Attachment 16 - Mechanical 2 of 2.pdf
PDF 865 KB Posted
- Solicitation number
- 36C77624R0087
About this file
This document contains mechanical drawings, equipment schedules, and control sequences for a federal construction project to replace an outpatient clinic facility. The project is for the Department of Veterans Affairs and is located at the US Coast Guard Air Station in Cape Cod, Massachusetts. The key details include:
The mechanical systems include a 80-ton air-cooled chiller with redundant chilled water pumps, a gas-fired condensing boiler system with redundant hot water pumps, variable air volume air handling units, terminal units, exhaust fans, and a steam humidifier. Control sequences are provided for the major mechanical systems, including the chiller plant, boiler plant, air handling unit, and variable air volume terminals. Equipment schedules are included for pumps, fans, air handling units, chillers, boilers, and air distribution devices. The project includes the replacement of the existing outpatient clinic facility at the Coast Guard base.
View the file
Other files
Show all 46
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AUTOMATIC FLOW CONTROL
DEVICE PRESET BY MANUF. W/
P & T TEST PORTS, STRAINER,
AND DRAIN.
CHWR
CHWS
SHUT-OFF
VALVE (TYP.)
P/T TEST PORTS
STRAINER W/ BLOWDOWN &
HOSE CONNECTION
(PROVIDE STAINLESS STEEL
STRAINER BASKET)
UNION (TYP.)
THERMOMETER W/
SEPARABLE WELL (TYP.)
MANUAL AIR VENT W/
AUTO SHUT-OFF COCK
COIL
AIRFLOW
PRESSURE
GAUGE &
COCK (TYP.)
TWO WAY
CONTROL
VALVE
NOTES:
1. PROVIDE 4 X DIAMETER OF STRIAGHT PIPE ON BOTH SIDES OF BALANCING VALVE.
2. ALL COMPONENTS FULL SIZE UNLESS NOTED OTHERWISE.
3. LOCATE UNIONS TO ALLOW FOR COIL PULL.
4. PROVIDE 3-WAY VALVE WHERE INDICATED IN DRAWINGS WITH CODED NOTE NEXT TO THE EQUIPMENT TAG.
AUTOMATIC FLOW CONTROL
DEVICE PRESET BY MANUF. W/
P & T TEST PORTS, STRAINER,
AND DRAIN.
CHWR
CHWS
SHUT-OFF
VALVE (TYP.)
P/T TEST PORTS
STRAINER W/
BLOWDOWN
UNION (TYP.)
THERMOMETER W/
SEPARABLE WELL (TYP.)
MANUAL AIR VENT W/
AUTO SHUT-OFF COCK
COIL
AIRFLOW
PRESSURE
GAUGE &
COCK (TYP.)
THREE WAY
CONTROL
VALVE
PLUG COCK
NOTES:
1. PROVIDE 4 X DIAMETER OF STRIAGHT PIPE ON BOTH SIDES OF BALANCING VALVE.
2. ALL COMPONENTS FULL SIZE UNLESS NOTED OTHERWISE.
3. LOCATE UNIONS TO ALLOW FOR COIL PULL.
SECTION "A-A"
"B" "B"
ACCESS PANEL
ACCESS DOOR
CASING GASKET HANDLE INSIDE
FLEXIBLE
WASHER
FACTORY
FABRICATED
LATCH
SECTION "B-B"
INSULATION
DUCT
GASKET
INSULATION
INSULATION
"A"
"A"
HOUSING WELDED TO
DUCT SECTION
ROUND OR
FLAT OVAL
DUCT
SECTION
COVER WITH
HANDLE AND
CHAIN RETAINER
GASKETED AND
PRESSURE SEALED
CHWR
PRESSURE GAUGE
(TYP.)
CHWS
BUTTERFLY VALVE
(TYP.)
TEMPERATURE TRANSMITTER
(TYP.)
THERMOMETER (TYP.)
FLOW SWITCH FLEX CONNECTION
(TYP.)
CONTROL
PANEL
NEC
CLEARANCE
4'-0"
NOTE: SUPPLY OUTLET AND RETURN INLET LOCATION MAY DIFFER BASED ON MANUFACTURER.
SA
FLOOR DRAIN
(SEE PLUMBING DRAWINGS
CONDENSATE MOUNTED
ON UNISTRUT SUPPORT
AND ANCHORED TO FLOOR
FINAL FILTER
SUPPLY FAN
PRE-FILTERS
RA
PLENUM
BASE RAIL
CONCRETE PAD
MIXING
BOX
FILTER ACCESS DOOR
FAN SECTION WITH ACCESS DOOR
DISCHARGE
PLENUM WITH
ACCESS DOOR
FLEX CONNECTION, TYP.
CHWS & RST
RA
OA
1 TO 2 GALLON, HOT-
DIP GALVANIZED TANK
PUMP DISCHARGE LINE
FILL FUNNEL W/
WEATHER PROOF
COVER
MANUAL AIR VENT
DRAIN VALVE
PIPE TO FLOOR
DRAIN
PUMP SUCTION LINE
BALL VALVE,
TYP.
A
B B
A
CONCRETE BASE
L
W
5D
5D
2D
ANCHOR BOLT (TYP)
PIPE SLEEVE (5D, 3" MIN.)
1"
WELD HEAD TO PLATE
OR BEND OVER END 5D
PLAN SECTION B-B
SECTION A-A (BASE POURED WITH FLOOR SLAB)
TYPICAL ANCHOR
BOLT NUT & WASHER
16"
EQUIPMENT BASE
L/1
PROVIDE DOUBLE SLAB
REINFORCING IN BASE AREA
SECTION A-A (BASE NOT POURED WITH SLAB)
PROVIDE #3 BARS 12" O.C.
EACH WAY IN THE BASE &
DOWEL BASE TO FLOOR
TYPICAL ANCHOR
BOLT NUT & WASHER EQUIPMENT BASE
L/1
NOTE:
L & W DIMENSIONS SHALL
BE 6" GREATER THAN THE
EQUIPMENT BASE PLATE.
HORIZONTAL
ABOVE 2" DIA. PIPE 2" DIA. PIPE AND SMALLER
VERTICAL
ABOVE 2" DIA. PIPE 2" DIA. PIPE AND SMALLER
2-1/2" DIA.
2-1/2" DIA.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
BI
M
- C on st ru ct
R ep la ce m en t O ut pa tie nt C lin ic
/0
C on st . R ep la ce . O ut pa tie nt
C lin ic
R
.rv t
2/ 9/
0:
:1
AM
M-501
MECHANICAL DETAILS REPLACEMENT OUTPATIENT
CLINIC DESIGN AT COAST
GUARD CAPE COD
JOINT BASE CAPE COD, BARNSTABLE MA
650-318
BUILDING 1
02/10/2023 JFR JJA
100% CONSTRUCTION
DOCUMENTS
N.T.S.
2-WAY PIPING DIAGRAM DETAIL1
N.T.S.
3-WAY PIPING DIAGRAM DETAIL2
N.T.S.
ACCESS PANEL AND DOOR DETAIL3
N.T.S.
ACCESS SECTION FOR ROUND DUCT DIAGRAM4
N.T.S.
AIR COOLED CHILLER PIPING DETAIL5
N.T.S.
AIR HANDLING UNIT DIAGRAM6
N.T.S.
CHEMICAL SHOT FEEDER DIAGRAM8
N.T.S.
CONCRETE EQUIPMENT BASES DETAIL9
N.T.S.
INSTALLATION OF THERMOMETER WELLS DIAGRAM7
Revisions Date
UNION
DRAIN PAN (FURNISHED
WITH UNIT)
PRIMER PLUG
CLEAN OUT
PITCH DOWN
TOWARD DRAIN
L DIMENSIONS:
L = H + J + PIPE DIAMETER
H = 1 INCH FOR EACH INCH OF NEGATIVE
PRESSURE (INTERNAL PLUS RETURN
STATIC PRESSURE) + 1 INCH
J = 1/2 H
H
J
18 GAUGE STAINLESS STEEL
STRAPS 1" WIDE MIN (DO
NOT BLOCK ACCESS
PANELS) 2-MIN PER 4'0".
WRAP CONTINUOUS OVER
CONDENSER AND SECURE
TO CONCRETE PAD WITH
1/4"X1-1/2" STAINLESS
STEEL CONCRETE SCREWS
OR ANCHORS. (EACH SIDE)
4" THK
FIBERMESH
REINFORCED
CONCRETE PAD
6" MIN
ALL
SIDES
CONDENSING UNIT
PROVIDE 6" CLEAR
GRAVEL AROUND
CONDENSER. SOD
THEREAFTER.
DDC CONTROL
PANEL BY DIV 23
NOTE:
120 V/24 VAC CONTROL PANEL
TRANSFORMER SIZED TO MEET
LOAD REQUIREMENTS OF
TERMINAL UNIT CONTROLLERS
AND MISCILANEOUS LOW VOLTAGE
EQUIPMENT.
CPT CONTROL
PANEL BY DIV 23
TERMINAL UNIT
(EXPAMPLE)
SWITCH
FUSE
SWITCH
TO TERMINAL UNITS AND LOW
VOLTAGE EQUIPMENT
LOW VOLTAGE
POWER BY DIV 23
24 VAC TO
TU
CONTROL
120 VAC BY DIV 26
SE
E
NO
TE
SEE NOTE 3
SEE NOTE 2
SEE NOTE 1
NOTES:
1. RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A MINIMUM OF 3 TIMES THE DIAMETER OF INLET.
2. A FLEXIBLE AIR DUCT CONNECTOR IS NOT MANDATORY FOR INLET TO THIS BOX, BUT ALLOWED TO ACCOMMODATE MINOR
OFFSETS. MAXIMUM LENGTH 3'-0".
3. A BRANCH DUCT SERVING AN INDIVIDUAL BOX MAY BE THE SAME SIZE AS THE BOX INLET, PROVIDED THE EQUIVALENT LENGTH
OF THE BRANCH DUCT, AS SHOWN, DOES NOT EXCEED 10 FEET. FOR LONGER LENGTHS, INCREASE THE DUCT SIZE AND PROVIDE A DUCT TRANSITION TO MAINTAIN THE DUCT STATIC PRESSURE DROP AT OR BELOW 0.2"/100'.
4. FLEXIBLE AIR DUCT CONNECTORS, WHEN USED FROM TERMINAL UNIT SUPPLY AIR DUCT TO DIFFUSER, SHALL NOT EXCEED
5'-0". USE RIGID ELBOWS FOR CHANGE OF DIRECTION GREATER THAN 45°.
5. COMPONENT ARRANGEMENT MAY VARY BY MANUFACTURER. PROVIDE INSULATION W/VAPOR BARRIER FOR CONNECTING
DUCT SECTIONS.
6. DUCT CONNECTION TO BOX SHALL BE SAME DIMENSIONS AS BOX OUTLET AND SHALL MAINTAIN THESE DIMENSIONS (UNLESS
OTHERWISE INDICATED) UNTIL CHANGE IN DUCT SIZE INDICATED ON DRAWINGS.
AIR TERMINAL
UNIT (CV OR VAV)
REHEAT COIL
FLEXIBLE AIR DUCT
CONNECTOR. SEE DETAIL
DIFFUSER (TYP.)
SEE SPECIFICATIONS FOR
CLAMPS AND SEALANT (TYP.)
SEE NOTE 5
FL
OW SEE NOTE 7
HANGERS MUST NOT DEFORM DUCT SHAPE
TRAPEZE HANGERS
SIZE BOLTS FOR LOAD
STRAP OR
ANGLE
OPTIONAL ATTACHMENTS STRAP
HANGER RODS,
WIRES OR
STRAPS
BAND; ONE HALF-
ROUND MAY BE USED IF
DUCT SHAPE IS
MAINTAINED
10" DIA. MAX. 36" DIA. MAX. 24" DIA. MAX.
SECURE
WIRE
HANGER LOAD
FASTENERS
W
1/3 W
R
1/3 W1/2W
W
2/3W
R
W
R
VANE
R SHALL
EQUAL
OR BE
GREATER
THAN W.
R SHALL
EQUAL OR
BE
GREATER
THAN 1/3W.
R SHALL
EQUAL OR
BE
GREATER
THAN 1/6W.
NOTES:
1. THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.
2. ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS ELBOWS. ALL SHORT RADIUS
ELBOWS SHALL HAVE VANES. VANES SHALL BE CONSTRUCTED, SUPPORTED AND FASTENED AS
RECOMMENDED BY SMACNA.
NOTES:
1. ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.
2. WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE REGARDLESS OF W
DIMENSION.
3. ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2" [40mm] MAXIMUM SPACE
BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE.
4. WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL BE DOUBLE VANE TYPE.
W1
W
MAIN EXHAUST OR RETURN
PLAN VIEW
AIR
FLOW AIR
FLOW
PROVIDE VOLUME DAMPER
AT EACH BRANCH DUCT
1/4W OR 4" MIN.
BRANCH
DUCT
VD
W
DISCHARGE
DOME
SPONGE RUBBER PAD
(VIB. ISOL.)
FACTORY PRE-
FAB. CURB
THERMAL &
ACOUSTICAL
INSULATION
BACKDRAFT
DAMPER
FLASHING ROOF
CONSTRUCTION
STEEL MESH
SCREEN
BUTTERFLY
DAMPER
MOTOR
NOTES:
ALL ROOF MOUNTED EQUIPMENT MUST ADHERE TO CURRENT
HURRICANE CODES REGARDING ROOF TIE-IN AND WIND RESISTANCE
GUY WIRE WITH TURNBUCKLE
(TYP. OF 3) 120° APART
CONNECT GUY WIRE TO
EQUIPMENT LIFTING LUGS
PIPE PORTAL FOR WIRE
CONNECTION.
FLASHING - REFER
TO ARCHITECTURAL
WIRE CONNECTION TO ROOF STRUCTURE. REFER
TO STRUCTURAL DRAWINGS FOR DETAIL.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
BI
M
- C on st ru ct
R ep la ce m en t O ut pa tie nt C lin ic
/0
C on st . R ep la ce . O ut pa tie nt
C lin ic
R
.rv t
2/ 9/
0:
:1
AM
M-502
MECHANICAL DETAILS REPLACEMENT OUTPATIENT
CLINIC DESIGN AT COAST
GUARD CAPE COD
JOINT BASE CAPE COD, BARNSTABLE MA
650-318
BUILDING 1
02/10/2023 JFR JJA
100% CONSTRUCTION
DOCUMENTS
N.T.S.
CONDENSATE DRAIN TRAP W/ FORMULA DIAGRAM1
N.T.S.
CONDENSING UNTI MOUNTED ON GRADE DIAGRAM2
N.T.S.
DDC PANEL & LOW VOLTAGE CONTROL POWER TRANSFORMER PANEL DIAGRAM3
N.T.S.
DUCT CONNECTIONS - AIR TERMINAL UNITS DIAGRAM4
N.T.S.
DUCT SUPPORT DIAGRAMS6
N.T.S.
DUCTWORK RADIUS ELBOWS DIAGRAM7
N.T.S.
DUCTWORK SQUARE VANE ELBOWS DIAGRAM8
N.T.S.
EXHAUST OR RETURN BRANCH DUCTWORK DIAGRAM9
N.T.S.
ROOF UPBLAST RELIEF FAN DIAGRAM5
FLEXIBLE DUCT
SIZE SAME AS
DIFFUSER INLET: 5'-0" MAX
LENGTH
12"
CEILING
SUPPORT SADDLE FROM
STRUCTURE
VOLUME DAMPER
W/ LOCKING QUAD
SADDLE
SHEET
METAL
CONICAL OUTLET
BRANCH DUCT
USE RIGID
ELBOWS FOR
CHANGE
OF DIRECTION
GREATER THAN
45°
SEE SPECIFICATIONS FOR
CLAMPS AND SEALANT (TYP.)
NOTE:
THE USE OF FLEXIBLE AIR DUCT CONNECTORS ARE NOT PERMITTED FOR THE
DEDICATED AHU SERVING THE SURGICAL
SUITE.
TYPICAL
DIFFUSER OR
REGISTER IN
LAY-IN CLG.
THERMAL INSULATION
SEE SPECIFICATIONS
ROUND FLEXIBLE CONNECTION
RECTANGULAR FLEXIBLE CONNECTION
FLANGED
CONNECTION ON
FAN SIDE
WASHER 1-1/2" [40mm] MIN. TO 3" [75mm] MAX. INSTALLED. 6" [150mm] NOMINAL WITH MATERIAL
TAUT
FLEXIBLE
MATERIAL AS
SPECIFIED
1"x1/8" [25x3mm] DRAW BAND
1"x1/8" [25x3mm] BAND IRON
BOLT ON 4" [100mm] CENTERS
5/16" [8mm] FLANGE
DUCT
SHEET METAL SCREWS
ON 12" [300mm]
CENTERS
RIVET ON 4"
[100mm]
CENTERS
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
1"x1/8" [25x3mm] BAND IRON
BOLT ON 4" [100mm] CENTERS
1" [25mm] FLANGE & HEMALTERNATE
POSITION OF
BOLT 1 1/2" [40mm]
POCKET SLIP
DUCT
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
[15mm] [15mm] [40mm]
1 1/2" [40mm] MIN. TO 3" [75mm] MAX. INSTALLED. 6" [150mm] NOMINAL WITH MATERIAL TAUT
FLANGED
CONNECTION
ON FAN SIDE
WASHER
FLEXIBLE MATERIAL AS
SPECIFIED
1/2" 1 1/2"1/2"
MAIN AIR DUCT
WITH INSULATION
MANUAL BALANCING DAMPER
STAINLESS STEEL DRAW BANDS
CEILING
FLEXIBLE DUCT
PROVIDE TYPICAL FLEX DUCT
CONNECTION
DISTRIBUTION PLENUM W/
INSULATION. INSULATION CAN
BE INTERNAL OR EXTERNAL
REFER TO SCHEDULE FOR
NUMBER OF SLOTS
TURNING VANES SHALL BE COMPLETELY
FLUTTER-PROOF; PERMANENTLY FIXED TYPE
MADE OF GALVANIZED STEEL. TURNING
VANES SHALL BE MINIMUM 26 GAUGE
DOUBLE WALL AIRFOIL TYPE. TURNING
VANES SHALL BE SECURELY FASTENED TO A
RUNNER; VANE EDGES SHALL PROJECT
AIRFLOW PARALLEL TO DUCT SIDES.
MANUAL BALANCING 45° BOOT FITTING
DAMPER, TYPICAL
DAMPER ACCESS
DOOR, TYP. FOR
ALL DAMPERS
SQUARE ELLS SHALL ONLY BE
USED WHERE THERE IS
INSUFFICIENT SPACE FOR
RADIUS ELLS.
PROVIDE INSULATION SHIELD
& INSERT FOR ALL PIPING
(8" [200mm] MIN.)
1-5/8" [43mm] 12 GAUGE CHANNEL OR 2"x2"x1/4" [50x50x6.4mm] ANGLE
1/2" [15mm] DIA.
HANGER RODS WITH
36" [900mm] MAX.
SPACING ON EACH
CHANNEL
WELD
SADDLE
INSULATION SHIELD
AT HANGER
PROVIDE HIGH
COMPRESSIVE STRENGTH
INSULATION (9 PSF MIN.
DENSITY) UNDER
INSULATION SHIELD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
HANGER ROD
NOTES:
SEE SPECIFER FOR DETAILED
HANGER REQUIREMENTS
5 FT
THRU [20]
6 8 10
[32][25] [40]
[65]
[50]
[75]
-1312 14 -16 -
[125][100]
[150]
[250]
[200]
[300]
[400]
[350]
[450]
[600]
[500]
20 241814 16128 1064 532 2 1/21 1/21 1 1/4
[9100] [9600][8500][7600] [8200][7000][5800] [6700][5200][4100] [4900][3700][3000] [3400][2700][2100]
--- --[4900] -[4100][3700] [4000] -[3000][2400][1800][1500]
THRU 3/4
[2100] [2100]
[2100]
[2700]
[2400]
SIDE VIEW TRAPEZE HANGER FOR UP
TO 1000 LB. [453KG] UNIFORM LOAD
ADJUSTABLE CLEVIS HANGER TYPE 1 - SEE
SPECIFICATIONS ADJUSTABLE CLEVIS HANGER TYPE 43 - SEE
SPECIFICATIONS
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOM. SIZE
PIPE
TUBING
IN.
[mm]
FT.
[mm]
FT.
[mm]
[25 mm
1"
M
AX
MOTOR & DRIVE
U.L. APPROVED
ELECTRICAL DISCONNECT
BIRDSCREEN
SPONGE RUBBER PAD
(VIB. ISOL.)
FACTORY PRE-
FAB. CURB
THERMAL &
ACOUSTICAL
INSULATION
BACKDRAFT
DAMPER
FLASHING
ROOF
CONSTRUCTION
EXHAUST
DUCTWORK
ALL ALUMINUM WHEEL
HUB & HOUSING
MOTOR DOME EXHAUST FAN
DISCHARGE
DOME
NOTES:
ALL ROOF MOUNTED EQUIPMENT MUST ADHERE TO CURRENT
HURRICANE CODES REGARDING ROOF TIE-IN AND WIND RESISTANCE
MITERED ELBOW
45°
3'0" MIN. ABOVE ROOF
5" M
IN
3" M
IN
DRAW BAND
METAL HOOD
METAL SLEEVE
ROOF SURFACE
3" MIN.
METAL SLEEVE
W/ 3" FLANGE-
NAIL 3" O.C.
BITUMEN STOP
DO NOT PROVIDE MESH
SCREEN AT TERMINATION
1. VERIFY SUPPLY/RETURN ORIENTATION ON BOILER.
2. PROVIDE EACH BOILER WITH ITS OWN CONDENSATION NEUTRALIZATION KIT.
3. LEVEL BOILER.
4. MAINTAIN MANUFACTURER'S RECOMMENDED CLEARANCES, INCLUDING ABOVE BOILER FOR BURNER ACCESS.
BOILER FLUE
VENT THRU ROOF
COMBUSTION
AIR VENT THRU ROOF
1-1/2" DRAIN
3/4" PVC DRAIN TO CONDENSATE
NEUTRALIZATION KIT PROVIDED BY
BOILER MANUFACTURER
4" CONCRETE
HOUSEKEEPING PAD
STAND
4" HHWS
4" HHWR
4" HHWS
1" PRESSURE
RELIEF VALVE TO DRAIN
4" HHWR
STRAINER W/ BLOW OFF
VALVE
UNION (TYP)
THERMOMETER
(TYP)
PRESSURE GAUGE & COCK
(TYP)
CALIBRATED BALANCING VALVE
SOLENOID VALVE
MANUAL VENT
AIR SEPARATOR (WITH
SUPPORT BRACKETS -
SEE SCHEDULE
DRAIN LINE TO
FLOOR DRAIN
PRESSURE
REDUCING VALVE
W/ CHECK
FLOOR
_" TO PUMP
SUCTION
M
_" COLD WATER
PIPE TO DOMESTIC
WATER MAKE-UP
WATER METER
HIGH CAPACITY
AUTOMATIC AIR VENT
AS-1
ET-1
CONNECT TO
SIDE OF MAIN
BLOWDOWN VALVE
PIPE TO FLOOR DRAIN
DRAIN
GATE VALVE
REDUCED PRESSURE
BACKFLOW PREVENTER
EXTEND NEW MAKE-
UP WATER LINE AS
REQUIRED
FULL SIZE BYPASS
LOOP WATER RETURN
SUPPORT FROM STRUCTURE
NOTE: ALL PIPE ACCESSORIES SHALL BE FULL LINE SIZE.
DIAPHRAGM TYPE
PRESSURIZED
EXPANSION TANK -
SEE SCHEDULE
SUSPENDED.
SUPPORTS PER
MANUFACTURERS
RECOMMENDATIONS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
BI
M
- C on st ru ct
R ep la ce m en t O ut pa tie nt C lin ic
/0
C on st . R ep la ce . O ut pa tie nt
C lin ic
R
.rv t
2/ 9/
0:
:1
AM
M-503
MECHANICAL DETAILS REPLACEMENT OUTPATIENT
CLINIC DESIGN AT COAST
GUARD CAPE COD
JOINT BASE CAPE COD, BARNSTABLE MA
650-318
BUILDING 1
02/10/2023 JFR JJA
100% CONSTRUCTION
DOCUMENTS
N.T.S.
FLEXIBLE AIR DUCT CONNECTOR DETAIL1
N.T.S.
FLEXIBLE DUCT CONNECTIONS DETAIL2
N.T.S.
LINEAR SLOT DIFFUSER DIAGRAM4
N.T.S.
LOW PRESSURE DUCTWORK DIAGRAM5
N.T.S.
PIPE HANGER DETAIL6
N.T.S.
ROOF DOWNBLAST EXHAUST FAN DIAGRAM7
N.T.S.
ROUND GOOSENECK DETAIL9
N.T.S.
CONDENSING BOILER DETAIL8
N.T.S.
EXPANSION TANK, AIR SEPARATOR & MAKE-UP WATER DETAIL3
VB
VB
SMACNA FIGURE 4-6
45° LEED IN RIGID DUCT TO AIR
TERMINAL UNIT.
MAIN SUPPLY
PLAN VIEW
FLOW
FL
OW
AIR SPLIT DUCT TAKE-OFF
PLAN VIEW
BRANCH DUCT TAKE-OFF PLAN
VIEW
SUPPLY REGISTER
TAKE-OFF PLAN VIEW
AIR
FLOW
AIR
FLOW
AI
R
FL
OW
SUPPLY REGISTER
OR BRANCH DUCT
TURNING VANES
MAIN
SUPPLY
DUCT
SEE FLOOR PLAN FOR
SPLIT DIMENSION
PROVIDE VOLUME
DAMPER
PROVIDE
VOLUME
DAMPER
ADJUSTABLE
METAL ROD
OR LINKAGE
TOP REGISTER
MAIN
SUPPLY
DUCT
VOLUME EXTRACTOR; ADJUSTABLE
FROM FULLY CLOSED POSITION TO
CFM NOTED ON FLOOR PLANS
AIR
FLOW
AIR
FLOW
1/4 W OR 4" MIN.
AIR
FLOW
MAIN SUPPLY
DUCT
AI
R
FL
OW
W
MANUAL FLOW CONTROL
BALANCING VALVE
MIN. 8 PIPE DIAMETERS
VIBRATION ISOLATOR
(TYP)
CHECK VALVE
PRESSURE GAGE WITH
SERVICE COCK
COUPLING GUARD
PUMP
MOTOR
GROUT IN PUMP BASE WHEN REQ'D BY
MFGR'S INSTALLATION INSTRUCTIONS
ANCHOR PUMP TO 4" THICK CONCRETE
PAD. PAD IS MIN. 3" LARGER THAN PUMP
BASE ON ALL SIDES.
3/4" DRAIN VALVE W/
HOSE CONNECTTION
FLOOR FLANGE
GROUT
SUPPORT
SUCTION DIFFUSER
1/4"
GLOBE OR NEEDLE
VALVE (TYP)
BUTTERFLY VALVE (TYP)
* STRAIGHT LENGTHS OF UNOBSTRUCTED PIPE WITHOUT INLINE APPURTENANCES SHALL
BE INSTALLED UP/DOWNSTREAM OF FLOW CONTROL BALANCING VALVE PER MFGR'S
INSTALLATION INSTRUCTIONS.
BASE
ELECTROMAGNETIC
INSERTION FLOW
METER. BASIS OF
DESIGN: ONICON
F-3500
INSERTION 1"
FULL PORT
BALL VALVE
FOR HOT TAP
REFER TO
MANUFACTURER'S
RECOMMENDATIONS
FOR UPSTREAM AND
DOWNSTREAM
DISTANCE
MIN. 5 DIA MIN. 10 DIA
MI
N.
DI
A
SINGLE BEND
ALLOWED IF
PRECEEDED BY
MIN. 9 DIA.
RTV OR SILICONE CAULKING
BETWEEN PLATES AND WALL
AIR INTAKE
TERMINAL
FASTENER
PVC COUPLING
(IF NECESSARY)
PVC PIPE
INTERIOR CMU WALL
1/4" TO 1/2" CLEARANCE
ALL AROUND
EXTERIOR WALL
COVER PLATE
XX'-0"
AFF
GUY WIRE.
TYPICAL OF 3,
120° APART
DISCHARGE
DUCT
HALF CLOSURE
BAND
HALF CLOSURE
BAND
GUY RING
DISCHARGE
OUTLET
NOTE: PROVIDE
STRUCTURAL STEEL
SUPPORT
PIPE PORTAL
3' 0"
STORM COLLAR
FLASHING - REFER
TO ARCHITECTURAL
ROOF
VENTILATED
ROOF THIMBLE
LISTED VENT CAP
NOTE: ALL HARDWARE
SHALL BE ALL STAINLESS
STEEL CONSTRUCTION.
FLASHING - REFER
TO ARCHITECTURAL
PIPE STRAPS AT APPROX. 18" INTERVALS
SELF REGULATING HEAT TRACE CABLE
ALUMINUM FOIL TAPE
WATERPROOF JACKET
OVER INSULATION
HEAT TRACE CABLE
END CAP
NO
TO POWER SUPPLY AT
DISCONNECT SWITCH
CONTACTOR
THERMOSTAT WITH AMBIENT
AIR SENSOR SET ON AT 35°F
WATER TIGHT
CONTROL BOX
1' - 6"
PIPE STRAPS
HOT-COLD JOINT
PIPE INSULATION AND ALUMINUM
FOIL TAPE NOT SHOWN
HEAT TRACE CABLE
EVENLY DISTRIBUTED
ALONG PIPE
SELF REGULATING TYPE
HEAT TRACE CABLE
VALVE
ALUMINUM FOIL TAPE AND
INSULATION NOT SHOWN
NOTE: PROVIDE WEATHER RESISTANT LABELING ON
EXTERIOR OF JACKET IDENTIFYING PIPES AS BEING
"ELECTRIC TRACED" WITH VOLTAGE INDICATED.
INDOOR UNIT (FCU-1)
WALL MOUNTING BRACKET
FURNISHED BY FCU MFGR
WALL SLEEVE WITH CAPS
FURNISHED BY FCU MFGR
1/2" ø DRAIN LINE TO FLOOR
SINK SEE DETAIL
THERMISTOR CABLE
POWER & HIGH VOLTAGE
CONTROL TO INDOOR UNIT
OUTDOOR UNIT (ACU-4)
SECURE TO CONCRETE PAD
4" THICK CONCREETE PAD
(MIN. 4" EXTENSION ALL SIDES)
AIRFLOW
AIRFLOW
INSULATED XX"ø RS. XX"ø RL
REFRIGERANT LINES
CONNECTION CABLE
TO THERMOSTAT
TOP OF UNIT
± X'-XX" AFF
STRUCTURE ABOVE
DUCT
ROD COUPLING
SEISMIC CABLE
ANCHOR
TRAPEZE SUPPORT SELF TAPPING SHEET METAL SCREWS
UPPER SUPPORT (FOR
SEISMIC BRACE)
CABLE BRACKET
ROD STIFFENER
THREADED ROD
STIFFENER CLAMP
45°±15°
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
BI
M
- C on st ru ct
R ep la ce m en t O ut pa tie nt C lin ic
/0
C on st . R ep la ce . O ut pa tie nt
C lin ic
R
.rv t
2/ 9/
0:
:1
AM
M-504
MECHANICAL DETAILS REPLACEMENT OUTPATIENT
CLINIC DESIGN AT COAST
GUARD CAPE COD
JOINT BASE CAPE COD, BARNSTABLE MA
650-318
BUILDING 1
02/10/2023 JFR JJA
100% CONSTRUCTION
DOCUMENTS
N.T.S.
TERMINAL UNIT SUPPLY DUCT TAKEOFF DIAGRAM1
N.T.S.
SUPPLY DUCTWORK TAKE-OFFS DIAGRAM2
N.T.S.
BASE MOUNTED CENTRIFUGAL PUMP DETAIL4
N.T.S.
HYDRONIC FLOW METER DETAIL3N.T.S.
BOILER HORIZONTAL INTAKE DETAIL6
N.T.S.
BOILER FLUE DETAIL7
N.T.S.
HEAT TRACING DETAIL8 N.T.S.
WALL MOUNTED MINI SPLIT DETAIL5
N.T.S.
SEISMIC DUCT HANGER DETAIL9
CLAMP
LOCK
NUTS
(TYP)
CROSS
BRACING RODS ALL
FOUR SIDES
HANGER
ROD
(TYP)
RESILIENT
PAD
BONDED
STEEL PLATE
NEOPRENE
WASHER & SLEEVE
ANCHOR
BOLTEQUIPMENT
BASE
FLOOR
FLOOR MOUNT
EQUIPMENT RESTRAINED BY RESILIENT
PADS (TYPE DS)
SEISMIC BRACING FOR
LIGHT SUSPENDED
EQUIPMENT
EQUIPMENT WEIGHT
250 LBS. OR LESS
NOTE: NOT REQUIRED FOR AIR TERMINAL UNITS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
BI
M
- C on st ru ct
R ep la ce m en t O ut pa tie nt C lin ic
/0
C on st . R ep la ce . O ut pa tie nt
C lin ic
R
.rv t
2/ 9/
0:
:2
AM
M-505
MECHANICAL DETAILS REPLACEMENT OUTPATIENT
CLINIC DESIGN AT COAST
GUARD CAPE COD
JOINT BASE CAPE COD, BARNSTABLE MA
650-318
BUILDING 1
02/10/2023 JFR JJA
100% CONSTRUCTION
DOCUMENTS
N.T.S.
SEISMIC BRACING FOR EQUIPMENT DETAIL1
ETHERNET/IP
BUILDING LEVEL
CONTROLLER
(BLC)
MSTP
COMMUNICATION
(TYPICAL) CH-111001
AHU-111001
CHWP-111002
FCSS-111001
TU-1110031
EF-111003
EF-111002
CHWP-111001
EF-121001
TU-111001
BL-111001
ETHERNET/IP
(TYPICAL)
HHWP-111002
HHWP-111001
FCSS-111003
FCSS-111002
GENERAL CONTROL REQUIREMENTS:
1. CONTRACTOR SHALL PROVIDE COMPLETE DDC AUTOMATIC TEMPERATURE CONTROL SYSTEM
UTILIZING A WEB-BASED INTERFACE RESTRICTED FOR AUTHORIZED VA PERSONNEL ONLY. CONTROL
SYSTEM SHALL BE METASYS BUILDING MANAGEMENT SYSTEM BY JOHNSON CONTROLS, INC. ALL
HVAC SYSTEM AND ANCILLARY COMPONENTS SHALL BE CONTROLLED BY THE NEW BUILDING
MANAGEMENT SYSTEM. FINAL CONNECTION OF NEW EQUIPMENT TO THE BUILDING MANAGEMENT
SYSTEM SHALL BE MADE BY A COMPANY AND TECHNICIANS FULLY QUALIFIED AND CERTIFIED BY
JOHNSON CONTROLS, INC. TO PROGRAM, INSTALL, ADJUST, REPAIR, MAINTAIN, MODIFY, OR
OTHERWISE MANIPULATE THE METASYS BUILDING MANAGEMENT SYSTEM BY JOHNSON CONTROLS,
INC. CURRENT COMPANY AND TECHNICIAN QUALIFICATIONS AND CERTIFICATIONS TO PROGRAM, INSTALL, ADJUST, REPAIR, MAINTAIN, MODIFY, OR OTHERWISE MANIPULATE THE JOHNSON
CONTROLS METASYS SYSTEM MUST BE MAINTAINED THROUGHOUT THE CONSTRUCTION OF THE
PROJECT INCLUDING ANY EXTENSIONS OF THE CONSTRUCTION PERFORMANCE PERIOD. IF THE
CONTRACTOR UTILIZES THE SERVICES OF A SUBCONTRACTOR OTHER THAN JOHNSON CONTROLS
TO PERFORM THIS WORK, THE CONTRACTOR SHALL PROVIDE THE VA, VIA SUBMITTAL, COPIES OF
FACTORY TRAINING CERTIFICATES FOR EACH TECHNICIAN WORKING ON THE METASYS SYSTEM
PRIOR TO COMMENCEMENT OF ANY CONTROLS WORK. THE VA WILL REVIEW THE CERTIFICATIONS AS PART OF THE SUBMITTAL PROCESS. CONTRACTOR SHALL CARRY THE COST OF THIS WORK IN
THEIR BID.
2. ALL DDC CONTROLS SHALL BE PROVIDED BY THE CONTRACTOR AND SHALL BE BACNET METASYS CONTROLS BY JOHNSON CONTROLS FOR AHUs, CHILLERS, FANS, FCUs, VAVs, CIRCULATING PUMPS, CONTROL VALVES, MOTORIZED DAMPERS, AND ANY OTHER EQUIPMENT OR ACCESSORIES AS NOTED
IN THE DRAWINGS AND SPECIFICATIONS.
3. ALL CONTROLS SHALL HAVE OCCUPIED AND UNOCCUPIED FUNCTIONS.
4. ALL SET POINTS SHALL BE FULLY ADJUSTABLE.
5. ALL MONITORED POINTS, INCLUDING STATUS (ON, OFF, FAILED) AND ANY ALARMS SHALL DISPLAY AT
THE DDC WORKSTATION(S).
6. WHERE 100% REDUNDANT MOTORIZED EQUIPMENT IS INSTALLED, THE TWO (OR MORE) PIECES OF EQUIPMENT SHALL ALTERNATE OPERATION ON AN ADJUSTABLE, EQUAL RUN-TIME BASIS. THE DDC SYSTEM SHALL DISPLAY CUMULATIVE RUN-TIME OF EACH UNIT. IF ONE UNIT FAILS, THE OTHER UNIT
SHALL START AUTOMATICALLY AND THE DDC SYSTEM SHALL GENERATE AN ALARM SIGNAL.
7. ALL INDIVIDUAL ROOM ENVIRONMENTAL PARAMETERS SHALL BE DESIGNED AND SET IN
ACCORDANCE WITH THE LATEST VERSION OF THE VA HVAC DESIGN MANUAL.
8. HVAC SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH THE LATEST VERSION OF THE VA HVAC
DESIGN MANUAL AND THE LATEST VERSIONS OF THOSE STANDARDS REFERENCED WITHIN THAT
MANUAL.
9. ALL EQUIPMENT SHALL BE ENERGY STAR CERTIFIED.
HP-111001
HP-111002
HP-111003
GWH-111001 1
GWH-111002 1
HWP-111001 2
MISC. SENSORS,
VALVES,
ACCESSORIES, ETC.
PROVIDE WITH WEB
BASED INTERFACE
(T S-
6)
OA
24VAC
NC(D
-1
(T S-
3)
VFD
(DPS-1)
PRE-
FILTERS
FROM FAS
F
(A
FS
-1
COOLING
COIL
(T S-
5)
(S
PS
-3
TO VAV BOXES
LOCATED
APPROXIMATELY
2/3RD WAY DOWN
SUPPLY DUCT
GENERAL:
1. THE UNIT SHALL BE AVAILABLE FOR OPERATION AT ALL TIMES, BUT IN GENERAL, THE UNIT SHALL RUN 24/7 TO MAINTAIN TEMPERATURE AND HUMIDITY CONDITIONS IN THE SPACE. UNIT SHALL BE NORMALLY STARTED AND STOPPED BY THE BUILDING LEVEL CONTROLLER (BLC).
2. H-O-A SWITCH SHALL BE KEPT IN THE "AUTO" POSITION. "HAND" AND "OFF" POSITIONS SHALL BE USED FOR MAINTENANCE ONLY.
3. ALL CONTROLS SHALL BE AUTOMATIC AND ALL SETPOINTS SHALL BE ADJUSTABLE.
4. COOLING MODE SHALL BE DEFINED AS ANY TIME THE OUTDOOR TEMPERATURE IS ABOVE 50 DEG. (ADJ), AND A CALL FOR COOLING EXISTS
FROM ANY ASSOCIATED PIECE OF EQUIPMENT. THE COOLING MODE SHALL EXTEND TO ONE HOUR BEYOND THE TIME THE CALL FOR COOLING IS
SATISFIED. THIS IS TO PREVENT SHORT CYCLING.
5. HEATING MODE SHALL BE DEFINED AS ANY TIME THE OUTDOOR TEMPERATURE IS BELOW 68 DEG. (ADJ), AND A CALL FOR HEATING EXISTS FROM
ANY ASSOCIATED PIECE OF EQUIPMENT.
6. FAN MONITORING SENSORS CS-1,2 AND AFM-1,2 SHALL BE FACTORY MOUNTED BY THE FAN MANUFACTURER.
7. SET-UP TRACKING FOR SA AND RA FANS BASED ON AIRFLOW SCHEDULE BELOW. ATC AND TAB CONTRACTOR SHALL CREATE A FAN TRACKING
CHART FOR USE IN TRACKING BUILDING PRESSURIZATION.
SYSTEM START / STOP:
1. WHEN THE AHU IS INDEXED TO OPERATE BY THE BLC, THE AHU SUPPLY FAN SHALL START AND ALL SAFETIES AND INTERLOCKS SHALL OPERATE THROUGH THE STARTER AND BYPASS CONTACTOR. SEE INTERLOCK SCHEDULE FOR AHU AND EXHAUST FAN INTERLOCKS.
AIR FLOW CONTROL AND RESET:
1. THE BLC SHALL MODULATE THE SA FAN VFD FREQUENCY BASED ON A SIGNAL FROM THE STATIC PRESSURE SENSOR SPS-3 LOCATED IN THE SUPPLY DUCT TO MAINTAIN THE STATIC PRESSURE SET POINT AS DETERMINED BY THE TEST AND BALANCE CONTRACTOR.
2. THE BLC SHALL MODULATE THE RELIEF FAN VFD FREQUENCY BASED ON A SIGNAL FROM THE STATIC PRESSURE SENSOR SPS-4 LOCATED IN THE RETURN DUCT TO MAINTAIN MINUS 1.5" WG (ADJUSTABLE). FINAL STATIC PRESSURE SET POINT SHALL BE DETERMINED BY THE TEST AND
BALANCE CONTRACTOR BASED ON THE AIR FLOW BALANCE SCHEDULE.
3. A HIGH LIMIT STATIC PRESSURE SENSOR SPS-2 DOWNSTREAM OF THE SUPPLY FAN SHALL PREVENT OVER PRESSURIZATION OF THE SUPPLY DUCTWORK. IF THE DISCHARGE STATIC PRESSURE RISES ABOVE THE SETPOINT AS MEASURED BY HIGH STATIC LIMIT, THE AHU UNIT SHALL DE- ENERGIZE AND SEND AN ALARM TO THE BLC. AHU SHALL NOT BE ALLOWED TO RUN UNTIL AN OPERATOR MANUALLY RESETS THE SENSOR AT
THE UNIT.
4. A LOW LIMIT STATIC PRESSURE SENSOR SPS-1 UPSTREAM OF THE RELIEF AIR FAN SHALL PREVENT UNDER PRESSURIZATION OF THE RETURN DUCTWORK. IF THE RETURN DUCT STATIC PRESSURE SENSOR FALLS BELOW MINUS 2" WG (ADJUSTABLE), THE UNIT SHALL SHUTDOWN AND
SEND AN ALARM TO THE BLC.
5. THE UNIT SHALL AUTOMATICALLY INCREASE/DECREASE IN SPEED WITH FILTER LOADING BASED UPON STATIC PRESSURE SENSOR SPS-3 SETPOINT (AS DETERMINED BY TAB CONTRACTOR). STATIC PRESSURE SENSOR SPS-3 SHALL BE LOCATED 2/3 DOWNSTREAM OF SUPPLY DUCT
RUN.
6. AFTER THE SA FAN STARTUP IS INDEXED FOR 30 MINUTES (ADJUSTABLE), THE BLC SHALL POLE ALL VAV CONTROLLER REQUEST FOR MAXIMUM DAMPER POSITIONS EVERY 5 MINUTES (ADJUSTABLE). IF THE NUMBER OF VAV CONTROLLERS AT MAXIMUM DAMPER POSITION ARE ≤ 2 (ADJUSTABLE), THE STATIC PRESSURE SENSOR SPS-3 SETPOINT SHALL REDUCE BY 0.04" WG (ADJUSTABLE). DURING THE NEXT POLE SEQUENCE, IF THE NUMBER OF VAV CONTROLLERS AT MAXIMUM POSITION ARE > 2 (ADJUSTABLE), THE STATIC PRESSURE SENSOR SETPOINT SHALL INCREASE BY 0.06" WG (ADJUSTABLE). THE STATIC PRESSURE SENSOR SETPOINT SHALL NOT BE INDEXED TO EXCEED THE HIGH LIMIT STATIC PRESSURE SETPOINT OR REDUCED BELOW THE LOW LIMIT STATIC PRESSURE SETPOINT. IF THE NUMBER OF REQUEST FROM A SINGLE VAV CONTROLLER EXCEED 6 (ADJUSTABLE) CONSECUTIVE REQUEST, THE BLC SHALL IGNORE THIS CONTROLLER REQUEST AND SEND AN
ALARM TO THE BLC.
SUPPLY AIR TEMPERATURE CONTROL AND RESET:
1. WHEN THE SUPPLY FAN IS ENERGIZED, THE CHILLED WATER CONTROL VALVE SHALL MODULATE TO MAINTAIN THE LEAVING AIR TEMPERATURE
SETPOINT OF 55°F (ADJUSTABLE).
2. DURING WINTER CONDITIONS, THE UNIT SHALL RAMP DOWN TO MINIMUM AIRFLOW (AS INDICATED BY THE "HEATING CFM" IN THE TERMINAL UNIT SCHEDULE) AND THE VAV BOXES' HEATING HOT WATER CONTROL VALVE SHALL MODULATE TO MAINTAIN ROOM TEMPERATURE SETPOINT (SEE
VAV TERMINAL UNIT SEQUENCE OF OPERATION FOR MORE INFORMATION).
3. WHEN AHU IS AT MINIMUM AIRFLOW FOR 30 MINUTES (ADJUSTABLE), THE SUPPLY AIR LAT AS SENSED BY TS-6 SHALL RESET UP IN 1°F INCREMENTS EVERY 30 MINUTES UNTIL RA RELATIVE HUMIDITY AT H-1 RISES ABOVE 60% AT WHICH TIME THE SUPPLY AIR LAT AT TS-6 SHALL BE RESET DOWN TO 55 DEGREES F IN 1°F INCREMENTS EVERY 10 MINUTES (ADJUSTABLE). IF THE DISCHARGE AIR TEMPERATURE DROPS BELOW THE MINIMUM LIMIT, A LOW TEMPERATURE ALARM SHALL BE SENT TO THE BLC. IF THE DISCHARGE AIR TEMPERATURE RISES ABOVE THE
MAXIMUM LIMIT, A HIGH TEMPERATURE ALARM SHALL BE SENT TO THE BLC.
OUTSIDE/RETURN AIR DAMPER CONTROL:
1. THE RETURN AIR DAMPER SHALL BE OPENED 100% AND THE OUTSIDE AIR DAMPER SHALL MODULATE TO MAINTAIN THE OUTSIDE AIR VOLUME
SETPOINT AS SCHEDULED.
2. WHEN THE OUTSIDE AIR DAMPER IS OPEN 100% AND THE OUTSIDE AIR VOLUME IS BELOW SETPOINT, THE RA DAMPER SHALL MODULATE TO
MAINTAIN THE OUTSIDE AIR VOLUME SETPOINT.
3. AN ALARM SHALL BE GENERATED AT THE OPERATOR'S WORKSTATION IF THE OUTDOOR AIRFLOW VARIES BY MORE THAN 10% FROM SETPOINT
FOR MORE THAN 10 MINUTES (ADJUSTABLE).
OUTSIDE AIR DEMAND CONTROL VENTILATION:
1. SYSTEM SHALL UTILIZE A LOCAL CO2 SENSOR AS PART OF THE WEATHER STATION AND THE BLC SHALL MONITOR AND COMPARE THE
MEASURED SPACE CO2 TO THE SPACE CO2 CONCENTRATION SETPOINT (ADJUSTABLE).
2. IF THE CARBON DIOXIDE DIFFERENTIAL BETWEEN ANY SPACE EQUIPPED WITH A CO2 SENSOR AND THE OUTDOOR AIR SENSOR CO2 EXCEEDS 500 PPM (ADJUSTABLE) THE VAV TERMINAL UNIT SHALL MODULATE DAMPER OPEN TOWARDS MAXIMUM SETTING UNTIL CO2 SENSOR FALLS
BELOW 500 PPM (ADJUSTABLE) FOR 10 MINUTES (ADJUSTABLE).
3. IF ANY CARBON DIOXIDE DIFFERENTIAL RISES TO 700 PPM, THE AIR HANDLING UNIT SHALL SEND AN ALARM TO THE BLC AND THE AIR HANDLING UNIT OUTSIDE AIR DAMPER SHALL MODULATE OPEN TOWARDS MAXIMUM SETTING OR UNTIL OUTSIDE AIR DAMPER REACHES FULL OPEN POSITION. ONCE THE MEASURED CO2 CONCENTRATION FALLS BELOW A DIFFERENTIAL OF 700 PPM, THE OUTSIDE AIR DAMPER SHALL
MODULATE TOWARD MINIMUM OUTDOOR AIR POSITION SETPOINT.
LOW TEMPERATURE OPERATION / SHUTDOWN:
1. IF THE AIR TEMPERATURE AS SENSED BY TS-3 DROPS BELOW 55°F (ADJUSTABLE), THE PRE-HEAT COIL HEATING HOT WATER VALVE SHALL MODULATE
V-1 TO MAINTAIN A DISCHARGE TEMPERATURE OF 65°F.
2. IF THE AIR TEMPERATURE AS SENSED BY TS-4 DROPS BELOW 40°F (ADJUSTABLE) THE DEMAND CONTROL OPERATION SHALL BE OVERRIDDEN AND THE OUTSIDE AIR DAMPER SHALL MODULATE CLOSED TO MAINTAIN THE MIXED AIR TEMPERATURE LOW LIMIT SETPOINT. WHEN THE MIXED AIR TEMPERATURE RISES ABOVE THE MIXED AIR LOW LIMIT SETPOINT, DEMAND CONTROL OPERATION SHALL BE RESTORED.
3. IF THE AIR TEMPERATURE AS SENSED BY TS-4 FALLS BELOW 35°F (ADJUSTABLE),THE SUPPLY FAN SHALL SHUTDOWN, THE OUTSIDE AIR DAMPER SHALL CLOSE, THE CHILLED AND HEATING HOT WATER VALVES SHALL OPEN 100%, AND A CRITICAL ALARM SHALL INDICATE AT THE BLC.
ECONOMIZER:
1. WHEN THE OUTDOOR AIR SENSOR AS SENSED AT T-2 IS BELOW 60°F (ADJUSTABLE), THE SUPPLY AIR LAT SENSOR AT TS-6 SHALL MODULATE THE OUTSIDE AIR DAMPER D-1, THE RETURN AIR DAMPER D-2, THEN THE SUPPLY AIR LAT SENSOR TS-6 SHALL MODULATE CHILLED WATER VALVE V-2, ALL IN
SEQUENCE ON TEMPERATURE RISE, TO MAINTAIN 55°F (ADJUSTABLE) SUPPLY AIR LAT.
A. WHEN THE OUTDOOR AIR SENSOR AS SENSED AT T-2 IS ABOVE 65°F (ADJUSTABLE) AND FLOW IS SENSED BY CHILLED WATER FLOW SENSOR WSF-1, THE T-2 SHALL OPEN THE OUTSIDE AIR DAMPER D-1 TO MINIMUM POSITION OR AS DESCRIBED UNDER "OUTDOOR AIR/RETURN AIR DAMPER CONTROL" AND THE RETURN AIR DAMPER IN OPPOSITE UNISON AND THE SUPPLY AIR LAT SHALL MODULATE THE CHILLED WATER VALVE V-2 TO
MAINTAIN 55°F (ADJUSTABLE).
B. LOW LIMIT ECONOMIZER SHUTOFF SHALL BE THE WHEN MIXED AIR TEMPERATURE AT TS-3 IS BELOW 50°F AT THE REQUIRED OUTDOOR AIRFLOW.
C. HIGH LIMIT ECONOMIZER SHUTOFF SHALL BE BY ELECTRONIC ENTHALPY CONTROL WHEN THE OUTDOOR ENTHALPY EXCEEDS THE RETURN AIR
ENTHALPY AS DETERMINED BY THE OUTDOOR AIR SENSOR T-1 DIVIDED BY THE OUTDOOR HUMIDITY SENSOR H-2 AND THE RETURN AIR SENSOR
TS-7 DIVIDED BY THE RETURN AIR HUMIDITY H-1 RESPECTIVELY.
D. IF NO FLOW IS SENSED AT THE CHILLED WATER FLOW SENSOR WHEN OA TEMPERATURE IS ABOVE 65°F AND THE UNIT IS IN OCCUPIED MODE, AN
ALARM SHALL BE SENT TO THE BLC,
2. IF THE ENTHALPY OF THE SUPPLY AIR EXCEEDS 28 BTU PER POUND OF DRY AIR, AS SENSED BY SA LAT TEMP/SA HUMIDITY H-3, THE OUTDOOR AIR DAMPER SHALL MODULATE CLOSED AND SA LAT SHALL MODULATE THE PREHEAT VALVE V-1 TO MAINTAIN 55°F (ADJUSTABLE).
HUMIDITY CONTROL:
1. WHENEVER RETURN AIR RELATIVE HUMIDITY IS AT OR ABOVE 60% (ADJUSTABLE), AS SENSED BY H-1, THE UNIT SHALL MAINTAIN A COOLING COIL
LEAVING AIR TEMPERATURE OF 55°F (ADJUSTABLE).
2. IF THE VFD IS AT MINIMUM SPEED AND THE SPACE TEMPERATURE DROPS BELOW HEATING SETPOINT OF 70°F (ADJUSTABLE), THE VAV BOXES' HEATING HOT WATER VALVE SHALL MODULATE TO PREVENT OVERCOOLING OF THE SPACE AND MAINTAIN SPACE TEMPERATURE SETPOINT.
3. WHEN RETURN AIR RELATIVE HUMIDITY HAS DROPPED BACK TO 50% RH (ADJUSTABLE) FOR MORE THAN 30 MINUTES (ADJUSTABLE), THE SUPPLY AIR
DISCHARGE TEMPERATURE SHALL INCREASE TO SCHEDULED OPERATION SETPOINT.
4. WHEN RETURN AIR RELATIVE HUMIDITY AS SENSED AT H-1 IS BELOW 30% (ADJUSTABLE), STEAM HUMIDIFIER SH-111001 SHALL ENERGIZE AND H-1 SHALL MODULATE V-3 TO MAINTAIN 35% (ADJUSTABLE) RELATIVE HUMIDITY. WHEN THE RETURN AIR HUMIDITY IS ABOVE 50% FOR MORE THAN 30 MINUTES
(ADJUSTABLE), STEAM HUMIDIFIER SH-111001 SHALL DE-ENERGIZE.
5. WHEN THE SA FAN IS OFF OR A LOSS OF AIRFLOW IS SENSED DURING A CALL FOR HUMIDIFICATION, THE STEAM HUMIDIFIER SHALL DE-ENERGIZE AND
THE ISOLATION VALVE V-3 SHALL CLOSE AND AN ALARM SENT TO THE BLC.
UN-OCCUPIED MODE:
1. THE UNIT SUPPLY FAN SHALL DE-ENERGIZE, THE OA DAMPER SHALL CLOSE, THE RA DAMPER SHALL OPEN, AND ALL VAV BOXES SHALL FULLY OPEN.
2. IF SPACE TEMPERATURE DROPS BELOW UN-OCCUPIED WINTER SPACE TEMPERATURE SET-POINT 55°F (ADJUSTABLE) AS MEASURED BY THE SPACE
TEMPERATURE SENSOR, THE SUPPLY FAN SHALL START AT 60% FULL SPEED AND ALL VAV BOX TEMPERATURE CONTROL ALGORITHMS SHALL BE
ENABLED TO MAINTAIN THE WINTER ZONE TEMPERATURE SET-POINTS.
3. IF SPACE TEMPERATURE RISES ABOVE THE SUMMER UN-OCCUPIED TEMPERATURE SET-POINT 78°F (ADJUSTABLE) AS MEASURED BY THE SPACE TEMPERATURE SENSOR, THE SUPPLY FAN SHALL ENERGIZE, THE CHILLED WATER VALVE SHALL MODULATE TO MAINTAIN THE UN-OCCUPIED TEMPERATURE SET-POINT DOWNSTREAM OF THE COOLING COIL AND ENABLE VAV ZONE TEMPERATURE CONTROL ALGORITHMS.
4. INTERLOCKED EXHAUST FANS SHALL NOT OPERATE DURING UN-OCCUPIED MODE.
SMOKE DETECTION SHUTDOWN:
1. UPON A SIGNAL FROM THE ASSOCIATED, HARD WIRED, INTERLOCKED, SMOKE DETECTOR (FURNISHED AND WIRED BY DIVISION 28, MOUNTED BY DIVISION 23) THAT SMOKE IS DETECTED IN THE AIR STREAM, THE FIRE ALARM SYSTEM SHALL SHUT DOWN THE AHU AND INTERLOCKED FANS, AND AT THE SAME TIME THE SMOKE DETECTOR SIGNAL SHALL DISPLAY AN ALARM AT THE BLC THAT THE UNIT AND ASSOCIATED FANS WERE SHUTDOWN FOR
SMOKE DETECTION.
2. AHU AND INTERLOCKED FANS SHALL RESTART TO NORMAL SEQUENCE AND SMOKE DAMPERS SHALL OPEN WHEN FIRE ALARM CIRCUIT IS RESET.
GRAPHICAL USER INTERFACE:
1. PROVIDE A COMPLETE GRAPHIC DISPLAY OF THE SYSTEM AT THE BLC WEB INTERFACE. THE DISPLAY SHALL SHOW ALL POINTS WITH THEIR MEASURED VALUES OR STATES, WHICH SHALL BE UPDATED CONTINUOUSLY AND SHOWN AS CURRENT VALUE.
CO
MM
UN
IC
AT
IO
N/
DA
TA
IN
TE
RF
AC
E
TE
MP
ER
AT
UR
E
HU
MI
DI
TY
DI
FF
. P
RE
SS
UR
E
ST
AT
IC
P
RE
SS
UR
E
FR
EQ
UE
NC
Y
RE
AL
T
IM
E
EF
FI
CI
EN
CY
SE
TP
OI
NT
A
DJ
US
TM
EN
T
OP
T.
S
TA
RT
/ S
TO
P
RE
SE
T
RU
N
TI
ME
SE
T
BA
CK
SE
T
UP
MO
RN
IN
G
W
AR
M-
UP
GR
AP
HI
C
SYSTEM ANALOG SYSTEM FEATURES
INPUT/OUTPUT SUMMARY
SYSTEM
MIXED AIR
FILTERS
STATIC PRESSURE
REMARKSVARIABLE AIR VOLUME
AIR HANDLING SYSTEM
BLC, HOA
CS-1; AFM-1; SPS-1,2,3
D-2; TS-7; H-1
TS-4, 5, 6; H-3
D-1; AFS-1; T-2; H-2; CO2-2
SPS-1,2,3
SD-1,2 (INTERLOCK W/ FIRE ALARM SYSTEM)
SPACE
DPS-1,2,3
T-1; H-1; CO2-1
SEQUENCE OF OPERATION
(T-1) (CO2-2)
CO
TS-3
CH
W
R
CH
W
S
(V-2)
V-1,2,3; WFS-1,2
REFER TO MECH.
PLANS FOR 2-WAY OR
3-WAY VALVE TYPE
NO
S
SPACE SENSORS
INPUT OUTPUT
CF
M
SP
EE
D
VA
LV
E
AC
TU
AT
OR
DA
MP
ER
A
CT
UA
TO
R
O
PE
N
DI
FF
. P
RE
SS
UR
E
SW
IT
CH
ST
AT
US
CU
RR
EN
T
RE
LA
Y
FL
OW
S W
IT
CH
ON
-O
FF
SP
EE
D
SI
GN
AL
EL
EC
. H
EA
T
ST
AG
ES
INPUT OUTPUT
DA
MP
ER
A
CT
UA
TO
R
PR
OO
F
CR
IT
IC
AL
DIGITAL
VA
LV
E
AC
TU
AT
OR
SP
EE
D
SW
IT
CH
DI
RT
Y
FI
LT
ER
HI
GH
-L
OW
V
AL
UE
HI
GH
/LO
W
P
RE
SS
UR
E
CO
2 L
EV
EL
TI
ME
S
CH
ED
UL
E / T
RE
ND
SUPPLY FAN
RETURN AIR
SUPPLY AIR
OUTSIDE AIR
COILS
ALARMS PROGRAMS
DUCT SMOKE DETECTORS
(WFS-1)
PREHEAT
COIL
(T S-
4)
SA DUCT SMOKE
DETECTOR
(T-2) (H-2)
OUTDOOR SENSORS
NOTE: REFER TO MECH.
PLANS FOR LOCATIONS.
NOTE: FACILITY SHALL HAVE ONE
OUTDOOR AIR WEATHER STATION
(CS-1)
HIGH LIMIT STATIC
PRESSURE SENSOR
(S
PS
-2
(H
IG
H-
LIM
IT
(CO2-1)
CO2
BACKDRAFT DAMPER
24VAC
NO
(D-2)
(S
PS
-1
LOW LIMIT STATIC
PRESSURE SENSOR
RARELIEF
VFD
FROM FAS
(CS-2)
HW
R
HW
S
(V-1)
REFER TO MECH.
PLANS FOR 2-WAY OR
3-WAY VALVE TYPE
NC
(WFS-1)
RELIEF AIR D-1
S
RA DUCT SMOKE DETECTOR
RF-121001
SA FAN ARRAY (TYP OF 4)
(T S-
7)
(H -1
(AFM-2)
(AFM-1)
BACKDRAFT DAMPER
(DPS-3)
FINAL
FILTERS
(DPS-2)
AFTER-
FILTERS
(H -3
ST
(V-3)
NC
(S
PS
-4
RELIEF FAN CS-2; AFM-2; SPS-4
(S D-
2)
(S D-
1)
SA
F
(A
FS
-1
REHEAT
COIL
GENERAL:
1. TERMINAL UNIT SHALL BE EQUIPPED WITH A TERMINAL UNIT MOUNTED CONTROLLER.
2. ALL CONTROLS SHALL BE AUTOMATIC AND ALL SETPOINTS SHALL BE ADJUSTABLE.
OPERATION:
1. SET POINTS SHALL BE AS FOLLOWS:
A. COOLING: 72°F (ADJUSTABLE)
B. HEATING: 68°F (ADJUSTABLE)
C. A DEADBAND OF 4°F BETWEEN HEATING AND COOLING SET POINTS SHALL BE MAINTAINED.
2. UPON FALL IN SPACE TEMPERATURE THE TERMINAL UNIT DAMPER WILL MODULATE TO MINIMUM POSITION.
3. ONCE THE DAMPER REACHES MINIMUM POSITION, THE SPACE TEMPERATURE SHALL BE ALLOWED TO DROP THROUGH A DEADBAND.
4. UPON FURTHER DROP IN SPACE TEMPERATURE, THE DAMPER SHALL OPEN TO HEATING POSITION (AS INDICATED IN SCHEDULE) AND
THE HEATING HOT WATER VALVE SHALL MODULATE TO MAINTAIN SET POINT ± 0.5°F. THE ADJUSTABLE TOLERANCE OF ± 0.5°F HAS
BEEN SELECTED TO PREVENT VALVE HUNTING.
5. THE REVERSE SHALL OCCUR ON THE RISE IN SPACE TEMPERATURE.
6. FOR TERMINAL UNITS THAT SERVE SPACES EQUIPPED WITH A CARBON DIOXIDE (CO2) SENSOR, IF THE DIFFERENTIAL BETWEEN ANY
SPACE CO2 AND THE OUTDOOR AIR SENSOR CO2 EXCEEDS 500 PPM (ADJUSTABLE), THE VAV TERMINAL UNIT CONTROLLER SHALL MODULATE DAMPER OPEN TOWARDS MAXIMUM SETTING UNTIL CO2 SENSOR FALLS BELOW 500 PPM (ADJUSTABLE) FOR 10 MINUTES (ADJUSTABLE).IF THE CO2 DIFFERENTIAL RISES TO 700 PPM, THE TERMINAL UNIT CONTROLLER SHALL DISPLAY A NOTIFICATION AT THE
BLC THAT THE AIR HANDLING UNIT IS IN DEMAND CONTROL VENTILATION MODE.
OCCUPIED/UNOCCUPIED MODES:
1. EACH TERMINAL UNIT SHALL HAVE THE OPTION FOR OCCUPIED AND UNOCCUPIED MODES WITHIN THE UNIT CONTROLLER.
OCCUPIED/UNOCCUPIED MODES SHALL HAVE UPPER AND LOWER SPACE TEMPERATURE SETPOINT LIMITS THAT SHALL BE PROGRAMMABLE THROUGH THE BLC WEB INTERFACE. REFER TO AHU-111001 & EF-121001 UN-OCCUPIED MODE SEQUENCE.
(D -1
SA
HH
W
R
HH
W
S
(T S-
1)
SEQUENCE OF OPERATION
(V-1)
REFER TO DRAWINGS FOR 2-WAY
OR 3-WAY VALVE TYPE
NO
CO
MM
UN
IC
AT
IN
TE
RF
AC
E
TE
MP
ER
AT
UR
E
HU
MI
DI
TY
DI
FF
. P
RE
SS
UR
E
ST
AT
IC
P
RE
SS
UR
E
FR
EQ
UE
NC
Y
RE
AL
T
IM
E
EF
FI
CI
EN
CY
SE
TP
OI
NT
A
DJ
US
TM
EN
T
OP
T.
S
TA
RT
/ S
TO
P
RE
SE
T
RU
N
TI
ME
SE
T
BA
CK
SE
T
UP
MO
RN
IN
G
W
AR
M-
UP
GR
AP
HI
C
SYSTEM ANALOG SYSTEM FEATURES
INPUT/OUTPUT SUMMARY
TERMINAL UNIT CONTROLLER
REMARKSVARIABLE AIR VOLUME
TERMINAL UNIT
TS-1, AFS-1, D-1
V-1, WFS-1
INPUT OUTPUT
FL
OW
R
AT
E
SP
EE
D
VA
LV
E
AC
TU
AT
OR
DA
MP
ER
A
CT
UA
TO
R
DI
FF
. P
RE
SS
UR
E
SW
IT
CH
ST
AT
US
CU
RR
EN
T
RE
LA
Y
FL
OW
S W
IT
CH
ON
-O
FF
SP
EE
D
SI
GN
AL
EL
EC
. H
EA
T
ST
AG
ES
INPUT OUTPUT
DA
MP
ER
A
CT
UA
TO
R
PR
OO
F
CO
MM
UN
IC
AT
IO
N
FA
ILU
RE
DIGITAL
VA
LV
E
AC
TU
AT
OR
SP
EE
D
SW
IT
CH
DI
RT
Y
FI
LT
ER
HI
GH
-L
OW
V
AL
UE
HI
GH
/LO
W
P
RE
SS
UR
E
CO
2 L
EV
EL
TI
ME
S
CH
ED
UL
E / T
RE
ND
SUPPLY AIR
REHEAT COIL
ALARMS PROGRAMS
SPACE
(T-1)
SPACE SENSORS
NOTE: REFER TO MECH.
PLANS FOR LOCATIONS.
(WFS-1)
T-1
(CO2-1)
CO2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
BI
M
- C on st ru ct
R ep la ce m en t O ut pa tie nt C lin ic
/0
C on st . R ep la ce . O ut pa tie nt
C lin ic
R
.rv t
5/ 4/
:1
1:
P M
M-701
MECHANICAL CONTROLS REPLACEMENT OUTPATIENT
CLINIC DESIGN AT COAST
GUARD CAPE COD
JOINT BASE CAPE COD, BARNSTABLE MA
650-318
BUILDING 1
02/10/2023 JFR JJA
100% CONSTRUCTION
DOCUMENTS
N.T.S.
BACNET SYSTEM ARCHITECTURE1
DRAWING NOTES:
1. CONTROL SYSTEM ARCHITECTURE SHOWN IS FOR DESIGN INTENT OF CONTROL SYSTEM. CONTROLS
CONTRACTOR SHALL ALTER SYSTEM ARCHITECTURE AS REQUIRED TO BEST FIT NEW CONTROL
SYSTEM AND TIE IN TO EXISTING SYSTEM.
2. PROVIDE LAMINATED COPIES OF ALL CONTROL DRAWINGS WITHIN EACH CONTROL PANEL.
3. CONTRACTOR IS RESPONSIBLE FOR COMPLETE AND OPERATIONAL DDC CONTROL SYSTEM.
SEQUENCE OF OPERATIONS AS SPECIFIED SHALL BE PROVIDED WITH ALL SYSTEM POINTS AND
INTEGRATED WITH ALL CONTROLS AND EQUIPMENT. CONTRACTOR IS RESPONSIBLE FOR PROVIDING
ALL SOFTWARE AND HARDWARE REQUIRED FOR ALL MECHANICAL EQUIPMENT TO BE CONTROLLED
AND MONITORED AS SPECIFIED IN THE SEQUENCE OF OPERATIONS.
N.T.S.
AHU-111001 & RF-121001 CONTROL DIAGRAM3 N.T.S.
VARIABLE AIR VOLUME TERMINAL UNIT CONTROL DIAGRAM2
CODED NOTES:
PLUMBING GAS WATER HEATER SHALL BE INTEGRATED WITH THE CONTROL SYSTEM TO INDICATE
STATUS AND HOT WATER SUPPLY TEMPERATURE.
PLUMBING HOT WATER RECIRCULATION PUMP SHALL BE INTEGRATED WITH THE CONTROL SYSTEM TO
INDICATE STATUS.
EXHAUST FAN SHALL BE INTEGRATED WITH THE CONTROL SYSTEM TO INDICATE STATUS.
GENERAL:
1. THE CHILLED WATER PLANT CONSISTS OF ONE (1) 80 TON AIR COOLED CHILLER WITH TWO (2) REDUNDANT CHILLED WATER PUMPS, EACH SERVED BY A SEPARATE VFD.
2. A 2-WAY MODULATING BYPASS VALVE (V-1) SHALL BE PROVIDED.
3. A DIRECT DIGITAL CONTROL (DDC) SYSTEM SHALL BE PROVIDED THAT INTERFACES WITH THE CHILLER FACTORY CONTROLS TO PROVIDE
FULL REMOTE CONTROL AND ALL INFORMATION FOR MONITORING AVAILABLE IN THE CHILLER CONTROLLER.
SYSTEM OPERATION:
1. EACH PUMP IS SIZED FOR THE FULL FLOW RATE TO GIVE THE PUMPING SYSTEM N+1 REDUNDANCY. THEREFORE, ONLY ONE PUMP SHALL
OPERATE AT A TIME. PUMP OPERATION SHALL BE AS FOLLOWS:
A. WEEK ONE: CHWP-111001 SHALL BE IN OPERATION AND CHWP-111002 SHALL BE DE-ENERGIZED (ADJUSTABLE).
B. WEEK TWO: CHWP-111002 SHALL BE IN OPERATION AND CHWP-111001 SHALL BE DE-ENERGIZED (ADJUSTABLE).
C. IF ANY ONE PUMP FAILS, AN ALARM SHALL BE SENT TO THE BUILDING LEVEL CONTROLLER (BLC), THE PUMP SHALL DE-ENERGIZE, AND THE NEXT PUMP SHALL ENERGIZE.
D. IF THE SYSTEM FAILS TO MEET CHILLED WATER SETPOINT, AN ALARM SHALL BE SENT TO BLC.
E. PUMP CHANGEOVER SHALL OCCUR AUTOMATICALLY THROUGH THE DDC SYSTEM.
2. WHENEVER THERE IS A REQUIREMENT FOR CHILLED WATER, THE CHILLED WATER SYSTEM SHALL BE INDEXED TO OPERATE.
3. UPON A REQUEST FROM THE DDC SYSTEM, THE CHILLER AND PUMP FOR THAT WEEK (ADJUSTABLE) SHALL BE ENERGIZED.
4. WHEN ALL CHILLED WATER VALVES ARE LESS THAN 85% OPEN, THE CHILLED WATER SYSTEM DIFFERENTIAL PRESSURE (DP) SETPOINT
WILL BE LOWERED BY 0.1 PSIG (ADJ.) OF THE CURRENT CHILLED WATER DP SETPOINT. THIS OCCURS EVERY 5 MINUTES UNTIL AT LEAST ONE VALVE IS MORE THAN 85% OPEN, OR IF THE SETPOINT IS EQUAL TO THE MIN. CHILLED WATER DP SETPOINT, OR IF THE PUMP VFD IS
AT A MIN. SPEED SETTING 22 HZ (ADJUSTABLE).
5. WHEN ANY CHILLED WATER VALVE IS MORE THAN 95% OPEN, THE CHILLED WATER DP SETPOINT WILL INCREASE BY 0.1 PSIG (ADJ.) OF THE CURRENT CHILLED WATER DP SETPOINT. THIS OCCURS EVERY 5 MINUTES UNTIL NO VALVE IS MORE THAN 95% OPEN, OR IF THE CHILLED WATER DP SETPOINT HAS RISEN TO THE SYSTEMS MAX. SETTING, OR IF THE PUMP'S VFD IS AT THE MAX. SETTING 60 HZ
(ADJUSTABLE).
6. ONCE THE PUMP AND CHILLER PROVE FLOW VIA DIFFERENTIAL PRESSURE TRANSMITTERS, THE CHILLERS SHALL BE RELEASED TO SEQUENCE. CONTINUOUSLY MONITOR THE PRESSURE DIFFERENTIAL AND PUMP DIFFERENTIAL PRESSURE TRANSMITTERS. CHILLERS
SHALL NOT BE CAPABLE OF OPERATING WITHOUT PROOF OF FLOW.
7. UPON A REQUEST FOR CHILLED WATER, THE DDC SYSTEM SHALL ENERGIZE THE CHILLED WATER PUMP SCHEDULED FOR THAT WEEK (ADJUSTABLE). UPON PROOF OF PRIMARY FLOW, THE DDC SYSTEM SHALL THEN ENERGIZE THE CHILLER THROUGH ITS LOCAL CONTROL
PANEL.
8. AFTER ENABLING THE LOCAL CHILLER PANEL, THE DDC SYSTEM SHALL MONITOR THE CHILLER RUNNING LOAD AMPS FOR PROOF OF
OPERATION.
9. THE LOCAL CHILLER CONTROL PANEL SHALL THEN CYCLE THE CHILLERS' COMPRESSORS IN SEQUENCE TO MAINTAIN THE EVAPORATOR LEAVING WATER TEMPERATURE AND RUNNING LOAD, AS RESET BY RESET, DEMAND LIMITING AND OTHER APPROPRIATE PROGRAMS.
CONTROLS:
1. THE LOCAL CHILLER OPERATION SHALL BE CONTROLLED BY AN INTELLIGENT MICRO-PROCESSOR BASED CONTROLLER IN COMMUNICATION WITH THE DDC SYSTEM VIA BACNET, HARDWIRED INDIVIDUAL POINTS, OR OTHERWISE AS REQUIRED TO BE
COMPATIBLE WITH THE CONTROLS INTERFACE(S) OF THE CHILLERS FURNISHED.
2. ALL OPERATIONAL DATA SHALL READ-OUT, AND BE OPERATOR MODIFIABLE THROUGH THE DDC WEB-BASED INTERFACE.
3. PROVIDE THE STATUS DISPLAY REPORTS, AND ALARM PARAMETERS AS SCHEDULED HEREIN.
4. THE CHILLER PLANT CONTROL PROGRAM SHALL BE FULLY EDITABLE AND SET-UP VIA POINT AND CLICK ON A STANDARD COMPUTER
SCREEN. IT SHALL NOT REQUIRE SPECIAL SOFTWARE TOOLS OR A TECHNICIAN TO OPERATE AND MODIFY CHILLER SEQUENCING
CONTROL.
5. THE CHILLER SEQUENCING SOFTWARE SHALL PERFORM THE FOLLOWING CONTROL STRATEGIES:
A. CHILLER PLANT SYSTEM SCHEDULING
B. CHILLER SEQUENCING
C. COLOR GRAPHIC BASED CHILLER PLANT STATUS SCREENS
D. COLOR GRAPHIC BASED CHILLER STATUS SCREENS
E. SYSTEM AND CHILLER DIAGNOSTIC MESSAGES
F. SYSTEM AND CHILLER REPORTS
6. CHILLER SEQUENCING - THE CHILLER SEQUENCING SOFTWARE WILL START AND STOP SYSTEM WATER PUMP AND CHILLER BASED UPON
SYSTEM LOAD.
A. WHEN THE CHILLED WATER SYSTEM IS ENABLED, THE CHILLER SYSTEM CONTROL WILL START THE SYSTEM CHILLED WATER PUMP
AND PROVE FLOW THROUGH THE EVAPORATOR.
7. ADDITIONAL CHILLER SEQUENCING FOR VARIABLE PRIMARY FLOW CHILLED WATER SYSTEMS:
A. THE SYSTEM CHILLED WATER SUPPLY SETPOINT SHALL BE 42°F (ADJUSTABLE). ALTERNATIVELY, THE CHILLED WATER SUPPLY TEMPERATURE SETPOINT SHALL INCREASE UP TO 44°F MAX. WHEN THE AIR HANDLING UNIT CHILLED WATER CONTROL VALVE IS < 50% FOR 10 MINUTES (ADJUSTABLE). THE CHILLED WATER SUPPLY TEMPERATURE SETPOINT SHALL NOT EXCEED 44°F. IF THE AIR HANDLING UNIT CHILLED WATER CONTROL VALVE ≥ 50% OPEN FOR 10 MINUTES (ADJUSTABLE), THE CHILLED WATER SUPPLY
SETPOINT SHALL RETURN TO THE CHILLED WATER SETPOINT OF 42°F (ADJUSTABLE).
B. THE CHILLER SEQUENCING SOFTWARE SHALL STOP THE CHILLER WHENEVER THERE IS NO CHILLED WATER SYSTEM DEMAND FOR
30 MINUTES (ADJUSTABLE).
CHILLER STATUS REPORTS:
1. PROVIDE AN OPERATING STATUS REPORT FOR EACH CHILLER. THE REPORT(S) SHALL PROVIDE THE PRESENT STATUS FOR THE FOLLOWING INFORMATION TO PROVIDE THE OPERATOR WITH CRITICAL CHILLER OPERATING DATA.
A. COMPRESSOR ON/OFF STATUS.
B. COMPRESSOR STARTS/RUN HOURS
C. COMPRESSOR PHASE 1/2/3 PERCENT RLA - SEPARATE FOR EACH COMPRESSOR
D. COMPRESSOR CURRENT DRAW - RLA PERCENT
E. ACTIVE CHILLER DIAGNOSTICS OR ALARMS
F. LEAVING CHILLED WATER TEMPERATURE
G. ENTERING CHILLED WATER TEMPERATURE
H. CHILLED WATER SETPOINT.
I. REFRIGERANT TEMPERATURE EVAPORATOR/CONDENSER - SEPARATE FOR EACH CIRCUIT
J. OPERATING MODE
K. CHILLER MODEL AND SERIAL NUMBER
L. CHILLED WATER CHILLER LOAD TRENDING: THE DDC SYSTEM SHALL CONTINUOUSLY MEASURE THE CHILLED WATER SUPPLY FLOW
RATE, AND THE CHWS AND CHWR TEMPERATURES, AND CALCULATE THE TOTAL BUILDING COOLING LOAD USING THE FORMULA
BELOW:
a. BUILDING LOAD (BTUH) = FLOW (GPM) X ((CHWS TEMP -CHWR TEMP) (DEG F) X 500).
DIAGNOSTICS/PROTECTION:
1. THE DDC SYSTEM SHALL BE ABLE TO ALARM FROM ALL SENSED POINTS AND DIAGNOSTIC ALARMS SENSED BY THE CHILLER
CONTROLLER.
A. ALARM LIMITS SHALL BE DESIGNATED FOR ALL SENSED POINTS.
B. SENSED DIAGNOSTIC POINTS SHALL INCLUDE THE FOLLOWING AT A MINIMUM:
C. SYSTEM CHILLED WATER SUPPLY TEMPERATURE
D. SYSTEM CHILLED WATER RETURN TEMPERATURE
CHILLER FREEZE PROTECTION:
1. WHEN OUTDOOR AIR TEMPERATURE IS 33 °F (ADJ.) OR BELOW THE CHILLED WATER PUMPS SHALL CYCLE AT MINIMUM FLOW AND THE HEAT TRACE SYSTEM SHALL ENERGIZE TO MAINTAIN WATER TEMPERATURE TO AVOID EVAPORATOR FREEZE. IF THE CHILLED WATER
TEMPERATURE FALLS BELOW 39 °F (ADJ.), AN ALARM SHALL BE SENT TO THE ECC.
PRIMARY VARIABLE SPEED CHILLED WATER CIRCULATION PUMPS STAGING CONTROL:
1. VARIABLE CHILLED WATER PUMP CONTROL: THE DDC SYSTEM SHALL CONTROL THE SPEED OF THE LEAD PRIMARY CHILLED WATER PUMP THROUGH THE VFD TO MAINTAIN 10 PSIG (ADJUSTABLE) DIFFERENTIAL PRESSURE AT THE DP TRANSMITTER LOCATED AT THE END OF THE CHILLED WATER LOOP. DP SETPOINT SHALL AUTOMATICALLY ADJUST TO MAINTAIN CHW VALVE POSITION (95% OF ALL CHILLED WATER VALVES SHALL BE LESS THAN 100% OPEN). UNDER NO CIRCUMSTANCE, HOWEVER, WILL THE VARIABLE FREQUENCY DRIVE APPLIED TO CHILLED WATER PUMP MOTOR BE ALLOWED TO EXCEED THE PUMP MOTOR FLA (FULL LOAD AMPS) AT ANY TIME. EACH VFD SHALL BE PROGRAMMED TO ACHIEVE THE FLA OF EACH MOTOR. ON A FAILURE OF THE PRIMARY PUMP DEDICATED TO A CHILLER, THE DDC SYSTEM SHALL AUTOMATICALLY SHUTDOWN ASSOCIATED CHILLER AND BRING ON THE NEXT SEQUENCED PUMP AND CHILLER AND SHALL CONTROL THE SPEED OF THE PUMP TO MAINTAIN THE DIFFERENTIAL PRESSURE AT THE END OF THE CHILLED WATER LOOP, AND
SEND AN ALARM OF THE FAILURE.
2. UNDER PROGRAM CONTROL, EACH CHILLED WATER PUMP VFD WILL BE AUTOMATICALLY STARTED AND STOPPED VIA A DDC COMMUNICATION BUS WITH AN ASSOCIATED DDC AO. A CURRENT SWITCH, INSTALLED AT EACH PUMP VFD, WILL PROVIDE ON/OFF
STATUS TO THE DDC AT ALL TIMES.
3. BASED UPON PUMP SPEED, PUMPS WILL BE STAGED ON AND OFF BY DDC TO ACCOMMODATE THE BUILDING FLOW RATE REQUIREMENTS UNDER THE FOLLOWING DDC OPERATIONAL SEQUENCES. UNDER AUTOMATIC CONTROL, SOFTWARE SUBROUTINES, USING "IF/THEN"
LOGIC STATEMENTS, WILL PROVIDE FOR "ON/OFF" STAGING AS DESCRIBED.
4. IF DDC SHOULD ATTEMPT TO AUTOMATICALLY START A PUMP AND THE ASSOCIATED SENSOR CAN NOT PROVIDE A SUCCESSFUL START, AN ALARM WILL BE ROUTED TO OPERATOR AT THE OWS (OPERATOR WORK STATION) INDICATING IMMEDIATE PUMP ATTENTION IS
NECESSARY AND THE NEXT OPERATIONAL SEQUENCE WILL THEN IMMEDIATELY BE ACTIVATED.
5. IF DDC SHOULD ATTEMPT TO AUTOMATICALLY STOP A PUMP AND THE ASSOCIATED CHILLER CAN NOT PROVIDE A SUCCESSFUL STOP, AN ALARM WILL BE ROUTED TO OPERATOR AT THE OWS INDICATING IMMEDIATE PUMP ATTENTION IS NECESSARY.
CHWP-111001
CHWP-111002
BT-111001 FM
AS-111001
ET-111001
CHWS MAIN
CHWR MAIN
SEQUENCE OF OPERATION
CH-111001
AHU-111001
FLOW METER, TYP.
NO
NO
NO
CHWS
CH
W
R
CH
W
R
CHWR
CHWS
BYPASS VAVLE
COMPRESSOR 1
CHILLED
WATER BTU
METER
BTU METER BASIS OF DESIGN:
ONICON SYSTEM-10 WITH
MATCHED TEMPERATURE
SENSORS AND FLOW METER.
BACNET INTERFACE WITH
METERING STATION.
(TT-4)
(WFS-2)
(WFS-1)
COMPRESSOR 2
COMPRESSOR 4
COMPRESSOR 3
NOTE: QUANTITY OF
COMPRESSORS MAY
VARY BASED ON
MANUFACTURER
(TT-1)
(TT-2)
(V-1)
(DPS-1)
(TT-3)
FM
VFD
VFD
CO
MM
UN
IC
AT
IN
TE
RF
AC
E
TE
MP
ER
AT
UR
E
HU
MI
DI
TY
DI
FF
. P
RE
SS
UR
E
ST
AT
IC
P
RE
SS
UR
E
FR
EQ
UE
NC
Y
RE
AL
T
IM
E
EF
FI
CI
EN
CY
SE
TP
OI
NT
A
DJ
US
TM
EN
T
OP
T.
S
TA
RT
/ S
TO
P
RE
SE
T
RU
N
TI
ME
SE
T
BA
CK
SE
T
UP
MO
RN
IN
G
W
AR
M-
UP
GR
AP
HI
C
SYSTEM ANALOG SYSTEM FEATURES
INPUT/OUTPUT SUMMARY
REMARKSCHILLED WATER
SYSTEM
TT-2, 3; DPS-1
TT-1, 4; WFS-1, 2; COMPRESSORS, CONDENSER FANS, ETC.
CHWS & R FLOW RATES
V-1
INPUT OUTPUT
FL
OW
R
AT
E
SP
EE
D
VA
LV
E
AC
TU
AT
OR
DA
MP
ER
A
CT
UA
TO
R
DI
FF
. P
RE
SS
UR
E
SW
IT
CH
ST
AT
US
CU
RR
EN
T
RE
LA
Y
FL
OW
S W
IT
CH
ON
-O
FF
SP
EE
D
SI
GN
AL
EL
EC
. H
EA
T
ST
AG
ES
INPUT OUTPUT
DA
MP
ER
A
CT
UA
TO
R
PR
OO
F
CO
MM
UN
IC
AT
IO
N
FA
ILU
RE
DIGITAL
VA
LV
E
AC
TU
AT
OR
SP
EE
D
SW
IT
CH
DI
RT
Y
FI
LT
ER
HI
GH
-L
OW
V
AL
UE
HI
GH
/LO
W
P
RE
SS
UR
E
CO
2 L
EV
EL
TI
ME
S
CH
ED
UL
E / T
RE
ND
ALARMS PROGRAMS
CH-111001
CHW FLOW RATES
BYPASS
BTU METER
PUMP VFDs
CHW SYSTEM
C. THE CHILLER SEQUENCING SOFTWARE SHALL NOT SHUTDOWN A CHILLER PUMP UNTIL ALL CHILLER COMPRESSORS ARE PROVEN
OFF.
D. FOR SYSTEMS USING AIR-COOLED CHILLERS, THE CHILLER SHALL BE ABLE TO CALL FOR ITS EVAPORATOR…