This federal contract opportunity solicitation is for infrastructure improvement services at the St. Cloud Veterans Affairs Health Care System campus in Minnesota. The contractor shall provide all labor, materials, tools and equipment to perform electrical upgrades including bonding and UPS systems, building management system integrations, telecommunications infrastructure upgrades including a diversified data center network path, fiber backbone upgrades both within and between buildings, as well as HVAC renovations, space reconfigurations and hazardous materials abatement. The solicitation is issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas.
View the file
Other files for this federal contract opportunity
Show all 50
Y1AZ--EHRM Infrastructure Upgrades Construction - St. Cloud has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXISTING FIBER - INSIDE
VFY EXIST
EXISTING FIBER - OUTSIDE
VFY EXIST
FIBER ROUTE - INSIDE
SEE TELECOM
FIBER ROUTE - OUTSIDE
SEE CIVIL
BUILDING OUTLINE
VFY EXIST
CORRIDOR OUTLINE
VFY EXIST
LEGEND
TO 8TH ST WEST ONLYTO 8TH ST EAST & WEST
44TH AVE.
TRAIL 1
TRAIL 2
TRANSFER
SWITCH
CAPACITOR
BANK (3)
SWITCH
(2)
15KV
MAIN
SW
BATT
35 KV
TO
15 KV
TRANSFORMER
35KV
FUSED
SWITCH
METER 35KV
SWITCH
GRAVEL
GRAVEL
GRAVEL
EXISTING
ROAD
CHAIN LINK FENCE
CHAIN LINK FENCE
16' GATE
GRAVEL
ELECTRICAL
SUBSTATION
G E N E R A T O R
FUEL LINES
CONDU ITS TO TU NNEL
M V
D U
C T
B A
N K
1 1 2 W
PHARMACY ADDITION
11 2 E
G E N E R A T O R
B
CORRIDOR LINK
A
C T
TR
A
IL
ER
174 s .f.
256 s .f.
185 s .f.
149 s ..f.
155 s .f.
104 s .f.
70 s. .f .
72 s .f.
110 s .f.
276 s .f.
112 s .f.
99 s .f.
57 s .f.
146 s .f.
434 s .f.
R A
MP
U P
1:
M A X
R A
MP
U P
1:
M A X
RA
M P
UP
1:2 0 M
AX
TRANSFER
SWITCH
CAPACITOR
BANK (3)
SWITCH
(2) 15KV
MAIN
SW
BATT
35 KV
TO
15 KV
TRANSFORMER
35KV
FUSED
SWITCH
METER 35KV
SWITCH
.3
TRANSFORMER
BUILD ING
#91
5,000 GAL.
UNDERGROUND
DIESEL FUEL TANK
EXISTIN G G AS SU P P LY EQ U IP M EN T TO R EM AIN
O P ER ATIO N AL DU R IN G D EM O LITIO N AN D N EW
C O N STR U C TIO N. P R O TEC T EQU IP M EN T AN D
P IP ELIN ES IN AC C O R D AN C E W ITH G AS SU P P LIER 'S
R EC O M M EN D ATIO N S
N EW G AS SU P P LY M AIN
IN TO B U ILD IN G
SP AR E
P H O N E LIN E
EXTEN D S TO
E XISTIN G
P H O N E IN
B O ILER R O O M
P ER P LAN .
SP AR E
P H O N E
LIN E TO
M ETER
TU N N EL
E XTEN D S
A D D ITIO N AL
2'- 0" U N D ER
B U ILD IN G
FUEL LINE
VENT LINE
1,000 GAL.
UNDERGROUND
DIESEL FUEL
TANK
1,000/5,000 GAL.
UNDERGROUND
DIESEL FUEL TANK
1,000 GAL.
UNDERGROUND
DIESEL FUEL TANK
1,000 GAL.
UNDERGROUND
DIESEL FUEL TANK
S 1
LIG H T
N EW G AS SU P P LY
(C O O R D IN ATE W ITH SU P P LIER )
12"D
10"D
"D
TP TP
EXIST. BUILDING
EXIST.
BUS STOP
CC
L O
O P
16"
20"
12"
3"
8"
DN
0.
0’
BIRDCAGE
B
IR
D C
A G
E
NSP ELECTRICAL
FOR HWY DEPT
T101
I.T.
CHILLER
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
VESTIBULE
DN
DN
DN
FD
DN
F B
F
B
F B
F
B
F B
F
B
SOUTH
VESTIBULE
PASS
THROUGH
LINK TO
BUILDI NG 51
6 3. 32 56
1 13 5. 35 78
PARKING
NO
PARKING
93 49
37 6
109 5
1A
S M
O K
E B
L D
G
SMOKE
BLDG
SMOKE
BLDG
S M
O K
E B
L D
G
SMOKE
BLDG
M.H.
STOR.
SMOKE
BLDG
SMOKE
BLDG
SMOKE
BLDG
SMOKE
BLDG
SMOKE
BLDG
STOR.
BIO-
HAZ.
SAUK RIVER
GP
HOLDING POND
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of
Minnesota.
Name:
Date: License Number: MN# 18157
Typed or Printed Name: Tom Olesak
OWNER AND
CONSULTANTS:
CONTACT:
ADDRESS:
MIKE ENGMARK
ST CLOUD VA MEDICAL CENTER
4801 VETERANS DRIVE
ST. CLOUD, MN 56303
NAME:
ADDRESS:
CONTACT:
ADVANCED STRUCTURAL TECHNOLOGIES
7301 OHMS LANE; SUITE 215
EDINA, MN 55439
ZACHARY CRAIG
PHONE:
NAME:
ADDRESS:
CONTACT:
SPECIALIZED ENGINEERING SOLUTIONS
10360 ELLISON CIRCLE
OMAHA, NE 68134
KRIS BURNHAM
PHONE: 402-991-5520
NAME:
ADDRESS:
CONTACT:
PHONE:
NAME:
ADDRESS:
CONTACT:
PHONE:
NAME:
ADDRESS:
CONTACT:
PHONE:
ANDERSON ENGINEERING OF MN, LLC
13605 1ST AVE NORTH, SUITE 100
PLYMOUTH, MN 55441
IAN WEBER
763-412-4000
ARCHITECT:
ANDERSON ENGINEERING OF MN, LLC
13605 1ST AVE NORTH, SUITE 100
PLYMOUTH, MN 55441
EDWARD MARKFORT
763-412-4000
952-854-9302
SPECIALIZED ENGINEERING SOLUTIONS
10360 ELLISON CIRCLE
OMAHA, NE 68134
KRIS BURNHAM
402-991-5520
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
COVER
DATE:
APPROVED: APPROVED: PROJECTS SECTION MANAGER
APPROVED: OIT MANAGER DATE: APPROVED: ASSISTANT CHIEF ENGINEER DATE:
APPROVED: SAFETY MANAGER
APPROVED: CHIEF OF POLICE
APPROVED: PATIENT SAFETY
DATE:
DATE:
DATE: APPROVED: EMS MANAGER
APPROVED: M/O MANAGER
DATE:
DATE:
DATE:DATE:
APPROVED: MEDICAL CENTER DIRECTOR
APPROVED: PROJECT COR DATE:
APPROVED: INFECTION CONTROL NURSE DATE:
APPROVED: SERVICE LINE DIRECTOR
APPROVED: GEMS COORDINATOR DATE:
DATE:
APPROVED: NURSE EXECUTIVE
APPROVED: CHIEF OF STAFF DATE:
APPROVED: DIRECTOR FMS
APPROVED: ASSOCIATE DIRECTOR
DATE:
DATE:
DATE:
DATE:APPROVED: DATE:
APPROVED: DATE:
APPROVED: DATE:
Main Campus, St. Cloud, Minnesota St. Cloud VA Health Care System
N
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
VICINITY MAP:
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHONE: 320-252-1670
CIVIL ENGINEER:
VA COR:
TELECOMMUNICATIONS ENGINEER:
CONTACT:
ADDRESS:
JONATHAN WEST
ST CLOUD VA MEDICAL CENTER
4801 VETERANS DRIVE
ST. CLOUD, MN 56303
PHONE: 504-250-2699
PROGRAM MANAGER:
EMAIL: Jonathan.West@vciint.com
STRUCTURAL ENGINEER:
MECH/ELEC/PLUMB/FIRE ENGINEER:
C
U s e rs
\P u b li c \D o c u m e n ts \R e v it
P ro je c ts
\1 -1
-R
E
M a rk fo rt
.r v t
/2
/2
:3 :3
P
M
11-GI000
BUILDING 11 COVER SHEET &
SHEET INDEX
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
EM EM
16305
BUILDING 11 - EHRM INFRASTRUCTURE UPGRADES
03/30/2022
0APPROX 150' 300'75'
SHEET INDEX - BUILDING 11
SHEET NO. SHEET TITLE
11-GI000 BUILDING 11 COVER SHEET & SHEET INDEX
11-GI101 BASEMENT FLOOR INFECTION CONTROL & PHASING PLAN
11-HA-1A REFERENCE - BASEMENT FIRST FLOOR ASBESTOS RE-SURVEY
11-HA-2A REFERENCE - SECOND ATTIC FLOOR ASBESTOS RE-SURVEY
11-AS100 BASEMENT, FIRST, AND SECOND FLOOR PLANS
11-TD100 BASEMENT FLOOR PLAN - TELECOM - DEMOLITION
11-TN100 BASEMENT FLOOR PLAN - TELECOMMUNICATIONS
11-TD110 FIRST FLOOR PLAN - TELECOM - DEMOLITION
11-TD120 SECOND FLOOR PLAN - TELECOM - DEMOLITION
11-TN110 FIRST FLOOR PLAN - TELECOMMUNICATIONS
11-TN120 SECOND FLOOR PLAN - TELECOMMUNICATIONS
11-TN200 BASEMENT FLOOR PLAN - TELECOM - CABLE DISTANCE
11-TN300 ENLARGED PLANS - TELECOMMUNICATIONS - DEMO
11-TN400 ENLARGED PLANS - TELECOMMUNICATIONS
11-E200 BASEMENT - ELECTRICAL
11-E300 ELECTRICAL ENLARGED PLANS
11-E600 ELECTRICAL SCHEDULES
11-M100 BASEMENT DEMOLITION - MECHANICAL
11-M200 BASEMENT FLOOR - MECHANICAL
SEE GENERAL SHEETS FOR ADDITIONAL INFORMATION
ROOM SCHEDULE
NO. NAME C
A
B
LI
N G
P A
T C
H P
A N
E L
F
IB
E R
P O
W E
R
B O
N D
IN
G
U P
S
D E
D
IC
A T
E D
C O
O
LI
N G
T E
M P
E R
A T
U R
E
H U
M
ID
IT
Y
R A
C K
S E
N S
O R
S P
A C
E
AREA
WIDTH
(FT)
LENGTH
(FT) REMARKS
BASEMENT
C00A TELECOM ROOM X X X X X X X X 117 SF 7.0 16.7 UPDATE EXIST IT/DATA ROOM TO EHRM TELECOM ROOM
STANDARDS. SEE TELECOM DRAWINGS
OPENING SCHEDULE
VA Building Number
ASSOCIATED ROOMS OPENING PANEL INFORMATION FRAME INFORMATION
H D
W G
R O
U P
F
IR
E L
A B
E L
(M
IN
G A
S K
E T
E
LE
C T
R
IC
A L
S L
A B
E L
COMMENTSFROM ROOM NAME TO ROOM NAME NUMBER WIDTH HEIGHT
PANEL
TYPE
2ND
PANEL
TYPE
PANEL
GLAZING FRAME TYPE
FRAME
GLAZING
HAZARDOUS MATERIAL SCHEDULE
LEVEL
ROOM
NO. ROOM NAME
QUESTIONABLE HAZARDOUS
ELEMENT POSSIBLE ABATEMENT ACTION
BASEMENT C00A TELECOM ROOM NONE. SEE 11-HA-1A NONE. ACM TO REMAIN UNDISTURBED
HAZARDOUS MATERIALS MAY BE ENCOUNTERED THROUGHOUT THE DISTRIBUTION ROUTING THROUGH CEILING PLENUMS AND UTILITY TUNNELS. INSTALLATION OF DISTRIBUTION SHALL NOT DISTURB
QUESTIONABLE HAZARDOUS MATERIAL.
LEAK PREVENTION / DIVERTER SCHEDULE
LEVEL
ROOM
NO. ROOM NAME OVERHEAD LEAK DIVERTER AND DRAIN PIPING LEAK PREVENTION BARRIER WATERPROOFING
BASEMENT C00A TELECOM ROOM YES
SEE GENERAL NOTES SHEET FOR DETAIL. MWP = MEMBRANE WATERPROOFING. MASONRY = FLUID-APPLIED WATERPROOFING. INT = INTERIOR. EXT = EXTERIOR
ICRA PHASE CONSTRUCTION ROOM SCHEDULE
LEVEL
ROOM
NO. ROOM NAME
CAI BLDG NAME /
FUNCTION
CONSTRUCTION
PROJECT ACTIVITY
INFECTION CONTROL
RISK GROUP
CONTROL
PROCEDURE CLASS SECTION
CONSTRUCTION ZONE /
OCCUPIED CONSTR
DAY /
NIGHT
BASEMENT C00A TELECOM ROOM EMPLOYEE TRAVEL /
CONTRACTING
TYPE C GROUP 1 CLASS II EAST OCCUPIED CONSTRUCTION NIGHT
SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.
FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.
BASEMENT
VACANT
UNEXCAVATED
UNEXCAVATED
CO0
CORR
VACANT
U P
U P
INFECTION CONTROL RISK ASSESSMENT (ICRA) LEGEND
LIMITS OF CONSTRUCTION
1 HOUR FIRE RATED ICRA / CONSTRUCTION BARRIER
LOCATION, AND DOOR, WHERE SHOWN
TEMPORARY NON-RATED (PLASTIC SHEETING) CONSTRUCTION BARRIER
LOCATION, WHERE APPROVED BY THE VA FOR USE IN RISK TYPE B.
UPGRADE TO 1 HOUR RATED PARTITION WHEN DIRECTED BY THE VA
C00A
TELECOM
ROOM
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of
Minnesota.
Name:
Date: License Number: MN# 18157
Typed or Printed Name: Tom Olesak
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10 C
U s e rs
\P u b li c \D o c u m e n ts \R e v it
P ro je c ts
\1 -1
-R
E
M a rk fo rt
.r v t
/2
/2
:3 :3
P
M
11-GI101
BASEMENT FLOOR INFECTION
CONTROL & PHASING PLAN
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
EM BMW
16305
03/30/2022
ROOM ICRA SCHEDULE
LEVEL
ROOM
NO. ROOM NAME CAI BLDG NAME / FUNCTION CONSTRUCTION PROJECT ACTIVITY INFECTION CONTROL RISK GROUP CONTROL PROCEDURE CLASS
BASEMENT C00A TELECOM ROOM EMPLOYEE TRAVEL / CONTRACTING TYPE C GROUP 1 CLASS II
SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.
FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.
1/4" = 1'-0"
BASEMENT - CONST BARRIER PLAN
N
0 8' 16'4'
-ASBESTOS-CONTAINING DOOR CAULK
-ASBESTOS-CONTAINING WINDOW GLAZING
CASTLE HILL ASSOCIATES, LLC.
N
S
W
E
LEGEND
BUILDING #11 - BASEMENT FLOOR PLAN BUILDING #11 - FIRST FLOOR PLAN
-ASBESTOS-CONTAINING WINDOW GLAZING
CASTLE HILL ASSOCIATES, LLC.
N
S
W
E
LEGEND
BUILDING #11 - SECOND FLOOR PLAN BUILDING #11 - ATTIC FLOOR PLAN
BASEMENT
VACANT
UNEXCAVATED
UNEXCAVATED
CO0
CORR
VACANT
U P
U
P COFFEE
M
IC
R O
W A
V E
A/C
A/CA/C
x
D E
S K
24X48
"L" DESK
24X48
"L" DESK
x
D E
S K
30x66
DESK
X
"L " D
E S
K
X
"L " D
E S
K
30x66
DESK
x
D E
S K
24X48
"L" DESK
x
D E
S K
24X48
"L" DESK
X
"L " D
E S
K
30x66
DESK
B O
O K
S B
O O
K S
BOOKSBOOKS
B O
O K
S
VERT.
FILE
VERT.
FILE
VERT.
FILE
VERT.
FILE
VERT.
FILE
V E
R T
F
IL
E
VERT.
FILE
VERT.
FILE
V E
R T
F
IL
E
V E
R T
F
IL
E
C O
P
IE
R
P R
IN
T
E R
PRINTER
R A
D
IA
T O
R
R A
D
IA
T O
R
RADIATOR
PORCH
OFFICE
C10
CORR
ENTRY
OFFICE
ROOM
BREAK
BATH
HAC
U P
D O
W N
OFFICE
200A
CLOSET
BATH
STAIR
C20
CORR
205A
STORAGE
OFFICE
OFFICE
D O
W N
C00A
TELECOM
ROOM
7'-0 1/2"
'-8
/4
C
B
11-AS100
C00A
TELECOM
ROOM
TELECOM
ROOM
C00A
TELECOM
ROOM
IN-03.01
2'-7" 4'-5 1/2"
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of
Minnesota.
Name:
Date: License Number: MN# 18157
Typed or Printed Name: Tom Olesak
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10 C
U s e rs
\P u b li c \D o c u m e n ts \R e v it
P ro je c ts
\1 -1
-R
E
M a rk fo rt
.r v t
/2
/2
:3 :4
P
M
11-AS100
BASEMENT, FIRST, AND
SECOND FLOOR PLANS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
EM EM
16305
03/30/2022
1/4" = 1'-0"
BASEMENT FLOOR - OVERALL PLAN
1/8" = 1'-0"
FIRST FLOOR - OVERALL PLAN
1/8" = 1'-0"
SECOND FLOOR - OVERALL PLAN
N0 8' 16'4' N
0 8' 16'4'
N0 8' 16'4'
N0 4' 8'2'
N0 4' 8'2'
1/4" = 1'-0"
PARTIAL DEMOLITION PLAN
1/4" = 1'-0"
REFLECTED CEILING PLAN
DE1
RC1
_DEMOLITION PLAN KEYED NOTES
DE1 PREPARE WALL FOR PLYWOOD BACKBOARD INSTALLATION AND EHRM
REQUIREMENTS, SEE FLOOR PLAN AND TELECOM DRAWINGS
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
_FLOOR PLAN KEYED NOTES
FL1 ALL FOUR PERIMETER WALL PARTITIONS APPLY 4' BY 8' AC GRADE ¾”
TRADE SIZE FIRE RATED PLYWOOD BACKBOARD FINISHED WITH
HIGH-GLOSS WHITE PAINT OVER TWO COATS OF FIRE RESISTANT PAINT
FOR SERVICE PROVIDER / SECURITY / VIDEO / ET CETERA. DO NOT PAINT
OVER FIRE RATING STAMP.
FL3 UPGRADE PARTITION TO 1 HOUR FIRE AND SMOKE BARRIER. PROVIDE
TESTED HEAD OF PARTITION ASSEMBLY WITH MATERIALS THAT RESIST
THE PASSAGE OF SMOKE. SEAL JOINT AT HEAD AND ALL PENETRATIONS
WITH FIRE CAULK.
FL14 PROVIDE UL RATED 1 HOUR HORIZONTAL SHAFT WALL ASSEMBLY AT
CEILING TIGHT TO UNDERSIDE OF EXISTING STRUCTURE ABOVE. WHERE
EXISTING FINISHES ARE DISTURBED ON PAINTED SURFACES, PAINT TO
MATCH ADJACENT FINISH. PAINT ENTIRE PARTITION ON INTERIOR
SPACES WHERE PATCHING OCCURS. PAINT CEILING TO MATCH
ADJACENT FINISH
FL20 TELECOM EQUIPMENT, SEE TELECOM DRAWINGS.
FL21 OVERHEAD LEAK DIVERTER, SEE PLUMBING.
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
_REFLECTED CEILING PLAN KEYED NOTES
RC1 LED LIGHTING, SEE ELECTRICAL. IN FRONT OF AND BEHIND CABINET
ROWS PROVIDE 500 LUMENS IN HORIZONTAL AND 200 LUMENS IN THE
VERTICAL AT 3 FT AFF. OPERATED BY MOTION SENSOR PER CABINET
ROW OR SECTION.
RC7 RATED CEILING SEE FLOOR PLAN KEYED NOTE 14
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
DE1
_SHEET NOTES
1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL
INFORMATION, LIFE SAFETY, ICRA, AND PHASING
2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE
CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING
CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO
THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND
ENGINEERS.
3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS
AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH
OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND
ENGINEERS.
4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND
PLUMBING DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL
DEMOLITION AND CONSTRUCTION REQUIREMENTS.
5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE AS
DETERMINED BY VA) WITH WALL MOUNT BRACKET AND CODE REQUIRED
SIGNAGE SHALL BE PROVIDED BY THE CONTRACTOR WITHIN TELECOM
ROOMS.
1/4" = 1'-0"
BASEMENT FLOOR PLAN
FL1
FL20
FL21
FL3
FL3
FL3
N0 4' 8'2'
FL3
RC7
FL14
VACANT
UNEXCAVATED
UNEXCAVATED
CO0
CORR
VACANT
U P
U P
11-TN300
LIMITS OF DATA CABLING DEMOLITION
E
WAP
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/1
/2
:5
:3
P
M
11-TD100
BASEMENT FLOOR PLAN -
TELECOM - DEMOLITION
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
SHEET NOTES:
1. REMOVE AND REPLACE EXISTING DATA CABLE: REMOVE ALL EXISTING DATA CABLES AND JACKS THROUGHOUT THIS AREA. REPLACE CABLES AND JACKS 1 FOR 1, AS REQUIRED BY THE NEW WORK PLANS.
REFER TO NEW WORK PLANS FOR SERVING COMMUNICATIONS ROOM LOCATION AND NEW CABLING
ROUTES.
N
0 4' 8'2' 1/4" = 1'-0"
BASEMENT FLOOR PLAN - ELECTRICAL - DEMOLITION
GENERAL NOTES:
A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.
COFFEE
M
IC
R O
W A
V E x
D E
S K
24X48
"L" DESK
24X48
"L" DESK
x
D E
S K
30x66
DESK
X
"L " D
E S
K
X
"L " D
E S
K
30x66
DESK
x
D E
S K
24X48
"L" DESK
x
D E
S K
24X48
"L" DESK
X
"L " D
E S
K
30x66
DESK
B O
O K
S B
O O
K S
BOOKSBOOKS
B O
O K
S
VERT.
FILE
VERT.
FILE
VERT.
FILE
VERT.
FILE
VERT.
FILE
V E
R T
F
IL
E
VERT.
FILE
VERT.
FILE
V E
R T
F
IL
E
V E
R T
F
IL
E
C O
P
IE
R
P R
IN
T
E R
PRINTER
R A
D
IA
T O
R
R A
D
IA
T O
R
RADIATOR
PORCH
OFFICE
C10
CORR
ENTRY
OFFICE
ROOM
BREAK
BATH
HAC
1ST FLOOR
U P
D O
W N
COFFEE
M
IC
R O
W A
V E x
D E
S K
24X48
"L" DESK
24X48
"L" DESK
x
D E
S K
30x66
DESK
X
"L " D
E S
K
X
"L " D
E S
K
30x66
DESK
x
D E
S K
24X48
"L" DESK
x
D E
S K
24X48
"L" DESK
X
"L " D
E S
K
30x66
DESK
B O
O K
S B
O O
K S
BOOKSBOOKS
B O
O K
S
VERT.
FILE
VERT.
FILE
VERT.
FILE
VERT.
FILE
VERT.
FILE
V E
R T
F
IL
E
VERT.
FILE
VERT.
FILE
V E
R T
F
IL
E
V E
R T
F
IL
E
C O
P
IE
R
P R
IN
T
E R
PRINTER
R A
D
IA
T O
R
R A
D
IA
T O
R
RADIATOR
PORCH
OFFICE
C10
CORR
ENTRY
OFFICE
ROOM
BREAK
BATH
HAC
1ST FLOOR
U P
D O
W N
LIMITS OF DATA CABLING DEMOLITION
WAP
WAP
4D
4D
3D/1
4D
4D
4D 4D 4D
4D4D
E
EE
E
E
E E
E
E
E
E
E
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/1
/2
:5
:3
P
M
11-TD110
FIRST FLOOR PLAN -
TELECOM - DEMOLITION
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
1/4" = 1'-0"
FIRST FLOOR PLAN - TELECOM - DEMOLITION
N
0 4' 8'2'
SHEET NOTES:
1. REMOVE AND REPLACE EXISTING DATA CABLE: REMOVE ALL EXISTING DATA CABLES AND JACKS THROUGHOUT THIS AREA. REPLACE CABLES AND JACKS 1 FOR 1, AS REQUIRED BY THE NEW WORK PLANS.
REFER TO NEW WORK PLANS FOR SERVING COMMUNICATIONS ROOM LOCATION AND NEW CABLING
ROUTES.
2ND FLOOR
OFFICE
200A
CLOSET
BATH
STAIR
C20
CORR
205A
STORAGE
OFFICE
OFFICE
D O
W N
LIMITS OF DATA CABLING DEMOLITION
E
EE E
E
E
E
E
E
E
4D
4D 2D 4D 4D
4D
4D
4D
3D/1
2D/2
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/1
/2
:5
:3
P
M
11-TD120
SECOND FLOOR PLAN -
TELECOM - DEMOLITION
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
N
0 4' 8'2' 1/4" = 1'-0"
SECOND FLOOR PLAN - TELECOM - DEMOLITION
SHEET NOTES:
1. REMOVE AND REPLACE EXISTING DATA CABLE: REMOVE ALL EXISTING DATA CABLES AND JACKS THROUGHOUT THIS AREA. REPLACE CABLES AND JACKS 1 FOR 1, AS REQUIRED BY THE NEW WORK PLANS.
REFER TO NEW WORK PLANS FOR SERVING COMMUNICATIONS ROOM LOCATION AND NEW CABLING
ROUTES.
UNEXCAVATED
UNEXCAVATED
CO0
CORR
VACANT
U P
U P
VACANT
UNEXCAVATED
UNEXCAVATED
CO0
CORR
VACANT
U P
U P
C
C00A
TELECOM ROOM
11-TN400
LIMITS OF DATA CABLING REPLACEMENT
FROM ROOM C00A
HORIZONTAL AND VERTICAL ROUTE
TO ROOM C00A
WAP
E
4" UP
4"
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/1
/2
:5
:3
P
M
11-TN100
BASEMENT FLOOR PLAN -
TELECOMMUNICATIONS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
N
0 4' 8'2' 1/4" = 1'-0"
BASEMENT FLOOR PLAN - TELECOMMUNICATIONS
A. REFER TO GENERAL NOTES ON SHEET T000 FOR ADDITIONAL SCOPE.
COFFEE
M
IC
R O
W A
V E
A/C
A/CA/C
x
D E
S K
24X48
"L" DESK
24X48
"L" DESK
x
D E
S K
30x66
DESK
X
"L " D
E S
K
X
"L " D
E S
K
30x66
DESK
x
D E
S K
24X48
"L" DESK
x
D E
S K
24X48
"L" DESK
X
"L " D
E S
K
30x66
DESK
B O
O K
S B
O O
K S
BOOKSBOOKS
B O
O K
S
VERT.
FILE
VERT.
FILE
VERT.
FILE
VERT.
FILE
VERT.
FILE
V E
R T
F
IL
E
VERT.
FILE
VERT.
FILE
V E
R T
F
IL
E
V E
R T
F
IL
E
C O
P
IE
R
P R
IN
T
E R
PRINTER
R A
D
IA
T O
R
R A
D
IA
T O
R
RADIATOR
PORCH
OFFICE
C10
CORR
ENTRY
OFFICE
ROOM
BREAK
BATH
HAC
1ST FLOOR
U P
D O
W N
LIMITS OF DATA CABLING REPLACEMENT
FROM ROOM C00A
HORIZONTAL AND
VERTICAL ROUTE TO
ROOM C00A
4D
4D
4D
4D
4D
3D/1
WAP
4D 4D
4D4D
WAP
E
EE
E
E
E E
E
E
E
E
E
DOWN AND UP4"
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/1
/2
:5
:3
P
M
11-TN110
FIRST FLOOR PLAN -
TELECOMMUNICATIONS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
N
0 4' 8'2' 1/4" = 1'-0"
FIRST FLOOR PLAN - TELECOMMUNICATIONS
NORTH
2ND FLOOR
OFFICE
200A
CLOSET
BATH
STAIR
C20
CORR
205A
STORAGE
OFFICE
OFFICE
D O
W N
LIMITS OF DATA CABLING REPLACEMENT
FROM ROOM C00A
HORIZONTAL AND VERTICAL ROUTE
TO ROOM C00A
2D 4D 4D
4D
4D
4D
3D/1
2D/2
4D
4D
E
EE E
E
E
E
E
E
E
DOWN4"
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/1
/2
:5
:3
P
M
11-TN120
SECOND FLOOR PLAN -
TELECOMMUNICATIONS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
N
0 4' 8'2'1/4" = 1'-0"
SECOND FLOOR PLAN - TELECOMMUNICATIONS
VACA NT
UNEX CAVA TED
UNEX CAVA TED
CO0
CORR
VACA NT
U P
U P
VACA NT
UNEX CAVA TED
UNEX CAVA TED
CO0
CORR
VACA NT
U P
U P
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/1
/2
:5
:4
P
M
11-TN200
BASEMENT FLOOR PLAN -
TELECOM - CABLE DISTANCE
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
0 30' 60'15' 1" = 30'-0"
BASEMENT FLOOR PLAN - TELECOM - CABLE DISTANCE
N
FAPS
E
D
TW
E
E
DR
DATA RACK
1 2
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/1
/2
:5
:4
P
M
11-TN300
ENLARGED PLANS -
TELECOMMUNICATIONS -
DEMO
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
1/4" = 1'-0"
ENALRGED PLAN - EXIST RM C00A - TELECOM - DEMO
N
0 4' 8'2'
GENERAL NOTES:
A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.
SHEET NOTES:
1. EXISTING TELECOMMUNICATIONS CAGE AND RACK SHALL BE INCLUDED WITHIN THE SCOPE OF DEMOLITION.
EXISTING CABLING AND ASSOCIATED OUTLETS SHALL BE REMOVED AND REPLACED 1 FOR 1 AND REFED FROM DISTRIBUTION EQUIPMENT LOCATED WITHIN THE NEW TELECOMMUNICATIONS ROOM. REFER TO GENERAL CABLING NOTES FOR APPROXIMATE QUANTITIES. REFER TO NEW WORK PLANS FOR SERVING
COMMUNICATIONS ROOM LOCATION AND NEW CABLING ROUTES.
2. EXISTING DATA CABINET TO BE REPLACED WITH NEW EHRM TE.
CABLING NOTE:
CABLING NOTES:
A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE. THE CABLE
RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE PRESENT IN THE SPACE AT THE COMPLETION OF THE
PROJECT.
1. ROOM C00A
EXISTING CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 57
DATA (CAT5): 0
DATA (CAT3): 0
CABLE RELOCATION COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
EXISTING CABLE TO REMAIN
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
FINAL CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
CR
AC
C
C
11-TN400
1 - a b
1 - c d
8" x2
CABLE TRAY
FAPS
E
E
E
KEYPAD
W
4"
DATA RACK
GROUND BAR
W
GROUND BAR
8"x2"
8" x2
NOTES:
1. REFER TO NEW WORK PLAN FOR RACK LOCATIONS.
2. COORDINATE EXACT RACK COUNT AND LOCATION WITH OWNER PRIOR TO PERMANENT INSTALLATION.
3. SEE PROJECT SPECIFICATIONS FOR ADDITIONAL RACK COMPONENTS.
4. RACK ELEVATION SHOWS A FULLY CONFIGURED SAMPLE RACK. CONTRACTOR TO PROVIDE REQUIRED EQUIPMENT TO
SUPPORT THE FINAL DATA COUNT FROM THE ENLARGED NEW SHEET. (NOT TO EXCEED 288 PORTS PER RACK).
5. COORDINATE FINAL RACK COMPONENT LAYOUT WITH OWNER'S IS/IT REPRESENTATIVE.
6. CONTRACTOR IS RESPONSIBLE FOR FINAL CABLE COUNT, QUANTITY OF PATCH PANELS, SWITCHES, FIBER ENCLOSURES, BLANKING PANELS, CABLE MANAGEMENT, AND MOUNTING HARDWARE NOT MARKED AS “OIT PROVIDED”.
7. PUNCHDOWN COPPER BACKBONES ON RACK MOUNT PATCH PANELS. TERMINATE ONE (1) PAIR PER PATCH PANEL PORT.
VERTICAL CABLE
MANAGEMENT (TYP)
RACK 1
1U 144 STRAND OM4 AND OS2 DISTRIBUTION PANEL
1U BONDING BUS BAR (BACK) 1U BLANKING PANEL (FRONT)
1U 48 PORT CAT5E BACKBONE PATCH PANEL
1U CABLE MANAGEMENT
1U CABLE MANAGEMENT
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
6U 5KW RACK MOUNT UPS
6U SPACE FOR FUTURE USE. PROVIDE BLANK
PANELS FOR UNUSED SPACES.
V E
R T
IC
A
L R
A C
K P
D U
V E
R T
IC
A
L R
A C
K P
D U
NEMA L21-20R (TYP)
CHANNEL RACK (TYP)
D
PROVIDE DATA CABLE TO RACK
MOUNTED UPS FOR CONNECTION
TO MONITORING SYSTEM
RACK 1
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
1U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
SPACE FOR FUTURE HORIZONTAL CABLE
DISTRIBUTION. PROVIDE BLANKING PANELS FOR
UNUSED SPACES.
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/1
/2
:5
:4
P
M
11-TN400
ENLARGED PLANS -
TELECOMMUNICATIONS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
N
0 2' 4'1'
0 4' 8'2' 0 4' 8'2' 0 4' 8'2' 0 4' 8'2'
GENERAL NOTES:
A. REFER TO GENERAL NOTES ON SHEET T000 FOR ADDITIONAL SCOPE.
CABLING NOTE:
CABLING NOTES:
A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE.
THE CABLE RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED
FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE
PRESENT IN THE SPACE AT THE COMPLETION OF THE PROJECT.
1. ROOM C00A
EXISTING CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 57
DATA (CAT5): 0
DATA (CAT3): 0
CABLE RELOCATION COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
EXISTING CABLE TO REMAIN
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
FINAL CABLE COUNT
DATA (CAT6A): 57
DATA (CAT6): 0
1/2" = 1'-0"
TELECOM - ENLARGED PLAN - TR C00A
1/4" = 1'-0"
1 - a
1/4" = 1'-0"
1 - b
1/4" = 1'-0"
1 - c
1/4" = 1'-0"
1 - d
NOT TO SCALE
COMMUNICATIONS - TYPICAL ONE RACK ELEVATION WITH RACK MOUNT UPS - TR C00A
UNEXCAVATED
UNEXCAVATED
CO0
CORR
VACANT
U P
U P
11-E300
11-E300
C00A
TELECOM
ROOM
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN#
03/30/2022
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.E
R
.r v t
/1
/2
:2
:5
P
M
11-E200
BASEMENT - ELECTRICAL
EHRM INFRASTRUCTURE
UPGRADES
656-21-235
TBD GJL
16305
1/8" = 1'-0"
BASEMENT - ELECTRICAL
100% CD 03/30
by certify that this plan, specification was prepared by me or under my d vision and that I am a duly Licensed eer under the laws of the State of M e:
03/30/202205-06-2022 by certify that this plan, specification was prepared by me or under my d vision and that I am a duly Licensed eer under the laws of the State of M e:
03/30/202205-06-2022
C00A
TELECOM
ROOM
11LB1-1
C00A
TELECOM
ROOM
11LB1-1-28
11LB1-1-37,39,41
11LB1-1-38,40,42
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN#
03/30/2022
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.E
R
.r v t
/1
/2
:2
:5
P
M
11-E300
ELECTRICAL ENLARGED
PLANS
EHRM INFRASTRUCTURE
UPGRADES
656-21-235
TBD GJL
16305
SHEET NOTES:
1. REFER TO TECHNOLOGY PLANS FOR IT ROOM
LAYOUT AND RACK LAYOUT/DETAILS.
2. REFER TO SHEET 0-GE400 DETAIL LAYOUT &
ONE-LINE OF RACK.
KEYNOTES:
1. COORDINATE FINAL LOCATION OF
RECEPTACLE L21-20R WITH TELECOM
CONTRACTOR. PROVIDE 3/4"C-4#12, 1#12 GND
TO PANEL FOR EACH RECEPTACLE.
2. PROVIDE EATON BLADEUPS, 5KW, 120/208V, 3-
PHASE,4-WIRE RACK MOUNTED UPS FOR EACH
RACK TOWER.
3. PROVIDE APC#AP8861 RPDU RACK PDU 2G
WITH L21-20P CORD. (120/208V, 3-PHASE, 20A,
ZERO U, 5.7 KW, 208V, (36) C13 (6) C19 (2) 5-20R
OUTLETS. PROVIDE TWO PER RACK, MOUNTED
PER MANUFACTURER'S REQUIREMENTS.
1/4" = 1'-0"
BASEMENT ENLAREGED - C00A - LIGHTING
1 1/4" = 1'-0"
BASEMENT ENLAREGED - C00A - POWER & SYSTEM
2N N
0 4' 8'2' 0 4' 8'2'
100% CD 03/30
by certify that this plan, specification was prepared by me or under my d vision and that I am a duly Licensed eer under the laws of the State of M e:
03/30/202205-06-2022 by certify that this plan, specification was prepared by me or under my d vision and that I am a duly Licensed eer under the laws of the State of M
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN#
03/30/2022
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.E
R
.r v t
/1
/2
:2
:5
P
M
11-E600
ELECTRICAL SCHEDULES
EHRM INFRASTRUCTURE
UPGRADES
656-21-235
TBD GJL
16305
CIRCUIT KEY NOTES: REARRANGE THIS CIRCUIT BREAKERS IN PANEL TO ALLOW FOR 3 CONSECUTIVE SPACES.
*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.
TOTAL ESTIMATED DEMAND AMPS: 28.8 A
TOTAL CONNECTED AMPS: 28.76 A
TOTAL ESTIMATED DEMAND LOAD: 10.36 kVA
Receptacles 0.36 kVA 100.00% 0.36 kVA TOTAL CONNECTED LOAD: 10.36 kVA
Power 10 kVA 100.00% 10 kVA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND
TOTALS*
LOAD SUMMARY
Total Amps: 27.78 30.78 27.78
Total Load: 3.33 kVA 3.69 kVA 3.33 kVA
-- 41 -- -- -- -- -- -- 1.67 1.67 -- -- -- -- -- -- 42 --
-- 39 -- -- -- -- -- -- 1.67 1.67 -- -- -- -- -- -- 40 --
37 L21-20R 20 A 3 1.67 1.67 3 20 A L21-20R 38
-- 35 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 36 --
-- 33 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 34 --
-- 31 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 32 --
-- 29 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 30 --
-- 27 EXISTING LOAD 20 A 1 -- -- -- 0 0.36 1 20 A Receptacles 28
-- 25 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 26 --
-- 23 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 24 --
-- 21 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 22 --
-- 19 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 20 --
-- 17 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 18 --
-- 15 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 16 --
-- 13 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 14 --
-- 11 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 12 --
-- 9 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 10 --
-- 7 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 8 --
-- 5 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 6 --
-- 3 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 4 --
-- 1 SPACE -- 1 -- -- -- -- 0 -- -- -- 1 20 A EXISTING LOAD 2 --
K E Y
CKT
NO. LOAD DESCRIPTION
OCPD
AMPS P
WIRE
SIZE
H N G
A B C
WIRE
SIZE
G N H
OCPD
P AMPS LOAD DESCRIPTION
CKT
NO.
K E Y
NOTES:
SCCR: 65 kA
LOCATION: TELECOM ROOM C00A WIRE: 4
FED FROM: 0 A/0P @ GROUND BUS PHASE: 3
ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye
MOUNTING: SURFACE MAIN: 100 A MCB
EXISTING PANEL 11LB1-1
100% CD 03/30
by certify that this plan, specification was prepared by me or under my d vision and that I am a duly Licensed eer under the laws of the State of M e:
03/30/202205-06-2022 by certify that this plan, specification was prepared by me or under my d vision and that I am a duly Licensed eer under the laws of the State of M x
D E
S K
X
"L " D
E S
K
X
"L " D
E S
K x
D E
S K
R A
D
IA
T O
R
VACANT
UNEXCAVATED
CO0
CORR
VACANT
HAC
U P
U P
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTA ARCHITECT/ENGINEER OF STAM
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 1
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN#
03/30/2022
B
IM
/2
.0
V A
S t C lo u d
E H
R M
I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.M
R
.r v t
/1
/2
:5
:4
P
M
11-M100
BASEMENT DEMOLITION
- MECHANICAL
EHRM
INFRASTRUCTURE
UPGRADES
656-21-235
RDL DJC
16305
1/4" = 1'-0"
BASEMENT DEMOLITION - MECHANICAL
1 0 8' 16'4'
N
FIELD VERIFICATION NOTES
1. THE HVAC CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID TO FIELD VERIFY ALL EXISTING CONDITIONS WHICH MAY AFFECT THEIR
BID. THE FOLLOWING ITEMS SHALL BE VERIFIED:
A. EXACT PLACEMENT, SIZE, CAPACITY, MANUFACTURER, AND CONDITION OF ALL EXISTING HVAC EQUIPMENT WITHIN SCOPE
OF WORK, WHETHER EXPLICITLY SHOWN OR NOT.
B. SIZE AND LOCATION OF ALL EXISTING DUCTWORK.
C. SIZE AND LOCATION OF ALL EXISTING GRILLES, REGISTERS AND DIFFUSERS.
D. SIZE AND LOCATION OF ALL EXISTING THERMOSTATIC CONTROL DEVICES.
E. SIZE AND LOCATION OF ALL EXISTING PLUMBING AND HYDRONIC PIPING
2. ALL REFERENCES ON THESE DRAWINGS TO EXISTING EQUIPMENT, DUCTWORK, DIFFUSERS, THERMOSTATS AND PIPING ARE FOR REFERENCE ONLY. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY ALL THESE ITEMS PRIOR TO BID AND INCLUDE IN THEIR
BID ANY AND ALL AMOUNTS REQUIRED TO ACCOMMODATE EXISTING CONDITIONS.
3. NO ALLOWANCES WILL BE MADE AFTER THE PROJECT HAS BEEN AWARDED FOR FAILURE TO VERIFY EXISTING CONDITIONS.
4. ANY DISCREPANCIES WHICH MAY AFFECT THE CONTRACTORS BID SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER AND
ARCHITECT FOR DIRECTION.
KEYNOTES 1/11-M100:
1. REMOVE EXISTING 2" HEATING WATER SUPPLY AND RETURN PIPING WHERE
SHOWN FOR REROUTING. PREPARE PIPE ENDS FOR NEW CONNECTION FIELD
VERIFY REQUIREMENTS.
2. REMOVE EXISTING FIRE SPRINKLER HEADS AND BRANCH LINE BACK AS SHOWN
FOR REROUTING. FIELD VERIFY REQUIREMENTS.
3. EXISTING 4" SANITARY DRAIN TO REMAIN.
100% CD 03/2
T x
D E
S K
X
"L " D
E S
K
X
"L " D
E S
K x
D E
S K
R A
D
IA
T O
R
VACANT
UNEXCAVATED
CO0
CORR
VACANT
HAC
U P
U P
C00A
TELECOM
ROOM
RACK PROVIDED
BY OTHERS
AC-11-1CP-11-1
CU-11-1
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTA ARCHITECT/ENGINEER OF STAM
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 1
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN#
03/30/2022
B
IM
/2
.0
V A
S t C lo u d
E H
R M
I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.M
R
.r v t
/1
/2
:5
:4
P
M
11-M200
BASEMENT FLOOR -
MECHANICAL
EHRM
INFRASTRUCTURE
UPGRADES
656-21-235
RDL DJC
16305
1/4" = 1'-0"
BASEMENT FLOOR - MECHANICAL
1 0 4' 8'2'
N
KEYNOTES 1/11-M200:
1. PROVIDE NEW WALL-MOUNTED DUCTLESS COOLING UNIT.
2. PROVIDE NEW THERMOSTAT.
3. PROVIDE CONDENSATE PUMP.
4. ROUTE 1" PUMPED CONDENSATE PIPE NORTH TO EXTERIOR WALL THEN RISE
INTO HAC 104 AND DISCHARGE TO MOP SINK, APPROXIMATELY 120 FEET.
COORDINATE FINAL ROUTING IN FIELD.
5. ROUTE REFRIGERANT PIPING TO NEW AIR-COOLED CONDENSING UNIT ON
GRADE. PROVIDE CONCRETE PAD.
6. REROUTE 2" HEATING WATER SUPPLY AND RETURN PIPING AND RECONNECT
AS SHOWN.
7. REROUTE EXISTING FIRE SPRINKLER BRANCH LINE AND PROVIDE NEW
SPRINKLER HEAD.
8. PROVIDE NEW AIR COOLED CONDENSING UNIT CU-11-1 ON GRADE ABOVE.
REFER TO REFRIGERANT PIPING DETAIL 1/0-GM400 AND PAD MOUNTING
DETAIL 3/0-GM401
9. EXISTING 4" SANITARY DRAIN. PROVIDE DRIP PAN. SEE DETAIL 6/0-GM400 FOR
REQUIREMENTS. DRIP PAN TO DISCHARGE TO NEAREST FLOOR DRAIN OR AREA
WELL.
10. REFERE TO 4/0-GM401 FOR WALL PENETRATION SEALING DETAIL.
11. PROVIDE NEW CONDENSATE DRIP PAN FOR ALL CONDENSATE PIPING. SEE
DETAIL 6/0-GM400 FOR REQUIREMENTS
1. THE HVAC CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID TO FIELD VERIFY ALL EXISTING CONDITIONS WHICH MAY AFFECT THEIR
BID. THE FOLLOWING ITEMS SHALL BE VERIFIED:
A. EXACT PLACEMENT, SIZE, CAPACITY, MANUFACTURER, AND CONDITION OF ALL EXISTING HVAC EQUIPMENT WITHIN SCOPE
OF WORK, WHETHER EXPLICITLY SHOWN OR NOT.
B. SIZE AND LOCATION OF ALL EXISTING DUCTWORK.
C. SIZE AND LOCATION OF ALL EXISTING GRILLES, REGISTERS AND DIFFUSERS.
D. SIZE AND LOCATION OF ALL EXISTING THERMOSTATIC CONTROL DEVICES.
E. SIZE AND LOCATION OF ALL EXISTING PLUMBING AND HYDRONIC PIPING
2. ALL REFERENCES ON THESE DRAWINGS TO EXISTING EQUIPMENT, DUCTWORK, DIFFUSERS, THERMOSTATS AND PIPING ARE FOR REFERENCE ONLY. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY ALL THESE ITEMS PRIOR TO BID AND INCLUDE IN THEIR
BID ANY AND ALL AMOUNTS REQUIRED TO ACCOMMODATE EXISTING CONDITIONS.
3. NO ALLOWANCES WILL BE MADE AFTER THE PROJECT HAS BEEN AWARDED FOR FAILURE TO VERIFY EXISTING CONDITIONS.
4. ANY DISCREPANCIES WHICH MAY AFFECT THE CONTRACTORS BID SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER AND
ARCHITECT FOR DIRECTION.
100% CD 03/2
| 11-GI000 - BUILDING 11 COVER SHEET & SHEET INDEX |
| 11-GI101 - BASEMENT FLOOR INFECTION CONTROL & PHASING PLAN |
| 11-HA-1A - REFERENCE - BASEMENT FIRST FLOOR ASBESTOS RE-SURVEY |
| 11-HA-2A - REFERENCE - SECOND ATTIC FLOOR ASBESTOS RE-SURVEY |
| 11-AS100 - BASEMENT, FIRST, AND SECOND FLOOR PLANS |
| 11-TD100 - BASEMENT FLOOR PLAN - TELECOM - DEMOLITION |
| 11-TD110 - FIRST FLOOR PLAN - TELECOM - DEMOLITION |
| 11-TD120 - SECOND FLOOR PLAN - TELECOM - DEMOLITION |
| 11-TN100 - BASEMENT FLOOR PLAN - TELECOMMUNICATIONS |
| 11-TN110 - FIRST FLOOR PLAN - TELECOMMUNICATIONS |
| 11-TN120 - SECOND FLOOR PLAN - TELECOMMUNICATIONS |
| 11-TN200 - BASEMENT FLOOR PLAN - TELECOM - CABLE DISTANCE |
| 11-TN300 - ENLARGED PLANS - TELECOMMUNICATIONS - DEMO |
| 11-TN400 - ENLARGED PLANS - TELECOMMUNICATIONS |
| 11-E200 - BASEMENT - ELECTRICAL |
| 11-E300 - ELECTRICAL ENLARGED PLANS |
| 11-E600 - ELECTRICAL SCHEDULES |
| 11-M100 - BASEMENT DEMOLITION - MECHANICAL |
| 11-M200 - BASEMENT FLOOR - MECHANICAL |