537-15-160 Construction Drawings 4 of 4.pdf
PDF 5 MB Posted
- Solicitation number
- 36C25220B0023
About this file
This solicitation seeks a contractor to provide construction and renovation services for an Emergency Department Observation Unit project at the Jesse Brown VA Medical Center in Chicago, Illinois. Key details include renovating space to create a fully functional observation unit, providing all necessary labor, materials, tools and supervision. The solicitation is issued by the Department of Veterans Affairs Veterans Health Administration Great Lakes Acquisition Center. Responses are due by the date specified in the solicitation. The selected contractor will be responsible for all work outlined in the scope of work.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ST
IS
CB
SS
DS
PB
PC
CDL
DL
MS
W
SC
C
SD
UON
E, EM
CFOI
OFOI
CFCI
OFCI
T
J
DESCRIPTION
DP
S
S
X
S LV3
S D
S K
PC
S
S LV4
S
U
N
OS
OS
GROUND FAULT PROTECTED DUPLEX WITH
WEATHER-PROOF "WHILE IN USE" TYPE DIE-CAST
METAL COVERPLATE WITH LOCKABLE ENCLOSURE AT
OUTLET - SEE SPECIFICATIONS
WP
ER
DUPLEX FOR ELECTRIC WATER COOLER: COORDINATE
EXACT LOCATION WITH PLUMBING CONTRACTOR TO
CONCEAL OUTLET BEHIND COOLER, PROVIDE READILY
ACCESSIBLE GFI DEVICE AT 18" ADJACENT TO WATER
COOLER
EWC
AUDIO/VIDEO INTERCOM STATION: MASTER WITH
SELECTIVE DOOR CONTROLS, POWER SUPPLIES & DOOR
RELAY CONTACTS AS REQUIRED FOR OPERATION OF ANY
DOOR IN THE SYSTEM AND VIEWING OF ANY AUDIO/VIDEO
INTERCOM REMOTE ON THE SYSTEM. AIPHONE#AX-MV
W/DESK STAND - COLOR BY ARCHITECT.
SAME AS ''IM'' EXCEPT WALL MOUNTED W
DOOR RELEASE PUSH-PLATE / INFRA-RED OPERATOR
STATION. PROVIDE ANY ADDITIONAL ROUGH-IN FOR
''EMERGENCY RELEASE'' OPERATOR STATIONS AS REQUIRED.
DOOR RELEASE CARD READER STATION. PROVIDE ANY
ADDITIONAL ROUGH-IN FOR ''EMERGENCY RELEASE''
OPERATOR STATIONS AS REQUIRED.
AUTOMATIC DOOR CONNECTION (MAY ALSO HAVE ELECTRIC
STRIKE/MAG-LOCK/ELECTRIFIED PANIC CONNECTION - SEE
ARCHITECTURAL HARDWARE SPECIFICATIONS)
FLOORBOX, COMBINATION POWER AND LOW
VOLTAGE, REFER TO FLOORBOX SCHEDULE
CLG
SS
POWER SUPPLY/CONTROL FOR AUDIO/VISUAL DEVICES
SAME AS ''CR'' EXCEPT MULLION MOUNT M
SLASH THROUGH ANY DEVICE INDICATES MOUNTING
ABOVE COUNTERTOP 4" ABOVE BACKSPLASH
CCTV CAMERA: CEILING MOUNT DOME
WP
''DOG-HOUSE'' TYPE TWIN DUPLEX RECEPTACLE WITH
ONE DUPLEX RECEPTACLE ON BOTH SIDES
AUDIO/VIDEO INTERCOM STATION: REMOTE WITH
FLUSH-MTD S.S. ENCLOSURE. AIPHONE #AX-DVF.
S VS
VS
EMERGENCY AUTOMATIC TRANSFER SWITCH FOR
LIGHTING CONTROLS (REFER TO DETAIL)
FILLED CENTER BAR INDICATES INTEGRAL GROUND FAULT
PROTECTION (GFCI)
NON-REVERSING MOTOR STARTER SNAP SWITCH
CONTRACTOR FURNISHED OWNER INSTALLED
CONTRACTOR FURNISHED CONTRACTOR INSTALLED
OWNER FURNISHED OWNER INSTALLED
OWNER FURNISHED CONTRACTOR INSTALLED
FLUSH MOUNTED REMOTE ALARM INDICATING
STATION/TEST SWITCH
PHOTO-ELECTRIC SMOKE DETECTOR
MAIN CONTROL PANEL CENTRAL PROCESSING UNIT (CPU)
DOOR ALARM/POSITION SWITCH
DOOR POWER SUPPLY
DOOR DELAYED EGRESS/ELECTRIFIED PANIC MECHANISM
TELEVISION SYSTEM OUTLET WITH DUPLEX RECEPTACLE,
COORDINATE LOCATION WITH WALL BRACKET WHERE
APPLICABLE
LIGHT SWITCH: LOW VOLTAGE
AS NOTED
AS NOTED
LIGHT SWITCH FOR UNDER-CABINET LIGHTS
6"ABV. DOOR
46"
6'-6'' TO
TOP
46" TO
LEVER
PULL STATION : DOUBLE ACTION
AUDIO-ONLY NOTIFICATION APPLIANCE
VISUAL-ONLY NOTIFICATION APPLIANCE
AUDIO/VISUAL NOTIFICATION APPLIANCE
NURSE CALL TERMINAL CABINET
INTERCOM CEILING SPEAKER
STAFF PRESENCE STATION
CODE BLUE STATION
STAFF STATION
BED INTERFACE
MASTER STATION ANNUNCIATOR
DOME LIGHT : WALL MOUNTED
DOME LIGHT : CEILING MOUNTED
EMERGENCY STATION : PULLCORD
EMERGENCY STATION : PUSHBUTTON
DUTY STATION
HEAT DETECTOR
CARBON MONOXIDE AUDIO/VISUAL NOTIFICATION
APPLIANCE
DOOR HOLDER : WALL TYPE
DOOR HOLDER : CLOSURE TYPE
DUCT SMOKE DETECTOR
REMOTE L.C.D. FIRE ALARM ANNUNCIATOR
ISOLATION MODULE
H.V.A.C. SMOKE DAMPER CONNECTION
UNLESS OTHERWISE NOTED
INDICATES EMERGENCY POWER
SPECIAL OUTLETS
HD
F
DH
ABV DOOR DH
ABV CLG DD
46"
I
SM
ABBREVIATIONS
NURSE CALL
DESCRIPTION
XLSL
STRIP FIXTURE
CROSS-HATCHING INDICATES LIGHT IS POWERED
FROM THE EMERGENCY-CRITICAL BRANCH
PARALLEL-HATCHING INDICATES LIGHT IS POWERED
FROM THE EMERGENCY-LIFE SAFETY BRANCH
POWER OUTLETS
SIMPLEX RECEPTACLE
DUPLEX RECEPTACLE-SAFETY TYPE, TAMPER-RESISTANT
DUPLEX RECEPTACLE
QUADRUPLEX RECEPTACLE
JUNCTION BOX, CEILING OR WALL
VOLTAGE/1PH RECEPTACLE, AS NOTED
VOLTAGE/3PH RECEPTACLE, AS NOTED
SS INDICATES SURGE SUPPRESION TYPE OUTLET(S)
EXAM LIGHT SWITCH
NIGHT LIGHT SWITCH WITH CONSTANTLY ILLUMINATED
HANDLE
LOW VOLTAGE DIMMER SWITCH
LINE VOLTAGE THREE-WAY SWITCH
LINE VOLTAGE FOUR-WAY SWITCH
KEYED SWITCH
OCCUPANCY OR VACANCY SENSOR SWITCH
OCCUPANCY OR VACANCY SENSOR, CEILING MOUNT
PHOTO-CELL AS NOTED
SURGICAL/EXAM LIGHT
EXIT LIGHT (CEILING, END, WALL MOUNT)
LIGHTING
REFER TO LUMINAIRE SCHEDULE FOR EXACT FIXTURE
SPECIFICATIONS, MOUNTING HEIGHTS, ETC.
SECURITY INTERCOM
SECURITY ACCESS CONTROL
SECURITY CCTV VIDEO SURVEILLANCE
DOOR RELEASE KEYSWITCH STATION
DOOR RELEASE KEYPAD STATION
MOTION SENSOR DOOR CONTROL
REMOTE DOOR RELEASE PUSH-BUTTON
CCTV CAMERA: WALL MOUNT DOME
CCTV POWER SUPPLIES/CONTROL PANEL 46"
DOOR
FRAME
ABV DOOR
8" ACT
DESCRIPTION
CLG
1'-6''
1'-6''
46"
46"
46"
46"
46"
46"
WALL, CLG
CLG
CLG
WALL
54"
46"
46"
46"
46"
46"
46"
46"
46"
46"
1'-6"
1'-6"
1'-6"
1'-6"
1'-6"
1'-6"
ON CNTR.
2'-2"
CLG
AS NOTED
18''
46"
46"
CLG
46"
6'-0''
46"
46"
CEIL.
CLG
7'-0"
S
S
FLOOR
S M TELEVISION SPLITTERS/AMPLIFIERS/DISTRIBUTION
TELEVISION
46" TV-HE
D R
A W
I N
G
S Y
M B
O L
SURFACE OR SUSPENDED CEILING FIXTURE (SLASH
INDICATES RECESSED)
POLE MOUNTED AREA LIGHT
EMERGENCY BATTERY WALL-PACK
WALL MOUNT FIXTURE ,
FLOODLIGHT
V
A
F
F
RI
INDICATES VANDAL-PROOF POLYCARBONATE COVER,
VANDAL PROOF COVERS SHALL BE UL LISTED FOR USE
WITH THE SPECIFIC DEVICE THEY ARE PROTECTING
PC
WALL
WALL
7'-6''
ADDRESSABLE RELAY MODULE R
WALL
ACCESS CONTROL POWER SUPPLIES/CONTROL PANEL 46"
46"
ABV CLG
ELECTRIC STRIKE AT LATCH
MAGNETIC LOCK(S) ABV DOOR
INDICATES EXTERIOR CAMERA RATED FOR
CONDITIONS, WET LOCATION LISTED, WITH
AUXILLARY HEATER
FLOORBOX, POWER ONLY, AS SCHEDULED FLOOR
DESCRIPTION
WP
BOX ON ANY DEVICE INDICATES SURFACE MOUNTED
BACKBOX/WIREMOLD
CONDUIT CONCEALED IN WALLS OR IN CEILING
SPACE: ARROW(S) INDICATE(S) HOME RUN & # OF
CIRCUITS: HASHMARKS INDICATE # OF
CONDUCTORS. DASHED LINE INDICATES CONDUIT
BELOW FLOOR.
PANELBOARD, SURFACE OR FLUSH MOUNTED
EQUIPMENT TAG, REFER TO EQUIPMENT SCHEDULE
MECHANICAL EQUIPMENT DESIGNATOR (SEE
MECH. SCHEDULES)
EQUIPMENT HARDWIRE CONNECTION (SEE DETAIL)
AS NOTED
AS SHOWN
MISCELLANEOUS
DISCONNECT SWITCH
MAGNETIC STARTER
MAGNETIC COMBINATION STARTER
ENCLOSED FLUSH MTD. CIRCUIT BREAKER
WEATHERPROOF - NEMA-3R, WET LOCATION LISTED.
PROVIDE COVERS, RATINGS, ETC, AS SUITABLE FOR
OUTDOORS.
PUSHBUTTON STATION
FLEXIBLE CONDUIT
TRANSFORMER
TAGGED NOTE
REVISION TAG
WIRE BASKET CABLE TRAY, SIZE AS NOTED
LOW VOLTAGE CABLE PATH
5'-0"
5'-0"
5'-0"
5'-0"
46"
6'-6'' TO TOP
SURGE PROTECTION DEVICE
THERMOSTAT PROVIDED BY MECHANICAL CONTRACTOR,
ELECTRICAL CONTRACTOR SHALL PROVIDE BACK-BOX
CONDUIT STUB-UP, REFER TO MECHANICAL DRAWINGS FOR
LOCATIONS
MED GAS ALARMS
MSA
LPA
MEDICAL GAS LINE PRESSURE ALARM (REFER TO DETAIL)
MEDICAL GAS MULTI-SIGNAL ALARM (REFER TO DETAIL)
DESCRIPTION
C A B L
IN
G /C
O N
D U
C T O
R S
O F
O I
C A B L
IN
G /C
O N
D U
C T O
R S
O F
C I
C A B L
IN
G /C
O N
D U
C T O
R S
C F
C I
IT
E M
U S E D
O N
P R O
JE
C T
D E V
IC
E S
O F
C I
D E V
IC
E S
C F
C I
SYSTEM D
E V
IC
E S
O F
O I
SECURITY: ACCESS CONTROL
SECURITY: INTERCOM
SECURITY: CCTV
SYSTEM
RESPONSIBILITY
MATRIX
OVERHEAD PAGING
FIRE ALARM
TELEVISION
DATA PROCESSING
TELEPHONE
NURSE CALL
SYSTEM RESPONSIBILITY GENERAL NOTES:
A. AT ALL SYSTEMS EQUIPMENT CABINET/TERMINAL BOARD LOCATIONS,
CONTRACTOR SHALL PROVIDE MINIMUM 1" CONDUIT STUB-OUT TO CABLE PATHS
AS REQUIRED BY SYSTEM VENDORS, TERMINATE CONDUIT AT CABINETS/ON
BACKBOARDS AS REQUIRED. COORDINATE EXACT REQUIREMENTS WITH
APPROPRIATE VENDORS PRIOR TO CONSTRUCTION.
B. REFER TO SPECIFICATIONS FOR REQUIREMENTS APPLICABLE TO ALL SYSTEMS
INCLUDING CABLING, CABLE MANAGEMENT, INSTALLATION, GROUNDING,
TESTING, LABELING, ETC.
C. WHERE INDICATED AS CFCI, THE CONTRACTOR SHALL PROVIDE THE SYSTEM
COMPLETE, INCLUDING ALL ROUGH-INS, CABLING, DEVICES, POWER, ETC. THE
CONTRACTOR SHALL CONTACT THE LISTED VENDOR FOR PRICING PRIOR TO BID.
ALL SYSTEMS SHALL MATCH EXISTING FACILITY STANDARDS AND BE FULLY
COMPATIBLE WITH ANY EXISTING SYSTEMS. ALL SYSTEM VENDORS SHALL
COORDINATE EXACT SYSTEM REQUIREMENTS WITH OWNER PRIOR TO BID. NEW
COMPONENTS SHALL BE INTERCONNECTED WITH EXISTING SYSTEMS WHERE
POSSIBLE. ALL NEW SYSTEM DESIGNS AND PROGRAMMING SHALL BE
COORDINATED WITH THE OWNER PRIOR TO ORDERING. ALL PROGRAMMING
SHALL BE INCLUDED AS REQUIRED BY THE COR. PROVIDE 4 HOURS OF TRAINING
FOR EACH SYSTEM.
PPPOWER POLE AS NOTED
SINGLE PATIENT STATION: WITH CALL CORD
AND (4) AUXILLIARY JACK INPUTS
SINGLE PATIENT STATION: WITH PILLOW SPEAKER
AND (4) AUXILLIARY JACK INPUTS
SINGLE PATIENT STATION: WITH SIDECOM AND (4)
AUXILLIARY JACK INPUTS
5'-0''
5'-0''
5'-0''
SPP
SPC
SPS
LIGHTING CONTROL SWITCHES
SV
S
S
VWALL VOLUME CONTROL
PAGING SPEAKER: WALL
PAGING SPEAKER W/ VOLUME CONTROL
PAGING SPEAKER: CEILING CLG
CLG
8'-0"
46"
OVERHEAD PAGING
CALL INITIATION STATION 46" C
FIRE ALARM
SYSTEM
SYMBOL
PUSH-TO-EXIT BUTTON 46" PE
SPD
J
ML
ES
SEC-A
NAC
CC
CC
CR
RR
DP
DA
IM
KP
IR
KS
MS
PP
CR
DS
AD
IM
FAA
FACP
NC-A
SEC-C
T
D R
A W
I
M B
O L
D R
A W
I
M B
O L
M O
U N
T I
H E
I G
H T
T
O
C
N T
E R
F
B
X
D R
A W
I
M B
O L
AS SHOWNLADDER CABLE TRAY, SIZE AS NOTED
AS SHOWNSOLID BOTTOM CABLE TRAY, SIZE AS NOTED
EQUIP-1
GROUND
NEUTRAL
PHASE
WALL, CLG
WALL, CLG V
A
F
CM
DEAD FRONT GFCI DEVICE, LABEL AND INSTALL IN READILY
ACCESSIBLE LOCATION
FILLED OUTER BARS INDICATES INTEGRAL INTEGRAL USB
OUTLETS IN ADDITION TO POWER RECEPTACLES
1'-6"
, J
VARIABLE FREQUENCY DRIVE 5'-0"
MOTOR CONNECTION, REFER TO EQUIPMENT
CONNECTION SCHEDULE
DUPLEX RECEPTACLE, CEILING MOUNTED CLG
CONDUIT UP
CONDUIT DOWN
WIREGUARD - PROVIDE MANUFACTURER'S SPECIFIC
GUARD FOR DEVICE NOTED
WIRELESS ACCESS POINT OUTLET WITH PROVISIONS FOR
(1 DATA OUTLET FOR ANTENNA. PROVIDE A COMPLETE
DATA OUTLET WITH FACEPLATE ABOVE CEILING, MOUNTED
AT AN ACCESSIBLE HEIGHT NO MORE THAN 24" ABOVE
CEILING. AT EACH OUTLET, PROVIDE A 20' COIL OF CABLE
AHEAD OF THE OUTLET FOR ADJUSTMENT OF FINAL OUTLET
LOCATION. THE CONTRACTOR SHALL COORDINATE EXACT
LOCATIONS WITH THE OWNER AND ADJUST OUTLET
LOCATIONS AT SUBSTANTIAL COMPLETION TO
ACCOMMODATE OWNER'S WAP LOCATIONS.
WAP
DATA OUTLET : PROVIDE A COMPLETE 6-PORT DATA
OUTLET WALLPLATE. AT EACH OUTLET, PROVIDE
PROVIDE (4)-RJ45 JACKS. REFER TO DETAIL FOR
CONFIGURATION. PROVIDE CAT6E CABLING FROM ALL
JACKS AND ROUTE TO NEW PATCH PANEL IN TELECOM
ROOM 14T3.
DATA / VOICE
1'-6"
SLINE VOLTAGE SWITCH 46"
CLG
M O
U N
T I
I G
H T
N T
E R
X
M O
U N
T I
I G
H T
N T
E R
X
M O
U N
T I
I G
H T
N T
E R
X
LV
CLG
CMCCTV MONITOR
I LL IN O IS
S N
A H
A
TR
E B
O R
NTHONY
LICENSED
PROFESSIONAL
OF
ENGINEER
062.059710
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
100% RE-SUBMIT 2020/06/29
C U s e rs
\j h u s to n \D o c u m e n ts
\R
I V
C E
E
L E
C T
R
IC
A L jh u s to n c m ta e g rs
.c o m
.r v t
/2
/2
:4
:5
A
M
EJ001
ELECTRICAL LEGEND
GUIDON-CMTA SDVOSB JV, LLC
1221 N. PENNSYLVANIA ST. SUITE 200
INDIANAPOLIS, IN 46202
CMTA CONSULTING ENGINEERS
903 SPRING ST.
JEFFERSONVILLE, IN 47130
EMERGENCY DEPARTMENT
RENOVATION
820 S. DAMEN AVE.
537-15-160
5/30/2020 CMTA CMTA
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Revisions: Date:
J
J
FUTURE ALARM "MULTI-PLEX' CONNECTIONS.
INTEGRATED "LINE PRESSURE ALARM"
PANEL (CFCI). REFER TO POWER
LOCATION(S).
FLOOR PLANS FOR NUMBER AND
WALL
MEDICAL GAS LINES (EXACT NO./LOCATION AS
TO EACH MEDICAL GAS LINE PER MANUFACTURER's
PULSE PRESSURE SENSORS (CFCI) CONNECTED
SUSPENDED CEILING
INDICATED ON MEDICAL GAS FLOOR PLANS.)
RECOMMENDATIONS.
LPA
TO EMERGENCY "LIFE SAFTY BRANCH"
120 VAC POWER SOURCE (SEE POWER
FLOOR PLANS FOR CIRCUIT).
3/4" CONDUIT UP IN WALL FROM THE
"LPA" TO 6" ABOVE CEILING FOR
BY MEDICAL GAS MANUFACTURER IN 1/2" CONDUIT
FROM EACH PULSE PRESSURE SENSOR TO THE "LPA".
PROVIDE ''BELDEN'' SHIELDED CABLE AS REQUIRED
E
4" x 4" J-BOX
AT STRUCTURE
120/277V
LIGHTING
BRANCH CIRCUIT
120/277V LIGHTING BRANCH
CIRCUIT TO LIGHT FIXTURES
PROVIDE 0-10V
LOW-VOLTAGE DIMMING
CONTROL WIRING TO
LIGHT FIXTURES
TO ADDITIONAL SENSORS IN
ROOM/AREA, WHERE SHOWN OR
REQUIRED, FOR 100% COVERAGE.
PROVIDE PLENUM RATED CAT6
CABLING BETWEEN ALL LIGHTING
CONTROL DEVICES.
SINGLE-ZONE CEILING MOUNTED VACANCY SENSOR(S) WITH DIMMING DIAGRAM
S D1
120/277V
LIGHTING
BRANCH CIRCUIT
120/277V LIGHTING BRANCH
CIRCUIT TO LIGHT FIXTURES
TO ADDITIONAL SENSORS IN
ROOM/AREA, WHERE SHOWN OR
REQUIRED, FOR 100% COVERAGE.
PROVIDE PLENUM RATED CAT6
CABLING BETWEEN ALL LIGHTING
CONTROL DEVICES.
DUAL-ZONE CEILING MOUNTED VACANCY SENSOR(S) WITH DIMMING DIAGRAM
S D2
PROVIDE 0-10V
LOW-VOLTAGE DIMMING
CONTROL WIRING TO
LIGHT FIXTURES
120/277V LIGHTING BRANCH
CIRCUIT TO LIGHT FIXTURES
120/277V
LIGHTING
BRANCH CIRCUIT
120/277V LIGHTING BRANCH
CIRCUIT TO LIGHT FIXTURES
LINE-VOLTAGE CONTROL
DEVICE, IF INDICATED
ON FLOOR PLANS.
TO ADDITIONAL SENSORS IN
ROOM/AREA, WHERE SHOWN OR
REQUIRED, FOR 100% COVERAGE.
PROVIDE PLENUM RATED CAT6
CABLING BETWEEN ALL LIGHTING
CONTROL DEVICES.
S
SINGLE-ZONE CEILING MOUNTED OCCUPANCY SENSOR(S) DIAGRAM
PROVIDE 0-10V
LOW-VOLTAGE DIMMING
CONTROL WIRING TO
LIGHT FIXTURES
CONNECTION TO AUXILIARY CONTACT BY
TCC. PROVIDE ADDITIONAL POWER PACK,
AS REQUIRED.
S, CONNECTION TO AUXILIARY CONTACT
BY TCC. PROVIDE ADDITIONAL POWER
PACK, AS REQUIRED.
CONNECTION TO AUXILIARY CONTACT
BY TCC. PROVIDE ADDITIONAL POWER
PACK, AS REQUIRED.
LIGHTING CONTROLS SEQUENCE OF OPERATIONS:
A. DAYLIGHT PHOTOCELL OPERATION: DEVICE SHALL BE SET TO MAINTAIN DESIGNED ARTIFICIAL
ILLUMINATION LEVEL IN EACH ZONE/AREA.
B. ALL LUMINAIRES WITHIN A DAYLIGHT ZONE SHALL BE SEPARATELY CONTROLLED FROM THE REST OF
THE GENERAL LIGHTING IN THE SPACE. THESE LUMINAIRES SHALL BE CONTROLLED USING AUTOMATIC
DAYLIGHT HARVESTING CONTROLS. THE DAYLIGHT HARVESTING CONTROLS SHALL PROVIDE SMOOTH
AND CONTINUOUS DIMMING. DIMMING SHALL BE INITIATED WHEN TOTAL ILLUMINATION (COMBINED
DAYLIGHT AND ELECTRIC LIGHTING) REACHES 150% OF THE MAINTAINED DESIGN ILLUMINANCE
PROVIDED BY THE ELECTRIC LIGHTING ONLY.
C. VACANCY SENSOR OPERATION: DEVICE SHALL BE MANUAL ON AND AUTOMATIC OFF. LIGHTING TO
TURN OFF AFTER 20 MINUTES OF NO OCCUPANCY.
D. OCCUPANCY SENSOR OPERATION: DEVICE SHALL BE AUTOMATIC ON AND AUTOMATIC OFF. LIGHTING
TO TURN OFF AFTER 15 MINUTES OF NO OCCUPANCY.
E. VACANCY SENSOR WITH DIMMING CONTROLS: PROVIDE 70% OF LIGHT IN ZONE WHEN WALL SWITCH IS
ACTIVATED. OCCUPANT SHALL BE ABLE TO ADJUST FROM 0% TO 100% 'ON' WITH RAISE/LOWER
BUTTONS.
F. OCCUPANCY SENSOR WITH DIMMING CONTROLS: PROVIDE 70% OF LIGHT IN ZONE WHEN OCCUPANCY
SENSOR IS ACTIVATED. OCCUPANT SHALL BE ABLE TO ADJUST FROM 0% TO 100% 'ON' WITH
RAISE/LOWER BUTTONS.
G. OCCUPANCY SENSOR CONTROL ZONES WITHOUT MANUAL OR DIGITAL SWITCHING SHALL BE
CONTROLLED BY OCCUPANCY SENSORS ONLY.
PD
VS VS
PD
VS VS
PD
PR
OS OS
D
TYPICAL SCHEMATIC INTEGRATING UL 924 POWER PACK
120/277V NORMAL
LIGHTING BRANCH
CIRCUIT
120/277V LIGHTING BRANCH
CIRCUIT TO LIGHT FIXTURES
PROVIDE PLENUM RATED CAT6
CABLING BETWEEN ALL LIGHTING
CONTROL DEVICES.
S D1/L1
PROVIDE 0-10V
LOW-VOLTAGE DIMMING
CONTROL WIRING TO
EMERGENCY LIGHT FIXTURES
120/277V LIGHTING BRANCH
CIRCUIT TO LIGHT FIXTURES
PROVIDE 0-10V
LOW-VOLTAGE DIMMING
CONTROL WIRING TO
LIGHT FIXTURES
CONNECTION TO AUXILIARY
CONTACT BY TCC. PROVIDE
ADDITIONAL POWER PACK,
AS REQUIRED.
VS VS
PD/PR
PD/PR
E
120/277V EMERGENCY
LIGHTING BRANCH
CIRCUIT
PROVIDE WHERE EMERGENCY AND
NORMAL POWER LIGHTING IS
CONTROLLED BY THE SAME LOW
VOLTAGE SWITCH.
A. PROVIDE AND FOR NON-DIMMING ZONES. NON-DIMMING ZONES DO NOT REQUIRE 0-10V WIRING.
B. PROVIDE AND WHEN CONTROLLING EMERGENCY LIGHTING BRANCH CIRCUIT.
C. VERIFY ALL WIRING REQUIREMENTS WITH MANUFACTURER OF LIGHTING CONTROL DEVICES
PRIOR TO ROUGH-IN. THIS SCHEMATIC DIAGRAM IS MEANT TO BE ILLUSTRATIVE ONLY.
D. LIGHTING CONTROL SYSTEM SHALL COMPLY WITH ENERGY CODE.
E. LIGHTING CONTROL DEVICES SHALL BE SENSOR SWITCH (nLIGHT), WATTSTOPPER (DLM) OR
COOPER CONTROLS. ALL DEVICES SHALL BE FURNISHED BY ONE MANUFACTURER.
S
LX
GENERAL LIGHTING CONTROL NOTES:
PR
PD
E
PR
E
TO ADDITIONAL SENSORS IN
ROOM/AREA, WHERE SHOWN
OR REQUIRED, FOR 100%
COVERAGE.
NOTES:
1. OS - OCCUPANCY SENSORS TO BE PROGRAMMED AS AUTOMATIC ON, AUTOMATIC OFF.
2. VS - VACANCY SENSORS TO BE PROGRAMMED AS MANUAL ON, AUTOMATIC OFF.
3. OR EQUAL BY SENSOR SWITCH.
4. SENSOR AUTOMATIC OFF TIME INTERVAL TO BE SET AT 20 MIN.
5. ADJUST SENSOR LOCATION AND SENSITIVITY LEVELS TO MINIMIZE NUISANCE TRIPPING
AND FALSE OFFS.
6. ALL DEVICES TO BE LOCATED IN ACCESSIBLE LOCATIONS APPROVED BY COR.
7. REFER TO SPECIFICATIONS FOR DEVICE FINISHES.
LIGHT SWITCH, 4-WAY
LIGHT SWITCH, SPST, GENERAL PURPOSE
LIGHT SWITCH, 3-WAY
LIGHT SWITCH, KEYED
FULL RANGE SLIDE DIMMER WITH ON/OFF BUTTON, 277VAC RATED
LIGHTING CONTROL LEGEND
DIGITAL WALL SWITCH, ON/OFF, SINGLE ZONE
SENSOR SWITCH
nPODM
DIGITAL WALL SWITCH, ON/OFF, TWO ZONE
SENSOR SWITCH
nPODM 2P
DIGITAL WALL SWITCH, ON/OFF, FOUR ZONE
SENSOR SWITCH
nPODM 4P
DIGITAL ON/OFF WALL SWITCH WITH DIMMING, SINGLE ZONE
SENSOR SWITCH
nPODM DX
DIGITAL ON/OFF WALL SWITCH WITH DIMMING, TWO ZONE
SENSOR SWITCH
nPODM 2P DX
OCCUPANCY SENSOR WALL SWITCH, DUAL TECHNOLOGY, SINGLE POLE,
(800W AT 120VAC, 1200W AT 277VAC)
SENSOR SWITCH
WSX PDT
VACANCY SENSOR WALL SWITCH, DUAL TECHNOLOGY, SINGLE POLE,
(800W AT 120VAC, 1200W AT 277VAC)
SENSOR SWITCH
WSX PDT VA
OCCUPANCY SENSOR WALL SWITCH WITH 0-10V DIMMING, DUAL
TECHNOLOGY, SINGLE POLE
SENSOR SWITCH
WSX PDT D
VACANCY SENSOR WALL SWITCH WITH 0-10V DIMMING, DUAL TECHNOLOGY,
SINGLE POLE
SENSOR SWITCH
WSX PDT D VA
POWER PACK RELAY, ON/OFF, SINGLE ZONE, 16A MP RATED
SENSOR SWITCH
nPP16
POWER PACK RELAY, ON/OFF, SINGLE ZONE, 16A MP RATED WITH 0-10V
DIMMING
SENSOR SWITCH
nPP16 D
CEILING MOUNTED EXTENDED RANGE DUAL-TECHNOLOGY OCCUPANCY
SENSOR, WITH AUXILIARY RELAY FOR CONNECTION TO BAS BY TCC.
SENSOR SWITCH
nCM PDT 9 RJB AR
CEILING MOUNTED EXTENDED RANGE DUAL-TECHNOLOGY VACANCY
SENSOR, WITH AUXILIARY RELAY FOR CONNECTION TO BAS BY TCC.
SENSOR SWITCH
nCM PDT 9 RJB AR
K
D
L1
L2
L4
D1
D2
OS
VS
OSD
VSD
PR
PD
OS
VS
LEVITON
SEE SPECS.
SEE SPECS.
SEE SPECS.
SEE SPECS.
WATTSTOPPER
LMRC-211
WATTSTOPPER
LMDM-101
WATTSTOPPER
LMSW-101
WATTSTOPPER
LMSW-102
WATTSTOPPER
LMSW-104
WATTSTOPPER
LMDM-104
WATTSTOPPER
DSW-301
WATTSTOPPER
DSW-301
WATTSTOPPER
DSW-311
WATTSTOPPER
DSW-311
WATTSTOPPER
LMDC-100
WATTSTOPPER
LMDC-100
WATTSTOPPER
LMRC-101
WATTSTOPPER
S
S
S
S
S
S
S
S
S
S
S
S
S
S
POWER PACK RELAY, ON/OFF, SINGLE ZONE, 16A MP RATED WITH UL924
EMERGENCY FUNCTION
SENSOR SWITCH
nPP16 ER
POWER PACK RELAY, ON/OFF, SINGLE ZONE, 16A MP RATED WITH 0-10V
DIMMING AND UL924 EMERGENCY FUNCTION
SENSOR SWITCH
nPP16 D ER
PR E
PD EWATTSTOPPER
WATTSTOPPER
T
(2) TWO GANGE 4X4 SQUARE,
2-1/8" DEEP, WITH SINGLE
GANG 1/2" EXTENSION RING
ROUTE 1" CONDUIT TO CABLING PATH.
PROVIDE GROUNDING JUMPER TO CABLE
TRAY AT EACH LOCATION.
MOUNT BOTH BESIDE TV
BRACKET, BOXES NO MORE
THAN 2" APART
120 VAC NORMAL POWER
CIRCUIT-SEE POWER
PLANS
DUPLEX
RECEPTACLE
TYPICAL KEYSTONE CAT 6E JACK AND
DATA CABLE TO PATCH PANEL LOCATION.
SEE DIV 27 SPECIFICATIONS.
BL
BLBL
ENGRAVE OUTLET PLATE TO IDENTIFY
SERVICES. REFER TO SPECIFICATIONS
FOR LABELLING REQUIREMENTS.
ROUTE 1" CONDUIT TO NURSE CALL
CONTROL IN HEADWALL
GENERAL NOTES:
1. MAINTAIN A MINIMUM CLEARANCE OF 305mm (12") ON ALL SIDES OF ROOF
PENETRATION FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE
PROPER FLASHING.
2. FLANGES OF ADJACENT FLASHINGS SHALL NOT BE CUT OR
OVERLAPPED.
3. VERIFY ROOF & STRUCTURAL SYSTEM WITH ARCHITECT.
4. COORDINATE FLASHING INSTALLATION WITH ROOFING CONTRACTOR TO
ENSURE PROPER METHODS & MATERIALS ARE USED TO MAINTAIN ROOF
WARRANTY.
PREFABRICATED RUBBER
BOOT CAP WITH GRADUATED
STEPS & WEATHER-PROOF
PRESSURE SEAL TO COLLAR
SEALANT AT PENETRATION
TO MEMBRANE JUNCTURE
BY ROOFING CONTRACTOR
MULTIPLE MEMBRANE STRIPPING
PLIES FEATHERED AT FIELD OF
ROOF BY ROOFING CONTRACTOR.
PRIME FLANGE BEFORE STRIPPING.
PREFABRICATED FORMED 1.52mm (0.06")
THICK ALUMINUM FLASHING ROUND
COLLAR WITH MIN. 76mm (3") WIDE
FLANGE. ATTACH TO ROOF PER
MANUFACTURER'S INSTRUCTIONS
CONDUIT CLAMP. SIZE AS
REQUIRED
BATT INSULATION
ROOF MEMBRANE
WATER CUT-OFF
MASTIC COMPATIBLE
WITH ROOF MEMBRANE
STAINLESS CLAMP, TYP.
9.52mm (3/8") MIN
GALVANIZED
THREADED ROD, TYP.
SEAL-OFF
FITTING,
TYP.
ROOF
STEEL
EXPANSION
ANCHOR
INTEGRAL GALVANIZED LIPPED
STEEL MOUNTING CHANNEL
CONDUIT,
TYP.
CONDUIT
CLAMP. SIZE
AS REQUIRED
LOCKING
SQUARE
WASHER &
LOCKNUT
(3'-0")
MAX
SEISMIC OR EXPANSION
JOINT. FIELD VERIFY
ACTUAL CONDITIONS &
LOCATIONS.
FLOOR OR ROOF STRUCTURE. FIELD
VERIFY ACTUAL CONDITIONS, TYP.
STRUCTURAL MEMBER
(BEAM, JOIST, ETC.), TYP.
JUNCTION BOX, TYP
(SIZE AS REQUIRED)
CONDUIT
TRAPEZE PER
SD260533-03,
TYP.
914mm
BEAM
CLAMP,
TYP.
CONDUIT,
TYP.
PROVIDE 127mm (5") OF SLACK AT
MIDPOINT BETWEEN TWO END OF
FLEXIBLE GALVANIZED STEEL CONDUIT.
PROVIDE GREEN INSULATED COPPER
EQUIPMENT GROUNDING CONDUCTOR
WITH FLEXIBLE CONDUIT.
INTEGRAL GALVANIZED
LIPPED STEEL
MOUNTING CHANNEL
STEEL
EXPANSION
ANCHOR
JUNCTION BOX
(SIZE AS REQUIRED)
CONDUIT FITTING
SPRING
NUT
PROVIDE EXTRA CABLE
TO MAKE COMPLETE LOOP
AROUND BOX PERIMETER
GENERAL NOTE:
1. DETAIL IS APPLICABLE ONLY FOR CONDUIT SMALLER THAN 76mm (3").
I LL IN O IS
S N
A H
A
TR
E B
O R
NTHONY
LICENSED
PROFESSIONAL
OF
ENGINEER
062.059710
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
100% RE-SUBMIT 2020/06/29
C U s e rs
\j h u s to n \D o c u m e n ts
\R
I V
C E
E
L E
C T
R
IC
A L jh u s to n c m ta e g rs
.c o m
.r v t
/2
/2
:4
:5
A
M
EJ100
LIGHT FIXTURE SCHEDULE AND
DETAILSGUIDON-CMTA SDVOSB JV, LLC
1221 N. PENNSYLVANIA ST. SUITE 200
INDIANAPOLIS, IN 46202
CMTA CONSULTING ENGINEERS
903 SPRING ST.
JEFFERSONVILLE, IN 47130
EMERGENCY DEPARTMENT
RENOVATION
820 S. DAMEN AVE.
537-15-160
5/30/2020 CMTA CMTA
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
ELEC - LUMINAIRE SCHEDULE
TYPE DESCRIPTION ACUITY FIXTURE COOPER FIXTURE PHILIPS FIXTURE MOUNTING LAMPS / CCT LUMENS WATTAGE VOLTAGE REMARKS
A1 2X2 LED LAY-IN FLAT PANEL WITH 0-10V DIMMING
AND POINT TO SUPPORT FROM STRUCTURE AT
EACH CORNER
LITHONIA
#EPANL-2X2-3400LM-80CRI-35K-MIN10-Z
T-MVOLT-E10WCP
METALUX 22FP3235C DAY-BRITE #2FXP38L835-2-DS-UNV-DIM RECESSED LED/3500K 3400 32 120/208V
A1E SAME AS 'A1' WITH INTEGRAL EMERGENCY BATTERY
PACK, TEST SWITCH AND SELF DIAGNOSTIC.
LITHONIA
#EPANL-2X2-3400LM-80CRI-35K-MIN10-Z
T-MVOLT-E10WCP
METALUX #22FP3235C-EL14W DAY-BRITE
#2FXP38L835-2-DS-UNV-DIM-EMLED
RECESSED LED/3500K 3400 32 120/208V
A2 2X2 LED LAY-IN FLAT PANEL WITH 0-10V DIMMING
AND POINT TO SUPPORT FROM STRUCTURE AT
EACH CORNER
LITHONIA
#EPANL-2X2-4800LM-80CRI-35K-MIN10-Z
T-MVOLT-E10WCP
METALUX 22FP4235C DAY-BRITE #2FXP45L835-2-DS-UNV-DIM RECESSED LED/3500K 4800 46 120/208V
A2E SAME AS 'A2' WITH INTEGRAL EMERGENCY BATTERY
PACK, TEST SWITCH AND SELF DIAGNOSTIC.
LITHONIA
#EPANL-2X2-4800LM-80CRI-35K-MIN10-Z
T-MVOLT-E10WCP
METALUX #22FP4235C-EL14W DAY-BRITE
#2FXP45L835-2-DS-UNV-DIM-EMLED
RECESSED LED/3500K 4800 46 120/208V
A5 2X2 RECESSED LED VANDAL RESISTANT FLANGED
LUMINAIRE WITH 0-10V DIMMING TO 1%
KURTZON
#VL-R-3-2X2-3LEDR-835-UNV-1-WHT
FAILSAFE
#FMR-D-24-2-LD4-3-STD-35-UNV-85-ED1
D-1-CPHF-SWBR
LOS ANGELES LTG.
#FSE120-4800L-2L-FSW-PPC2-1DRDM-U
NV-2-835
RECESSED LED/3500K 4325 55 120/208V
A5E SAME AS 'A5' WITH INTEGRAL EMERGENCY BATTERY
PACK, TEST SWITCH AND SELF DIAGNOSTIC.
KURTZON
#VL-R-3-2X2-3LEDR-835-UNV-1-EM10-W
HT
FAILSAFE
#FMR-D-24-2-LD4-3-STD-35-UNV-85-ED1
D-1-EL10W-CPHF-SWBR
LOS ANGELES LTG.
#FSE120-4800L-2L-FSW-PPC2-BPL10-1D
RDM-UNV-2-835
RECESSED LED/3500K 4325 55 120/208V
B1 2X4 LED LAY-IN FLAT PANEL WITH 0-10V DIMMING
AND POINT TO SUPPORT FROM STRUCTURE AT
EACH CORNER.
LITHONIA
#EPANL-2X4-4800LM-80CRI-35K-MIN10-Z
T-MVOLT
METALUX #24FP4735C DAY-BRITE #2FXP48L835-4-DS-UNV-DIM RECESSED LED/3500K 4460 41 120/208V
B1E SAME AS 'B1' WITH INTEGRAL EMERGENCY BATTERY
PACK, TEST SWITCH AND SELF DIAGNOSTIC.
LITHONIA
#EPANL-2X4-4800LM-80CRI-35K-MIN10-Z
T-MVOLT-E10WCP
METALUX #24FP4735C-EL14W DAY-BRITE
#2FXP48L835-4-DS-UNV-DIM-EMLED
RECESSED LED/3500K 4460 41 120/208V
D1 6" RECESSED LED CAN LIGHT FIXTURE WITH 0-10V
DIMMING. WHITE REFLECTOR AND FLANGE.
LITHONIA
#LDN6-35-15-L06-WR-MVOLT-GZ1-90CRI
HALO
#HC6-15-D010-HM6-12-935-61-MD-W
LIGHTOLIER
#6RN-C6L-15935MZ10U-C6RDLWH
RECESSED LED/3500K 1500 18 120/208V
D5 6" LED RECESSED VANDAL RESISTANT DOWNLIGHT
WITH 0-10V DIMMING TO 1%. SELF FLANGED AND
POLYCARBONATE BOTTOM LENS.
KURTZON
#VL-PBD-4-8-DLM15-835-UNV-WB-WT-FP
L-TPWHT
FAIL SAFE #FLD6BX-10-D010
FEU6B-1/2-80-35 F6LBXV-M-1-MW-BL85
LIGHTOLIER
#6RN-C6L-10935MZ10U-C6RDLWH
RECESSED LED/3500K 1000 12 120/208V
K1 10' LINEAR RECESSED LED WITH 0-10V DIMMING TO
10%
FOCAL POINT
#FSM2L-FL-625LF-35K-1C-UNV-LD1-WH-
10FT
NEO-RAY
#S123DR-S-775-835-XX-10F-1-U-F-W
PRECISION ARCHITECTURAL LTG
#MLR2-HO-K35-80-10-XX-LOH-UNV-DIM1
RECESSED LED/3500K 6250 78 120/208V
K1E SAME AS 'K1' WITH INTEGRAL EMERGENCY BATTERY
PACK, TEST SWITCH AND SELF DIAGNOSTIC.
FOCAL POINT
#FSM2L-FL-625LF-35K-1C-UNV-LD1-1EM
-WH-10FT
NEO-RAY
#S123DR-S-775-835-XX-10F-1-B2-U-F-W
PRECISION ARCHITECTURAL LTG
#MLR2-HO-K35-80-10-XX-LOH-UNV-DIM1
-EBPLST
RECESSED LED/3500K 6250 78 120/208V
K2 6' LINEAR RECESSED LED WITH 0-10V DIMMING TO
10%
FOCAL POINT
#FSM2L-FL-625LF-35K-1C-UNV-LD1-WH-
6FT
NEO-RAY
#S123DR-S-775-835-XX-6F-1-U-F-W
PRECISION ARCHITECTURAL LTG
#MLR2-HO-K35-80-06-XX-LOH-UNV-DIM1
RECESSED LED/3500K 3750 47 120/208V
K2E SAME AS 'K2' WITH INTEGRAL EMERGENCY BATTERY
PACK, TEST SWITCH AND SELF DIAGNOSTIC.
FOCAL POINT
#FSM2L-FL-625LF-35K-1C-UNV-LD1-1EM
-WH-6FT
NEO-RAY
#S123DR-S-775-835-XX-6F-1-B2-U-F-W
PRECISION ARCHITECTURAL LTG
#MLR2-HO-K35-80-06-XX-LOH-UNV-DIM1
-EBPLST
RECESSED LED/3500K 3750 47 120/208V
L1 4' LED GASKETED AND SEALED INDUSTRIAL STRIP
WITH ACRYLIC LENS AND INTEGRAL MOTION
SENSOR FOR ON/OFF CONTROLS. STEM MOUNTED
WITH THREADED ROD MOUNTING ASSEMBLY.
LITHONIA
#FEM-L48-4000LM-IMAFL-WD-MVOLT-GZ
10-35K-80CRI-DPMB-SBOR10
METALUX
#4VT3-LD5-4-W-UNV-L835-CD1-MSWL20
DAY-BRITE
#DWAE35L835-4-UNV-MD360W
PENDANT LED/3500K 3824 24 120/208V
L1E SAME AS 'L1' WITH INTEGRAL EMERGENCY BATTERY
PACK, TEST SWITCH AND SELF DIAGNOSTIC.
LITHONIA
#FEM-L48-4000LM-IMAFL-WD-MVOLT-GZ
10-35K-80CRI-DPMB-E10WMCP-SBOR10
METALUX
#4VT3-LD5-4-W-UNV-EL10W-L835-CD1-
MSWL20
DAY-BRITE
#DWAE35L835-4-UNV-MD360W
PENDANT LED/3500K 3824 24 120/208V
U1 2' LED UNDERCABINET LIGHT. HEAVY GUAGE
ALUMINUM HOUSING MATTE WHITE FINISH. 90 CRI.
LITHONIA
#UCLD-18IN-30K-90CRI-WH-UCDJB
HALO #HU10-24-D-9-30-P-HU109 RDA #UC-LED20-WW SURFACE LED/3500K 1500 17 120/208V
X1 CHICAGO EDGE-LIT LED EXIT SIGN. CEILING
MOUNTED WITH RECESSED HOUSING. SINGLE FACE,
NO ARROW.
LITHONIA #EDGC-1-RW-CH3-EL SURE-LITES #ECHX-6-SHWH CHLORIDE #CE2RWWSWLARA RECESSED LED 2 120/208V OWNER TO SELECT FROM THE FULL LINE OF AVAILABLE
OPTIONS IN THE SUBMITTAL FOR THE SURE-LITES #ECHX
SERIES EXIT SIGN (OR EQUIVALENT) REFER TO FLOOR PLAN
FOR NUMBER OF SIDES AND CHEVRON REQUIREMENTS.
X2 SAME AS 'X1' EXCEPT ARROW RIGHT. LITHONIA #EDGC-1-RW-CH3-EL SURE-LITES #ECHX-6-SHWH CHLORIDE #CE2RWWSWLARA RECESSED LED 2 120/208V OWNER TO SELECT FROM THE FULL LINE OF AVAILABLE
OPTIONS IN THE SUBMITTAL FOR THE SURE-LITES #ECHX
SERIES EXIT SIGN (OR EQUIVALENT) REFER TO FLOOR PLAN
FOR NUMBER OF SIDES AND CHEVRON REQUIREMENTS.
X4 SAME AS 'X3' EXCEPT DOUBLE FACE. LITHONIA #EDGC-1-RW-CH3-EL SURE-LITES #ECHX-6-SHWH CHLORIDE #CE2RWWSWLARA RECESSED LED 2 120/208V OWNER TO SELECT FROM THE FULL LINE OF AVAILABLE
OPTIONS IN THE SUBMITTAL FOR THE SURE-LITES #ECHX
SERIES EXIT SIGN (OR EQUIVALENT) REFER TO FLOOR PLAN
FOR NUMBER OF SIDES AND CHEVRON REQUIREMENTS.
NOT TO SCALEEJ100
1 TYPICAL MEDICAL GAS / LINE PRESSURE DETAIL
SCALE: 12" = 1'-0"EJ100
2 LIGHTING CONTROL DETAILS
SCALE: 12" = 1'-0"EJ100
3 TELEVISION OUTLET INSTALLATION DETAIL
NOT TO SCALEEJ100
4 CONDUIT ROOF PENETRATION DETAIL
NOT TO SCALEEJ100
5 CONDUIT EXPANSION JOINT CROSSING DETAIL - FLEXIBLE CONDUIT
SEISMIC SUPPORT
RECESSED MOUNTED FIXTURE
NO SCALE
SEISMIC SUPPORT
PENDANT MOUNTED FIXTURE
NO SCALE
NO SCALE
NO SCALE
NO SCALE
WALL PENETRATION FIRE PROOFING
D
C
D ML
C
ES
MD
RE
MD
ACMACM
NO SCALE
FLOOR PENETRATION FIRE PROOFING
SEISMIC CONCRETE WALL-MOUNTED EQUIPMENT
VOICE AND DATA WIRING IDENTIFICATIONTYPICAL COMBINATION TEL/DATA OUTLET
NO SCALE
ELECTRIC STRIKEMAGNETIC LOCK
NO SCALE
TYPICAL WIRING DIAGRAM FOR PROXIMITY CARD READER
MOTOR CONDUIT CONNECTION
NO SCALESEISMIC SUPPORT
RECESSED MOUNTED FIXTURE
NO SCALE
ANCHORAGE
NO SCALE
NO SCALE
LOCATIONS OF BRACING - PLAN VIEW
CONDUIT SUPPORT SEISMIC SWAY BRACING CABLES
NO SCALE
TRAPEZE SUPPORT SEISMIC SWAY BRACING CABLES
NO SCALE
SEISMIC STIFFENER FOR THREADED RODS
NO SCALE
TRAPEZE TRANSVERSE & LONGITUDINAL BRACING DETAIL
NO SCALE
SLAB HUNG LARGE CONDUIT SEISMIC SUPPORT
NO SCALE
SEISMIC SWAY BRACING CABLE ANCHOR
NO SCALE
NO SCALE
SEISMIC ISOLATOR NOTES FOR SEISMIC BRACING
SEISMIC ANCHOR BOLT (SAB)
NO SCALE
TO MASONRY OR CONCRETE
LATERAL BRACING ATTACHEMENT
ISOLATED POWER PANEL WIRING DIAGRAM
NO SCALE
DOOR ELECTRICAL ROOMDOOR ELECTRICAL ROOM
RR
NOTE:
INSERT #2 TAPPING SCREWS
THRU CLAMP AND TEE BAR
(2 PER CLAMP)
RECESSED
TROFFER
SEISMIC SUPPORTED
TEE BAR CEILING
ONE #CHB CADDY CLIP
ATTACHED TO EACH
END OF FIXTURE WITH
10-32x1/2 MACHINE
SCREW AND NUT.
2 PER 4' FIXTURE,
4 PER 8' FIXTURE.
CONDUIT
STEM
CADDY SPEED
LINK
HOOK
ANCHOR IN CONCRETE
WITH EXPANSION BOLT
OR LEAD ANCHOR
CADDY AB
ANGLE BRACKET
CADDY SLD2L
CABLE HANGER
(2) RJ45 JACKS
NOTE: PROVIDE BLANK INSERTS ON ALL UN-USED PORTS.
D D
D
GROMMETT
(2) RJ45 JACKS
LAY-IN
CEILING
4" X 4" X 2.5" BOX
WITH SINGLE
GANG
TRIM RING
1" CONDUIT
FOR VOICE AND
DATA
(IN WALL)
COVERPLATE SHALL
ACCOMODATE
VOICE
AND DATA CABLES.
(2) BLANK BUILDING NUMBER
1.XXXX.01 D
TYPEWRITTEN PERMANENT CABLE
IDENTIFICATION TAG ON EACH END
OF CABLE AFTER TERMINATIONS-
(AT DEVICE AND IDF/MDF)
VOICE/DATA CABLE. SEE SPECIFICATIONS
JACKET
DROP NUMBER IN ROOM.
NUMBERING SHALL
START
FROM THE LEFT, AS YOU
WALK IN THE DOORWAY,
AND CONTINUE AROUND
THE ROOM CLOCKWISE
ROOM NUMBER SERVED
UNSHIELDED TWISTED
PAIR
(TYPICAL OF 4)
iSTAR
SECURITY
PANEL
NORMALLY
CLOSED
RELAY
DOOR
LOCK
POWER
SUPPLY
18 AWG FOR DISTANCES GREATER THAN 300 FEET
* USE 20 AWG FOR DISTANCES GREATER THEN 200 FEET AND
22 AWG, 6 COND., SHIELDED*WIEGAND READER WIRING
18 AWG., 2 COND., SHIELDEDSIGNAL WIRING
22 AWG., 4 COND.
18 AWG., 2 COND.
CABLE TYPE
POWER AND SIGNAL WIRING
POWER SUPPLY WIRING
DESCRIPTIONSYMBOL
NORMALLY
CLOSED
RELAY
iSTAR
SECURITY
PANEL
DOOR
LOCK
POWER
SUPPLY
FIRESTOP
FILL
MATERIAL
(TYPICAL)
5/8" GYPSUM
WALLBOARD
(TYPICAL)
FLOOR
SLAB
CSD SPLIT
FIRE-SAFE
SLEEVE
ANCHORED
FROM
BELOW
CORE DRILLED
HOLE OR
STEEL PIPE
SLEEVE
FIRESTOP
FORMING
MATERIAL
(TYPICAL)
METAL STUD
CONDUIT OR
SLEEVE
TELECOMMUNICATIONS
CSD SPLIT
SEALING
PLUG
CONDUIT OR
SLEEVE
TELECOMMUNICATIONS
CABLE TYPE - D=DATA; V=VOICE; W=WIRELESS AP
PROVIDE STAINLESS STEEL 2-HOLE STRAPS
FOR CONDUIT SUPPORT.
1.
PHASE
CONDUCTORS
AND EQUIPMENT
GRD'G CONDUCTOR
STARTER/
DISCONNECT/
VFD
WALL
PAD
FLOOR
TERMINAL BOX
MOTOR
LIQUIDTIGHT CONDUIT
CONNECTOR
(2) PLACES (TYP.)
CONDUIT
LIQUIDTIGHT
FLEXIBLE METAL
CONDUIT (TYP)
CADDY SFCLT
SEISMIC FIXTURE
CLAMP (SFC) WITH
SELF TAPPING
SCREWS ONE(1)
AT EACH CORNER
(TYP. OF 4)
CEILING GRID
SUPPORT BY G.C.
CEILING GRID SUPPORT
BY G.C.
NOTES
1. SFC MAIN RUNNER FLANGE SHALL BE INSTALLED UNDER
THE LIGHT FIXTURE FLANGE.
2. SFC CROSS RUNNER FLANGE SHALL BE INSTALLED OVER
THE LIGHT FIXTURE FLANGE.
MINIMUM OF 3/8" EYEBOLT, WASHER AND
NUT THROUGH STEEL STRUCTURE OR
ANCHOR IN CONCRETE WITH EXPANSION
BOLT OR LEAD ANCHOR
10'
MAX
BACK OF
STEEL PANEL
INSIDE NEOPRENE
ELEMENT
SEISMIC
ANCHOR BOLT
TYPE "SAB"
OUTER
STEEL SLEEVE
OUTSIDE
NEOPRENE
ELEMENT
STEEL DISK
ELONGATED INNER
STEEL SLEEVE
NOTES:
1. BASED ON MASON INDUSTRIES INC. TYPE "PB" NEOPRENE
BUSHING.
d d
TAR
U
N
A
RUN `B'
LL
TT T TBT
`TA' CAN BE USED AS LONGITUDINAL
BRACE FOR RUN `B' AND `TB' AS
LONGITUDINAL BRACE FOR RUN `A'
WHEN `d' IS < 24" FOR CONDUITS
PROVIDE TRANSVERSE
BRACE AT LAST
VERTICAL SUPPORT
MAXIMUM SPACING FOR
TRANSVERSE BRACES
(TYPICAL)
MAXIMUM SPACING FOR
LONGITUDINAL BRACES
NOTES:
1. REFER TO OTHER DETAILS FOR GENERAL REQUIREMENTS FOR SPACING
OF BRACES.
`T' - INDICATES TRANSVERSE BRACING - 1 SOLID BRACE.
'L' - INDICATES LONGITUDINAL BRACING - 1 SOLID BRACE AT
INDIVIDUAL CONDUITS AND 2 SOLID BRACES AT TRAPEZE
HANGERS
MAX
10'
45°TYP.
PLAN VIEW
PIPE
HANGER
(TYP.)
SLACK 1/8"
AIRCRAFT
CABLE (TYP.)
SEISMIC
CABLE
BRACE (TYP.)
SINGLE CONDUIT
2-1/2" OR
LARGER
ALL
THREADED
ROD
(TYP.)
45°TYP.
PLAN VIEW
TRAPEZE
SUPPORTED
CONDUITS
SLACK 1/8"
AIRCRAFT
CABLE (TYP.)
SEISMIC
CABLE
BRACE (TYP.)
TRAPEZE TYPE
SUPPORTS
(TYP.)
ROD STIFFENER CHART
NOTE: MINIMUM OF (2) "SCR"
REQUIRED
PER ROD.
(mm)INCHES
ATR
SIZE
"X" MAX. SPACING
BETWEEN ROD CLAMP
(457.2)
(584.2)
(711.2)
(838.2)
18"
23"
28"
33"
1/2"-13
5/8"-11 3/4"-10 7/8"-9
NOTE: IF ROD STIFFENER IS REQUIRED
SEE ADJACENT CHART.
(mm)INCHES
ATR
SIZE
MAX. ROD LENGTH
WITHOUT ROD STIFFENER
(635.0) (787.4)
(939.8) (1092.2)
25" 31"
37" 43"
1/2"-13 5/8"-11
3/4"-10 7/8"-9
6" MAX
"X"
"X"
6" MAX
SEISMIC ANCHOR AND
ANCHOR BOLT
STRUCTURE
ALL THREADED
ROD (ATR)
CLAMPS
(3) PER ROD
STIFFENER
ANGLE
ATTACHED TO
PIPE CLAMP OR
U-TYPE CHANNEL
SECTION A-A
"SRC"
ROD
CLAMP
ANGLE
ROD
NOTE:
1. BASED ON MASON INDUSTRIES INC. TYPE "SRC" ROD CLAMP.
NOTE:
1. ADD LONGITUDINAL BRACES AT EACH END, IF REQUIRED AT
THIS LOCATION.
B-LINE
B22 CHANNEL
SIZE AS REQUIRED
MASON
SCBH
ADJUSTABLE
HINGE
TRANSVERSE
BRACE
HEX NUT AND
SQUARE WASHER
B-LINE
B2400 SERIES
PIPE STRAPS
ROD
STIFFENER
MASON
SCB
ADJUSTABLE
HINGE
1 (MIN.)
6" (MIN.)
1/4" AIRCRAFT
CABLE
ALL THREADED
RODBUILDING
STRUCTURE
SEISMIC ANCHORS
CABLE
NUT &
WASHER
S
PIPE
HANGER
THREDED ROD
MAX. 10FT.
SPACING
SLACK SWAY
BRACING CABLE
1/8" GAL.
STEEL AT
APPROPRIATE
INTERVALS
SEISMIC CABLE
BRACE (2)
REQUIRED PER
CABLE
LOCATED 12" OR
MORE FROM STRUCTURE
SEISMIC
CABLE
BRACE
NOTES:
1. BASED ON MASON INDUSTRIES INC. TYPE "SCB" BRACE.
SLACK 1/8"
GAL. STEEL
AIRCRAFT CABLE
SWIVEL
CONNECTION
ANCHORED TO
STRUCTURE
ABOVE
(2) SEISMIC
CABLE BRACES
PER CABLE
TYPE "SCB"
NOTE
1. BASED ON MASON INDUSTRIES INC. TYPE "HG" NEOPRENE
ISOLATOR.
OVERSIZED HOLE
SEISMIC ANCHOR
CONCRETE
FLOOR
EQUIPMENT
SUPPORT
LEG
SEISMIC ANCHOR
BOLT
STEEL WASHER
NEOPRENE
BUSHING
"TYPE HG"
FIELD TRIM BUSHING
TO MATCH HOLE DEPTH
T
NOTE:
LATERAL DIRECTION OF SWAY BRACING CABLES SHALL
ALTERNATE AS SHOWN AT APPROPRIATE INTERVALS.
NOTE:
LATERAL DIRECTION OF SWAY BRACING CABLES SHALL
ALTERNATE AS SHOWN AT APPROPRIATE INTERVALS.
GENERAL
1. IMPORTANCE FACTOR Ip = 1.5.
2. HANGERS AND ATTACHMENT METHODS TO STRUCTURAL MEMBERS SHALL
USE DEVICES INCLUDED IN FEDERAL SPECIFICATION WW-H-171
(MSS SP-58) OR BE BOLTED/WELDED AS APPROVED BY THE ENGINEER.
BRACES SHALL BE CONNECTED TO THE HANGERS/SUPPORTS FOR
CONDUIT.
3. SEE THE SPECIFICATIONS FOR REQUIRED STRENGTH OF BRACING.
4. ALL ELECTRICAL COMPONENT SUPPORTS AND MEANS BY WHICH THEY ARE
ATTACHED TO THE COMPONENT SHALL BE DESIGNED FOR THE FORCES
AND DISPLACEMENTS DETERMINED BY ASCE 7 SECTIONS 13.3.1 AND
13.3.2.
EXCEPTIONS:
a. CONDUIT LESS THEN TRADE SIZE 2.5".
b. TRAPEZE ASSEMBLIES SUPPORTING CONDUIT, BUS DUCT OR CABLE
TRAYS WHERE THE TOTAL WEIGHT SUPPORTED BY THE TRAPEZZE
ASSEMBLY IS LESS THEN 10LB/FT.
c. CONDUIT SUSPENDED LESS THEN 12" TO STRUCTURE.
5. LATERAL SEISMIC FORCE SHALL BE CONSIDERED TO ACT CONCURRENTLY
WITH THE DEAD LOAD. THE SLENDERNESS RATIO (l/r) OF BRACES SHALL
NOT EXCEED 200, WHERE (l) IS THE LENGTH OF THE BRACE AND (r) IS
THE LEAST RADIUS OF GYRATION, BOTH IN INCHES.
6. TYPICAL SEISMIC DETAILS ARE PROVIDED ON THE DRAWINGS FOR
REFERENCE ONLY. CONTRACTOR SHALL PROVIDE SHOP DRAWINGS TO COR
FOR REVIEW AND APPROVAL. SHOP DRAWINGS SHALL SHOW ALL
EQUIPMENT ANCHORAGE TO WALLS/CEILINGS/FLOORS AND SHALL INCLUDE
SIZE OF SEISMIC ANCHOR BOLTS USED FOR EACH SYSTEM.
7. BRACES FOR SINGLE CONDUIT SUPPORTS SHALL BE ATTACHED
DIRECTLY TO THE CONDUIT, NOT TO THE CONDUIT HANGER.
8. ALL BRACING SHALL BE LOCATED WITHIN 6" OF THE VERTICAL HANGER
SUPPORT.
9. TRUSS CHORDS OF BAR JOISTS OR FROM CONCRETE MEMBERS.
10. IDENTIFY POSITION OF REINFORCING STEEL PRIOR TO DRILLING HOLES
FOR ANCHORS TO AVOID DAMAGE OF EXISTING REINFORCING. NOTIFY
COR IF REINFORCING STEEL IS ENCOUNTERED DURING DRILLING.
SEISMIC ANCHOR AND
ANCHOR BOLT
NOTE:
DRILLED-IN AND STUD-WEDGE OR FEMALE-WEDGE TYPE IN ZINC-COATED
STEEL FOR INTERIOR APPLICATIONS AND STAINLESS STEEL FOR EXTERIOR
APPLICATIONS. SELECT ANCHOR BOLTS WITH STRENGTH REQUIRED FOR
ANCHOR AND AS TESTED ACCORDING TO ASTM E 488. MINIMUM LENGTH OF
EIGHT TIMES DIAMETER. MASON INDUSTRIES, INC. TYPE SAB OR APPROVED
EQUAL.
SAB
WEDGE
ANCHO
R
CAP SCREW
WITH
STANDARD
WASHER
SEISMIC
ANCHOR
INTERNALLY
THREADED
EXPANSIO
N
WEDGE
PULL
THROUGH
RESISTANT
SHOULDER
ADJUSTABLE
MOUNTING
BRACKET
T-BAR
CEILING
GRID
SHEET METAL
SCREWC-BAR
TO T-BAR PLUS
SAME ON DIAGONAL
MOUNT C-BAR LIGHT
FIXTURE SUPPORT
CHANNEL ON T-BAR
MOUNT ADJUSTABLE
MOUNTING
BRACKETS
TO LIGHT FIXTURE
AND C-CHANNEL
5/8" BOLT B-LINE, B22 CHANNEL
LONGITUDINAL OR
TRANSVERSE BRACE
(9'-4" MAX LENGTH)
1/2"x1-1/4" HEX
HEAD CAP SCREWS
AND N225WO NUTS
EXPANSION
ANCHOR
11. AT RISERS, PROVIDE LATERAL RESTRAINT AT THE TOP AND BOTTOM OF
THE RISER, AND AT INTERMEDIATE POINTS NOT TO EXCEED 30FT.
12. STACKED TRAPEZES SUPPORTED BY THE SAME RODS SHALL BE BRACED
INDEPENDENTLY FROM ONE ANOTHER. THE ROD SUPPORTS IN EACH
SECTION MAY REQUIRED STIFFENERS.
13. PROVIDE CONDUITS THAT ARE RIGIDLY SECURED TO THE BUILDING
STRUCTURE ON OPPOSITE SIDES OF A BUILDING EXPANSION JOINT WITH
JUNCTION BOXES ON BOTH SIDES OF THE JOINT. CONNECT JUNCTION
BOXES WITH 15 INCHES OF SLACK FLEXIBLE CONDUIT.
14. SWAY BRACING SPACING PER STRAIGHT LENGTH OF CONDUIT:
A. SINGLE STEEL CONDUIT LARGER THAN 2-1/2":
TRANSVERSE - 40'; LONGITUDINAL - 80'
B. SINGLE EMT CONDUIT LARGER THAN 2-1/2":
TRANSVERSE - 20'; LONGITUDINAL - 40'
C. TRAPEZE SUPPORT: TRANSVERSE - 40'; LONGITUDINAL - 40'.
D. IF SWAY BRACING IS PROVIDED AT 45° ANGLE TO SATISFY BOTH
TRANSVERSE AND LONGITUDINAL SPACING THAN THE TRANSVERSE
SPACING REQUIREMENTS SHALL BE USED.
15. A STRAIGHT LENGTH OF CONDUIT IS DEFINED 10' OR GREATER IN
LENGTH. A HORIZONTAL OFFSET IS ALLOWED PER STRAIGHT LENGTH
WITHOUT ADDITIONAL BRACING IF THE OFFSET IS LESS THEN THE
TRANSVERSE BRACE SPACING DIVIDED BY 16 OR AS RECOMMENDED BY
THE SEISMIC BRACING MANUFACTURER.
INNER NEOPRENE
BUSHING
TYPE "PB"
NOTES:
1. COORDINATE ALL DEVICE, WIRING AND PROGRAMING REQUIREMENTS
TO
MATCH THE EXISTING FACILITY STANDARD.
NO SCALE
B B
D
I LL IN O IS
S N
A H
A
TR
E B
O R
NTHONY
LICENSED
PROFESSIONAL
OF
ENGINEER
062.059710
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
100% RE-SUBMIT 2020/06/29
C U s e rs
\j h u s to n \D o c u m e n ts
\R
I V
C E
E
L E
C T
R
IC
A L jh u s to n c m ta e g rs
.c o m
.r v t
/2
/2
:4
:0
A
M
EJ101
ELECTRICAL DETAILS
GUIDON-CMTA SDVOSB JV, LLC
1221 N. PENNSYLVANIA ST. SUITE 200
INDIANAPOLIS, IN 46202
CMTA CONSULTING ENGINEERS
903 SPRING ST.
JEFFERSONVILLE, IN 47130
EMERGENCY DEPARTMENT
RENOVATION
820 S. DAMEN AVE.
537-15-160
5/30/2020 CMTA CMTA
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
EMERGENCY UNIT SUBSTATION
FROM GEN H.V.
SUBSTATION 4160V
3 33∅
2000A FR
2000A TR
2000A BUS
480Y/277V
4160V
BRANCH
SERVING
THIS
BUILDING
BP
NE
L
BPBP
NE
L
BPBP
NE
L
BP
1600A FR
1200A TR
800A FR
175A TR
800A FR
800A TR
STUB TO NEAR DIST EQUIP (TYP)
LP-1-1
LP-3-1
LP-5-1
LP-7-1
LP-9-1
H-DP-3-1
H-DP-6-1
H-DP-9-1
H-DP-R-1
H-DP-1-1
LDP-1-1
H-EDP-2-2
H-EDP-5-1
H-EDP-8-1
H-EDP-12-1
EDP-2-1
M A
IN
LSDP-2-1
CP-1-1
CP-3-1
CDP-2-1
CP-5-1
CP-7-1
CP-9-1
ATS-3 ATS-2 ATS-1
T-3
T-2
DS-2
DS-1
112.5 KVA
500 KVA
TRANSFER S3ITCH ROOM
NORMAL UNIT SUBSTATION
2ND FLOOR
1ST FLOOR
T-1
750 KVA
2ND FLOOR
3RD FLOOR
4TH FLOOR
5TH FLOOR
6TH FLOOR
7TH FLOOR
8TH FLOOR
9TH FLOOR
10TH FLOOR
ROOF
FROM
H-DP-1-1
FROM
EDP-2-1
CDP-2-1 1ST FLOOR
2000 KVA OA
2300 KVA FA
4160VD - 480Y/277V
FROM NORMAL H.V.
SUBSTATION 4160V
3 33∅
1200A-4P 200A -3P 800A-3P
1200A MLO, 480Y/277V
2500A MCB 3/O GFI, 208Y/120V
800A
(TYP.)
400A
(TYP.)
200A
800A800A
(TYP.)
1600A MCB 3/O GFI, 208Y/120V, 65K AIC
400A MCB 3/O GFI, 208Y/120V, 65K AIC
1200A MLO, 480Y/277V, 65K AIC
400A
(TYP.)
LA
FROM
65K AIC
65K AIC
M A
IN
1200A
FR
3200A FR
3200A TR GFI
3200A BUS
480Y/277V
1200A
FR
CONTROL
CUBE
MAIN
1200A
FR
50/51
50/51
MAIN
1600A FR
1200A TR/GFI
800A FR
175A TR
800A FR
800A TR
1600A FR
1200A TR/GFI
1600A FR
1200A TR/GFI
1600A FR
SPACE
1600A FR
SPACE
1600A FR
SPACE
480V 65KAIC 480V 65KAIC 480V 65KAIC
M A
IN
800A FEED
THROUGH
208Y/120V, 50K AIC
800A FEED
THROUGH
208Y/120V, 50K AIC
800A MLO
208Y/120V, 50K AIC
800A MLO
208Y/120V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A MLO
480Y/277V, 50K AIC
ST
U
B T
O N
EA
R D
IS
T E
Q U
IP
BLDG C1
225A 208Y/120V, 50K AIC
1/4"x4"X18" CU
GROUNDING BAR
ON STANDOFFS IN
NEMA 1
ENCLOSURE
1#500 CU
INSULATED IN
1-1/2" C
EXOTHERMIC
3ELDS TYP
1#500 CU
INSULATED IN
1-1/2" C
1#500 CU
INSULATED IN
1-1/2" C
1#500 CU
INSULATED IN
1-1/2" C
1#500 CU
INSULATED IN
1-1/2" C
1#500 CU
INSULATED IN
1-1/2" C
1#500 CU
INSULATED IN
1-1/2" C
1#500 CU
INSULATED IN
1-1/2" C
1#500 CU
INSULATED IN
1-1/2" C
1#500 CU
INSULATED IN
1-1/2" C
1#500 CU
INSULATED IN
1-1/2" C TO THE
MAIN GROUNDING
BAR IN BLD 1C
225A MLO
480Y/277V, 50K AIC
100A MLO
208Y/120V, 50K AIC
100A MLO
208Y/120V, 50K AIC
225A
100A
225A
100A
(4) 100-3P
AND (12)
20A-1P CBS.
GENERATORS
LOCATED IN BUILDING 42.
EXISTING NORMAL S3ITCHGEAR
4160V
NOTE 22
LOCATED ON THE FIRST
FLOOR OF BUILDING 1C
50/51
800A FEED
THROUGH
208Y/120V, 50K AIC
800A FEED
THROUGH
208Y/120V, 50K AIC
800A MLO
208Y/120V, 50K AIC
800A MLO
208Y/120V, 50K AIC
800A FEED
THROUGH
208Y/120V, 50K AIC
800A FEED
THROUGH
208Y/120V, 50K AIC
800A MLO
208Y/120V, 50K AIC
800A MLO
208Y/120V, 50K AIC
800A FEED
THROUGH
208Y/120V, 50K AIC
800A FEED
THROUGH
208Y/120V, 50K AIC
800A MLO
208Y/120V, 50K AIC
800A MLO
208Y/120V, 50K AIC
800A FEED
THROUGH
208Y/120V, 50K AIC
800A FEED
THROUGH
208Y/120V, 50K AIC
800A MLO
208Y/120V, 50K AIC
800A MLO
208Y/120V, 50K AIC
400A MLO
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A MLO
480Y/277V, 50K AIC
400A MLO
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A MLO
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A MLO
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
FROM
LDP-1-1
CLP-C1
LP-C1
H-DP-C1
H-EDP-C1
H-EDP-1-1
H-EDP-3-1
H-EDP-4-1
H-EDP-6-1
H-EDP-7-1
H-EDP-9-1
H-EDP-10-1
H-DP-2-1
H-DP-4-1
H-DP-2-1
H-DP-5-1
H-DP-7-1
H-DP-8-1
H-DP-10-1
H-EDP-R-1
H-EDP-8-1
H-EDP-5-1
H-EDP-2-1
CLP-10-1
CLP-9-1
CLP-8-1
CLP-7-1
CLP-6-1
CLP-5-1
CLP-4-1
CLP-3-1
CLP-2-1
CLP-1-1
LP-10-1
LP-9-1
LP-8-1
LP-7-1
LP-1-1
H-DP-R-1
H-DP-6-1
H-DP-3-1
H-DP-9-1
LP-6-1
LP-5-1
LP-4-1
LP-3-1
LP-2-1
208Y/120V/3Φ/4W
GECP
225A
EMERGENCY
CRITICAL
NEW PANEL
208Y/120V/3Φ/4W
GP
225A
NORMAL
NEW PANEL
480Y/277V/3Φ/4W
GECP
100A
EMERGENCY
EQUIPMENT
NEW PANEL
RISER LINE LEGEND:
NE3 CONSTRUCTION
EXISTING TO REMAIN
XXX
XXX
A 1 1 2A
B
ALL EQUIPMENT IS EXISTING TO REMAIN, EXCEPT 3HERE NOTED OTHER3ISE.
NEW FEEDER NOTES:
A. PROVIDE (4) #4/0 A3G AND (1) #2 A3G GND IN 3" C.
B. PROVIDE (4) #1 A3G AND (1) #6 A3G GND IN 2" C.
RISER TAGGED NOTES:
1. PROVIDE NE3 225A TRIP RATING PLUG IN EXISTING 250A
GE SPECTRA SERIES CIRCUIT BREAKER. TRIP RATING
PLUG TO BE GE #GTP0225U0306.
2. PROVIDE NE3 100A CIRCUIT BREAKER IN AVAILABLE
BREAKER SPACE IN EXISTING GE SPECTRA SERIES
DISTRIBUTION PANELBOARD. CIRCUIT BREAKER TO BE GE
#SGHC3601L3XX.
50 KAIC 50 KAIC 50 KAIC
I LL IN O IS
S N
A H
A
TR
E B
O R
NTHONY
LICENSED
PROFESSIONAL
OF
ENGINEER
062.059710
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
100% RE-SUBMIT 2020/06/29
C U s e rs
\j h u s to n \D o c u m e n ts
\R
I V
C E
E
L E
C T
R
IC
A L jh u s to n c m ta e g rs
.c o m
.r v t
/2
/2
:4
:0
A
M
EJ200
POWER RISER DIAGRAM
GUIDON-CMTA SDVOSB JV, LLC
1221 N. PENNSYLVANIA ST. SUITE 200
INDIANAPOLIS, IN 46202
CMTA CONSULTING ENGINEERS
903 SPRING ST.
JEFFERSONVILLE, IN 47130
EMERGENCY DEPARTMENT
RENOVATION
820 S. DAMEN AVE.
537-15-160
5/30/2020 CMTA CMTA
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
NO SCALEEJ200
1 POWER RISER DIAGRAM
I LL IN O IS
N
A H
A
TR
E B
O R
NTHONY
LICENSED
PROFESSIONAL
OF
ENGINEER
062.059710
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
100% RE-SUBMIT 2020/06/29
C U s e rs
\j h u s to n \D o c u m e n ts
\R
I V
C E
E
L E
C T
R
IC
A L jh u s to n c m ta e g rs
.c o m
.r v t
/2
/2
:4
:0
A
M
EJ201
PANEL SCHEDULES
GUIDON-CMTA SDVOSB JV, LLC
1221 N. PENNSYLVANIA ST. SUITE 200
INDIANAPOLIS, IN 46202
CMTA CONSULTING ENGINEERS
903 SPRING ST.
JEFFERSONVILLE, IN 47130
EMERGENCY DEPARTMENT
RENOVATION
820 S. DAMEN AVE.
537-15-160
5/30/2020 CMTA CMTA
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
NOTES: WHERE NOT LISTED, WIRE AND CONDUIT SHALL BE BE MINIMUM PER SPECIFICATIONS. SPARE BREAKERS TO BE 20A/1P.
KITCH 800 VA 100.00% 800 VA TOTAL ESTIMATED DEMAND CURRENT: 61 A
REC 25280 VA 69.78% 17640 VA TOTAL CONNECTED CURRENT: 82 A
LTNG 2092 VA 100.00% 2092 VA TOTAL ESTIMATED DEMAND: 21819 VA
EQUIP 1300 VA 100.00% 1300 VA TOTAL CONNECTED LOAD: 29459 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL CURRENT (A): 99 A 83 A 68 A
TOTAL LOAD (kVA): 11.6 kVA 9.7 kVA 8.2 kVA
SPARE -- -- -- 20 1 53 0.0 0.0 54 1 20 -- -- -- SPARE
SPARE -- -- -- 20 1 51 0.0 0.0 52 1 20 -- -- -- SPARE
SPARE -- -- -- 20 1 49 0.0 0.0 50 1 20 -- -- -- SPARE
SPARE -- -- -- 20 1 47 0.0 0.0 48 1 20 -- -- -- SPARE
SPARE -- -- -- 20 1 45 0.0 0.0 46 1 20 -- -- -- SPARE
SPARE -- -- -- 20 1 43 0.0 0.0 44 1 20 -- -- -- SPARE
SPARE -- -- -- 20 1 41 0.0 0.0 42 1 20 -- -- -- SPARE
SPARE -- -- -- 20 1 39 0.0 0.0 40 1 20 -- -- -- SPARE
RM 1499C REC 12 12 3/4 20 1 37 0.2 0.2 38 1 20 3/4 12 12 RM 1499C REC
RMS 1453 & 1451 REC 10 10 3/4 20 1 35 0.7 0.2 36 1 20 3/4 12 12 LTNG
RM 1474C REC 12 12 3/4 20 1 33 1.1 0.7 34 1 20 3/4 10 10 RMS 1449 & 1450 REC
RM 1470 REC 12 12 3/4 20 1 31 0.9 0.9 32 1 20 3/4 12 12 RM 1470 REC
RM 1466 REC 12 12 3/4 20 1 29 0.7 0.5 30 1 20 3/4 12 12 RMS 1499B & 1499C REC
LTNG 12 12 3/4 20 1 27 0.7 0.9 28 1 20 3/4 12 12 RM 1454 REC
RM 1462 REC 12 12 3/4 20 1 25 0.4 1.2 26 1 20 3/4 12 12 LTNG
RM 1462 REC 12 12 3/4 20 1 23 0.2 1.3 24 1 20 3/4 10 10 RM 1474B REC
RM 1475 REC 10 10 3/4 20 1 21 0.7 0.7 22 1 20 3/4 10 10 RM 1475 REC
RM 1473 REC 12 12 3/4 20 1 19 0.6 0.8 20 1 20 3/4 12 12 RM 1462 REFRIGERATOR
RM 1470G REC 12 12 3/4 20 1 17 0.9 0.5 18 1 20 3/4 12 12 RM 1473 HEADWALL REC
RM 1470J HEADWALL REC 12 12 3/4 20 1 15 0.5 0.5 16 1 20 3/4 12 12 RM 1470G HEADWALL REC
RM 1470H REC 12 12 3/4 20 1 13 0.9 1.2 14 1 20 3/4 12 12 RM 1470J REC
RM 1470 REC 12 12 3/4 20 1 11 1.1 0.5 12 1 20 3/4 12 12 RM 1470H HEADWALL REC
RM 1470 REC 12 12 3/4 20 1 9 1.1 0.7 10 1 20 3/4 12 12 RM 1470 REC
RMS 1467, 1471 & 1404A REC 12 12 3/4 20 1 7 0.7 1.9 8 1 20 3/4 12 12 RM 1470 REC
RMS 1462 & 1462A REC 12 12 3/4 20 1 5 0.7 0.7 6 1 20 3/4 12 12 RM 1456 REC
RMS 1466B & 1466C REC 12 12 3/4 20 1 3 0.9 1.1 4 1 20 3/4 12 12 RM 1464 REC
RMS 1478 & 1474 REC 12 12 3/4 20 1 1 0.9 0.9 2 1 20 3/4 12 12 RM 1452 REC
CIRCUIT DESCRIPTION WIRE GND C OCP P CKT A B C CKT P OCP C GND WIRE CIRCUIT DESCRIPTION
AMPERES: 225 A MOUNTING: SURFACE SUPPLY FROM: LP-1-1
VOLTAGE: 208Y/120V,3P,4W SPD: Yes LOCATION: ELECTRICAL 14E6
PANEL: GP MAINS TYPE: MLO PANEL INTERRUPTING RATING: MIN 50KAIC
PANELBOARD AND WIRING SCHEDULE AVAILABLE FAULT CURRENT:
NOTES: WHERE NOT LISTED, WIRE AND CONDUIT SHALL BE BE MINIMUM PER SPECIFICATIONS. SPARE BREAKERS TO BE 20A/1P.
TOTAL ESTIMATED DEMAND CURRENT: 56 A
REC 16540 VA 80.23% 13270 VA TOTAL CONNECTED CURRENT: 66 A
LTNG 1787 VA 100.00% 1787 VA TOTAL ESTIMATED DEMAND: 20332 VA
EQUIP 5290 VA 100.00% 5290 VA TOTAL CONNECTED LOAD: 23602 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL CURRENT (A): 64 A 66 A 67 A
TOTAL LOAD (kVA): 7.7 kVA 7.8 kVA 8.0 kVA
SPARE -- -- -- 20 1 53 0.0 0.0 54 1 20 -- -- -- SPARE
SPARE -- -- -- 20 1 51 0.0 0.0 52 1 20 -- -- -- SPARE
SPARE -- -- -- 20 1 49 0.0 0.0 50 1 20 -- -- -- SPARE
SPARE -- -- -- 20 1 47 0.0 0.0 48 1 20 -- -- -- SPARE
SPARE -- -- -- 20 1 45 0.0 0.0 46 1 20 -- -- -- SPARE
RM 1456 REC 12 12 3/4 20 1 43 0.5 0.0 44 1 20 -- -- -- SPARE
RM 1454 REC 12 12 3/4 20 1 41 0.7 0.0 42 1 20 -- -- -- SPARE
EF-1 10 10 1 20 1 39 1.0 0.0 40 1 20 -- -- -- SPARE
RM 1449 OH DOOR 10 10 3/4 20 1 37 0.5 0.0 38 1 20 -- -- -- SPARE
RM 1450 OH DOOR 12 12 3/4 20 1 35 0.5 0.0 36 1 20 -- -- -- SPARE
RM 1451 OH DOOR 10 10 3/4 20 1 33 0.5 0.0 34 1 20 -- -- -- SPARE
RM 1453 OH DOOR 10 10 3/4 20 1 31 0.5 0.0 32 1 20 -- -- -- SPARE
RM 1478 OH DOOR 12 12 3/4 20 1 29 0.5 0.0 30 1 20 -- -- -- SPARE
RM 1470J PATIENT LIFT 12 12 3/4 20 1 27 0.2 0.0 28 1 20 -- -- -- SPARE
RM 1470H PATIENT LIFT 12 12 3/4 20 1 25 0.2 0.2 26 1 20 3/4 12 12 RM 1470G PATIENT LIFT
RM 1472 ICE MAKER 12 12 3/4 20 1 23 0.8 0.9 24 1 20 3/4 12 12 RM 1470 REC
RM 1472 UC REFRIGERATOR 12 12 3/4 20 1 21 0.8 1.0 22 1 20 3/4 12 12 RM 1470 COPIER
RM 1470 REC 12 12 3/4 20 1 19 1.3 0.5 20 1 20 3/4 12 12 RM1472 PYXIS REC
RM 1470 REC 12 12 3/4 20 1 17 1.3 0.2 18 1 20 3/4 12 12 LTNG
RM 1451 REC 10 10 3/4 20 1 15 0.7 0.7 16 1 20 3/4 10 10 RM 1453 REC
RM 1475 REC 10 10 3/4 20 1 13 0.7 0.7 14 1 20 3/4 10 10 RM 1450 REC
LTNG 12 12 3/4 20 1 11 0.8 0.5 12 1 20 3/4 12 12 RMS 1499B & 1499C REC
RM 1470 REC 12 12 3/4 20 1 9 0.5 0.8 10 1 20 3/4 12 12 LTNG
RM 1473 HEADWALL REC 12 12 3/4 20 1 7 0.9 0.7 8 1 20 3/4 10 10 RM 1449 REC
RM 1470J HEADWALL REC 12 12 3/4 20 1 5 0.9 0.9 6 1 20 3/4 12 12 RM 1470G HEADWALL REC
RMS 1474A & 1474C REC 12 12 3/4 20 1 3 0.7 0.9 4 1 20 3/4 12 12 RM 1470H HEADWALL REC
RM 1478 REC 12 12 3/4 20 1 1 0.7 0.3 2 1 20 3/4 12 12 ISO RM PRESSURE MONITORS
CIRCUIT DESCRIPTION WIRE GND C OCP P CKT A B C CKT P OCP C GND WIRE CIRCUIT DESCRIPTION
AMPERES: 225 A MOUNTING: SURFACE SUPPLY FROM: CLP-1-1
VOLTAGE: 208Y/120V,3P,4W SPD: Yes LOCATION: ELECTRICAL 14E6
PANEL: GECP MAINS TYPE: MLO PANEL INTERRUPTING RATING: MIN 50KAIC
PANELBOARD AND WIRING SCHEDULE AVAILABLE FAULT CURRENT:
NOTES: WHERE NOT LISTED, WIRE AND CONDUIT SHALL BE BE MINIMUM PER SPECIFICATIONS. SPARE BREAKERS TO BE 20A/1P.
TOTAL ESTIMATED DEMAND CURRENT: 2 A
TOTAL CONNECTED CURRENT: 2 A
TOTAL ESTIMATED DEMAND: 2000 VA
EQUIP 2000 VA 100.00% 2000 VA TOTAL CONNECTED LOAD: 2000 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL CURRENT (A): 2 A 2 A 2 A
TOTAL LOAD (kVA): 0.7 kVA 0.7 kVA 0.7 kVA
SPACE -- -- -- -- -- 41 0.0 0.0 42 -- -- -- -- -- SPACE
SPACE -- -- -- -- -- 39 0.0 0.0 40 -- -- -- -- -- SPACE
SPACE -- -- -- -- -- 37 0.0 0.0 38 -- -- -- -- -- SPACE
SPACE -- -- -- -- -- 35 0.0 0.0 36 -- -- -- -- -- SPACE
SPACE -- -- -- -- -- 33 0.0 0.0 34 -- -- -- -- -- SPACE
SPACE -- -- -- -- -- 31 0.0 0.0 32 -- -- -- -- -- SPACE
SPACE -- -- -- -- -- 29 0.0 0.0 30 -- -- -- -- -- SPACE
SPACE -- -- -- -- -- 27 0.0 0.0 28 -- -- -- -- -- SPACE
SPACE -- -- -- -- -- 25 0.0 0.0 26 -- -- -- -- -- SPACE
SPACE -- -- -- -- -- 23 0.0 0.0 24 -- -- -- -- -- SPACE
SPACE -- -- -- -- -- 21 0.0 0.0 22 -- -- -- -- -- SPACE
SPACE -- -- -- -- -- 19 0.0 0.0 20 -- -- -- -- -- SPACE
SPACE -- -- -- -- -- 17 0.0 0.0 18 -- -- -- -- -- SPACE
SPACE -- -- -- -- -- 15 0.0 0.0 16 -- -- -- -- -- SPACE
SPACE -- -- -- -- -- 13 0.0 0.0 14 -- -- -- -- -- SPACE
SPARE -- -- -- 20 1 11 0.0 0.0 12 1 20 -- -- -- SPARE
SPARE -- -- -- 20 1 9 0.0 0.0 10 1 20 -- -- -- SPARE
SPARE -- -- -- 20 1 7 0.0 0.0 8 1 20 -- -- -- SPARE
5 0.3 0.3 6
3 0.3 0.3 4AHU-1 6 10 1 45 3
1 0.3 0.3 2
3 20 3/4 12 12 RF-1
CIRCUIT DESCRIPTION WIRE GND C OCP P CKT A B C CKT P OCP C GND WIRE CIRCUIT DESCRIPTION
AMPERES: 100 A MOUNTING: SURFACE SUPPLY FROM: H-EDP-1-1
VOLTAGE: 480Y/277V,3P,4W SPD: Yes LOCATION: MECH ROOM 1499B
PANEL: GEQP MAINS…