8. Sheet G007_w Stamp.pdf
PDF 153 KB Posted
- Solicitation number
- 36C26126R0036
About this file
This document is a utility coordination plan for a temporary trailer site at the Mather VA Medical Center in Mather, California. The plan provides detailed specifications for electrical, sanitary/sewer, domestic water, and fiber/telecom utility connections required to support temporary outpatient pharmacy trailers and related facilities during a renovation project (Project Number 19-103, Drawing Number 612A4-19-016).
The electrical requirements include providing power from Building 107 to the temporary trailers via overhead service as soon as possible, utilizing two temporary power poles with a 300 kVA transformer rated at 10,000 AIC short circuit capacity. Sanitary infrastructure requires installation of a holding basin for human effluent with a new 4-inch PVC sanitary line routed from the temporary building at a minimum 2% slope. Domestic water service calls for a 2-inch connection from the existing building system with a backflow preventer and point-of-use hot water generation at each sink location. Fiber/telecom infrastructure requires connecting to existing fiber from the vault north of the trailer location and routing new fiber to OIT Room B650. All work must be coordinated with ongoing hospital operations to minimize disruption, with the contractor required to field verify exact utility locations and depths, provide trenching where necessary, and restore all disturbed areas to their original condition. The document is dated May 19, 2026, and marked as 100% Bid Documents.
View the file
Other files
Show all 39
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CANTEEN PARKING
TEMPORARY
OUTPATIENT
PHARMACY (3
TRAILERS LINKED
TOGETHER)
TEMPORARY WAITING
OUTPATIENT PHARMACY
(2 TRAILERS LINKED
TOGETHER)
PHARMACY
VAULT
BLDG 649
BLDG 647
BLDG 650
HOSPITAL W
AY
TEMP FIBER
SEE NOTES
F1-5
TEMP DOMESTIC
2" WATER SEE
NOTES P1-4
SANITARY
HOLDING BASIN
TEMP 4" PVC
SANITARY PIPING
SEE S1-4
TEMP ELECTRICAL LINE
SEE NOTES E1-8
ISO VAVLE
BACKFLOW PREVENTER
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:2
:5
P
M
G - 007
UTILITY COORDINATION FOR TEMP
TRAILER PLAN
7 7EFJ
RENOVATION OF
OUTPATIENT PHARMACY
AND HVAC
MATHER VAMC
10535 HOSPITAL WAY,
MATHER,CA, 95655 MAY 19, 2026
100% BID DOCUMENTS
612A4-19-01619-103
JAV
Scale: 1/16" = 1'-0"
UTILITY COORDINATION FOR TEMP TRAILER SITE PLAN
GENERAL / COORDINATION
G-1 ALL UTILITY ROUTES SHOWN ARE DIAGRAMMATIC.
CONTRACTOR SHALL FIELD VERIFY EXACT LOCATIONS
AND DEPTHS OF EXISTING UTILITIES PRIOR TO
CONSTRUCTION.
G-2 COORDINATE ALL WORK WITH ONGOING HOSPITAL
OPERATIONS TO MINIMIZE DISRUPTION.
G-3 PROVIDE RESTORATION OF ALL DISTURBED AREAS
TO ORIGINAL CONDITION.
ELECTRICAL POWER (OVER HEAD AS SOON AS POSSIBLE)
E-1 PROVIDE POWER FROM BUILDING 107 DISTRIBUTION
PANEL TO TEMPORARY TRAILER (SEE ELECTRICAL PLANS
FOR CONTINUATION).
E-2 INSTALL AT-GRADE CONDUIT FROM TRAILER TO FIRST
TRANSITION POINT PER ELECTRICAL PLANS.
E-3 PROVIDE ELECTRICAL TRENCHING ACROSS SITE
WHERE REQUIRED TO ROUTE FEEDERS (LIMIT
DISTURBANCE AREA).
E-4 CONNECT TO PROPOSED TEMPORARY POWER POLE
(POLE #1) PER ELECTRICAL PLANS.
E-5 PROVIDE OVERHEAD SERVICE FROM TEMPORARY
POWER POLE (POLE #1) TO SECOND TEMPORARY POWER
POLE (POLE #2).
E-6 EXTEND OVERHEAD SERVICE FROM POLE #2 TO
TEMPORARY LAB (TRAILER).
E-7 TEMPORARY LAB SHALL BE SERVED BY 300 kVA
TRANSFORMER WITH 10,000 AIC SHORT CIRCUIT RATING
(VERIFY FINAL WITH ELECTRICAL ENGINEER).
E-8 ONTRACTOR TO COORDINATE ALL CLEARANCES,
POLE LOCATIONS, AND UTILITY REQUIREMENTS WITH VA
AND LOCAL AUTHORITIES.
SANITARY / SEWER
S-1 INSTALL HOLDING BASIN FOR HUMAN EFFLUENT PER
PLUMBING PLANS.
S-2 CONNECT NEW 4-INCH PVC SDR-26 SANITARY LINE
FROM TEMPORARY BUILDING TO HOLDING BASIN.
S-3 PROVIDE MINIMUM SLOPE OF 2% FOR ALL SANITARY
PIPING.
S-4 COORDINATE EXACT LOCATION OF HOLDING BASIN
WITH SITE AND MAINTAIN REQUIRED CLEARANCES FROM
UTILITIES AND STRUCTURES.
DOMESTIC WATER
P-1 PROVIDE 2-INCH DOMESTIC WATER SERVICE
CONNECTION FROM EXISTING BUILDING SYSTEM (MATCH
EXISTING LABORATORY STANDARD PER VA DETAIL
612-907).
P-2 PROVIDE BACKFLOW PREVENTER AT POINT OF
CONNECTION IN ACCORDANCE WITH VA AND LOCAL CODE
REQUIREMENTS.
P-3 ROUTE DOMESTIC WATER LINE FROM BUILDING
CONNECTION TO TEMPORARY TRAILER. CONTRACTOR TO
VERIFY EXACT CONNECTION POINT AND CAPACITY.
P-4 PROVIDE POINT-OF-USE HOT WATER GENERATION
(INSTANTANEOUS WATER HEATERS OR MIXING DEVICES)
AT EACH SINK LOCATION WITHIN TRAILER.
FIBER / TELECOM
F-1 CONNECT TO EXISTING FIBER FROM EXISTING VAULT
LOCATED NORTH OF TRAILER LOCATION (SEE – FIBER
OPTIC ROUTE ‘F’ PLAN). TRENCHING REQ'd).
F-2 ROUTE NEW FIBER UTILIZING EXISTING PATHWAY
(FIBER OPTIC ROUTE ‘F’) SOUTH OF BUILDING T8,
FOLLOWING EXISTING UNDERGROUND/DUCT BANK
ALIGNMENT.
F-3 EXTEND FIBER CONTINUOUSLY TO OIT ROOM B650
(ROOM 1E272). COORDINATE EXACT ENTRY POINT AND
TERMINATION WITH VA OIT.
F-4 CONTRACTOR TO VERIFY EXISTING PATHWAY
CAPACITY AND CONDITION PRIOR TO INSTALLATION.
PROVIDE NEW CONDUIT WHERE THE EXISTING PATHWAY
IS NOT VIABLE.
F-5 PROVIDE TELECOM HAND HOLD FOR SERVICE CABLE
FOR FUTURE USE AND CONVENIENCE ACCESS POINT.
3 Progress Issuance 4 Date 4 mnorris Text Box
UTILITY COORDINATION/
DIAGRAMMATIC FOR COORDINATION PURPOSES/
CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AND FINAL INSTALLATION REQUIREMENTS mnorris Ellipse
VHAMACMalonA Rectangle
VHAMACMalonA Callout Panel QHD1001A
VHAMACMalonA Text Box
VHAMACMalonA Image
| Sheets |
| G - 007 - UTILITY COORDINATION FOR TEMP TRAILER PLAN |
File details come from the government source that posted it. Updated .