Attachment 10.1 Aboveground Storage Tank Inspection Form 372.xlsx

XLSX spreadsheet 15 KB Posted

Attached to
Facility Maintenance Services at Fort McCoy, WI
Solicitation number
W912ES22R0011
Issued by

About this file

This document contains a monthly aboveground storage tank inspection form and related corrective action instructions for Fort McCoy in Wisconsin. The inspection form is a table that includes checks for leaks, corrosion, venting issues, caps/covers, secondary containment integrity, presence of debris or oil, and alarm functioning on leak detection systems. The corrective action instructions provide guidance on addressing issues such as leaks, corrosion, missing vents or caps, debris or oil in containment areas, and alarm activation. Contractors must maintain inspection records for three years and report any issues to the Fort McCoy DPW Environmental department along with details of corrective measures taken.

A related federal contract opportunity involves providing facility maintenance services at Fort McCoy. The contractor will perform maintenance, repairs, and preventive maintenance to keep facilities, utilities, equipment, and areas in full working capacity and meeting intended purposes. This includes maintaining, repairing, and installing all facility and building components, devices, equipment, and associated subsystems according to manufacturer manuals. The solicitation is issued by the Department of the Army Corps of Engineers District in St. Paul, Minnesota.

View the file

Other files

File Type Posted
Amendment 0003 .pdf PDF
Amendment 0002.pdf PDF
Amendment 0002 Site Visit List .pdf PDF
Amendment 0001.pdf PDF
CBA Fort McCoy July 1 2021 - June 30 2024 .pdf PDF
Attachment 9 Available Automation Equipment.xlsx XLSX spreadsheet
Attachment 3.7 Cathodic Protection.xlsx XLSX spreadsheet
Attachment 10 Form TR-WM-118.pdf PDF
Attachment 7 Government Furnished Facilities.xlsx XLSX spreadsheet
Attachment 3.3 Fire Suppression (Wet Pipe).xlsx XLSX spreadsheet
Attachment 3.1 Fire Suppression (Ansul-Chemical).xlsx XLSX spreadsheet
Attachment 6 Historical Workload Service Orders.xlsx XLSX spreadsheet
Attachment 8 Facility Maintenance Repair ATOPSEC Cover Sheet.pdf PDF
Attachment 3.8 Cathodic Protection WWTP.pdf PDF
Attachment 4 Ice Melt Monthly Report.xlsx XLSX spreadsheet
Attachment 3.11 Water Meters Calibration.xlsx XLSX spreadsheet
Attachment 13 Facility Activation.xlsx XLSX spreadsheet
Attachment 1 Performance Requirements Summary.docx DOCX document
Blank Price Schedule - FM Services 15 FEB 2022.xlsx XLSX spreadsheet
Attachment 15 DD Form 254.pdf PDF
Attachment 3.5 Fire Alarm System.docx DOCX document
Attachment 16 Wisconsin HVAC Qualifier Application.pdf PDF
Attachment 18 Water System Valves Lines and Hydrants.pdf PDF
Attachment 21 FMF452 Installation Access Pass Request .pdf PDF
Attachment 3.4 Fire Suppression (Dry Pipe).xlsx XLSX spreadsheet
Attachment 20 FMF451 Installation Access NCIC-III Check Request .pdf PDF
Attachment 3.10 Runway Lighting.pdf PDF
Attachment 3.2 Fire Suppression (Kitchen Hood Cleaning).xlsx XLSX spreadsheet
Attachment 2 Fort McCoy Base Data.xlsx XLSX spreadsheet
Solicitation Fort McCoy Fac Maint Services .pdf PDF
Attachment 12 Generator Log.xlsx XLSX spreadsheet
Attachment 3.6 Earth Bond Testing.xlsx XLSX spreadsheet
Attachment 3.9 Elevators and Lifts.xlsx XLSX spreadsheet
Attachment 14 Facility Deactivation.docx DOCX document
Attachment 3.7.1 TR-WM-141 UST Corrosion Protection Test Form.pdf PDF
Attachment 19 POL System Block Book.pdf PDF
Past Performance Questionnaire.pdf PDF
Attachment 6.1 Historical Workload Service Orders.xlsx XLSX spreadsheet
Attachment 11 Facility Standards.docx DOCX document
Attachment 3 PM Task and Frequency Chart.xlsx XLSX spreadsheet
Show all 40

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Table 1

MONTHLY ABOVEGROUND STORAGE TANK INSPECTION FORM

Prescribing Directive: Fort McCoy Pamphlet 420-28

Date
General Tank ConditionPipe / Hose / NozzleSecondary Containment (Double Walled or Single Walled with Vault)Leak Detection System (if applicable)Other observations or corrective measures taken
LocationInspected byLiquid
Level1. Any signs of leaks?2. Any rusting or pitting?3. Normal or emergency vents missing or nonfunctioning?4. Covers and caps missing or open?5. Any signs of leaks?6. Any rusting, pitting, or excessive
wear?7. Any visible damage?8. Any water or debris present?9. Any visible POL?10. Alarming?
Y / NY / NY / NY / NY / NY / NY / NY / NY / NY / N
Y / NY / NY / NY / NY / NY / NY / NY / NY / NY / N
Y / NY / NY / NY / NY / NY / NY / NY / NY / NY / N
Y / NY / NY / NY / NY / NY / NY / NY / NY / NY / N
Y / NY / NY / NY / NY / NY / NY / NY / NY / NY / N
Y / NY / NY / NY / NY / NY / NY / NY / NY / NY / N
Y / NY / NY / NY / NY / NY / NY / NY / NY / NY / N
Y / NY / NY / NY / NY / NY / NY / NY / NY / NY / N
Y / NY / NY / NY / NY / NY / NY / NY / NY / NY / N
Y / NY / NY / NY / NY / NY / NY / NY / NY / NY / N
Y / NY / NY / NY / NY / NY / NY / NY / NY / NY / N
Y / NY / NY / NY / NY / NY / NY / NY / NY / NY / N
NOTE: 1. Make sure to inspect all around the tank, piping, and secondary containment.

2. See page two (2) if you answered YES to any of the above questions.

3. Maintain a copy for three (3) years.

FORT MCCOY FORM 372 OCT 2013
Previous versions of this form are obsolete
PE v1.00
MONTHLY ABOVEGROUND STORAGE TANK INSPECTION FORM

Prescribing Directive: Fort McCoy Pamphlet 420-28

CORRECTIVE ACTIONS TO BE TAKEN IF YOU ANSWERED YES TO ANY OF THE QUESTIONS ON PAGE ONE
1.Contain leaked material with spill pads or by other appropriate means. If greater than a gallon is spilled call 911 if in the Cantonment area or call Range Control (388

-4848) if outside the Cantonment area. If less than a gallon clean up and dispose of material properly. If possible fix the leak or submit a work order to get the leak fixed also notify DPW Environmental (2-6501) of the leak.

2.If individual rust or pit marks are larger than a quarter or several marks cover an area larger than your hand submit a work order to repair the corrosion. Also notify DPW Environmental (2-6501) of the tank condition and corrective measures taken.
3.All tanks are required to have two vents for the primary tank and two vents for the secondary tank (if double walled). If the tank does not have the appropriate vent system submit a work order and also notify DPW Environmental (2-6501) of the corrective measures taken.
4.The fill cap should remain closed and secured when not in use. If a cap is missing a purchase request or work order should be submitted to obtain a new cap.
5.Contain leaked material with spill pads or by other appropriate means. If greater than a gallon is spilled call 911 if in the Cantonment area or call Range Control (388

-4848) if outside the Cantonment area. If less than a gallon clean up and dispose of material properly. If possible fix the leak or submit a work order to get the leak fixed also notify DPW Environmental (2-6501) of the leak.

6.If rust or pit marks are larger than a quarter or several marks cover an area larger than your hand submit a work order. Also notify DPW Environmental (2-6501) of the tank condition and corrective measures taken.
7.Cracks in the secondary containment may reduce the ability of the structure to contain any leaks or spills. Contact DPW Environmental (2-6501) to determine if corrective actions are necessary.
8a. (Single Walled)The secondary containment should be free of debris and water to maximize the containment capacity. Remove any debris that has collected in the containment area. If water is present check if there is a POL odor or sheen on the water. Contact DPW Environmental (2-6501) if a sheen or odor is present. If there is no sheen or odor follow the instruction on Fort McCoy Form 374 prior to discharging the water.
8b.

(Double

Walled)Contact DPW Environmental (2-6501).
9.If POL is present place oil absorbent or other means to contain the POL. If greater than a gallon is released call 911 if in the Cantonment area or call Range Control (388-

4848) if outside the Cantonment area. If less than a gallon clean up and dispose of material properly. Determine where the POL came from and address condition as necessary notify DPW Environmental (2-6501) of any corrective measures that are taken.

10.If the system is equipped with a leak detection system and the alarm is sounding; determine the reason for the alarm and notify DPW Environmental (2-6501) of any corrective measures that are taken.
Page 2
FORT MCCOY FORM 372 OCT 2013
Previous versions of this form are obsolete
PE v1.00