About this file

This file contains construction specifications for integrated door assemblies for an emergency department renovation project. The project scope includes providing all tools, materials, labor and supervision to construct and renovate an emergency department observation unit at the Jesse Brown VA Medical Center in Chicago, Illinois. The specifications cover metal doors, frames, continuous hinges, exit devices, hardware finishes, installation requirements and door schedules. Integrated door assemblies must meet fire resistance, smoke resistance and cycle testing standards. Recycled steel content and low VOC emission levels are required.

View the file

Other files

File Type Posted
AE Responses 537-15-160 Consolidated RFI Amendment 6.xlsx XLSX spreadsheet
36C25220B0023 0006.docx DOCX document
537-15-160 SOW - Mod2.docx DOCX document
IFB Bid opening invitation changed to 10SEP.pdf PDF
36C25220B0023 0005.docx DOCX document
AE Responses 537-15-160 Consolidated RFI Amendment 4.pdf PDF
085113 - Psychiatric windows.docx DOCX document
36C25220B0023 0004.docx DOCX document
087100 - Door Hardware.docx DOCX document
Basement sketch Question 64.png PNG image
024100 - Demolition.pdf PDF
SIGNED Brand Name J and A.pdf PDF
36C25220B0023 0003.docx DOCX document
262416 - Panels.pdf PDF
264313 - Surge Protective Devices.pdf PDF
537-15-160 Consolidated RFI-ADD1.pdf PDF
Bid opening change to 10 AUG Meeting Invitation.pdf PDF
260573 - OCP Device Coordination Study.pdf PDF
C03 36C25220B0023 0002.docx DOCX document
EJ200 - Addendum 1 Elec - 07.23.20.pdf PDF
RFI-001_Guidon Addendum 1.pdf PDF
000100 - Specification Table of Contents.pdf PDF
537-15-160 SOW - Mod1.pdf PDF
ED201 - Addendum 1 Elec - 07.23.20.pdf PDF
36C25220B0023 A0001.docx DOCX document
ATCH 2 537-15-160 sign in sheets 8-9 jul 2020.pdf PDF
ATCH 1 537-15-160 Construction Bid Opening Meeting.pdf PDF
537-15-160 Construction Drawings 1 of 4.pdf PDF
537-15-160 Construction Drawings 3 of 4.pdf PDF
537-15-160 Construction Drawings 2 of 4.pdf PDF
S02 36C25220B0023_2_7-1-2020.docx DOCX document
537-15-160 Construction Drawings 4 of 4.pdf PDF
537-15-160 Project Manual Vol2.pdf PDF
537-15-160 Project Manual Vol1.pdf PDF
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Jesse Brown VAMC VA: 537-15-160 Emergency Department Renovations Chicago, IL 60612 9-1-13 100% Construction Documents May 30, 2020 Revised August 18, 2020

SECTION 08 17 10

INTEGRATED DOOR ASSEMBLIES

GENERAL

SUMMARY

Section Includes:

Integrated door assemblies including metal door frame, door, and hardware, unless specified in another Section, installed at crosscorridor locations.

Smoke and draft control seals, unless specified in another Section.

RELATED REQUIREMENTS

NonFlooring Adhesives and Sealants and Paints and Coatings VOC Limits: Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS.

Lock Cylinders: Section 08 71 00, DOOR HARDWARE.

Automatic Door Operators: Section 08 71 13, AUTOMATIC DOOR OPERATORS.

Electrical Power: DIVISION 26, ELECTRICAL.

APPLICABLE PUBLICATIONS

Comply with references to extent specified in this section.

Builders Hardware Manufacturers Association (BHMA):

A156.314 - Exit Devices.

A156.2606 - Continuous Hinges.

A156.3214 - Integrated Door Opening Assemblies.

ASTM International (ASTM):

A1011/A1011M14 - Steel, Sheet and Strip, HotRolled, Carbon, Structural, HighStrength LowAlloy, HighStrength LowAlloy with Improved Formability, and UltraHigh Strength.

E218007(2012) - Determining the Activity of Incorporated Antimicrobial Agents in Polymeric or Hydrophobic Materials.

Door and Hardware Institute (DHI):

Recommended Locations for Architectural Hardware for Standard Doors & Frames (2004).

Recommended Locations for Builders' Hardware Custom Steel Doors & Frames (1996).

National Fire Protection Association (NFPA):

10516 - Smoke Door Assemblies and Other Opening Protectives.

25212 - Fire Tests of Door Assemblies.

Steel Door Institute (SDI):

A250.311 - Test Procedure and Acceptance Criteria for Factory Applied Finish Coatings for Steel Doors and Frames.

A250.814 - Specifications for Standard Steel Doors and Frames.

A250.1011 - Test Procedure and Acceptance Criteria for Prime Painted Steel Surfaces for Steel Doors and Frames.

UL LLC (UL):

10C09 - Positive Pressure Fire Tests of Door Assemblies.

178415 - Air Leakage Tests of Door Assemblies and Other Opening Protectives.

PREINSTALLATION MEETINGS

Conduct preinstallation meeting at project site minimum 30 days before beginning Work of this section.

Required Participants:

Contracting Officer's Representative.

Architect/Engineer.

Contractor.

Installer.

Other installers responsible for adjacent and intersecting work, including electrical.

Meeting Agenda: Distribute agenda to participants minimum 3 days before meeting.

Installation schedule.

Installation sequence.

Preparatory work.

Protection before, during, and after installation.

Installation.

Transitions and connections to other work.

Other items affecting successful completion.

Document and distribute meeting minutes to participants to record decisions affecting installation.

SUBMITTALS

Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

Submittal Drawings:

Show size, configuration, and fabrication and installation details.

For each opening, list finish hardware items included in assembly, finish, degree of opening, and electrical roughin requirements according to Door Schedule.

Submit templates to door and frame manufacturers to ensure proper size and location of hardware.

Manufacturer's Literature and Data:

Description of each product.

Installation instructions.

Sustainable Construction Submittals:

Recycled Content: Identify postconsumer and preconsumer recycled content percentage by weight.

Low PollutantEmitting Materials:

Show volatile organic compound types and quantities.

Certificates: Indicate integrated door assemblies comply with specifications.

Show fire rated integrated door assembly is UL Listed for specified application.

Qualifications: Substantiate qualifications comply with specifications.

Installer.

Operation and Maintenance Data:

Care instructions for each exposed finish product.

Maintenance and adjustment instructions for integrated door assemblies.

QUALITY ASSURANCE

Installer Qualifications:

Regularly installs specified products.

Installed specified products with satisfactory service on five similar installations for minimum five years.

Provide contact names and addresses for completed projects when requested by Contracting Officer's Representative.

DELIVERY

Deliver products in manufacturer's original sealed packaging.

Mark packaging, legibly. Indicate manufacturer's name.

Before installation, return or dispose of products within distorted, damaged, or opened packaging.

STORAGE AND HANDLING

Store products indoors in dry, weathertight facility.

Protect products from damage during handling and construction operations.

FIELD CONDITIONS

Field Measurements: Verify field conditions affecting integrated door assembly fabrication and installation. Show field measurements on Submittal Drawings.

Coordinate field measurement and fabrication schedule to avoid delay.

Coordinate electrical work for electrified hardware installation.

WARRANTY

Construction Warranty: FAR clause 52.24621, "Warranty of Construction."

Manufacturer's Warranty: Warrant door closers and hinges against material and manufacturing defects.

Warranty Periods:

Door Closers: 10 years.

Steel Pinned Continuous Hinges: 10 years.

PRODUCTS

SYSTEM PERFORMANCE

Design integrated door assemblies complying with specified performance:

BHMA A156.32: Grade 1: 1,000,000 cycles.

Fire Rated Doors:

Fire Resistance Rating: As shown in Door Schedule.

Label: Comply with NFPA 252, UL 10C, and labeled by qualified testing and inspection agency showing fire resistance rating.

Smoke Rated Doors:

Smoke Resistance Rating: As shown in Door Schedule.

Label: Comply with NFPA 105, UL 1784, and labeled by qualified testing and inspection agency showing smoke resistance rating.

PRODUCTS - GENERAL

Provide each integrated door assembly from one manufacturer.

Sustainable Construction Requirements:

Steel Recycled Content: 30 percent total recycled content, minimum.

Low PollutantEmitting Materials: Comply with VOC limits specified in Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS for the following products:

Nonflooring adhesives and sealants.

Paints and coatings.

INTEGRATED DOOR ASSEMBLY

Metal Doors: SDI A250.8; Level 2 and Physical Performance Level B, heavy duty; Model 2 seamless.

Face: ASTM A1011/A1011M; cold rolled steel, 1.0 mm (0.04 inches) thick, minimum.

Core: Kraft paper honeycomb or polystyrene.

Thickness: 44 mm (13/4 inch).

Reinforce door for hardware installation.

Metal Frames: SDI A250.8 Level 2.

Metal: ASTM A1011/A1011M; cold rolled steel, 1.3 mm (0.05 inches) thick, minimum.

Construction: Continuously welded.

Reinforce frame for hardware.

Continuous Hinges: 2.3 mm (0.09 inches) thick.

Other Hardware: Comply with SDI A250.8.

Frame Anchors: Provide adjustable type anchors coordinated with wall construction, minimum 4 per jamb.

Integrated Hardware:

Exit Device: BHMA A156.3; Grade 1, passage function, inset in door face, clean and unobtrusive in design.

Push Bar End Caps: Metal, plated satin nickel (BHMA 619) finish.

Exit Device Trim: Lever matching door hardware specified in Section 08 71 00, DOOR HARDWARE.

Continuous Hinges: BHMA A156.26.

Plastic Laminate Clad Doors: Wraparound style hinge guards and provide stainless steel wraparound edge guards at strike edge of door.

Other Hardware: As scheduled in this section.

FINISHES

Hardware Finish Symbols:

Table 1 Hardware Finish Symbols

US26D
626/652
Satin Chrome Plated

Finish Requirements:

Door Faces: Prime painted, SDI A250.10 Frames: Prime painted, SDI A250.10.

Door Hardware:

Continuous Hinges: BHMA 630.

Push Bar: BHMA 630 clad with BHMA 619 end caps.

Exit Device Trim: BHMA 630.

Push/Pull Trim: BHMA 626.

Door Closers: BHMA 689.

Miscellaneous: To match other finishes.

AntiMicrobial Coating: ASTM E2180; ionic silver coating.

Apply coating to handoperated hardware including levers, pulls, push bars, push plates, and paddles.

EXECUTION

PREPARATION

Examine and verify substrate suitability for product installation.

Protect existing construction and completed work from damage.

INSTALLATION - INTEGRATED DOOR ASSEMBLIES

Install products according to manufacturer's instructions and approved submittal drawings.

Install door hardware at locations indicated in DHI Recommended Locations for Architectural Hardware for Standard Steel Doors & Frames and DHI Recommended Locations for Builders' Hardware Custom Steel Doors & Frames, unless otherwise indicated, or to comply with requirements of governing regulations, or if otherwise directed by Contracting Officer's Representative.

Install door hardware in compliance with manufacturers' instructions, and templates. Comply with specified degree of opening for doors with automatic operators and overhead door closers. Securely fasten hardware. Confirm operating parts move freely and smoothly without binding, sticking, and excessive clearance.

Coordinate installation and interface wiring with fire alarm and smoke detection systems. Provide auxiliary contacts, relays, and interface for fire alarm and security systems.

Remove or protect door hardware, before painting and finishing performed after integrated door assembly installation.

Adjust and check door assembly and each operating hardware item to ensure correct operation and function. Replace products which cannot be adjusted to operate as intended.

Final Adjustment: Perform final hardware check and adjustment maximum one month before building acceptance or partial building occupancy.

CLEANING

Clean exposed surfaces, including hardware. Do not use cleaners that will harm finishes.

PROTECTION

Protect integrated door assemblies from construction operations.

SCHEDULES

The following is a general listing of the Integrated Door Assembly requirements and is not intended for use as a final door submittal. Provide hardware items required by established standards and practices, and to meet IBC and NFPA 101 whether specified or not in the following listed groups.

HWSH4

Each [AC, EL, REX, DPS]Integrated Door to Have:
RATED

1 Steel Frame

1 Integrated Door w/Elec. Exit Device Q2131 x TYPE 8 ELECTRIC DEVICE (E01, E05/E06VERIFY)x F13 LEVER

1Continuous Transfer Hinge
A51031B x 4THRUWIRE TRANSFER x INHINGE ACCESS PANEL
1Power Supply
REGULATED, FILTERED, 24VDC, AMPERAGE

AS REQUIRED

1Closer
C02021 (PT4D, PT4F, PT4H)
1Armor Plate
J101 x 1.275 mm (0.050 inch) THICKNESS
1Floor Stop
L02121 x 3 FASTENERS
1Set SelfAdhesive Seals
R0E154

1 Alarm Contact

120VAC POWER, CONDUIT, AND WIRING BY DIVISION 26.

CARD READER BY DIVISION 28.

LOCK CYLINDER BY SECTION 08 71 00, DOOR HARDWARE.

HW-SH-9

Each [AC, EL, REX, DPS] Pair to Have: RATED

HingesQUANTITY & TYPE AS REQUIRED
1Transfer Hinge4-WIRE TYPE AS REQUIRED
1Set Auto Flush BoltsTYPE 25
1Dust Proof StrikeL04021
1Electrified LockF07 (E01-REX, E06) 24VDC
1Power SupplyREGULATED, FILTERED, 24VDC, AMPERAGE
AS REQUIRED
1CoordinatorTYPE 21A
1Overlapping Astragal withR0Y634 x R0Y154 x THRU-BOLTS
Self-Adhesive Seal
2ClosersC02011/C02021
2Kick PlatesJ102 (@ STORAGE ROOMS ONLY)
2Floor StopsL02121 x 3 FASTENERS
1Set Self-Adhesive SealsR0Y154
2Alarm Contacts

120VAC POWER, CONDUIT, AND WIRING BY DIVISION 26.

CARD READER BY DIVISION 28.

- E N D -