Atch 17 - BLDG 11.pdf

PDF 6 MB Posted

Attached to
Y1AZ--EHRM Infrastructure Upgrades Construction - St. Cloud Federal contract opportunity
Solicitation number
36C77622B0035
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This federal contract opportunity solicitation is for infrastructure improvement services at the St. Cloud Veterans Affairs Health Care System campus in Minnesota. The contractor shall provide all labor, materials, tools and equipment to perform electrical upgrades including bonding and UPS systems, building management system integrations, telecommunications infrastructure upgrades including a diversified data center network path, fiber backbone upgrades both within and between buildings, as well as HVAC renovations, space reconfigurations and hazardous materials abatement. The solicitation is issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas.

View the file

Other files for this federal contract opportunity

Other files attached to Y1AZ--EHRM Infrastructure Upgrades Construction - St. Cloud, newest first.
File Type Posted
Technical Questions - LATE - St. Cloud 8-10-22.pdf PDF
01-M204 - ROOF REMODEL -MECHANICAL.pdf PDF
Atch 41 - Construction Wage Rates - Stearns 7-29-22.pdf PDF
Specifications Addendum Information.pdf PDF
Drawings Addendum Information.pdf PDF
Atch 1 - Specifications Volume 1 addendum.pdf PDF
Atch 11 - BLDG 5 addendum.pdf PDF
Atch 17 - BLDG 11 addendum.pdf PDF
Atch 18 - BLDG 14 addendum.pdf PDF
Atch 28 - BLDG 108 addendum.pdf PDF
Atch 33 - BLDG 116 addendum.pdf PDF
Atch 3 - Specifications Volume 3 - Asbestos addendum.pdf PDF
Atch 4 - General 1 of 2 addendum.pdf PDF
Atch 6 - BLDG 1 - 1 of 2 addendum.pdf PDF
Atch 8 - BLDG 2 addendum.pdf PDF
Atch 9 - BLDG 3 addendum.pdf PDF
Atch 12 - BLDG 6 addendum.pdf PDF
Atch 13 - BLDG 7 and 13 addendum.pdf PDF
Atch 27 - BLDG 96 addendum.pdf PDF
Atch 30 - BLDG 111 addendum.pdf PDF
Atch 31 - BLDG 112 addendum.pdf PDF
Site Visit Sign-in Sheets - 6-28-22 - 6-30-22.pdf PDF
Atch 4 - General 1 of 2.pdf PDF
Atch 5 - General 2 of 2.pdf PDF
Atch 8 - BLDG 2.pdf PDF
Atch 23 - BLDG 50.pdf PDF
Atch 24 - BLDG 51.pdf PDF
Atch 27 - BLDG 96.pdf PDF
Atch 31 - BLDG 112.pdf PDF
Atch 10 - BLDG 4.pdf PDF
Atch 34 - BLDG 118.pdf PDF
36C77622B0035 - 6-9-22.pdf PDF
Atch 6 - BLDG 1 - 1 of 2.pdf PDF
Atch 16 - BLDG 10.pdf PDF
Atch 19 - BLDG 28.pdf PDF
Atch 22 - BLDG 49.pdf PDF
Atch 35 - ADHC.pdf PDF
Atch 2 - Specifications Volume 2.pdf PDF
Atch 3 - Specifications Volume 3 - Asbestos.pdf PDF
Atch 9 - BLDG 3.pdf PDF
Atch 11 - BLDG 5.pdf PDF
Atch 13 - BLDG 7 and 13.pdf PDF
Atch 14 - BLDG 8.pdf PDF
Atch 29 - BLDG 109 and 57.pdf PDF
Atch 33 - BLDG 116.pdf PDF
Atch 37 - Brand Name Justification - St. Cloud.pdf PDF
Atch 38 - Contractor Core Work Hours.pdf PDF
Atch 39 - COVID-19 Safety Protocols 12-14-21.pdf PDF
Atch 41 - Construction Wage Rates - Stearns 4-1-22.pdf PDF
Atch 42 - Contractor Safety - Environmental Form.docx DOCX document
Show all 50

Y1AZ--EHRM Infrastructure Upgrades Construction - St. Cloud has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EXISTING FIBER - INSIDE

VFY EXIST

EXISTING FIBER - OUTSIDE

VFY EXIST

FIBER ROUTE - INSIDE

SEE TELECOM

FIBER ROUTE - OUTSIDE

SEE CIVIL

BUILDING OUTLINE

VFY EXIST

CORRIDOR OUTLINE

VFY EXIST

LEGEND

TO 8TH ST WEST ONLYTO 8TH ST EAST & WEST

44TH AVE.

TRAIL 1

TRAIL 2

TRANSFER

SWITCH

CAPACITOR

BANK (3)

SWITCH

(2)

15KV

MAIN

SW

BATT

35 KV

TO

15 KV

TRANSFORMER

35KV

FUSED

SWITCH

METER 35KV

SWITCH

GRAVEL

GRAVEL

GRAVEL

EXISTING

ROAD

CHAIN LINK FENCE

CHAIN LINK FENCE

16' GATE

GRAVEL

ELECTRICAL

SUBSTATION

G E N E R A T O R

FUEL LINES

CONDU ITS TO TU NNEL

M V

D U

C T

B A

N K

1 1 2 W

PHARMACY ADDITION

11 2 E

G E N E R A T O R

B

CORRIDOR LINK

A

C T

TR

A

IL

ER

174 s .f.

256 s .f.

185 s .f.

149 s ..f.

155 s .f.

104 s .f.

70 s. .f .

72 s .f.

110 s .f.

276 s .f.

112 s .f.

99 s .f.

57 s .f.

146 s .f.

434 s .f.

R A

MP

U P

1:

M A X

R A

MP

U P

1:

M A X

RA

M P

UP

1:2 0 M

AX

TRANSFER

SWITCH

CAPACITOR

BANK (3)

SWITCH

(2) 15KV

MAIN

SW

BATT

35 KV

TO

15 KV

TRANSFORMER

35KV

FUSED

SWITCH

METER 35KV

SWITCH

.3

TRANSFORMER

BUILD ING

#91

5,000 GAL.

UNDERGROUND

DIESEL FUEL TANK

EXISTIN G G AS SU P P LY EQ U IP M EN T TO R EM AIN

O P ER ATIO N AL DU R IN G D EM O LITIO N AN D N EW

C O N STR U C TIO N. P R O TEC T EQU IP M EN T AN D

P IP ELIN ES IN AC C O R D AN C E W ITH G AS SU P P LIER 'S

R EC O M M EN D ATIO N S

N EW G AS SU P P LY M AIN

IN TO B U ILD IN G

SP AR E

P H O N E LIN E

EXTEN D S TO

E XISTIN G

P H O N E IN

B O ILER R O O M

P ER P LAN .

SP AR E

P H O N E

LIN E TO

M ETER

TU N N EL

E XTEN D S

A D D ITIO N AL

2'- 0" U N D ER

B U ILD IN G

FUEL LINE

VENT LINE

1,000 GAL.

UNDERGROUND

DIESEL FUEL

TANK

1,000/5,000 GAL.

UNDERGROUND

DIESEL FUEL TANK

1,000 GAL.

UNDERGROUND

DIESEL FUEL TANK

1,000 GAL.

UNDERGROUND

DIESEL FUEL TANK

S 1

LIG H T

N EW G AS SU P P LY

(C O O R D IN ATE W ITH SU P P LIER )

12"D

10"D

"D

TP TP

EXIST. BUILDING

EXIST.

BUS STOP

CC

L O

O P

16"

20"

12"

3"

8"

DN

0.

0’

BIRDCAGE

B

IR

D C

A G

E

NSP ELECTRICAL

FOR HWY DEPT

T101

I.T.

CHILLER

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

VESTIBULE

DN

DN

DN

FD

DN

F B

F

B

F B

F

B

F B

F

B

SOUTH

VESTIBULE

PASS

THROUGH

LINK TO

BUILDI NG 51

6 3. 32 56

1 13 5. 35 78

PARKING

NO

PARKING

93 49

37 6

109 5

1A

S M

O K

E B

L D

G

SMOKE

BLDG

SMOKE

BLDG

S M

O K

E B

L D

G

SMOKE

BLDG

M.H.

STOR.

SMOKE

BLDG

SMOKE

BLDG

SMOKE

BLDG

SMOKE

BLDG

SMOKE

BLDG

STOR.

BIO-

HAZ.

SAUK RIVER

GP

HOLDING POND

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

OWNER AND

CONSULTANTS:

CONTACT:

ADDRESS:

MIKE ENGMARK

ST CLOUD VA MEDICAL CENTER

4801 VETERANS DRIVE

ST. CLOUD, MN 56303

NAME:

ADDRESS:

CONTACT:

ADVANCED STRUCTURAL TECHNOLOGIES

7301 OHMS LANE; SUITE 215

EDINA, MN 55439

ZACHARY CRAIG

PHONE:

NAME:

ADDRESS:

CONTACT:

SPECIALIZED ENGINEERING SOLUTIONS

10360 ELLISON CIRCLE

OMAHA, NE 68134

KRIS BURNHAM

PHONE: 402-991-5520

NAME:

ADDRESS:

CONTACT:

PHONE:

NAME:

ADDRESS:

CONTACT:

PHONE:

NAME:

ADDRESS:

CONTACT:

PHONE:

ANDERSON ENGINEERING OF MN, LLC

13605 1ST AVE NORTH, SUITE 100

PLYMOUTH, MN 55441

IAN WEBER

763-412-4000

ARCHITECT:

ANDERSON ENGINEERING OF MN, LLC

13605 1ST AVE NORTH, SUITE 100

PLYMOUTH, MN 55441

EDWARD MARKFORT

763-412-4000

952-854-9302

SPECIALIZED ENGINEERING SOLUTIONS

10360 ELLISON CIRCLE

OMAHA, NE 68134

KRIS BURNHAM

402-991-5520

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

COVER

DATE:

APPROVED: APPROVED: PROJECTS SECTION MANAGER

APPROVED: OIT MANAGER DATE: APPROVED: ASSISTANT CHIEF ENGINEER DATE:

APPROVED: SAFETY MANAGER

APPROVED: CHIEF OF POLICE

APPROVED: PATIENT SAFETY

DATE:

DATE:

DATE: APPROVED: EMS MANAGER

APPROVED: M/O MANAGER

DATE:

DATE:

DATE:DATE:

APPROVED: MEDICAL CENTER DIRECTOR

APPROVED: PROJECT COR DATE:

APPROVED: INFECTION CONTROL NURSE DATE:

APPROVED: SERVICE LINE DIRECTOR

APPROVED: GEMS COORDINATOR DATE:

DATE:

APPROVED: NURSE EXECUTIVE

APPROVED: CHIEF OF STAFF DATE:

APPROVED: DIRECTOR FMS

APPROVED: ASSOCIATE DIRECTOR

DATE:

DATE:

DATE:

DATE:APPROVED: DATE:

APPROVED: DATE:

APPROVED: DATE:

Main Campus, St. Cloud, Minnesota St. Cloud VA Health Care System

N

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

VICINITY MAP:

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHONE: 320-252-1670

CIVIL ENGINEER:

VA COR:

TELECOMMUNICATIONS ENGINEER:

CONTACT:

ADDRESS:

JONATHAN WEST

ST CLOUD VA MEDICAL CENTER

4801 VETERANS DRIVE

ST. CLOUD, MN 56303

PHONE: 504-250-2699

PROGRAM MANAGER:

EMAIL: Jonathan.West@vciint.com

STRUCTURAL ENGINEER:

MECH/ELEC/PLUMB/FIRE ENGINEER:

C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -1

-R

E

M a rk fo rt

.r v t

/2

/2

:3 :3

P

M

11-GI000

BUILDING 11 COVER SHEET &

SHEET INDEX

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM EM

16305

BUILDING 11 - EHRM INFRASTRUCTURE UPGRADES

03/30/2022

0APPROX 150' 300'75'

SHEET INDEX - BUILDING 11

SHEET NO. SHEET TITLE

11-GI000 BUILDING 11 COVER SHEET & SHEET INDEX

11-GI101 BASEMENT FLOOR INFECTION CONTROL & PHASING PLAN

11-HA-1A REFERENCE - BASEMENT FIRST FLOOR ASBESTOS RE-SURVEY

11-HA-2A REFERENCE - SECOND ATTIC FLOOR ASBESTOS RE-SURVEY

11-AS100 BASEMENT, FIRST, AND SECOND FLOOR PLANS

11-TD100 BASEMENT FLOOR PLAN - TELECOM - DEMOLITION

11-TN100 BASEMENT FLOOR PLAN - TELECOMMUNICATIONS

11-TD110 FIRST FLOOR PLAN - TELECOM - DEMOLITION

11-TD120 SECOND FLOOR PLAN - TELECOM - DEMOLITION

11-TN110 FIRST FLOOR PLAN - TELECOMMUNICATIONS

11-TN120 SECOND FLOOR PLAN - TELECOMMUNICATIONS

11-TN200 BASEMENT FLOOR PLAN - TELECOM - CABLE DISTANCE

11-TN300 ENLARGED PLANS - TELECOMMUNICATIONS - DEMO

11-TN400 ENLARGED PLANS - TELECOMMUNICATIONS

11-E200 BASEMENT - ELECTRICAL

11-E300 ELECTRICAL ENLARGED PLANS

11-E600 ELECTRICAL SCHEDULES

11-M100 BASEMENT DEMOLITION - MECHANICAL

11-M200 BASEMENT FLOOR - MECHANICAL

SEE GENERAL SHEETS FOR ADDITIONAL INFORMATION

ROOM SCHEDULE

NO. NAME C

A

B

LI

N G

P A

T C

H P

A N

E L

F

IB

E R

P O

W E

R

B O

N D

IN

G

U P

S

D E

D

IC

A T

E D

C O

O

LI

N G

T E

M P

E R

A T

U R

E

H U

M

ID

IT

Y

R A

C K

S E

N S

O R

S P

A C

E

AREA

WIDTH

(FT)

LENGTH

(FT) REMARKS

BASEMENT

C00A TELECOM ROOM X X X X X X X X 117 SF 7.0 16.7 UPDATE EXIST IT/DATA ROOM TO EHRM TELECOM ROOM

STANDARDS. SEE TELECOM DRAWINGS

OPENING SCHEDULE

VA Building Number

ASSOCIATED ROOMS OPENING PANEL INFORMATION FRAME INFORMATION

H D

W G

R O

U P

F

IR

E L

A B

E L

(M

IN

G A

S K

E T

E

LE

C T

R

IC

A L

S L

A B

E L

COMMENTSFROM ROOM NAME TO ROOM NAME NUMBER WIDTH HEIGHT

PANEL

TYPE

2ND

PANEL

TYPE

PANEL

GLAZING FRAME TYPE

FRAME

GLAZING

HAZARDOUS MATERIAL SCHEDULE

LEVEL

ROOM

NO. ROOM NAME

QUESTIONABLE HAZARDOUS

ELEMENT POSSIBLE ABATEMENT ACTION

BASEMENT C00A TELECOM ROOM NONE. SEE 11-HA-1A NONE. ACM TO REMAIN UNDISTURBED

HAZARDOUS MATERIALS MAY BE ENCOUNTERED THROUGHOUT THE DISTRIBUTION ROUTING THROUGH CEILING PLENUMS AND UTILITY TUNNELS. INSTALLATION OF DISTRIBUTION SHALL NOT DISTURB

QUESTIONABLE HAZARDOUS MATERIAL.

LEAK PREVENTION / DIVERTER SCHEDULE

LEVEL

ROOM

NO. ROOM NAME OVERHEAD LEAK DIVERTER AND DRAIN PIPING LEAK PREVENTION BARRIER WATERPROOFING

BASEMENT C00A TELECOM ROOM YES

SEE GENERAL NOTES SHEET FOR DETAIL. MWP = MEMBRANE WATERPROOFING. MASONRY = FLUID-APPLIED WATERPROOFING. INT = INTERIOR. EXT = EXTERIOR

ICRA PHASE CONSTRUCTION ROOM SCHEDULE

LEVEL

ROOM

NO. ROOM NAME

CAI BLDG NAME /

FUNCTION

CONSTRUCTION

PROJECT ACTIVITY

INFECTION CONTROL

RISK GROUP

CONTROL

PROCEDURE CLASS SECTION

CONSTRUCTION ZONE /

OCCUPIED CONSTR

DAY /

NIGHT

BASEMENT C00A TELECOM ROOM EMPLOYEE TRAVEL /

CONTRACTING

TYPE C GROUP 1 CLASS II EAST OCCUPIED CONSTRUCTION NIGHT

SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.

FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.

BASEMENT

VACANT

UNEXCAVATED

UNEXCAVATED

CO0

CORR

VACANT

U P

U P

INFECTION CONTROL RISK ASSESSMENT (ICRA) LEGEND

LIMITS OF CONSTRUCTION

1 HOUR FIRE RATED ICRA / CONSTRUCTION BARRIER

LOCATION, AND DOOR, WHERE SHOWN

TEMPORARY NON-RATED (PLASTIC SHEETING) CONSTRUCTION BARRIER

LOCATION, WHERE APPROVED BY THE VA FOR USE IN RISK TYPE B.

UPGRADE TO 1 HOUR RATED PARTITION WHEN DIRECTED BY THE VA

C00A

TELECOM

ROOM

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -1

-R

E

M a rk fo rt

.r v t

/2

/2

:3 :3

P

M

11-GI101

BASEMENT FLOOR INFECTION

CONTROL & PHASING PLAN

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM BMW

16305

03/30/2022

ROOM ICRA SCHEDULE

LEVEL

ROOM

NO. ROOM NAME CAI BLDG NAME / FUNCTION CONSTRUCTION PROJECT ACTIVITY INFECTION CONTROL RISK GROUP CONTROL PROCEDURE CLASS

BASEMENT C00A TELECOM ROOM EMPLOYEE TRAVEL / CONTRACTING TYPE C GROUP 1 CLASS II

SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.

FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.

1/4" = 1'-0"

BASEMENT - CONST BARRIER PLAN

N

0 8' 16'4'

-ASBESTOS-CONTAINING DOOR CAULK

-ASBESTOS-CONTAINING WINDOW GLAZING

CASTLE HILL ASSOCIATES, LLC.

N

S

W

E

LEGEND

BUILDING #11 - BASEMENT FLOOR PLAN BUILDING #11 - FIRST FLOOR PLAN

-ASBESTOS-CONTAINING WINDOW GLAZING

CASTLE HILL ASSOCIATES, LLC.

N

S

W

E

LEGEND

BUILDING #11 - SECOND FLOOR PLAN BUILDING #11 - ATTIC FLOOR PLAN

BASEMENT

VACANT

UNEXCAVATED

UNEXCAVATED

CO0

CORR

VACANT

U P

U

P COFFEE

M

IC

R O

W A

V E

A/C

A/CA/C

x

D E

S K

24X48

"L" DESK

24X48

"L" DESK

x

D E

S K

30x66

DESK

X

"L " D

E S

K

X

"L " D

E S

K

30x66

DESK

x

D E

S K

24X48

"L" DESK

x

D E

S K

24X48

"L" DESK

X

"L " D

E S

K

30x66

DESK

B O

O K

S B

O O

K S

BOOKSBOOKS

B O

O K

S

VERT.

FILE

VERT.

FILE

VERT.

FILE

VERT.

FILE

VERT.

FILE

V E

R T

F

IL

E

VERT.

FILE

VERT.

FILE

V E

R T

F

IL

E

V E

R T

F

IL

E

C O

P

IE

R

P R

IN

T

E R

PRINTER

R A

D

IA

T O

R

R A

D

IA

T O

R

RADIATOR

PORCH

OFFICE

C10

CORR

ENTRY

OFFICE

ROOM

BREAK

BATH

HAC

U P

D O

W N

OFFICE

200A

CLOSET

BATH

STAIR

C20

CORR

205A

STORAGE

OFFICE

OFFICE

D O

W N

C00A

TELECOM

ROOM

7'-0 1/2"

'-8

/4

C

B

11-AS100

C00A

TELECOM

ROOM

TELECOM

ROOM

C00A

TELECOM

ROOM

IN-03.01

2'-7" 4'-5 1/2"

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -1

-R

E

M a rk fo rt

.r v t

/2

/2

:3 :4

P

M

11-AS100

BASEMENT, FIRST, AND

SECOND FLOOR PLANS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM EM

16305

03/30/2022

1/4" = 1'-0"

BASEMENT FLOOR - OVERALL PLAN

1/8" = 1'-0"

FIRST FLOOR - OVERALL PLAN

1/8" = 1'-0"

SECOND FLOOR - OVERALL PLAN

N0 8' 16'4' N

0 8' 16'4'

N0 8' 16'4'

N0 4' 8'2'

N0 4' 8'2'

1/4" = 1'-0"

PARTIAL DEMOLITION PLAN

1/4" = 1'-0"

REFLECTED CEILING PLAN

DE1

RC1

_DEMOLITION PLAN KEYED NOTES

DE1 PREPARE WALL FOR PLYWOOD BACKBOARD INSTALLATION AND EHRM

REQUIREMENTS, SEE FLOOR PLAN AND TELECOM DRAWINGS

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

_FLOOR PLAN KEYED NOTES

FL1 ALL FOUR PERIMETER WALL PARTITIONS APPLY 4' BY 8' AC GRADE ¾”

TRADE SIZE FIRE RATED PLYWOOD BACKBOARD FINISHED WITH

HIGH-GLOSS WHITE PAINT OVER TWO COATS OF FIRE RESISTANT PAINT

FOR SERVICE PROVIDER / SECURITY / VIDEO / ET CETERA. DO NOT PAINT

OVER FIRE RATING STAMP.

FL3 UPGRADE PARTITION TO 1 HOUR FIRE AND SMOKE BARRIER. PROVIDE

TESTED HEAD OF PARTITION ASSEMBLY WITH MATERIALS THAT RESIST

THE PASSAGE OF SMOKE. SEAL JOINT AT HEAD AND ALL PENETRATIONS

WITH FIRE CAULK.

FL14 PROVIDE UL RATED 1 HOUR HORIZONTAL SHAFT WALL ASSEMBLY AT

CEILING TIGHT TO UNDERSIDE OF EXISTING STRUCTURE ABOVE. WHERE

EXISTING FINISHES ARE DISTURBED ON PAINTED SURFACES, PAINT TO

MATCH ADJACENT FINISH. PAINT ENTIRE PARTITION ON INTERIOR

SPACES WHERE PATCHING OCCURS. PAINT CEILING TO MATCH

ADJACENT FINISH

FL20 TELECOM EQUIPMENT, SEE TELECOM DRAWINGS.

FL21 OVERHEAD LEAK DIVERTER, SEE PLUMBING.

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

_REFLECTED CEILING PLAN KEYED NOTES

RC1 LED LIGHTING, SEE ELECTRICAL. IN FRONT OF AND BEHIND CABINET

ROWS PROVIDE 500 LUMENS IN HORIZONTAL AND 200 LUMENS IN THE

VERTICAL AT 3 FT AFF. OPERATED BY MOTION SENSOR PER CABINET

ROW OR SECTION.

RC7 RATED CEILING SEE FLOOR PLAN KEYED NOTE 14

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

DE1

_SHEET NOTES

1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL

INFORMATION, LIFE SAFETY, ICRA, AND PHASING

2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE

CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING

CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO

THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND

ENGINEERS.

3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS

AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH

OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND

ENGINEERS.

4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND

PLUMBING DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL

DEMOLITION AND CONSTRUCTION REQUIREMENTS.

5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE AS

DETERMINED BY VA) WITH WALL MOUNT BRACKET AND CODE REQUIRED

SIGNAGE SHALL BE PROVIDED BY THE CONTRACTOR WITHIN TELECOM

ROOMS.

1/4" = 1'-0"

BASEMENT FLOOR PLAN

FL1

FL20

FL21

FL3

FL3

FL3

N0 4' 8'2'

FL3

RC7

FL14

VACANT

UNEXCAVATED

UNEXCAVATED

CO0

CORR

VACANT

U P

U P

11-TN300

LIMITS OF DATA CABLING DEMOLITION

E

WAP

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:5

:3

P

M

11-TD100

BASEMENT FLOOR PLAN -

TELECOM - DEMOLITION

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

SHEET NOTES:

1. REMOVE AND REPLACE EXISTING DATA CABLE: REMOVE ALL EXISTING DATA CABLES AND JACKS THROUGHOUT THIS AREA. REPLACE CABLES AND JACKS 1 FOR 1, AS REQUIRED BY THE NEW WORK PLANS.

REFER TO NEW WORK PLANS FOR SERVING COMMUNICATIONS ROOM LOCATION AND NEW CABLING

ROUTES.

N

0 4' 8'2' 1/4" = 1'-0"

BASEMENT FLOOR PLAN - ELECTRICAL - DEMOLITION

GENERAL NOTES:

A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.

COFFEE

M

IC

R O

W A

V E x

D E

S K

24X48

"L" DESK

24X48

"L" DESK

x

D E

S K

30x66

DESK

X

"L " D

E S

K

X

"L " D

E S

K

30x66

DESK

x

D E

S K

24X48

"L" DESK

x

D E

S K

24X48

"L" DESK

X

"L " D

E S

K

30x66

DESK

B O

O K

S B

O O

K S

BOOKSBOOKS

B O

O K

S

VERT.

FILE

VERT.

FILE

VERT.

FILE

VERT.

FILE

VERT.

FILE

V E

R T

F

IL

E

VERT.

FILE

VERT.

FILE

V E

R T

F

IL

E

V E

R T

F

IL

E

C O

P

IE

R

P R

IN

T

E R

PRINTER

R A

D

IA

T O

R

R A

D

IA

T O

R

RADIATOR

PORCH

OFFICE

C10

CORR

ENTRY

OFFICE

ROOM

BREAK

BATH

HAC

1ST FLOOR

U P

D O

W N

COFFEE

M

IC

R O

W A

V E x

D E

S K

24X48

"L" DESK

24X48

"L" DESK

x

D E

S K

30x66

DESK

X

"L " D

E S

K

X

"L " D

E S

K

30x66

DESK

x

D E

S K

24X48

"L" DESK

x

D E

S K

24X48

"L" DESK

X

"L " D

E S

K

30x66

DESK

B O

O K

S B

O O

K S

BOOKSBOOKS

B O

O K

S

VERT.

FILE

VERT.

FILE

VERT.

FILE

VERT.

FILE

VERT.

FILE

V E

R T

F

IL

E

VERT.

FILE

VERT.

FILE

V E

R T

F

IL

E

V E

R T

F

IL

E

C O

P

IE

R

P R

IN

T

E R

PRINTER

R A

D

IA

T O

R

R A

D

IA

T O

R

RADIATOR

PORCH

OFFICE

C10

CORR

ENTRY

OFFICE

ROOM

BREAK

BATH

HAC

1ST FLOOR

U P

D O

W N

LIMITS OF DATA CABLING DEMOLITION

WAP

WAP

4D

4D

3D/1

4D

4D

4D 4D 4D

4D4D

E

EE

E

E

E E

E

E

E

E

E

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:5

:3

P

M

11-TD110

FIRST FLOOR PLAN -

TELECOM - DEMOLITION

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

1/4" = 1'-0"

FIRST FLOOR PLAN - TELECOM - DEMOLITION

N

0 4' 8'2'

SHEET NOTES:

1. REMOVE AND REPLACE EXISTING DATA CABLE: REMOVE ALL EXISTING DATA CABLES AND JACKS THROUGHOUT THIS AREA. REPLACE CABLES AND JACKS 1 FOR 1, AS REQUIRED BY THE NEW WORK PLANS.

REFER TO NEW WORK PLANS FOR SERVING COMMUNICATIONS ROOM LOCATION AND NEW CABLING

ROUTES.

2ND FLOOR

OFFICE

200A

CLOSET

BATH

STAIR

C20

CORR

205A

STORAGE

OFFICE

OFFICE

D O

W N

LIMITS OF DATA CABLING DEMOLITION

E

EE E

E

E

E

E

E

E

4D

4D 2D 4D 4D

4D

4D

4D

3D/1

2D/2

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:5

:3

P

M

11-TD120

SECOND FLOOR PLAN -

TELECOM - DEMOLITION

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

N

0 4' 8'2' 1/4" = 1'-0"

SECOND FLOOR PLAN - TELECOM - DEMOLITION

SHEET NOTES:

1. REMOVE AND REPLACE EXISTING DATA CABLE: REMOVE ALL EXISTING DATA CABLES AND JACKS THROUGHOUT THIS AREA. REPLACE CABLES AND JACKS 1 FOR 1, AS REQUIRED BY THE NEW WORK PLANS.

REFER TO NEW WORK PLANS FOR SERVING COMMUNICATIONS ROOM LOCATION AND NEW CABLING

ROUTES.

UNEXCAVATED

UNEXCAVATED

CO0

CORR

VACANT

U P

U P

VACANT

UNEXCAVATED

UNEXCAVATED

CO0

CORR

VACANT

U P

U P

C

C00A

TELECOM ROOM

11-TN400

LIMITS OF DATA CABLING REPLACEMENT

FROM ROOM C00A

HORIZONTAL AND VERTICAL ROUTE

TO ROOM C00A

WAP

E

4" UP

4"

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:5

:3

P

M

11-TN100

BASEMENT FLOOR PLAN -

TELECOMMUNICATIONS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

N

0 4' 8'2' 1/4" = 1'-0"

BASEMENT FLOOR PLAN - TELECOMMUNICATIONS

A. REFER TO GENERAL NOTES ON SHEET T000 FOR ADDITIONAL SCOPE.

COFFEE

M

IC

R O

W A

V E

A/C

A/CA/C

x

D E

S K

24X48

"L" DESK

24X48

"L" DESK

x

D E

S K

30x66

DESK

X

"L " D

E S

K

X

"L " D

E S

K

30x66

DESK

x

D E

S K

24X48

"L" DESK

x

D E

S K

24X48

"L" DESK

X

"L " D

E S

K

30x66

DESK

B O

O K

S B

O O

K S

BOOKSBOOKS

B O

O K

S

VERT.

FILE

VERT.

FILE

VERT.

FILE

VERT.

FILE

VERT.

FILE

V E

R T

F

IL

E

VERT.

FILE

VERT.

FILE

V E

R T

F

IL

E

V E

R T

F

IL

E

C O

P

IE

R

P R

IN

T

E R

PRINTER

R A

D

IA

T O

R

R A

D

IA

T O

R

RADIATOR

PORCH

OFFICE

C10

CORR

ENTRY

OFFICE

ROOM

BREAK

BATH

HAC

1ST FLOOR

U P

D O

W N

LIMITS OF DATA CABLING REPLACEMENT

FROM ROOM C00A

HORIZONTAL AND

VERTICAL ROUTE TO

ROOM C00A

4D

4D

4D

4D

4D

3D/1

WAP

4D 4D

4D4D

WAP

E

EE

E

E

E E

E

E

E

E

E

DOWN AND UP4"

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:5

:3

P

M

11-TN110

FIRST FLOOR PLAN -

TELECOMMUNICATIONS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

N

0 4' 8'2' 1/4" = 1'-0"

FIRST FLOOR PLAN - TELECOMMUNICATIONS

NORTH

2ND FLOOR

OFFICE

200A

CLOSET

BATH

STAIR

C20

CORR

205A

STORAGE

OFFICE

OFFICE

D O

W N

LIMITS OF DATA CABLING REPLACEMENT

FROM ROOM C00A

HORIZONTAL AND VERTICAL ROUTE

TO ROOM C00A

2D 4D 4D

4D

4D

4D

3D/1

2D/2

4D

4D

E

EE E

E

E

E

E

E

E

DOWN4"

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:5

:3

P

M

11-TN120

SECOND FLOOR PLAN -

TELECOMMUNICATIONS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

N

0 4' 8'2'1/4" = 1'-0"

SECOND FLOOR PLAN - TELECOMMUNICATIONS

VACA NT

UNEX CAVA TED

UNEX CAVA TED

CO0

CORR

VACA NT

U P

U P

VACA NT

UNEX CAVA TED

UNEX CAVA TED

CO0

CORR

VACA NT

U P

U P

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:5

:4

P

M

11-TN200

BASEMENT FLOOR PLAN -

TELECOM - CABLE DISTANCE

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

0 30' 60'15' 1" = 30'-0"

BASEMENT FLOOR PLAN - TELECOM - CABLE DISTANCE

N

FAPS

E

D

TW

E

E

DR

DATA RACK

1 2

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:5

:4

P

M

11-TN300

ENLARGED PLANS -

TELECOMMUNICATIONS -

DEMO

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

1/4" = 1'-0"

ENALRGED PLAN - EXIST RM C00A - TELECOM - DEMO

N

0 4' 8'2'

GENERAL NOTES:

A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.

SHEET NOTES:

1. EXISTING TELECOMMUNICATIONS CAGE AND RACK SHALL BE INCLUDED WITHIN THE SCOPE OF DEMOLITION.

EXISTING CABLING AND ASSOCIATED OUTLETS SHALL BE REMOVED AND REPLACED 1 FOR 1 AND REFED FROM DISTRIBUTION EQUIPMENT LOCATED WITHIN THE NEW TELECOMMUNICATIONS ROOM. REFER TO GENERAL CABLING NOTES FOR APPROXIMATE QUANTITIES. REFER TO NEW WORK PLANS FOR SERVING

COMMUNICATIONS ROOM LOCATION AND NEW CABLING ROUTES.

2. EXISTING DATA CABINET TO BE REPLACED WITH NEW EHRM TE.

CABLING NOTE:

CABLING NOTES:

A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE. THE CABLE

RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE PRESENT IN THE SPACE AT THE COMPLETION OF THE

PROJECT.

1. ROOM C00A

EXISTING CABLE COUNT

DATA (CAT6): 0

DATA (CAT5e): 57

DATA (CAT5): 0

DATA (CAT3): 0

CABLE RELOCATION COUNT

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

EXISTING CABLE TO REMAIN

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

FINAL CABLE COUNT

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

CR

AC

C

C

11-TN400

1 - a b

1 - c d

8" x2

CABLE TRAY

FAPS

E

E

E

KEYPAD

W

4"

DATA RACK

GROUND BAR

W

GROUND BAR

8"x2"

8" x2

NOTES:

1. REFER TO NEW WORK PLAN FOR RACK LOCATIONS.

2. COORDINATE EXACT RACK COUNT AND LOCATION WITH OWNER PRIOR TO PERMANENT INSTALLATION.

3. SEE PROJECT SPECIFICATIONS FOR ADDITIONAL RACK COMPONENTS.

4. RACK ELEVATION SHOWS A FULLY CONFIGURED SAMPLE RACK. CONTRACTOR TO PROVIDE REQUIRED EQUIPMENT TO

SUPPORT THE FINAL DATA COUNT FROM THE ENLARGED NEW SHEET. (NOT TO EXCEED 288 PORTS PER RACK).

5. COORDINATE FINAL RACK COMPONENT LAYOUT WITH OWNER'S IS/IT REPRESENTATIVE.

6. CONTRACTOR IS RESPONSIBLE FOR FINAL CABLE COUNT, QUANTITY OF PATCH PANELS, SWITCHES, FIBER ENCLOSURES, BLANKING PANELS, CABLE MANAGEMENT, AND MOUNTING HARDWARE NOT MARKED AS “OIT PROVIDED”.

7. PUNCHDOWN COPPER BACKBONES ON RACK MOUNT PATCH PANELS. TERMINATE ONE (1) PAIR PER PATCH PANEL PORT.

VERTICAL CABLE

MANAGEMENT (TYP)

RACK 1

1U 144 STRAND OM4 AND OS2 DISTRIBUTION PANEL

1U BONDING BUS BAR (BACK) 1U BLANKING PANEL (FRONT)

1U 48 PORT CAT5E BACKBONE PATCH PANEL

1U CABLE MANAGEMENT

1U CABLE MANAGEMENT

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

6U 5KW RACK MOUNT UPS

6U SPACE FOR FUTURE USE. PROVIDE BLANK

PANELS FOR UNUSED SPACES.

V E

R T

IC

A

L R

A C

K P

D U

V E

R T

IC

A

L R

A C

K P

D U

NEMA L21-20R (TYP)

CHANNEL RACK (TYP)

D

PROVIDE DATA CABLE TO RACK

MOUNTED UPS FOR CONNECTION

TO MONITORING SYSTEM

RACK 1

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U CABLE MANAGEMENT

VA OIT PROVIDED 1U 48 PORT SWITCH

2U CABLE MANAGEMENT

VA OIT PROVIDED 1U 48 PORT SWITCH

VA OIT PROVIDED 1U 48 PORT SWITCH

2U CABLE MANAGEMENT

1U CABLE MANAGEMENT

VA OIT PROVIDED 1U 48 PORT SWITCH

2U CABLE MANAGEMENT

VA OIT PROVIDED 1U 48 PORT SWITCH

2U CABLE MANAGEMENT

2U CABLE MANAGEMENT

VA OIT PROVIDED 1U 48 PORT SWITCH

SPACE FOR FUTURE HORIZONTAL CABLE

DISTRIBUTION. PROVIDE BLANKING PANELS FOR

UNUSED SPACES.

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:5

:4

P

M

11-TN400

ENLARGED PLANS -

TELECOMMUNICATIONS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

N

0 2' 4'1'

0 4' 8'2' 0 4' 8'2' 0 4' 8'2' 0 4' 8'2'

GENERAL NOTES:

A. REFER TO GENERAL NOTES ON SHEET T000 FOR ADDITIONAL SCOPE.

CABLING NOTE:

CABLING NOTES:

A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE.

THE CABLE RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED

FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE

PRESENT IN THE SPACE AT THE COMPLETION OF THE PROJECT.

1. ROOM C00A

EXISTING CABLE COUNT

DATA (CAT6): 0

DATA (CAT5e): 57

DATA (CAT5): 0

DATA (CAT3): 0

CABLE RELOCATION COUNT

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

EXISTING CABLE TO REMAIN

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

FINAL CABLE COUNT

DATA (CAT6A): 57

DATA (CAT6): 0

1/2" = 1'-0"

TELECOM - ENLARGED PLAN - TR C00A

1/4" = 1'-0"

1 - a

1/4" = 1'-0"

1 - b

1/4" = 1'-0"

1 - c

1/4" = 1'-0"

1 - d

NOT TO SCALE

COMMUNICATIONS - TYPICAL ONE RACK ELEVATION WITH RACK MOUNT UPS - TR C00A

UNEXCAVATED

UNEXCAVATED

CO0

CORR

VACANT

U P

U P

11-E300

11-E300

C00A

TELECOM

ROOM

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.E

R

.r v t

/1

/2

:2

:5

P

M

11-E200

BASEMENT - ELECTRICAL

EHRM INFRASTRUCTURE

UPGRADES

656-21-235

TBD GJL

16305

1/8" = 1'-0"

BASEMENT - ELECTRICAL

100% CD 03/30

by certify that this plan, specification was prepared by me or under my d vision and that I am a duly Licensed eer under the laws of the State of M e:

03/30/202205-06-2022 by certify that this plan, specification was prepared by me or under my d vision and that I am a duly Licensed eer under the laws of the State of M e:

03/30/202205-06-2022

C00A

TELECOM

ROOM

11LB1-1

C00A

TELECOM

ROOM

11LB1-1-28

11LB1-1-37,39,41

11LB1-1-38,40,42

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.E

R

.r v t

/1

/2

:2

:5

P

M

11-E300

ELECTRICAL ENLARGED

PLANS

EHRM INFRASTRUCTURE

UPGRADES

656-21-235

TBD GJL

16305

SHEET NOTES:

1. REFER TO TECHNOLOGY PLANS FOR IT ROOM

LAYOUT AND RACK LAYOUT/DETAILS.

2. REFER TO SHEET 0-GE400 DETAIL LAYOUT &

ONE-LINE OF RACK.

KEYNOTES:

1. COORDINATE FINAL LOCATION OF

RECEPTACLE L21-20R WITH TELECOM

CONTRACTOR. PROVIDE 3/4"C-4#12, 1#12 GND

TO PANEL FOR EACH RECEPTACLE.

2. PROVIDE EATON BLADEUPS, 5KW, 120/208V, 3-

PHASE,4-WIRE RACK MOUNTED UPS FOR EACH

RACK TOWER.

3. PROVIDE APC#AP8861 RPDU RACK PDU 2G

WITH L21-20P CORD. (120/208V, 3-PHASE, 20A,

ZERO U, 5.7 KW, 208V, (36) C13 (6) C19 (2) 5-20R

OUTLETS. PROVIDE TWO PER RACK, MOUNTED

PER MANUFACTURER'S REQUIREMENTS.

1/4" = 1'-0"

BASEMENT ENLAREGED - C00A - LIGHTING

1 1/4" = 1'-0"

BASEMENT ENLAREGED - C00A - POWER & SYSTEM

2N N

0 4' 8'2' 0 4' 8'2'

100% CD 03/30

by certify that this plan, specification was prepared by me or under my d vision and that I am a duly Licensed eer under the laws of the State of M e:

03/30/202205-06-2022 by certify that this plan, specification was prepared by me or under my d vision and that I am a duly Licensed eer under the laws of the State of M

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.E

R

.r v t

/1

/2

:2

:5

P

M

11-E600

ELECTRICAL SCHEDULES

EHRM INFRASTRUCTURE

UPGRADES

656-21-235

TBD GJL

16305

CIRCUIT KEY NOTES: REARRANGE THIS CIRCUIT BREAKERS IN PANEL TO ALLOW FOR 3 CONSECUTIVE SPACES.

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 28.8 A

TOTAL CONNECTED AMPS: 28.76 A

TOTAL ESTIMATED DEMAND LOAD: 10.36 kVA

Receptacles 0.36 kVA 100.00% 0.36 kVA TOTAL CONNECTED LOAD: 10.36 kVA

Power 10 kVA 100.00% 10 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 27.78 30.78 27.78

Total Load: 3.33 kVA 3.69 kVA 3.33 kVA

-- 41 -- -- -- -- -- -- 1.67 1.67 -- -- -- -- -- -- 42 --

-- 39 -- -- -- -- -- -- 1.67 1.67 -- -- -- -- -- -- 40 --

37 L21-20R 20 A 3 1.67 1.67 3 20 A L21-20R 38

-- 35 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 36 --

-- 33 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 34 --

-- 31 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 32 --

-- 29 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 30 --

-- 27 EXISTING LOAD 20 A 1 -- -- -- 0 0.36 1 20 A Receptacles 28

-- 25 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 26 --

-- 23 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 24 --

-- 21 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 22 --

-- 19 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 20 --

-- 17 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 18 --

-- 15 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 16 --

-- 13 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 14 --

-- 11 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 12 --

-- 9 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 10 --

-- 7 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 8 --

-- 5 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 6 --

-- 3 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 4 --

-- 1 SPACE -- 1 -- -- -- -- 0 -- -- -- 1 20 A EXISTING LOAD 2 --

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

SCCR: 65 kA

LOCATION: TELECOM ROOM C00A WIRE: 4

FED FROM: 0 A/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MCB

EXISTING PANEL 11LB1-1

100% CD 03/30

by certify that this plan, specification was prepared by me or under my d vision and that I am a duly Licensed eer under the laws of the State of M e:

03/30/202205-06-2022 by certify that this plan, specification was prepared by me or under my d vision and that I am a duly Licensed eer under the laws of the State of M x

D E

S K

X

"L " D

E S

K

X

"L " D

E S

K x

D E

S K

R A

D

IA

T O

R

VACANT

UNEXCAVATED

CO0

CORR

VACANT

HAC

U P

U P

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTA ARCHITECT/ENGINEER OF STAM

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 1

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.M

R

.r v t

/1

/2

:5

:4

P

M

11-M100

BASEMENT DEMOLITION

- MECHANICAL

EHRM

INFRASTRUCTURE

UPGRADES

656-21-235

RDL DJC

16305

1/4" = 1'-0"

BASEMENT DEMOLITION - MECHANICAL

1 0 8' 16'4'

N

FIELD VERIFICATION NOTES

1. THE HVAC CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID TO FIELD VERIFY ALL EXISTING CONDITIONS WHICH MAY AFFECT THEIR

BID. THE FOLLOWING ITEMS SHALL BE VERIFIED:

A. EXACT PLACEMENT, SIZE, CAPACITY, MANUFACTURER, AND CONDITION OF ALL EXISTING HVAC EQUIPMENT WITHIN SCOPE

OF WORK, WHETHER EXPLICITLY SHOWN OR NOT.

B. SIZE AND LOCATION OF ALL EXISTING DUCTWORK.

C. SIZE AND LOCATION OF ALL EXISTING GRILLES, REGISTERS AND DIFFUSERS.

D. SIZE AND LOCATION OF ALL EXISTING THERMOSTATIC CONTROL DEVICES.

E. SIZE AND LOCATION OF ALL EXISTING PLUMBING AND HYDRONIC PIPING

2. ALL REFERENCES ON THESE DRAWINGS TO EXISTING EQUIPMENT, DUCTWORK, DIFFUSERS, THERMOSTATS AND PIPING ARE FOR REFERENCE ONLY. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY ALL THESE ITEMS PRIOR TO BID AND INCLUDE IN THEIR

BID ANY AND ALL AMOUNTS REQUIRED TO ACCOMMODATE EXISTING CONDITIONS.

3. NO ALLOWANCES WILL BE MADE AFTER THE PROJECT HAS BEEN AWARDED FOR FAILURE TO VERIFY EXISTING CONDITIONS.

4. ANY DISCREPANCIES WHICH MAY AFFECT THE CONTRACTORS BID SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER AND

ARCHITECT FOR DIRECTION.

KEYNOTES 1/11-M100:

1. REMOVE EXISTING 2" HEATING WATER SUPPLY AND RETURN PIPING WHERE

SHOWN FOR REROUTING. PREPARE PIPE ENDS FOR NEW CONNECTION FIELD

VERIFY REQUIREMENTS.

2. REMOVE EXISTING FIRE SPRINKLER HEADS AND BRANCH LINE BACK AS SHOWN

FOR REROUTING. FIELD VERIFY REQUIREMENTS.

3. EXISTING 4" SANITARY DRAIN TO REMAIN.

100% CD 03/2

T x

D E

S K

X

"L " D

E S

K

X

"L " D

E S

K x

D E

S K

R A

D

IA

T O

R

VACANT

UNEXCAVATED

CO0

CORR

VACANT

HAC

U P

U P

C00A

TELECOM

ROOM

RACK PROVIDED

BY OTHERS

AC-11-1CP-11-1

CU-11-1

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTA ARCHITECT/ENGINEER OF STAM

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 1

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.M

R

.r v t

/1

/2

:5

:4

P

M

11-M200

BASEMENT FLOOR -

MECHANICAL

EHRM

INFRASTRUCTURE

UPGRADES

656-21-235

RDL DJC

16305

1/4" = 1'-0"

BASEMENT FLOOR - MECHANICAL

1 0 4' 8'2'

N

KEYNOTES 1/11-M200:

1. PROVIDE NEW WALL-MOUNTED DUCTLESS COOLING UNIT.

2. PROVIDE NEW THERMOSTAT.

3. PROVIDE CONDENSATE PUMP.

4. ROUTE 1" PUMPED CONDENSATE PIPE NORTH TO EXTERIOR WALL THEN RISE

INTO HAC 104 AND DISCHARGE TO MOP SINK, APPROXIMATELY 120 FEET.

COORDINATE FINAL ROUTING IN FIELD.

5. ROUTE REFRIGERANT PIPING TO NEW AIR-COOLED CONDENSING UNIT ON

GRADE. PROVIDE CONCRETE PAD.

6. REROUTE 2" HEATING WATER SUPPLY AND RETURN PIPING AND RECONNECT

AS SHOWN.

7. REROUTE EXISTING FIRE SPRINKLER BRANCH LINE AND PROVIDE NEW

SPRINKLER HEAD.

8. PROVIDE NEW AIR COOLED CONDENSING UNIT CU-11-1 ON GRADE ABOVE.

REFER TO REFRIGERANT PIPING DETAIL 1/0-GM400 AND PAD MOUNTING

DETAIL 3/0-GM401

9. EXISTING 4" SANITARY DRAIN. PROVIDE DRIP PAN. SEE DETAIL 6/0-GM400 FOR

REQUIREMENTS. DRIP PAN TO DISCHARGE TO NEAREST FLOOR DRAIN OR AREA

WELL.

10. REFERE TO 4/0-GM401 FOR WALL PENETRATION SEALING DETAIL.

11. PROVIDE NEW CONDENSATE DRIP PAN FOR ALL CONDENSATE PIPING. SEE

DETAIL 6/0-GM400 FOR REQUIREMENTS

1. THE HVAC CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID TO FIELD VERIFY ALL EXISTING CONDITIONS WHICH MAY AFFECT THEIR

BID. THE FOLLOWING ITEMS SHALL BE VERIFIED:

A. EXACT PLACEMENT, SIZE, CAPACITY, MANUFACTURER, AND CONDITION OF ALL EXISTING HVAC EQUIPMENT WITHIN SCOPE

OF WORK, WHETHER EXPLICITLY SHOWN OR NOT.

B. SIZE AND LOCATION OF ALL EXISTING DUCTWORK.

C. SIZE AND LOCATION OF ALL EXISTING GRILLES, REGISTERS AND DIFFUSERS.

D. SIZE AND LOCATION OF ALL EXISTING THERMOSTATIC CONTROL DEVICES.

E. SIZE AND LOCATION OF ALL EXISTING PLUMBING AND HYDRONIC PIPING

2. ALL REFERENCES ON THESE DRAWINGS TO EXISTING EQUIPMENT, DUCTWORK, DIFFUSERS, THERMOSTATS AND PIPING ARE FOR REFERENCE ONLY. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY ALL THESE ITEMS PRIOR TO BID AND INCLUDE IN THEIR

BID ANY AND ALL AMOUNTS REQUIRED TO ACCOMMODATE EXISTING CONDITIONS.

3. NO ALLOWANCES WILL BE MADE AFTER THE PROJECT HAS BEEN AWARDED FOR FAILURE TO VERIFY EXISTING CONDITIONS.

4. ANY DISCREPANCIES WHICH MAY AFFECT THE CONTRACTORS BID SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER AND

ARCHITECT FOR DIRECTION.

100% CD 03/2

11-GI000 - BUILDING 11 COVER SHEET & SHEET INDEX
11-GI101 - BASEMENT FLOOR INFECTION CONTROL & PHASING PLAN
11-HA-1A - REFERENCE - BASEMENT FIRST FLOOR ASBESTOS RE-SURVEY
11-HA-2A - REFERENCE - SECOND ATTIC FLOOR ASBESTOS RE-SURVEY
11-AS100 - BASEMENT, FIRST, AND SECOND FLOOR PLANS
11-TD100 - BASEMENT FLOOR PLAN - TELECOM - DEMOLITION
11-TD110 - FIRST FLOOR PLAN - TELECOM - DEMOLITION
11-TD120 - SECOND FLOOR PLAN - TELECOM - DEMOLITION
11-TN100 - BASEMENT FLOOR PLAN - TELECOMMUNICATIONS
11-TN110 - FIRST FLOOR PLAN - TELECOMMUNICATIONS
11-TN120 - SECOND FLOOR PLAN - TELECOMMUNICATIONS
11-TN200 - BASEMENT FLOOR PLAN - TELECOM - CABLE DISTANCE
11-TN300 - ENLARGED PLANS - TELECOMMUNICATIONS - DEMO
11-TN400 - ENLARGED PLANS - TELECOMMUNICATIONS
11-E200 - BASEMENT - ELECTRICAL
11-E300 - ELECTRICAL ENLARGED PLANS
11-E600 - ELECTRICAL SCHEDULES
11-M100 - BASEMENT DEMOLITION - MECHANICAL
11-M200 - BASEMENT FLOOR - MECHANICAL