6. Sheet ES101 - ELECTRICAL SITE PLAN_SEALED_signed.pdf

PDF 3 MB Posted

Attached to
Z1DA--612A4-19-016 | Renovate Outpatient Pharmacy and HVAC
Solicitation number
36C26126R0036
Issued by

About this file

This document is an electrical site plan for a federal construction project at the Mather Veterans Affairs Medical Center (VAMC) in Mather, California. The project involves the renovation of the outpatient pharmacy and HVAC systems, with temporary trailer facilities to support operations during construction. The electrical plan specifies the installation of temporary infrastructure including a 75 KVA minimum pad-mounted transformer (277/480V primary, 120/208V secondary) and a temporary panelboard (225A, 120/208V minimum) to support three linked pharmacy trailers and two linked patient waiting trailers. The plan requires connection to existing switchboard 'QHD1001A' located in Building 701, with scheduled tie-in to be coordinated one month in advance and performed during off-hours to minimize operational disruption.

Key electrical requirements include installation of LSIG breakers in the temporary trailer panelboard, 100A fuses for transformer protection, overhead conductors (Type W or SOOW cable) maintained at minimum 18 feet above ground grade with orange power line markers and routing along galvanized guy wire, and a treated Southern Yellow Pine pole (Class 4, 35 feet above ground) for supporting overhead wiring with maximum pole spacing of 25 feet. Additional specifications mandate a wall-mounted junction box for incoming fiber at the new pharmacy trailer, weather-rated fiber conduit routed to 25 feet above ground grade, building-mounted steel mast assembly (positioned to avoid surveillance camera interference), and coordination with the Contracting Officer Representative (COR) and civil contractor for final equipment locations. The project documents are identified as 100% bid documents, drawing number ES101, VA Project Number 19-103, and prepared by Apogee Consulting Group, P.A., with a document date of May 19, 2026.

View the file

Other files

File Type Posted
36C26126C0064 Award Notice.docx DOCX document
36C26126R0036 0005.docx DOCX document
36C26126R0036 0004.docx DOCX document
9- Site Visit log.jpeg JPEG file
8- VHA ICRA_612A4-19-016 Bid.pdf PDF
5- EQUIPMENT AND FURNITURE SCHEDULE_TEMPORARY TRAILER.xlsx XLSX spreadsheet
2- 087100 Door Hardware.docx DOCX document
1- RFI answers - 36C26126R0036 - Pharmacy - 612A4-19-016.xlsx XLSX spreadsheet
7- B650 As builts 2014.pdf PDF
3- 281300-Physical access control SYStem.doc DOC document
36C26126R0036 0003.docx DOCX document
6- Utilty Map- Canteen Parking Lot.pdf PDF
4- Pre-Inspection Submittals Checklist to Bidders.xlsx XLSX spreadsheet
36C26126R0036 0002.docx DOCX document
36C26126R0036 0001.docx DOCX document
11. Sheets I-001, I-101, and I-401.pdf PDF
Brand Name Justification.pdf PDF
Past Performance Questionnaire.docx DOCX document
12. VA Provided Vault door cut sheet.pdf PDF
10. Spec Section 09 06 00 Schedof Finishes.docx DOCX document
8. Sheet G007_w Stamp.pdf PDF
36C26126R0036_2.docx DOCX document
13. 070150.19 PrepReRoof.docx DOCX document
9. NorCal Finish Standards 2025.pdf PDF
2. 010000 - General Requirements - CAEdits.docx DOCX document
0. Adendum to 19-103 Specs 100percent BD 20231108 -sumary of changes-.doc DOC document
S02 RFI FORM.docx DOCX document
VAAR 852.219-75.docx DOCX document
14. 087100 Door Hardware.docx DOCX document
7. Sheet G-006_-signed.pdf PDF
5. 013323 Shop Drawings-CA Edits.docx DOCX document
4. 013216.15 Project Sched. Small - CA Edits.docx DOCX document
3. 015000.01 Temporary Facilities and Controls - Pharmacy Trailer_CHANGES.docx DOCX document
1. 000110 TOC.docx DOCX document
SAFETY - ENVIRONMENTAL RECORD AND EXPERIENCE MODIFICATION RATE.docx DOCX document
DIVISIONAL COST BREAK-OUT.docx DOCX document
19-103 SubReg 100percent BD 20231013 .pdf PDF
19-103 Specs 100percent BD 20231108 .pdf PDF
19-103 DWGs 100 BD 20231012 .pdf PDF
Show all 39

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CANTEEN PARKING

TEMPORARY

OUTPATIENT

PHARMACY (3

TRAILERS LINKED

TOGETHER)

TEMPORARY WAITING

OUTPATIENT PHARMACY

(2 TRAILERS LINKED

TOGETHER)

PHARMACY

VAULT

BLDG 649

BLDG 647

BLDG 650

HOSPITAL W

AY

J

T

J

ETR2

E

E

BLDG 701

EXISTING UNDERGROUND VAULT

EXISTING

UNDERGROUND

VAULT

NEW

EXISTING

DEMOLISH

REPLACE

TEMP TRAILER XMFR

75 KVA (MIN)

277/480V PRI

120/208V SEC

TEMP TRAILER PNL

120/208V, 225A (MIN)225A

150A

150A

TO TEMP PHARMACY

TRAILER CONNECTION

TO TEMP PATIENT

TRAILER CONNECTION

200A

EXISTING SWBD

'QHD1001A'

277/480V, 800A

600A

TO EXISTING MCC

'QMCC61A'

400A

TO EXISTING PNL

'QH21A'

250A

TO EXISTING PNL

'QH656A'

600A

TO EXISTING PNL

'QH650A'

600A

TO EXISTING PNL

'CH656B'

4 - 3/0 AWG, 6 AWG EG IN EXISTING CONDUIT (MIN)

4 - 2/0 AWG, 4 AWG EG IN 2 1/2" CONDUIT (MIN)

4 - 1 AWG, 6 AWG EG IN 2" CONDUIT (MIN)

4 - 1 AWG, 6 AWG EG IN 2" CONDUIT (MIN)

FROM EXISTING

ATS 'ATS 4'

TEMP XMFR DISC

NEMA 3R, 100A4 - 3 AWG, 4 AWG EG IN 1 1/4" CONDUIT (MIN)

EXISTING UNDERGROUND

VAULT OUTSIDE OF BLDG

EXISTING UNDERGROUND

VAULT INSIDE OF BLDG 701

EMPTY

CONDUITS FROM

UNDERGROUND

VAULT OUTSIDE

OF BLDG 647

EMPTY CONDUITS FROM

UNDERGROUND VAULT

INSIDE OF BLDG 701

Engineers Architects

## KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/1

/2

:4

:2

P

M

ES101

ELECTRICAL SITE PLAN

2 12EFJ

RENOVATION OF

OUTPATIENT PHARMACY

AND HVAC

MATHER VAMC

10535 HOSPITAL WAY,

MATHER,CA, 95655 MAY 19, 2026

100% BID DOCUMENTS

612A4-19-01619-103

JAV

Scale: 1/16" = 1'-0"

ELECTRICAL SITE PLAN

1 PROVIDE WALL MOUNTED JUNCTION BOX AT

NEW PHARMACY TRAILER FOR INCOMING

FIBER.

2 PROVIDE CONDUIT MOUNTED TO EXTERIOR

BUILDING WALL TO 25’ AFG

3 FIBER TO HAVE WEATHER RATED JACKET

AND BE ROUTED ALONG 1/4 “ GUY WIRE

4 PROVIDE TEMPORARY PAD MOUNTED

TRANSFORMER AND TEMPORARY

PANELBOARD FOR NEW PHARMACY TRAILER.

COORDINATE WITH COR AND CIVIL

CONTRACTOR FOR FINAL LOCATION OF

EQUIPMENT. SEE TEMPORARY TRAILER

SINGLE LINE FOR MORE INFORMATION.

5 PROVIDE EQUIPMENT CONNECTIONS TO

TEMPORARY PHARMACY AND PATIENT

TRAILER. SEE TEMPORARY TRAILER SINGLE

LINE FOR MORE INFORMATION. REPLACE

EXISTING PLUG WITH 200A RATED TRIP PLUG

AND PROVIDE NEW TEMPORARY FEEDER

FROM EXISTING SPARE BREAKER.

6 PROVIDE AND INSTALL LSIG BREAKERS IN

TEMP TRAILER PNL. SEE SPECIFIED RATING

ON THE TEMPORARY TRAILER SINGLE LINE

DIAGRAM.

7 PROVIDE AND INSTALL FUSES BASED ON

TRANSFORMER SIZING. FOR MINIMUM

REQUIRED 75 KVA TRANSFORMER, 100A

FUSES TO PROTECT EQUIPMENT

8 PROVIDE TEMPORARY FEEDER TIE-IN TO

EXISTING SWBD 'QHD1001A' LOCATED IN

BUILDING 701. FEEDER TIE-IN TO EXISTING

INFRASTRUCTURE TO BE SCHEDULED WITH

THE VA 1 MONTH IN ADVANCE AND

PERFORMED OFF HOURS.

9 PROVIDE BUILDING MOUNTED STEEL ARM

MAST ASSEMBLY. MAST ASSEMBLY SHALL

NOT INTERFERE WITH ANY SURVEILLANCE

CAMERA FIELD OF VIEW. REFER TO DETAILS

FOR ADDITIONAL INFORMATION.

10 OVERHEAD CONDUCTORS MUST BE TYPE W

OR SOOW A MINIMUM OF 18'-0" AFG AT ANY

POINT, WITH AN ORANGE 9 INCH DIAMETER

STANDARD ABS POWER LINE MARKER IN THE

CENTER OF THE OVERHEAD LINE. ROUT

ALONG GALVANIZED 3/8” GUY WIRE. MAX

POLE SPACING TO BE 25’

11 PROVIDE A TREATED SOUTHERN YELLOW

PINE (CLASS 4) 35FT AFG FOR OVERHEAD

WIRING. TOTAL POLE HEIGHT TO BE VERIFIED

IN FIELD BY CONTRACTOR PER SOIL

CONDITIONS. ASSUME 10’ BURY DEPTH

PROVIDE A MAST ASSEMBLY TO ACCEPT

CONDUCTORS FROM BUILDING 701 TO

TEMPORARY BUILDING EXTERIOR

TRANSFORMER.

Scale: No Scale

TEMPORARY TRAILER ONE-LINE DIAGRAM0 8 16 32

NORTH

Scale: No Scale

EXISTING UNDERGROUND VAULT PHOTOS

Scale: No Scale

EXISTING SWBD 'QHD1001A'

A. SCHEDULED SHUTDOWNS FOR DEVICE

INSTALLATION TO BE APPROVED BY COR.

B. ELECTRICAL CONTRACTOR SHALL FOLLOW

SITE LOCK-OUT/TAG-OUT GUIDELINES TO DE-

ENERGIZE EQUIPMENT.

C. PROVIDE AND INSTALL ALL DEVICES SHOWN

ON THIS PLAN.

D. SEE PROJECT SPECIFICATIONS FOR SPECIFIC

REQUIREMENTS PERTAINING TO THE

INTERIOR ELECTRICAL AND

TELECOMMUNICATION REQUIREMENTS FOR

THE TEMPORARY TRAILERS.

Docusign Envelope ID: 63EEA22A-72AA-8376-820E-8EF5BF3C2964

5/21/2026

Sheets
ES101 - ELECTRICAL SITE PLAN
2026-05-21T14:44:32-0700
Digitally verifiable PDF exported from www.docusign.com

File details come from the government source that posted it. Updated .