087100 - Door Hardware.docx
DOCX document 73 KB Posted
- Solicitation number
- 36C25220B0023
About this file
This document is a specification for door hardware required for the Emergency Department Observation Unit Renovation project at the Jesse Brown VA Medical Center in Chicago, Illinois. The specification details the various door hardware sets needed, including continuous hinges, locks and latches, closers, stops, thresholds, and seals. Set HW-1R covers basic rated and non-rated interior doors. Set HW-2 includes key privacy indicators and closers. Mental health area sets HW-MH2 and HW-MH9 specify anti-ligature hardware. Sliding door set HW-MH8 lists an accurate door system. Materials, finishes, and installation requirements are also provided to ensure code compliance and appropriate functionality of all door hardware.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Jesse Brown VAMC VA: 537-15-160 Emergency Department Renovations Chicago, IL 60612 1-01-16 100% Construction Documents May 30, 2020 Revised 8-18-2020
SECTION 08 71 00
DOOR HARDWARE
PART 1 - GENERAL
1.1 DESCRIPTION
A. Door hardware and related items necessary for complete installation and operation of doors.
1.2 RELATED WORK
| A. | Caulking: Section 07 92 00 JOINT SEALANTS. |
| B. | Application of Hardware: Section 08 14 00, WOOD DOORS, Section 08 11 13, HOLLOW METAL DOORS AND FRAMES, Section INTENSIVE CARE UNIT/CRITICAL CARE UNIT (ICU/CCU) ENTRANCES Section 08 71 13, AUTOMATIC DOOR OPERATORS, Section 08 71 13.11. |
| D. | Painting: Section 09 91 00, PAINTING. |
| E. | Card Readers: Section 28 13 11, PHYSICAL ACCESS CONTROL SYSTEMS. |
| F. | Electrical: Division 26, ELECTRICAL. |
| G. | Fire Detection: Section 28 31 00, FIRE DETECTION AND ALARM. |
1.3 GENERAL
| A. | All hardware shall comply with UFAS, (Uniform Federal Accessible Standards) unless specified otherwise. |
| B. | Provide rated door hardware assemblies where required by most current version of the International Building Code (IBC). |
| C. | Hardware for Labeled Fire Doors and Exit Doors: Conform to requirements of NFPA 80 for labeled fire doors and to NFPA 101 for exit doors, as well as to other requirements specified. Provide hardware listed by UL, except where heavier materials, large size, or better grades are specified herein under paragraph HARDWARE SETS. In lieu of UL labeling and listing, test reports from a nationally recognized testing agency may be submitted showing that hardware has been tested in accordance with UL test methods and that it conforms to NFPA requirements. |
| D. | Hardware for application on metal and wood doors and frames shall be made to standard templates. Furnish templates to the fabricator of these items in sufficient time so as not to delay the construction. |
| E. | The following items shall be of the same manufacturer, except as otherwise specified: |
| 1. | Mortise locksets. |
| 2. | Hinges for hollow metal and wood doors. |
| 3. | Surface applied overhead door closers. |
| 4. | Exit devices. |
1.4 WARRANTY
| A. | Automatic door operators shall be subject to the terms of FAR Clause 52.246-21, except that the Warranty period shall be two years in lieu of one year for all items except as noted below: |
| 1. | Locks, latchsets, and panic hardware: 5 years. |
| 2. | Door closers and continuous hinges: 10 years. |
1.5 MAINTENANCE MANUALS
A. In accordance with Section 01 00 00, GENERAL REQUIREMENTS Article titled "INSTRUCTIONS", furnish maintenance manuals and instructions on all door hardware. Provide installation instructions with the submittal documentation.
1.6 SUBMITTALS
| A. | Submittals shall be in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA AND SAMPLES. Submit 6 copies of the schedule per Section 01 33 23. Submit 2 final copies of the final approved schedules to VAMC Locksmith as record copies (VISN Locksmith if the VAMC does not have a locksmith). |
| B. | Hardware Schedule: Prepare and submit hardware schedule in the following form: |
| Hardware Item | |
| Quantity | |
| Size | |
| Reference Publication Type No. | |
| Finish | |
| Mfr. Name and Catalog No. | |
| Key Control Symbols | |
| UL Mark (if fire rated and listed) | |
| ANSI/BHMA Finish Designation |
| C. | Samples and Manufacturers' Literature: |
| 1. | Samples: All hardware items (proposed for the project) that have not been previously approved by Builders Hardware Manufacturers Association shall be submitted for approval. Tag and mark all items with manufacturer's name, catalog number and project number. |
| 2. | Samples are not required for hardware listed in the specifications by manufacturer's catalog number, if the contractor proposes to use the manufacturer's product specified. |
| D. | Certificate of Compliance and Test Reports: Submit certificates that hardware conforms to the requirements specified herein. Certificates shall be accompanied by copies of reports as referenced. The testing shall have been conducted either in the manufacturer's plant and certified by an independent testing laboratory or conducted in an independent laboratory, within four years of submittal of reports for approval. |
1.7 DELIVERY AND MARKING
A. Deliver items of hardware to job site in their original containers, complete with necessary appurtenances including screws, keys, and instructions. Tag one of each different item of hardware and deliver to COR for reference purposes. Tag shall identify items by Project Specification number and manufacturer's catalog number. These items shall remain on file in COR’s office until all other similar items have been installed in project, at which time the COR will deliver items on file to Contractor for installation in predetermined locations on the project.
1.8 preinstallation meeting
| A. | Convene a preinstallation meeting not less than 30 days before start of installation of door hardware. Require attendance of parties directly affecting work of this section, including Contractor and Installer, Architect, Project Engineer and VA Locksmith, Hardware Consultant, and Hardware Manufacturer’s Representative. Review the following: |
| 1. | Inspection of door hardware. |
| 2. | Job and surface readiness. |
| 3. | Coordination with other work. |
| 4. | Protection of hardware surfaces. |
| 5. | Substrate surface protection. |
| 6. | Installation. |
| 7. | Adjusting. |
| 8. | Repair. |
| 9. | Field quality control. |
10. Cleaning.
1.9 INSTRUCTIONS
| A. | Hardware Set Symbols on Drawings: Except for protective plates, door stops, mutes, thresholds and the like specified herein, hardware requirements for each door are indicated on drawings by symbols. Symbols for hardware sets consist of letters (e.g., "HW") followed by a number. Each number designates a set of hardware items applicable to a door type. |
| B. | Keying: All cylinders shall be keyed into existing system. Provide removable core cylinders that are removable only with a special key or tool without disassembly of knob or lockset. Cylinders shall be 7 pin type. Keying information shall be furnished at a later date by the COR. |
| C. | Keying: A new Great Grandmaster key shall be established for this project. The key system shall be small format (Best size and profile) removable core type as previously described. The key blanks shall be protected by a utility patent with a minimum seven years remaining on the patent from the start of construction, and protected by contract-controlled distribution. The manufacturer shall furnish code pattern listings in both paper and electronic formats so keys may be reproduced by code.; provide electronic format in file type required by project’s key control software. The manufacturer shall design the new key system with the capacity to rekey the existing system and also provide for 25 percent expansion capability beyond this requirement. Submit a keying chart for approval showing proposed keying layout and listing expansion capacity. |
| 1. | Keying information will be furnished to the Contractor by the COR |
| 2. | Supply information regarding key control of cylinder locks to manufacturers of equipment having cylinder type locks. Notify COR Engineer immediately when and to whom keys or keying information is supplied. Return all such keys to the COR. |
1.10 APPLICABLE PUBLICATIONS
| A. | The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. In text, hardware items are referred to by series, types, etc., listed in such specifications and standards, except as otherwise specified. |
| B. | American Society for Testing and Materials (ASTM): |
| F883-04 | Padlocks |
E2180-07................Standard Test Method for Determining the Activity of Incorporated Antimicrobial Agent(s) In Polymeric or Hydrophobic Materials
| C. | American National Standards Institute/Builders Hardware Manufacturers Association (ANSI/BHMA): |
| A156.1-06 | Butts and Hinges |
| A156.2-03 | Bored and Pre-assembled Locks and Latches |
| A156.3-08 | Exit Devices, Coordinators, and Auto Flush Bolts |
| A156.4-08 | Door Controls (Closers) |
| A156.5-14 | Cylinders and Input Devices for Locks. |
| A156.6-05 | Architectural Door Trim |
| A156.8-05 | Door Controls-Overhead Stops and Holders |
| A156.11-14 | Cabinet Locks |
A156.12-05 .............Interconnected Locks and Latches A156.13-05 Mortise Locks and Latches Series 1000 A156.14-07 .............Sliding and Folding Door Hardware
| A156.15-06 | Release Devices-Closer Holder, Electromagnetic and Electromechanical |
| A156.16-08 | Auxiliary Hardware |
A156.17-04 .............Self-Closing Hinges and Pivots A156.18-06 Materials and Finishes A156.20-06 .............Strap and Tee Hinges, and Hasps
| A156.21-09 | Thresholds |
| A156.22-05 | Door Gasketing and Edge Seal Systems |
| A156.23-04 | Electromagnetic Locks |
| A156.24-03 | Delayed Egress Locking Systems |
A156.25-07 .............Electrified Locking Devices A156.26-06 Continuous Hinges A156.28-07 .............Master Keying Systems A156.29-07 .............Exit Locks and Alarms A156.30-03 .............High Security Cylinders
| A156.31-07 | Electric Strikes and Frame Mounted Actuators |
| A156.36-10 | Auxiliary Locks |
| A250.8-03 | Standard Steel Doors and Frames |
| D. | National Fire Protection Association (NFPA): |
| 80-10 | Fire Doors and Other Opening Protectives |
| 101-09 | Life Safety Code |
| E. | Underwriters Laboratories, Inc. (UL): |
| Building Materials Directory (2008) |
PART 2 - PRODUCTS
2.1 CONTINUOUS HINGES
| A. | ANSI/BHMA A156.26, Grade 1-600. |
| 1. | Listed under Category N in BHMA's "Certified Product Directory." |
| B. | General: Minimum 0.120-inch- (3.0-mm-) thick, hinge leaves with minimum overall width of 4 inches (102 mm); fabricated to full height of door and frame and to template screw locations; with components finished after milling and drilling are complete |
| C. | 1. Continuous, Barrel-Type Hinges: Hinge with knuckles formed around a Teflon-coated 6.35mm (0.25-inch) minimum diameter pin that extends entire length of hinge. |
| 2. | Base Metal for Interior Hinges: Stainless steel. |
| 3. | Base Metal for Hinges for Fire-Rated Assemblies: Stainless steel. |
| 4. | Provide with non-removable pin (hospital tip option) at lockable outswing doors. |
| 5. | Where required to clear adjacent casing, trim, and wall conditions and allow full door swing, provide wide throw hinges of minimum width required. |
| 6. | Provide with manufacturer’s cut-outs for separate mortised power transfers and/or mortised automatic door bottoms where they occur. |
| 7. | Where thru-wire power transfers are integral to the hinge, provide hinge with easily removable portion to allow easy access to wiring connections. |
| 8. | Where models are specified that provide an integral wrap-around edge guard for the hinge edge of the door, provide manufacturer’s adjustable threaded stud and machine screw mechanism to allow the door to be adjusted within the wrap-around edge guard. |
2.2 DOOR CLOSING DEVICES
A. Closing devices shall be products of one manufacturer for each type specified.
2.3 OVERHEAD CLOSERS
| A. | Conform to ANSI A156.4, Grade 1. |
| B. | Closers shall conform to the following: |
| 1. | The closer shall have minimum 50 percent adjustable closing force over minimum value for that closer and have adjustable hydraulic back check effective between 60 degrees and 85 degrees of door opening. |
| 2. | Where specified, closer shall have hold-open feature. |
| 3. | Size Requirements: Provide multi-size closers, sizes 1 through 6, except where multi-size closer is not available for the required application. |
| 4. | Material of closer body shall be forged or cast. |
| 5. | Arm and brackets for closers shall be steel, malleable iron or high strength ductile cast iron. |
| 6. | Closers shall have full size metal cover; plastic covers will not be accepted. |
| 7. | Closers shall have adjustable hydraulic back-check, separate valves for closing and latching speed, adjustable back-check positioning valve, and adjustable delayed action valve. |
| 8. | Provide closers with any accessories required for the mounting application, including (but not limited to) drop plates, special soffit plates, spacers for heavy-duty parallel arm fifth screws, bull-nose or other regular arm brackets, longer or shorter arm assemblies, and special factory templating. Provide special arms, drop plates, and templating as needed to allow mounting at doors with overhead stops and/or holders. |
9. Closer arms or backcheck valve shall not be used to stop the door from overswing, except in applications where a separate wall, floor, or overhead stop cannot be used.
10. Provide parallel arm closers with heavy duty rigid arm.
11. Where closers are to be installed on the push side of the door, provide parallel arm type except where conditions require use of top jamb arm.
12. Provide all surface closers with the same body attachment screw pattern for ease of replacement and maintenance.
13. All closers shall have a 1 ½” (38mm) minimum piston diameter.
2.4 DOOR STOPS
| A. | Conform to ANSI A156.16. |
| B. | Provide door stops wherever an opened door or any item of hardware thereon would strike a wall, column, equipment or other parts of building construction. For concrete, masonry or quarry tile construction, use lead expansion shields for mounting door stops. |
| C. | Where cylindrical locks with turn pieces or pushbuttons occur, equip wall bumpers Type L02251 (rubber pads having concave face) to receive turn piece or button. |
| E. | Where drywall partitions occur, use floor stops, Type L02141 or L02161 in office areas, Type L02121 elsewhere. |
| F. | Omit stops where floor mounted door holders are required and where automatic operated doors occur. |
| G. | Provide appropriate roller bumper for each set of doors (except where closet doors occur) where two doors would interfere with each other in swinging. |
| H. | Provide appropriate door mounted stop on doors in individual toilets where floor or wall mounted stops cannot be used. |
| I. | Provide overhead surface applied stop Type C02541, ANSI A156.8 on patient toilet doors in bedrooms where toilet door could come in contact with the bedroom door. |
| J. | Provide door stops on doors where combination closer magnetic holders are specified, except where wall stops cannot be used or where floor stops cannot be installed within 4-inches of the wall. |
| K. | Where the specified wall or floor stop cannot be used, provide concealed overhead stops (surface-mounted where concealed cannot be used). |
2.5 OVERHEAD DOOR STOPS and HOLDERS
A. Conform to ANSI Standard A156.8. Overhead holders shall be of sizes recommended by holder manufacturer for each width of door. Set overhead holders for 110 degree opening, unless limited by building construction or equipment. Provide Grade 1 overhead concealed slide type: stop-only at rated doors and security doors, hold-open type with exposed hold-open on/off control at all other doors requiring overhead door stops.
2.6 LOCKS AND LATCHES
| A. | Conform to ANSI A156.2. Locks and latches for doors 45 mm (1-3/4 inch) thick or over shall have beveled fronts. Cylinder shall be removable by special key or tool. Construct all cores so that they will be interchangeable into the core housings of all mortise locks, rim locks, cylindrical locks, and any other type lock included in the Great Grand Master Key System. Disassembly of lever or lockset shall not be required to remove core from lockset. All locksets or latches on double doors with fire label shall have latch bolt with 19 mm (3/4 inch) throw, unless shorter throw allowed by the door manufacturer’s fire label. Provide temporary keying device or construction core to allow opening and closing during construction and prior to the installation of final cores. |
| B. | In addition to above requirements, locks and latches shall comply with following requirements: |
| 1. | Mortise Lock and Latch Sets: Conform to ANSI/BHMA A156.13. Mortise locksets shall be series 1000, minimum Grade 2. No substitute lever material shall be accepted. All locks and latchsets shall be furnished with 122.55 mm (4-7/8-inch) curved lip strike and wrought box. Lock function F02 shall be furnished with emergency tools/keys for emergency entrance. Furnish armored fronts for all mortise locks. All locks must be compatible with a Best 7 pin; F type core. |
| 3. | Auxiliary locks shall be as specified under hardware sets and conform to ANSI A156.36. |
| 4. | Locks on designated doors in Psychiatric (Mental Health) areas shall be paddle type with arrow projection covers and be UL Listed. Provide these locks with paddle in the down position on both sides of the door. Locks shall be fabricated of wrought stainless steel. |
| 5. | Privacy locks in non-mental-health patient rooms shall have an inside thumbturn for privacy and an outside thumbturn for emergency entrance. Single occupancy patient privacy doors shall typically swing out; where such doors cannot swing out, provide center-pivoted doors with rescue hardware (see HW-2B). |
2.7 ELECTRIC STRIKES
| A. | ANSI/ BHMA A156.31 Grade 1. |
| B. | General: Use fail-secure electric strikes at fire-rated doors. |
2.8 KEYS
| A. | Stamp all keys with change number and key set symbol. Furnish keys in quantities as follows: |
| Locks/Keys | |
| Quantity |
| Cylinder locks |
| 2 keys each |
| Cylinder lock change key blanks |
| 100 each different key way |
| Masterkeyed sets |
| 6 keys each |
| Grand Master sets |
| 6 keys each |
| Great Grand Master set |
| 5 keys |
| Control key |
| 2 keys |
B. Psychiatric keys shall be cut so that first two bittings closest to the key shoulder are shallow to provide greater strength at point of greatest torque.
2.9 ARMOR PLATES, KICK PLATES, MOP PLATES AND DOOR EDGING
| A. | Conform to ANSI Standard A156.6. |
| B. | Provide protective plates and door edging as specified below: |
| 1. | Kick plates, mop plates and armor plates of metal, Type J100 series. |
| 2. | Provide kick plates and mop plates where specified. Kick plates shall be 254 mm (10 inches) or 305 mm (12 inches) high. Mop plates shall be 152 mm (6 inches) high. Both kick and mop plates shall be minimum 1.27 mm (0.050 inches) thick. Provide kick and mop plates beveled on all 4 edges (B4E). On push side of doors where jamb stop extends to floor, make kick plates 38 mm (1-1/2 inches) less than width of door, except pairs of metal doors which shall have plates 25 mm (1 inch) less than width of each door. Extend all other kick and mop plates to within 6 mm (1/4 inch) of each edge of doors. Kick and mop plates shall butt astragals. For jamb stop requirements, see specification sections pertaining to door frames. |
| 3. | Kick plates and/or mop plates are not required on following door sides: |
| a. | Armor plate side of doors; |
| b. | Closet side of closet doors; |
| 4. | Armor plates for doors are listed under Article "Hardware Sets". Armor plates shall be thickness as noted in the hardware set, 875 mm (35 inches) high and 38 mm (1-1/2 inches) less than width of doors, except on pairs of metal doors. Provide armor plates beveled on all 4 edges (B4E). Plates on pairs of metal doors shall be 25 mm (1 inch) less than width of each door. Where top of intermediate rail of door is less than 875 mm (35 inches) from door bottom, extend armor plates to within 13 mm (1/2 inch) of top of intermediate rail. On doors equipped with panic devices, extend armor plates to within 13 mm (1/2 inch) of panic bolt push bar. |
| 5. | Provide stainless steel edge guards where so specified at wood doors. Provide mortised type instead of surface type except where door construction and/or ratings will not allow. Provide edge guards of bevel and thickness to match wood door. Provide edge guards with factory cut-outs for door hardware that must be installed through or extend through the edge guard. Provide full-height edge guards except where door rating does not allow; in such cases, provide edge guards to height of bottom of typical lockset armor front. Forward edge guards to wood door manufacturer for factory installation on doors. |
2.10 FLUSH BOLTS (AUTOMATIC)
| A. | Conform to ANSI A156.3. Dimension of flush bolts shall conform to ANSI A115. Bolts shall conform to Underwriters Laboratories, Inc., requirements for fire door hardware. Flush bolts shall automatically latch and unlatch. Furnish dustproof strikes conforming to ANSI A156.16 for bottom flushbolt. Face plates for dustproof strike shall be rectangular and not less than 38 mm by 90 mm (1-1/2 by 3-1/2 inches). |
| B. | At interior doors, provide auto flush bolts less bottom bolt, unless otherwise specified, except at wood pairs with fire-rating greater than 20 minutes; provide fire pins as required by auto flush bolt and door fire labels. |
2.11 COORDINATORS
A. Conform to ANSI A156.16. Coordinators, when specified for fire doors, shall comply with Underwriters Laboratories, Inc., requirements for fire door hardware. Coordinator may be omitted on interior pairs of non-labeled open where open back strike is used. Open back strike shall not be used on labeled doors. Paint coordinators to match door frames, unless coordinators are plated. Provide bar type coordinators, except where gravity coordinators are required at acoustic pairs. For bar type coordinators, provide filler bars for full width and, as required, brackets for push-side surface mounted closers, overhead stops, and vertical rod panic strikes.
2.12 MISCELLANEOUS HARDWARE
| A. | Access Doors (including Sheet Metal, Screen and Woven Wire Mesh Types): Except for fire-rated doors and doors to Temperature Control Cabinets, equip each single or double metal access door with locks compatible with a Best 7 pin; F type core, conforming to ANSI A156.11. Key locks as directed. Ship lock prepaid to the door manufacturer. Hinges shall be provided by door manufacturer. |
| B. | Mutes: Conform to ANSI A156.16. Provide door mutes or door silencers Type L03011 or L03021, depending on frame material, of white or light gray color, on each steel or wood door frame, except at fire-rated frames. Furnish 3 mutes for single doors and 2 mutes for each pair of doors, except double-acting doors. Provide 2 mutes for each edge of sliding door which would contact door frame. |
2.13 FINISHES
| A. | Exposed surfaces of hardware shall have ANSI A156.18, finishes as specified below. Finishes on all hinges, pivots, closers, thresholds, etc., shall be as specified below under "Miscellaneous Finishes." For field painting (final coat) of ferrous hardware, see Section 09 91 00, PAINTING. |
| B. | 626 or 630: All surfaces on interior of buildings, except where other finishes are specified. |
| C. | Miscellaneous Finishes: |
| 1. | Hinges --interior doors: 630. |
| 2. | Pivots: Match door trim. |
| 3. | Door Closers: Factory applied paint finish. Dull or Satin Aluminum color. |
| D. | Hardware Finishes for Existing Buildings: U.S. Standard finishes shall match finishes of hardware in (similar) existing spaces except where otherwise specified. |
| E. | Special Finish: Exposed surfaces of hardware for dark bronze anodized aluminum doors shall have oxidized oil rubbed bronze finish (dark bronze) finish on door closers shall closely match doors. |
| F. | Anti-microbial Coating: All hand-operated hardware (levers, pulls, push bars, push plates, paddles, and panic bars) shall be provided with an anti-microbial/anti-fungal coating that has passed ASTM E2180 tests. Coating to consist of ionic silver (Ag+). Silver ions surround bacterial cells, inhibiting growth of bacteria, mold, and mildew by blockading food and respiration supplies. |
2.14 BASE METALS
| A. | Apply specified U.S. Standard finishes on different base metals as following: |
| Finish | |
| Base Metal |
| 626 |
| Brass or bronze |
| 630 |
| Stainless steel |
PART 3 - EXECUTION
3.1 HARDWARE HEIGHTS
| A. | For existing buildings locate hardware on doors at heights to match existing hardware. The Contractor shall visit the site, verify location of existing hardware and submit locations to VA COR for approval. |
| B. | Hardware Heights from Finished Floor: |
| 1. | Exit devices centerline of strike (where applicable) 1024 mm (40-5/16 inches). |
| 2. | Locksets and latch sets centerline of strike 1024 mm (40-5/16 inches). |
| 3. | Deadlocks centerline of strike 1219 mm (48 inches). |
| 4. | Hospital arm pull 1168 mm (46 inches) to centerline of bottom supporting bracket. |
| 5. | Centerline of door pulls to be 1016 mm (40 inches). |
| 6. | Locate other hardware at standard commercial heights. Locate push and pull plates to prevent conflict with other hardware. |
3.2 INSTALLATION
A. Closer devices, including those with hold-open features, shall be equipped and mounted to provide maximum door opening permitted by building construction or equipment. Closers shall be mounted on side of door inside rooms, inside stairs, and away from corridors Where closers are mounted on doors they shall be mounted with sex nuts and bolts; foot shall be fastened to frame with machine screws.
| B. | Hinge Size Requirements: |
| Door Thickness | |
| Door Width | |
| Hinge Height |
| 45 mm (1-3/4 inch) |
| 900 mm (3 feet) and less |
| 113 mm (4-1/2 inches) |
| 45 mm (1-3/4 inch) |
| Over 900 mm (3 feet) but |
not more than 1200 mm (4 feet) 125 mm (5 inches)
| 35 mm (13/8 inch) (hollow core wood doors) |
| Not over 1200 mm (4 feet) |
| 113 mm (4-1/2 inches) |
| C. | Hinge leaves shall be sufficiently wide to allow doors to swing clear of door frame trim and surrounding conditions. |
| D. | Where new hinges are specified for new doors in existing frames or existing doors in new frames, sizes of new hinges shall match sizes of existing hinges; or, contractor may reuse existing hinges provided hinges are restored to satisfactory operating condition as approved by COR. Existing hinges shall not be reused on door openings having new doors and new frames. Coordinate preparation for hinge cut-outs and screw-hole locations on doors and frames. |
| E. | Hinges Required Per Door: |
| Doors 1500 mm (5 ft) or less in height | |
| 2 butts |
| Doors over 1500 mm (5 ft) high and not over 2280 mm (7 ft 6 in) high |
| 3 butts |
| Doors over 2280 mm (7 feet 6 inches) high |
| 4 butts |
| Dutch type doors |
| 4 butts |
| Doors with spring hinges 1370 mm (4 feet 6 inches) high or less |
| 2 butts |
| Doors with spring hinges over 1370 mm (4 feet 6 inches) |
| 3 butts |
| F. | Fastenings: Suitable size and type and shall harmonize with hardware as to material and finish. Provide machine screws and lead expansion shields to secure hardware to concrete, ceramic or quarry floor tile, or solid masonry. Fiber or rawl plugs and adhesives are not permitted. All fastenings exposed to weather shall be of nonferrous metal. |
| G. | After locks have been installed; show in presence of COR that keys operate their respective locks in accordance with keying requirements. (All keys, Master Key level and above shall be sent Registered Mail to the Medical Center Director along with the bitting list. Also a copy of the invoice shall be sent to the COR for his records.) Installation of locks which do not meet specified keying requirements shall be considered sufficient justification for rejection and replacement of all locks installed on project. |
3.3 FINAL INSPECTION
| A. | Installer to provide letter to VA COR that upon completion, installer has visited the Project and has accomplished the following: |
| 1. | Re-adjust hardware. |
| 2. | Evaluate maintenance procedures and recommend changes or additions, and instruct VA personnel. |
| 3. | Identify items that have deteriorated or failed. |
| 4. | Submit written report identifying problems. |
3.4 DEMONSTRATION
A. Demonstrate efficacy of mechanical hardware and electrical, and electronic hardware systems, including adjustment and maintenance procedures, to satisfaction of COR and VA Locksmith.
3.5 HARDWARE SETS
| A. | Following sets of hardware correspond to hardware symbols shown on drawings. Only those hardware sets that are shown on drawings will be required. Disregard hardware sets listed in specifications but not shown on drawings. |
| B. | Hardware Consultant working on a project will be responsible for providing additional information regarding these hardware sets. The numbers shown in the following sets come from BHMA standards. |
ELECTRIC HARDWARE ABBREVIATIONS LEGEND:
ADO = Automatic Door Operator EMCH = Electro-Mechanical Closer-Holder MHO = Magnetic Hold-Open (wall- or floor-mounted)
INTERIOR SINGLE DOORS
HW-1R
Each Door to Have: RATED/NON-RATED
| 1 | Continuous Hinge | ||
| 1 | Latchset | F04 | |
| 1 | Kick Plate | J102 | |
| 1 | Closer (@ rated doors) | C02011/C02021 | |
| 1 | Wall Stop | L02101 CONVEX | |
| 1 | Set Self-Adhesive Seals | R0Y154 |
HW-2
Each Door to Have: RATED/NON-RATED
| 1 | Continuous Hinges | QUANTITY & TYPE AS REQUIRED | |||
| 1 | Keyed Privacy Indicator Lock | F13 x OCCUPANCY INDICATOR | |||
| 1 | Closer | C02011/C02021 | |||
| 1 | Kick Plate | J102 | |||
| 1 | Mop Plate (@ Inswing Doors) | J103 | |||
| 1 | Floor Stop | L02121 x 3 FASTENERS | |||
| 1 | Set Self-Adhesive Seals | R0Y154 |
STONE THRESHOLD BY OTHER TRADES.
HW-3G
Each Door to Have: NON-RATED
| 1 | Continuous Hinges | QUANTITY & TYPE AS REQUIRED | |||
| 1 | Office Lock | F04 | |||
| 1 | Floor Stop | L02121 x 3 FASTENERS | |||
| 1 | Coat Hook | L03121 | |||
| 1 | Door Viewer | (Mental Health Only) | L03221 – 190° (VIEW INTO CORRIDOR) | ||
| 1 | Threshold | J32300 x 57 MM WIDTH (2-1/4 INCHES) | |||
| 1 | Auto Door Bottom | R0Y346 – HEAVY DUTY | |||
| 2 | Sets Self-Adhesive Seals | R0Y154 |
OMIT VIEWER IF DOOR PROVIDED WITH VISION LITE.
OMIT COAT HOOK WHERE GLASS LITE PREVENTS INSTALLATION.
HW-4R
Each Door to Have: RATED
| 1 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | ||||
| X ADJUSTA-SCREWS x 4-THRUWIRE TRANSFER | ||||||
| X IN-HINGE ACCESS PANEL | ||||||
| 1 | Classroom Lock | F05 | ||||
| 1 | Electric Strike | E09311 (FAIL-SECURE), 24VDC | ||||
| 1 | Power Supply | REGULATED, FILTERED, 24VDC, AMPERAGE | ||||
| AS REQUIRED | ||||||
| 1 | Kick Plate | J102 | ||||
| 1 | Mop Plate (@ Inswing Doors) | J103 @ TOILET ROOMS ONLY | ||||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | ||||
| 1 | Floor Stop | L02121 x 3 FASTENERS | ||||
| 2 | Set Self-Adhesive Seals | R0Y154 |
POWER TRANSFER FOR RE-ACTIVATION SENSOR WIRING (RE-ACTIVATION SENSORS PROVIDED BY SECTION 08 71 13).
CARD READER BY DIVISION 28.
HW-5B
Each Door to Have: RATED
| 1 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | ||||
| X ADJUSTA-SCREWS | ||||||
| 1 | Storeroom Lock | F07 | ||||
| 1 | Closer | C02011/C02021 | ||||
| 1 | Armor Plate | J101 x 1.275 MM (0.050 INCH) THICKNESS | ||||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | ||||
| 1 | Floor Stop | L02121 x 3 FASTENERS | ||||
| 1 | Set Self-Adhesive Seals | R0Y154 |
HW-5D
Each Door to Have: NON-RATED
| Continuous Hinges | QUANTITY & TYPE AS REQUIRED | |||
| 1 | Storeroom Lock | F07 | ||
| 1 | Kick Plate | J102 (@ STORAGE, EVM, & HAC ROOMS ONLY) | ||
| 1 | Floor Stop (@ Inswing Doors) | L02121 x 3 FASTENERS | ||
| 1 | Wall Stop (@ Outswing Doors) | L02101 CONVEX | ||
| 3 | Silencers | L03011 |
HW-5G
Each Door to Have: NON-RATED
| 1 | Continuous Hinges | QUANTITY & TYPE AS REQUIRED | ||
| 1 | Storeroom Lock | F07 | ||
| 1 | Kick Plate | J102 | ||
| 1 | Floor Stop | L02121 x 3 FASTENERS | ||
| 1 | Threshold | J32300 x 57 MM WIDTH (2-1/4 INCHES) | ||
| 1 | Auto Door Bottom | R0Y346 – HEAVY DUTY | ||
| 2 | Sets Self-Adhesive Seals | R0Y154 |
INTERIOR PAIRS OF DOORS
HW-8F
Each [ADO] Pair to Have: NON-RATED
| 2 | Continuous Hinges | x INTEGRAL HINGE GUARD CHANNEL | ||||
| X ADJUSTA-SCREWS x 4-THRUWIRE TRANSFERS | ||||||
| X IN-HINGE ACCESS PANEL | ||||||
| 2 | Push Plate | J304 8” x 16” | ||||
| 2 | Hospital Grip | J401 | ||||
| 2 | Kick Plate | J102 | ||||
| 2 | Mop Plate (@ Inswing Doors) | J103 | ||||
| 2 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | ||||
| 2 | Floor Stop | L02121 x 3 FASTENERS | ||||
| 2 | Auto Door Bottoms | R0Y346 – HEAVY DUTY | ||||
| 2 | Set Self-Adhesive Seals | R0Y154 |
AUTOMATIC DOOR OPERATORS AND CONTROLS BY SECTION 08 71 13, AUTOMATIC DOOR OPERATORS.
POWER TRANSFERS FOR RE-ACTIVATION SENSOR WIRING (RE-ACTIVATION SENSORS PROVIDED BY SECTION 08 71 13).
SECURITY HARDWARE ABBREVIATIONS LEGEND:
AC = Access Control Device (Card reader, biometric reader, keypad, etc.)
ADO = Automatic Door Operator DEPH = Delayed Egress Panic Exit Device DPS = Door Position Switch (Door or Alarm Contact) EL = Electric Lock or Electric Lever Exit Device PB = Push-button Combination Lock (stand-alone) ELR = Electric Latch Retraction Exit Device REX = Request-to-Exit Switch in Latching Device Inside Trim
INTERIOR SINGLE SECURITY DOORS
HW-SH-3C
Each [PB] Door to Have: NON-RATED/RATED
| 1 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | ||||
| X ADJUSTA-SCREWS | ||||||
| 1 | Push-button Combination Lock | N3 – A156.13 F07 G1 E06 | ||||
| 1 | Closer | C02011/C02021 | ||||
| 1 | Armor Plate | J101 x 1.275 MM (0.050 INCH) THICKNESS | ||||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | ||||
| 1 | Floor Stop | L02121 x 3 FASTENERS | ||||
| 1 | Set Self-Adhesive Seals | R0Y154 |
HW-SH-3E
Each [AC, EL, REX, DPS] Door to Have: RATED
| 1 | Continuous Hinges | QUANTITY & TYPE AS REQUIRED | ||||
| 1 | Transfer Hinge | 4-WIRE TYPE AS REQUIRED | ||||
| 1 | Electrified Occupancy | F13-MODIFIED (E01-REX, E06) 24VDC | ||||
| Indicator Lock | X OCCUPANCY INDICATOR X KEY RETRACTS | |||||
| LATCHBOLT AND DEADBOLT X INTERNAL | ||||||
| DEADBOLT MONITOR SWITCH | ||||||
| 1 | Power Supply | REGULATED, FILTERED, 24VDC, AMPERAGE | ||||
| AS REQUIRED | ||||||
| 1 | Closer | C02011/C02021 | ||||
| 1 | Floor Stop | L02121 x 3 FASTENERS | ||||
| 1 | Threshold | J32300 x 57 mm width (2-1/4 inches) | ||||
| 1 | Auto Door Bottom | R0Y346 – HEAVY DUTY | ||||
| 2 | Sets Self-Adhesive Seals | R0Y154 | ||||
| 1 | Alarm Contact |
INTERNAL DEADBOLT MONITOR SWITCH SHUNTS ACCESS CONTROL DEVICE WHEN DEADBOLT IS THROWN.
120VAC POWER, CONDUIT, AND WIRING BY DIVISION 26.
CARD READER BY DIVISION 28.
BY DIVISION 26.
HW-SH-4
Each [AC, EL, REX, DPS] Integrated Door to Have: RATED
1 Key Cylinder TYPE AS REQUIRED
BALANCE OF HARDWARE BY SECTION 08 17 10, INTEGRATED DOOR ASSEMBLIES
HW-SH-9
Each [AC, EL, REX, DPS] Pair to Have: RATED
| Hinges | QUANTITY & TYPE AS REQUIRED | |||||
| 1 | Transfer Hinge | 4-WIRE TYPE AS REQUIRED | ||||
| 1 | Set Auto Flush Bolts | TYPE 25 | ||||
| 1 | Dust Proof Strike | L04021 | ||||
| 1 | Electrified Lock | F07 (E01-REX, E06) 24VDC | ||||
| 1 | Power Supply | REGULATED, FILTERED, 24VDC, AMPERAGE | ||||
| AS REQUIRED | ||||||
| 1 | Coordinator | TYPE 21A | ||||
| 1 | Overlapping Astragal with | R0Y634 x R0Y154 x THRU-BOLTS | ||||
| Self-Adhesive Seal | ||||||
| 2 | Closers | C02011/C02021 | ||||
| 2 | Kick Plates | J102 (@ STORAGE ROOMS ONLY) | ||||
| 2 | Floor Stops | L02121 x 3 FASTENERS | ||||
| 1 | Set Self-Adhesive Seals | R0Y154 | ||||
| 2 | Alarm Contacts |
120VAC POWER, CONDUIT, AND WIRING BY DIVISION 26.
CARD READER BY DIVISION 28.
HW-SH-9A
Each [PB] Pair to Have: RATED
| 2 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | ||||
| X ADJUSTA-SCREWS | ||||||
| 1 | Set Auto Flush Bolts | TYPE 25 | ||||
| 1 | Dust Proof Strike | L04021 | ||||
| 1 | Push-button Combination Lock | N3 – A156.13 F07 G1 E06 | ||||
| 1 | Coordinator | TYPE 21A | ||||
| 1 | Overlapping Astragal with | R0Y634 x R0Y154 x THRU-BOLTS | ||||
| Self-Adhesive Seal | ||||||
| 2 | Closers | C02011/C02021 | ||||
| 2 | Armor Plates | J101 x 1.275 MM (0.050 INCH) THICKNESS | ||||
| 2 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | ||||
| 2 | Floor Stops | L02121 x 3 FASTENERS | ||||
| 1 | Set Self-Adhesive Seals | R0Y154 |
MENTAL HEALTH AREAS
HW-MH2
Each Door to Have: NON-RATED
| 1 | Continuous Hinges | QUANTITY & TYPE AS REQUIRED x HOSPITAL | ||||
| TIP | ||||||
| 1 | Keyed Privacy Lock | F12-MOD x TURNPIECE BOTH SIDES x LESS | ||||
| TRIM | ||||||
| 1 | Set Anti-Ligature Trim | |||||
| 2 | Anti-Ligature Thumbturns | |||||
| 1 | Kick Plate | J102 | ||||
| 1 | Mop Plate (@ Inswing Doors) | J103 | ||||
| 1 | Floor Stop | L02121 x 3 FASTENERS | ||||
| 1 | Auto Door Bottom | R0Y346 – HEAVY DUTY | ||||
| 1 | Set Seals | R0Y164 |
PROVIDE SECURITY FASTENERS FOR ALL HARDWARE ITEMS.
STONE THRESHOLD BY OTHER TRADES.
HW-MH7
| Each Door to Have: | RATED/NON-RATED | |||||||
| Totals | Each | Assembly to have: | ||||||
| (1) | EA | HD CENTER PIVOT | 0370, SEC | 626 | ABH | |||
| (1) | EA | PASSAGE SET | L9010 03A | 630 | SCH | |||
| (2) | EA | ANTI LIGATURE PULLS | L9010-SL1 | |||||
| (1) | EA | ASTRAGAL | A635 84" | AL | NGP | |||
| (2) | EA | KICK PLATE | 8400 12" X 46 1/2" | 630 | IVE | |||
| (1) | EA | WALL STOP | WS406CVX | 630 | IVE | |||
| (1) | EA | EMERGENCY DOOR STOP | DS-6 (48” AFF) | 626 | MCK |
MORTISE LOCK WITH ASA STRIKE DOOR DOOR IS TO BE OFFSET HUNG TO EXAM ROOM SIDE.
A635 SIGHT SEAL INSTALLED ON LOCK EDGE ONLY - SQUARE EDGE WITH 1/4" DOOR-FRAME CLARANCE. TYPICAL 1/16" CLEARANCE ON PIVOT EDGE WITH 2" RADIUS - NO SIGHT SEAL REQUIRED.
DUE TO WEIGHT AND SIZE OF THIS DOOR, A HEAVY DUTY (ABH 0370) PIVOT SET (UP TO 500 lbs), WITH SECURITY FASTENERS (SEC) IS SCHEDULED HERE.
NO CLOSER REQUIRED AT RATED DOORS DUE TO EXEMPTION FOR PATIENT ROOM DOORS.
Hardware Set 176 1 Sliding Door System LR-SDS-9501 x FF US26D Accurate 1 Mortise Cylinder 30-016 626 Schlage 1 Anti-Ligature Collar 861B 26D ILCO 1 Permanent Core 23-030 x T 626 Schlag Hardware Set 176 1 Sliding Door System LR-SDS-9501 x FF US26D Accurate 1 Mortise Cylinder 30-016 626 Schlage 1 Anti-Ligature Collar 861B 26D ILCO 1 Permanent Core 23-030 x T 626 Schlag Hardware Set 176 1 Sliding Door System LR-SDS-9501 x FF US26D Accurate 1 Mortise Cylinder 30-016 626 Schlage 1 Anti-Ligature Collar 861B 26D ILCO 1 Permanent Core 23-030 x T 626 Schlage
HW-MH8
| Each Door to Have: | RATED/NON-RATED | ||||||
| Totals | Each | Assembly to have: | |||||
| (1) | EA | SLIDING DOOR SYSTEM | LR-SDS-9501xFF | 626 | ACCURATE | ||
| (1) | EA | MORTISE CYLINDER | 30-016 | 626 | SCH | ||
| (2) | EA | ANTI LIGATURE COLLAR | 861B | 26D | ILCO | ||
| (2) | EA | KICK PLATE | 8400 12" X 46 1/2" | 630 | IVE |
HW-MH9
| Each Door to Have: | RATED/NON-RATED | |||||||
| Totals | Each | Assembly to have: | ||||||
| (1) | EA | HD CENTER PIVOT | 0370, SEC | 626 | ABH | |||
| (1) | EA | KEYED PRIVACY INDICATOR LOCK F13 x OCCUPANCY INDICATOR | ||||||
| (2) | EA | ANTI LIGATURE PULLS | L9010-SL1 | |||||
| (1) | EA | ASTRAGAL | A635 84" | AL | NGP | |||
| (2) | EA | KICK PLATE | 8400 12" X 46 1/2" | 630 | IVE | |||
| (1) | EA | WALL STOP | WS406CVX | 630 | IVE | |||
| (1) | EA | EMERGENCY DOOR STOP | DS-6 (48” AFF) | 626 | MCK |
MORTISE LOCK WITH ASA STRIKE DOOR HAS BEEN SCHEDULED TO MATCH CROWN POINT VA FACILITY. DOOR IS TO BE OFFSET HUNG TO EXAM ROOM SIDE.
A635 SIGHT SEAL INSTALLED ON LOCK EDGE ONLY - SQUARE EDGE WITH 1/4" DOOR-FRAME CLARANCE. TYPICAL 1/16" CLEARANCE ON PIVOT EDGE WITH 2" RADIUS - NO SIGHT SEAL REQUIRED.
DUE TO WEIGHT AND SIZE OF THIS DOOR, A HEAVY DUTY (ABH 0370) PIVOT SET (UP TO 500 lbs), WITH SECURITY FASTENERS (SEC) IS SCHEDULED HERE
- E N D 08 71 00-1
File details come from the government source that posted it. Updated .