About this file

This solicitation seeks a contractor to provide construction and renovation services for an Emergency Department Observation Unit project at the Jesse Brown VA Medical Center in Chicago, Illinois. Key details include renovating space to create a fully functional observation unit, providing all necessary labor, materials, tools and supervision. The solicitation is issued by the Department of Veterans Affairs Veterans Health Administration Great Lakes Acquisition Center. Responses are due by the date specified in the solicitation. The selected contractor will be responsible for all work outlined in the scope of work.

View the file

Other files

File Type Posted
AE Responses 537-15-160 Consolidated RFI Amendment 6.xlsx XLSX spreadsheet
36C25220B0023 0006.docx DOCX document
537-15-160 SOW - Mod2.docx DOCX document
IFB Bid opening invitation changed to 10SEP.pdf PDF
36C25220B0023 0005.docx DOCX document
AE Responses 537-15-160 Consolidated RFI Amendment 4.pdf PDF
085113 - Psychiatric windows.docx DOCX document
081710 - Integrated Door Assemblies.docx DOCX document
36C25220B0023 0004.docx DOCX document
087100 - Door Hardware.docx DOCX document
Basement sketch Question 64.png PNG image
024100 - Demolition.pdf PDF
SIGNED Brand Name J and A.pdf PDF
36C25220B0023 0003.docx DOCX document
262416 - Panels.pdf PDF
264313 - Surge Protective Devices.pdf PDF
537-15-160 Consolidated RFI-ADD1.pdf PDF
Bid opening change to 10 AUG Meeting Invitation.pdf PDF
260573 - OCP Device Coordination Study.pdf PDF
C03 36C25220B0023 0002.docx DOCX document
EJ200 - Addendum 1 Elec - 07.23.20.pdf PDF
RFI-001_Guidon Addendum 1.pdf PDF
000100 - Specification Table of Contents.pdf PDF
537-15-160 SOW - Mod1.pdf PDF
ED201 - Addendum 1 Elec - 07.23.20.pdf PDF
36C25220B0023 A0001.docx DOCX document
ATCH 2 537-15-160 sign in sheets 8-9 jul 2020.pdf PDF
ATCH 1 537-15-160 Construction Bid Opening Meeting.pdf PDF
537-15-160 Construction Drawings 1 of 4.pdf PDF
537-15-160 Construction Drawings 3 of 4.pdf PDF
537-15-160 Construction Drawings 2 of 4.pdf PDF
S02 36C25220B0023_2_7-1-2020.docx DOCX document
537-15-160 Project Manual Vol2.pdf PDF
537-15-160 Project Manual Vol1.pdf PDF
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ST

IS

CB

SS

DS

PB

PC

CDL

DL

MS

W

SC

C

SD

UON

E, EM

CFOI

OFOI

CFCI

OFCI

T

J

DESCRIPTION

DP

S

S

X

S LV3

S D

S K

PC

S

S LV4

S

U

N

OS

OS

GROUND FAULT PROTECTED DUPLEX WITH

WEATHER-PROOF "WHILE IN USE" TYPE DIE-CAST

METAL COVERPLATE WITH LOCKABLE ENCLOSURE AT

OUTLET - SEE SPECIFICATIONS

WP

ER

DUPLEX FOR ELECTRIC WATER COOLER: COORDINATE

EXACT LOCATION WITH PLUMBING CONTRACTOR TO

CONCEAL OUTLET BEHIND COOLER, PROVIDE READILY

ACCESSIBLE GFI DEVICE AT 18" ADJACENT TO WATER

COOLER

EWC

AUDIO/VIDEO INTERCOM STATION: MASTER WITH

SELECTIVE DOOR CONTROLS, POWER SUPPLIES & DOOR

RELAY CONTACTS AS REQUIRED FOR OPERATION OF ANY

DOOR IN THE SYSTEM AND VIEWING OF ANY AUDIO/VIDEO

INTERCOM REMOTE ON THE SYSTEM. AIPHONE#AX-MV

W/DESK STAND - COLOR BY ARCHITECT.

SAME AS ''IM'' EXCEPT WALL MOUNTED W

DOOR RELEASE PUSH-PLATE / INFRA-RED OPERATOR

STATION. PROVIDE ANY ADDITIONAL ROUGH-IN FOR

''EMERGENCY RELEASE'' OPERATOR STATIONS AS REQUIRED.

DOOR RELEASE CARD READER STATION. PROVIDE ANY

ADDITIONAL ROUGH-IN FOR ''EMERGENCY RELEASE''

OPERATOR STATIONS AS REQUIRED.

AUTOMATIC DOOR CONNECTION (MAY ALSO HAVE ELECTRIC

STRIKE/MAG-LOCK/ELECTRIFIED PANIC CONNECTION - SEE

ARCHITECTURAL HARDWARE SPECIFICATIONS)

FLOORBOX, COMBINATION POWER AND LOW

VOLTAGE, REFER TO FLOORBOX SCHEDULE

CLG

SS

POWER SUPPLY/CONTROL FOR AUDIO/VISUAL DEVICES

SAME AS ''CR'' EXCEPT MULLION MOUNT M

SLASH THROUGH ANY DEVICE INDICATES MOUNTING

ABOVE COUNTERTOP 4" ABOVE BACKSPLASH

CCTV CAMERA: CEILING MOUNT DOME

WP

''DOG-HOUSE'' TYPE TWIN DUPLEX RECEPTACLE WITH

ONE DUPLEX RECEPTACLE ON BOTH SIDES

AUDIO/VIDEO INTERCOM STATION: REMOTE WITH

FLUSH-MTD S.S. ENCLOSURE. AIPHONE #AX-DVF.

S VS

VS

EMERGENCY AUTOMATIC TRANSFER SWITCH FOR

LIGHTING CONTROLS (REFER TO DETAIL)

FILLED CENTER BAR INDICATES INTEGRAL GROUND FAULT

PROTECTION (GFCI)

NON-REVERSING MOTOR STARTER SNAP SWITCH

CONTRACTOR FURNISHED OWNER INSTALLED

CONTRACTOR FURNISHED CONTRACTOR INSTALLED

OWNER FURNISHED OWNER INSTALLED

OWNER FURNISHED CONTRACTOR INSTALLED

FLUSH MOUNTED REMOTE ALARM INDICATING

STATION/TEST SWITCH

PHOTO-ELECTRIC SMOKE DETECTOR

MAIN CONTROL PANEL CENTRAL PROCESSING UNIT (CPU)

DOOR ALARM/POSITION SWITCH

DOOR POWER SUPPLY

DOOR DELAYED EGRESS/ELECTRIFIED PANIC MECHANISM

TELEVISION SYSTEM OUTLET WITH DUPLEX RECEPTACLE,

COORDINATE LOCATION WITH WALL BRACKET WHERE

APPLICABLE

LIGHT SWITCH: LOW VOLTAGE

AS NOTED

AS NOTED

LIGHT SWITCH FOR UNDER-CABINET LIGHTS

6"ABV. DOOR

46"

6'-6'' TO

TOP

46" TO

LEVER

PULL STATION : DOUBLE ACTION

AUDIO-ONLY NOTIFICATION APPLIANCE

VISUAL-ONLY NOTIFICATION APPLIANCE

AUDIO/VISUAL NOTIFICATION APPLIANCE

NURSE CALL TERMINAL CABINET

INTERCOM CEILING SPEAKER

STAFF PRESENCE STATION

CODE BLUE STATION

STAFF STATION

BED INTERFACE

MASTER STATION ANNUNCIATOR

DOME LIGHT : WALL MOUNTED

DOME LIGHT : CEILING MOUNTED

EMERGENCY STATION : PULLCORD

EMERGENCY STATION : PUSHBUTTON

DUTY STATION

HEAT DETECTOR

CARBON MONOXIDE AUDIO/VISUAL NOTIFICATION

APPLIANCE

DOOR HOLDER : WALL TYPE

DOOR HOLDER : CLOSURE TYPE

DUCT SMOKE DETECTOR

REMOTE L.C.D. FIRE ALARM ANNUNCIATOR

ISOLATION MODULE

H.V.A.C. SMOKE DAMPER CONNECTION

UNLESS OTHERWISE NOTED

INDICATES EMERGENCY POWER

SPECIAL OUTLETS

HD

F

DH

ABV DOOR DH

ABV CLG DD

46"

I

SM

ABBREVIATIONS

NURSE CALL

DESCRIPTION

XLSL

STRIP FIXTURE

CROSS-HATCHING INDICATES LIGHT IS POWERED

FROM THE EMERGENCY-CRITICAL BRANCH

PARALLEL-HATCHING INDICATES LIGHT IS POWERED

FROM THE EMERGENCY-LIFE SAFETY BRANCH

POWER OUTLETS

SIMPLEX RECEPTACLE

DUPLEX RECEPTACLE-SAFETY TYPE, TAMPER-RESISTANT

DUPLEX RECEPTACLE

QUADRUPLEX RECEPTACLE

JUNCTION BOX, CEILING OR WALL

VOLTAGE/1PH RECEPTACLE, AS NOTED

VOLTAGE/3PH RECEPTACLE, AS NOTED

SS INDICATES SURGE SUPPRESION TYPE OUTLET(S)

EXAM LIGHT SWITCH

NIGHT LIGHT SWITCH WITH CONSTANTLY ILLUMINATED

HANDLE

LOW VOLTAGE DIMMER SWITCH

LINE VOLTAGE THREE-WAY SWITCH

LINE VOLTAGE FOUR-WAY SWITCH

KEYED SWITCH

OCCUPANCY OR VACANCY SENSOR SWITCH

OCCUPANCY OR VACANCY SENSOR, CEILING MOUNT

PHOTO-CELL AS NOTED

SURGICAL/EXAM LIGHT

EXIT LIGHT (CEILING, END, WALL MOUNT)

LIGHTING

REFER TO LUMINAIRE SCHEDULE FOR EXACT FIXTURE

SPECIFICATIONS, MOUNTING HEIGHTS, ETC.

SECURITY INTERCOM

SECURITY ACCESS CONTROL

SECURITY CCTV VIDEO SURVEILLANCE

DOOR RELEASE KEYSWITCH STATION

DOOR RELEASE KEYPAD STATION

MOTION SENSOR DOOR CONTROL

REMOTE DOOR RELEASE PUSH-BUTTON

CCTV CAMERA: WALL MOUNT DOME

CCTV POWER SUPPLIES/CONTROL PANEL 46"

DOOR

FRAME

ABV DOOR

8" ACT

DESCRIPTION

CLG

1'-6''

1'-6''

46"

46"

46"

46"

46"

46"

WALL, CLG

CLG

CLG

WALL

54"

46"

46"

46"

46"

46"

46"

46"

46"

46"

1'-6"

1'-6"

1'-6"

1'-6"

1'-6"

1'-6"

ON CNTR.

2'-2"

CLG

AS NOTED

18''

46"

46"

CLG

46"

6'-0''

46"

46"

CEIL.

CLG

7'-0"

S

S

FLOOR

S M TELEVISION SPLITTERS/AMPLIFIERS/DISTRIBUTION

TELEVISION

46" TV-HE

D R

A W

I N

G

S Y

M B

O L

SURFACE OR SUSPENDED CEILING FIXTURE (SLASH

INDICATES RECESSED)

POLE MOUNTED AREA LIGHT

EMERGENCY BATTERY WALL-PACK

WALL MOUNT FIXTURE ,

FLOODLIGHT

V

A

F

F

RI

INDICATES VANDAL-PROOF POLYCARBONATE COVER,

VANDAL PROOF COVERS SHALL BE UL LISTED FOR USE

WITH THE SPECIFIC DEVICE THEY ARE PROTECTING

PC

WALL

WALL

7'-6''

ADDRESSABLE RELAY MODULE R

WALL

ACCESS CONTROL POWER SUPPLIES/CONTROL PANEL 46"

46"

ABV CLG

ELECTRIC STRIKE AT LATCH

MAGNETIC LOCK(S) ABV DOOR

INDICATES EXTERIOR CAMERA RATED FOR

CONDITIONS, WET LOCATION LISTED, WITH

AUXILLARY HEATER

FLOORBOX, POWER ONLY, AS SCHEDULED FLOOR

DESCRIPTION

WP

BOX ON ANY DEVICE INDICATES SURFACE MOUNTED

BACKBOX/WIREMOLD

CONDUIT CONCEALED IN WALLS OR IN CEILING

SPACE: ARROW(S) INDICATE(S) HOME RUN & # OF

CIRCUITS: HASHMARKS INDICATE # OF

CONDUCTORS. DASHED LINE INDICATES CONDUIT

BELOW FLOOR.

PANELBOARD, SURFACE OR FLUSH MOUNTED

EQUIPMENT TAG, REFER TO EQUIPMENT SCHEDULE

MECHANICAL EQUIPMENT DESIGNATOR (SEE

MECH. SCHEDULES)

EQUIPMENT HARDWIRE CONNECTION (SEE DETAIL)

AS NOTED

AS SHOWN

MISCELLANEOUS

DISCONNECT SWITCH

MAGNETIC STARTER

MAGNETIC COMBINATION STARTER

ENCLOSED FLUSH MTD. CIRCUIT BREAKER

WEATHERPROOF - NEMA-3R, WET LOCATION LISTED.

PROVIDE COVERS, RATINGS, ETC, AS SUITABLE FOR

OUTDOORS.

PUSHBUTTON STATION

FLEXIBLE CONDUIT

TRANSFORMER

TAGGED NOTE

REVISION TAG

WIRE BASKET CABLE TRAY, SIZE AS NOTED

LOW VOLTAGE CABLE PATH

5'-0"

5'-0"

5'-0"

5'-0"

46"

6'-6'' TO TOP

SURGE PROTECTION DEVICE

THERMOSTAT PROVIDED BY MECHANICAL CONTRACTOR,

ELECTRICAL CONTRACTOR SHALL PROVIDE BACK-BOX

CONDUIT STUB-UP, REFER TO MECHANICAL DRAWINGS FOR

LOCATIONS

MED GAS ALARMS

MSA

LPA

MEDICAL GAS LINE PRESSURE ALARM (REFER TO DETAIL)

MEDICAL GAS MULTI-SIGNAL ALARM (REFER TO DETAIL)

DESCRIPTION

C A B L

IN

G /C

O N

D U

C T O

R S

O F

O I

C A B L

IN

G /C

O N

D U

C T O

R S

O F

C I

C A B L

IN

G /C

O N

D U

C T O

R S

C F

C I

IT

E M

U S E D

O N

P R O

JE

C T

D E V

IC

E S

O F

C I

D E V

IC

E S

C F

C I

SYSTEM D

E V

IC

E S

O F

O I

SECURITY: ACCESS CONTROL

SECURITY: INTERCOM

SECURITY: CCTV

SYSTEM

RESPONSIBILITY

MATRIX

OVERHEAD PAGING

FIRE ALARM

TELEVISION

DATA PROCESSING

TELEPHONE

NURSE CALL

SYSTEM RESPONSIBILITY GENERAL NOTES:

A. AT ALL SYSTEMS EQUIPMENT CABINET/TERMINAL BOARD LOCATIONS,

CONTRACTOR SHALL PROVIDE MINIMUM 1" CONDUIT STUB-OUT TO CABLE PATHS

AS REQUIRED BY SYSTEM VENDORS, TERMINATE CONDUIT AT CABINETS/ON

BACKBOARDS AS REQUIRED. COORDINATE EXACT REQUIREMENTS WITH

APPROPRIATE VENDORS PRIOR TO CONSTRUCTION.

B. REFER TO SPECIFICATIONS FOR REQUIREMENTS APPLICABLE TO ALL SYSTEMS

INCLUDING CABLING, CABLE MANAGEMENT, INSTALLATION, GROUNDING,

TESTING, LABELING, ETC.

C. WHERE INDICATED AS CFCI, THE CONTRACTOR SHALL PROVIDE THE SYSTEM

COMPLETE, INCLUDING ALL ROUGH-INS, CABLING, DEVICES, POWER, ETC. THE

CONTRACTOR SHALL CONTACT THE LISTED VENDOR FOR PRICING PRIOR TO BID.

ALL SYSTEMS SHALL MATCH EXISTING FACILITY STANDARDS AND BE FULLY

COMPATIBLE WITH ANY EXISTING SYSTEMS. ALL SYSTEM VENDORS SHALL

COORDINATE EXACT SYSTEM REQUIREMENTS WITH OWNER PRIOR TO BID. NEW

COMPONENTS SHALL BE INTERCONNECTED WITH EXISTING SYSTEMS WHERE

POSSIBLE. ALL NEW SYSTEM DESIGNS AND PROGRAMMING SHALL BE

COORDINATED WITH THE OWNER PRIOR TO ORDERING. ALL PROGRAMMING

SHALL BE INCLUDED AS REQUIRED BY THE COR. PROVIDE 4 HOURS OF TRAINING

FOR EACH SYSTEM.

PPPOWER POLE AS NOTED

SINGLE PATIENT STATION: WITH CALL CORD

AND (4) AUXILLIARY JACK INPUTS

SINGLE PATIENT STATION: WITH PILLOW SPEAKER

AND (4) AUXILLIARY JACK INPUTS

SINGLE PATIENT STATION: WITH SIDECOM AND (4)

AUXILLIARY JACK INPUTS

5'-0''

5'-0''

5'-0''

SPP

SPC

SPS

LIGHTING CONTROL SWITCHES

SV

S

S

VWALL VOLUME CONTROL

PAGING SPEAKER: WALL

PAGING SPEAKER W/ VOLUME CONTROL

PAGING SPEAKER: CEILING CLG

CLG

8'-0"

46"

OVERHEAD PAGING

CALL INITIATION STATION 46" C

FIRE ALARM

SYSTEM

SYMBOL

PUSH-TO-EXIT BUTTON 46" PE

SPD

J

ML

ES

SEC-A

NAC

CC

CC

CR

RR

DP

DA

IM

KP

IR

KS

MS

PP

CR

DS

AD

IM

FAA

FACP

NC-A

SEC-C

T

D R

A W

I

M B

O L

D R

A W

I

M B

O L

M O

U N

T I

H E

I G

H T

T

O

C

N T

E R

F

B

X

D R

A W

I

M B

O L

AS SHOWNLADDER CABLE TRAY, SIZE AS NOTED

AS SHOWNSOLID BOTTOM CABLE TRAY, SIZE AS NOTED

EQUIP-1

GROUND

NEUTRAL

PHASE

WALL, CLG

WALL, CLG V

A

F

CM

DEAD FRONT GFCI DEVICE, LABEL AND INSTALL IN READILY

ACCESSIBLE LOCATION

FILLED OUTER BARS INDICATES INTEGRAL INTEGRAL USB

OUTLETS IN ADDITION TO POWER RECEPTACLES

1'-6"

, J

VARIABLE FREQUENCY DRIVE 5'-0"

MOTOR CONNECTION, REFER TO EQUIPMENT

CONNECTION SCHEDULE

DUPLEX RECEPTACLE, CEILING MOUNTED CLG

CONDUIT UP

CONDUIT DOWN

WIREGUARD - PROVIDE MANUFACTURER'S SPECIFIC

GUARD FOR DEVICE NOTED

WIRELESS ACCESS POINT OUTLET WITH PROVISIONS FOR

(1 DATA OUTLET FOR ANTENNA. PROVIDE A COMPLETE

DATA OUTLET WITH FACEPLATE ABOVE CEILING, MOUNTED

AT AN ACCESSIBLE HEIGHT NO MORE THAN 24" ABOVE

CEILING. AT EACH OUTLET, PROVIDE A 20' COIL OF CABLE

AHEAD OF THE OUTLET FOR ADJUSTMENT OF FINAL OUTLET

LOCATION. THE CONTRACTOR SHALL COORDINATE EXACT

LOCATIONS WITH THE OWNER AND ADJUST OUTLET

LOCATIONS AT SUBSTANTIAL COMPLETION TO

ACCOMMODATE OWNER'S WAP LOCATIONS.

WAP

DATA OUTLET : PROVIDE A COMPLETE 6-PORT DATA

OUTLET WALLPLATE. AT EACH OUTLET, PROVIDE

PROVIDE (4)-RJ45 JACKS. REFER TO DETAIL FOR

CONFIGURATION. PROVIDE CAT6E CABLING FROM ALL

JACKS AND ROUTE TO NEW PATCH PANEL IN TELECOM

ROOM 14T3.

DATA / VOICE

1'-6"

SLINE VOLTAGE SWITCH 46"

CLG

M O

U N

T I

I G

H T

N T

E R

X

M O

U N

T I

I G

H T

N T

E R

X

M O

U N

T I

I G

H T

N T

E R

X

LV

CLG

CMCCTV MONITOR

I LL IN O IS

S N

A H

A

TR

E B

O R

NTHONY

LICENSED

PROFESSIONAL

OF

ENGINEER

062.059710

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

100% RE-SUBMIT 2020/06/29

C U s e rs

\j h u s to n \D o c u m e n ts

\R

I V

C E

E

L E

C T

R

IC

A L jh u s to n c m ta e g rs

.c o m

.r v t

/2

/2

:4

:5

A

M

EJ001

ELECTRICAL LEGEND

GUIDON-CMTA SDVOSB JV, LLC

1221 N. PENNSYLVANIA ST. SUITE 200

INDIANAPOLIS, IN 46202

CMTA CONSULTING ENGINEERS

903 SPRING ST.

JEFFERSONVILLE, IN 47130

EMERGENCY DEPARTMENT

RENOVATION

820 S. DAMEN AVE.

537-15-160

5/30/2020 CMTA CMTA

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Revisions: Date:

J

J

FUTURE ALARM "MULTI-PLEX' CONNECTIONS.

INTEGRATED "LINE PRESSURE ALARM"

PANEL (CFCI). REFER TO POWER

LOCATION(S).

FLOOR PLANS FOR NUMBER AND

WALL

MEDICAL GAS LINES (EXACT NO./LOCATION AS

TO EACH MEDICAL GAS LINE PER MANUFACTURER's

PULSE PRESSURE SENSORS (CFCI) CONNECTED

SUSPENDED CEILING

INDICATED ON MEDICAL GAS FLOOR PLANS.)

RECOMMENDATIONS.

LPA

TO EMERGENCY "LIFE SAFTY BRANCH"

120 VAC POWER SOURCE (SEE POWER

FLOOR PLANS FOR CIRCUIT).

3/4" CONDUIT UP IN WALL FROM THE

"LPA" TO 6" ABOVE CEILING FOR

BY MEDICAL GAS MANUFACTURER IN 1/2" CONDUIT

FROM EACH PULSE PRESSURE SENSOR TO THE "LPA".

PROVIDE ''BELDEN'' SHIELDED CABLE AS REQUIRED

E

4" x 4" J-BOX

AT STRUCTURE

120/277V

LIGHTING

BRANCH CIRCUIT

120/277V LIGHTING BRANCH

CIRCUIT TO LIGHT FIXTURES

PROVIDE 0-10V

LOW-VOLTAGE DIMMING

CONTROL WIRING TO

LIGHT FIXTURES

TO ADDITIONAL SENSORS IN

ROOM/AREA, WHERE SHOWN OR

REQUIRED, FOR 100% COVERAGE.

PROVIDE PLENUM RATED CAT6

CABLING BETWEEN ALL LIGHTING

CONTROL DEVICES.

SINGLE-ZONE CEILING MOUNTED VACANCY SENSOR(S) WITH DIMMING DIAGRAM

S D1

120/277V

LIGHTING

BRANCH CIRCUIT

120/277V LIGHTING BRANCH

CIRCUIT TO LIGHT FIXTURES

TO ADDITIONAL SENSORS IN

ROOM/AREA, WHERE SHOWN OR

REQUIRED, FOR 100% COVERAGE.

PROVIDE PLENUM RATED CAT6

CABLING BETWEEN ALL LIGHTING

CONTROL DEVICES.

DUAL-ZONE CEILING MOUNTED VACANCY SENSOR(S) WITH DIMMING DIAGRAM

S D2

PROVIDE 0-10V

LOW-VOLTAGE DIMMING

CONTROL WIRING TO

LIGHT FIXTURES

120/277V LIGHTING BRANCH

CIRCUIT TO LIGHT FIXTURES

120/277V

LIGHTING

BRANCH CIRCUIT

120/277V LIGHTING BRANCH

CIRCUIT TO LIGHT FIXTURES

LINE-VOLTAGE CONTROL

DEVICE, IF INDICATED

ON FLOOR PLANS.

TO ADDITIONAL SENSORS IN

ROOM/AREA, WHERE SHOWN OR

REQUIRED, FOR 100% COVERAGE.

PROVIDE PLENUM RATED CAT6

CABLING BETWEEN ALL LIGHTING

CONTROL DEVICES.

S

SINGLE-ZONE CEILING MOUNTED OCCUPANCY SENSOR(S) DIAGRAM

PROVIDE 0-10V

LOW-VOLTAGE DIMMING

CONTROL WIRING TO

LIGHT FIXTURES

CONNECTION TO AUXILIARY CONTACT BY

TCC. PROVIDE ADDITIONAL POWER PACK,

AS REQUIRED.

S, CONNECTION TO AUXILIARY CONTACT

BY TCC. PROVIDE ADDITIONAL POWER

PACK, AS REQUIRED.

CONNECTION TO AUXILIARY CONTACT

BY TCC. PROVIDE ADDITIONAL POWER

PACK, AS REQUIRED.

LIGHTING CONTROLS SEQUENCE OF OPERATIONS:

A. DAYLIGHT PHOTOCELL OPERATION: DEVICE SHALL BE SET TO MAINTAIN DESIGNED ARTIFICIAL

ILLUMINATION LEVEL IN EACH ZONE/AREA.

B. ALL LUMINAIRES WITHIN A DAYLIGHT ZONE SHALL BE SEPARATELY CONTROLLED FROM THE REST OF

THE GENERAL LIGHTING IN THE SPACE. THESE LUMINAIRES SHALL BE CONTROLLED USING AUTOMATIC

DAYLIGHT HARVESTING CONTROLS. THE DAYLIGHT HARVESTING CONTROLS SHALL PROVIDE SMOOTH

AND CONTINUOUS DIMMING. DIMMING SHALL BE INITIATED WHEN TOTAL ILLUMINATION (COMBINED

DAYLIGHT AND ELECTRIC LIGHTING) REACHES 150% OF THE MAINTAINED DESIGN ILLUMINANCE

PROVIDED BY THE ELECTRIC LIGHTING ONLY.

C. VACANCY SENSOR OPERATION: DEVICE SHALL BE MANUAL ON AND AUTOMATIC OFF. LIGHTING TO

TURN OFF AFTER 20 MINUTES OF NO OCCUPANCY.

D. OCCUPANCY SENSOR OPERATION: DEVICE SHALL BE AUTOMATIC ON AND AUTOMATIC OFF. LIGHTING

TO TURN OFF AFTER 15 MINUTES OF NO OCCUPANCY.

E. VACANCY SENSOR WITH DIMMING CONTROLS: PROVIDE 70% OF LIGHT IN ZONE WHEN WALL SWITCH IS

ACTIVATED. OCCUPANT SHALL BE ABLE TO ADJUST FROM 0% TO 100% 'ON' WITH RAISE/LOWER

BUTTONS.

F. OCCUPANCY SENSOR WITH DIMMING CONTROLS: PROVIDE 70% OF LIGHT IN ZONE WHEN OCCUPANCY

SENSOR IS ACTIVATED. OCCUPANT SHALL BE ABLE TO ADJUST FROM 0% TO 100% 'ON' WITH

RAISE/LOWER BUTTONS.

G. OCCUPANCY SENSOR CONTROL ZONES WITHOUT MANUAL OR DIGITAL SWITCHING SHALL BE

CONTROLLED BY OCCUPANCY SENSORS ONLY.

PD

VS VS

PD

VS VS

PD

PR

OS OS

D

TYPICAL SCHEMATIC INTEGRATING UL 924 POWER PACK

120/277V NORMAL

LIGHTING BRANCH

CIRCUIT

120/277V LIGHTING BRANCH

CIRCUIT TO LIGHT FIXTURES

PROVIDE PLENUM RATED CAT6

CABLING BETWEEN ALL LIGHTING

CONTROL DEVICES.

S D1/L1

PROVIDE 0-10V

LOW-VOLTAGE DIMMING

CONTROL WIRING TO

EMERGENCY LIGHT FIXTURES

120/277V LIGHTING BRANCH

CIRCUIT TO LIGHT FIXTURES

PROVIDE 0-10V

LOW-VOLTAGE DIMMING

CONTROL WIRING TO

LIGHT FIXTURES

CONNECTION TO AUXILIARY

CONTACT BY TCC. PROVIDE

ADDITIONAL POWER PACK,

AS REQUIRED.

VS VS

PD/PR

PD/PR

E

120/277V EMERGENCY

LIGHTING BRANCH

CIRCUIT

PROVIDE WHERE EMERGENCY AND

NORMAL POWER LIGHTING IS

CONTROLLED BY THE SAME LOW

VOLTAGE SWITCH.

A. PROVIDE AND FOR NON-DIMMING ZONES. NON-DIMMING ZONES DO NOT REQUIRE 0-10V WIRING.

B. PROVIDE AND WHEN CONTROLLING EMERGENCY LIGHTING BRANCH CIRCUIT.

C. VERIFY ALL WIRING REQUIREMENTS WITH MANUFACTURER OF LIGHTING CONTROL DEVICES

PRIOR TO ROUGH-IN. THIS SCHEMATIC DIAGRAM IS MEANT TO BE ILLUSTRATIVE ONLY.

D. LIGHTING CONTROL SYSTEM SHALL COMPLY WITH ENERGY CODE.

E. LIGHTING CONTROL DEVICES SHALL BE SENSOR SWITCH (nLIGHT), WATTSTOPPER (DLM) OR

COOPER CONTROLS. ALL DEVICES SHALL BE FURNISHED BY ONE MANUFACTURER.

S

LX

GENERAL LIGHTING CONTROL NOTES:

PR

PD

E

PR

E

TO ADDITIONAL SENSORS IN

ROOM/AREA, WHERE SHOWN

OR REQUIRED, FOR 100%

COVERAGE.

NOTES:

1. OS - OCCUPANCY SENSORS TO BE PROGRAMMED AS AUTOMATIC ON, AUTOMATIC OFF.

2. VS - VACANCY SENSORS TO BE PROGRAMMED AS MANUAL ON, AUTOMATIC OFF.

3. OR EQUAL BY SENSOR SWITCH.

4. SENSOR AUTOMATIC OFF TIME INTERVAL TO BE SET AT 20 MIN.

5. ADJUST SENSOR LOCATION AND SENSITIVITY LEVELS TO MINIMIZE NUISANCE TRIPPING

AND FALSE OFFS.

6. ALL DEVICES TO BE LOCATED IN ACCESSIBLE LOCATIONS APPROVED BY COR.

7. REFER TO SPECIFICATIONS FOR DEVICE FINISHES.

LIGHT SWITCH, 4-WAY

LIGHT SWITCH, SPST, GENERAL PURPOSE

LIGHT SWITCH, 3-WAY

LIGHT SWITCH, KEYED

FULL RANGE SLIDE DIMMER WITH ON/OFF BUTTON, 277VAC RATED

LIGHTING CONTROL LEGEND

DIGITAL WALL SWITCH, ON/OFF, SINGLE ZONE

SENSOR SWITCH

nPODM

DIGITAL WALL SWITCH, ON/OFF, TWO ZONE

SENSOR SWITCH

nPODM 2P

DIGITAL WALL SWITCH, ON/OFF, FOUR ZONE

SENSOR SWITCH

nPODM 4P

DIGITAL ON/OFF WALL SWITCH WITH DIMMING, SINGLE ZONE

SENSOR SWITCH

nPODM DX

DIGITAL ON/OFF WALL SWITCH WITH DIMMING, TWO ZONE

SENSOR SWITCH

nPODM 2P DX

OCCUPANCY SENSOR WALL SWITCH, DUAL TECHNOLOGY, SINGLE POLE,

(800W AT 120VAC, 1200W AT 277VAC)

SENSOR SWITCH

WSX PDT

VACANCY SENSOR WALL SWITCH, DUAL TECHNOLOGY, SINGLE POLE,

(800W AT 120VAC, 1200W AT 277VAC)

SENSOR SWITCH

WSX PDT VA

OCCUPANCY SENSOR WALL SWITCH WITH 0-10V DIMMING, DUAL

TECHNOLOGY, SINGLE POLE

SENSOR SWITCH

WSX PDT D

VACANCY SENSOR WALL SWITCH WITH 0-10V DIMMING, DUAL TECHNOLOGY,

SINGLE POLE

SENSOR SWITCH

WSX PDT D VA

POWER PACK RELAY, ON/OFF, SINGLE ZONE, 16A MP RATED

SENSOR SWITCH

nPP16

POWER PACK RELAY, ON/OFF, SINGLE ZONE, 16A MP RATED WITH 0-10V

DIMMING

SENSOR SWITCH

nPP16 D

CEILING MOUNTED EXTENDED RANGE DUAL-TECHNOLOGY OCCUPANCY

SENSOR, WITH AUXILIARY RELAY FOR CONNECTION TO BAS BY TCC.

SENSOR SWITCH

nCM PDT 9 RJB AR

CEILING MOUNTED EXTENDED RANGE DUAL-TECHNOLOGY VACANCY

SENSOR, WITH AUXILIARY RELAY FOR CONNECTION TO BAS BY TCC.

SENSOR SWITCH

nCM PDT 9 RJB AR

K

D

L1

L2

L4

D1

D2

OS

VS

OSD

VSD

PR

PD

OS

VS

LEVITON

SEE SPECS.

SEE SPECS.

SEE SPECS.

SEE SPECS.

WATTSTOPPER

LMRC-211

WATTSTOPPER

LMDM-101

WATTSTOPPER

LMSW-101

WATTSTOPPER

LMSW-102

WATTSTOPPER

LMSW-104

WATTSTOPPER

LMDM-104

WATTSTOPPER

DSW-301

WATTSTOPPER

DSW-301

WATTSTOPPER

DSW-311

WATTSTOPPER

DSW-311

WATTSTOPPER

LMDC-100

WATTSTOPPER

LMDC-100

WATTSTOPPER

LMRC-101

WATTSTOPPER

S

S

S

S

S

S

S

S

S

S

S

S

S

S

POWER PACK RELAY, ON/OFF, SINGLE ZONE, 16A MP RATED WITH UL924

EMERGENCY FUNCTION

SENSOR SWITCH

nPP16 ER

POWER PACK RELAY, ON/OFF, SINGLE ZONE, 16A MP RATED WITH 0-10V

DIMMING AND UL924 EMERGENCY FUNCTION

SENSOR SWITCH

nPP16 D ER

PR E

PD EWATTSTOPPER

WATTSTOPPER

T

(2) TWO GANGE 4X4 SQUARE,

2-1/8" DEEP, WITH SINGLE

GANG 1/2" EXTENSION RING

ROUTE 1" CONDUIT TO CABLING PATH.

PROVIDE GROUNDING JUMPER TO CABLE

TRAY AT EACH LOCATION.

MOUNT BOTH BESIDE TV

BRACKET, BOXES NO MORE

THAN 2" APART

120 VAC NORMAL POWER

CIRCUIT-SEE POWER

PLANS

DUPLEX

RECEPTACLE

TYPICAL KEYSTONE CAT 6E JACK AND

DATA CABLE TO PATCH PANEL LOCATION.

SEE DIV 27 SPECIFICATIONS.

BL

BLBL

ENGRAVE OUTLET PLATE TO IDENTIFY

SERVICES. REFER TO SPECIFICATIONS

FOR LABELLING REQUIREMENTS.

ROUTE 1" CONDUIT TO NURSE CALL

CONTROL IN HEADWALL

GENERAL NOTES:

1. MAINTAIN A MINIMUM CLEARANCE OF 305mm (12") ON ALL SIDES OF ROOF

PENETRATION FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE

PROPER FLASHING.

2. FLANGES OF ADJACENT FLASHINGS SHALL NOT BE CUT OR

OVERLAPPED.

3. VERIFY ROOF & STRUCTURAL SYSTEM WITH ARCHITECT.

4. COORDINATE FLASHING INSTALLATION WITH ROOFING CONTRACTOR TO

ENSURE PROPER METHODS & MATERIALS ARE USED TO MAINTAIN ROOF

WARRANTY.

PREFABRICATED RUBBER

BOOT CAP WITH GRADUATED

STEPS & WEATHER-PROOF

PRESSURE SEAL TO COLLAR

SEALANT AT PENETRATION

TO MEMBRANE JUNCTURE

BY ROOFING CONTRACTOR

MULTIPLE MEMBRANE STRIPPING

PLIES FEATHERED AT FIELD OF

ROOF BY ROOFING CONTRACTOR.

PRIME FLANGE BEFORE STRIPPING.

PREFABRICATED FORMED 1.52mm (0.06")

THICK ALUMINUM FLASHING ROUND

COLLAR WITH MIN. 76mm (3") WIDE

FLANGE. ATTACH TO ROOF PER

MANUFACTURER'S INSTRUCTIONS

CONDUIT CLAMP. SIZE AS

REQUIRED

BATT INSULATION

ROOF MEMBRANE

WATER CUT-OFF

MASTIC COMPATIBLE

WITH ROOF MEMBRANE

STAINLESS CLAMP, TYP.

9.52mm (3/8") MIN

GALVANIZED

THREADED ROD, TYP.

SEAL-OFF

FITTING,

TYP.

ROOF

STEEL

EXPANSION

ANCHOR

INTEGRAL GALVANIZED LIPPED

STEEL MOUNTING CHANNEL

CONDUIT,

TYP.

CONDUIT

CLAMP. SIZE

AS REQUIRED

LOCKING

SQUARE

WASHER &

LOCKNUT

(3'-0")

MAX

SEISMIC OR EXPANSION

JOINT. FIELD VERIFY

ACTUAL CONDITIONS &

LOCATIONS.

FLOOR OR ROOF STRUCTURE. FIELD

VERIFY ACTUAL CONDITIONS, TYP.

STRUCTURAL MEMBER

(BEAM, JOIST, ETC.), TYP.

JUNCTION BOX, TYP

(SIZE AS REQUIRED)

CONDUIT

TRAPEZE PER

SD260533-03,

TYP.

914mm

BEAM

CLAMP,

TYP.

CONDUIT,

TYP.

PROVIDE 127mm (5") OF SLACK AT

MIDPOINT BETWEEN TWO END OF

FLEXIBLE GALVANIZED STEEL CONDUIT.

PROVIDE GREEN INSULATED COPPER

EQUIPMENT GROUNDING CONDUCTOR

WITH FLEXIBLE CONDUIT.

INTEGRAL GALVANIZED

LIPPED STEEL

MOUNTING CHANNEL

STEEL

EXPANSION

ANCHOR

JUNCTION BOX

(SIZE AS REQUIRED)

CONDUIT FITTING

SPRING

NUT

PROVIDE EXTRA CABLE

TO MAKE COMPLETE LOOP

AROUND BOX PERIMETER

GENERAL NOTE:

1. DETAIL IS APPLICABLE ONLY FOR CONDUIT SMALLER THAN 76mm (3").

I LL IN O IS

S N

A H

A

TR

E B

O R

NTHONY

LICENSED

PROFESSIONAL

OF

ENGINEER

062.059710

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

100% RE-SUBMIT 2020/06/29

C U s e rs

\j h u s to n \D o c u m e n ts

\R

I V

C E

E

L E

C T

R

IC

A L jh u s to n c m ta e g rs

.c o m

.r v t

/2

/2

:4

:5

A

M

EJ100

LIGHT FIXTURE SCHEDULE AND

DETAILSGUIDON-CMTA SDVOSB JV, LLC

1221 N. PENNSYLVANIA ST. SUITE 200

INDIANAPOLIS, IN 46202

CMTA CONSULTING ENGINEERS

903 SPRING ST.

JEFFERSONVILLE, IN 47130

EMERGENCY DEPARTMENT

RENOVATION

820 S. DAMEN AVE.

537-15-160

5/30/2020 CMTA CMTA

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

ELEC - LUMINAIRE SCHEDULE

TYPE DESCRIPTION ACUITY FIXTURE COOPER FIXTURE PHILIPS FIXTURE MOUNTING LAMPS / CCT LUMENS WATTAGE VOLTAGE REMARKS

A1 2X2 LED LAY-IN FLAT PANEL WITH 0-10V DIMMING

AND POINT TO SUPPORT FROM STRUCTURE AT

EACH CORNER

LITHONIA

#EPANL-2X2-3400LM-80CRI-35K-MIN10-Z

T-MVOLT-E10WCP

METALUX 22FP3235C DAY-BRITE #2FXP38L835-2-DS-UNV-DIM RECESSED LED/3500K 3400 32 120/208V

A1E SAME AS 'A1' WITH INTEGRAL EMERGENCY BATTERY

PACK, TEST SWITCH AND SELF DIAGNOSTIC.

LITHONIA

#EPANL-2X2-3400LM-80CRI-35K-MIN10-Z

T-MVOLT-E10WCP

METALUX #22FP3235C-EL14W DAY-BRITE

#2FXP38L835-2-DS-UNV-DIM-EMLED

RECESSED LED/3500K 3400 32 120/208V

A2 2X2 LED LAY-IN FLAT PANEL WITH 0-10V DIMMING

AND POINT TO SUPPORT FROM STRUCTURE AT

EACH CORNER

LITHONIA

#EPANL-2X2-4800LM-80CRI-35K-MIN10-Z

T-MVOLT-E10WCP

METALUX 22FP4235C DAY-BRITE #2FXP45L835-2-DS-UNV-DIM RECESSED LED/3500K 4800 46 120/208V

A2E SAME AS 'A2' WITH INTEGRAL EMERGENCY BATTERY

PACK, TEST SWITCH AND SELF DIAGNOSTIC.

LITHONIA

#EPANL-2X2-4800LM-80CRI-35K-MIN10-Z

T-MVOLT-E10WCP

METALUX #22FP4235C-EL14W DAY-BRITE

#2FXP45L835-2-DS-UNV-DIM-EMLED

RECESSED LED/3500K 4800 46 120/208V

A5 2X2 RECESSED LED VANDAL RESISTANT FLANGED

LUMINAIRE WITH 0-10V DIMMING TO 1%

KURTZON

#VL-R-3-2X2-3LEDR-835-UNV-1-WHT

FAILSAFE

#FMR-D-24-2-LD4-3-STD-35-UNV-85-ED1

D-1-CPHF-SWBR

LOS ANGELES LTG.

#FSE120-4800L-2L-FSW-PPC2-1DRDM-U

NV-2-835

RECESSED LED/3500K 4325 55 120/208V

A5E SAME AS 'A5' WITH INTEGRAL EMERGENCY BATTERY

PACK, TEST SWITCH AND SELF DIAGNOSTIC.

KURTZON

#VL-R-3-2X2-3LEDR-835-UNV-1-EM10-W

HT

FAILSAFE

#FMR-D-24-2-LD4-3-STD-35-UNV-85-ED1

D-1-EL10W-CPHF-SWBR

LOS ANGELES LTG.

#FSE120-4800L-2L-FSW-PPC2-BPL10-1D

RDM-UNV-2-835

RECESSED LED/3500K 4325 55 120/208V

B1 2X4 LED LAY-IN FLAT PANEL WITH 0-10V DIMMING

AND POINT TO SUPPORT FROM STRUCTURE AT

EACH CORNER.

LITHONIA

#EPANL-2X4-4800LM-80CRI-35K-MIN10-Z

T-MVOLT

METALUX #24FP4735C DAY-BRITE #2FXP48L835-4-DS-UNV-DIM RECESSED LED/3500K 4460 41 120/208V

B1E SAME AS 'B1' WITH INTEGRAL EMERGENCY BATTERY

PACK, TEST SWITCH AND SELF DIAGNOSTIC.

LITHONIA

#EPANL-2X4-4800LM-80CRI-35K-MIN10-Z

T-MVOLT-E10WCP

METALUX #24FP4735C-EL14W DAY-BRITE

#2FXP48L835-4-DS-UNV-DIM-EMLED

RECESSED LED/3500K 4460 41 120/208V

D1 6" RECESSED LED CAN LIGHT FIXTURE WITH 0-10V

DIMMING. WHITE REFLECTOR AND FLANGE.

LITHONIA

#LDN6-35-15-L06-WR-MVOLT-GZ1-90CRI

HALO

#HC6-15-D010-HM6-12-935-61-MD-W

LIGHTOLIER

#6RN-C6L-15935MZ10U-C6RDLWH

RECESSED LED/3500K 1500 18 120/208V

D5 6" LED RECESSED VANDAL RESISTANT DOWNLIGHT

WITH 0-10V DIMMING TO 1%. SELF FLANGED AND

POLYCARBONATE BOTTOM LENS.

KURTZON

#VL-PBD-4-8-DLM15-835-UNV-WB-WT-FP

L-TPWHT

FAIL SAFE #FLD6BX-10-D010

FEU6B-1/2-80-35 F6LBXV-M-1-MW-BL85

LIGHTOLIER

#6RN-C6L-10935MZ10U-C6RDLWH

RECESSED LED/3500K 1000 12 120/208V

K1 10' LINEAR RECESSED LED WITH 0-10V DIMMING TO

10%

FOCAL POINT

#FSM2L-FL-625LF-35K-1C-UNV-LD1-WH-

10FT

NEO-RAY

#S123DR-S-775-835-XX-10F-1-U-F-W

PRECISION ARCHITECTURAL LTG

#MLR2-HO-K35-80-10-XX-LOH-UNV-DIM1

RECESSED LED/3500K 6250 78 120/208V

K1E SAME AS 'K1' WITH INTEGRAL EMERGENCY BATTERY

PACK, TEST SWITCH AND SELF DIAGNOSTIC.

FOCAL POINT

#FSM2L-FL-625LF-35K-1C-UNV-LD1-1EM

-WH-10FT

NEO-RAY

#S123DR-S-775-835-XX-10F-1-B2-U-F-W

PRECISION ARCHITECTURAL LTG

#MLR2-HO-K35-80-10-XX-LOH-UNV-DIM1

-EBPLST

RECESSED LED/3500K 6250 78 120/208V

K2 6' LINEAR RECESSED LED WITH 0-10V DIMMING TO

10%

FOCAL POINT

#FSM2L-FL-625LF-35K-1C-UNV-LD1-WH-

6FT

NEO-RAY

#S123DR-S-775-835-XX-6F-1-U-F-W

PRECISION ARCHITECTURAL LTG

#MLR2-HO-K35-80-06-XX-LOH-UNV-DIM1

RECESSED LED/3500K 3750 47 120/208V

K2E SAME AS 'K2' WITH INTEGRAL EMERGENCY BATTERY

PACK, TEST SWITCH AND SELF DIAGNOSTIC.

FOCAL POINT

#FSM2L-FL-625LF-35K-1C-UNV-LD1-1EM

-WH-6FT

NEO-RAY

#S123DR-S-775-835-XX-6F-1-B2-U-F-W

PRECISION ARCHITECTURAL LTG

#MLR2-HO-K35-80-06-XX-LOH-UNV-DIM1

-EBPLST

RECESSED LED/3500K 3750 47 120/208V

L1 4' LED GASKETED AND SEALED INDUSTRIAL STRIP

WITH ACRYLIC LENS AND INTEGRAL MOTION

SENSOR FOR ON/OFF CONTROLS. STEM MOUNTED

WITH THREADED ROD MOUNTING ASSEMBLY.

LITHONIA

#FEM-L48-4000LM-IMAFL-WD-MVOLT-GZ

10-35K-80CRI-DPMB-SBOR10

METALUX

#4VT3-LD5-4-W-UNV-L835-CD1-MSWL20

DAY-BRITE

#DWAE35L835-4-UNV-MD360W

PENDANT LED/3500K 3824 24 120/208V

L1E SAME AS 'L1' WITH INTEGRAL EMERGENCY BATTERY

PACK, TEST SWITCH AND SELF DIAGNOSTIC.

LITHONIA

#FEM-L48-4000LM-IMAFL-WD-MVOLT-GZ

10-35K-80CRI-DPMB-E10WMCP-SBOR10

METALUX

#4VT3-LD5-4-W-UNV-EL10W-L835-CD1-

MSWL20

DAY-BRITE

#DWAE35L835-4-UNV-MD360W

PENDANT LED/3500K 3824 24 120/208V

U1 2' LED UNDERCABINET LIGHT. HEAVY GUAGE

ALUMINUM HOUSING MATTE WHITE FINISH. 90 CRI.

LITHONIA

#UCLD-18IN-30K-90CRI-WH-UCDJB

HALO #HU10-24-D-9-30-P-HU109 RDA #UC-LED20-WW SURFACE LED/3500K 1500 17 120/208V

X1 CHICAGO EDGE-LIT LED EXIT SIGN. CEILING

MOUNTED WITH RECESSED HOUSING. SINGLE FACE,

NO ARROW.

LITHONIA #EDGC-1-RW-CH3-EL SURE-LITES #ECHX-6-SHWH CHLORIDE #CE2RWWSWLARA RECESSED LED 2 120/208V OWNER TO SELECT FROM THE FULL LINE OF AVAILABLE

OPTIONS IN THE SUBMITTAL FOR THE SURE-LITES #ECHX

SERIES EXIT SIGN (OR EQUIVALENT) REFER TO FLOOR PLAN

FOR NUMBER OF SIDES AND CHEVRON REQUIREMENTS.

X2 SAME AS 'X1' EXCEPT ARROW RIGHT. LITHONIA #EDGC-1-RW-CH3-EL SURE-LITES #ECHX-6-SHWH CHLORIDE #CE2RWWSWLARA RECESSED LED 2 120/208V OWNER TO SELECT FROM THE FULL LINE OF AVAILABLE

OPTIONS IN THE SUBMITTAL FOR THE SURE-LITES #ECHX

SERIES EXIT SIGN (OR EQUIVALENT) REFER TO FLOOR PLAN

FOR NUMBER OF SIDES AND CHEVRON REQUIREMENTS.

X4 SAME AS 'X3' EXCEPT DOUBLE FACE. LITHONIA #EDGC-1-RW-CH3-EL SURE-LITES #ECHX-6-SHWH CHLORIDE #CE2RWWSWLARA RECESSED LED 2 120/208V OWNER TO SELECT FROM THE FULL LINE OF AVAILABLE

OPTIONS IN THE SUBMITTAL FOR THE SURE-LITES #ECHX

SERIES EXIT SIGN (OR EQUIVALENT) REFER TO FLOOR PLAN

FOR NUMBER OF SIDES AND CHEVRON REQUIREMENTS.

NOT TO SCALEEJ100

1 TYPICAL MEDICAL GAS / LINE PRESSURE DETAIL

SCALE: 12" = 1'-0"EJ100

2 LIGHTING CONTROL DETAILS

SCALE: 12" = 1'-0"EJ100

3 TELEVISION OUTLET INSTALLATION DETAIL

NOT TO SCALEEJ100

4 CONDUIT ROOF PENETRATION DETAIL

NOT TO SCALEEJ100

5 CONDUIT EXPANSION JOINT CROSSING DETAIL - FLEXIBLE CONDUIT

SEISMIC SUPPORT

RECESSED MOUNTED FIXTURE

NO SCALE

SEISMIC SUPPORT

PENDANT MOUNTED FIXTURE

NO SCALE

NO SCALE

NO SCALE

NO SCALE

WALL PENETRATION FIRE PROOFING

D

C

D ML

C

ES

MD

RE

MD

ACMACM

NO SCALE

FLOOR PENETRATION FIRE PROOFING

SEISMIC CONCRETE WALL-MOUNTED EQUIPMENT

VOICE AND DATA WIRING IDENTIFICATIONTYPICAL COMBINATION TEL/DATA OUTLET

NO SCALE

ELECTRIC STRIKEMAGNETIC LOCK

NO SCALE

TYPICAL WIRING DIAGRAM FOR PROXIMITY CARD READER

MOTOR CONDUIT CONNECTION

NO SCALESEISMIC SUPPORT

RECESSED MOUNTED FIXTURE

NO SCALE

ANCHORAGE

NO SCALE

NO SCALE

LOCATIONS OF BRACING - PLAN VIEW

CONDUIT SUPPORT SEISMIC SWAY BRACING CABLES

NO SCALE

TRAPEZE SUPPORT SEISMIC SWAY BRACING CABLES

NO SCALE

SEISMIC STIFFENER FOR THREADED RODS

NO SCALE

TRAPEZE TRANSVERSE & LONGITUDINAL BRACING DETAIL

NO SCALE

SLAB HUNG LARGE CONDUIT SEISMIC SUPPORT

NO SCALE

SEISMIC SWAY BRACING CABLE ANCHOR

NO SCALE

NO SCALE

SEISMIC ISOLATOR NOTES FOR SEISMIC BRACING

SEISMIC ANCHOR BOLT (SAB)

NO SCALE

TO MASONRY OR CONCRETE

LATERAL BRACING ATTACHEMENT

ISOLATED POWER PANEL WIRING DIAGRAM

NO SCALE

DOOR ELECTRICAL ROOMDOOR ELECTRICAL ROOM

RR

NOTE:

INSERT #2 TAPPING SCREWS

THRU CLAMP AND TEE BAR

(2 PER CLAMP)

RECESSED

TROFFER

SEISMIC SUPPORTED

TEE BAR CEILING

ONE #CHB CADDY CLIP

ATTACHED TO EACH

END OF FIXTURE WITH

10-32x1/2 MACHINE

SCREW AND NUT.

2 PER 4' FIXTURE,

4 PER 8' FIXTURE.

CONDUIT

STEM

CADDY SPEED

LINK

HOOK

ANCHOR IN CONCRETE

WITH EXPANSION BOLT

OR LEAD ANCHOR

CADDY AB

ANGLE BRACKET

CADDY SLD2L

CABLE HANGER

(2) RJ45 JACKS

NOTE: PROVIDE BLANK INSERTS ON ALL UN-USED PORTS.

D D

D

GROMMETT

(2) RJ45 JACKS

LAY-IN

CEILING

4" X 4" X 2.5" BOX

WITH SINGLE

GANG

TRIM RING

1" CONDUIT

FOR VOICE AND

DATA

(IN WALL)

COVERPLATE SHALL

ACCOMODATE

VOICE

AND DATA CABLES.

(2) BLANK BUILDING NUMBER

1.XXXX.01 D

TYPEWRITTEN PERMANENT CABLE

IDENTIFICATION TAG ON EACH END

OF CABLE AFTER TERMINATIONS-

(AT DEVICE AND IDF/MDF)

VOICE/DATA CABLE. SEE SPECIFICATIONS

JACKET

DROP NUMBER IN ROOM.

NUMBERING SHALL

START

FROM THE LEFT, AS YOU

WALK IN THE DOORWAY,

AND CONTINUE AROUND

THE ROOM CLOCKWISE

ROOM NUMBER SERVED

UNSHIELDED TWISTED

PAIR

(TYPICAL OF 4)

iSTAR

SECURITY

PANEL

NORMALLY

CLOSED

RELAY

DOOR

LOCK

POWER

SUPPLY

18 AWG FOR DISTANCES GREATER THAN 300 FEET

* USE 20 AWG FOR DISTANCES GREATER THEN 200 FEET AND

22 AWG, 6 COND., SHIELDED*WIEGAND READER WIRING

18 AWG., 2 COND., SHIELDEDSIGNAL WIRING

22 AWG., 4 COND.

18 AWG., 2 COND.

CABLE TYPE

POWER AND SIGNAL WIRING

POWER SUPPLY WIRING

DESCRIPTIONSYMBOL

NORMALLY

CLOSED

RELAY

iSTAR

SECURITY

PANEL

DOOR

LOCK

POWER

SUPPLY

FIRESTOP

FILL

MATERIAL

(TYPICAL)

5/8" GYPSUM

WALLBOARD

(TYPICAL)

FLOOR

SLAB

CSD SPLIT

FIRE-SAFE

SLEEVE

ANCHORED

FROM

BELOW

CORE DRILLED

HOLE OR

STEEL PIPE

SLEEVE

FIRESTOP

FORMING

MATERIAL

(TYPICAL)

METAL STUD

CONDUIT OR

SLEEVE

TELECOMMUNICATIONS

CSD SPLIT

SEALING

PLUG

CONDUIT OR

SLEEVE

TELECOMMUNICATIONS

CABLE TYPE - D=DATA; V=VOICE; W=WIRELESS AP

PROVIDE STAINLESS STEEL 2-HOLE STRAPS

FOR CONDUIT SUPPORT.

1.

PHASE

CONDUCTORS

AND EQUIPMENT

GRD'G CONDUCTOR

STARTER/

DISCONNECT/

VFD

WALL

PAD

FLOOR

TERMINAL BOX

MOTOR

LIQUIDTIGHT CONDUIT

CONNECTOR

(2) PLACES (TYP.)

CONDUIT

LIQUIDTIGHT

FLEXIBLE METAL

CONDUIT (TYP)

CADDY SFCLT

SEISMIC FIXTURE

CLAMP (SFC) WITH

SELF TAPPING

SCREWS ONE(1)

AT EACH CORNER

(TYP. OF 4)

CEILING GRID

SUPPORT BY G.C.

CEILING GRID SUPPORT

BY G.C.

NOTES

1. SFC MAIN RUNNER FLANGE SHALL BE INSTALLED UNDER

THE LIGHT FIXTURE FLANGE.

2. SFC CROSS RUNNER FLANGE SHALL BE INSTALLED OVER

THE LIGHT FIXTURE FLANGE.

MINIMUM OF 3/8" EYEBOLT, WASHER AND

NUT THROUGH STEEL STRUCTURE OR

ANCHOR IN CONCRETE WITH EXPANSION

BOLT OR LEAD ANCHOR

10'

MAX

BACK OF

STEEL PANEL

INSIDE NEOPRENE

ELEMENT

SEISMIC

ANCHOR BOLT

TYPE "SAB"

OUTER

STEEL SLEEVE

OUTSIDE

NEOPRENE

ELEMENT

STEEL DISK

ELONGATED INNER

STEEL SLEEVE

NOTES:

1. BASED ON MASON INDUSTRIES INC. TYPE "PB" NEOPRENE

BUSHING.

d d

TAR

U

N

A

RUN `B'

LL

TT T TBT

`TA' CAN BE USED AS LONGITUDINAL

BRACE FOR RUN `B' AND `TB' AS

LONGITUDINAL BRACE FOR RUN `A'

WHEN `d' IS < 24" FOR CONDUITS

PROVIDE TRANSVERSE

BRACE AT LAST

VERTICAL SUPPORT

MAXIMUM SPACING FOR

TRANSVERSE BRACES

(TYPICAL)

MAXIMUM SPACING FOR

LONGITUDINAL BRACES

NOTES:

1. REFER TO OTHER DETAILS FOR GENERAL REQUIREMENTS FOR SPACING

OF BRACES.

`T' - INDICATES TRANSVERSE BRACING - 1 SOLID BRACE.

'L' - INDICATES LONGITUDINAL BRACING - 1 SOLID BRACE AT

INDIVIDUAL CONDUITS AND 2 SOLID BRACES AT TRAPEZE

HANGERS

MAX

10'

45°TYP.

PLAN VIEW

PIPE

HANGER

(TYP.)

SLACK 1/8"

AIRCRAFT

CABLE (TYP.)

SEISMIC

CABLE

BRACE (TYP.)

SINGLE CONDUIT

2-1/2" OR

LARGER

ALL

THREADED

ROD

(TYP.)

45°TYP.

PLAN VIEW

TRAPEZE

SUPPORTED

CONDUITS

SLACK 1/8"

AIRCRAFT

CABLE (TYP.)

SEISMIC

CABLE

BRACE (TYP.)

TRAPEZE TYPE

SUPPORTS

(TYP.)

ROD STIFFENER CHART

NOTE: MINIMUM OF (2) "SCR"

REQUIRED

PER ROD.

(mm)INCHES

ATR

SIZE

"X" MAX. SPACING

BETWEEN ROD CLAMP

(457.2)

(584.2)

(711.2)

(838.2)

18"

23"

28"

33"

1/2"-13

5/8"-11 3/4"-10 7/8"-9

NOTE: IF ROD STIFFENER IS REQUIRED

SEE ADJACENT CHART.

(mm)INCHES

ATR

SIZE

MAX. ROD LENGTH

WITHOUT ROD STIFFENER

(635.0) (787.4)

(939.8) (1092.2)

25" 31"

37" 43"

1/2"-13 5/8"-11

3/4"-10 7/8"-9

6" MAX

"X"

"X"

6" MAX

SEISMIC ANCHOR AND

ANCHOR BOLT

STRUCTURE

ALL THREADED

ROD (ATR)

CLAMPS

(3) PER ROD

STIFFENER

ANGLE

ATTACHED TO

PIPE CLAMP OR

U-TYPE CHANNEL

SECTION A-A

"SRC"

ROD

CLAMP

ANGLE

ROD

NOTE:

1. BASED ON MASON INDUSTRIES INC. TYPE "SRC" ROD CLAMP.

NOTE:

1. ADD LONGITUDINAL BRACES AT EACH END, IF REQUIRED AT

THIS LOCATION.

B-LINE

B22 CHANNEL

SIZE AS REQUIRED

MASON

SCBH

ADJUSTABLE

HINGE

TRANSVERSE

BRACE

HEX NUT AND

SQUARE WASHER

B-LINE

B2400 SERIES

PIPE STRAPS

ROD

STIFFENER

MASON

SCB

ADJUSTABLE

HINGE

1 (MIN.)

6" (MIN.)

1/4" AIRCRAFT

CABLE

ALL THREADED

RODBUILDING

STRUCTURE

SEISMIC ANCHORS

CABLE

NUT &

WASHER

S

PIPE

HANGER

THREDED ROD

MAX. 10FT.

SPACING

SLACK SWAY

BRACING CABLE

1/8" GAL.

STEEL AT

APPROPRIATE

INTERVALS

SEISMIC CABLE

BRACE (2)

REQUIRED PER

CABLE

LOCATED 12" OR

MORE FROM STRUCTURE

SEISMIC

CABLE

BRACE

NOTES:

1. BASED ON MASON INDUSTRIES INC. TYPE "SCB" BRACE.

SLACK 1/8"

GAL. STEEL

AIRCRAFT CABLE

SWIVEL

CONNECTION

ANCHORED TO

STRUCTURE

ABOVE

(2) SEISMIC

CABLE BRACES

PER CABLE

TYPE "SCB"

NOTE

1. BASED ON MASON INDUSTRIES INC. TYPE "HG" NEOPRENE

ISOLATOR.

OVERSIZED HOLE

SEISMIC ANCHOR

CONCRETE

FLOOR

EQUIPMENT

SUPPORT

LEG

SEISMIC ANCHOR

BOLT

STEEL WASHER

NEOPRENE

BUSHING

"TYPE HG"

FIELD TRIM BUSHING

TO MATCH HOLE DEPTH

T

NOTE:

LATERAL DIRECTION OF SWAY BRACING CABLES SHALL

ALTERNATE AS SHOWN AT APPROPRIATE INTERVALS.

NOTE:

LATERAL DIRECTION OF SWAY BRACING CABLES SHALL

ALTERNATE AS SHOWN AT APPROPRIATE INTERVALS.

GENERAL

1. IMPORTANCE FACTOR Ip = 1.5.

2. HANGERS AND ATTACHMENT METHODS TO STRUCTURAL MEMBERS SHALL

USE DEVICES INCLUDED IN FEDERAL SPECIFICATION WW-H-171

(MSS SP-58) OR BE BOLTED/WELDED AS APPROVED BY THE ENGINEER.

BRACES SHALL BE CONNECTED TO THE HANGERS/SUPPORTS FOR

CONDUIT.

3. SEE THE SPECIFICATIONS FOR REQUIRED STRENGTH OF BRACING.

4. ALL ELECTRICAL COMPONENT SUPPORTS AND MEANS BY WHICH THEY ARE

ATTACHED TO THE COMPONENT SHALL BE DESIGNED FOR THE FORCES

AND DISPLACEMENTS DETERMINED BY ASCE 7 SECTIONS 13.3.1 AND

13.3.2.

EXCEPTIONS:

a. CONDUIT LESS THEN TRADE SIZE 2.5".

b. TRAPEZE ASSEMBLIES SUPPORTING CONDUIT, BUS DUCT OR CABLE

TRAYS WHERE THE TOTAL WEIGHT SUPPORTED BY THE TRAPEZZE

ASSEMBLY IS LESS THEN 10LB/FT.

c. CONDUIT SUSPENDED LESS THEN 12" TO STRUCTURE.

5. LATERAL SEISMIC FORCE SHALL BE CONSIDERED TO ACT CONCURRENTLY

WITH THE DEAD LOAD. THE SLENDERNESS RATIO (l/r) OF BRACES SHALL

NOT EXCEED 200, WHERE (l) IS THE LENGTH OF THE BRACE AND (r) IS

THE LEAST RADIUS OF GYRATION, BOTH IN INCHES.

6. TYPICAL SEISMIC DETAILS ARE PROVIDED ON THE DRAWINGS FOR

REFERENCE ONLY. CONTRACTOR SHALL PROVIDE SHOP DRAWINGS TO COR

FOR REVIEW AND APPROVAL. SHOP DRAWINGS SHALL SHOW ALL

EQUIPMENT ANCHORAGE TO WALLS/CEILINGS/FLOORS AND SHALL INCLUDE

SIZE OF SEISMIC ANCHOR BOLTS USED FOR EACH SYSTEM.

7. BRACES FOR SINGLE CONDUIT SUPPORTS SHALL BE ATTACHED

DIRECTLY TO THE CONDUIT, NOT TO THE CONDUIT HANGER.

8. ALL BRACING SHALL BE LOCATED WITHIN 6" OF THE VERTICAL HANGER

SUPPORT.

9. TRUSS CHORDS OF BAR JOISTS OR FROM CONCRETE MEMBERS.

10. IDENTIFY POSITION OF REINFORCING STEEL PRIOR TO DRILLING HOLES

FOR ANCHORS TO AVOID DAMAGE OF EXISTING REINFORCING. NOTIFY

COR IF REINFORCING STEEL IS ENCOUNTERED DURING DRILLING.

SEISMIC ANCHOR AND

ANCHOR BOLT

NOTE:

DRILLED-IN AND STUD-WEDGE OR FEMALE-WEDGE TYPE IN ZINC-COATED

STEEL FOR INTERIOR APPLICATIONS AND STAINLESS STEEL FOR EXTERIOR

APPLICATIONS. SELECT ANCHOR BOLTS WITH STRENGTH REQUIRED FOR

ANCHOR AND AS TESTED ACCORDING TO ASTM E 488. MINIMUM LENGTH OF

EIGHT TIMES DIAMETER. MASON INDUSTRIES, INC. TYPE SAB OR APPROVED

EQUAL.

SAB

WEDGE

ANCHO

R

CAP SCREW

WITH

STANDARD

WASHER

SEISMIC

ANCHOR

INTERNALLY

THREADED

EXPANSIO

N

WEDGE

PULL

THROUGH

RESISTANT

SHOULDER

ADJUSTABLE

MOUNTING

BRACKET

T-BAR

CEILING

GRID

SHEET METAL

SCREWC-BAR

TO T-BAR PLUS

SAME ON DIAGONAL

MOUNT C-BAR LIGHT

FIXTURE SUPPORT

CHANNEL ON T-BAR

MOUNT ADJUSTABLE

MOUNTING

BRACKETS

TO LIGHT FIXTURE

AND C-CHANNEL

5/8" BOLT B-LINE, B22 CHANNEL

LONGITUDINAL OR

TRANSVERSE BRACE

(9'-4" MAX LENGTH)

1/2"x1-1/4" HEX

HEAD CAP SCREWS

AND N225WO NUTS

EXPANSION

ANCHOR

11. AT RISERS, PROVIDE LATERAL RESTRAINT AT THE TOP AND BOTTOM OF

THE RISER, AND AT INTERMEDIATE POINTS NOT TO EXCEED 30FT.

12. STACKED TRAPEZES SUPPORTED BY THE SAME RODS SHALL BE BRACED

INDEPENDENTLY FROM ONE ANOTHER. THE ROD SUPPORTS IN EACH

SECTION MAY REQUIRED STIFFENERS.

13. PROVIDE CONDUITS THAT ARE RIGIDLY SECURED TO THE BUILDING

STRUCTURE ON OPPOSITE SIDES OF A BUILDING EXPANSION JOINT WITH

JUNCTION BOXES ON BOTH SIDES OF THE JOINT. CONNECT JUNCTION

BOXES WITH 15 INCHES OF SLACK FLEXIBLE CONDUIT.

14. SWAY BRACING SPACING PER STRAIGHT LENGTH OF CONDUIT:

A. SINGLE STEEL CONDUIT LARGER THAN 2-1/2":

TRANSVERSE - 40'; LONGITUDINAL - 80'

B. SINGLE EMT CONDUIT LARGER THAN 2-1/2":

TRANSVERSE - 20'; LONGITUDINAL - 40'

C. TRAPEZE SUPPORT: TRANSVERSE - 40'; LONGITUDINAL - 40'.

D. IF SWAY BRACING IS PROVIDED AT 45° ANGLE TO SATISFY BOTH

TRANSVERSE AND LONGITUDINAL SPACING THAN THE TRANSVERSE

SPACING REQUIREMENTS SHALL BE USED.

15. A STRAIGHT LENGTH OF CONDUIT IS DEFINED 10' OR GREATER IN

LENGTH. A HORIZONTAL OFFSET IS ALLOWED PER STRAIGHT LENGTH

WITHOUT ADDITIONAL BRACING IF THE OFFSET IS LESS THEN THE

TRANSVERSE BRACE SPACING DIVIDED BY 16 OR AS RECOMMENDED BY

THE SEISMIC BRACING MANUFACTURER.

INNER NEOPRENE

BUSHING

TYPE "PB"

NOTES:

1. COORDINATE ALL DEVICE, WIRING AND PROGRAMING REQUIREMENTS

TO

MATCH THE EXISTING FACILITY STANDARD.

NO SCALE

B B

D

I LL IN O IS

S N

A H

A

TR

E B

O R

NTHONY

LICENSED

PROFESSIONAL

OF

ENGINEER

062.059710

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

100% RE-SUBMIT 2020/06/29

C U s e rs

\j h u s to n \D o c u m e n ts

\R

I V

C E

E

L E

C T

R

IC

A L jh u s to n c m ta e g rs

.c o m

.r v t

/2

/2

:4

:0

A

M

EJ101

ELECTRICAL DETAILS

GUIDON-CMTA SDVOSB JV, LLC

1221 N. PENNSYLVANIA ST. SUITE 200

INDIANAPOLIS, IN 46202

CMTA CONSULTING ENGINEERS

903 SPRING ST.

JEFFERSONVILLE, IN 47130

EMERGENCY DEPARTMENT

RENOVATION

820 S. DAMEN AVE.

537-15-160

5/30/2020 CMTA CMTA

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

EMERGENCY UNIT SUBSTATION

FROM GEN H.V.

SUBSTATION 4160V

3 33∅

2000A FR

2000A TR

2000A BUS

480Y/277V

4160V

BRANCH

SERVING

THIS

BUILDING

BP

NE

L

BPBP

NE

L

BPBP

NE

L

BP

1600A FR

1200A TR

800A FR

175A TR

800A FR

800A TR

STUB TO NEAR DIST EQUIP (TYP)

LP-1-1

LP-3-1

LP-5-1

LP-7-1

LP-9-1

H-DP-3-1

H-DP-6-1

H-DP-9-1

H-DP-R-1

H-DP-1-1

LDP-1-1

H-EDP-2-2

H-EDP-5-1

H-EDP-8-1

H-EDP-12-1

EDP-2-1

M A

IN

LSDP-2-1

CP-1-1

CP-3-1

CDP-2-1

CP-5-1

CP-7-1

CP-9-1

ATS-3 ATS-2 ATS-1

T-3

T-2

DS-2

DS-1

112.5 KVA

500 KVA

TRANSFER S3ITCH ROOM

NORMAL UNIT SUBSTATION

2ND FLOOR

1ST FLOOR

T-1

750 KVA

2ND FLOOR

3RD FLOOR

4TH FLOOR

5TH FLOOR

6TH FLOOR

7TH FLOOR

8TH FLOOR

9TH FLOOR

10TH FLOOR

ROOF

FROM

H-DP-1-1

FROM

EDP-2-1

CDP-2-1 1ST FLOOR

2000 KVA OA

2300 KVA FA

4160VD - 480Y/277V

FROM NORMAL H.V.

SUBSTATION 4160V

3 33∅

1200A-4P 200A -3P 800A-3P

1200A MLO, 480Y/277V

2500A MCB 3/O GFI, 208Y/120V

800A

(TYP.)

400A

(TYP.)

200A

800A800A

(TYP.)

1600A MCB 3/O GFI, 208Y/120V, 65K AIC

400A MCB 3/O GFI, 208Y/120V, 65K AIC

1200A MLO, 480Y/277V, 65K AIC

400A

(TYP.)

LA

FROM

65K AIC

65K AIC

M A

IN

1200A

FR

3200A FR

3200A TR GFI

3200A BUS

480Y/277V

1200A

FR

CONTROL

CUBE

MAIN

1200A

FR

50/51

50/51

MAIN

1600A FR

1200A TR/GFI

800A FR

175A TR

800A FR

800A TR

1600A FR

1200A TR/GFI

1600A FR

1200A TR/GFI

1600A FR

SPACE

1600A FR

SPACE

1600A FR

SPACE

480V 65KAIC 480V 65KAIC 480V 65KAIC

M A

IN

800A FEED

THROUGH

208Y/120V, 50K AIC

800A FEED

THROUGH

208Y/120V, 50K AIC

800A MLO

208Y/120V, 50K AIC

800A MLO

208Y/120V, 50K AIC

400A FEED

THROUGH

480Y/277V, 50K AIC

400A FEED

THROUGH

480Y/277V, 50K AIC

400A MLO

480Y/277V, 50K AIC

ST

U

B T

O N

EA

R D

IS

T E

Q U

IP

BLDG C1

225A 208Y/120V, 50K AIC

1/4"x4"X18" CU

GROUNDING BAR

ON STANDOFFS IN

NEMA 1

ENCLOSURE

1#500 CU

INSULATED IN

1-1/2" C

EXOTHERMIC

3ELDS TYP

1#500 CU

INSULATED IN

1-1/2" C

1#500 CU

INSULATED IN

1-1/2" C

1#500 CU

INSULATED IN

1-1/2" C

1#500 CU

INSULATED IN

1-1/2" C

1#500 CU

INSULATED IN

1-1/2" C

1#500 CU

INSULATED IN

1-1/2" C

1#500 CU

INSULATED IN

1-1/2" C

1#500 CU

INSULATED IN

1-1/2" C

1#500 CU

INSULATED IN

1-1/2" C

1#500 CU

INSULATED IN

1-1/2" C TO THE

MAIN GROUNDING

BAR IN BLD 1C

225A MLO

480Y/277V, 50K AIC

100A MLO

208Y/120V, 50K AIC

100A MLO

208Y/120V, 50K AIC

225A

100A

225A

100A

(4) 100-3P

AND (12)

20A-1P CBS.

GENERATORS

LOCATED IN BUILDING 42.

EXISTING NORMAL S3ITCHGEAR

4160V

NOTE 22

LOCATED ON THE FIRST

FLOOR OF BUILDING 1C

50/51

800A FEED

THROUGH

208Y/120V, 50K AIC

800A FEED

THROUGH

208Y/120V, 50K AIC

800A MLO

208Y/120V, 50K AIC

800A MLO

208Y/120V, 50K AIC

800A FEED

THROUGH

208Y/120V, 50K AIC

800A FEED

THROUGH

208Y/120V, 50K AIC

800A MLO

208Y/120V, 50K AIC

800A MLO

208Y/120V, 50K AIC

800A FEED

THROUGH

208Y/120V, 50K AIC

800A FEED

THROUGH

208Y/120V, 50K AIC

800A MLO

208Y/120V, 50K AIC

800A MLO

208Y/120V, 50K AIC

800A FEED

THROUGH

208Y/120V, 50K AIC

800A FEED

THROUGH

208Y/120V, 50K AIC

800A MLO

208Y/120V, 50K AIC

800A MLO

208Y/120V, 50K AIC

400A MLO

480Y/277V, 50K AIC

400A FEED

THROUGH

480Y/277V, 50K AIC

400A FEED

THROUGH

480Y/277V, 50K AIC

400A FEED

THROUGH

480Y/277V, 50K AIC

400A MLO

480Y/277V, 50K AIC

400A MLO

480Y/277V, 50K AIC

400A FEED

THROUGH

480Y/277V, 50K AIC

400A FEED

THROUGH

480Y/277V, 50K AIC

400A FEED

THROUGH

480Y/277V, 50K AIC

400A FEED

THROUGH

480Y/277V, 50K AIC

400A FEED

THROUGH

480Y/277V, 50K AIC

400A FEED

THROUGH

480Y/277V, 50K AIC

400A MLO

480Y/277V, 50K AIC

400A FEED

THROUGH

480Y/277V, 50K AIC

400A FEED

THROUGH

480Y/277V, 50K AIC

400A MLO

480Y/277V, 50K AIC

400A FEED

THROUGH

480Y/277V, 50K AIC

400A FEED

THROUGH

480Y/277V, 50K AIC

400A FEED

THROUGH

480Y/277V, 50K AIC

FROM

LDP-1-1

CLP-C1

LP-C1

H-DP-C1

H-EDP-C1

H-EDP-1-1

H-EDP-3-1

H-EDP-4-1

H-EDP-6-1

H-EDP-7-1

H-EDP-9-1

H-EDP-10-1

H-DP-2-1

H-DP-4-1

H-DP-2-1

H-DP-5-1

H-DP-7-1

H-DP-8-1

H-DP-10-1

H-EDP-R-1

H-EDP-8-1

H-EDP-5-1

H-EDP-2-1

CLP-10-1

CLP-9-1

CLP-8-1

CLP-7-1

CLP-6-1

CLP-5-1

CLP-4-1

CLP-3-1

CLP-2-1

CLP-1-1

LP-10-1

LP-9-1

LP-8-1

LP-7-1

LP-1-1

H-DP-R-1

H-DP-6-1

H-DP-3-1

H-DP-9-1

LP-6-1

LP-5-1

LP-4-1

LP-3-1

LP-2-1

208Y/120V/3Φ/4W

GECP

225A

EMERGENCY

CRITICAL

NEW PANEL

208Y/120V/3Φ/4W

GP

225A

NORMAL

NEW PANEL

480Y/277V/3Φ/4W

GECP

100A

EMERGENCY

EQUIPMENT

NEW PANEL

RISER LINE LEGEND:

NE3 CONSTRUCTION

EXISTING TO REMAIN

XXX

XXX

A 1 1 2A

B

ALL EQUIPMENT IS EXISTING TO REMAIN, EXCEPT 3HERE NOTED OTHER3ISE.

NEW FEEDER NOTES:

A. PROVIDE (4) #4/0 A3G AND (1) #2 A3G GND IN 3" C.

B. PROVIDE (4) #1 A3G AND (1) #6 A3G GND IN 2" C.

RISER TAGGED NOTES:

1. PROVIDE NE3 225A TRIP RATING PLUG IN EXISTING 250A

GE SPECTRA SERIES CIRCUIT BREAKER. TRIP RATING

PLUG TO BE GE #GTP0225U0306.

2. PROVIDE NE3 100A CIRCUIT BREAKER IN AVAILABLE

BREAKER SPACE IN EXISTING GE SPECTRA SERIES

DISTRIBUTION PANELBOARD. CIRCUIT BREAKER TO BE GE

#SGHC3601L3XX.

50 KAIC 50 KAIC 50 KAIC

I LL IN O IS

S N

A H

A

TR

E B

O R

NTHONY

LICENSED

PROFESSIONAL

OF

ENGINEER

062.059710

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

100% RE-SUBMIT 2020/06/29

C U s e rs

\j h u s to n \D o c u m e n ts

\R

I V

C E

E

L E

C T

R

IC

A L jh u s to n c m ta e g rs

.c o m

.r v t

/2

/2

:4

:0

A

M

EJ200

POWER RISER DIAGRAM

GUIDON-CMTA SDVOSB JV, LLC

1221 N. PENNSYLVANIA ST. SUITE 200

INDIANAPOLIS, IN 46202

CMTA CONSULTING ENGINEERS

903 SPRING ST.

JEFFERSONVILLE, IN 47130

EMERGENCY DEPARTMENT

RENOVATION

820 S. DAMEN AVE.

537-15-160

5/30/2020 CMTA CMTA

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

NO SCALEEJ200

1 POWER RISER DIAGRAM

I LL IN O IS

N

A H

A

TR

E B

O R

NTHONY

LICENSED

PROFESSIONAL

OF

ENGINEER

062.059710

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

100% RE-SUBMIT 2020/06/29

C U s e rs

\j h u s to n \D o c u m e n ts

\R

I V

C E

E

L E

C T

R

IC

A L jh u s to n c m ta e g rs

.c o m

.r v t

/2

/2

:4

:0

A

M

EJ201

PANEL SCHEDULES

GUIDON-CMTA SDVOSB JV, LLC

1221 N. PENNSYLVANIA ST. SUITE 200

INDIANAPOLIS, IN 46202

CMTA CONSULTING ENGINEERS

903 SPRING ST.

JEFFERSONVILLE, IN 47130

EMERGENCY DEPARTMENT

RENOVATION

820 S. DAMEN AVE.

537-15-160

5/30/2020 CMTA CMTA

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

NOTES: WHERE NOT LISTED, WIRE AND CONDUIT SHALL BE BE MINIMUM PER SPECIFICATIONS. SPARE BREAKERS TO BE 20A/1P.

KITCH 800 VA 100.00% 800 VA TOTAL ESTIMATED DEMAND CURRENT: 61 A

REC 25280 VA 69.78% 17640 VA TOTAL CONNECTED CURRENT: 82 A

LTNG 2092 VA 100.00% 2092 VA TOTAL ESTIMATED DEMAND: 21819 VA

EQUIP 1300 VA 100.00% 1300 VA TOTAL CONNECTED LOAD: 29459 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL CURRENT (A): 99 A 83 A 68 A

TOTAL LOAD (kVA): 11.6 kVA 9.7 kVA 8.2 kVA

SPARE -- -- -- 20 1 53 0.0 0.0 54 1 20 -- -- -- SPARE

SPARE -- -- -- 20 1 51 0.0 0.0 52 1 20 -- -- -- SPARE

SPARE -- -- -- 20 1 49 0.0 0.0 50 1 20 -- -- -- SPARE

SPARE -- -- -- 20 1 47 0.0 0.0 48 1 20 -- -- -- SPARE

SPARE -- -- -- 20 1 45 0.0 0.0 46 1 20 -- -- -- SPARE

SPARE -- -- -- 20 1 43 0.0 0.0 44 1 20 -- -- -- SPARE

SPARE -- -- -- 20 1 41 0.0 0.0 42 1 20 -- -- -- SPARE

SPARE -- -- -- 20 1 39 0.0 0.0 40 1 20 -- -- -- SPARE

RM 1499C REC 12 12 3/4 20 1 37 0.2 0.2 38 1 20 3/4 12 12 RM 1499C REC

RMS 1453 & 1451 REC 10 10 3/4 20 1 35 0.7 0.2 36 1 20 3/4 12 12 LTNG

RM 1474C REC 12 12 3/4 20 1 33 1.1 0.7 34 1 20 3/4 10 10 RMS 1449 & 1450 REC

RM 1470 REC 12 12 3/4 20 1 31 0.9 0.9 32 1 20 3/4 12 12 RM 1470 REC

RM 1466 REC 12 12 3/4 20 1 29 0.7 0.5 30 1 20 3/4 12 12 RMS 1499B & 1499C REC

LTNG 12 12 3/4 20 1 27 0.7 0.9 28 1 20 3/4 12 12 RM 1454 REC

RM 1462 REC 12 12 3/4 20 1 25 0.4 1.2 26 1 20 3/4 12 12 LTNG

RM 1462 REC 12 12 3/4 20 1 23 0.2 1.3 24 1 20 3/4 10 10 RM 1474B REC

RM 1475 REC 10 10 3/4 20 1 21 0.7 0.7 22 1 20 3/4 10 10 RM 1475 REC

RM 1473 REC 12 12 3/4 20 1 19 0.6 0.8 20 1 20 3/4 12 12 RM 1462 REFRIGERATOR

RM 1470G REC 12 12 3/4 20 1 17 0.9 0.5 18 1 20 3/4 12 12 RM 1473 HEADWALL REC

RM 1470J HEADWALL REC 12 12 3/4 20 1 15 0.5 0.5 16 1 20 3/4 12 12 RM 1470G HEADWALL REC

RM 1470H REC 12 12 3/4 20 1 13 0.9 1.2 14 1 20 3/4 12 12 RM 1470J REC

RM 1470 REC 12 12 3/4 20 1 11 1.1 0.5 12 1 20 3/4 12 12 RM 1470H HEADWALL REC

RM 1470 REC 12 12 3/4 20 1 9 1.1 0.7 10 1 20 3/4 12 12 RM 1470 REC

RMS 1467, 1471 & 1404A REC 12 12 3/4 20 1 7 0.7 1.9 8 1 20 3/4 12 12 RM 1470 REC

RMS 1462 & 1462A REC 12 12 3/4 20 1 5 0.7 0.7 6 1 20 3/4 12 12 RM 1456 REC

RMS 1466B & 1466C REC 12 12 3/4 20 1 3 0.9 1.1 4 1 20 3/4 12 12 RM 1464 REC

RMS 1478 & 1474 REC 12 12 3/4 20 1 1 0.9 0.9 2 1 20 3/4 12 12 RM 1452 REC

CIRCUIT DESCRIPTION WIRE GND C OCP P CKT A B C CKT P OCP C GND WIRE CIRCUIT DESCRIPTION

AMPERES: 225 A MOUNTING: SURFACE SUPPLY FROM: LP-1-1

VOLTAGE: 208Y/120V,3P,4W SPD: Yes LOCATION: ELECTRICAL 14E6

PANEL: GP MAINS TYPE: MLO PANEL INTERRUPTING RATING: MIN 50KAIC

PANELBOARD AND WIRING SCHEDULE AVAILABLE FAULT CURRENT:

NOTES: WHERE NOT LISTED, WIRE AND CONDUIT SHALL BE BE MINIMUM PER SPECIFICATIONS. SPARE BREAKERS TO BE 20A/1P.

TOTAL ESTIMATED DEMAND CURRENT: 56 A

REC 16540 VA 80.23% 13270 VA TOTAL CONNECTED CURRENT: 66 A

LTNG 1787 VA 100.00% 1787 VA TOTAL ESTIMATED DEMAND: 20332 VA

EQUIP 5290 VA 100.00% 5290 VA TOTAL CONNECTED LOAD: 23602 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL CURRENT (A): 64 A 66 A 67 A

TOTAL LOAD (kVA): 7.7 kVA 7.8 kVA 8.0 kVA

SPARE -- -- -- 20 1 53 0.0 0.0 54 1 20 -- -- -- SPARE

SPARE -- -- -- 20 1 51 0.0 0.0 52 1 20 -- -- -- SPARE

SPARE -- -- -- 20 1 49 0.0 0.0 50 1 20 -- -- -- SPARE

SPARE -- -- -- 20 1 47 0.0 0.0 48 1 20 -- -- -- SPARE

SPARE -- -- -- 20 1 45 0.0 0.0 46 1 20 -- -- -- SPARE

RM 1456 REC 12 12 3/4 20 1 43 0.5 0.0 44 1 20 -- -- -- SPARE

RM 1454 REC 12 12 3/4 20 1 41 0.7 0.0 42 1 20 -- -- -- SPARE

EF-1 10 10 1 20 1 39 1.0 0.0 40 1 20 -- -- -- SPARE

RM 1449 OH DOOR 10 10 3/4 20 1 37 0.5 0.0 38 1 20 -- -- -- SPARE

RM 1450 OH DOOR 12 12 3/4 20 1 35 0.5 0.0 36 1 20 -- -- -- SPARE

RM 1451 OH DOOR 10 10 3/4 20 1 33 0.5 0.0 34 1 20 -- -- -- SPARE

RM 1453 OH DOOR 10 10 3/4 20 1 31 0.5 0.0 32 1 20 -- -- -- SPARE

RM 1478 OH DOOR 12 12 3/4 20 1 29 0.5 0.0 30 1 20 -- -- -- SPARE

RM 1470J PATIENT LIFT 12 12 3/4 20 1 27 0.2 0.0 28 1 20 -- -- -- SPARE

RM 1470H PATIENT LIFT 12 12 3/4 20 1 25 0.2 0.2 26 1 20 3/4 12 12 RM 1470G PATIENT LIFT

RM 1472 ICE MAKER 12 12 3/4 20 1 23 0.8 0.9 24 1 20 3/4 12 12 RM 1470 REC

RM 1472 UC REFRIGERATOR 12 12 3/4 20 1 21 0.8 1.0 22 1 20 3/4 12 12 RM 1470 COPIER

RM 1470 REC 12 12 3/4 20 1 19 1.3 0.5 20 1 20 3/4 12 12 RM1472 PYXIS REC

RM 1470 REC 12 12 3/4 20 1 17 1.3 0.2 18 1 20 3/4 12 12 LTNG

RM 1451 REC 10 10 3/4 20 1 15 0.7 0.7 16 1 20 3/4 10 10 RM 1453 REC

RM 1475 REC 10 10 3/4 20 1 13 0.7 0.7 14 1 20 3/4 10 10 RM 1450 REC

LTNG 12 12 3/4 20 1 11 0.8 0.5 12 1 20 3/4 12 12 RMS 1499B & 1499C REC

RM 1470 REC 12 12 3/4 20 1 9 0.5 0.8 10 1 20 3/4 12 12 LTNG

RM 1473 HEADWALL REC 12 12 3/4 20 1 7 0.9 0.7 8 1 20 3/4 10 10 RM 1449 REC

RM 1470J HEADWALL REC 12 12 3/4 20 1 5 0.9 0.9 6 1 20 3/4 12 12 RM 1470G HEADWALL REC

RMS 1474A & 1474C REC 12 12 3/4 20 1 3 0.7 0.9 4 1 20 3/4 12 12 RM 1470H HEADWALL REC

RM 1478 REC 12 12 3/4 20 1 1 0.7 0.3 2 1 20 3/4 12 12 ISO RM PRESSURE MONITORS

CIRCUIT DESCRIPTION WIRE GND C OCP P CKT A B C CKT P OCP C GND WIRE CIRCUIT DESCRIPTION

AMPERES: 225 A MOUNTING: SURFACE SUPPLY FROM: CLP-1-1

VOLTAGE: 208Y/120V,3P,4W SPD: Yes LOCATION: ELECTRICAL 14E6

PANEL: GECP MAINS TYPE: MLO PANEL INTERRUPTING RATING: MIN 50KAIC

PANELBOARD AND WIRING SCHEDULE AVAILABLE FAULT CURRENT:

NOTES: WHERE NOT LISTED, WIRE AND CONDUIT SHALL BE BE MINIMUM PER SPECIFICATIONS. SPARE BREAKERS TO BE 20A/1P.

TOTAL ESTIMATED DEMAND CURRENT: 2 A

TOTAL CONNECTED CURRENT: 2 A

TOTAL ESTIMATED DEMAND: 2000 VA

EQUIP 2000 VA 100.00% 2000 VA TOTAL CONNECTED LOAD: 2000 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL CURRENT (A): 2 A 2 A 2 A

TOTAL LOAD (kVA): 0.7 kVA 0.7 kVA 0.7 kVA

SPACE -- -- -- -- -- 41 0.0 0.0 42 -- -- -- -- -- SPACE

SPACE -- -- -- -- -- 39 0.0 0.0 40 -- -- -- -- -- SPACE

SPACE -- -- -- -- -- 37 0.0 0.0 38 -- -- -- -- -- SPACE

SPACE -- -- -- -- -- 35 0.0 0.0 36 -- -- -- -- -- SPACE

SPACE -- -- -- -- -- 33 0.0 0.0 34 -- -- -- -- -- SPACE

SPACE -- -- -- -- -- 31 0.0 0.0 32 -- -- -- -- -- SPACE

SPACE -- -- -- -- -- 29 0.0 0.0 30 -- -- -- -- -- SPACE

SPACE -- -- -- -- -- 27 0.0 0.0 28 -- -- -- -- -- SPACE

SPACE -- -- -- -- -- 25 0.0 0.0 26 -- -- -- -- -- SPACE

SPACE -- -- -- -- -- 23 0.0 0.0 24 -- -- -- -- -- SPACE

SPACE -- -- -- -- -- 21 0.0 0.0 22 -- -- -- -- -- SPACE

SPACE -- -- -- -- -- 19 0.0 0.0 20 -- -- -- -- -- SPACE

SPACE -- -- -- -- -- 17 0.0 0.0 18 -- -- -- -- -- SPACE

SPACE -- -- -- -- -- 15 0.0 0.0 16 -- -- -- -- -- SPACE

SPACE -- -- -- -- -- 13 0.0 0.0 14 -- -- -- -- -- SPACE

SPARE -- -- -- 20 1 11 0.0 0.0 12 1 20 -- -- -- SPARE

SPARE -- -- -- 20 1 9 0.0 0.0 10 1 20 -- -- -- SPARE

SPARE -- -- -- 20 1 7 0.0 0.0 8 1 20 -- -- -- SPARE

5 0.3 0.3 6

3 0.3 0.3 4AHU-1 6 10 1 45 3

1 0.3 0.3 2

3 20 3/4 12 12 RF-1

CIRCUIT DESCRIPTION WIRE GND C OCP P CKT A B C CKT P OCP C GND WIRE CIRCUIT DESCRIPTION

AMPERES: 100 A MOUNTING: SURFACE SUPPLY FROM: H-EDP-1-1

VOLTAGE: 480Y/277V,3P,4W SPD: Yes LOCATION: MECH ROOM 1499B

PANEL: GEQP MAINS…

This is the start of the file's text. The full file is on GovTribe.