EJ200 - Addendum 1 Elec - 07.23.20.pdf
PDF 157 KB Posted
- Solicitation number
- 36C25220B0023
About this file
This document includes a partial power riser diagram and addendum for an emergency department renovation project at a Department of Veterans Affairs medical center. The project involves renovations to create a new emergency department observation unit, including demolition of existing electrical equipment and installation of new panels, breakers, feeders, and wiring to support equipment in the renovated space. Specific scope items include a new 225A emergency panel, 100A normal panel, feeders from 50-800A, and demolition of designated existing infrastructure. The project is a firm-fixed price contract to be awarded under solicitation number 36C25220B0023 by the VA Great Lakes Acquisition Center.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EMERGENCY UNIT SUBSTATION
FROM GEN H.V.
SUBSTATION 4160V
3 33∅
2000A FR
2000A TR
2000A BUS
480Y/277V
4160V
BRANCH
SERVING
THIS
BUILDING
BP
NE
L
BPBP
NE
L
BPBP
NE
L
BP
1600A FR
1200A TR
800A FR
175A TR
800A FR
800A TR
STUB TO NEAR DIST EQUIP (TYP)
LP-1-1
LP-3-1
LP-5-1
LP-7-1
LP-9-1
H-DP-3-1
H-DP-6-1
H-DP-9-1
H-DP-R-1
H-DP-1-1
LDP-1-1
H-EDP-2-2
H-EDP-5-1
H-EDP-8-1
H-EDP-12-1
EDP-2-1
M A
IN
LSDP-2-1
CP-1-1
CP-3-1
CDP-2-1
CP-5-1
CP-7-1
CP-9-1
ATS-3 ATS-2 ATS-1
T-3
T-2
DS-2
DS-1
112.5 KVA
500 KVA
TRANSFER S3ITCH ROOM
NORMAL UNIT SUBSTATION
2ND FLOOR
1ST FLOOR
T-1
750 KVA
2ND FLOOR
3RD FLOOR
4TH FLOOR
5TH FLOOR
6TH FLOOR
7TH FLOOR
8TH FLOOR
9TH FLOOR
10TH FLOOR
ROOF
FROM
H-DP-1-1
FROM
EDP-2-1
CDP-2-1 1ST FLOOR
2000 KVA OA
2300 KVA FA
4160VD - 480Y/277V
FROM NORMAL H.V.
SUBSTATION 4160V
3 33∅
1200A-4P 200A -3P 800A-3P
1200A MLO, 480Y/277V
2500A MCB 3/O GFI, 208Y/120V
800A
(TYP.)
400A
(TYP.)
200A
800A800A
(TYP.)
1600A MCB 3/O GFI, 208Y/120V, 65K AIC
400A MCB 3/O GFI, 208Y/120V, 65K AIC
1200A MLO, 480Y/277V, 65K AIC
400A
(TYP.)
LA
FROM
65K AIC
65K AIC
M A
IN
1200A
FR
3200A FR
3200A TR GFI
3200A BUS
480Y/277V
1200A
FR
CONTROL
CUBE
MAIN
1200A
FR
50/51
50/51
MAIN
1600A FR
1200A TR/GFI
800A FR
175A TR
800A FR
800A TR
1600A FR
1200A TR/GFI
1600A FR
1200A TR/GFI
1600A FR
SPACE
1600A FR
SPACE
1600A FR
SPACE
480V 65KAIC 480V 65KAIC 480V 65KAIC
M A
IN
800A FEED
THROUGH
208Y/120V, 50K AIC
800A FEED
THROUGH
208Y/120V, 50K AIC
800A MLO
208Y/120V, 50K AIC
800A MLO
208Y/120V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A MLO
480Y/277V, 50K AIC
ST
U
B T
O N
EA
R D
IS
T E
Q U
IP
BLDG C1
225A 208Y/120V, 50K AIC
1/4"x4"X18" CU
GROUNDING BAR
ON STANDOFFS IN
NEMA 1
ENCLOSURE
1#500 CU
INSULATED IN
1-1/2" C
EXOTHERMIC
3ELDS TYP
1#500 CU
INSULATED IN
1-1/2" C
1#500 CU
INSULATED IN
1-1/2" C
1#500 CU
INSULATED IN
1-1/2" C
1#500 CU
INSULATED IN
1-1/2" C
1#500 CU
INSULATED IN
1-1/2" C
1#500 CU
INSULATED IN
1-1/2" C
1#500 CU
INSULATED IN
1-1/2" C
1#500 CU
INSULATED IN
1-1/2" C
1#500 CU
INSULATED IN
1-1/2" C
1#500 CU
INSULATED IN
1-1/2" C TO THE
MAIN GROUNDING
BAR IN BLD 1C
225A MLO
480Y/277V, 50K AIC
100A MLO
208Y/120V, 50K AIC
100A MLO
208Y/120V, 50K AIC
225A
100A
225A
100A
(4) 100-3P
AND (12)
20A-1P CBS.
GENERATORS
LOCATED IN BUILDING 42.
EXISTING NORMAL S3ITCHGEAR
4160V
NOTE 22
LOCATED ON THE FIRST
FLOOR OF BUILDING 1C
50/51
800A FEED
THROUGH
208Y/120V, 50K AIC
800A FEED
THROUGH
208Y/120V, 50K AIC
800A MLO
208Y/120V, 50K AIC
800A MLO
208Y/120V, 50K AIC
800A FEED
THROUGH
208Y/120V, 50K AIC
800A FEED
THROUGH
208Y/120V, 50K AIC
800A MLO
208Y/120V, 50K AIC
800A MLO
208Y/120V, 50K AIC
800A FEED
THROUGH
208Y/120V, 50K AIC
800A FEED
THROUGH
208Y/120V, 50K AIC
800A MLO
208Y/120V, 50K AIC
800A MLO
208Y/120V, 50K AIC
800A FEED
THROUGH
208Y/120V, 50K AIC
800A FEED
THROUGH
208Y/120V, 50K AIC
800A MLO
208Y/120V, 50K AIC
800A MLO
208Y/120V, 50K AIC
400A MLO
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A MLO
480Y/277V, 50K AIC
400A MLO
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A MLO
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A MLO
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
400A FEED
THROUGH
480Y/277V, 50K AIC
FROM
LDP-1-1
CLP-C1
LP-C1
H-DP-C1
H-EDP-C1
H-EDP-1-1
H-EDP-3-1
H-EDP-4-1
H-EDP-6-1
H-EDP-7-1
H-EDP-9-1
H-EDP-10-1
H-DP-2-1
H-DP-4-1
H-DP-2-1
H-DP-5-1
H-DP-7-1
H-DP-8-1
H-DP-10-1
H-EDP-R-1
H-EDP-8-1
H-EDP-5-1
H-EDP-2-1
CLP-10-1
CLP-9-1
CLP-8-1
CLP-7-1
CLP-6-1
CLP-5-1
CLP-4-1
CLP-3-1
CLP-2-1
CLP-1-1
LP-10-1
LP-9-1
LP-8-1
LP-7-1
LP-1-1
H-DP-R-1
H-DP-6-1
H-DP-3-1
H-DP-9-1
LP-6-1
LP-5-1
LP-4-1
LP-3-1
LP-2-1
208Y/120V/3Φ/4W
GECP
225A
EMERGENCY
CRITICAL
NEW PANEL
480Y/277V/3Φ/4W
GEQP
100A
EMERGENCY
EQUIPMENT
NEW PANEL
RISER LINE LEGEND:
NE3 CONSTRUCTION
EXISTING TO REMAIN
XXX
XXX
A 1 2 1B
A
ALL EQUIPMENT IS EXISTING TO REMAIN, EXCEPT 3HERE NOTED OTHER3ISE.
NEW FEEDER NOTES:
A. PROVIDE (4) #4/0 A3G AND (1) #2 A3G GND IN 3" C.
B. PROVIDE (4) #1 A3G AND (1) #6 A3G GND IN 2" C.
RISER TAGGED NOTES:
1. PROVIDE NE3 225A TRIP RATING PLUG IN EXISTING 250A
GE SPECTRA SERIES CIRCUIT BREAKER. TRIP RATING
PLUG TO BE GE #GTP0225U0306.
2. PROVIDE NE3 3P, 100A CIRCUIT BREAKER IN AVAILABLE
SPACE IN EXISTING GE SPECTRA SERIES DISTRIBUTION
PANELBOARD. CIRCUIT BREAKER TO BE GE LSI
ELECTRONIC TRIP 3ITH 65KA INTERRUPTING RATING.
50 KAIC 50 KAIC
208Y/120V/3Φ/4W
GP
225A
NORMAL
NEW PANEL
50 KAIC
QBA
EXIST. PANEL
BASEMENT- BUILDING 1A
FIRST FLOOR
QBA-2
PANEL
3P, 100A
3P, 50A
3P, 20A
VFD-B
7.5 HP
7.5 HP
SUPPLY
FAN
3 HP
RETURN
FAN
VFD-A
3 HP
C
E
EXISTING RISER LINE LEGEND:
TO BE DEMOLISHED
EXISTING TO REMAIN
XXX
XXX
EXISTING FEEDER NOTES:
C. DEMOLISH (4) #1 A3G AND (1) #8 A3G GND IN 1-1/2" C.
D. DEMOLISH (3) #6 A3G AND (1) #10 A3G GND IN 1" C.
E. DEMOLISH (3) #12 A3G AND (1) #12 A3G GND IN 3/4" C.
EXISTING RISER TAGGED NOTES:
3. EQUIPMENT INDICATED TO BE DEMOLISHED. ALL 3IRING,
CONDUIT AND ASSOCIATED MOUNTING HARD3ARE SHALL
BE COMPLETELY REMOVED BACK TO ELECTRICAL PANEL.
4. PROVIDE LABELING FOR EXISTING 3P, 100A CIRCUIT
BREAKER TO READ "SPARE".
D
3 3
I LL IN O IS
S N
A H
A
TR
E B
O R
NTHONY
LICENSED
PROFESSIONAL
OF
ENGINEER
062.059710
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
100% RE-SUBMIT 2020/06/29
Revisions: Date:
C U s e rs
\s m o o re
\D o c u m e n ts
\R
I V
C E
E
L E
C T
R
IC
A L s m o o re Q
F A
.r v t
/2
/2
:3
:4
P
M
EJ200
POWER RISER DIAGRAM
GUIDON-CMTA SDVOSB JV, LLC
1221 N. PENNSYLVANIA ST. SUITE 200
INDIANAPOLIS, IN 46202
CMTA CONSULTING ENGINEERS
903 SPRING ST.
JEFFERSONVILLE, IN 47130
EMERGENCY DEPARTMENT
RENOVATION
820 S. DAMEN AVE.
537-15-160
5/30/2020 CMTA CMTA
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
NO SCALEEJ200
1 PARTIAL POWER RISER DIAGRAM
Addendum No. 1 2020/07/23
NO SCALEEJ200
2 PARTIAL EXISTING RISER DIAGRAM
| Sheets |
| ED201 - PARTIAL FIRST FLOOR PLAN - POWER DEMOLITION |
| EJ200 - POWER RISER DIAGRAM |
File details come from the government source that posted it. Updated .