Atch 23 - BLDG 50.pdf

PDF 8 MB Posted

Attached to
Y1AZ--EHRM Infrastructure Upgrades Construction - St. Cloud Federal contract opportunity
Solicitation number
36C77622B0035
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This solicitation requests proposals for infrastructure upgrades at the St. Cloud Veterans Affairs Health Care System campus. Required work includes electrical, bonding and grounding, UPS systems, building automation interfaces, physical security upgrades, fiber infrastructure installation and upgrades both within and between buildings, hazardous materials abatement, and HVAC renovations and expansions. The solicitation also involves assessing requirements for the main server room and data center infrastructure security. The opportunity is available through the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas. Offerors should furnish all labor, materials, tools and equipment to complete the upgrades in accordance with provided specifications and drawings.

View the file

Other files for this federal contract opportunity

Other files attached to Y1AZ--EHRM Infrastructure Upgrades Construction - St. Cloud, newest first.
File Type Posted
Technical Questions - LATE - St. Cloud 8-10-22.pdf PDF
01-M204 - ROOF REMODEL -MECHANICAL.pdf PDF
Atch 5 - General 2 of 2 addendum.pdf PDF
Atch 14 - BLDG 8 addendum.pdf PDF
Atch 15 - BLDG 9 addendum.pdf PDF
Atch 20 - BLDG 29 addendum.pdf PDF
Atch 22 - BLDG 49 addendum.pdf PDF
Atch 24 - BLDG 51 addendum.pdf PDF
Atch 25 - BLDG 54 and 69 addendum.pdf PDF
Atch 32 - BLDG 115 addendum.pdf PDF
OIT Design Requirements - St. Cloud - Backbone Cabling.zip ZIP file
Atch 10 - BLDG 4 addendum.pdf PDF
Atch 21 - BLDG 48 addendum.pdf PDF
Specifications Addendum Information.pdf PDF
Drawings Addendum Information.pdf PDF
Atch 1 - Specifications Volume 1 addendum.pdf PDF
Atch 11 - BLDG 5 addendum.pdf PDF
Atch 17 - BLDG 11 addendum.pdf PDF
Atch 18 - BLDG 14 addendum.pdf PDF
Atch 28 - BLDG 108 addendum.pdf PDF
Atch 33 - BLDG 116 addendum.pdf PDF
36C77622B0035 0001.pdf PDF
Site Visit Sign-in Sheets - 6-28-22 - 6-30-22.pdf PDF
Atch 1 - Specifications Volume 1.pdf PDF
Atch 7 - BLDG 1 - 2 of 2.pdf PDF
Atch 12 - BLDG 6.pdf PDF
Atch 15 - BLDG 9.pdf PDF
Atch 18 - BLDG 14.pdf PDF
Atch 21 - BLDG 48.pdf PDF
Atch 25 - BLDG 54 and 69.pdf PDF
Atch 26 - BLDG 95 and 88.pdf PDF
Atch 28 - BLDG 108.pdf PDF
Atch 30 - BLDG 111.pdf PDF
Atch 32 - BLDG 115.pdf PDF
Atch 36 - Parking Structure.pdf PDF
Atch 40 - Limitations on Subcontracting - Construction.docx DOCX document
Atch 43 - Site Visit Instructions.pdf PDF
Atch 20 - BLDG 29.pdf PDF
Atch 4 - General 1 of 2.pdf PDF
Atch 5 - General 2 of 2.pdf PDF
Atch 8 - BLDG 2.pdf PDF
Atch 24 - BLDG 51.pdf PDF
Atch 27 - BLDG 96.pdf PDF
Atch 31 - BLDG 112.pdf PDF
Atch 10 - BLDG 4.pdf PDF
Atch 34 - BLDG 118.pdf PDF
Atch 2 - Specifications Volume 2.pdf PDF
Atch 3 - Specifications Volume 3 - Asbestos.pdf PDF
Atch 9 - BLDG 3.pdf PDF
Atch 11 - BLDG 5.pdf PDF
Show all 50

Y1AZ--EHRM Infrastructure Upgrades Construction - St. Cloud has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EXISTING FIBER - INSIDE

VFY EXIST

EXISTING FIBER - OUTSIDE

VFY EXIST

FIBER ROUTE - INSIDE

SEE TELECOM

FIBER ROUTE - OUTSIDE

SEE CIVIL

BUILDING OUTLINE

VFY EXIST

CORRIDOR OUTLINE

VFY EXIST

LEGEND

TO 8TH ST WEST ONLYTO 8TH ST EAST & WEST

44TH AVE.

TRAIL 1

TRANSFER

SWITCH

CAPACITOR

BANK (3)

SWITCH

(2)

15KV

MAIN

SW

BATT

35 KV

TO

15 KV

TRANSFORMER

35KV

FUSED

SWITCH

METER 35KV

SWITCH

GRAVEL

GRAVEL

GRAVEL

EXISTING

ROAD

CHAIN LINK FENCE

CHAIN LINK FENCE

16' GATE

GRAVEL

ELECTRICAL

SUBSTATION

G E N E R A T O R

FUEL LINES

CONDU ITS TO TU NNEL

M V

D U

C T

B A

N K

1 1 2 W

PHARMACY ADDITION

11 2 E

G E N E R A T O R

B

CORRIDOR LINK

A

C T

TR

A

IL

ER

174 s .f.

256 s .f.

185 s .f.

149 s ..f.

155 s .f.

104 s .f.

70 s. .f .

72 s .f.

110 s .f.

276 s .f.

112 s .f.

99 s .f.

57 s .f.

146 s .f.

434 s .f.

R A

MP

U P

1:

M A X

R A

MP

U P

1:

M A X

RA

M P

UP

1:2 0 M

AX

TRANSFER

SWITCH

CAPACITOR

BANK (3)

SWITCH

(2) 15KV

MAIN

SW

BATT

35 KV

TO

15 KV

TRANSFORMER

35KV

FUSED

SWITCH

METER 35KV

SWITCH

.3

TRANSFORMER

BUILD ING

#91

5,000 GAL.

UNDERGROUND

DIESEL FUEL TANK

EXISTIN G G AS SU P P LY EQ U IP M EN T TO R EM AIN

O P ER ATIO N AL DU R IN G D EM O LITIO N AN D N EW

C O N STR U C TIO N. P R O TEC T EQU IP M EN T AN D

P IP ELIN ES IN AC C O R D AN C E W ITH G AS SU P P LIER 'S

R EC O M M EN D ATIO N S

N EW G AS SU P P LY M AIN

IN TO B U ILD IN G

SP AR E

P H O N E LIN E

EXTEN D S TO

E XISTIN G

P H O N E IN

B O ILER R O O M

P ER P LAN .

SP AR E

P H O N E

LIN E TO

M ETER

TU N N EL

E XTEN D S

A D D ITIO N AL

2'- 0" U N D ER

B U ILD IN G

FUEL LINE

VENT LINE

1,000 GAL.

UNDERGROUND

DIESEL FUEL

TANK

1,000/5,000 GAL.

UNDERGROUND

DIESEL FUEL TANK

1,000 GAL.

UNDERGROUND

DIESEL FUEL TANK

1,000 GAL.

UNDERGROUND

DIESEL FUEL TANK

S 1

LIG H T

N EW G AS SU P P LY

(C O O R D IN ATE W ITH SU P P LIER )

12"D

10"D

"D

TP TP

EXIST. BUILDING

CC

L O

O P

16"

20"

12"

3"

8"

DN

BIRDCAGE

B

IR

D C

A G

E

T101

I.T.

CHILLER

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

VESTIBULE

DN

DN

DN

FD

DN

F B

F

B

F B

F

B

F B

F

B

SOUTH

VESTIBULE

PASS

THROUGH

LINK TO

BUILDI NG 51

6 3. 32 56

1 13 5. 35 78

PARKING

NO

PARKING

93 49

37 6

109 5

1A

S M

O K

E B

L D

G

SMOKE

BLDG

SMOKE

BLDG

S M

O K

E B

L D

G

SMOKE

BLDG

M.H.

STOR.

SMOKE

BLDG

SMOKE

BLDG

SMOKE

BLDG

SMOKE

BLDG

SMOKE

BLDG

STOR.

BIO-

HAZ.

SAUK RIVER

GP

HOLDING POND

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

OWNER AND

CONSULTANTS:

CONTACT:

ADDRESS:

MIKE ENGMARK

ST CLOUD VA MEDICAL CENTER

4801 VETERANS DRIVE

ST. CLOUD, MN 56303

NAME:

ADDRESS:

CONTACT:

ADVANCED STRUCTURAL TECHNOLOGIES

7301 OHMS LANE; SUITE 215

EDINA, MN 55439

ZACHARY CRAIG

PHONE:

NAME:

ADDRESS:

CONTACT:

SPECIALIZED ENGINEERING SOLUTIONS

10360 ELLISON CIRCLE

OMAHA, NE 68134

KRIS BURNHAM

PHONE: 402-991-5520

NAME:

ADDRESS:

CONTACT:

PHONE:

NAME:

ADDRESS:

CONTACT:

PHONE:

NAME:

ADDRESS:

CONTACT:

PHONE:

ANDERSON ENGINEERING OF MN, LLC

13605 1ST AVE NORTH, SUITE 100

PLYMOUTH, MN 55441

IAN WEBER

763-412-4000

ARCHITECT:

ANDERSON ENGINEERING OF MN, LLC

13605 1ST AVE NORTH, SUITE 100

PLYMOUTH, MN 55441

EDWARD MARKFORT

763-412-4000

952-854-9302

SPECIALIZED ENGINEERING SOLUTIONS

10360 ELLISON CIRCLE

OMAHA, NE 68134

KRIS BURNHAM

402-991-5520

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

COVER

DATE:

APPROVED: APPROVED: PROJECTS SECTION MANAGER

APPROVED: OIT MANAGER DATE: APPROVED: ASSISTANT CHIEF ENGINEER DATE:

APPROVED: SAFETY MANAGER

APPROVED: CHIEF OF POLICE

APPROVED: PATIENT SAFETY

DATE:

DATE:

DATE: APPROVED: EMS MANAGER

APPROVED: M/O MANAGER

DATE:

DATE:

DATE:DATE:

APPROVED: MEDICAL CENTER DIRECTOR

APPROVED: PROJECT COR DATE:

APPROVED: INFECTION CONTROL NURSE DATE:

APPROVED: SERVICE LINE DIRECTOR

APPROVED: GEMS COORDINATOR DATE:

DATE:

APPROVED: NURSE EXECUTIVE

APPROVED: CHIEF OF STAFF DATE:

APPROVED: DIRECTOR FMS

APPROVED: ASSOCIATE DIRECTOR

DATE:

DATE:

DATE:

DATE:APPROVED: DATE:

APPROVED: DATE:

APPROVED: DATE:

Main Campus, St. Cloud, Minnesota St. Cloud VA Health Care System

N

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

VICINITY MAP:

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHONE: 320-252-1670

CIVIL ENGINEER:

VA COR:

TELECOMMUNICATIONS ENGINEER:

CONTACT:

ADDRESS:

JONATHAN WEST

ST CLOUD VA MEDICAL CENTER

4801 VETERANS DRIVE

ST. CLOUD, MN 56303

PHONE: 504-250-2699

PROGRAM MANAGER:

EMAIL: Jonathan.West@vciint.com

STRUCTURAL ENGINEER:

MECH/ELEC/PLUMB/FIRE ENGINEER:

C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -5

-R

E

M a rk fo rt

.r v t

/2

/2

:3 :5

P

M

50-GI000

BUILDING 50 COVER SHEET &

SHEET INDEX

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM EM

16305

BUILDING 50 - EHRM INFRASTRUCTURE UPGRADES

03/30/2022

0APPROX 150' 300'75'

SHEET INDEX - BUILDING 50

SHEET NO. SHEET TITLE

50-GI000 BUILDING 50 COVER SHEET & SHEET INDEX

50-GI101 BASEMENT FLOOR - INFECTION CONTROL & PHASING PLAN

50-HA-1A REFERENCE - CRAWLSPACE FLOOR ASBESTOS RE-SURVEY

50-HA-2A REFERENCE - BASEMENT FLOOR ASBESTOS RE-SURVEY

50-HA-3A REFERENCE - FIRST FLOOR ASBESTOS RE-SURVEY

50-HA-4A REFERENCE - SECOND FLOOR ASBESTOS RE-SURVEY

50-HA-5A REFERENCE - ATTIC FLOOR ASBESTOS RE-SURVEY

50-AS100 BASEMENT PLANS

50-AS110 FIRST FLOOR - OVERALL PLAN

50-AS120 SECOND FLOOR - OVERALL PLAN

50-TD100 BASEMENT FLOOR PLAN - TELECOM - DEMOLITION

50-TD110 FIRST FLOOR PLAN - TELECOM - DEMOLITION

50-TD120 SECOND FLOOR PLAN - TELECOM - DEMOLITION

50-TN100 BASEMENT FLOOR PLAN - TELECOMMUNICATIONS

50-TN110 FIRST FLOOR PLAN - TELECOMMUNICATIONS

50-TN120 SECOND FLOOR PLAN - TELECOMMUNICATIONS

50-TN200 BASEMENT FLOOR PLAN - TELECOM - CABLE DISTANCE

50-TN300 ENLARGED PLANS - TELECOMMUNICATIONS - DEMO

50-TN400 ENLARGED PLANS - TELECOMMUNICATIONS

50-E100 BASEMENT FLOOR PLAN - ELECTRICAL

50-E101 FIRST FLOOR PLAN - ELECTRICAL

50-E300 ENLARGED PLANS - ELECTRICAL

50-E500 ELECTRICAL POWER DIAGRAMS

50-E600 ELECTRICAL SCHEDULES

50-M100 BASEMENT DEMOLITION PLAN - MECHANICAL

50-M200 BASEMENT FLOOR PLAN - MECHANICAL

SEE GENERAL SHEETS FOR ADDITIONAL INFORMATION

ROOM SCHEDULE

NO. NAME C

A

B

LI

N G

P A

T C

H P

A N

E L

F

IB

E R

P O

W E

R

B O

N D

IN

G

U P

S

D E

D

IC

A T

E D

C O

O

LI

N G

T E

M P

E R

A T

U R

E

H U

M

ID

IT

Y

R A

C K

S E

N S

O R

S P

A C

E

AREA

WIDTH

(FT)

LENGTH

(FT)

HT TO

CLG

STRUCT REMARKS

BASEMENT

020 TELECOM ROOM X X X X X X X X X X X 138 SF 10.3 11.9 12.00 CONSTRUCT TO EHRM TELECOM ROOM STANDARDS. SEE

TELECOM DRAWINGS

023C EXIST RM 40 SF 6.1 6.5 12.00 DECOMMISSION EXIST IT/DATA ROOM. SEE TELECOM

DRAWINGS RELOCATE FUNCTIONS TO ROOM 020

FIRST FLOOR

103A EXIST RM 41 SF 11.1 3.7 12.00 DECOMMISSION EXIST IT/DATA ROOM. SEE TELECOM

DRAWINGS RELOCATE FUNCTIONS TO ROOM 020

OPENING SCHEDULE

VA Building Number

ASSOCIATED ROOMS OPENING PANEL INFORMATION FRAME INFORMATION

H D

W G

R O

U P

F

IR

E L

A B

E L

(M

IN

G A

S K

E T

E

LE

C T

R

IC

A L

S L

A B

E L

COMMENTSFROM ROOM NAME TO ROOM NAME NUMBER WIDTH HEIGHT

PANEL

TYPE

2ND

PANEL

TYPE

PANEL

GLAZING FRAME TYPE

FRAME

GLAZING

50 TELECOM ROOM 020 3'-0" 7'-0" WD-F NONE HMS-1 NONE HW-3.2B 45 Y Y Y

HAZARDOUS MATERIAL SCHEDULE

LEVEL

ROOM

NO. ROOM NAME

QUESTIONABLE HAZARDOUS

ELEMENT POSSIBLE ABATEMENT ACTION

BASEMENT 020 TELECOM ROOM ASBESTOS CONTAINING FIRE

DOOR. SEE 50-HA-2A

REMOVE HAZARDOUS MATERIAL UNDER FULL CONTAINMENT

BASEMENT 023C EXIST RM NONE. SEE 50-HA-2A NONE. ACM TO REMAIN UNDISTURBED

FIRST FLOOR 103A EXIST RM NONE. SEE 50-HA-3A NONE. ACM TO REMAIN UNDISTURBED

HAZARDOUS MATERIALS MAY BE ENCOUNTERED THROUGHOUT THE DISTRIBUTION ROUTING THROUGH CEILING PLENUMS AND UTILITY TUNNELS. INSTALLATION OF DISTRIBUTION SHALL NOT DISTURB

QUESTIONABLE HAZARDOUS MATERIAL.

LEAK PREVENTION / DIVERTER SCHEDULE

LEVEL

ROOM

NO. ROOM NAME OVERHEAD LEAK DIVERTER AND DRAIN PIPING LEAK PREVENTION BARRIER WATERPROOFING

BASEMENT 020 TELECOM ROOM YES

BASEMENT 023C EXIST RM

FIRST FLOOR 103A EXIST RM

SEE GENERAL NOTES SHEET FOR DETAIL. MWP = MEMBRANE WATERPROOFING. MASONRY = FLUID-APPLIED WATERPROOFING. INT = INTERIOR. EXT = EXTERIOR

ICRA PHASE CONSTRUCTION ROOM SCHEDULE

LEVEL

ROOM

NO. ROOM NAME

CAI BLDG NAME /

FUNCTION

CONSTRUCTION

PROJECT ACTIVITY

INFECTION CONTROL

RISK GROUP

CONTROL

PROCEDURE CLASS SECTION

CONSTRUCTION ZONE /

OCCUPIED CONSTR

DAY /

NIGHT

BASEMENT 020 TELECOM ROOM EXTENDED CARE TYPE C GROUP 1 CLASS II WEST ZONE50 DAY

BASEMENT 023C EXIST RM EXTENDED CARE TYPE B GROUP 1 CLASS II WEST OCCUPIED CONSTRUCTION DAY

FIRST FLOOR 103A EXIST RM EXTENDED CARE TYPE B GROUP 3 CLASS II WEST OCCUPIED CONSTRUCTION DAY

SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.

FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.

TOILET

5 6

7A

7B

KITCHEN

TRAY SERVICE

STAIR

HALL

UPPER PART

SERVICE ROOM

DIETICIANS

OFFICE

KITCHEN

DISHWASHING AREA

HAC

10A

CART

STAGING

10B

EMPLOYEE

LOUNGE

TOILET

11B

TOILET

11A

HAC

STAIR

HALL

SPD

STORAGE

14C

PIPE CHASE

ELEC.

ROOM

SOILED LIN

& TRASH

15A

MALE

LOCKERS

EQUIP.

STORAGE

STORAGE

2B

LINEN

CHUTE

VENDING

4C

FAMILY

MEDITATION

4A

CORRIDOR

C0SE

7C

STAIRWELL

4B

CORRIDOR

C0C

STORAGE

2A

STORAGE

STERILE

STAGING

DECONTAM.

LOCKER

DECON

TOILET

18A

OXYGEN

STORAGE

RECEIVING/

DECONTAM.

MANUAL

WASH

17B

EQUIPMENT

17C

ELEV EQUIP

ELECTRIC

23A

ELECT.

ROOM

23A

PHONE

23B

LOW TEMP

STERILIZATION

19C

PREP/

ASSEMBLY

19B

ACCESS

CLOSET

19A

STAIRWELL

19D

MECH

14B

CORRIDOR

STORAGE

14A

MECH

ROOM

4D

SCAN & FILE

ROOM

HAC

4E

3' -8

11'-6 1/4"

023C

EXIST RM

TELECOM

ROOM

INFECTION CONTROL RISK ASSESSMENT (ICRA) LEGEND

LIMITS OF CONSTRUCTION

1 HOUR FIRE RATED ICRA / CONSTRUCTION BARRIER

LOCATION, AND DOOR, WHERE SHOWN

TEMPORARY NON-RATED (PLASTIC SHEETING) CONSTRUCTION BARRIER

LOCATION, WHERE APPROVED BY THE VA FOR USE IN RISK TYPE B.

UPGRADE TO 1 HOUR RATED PARTITION WHEN DIRECTED BY THE VA

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -5

-R

E

M a rk fo rt

.r v t

/2

/2

:4 :0

P

M

50-GI101

BASEMENT FLOOR -

INFECTION CONTROL &

PHASING PLAN

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM BMW

16305

03/30/2022

1/8" = 1'-0"

FIRST FLOOR - CONST BARRIER PLAN

ROOM ICRA SCHEDULE

LEVEL

ROOM

NO. ROOM NAME CAI BLDG NAME / FUNCTION CONSTRUCTION PROJECT ACTIVITY INFECTION CONTROL RISK GROUP CONTROL PROCEDURE CLASS

BASEMENT 020 TELECOM ROOM EXTENDED CARE TYPE C GROUP 1 CLASS II

BASEMENT 023C EXIST RM EXTENDED CARE TYPE B GROUP 1 CLASS II

FIRST FLOOR 103A EXIST RM EXTENDED CARE TYPE B GROUP 3 CLASS II

SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.

FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.

ZONE 50

0 8' 16'4'

N

-ASBESTOS-CONTAMINATED SOIL

CASTLE HILL ASSOCIATES, LLC.

N

S

W

E

BUILDING #50 - CRAWLSPACE FLOOR PLAN

LEGEND

-POSITIVE SAMPLE LOCATION

-SAMPLE LOCATION

-ASBESTOS-CONTAINING FIRE DOOR

-ASBESTOS-CONTAINING PIPE INSULATION (VERTICAL RISERS)

-ASBESTOS-CONTAINING 12"X12" FLOOR TILE AND MASTIC

-ASBESTOS-CONTAINING TRANSITE INSIDE CONVECTOR

-ASBESTOS-CONTAINING FLOOR TILE AND MASTIC UNDER CARPET

-ASBESTOS-CONTAINING PIPE INSULATION (HORIZONTAL RUNS)

CASTLE HILL ASSOCIATES, LLC.

NS

W E

LEGEND

BUILDING #50 - BASEMENT FLOOR PLAN

-ASBESTOS-CONTAINING PIPE INSULATION (VERTICAL RISERS)

-ASBESTOS-CONTAINING TRANSITE INSIDE CONVECTOR

-ASBESTOS-CONTAINING PIPE INSULATION (HORIZONTAL RUNS)

CASTLE HILL ASSOCIATES, LLC.

NS

W E

BUILDING #50 - FIRST FLOOR PLAN

-ASBESTOS-CONTAINING TRANSITE INSIDE CONVECTOR

-ASBESTOS-CONTAINING DUCT SEAM SEALANT

CASTLE HILL ASSOCIATES, LLC.

NS

W E

BUILDING #50 - SECOND FLOOR PLAN

-ASBESTOS-CONTAINING PIPE INSULATION (HORIZONTAL RUNS)

CASTLE HILL ASSOCIATES, LLC.

NS

W E

BUILDING #50 - ATTIC FLOOR PLAN

7A

7B

KITCHEN

TRAY SERVICE

STAIR

HALL

UPPER PART

SERVICE ROOM

DIETICIANS

OFFICE

KITCHEN

DISHWASHING AREA

HAC

10A

CART

STAGING

10B

EMPLOYEE

LOUNGE

TOILET

11B

TOILET

11A

HAC

STAIR

HALL

SPD

STORAGE

14C

PIPE CHASE

ELEC.

ROOM

SOILED LIN

& TRASH

15A

MALE

LOCKERS

EQUIP.

STORAGE

STORAGE

2B

LINEN

CHUTE

VENDING

4C

FAMILY

MEDITATION

4A

CORRIDOR

C0SE

7C

STAIRWELL

4B

CORRIDOR

C0C

STORAGE

2A

STORAGE

STERILE

STAGING

DECONTAM.

LOCKER

DECON

TOILET

18A

OXYGEN

STORAGE

RECEIVING/

DECONTAM.

MANUAL

WASH

17B

EQUIPMENT

17C

ELEV EQUIP

ELECTRIC

23A

ELECT.

ROOM

23A

PHONE

23B

LOW TEMP

STERILIZATION

19C

PREP/

ASSEMBLY

19B

ACCESS

CLOSET

19A

STAIRWELL

19D

MECH

14B

CORRIDOR

STORAGE

14A

MECH

ROOM

4D

SCAN & FILE

ROOM

HAC

4E

6'-6 13/32"

6' -1

3' -8

11'-6 1/4"

50-AS100

3 10'-3"

'-1

1"

023C

EXIST RM

TELECOM

ROOM

IN-03.01

B3b B3b

TELECOM

ROOM

5' -4

3'

-0

4' -3

/4

TELECOM

ROOM

TELECOM

ROOM

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -5

-R

E

M a rk fo rt

.r v t

/2

/2

:4 :0

P

M

50-AS100

BASEMENT PLANS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM EM

16305

03/30/2022

N

0 8' 16'4'

1/8" = 1'-0"

BASEMENT FLOOR - OVERALL PLAN

1/4" = 1'-0"3

ENLARGED FLOOR PLAN

0 4' 8'2'

1/4" = 1'-0"

DEMOLITION PLAN

0 4' 8'2'

1/4" = 1'-0"

REFLECTED CEILING PLAN

0 4' 8'2'

FL2

RC1 RC2

_DEMOLITION PLAN KEYED NOTES

DE1 PREPARE WALL FOR PLYWOOD BACKBOARD INSTALLATION AND EHRM

REQUIREMENTS, SEE FLOOR PLAN AND TELECOM DRAWINGS

DE2 REMOVE AND SALVAGE DOOR AND PREPARE OPENING TO

ACCOMMODATE PLAN. SEE FLOOR PLAN AND DOOR SCHEDULE

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

_FLOOR PLAN KEYED NOTES

FL1 ALL FOUR PERIMETER WALL PARTITIONS APPLY 4' BY 8' AC GRADE ¾”

TRADE SIZE FIRE RATED PLYWOOD BACKBOARD FINISHED WITH

HIGH-GLOSS WHITE PAINT OVER TWO COATS OF FIRE RESISTANT PAINT

FOR SERVICE PROVIDER / SECURITY / VIDEO / ET CETERA. DO NOT PAINT

OVER FIRE RATING STAMP.

FL2 DOOR, SIZE AS SCHEDULED, FIRE RESISTANT AS SCHEDULED

FL3 UPGRADE PARTITION TO 1 HOUR FIRE AND SMOKE BARRIER. PROVIDE

TESTED HEAD OF PARTITION ASSEMBLY WITH MATERIALS THAT RESIST

THE PASSAGE OF SMOKE. SEAL JOINT AT HEAD AND ALL PENETRATIONS

WITH FIRE CAULK.

FL4 PATCH TO MATCH FINISHES DISTURBED BY CONSTRUCTION TO MATCH

EXISTING; FLOOR AND WALL. CONTRACTOR TO PROVIDE LABOR AND

MATERIAL.

FL6 FINISH NEW PARTITIONS TO MATCH EXISTING PARTITIONS THIS AREA

FL15 PROVIDE BLACK OUT FILM AT EXISTING WINDOW. NOTED WINDOW SIZE IS

APPROXIMATE. PROVIDE METAL SECURITY SCREEN AT EXTERIOR

WINDOW. INFILL INTERIOR OF WINDOW WITH METAL STUD PARTITION.

FL20 TELECOM EQUIPMENT, SEE TELECOM DRAWINGS.

FL21 OVERHEAD LEAK DIVERTER, SEE PLUMBING.

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

_REFLECTED CEILING PLAN KEYED NOTES

RC1 LED LIGHTING, SEE ELECTRICAL. IN FRONT OF AND BEHIND CABINET

ROWS PROVIDE 500 LUMENS IN HORIZONTAL AND 200 LUMENS IN THE

VERTICAL AT 3 FT AFF. OPERATED BY MOTION SENSOR PER CABINET

ROW OR SECTION.

RC2 OPEN TO STRUCTURAL FLOOR ABOVE

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

N

N

N

FL1

FL3 FL3

DE1

DE1 DE1

DE2

FL15

FL6

FL20

FL21

FL4 FL4

_SHEET NOTES

1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL

INFORMATION, LIFE SAFETY, ICRA, AND PHASING

2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE

CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING

CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO

THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND

ENGINEERS.

3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS

AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH

OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND

ENGINEERS.

4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND

PLUMBING DRAWINGS AND SPECIFCATIONS FOR ADDITIONAL

DEMOLITION AND CONSTRUCTION REQUIREMENTS.

5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE AS

DETERMINED BY VA) WITH WALL MOUNT BRACKET AND CODE REQUIRED

SIGNAGE SHALL BE PROVIDED BY THE CONTRACTOR WITHIN TELECOM

ROOMS.

KITCHEN

CONFERENCE

1 BED

TOILET

CLEAN

UTILITY

2 BED

PATIENT

BATHROOM

2 BED

TOILET

4 BED

TOILET

STAIR

1 BED

PATIENT

BATHROOM

MULTI

PURPOSE

SWS

OFFICE

SHOWER ROOM

1 BED

2 BED

4 BED

TOILET

2 BED

1 BED

STAIR

HALL

SOILED UTILITY

HAC

CLEAN

LINEN

TLT

1 BED

ANTE

ROOM

TOILET

OFFICE

PATIENT

LOUNGE

NURSE

STATION

NOURISHMENT

TOILET

MEDICINE

CLEAN

LINEN

HAC

SUPPLY

STORAGE

144STAIR

HALL

1 BED

2 BED

4 BED

TOILET

2 BED

1 BED

SHOWER

ROOM

DAYROOM

VESTIBULE

DAYROOM

104EXAM

1 BED

TOILET

TOILET

1 BED

TOILET

SHOWER

2 BED

SOILED

UTILITY

1 BED

2 BED

TOILET

SHOWER

1 BED

STAIR

4 BED

TOILET

SHWR

GROOM

TOILET

STAIR

ACCESS

CORR

PHONE

ALCOVE ALCOVE

DF

ELEVATOR

GROOM

SHWR

TUB

STAIR

ACCESS

TUB

TOILET

PIPE CHASE

133A

PIPE

CHASE

168A

CORRIDOR

C1N

CORRIDOR

C1C

CORRIDOR

C1C

CORRIDOR

C1S

OXYGEN

CLOSET

CLOSET

LINEN

CART

128A

TV

11'-1 3/4"

3' -8

103A

EXIST RM

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -5

-R

E

M a rk fo rt

.r v t

/2

/2

:4 :1

P

M

50-AS110

FIRST FLOOR - OVERALL PLAN

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM EM

16305

03/30/2022

1/8" = 1'-0"

FIRST FLOOR - OVERALL PLAN

0 8' 16'4'

N

_SHEET NOTES

1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL

INFORMATION, LIFE SAFETY, ICRA, AND PHASING

2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE

CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING

CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO

THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND

ENGINEERS.

3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS

AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH

OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND

ENGINEERS.

4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND

PLUMBING DRAWINGS AND SPECIFCATIONS FOR ADDITIONAL

DEMOLITION AND CONSTRUCTION REQUIREMENTS.

5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE AS

DETERMINED BY VA) WITH WALL MOUNT BRACKET AND CODE REQUIRED

CORRIDOR

C2C

STAIR

1 BED

TOILET

ACCESS

STAIR

4 BED

TOILET

TOILET/

SHOWER

1 BED

TOILET/

SHOWER

1 BED

1 BED

SHOWER ROOM

PIPE

CHASE

233A

SUPPLY

STORAGE

HAC

CORRIDOR

C2S

OFFICE

TUB

SOILED

UTILITY

1 BED

TOILET

SOCIAL

WORKER

SPD

STORAGE

1 BED

1 BED

STAIR

HALL

STAIR

HALL

1 BED

NOURISH

CLEAN

LINEN

PHONE

1 BED

OFFICE

TOILET

PATIENT

DINING RM

NURSE

STATION

MEDICINE

1 BED

TOILET

4 BED

TOILET

249A

TOILET

250A

TOILET

TOILET

4 BED

ACCESS

STAIR

STAIR

TOILET

2 BED

ROOM

2 BED

1 BED

ROOM

TOILET

CONFERENCE

OFFICE

267A

OFFICE

263A

1 BED

TOILET

294A

UNASSIGNED

295A

ELEVATOR

ANTE

ROOM

2 BED

CLEAN

LINEN

HAC

1 BED

BATH

BATH

252A

TOILET

ISOLATION

1 BED

STORAGE

SOILED UTILITY

CLEAN

UTILITY

TOILET

TOILET

CORRIDOR

C2N

SHOWER ROOM

MULTI

PURPOSE

CLOSET CLOSET TOILET

SHWR

TUB

STAIR

HALL

OFFICE

OFFICE

OFFICE

OFFICE

PIPE

CHASE

268A

OFFICE

1 BED

OFFICE

TOILET

264A

OFFICE

CLOSET

228C

LINEN

CART

270ASHOWER

228B

MEDROOM

228A

OFFICE

PHONE

201A

11'-1 3/4"

3' -8

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -5

-R

E

M a rk fo rt

.r v t

/2

/2

:4 :1

P

M

50-AS120

SECOND FLOOR - OVERALL

PLAN

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM EM

16305

03/30/2022

1/8" = 1'-0"

SECOND FLOOR - OVERALL PLAN

0 8' 16'4'

N

_SHEET NOTES

1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL

INFORMATION, LIFE SAFETY, ICRA, AND PHASING

2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE

CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING

CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO

THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND

ENGINEERS.

3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS

AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH

OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND

ENGINEERS.

4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND

PLUMBING DRAWINGS AND SPECIFCATIONS FOR ADDITIONAL

DEMOLITION AND CONSTRUCTION REQUIREMENTS.

5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE AS

DETERMINED BY VA) WITH WALL MOUNT BRACKET AND CODE REQUIRED

R R

RR

R

RR

R R

R

T O

P

TOP

TOP

T O

P

ROOM

SCAN & FILE

4B

STAIR

C0SE

CORR 2A

STORAGE

4A

MEDITATION

FAMILY

4C

ROOM

LACTATE

BATH

7B

7A

HAC

TRAY SERVICE

KITCHEN

7C

STAIR MECH RM

UPPER

CHUTE

LINEN

2B

STORAGE

STORAGE

EQUIP.

LOCKERS

MALE

OFFICE

RECREATION

DISHWASHING

KITCHEN

10A

HAC

C0C

CORRIDOR

10B

STAGING

CART

LOUNGE

EMPLOYEE

11A

BATH

11B

BATH

HAC 13

STAIR

ELECT

15B

CHASE

PIPE

15A

UTILITY

STORAGE

19D

STAIR

CHASE

PIPE

E01

ELEVATOR

MECH

14A

STORAGE

14B

MECH

14C

STORAGE

SPD

CORR

4D

ROOM

MECH

EQUIP.

ELEVATOR

E02

ELEVATOR

23A

ROOM

ELECT.

23B

PHONE

DECONTAM

RECEIVING/

19A

CLOSET

ACCESS

19B

ASSEMBLY

PREP/

19C

STERILIZATION

LOW TEMP

LOCKER

DECONTAM.

18A

TOILET

DECONTAM.

STAGING

STERILE

17B

WASH

MANUAL

17C

EQUIPMENT4E

HAC

LIMITS OF DATA CABLING DEMOLITION

50-TN300

50-TN300

EE E

E

E

E

12"x2"

"x

2"

12"x2" 12"x2"

"x

2"

"x 2"

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:4

:3

P

M

50-TD100

BASEMENT FLOOR PLAN -

TELECOM - DEMOLITION

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

SHEET NOTES:

1. REMOVE AND REPLACE EXISTING DATA CABLE: REMOVE ALL EXISTING DATA CABLES AND JACKS THROUGHOUT THIS AREA. REPLACE CABLES AND JACKS 1 FOR 1, AS REQUIRED BY THE NEW WORK PLANS.

REFER TO NEW WORK PLANS FOR SERVING COMMUNICATIONS ROOM LOCATION AND NEW CABLING

ROUTES.

N

0 8' 16'4' 1/8" = 1'-0"

BASEMENT FLOOR PLAN - TELECOM - DEMOLITION

GENERAL NOTES:

A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.

LIGHTLIGHT

LIG

H

T LI

G

H T

LIGHT

LIGHTLIGHT

LIG

H

T LI

G

H T

LIGHT

LIGHT

LIGHT

LIGHT

LI

G

H T

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LI

G

H T

LI

G

H T

LIGHT

LIGHT LIGHT

LI

G

H T

LI

G

H T

LIGHT LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIG

H

T

LIGHT

LIGHT

LIGHT

LIG

H

T

AOVAOV

A O

V A O

V

AOV

AOVAOV

A O

V A O

V

AOV

AOV

AOV

AOV

A O

V

AOV

AOV

AOV

AOV

AOV

AOV

AOV

AOV

A O

V

A O

V

AOV

AOV AOV

A O

V

A O

V

AOV AOV

AOV

AOV

AOV

AOV

AOV

AOV

AOV

A O

V

AOV

AOV

AOV

A O

V

GROOM

SHWR

TOILET

TUB

SHWR

GROOMTUB

4 BED

BATH

1 BED

1 BED

STAIR

BATH

BATH

2 BED

2 BED

1 BED

SHOWER

UTILITY

SOILED

BATH

1 BED

MANAGER

NURSE

DAYROOM

STATION

NURSE

C1C

CORRIDOR

NOURISHMENT

MED

BATH

LINEN

CLEAN

HAC

SUPPLIES

STAIR

C1S

CORRIDOR

133A

CHASE

PIPE

1 BED

2 BED

4 BED

BATH

2 BED

1 BED

ENTRY

LOUNGE

VISITORS

PHONE

E01

ELEVATOR

1 BED

ANTE

BATH

OFFICE

LOUNGE

PATIENT

BATH

SOILED UTILITY

LINEN

CLEAN

HAC

CONFERENCE

1 BED

STAIR

1 BED

2 BED

4 BED

BATH

2 BED

1 BED 168A

CHASE

PIPE

BATH

C1N

CORRIDOR

SHOWER

OFFICE

SWS

PURPOSE

MULTI

BATH

1 BED

STAIR

BATH

4 BED

BATH

2 BED

BATH

2 BED

UTILITY

CLEAN

BATH

BATH

OXYGEN

128A

CART

LINEN

BATH

E02

ELEVATOR

FIRE EXT.

LAUNDRY

CHUTE

TV

LIMITS OF DATA CABLING DEMOLITION

50-TN300

E

E

E

E

E

E

E

E

"x

2"

"x

2"

"x 2"

"x

2"

12"x2"12"x2"

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:4

:3

P

M

50-TD110

FIRST FLOOR PLAN -

TELECOM - DEMOLITION

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

1/8" = 1'-0"

FIRST FLOOR PLAN - TELECOM - DEMOLITION

N

0 8' 16'4'

SHEET NOTES:

1. REMOVE AND REPLACE EXISTING DATA CABLE: REMOVE ALL EXISTING DATA CABLES AND JACKS THROUGHOUT THIS AREA. REPLACE CABLES AND JACKS 1 FOR 1, AS REQUIRED BY THE NEW WORK PLANS.

REFER TO NEW WORK PLANS FOR SERVING COMMUNICATIONS ROOM LOCATION AND NEW CABLING

ROUTES.

LIGHT LIGHT

LIG

H

T

LI

G

H T

LIGHT LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHTLIGHT

LIG

H

T

LI

G

H T

LIGHT

LI

G

H

T LIG

H T

LIG

H

T

LIGHTLIGHT

LIGHT LIGHT

LIGHT

LI

G

H T

LIGHT

LI

G

H T

LIGHTLIGHT

LIG

H

T

LI

G

H T

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIG

H

T

LIGHT

LIGHT

LI

G

H T

LIGHT

LI

G

H T

LIGHT

MEDCART

O M

N I

CELL

A O

V

AOV

A O

V

A O

V

AOV

AOV AOV

AOV

AOV

AOV

AOV

AOVAOV

A O

V

A O

V

AOV

A O

V

AOVAOV

AOV AOV

AOV

A O

V

AOV

A O

V

AOVAOV

A O

V

A O

V

AOV

AOV

AOV

AOV

AOV

A O

V

3 _ 4

AOV

AOV

A O

V

AOV

A O

V

AOV

STAIR

1 BED

BATH

4 BED

BATH

BATH

1 BED

BATH

1 BED

1 BED

233A

CHASE

PIPE

SUPPLY STORAGE

HAC229

STORAGE

SPD

STAIR

C2S

CORRIDOR

SHOWER

OFFICE

TUB

UTILITY

SOILED

1 BED

BATH

WORKER

SOCIAL

1 BED

1 BED

1 BED

NOURISH

BATH

LINEN

CLEAN

C2C

CORRIDOR

1 BED

MANAGER

NURSE

DINING

PATIENT

STATION

NURSE

MED

1 BED

BATH

4 BED

249A

BATH 250A

BATH

STAIR

1 BED

4 BED

BATH

BATH

BATH

2 BED

2 BED

BATH

CONFERENCE

STAIR

1 BED

HAC

LINEN

CLEAN255

1 BED

ANTE

294A

BATH

E01

ELEV

295A

UNASSIGNED

201A

PHONE

2 BED

BATH253

BATH

252A

BATH

1 BED

ISOLATION

STORAGE

SOILED UTILITY

UTILITY

CLEAN

BATH

CLOSET

PURPOSE

MULTI

SHWR

SHWR

TUB

268A

CHASE

PIPE

OFFICE

1 BED

228B

SHOWER

228C

CLOSET

270A

CART

LINEN

228A

MED ROOM

OFFICE

NURSE/MGR

E02

ELEV

BATH

1 BED

2 BED

2 BED

1 BED

4 BED

FIRE EXT.

LAUNDRY

CHUTE

LIMITS OF DATA CABLING DEMOLITION

E

E

E

E

E

E

E

E

EE

E

"x

2"

"x

2" 12 "x

2"

"x 2"

"x

2"

12"x2" 12"x2"

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:4

:3

P

M

50-TD120

SECOND FLOOR PLAN -

TELECOM - DEMOLITION

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

1/8" = 1'-0"

SECOND FLOOR PLAN - TELECOM - DEMOLITION

N

0 8' 16'4'

SHEET NOTES:

1. REMOVE AND REPLACE EXISTING DATA CABLE: REMOVE ALL EXISTING DATA CABLES AND JACKS THROUGHOUT THIS AREA. REPLACE CABLES AND JACKS 1 FOR 1, AS REQUIRED BY THE NEW WORK PLANS.

REFER TO NEW WORK PLANS FOR SERVING COMMUNICATIONS ROOM LOCATION AND NEW CABLING

ROUTES.

7A

7B

KITCHEN

TRAY SERVICE

STAIR

HALL

UPPER PART

SERVICE ROOM

DIETICIANS

OFFICE

KITCHEN

DISHWASHING AREA

HAC

10A

CART

STAGING

10B

EMPLOYEE

LOUNGE

TOILET

11B

TOILET

11A

HAC

STAIR

HALL

SPD

STORAGE

14C

PIPE CHASE

ELEC.

ROOM

SOILED LIN

& TRASH

15A

MALE

LOCKERS

EQUIP.

STORAGE

STORAGE

2B

LINEN

CHUTE

VENDING

4C

FAMILY

MEDITATION

4A

CORRIDOR

C0SE

7C

STAIRWELL

4B

CORRIDOR

C0C

STORAGE

2A

STORAGE

STERILE

STAGING

DECONTAM.

LOCKER

DECON

TOILET

18A

OXYGEN

STORAGE

RECEIVING/

DECONTAM.

MANUAL

WASH

17B

EQUIPMENT

17C

ELEV EQUIP

ELECTRIC

23A

ELECT.

ROOM

23A

PHONE

23B

LOW TEMP

STERILIZATION

19C

PREP/

ASSEMBLY

19B

ACCESS

CLOSET

19A

STAIRWELL

19D

MECH

14B

CORRIDOR

STORAGE

14A

MECH

ROOM

4D

SCAN & FILE

ROOM

HAC

4E

023C

EXIST RM

023B

EXIST (NIC)

50-TN400

TELECOM ROOM

LIMITS OF DATA CABLING REPLACEMENT FROM ROOM 020

C4 126"

4"

EE E

E

E

E

"x

2"

"x

2"

12"x2"12"x2"

"x

2"

12"x2"

12"x4"

12"x4"C4 126"

"x

4"

12"x4"

C4 126"

12"x4"

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:4

:4

P

M

50-TN100

BASEMENT FLOOR PLAN -

TELECOMMUNICATIONS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

N

0 8' 16'4' 1/8" = 1'-0"

BASEMENT FLOOR PLAN - TELECOMMUNICATIONS

A. REFER TO GENERAL NOTES ON SHEET T000 FOR ADDITIONAL SCOPE.

GENERAL NOTES:

SHEET NOTES:

1. CONTRACTOR TO PROVIDE NEW WIRE BASKET, AS NEEDED, TO MAINTAIN A 50% OR LESS FILL OF THE CABLE TRAY SYSTEM FOR THE FLOOR. THE NEW WIRE BASKET WILL MATCH THE SIZE AND DISTANCE, EITHER BESIDE OR BELOW THE EXISTING CABLE TRAY, TO MATCH THE EXISTING TELECOM CABLE TRAY.

CONFERENCE

1 BED

TOILET

CLEAN

UTILITY

2 BED

PATIENT

BATHROOM

2 BED

TOILET

4 BED

TOILET

STAIR

1 BED

PATIENT

BATHROOM

MULTI

PURPOSE

SWS

OFFICE

SHOWER ROOM

1 BED

2 BED

4 BED

TOILET

2 BED

1 BED

STAIR

HALL

SOILED UTILITY

HAC

CLEAN

LINEN

TLT

1 BED

ANTE

ROOM

TOILET

OFFICE

PATIENT

LOUNGE

NURSE

STATION

NOURISHMENT

TOILET

MEDICINE

CLEAN

LINEN

143HAC

SUPPLY

STORAGE

144STAIR

HALL

1 BED

2 BED

4 BED

TOILET

2 BED

1 BED

SHOWER

ROOM

DAYROOM

VESTIBULE

DAYROOM

104EXAM

1 BED

TOILET

TOILET

1 BED

TOILET

SHOWER

2 BED

SOILED

UTILITY

1 BED

2 BED

TOILET

SHOWER

1 BED

STAIR

4 BED

TOILET

SHWR

GROOM

TOILET

STAIR

ACCESS

CORR

PHONE

ALCOVE ALCOVE

DF

CLOSET

103A

ELEVATOR

GROOM

SHWR

TUB

STAIR

ACCESS

TUB

TOILET

PIPE CHASE

133A

PIPE

CHASE

168A

CORRIDOR

C1N

CORRIDOR

C1C

CORRIDOR

C1C

CORRIDOR

C1S

OXYGEN

CLOSET

CLOSET

LINEN

CART

128A

TV

KITCHEN

CONFERENCE

1 BED

TOILET

CLEAN

UTILITY

2 BED

PATIENT

BATHROOM

2 BED

TOILET

4 BED

TOILET

STAIR

1 BED

PATIENT

BATHROOM

MULTI

PURPOSE

SWS

OFFICE

SHOWER ROOM

1 BED

2 BED

4 BED

TOILET

2 BED

1 BED

STAIR

HALL

SOILED UTILITY

HAC

CLEAN

LINEN

TLT

1 BED

ANTE

ROOM

TOILET

OFFICE

PATIENT

LOUNGE

NURSE

STATION

NOURISHMENT

TOILET

MEDICINE

CLEAN

LINEN

143HAC

SUPPLY

STORAGE

144STAIR

HALL

1 BED

2 BED

4 BED

TOILET

2 BED

1 BED

SHOWER

ROOM

DAYROOM

VESTIBULE

DAYROOM

104EXAM

1 BED

TOILET

TOILET

1 BED

TOILET

SHOWER

2 BED

SOILED

UTILITY

1 BED

2 BED

TOILET

SHOWER

1 BED

STAIR

4 BED

TOILET

SHWR

GROOM

TOILET

STAIR

ACCESS

CORR

PHONE

ALCOVE ALCOVE

DF

CLOSET

103A

ELEVATOR

GROOM

SHWR

TUB

STAIR

ACCESS

TUB

TOILET

PIPE CHASE

133A

PIPE

CHASE

168A

CORRIDOR

C1N

CORRIDOR

C1C

CORRIDOR

C1C

CORRIDOR

C1S

OXYGEN

CLOSET

CLOSET

LINEN

CART

128A

TV

LIMITS OF DATA CABLING REPLACEMENT FROM ROOM 020

1 E

E

E

E

E

E

"x

2"

"x

2"

12"x2"

"x

2"

12"x2"

"x

2"

E

E

"x

2"

12" LADDER

"x

2"

12"x2"

C4 126"

12"x4"

F2

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:4

:4

P

M

50-TN110

FIRST FLOOR PLAN -

TELECOMMUNICATIONS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

1/8" = 1'-0"

FIRST FLOOR PLAN - TELECOMMUNICATIONS

N

0 8' 16'4'

A. REFER TO GENERAL NOTES ON SHEET T000 FOR ADDITIONAL SCOPE.

GENERAL NOTES:

SHEET NOTES:

1. CONTRACTOR TO PROVIDE NEW WIRE BASKET, AS NEEDED, TO MAINTAIN A 50% OR LESS FILL OF THE CABLE

CORRIDOR

C2C

STAIR

1 BED

TOILET

ACCESS

STAIR

4 BED

TOILET

TOILET/

SHOWER

1 BED

TOILET/

SHOWER

1 BED

1 BED

SHOWER ROOM

PIPE

CHASE

233A

SUPPLY

STORAGE

HAC

CORRIDOR

C2S

OFFICE

TUB

SOILED

UTILITY

1 BED

TOILET

SOCIAL

WORKER

SPD

STORAGE

1 BED

1 BED

STAIR

HALL

STAIR

HALL

1 BED

NOURISH

CLEAN

LINEN

PHONE

1 BED

OFFICE

TOILET

PATIENT

DINING RM

NURSE

STATION

MEDICINE

1 BED

TOILET

4 BED

TOILET

249A

TOILET

250A

TOILET

TOILET

4 BED

ACCESS

STAIR

STAIR

TOILET

2 BED

ROOM

2 BED

1 BED

ROOM

TOILET

CONFERENCE

OFFICE

267A

OFFICE

263A

1 BED

TOILET

294A

UNASSIGNED

295A

ELEVATOR

ANTE

ROOM

2 BED

CLEAN

LINEN

HAC

1 BED

BATH

BATH

252A

TOILET

ISOLATION

1 BED

STORAGE

SOILED UTILITY

CLEAN

UTILITY

TOILET

TOILET

CORRIDOR

C2N

SHOWER ROOM

MULTI

PURPOSE

CLOSET CLOSET TOILET

SHWR

TUB

STAIR

HALL

OFFICE

OFFICE

OFFICE

OFFICE

PIPE

CHASE

268A

OFFICE

1 BED

OFFICE

TOILET

264A

OFFICE

CLOSET

228C

LINEN

CART

270ASHOWER

228B

MEDROOM

228A

OFFICE

PHONE

201A

11'-1 3/4"

3' -8

LIMITS OF DATA CABLING REPLACEMENT FROM ROOM 020

1 E

E

E

E

E

E

"x

2"

"x

2"

12"x2"

"x

2"

12"x2"

"x

2"

E

E

"x

2"

EE

E

"x

2"

"x

2"

12"x2"

F2

12" LADDER

C4 126"

12"x4"

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:4

:4

P

M

50-TN120

SECOND FLOOR PLAN -

TELECOMMUNICATIONS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

1/8" = 1'-0"

SECOND FLOOR PLAN - TELECOMMUNICATIONS

N

0 8' 16'4'

A. REFER TO GENERAL NOTES ON SHEET T000 FOR ADDITIONAL SCOPE.

SHEET NOTES:

SHEET NOTES:

1. CONTRACTOR TO PROVIDE NEW WIRE BASKET, AS NEEDED, TO MAINTAIN A 50% OR LESS FILL OF THE CABLE

7A

7B

KITCHEN

TRAY SE RVICE

STAIR

HALL

UPPER PART

SERVI CE R OOM

DIETICIANS

OFFICE

KITCHEN

DISHWASHI NG AREA

HAC

10A

CART

STAGING

10B

EMP LOYE E

LOU NGE

TOILET

11B

TOILET

11A

HAC

STAIR

HALL

SPD

STOR AGE

14C

PIPE CHASE

ELEC.

ROOM

SOILED LIN

& TRASH

15A

MALE

LOC KE RS

EQUIP.

STOR AGE

STOR AGE

2B

LINEN

CHUTE

VENDING

4C

FAMI LY

MEDITA TION

4A

CORRI DOR

C0SE

7C

STAIRWELL

4B

CORRI DOR

C0C

STOR AGE

2A

STOR AGE

STERILE

STAGING

DECONTA M.

LOCK ER

DEC ON

TOILET

18A

OXY GE N

STOR AGE

RECEIVING/

DECONTA M.

MANU AL

WASH

17B

EQUI PME NT

17C

ELEV E QUIP

ELECTRIC

23A

ELECT.

ROOM

23A

PHONE

23B

LOW TE MP

STERILI ZATION

19C

PREP/

ASS EMB LY

19B

ACCESS

CLOSE T

19A

STAIR WELL

19D

MECH

14B

CORRI DOR

STOR AGE

14A

MECH

ROOM

4D

SCAN & FILE

ROOM

HAC

4E

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:4

:4

P

M

50-TN200

BASEMENT FLOOR PLAN -

TELECOM - CABLE DISTANCE

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

1" = 30'-0"

BASEMENT FLOOR PLAN - TELECOM - CABLE DISTANCE

N

0 30' 60'15'

PHONE

E01

PP PSP TW

E E E

E

R

DATA RACK

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:4

:4

P

M

50-TN300

ENLARGED PLANS -

TELECOMMUNICATIONS -

DEMO

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

1/4" = 1'-0"

ENLARGED PLAN - EXIST RM 20 - TELECOM - DEMO

1/4" = 1'-0"

ENLARGED PLAN - TR 023C - TELECOM - DEMO

0 4' 8'2'

N

N

0 4' 8'2'

0 4' 8'2'

N

GENERAL NOTES:

A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.

SHEET NOTES:

1. EXISTING TELECOMMUNICATIONS CAGE AND RACK SHALL BE INCLUDED WITHIN THE SCOPE OF DEMOLITION.

EXISTING CABLING AND ASSOCIATED OUTLETS SHALL BE REMOVED AND REPLACED 1 FOR 1 AND REFED FROM DISTRIBUTION EQUIPMENT LOCATED WITHIN THE NEW TELECOMMUNICATIONS ROOM. REFER TO GENERAL CABLING NOTES FOR APPROXIMATE QUANTITIES. REFER TO NEW WORK PLANS FOR SERVING

COMMUNICATIONS ROOM LOCATION AND NEW CABLING ROUTES.

2. EXISTING CABLE TRAY, SECURITY CAMERAS, GROUND BUS BARS, AND RACKS FROM DECOMMISSIONED

ROOMS ARE TO BE REUSED, WHEN POSSBILE, IN NEW CONSTRUCTION TRS.

CABLING NOTE:

CABLING NOTES:

A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE. THE CABLE

RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE PRESENT IN THE SPACE AT THE COMPLETION OF THE

PROJECT.

1. ROOM 23C

EXISTING CABLE COUNT

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

CABLE RELOCATION COUNT

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

EXISTING CABLE TO REMAIN

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

FINAL CABLE COUNT

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

2. ROOM 103

EXISTING CABLE COUNT

DATA (CAT6): 0

DATA (CAT5e): 348

DATA (CAT5): 0

DATA (CAT3): 0

CABLE RELOCATION COUNT

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

EXISTING CABLE TO REMAIN

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

FINAL CABLE COUNT

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

1/4" = 1'-0"

ENLARGED PLAN - EXIST RM 103 - DEMO

AC

CR

C 50-TN400

1 - a b

1 - c d

C4 126"

12"x4"

18"x4"

12"x4"

"x

4"

"x

4"

TELECOM ROOM

DATA RACK

CABLE TRAY

KEYPAD

W

4"

12"x4"

C4 126"

12"x4"

AC

NOTES:

1. REFER TO NEW WORK PLAN FOR RACK LOCATIONS.

2. COORDINATE EXACT RACK COUNT AND LOCATION WITH OWNER PRIOR TO PERMANENT INSTALLATION.

3. SEE PROJECT SPECIFICATIONS FOR ADDITIONAL RACK COMPONENTS.

4. CONTRACTOR TO PROVIDE PATCH PANELS AND HORIZONTAL CABLE MANAGEMENT TO SUPPORT THE DATA COUNT ON

THE WORK PLAN + 1 ADDITIONAL SPARE PATCH PANEL. (NOT TO EXCEED 288 PORTS PER RACK)

5. SPARE RACKS WITH NO HARDWARE CONFIGURED IN THEM MUST HAVE THE STANDARD UPS INSTALLED UNLESS THE

ROOM HAS A CENTRAL UPS SOURCE.

6. COORDINATE FINAL RACK COMPONENT LAYOUT WITH OWNER'S IS/IT REPRESENTATIVE.

7. CONTRACTOR IS RESPONSIBLE FOR FINAL CABLE COUNT, QUANTITY OF PATCH PANELS, SWITCHES, FIBER

ENCLOSURES, BLANKING PANELS, CABLE MANAGEMENT, AND MOUNTING HARDWARE NOT MARKED AS “OIT PROVIDED”.

8. PUNCHDOWN COPPER BACKBONES ON RACK MOUNT PATCH PANELS. TERMINATE ONE (1) PAIR PER PATCH PANEL PORT.

VERTICAL CABLE

MANAGEMENT (TYP)

RACK 1

1U 144 STRAND OM4 AND OS2 DISTRIBUTION PANEL

1U BONDING BUS BAR (BACK) 1U BLANKING PANEL (FRONT)

1U 48 PORT CAT5E BACKBONE PATCH PANEL

1U CABLE MANAGEMENT

1U CABLE MANAGEMENT

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

6U 5KW RACK MOUNT UPS

V E

R T

IC

A

L R

A C

K P

D U

V E

R T

IC

A

L R

A C

K P

D U

NEMA L21-20R (TYP)

CHANNEL RACK (TYP)

D

PROVIDE DATA CABLE TO RACK

MOUNTED UPS FOR CONNECTION

TO MONITORING SYSTEM

RACK 1

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U CABLE MANAGEMENT

2U CABLE MANAGEMENT

2U CABLE MANAGEMENT

1U CABLE MANAGEMENT

2U CABLE MANAGEMENT

2U CABLE MANAGEMENT

2U CABLE MANAGEMENT

1U BONDING BUS BAR (BACK) 1U BLANKING PANEL (FRONT)

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

6U 5KW RACK MOUNT UPS

V E

R T

IC

A

L R

A C

K P

D U

V E

R T

IC

A

L R

A C

K P

D U

NEMA L21-20R (TYP)

D

RACK 2

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U CABLE MANAGEMENT

2U CABLE MANAGEMENT

2U CABLE MANAGEMENT

1U CABLE MANAGEMENT

2U CABLE MANAGEMENT

2U CABLE MANAGEMENT

2U CABLE MANAGEMENT

RACK 2

6U SPACE FOR FUTURE USE. PROVIDE BLANK

PANELS FOR UNUSED SPACES.

VA OIT PROVIDED 1U 48 PORT SWITCH

VA OIT PROVIDED 1U 48 PORT SWITCH

VA OIT PROVIDED 1U 48 PORT SWITCH

VA OIT PROVIDED 1U 48 PORT SWITCH

VA OIT PROVIDED 1U 48 PORT SWITCH

VA OIT PROVIDED 1U 48 PORT SWITCH

SPACE FOR FUTURE HORIZONTAL CABLE

DISTRIBUTION. PROVIDE BLANKING PANELS FOR

UNUSED SPACES.

6U SPACE FOR FUTURE USE. PROVIDE BLANK

PANELS FOR UNUSED SPACES.

VA OIT PROVIDED 1U 48 PORT SWITCH

VA OIT PROVIDED 1U 48 PORT SWITCH

VA OIT PROVIDED 1U 48 PORT SWITCH

VA OIT PROVIDED 1U 48 PORT SWITCH

VA OIT PROVIDED 1U 48 PORT SWITCH

VA OIT PROVIDED 1U 48 PORT SWITCH

SPACE FOR FUTURE HORIZONTAL CABLE

DISTRIBUTION. PROVIDE BLANKING PANELS FOR

UNUSED SPACES.

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:4

:4

P

M

50-TN400

ENLARGED PLANS -

TELECOMMUNICATIONS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

1/2" = 1'-0"

ENALRGED PLAN - TR 020 - TELECOM

1/4" = 1'-0"

1 - a 1/4" = 1'-0"

1 - b

1/4" = 1'-0"4 1 - c

1/4" = 1'-0"

1 - d

NO SCALE

COMMUNICATIONS - TYPICAL TWO RACK ELEVATION WITH RACK MOUNT UPS - RM 020

N

0 2' 4'1'

GENERAL NOTES:

A. REFER TO GENERAL NOTES ON SHEET T000 FOR ADDITIONAL SCOPE.

CABLING NOTE:

CABLING NOTES:

A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE.

THE CABLE RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED

FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE

PRESENT IN THE SPACE AT THE COMPLETION OF THE PROJECT.

1. ROOM 020

EXISTING CABLE COUNT

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

CABLE RELOCATION COUNT

DATA (CAT6): 0

DATA (CAT5e): 348 FROM ROOM 103

DATA (CAT5): 0

DATA (CAT3): 0

EXISTING CABLE TO REMAIN

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

FINAL CABLE COUNT

DATA (CAT6A): 348

DATA (CAT6): 0

0 4' 8'2' 0 4' 8'2' 0 4' 8'2' 0 4' 8'2'

SHEET NOTES:

1. PROVIDE A NEW ACCESS CONTROL PANEL TO BE INSTALLED IN THE TELECOM ROOM. THE CARD READER AND KEYPAD FOR THIS ROOM TO BE WIRED TO THE NEW ACCESS CONTROL PANEL. EXISTING CARD READERS AND KEYPADS WILL BE MOVED TO THE NEW CONTROL PANEL UNDER A DIFFERENT PROJECT.

7A

7B

KITCHEN

TRAY SERVICE

STAIR

HALL

UPPER PART

SERVICE ROOM

DIETICIANS

OFFICE

KITCHEN

DISHWASHING AREA

HAC

10A

CART

STAGING

10B

EMPLOYEE

LOUNGE

TOILET

11B

TOILET

11A

HAC

STAIR

HALL

SPD

STORAGE

14C

PIPE CHASE

ELEC.

ROOM

SOILED LIN

& TRASH

15A

MALE

LOCKERS

EQUIP.

STORAGE

STORAGE

2B

LINEN

CHUTE

VENDING

4C

FAMILY

MEDITATION

4A

CORRIDOR

C0SE

7C

STAIRWELL

4B

CORRIDOR

C0C

STORAGE

2A

STORAGE

STERILE

STAGING

DECONTAM.

LOCKER

DECON

TOILET

18A

OXYGEN

STORAGE

RECEIVING/

DECONTAM.

MANUAL

WASH

17B

EQUIPMENT

17C

ELEV EQUIP

ELECTRIC

23A

ELECT.

ROOM

23A

PHONE

23B

LOW TEMP

STERILIZATION

19C

PREP/

ASSEMBLY

19B

ACCESS

CLOSET

19A

STAIRWELL

19D

MECH

14B

CORRIDOR

STORAGE

14A

MECH

ROOM

4D

SCAN & FILE

ROOM

HAC

4E

023C

EXIST RM

TELECOM

ROOM

50-E300

50-E300

50-E300

50-E300

FACP

ATS-EQ

50-MDP-2

50-ECB-1

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.E

R

.r v t

/6

/2

:4

:5

A

M

50-E100

BASEMENT FLOOR PLAN -

ELECTRICAL

EHRM INFRASTRUCTURE

UPGRADES

656-21-235

TBD GJL

16305

0 8' 16'4'

N

SCALE: 1/8" = 1'-0"50-E100

1 BASEMENT FLOOR PLAN - ELECTRICAL

100% CD 03/30

STAMP

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN# hereby certify that this plan, specification or port was prepared by me or under my direc upervision and that I am a duly Licensed ngineer under the laws of the State of Minn ame:

ate: 03/30/2022 cense Number: MN# 05-06-2022

E

CONFERENCE

1 BED

TOILET

CLEAN

UTILITY

2 BED

PATIENT

BATHROOM

2 BED

TOILET

4 BED

TOILET

STAIR

1 BED

PATIENT

BATHROOM

MULTI

PURPOSE

SWS

OFFICE

SHOWER ROOM

1 BED

2 BED

4 BED

TOILET

2 BED

1 BED

STAIR

HALL

SOILED UTILITY

HAC

CLEAN

LINEN

TLT

1 BED

ANTE

ROOM

TOILET

OFFICE

PATIENT

LOUNGE

NURSE

STATION

NOURISHMENT

TOILET

MEDICINE

CLEAN

LINEN

143HAC

SUPPLY

STORAGE

144STAIR

HALL

1 BED

2 BED

4 BED

TOILET

2 BED

1 BED

SHOWER

ROOM

DAYROOM

VESTIBULE

DAYROOM

104EXAM

1 BED

TOILET

TOILET

1 BED

TOILET

SHOWER

2 BED

SOILED

UTILITY

1 BED

2 BED

TOILET

SHOWER

1 BED

STAIR

4 BED

TOILET

SHWR

GROOM

TOILET

STAIR

ACCESS

CORR

PHONE

ALCOVE ALCOVE

DF

CLOSET

103A

ELEVATOR

GROOM

SHWR

TUB

STAIR

ACCESS

TUB

TOILET

PIPE CHASE

133A

PIPE

CHASE

168A

CORRIDOR

C1N

CORRIDOR

C1C

CORRIDOR

C1C

CORRIDOR

C1S

OXYGEN

CLOSET

CLOSET

LINEN

CART

128A

TV

CU-50-1

B50IT-1-CR-5,7

B50IT-1-5

WP

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.E

R

.r v t

/6

/2

:4

:5

A

M

50-E101

FIRST FLOOR PLAN -

ELECTRICAL

EHRM INFRASTRUCTURE

UPGRADES

656-21-235

TBD GJL

16305

SCALE: 1/8" = 1'-0"50-E101

1 FIRST FLOOR PLAN - ELECTRICAL

0 8' 16'4'

N

KEYNOTES:

1. PROVIDE ELECTRICAL CONNECTION TO

CONDENSING UNIT, AS REQUIRED.

COORDINATE FINAL LOCATION AND

CONNECTION REQUIREMENTS WITH

MECHANICAL.

100% CD 03/30

STAMP

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN# hereby certify that this plan, specification or port was prepared by me or under my direc upervision and that I am a duly Licensed ngineer under the laws of the State of Minn ame:

ate: 03/30/2022

SD

PIPE CHASE

ELEC.

ROOM

SD

E

TELECOM

ROOM

50-MDP

ES-TS

TELECOM

ROOM

A

B50IT-1

A

B50IT-1-CR

TELECOM

ROOM

B50IT-1

B50IT-1-CR

B50IT-1-CR-1

B50IT-1-1

B50IT-1-CR-1

B50IT-1-1

B50IT-1-CR-1 B50IT-1-1

B50IT-1-CR-2,4,6

B50IT-1-2,4,6

6 7

AC-50-1

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.E

R

.r v t

/6

/2

:4

:5

A

M

50-E300

ENLARGED PLANS -

ELECTRICAL

EHRM INFRASTRUCTURE

UPGRADES

656-21-235

TBD GJL

16305

N O R

HT

1/4" = 1'-0"

TELECOM ROOM - ELECTRICAL

DEMOLITION

N O R

HT

1/4" = 1'-0"

BASEMENT FLOOR PLAN -

EXISTING ELECTRICAL ROOM

N O R

HT

1/4" = 1'-0"

TELECOM ROOM - LIGHTING

N O R

HT

1/4" = 1'-0"

TELECOM ROOM - POWER & SYSTEM

KEYNOTES:

1. INDOOR UNIT TO BE POWERED BY OUTDOOR

UNIT. COORDINATE EXACT LOCATION WITH

M.C.

2. CONNECT SMOKE DETECTOR TO NEAREST

EXISTING SLC.

3. DISCONNECT AND REMOVE EXISTING LIGHTS

AND RECEPTACLES IN ROOM. MAINTAIN

CIRCUIT CONTINUITY TO ADJOINING ROOMS.

4. COORDINATE FINAL LOCATION OF

RECEPTACLE L21-30R WITH TELECOM

CONTRACTOR. PROVIDE 3/4"C-4#10, 1#10 GND

TO PANEL FOR EACH RECEPTACLE.

5. PROVIDE EATON BLADEUPS, 5KW, 120/208V, 3-

PHASE,4-WIRE RACK MOUNTED UPS FOR EACH

RACK TOWER.

6. PROVIDE APC#AP8861 RPDU RACK PDU 2G

WITH L21-20P CORD. (120/208V, 3-PHASE, 20A,

ZERO U, 5.7 KW, 208V, (36) C13 (6) C19 (2) 5-20R

OUTLETS. PROVIDE TWO PER RACK, MOUNTED

PER MANUFACTURER'S REQUIREMENTS.

7. PROVIDE ONE RACK MOUNTED ZONE PDU

UNIT. 30 AMP 3 PHASE, 120/208V, 5-WIRE WITH

(4) L21-30R, (6) 5-20R AND TWO 10' POWER

CORDS. ZONIT#ZPDS-208V-30A-L21-4L21-20R-

CR.

100% CD 03/30

STAMP

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN# hereby certify that this plan, specification or port was prepared by me or under my direc upervision and that I am a duly Licensed ngineer under the laws of the State of Minn ame:

ate: 03/30/2022

BASEMENT

FIRST FLOOR

B50IT-1

100Y

50MDP-2

B50IT-1-CR

100Y

50EQDP

1 1

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.E

R

.r v t

/6

/2

:4

:5

A

M

50-E500

ELECTRICAL ONE-LINE

DIAGRAMS AND SCHEDULES

EHRM INFRASTRUCTURE

UPGRADES

656-21-235

TBD GJL

16305

NO SCALE

PARTIAL POWER RISER

KEYNOTES:

1. PROVIDE NEW 100A/3P CIRCUIT BREAKERS IN

EXISTING PANEL TO MATCH EXISTING TYPE

AND AIC RATING.

100% CD 03/30

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 2.1 A

TOTAL CONNECTED AMPS: 2.06 A

Receptacles 0.72 kVA 100.00% 0.72 kVA TOTAL ESTIMATED DEMAND LOAD: 0.742 kVA

Power 0 kVA 0.00% 0 kVA TOTAL CONNECTED LOAD: 0.74 kVA

Lighting 0.022 kVA 100.00% 0.022 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 4.70 0.19 1.70

Total Load: 0.54 kVA 0.02 kVA 0.18 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 18 --

-- 15 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 16 --

-- 13 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 14 --

-- 11 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 12 --

-- 9 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 10 --

-- 7 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 8 --

5 WP GFI 20 A 1 0.18 0 -- -- -- -- -- -- 6 --

3 TELECOM ROOM LIGHTING 20 A 1 0.02 0 -- -- -- -- -- -- 4 --

1 TELECOM ROOM RECEPTACLE 20 A 1 0.54 0 3 20 A L21-30R 2

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

ISC UNKNOWN 0.00 kA

SCCR: 10 kA

LOCATION: TELECOM ROOM 020 WIRE: 4

FED FROM: 0 A/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MCB

PANEL B50IT-1

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 7.1 A

TOTAL CONNECTED AMPS: 7.11 A

Receptacles 0.54 kVA 100.00% 0.54 kVA TOTAL ESTIMATED DEMAND LOAD: 2.562 kVA

Power 2 kVA 100.00% 2 kVA TOTAL CONNECTED LOAD: 2.56 kVA

Lighting 0.022 kVA 100.00% 0.022 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 14.09 0.19 9.59

Total Load: 1.54 kVA 0.02 kVA 1.00 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 18 --

-- 15 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 16 --

-- 13 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 14 --

-- 11 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 12 --

-- 9 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 10 --

-- 7 -- -- -- -- -- -- 1 0 -- -- -- 1 20 A SPARE 8 --

5 CU-50-1 20 A 2 1 0 -- -- -- -- -- -- 6 --

3 TELECOM ROOM LIGHTING 20 A 1 0.02 0 -- -- -- -- -- -- 4 --

1 TELECOM ROOM RECEPTACLE 20 A 1 0.54 0 3 20 A L21-30R 2

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

ISC UNKNOWN 0.00 kA

SCCR: 10 kA

LOCATION: TELECOM ROOM 020 WIRE: 4

FED FROM: 0 A/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MCB

PANEL B50IT-1-CR

50-MDP-2 50-EQDP

STAMP

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

Licens…