Atch 6 - BLDG 1 - 1 of 2.pdf

PDF 14 MB Posted

Attached to
Y1AZ--EHRM Infrastructure Upgrades Construction - St. Cloud Federal contract opportunity
Solicitation number
36C77622B0035
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This document includes a federal contract opportunity solicitation for infrastructure upgrades at the St. Cloud Veterans Affairs Health Care System. The solicitation seeks a contractor to furnish all labor, materials, tools and equipment for electrical, bonding, UPS, building management system, access security, and HVAC improvements. The scope of work also includes assessing needs for and performing renovations and expansions of existing space, physical security upgrades to data center and main server room systems and infrastructure, installing a diversified path to the data center for the WAN, and accessing and upgrading the fiber infrastructure backbone campus wide within and between buildings. Hazardous materials abatement is required. All work must be completed according to specifications and contract drawings. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center Austin.

View the file

Other files for this federal contract opportunity

Other files attached to Y1AZ--EHRM Infrastructure Upgrades Construction - St. Cloud, newest first.
File Type Posted
Atch 41 - Construction Wage Rates - Stearns 7-29-22.pdf PDF
Technical Questions - LATE - St. Cloud 8-10-22.pdf PDF
01-M204 - ROOF REMODEL -MECHANICAL.pdf PDF
Atch 3 - Specifications Volume 3 - Asbestos addendum.pdf PDF
Atch 4 - General 1 of 2 addendum.pdf PDF
Atch 6 - BLDG 1 - 1 of 2 addendum.pdf PDF
Atch 8 - BLDG 2 addendum.pdf PDF
Atch 9 - BLDG 3 addendum.pdf PDF
Atch 12 - BLDG 6 addendum.pdf PDF
Atch 13 - BLDG 7 and 13 addendum.pdf PDF
Atch 27 - BLDG 96 addendum.pdf PDF
Atch 30 - BLDG 111 addendum.pdf PDF
Atch 31 - BLDG 112 addendum.pdf PDF
Specifications Addendum Information.pdf PDF
Drawings Addendum Information.pdf PDF
Atch 1 - Specifications Volume 1 addendum.pdf PDF
Atch 11 - BLDG 5 addendum.pdf PDF
Atch 17 - BLDG 11 addendum.pdf PDF
Atch 18 - BLDG 14 addendum.pdf PDF
Atch 28 - BLDG 108 addendum.pdf PDF
Atch 33 - BLDG 116 addendum.pdf PDF
Site Visit Sign-in Sheets - 6-28-22 - 6-30-22.pdf PDF
36C77622B0035 - 6-9-22.pdf PDF
Atch 16 - BLDG 10.pdf PDF
Atch 19 - BLDG 28.pdf PDF
Atch 22 - BLDG 49.pdf PDF
Atch 35 - ADHC.pdf PDF
Atch 4 - General 1 of 2.pdf PDF
Atch 5 - General 2 of 2.pdf PDF
Atch 8 - BLDG 2.pdf PDF
Atch 23 - BLDG 50.pdf PDF
Atch 24 - BLDG 51.pdf PDF
Atch 27 - BLDG 96.pdf PDF
Atch 31 - BLDG 112.pdf PDF
Atch 10 - BLDG 4.pdf PDF
Atch 34 - BLDG 118.pdf PDF
Atch 1 - Specifications Volume 1.pdf PDF
Atch 7 - BLDG 1 - 2 of 2.pdf PDF
Atch 12 - BLDG 6.pdf PDF
Atch 15 - BLDG 9.pdf PDF
Atch 18 - BLDG 14.pdf PDF
Atch 21 - BLDG 48.pdf PDF
Atch 25 - BLDG 54 and 69.pdf PDF
Atch 26 - BLDG 95 and 88.pdf PDF
Atch 28 - BLDG 108.pdf PDF
Atch 30 - BLDG 111.pdf PDF
Atch 32 - BLDG 115.pdf PDF
Atch 36 - Parking Structure.pdf PDF
Atch 40 - Limitations on Subcontracting - Construction.docx DOCX document
Atch 43 - Site Visit Instructions.pdf PDF
Show all 50

Y1AZ--EHRM Infrastructure Upgrades Construction - St. Cloud has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EXISTING FIBER - INSIDE

VFY EXIST

EXISTING FIBER - OUTSIDE

VFY EXIST

FIBER ROUTE - INSIDE

SEE TELECOM

FIBER ROUTE - OUTSIDE

SEE CIVIL

BUILDING OUTLINE

VFY EXIST

CORRIDOR OUTLINE

VFY EXIST

LEGEND

TO 8TH ST WEST ONLYTO 8TH ST EAST & WEST

44TH AVE.

TRAIL 1

TRAIL 2

TRANSFER

SWITCH

CAPACITOR

BANK (3)

SWITCH

(2)

15KV

MAIN

SW

BATT

35 KV

TO

15 KV

TRANSFORMER

35KV

FUSED

SWITCH

METER 35KV

SWITCH

GRAVEL

GRAVEL

GRAVEL

EXISTING

ROAD

CHAIN LINK FENCE

CHAIN LINK FENCE

16' GATE

GRAVEL

ELECTRICAL

SUBSTATION

G E N E R A T O R

FUEL LINES

CONDU ITS TO TU NNEL

M V

D U

C T

B A

N K

1 1 2 W

PHARMACY ADDITION

11 2 E

G E N E R A T O R

B

CORRIDOR LINK

A

C T

TR

A

IL

ER

174 s .f.

256 s .f.

185 s .f.

149 s ..f.

155 s .f.

104 s .f.

70 s. .f .

72 s .f.

110 s .f.

276 s .f.

112 s .f.

99 s .f.

57 s .f.

146 s .f.

434 s .f.

R A

MP

U P

1:

M A X

R A

MP

U P

1:

M A X

RA

M P

UP

1:2 0 M

AX

TRANSFER

SWITCH

CAPACITOR

BANK (3)

SWITCH

(2) 15KV

MAIN

SW

BATT

35 KV

TO

15 KV

TRANSFORMER

35KV

FUSED

SWITCH

METER 35KV

SWITCH

.3

TRANSFORMER

BUILD ING

#91

5,000 GAL.

UNDERGROUND

DIESEL FUEL TANK

EXISTIN G G AS SU P P LY EQ U IP M EN T TO R EM AIN

O P ER ATIO N AL DU R IN G D EM O LITIO N AN D N EW

C O N STR U C TIO N. P R O TEC T EQU IP M EN T AN D

P IP ELIN ES IN AC C O R D AN C E W ITH G AS SU P P LIER 'S

R EC O M M EN D ATIO N S

N EW G AS SU P P LY M AIN

IN TO B U ILD IN G

SP AR E

P H O N E LIN E

EXTEN D S TO

E XISTIN G

P H O N E IN

B O ILER R O O M

P ER P LAN .

SP AR E

P H O N E

LIN E TO

M ETER

TU N N EL

E XTEN D S

A D D ITIO N AL

2'- 0" U N D ER

B U ILD IN G

FUEL LINE

VENT LINE

1,000 GAL.

UNDERGROUND

DIESEL FUEL

TANK

1,000/5,000 GAL.

UNDERGROUND

DIESEL FUEL TANK

1,000 GAL.

UNDERGROUND

DIESEL FUEL TANK

1,000 GAL.

UNDERGROUND

DIESEL FUEL TANK

S 1

LIG H T

N EW G AS SU P P LY

(C O O R D IN ATE W ITH SU P P LIER )

12"D

10"D

"D

TP TP

EXIST. BUILDING

EXIST.

BUS STOP

CC

L O

O P

16"

20"

12"

3"

8"

DN

0.

0’

BIRDCAGE

B

IR

D C

A G

E

NSP ELECTRICAL

FOR HWY DEPT

T101

I.T.

CHILLER

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

VESTIBULE

DN

DN

DN

FD

DN

F B

F

B

F B

F

B

F B

F

B

SOUTH

VESTIBULE

PASS

THROUGH

LINK TO

BUILDI NG 51

6 3. 32 56

1 13 5. 35 78

PARKING

NO

PARKING

93 49

37 6

109 5

S M

O K

E B

L D

G

SMOKE

BLDG

SMOKE

BLDG

S M

O K

E B

L D

G

SMOKE

BLDG

M.H.

STOR.

SMOKE

BLDG

SMOKE

BLDG

SMOKE

BLDG

SMOKE

BLDG

SMOKE

BLDG

STOR.

BIO-

HAZ.

SAUK RIVER

GP

HOLDING POND

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

OWNER AND

CONSULTANTS:

CONTACT:

ADDRESS:

MIKE ENGMARK

ST CLOUD VA MEDICAL CENTER

4801 VETERANS DRIVE

ST. CLOUD, MN 56303

NAME:

ADDRESS:

CONTACT:

ADVANCED STRUCTURAL TECHNOLOGIES

7301 OHMS LANE; SUITE 215

EDINA, MN 55439

ZACHARY CRAIG

PHONE:

NAME:

ADDRESS:

CONTACT:

SPECIALIZED ENGINEERING SOLUTIONS

10360 ELLISON CIRCLE

OMAHA, NE 68134

KRIS BURNHAM

PHONE: 402-991-5520

NAME:

ADDRESS:

CONTACT:

PHONE:

NAME:

ADDRESS:

CONTACT:

PHONE:

NAME:

ADDRESS:

CONTACT:

PHONE:

ANDERSON ENGINEERING OF MN, LLC

13605 1ST AVE NORTH, SUITE 100

PLYMOUTH, MN 55441

IAN WEBER

763-412-4000

ARCHITECT:

ANDERSON ENGINEERING OF MN, LLC

13605 1ST AVE NORTH, SUITE 100

PLYMOUTH, MN 55441

EDWARD MARKFORT

763-412-4000

952-854-9302

SPECIALIZED ENGINEERING SOLUTIONS

10360 ELLISON CIRCLE

OMAHA, NE 68134

KRIS BURNHAM

402-991-5520

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

COVER

DATE:

APPROVED: APPROVED: PROJECTS SECTION MANAGER

APPROVED: OIT MANAGER DATE: APPROVED: ASSISTANT CHIEF ENGINEER DATE:

APPROVED: SAFETY MANAGER

APPROVED: CHIEF OF POLICE

APPROVED: PATIENT SAFETY

DATE:

DATE:

DATE: APPROVED: EMS MANAGER

APPROVED: M/O MANAGER

DATE:

DATE:

DATE:DATE:

APPROVED: MEDICAL CENTER DIRECTOR

APPROVED: PROJECT COR DATE:

APPROVED: INFECTION CONTROL NURSE DATE:

APPROVED: SERVICE LINE DIRECTOR

APPROVED: GEMS COORDINATOR DATE:

DATE:

APPROVED: NURSE EXECUTIVE

APPROVED: CHIEF OF STAFF DATE:

APPROVED: DIRECTOR FMS

APPROVED: ASSOCIATE DIRECTOR

DATE:

DATE:

DATE:

DATE:APPROVED: DATE:

APPROVED: DATE:

APPROVED: DATE:

Main Campus, St. Cloud, Minnesota St. Cloud VA Health Care System

N

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

VICINITY MAP:

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHONE: 320-252-1670

CIVIL ENGINEER:

VA COR:

TELECOMMUNICATIONS ENGINEER:

CONTACT:

ADDRESS:

JONATHAN WEST

ST CLOUD VA MEDICAL CENTER

4801 VETERANS DRIVE

ST. CLOUD, MN 56303

PHONE: 504-250-2699

PROGRAM MANAGER:

EMAIL: Jonathan.West@vciint.com

STRUCTURAL ENGINEER:

MECH/ELEC/PLUMB/FIRE ENGINEER:

C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -1

-R E

M a rk fo rt

.r v t

/2

/2

:3

:1

A

M

1-GI000

BUILDING 1 COVER SHEET &

SHEET INDEX

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

TO, EM PC, EM

16305

BUILDING 1 - EHRM INFRASTRUCTURE UPGRADES

03/30/2022

0APPROX 150' 300'75'

PROPOSED ADDITION

SHEET INDEX - BUILDING 1 - SET 1 OF 2

SHEET NO. SHEET TITLE

1-GI000 BUILDING 1 COVER SHEET & SHEET INDEX

1-GI101 BASEMENT FLOOR - INFECTION CONTROL & PHASING PLAN

1-GI111 FIRST FLOOR - INFECTION CONTROL & PHASING PLAN

1-GI120 SECOND FLOOR LIFE SAFETY PLAN

1-GI121 SECOND FLOOR - INFECTION CONTROL & PHASING PLAN

1-HA-1A REFERENCE - BASEMENT FLOOR ASBESTOS RE-SURVEY

1-HA-2A REFERENCE - FIRST FLOOR ASBESTOS RE-SURVEY

1-HA-3A REFERENCE - SECOND FLOOR ASBESTOS RE-SURVEY

1-HA-4A REFERENCE - THIRD / ATTIC FLOOR ASBESOTS RE-SURVEY

1-AS100 BASEMENT FLOOR - OVERALL PLAN

1-AS110 FIRST FLOOR - OVERALL PLAN

1-AS120 SECOND FLOOR - OVERALL PLAN

1-AS130 ATTIC FLOOR - OVERALL PLAN

1-AS400 LARGE SCALE PLANS

1-AS430 BUILDING ADDITION AND ROOF PLAN

1-AS600 ELEVATIONS, DETAILS, SCHEDULES

1-AS601 INTERIOR PARTITION TYPES AND DETAILS

1-AS602 SECTION DETAILS

1-S120 SECOND FLOOR PLAN - OVERALL

1-S130 ATTIC FLOOR PLAN - OVERALL

1-S400 LARGE SCALE PLANS

01-E100 BASEMENT DEMOLITION - ELECTRICAL

01-E101 FIRST FLOOR DEMOLITION - ELECTRICAL

01-E200 BASEMENT - ELECTRICAL

01-E201 FIRST FLOOR - ELECTRICAL

01-E202 SECOND FLOOR - ELECTRICAL

01-E204 ROOF - ELECTRICAL

01-M000 MECHANICAL COVERSHEET

01-M100 BASEMENT DEMOLITION - MECHANICAL

01-M101 FIRST FLOOR DEMOLITION - MECHANICAL

01-M102 SECOND FLOOR DEMOLITION - MECHANICAL

01-M200 BASEMENT REMODEL - MECHANICAL

01-M201 FIRST FLOOR REMODEL - MECHANICAL

01-M202 SECOND FLOOR REMODEL - MECHANICAL

01-M400 MECHANICAL DETAILS AND DIAGRAMS

01-M600 MECHANICAL SCHEDULES

SEE GENERAL AND SET 2 SHEETS FOR ADDITIONAL INFORMATION

SHEET INDEX - BUILDING 1 - SET 2 OF 2

SHEET NO. SHEET TITLE

1-TD100 BASEMENT FLOOR PLAN - TELECOM - DEMOLITION

1-TD110 FIRST FLOOR PLAN - TELECOM - DEMOLITION

1-TD120 SECOND FLOOR PLAN - TELECOM - DEMOLITION

1-TD130 THIRD FLOOR PLAN - TELECOM - DEMOLITION

1-TN100 BASEMENT FLOOR PLAN - TELECOMMUNICATIONS

1-TN110 FIRST FLOOR PLAN - TELECOMMUNICATIONS

1-TN120 SECOND FLOOR PLAN - TELECOMMUNICATIONS

1-TN130 THIRD FLOOR PLAN - TELECOMMUNICATIONS

1-TN200 BASEMENT FLOOR PLAN - TELECOM - CABLE DISTANCE

1-TN210 FIRST FLOOR PLAN - TELECOM - CABLE DISTANCE

1-TN220 SECOND FLOOR PLAN - TELECOM - CABLE DISTANCE

1-TN230 THIRD FLOOR PLAN - TELECOM - CABLE DISTANCE

1-TN300 ENLARGED PLANS - TELECOMMUNICATIONS - DEMO

1-TN400 ENLARGED PLANS - TELECOMMUNICATIONS

1-TN401 ENLARGED PLANS - TELECOMMUNICATIONS

1-TN402 ENLARGED PLANS - TELECOMMUNICATIONS

1-TN403 ENLARGED PLANS - TELECOMMUNICATIONS

SEE GENERAL AND SET 1 SHEETS FOR ADDITIONAL INFORMATION

52.1183

36.0000

X

C O

N F

E R

E N

C E

T A

B

LE

W / 1

E

R G

O C

H A

IR

S

PROXMIA

48" FLAT

SCREEN

TELEVISION

AEC

CB1

DACC

GAC

LCC

CR

4D

BATH 4C

LOCKER

MALE

C0C

CORRIDOR

PHONE

LOBBY

HAC

HEALTH

OCC.

HAC

LOCKER

4A

LOCKER

FEMALE

4B

BATH

STOR

STAIR

12A

ELECTRICAL

MECHANICAL

MECHANICAL

ELECTRICAL

C0N

CORR

18A

MECHANICAL

19A

MECH

ELEV

MECAHNICAL

HEATER

EXAM ROOM

RADIOLOGY

SOUND

ULTRA

EXAM

32A

BATH

STAIR

OFFICE

X-RAY 1

UNEXCAVATED35

MECH

PROCESSING

FILM

37A

EQUIP

X-RAY 2

WAITING

CHANGE 38A

BATH

CLOSET

33A

EQUIP

OFFICE29

STOR

C0W

CORR

30A

MECH

STAIR

OFFICE

5A

OFFICE

PHYSICIAN

5C

CORR

5B

MECH

OFFICE

5D

ROOM

MECH

C0-B2

CORR

A01

HAC

A02

EQUIP

ELEV

C0-B1

CORR

A06

ELECTRICAL

A05A

MECHANICAL

A05B

STORAGE

ASB

STAIR

C0-B4

CORR

C0-B3

CORR

A10

SPACE

MECH.

E-A1

ELEV

A03

PHONE

36D

CONTROL

36E

EQUIP

36C

CT SCAN

CORRIDOR

36B

TOILET

36A

CHANGE

IMAGING

RT CLINIC

ABG LAB/

PFT LAB

HAC

LAB CLASSROOM

APAP/CPAP

EKG LAB

EDUCATION

RT CLINIC/

SOILED

CP

WORKROOM

STAFF

STORAGE

PROSTHETICS

OFFICE

LINEN

CLEAN

A60

OFFICE

A61

OFFICE

A62

OFFICE

A59

STORAGE

SUPPLY

A63

HEMA/COAG

CHEM/URINE/

A67

LOUNGE

CONF./

A68

BANK

BLOOD

A64

MICROBIOLOGY

A56

RECEP.

A58A

PHLEB

A58B

PHLEB

A58C

PHLEB

A58H

PHLEB

A58I

PHLEB

A58J

PHLEB

A58G

PHLEB

A58D

PHLEB

A58K

PHLEB

A58F

PHLEB

A58E

PHLEB

A57A

TOILET

A57B

TOILET

A57C

TOILET

A57C

COLLECTION

A66

LOCKER

A65

TOILET

C0-B1

WAITING

C0-H1

CORR

C0-H5

CORR

C0-C2

CORR C0-H2

CORR

C0-H4

CORR

C0-H3

CORR

A58

PHLEB

A58

PHLEB

C0-H6

CORR

C0-H7

CORR

2C

RECEPTION

WAITING

2A

MEN 2B

WOMEN

53A

STOR

E-01

ELEV

E-02

ELEV

16A

ROOM

MG

10B

HEALTH

OCC.

10A

HEALTH

OCC.

HEALTH

OCC.

30B

OFFICE

30C

OFFICE

8D

EQUIP

8I

MECHANICAL

8A

MRI

7F

INTAKE

7E

INTAKE

7D

HAC

7C

TOILET

7B

CHANGING

7A

CHANGING

COE

CORRIDOR

7G

FOYER

8H

VESTIBULE

8B

CONTROL

8C

HALL

8E

LINEN

8F

SOIL

8G

CLEAN

L

R

A05C

TELECOM

ROOM

005F

TELECOM

ROOM

7'-11 3/4"

005E

LOCKER

ZONE 1B

CONSTRUCTION / ICRA BARRIER

ZONE 1A

CONSTRUCTION / ICRA BARRIER

LIMITS OF CONSTRUCTION

INFECTION CONTROL RISK ASSESSMENT (ICRA) LEGEND

LIMITS OF CONSTRUCTION

1 HOUR FIRE RATED ICRA / CONSTRUCTION BARRIER

LOCATION, AND DOOR, WHERE SHOWN

TEMPORARY NON-RATED (PLASTIC SHEETING) CONSTRUCTION BARRIER

LOCATION, WHERE APPROVED BY THE VA FOR USE IN RISK TYPE B.

UPGRADE TO 1 HOUR RATED PARTITION WHEN DIRECTED BY THE VA

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -1

-R E

M a rk fo rt

.r v t

/2

/2

:1 :2

P

M

1-GI101

BASEMENT FLOOR -

INFECTION CONTROL &

PHASING PLAN

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM BMW

16305

03/30/2022

1/8" = 1'-0"

BASEMENT FLOOR - CONST BARRIER PLAN

ROOM ICRA SCHEDULE

LEVEL

ROOM

NO. ROOM NAME CAI BLDG NAME / FUNCTION CONSTRUCTION PROJECT ACTIVITY INFECTION CONTROL RISK GROUP CONTROL PROCEDURE CLASS

BASEMENT 005C CORRIDOR AMB CARE / MEDICAL TYPE D GROUP 1 CLASS III/IV

BASEMENT 005D MECH AMB CARE / MEDICAL TYPE D GROUP 1 CLASS III/IV

BASEMENT 005E LOCKER AMB CARE / MEDICAL TYPE D GROUP 1 CLASS III/IV

BASEMENT 005F TELECOM ROOM AMB CARE / MEDICAL TYPE D GROUP 1 CLASS III/IV

BASEMENT A003 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 2 CLASS II

BASEMENT A05A MECH AMB CARE / MEDICAL TYPE C GROUP 2 CLASS III

BASEMENT A05C TELECOM ROOM AMB CARE / MEDICAL TYPE C GROUP 1 CLASS II

FIRST FLOOR 127 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 2 CLASS II

FIRST FLOOR A101 TELECOM ROOM AMB CARE / MEDICAL TYPE C GROUP 2 CLASS III

SECOND FLOOR 229 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 2 CLASS II

SECOND FLOOR A200 TELECOM ROOM AMB CARE / MEDICAL TYPE D GROUP 2 CLASS IV

SECOND FLOOR A216 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 2 CLASS II

SECOND FLOOR A225 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 4 CLASS III/IV

SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.

FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.

SEQUENCE OF EVENTS - ZONE 1A

• SELECTIVE UPGRADE TO EXISTING INFORMATION TECHNOLOGY TO ENABLE

BUILDING TOTAL UPGRADE PROCESS

• INITIAL ICRA AND ILSM

• CONSTRUCTION OF BARRIER IN ONE NIGHT SHIFT. BARRIER INCLUDES DOOR

AND PARTITION TO BECOME PERMANENT CONSTRUCTION OF ROOM

• CONSTRUCT ROOMS AS DIRECTED, SEE ASSOCIATED DRAWINGS FROM

STRUCTURAL, ELECTRICAL, MECHANICAL, TELECOM, AND FINISHES

• INSTALL TEMPORARY PROTECTION AND CONDUCT SELECTIVE DEMOLITION TO

ENABLE UPGRADES

• INSTALL COMMON CABLE INFRASTRUCTURE

• CONSTRUCT COMMUNICATION BACKBONE

• INSTALL CAT 6A

• DECOMMISSION EXISTING NON-EHRM INFORMATION TECHNOLOGY ROOMS

SEQUENCE OF EVENTS - ZONE 1B

• SELECTIVE UPGRADE TO EXISTING INFORMATION TECHNOLOGY TO ENABLE

BUILDING TOTAL UPGRADE PROCESS

• INITIAL ICRA AND ILSM

• CONSTRUCTION OF BARRIER IN ONE NIGHT SHIFT AT ENTRY TO CORRIDOR

AND NEXT TO MECH 5B

• DEMOLISH

• CONSTRUCT ROOMS AS DIRECTED, SEE ASSOCIATED DRAWINGS FROM

STRUCTURAL, ELECTRICAL, MECHANICAL, TELECOM, AND FINISHES

• INSTALL TEMPORARY PROTECTION AND CONDUCT SELECTIVE DEMOLITION TO

ENABLE UPGRADES

• INSTALL COMMON CABLE INFRASTRUCTURE

• CONSTRUCT COMMUNICATION BACKBONE

• INSTALL CAT 6A

• DECOMMISSION EXISTING NON-EHRM INFORMATION TECHNOLOGY ROOMS

SUGGESTED SEQUENCE. FINAL INSTALLATION SEQUENCE TO BE MADE AT A LATER DATE.

FRIDGE

24X26

SCALE

COPIER

PRINTER

F R

O N

T

ENTRY

128A

RECEPTION

STAIR120

WAITING

STAIR

MAA

REGISTRATION

REGISTRATION168

EXAM

EXAM

STOR

WHCHR

LOBBY

ELEV

C1NC

CORR

127A

PHONE

MECH

128B

V.I.C.

128C

OUT

CHECK

STOR

C1WI

CORR

EXAM

EXAM

EXAM

EXAM

STATION

NURSE

173A

MED

EXAM

EXAM165

NURSING

EXAM

EXAM

NURSING

160B

BATH

INTAKE

PROCEDURE

SPECIAL

160A

UTILITY

CLEAN

173B

INTAKE

C1WH

CORR

C1WG

CORR

ELEC

MECH

EXAM

INT

C1WF

CORR

EXAM

INT

EXAM

INT

EXAM

INT

EXAM

INT

EXAM

INT

STAIR

C1WJ

CORR

COPY

CONSULT

PHARM.

STAIR

C1WA

CORR

MALE

FEMALE

CHASE

WAITING

BATH

UTILITY

CLEAN

EXAM

EXAM

CONSULT

PHARM.

C1WD

CORR

EXAM

EXAM

UTILITY

CLEAN

CHART

NURSE/

OFFICE

NURSE

EXAM

EXAM

C1WB

CORR

EXAM

EXAM

EXAM

NURSING

EXAM

WAITING

152A

MED

C1WE

CORR

C1WC

CORR

ROOF

A111

VEST

TRIAGE

A110

OFFICE A109

EXAM

E-A1

ELEV

A-1

STAIR A108

STAFF

A107A

DICTATION

A107B

CLOSET

C0-2

CORR

A106

HAC A105

CONSULT

PHARM

A104

NURSING

A103

NURSING

C0-1

CORRIDOR

A127A

CHECK-OUT

A126

INTAKE

A125

EXAM

CO-5

CORR

A124

EXAM

A123

EXAM

A122

EXAM

A121

OFFICE

A120

UTIL

SOILED

A118

ALCOVE

NURSE

A117

MED

CO-3

CORRIDOR

A112

EXAM

A113

EXAM

A116

UTILITY

SOILED

A119

EXAM

C0-4

CORRIDOR

A114

EXAM

A115

EXAM

AS1

STAIR

A141

STORAGE

EQUIP.

A140

EXAM

A139

EXAM

A138

EXAM

A137

DICTATION

A136

EXAM

A135

EXAM

A134

OUT

CHECK

A133

PASSAGE

STAFF A132

STORAGE

CO-7

CORRIDOR

A142

STORAGE

CLEAN

A143

EXAM

A144

EXAM

A145

EXAM CO-3

CORR

A146

EXAM

A147

STORAGE

A127D

ROOM

MED A127C

STATION

NURSE

A127B

IN

CHECKCO-6

CORR

A131

MEN A130

CHASE

A129

WAITING

A128

WAITING

A102B

CHASE

A102A

WOMEN

A101

COMM

TELE-

A112A

LINEN

REGISTRATION

INTAKE

INTAKE

STAFF

111A

M.O.D.

111C

EQUIPMENT

SUPPLY

111D

PURPOSE

MULTI

111B

TOILET

WAITING

101A

TOILET

UNISEX

HAC

UTILITIES

CLEAN

UTILITIES

SOILED

LOCKERS

MED

STATION

NURSE

108A

TELEMETRY

108B

TELEMETRY

108C

TOILET

108D

TELEMETRY

108E

TELEMETRY

109C

TELEMETRY

PROCEDURE/

109B

TELEMETRY

109A

TELEMETRY

109D

TOILET

AMBULANCE

C1EC

CORRIDOR

C1EA

CORRIDOR

NOUR

C1ED

CORRIDOR

111E

CAMERAS

HOLDING/

111F

ANTE

HOLDING/

TOILET

C1EB

CORRIDOR

TOILET

STAFF

E-01

ELEV

E-02

ELEV

A117A

UNISEX

ROOF

FLAT

DECONTAM

ZONE 1D

INFECTION CONTROL RISK ASSESSMENT (ICRA) LEGEND

LIMITS OF CONSTRUCTION

1 HOUR FIRE RATED ICRA / CONSTRUCTION BARRIER

LOCATION, AND DOOR, WHERE SHOWN

TEMPORARY NON-RATED (PLASTIC SHEETING) CONSTRUCTION BARRIER

LOCATION, WHERE APPROVED BY THE VA FOR USE IN RISK TYPE B.

UPGRADE TO 1 HOUR RATED PARTITION WHEN DIRECTED BY THE VA

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -1

-R E

M a rk fo rt

.r v t

/2

/2

:1 :4

P

M

1-GI111

FIRST FLOOR - INFECTION

CONTROL & PHASING PLAN

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM BMW

16305

03/30/2022

1/8" = 1'-0"

FIRST FLOOR - CONST BARRIER PLAN

ROOM ICRA SCHEDULE

LEVEL

ROOM

NO. ROOM NAME CAI BLDG NAME / FUNCTION CONSTRUCTION PROJECT ACTIVITY INFECTION CONTROL RISK GROUP CONTROL PROCEDURE CLASS

BASEMENT 005C CORRIDOR AMB CARE / MEDICAL TYPE D GROUP 1 CLASS III/IV

BASEMENT 005D MECH AMB CARE / MEDICAL TYPE D GROUP 1 CLASS III/IV

BASEMENT 005E LOCKER AMB CARE / MEDICAL TYPE D GROUP 1 CLASS III/IV

BASEMENT 005F TELECOM ROOM AMB CARE / MEDICAL TYPE D GROUP 1 CLASS III/IV

BASEMENT A003 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 2 CLASS II

BASEMENT A05A MECH AMB CARE / MEDICAL TYPE C GROUP 2 CLASS III

BASEMENT A05C TELECOM ROOM AMB CARE / MEDICAL TYPE C GROUP 1 CLASS II

FIRST FLOOR 127 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 2 CLASS II

FIRST FLOOR A101 TELECOM ROOM AMB CARE / MEDICAL TYPE C GROUP 2 CLASS III

SECOND FLOOR 229 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 2 CLASS II

SECOND FLOOR A200 TELECOM ROOM AMB CARE / MEDICAL TYPE D GROUP 2 CLASS IV

SECOND FLOOR A216 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 2 CLASS II

SECOND FLOOR A225 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 4 CLASS III/IV

SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.

FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.

A -O

-V

DN

UP

DN

UP

A200

TELECOM

ROOM

6' -1

/4

16'-0"

9'-8" 7'

-6

E A

HE

TO EXIT ACCESS

FE

127' - 9"

E A

HE

LIFE SAFETY SYMBOLS

SMOKE TIGHT

ASSEMBLY

1 HOUR FIRE

BARRIER

2 HOUR FIRE

BARRIER

3 HOUR FIRE

BARRIER

1 HOUR FIRE &

SMOKE BARRIER

2 HOUR FIRE &

SMOKE BARRIER

3 HOUR FIRE &

SMOKE BARRIER

HE

TRAVEL DISTANCE

100'-10"

TRAVEL DISTANCE

EA

EDEXIT EXIT

HORIZONTAL EXIT

EXIT DISCHARGE

EXIT ACCESS

FIRE

EXTINGUISHER

FE

FIRE

EXTINGUISHER

CABINET

FEC

LIMITS OF

CONSTRUCTION

SMOKE

COMPARTMENT

BOUNDARY

HEALTH CARE

SUITE

NOTE: NOT ALL SYMBOLS MY BE USED ON EACH PLAN

OCCUPANCY

SEPARATION

SHAFT

ADJACENT SYMBOLS SHOW PARTITION RATING AND

DAMPER REQUIREMENTS

HAZARDOUS USE

ADJACENT SYMBOLS SHOW PARTITION RATING.

OPENINGS REQUIRE CLOSER & LATCH

EXIT PASSAGEWAY

RATE AS STAIR

ALL OPENINGS TO BE RATED AS STAIR SHAFT

CORRIDOR

WALLS TO LIMIT THE TRANSFER OF SMOKE

ADJUNCT CORRIDOR or PSYCHIATRIC AREA or CONSTRUCTED WITH MIN. 4'-0" CLEAR

WITH (PER CHAPTER 19)

AREA SEPARATIONS / FIRE WALLS

TYPE(S) OF CONSTRUCTION

CONSTRUCTION TYPE(S)

SEE LIFE SAFETY PLANS

(IBC CHAPTER 6) IBC II-A

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -1

-R E

M a rk fo rt

.r v t

/2

/2

:1 :0

P

M

1-GI120

SECOND FLOOR LIFE SAFETY

PLAN

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM BMW

16305

03/30/2022

1/8" = 1'-0"

SECOND FLOOR LIFE SAFETY PLAN

N

0 8' 16'4'

VAO

VAO

VAO

VAO

OAV

O

A

V

O AV

OAV

O AV

O

A

V

O

A

V

OAV

DICT.

A -O

-V

STAIR

210A

CORRIDOR

C2EA

STAIR

EXAM

CORRIDOR

C2C

UTILITY

229A

PHONE

ELEVATOR

LOBBY

CORRIDOR

C2N

CORRIDOR

INTAKE

230A

INTAKE

230B

TOILET

230C

EXAM

CORRIDOR

C2W

CORRIDOR

C2CA

SCOPE

STORAGE

STAFF

LOCKER

NURSE

STATION

237A

RECOVERY

WHEELCHAIR

TOILET

MEDS

PATIENT

INSTR

TOILET

235A

PROCTO

PROCEDURE

HOLDING

SOILED

UTILITY

ENDOSCOPY

PROCEDURE

SOILED

LINEN

ENDOSCOPY

PROCEDURE

STORAGE

CORRIDOR

C2WC

CORRIDOR

C2WB

TOILET

UROLOGY

PROCEDURE

TEST/

TOILET

UROLOGY

PROCEDURE

CORRIDOR

C2WA

STAIR

MINOR

PROCEDURE

MINOR

PROCEDURE

HAC

243A

STAIR

243B

CALL

CENTER

NURSING

SKIN

INTEGRITY

210F

EXAM

210E

EXAM

210C

EXAM

210B

EXAM

210A

WAITING

LINEN

210D

CORRIDOR

C2EC

CORRIDOR

C2ED

CORRIDOR

C2EB

EXAM

215D

EXAM

215C

EXAM

215B

EXAM

215A

STORAGE

HAC

PAC

TEL-MED

INTAKE

STAFF

STAFF

LOCKERS

221A

CLEAN

SOILED

BCG

MANAGER

OFFICE

STOR.

WAITING

STAFF

221WAITING

202RECEPTION

PATIENT

TOILET

STAFF

TOILET

ANESTHESIA

OFFICE

A233

ANESTHESIA

WORKROOM

A232

EQUIPMENT

ROOM

A231

SOILED

A230

LOUNGE

A229

CORRIDOR

C2-A7

HALL

C2-A6

HALL

C2-A5

O.R.

A223 O.R.

A222 O.R.

A219

RECOVERY

A213A

CLEAN

A225

HALL

C2-A8

CORRIDOR

C2-A9

SUB

STERILE

A224

CLEAN

CORE

A218

SUB

STERILE

A220

STORAGE

A221

HALL

C2-A4

HALL

C2-A2

HAC

A226

HALL

C2-A11

RAMP

C2-A12

ELECT.

A216

ELEV.

LOBBY

C2-A12

STERILE

SUPPLIES

A217

RECOVERY

A214

RECOVERY

A213B

RECOVERY

A213C

RECOVERY

ISOLATION

A215

HAC

A203

INTAKE

A204

INTAKE

A205

INTAKE

A208

INTAKE

A207

NURSE

A210

HALL

C2-A3

SCHEDULING

A201

HEAD

NURSE

A202

WOMEN'S

LOCKER

A227

SOILED

A212

CLEAN

A211

STAFF

TOILET

A209

PATIENT

TOILET

A206

MEDS

A210A

NOUR

A210B

RAMP

C2-A1

SURGERY

RECEPTION

225A

SURGERY

WAITING

CONSULT

STAIRS

A234

DN

UP

DN

UP

A200

TELECOM

ROOM

ALIGN

(60" MIN CLR)

+/- 5' -3"

LIMITS OF CONSTRUCTION

ZONE 1C

CONSTRUCTION / ICRA BARRIER

INFECTION CONTROL RISK ASSESSMENT (ICRA) LEGEND

LIMITS OF CONSTRUCTION

1 HOUR FIRE RATED ICRA / CONSTRUCTION BARRIER

LOCATION, AND DOOR, WHERE SHOWN

TEMPORARY NON-RATED (PLASTIC SHEETING) CONSTRUCTION BARRIER

LOCATION, WHERE APPROVED BY THE VA FOR USE IN RISK TYPE B.

UPGRADE TO 1 HOUR RATED PARTITION WHEN DIRECTED BY THE VA

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -1

-R E

M a rk fo rt

.r v t

/2

/2

:1 :3

P

M

1-GI121

SECOND FLOOR - INFECTION

CONTROL & PHASING PLAN

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM BMW

16305

03/30/2022

1/8" = 1'-0"

SECOND FLOOR - CONST BARRIER PLAN

ROOM ICRA SCHEDULE

LEVEL

ROOM

NO. ROOM NAME CAI BLDG NAME / FUNCTION CONSTRUCTION PROJECT ACTIVITY INFECTION CONTROL RISK GROUP CONTROL PROCEDURE CLASS

BASEMENT 005C CORRIDOR AMB CARE / MEDICAL TYPE D GROUP 1 CLASS III/IV

BASEMENT 005D MECH AMB CARE / MEDICAL TYPE D GROUP 1 CLASS III/IV

BASEMENT 005E LOCKER AMB CARE / MEDICAL TYPE D GROUP 1 CLASS III/IV

BASEMENT 005F TELECOM ROOM AMB CARE / MEDICAL TYPE D GROUP 1 CLASS III/IV

BASEMENT A003 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 2 CLASS II

BASEMENT A05A MECH AMB CARE / MEDICAL TYPE C GROUP 2 CLASS III

BASEMENT A05C TELECOM ROOM AMB CARE / MEDICAL TYPE C GROUP 1 CLASS II

FIRST FLOOR 127 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 2 CLASS II

FIRST FLOOR A101 TELECOM ROOM AMB CARE / MEDICAL TYPE C GROUP 2 CLASS III

SECOND FLOOR 229 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 2 CLASS II

SECOND FLOOR A200 TELECOM ROOM AMB CARE / MEDICAL TYPE D GROUP 2 CLASS IV

SECOND FLOOR A216 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 2 CLASS II

SECOND FLOOR A225 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 4 CLASS III/IV

SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.

FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.

SEQUENCE OF EVENTS - ZONE 1C

• SELECTIVE UPGRADE TO EXISTING INFORMATION TECHNOLOGY TO ENABLE

BUILDING TOTAL UPGRADE PROCESS

• INITIAL ICRA AND ILSM

• CONSTRUCTION OF BARRIER IN ONE NIGHT SHIFT. BARRIER INCLUDES DOOR

AND PARTITION TO BECOME PERMANENT CONSTRUCTION OF ROOM

• CONSTRUCT ROOMS AS DIRECTED, SEE ASSOCIATED DRAWINGS FROM

STRUCTURAL, ELECTRICAL, MECHANICAL, TELECOM, AND FINISHES

• INSTALL TEMPORARY PROTECTION AND CONDUCT SELECTIVE DEMOLITION TO

ENABLE UPGRADES

• INSTALL COMMON CABLE INFRASTRUCTURE

• CONSTRUCT COMMUNICATION BACKBONE

• INSTALL CAT 6A

• DECOMMISSION EXISTING NON-EHRM INFORMATION TECHNOLOGY ROOMS

-ASBESTOS-CONTAINING FIRE DOOR

-ASBESTOS-CONTAINING HARD FITTINGS ON FIBERGLASS

-ASBESTOS-CONTAMINATED SOIL IN CRAWLSPACE

-ASBESTOS-CONTAINING 12"X12" FLOOR TILE AND MASTIC

CASTLE HILL ASSOCIATES, LLC.

N

S

W

E

LEGEND

BUILDING #1 - BASEMENT FLOOR PLAN

-POSITIVE SAMPLE LOCATION

-SAMPLE LOCATION

-ASBESTOS-CONTAINING BLACK TAR ON RAIN LEADER

-ASBESTOS-CONTAINING 9"X9" FLOOR TILE AND MASTIC

-ASBESTOS-CONTAINING MASTIC UNDER 9"X9" FLOOR TILE

-ASBESTOS-CONTAINING HARD FITTINGS ON FIBERGLASS

-ASBESTOS-CONTAINING PIPE INSULATION (VERTICAL RISERS)

-ASBESTOS-CONTAINING CAULK ON BRICK WALL

CASTLE HILL ASSOCIATES, LLC.

LEGEND

BUILDING #1 - FIRST FLOOR PLAN

N

S

W E

-ASBESTOS-CONTAINING PIPE INSULATION (VERTICAL RISERS)

-ASBESTOS-CONTAINING 12"X12" FLOOR TILE AND MASTIC

-ASBESTOS-CONTAINING MASTIC UNDER 9"X9" FLOOR TILE

CASTLE HILL ASSOCIATES, LLC.

N

S

W E

LEGEND

BUILDING #1 - SECOND FLOOR PLAN

-ASBESTOS-CONTAINING HARD FITTINGS ON FIBERGLASS

CASTLE HILL ASSOCIATES, LLC.

N

S

W E

LEGEND BUILDING #1 - THIRD FLOOR PLAN

BUILDING #1 - THIRD FLOOR ATTIC ROOF

36.0000

X

C O

N F

E R

E N

C E

T A

B

LE

W / 1

E

R G

O C

H A

IR

S

PROXMIA

48" FLAT

SCREEN

TELEVISION

AEC

CB1

DACC

GAC

LCC

CR

4D

BATH 4C

LOCKER

MALE

C0C

CORRIDOR

PHONE

LOBBY

HAC

HEALTH

OCC.

HAC

LOCKER

4A

LOCKER

FEMALE

4B

BATH

STOR

STAIR

12A

ELECTRICAL

MECHANICAL

MECHANICAL

ELECTRICAL

C0N

CORR

18A

MECHANICAL

19A

MECH

ELEV

MECAHNICAL

HEATER

EXAM ROOM

RADIOLOGY

SOUND

ULTRA

EXAM

32A

BATH

STAIR

OFFICE

X-RAY 1

UNEXCAVATED35

MECH

PROCESSING

FILM

37A

EQUIP

X-RAY 2

WAITING

CHANGE 38A

BATH

CLOSET

33A

EQUIP

OFFICE29

STOR

C0W

CORR

30A

MECH

STAIR

OFFICE

5A

OFFICE

PHYSICIAN

5C

CORR

5B

MECH

OFFICE

5D

ROOM

MECH

C0-B2

CORR

A01

HAC

A02

EQUIP

ELEV

C0-B1

CORR

A06

ELECTRICAL

A05A

MECHANICAL

A05B

STORAGE

ASB

STAIR

C0-B4

CORR

C0-B3

CORR

A10

SPACE

MECH.

E-A1

ELEV

A03

PHONE

36D

CONTROL

36E

EQUIP

36C

CT SCAN

CORRIDOR

36B

TOILET

36A

CHANGE

IMAGING

RT CLINIC

ABG LAB/

PFT LAB

HAC

LAB CLASSROOM

APAP/CPAP

EKG LAB

EDUCATION

RT CLINIC/

SOILED

CP

WORKROOM

STAFF

STORAGE

PROSTHETICS

OFFICE

LINEN

CLEAN

A60

OFFICE

A61

OFFICE

A62

OFFICE

A59

STORAGE

SUPPLY

A63

HEMA/COAG

CHEM/URINE/

A67

LOUNGE

CONF./

A68

BANK

BLOOD

A64

MICROBIOLOGY

A56

RECEP.

A58A

PHLEB

A58B

PHLEB

A58C

PHLEB

A58H

PHLEB

A58I

PHLEB

A58J

PHLEB

A58G

PHLEB

A58D

PHLEB

A58K

PHLEB

A58F

PHLEB

A58E

PHLEB

A57A

TOILET

A57B

TOILET

A57C

TOILET

A57C

COLLECTION

A66

LOCKER

A65

TOILET

C0-B1

WAITING

C0-H1

CORR

C0-H5

CORR

C0-C2

CORR C0-H2

CORR

C0-H4

CORR

C0-H3

CORR

A58

PHLEB

A58

PHLEB

C0-H6

CORR

C0-H7

CORR

2C

RECEPTION

WAITING

2A

MEN 2B

WOMEN

53A

STOR

E-01

ELEV

E-02

ELEV

16A

ROOM

MG

10B

HEALTH

OCC.

10A

HEALTH

OCC.

HEALTH

OCC.

30B

OFFICE

30C

OFFICE

8D

EQUIP

8I

MECHANICAL

8A

MRI

7F

INTAKE

7E

INTAKE

7D

HAC

7C

TOILET

7B

CHANGING

7A

CHANGING

COE

CORRIDOR

7G

FOYER

8H

VESTIBULE

8B

CONTROL

8C

HALL

8E

LINEN

8F

SOIL

8G

CLEAN

A05C

TELECOM

ROOM

005F

TELECOM

ROOM

'-0

12'-0"

'-8

/4

4'-9 1/4"

'-6

3'-3"

10'-0"

7'-11 3/4"

6'-0"

1' -6

3'-0"

3' -0

1-AS400

1-AS400

005E

LOCKER

A05C

5F

5E

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -1

-R E

M a rk fo rt

.r v t

/2

/2

:1 :1

P

M

1-AS100

BASEMENT FLOOR - OVERALL

PLAN

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

TO, EM PC, EM

16305

03/30/2022

1/8" = 1'-0"

BASEMENT FLOOR - OVERALL PLAN

N

0 8' 16'4'

_SHEET NOTES

1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL

INFORMATION, LIFE SAFETY, ICRA, AND PHASING

2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE

CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING

CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO

THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND

ENGINEERS.

3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS

AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH

OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND

ENGINEERS.

4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND

PLUMBING DRAWINGS FOR ADDITIONAL DEMOLITION AND

CONSTRUCTION REQUIREMENTS.

5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE) WITH

WALL MOUNT BRACKET AND CODE REQUIRED SIGNAGE SHALL BE

PROVIDED WITHIN TELECOM ROOMS.

SCALE

UPDATED 9/1/06

BUILDING 1 FIRST FLOOR

COPIER

PRINTER

F R

O N

T

ENTRY

128A

RECEPTION

STAIR120

WAITING

STAIR

MAA

REGISTRATION

REGISTRATION168

EXAM

EXAM

STOR

WHCHR

LOBBY

ELEV

C1NC

CORR

127A

PHONE

MECH

128B

V.I.C.

128C

OUT

CHECK

STOR

C1WI

CORR

EXAM

EXAM

EXAM

EXAM

STATION

NURSE

173A

MED

EXAM

EXAM165

NURSING

EXAM

EXAM

NURSING

160B

BATH

INTAKE

PROCEDURE

SPECIAL

160A

UTILITY

CLEAN

173B

INTAKE

C1WH

CORR

C1WG

CORR

ELEC

MECH

EXAM

INT

C1WF

CORR

EXAM

INT

EXAM

INT

EXAM

INT

EXAM

INT

EXAM

INT

STAIR

C1WJ

CORR

COPY

CONSULT

PHARM.

STAIR

C1WA

CORR

MALE

FEMALE

CHASE

WAITING

BATH

UTILITY

CLEAN

EXAM

EXAM

CONSULT

PHARM.

C1WD

CORR

EXAM

EXAM

UTILITY

CLEAN

CHART

NURSE/

OFFICE

NURSE

EXAM

EXAM

C1WB

CORR

EXAM

EXAM

EXAM

NURSING

EXAM

WAITING

152A

MED

C1WE

CORR

C1WC

CORR

ROOF

A111

VEST

TRIAGE

A110

OFFICE A109

EXAM

E-A1

ELEV

A-1

STAIR A108

STAFF

A107A

DICTATION

A107B

CLOSET

C0-2

CORR

A106

HAC A105

CONSULT

PHARM

A104

NURSING

A103

NURSING

C0-1

CORRIDOR

A127A

CHECK-OUT

A126

INTAKE

A125

EXAM

CO-5

CORR

A124

EXAM

A123

EXAM

A122

EXAM

A121

OFFICE

A120

UTIL

SOILED

A118

ALCOVE

NURSE

A117

MED

CO-3

CORRIDOR

A112

EXAM

A113

EXAM

A116

UTILITY

SOILED

A119

EXAM

C0-4

CORRIDOR

A114

EXAM

A115

EXAM

AS1

STAIR

A141

STORAGE

EQUIP.

A140

EXAM

A139

EXAM

A138

EXAM

A137

DICTATION

A136

EXAM

A135

EXAM

A134

OUT

CHECK

A133

PASSAGE

STAFF A132

STORAGE

CO-7

CORRIDOR

A142

STORAGE

CLEAN

A143

EXAM

A144

EXAM

A145

EXAM CO-3

CORR

A146

EXAM

A147

STORAGE

A127D

ROOM

MED A127C

STATION

NURSE

A127B

IN

CHECKCO-6

CORR

A131

MEN A130

CHASE

A129

WAITING

A128

WAITING

A102B

CHASE

A102A

WOMEN

A101

COMM

TELE-

A112A

LINEN

REGISTRATION

INTAKE

INTAKE

STAFF

111A

M.O.D.

111C

EQUIPMENT

SUPPLY

111D

PURPOSE

MULTI

111B

TOILET

WAITING

101A

TOILET

UNISEX

HAC

UTILITIES

CLEAN

UTILITIES

SOILED

LOCKERS

MED

STATION

NURSE

108A

TELEMETRY

108B

TELEMETRY

108C

TOILET

108D

TELEMETRY

108E

TELEMETRY

109C

TELEMETRY

PROCEDURE/

109B

TELEMETRY

109A

TELEMETRY

109D

TOILET

AMBULANCE

C1EC

CORRIDOR

C1EA

CORRIDOR

NOUR

C1ED

CORRIDOR

111E

CAMERAS

HOLDING/

111F

ANTE

HOLDING/

TOILET

C1EB

CORRIDOR

TOILET

STAFF

E-01

ELEV

E-02

ELEV

A117A

UNISEX

ROOF

FLAT

DECONTAM

BUILDING 1 ANNEX LOCATION

BUILDING 1 MAIN ENTRANCE

KIOSK

KIOSK

9' -6

/4

14'-0 3/4"

'-1

3/

4"

5'-5 1/4"

'-6

1-AS400

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -1

-R E

M a rk fo rt

.r v t

/2

/2

:1 :4

P

M

1-AS110

FIRST FLOOR - OVERALL PLAN

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

TO, EM PC, EM

16305

03/30/2022

N

0 8' 16'4'

_SHEET NOTES

1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL

INFORMATION, LIFE SAFETY, ICRA, AND PHASING

2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE

CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING

CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO

THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND

ENGINEERS.

3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS

AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH

OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND

ENGINEERS.

4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND

PLUMBING DRAWINGS FOR ADDITIONAL DEMOLITION AND

CONSTRUCTION REQUIREMENTS.

5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE) WITH

WALL MOUNT BRACKET AND CODE REQUIRED SIGNAGE SHALL BE

PROVIDED WITHIN TELECOM ROOMS.

1/8" = 1'-0"1

FIRST FLOOR - OVERALL PLAN

A -O

-V

DN

UP

DN

UP

A200

TELECOM

ROOM

6' -1

/4

16'-0"

9'-8"

7' -6

5'-6"

9' -5

1-AS430

ALIGN

1-AS600

1-AS600

A200

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -1

-R E

M a rk fo rt

.r v t

/2

/2

:1 :1

P

M

1-AS120

SECOND FLOOR - OVERALL

PLAN

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

TO, EM PC, EM

16305

03/30/2022

1/8" = 1'-0"1

SECOND FLOOR - OVERALL PLAN

N

0 8' 16'4'

_SHEET NOTES

1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL

INFORMATION, LIFE SAFETY, ICRA, AND PHASING

2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE

CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING

CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO

THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND

ENGINEERS.

3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS

AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH

OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND

ENGINEERS.

4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND

PLUMBING DRAWINGS FOR ADDITIONAL DEMOLITION AND

CONSTRUCTION REQUIREMENTS.

5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE) WITH

CONVECTORCONVECTOR

CONVECTOR CONVECTOR CONVECTOR CONVECTORCONVECTOR

OFFICE

PURPOSE

MULTI

STAIR

PHONE

OFFICE

OFFICE

OFFICE

BATH

HAC

OFFICE

MED. DIR.

ACCESS

ATTIC

C3C

CORRIDOR

OFFICE

DN

STAIR A

1-AS430

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -1

-R E

M a rk fo rt

.r v t

/2

/2

:1 :0

P

M

1-AS130

ATTIC FLOOR - OVERALL

PLAN

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

TO, EM PC, EM

16305

03/30/2022

1/8" = 1'-0"

ATTIC FLOOR - OVERALL PLAN

N

0 8' 16'4'

_SHEET NOTES

1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL

INFORMATION, LIFE SAFETY, ICRA, AND PHASING

2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE

CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING

CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO

THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND

ENGINEERS.

3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS

AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH

OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND

ENGINEERS.

4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND

PLUMBING DRAWINGS FOR ADDITIONAL DEMOLITION AND

CONSTRUCTION REQUIREMENTS.

5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE) WITH

5C

5C

005F

TELECOM

ROOM

3'-3"

6'-0"

1' -6

3'-0"

3' -0

5E

5F

005D

MECH

005C

CORRIDOR

005E

LOCKER

V .I.

F

3' -6

E

X

IS

T

005B

EXIST

MECH

IN-04.01

IN-03.01

3'-10" 2'-6" 3'-8"

3' -1

B3b

B3bB3b

XN3

3'-3"

3' -3

10'-0"

(9

LO

C

K E

R S

(8) LOCKERS

(7) LOCKERS

(5

LO

C

K E

R S

(4

LO

C

K E

R S

(4

LO

C

K E

R S

(5) LOCKERS

(1 3)

L O

C K

E R

S

005E

LOCKER

6'-4" 3'-4"

1' -6

'-1

3/ 4"

, V .I.

F

005F

TELECOM

ROOM

TELECOM

ROOM

LOCKER

LOCKER

A05C

TELECOM

ROOM

A05C

A6bsA6bs

A05A

MECH

IN-03.01

3'-1 3/4" 4'-3 1/2"

3' -7

/4

2'

-6

3' -1

0"

A6bs

13'-2 1/2"

'-7

/4

TELECOM

ROOM

TELECOM

ROOM

A101

TELECOM

ROOM

IN-03.01

2'-5 1/2" 7'-5 1/4" 4'-2"

3' -5

/4

2'

-6

3' -7

TELECOM

ROOM

TELECOM

ROOM

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -1

-R E

M a rk fo rt

.r v t

/2

/2

:1 :4

P

M

1-AS400

LARGE SCALE PLANS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

TO, EM PC, EM

16305

03/30/2022

1/4" = 1'-0"

ENLARGED FLOOR PLAN - RM 5F

1/8" = 1'-0"

DEMOLITION PLAN - RM 5F

1/8" = 1'-0"

REFLECTED CEILING PLAN - RM 5F

1/4" = 1'-0"

ENLARGED FLOOR PLAN - RM A05C

1/8" = 1'-0"

DEMOLITION PLAN - RM A05A

1/8" = 1'-0"

REFLECTED CEILING PLAN - RM A05C

N

0 4' 8'2'

N

0 4' 8'2'

N

0 8' 16'4'

N

0 8' 16'4'

N

0 8' 16'4'

N

0 8' 16'4'

1/4" = 1'-0"

ENLARGED FLOOR PLAN - RM A101

1/8" = 1'-0"

DEMOLITION PLAN - RM A101

1/8" = 1'-0"

REFLECTED CEILING PLAN - RM A101

N

0 4' 8'2'

N

0 8' 16'4'

N

0 8' 16'4'

_DEMOLITION PLAN KEYED NOTES

DE23 PREPARE EXISTING PARTITION FOR LEAK PREVENTION BARRIER. SEE FLOOR PLAN AND

SHEET AS601

DE26 REFER TO MECHANICAL FOR REMOVAL OF ROOFTOP UNIT

DE27 CAREFULLY REMOVE EXISTING ROOFTOP TILE AND SALVAGE FOR REINSTALLATION

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

_DEMOLITION PLAN KEYED NOTES

DE1 PREPARE WALL FOR PLYWOOD BACKBOARD INSTALLATION AND EHRM REQUIREMENTS,

SEE FLOOR PLAN AND TELECOM DRAWINGS

DE2 REMOVE AND SALVAGE DOOR AND PREPARE OPENING TO ACCOMMODATE PLAN. SEE

FLOOR PLAN AND DOOR SCHEDULE

DE5 REMOVE AND SALVAGE ROOM IDENTIFICATION SIGN FOR REINSTALLATION

DE6 REMOVE PARTITION TO THE EXTENTS SHOWN

DE7 PARTIALLY REMOVE WALL TO ACCOMMODATE PLAN AS REQUIRED. COORDINATE TEMP

SHORING WITH STRUCTURAL. SEE FLOOR PLAN

DE8 REMOVE EXISTING ROOF ASSEMBLY AS REQUIRED TO BUILD NEW ROOM, REFER TO

MECHANICAL AND ELECTRICAL FOR REMOVAL OF ROOFTOP EQUIPMENT

DE11 REMOVE EXISTING EXTERIOR PANEL SYSTEM BACK TO STRUCTURE TO THE EXTENTS

SHOWN. PREPARE FOR INSTALLATION OF NEW FURRING WALL.

DE14 REFER TO ELECTRICAL FOR REMOVAL OF DEVICES.

DE18 REMOVE AND SALVAGE LOCKERS FOR REINSTALLATION

DE20 RELOCATE CHILL WATER AND SNOW MELT SYSTEM, SEE MECHANICAL AND PLUMBING

DE21 PREPARE FLOOR FOR FINISH AND RATED PARTITIONS, SEE FLOOR PLAN

DE22 REMOVE EXISTING GUARD RAIL AS REQUIRED FOR NEW CONSTRUCTION AND PREPARE

END OF REMAINING RAIL FOR NEW ENDCAPS

_FLOOR PLAN KEYED NOTES

FL22 LEAK PREVENTION BARRIER WATERPROOFING DETAIL AT EXISTING

PARTITION. SEE AS601.

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

_FLOOR PLAN KEYED NOTES

FL1 ALL FOUR PERIMETER WALL PARTITIONS APPLY 4' BY 8' AC GRADE ¾” TRADE

SIZE FIRE RATED PLYWOOD BACKBOARD FINISHED WITH HIGH-GLOSS WHITE

PAINT OVER TWO COATS OF FIRE RESISTANT PAINT FOR SERVICE PROVIDER

/ SECURITY / VIDEO / ET CETERA. DO NOT PAINT OVER FIRE RATING STAMP.

FL2 DOOR, SIZE AS SCHEDULED, FIRE RESISTANT AS SCHEDULED.

FL3 UPGRADE PARTITION TO 1 HOUR FIRE AND SMOKE BARRIER. PROVIDE

TESTED HEAD OF PARTITION ASSEMBLY WITH MATERIALS THAT RESIST THE

PASSAGE OF SMOKE. SEAL JOINT AT HEAD AND ALL PENETRATIONS WITH

FIRE CAULK.

FL5 FINISH PARTITION WITH P-2 & RB-1.

FL13 DRYWALL PENETRATION BARRIER MESH.

FL16 MOUNT 5/8" GYPSUM BOARD TO EXISTING STEEL STUDS. UPGRADE

PARTITION TO 1 HOUR FIRE AND SMOKE BARRIER. PROVIDE TESTED HEAD

OF PARTITION ASSEMBLY WITH MATERIALS THAT RESIST THE PASSAGE OF

SMOKE. SEAL JOINT AT HEAD AND ALL PENETRATIONS WITH FIRE CAULK.

FL17 PREFINISHED METAL DOWNSPOUT AND PRECAST CONCRETE SPLASH

BLOCK.

FL18 FULL HEIGHT PREFINISHED METAL LOCKERS. RECONFIGURE LAYOUT AS

SHOWN. PROVIDE ALL NECESSARY TRANSITION COMPONENTS. MATCH

EXISTING TYPE AND FINISH.

FL20 TELECOM EQUIPMENT, SEE TELECOM DRAWINGS.

DE1

FL1

FL2

RC1

RC2

FL2

_REFLECTED CEILING PLAN KEYED NOTES

RC1 LED LIGHTING, SEE ELECTRICAL. IN FRONT OF AND BEHIND CABINET

ROWS PROVIDE 500 LUMENS IN HORIZONTAL AND 200 LUMENS IN THE

VERTICAL AT 3 FT AFF. OPERATED BY MOTION SENSOR PER CABINET

ROW OR SECTION.

RC2 OPEN TO STRUCTURAL FLOOR ABOVE

RC3 ACT SYSTEM AND 2X4 LIGHT FIXTURE, MATCH EXIST ADJACENT CEILING.

SEE ELECTRICAL

RC4 PATCH AND ALIGN ACT WITH EXISTING

RC5 EXISTING CEILING TO REMAIN

RC6 GYP SOFFIT. 1/2" GYP BD ON MTL STUD AFFIXED TO OPENING LIMITS,

PAINT

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

RC1

RC1

DE1

FL5

RC3

RC3

RC4

RC5

RC6

RC5

RC5

DE1

FL5

DE5DE1

DE2

DE6

DE7

FL1

FL5

FL5

FL5

FL1

DE1

DE1

DE1DE18

FL18

FL18

FL20

FL20

FL20

DE20 DE21

DE21

DE21

FL3

FL3

FL3 FL22

DE23

FL22

FL3

FL3

_SHEET NOTES

1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL

INFORMATION, LIFE SAFETY, ICRA, AND PHASING

2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE

CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING

CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO

THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND

ENGINEERS.

3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS

AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH

OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND

ENGINEERS.

4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND

PLUMBING DRAWINGS FOR ADDITIONAL DEMOLITION AND

CONSTRUCTION REQUIREMENTS.

5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE) WITH

WALL MOUNT BRACKET AND CODE REQUIRED SIGNAGE SHALL BE

PROVIDED WITHIN TELECOM ROOMS.

RC2

S

LO

P E

D O

W

1/

4"

1' -0

1-AS602

1-AS602

1-AS602

1-AS602

30.00°

1-AS600

1-AS600

'-1

1/

2" 3'

-4

2' -0

V .I.

F

'-2

/2

E

X

IS

T 157 SF

A200

TELECOM

ROOM

A200

'-2

/2

11'-3 3/4"

C2-A1

RAMP

IN-03.01

1-AS601

1-AS601

1-AS601

1-AS601

3'-9" 2'-6" 3'-11 1/2"

2' -7

/2

7'

-6

/4

5' -6

/4

1-AS601

1-AS600

1-AS600

1-AS601

1-AS601

TELECOM

ROOM

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -1

-R E

M a rk fo rt

.r v t

/2

/2

:1 :1

P

M

1-AS430

BUILDING ADDITION AND

ROOF PLAN

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM BMW

16305

03/30/2022

1/4" = 1'-0"

ROOF PLAN - RM A200

N

0 4' 8'2'

RO1

N

0 4' 8'2'

DE7

DE8

DE11

DE11

DE14

1/4" = 1'-0"

DEMOLITION PLAN - RM A200

_ROOF PLAN KEYED NOTES

RO1 SLOPE ROOF TO DRAIN MINIMUM 1/4" PER FOOT

RO3 RELOCATE EXISTING ROOF TILES AROUND RELOCATED ROOFTOP UNIT.

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

N

0 4' 8'2'

FL1

FL2

FL13

FL1

FL16

FL17

FL20

FL16

1/4" = 1'-0"

ENLARGED FLOOR PLAN - RM A200

N

0 4' 8'2'

RC1

RC5

RC6

1/4" = 1'-0"

REFLECTED CEILING PLAN - RM A200

_REFLECTED CEILING PLAN KEYED NOTES

RC1 LED LIGHTING, SEE ELECTRICAL. IN FRONT OF AND BEHIND CABINET

ROWS PROVIDE 500 LUMENS IN HORIZONTAL AND 200 LUMENS IN THE

VERTICAL AT 3 FT AFF. OPERATED BY MOTION SENSOR PER CABINET

ROW OR SECTION.

RC2 OPEN TO STRUCTURAL FLOOR ABOVE

RC3 ACT SYSTEM AND 2X4 LIGHT FIXTURE, MATCH EXIST ADJACENT CEILING.

SEE ELECTRICAL

RC4 PATCH AND ALIGN ACT WITH EXISTING

RC5 EXISTING CEILING TO REMAIN

RC6 GYP SOFFIT. 1/2" GYP BD ON MTL STUD AFFIXED TO OPENING LIMITS,

PAINT

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

DE22

RO3

DE27

DE26

_SHEET NOTES

1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL

INFORMATION, LIFE SAFETY, ICRA, AND PHASING

2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE

CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING

CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO

THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND

ENGINEERS.

3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS

AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH

OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND

ENGINEERS.

4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND

PLUMBING DRAWINGS FOR ADDITIONAL DEMOLITION AND

CONSTRUCTION REQUIREMENTS.

5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE) WITH

WALL MOUNT BRACKET AND CODE REQUIRED SIGNAGE SHALL BE

PROVIDED WITHIN TELECOM ROOMS.

DEMOLITION PLAN KEYED NOTES

DE1 PREPARE WALL FOR PLYWOOD BACKBOARD INSTALLATION AND EHRM REQUIREMENTS,

SEE FLOOR PLAN AND TELECOM DRAWINGS

DE2 REMOVE AND SALVAGE DOOR AND PREPARE OPENING TO ACCOMMODATE PLAN. SEE

FLOOR PLAN AND DOOR SCHEDULE

DE5 REMOVE AND SALVAGE ROOM IDENTIFICATION SIGN FOR REINSTALLATION

DE6 REMOVE PARTITION TO THE EXTENTS SHOWN

DE7 PARTIALLY REMOVE WALL TO ACCOMMODATE PLAN AS REQUIRED. COORDINATE TEMP

SHORING WITH STRUCTURAL. SEE FLOOR PLAN

DE8 REMOVE EXISTING ROOF ASSEMBLY AS REQUIRED TO BUILD NEW ROOM, REFER TO

MECHANICAL AND ELECTRICAL FOR REMOVAL OF ROOFTOP EQUIPMENT

DE11 REMOVE EXISTING EXTERIOR PANEL SYSTEM BACK TO STRUCTURE TO THE EXTENTS

SHOWN. PREPARE FOR INSTALLATION OF NEW FURRING WALL.

DE14 REFER TO ELECTRICAL FOR REMOVAL OF DEVICES.

DE18 REMOVE AND SALVAGE LOCKERS FOR REINSTALLATION

DE20 RELOCATE CHILL WATER AND SNOW MELT SYSTEM, SEE MECHANICAL AND PLUMBING

DE21 PREPARE FLOOR FOR FINISH AND RATED PARTITIONS, SEE FLOOR PLAN

DE22 REMOVE EXISTING GUARD RAIL AS REQUIRED FOR NEW CONSTRUCTION AND PREPARE

END OF REMAINING RAIL FOR NEW ENDCAPS

DE23 PREPARE EXISTING PARTITION FOR LEAK PREVENTION BARRIER. SEE FLOOR PLAN AND

SHEET AS601

DE26 REFER TO MECHANICAL FOR REMOVAL OF ROOFTOP UNIT

DE27 CAREFULLY REMOVE EXISTING ROOFTOP TILE AND SALVAGE FOR REINSTALLATION

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

FLOOR PLAN KEYED NOTES

FL1 ALL FOUR PERIMETER WALL PARTITIONS APPLY 4' BY 8' AC GRADE ¾”

TRADE SIZE FIRE RATED PLYWOOD BACKBOARD FINISHED WITH

HIGH-GLOSS WHITE PAINT OVER TWO COATS OF FIRE RESISTANT PAINT

FOR SERVICE PROVIDER / SECURITY / VIDEO / ET CETERA. DO NOT PAINT

OVER FIRE RATING STAMP.

FL2 DOOR, SIZE AS SCHEDULED, FIRE RESISTANT AS SCHEDULED.

FL3 UPGRADE PARTITION TO 1 HOUR FIRE AND SMOKE BARRIER. PROVIDE

TESTED HEAD OF PARTITION ASSEMBLY WITH MATERIALS THAT RESIST

THE PASSAGE OF SMOKE. SEAL JOINT AT HEAD AND ALL PENETRATIONS

WITH FIRE CAULK.

FL5 FINISH PARTITION WITH P-2 & RB-1.

FL13 DRYWALL PENETRATION BARRIER MESH.

FL16 MOUNT 5/8" GYPSUM BOARD TO EXISTING STEEL STUDS. UPGRADE

PARTITION TO 1 HOUR FIRE AND SMOKE BARRIER. PROVIDE TESTED

HEAD OF PARTITION ASSEMBLY WITH MATERIALS THAT RESIST THE

PASSAGE OF SMOKE. SEAL JOINT AT HEAD AND ALL PENETRATIONS WITH

FIRE CAULK.

FL17 PREFINISHED METAL DOWNSPOUT AND PRECAST CONCRETE SPLASH

BLOCK.

FL18 FULL HEIGHT PREFINISHED METAL LOCKERS. RECONFIGURE LAYOUT AS

SHOWN. PROVIDE ALL NECESSARY TRANSITION COMPONENTS. MATCH

EXISTING TYPE AND FINISH.

FL20 TELECOM EQUIPMENT, SEE TELECOM DRAWINGS.

FL22 LEAK PREVENTION BARRIER WATERPROOFING DETAIL AT EXISTING

PARTITION. SEE AS601.

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

FL1

FL13

SM1

9 1/4" 3 3/8"

1'-0 5/8"

WALL ASSEMBLY

EIFS PANEL

3/8" DRAINAGE BOARD

BUILDING MEMBRANE

5/8" GYPSUM SHEATHING

8" METAL STUDS @ 16" OC

5/8" GPBD

STEEL WIRE MESH

XN3

(1 ) LAYER 5/8" GYPSUM

BOARD EACH SIDE

3 5/8" METAL STUD

FRAMING

3" SOUND ATTENUATING

INSULATION

(1 ) LAYER 5/8" GYPSUM

BOARD

3 5/8" METAL STUD

FRAMING

STC 49

4 7/8"4 1/4"

B3

(1 ) LAYER 5/8" GYPSUM

BOARD EACH SIDE

6" METAL STUD FRAMING

3" SOUND ATTENUATING

INSULATION

STC 49

7 1/4"

B6

VARIES

A S

S C

H E

D

METAL STUDS

GYP BD

HM FRAME

DOOR AS SCHED

2"

METAL RUNNER

NOTE:

1. FOR PARTITION THICKNESS SEE PLANS

AND PARTITION TYPES

VARIES

2"

A S

S C

H E

D

HM FRAME

DOOR AS SCHED

METAL STUDS

GYP BD

NOTE:

1. FOR PARTITION THICKNESS SEE PLANS

AND PARTITION TYPES

1-AS601

1-AS601

EIFS PANEL

EIFS REVEAL

PREFINISHED METAL FLASHING

1-AS601

1-AS601

EIFS PANEL

EIFS REVEAL

PREFINISHED METAL FLASHING

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -1

-R E

M a rk fo rt

.r v t

/2

/2

:1 :5

P

M

1-AS600

ELEVATIONS, DETAILS,

SCHEDULES

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

TO, EM PC, EM

16305

03/30/2022

OPENING SCHEDULE

VA Building Number

ASSOCIATED ROOMS OPENING PANEL INFORMATION FRAME INFORMATION

H D

W G

R O

U P

F

IR

E L

A B

E L

(M

IN

G A

S K

E T

E

LE

C T

R

IC

A L

S L

A B

E L

COMMENTSFROM ROOM NAME TO ROOM NAME NUMBER WIDTH HEIGHT

PANEL

TYPE

2ND

PANEL

TYPE

PANEL

GLAZING FRAME TYPE

FRAME

GLAZING

1 CORRIDOR LOCKER 005E 3'-0" 7'-0" WD-F NONE HMS-1 NONE HW-5 -- -- -- -- LOCKER ROOM DOOR

1 TELECOM ROOM 005F 3'-0" 7'-0" WD-F NONE HMM-1 NONE HW-3.2B 45 Y Y Y

1 MECH TELECOM ROOM A05C 3'-0" 7'-0" HM-F NONE HMS-1 NONE HW-3.2B 45 Y Y Y

1 TELECOM ROOM A200 3'-0" 7'-0" WD-F NONE HMM-1 NONE HW-3.2B 45 Y Y Y

ROOM SCHEDULE

NO. NAME C

A

B

LI

N G

P A

T C

H P

A N

E L

F

IB

E R

P O

W E

R

B O

N D

IN

G

U P

S

D E

D

IC

A T

E D

C O

O

LI

N G

T E

M P

E R

A T

U R

E

H U

M

ID

IT

Y

R A

C K

S E

N S

O R

S P

A C

E

AREA

WIDTH

(FT)

LENGTH

(FT)

HT TO

CLG

STRUCT REMARKS

BASEMENT

005C CORRIDOR 34 SF 7.17 MODIFIED FOR LOCKER ROOM EXPANSION, MATCH

EXIST

005D MECH 236 SF 9.17 MODIFIED FOR LOCKER ROOM EXPANSION, SEE MECH

DRAWINGS FOR ADDITIONAL REMARKS

005E LOCKER 291 SF 7.17 MATCH EXIST LOCKER ROOM FINISHES, PROVIDE 54

LOCKERS IN AREA ADJACENT TO TR.

005F TELECOM ROOM X X X X X X X X X X X 137 SF 10.0 13.7 9.17 CONSTRUCT TO EHRM TELECOM ROOM STANDARDS.

SEE TELECOM DRAWINGS

A003 EXIST RM 64 SF 4.8 13.5 9.00 DECOMMISSION EXIST IT/DATA ROOM. SEE TELECOM

DRAWINGS

A05A MECH 1677 SF 9.58 MODIFIED FOR TELECOM ROOM, SEE MECH DRAWINGS

FOR ADDITIONAL REMARKS

A05C TELECOM ROOM X X X X X X X X X X X 118 SF 12.0 10.0 9.58 CONSTRUCT TO EHRM TELECOM ROOM STANDARDS.

SEE TELECOM DRAWINGS. RELOCATE CHILLED WATER

PUMPS AND SNOW MELT SYSTEM. SEE MECH

DRAWINGS

FIRST FLOOR

127 EXIST RM 74 SF 5.4 12.5 DECOMMISSION EXIST IT/DATA ROOM. SEE TELECOM

DRAWINGS

A101 TELECOM ROOM X X X X X X X 142 SF 9.6 14.1 8.17 UPDATE EXIST IT/DATA ROOM TO EHRM TELECOM

ROOM STANDARDS. SEE TELECOM DRAWINGS

SECOND FLOOR

229 EXIST RM 52 SF 5.5 9.4 DECOMMISSION EXIST IT/DATA ROOM. SEE TELECOM

DRAWINGS

A200 TELECOM ROOM X X X X X X X X X X X 157 SF 10.0 15.4 10.00 CONSTRUCT ADDITION. CONSTRUCT TO EHRM

TELECOM ROOM STANDARDS. SEE TELECOM

DRAWINGS. TELECOM ROOM ON ROOF FOR FIRST

FLOOR, TR SERVES 2ND AND 3RD FLOORS

A216 EXIST RM 98 SF 6.1 16.0 DECOMMISSION EXIST IT/DATA ROOM. SEE TELECOM

DRAWINGS

A225 EXIST RM 90 SF 9.7 7.5 DECOMMISSION EXIST IT/DATA ROOM. SEE TELECOM

DRAWINGS

TYPES - WALL / PARTITIONS

1 1/2" = 1'-0"

HM DOOR FRAME IN METAL STUD PARTITION - HEAD 1 1/2" = 1'-0"

HM DOOR FRAME IN METAL STUD PARTITION - JAMB

1/4" = 1'-0"

SOUTH ELEVATION - RM A200

1/4" = 1'-0"

WEST ELEVATION - RM A200

HAZARDOUS MATERIAL SCHEDULE

LEVEL

ROOM

NO. ROOM NAME

QUESTIONABLE HAZARDOUS

ELEMENT POSSIBLE ABATEMENT ACTION

BASEMENT 005C CORRIDOR NONE. SEE 1-HA-1A NONE. ACM TO REMAIN UNDISTURBED

BASEMENT 005D MECH ASBESTOS CONTAINING HARD

FITTINGS. SEE 1-HA-1A

REMOVE HAZARDOUS MATERIAL UNDER FULL CONTAINMENT

BASEMENT 005E LOCKER ASBESTOS CONTAINING HARD

FITTINGS. SEE 1-HA-1A

REMOVE HAZARDOUS MATERIAL UNDER FULL CONTAINMENT

BASEMENT 005F TELECOM ROOM NONE. SEE 1-HA-1A NONE. ACM TO REMAIN UNDISTURBED

BASEMENT A003 EXIST RM NONE. SEE 1-HA-1A NONE. ACM TO REMAIN UNDISTURBED

BASEMENT A05A MECH NONE. SEE 1-HA-1A NONE. ACM TO REMAIN UNDISTURBED

BASEMENT A05C TELECOM ROOM NONE. SEE 1-HA-1A NONE. ACM TO REMAIN UNDISTURBED

FIRST FLOOR 127 EXIST RM ACM. SEE 1-HA-2A NONE. ACM TO REMAIN UNDISTURBED

FIRST FLOOR A101 TELECOM ROOM NONE. SEE 1-HA-2A NONE. ACM TO REMAIN UNDISTURBED

SECOND FLOOR 229 EXIST RM ACM. SEE 1-HA-3A NONE. ACM TO REMAIN UNDISTURBED

SECOND FLOOR A200 TELECOM ROOM NONE NONE, BUILDING ADDITION

SECOND FLOOR A216 EXIST RM NONE. SEE 1-HA-3A NONE. ACM TO REMAIN UNDISTURBED

SECOND FLOOR A225 EXIST RM NONE. SEE 1-HA-3A NONE. ACM TO REMAIN UNDISTURBED

HAZARDOUS MATERIALS MAY BE ENCOUNTERED THROUGHOUT THE DISTRIBUTION ROUTING THROUGH CEILING PLENUMS AND UTILITY TUNNELS. INSTALLATION OF DISTRIBUTION SHALL NOT DISTURB

QUESTIONABLE HAZARDOUS MATERIAL.

LEAK PREVENTION / DIVERTER SCHEDULE

LEVEL

ROOM

NO. ROOM NAME OVERHEAD LEAK DIVERTER AND DRAIN PIPING LEAK PREVENTION BARRIER WATERPROOFING

BASEMENT 005C CORRIDOR

BASEM…