Attachment 16 - Mechanical 2 of 2.pdf

PDF 865 KB Posted

Attached to
Y1DZ--VHA Minor Construction - Project 650-318 - New Otis CBOC for Providence VAMC
Solicitation number
36C77624R0087
Issued by

About this file

This document contains mechanical drawings, equipment schedules, and control sequences for a federal construction project to replace an outpatient clinic facility. The project is for the Department of Veterans Affairs and is located at the US Coast Guard Air Station in Cape Cod, Massachusetts. The key details include:

The mechanical systems include a 80-ton air-cooled chiller with redundant chilled water pumps, a gas-fired condensing boiler system with redundant hot water pumps, variable air volume air handling units, terminal units, exhaust fans, and a steam humidifier. Control sequences are provided for the major mechanical systems, including the chiller plant, boiler plant, air handling unit, and variable air volume terminals. Equipment schedules are included for pumps, fans, air handling units, chillers, boilers, and air distribution devices. The project includes the replacement of the existing outpatient clinic facility at the Coast Guard base.

View the file

Other files

File Type Posted
36C77624R0087 0009.docx DOCX document
36C77624R0087 0008 Request for Propsoals 9.18.2024.docx DOCX document
36C77624R0087 00008 - Wage Determination 9.18.24.pdf PDF
36C77624R0087 0008 Request for Propsoals 9.18.2024.docx DOCX document
36C77624R0087 0008.docx DOCX document
36C77624R0087 0006.docx DOCX document
Answers to RFIs - 36C77624R0087 amendment 0006 Mass..docx DOCX document
36C77624R0087 0007.docx DOCX document
36C77624R0087 0006.docx DOCX document
Rhoad Island Note regarding FAR 52.229-3.docx DOCX document
USCG Cape Cod - SNELL STATEMENT OF SPECIAL INSPECTIONS - SNELL DSS 2024-06-24.pdf PDF
Answers to RFIs - 36C77624R0087 amendment 0006.docx DOCX document
S06 - Wage Determination 6-14-24.pdf PDF
AMENDMENT 0005 PRICE COST SCHEDULE.docx DOCX document
S06 36C77624R0087 0005.docx DOCX document
Answers to RFIs - 36C77624R0087 amendment 0005.docx DOCX document
01 00 00-VA SPEC-GENERAL REQUIREMENTS_Add1.pdf PDF
S06 36C77624R0087 0004.docx DOCX document
S06 36C77624R0087 0003.docx DOCX document
S06 36C77624R0087 0002.docx DOCX document
Attachment 9 - Architectural 4 of 5.pdf PDF
36C77624R0087 0001.docx DOCX document
Attachment 9 - Architectural 4 of 5.zip ZIP file
Attachment 19 - Telecom.pdf PDF
Attachment 17 - Electrical 1 of 2.pdf PDF
Attachment 1 - Specifications_Rev_05.2024.pdf PDF
Attachment 22 - Small Business Subcontracting Plan Template.docx DOCX document
Attachment 12 - Fire Alarm.pdf PDF
36C77624R0087_1.docx DOCX document
Attachment 20 - Brand Name - Redacted.pdf PDF
Attachment 13 - Fire Protection.pdf PDF
Attachment 11 - Structural.pdf PDF
Attachment 4 - Civil.pdf PDF
Attachment 10 - Architectural 5 of 5.pdf PDF
Attachment 9 - Architectural 4 of 5.pdf PDF
Attachment 7 - Architectural 2 of 4.pdf PDF
Attachment 5 - Landscape.pdf PDF
Attachment 8 - Architectural 3 of 4.pdf PDF
Attachment 21 - wage determination.pdf PDF
Attachment 2 - General.pdf PDF
Attachment 23 - Division Breakdown Pricing.xls XLS spreadsheet
Attachment 6 - Architectural 1 of 4.pdf PDF
Attachment 14 - Plumbing.pdf PDF
Attachment 18 - Electrical 2 of 2.pdf PDF
Attachment 3 - Existing Conditions.pdf PDF
Attachment 15 - Mechanical 1 of 2.pdf PDF
Show all 46

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AUTOMATIC FLOW CONTROL

DEVICE PRESET BY MANUF. W/

P & T TEST PORTS, STRAINER,

AND DRAIN.

CHWR

CHWS

SHUT-OFF

VALVE (TYP.)

P/T TEST PORTS

STRAINER W/ BLOWDOWN &

HOSE CONNECTION

(PROVIDE STAINLESS STEEL

STRAINER BASKET)

UNION (TYP.)

THERMOMETER W/

SEPARABLE WELL (TYP.)

MANUAL AIR VENT W/

AUTO SHUT-OFF COCK

COIL

AIRFLOW

PRESSURE

GAUGE &

COCK (TYP.)

TWO WAY

CONTROL

VALVE

NOTES:

1. PROVIDE 4 X DIAMETER OF STRIAGHT PIPE ON BOTH SIDES OF BALANCING VALVE.

2. ALL COMPONENTS FULL SIZE UNLESS NOTED OTHERWISE.

3. LOCATE UNIONS TO ALLOW FOR COIL PULL.

4. PROVIDE 3-WAY VALVE WHERE INDICATED IN DRAWINGS WITH CODED NOTE NEXT TO THE EQUIPMENT TAG.

AUTOMATIC FLOW CONTROL

DEVICE PRESET BY MANUF. W/

P & T TEST PORTS, STRAINER,

AND DRAIN.

CHWR

CHWS

SHUT-OFF

VALVE (TYP.)

P/T TEST PORTS

STRAINER W/

BLOWDOWN

UNION (TYP.)

THERMOMETER W/

SEPARABLE WELL (TYP.)

MANUAL AIR VENT W/

AUTO SHUT-OFF COCK

COIL

AIRFLOW

PRESSURE

GAUGE &

COCK (TYP.)

THREE WAY

CONTROL

VALVE

PLUG COCK

NOTES:

1. PROVIDE 4 X DIAMETER OF STRIAGHT PIPE ON BOTH SIDES OF BALANCING VALVE.

2. ALL COMPONENTS FULL SIZE UNLESS NOTED OTHERWISE.

3. LOCATE UNIONS TO ALLOW FOR COIL PULL.

SECTION "A-A"

"B" "B"

ACCESS PANEL

ACCESS DOOR

CASING GASKET HANDLE INSIDE

FLEXIBLE

WASHER

FACTORY

FABRICATED

LATCH

SECTION "B-B"

INSULATION

DUCT

GASKET

INSULATION

INSULATION

"A"

"A"

HOUSING WELDED TO

DUCT SECTION

ROUND OR

FLAT OVAL

DUCT

SECTION

COVER WITH

HANDLE AND

CHAIN RETAINER

GASKETED AND

PRESSURE SEALED

CHWR

PRESSURE GAUGE

(TYP.)

CHWS

BUTTERFLY VALVE

(TYP.)

TEMPERATURE TRANSMITTER

(TYP.)

THERMOMETER (TYP.)

FLOW SWITCH FLEX CONNECTION

(TYP.)

CONTROL

PANEL

NEC

CLEARANCE

4'-0"

NOTE: SUPPLY OUTLET AND RETURN INLET LOCATION MAY DIFFER BASED ON MANUFACTURER.

SA

FLOOR DRAIN

(SEE PLUMBING DRAWINGS

CONDENSATE MOUNTED

ON UNISTRUT SUPPORT

AND ANCHORED TO FLOOR

FINAL FILTER

SUPPLY FAN

PRE-FILTERS

RA

PLENUM

BASE RAIL

CONCRETE PAD

MIXING

BOX

FILTER ACCESS DOOR

FAN SECTION WITH ACCESS DOOR

DISCHARGE

PLENUM WITH

ACCESS DOOR

FLEX CONNECTION, TYP.

CHWS & RST

RA

OA

1 TO 2 GALLON, HOT-

DIP GALVANIZED TANK

PUMP DISCHARGE LINE

FILL FUNNEL W/

WEATHER PROOF

COVER

MANUAL AIR VENT

DRAIN VALVE

PIPE TO FLOOR

DRAIN

PUMP SUCTION LINE

BALL VALVE,

TYP.

A

B B

A

CONCRETE BASE

L

W

5D

5D

2D

ANCHOR BOLT (TYP)

PIPE SLEEVE (5D, 3" MIN.)

1"

WELD HEAD TO PLATE

OR BEND OVER END 5D

PLAN SECTION B-B

SECTION A-A (BASE POURED WITH FLOOR SLAB)

TYPICAL ANCHOR

BOLT NUT & WASHER

16"

EQUIPMENT BASE

L/1

PROVIDE DOUBLE SLAB

REINFORCING IN BASE AREA

SECTION A-A (BASE NOT POURED WITH SLAB)

PROVIDE #3 BARS 12" O.C.

EACH WAY IN THE BASE &

DOWEL BASE TO FLOOR

TYPICAL ANCHOR

BOLT NUT & WASHER EQUIPMENT BASE

L/1

NOTE:

L & W DIMENSIONS SHALL

BE 6" GREATER THAN THE

EQUIPMENT BASE PLATE.

HORIZONTAL

ABOVE 2" DIA. PIPE 2" DIA. PIPE AND SMALLER

VERTICAL

ABOVE 2" DIA. PIPE 2" DIA. PIPE AND SMALLER

2-1/2" DIA.

2-1/2" DIA.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

BI

M

- C on st ru ct

R ep la ce m en t O ut pa tie nt C lin ic

/0

C on st . R ep la ce . O ut pa tie nt

C lin ic

R

.rv t

2/ 9/

0:

:1

AM

M-501

MECHANICAL DETAILS REPLACEMENT OUTPATIENT

CLINIC DESIGN AT COAST

GUARD CAPE COD

JOINT BASE CAPE COD, BARNSTABLE MA

650-318

BUILDING 1

02/10/2023 JFR JJA

100% CONSTRUCTION

DOCUMENTS

N.T.S.

2-WAY PIPING DIAGRAM DETAIL1

N.T.S.

3-WAY PIPING DIAGRAM DETAIL2

N.T.S.

ACCESS PANEL AND DOOR DETAIL3

N.T.S.

ACCESS SECTION FOR ROUND DUCT DIAGRAM4

N.T.S.

AIR COOLED CHILLER PIPING DETAIL5

N.T.S.

AIR HANDLING UNIT DIAGRAM6

N.T.S.

CHEMICAL SHOT FEEDER DIAGRAM8

N.T.S.

CONCRETE EQUIPMENT BASES DETAIL9

N.T.S.

INSTALLATION OF THERMOMETER WELLS DIAGRAM7

Revisions Date

UNION

DRAIN PAN (FURNISHED

WITH UNIT)

PRIMER PLUG

CLEAN OUT

PITCH DOWN

TOWARD DRAIN

L DIMENSIONS:

L = H + J + PIPE DIAMETER

H = 1 INCH FOR EACH INCH OF NEGATIVE

PRESSURE (INTERNAL PLUS RETURN

STATIC PRESSURE) + 1 INCH

J = 1/2 H

H

J

18 GAUGE STAINLESS STEEL

STRAPS 1" WIDE MIN (DO

NOT BLOCK ACCESS

PANELS) 2-MIN PER 4'0".

WRAP CONTINUOUS OVER

CONDENSER AND SECURE

TO CONCRETE PAD WITH

1/4"X1-1/2" STAINLESS

STEEL CONCRETE SCREWS

OR ANCHORS. (EACH SIDE)

4" THK

FIBERMESH

REINFORCED

CONCRETE PAD

6" MIN

ALL

SIDES

CONDENSING UNIT

PROVIDE 6" CLEAR

GRAVEL AROUND

CONDENSER. SOD

THEREAFTER.

DDC CONTROL

PANEL BY DIV 23

NOTE:

120 V/24 VAC CONTROL PANEL

TRANSFORMER SIZED TO MEET

LOAD REQUIREMENTS OF

TERMINAL UNIT CONTROLLERS

AND MISCILANEOUS LOW VOLTAGE

EQUIPMENT.

CPT CONTROL

PANEL BY DIV 23

TERMINAL UNIT

(EXPAMPLE)

SWITCH

FUSE

SWITCH

TO TERMINAL UNITS AND LOW

VOLTAGE EQUIPMENT

LOW VOLTAGE

POWER BY DIV 23

24 VAC TO

TU

CONTROL

120 VAC BY DIV 26

SE

E

NO

TE

SEE NOTE 3

SEE NOTE 2

SEE NOTE 1

NOTES:

1. RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A MINIMUM OF 3 TIMES THE DIAMETER OF INLET.

2. A FLEXIBLE AIR DUCT CONNECTOR IS NOT MANDATORY FOR INLET TO THIS BOX, BUT ALLOWED TO ACCOMMODATE MINOR

OFFSETS. MAXIMUM LENGTH 3'-0".

3. A BRANCH DUCT SERVING AN INDIVIDUAL BOX MAY BE THE SAME SIZE AS THE BOX INLET, PROVIDED THE EQUIVALENT LENGTH

OF THE BRANCH DUCT, AS SHOWN, DOES NOT EXCEED 10 FEET. FOR LONGER LENGTHS, INCREASE THE DUCT SIZE AND PROVIDE A DUCT TRANSITION TO MAINTAIN THE DUCT STATIC PRESSURE DROP AT OR BELOW 0.2"/100'.

4. FLEXIBLE AIR DUCT CONNECTORS, WHEN USED FROM TERMINAL UNIT SUPPLY AIR DUCT TO DIFFUSER, SHALL NOT EXCEED

5'-0". USE RIGID ELBOWS FOR CHANGE OF DIRECTION GREATER THAN 45°.

5. COMPONENT ARRANGEMENT MAY VARY BY MANUFACTURER. PROVIDE INSULATION W/VAPOR BARRIER FOR CONNECTING

DUCT SECTIONS.

6. DUCT CONNECTION TO BOX SHALL BE SAME DIMENSIONS AS BOX OUTLET AND SHALL MAINTAIN THESE DIMENSIONS (UNLESS

OTHERWISE INDICATED) UNTIL CHANGE IN DUCT SIZE INDICATED ON DRAWINGS.

AIR TERMINAL

UNIT (CV OR VAV)

REHEAT COIL

FLEXIBLE AIR DUCT

CONNECTOR. SEE DETAIL

DIFFUSER (TYP.)

SEE SPECIFICATIONS FOR

CLAMPS AND SEALANT (TYP.)

SEE NOTE 5

FL

OW SEE NOTE 7

HANGERS MUST NOT DEFORM DUCT SHAPE

TRAPEZE HANGERS

SIZE BOLTS FOR LOAD

STRAP OR

ANGLE

OPTIONAL ATTACHMENTS STRAP

HANGER RODS,

WIRES OR

STRAPS

BAND; ONE HALF-

ROUND MAY BE USED IF

DUCT SHAPE IS

MAINTAINED

10" DIA. MAX. 36" DIA. MAX. 24" DIA. MAX.

SECURE

WIRE

HANGER LOAD

FASTENERS

W

1/3 W

R

1/3 W1/2W

W

2/3W

R

W

R

VANE

R SHALL

EQUAL

OR BE

GREATER

THAN W.

R SHALL

EQUAL OR

BE

GREATER

THAN 1/3W.

R SHALL

EQUAL OR

BE

GREATER

THAN 1/6W.

NOTES:

1. THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.

2. ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS ELBOWS. ALL SHORT RADIUS

ELBOWS SHALL HAVE VANES. VANES SHALL BE CONSTRUCTED, SUPPORTED AND FASTENED AS

RECOMMENDED BY SMACNA.

NOTES:

1. ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.

2. WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE REGARDLESS OF W

DIMENSION.

3. ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2" [40mm] MAXIMUM SPACE

BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE.

4. WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL BE DOUBLE VANE TYPE.

W1

W

MAIN EXHAUST OR RETURN

PLAN VIEW

AIR

FLOW AIR

FLOW

PROVIDE VOLUME DAMPER

AT EACH BRANCH DUCT

1/4W OR 4" MIN.

BRANCH

DUCT

VD

W

DISCHARGE

DOME

SPONGE RUBBER PAD

(VIB. ISOL.)

FACTORY PRE-

FAB. CURB

THERMAL &

ACOUSTICAL

INSULATION

BACKDRAFT

DAMPER

FLASHING ROOF

CONSTRUCTION

STEEL MESH

SCREEN

BUTTERFLY

DAMPER

MOTOR

NOTES:

ALL ROOF MOUNTED EQUIPMENT MUST ADHERE TO CURRENT

HURRICANE CODES REGARDING ROOF TIE-IN AND WIND RESISTANCE

GUY WIRE WITH TURNBUCKLE

(TYP. OF 3) 120° APART

CONNECT GUY WIRE TO

EQUIPMENT LIFTING LUGS

PIPE PORTAL FOR WIRE

CONNECTION.

FLASHING - REFER

TO ARCHITECTURAL

WIRE CONNECTION TO ROOF STRUCTURE. REFER

TO STRUCTURAL DRAWINGS FOR DETAIL.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

BI

M

- C on st ru ct

R ep la ce m en t O ut pa tie nt C lin ic

/0

C on st . R ep la ce . O ut pa tie nt

C lin ic

R

.rv t

2/ 9/

0:

:1

AM

M-502

MECHANICAL DETAILS REPLACEMENT OUTPATIENT

CLINIC DESIGN AT COAST

GUARD CAPE COD

JOINT BASE CAPE COD, BARNSTABLE MA

650-318

BUILDING 1

02/10/2023 JFR JJA

100% CONSTRUCTION

DOCUMENTS

N.T.S.

CONDENSATE DRAIN TRAP W/ FORMULA DIAGRAM1

N.T.S.

CONDENSING UNTI MOUNTED ON GRADE DIAGRAM2

N.T.S.

DDC PANEL & LOW VOLTAGE CONTROL POWER TRANSFORMER PANEL DIAGRAM3

N.T.S.

DUCT CONNECTIONS - AIR TERMINAL UNITS DIAGRAM4

N.T.S.

DUCT SUPPORT DIAGRAMS6

N.T.S.

DUCTWORK RADIUS ELBOWS DIAGRAM7

N.T.S.

DUCTWORK SQUARE VANE ELBOWS DIAGRAM8

N.T.S.

EXHAUST OR RETURN BRANCH DUCTWORK DIAGRAM9

N.T.S.

ROOF UPBLAST RELIEF FAN DIAGRAM5

FLEXIBLE DUCT

SIZE SAME AS

DIFFUSER INLET: 5'-0" MAX

LENGTH

12"

CEILING

SUPPORT SADDLE FROM

STRUCTURE

VOLUME DAMPER

W/ LOCKING QUAD

SADDLE

SHEET

METAL

CONICAL OUTLET

BRANCH DUCT

USE RIGID

ELBOWS FOR

CHANGE

OF DIRECTION

GREATER THAN

45°

SEE SPECIFICATIONS FOR

CLAMPS AND SEALANT (TYP.)

NOTE:

THE USE OF FLEXIBLE AIR DUCT CONNECTORS ARE NOT PERMITTED FOR THE

DEDICATED AHU SERVING THE SURGICAL

SUITE.

TYPICAL

DIFFUSER OR

REGISTER IN

LAY-IN CLG.

THERMAL INSULATION

SEE SPECIFICATIONS

ROUND FLEXIBLE CONNECTION

RECTANGULAR FLEXIBLE CONNECTION

FLANGED

CONNECTION ON

FAN SIDE

WASHER 1-1/2" [40mm] MIN. TO 3" [75mm] MAX. INSTALLED. 6" [150mm] NOMINAL WITH MATERIAL

TAUT

FLEXIBLE

MATERIAL AS

SPECIFIED

1"x1/8" [25x3mm] DRAW BAND

1"x1/8" [25x3mm] BAND IRON

BOLT ON 4" [100mm] CENTERS

5/16" [8mm] FLANGE

DUCT

SHEET METAL SCREWS

ON 12" [300mm]

CENTERS

RIVET ON 4"

[100mm]

CENTERS

SHEET METAL AS

SPECIFIED FOR

DUCTWORK.

1"x1/8" [25x3mm] BAND IRON

BOLT ON 4" [100mm] CENTERS

1" [25mm] FLANGE & HEMALTERNATE

POSITION OF

BOLT 1 1/2" [40mm]

POCKET SLIP

DUCT

SHEET METAL AS

SPECIFIED FOR

DUCTWORK.

[15mm] [15mm] [40mm]

1 1/2" [40mm] MIN. TO 3" [75mm] MAX. INSTALLED. 6" [150mm] NOMINAL WITH MATERIAL TAUT

FLANGED

CONNECTION

ON FAN SIDE

WASHER

FLEXIBLE MATERIAL AS

SPECIFIED

1/2" 1 1/2"1/2"

MAIN AIR DUCT

WITH INSULATION

MANUAL BALANCING DAMPER

STAINLESS STEEL DRAW BANDS

CEILING

FLEXIBLE DUCT

PROVIDE TYPICAL FLEX DUCT

CONNECTION

DISTRIBUTION PLENUM W/

INSULATION. INSULATION CAN

BE INTERNAL OR EXTERNAL

REFER TO SCHEDULE FOR

NUMBER OF SLOTS

TURNING VANES SHALL BE COMPLETELY

FLUTTER-PROOF; PERMANENTLY FIXED TYPE

MADE OF GALVANIZED STEEL. TURNING

VANES SHALL BE MINIMUM 26 GAUGE

DOUBLE WALL AIRFOIL TYPE. TURNING

VANES SHALL BE SECURELY FASTENED TO A

RUNNER; VANE EDGES SHALL PROJECT

AIRFLOW PARALLEL TO DUCT SIDES.

MANUAL BALANCING 45° BOOT FITTING

DAMPER, TYPICAL

DAMPER ACCESS

DOOR, TYP. FOR

ALL DAMPERS

SQUARE ELLS SHALL ONLY BE

USED WHERE THERE IS

INSUFFICIENT SPACE FOR

RADIUS ELLS.

PROVIDE INSULATION SHIELD

& INSERT FOR ALL PIPING

(8" [200mm] MIN.)

1-5/8" [43mm] 12 GAUGE CHANNEL OR 2"x2"x1/4" [50x50x6.4mm] ANGLE

1/2" [15mm] DIA.

HANGER RODS WITH

36" [900mm] MAX.

SPACING ON EACH

CHANNEL

WELD

SADDLE

INSULATION SHIELD

AT HANGER

PROVIDE HIGH

COMPRESSIVE STRENGTH

INSULATION (9 PSF MIN.

DENSITY) UNDER

INSULATION SHIELD

INSULATION (VAPOR

BARRIER TYPE IS

REQUIRED FOR LOW

TEMPERATURE PIPE)

HANGER ROD

NOTES:

SEE SPECIFER FOR DETAILED

HANGER REQUIREMENTS

5 FT

THRU [20]

6 8 10

[32][25] [40]

[65]

[50]

[75]

-1312 14 -16 -

[125][100]

[150]

[250]

[200]

[300]

[400]

[350]

[450]

[600]

[500]

20 241814 16128 1064 532 2 1/21 1/21 1 1/4

[9100] [9600][8500][7600] [8200][7000][5800] [6700][5200][4100] [4900][3700][3000] [3400][2700][2100]

--- --[4900] -[4100][3700] [4000] -[3000][2400][1800][1500]

THRU 3/4

[2100] [2100]

[2100]

[2700]

[2400]

SIDE VIEW TRAPEZE HANGER FOR UP

TO 1000 LB. [453KG] UNIFORM LOAD

ADJUSTABLE CLEVIS HANGER TYPE 1 - SEE

SPECIFICATIONS ADJUSTABLE CLEVIS HANGER TYPE 43 - SEE

SPECIFICATIONS

MAXIMUM PIPE/TUBING SUPPORT SPACING

NOM. SIZE

PIPE

TUBING

IN.

[mm]

FT.

[mm]

FT.

[mm]

[25 mm

1"

M

AX

MOTOR & DRIVE

U.L. APPROVED

ELECTRICAL DISCONNECT

BIRDSCREEN

SPONGE RUBBER PAD

(VIB. ISOL.)

FACTORY PRE-

FAB. CURB

THERMAL &

ACOUSTICAL

INSULATION

BACKDRAFT

DAMPER

FLASHING

ROOF

CONSTRUCTION

EXHAUST

DUCTWORK

ALL ALUMINUM WHEEL

HUB & HOUSING

MOTOR DOME EXHAUST FAN

DISCHARGE

DOME

NOTES:

ALL ROOF MOUNTED EQUIPMENT MUST ADHERE TO CURRENT

HURRICANE CODES REGARDING ROOF TIE-IN AND WIND RESISTANCE

MITERED ELBOW

45°

3'0" MIN. ABOVE ROOF

5" M

IN

3" M

IN

DRAW BAND

METAL HOOD

METAL SLEEVE

ROOF SURFACE

3" MIN.

METAL SLEEVE

W/ 3" FLANGE-

NAIL 3" O.C.

BITUMEN STOP

DO NOT PROVIDE MESH

SCREEN AT TERMINATION

1. VERIFY SUPPLY/RETURN ORIENTATION ON BOILER.

2. PROVIDE EACH BOILER WITH ITS OWN CONDENSATION NEUTRALIZATION KIT.

3. LEVEL BOILER.

4. MAINTAIN MANUFACTURER'S RECOMMENDED CLEARANCES, INCLUDING ABOVE BOILER FOR BURNER ACCESS.

BOILER FLUE

VENT THRU ROOF

COMBUSTION

AIR VENT THRU ROOF

1-1/2" DRAIN

3/4" PVC DRAIN TO CONDENSATE

NEUTRALIZATION KIT PROVIDED BY

BOILER MANUFACTURER

4" CONCRETE

HOUSEKEEPING PAD

STAND

4" HHWS

4" HHWR

4" HHWS

1" PRESSURE

RELIEF VALVE TO DRAIN

4" HHWR

STRAINER W/ BLOW OFF

VALVE

UNION (TYP)

THERMOMETER

(TYP)

PRESSURE GAUGE & COCK

(TYP)

CALIBRATED BALANCING VALVE

SOLENOID VALVE

MANUAL VENT

AIR SEPARATOR (WITH

SUPPORT BRACKETS -

SEE SCHEDULE

DRAIN LINE TO

FLOOR DRAIN

PRESSURE

REDUCING VALVE

W/ CHECK

FLOOR

_" TO PUMP

SUCTION

M

_" COLD WATER

PIPE TO DOMESTIC

WATER MAKE-UP

WATER METER

HIGH CAPACITY

AUTOMATIC AIR VENT

AS-1

ET-1

CONNECT TO

SIDE OF MAIN

BLOWDOWN VALVE

PIPE TO FLOOR DRAIN

DRAIN

GATE VALVE

REDUCED PRESSURE

BACKFLOW PREVENTER

EXTEND NEW MAKE-

UP WATER LINE AS

REQUIRED

FULL SIZE BYPASS

LOOP WATER RETURN

SUPPORT FROM STRUCTURE

NOTE: ALL PIPE ACCESSORIES SHALL BE FULL LINE SIZE.

DIAPHRAGM TYPE

PRESSURIZED

EXPANSION TANK -

SEE SCHEDULE

SUSPENDED.

SUPPORTS PER

MANUFACTURERS

RECOMMENDATIONS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

BI

M

- C on st ru ct

R ep la ce m en t O ut pa tie nt C lin ic

/0

C on st . R ep la ce . O ut pa tie nt

C lin ic

R

.rv t

2/ 9/

0:

:1

AM

M-503

MECHANICAL DETAILS REPLACEMENT OUTPATIENT

CLINIC DESIGN AT COAST

GUARD CAPE COD

JOINT BASE CAPE COD, BARNSTABLE MA

650-318

BUILDING 1

02/10/2023 JFR JJA

100% CONSTRUCTION

DOCUMENTS

N.T.S.

FLEXIBLE AIR DUCT CONNECTOR DETAIL1

N.T.S.

FLEXIBLE DUCT CONNECTIONS DETAIL2

N.T.S.

LINEAR SLOT DIFFUSER DIAGRAM4

N.T.S.

LOW PRESSURE DUCTWORK DIAGRAM5

N.T.S.

PIPE HANGER DETAIL6

N.T.S.

ROOF DOWNBLAST EXHAUST FAN DIAGRAM7

N.T.S.

ROUND GOOSENECK DETAIL9

N.T.S.

CONDENSING BOILER DETAIL8

N.T.S.

EXPANSION TANK, AIR SEPARATOR & MAKE-UP WATER DETAIL3

VB

VB

SMACNA FIGURE 4-6

45° LEED IN RIGID DUCT TO AIR

TERMINAL UNIT.

MAIN SUPPLY

PLAN VIEW

FLOW

FL

OW

AIR SPLIT DUCT TAKE-OFF

PLAN VIEW

BRANCH DUCT TAKE-OFF PLAN

VIEW

SUPPLY REGISTER

TAKE-OFF PLAN VIEW

AIR

FLOW

AIR

FLOW

AI

R

FL

OW

SUPPLY REGISTER

OR BRANCH DUCT

TURNING VANES

MAIN

SUPPLY

DUCT

SEE FLOOR PLAN FOR

SPLIT DIMENSION

PROVIDE VOLUME

DAMPER

PROVIDE

VOLUME

DAMPER

ADJUSTABLE

METAL ROD

OR LINKAGE

TOP REGISTER

MAIN

SUPPLY

DUCT

VOLUME EXTRACTOR; ADJUSTABLE

FROM FULLY CLOSED POSITION TO

CFM NOTED ON FLOOR PLANS

AIR

FLOW

AIR

FLOW

1/4 W OR 4" MIN.

AIR

FLOW

MAIN SUPPLY

DUCT

AI

R

FL

OW

W

MANUAL FLOW CONTROL

BALANCING VALVE

MIN. 8 PIPE DIAMETERS

VIBRATION ISOLATOR

(TYP)

CHECK VALVE

PRESSURE GAGE WITH

SERVICE COCK

COUPLING GUARD

PUMP

MOTOR

GROUT IN PUMP BASE WHEN REQ'D BY

MFGR'S INSTALLATION INSTRUCTIONS

ANCHOR PUMP TO 4" THICK CONCRETE

PAD. PAD IS MIN. 3" LARGER THAN PUMP

BASE ON ALL SIDES.

3/4" DRAIN VALVE W/

HOSE CONNECTTION

FLOOR FLANGE

GROUT

SUPPORT

SUCTION DIFFUSER

1/4"

GLOBE OR NEEDLE

VALVE (TYP)

BUTTERFLY VALVE (TYP)

* STRAIGHT LENGTHS OF UNOBSTRUCTED PIPE WITHOUT INLINE APPURTENANCES SHALL

BE INSTALLED UP/DOWNSTREAM OF FLOW CONTROL BALANCING VALVE PER MFGR'S

INSTALLATION INSTRUCTIONS.

BASE

ELECTROMAGNETIC

INSERTION FLOW

METER. BASIS OF

DESIGN: ONICON

F-3500

INSERTION 1"

FULL PORT

BALL VALVE

FOR HOT TAP

REFER TO

MANUFACTURER'S

RECOMMENDATIONS

FOR UPSTREAM AND

DOWNSTREAM

DISTANCE

MIN. 5 DIA MIN. 10 DIA

MI

N.

DI

A

SINGLE BEND

ALLOWED IF

PRECEEDED BY

MIN. 9 DIA.

RTV OR SILICONE CAULKING

BETWEEN PLATES AND WALL

AIR INTAKE

TERMINAL

FASTENER

PVC COUPLING

(IF NECESSARY)

PVC PIPE

INTERIOR CMU WALL

1/4" TO 1/2" CLEARANCE

ALL AROUND

EXTERIOR WALL

COVER PLATE

XX'-0"

AFF

GUY WIRE.

TYPICAL OF 3,

120° APART

DISCHARGE

DUCT

HALF CLOSURE

BAND

HALF CLOSURE

BAND

GUY RING

DISCHARGE

OUTLET

NOTE: PROVIDE

STRUCTURAL STEEL

SUPPORT

PIPE PORTAL

3' 0"

STORM COLLAR

FLASHING - REFER

TO ARCHITECTURAL

ROOF

VENTILATED

ROOF THIMBLE

LISTED VENT CAP

NOTE: ALL HARDWARE

SHALL BE ALL STAINLESS

STEEL CONSTRUCTION.

FLASHING - REFER

TO ARCHITECTURAL

PIPE STRAPS AT APPROX. 18" INTERVALS

SELF REGULATING HEAT TRACE CABLE

ALUMINUM FOIL TAPE

WATERPROOF JACKET

OVER INSULATION

HEAT TRACE CABLE

END CAP

NO

TO POWER SUPPLY AT

DISCONNECT SWITCH

CONTACTOR

THERMOSTAT WITH AMBIENT

AIR SENSOR SET ON AT 35°F

WATER TIGHT

CONTROL BOX

1' - 6"

PIPE STRAPS

HOT-COLD JOINT

PIPE INSULATION AND ALUMINUM

FOIL TAPE NOT SHOWN

HEAT TRACE CABLE

EVENLY DISTRIBUTED

ALONG PIPE

SELF REGULATING TYPE

HEAT TRACE CABLE

VALVE

ALUMINUM FOIL TAPE AND

INSULATION NOT SHOWN

NOTE: PROVIDE WEATHER RESISTANT LABELING ON

EXTERIOR OF JACKET IDENTIFYING PIPES AS BEING

"ELECTRIC TRACED" WITH VOLTAGE INDICATED.

INDOOR UNIT (FCU-1)

WALL MOUNTING BRACKET

FURNISHED BY FCU MFGR

WALL SLEEVE WITH CAPS

FURNISHED BY FCU MFGR

1/2" ø DRAIN LINE TO FLOOR

SINK SEE DETAIL

THERMISTOR CABLE

POWER & HIGH VOLTAGE

CONTROL TO INDOOR UNIT

OUTDOOR UNIT (ACU-4)

SECURE TO CONCRETE PAD

4" THICK CONCREETE PAD

(MIN. 4" EXTENSION ALL SIDES)

AIRFLOW

AIRFLOW

INSULATED XX"ø RS. XX"ø RL

REFRIGERANT LINES

CONNECTION CABLE

TO THERMOSTAT

TOP OF UNIT

± X'-XX" AFF

STRUCTURE ABOVE

DUCT

ROD COUPLING

SEISMIC CABLE

ANCHOR

TRAPEZE SUPPORT SELF TAPPING SHEET METAL SCREWS

UPPER SUPPORT (FOR

SEISMIC BRACE)

CABLE BRACKET

ROD STIFFENER

THREADED ROD

STIFFENER CLAMP

45°±15°

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

BI

M

- C on st ru ct

R ep la ce m en t O ut pa tie nt C lin ic

/0

C on st . R ep la ce . O ut pa tie nt

C lin ic

R

.rv t

2/ 9/

0:

:1

AM

M-504

MECHANICAL DETAILS REPLACEMENT OUTPATIENT

CLINIC DESIGN AT COAST

GUARD CAPE COD

JOINT BASE CAPE COD, BARNSTABLE MA

650-318

BUILDING 1

02/10/2023 JFR JJA

100% CONSTRUCTION

DOCUMENTS

N.T.S.

TERMINAL UNIT SUPPLY DUCT TAKEOFF DIAGRAM1

N.T.S.

SUPPLY DUCTWORK TAKE-OFFS DIAGRAM2

N.T.S.

BASE MOUNTED CENTRIFUGAL PUMP DETAIL4

N.T.S.

HYDRONIC FLOW METER DETAIL3N.T.S.

BOILER HORIZONTAL INTAKE DETAIL6

N.T.S.

BOILER FLUE DETAIL7

N.T.S.

HEAT TRACING DETAIL8 N.T.S.

WALL MOUNTED MINI SPLIT DETAIL5

N.T.S.

SEISMIC DUCT HANGER DETAIL9

CLAMP

LOCK

NUTS

(TYP)

CROSS

BRACING RODS ALL

FOUR SIDES

HANGER

ROD

(TYP)

RESILIENT

PAD

BONDED

STEEL PLATE

NEOPRENE

WASHER & SLEEVE

ANCHOR

BOLTEQUIPMENT

BASE

FLOOR

FLOOR MOUNT

EQUIPMENT RESTRAINED BY RESILIENT

PADS (TYPE DS)

SEISMIC BRACING FOR

LIGHT SUSPENDED

EQUIPMENT

EQUIPMENT WEIGHT

250 LBS. OR LESS

NOTE: NOT REQUIRED FOR AIR TERMINAL UNITS.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

BI

M

- C on st ru ct

R ep la ce m en t O ut pa tie nt C lin ic

/0

C on st . R ep la ce . O ut pa tie nt

C lin ic

R

.rv t

2/ 9/

0:

:2

AM

M-505

MECHANICAL DETAILS REPLACEMENT OUTPATIENT

CLINIC DESIGN AT COAST

GUARD CAPE COD

JOINT BASE CAPE COD, BARNSTABLE MA

650-318

BUILDING 1

02/10/2023 JFR JJA

100% CONSTRUCTION

DOCUMENTS

N.T.S.

SEISMIC BRACING FOR EQUIPMENT DETAIL1

ETHERNET/IP

BUILDING LEVEL

CONTROLLER

(BLC)

MSTP

COMMUNICATION

(TYPICAL) CH-111001

AHU-111001

CHWP-111002

FCSS-111001

TU-1110031

EF-111003

EF-111002

CHWP-111001

EF-121001

TU-111001

BL-111001

ETHERNET/IP

(TYPICAL)

HHWP-111002

HHWP-111001

FCSS-111003

FCSS-111002

GENERAL CONTROL REQUIREMENTS:

1. CONTRACTOR SHALL PROVIDE COMPLETE DDC AUTOMATIC TEMPERATURE CONTROL SYSTEM

UTILIZING A WEB-BASED INTERFACE RESTRICTED FOR AUTHORIZED VA PERSONNEL ONLY. CONTROL

SYSTEM SHALL BE METASYS BUILDING MANAGEMENT SYSTEM BY JOHNSON CONTROLS, INC. ALL

HVAC SYSTEM AND ANCILLARY COMPONENTS SHALL BE CONTROLLED BY THE NEW BUILDING

MANAGEMENT SYSTEM. FINAL CONNECTION OF NEW EQUIPMENT TO THE BUILDING MANAGEMENT

SYSTEM SHALL BE MADE BY A COMPANY AND TECHNICIANS FULLY QUALIFIED AND CERTIFIED BY

JOHNSON CONTROLS, INC. TO PROGRAM, INSTALL, ADJUST, REPAIR, MAINTAIN, MODIFY, OR

OTHERWISE MANIPULATE THE METASYS BUILDING MANAGEMENT SYSTEM BY JOHNSON CONTROLS,

INC. CURRENT COMPANY AND TECHNICIAN QUALIFICATIONS AND CERTIFICATIONS TO PROGRAM, INSTALL, ADJUST, REPAIR, MAINTAIN, MODIFY, OR OTHERWISE MANIPULATE THE JOHNSON

CONTROLS METASYS SYSTEM MUST BE MAINTAINED THROUGHOUT THE CONSTRUCTION OF THE

PROJECT INCLUDING ANY EXTENSIONS OF THE CONSTRUCTION PERFORMANCE PERIOD. IF THE

CONTRACTOR UTILIZES THE SERVICES OF A SUBCONTRACTOR OTHER THAN JOHNSON CONTROLS

TO PERFORM THIS WORK, THE CONTRACTOR SHALL PROVIDE THE VA, VIA SUBMITTAL, COPIES OF

FACTORY TRAINING CERTIFICATES FOR EACH TECHNICIAN WORKING ON THE METASYS SYSTEM

PRIOR TO COMMENCEMENT OF ANY CONTROLS WORK. THE VA WILL REVIEW THE CERTIFICATIONS AS PART OF THE SUBMITTAL PROCESS. CONTRACTOR SHALL CARRY THE COST OF THIS WORK IN

THEIR BID.

2. ALL DDC CONTROLS SHALL BE PROVIDED BY THE CONTRACTOR AND SHALL BE BACNET METASYS CONTROLS BY JOHNSON CONTROLS FOR AHUs, CHILLERS, FANS, FCUs, VAVs, CIRCULATING PUMPS, CONTROL VALVES, MOTORIZED DAMPERS, AND ANY OTHER EQUIPMENT OR ACCESSORIES AS NOTED

IN THE DRAWINGS AND SPECIFICATIONS.

3. ALL CONTROLS SHALL HAVE OCCUPIED AND UNOCCUPIED FUNCTIONS.

4. ALL SET POINTS SHALL BE FULLY ADJUSTABLE.

5. ALL MONITORED POINTS, INCLUDING STATUS (ON, OFF, FAILED) AND ANY ALARMS SHALL DISPLAY AT

THE DDC WORKSTATION(S).

6. WHERE 100% REDUNDANT MOTORIZED EQUIPMENT IS INSTALLED, THE TWO (OR MORE) PIECES OF EQUIPMENT SHALL ALTERNATE OPERATION ON AN ADJUSTABLE, EQUAL RUN-TIME BASIS. THE DDC SYSTEM SHALL DISPLAY CUMULATIVE RUN-TIME OF EACH UNIT. IF ONE UNIT FAILS, THE OTHER UNIT

SHALL START AUTOMATICALLY AND THE DDC SYSTEM SHALL GENERATE AN ALARM SIGNAL.

7. ALL INDIVIDUAL ROOM ENVIRONMENTAL PARAMETERS SHALL BE DESIGNED AND SET IN

ACCORDANCE WITH THE LATEST VERSION OF THE VA HVAC DESIGN MANUAL.

8. HVAC SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH THE LATEST VERSION OF THE VA HVAC

DESIGN MANUAL AND THE LATEST VERSIONS OF THOSE STANDARDS REFERENCED WITHIN THAT

MANUAL.

9. ALL EQUIPMENT SHALL BE ENERGY STAR CERTIFIED.

HP-111001

HP-111002

HP-111003

GWH-111001 1

GWH-111002 1

HWP-111001 2

MISC. SENSORS,

VALVES,

ACCESSORIES, ETC.

PROVIDE WITH WEB

BASED INTERFACE

(T S-

6)

OA

24VAC

NC(D

-1

(T S-

3)

VFD

(DPS-1)

PRE-

FILTERS

FROM FAS

F

(A

FS

-1

COOLING

COIL

(T S-

5)

(S

PS

-3

TO VAV BOXES

LOCATED

APPROXIMATELY

2/3RD WAY DOWN

SUPPLY DUCT

GENERAL:

1. THE UNIT SHALL BE AVAILABLE FOR OPERATION AT ALL TIMES, BUT IN GENERAL, THE UNIT SHALL RUN 24/7 TO MAINTAIN TEMPERATURE AND HUMIDITY CONDITIONS IN THE SPACE. UNIT SHALL BE NORMALLY STARTED AND STOPPED BY THE BUILDING LEVEL CONTROLLER (BLC).

2. H-O-A SWITCH SHALL BE KEPT IN THE "AUTO" POSITION. "HAND" AND "OFF" POSITIONS SHALL BE USED FOR MAINTENANCE ONLY.

3. ALL CONTROLS SHALL BE AUTOMATIC AND ALL SETPOINTS SHALL BE ADJUSTABLE.

4. COOLING MODE SHALL BE DEFINED AS ANY TIME THE OUTDOOR TEMPERATURE IS ABOVE 50 DEG. (ADJ), AND A CALL FOR COOLING EXISTS

FROM ANY ASSOCIATED PIECE OF EQUIPMENT. THE COOLING MODE SHALL EXTEND TO ONE HOUR BEYOND THE TIME THE CALL FOR COOLING IS

SATISFIED. THIS IS TO PREVENT SHORT CYCLING.

5. HEATING MODE SHALL BE DEFINED AS ANY TIME THE OUTDOOR TEMPERATURE IS BELOW 68 DEG. (ADJ), AND A CALL FOR HEATING EXISTS FROM

ANY ASSOCIATED PIECE OF EQUIPMENT.

6. FAN MONITORING SENSORS CS-1,2 AND AFM-1,2 SHALL BE FACTORY MOUNTED BY THE FAN MANUFACTURER.

7. SET-UP TRACKING FOR SA AND RA FANS BASED ON AIRFLOW SCHEDULE BELOW. ATC AND TAB CONTRACTOR SHALL CREATE A FAN TRACKING

CHART FOR USE IN TRACKING BUILDING PRESSURIZATION.

SYSTEM START / STOP:

1. WHEN THE AHU IS INDEXED TO OPERATE BY THE BLC, THE AHU SUPPLY FAN SHALL START AND ALL SAFETIES AND INTERLOCKS SHALL OPERATE THROUGH THE STARTER AND BYPASS CONTACTOR. SEE INTERLOCK SCHEDULE FOR AHU AND EXHAUST FAN INTERLOCKS.

AIR FLOW CONTROL AND RESET:

1. THE BLC SHALL MODULATE THE SA FAN VFD FREQUENCY BASED ON A SIGNAL FROM THE STATIC PRESSURE SENSOR SPS-3 LOCATED IN THE SUPPLY DUCT TO MAINTAIN THE STATIC PRESSURE SET POINT AS DETERMINED BY THE TEST AND BALANCE CONTRACTOR.

2. THE BLC SHALL MODULATE THE RELIEF FAN VFD FREQUENCY BASED ON A SIGNAL FROM THE STATIC PRESSURE SENSOR SPS-4 LOCATED IN THE RETURN DUCT TO MAINTAIN MINUS 1.5" WG (ADJUSTABLE). FINAL STATIC PRESSURE SET POINT SHALL BE DETERMINED BY THE TEST AND

BALANCE CONTRACTOR BASED ON THE AIR FLOW BALANCE SCHEDULE.

3. A HIGH LIMIT STATIC PRESSURE SENSOR SPS-2 DOWNSTREAM OF THE SUPPLY FAN SHALL PREVENT OVER PRESSURIZATION OF THE SUPPLY DUCTWORK. IF THE DISCHARGE STATIC PRESSURE RISES ABOVE THE SETPOINT AS MEASURED BY HIGH STATIC LIMIT, THE AHU UNIT SHALL DE- ENERGIZE AND SEND AN ALARM TO THE BLC. AHU SHALL NOT BE ALLOWED TO RUN UNTIL AN OPERATOR MANUALLY RESETS THE SENSOR AT

THE UNIT.

4. A LOW LIMIT STATIC PRESSURE SENSOR SPS-1 UPSTREAM OF THE RELIEF AIR FAN SHALL PREVENT UNDER PRESSURIZATION OF THE RETURN DUCTWORK. IF THE RETURN DUCT STATIC PRESSURE SENSOR FALLS BELOW MINUS 2" WG (ADJUSTABLE), THE UNIT SHALL SHUTDOWN AND

SEND AN ALARM TO THE BLC.

5. THE UNIT SHALL AUTOMATICALLY INCREASE/DECREASE IN SPEED WITH FILTER LOADING BASED UPON STATIC PRESSURE SENSOR SPS-3 SETPOINT (AS DETERMINED BY TAB CONTRACTOR). STATIC PRESSURE SENSOR SPS-3 SHALL BE LOCATED 2/3 DOWNSTREAM OF SUPPLY DUCT

RUN.

6. AFTER THE SA FAN STARTUP IS INDEXED FOR 30 MINUTES (ADJUSTABLE), THE BLC SHALL POLE ALL VAV CONTROLLER REQUEST FOR MAXIMUM DAMPER POSITIONS EVERY 5 MINUTES (ADJUSTABLE). IF THE NUMBER OF VAV CONTROLLERS AT MAXIMUM DAMPER POSITION ARE ≤ 2 (ADJUSTABLE), THE STATIC PRESSURE SENSOR SPS-3 SETPOINT SHALL REDUCE BY 0.04" WG (ADJUSTABLE). DURING THE NEXT POLE SEQUENCE, IF THE NUMBER OF VAV CONTROLLERS AT MAXIMUM POSITION ARE > 2 (ADJUSTABLE), THE STATIC PRESSURE SENSOR SETPOINT SHALL INCREASE BY 0.06" WG (ADJUSTABLE). THE STATIC PRESSURE SENSOR SETPOINT SHALL NOT BE INDEXED TO EXCEED THE HIGH LIMIT STATIC PRESSURE SETPOINT OR REDUCED BELOW THE LOW LIMIT STATIC PRESSURE SETPOINT. IF THE NUMBER OF REQUEST FROM A SINGLE VAV CONTROLLER EXCEED 6 (ADJUSTABLE) CONSECUTIVE REQUEST, THE BLC SHALL IGNORE THIS CONTROLLER REQUEST AND SEND AN

ALARM TO THE BLC.

SUPPLY AIR TEMPERATURE CONTROL AND RESET:

1. WHEN THE SUPPLY FAN IS ENERGIZED, THE CHILLED WATER CONTROL VALVE SHALL MODULATE TO MAINTAIN THE LEAVING AIR TEMPERATURE

SETPOINT OF 55°F (ADJUSTABLE).

2. DURING WINTER CONDITIONS, THE UNIT SHALL RAMP DOWN TO MINIMUM AIRFLOW (AS INDICATED BY THE "HEATING CFM" IN THE TERMINAL UNIT SCHEDULE) AND THE VAV BOXES' HEATING HOT WATER CONTROL VALVE SHALL MODULATE TO MAINTAIN ROOM TEMPERATURE SETPOINT (SEE

VAV TERMINAL UNIT SEQUENCE OF OPERATION FOR MORE INFORMATION).

3. WHEN AHU IS AT MINIMUM AIRFLOW FOR 30 MINUTES (ADJUSTABLE), THE SUPPLY AIR LAT AS SENSED BY TS-6 SHALL RESET UP IN 1°F INCREMENTS EVERY 30 MINUTES UNTIL RA RELATIVE HUMIDITY AT H-1 RISES ABOVE 60% AT WHICH TIME THE SUPPLY AIR LAT AT TS-6 SHALL BE RESET DOWN TO 55 DEGREES F IN 1°F INCREMENTS EVERY 10 MINUTES (ADJUSTABLE). IF THE DISCHARGE AIR TEMPERATURE DROPS BELOW THE MINIMUM LIMIT, A LOW TEMPERATURE ALARM SHALL BE SENT TO THE BLC. IF THE DISCHARGE AIR TEMPERATURE RISES ABOVE THE

MAXIMUM LIMIT, A HIGH TEMPERATURE ALARM SHALL BE SENT TO THE BLC.

OUTSIDE/RETURN AIR DAMPER CONTROL:

1. THE RETURN AIR DAMPER SHALL BE OPENED 100% AND THE OUTSIDE AIR DAMPER SHALL MODULATE TO MAINTAIN THE OUTSIDE AIR VOLUME

SETPOINT AS SCHEDULED.

2. WHEN THE OUTSIDE AIR DAMPER IS OPEN 100% AND THE OUTSIDE AIR VOLUME IS BELOW SETPOINT, THE RA DAMPER SHALL MODULATE TO

MAINTAIN THE OUTSIDE AIR VOLUME SETPOINT.

3. AN ALARM SHALL BE GENERATED AT THE OPERATOR'S WORKSTATION IF THE OUTDOOR AIRFLOW VARIES BY MORE THAN 10% FROM SETPOINT

FOR MORE THAN 10 MINUTES (ADJUSTABLE).

OUTSIDE AIR DEMAND CONTROL VENTILATION:

1. SYSTEM SHALL UTILIZE A LOCAL CO2 SENSOR AS PART OF THE WEATHER STATION AND THE BLC SHALL MONITOR AND COMPARE THE

MEASURED SPACE CO2 TO THE SPACE CO2 CONCENTRATION SETPOINT (ADJUSTABLE).

2. IF THE CARBON DIOXIDE DIFFERENTIAL BETWEEN ANY SPACE EQUIPPED WITH A CO2 SENSOR AND THE OUTDOOR AIR SENSOR CO2 EXCEEDS 500 PPM (ADJUSTABLE) THE VAV TERMINAL UNIT SHALL MODULATE DAMPER OPEN TOWARDS MAXIMUM SETTING UNTIL CO2 SENSOR FALLS

BELOW 500 PPM (ADJUSTABLE) FOR 10 MINUTES (ADJUSTABLE).

3. IF ANY CARBON DIOXIDE DIFFERENTIAL RISES TO 700 PPM, THE AIR HANDLING UNIT SHALL SEND AN ALARM TO THE BLC AND THE AIR HANDLING UNIT OUTSIDE AIR DAMPER SHALL MODULATE OPEN TOWARDS MAXIMUM SETTING OR UNTIL OUTSIDE AIR DAMPER REACHES FULL OPEN POSITION. ONCE THE MEASURED CO2 CONCENTRATION FALLS BELOW A DIFFERENTIAL OF 700 PPM, THE OUTSIDE AIR DAMPER SHALL

MODULATE TOWARD MINIMUM OUTDOOR AIR POSITION SETPOINT.

LOW TEMPERATURE OPERATION / SHUTDOWN:

1. IF THE AIR TEMPERATURE AS SENSED BY TS-3 DROPS BELOW 55°F (ADJUSTABLE), THE PRE-HEAT COIL HEATING HOT WATER VALVE SHALL MODULATE

V-1 TO MAINTAIN A DISCHARGE TEMPERATURE OF 65°F.

2. IF THE AIR TEMPERATURE AS SENSED BY TS-4 DROPS BELOW 40°F (ADJUSTABLE) THE DEMAND CONTROL OPERATION SHALL BE OVERRIDDEN AND THE OUTSIDE AIR DAMPER SHALL MODULATE CLOSED TO MAINTAIN THE MIXED AIR TEMPERATURE LOW LIMIT SETPOINT. WHEN THE MIXED AIR TEMPERATURE RISES ABOVE THE MIXED AIR LOW LIMIT SETPOINT, DEMAND CONTROL OPERATION SHALL BE RESTORED.

3. IF THE AIR TEMPERATURE AS SENSED BY TS-4 FALLS BELOW 35°F (ADJUSTABLE),THE SUPPLY FAN SHALL SHUTDOWN, THE OUTSIDE AIR DAMPER SHALL CLOSE, THE CHILLED AND HEATING HOT WATER VALVES SHALL OPEN 100%, AND A CRITICAL ALARM SHALL INDICATE AT THE BLC.

ECONOMIZER:

1. WHEN THE OUTDOOR AIR SENSOR AS SENSED AT T-2 IS BELOW 60°F (ADJUSTABLE), THE SUPPLY AIR LAT SENSOR AT TS-6 SHALL MODULATE THE OUTSIDE AIR DAMPER D-1, THE RETURN AIR DAMPER D-2, THEN THE SUPPLY AIR LAT SENSOR TS-6 SHALL MODULATE CHILLED WATER VALVE V-2, ALL IN

SEQUENCE ON TEMPERATURE RISE, TO MAINTAIN 55°F (ADJUSTABLE) SUPPLY AIR LAT.

A. WHEN THE OUTDOOR AIR SENSOR AS SENSED AT T-2 IS ABOVE 65°F (ADJUSTABLE) AND FLOW IS SENSED BY CHILLED WATER FLOW SENSOR WSF-1, THE T-2 SHALL OPEN THE OUTSIDE AIR DAMPER D-1 TO MINIMUM POSITION OR AS DESCRIBED UNDER "OUTDOOR AIR/RETURN AIR DAMPER CONTROL" AND THE RETURN AIR DAMPER IN OPPOSITE UNISON AND THE SUPPLY AIR LAT SHALL MODULATE THE CHILLED WATER VALVE V-2 TO

MAINTAIN 55°F (ADJUSTABLE).

B. LOW LIMIT ECONOMIZER SHUTOFF SHALL BE THE WHEN MIXED AIR TEMPERATURE AT TS-3 IS BELOW 50°F AT THE REQUIRED OUTDOOR AIRFLOW.

C. HIGH LIMIT ECONOMIZER SHUTOFF SHALL BE BY ELECTRONIC ENTHALPY CONTROL WHEN THE OUTDOOR ENTHALPY EXCEEDS THE RETURN AIR

ENTHALPY AS DETERMINED BY THE OUTDOOR AIR SENSOR T-1 DIVIDED BY THE OUTDOOR HUMIDITY SENSOR H-2 AND THE RETURN AIR SENSOR

TS-7 DIVIDED BY THE RETURN AIR HUMIDITY H-1 RESPECTIVELY.

D. IF NO FLOW IS SENSED AT THE CHILLED WATER FLOW SENSOR WHEN OA TEMPERATURE IS ABOVE 65°F AND THE UNIT IS IN OCCUPIED MODE, AN

ALARM SHALL BE SENT TO THE BLC,

2. IF THE ENTHALPY OF THE SUPPLY AIR EXCEEDS 28 BTU PER POUND OF DRY AIR, AS SENSED BY SA LAT TEMP/SA HUMIDITY H-3, THE OUTDOOR AIR DAMPER SHALL MODULATE CLOSED AND SA LAT SHALL MODULATE THE PREHEAT VALVE V-1 TO MAINTAIN 55°F (ADJUSTABLE).

HUMIDITY CONTROL:

1. WHENEVER RETURN AIR RELATIVE HUMIDITY IS AT OR ABOVE 60% (ADJUSTABLE), AS SENSED BY H-1, THE UNIT SHALL MAINTAIN A COOLING COIL

LEAVING AIR TEMPERATURE OF 55°F (ADJUSTABLE).

2. IF THE VFD IS AT MINIMUM SPEED AND THE SPACE TEMPERATURE DROPS BELOW HEATING SETPOINT OF 70°F (ADJUSTABLE), THE VAV BOXES' HEATING HOT WATER VALVE SHALL MODULATE TO PREVENT OVERCOOLING OF THE SPACE AND MAINTAIN SPACE TEMPERATURE SETPOINT.

3. WHEN RETURN AIR RELATIVE HUMIDITY HAS DROPPED BACK TO 50% RH (ADJUSTABLE) FOR MORE THAN 30 MINUTES (ADJUSTABLE), THE SUPPLY AIR

DISCHARGE TEMPERATURE SHALL INCREASE TO SCHEDULED OPERATION SETPOINT.

4. WHEN RETURN AIR RELATIVE HUMIDITY AS SENSED AT H-1 IS BELOW 30% (ADJUSTABLE), STEAM HUMIDIFIER SH-111001 SHALL ENERGIZE AND H-1 SHALL MODULATE V-3 TO MAINTAIN 35% (ADJUSTABLE) RELATIVE HUMIDITY. WHEN THE RETURN AIR HUMIDITY IS ABOVE 50% FOR MORE THAN 30 MINUTES

(ADJUSTABLE), STEAM HUMIDIFIER SH-111001 SHALL DE-ENERGIZE.

5. WHEN THE SA FAN IS OFF OR A LOSS OF AIRFLOW IS SENSED DURING A CALL FOR HUMIDIFICATION, THE STEAM HUMIDIFIER SHALL DE-ENERGIZE AND

THE ISOLATION VALVE V-3 SHALL CLOSE AND AN ALARM SENT TO THE BLC.

UN-OCCUPIED MODE:

1. THE UNIT SUPPLY FAN SHALL DE-ENERGIZE, THE OA DAMPER SHALL CLOSE, THE RA DAMPER SHALL OPEN, AND ALL VAV BOXES SHALL FULLY OPEN.

2. IF SPACE TEMPERATURE DROPS BELOW UN-OCCUPIED WINTER SPACE TEMPERATURE SET-POINT 55°F (ADJUSTABLE) AS MEASURED BY THE SPACE

TEMPERATURE SENSOR, THE SUPPLY FAN SHALL START AT 60% FULL SPEED AND ALL VAV BOX TEMPERATURE CONTROL ALGORITHMS SHALL BE

ENABLED TO MAINTAIN THE WINTER ZONE TEMPERATURE SET-POINTS.

3. IF SPACE TEMPERATURE RISES ABOVE THE SUMMER UN-OCCUPIED TEMPERATURE SET-POINT 78°F (ADJUSTABLE) AS MEASURED BY THE SPACE TEMPERATURE SENSOR, THE SUPPLY FAN SHALL ENERGIZE, THE CHILLED WATER VALVE SHALL MODULATE TO MAINTAIN THE UN-OCCUPIED TEMPERATURE SET-POINT DOWNSTREAM OF THE COOLING COIL AND ENABLE VAV ZONE TEMPERATURE CONTROL ALGORITHMS.

4. INTERLOCKED EXHAUST FANS SHALL NOT OPERATE DURING UN-OCCUPIED MODE.

SMOKE DETECTION SHUTDOWN:

1. UPON A SIGNAL FROM THE ASSOCIATED, HARD WIRED, INTERLOCKED, SMOKE DETECTOR (FURNISHED AND WIRED BY DIVISION 28, MOUNTED BY DIVISION 23) THAT SMOKE IS DETECTED IN THE AIR STREAM, THE FIRE ALARM SYSTEM SHALL SHUT DOWN THE AHU AND INTERLOCKED FANS, AND AT THE SAME TIME THE SMOKE DETECTOR SIGNAL SHALL DISPLAY AN ALARM AT THE BLC THAT THE UNIT AND ASSOCIATED FANS WERE SHUTDOWN FOR

SMOKE DETECTION.

2. AHU AND INTERLOCKED FANS SHALL RESTART TO NORMAL SEQUENCE AND SMOKE DAMPERS SHALL OPEN WHEN FIRE ALARM CIRCUIT IS RESET.

GRAPHICAL USER INTERFACE:

1. PROVIDE A COMPLETE GRAPHIC DISPLAY OF THE SYSTEM AT THE BLC WEB INTERFACE. THE DISPLAY SHALL SHOW ALL POINTS WITH THEIR MEASURED VALUES OR STATES, WHICH SHALL BE UPDATED CONTINUOUSLY AND SHOWN AS CURRENT VALUE.

CO

MM

UN

IC

AT

IO

N/

DA

TA

IN

TE

RF

AC

E

TE

MP

ER

AT

UR

E

HU

MI

DI

TY

DI

FF

. P

RE

SS

UR

E

ST

AT

IC

P

RE

SS

UR

E

FR

EQ

UE

NC

Y

RE

AL

T

IM

E

EF

FI

CI

EN

CY

SE

TP

OI

NT

A

DJ

US

TM

EN

T

OP

T.

S

TA

RT

/ S

TO

P

RE

SE

T

RU

N

TI

ME

SE

T

BA

CK

SE

T

UP

MO

RN

IN

G

W

AR

M-

UP

GR

AP

HI

C

SYSTEM ANALOG SYSTEM FEATURES

INPUT/OUTPUT SUMMARY

SYSTEM

MIXED AIR

FILTERS

STATIC PRESSURE

REMARKSVARIABLE AIR VOLUME

AIR HANDLING SYSTEM

BLC, HOA

CS-1; AFM-1; SPS-1,2,3

D-2; TS-7; H-1

TS-4, 5, 6; H-3

D-1; AFS-1; T-2; H-2; CO2-2

SPS-1,2,3

SD-1,2 (INTERLOCK W/ FIRE ALARM SYSTEM)

SPACE

DPS-1,2,3

T-1; H-1; CO2-1

SEQUENCE OF OPERATION

(T-1) (CO2-2)

CO

TS-3

CH

W

R

CH

W

S

(V-2)

V-1,2,3; WFS-1,2

REFER TO MECH.

PLANS FOR 2-WAY OR

3-WAY VALVE TYPE

NO

S

SPACE SENSORS

INPUT OUTPUT

CF

M

SP

EE

D

VA

LV

E

AC

TU

AT

OR

DA

MP

ER

A

CT

UA

TO

R

O

PE

N

DI

FF

. P

RE

SS

UR

E

SW

IT

CH

ST

AT

US

CU

RR

EN

T

RE

LA

Y

FL

OW

S W

IT

CH

ON

-O

FF

SP

EE

D

SI

GN

AL

EL

EC

. H

EA

T

ST

AG

ES

INPUT OUTPUT

DA

MP

ER

A

CT

UA

TO

R

PR

OO

F

CR

IT

IC

AL

DIGITAL

VA

LV

E

AC

TU

AT

OR

SP

EE

D

SW

IT

CH

DI

RT

Y

FI

LT

ER

HI

GH

-L

OW

V

AL

UE

HI

GH

/LO

W

P

RE

SS

UR

E

CO

2 L

EV

EL

TI

ME

S

CH

ED

UL

E / T

RE

ND

SUPPLY FAN

RETURN AIR

SUPPLY AIR

OUTSIDE AIR

COILS

ALARMS PROGRAMS

DUCT SMOKE DETECTORS

(WFS-1)

PREHEAT

COIL

(T S-

4)

SA DUCT SMOKE

DETECTOR

(T-2) (H-2)

OUTDOOR SENSORS

NOTE: REFER TO MECH.

PLANS FOR LOCATIONS.

NOTE: FACILITY SHALL HAVE ONE

OUTDOOR AIR WEATHER STATION

(CS-1)

HIGH LIMIT STATIC

PRESSURE SENSOR

(S

PS

-2

(H

IG

H-

LIM

IT

(CO2-1)

CO2

BACKDRAFT DAMPER

24VAC

NO

(D-2)

(S

PS

-1

LOW LIMIT STATIC

PRESSURE SENSOR

RARELIEF

VFD

FROM FAS

(CS-2)

HW

R

HW

S

(V-1)

REFER TO MECH.

PLANS FOR 2-WAY OR

3-WAY VALVE TYPE

NC

(WFS-1)

RELIEF AIR D-1

S

RA DUCT SMOKE DETECTOR

RF-121001

SA FAN ARRAY (TYP OF 4)

(T S-

7)

(H -1

(AFM-2)

(AFM-1)

BACKDRAFT DAMPER

(DPS-3)

FINAL

FILTERS

(DPS-2)

AFTER-

FILTERS

(H -3

ST

(V-3)

NC

(S

PS

-4

RELIEF FAN CS-2; AFM-2; SPS-4

(S D-

2)

(S D-

1)

SA

F

(A

FS

-1

REHEAT

COIL

GENERAL:

1. TERMINAL UNIT SHALL BE EQUIPPED WITH A TERMINAL UNIT MOUNTED CONTROLLER.

2. ALL CONTROLS SHALL BE AUTOMATIC AND ALL SETPOINTS SHALL BE ADJUSTABLE.

OPERATION:

1. SET POINTS SHALL BE AS FOLLOWS:

A. COOLING: 72°F (ADJUSTABLE)

B. HEATING: 68°F (ADJUSTABLE)

C. A DEADBAND OF 4°F BETWEEN HEATING AND COOLING SET POINTS SHALL BE MAINTAINED.

2. UPON FALL IN SPACE TEMPERATURE THE TERMINAL UNIT DAMPER WILL MODULATE TO MINIMUM POSITION.

3. ONCE THE DAMPER REACHES MINIMUM POSITION, THE SPACE TEMPERATURE SHALL BE ALLOWED TO DROP THROUGH A DEADBAND.

4. UPON FURTHER DROP IN SPACE TEMPERATURE, THE DAMPER SHALL OPEN TO HEATING POSITION (AS INDICATED IN SCHEDULE) AND

THE HEATING HOT WATER VALVE SHALL MODULATE TO MAINTAIN SET POINT ± 0.5°F. THE ADJUSTABLE TOLERANCE OF ± 0.5°F HAS

BEEN SELECTED TO PREVENT VALVE HUNTING.

5. THE REVERSE SHALL OCCUR ON THE RISE IN SPACE TEMPERATURE.

6. FOR TERMINAL UNITS THAT SERVE SPACES EQUIPPED WITH A CARBON DIOXIDE (CO2) SENSOR, IF THE DIFFERENTIAL BETWEEN ANY

SPACE CO2 AND THE OUTDOOR AIR SENSOR CO2 EXCEEDS 500 PPM (ADJUSTABLE), THE VAV TERMINAL UNIT CONTROLLER SHALL MODULATE DAMPER OPEN TOWARDS MAXIMUM SETTING UNTIL CO2 SENSOR FALLS BELOW 500 PPM (ADJUSTABLE) FOR 10 MINUTES (ADJUSTABLE).IF THE CO2 DIFFERENTIAL RISES TO 700 PPM, THE TERMINAL UNIT CONTROLLER SHALL DISPLAY A NOTIFICATION AT THE

BLC THAT THE AIR HANDLING UNIT IS IN DEMAND CONTROL VENTILATION MODE.

OCCUPIED/UNOCCUPIED MODES:

1. EACH TERMINAL UNIT SHALL HAVE THE OPTION FOR OCCUPIED AND UNOCCUPIED MODES WITHIN THE UNIT CONTROLLER.

OCCUPIED/UNOCCUPIED MODES SHALL HAVE UPPER AND LOWER SPACE TEMPERATURE SETPOINT LIMITS THAT SHALL BE PROGRAMMABLE THROUGH THE BLC WEB INTERFACE. REFER TO AHU-111001 & EF-121001 UN-OCCUPIED MODE SEQUENCE.

(D -1

SA

HH

W

R

HH

W

S

(T S-

1)

SEQUENCE OF OPERATION

(V-1)

REFER TO DRAWINGS FOR 2-WAY

OR 3-WAY VALVE TYPE

NO

CO

MM

UN

IC

AT

IN

TE

RF

AC

E

TE

MP

ER

AT

UR

E

HU

MI

DI

TY

DI

FF

. P

RE

SS

UR

E

ST

AT

IC

P

RE

SS

UR

E

FR

EQ

UE

NC

Y

RE

AL

T

IM

E

EF

FI

CI

EN

CY

SE

TP

OI

NT

A

DJ

US

TM

EN

T

OP

T.

S

TA

RT

/ S

TO

P

RE

SE

T

RU

N

TI

ME

SE

T

BA

CK

SE

T

UP

MO

RN

IN

G

W

AR

M-

UP

GR

AP

HI

C

SYSTEM ANALOG SYSTEM FEATURES

INPUT/OUTPUT SUMMARY

TERMINAL UNIT CONTROLLER

REMARKSVARIABLE AIR VOLUME

TERMINAL UNIT

TS-1, AFS-1, D-1

V-1, WFS-1

INPUT OUTPUT

FL

OW

R

AT

E

SP

EE

D

VA

LV

E

AC

TU

AT

OR

DA

MP

ER

A

CT

UA

TO

R

DI

FF

. P

RE

SS

UR

E

SW

IT

CH

ST

AT

US

CU

RR

EN

T

RE

LA

Y

FL

OW

S W

IT

CH

ON

-O

FF

SP

EE

D

SI

GN

AL

EL

EC

. H

EA

T

ST

AG

ES

INPUT OUTPUT

DA

MP

ER

A

CT

UA

TO

R

PR

OO

F

CO

MM

UN

IC

AT

IO

N

FA

ILU

RE

DIGITAL

VA

LV

E

AC

TU

AT

OR

SP

EE

D

SW

IT

CH

DI

RT

Y

FI

LT

ER

HI

GH

-L

OW

V

AL

UE

HI

GH

/LO

W

P

RE

SS

UR

E

CO

2 L

EV

EL

TI

ME

S

CH

ED

UL

E / T

RE

ND

SUPPLY AIR

REHEAT COIL

ALARMS PROGRAMS

SPACE

(T-1)

SPACE SENSORS

NOTE: REFER TO MECH.

PLANS FOR LOCATIONS.

(WFS-1)

T-1

(CO2-1)

CO2

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

BI

M

- C on st ru ct

R ep la ce m en t O ut pa tie nt C lin ic

/0

C on st . R ep la ce . O ut pa tie nt

C lin ic

R

.rv t

5/ 4/

:1

1:

P M

M-701

MECHANICAL CONTROLS REPLACEMENT OUTPATIENT

CLINIC DESIGN AT COAST

GUARD CAPE COD

JOINT BASE CAPE COD, BARNSTABLE MA

650-318

BUILDING 1

02/10/2023 JFR JJA

100% CONSTRUCTION

DOCUMENTS

N.T.S.

BACNET SYSTEM ARCHITECTURE1

DRAWING NOTES:

1. CONTROL SYSTEM ARCHITECTURE SHOWN IS FOR DESIGN INTENT OF CONTROL SYSTEM. CONTROLS

CONTRACTOR SHALL ALTER SYSTEM ARCHITECTURE AS REQUIRED TO BEST FIT NEW CONTROL

SYSTEM AND TIE IN TO EXISTING SYSTEM.

2. PROVIDE LAMINATED COPIES OF ALL CONTROL DRAWINGS WITHIN EACH CONTROL PANEL.

3. CONTRACTOR IS RESPONSIBLE FOR COMPLETE AND OPERATIONAL DDC CONTROL SYSTEM.

SEQUENCE OF OPERATIONS AS SPECIFIED SHALL BE PROVIDED WITH ALL SYSTEM POINTS AND

INTEGRATED WITH ALL CONTROLS AND EQUIPMENT. CONTRACTOR IS RESPONSIBLE FOR PROVIDING

ALL SOFTWARE AND HARDWARE REQUIRED FOR ALL MECHANICAL EQUIPMENT TO BE CONTROLLED

AND MONITORED AS SPECIFIED IN THE SEQUENCE OF OPERATIONS.

N.T.S.

AHU-111001 & RF-121001 CONTROL DIAGRAM3 N.T.S.

VARIABLE AIR VOLUME TERMINAL UNIT CONTROL DIAGRAM2

CODED NOTES:

PLUMBING GAS WATER HEATER SHALL BE INTEGRATED WITH THE CONTROL SYSTEM TO INDICATE

STATUS AND HOT WATER SUPPLY TEMPERATURE.

PLUMBING HOT WATER RECIRCULATION PUMP SHALL BE INTEGRATED WITH THE CONTROL SYSTEM TO

INDICATE STATUS.

EXHAUST FAN SHALL BE INTEGRATED WITH THE CONTROL SYSTEM TO INDICATE STATUS.

GENERAL:

1. THE CHILLED WATER PLANT CONSISTS OF ONE (1) 80 TON AIR COOLED CHILLER WITH TWO (2) REDUNDANT CHILLED WATER PUMPS, EACH SERVED BY A SEPARATE VFD.

2. A 2-WAY MODULATING BYPASS VALVE (V-1) SHALL BE PROVIDED.

3. A DIRECT DIGITAL CONTROL (DDC) SYSTEM SHALL BE PROVIDED THAT INTERFACES WITH THE CHILLER FACTORY CONTROLS TO PROVIDE

FULL REMOTE CONTROL AND ALL INFORMATION FOR MONITORING AVAILABLE IN THE CHILLER CONTROLLER.

SYSTEM OPERATION:

1. EACH PUMP IS SIZED FOR THE FULL FLOW RATE TO GIVE THE PUMPING SYSTEM N+1 REDUNDANCY. THEREFORE, ONLY ONE PUMP SHALL

OPERATE AT A TIME. PUMP OPERATION SHALL BE AS FOLLOWS:

A. WEEK ONE: CHWP-111001 SHALL BE IN OPERATION AND CHWP-111002 SHALL BE DE-ENERGIZED (ADJUSTABLE).

B. WEEK TWO: CHWP-111002 SHALL BE IN OPERATION AND CHWP-111001 SHALL BE DE-ENERGIZED (ADJUSTABLE).

C. IF ANY ONE PUMP FAILS, AN ALARM SHALL BE SENT TO THE BUILDING LEVEL CONTROLLER (BLC), THE PUMP SHALL DE-ENERGIZE, AND THE NEXT PUMP SHALL ENERGIZE.

D. IF THE SYSTEM FAILS TO MEET CHILLED WATER SETPOINT, AN ALARM SHALL BE SENT TO BLC.

E. PUMP CHANGEOVER SHALL OCCUR AUTOMATICALLY THROUGH THE DDC SYSTEM.

2. WHENEVER THERE IS A REQUIREMENT FOR CHILLED WATER, THE CHILLED WATER SYSTEM SHALL BE INDEXED TO OPERATE.

3. UPON A REQUEST FROM THE DDC SYSTEM, THE CHILLER AND PUMP FOR THAT WEEK (ADJUSTABLE) SHALL BE ENERGIZED.

4. WHEN ALL CHILLED WATER VALVES ARE LESS THAN 85% OPEN, THE CHILLED WATER SYSTEM DIFFERENTIAL PRESSURE (DP) SETPOINT

WILL BE LOWERED BY 0.1 PSIG (ADJ.) OF THE CURRENT CHILLED WATER DP SETPOINT. THIS OCCURS EVERY 5 MINUTES UNTIL AT LEAST ONE VALVE IS MORE THAN 85% OPEN, OR IF THE SETPOINT IS EQUAL TO THE MIN. CHILLED WATER DP SETPOINT, OR IF THE PUMP VFD IS

AT A MIN. SPEED SETTING 22 HZ (ADJUSTABLE).

5. WHEN ANY CHILLED WATER VALVE IS MORE THAN 95% OPEN, THE CHILLED WATER DP SETPOINT WILL INCREASE BY 0.1 PSIG (ADJ.) OF THE CURRENT CHILLED WATER DP SETPOINT. THIS OCCURS EVERY 5 MINUTES UNTIL NO VALVE IS MORE THAN 95% OPEN, OR IF THE CHILLED WATER DP SETPOINT HAS RISEN TO THE SYSTEMS MAX. SETTING, OR IF THE PUMP'S VFD IS AT THE MAX. SETTING 60 HZ

(ADJUSTABLE).

6. ONCE THE PUMP AND CHILLER PROVE FLOW VIA DIFFERENTIAL PRESSURE TRANSMITTERS, THE CHILLERS SHALL BE RELEASED TO SEQUENCE. CONTINUOUSLY MONITOR THE PRESSURE DIFFERENTIAL AND PUMP DIFFERENTIAL PRESSURE TRANSMITTERS. CHILLERS

SHALL NOT BE CAPABLE OF OPERATING WITHOUT PROOF OF FLOW.

7. UPON A REQUEST FOR CHILLED WATER, THE DDC SYSTEM SHALL ENERGIZE THE CHILLED WATER PUMP SCHEDULED FOR THAT WEEK (ADJUSTABLE). UPON PROOF OF PRIMARY FLOW, THE DDC SYSTEM SHALL THEN ENERGIZE THE CHILLER THROUGH ITS LOCAL CONTROL

PANEL.

8. AFTER ENABLING THE LOCAL CHILLER PANEL, THE DDC SYSTEM SHALL MONITOR THE CHILLER RUNNING LOAD AMPS FOR PROOF OF

OPERATION.

9. THE LOCAL CHILLER CONTROL PANEL SHALL THEN CYCLE THE CHILLERS' COMPRESSORS IN SEQUENCE TO MAINTAIN THE EVAPORATOR LEAVING WATER TEMPERATURE AND RUNNING LOAD, AS RESET BY RESET, DEMAND LIMITING AND OTHER APPROPRIATE PROGRAMS.

CONTROLS:

1. THE LOCAL CHILLER OPERATION SHALL BE CONTROLLED BY AN INTELLIGENT MICRO-PROCESSOR BASED CONTROLLER IN COMMUNICATION WITH THE DDC SYSTEM VIA BACNET, HARDWIRED INDIVIDUAL POINTS, OR OTHERWISE AS REQUIRED TO BE

COMPATIBLE WITH THE CONTROLS INTERFACE(S) OF THE CHILLERS FURNISHED.

2. ALL OPERATIONAL DATA SHALL READ-OUT, AND BE OPERATOR MODIFIABLE THROUGH THE DDC WEB-BASED INTERFACE.

3. PROVIDE THE STATUS DISPLAY REPORTS, AND ALARM PARAMETERS AS SCHEDULED HEREIN.

4. THE CHILLER PLANT CONTROL PROGRAM SHALL BE FULLY EDITABLE AND SET-UP VIA POINT AND CLICK ON A STANDARD COMPUTER

SCREEN. IT SHALL NOT REQUIRE SPECIAL SOFTWARE TOOLS OR A TECHNICIAN TO OPERATE AND MODIFY CHILLER SEQUENCING

CONTROL.

5. THE CHILLER SEQUENCING SOFTWARE SHALL PERFORM THE FOLLOWING CONTROL STRATEGIES:

A. CHILLER PLANT SYSTEM SCHEDULING

B. CHILLER SEQUENCING

C. COLOR GRAPHIC BASED CHILLER PLANT STATUS SCREENS

D. COLOR GRAPHIC BASED CHILLER STATUS SCREENS

E. SYSTEM AND CHILLER DIAGNOSTIC MESSAGES

F. SYSTEM AND CHILLER REPORTS

6. CHILLER SEQUENCING - THE CHILLER SEQUENCING SOFTWARE WILL START AND STOP SYSTEM WATER PUMP AND CHILLER BASED UPON

SYSTEM LOAD.

A. WHEN THE CHILLED WATER SYSTEM IS ENABLED, THE CHILLER SYSTEM CONTROL WILL START THE SYSTEM CHILLED WATER PUMP

AND PROVE FLOW THROUGH THE EVAPORATOR.

7. ADDITIONAL CHILLER SEQUENCING FOR VARIABLE PRIMARY FLOW CHILLED WATER SYSTEMS:

A. THE SYSTEM CHILLED WATER SUPPLY SETPOINT SHALL BE 42°F (ADJUSTABLE). ALTERNATIVELY, THE CHILLED WATER SUPPLY TEMPERATURE SETPOINT SHALL INCREASE UP TO 44°F MAX. WHEN THE AIR HANDLING UNIT CHILLED WATER CONTROL VALVE IS < 50% FOR 10 MINUTES (ADJUSTABLE). THE CHILLED WATER SUPPLY TEMPERATURE SETPOINT SHALL NOT EXCEED 44°F. IF THE AIR HANDLING UNIT CHILLED WATER CONTROL VALVE ≥ 50% OPEN FOR 10 MINUTES (ADJUSTABLE), THE CHILLED WATER SUPPLY

SETPOINT SHALL RETURN TO THE CHILLED WATER SETPOINT OF 42°F (ADJUSTABLE).

B. THE CHILLER SEQUENCING SOFTWARE SHALL STOP THE CHILLER WHENEVER THERE IS NO CHILLED WATER SYSTEM DEMAND FOR

30 MINUTES (ADJUSTABLE).

CHILLER STATUS REPORTS:

1. PROVIDE AN OPERATING STATUS REPORT FOR EACH CHILLER. THE REPORT(S) SHALL PROVIDE THE PRESENT STATUS FOR THE FOLLOWING INFORMATION TO PROVIDE THE OPERATOR WITH CRITICAL CHILLER OPERATING DATA.

A. COMPRESSOR ON/OFF STATUS.

B. COMPRESSOR STARTS/RUN HOURS

C. COMPRESSOR PHASE 1/2/3 PERCENT RLA - SEPARATE FOR EACH COMPRESSOR

D. COMPRESSOR CURRENT DRAW - RLA PERCENT

E. ACTIVE CHILLER DIAGNOSTICS OR ALARMS

F. LEAVING CHILLED WATER TEMPERATURE

G. ENTERING CHILLED WATER TEMPERATURE

H. CHILLED WATER SETPOINT.

I. REFRIGERANT TEMPERATURE EVAPORATOR/CONDENSER - SEPARATE FOR EACH CIRCUIT

J. OPERATING MODE

K. CHILLER MODEL AND SERIAL NUMBER

L. CHILLED WATER CHILLER LOAD TRENDING: THE DDC SYSTEM SHALL CONTINUOUSLY MEASURE THE CHILLED WATER SUPPLY FLOW

RATE, AND THE CHWS AND CHWR TEMPERATURES, AND CALCULATE THE TOTAL BUILDING COOLING LOAD USING THE FORMULA

BELOW:

a. BUILDING LOAD (BTUH) = FLOW (GPM) X ((CHWS TEMP -CHWR TEMP) (DEG F) X 500).

DIAGNOSTICS/PROTECTION:

1. THE DDC SYSTEM SHALL BE ABLE TO ALARM FROM ALL SENSED POINTS AND DIAGNOSTIC ALARMS SENSED BY THE CHILLER

CONTROLLER.

A. ALARM LIMITS SHALL BE DESIGNATED FOR ALL SENSED POINTS.

B. SENSED DIAGNOSTIC POINTS SHALL INCLUDE THE FOLLOWING AT A MINIMUM:

C. SYSTEM CHILLED WATER SUPPLY TEMPERATURE

D. SYSTEM CHILLED WATER RETURN TEMPERATURE

CHILLER FREEZE PROTECTION:

1. WHEN OUTDOOR AIR TEMPERATURE IS 33 °F (ADJ.) OR BELOW THE CHILLED WATER PUMPS SHALL CYCLE AT MINIMUM FLOW AND THE HEAT TRACE SYSTEM SHALL ENERGIZE TO MAINTAIN WATER TEMPERATURE TO AVOID EVAPORATOR FREEZE. IF THE CHILLED WATER

TEMPERATURE FALLS BELOW 39 °F (ADJ.), AN ALARM SHALL BE SENT TO THE ECC.

PRIMARY VARIABLE SPEED CHILLED WATER CIRCULATION PUMPS STAGING CONTROL:

1. VARIABLE CHILLED WATER PUMP CONTROL: THE DDC SYSTEM SHALL CONTROL THE SPEED OF THE LEAD PRIMARY CHILLED WATER PUMP THROUGH THE VFD TO MAINTAIN 10 PSIG (ADJUSTABLE) DIFFERENTIAL PRESSURE AT THE DP TRANSMITTER LOCATED AT THE END OF THE CHILLED WATER LOOP. DP SETPOINT SHALL AUTOMATICALLY ADJUST TO MAINTAIN CHW VALVE POSITION (95% OF ALL CHILLED WATER VALVES SHALL BE LESS THAN 100% OPEN). UNDER NO CIRCUMSTANCE, HOWEVER, WILL THE VARIABLE FREQUENCY DRIVE APPLIED TO CHILLED WATER PUMP MOTOR BE ALLOWED TO EXCEED THE PUMP MOTOR FLA (FULL LOAD AMPS) AT ANY TIME. EACH VFD SHALL BE PROGRAMMED TO ACHIEVE THE FLA OF EACH MOTOR. ON A FAILURE OF THE PRIMARY PUMP DEDICATED TO A CHILLER, THE DDC SYSTEM SHALL AUTOMATICALLY SHUTDOWN ASSOCIATED CHILLER AND BRING ON THE NEXT SEQUENCED PUMP AND CHILLER AND SHALL CONTROL THE SPEED OF THE PUMP TO MAINTAIN THE DIFFERENTIAL PRESSURE AT THE END OF THE CHILLED WATER LOOP, AND

SEND AN ALARM OF THE FAILURE.

2. UNDER PROGRAM CONTROL, EACH CHILLED WATER PUMP VFD WILL BE AUTOMATICALLY STARTED AND STOPPED VIA A DDC COMMUNICATION BUS WITH AN ASSOCIATED DDC AO. A CURRENT SWITCH, INSTALLED AT EACH PUMP VFD, WILL PROVIDE ON/OFF

STATUS TO THE DDC AT ALL TIMES.

3. BASED UPON PUMP SPEED, PUMPS WILL BE STAGED ON AND OFF BY DDC TO ACCOMMODATE THE BUILDING FLOW RATE REQUIREMENTS UNDER THE FOLLOWING DDC OPERATIONAL SEQUENCES. UNDER AUTOMATIC CONTROL, SOFTWARE SUBROUTINES, USING "IF/THEN"

LOGIC STATEMENTS, WILL PROVIDE FOR "ON/OFF" STAGING AS DESCRIBED.

4. IF DDC SHOULD ATTEMPT TO AUTOMATICALLY START A PUMP AND THE ASSOCIATED SENSOR CAN NOT PROVIDE A SUCCESSFUL START, AN ALARM WILL BE ROUTED TO OPERATOR AT THE OWS (OPERATOR WORK STATION) INDICATING IMMEDIATE PUMP ATTENTION IS

NECESSARY AND THE NEXT OPERATIONAL SEQUENCE WILL THEN IMMEDIATELY BE ACTIVATED.

5. IF DDC SHOULD ATTEMPT TO AUTOMATICALLY STOP A PUMP AND THE ASSOCIATED CHILLER CAN NOT PROVIDE A SUCCESSFUL STOP, AN ALARM WILL BE ROUTED TO OPERATOR AT THE OWS INDICATING IMMEDIATE PUMP ATTENTION IS NECESSARY.

CHWP-111001

CHWP-111002

BT-111001 FM

AS-111001

ET-111001

CHWS MAIN

CHWR MAIN

SEQUENCE OF OPERATION

CH-111001

AHU-111001

FLOW METER, TYP.

NO

NO

NO

CHWS

CH

W

R

CH

W

R

CHWR

CHWS

BYPASS VAVLE

COMPRESSOR 1

CHILLED

WATER BTU

METER

BTU METER BASIS OF DESIGN:

ONICON SYSTEM-10 WITH

MATCHED TEMPERATURE

SENSORS AND FLOW METER.

BACNET INTERFACE WITH

METERING STATION.

(TT-4)

(WFS-2)

(WFS-1)

COMPRESSOR 2

COMPRESSOR 4

COMPRESSOR 3

NOTE: QUANTITY OF

COMPRESSORS MAY

VARY BASED ON

MANUFACTURER

(TT-1)

(TT-2)

(V-1)

(DPS-1)

(TT-3)

FM

VFD

VFD

CO

MM

UN

IC

AT

IN

TE

RF

AC

E

TE

MP

ER

AT

UR

E

HU

MI

DI

TY

DI

FF

. P

RE

SS

UR

E

ST

AT

IC

P

RE

SS

UR

E

FR

EQ

UE

NC

Y

RE

AL

T

IM

E

EF

FI

CI

EN

CY

SE

TP

OI

NT

A

DJ

US

TM

EN

T

OP

T.

S

TA

RT

/ S

TO

P

RE

SE

T

RU

N

TI

ME

SE

T

BA

CK

SE

T

UP

MO

RN

IN

G

W

AR

M-

UP

GR

AP

HI

C

SYSTEM ANALOG SYSTEM FEATURES

INPUT/OUTPUT SUMMARY

REMARKSCHILLED WATER

SYSTEM

TT-2, 3; DPS-1

TT-1, 4; WFS-1, 2; COMPRESSORS, CONDENSER FANS, ETC.

CHWS & R FLOW RATES

V-1

INPUT OUTPUT

FL

OW

R

AT

E

SP

EE

D

VA

LV

E

AC

TU

AT

OR

DA

MP

ER

A

CT

UA

TO

R

DI

FF

. P

RE

SS

UR

E

SW

IT

CH

ST

AT

US

CU

RR

EN

T

RE

LA

Y

FL

OW

S W

IT

CH

ON

-O

FF

SP

EE

D

SI

GN

AL

EL

EC

. H

EA

T

ST

AG

ES

INPUT OUTPUT

DA

MP

ER

A

CT

UA

TO

R

PR

OO

F

CO

MM

UN

IC

AT

IO

N

FA

ILU

RE

DIGITAL

VA

LV

E

AC

TU

AT

OR

SP

EE

D

SW

IT

CH

DI

RT

Y

FI

LT

ER

HI

GH

-L

OW

V

AL

UE

HI

GH

/LO

W

P

RE

SS

UR

E

CO

2 L

EV

EL

TI

ME

S

CH

ED

UL

E / T

RE

ND

ALARMS PROGRAMS

CH-111001

CHW FLOW RATES

BYPASS

BTU METER

PUMP VFDs

CHW SYSTEM

C. THE CHILLER SEQUENCING SOFTWARE SHALL NOT SHUTDOWN A CHILLER PUMP UNTIL ALL CHILLER COMPRESSORS ARE PROVEN

OFF.

D. FOR SYSTEMS USING AIR-COOLED CHILLERS, THE CHILLER SHALL BE ABLE TO CALL FOR ITS EVAPORATOR…