SHOP DRAWINGS.
32. UNLESS NOTED AS EXISTING, ALL ELECTRICAL INDICATED ON THE CONTRACT DOCUMENTS
SHALL BE NEW, SHALL BE U.L. LISTED, AND SHALL BEAR A U.L. LABEL. WHERE NO U.L. LABEL OR
LISTING IS AVAILABLE, THE MATERIAL SHALL BE LISTED WITH AN APPROVED, NATIONALLY
RECOGNIZED ELECTRICAL TESTING AGENCY.
33. PROVIDE EXPERIENCED, QUALIFIED AND RESPONSIBLE SUPERVISION FOR ALL WORK
REQUIRED BY THE CONTRACT DOCUMENTS. ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED
IN A NEAT AND WORKMANLIKE MANNER, TO THE SATISFACTION OF THE ARCHITECT/ENGINEER
AND OWNER.
34. THE ELECTRICAL PORTION OF THE CONTRACT DOCUMENTS ARE COORDINATED WITH THE
DESIGN BASIS EQUIPMENT SPECIFIED BY DIVISION 26 AND OTHER DIVISIONS. WHERE THE
CONTRACTOR ELECTS TO SUBSTITUTE A PRODUCT IN LIEU OF PROVIDING THE DESIGN BASIS,
AND SAID SUBSTITUTION IS ACCEPTED BY THE A/E AND OWNER, THE CONTRACTOR SHALL MAKE
ALL CORRECTIONS TO THE ELECTRICAL SYSTEM NECESSARY IN ORDER TO ENSURE A
COMPLETE AND OPERATIONAL INSTALLATION OF THE EQUIPMENT AT NO ADDITIONAL COSTS.
WHERE THE CONTRACTOR'S DESIGN SUBSTITUTION RESULTS IN THE NEED FOR THE ENGINEER
TO REVISE THE CONTRACT DOCUMENTS, THE ENGINEER RESERVES THE RIGHT TO REQUEST
COMPENSATION FROM THE CONTRACTOR FOR SAID SERVICES.
35. MAINTAIN A CURRENT AND ACCURATE SET OF PROJECT RECORD DOCUMENTS (AS-BUILTS) AT
THE SITE THROUGHOUT THE DURATION OF THE PROJECT. RECORD DRAWINGS SHALL BE
UPDATED EACH DAY TO REFLECT THE ACTUAL LOCATIONS, SIZES, ROUTING, ETC. OF EACH
PORTION OF THE ELECTRICAL SYSTEM AFFECTED BY THIS WORK. A FINAL SET OF RECORD
DOCUMENTS SHALL BE ISSUED TO THE A/E FOR REVIEW AND THEN SUBMITTED TO THE OWNER
WITHIN 30 DAYS AFTER THE DATE OF FINAL ACCEPTANCE. PROVIDE RECORD DRAWINGS OF
THE ACTUAL INSTALLATION INCLUDING SINGLE LINE DIAGRAM, POWER RISER DIAGRAM OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM, SITE PLANS AND ALL ELECTRICAL FLOOR PLANS, DETAILS, PANEL SCHEDULES, ETC.
36. OWNER FURNISHED EQUIPMENT: VERIFY AND COORDINATE ELECTRICAL ROUGH IN
REQUIREMENTS FOR OWNER FURNISHED EQUIPMENT PRIOR TO ROUGH IN.
37. WHERE SUBMITTED EQUIPMENT REQUIRES REVISION TO OVERCURRENT PROTECTION,
CONDUIT OR WIRING, MAKE CHANGES IN ACCORDANCE WITH APPLICABLE CODES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
BI
M
- C on st ru ct
R ep la ce m en t O ut pa tie nt C lin ic
/0
C on st . R ep la ce . O ut pa tie nt
C lin ic
R
.rv t
2/ 9/
2:
:3
PM
E-002
ELECTRICAL GENERAL NOTES REPLACEMENT OUTPATIENT
CLINIC DESIGN AT COAST
GUARD CAPE COD
JOINT BASE CAPE COD, BARNSTABLE MA
650-318
BUILDING 1
02/10/2023 JFR KEM
100% CONSTRUCTION
DOCUMENTS
C
C
C C
C
C
C
C
C
C
C
CCCCC
C C C C CC
C C
CCCCCCC
C C
C C
CCC
UE
U E
S
PSFMFMFMFMFMFM V
GAS
LINE POST
APPROX. GAS
MAIN
APPROX. GAS
MAIN
UP #8UP #9 UP #601/7
J
J
J
J J
J J
SB
SA
SB2 SB
BAR CT CABINET
CONNERY AVENUE
PAD MOUNTED UTILITY
TRANSFORMER
PRIMARY ELECTRICAL FEED - SEE ONE-LINE
DIAGRAM ON SHEET E-601 AND
UNDERGROUND CONDUIT DETAIL #2 ON THIS
SHEET.
UNDERGROUND CONDUITS FOR CATV,
INTERNET AND TELECOMMUNICATIONS
SERVICES, REFER TO SHEET T-101 FOR
ADDITIONAL INFORMATION.
RUN COMMUNICATIONS CONDUIT UP 8' ON
UTILITY POLE AND PROVIDE METAL GUARD
TO ATTACHMENT POINT FROM UTILITY
EXISTING
UTILITY POLE
SECONDARY ELECTRICAL FEED - SEE
ELECTRICAL ONE-LINE DIAGRAM ON SHEET
E-601 AND CONCRETE ENCASED
UNDERGROUND CONDUIT DETAIL
SA
SA
SA SA
SA
SA
SA
SA
SA
SB2
ELECTRICAL UTILITY METER
(3) GROUND RODS - REFER TO
SYSTEM GROUNDING DETAIL
FOR REQUIREMENTS
FLG FLG
FLG
2TYPICAL
HH
HH
HH
HLP1
LOS1
LOS1-17
HLP1-4
HLP1-4
HLP1-4
HLP1-4
HLP1-4
HLP1-4
HLP1-9
HLP1-9 HLP1-9
HLP1-2
HLP1-2 HLP1-2
HLP1-2
HLP1-2HLP1-2
HLP1-4
HLP1-2
HMP1
HMP1-25,27,29
LOS1-12
LOS1-17
LOS1-13
LOS1-15
8 9
LRP3A-65
LRP3A-62,64
HH
12 13 14 15
12 13 14 15
CONCRETE BOLLARDS BY OTHERS
SC
HLP1-4
HH
SL
HLP1-9
PC
FLGFLG
HH
TLRP1
DIRECT BURIAL CONDUIT
24" BELOW GRADE
MARKING
TAPE
FINISHED GRADE PAVING CONSTRUCTION AS
SPECIFIED BY CIVIL ENGINEER
0'
1/
" M
IN
IM
U M
6" M
IN3" CONCRETE ABOVE
AND BELOW CONDUIT
12" MINIMUM
(4 2"
M
IN
MU
M
FO
R
EL
EC
TR
IC
S
ER
VI
CE
PR
IM
AR
Y
CO
ND
UI
TS
CO
M
PA
CT
ED
ST
ON
E
BA
CK
FI
LL
DIRECT BURIAL CONDUIT
24" BELOW GRADE
MARKING
TAPE
FINISHED GRADE PAVING CONSTRUCTION AS
SPECIFIED BY CIVIL ENGINEER
12" MINIMUM
0'
1/
" M
IN
IM
U M
6" M
IN3" SAND ABOVE AND
BELOW CONDUIT
(4 2"
M
IN
MU
M
FO
R
EL
EC
TR
IC
S
ER
VI
CE
PR
IM
AR
Y
CO
ND
UI
TS
CO
M
PA
CT
ED
ST
ON
E
BA
CK
FI
LL
6'
0"
6' - 6"
1'
3" 0'
6" 0'
4"
0'
9"
1' - 6" 3' - 6" 1' - 6"
0'
6" 0'
4"
0' - 6" 0' - 4"
0' - 3" 0' - 6"
5/8" x 8'-0" GROUND ROD - TYPICAL OF 2.
COMPRESSION GROUNDING
CONNECTOR OR CADWELD.
4" DIA. GALVANIZED SCH. 40 STEEL
CONDUIT SECONDARY SERVICE (36"
RADIOUS QUARTER-BEND).
#4/0 AWG STRANDED CU GROUND LOOP.
#4/0 AWG CU TYP.
GROUND WIRE CONNECTION, TYPICAL.
4" OR 5" DIA. GALVANIZED SCH. 40 STEEL
CONDUIT PRIMARY SERVICE.
1/2" THICK SEALANT BEAD
APPLIED ALL AROUND
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
BI
M
- C on st ru ct
R ep la ce m en t O ut pa tie nt C lin ic
/0
C on st . R ep la ce . O ut pa tie nt
C lin ic
R
.rv t
2/ 9/
2:
:3
PM
E-100
ELECTRICAL SITE PLAN REPLACEMENT OUTPATIENT
CLINIC DESIGN AT COAST
GUARD CAPE COD
JOINT BASE CAPE COD, BARNSTABLE MA
650-318
BUILDING 1
02/10/2023 JFR KEM
100% CONSTRUCTION
DOCUMENTS
1/16" = 1'-0"E-100
4 SITE PLAN - ELECTRICAL
CODED NOTES:
DRAWING NOTES:
PROVIDE BAR CT CABINET AND METER SOCKET WITH 1" CONDUIT CONNECTION. SEE ONE-LINE
DIAGRAM ON SHEET E-601 FOR FURTHER INFORMATION. PROVIDE HOT DIPPED GALVANIZED
UNISTRUT SUPPORT RACK AND REQUIRED MOUNTING HARDWARE FOR MOUNTING ADJACENT TO
TRANSFORMER. VERIFY ALL TRANSFORMER CLEARANCES ARE MAINTAINED.
COORDINATE EXACT LOCATION AND AIMING OF FIXTURE IN FIELD WITH FLAG POLE HEIGHT. REFER
TO LIGHTING CONTACTOR WIRING DIAGRAM ON SHEET E-601 FOR ADDITIONAL INFORMATION.
COORDINATE EXACT LOCATION OF LIGHT POLE AND FIXTURE WITH FENCE RAILING AND CIVIL PLAN
C001 PRIOR TO CONSTRUCTION.
EMERGENCY PHONE CONNECTION. BASIS OF DESIGN: CODE BLUE CB-1-S (POE) TO BE FED FROM NEAREST CCTV POWER SUPPLY. COORDINATE ELECTRICAL REQUIREMENTS WITH FINAL EQUIPMENT
SELECTION. REFER TO T-101 DETAIL #2 FOR FURTHER INFORMATION.
FOR CONNECTION TO MEDIA CONVERTER. SEE TELECOM SHEET T-101 FOR HANDHOLE
REQUIREMENTS AND FURTHER INFORMATION.
PROVIDE 2#12 AWG + 1#12 AWG GND IN 3/4" UNDERGROUND PVC FOR PROPOSED BRANCH CIRCUIT
RUN (TOTAL CIRCUIT LENGTH~200').
PROVIDE 2#12 AWG + 1#12 AWG GND IN 3/4" UNDERGROUND PVC FOR PROPOSED BRANCH CIRCUIT
RUN (TOTAL CIRCUIT LENGTH~70').
PROVIDE 2#10 AWG + 1#10 AWG GND IN 3/4" UNDERGROUND PVC FOR PROPOSED BRANCH CIRCUIT
RUN (TOTAL CIRCUIT LENGTH~308'). CONDUCTORS ADJUSTED FOR VOLTAGE DROP.
PROVIDE 2#10 AWG + 1#10 AWG GND IN 3/4" UNDERGROUND PVC FOR PROPOSED BRANCH CIRCUIT
RUN (TOTAL CIRCUIT LENGTH~611'). CONDUCTORS ADJUSTED FOR VOLTAGE DROP.
PROVIDE 2#12 AWG + 1#12 AWG GND IN 3/4" UNDERGROUND PVC FOR PROPOSED BRANCH CIRCUIT
RUN (TOTAL CIRCUIT LENGTH~401').
PROVIDE 2#12 AWG + 1#12 AWG GND IN 3/4" UNDERGROUND PVC FOR PROPOSED BRANCH CIRCUIT
RUN (TOTAL CIRCUIT LENGTH~96').
LIFT STATION POWER CIRCUIT. PROVIDE 3#6 AWG + 1#10 AWG GND IN 1" UNDERGROUND PVC FOR
PROPOSED BRANCH CIRCUIT RUN (TOTAL CIRCUIT LENGTH~300'). CONDUCTORS ADJUSTED FOR
VOLTAGE DROP.
GENERATOR BATTERY CHARGING CIRCUIT. PROVIDE 2#10 AWG + 1#10 AWG GND IN 1"
UNDERGROUND PVC FOR PROPOSED BRANCH CIRCUIT RUN (TOTAL CIRCUIT LENGTH~300').
CONDUCTORS ADJUSTED FOR VOLTAGE DROP.
GENERATOR JACKET HEATER CIRCUIT. PROVIDE 2#4 AWG + 1#4 AWG GND IN 1-1/2" UNDERGROUND PVC FOR PROPOSED BRANCH CIRCUIT RUN (TOTAL CIRCUIT LENGTH~300'). CONDUCTORS ADJUSTED
FOR VOLTAGE DROP.
GENERATOR CONTROL CABLING IN 1" UNDERGROUND PVC CONDUIT FROM GENERATOR REMOTE
PANEL LOCATED IN ROOM 107.
APPROXIMATE LOCATION OF NEW LIFT STATION. COORDINATE EXACT LOCATION ON SITE AND WITH
CIVIL DRAWINGS PRIOR TO CONSTRUCTION.
NEW ATS FOR LIFT STATION BACKUP POWER. COORDINATE EXACT LOCATION ON SITE AND WITH
CIVIL DRAWINGS PRIOR TO CONSTRUCTION. REFER TO SHEET E-601 FOR ADDITIONAL ATS
INFORMATION.
NEW DIESEL GENERATOR FOR LIFT STATION BACKUP POWER. COORDINATE EXACT LOCATION ON
SITE AND WITH CIVIL DRAWINGS PRIOR TO CONSTRUCTION. REFER TO SHEET E-601 FOR ADDITIONAL
GENERATOR INFORMATION.
GENERATOR REMOTE EMERGENCY POWER OFF BUTTON (NEC 445.18) LOCATED IN ELECTRICAL
ROOM 161. REFER TO SHEET E-204 FOR LOCATION. SEE GENERATOR CONTROL DIAGRAM ON SHEET
E-601 FOR DETAILS.
ILLUMINATED SIGN POWER CIRCUIT. PROVIDE 2#10 AWG + 1#10 AWG GND IN 1" UNDERGROUND PVC FOR PROPOSED BRANCH CIRCUIT RUN (TOTAL CIRCUIT LENGTH~550'). CONDUCTORS ADJUSTED FOR
VOLTAGE DROP.
WALL MOUNTED SIGN LIGHT. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT WITH CIVIL
PLANS AND ARCHITECTURAL SIGN ELEVATIONS PRIOR TO CONSTRUCTION. REFER TO LIGHTING
CONTACTOR WIRING DIAGRAM ON SHEET E-601 FOR ADDITIONAL INFORMATION.
PHOTOCELL FOR CONTROL OF SIGN AND FLAG POLE LIGHT FIXTURES MOUNTED ON NORTH FACING SIDE OF BUILDING ROOF. COORDINATE EXACT LOCATION OF SENSOR IN FIELD WITH ALL OTHER TRADES PRIOR TO CONSTRUCTION. PROVIDE CABLING AS REQUIRED FOR CONNECTION TO LIGHTING
CONTACTOR. REFER TO SHEET E-601 FOR ADDITIONAL INFORMATION.
PROVIDE 2#10 AWG + 1#10 AWG GND IN 3/4" UNDERGROUND PVC FOR PROPOSED BRANCH CIRCUIT
RUN (TOTAL CIRCUIT LENGTH~500'). CONDUCTORS ADJUSTED FOR VOLTAGE DROP.
PROVIDE 12"X12"X12" PRECAST TRAFFIC RATED PULL BOX.
1. EXACT UNDERGROUND CONDUIT ROUTING INDICATED ON THIS PLAN IS DIAGRAMMATIC. FINAL
ROUTING TO BE DETERMINED IN THE FIELD AND COORDINATED WITH ALL OTHER UTILITIES.
2. COORDINATE THE INSTALLATION OF ALL NEW LIGHT POLES AND BASES WITH SITE CIVIL CONTRACTOR.
ALL UNDERGROUND WORK SHALL BE INSTALLED PRIOR TO PAVING. NO SAWCUTTING OR PATCHING
AS A RESULT OF IMPROPER COORDINATION IS PERMITTED.
3. ALL WIRE SHALL BE 600 VOLT THHN-THWN, 90 DEGREE INSULATED AND SHALL BE COPPER.
4. ALL UNDERGROUND WIRING SHALL BE RUN IN SCHEDULE 40 PVC CONDUIT AND DIRECT BURIED AT A MINIMUM DEPTH OF 36" BELOW GRADE. SEE UNDERGROUND CONDUIT DETAIL #1 ON THIS SHEET FOR
DETAIL REQUIREMENTS. SEE UNDERGROUND CONDUIT DETAIL #2 ON THIS SHEET FOR CONDUIT
ROUTED BELOW DRIVES AND PAVEMENT.
5. ALL LIGHT POLES SHALL BE MOUNTED A MINIMUM 24" FROM THE FACE OF THE CURB.
6. SEE SHEET E-101 FOR UTILITY POLE COORDINATION AND REQUIREMENTS.
N.T.S.
UNDERGROUND CONDUIT DETAIL #22
N.T.S.
UNDERGROUND CONDUIT DETAIL #11
0 8' 16' 32' 48'
1/16" = 1'-0"
N
N.T.S.
UTILITY TRANSFORMER PAD DETAIL3
C
C C
C
C
C
C
C
C
C
CCCCC
C C C C CC
C C
CCCCCCC
C C
C C
CCC
UE
U E
S
PSFMFMFMFMFMFM V
GAS
LINE POST
APPROX. GAS
MAIN
APPROX. GAS
MAIN
UP #8UP #9
UP #10
UP #601/7
CONNERY AVENUE
EXISTING UTILITY POLE #10 - TO BE RELOCATED EXISTING UTILITY POLE #9 - TO BE RELOCATED EXISTING UTILITY POLE #8 - TO REMAIN EXISTING UTILITY POLE #7 - TO REMAIN
RELOCATED UTILITY POLE #9
RELOCATED UTILITY POLE #10 1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
BI
M
- C on st ru ct
R ep la ce m en t O ut pa tie nt C lin ic
/0
C on st . R ep la ce . O ut pa tie nt
C lin ic
R
.rv t
2/ 9/
2:
:3
PM
E-101
UTILITY SITE PLAN REPLACEMENT OUTPATIENT
CLINIC DESIGN AT COAST
GUARD CAPE COD
JOINT BASE CAPE COD, BARNSTABLE MA
650-318
BUILDING 1
02/10/2023 JFR KEM
100% CONSTRUCTION
DOCUMENTS
1" = 20'-0"E-101
1 UTILITY SITE PLAN - ELECTRICAL
CODED NOTES:
DRAWING NOTES:
CONTRACTOR TO COORDINATE RELOCATION OF UTILITY POLE WITH LOCAL UTILITY. UTILITY POLE
RELOCATION WORK TO BE PERFORMED BY LOCAL UTILITY PERSONNEL.
1. COORDINATE EXACT LOCATIONS OF EXISTING UTILITY POLES PRIOR TO CONSTRUCTION.
2. CONTRACTOR TO COORDINATE ALL UTILITY POLE WORK WITH UTILITY PRIOR TO CONSTRUCTION.
0 8' 16' 32' 48'
1/16" = 1'-0"
N
R
EF
R
EF
OS OS
OS
LPP
OS
OS
LPP
LPP
OS LPD
OS
OS OS
OS
OS
OS
LPP OS
LPD
LPD
OS
OS
OSOS
OS
OS
OS
OS
OS
OS
OS
LPD
OS OS OS
OS
OSOS
OS
LPD
OS
OS
OS
OS
OS
LPD
LPD
LPP
LPP
LPD
OS
LPE
LPP LPE
LPE
LPD
LPD
LPE
LPP LPE
OS
LPD
LPE
LPE
J
H G F E D
I
VESTIBULE
WAITING
CORRIDOR
WAITING
RECEPTION
RECEPTION
WORKROOM
NURSE MANAGER
TOILET PUBLIC
TOILET PUBLIC
VOLUNTEER
CORRIDOR
SOCIAL WORKER
CLOSET
ELEC
SPECIMEN
COLLECTION
TOILET WMN'S
TOILET PATIENT
EXAM RM WOMEN'S
HEALTH
ULTRASOUND
TREATMENT
EXERCISE AREA
138 EXAM / PT/OT
EXAM / TRIAGE
PROCEDURE
ROOM, GENERAL
TOILET PROC.
TOILET STAFF
EXAM /
TELE-HEALTH
EXAM
CLOSET
151CORRIDOR
MED ROOM
TOILET STAFF
TEAM WORK AREA
EXAM/TRIAGE
EXAM / MENTAL
HEALTH
EXAM /
TELE-HEALTH
EXAM / EYE TEST
EXAM
114MULTI-PURPOSE
ROOM
MULTI-PURPOSE
ROOM
GROUP THERAPY
ROOM, MENTAL
HEALTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
A1 A1
A1 A1
A1A1
AX4
AX4
AX4
AX4
AX4
AX4 AX4 AX4
A2 A2
A2
A2A2
A2
AX4
A1
A1
A1
A1
A1
A1
A1
A1 A1
A1
A1 A2
A1
A2
A2A2
A1
A1 A1
A2
A2
A2 A2
A2
A2 A2 A2
A2
A2 A2
A2
A1 A1
A2 A2
A1
A1 A1
A1A1
A1 A1 A1
A1
A1 A1
A1
A1 A1
A1
A1
A1 A1 A1 A1
A2 A2
A2A2
A2A2
A2 A2
A1A1A1A1
A1
A1 A2
A2 A2
A2
A1A1A1
A2 A2
A1 A2
A2
A1
A1
AX4AX4
A1
A1
A1 A1 A1A1 A1A1
A1A1
A1 A1
A1
AX4
AX4
A1 A1 A1
A1 A1 A1
A2
A2 A2
A2
A1 A1
A1 A1
AX4
AX4
AX4
A1 A1 A1
A1 A1 A1 A1
A1A1
A1
A1
A1
A1
A1 A1
A1
A1 A1
A1 A1
A1
A1
A1
A1
A1
A1
A1 A1
A1 A1 A1
A1 A1
A1
A2A2
A2 A2
A2 A2
A2A2
A1
A1
A1 A1
A1
A1 A1
A1 A1
A1 A1
A2A2
A2 A2
A1 A1 A1 A1 A1 A1
A2 A2
A2 A2
A1 A1
A2
A2 A2
A2
A1 A1
A1
A1
A1
A1A1
A1A1
A1A1
A1
A1
A1
D1
A1
D1
D1
D1
D1
D1 D1
D1
D1
D1 D1
D1
D1
D1
D1
D1
D1
D1
L1
L1
WAITING
OS
OS
OSD OSD OSD OSD OSD OSDOSD
OS
OS
OS
D1
LV1D
LV1Dn
LV1D
LV1D
LV1D
OS OS
LV1c
LV1c
LV1c
LV1c
LV1a
LV1a
OS
OS
LV1D
X2
X1
X1
X1
X2
X1
X1
X1
X2
X1
X1
X1 c c c cc c c c c cc c c c c c c c c ccc c c c c c c c c c aa a a a a a a a a a a a a a a a a a a a a a p p p b b b b b b b b b b b b b b b b b b b b b b b b b c ad ad ad p ad p ad
SL1
SL1
SL1
X1
SL1 SL1
OS
adc
PS
PS
LV1Dm c c c c c
LPDE
a a
L1
FIXTURE TYPE 'WG', ZONE 'd' (TYPICAL FOR 27) d
LV1Dd
LIGHTING PARTITION
SENSORS
LV1Dj j j j
V1 V1
V1
V1
V1
V1
V1
D D D
D
D D
D
DD
D
D n n n n nn n m m m m m m m m m mm m m
LV1Dn
D c c
LV1p pp
OSD
OS
M
AT
C H
LI
N
E -C
O N
TI
N
U
ED
O N
D W
G
/E -2
H.2 H.1 F.7 F.5 F.3 E.5 D.9 D.7 D.6 D.5 D.3 C.6 C.5 C.3
5.5
3.7 3.6
3.3
3.1
2.7
2.5
2.4
1.9
1.5
1.3
TOILET PATIENT
125 EXAM / AUDIOLOGY
d d d d j j j
LV1Dd
AX4B AX4BAX4B
AX4B
AX4B
AX4B
AX4B
g g f f h hh
SQ4
SQ4
A1
A1
A1 a a a
A1
A1 a a
L1 c f f f
LV1Df j d f
LV1D
D
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
163c
LV1Df d j j g f g f
HLP1-23 HLP1-23
HLP1-23 HLP1-23
HLP1-23 HLP1-23
HLP1-23 HLP1-23 INV-1 HLP1-23 HLP1-23 HLP1-23 INV-1 HLP1-23 HLP1-23 INV-1
HLP1-23
HLP1-23
INV-1
INV-1
m m
INV-1
INV-1 HLP1-23
HLP1-23
HLP1-23
HLP1-23HLP1-23
HLP1-23
HLP1-23HLP1-23HLP1-23INV-1HLP1-23
INV-1
INV-1
HLP1-8
INV-1
INV-1 INV-1
INV-1
INV-1
INV-1
INV-1
INV-1
INV-1
INV-1
INV-1
INV-1
INV-1
INV-1
INV-1
INV-1
INV-1
INV-1 INV-1 INV-1 INV-1
INV-1INV-1
INV-1
HLP1-23
HLP1-7HLP1-7
HLP1-7 HLP1-7
HLP1-7HLP1-7
HLP1-7HLP1-7
HLP1-7HLP1-7
HLP1-7
HLP1-7
HLP1-7 HLP1-7 HLP1-7 HLP1-7 HLP1-7
HLP1-7HLP1-7
HLP1-7 HLP1-7
HLP1-7
HLP1-7
HLP1-7 HLP1-7
HLP1-7HLP1-7
HLP1-7 HLP1-7
HLP1-7
HLP1-7
HLP1-7
HLP1-7HLP1-7HLP1-7
HLP1-7 HLP1-7
HLP1-7HLP1-7
HLP1-21HLP1-21HLP1-21
HLP1-21
HLP1-21 HLP1-21
HLP1-21 HLP1-21
INV-1
HLP1-21
HLP1-21
HLP1-21
HLP1-21
V1
HLP1-17HLP1-17
HLP1-17 HLP1-17HLP1-17
HLP1-17HLP1-17
HLP1-17HLP1-17
HLP1-17HLP1-17
HLP1-17HLP1-17
HLP1-17HLP1-17
HLP1-17HLP1-17HLP1-17
HLP1-17 HLP1-17HLP1-17
HLP1-17HLP1-17
HLP1-17
HLP1-17
HLP1-17HLP1-17
HLP1-17HLP1-17HLP1-17
HLP1-17 HLP1-17
HLP1-17HLP1-17HLP1-17HLP1-17
HLP1-17 HLP1-17 HLP1-17
HLP1-17HLP1-17HLP1-17HLP1-17
A1
HLP1-17 HLP1-17 HLP1-17
HLP1-17HLP1-17
HLP1-17 HLP1-17
HLP1-17HLP1-17
HLP1-17 HLP1-17
HLP1-19
HLP1-19 HLP1-19
HLP1-19 HLP1-19
HLP1-19 HLP1-19
HLP1-19 HLP1-19
HLP1-19 HLP1-19
HLP1-19
HLP1-19
HLP1-19
HLP1-19
HLP1-19
HLP1-19 HLP1-19
HLP1-19 HLP1-19
HLP1-19 HLP1-19
HLP1-19
HLP1-19
HLP1-19 HLP1-19
HLP1-19
HLP1-19 HLP1-19
HLP1-19 HLP1-19
HLP1-19
HLP1-5
HLP1-5
HLP1-5
HLP1-5
HLP1-5
HLP1-5
HLP1-5
HLP1-5
HLP1-5
HLP1-5
HLP1-5
HLP1-5
HLP1-5 HLP1-5
HLP1-5
HLP1-5
HLP1-5 HLP1-5
HLP1-5
HLP1-5
HLP1-5
HLP1-5
HLP1-5
HLP1-5
HLP1-5 HLP1-5
HLP1-5 HLP1-5
HLP1-5 HLP1-5
HLP1-5
HLP1-5
HLP1-19 HLP1-19
HLP1-19HLP1-19
HLP1-5
HLP1-5
HLP1-5
HLP1-5
HLP1-5
INV-1HLP1-8INV-1
HLP1-8
HLP1-8
HLP1-8
HLP1-8
HLP1-8
HLP1-8
HLP1-8
HLP1-8
HLP1-8
HLP1-8
HLP1-8
HLP1-8 HLP1-8 HLP1-8 HLP1-8 HLP1-8 HLP1-8 HLP1-8
HLP1-8
INV-1
HLP1-8
HLP1-8
HLP1-8
HLP1-8
HLP1-8
HLP1-19
HLP1-19
HLP1-19
HLP1-19
CLOSET
HLP1-8 HLP1-8
HLP1-8
HLP1-8
HLP1-8
HLP1-8 HLP1-8 HLP1-8 HLP1-8 HLP1-8 HLP1-8
HLP1-6HLP1-6
HLP1-6HLP1-6
HLP1-6
HLP1-6
INV-2
h
P1
P1
P1
P1
P1j j j d d
AX4
b h
HLP1-8
HLP1-5 HLP1-5
HLP1-5
HLP1-5
HLP1-5
OS
SQ4
INV-2
SQ4SQ4
SQ4
SQ4
SQ4
SQ4
HLP1-6HLP1-6
HLP1-6
HLP1-6
HLP1-6
HLP1-6
3 333
X1
INV-1
1 SL HLP1-6
A1 aHLP1-23
A1 aHLP1-23 m nn c
X2
HLP1-8
X2
X2
INV-1 INV-1
INV-1
LV1b
LV1b
LV1b
LV1b
LV1h
LV1g
LV1f
C1 C1
HLP1-5HLP1-5
b
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
BI
M
- C on st ru ct
R ep la ce m en t O ut pa tie nt C lin ic
/0
C on st . R ep la ce . O ut pa tie nt
C lin ic
R
.rv t
2/ 9/
2:
:4
PM
E-201
PARTIAL FIRST FLOOR PLAN -
ELEC. LIGHTING - WEST
REPLACEMENT OUTPATIENT
CLINIC DESIGN AT COAST
GUARD CAPE COD
JOINT BASE CAPE COD, BARNSTABLE MA
650-318
BUILDING 1
02/10/2023 JFR KEM
100% CONSTRUCTION
DOCUMENTS
0 4' 8' 12' 16'
3/16" = 1'-0"
N
3/16" = 1'-0"E-201
1 FIRST FLOOR PLAN - ELEC. LIGHTING PLAN - WEST
CODED NOTES:
EXTERIOR LIGHTING FIXTURES SHALL BE CONTROLLED WITH AREA SITE LIGHTING WITH SWITCHPACK
TO BE WAVELINX PRO WSP-UV-010.
EXTERIOR LIGHTING FIXTURES SHALL BE CONTROLLED WITH AREA SITE LIGHTING WITH UL924 LIFE
SAFETY SWITCHPACK TO BE WAVELINX PRO WSP-UV-010-EM.
ALIGN FIXTURE IN CEILING PLANKS.
PROVIDE JUNCTION BOX AND 3/4" CONDUIT WITH PULLWIRE UP TO ACCESSIBLE CEILING SPACE FOR LOW VOLTAGE PROCEDURE LIGHT CONTROL. SEE FIXTURE TYPE C1 IN LIGHTING FIXTURE SCHEDULE
FOR FURTHER DETAILS.
DRAWING NOTES:
1. LIFE SAFETY LIGHTING SHALL BE CONNECTED TO A CENTRAL BATTERY INVERTER. ALL LIGHTING
FIXTURES SHALL BE CONTROLLED BY LOCAL LIGHTING CONTROLS.
REF.
OS OS
OS
OS
OS OS
OS
OS
LPD
LPD
OS
LPD
LPP
LPP
LPP
LPE
LPE
LPE LPP
LPE
C B A
OFFICE
UTILITY SOILED
MECHANICAL
162JANITOR CLOSET
WORKSTATIONS,
MENTAL HEALTH
STAFF LOUNGE &
LOCKERS
STORAGE MEDICAL
& GENERAL
TLMP1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A2
A2 A2
A2
A2
A2
A2 A2 A2
A2A2 A2
L2
L2
A1 A1
A1 A1
A1
A1
A1
A1
A1
A1
A1
A1A1
A1
A1A1
L1
L1
L1
L1
L1 L1
OS
k k k k k k k kk k
LV1D LV1D
LV1a
X2
X1 a a a a a a a a p p ad a p
SL1
SL1
SL1
OS
OFFICE
OS
UTILITY CLEAN
LV1
ELECTRICAL ROOM
L1
LV1
LV1
LV1Dk
L2
M
AT
C H
LI
N
E -C
O N
TI
N
U
ED
O N
D W
G
/E -2
B.7 A.4
5.5
3.7
3.6
3.3
3.1
2.7
2.5
2.4
1.9
1.5
1.3
SL1
SQ4
LV1
LV1
L1 L1 L1
L1 L1 L1
A1
A1 A1
INV-1
HLP1-1
INV-1
HLP1-1 HLP1-1HLP1-1HLP1-1
HLP1-23 INV-1
HLP1-1 HLP1-1
INV-1
HLP1-1
HLP1-1
HLP1-1 HLP1-1 HLP1-1
HLP1-1
HLP1-1
HLP1-1
HLP1-1
HLP1-1
HLP1-1
HLP1-23
HLP1-23
HLP1-23
HLP1-23
HLP1-23
HLP1-1
HLP1-1
HLP1-1
INV-1
HLP1-1
HLP1-1 HLP1-1
HLP1-1
HLP1-1
HLP1-1 INV-1
HLP1-1 HLP1-1
HLP1-1
HLP1-1 HLP1-1 HLP1-1 HLP1-1
HLP1-1HLP1-1HLP1-1HLP1-1
INV-1
INV-1
INV-1
INV-1
INV-1
INV-1
INV-1
INV-1
HLP1-6
HLP1-6
HLP1-6
HLP1-6
INV-2
LRP2A
LRP1A
LMP1
UPS
LOS1
TLRP1
TLRP2
HMP1
HLP1
MDP
SL2
SL2
INV-2
INV-2
COMMUNICATIONS
L2
HLP1-1
a
A1
HLP1-23
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
BI
M
- C on st ru ct
R ep la ce m en t O ut pa tie nt C lin ic
/0
C on st . R ep la ce . O ut pa tie nt
C lin ic
R
.rv t
2/ 9/
2:
:5
PM
E-202
PARTIAL FIRST FLOOR PLAN -
ELEC. LIGHTING - EAST
REPLACEMENT OUTPATIENT
CLINIC DESIGN AT COAST
GUARD CAPE COD
JOINT BASE CAPE COD, BARNSTABLE MA
650-318
BUILDING 1
02/10/2023 JFR KEM
100% CONSTRUCTION
DOCUMENTS
3/16" = 1'-0"E-202
1 FIRST FLOOR PLAN - ELEC. LIGHTING PLAN - EAST
CODED NOTES:
EXTERIOR LIGHTING FIXTURES SHALL BE CONTROLLED WITH AREA SITE LIGHTING WITH SWITCHPACK
TO BE WAVELINX PRO WSP-UV-010 OR EQUAL.
EXTERIOR LIGHTING FIXTURES SHALL BE CONTROLLED WITH AREA SITE LIGHTING WITH UL924 LIFE
SAFETY SWITCHPACK TO BE WAVELINX PRO WSP-UV-010-EM OR EQUAL.
WIRELESS CONTROL GATEWAY TO CONTROL EXTERIOR LIGHTING. SEE LUMINAIRE SCHEDULE
NOTE 6 ON SHEET E-801.
BATTERY LIGHTING INVERTER INV. REFER TO ONE-LINE DIAGRAM ON SHEET E-601 FOR FURTHER
INFORMATION.
DRAWING NOTES:
0 4' 8' 12' 16'
3/16" = 1'-0"
N
1. LIFE SAFETY LIGHTING SHALL BE CONNECTED TO A CENTRAL BATTERY INVERTER. ALL LIGHTING
FIXTURES SHALL BE CONTROLLED BY LOCAL LIGHTING CONTROLS.
R
EF
R
EF
J
J
J
J
J
J
J J
J
J
M
J
J
J
J J
J
J
J
J J
J
J
J
J
J J
J J
J
J
J
J
J
J JJ J
J J
J
J
J
J
J
J
J
J
J
J
J
J
J J
JJ
J
J J
JJ
J J
J
J
J
J J J J J J J
J
JJ
J
J
J
J
J
J
J J
J
J
J
J
J
J
J
J
J J
JJ
J
H G F E D
I
VESTIBULE
WAITING
CORRIDOR
WAITING
105 RECEPTION
RECEPTION
WORKROOM
NURSE MANAGER
TOILET PUBLIC
TOILET PUBLIC
VOLUNTEER
CORRIDOR
SOCIAL WORKER
CLOSET
ELEC
SPECIMEN
COLLECTION
TOILET WMN'S
TOILET PATIENT
EXAM RM WOMEN'S
HEALTH
ULTRASOUND
TREATMENT
EXERCISE AREA
EXAM / PT/OT
EXAM / TRIAGE
PROCEDURE
ROOM, GENERAL
TOILET PROC.
TOILET STAFF
EXAM /
TELE-HEALTH
EXAM
CLOSET
CORRIDOR
MED ROOM
TOILET STAFF
TEAM WORK AREA
EXAM/TRIAGE
EXAM / MENTAL
HEALTH
EXAM /
TELE-HEALTH
EXAM / AUDIOLOGY
EXAM / EYE TEST
EXAM
MULTI-PURPOSE
ROOM
MULTI-PURPOSE
ROOM
GROUP THERAPY
ROOM, MENTAL
HEALTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
CONSULT RM,
MENTAL HLTH
LRP3A
G,48"
G
G,CH
G,48" G,48"G,48"
G,+48"
TV,60"
TV,60"
G
G,CH G,CH
G
G,CH
G
G,CH
G
G,CH
G
G,CH
G
G,CH
G
FACP
G,44"
G,48"
G,48"
G,+48"
G,+48"
CH
CH
+48",G
44",G
+48",G
44",G
+36"
G
G,CH
G,+48"
CH,G
CH,G
G,36"
+48"
TV,G,60"
G,44"
+36",G
G
+48"
44",G
+36"
G,48"
7 7 7
9 9
+48"
48"
USB
USBUSB
USB
M
AT
C H
LI
N
E -C
O N
TI
N
U
ED
O N
D W
G
/E -2
H.2 H.1 F.7 F.5 F.3 E.5 D.9 D.7 D.6 D.5 D.3 C.6 C.5 C.3
5.5
3.7
3.6
3.3
3.1
2.7
2.5
2.4
1.9
1.5
1.3
USB
44",G
G,44"
TOILET PATIENT
+60"
44"
15 15
LOS1-3
LRP3A-37
LRP3B-10
LRP3B-10
LRP3B-10
LRP3A-18
LRP3A-18
LRP3A-31
LRP3A-23
LRP3A-23
LRP3A-23
LRP3A-20 LRP3A-20
LRP3A-20
LRP3A-20
LRP3A-14
LRP3A-14
LRP3A-14
LRP3A-14
LRP3A-7
LRP3A-28
LRP3B-20 LRP3B-20
LRP3A-28
LRP3A-23
LRP3A-31
LRP3B-20
LRP3A-28
LRP2B-4
LRP3B-21
LRP3A-28
LRP2B-4
LRP3B-21
LRP3A-31
LRP2B-6
LRP3B-21
LRP2B-4
LRP2B-8
LRP2B-5
LRP2B-4
LRP3B-3
LRP3B-3
LRP3A-16 LRP3A-17
LRP3A-12
LRP3A-12
LRP3A-42
LRP3A-43
LRP3A-42
LRP3A-53
LRP3A-54
LRP3A-53
LRP3A-50
LRP3A-50
LRP3A-49
LRP2B-13
LRP2B-13
LRP2B-14LRP3A-31 LRP2B-7LRP3A-34
LRP3A-32
LRP2B-10LRP3A-33
LRP3A-33
LRP3A-26
LRP3A-26
LRP3A-25
LRP3A-12
LRP3A-11
LRP3A-44
LRP3A-45
LRP3A-46 LRP3A-46
LRP3A-45 LRP3A-45
LRP3A-61,63
LRP3A-46
LRP2B-12
LRP2B-11
LRP2B-11
LRP2B-11
LRP3A-52
LRP3A-52
LRP3A-51
LRP3A-38
LRP3A-36
LRP3A-38
LRP3A-37
LRP3A-37
LRP3B-11
LRP3A-17
LRP3A-17
LRP3A-14
LRP3B-4
LRP3A-17
LRP3A-35
LRP3A-35LRP3A-35
LRP3A-17
LRP3A-37
LRP3A-47
LRP3A-47LRP3A-37LRP3A-37
LRP3A-35LRP3A-35
LRP2B-11
LRP3A-6
LRP3A-7
LRP3A-7
LOS1-1
LRP3B-2 LRP3A-44
LRP3A-18
LRP2B-6
LRP2B-8
LRP3A-46
LRP3A-44
LRP3A-44
LRP3A-45
LRP3A-44
LRP3A-43
LOS1-2
LRP3A-17
LRP3A-48
LRP3A-5
LRP3A-18
LRP3A-7
LRP3A-4
LRP3A-4
LRP3A-4
LRP3A-5
LRP3A-5
LRP3A-1
LRP3A-2
LRP3A-2
LRP3A-2 LRP3A-2
LRP3A-6
LRP3A-8 LRP3A-8
LRP3A-8
LRP3A-8
LRP3A-8
LRP3A-9
LRP3A-10 LRP3A-10
LRP3A-10
LRP3A-10
LRP3A-12
LOS1-7
LOS1-6
LOS1-6
LOS1-6
LOS1-9
LRP3A-13
LRP3A-15
LOS1-6
LOS1-7
LOS1-7
LOS1-7
LOS1-6
LOS1-7
LOS1-8
LOS1-9
LOS1-8
CORRIDOR
LOS1-6
LRP3A-13
ALCOVE, SCALE
LOS1-2
LOS1-4
LRP3A-19 LRP3A-19
LRP3A-19
LRP3A-19
LRP3A-19
LRP3A-22
LRP3A-24
TV,60"
LRP3A-22
LRP3A-24
LRP3A-26
+36"
+36" +36"
+36" +48",G
+36"
LRP3A-38
+48"
+36"
LRP3A-33
LRP3A-27
+36" +36" +36"
CH,G
CH
CH,G
LRP3A-27 LRP3A-27 LRP3A-27 LRP2B-9 LRP2B-9 LRP2B-9 LRP2B-9
LRP2B-10
LRP3A-27
LRP3A-29 LRP3A-29 LRP3A-29
LRP3A-36
LRP3A-36
LRP3A-39
LRP3A-39
LRP3A-39
LRP3A-39
LRP3A-40
LRP3A-41
+36"
+48"
LRP3A-43
LRP3A-33
LRP3A-52
LRP3A-52
LRP3A-47
LRP3A-47
LRP3A-53
LRP3A-53
LRP3A-50
LRP3A-50
LRP2B-13
LRP2B-13
LRP2B-9
LRP2B-10
LRP2B-5LRP2B-5LRP2B-3LRP2B-3
MS-EPAR
LRP3A-56
LRP3A-55
+48"
+48" +48"
LRP3A-58
+48"
LRP3A-57
LRP2B-1
LRP3A-60
LRP3A-59
LRP3A-6
LRP3A-6
+48"
+48"
LRP3B-7
+48"+48"
+48" +48"
LRP3B-8LRP3B-9
+48"
+48"
LRP2B-2
+48" +48"
+48"
LRP3B-611
+48"
+48"
LRP3B-5
LRP3B-4 LRP3B-4
LRP3B-3
LRP3B-3
LRP3B-4
LRP3B-4
LRP3B-2
+48"
LRP3B
LRP3B-12
+48"
LRP3B-12
+48"
TV,72"
LRP3A-2
LRP3A-24
TV,72"
LRP3A-1
USB
LRP3A-1
44"
LRP3A-6
G,44"
LRP3A-10
+48"
LRP3A-3
LRP3A-30
G,CH
LRP3A-12
+48"
+48"
LRP3B-1
+48"+48"
LRP3B-13
LRP3B-14
LRP3B-15 LRP3B-15
LRP3B-15 23
23 23
LRP3B-14
LRP3B-14 23
LRP3B-14
LRP3B-26
23 LRP3B-16
LRP3B-16 LRP3B-16 LRP3B-1623 23 23 LRP3B-17 LRP3B-17 LRP3B-17 LRP3B-17
LRP3B-18
LRP3B-18
LRP3B-18 23
LRP3B-19 24
LRP3B-23
LRP3B-23
LRP3B-23
LRP3B-24
20LRP3B-24
CH LRP2B-11
LRP3B-26
LRP3B-1623
23 23 23 23
LRP3B-18
LRP3B-27 23LRP3B-27 23
LRP3B-28
LRP3B-28
LRP3B-28
LRP3B-28
LRP3B-28 23
LRP3B-29
LRP3B-29
LRP3B-29
LRP3B-29 23
LRP3B-30LRP3B-30
LRP3B-30LRP3B-30
23 23
LRP1B-9,1110
LRP2A-1
LRP2A-5 LRP2A-6
LRP2A-4 LRP2A-3
LRP2A-7 LRP2A-8
LRP2A-2
G,WP
G,WP
G,WP
LRP1B-10
LRP1B-10
LRP1B-10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
BI
M
- C on st ru ct
R ep la ce m en t O ut pa tie nt C lin ic
/0
C on st . R ep la ce . O ut pa tie nt
C lin ic
R
.rv t
2/ 9/
2:
:0
PM
E-203
PARTIAL FIRST FLOOR PLAN -
ELEC. POWER - WEST
REPLACEMENT OUTPATIENT
CLINIC DESIGN AT COAST
GUARD CAPE COD
JOINT BASE CAPE COD, BARNSTABLE MA
650-318
BUILDING 1
02/10/2023 JFR KEM
100% CONSTRUCTION
DOCUMENTS
CODED NOTES:
REFRIGERATOR - 120V, 1.0KW ASSUMED. WIRE TO 20/1 POLE GFCI BRANCH CIRCUIT BREAKER
INDICATED.
COPIER - 120V, 1.5KW ASSUMED.
NOTE REMOVED.
NOTE REMOVED.
MEDICATION DISPENSING SYSTEM AND REFRIGERATOR - 120V, 1.0KW ASSUMED.
EXAM CHAIR - 120V, 1.5KW ASSUMED.
PROVIDE RECESSED IN-GRADE 4-GANG RECTANGULAR FLOOR BOX (HUBBELL #AFB4G50), 5.5" DEEP
MINIMUM, UL514A SCRUBSHIELD COMPLIANT, BLACK POWER COATED COVER (HUBBELL #
4GAFBCVRBK), (2) DUPLEX PLATES (HUBBELL #FBMPDUP), (2) TELEDATA KEYSTONE JACK PLATES (HUBBELL #FBMP6KS) AND ALL PARTS AND ACCESSORIES FOR A COMPLETE SYSTEM. EQUALS BY FSR OR WIREMOLD. PROVIDE (1) 1" CONDUIT WITH PULLWIRE TO ACCESSIBLE CEILING SPACE FOR
DATA/AV CABLING BY OTHERS.
PROVIDE 120V POWER FOR WATER FOUNTAIN WITH BOTTLE FILLER - 120V, 1.0 AMPERE, 0.12KW.
WIRE TO 20/1 GFCI BRANCH CIRCUIT BREAKER INDICATED. COORDINATE WITH FOUNTAIN INSTALLER
FOR MOUNTING LOCATION.
PROVIDE RECESSED IN-GRADE 2-GANG RECTANGULAR FLOOR BOX (HUBBELL #AFB2G50), 5" DEEP
MINIMUM, UL514A SCRUBSHIELD COMPLIANT, BLACK POWER COATED COVER (HUBBELL #
2GAFBCVRBK), DUPLEX PLATE (HUBBELL #FBMPDUP), TELEDATA KEYSTONE JACK PLATE (HUBBELL
#FBMP6KS) AND ALL PARTS AND ACCESSORIES FOR A COMPLETE SYSTEM. EQUALS BY FSR OR
WIREMOLD. PROVIDE (1) 1" CONDUIT WITH PULLWIRE TO ACCESSIBLE CEILING SPACE FOR DATA/AV
CABLING BY OTHERS.
JUNCTION BOX FOR FUTURE X-RAY. PROVIDE (2) #12AWG CU, #12AWG CU GROUND IN 3/4" CONDUIT
TO LOCATION SHOWN. CONTRACTOR TO LABEL JUNCTION FOR FUTURE X-RAY USE.
MOTORIZED DOOR WITH PUSH PAD CONTROLS BY GENERAL CONTRACTOR. ELECTRICAL
CONTRACTOR TO INSTALL ALL POWER AND CONTROL WIRING AND MOUNT PUSH PAD CONTROL
STATIONS. ALL CONDUIT AND WIRING MUST BE CONCEALED. COORDINATE EXACT PUSH PAD
LOCATIONS WITH OWNER PRIOR TO ROUGH-IN.
ELECTRICAL CONNECTION FOR PATIENT LIFT. COORDINATE EXACT LOCATION AND MOUNTING
HEIGHT WITH PATIENT LIFT PRIOR TO CONSTRUCTION.
POWERED PARTITION CONTROLS. COORDINATE EXACT LOCATION AND INSTALLATION
REQUIREMENTS WITH POWERED PARTITION INSTALLATION INSTRUCTIONS. PROVIDE BACK BOX AND
3/4" CONDUIT WITH PULL STRING TO ABOVE ACCESSIBLE CEILING FOR POWERED PARTITION
CONTROL CABLING.
SAFETY DISCONNECT FOR POWERED PARTITION MOUNTED AT 7'-0" AFF. COORDINATE EXACT
LOCATION OF DISCONNECT WITH POWERED PARTITION CLEARANCES.
PROVIDE 120V JUNCTION BOX ABOVE ACCESSIBLE CEILING ON SECURE SIDE OF DOOR FOR ACCESS
CONTROL HARDWARE. PROVIDE LABEL STATING "ACCESS CONTROL 120V" AND CONNECT TO
BRANCH CIRCUIT BREAKER INDICATED WITH LOCK-ON ACCESSORY.
GENERATOR REMOTE ANNUNCIATOR PANEL. SEE GENERATOR CONTROL DIAGRAM ON SHEET E-601
FOR DETAILS. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT WITH VA PRIOR TO
CONSTRUCTION.
DUPLEX OUTLET FOR MINI FRIG LOCATED BELOW COUNTER. COORDINATE EXACT LOCATION AND
MOUNTING HEIGHT OF RECEPTACLE WITH MILL WORK PRIOR TO CONSTRUCTION. RECEPTACLE TO
BE CONNECTED TO GFCI TYPE BREAKER.
CONDUIT ROUTED BELOW SLAB TO NEAREST FULL HEIGHT WALL.
ULTRASOUND MACHINE OUTLET. COORDINATE EXACT LOCATION WITH ARCHITECTURAL EQUIPMENT
LAYOUT PRIOR TO CONSTRUCTION.
AED CABINET - 120V, 0.5KW ASSUMED.
SHREDDER - 120V, 0.5KW ASSUMED.
E.C. TO…