36E77620R0001-010.pdf
PDF Posted
- Solicitation number
- 36E77620R0001
About this file
This document provides details for a federal construction contract opportunity for a new mental health building project. The Department of Veterans Affairs will solicit bids and award a firm-fixed-price contract for design-bid-build construction services located at 830 Chalkstone Ave in Providence, Rhode Island. The project scope includes site preparation, demolition, and construction of a three-story, approximately 15,300 square foot freestanding building to provide new mental health program area. Corresponding site and utility work is also required. The solicitation will be a request for proposal conducted in accordance with FAR Parts 15, 19, and 36 and evaluated using procedures in the solicitation. The opportunity is set aside as a total Service-Disabled Veteran-Owned Small Business set-aside. The NAICS code is 236220 with a size standard of $36.5 million. The solicitation will issue on or around December 20, 2019 with a period of performance of approximately 600 calendar days from notice to proceed. The magnitude of construction is estimated between $10-20 million. Questions must be submitted in writing by email no later than the date specified in the solicitation.
36E77620R0001 Attachment 9 - CD Drawings - LS.pdf
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
R E
F
REF.
UP
IBC Building “Use” Groups Business (B)
NFPA 101 Building Occupancies Business
Building height 3 Stories
Number of stories below grade 0
Footprint (Approximately) 6,350 ft2
Construction Type II-B [IBC], II (000) [NFPA]
Site access Regent Avenue
Suppression System Fully sprinklered; NFPA-13 2016 compliant
Fire Alarm System Addressable; NPPA-72 2016 compliant
Floor Egress Capacity
Basement Stair 1 Stair 2
Door – 34”/0.2 = 170 persons
Door – 34”/0.2 = 170 persons
Stair – 44”/0.3 = 146 persons
Stair – 44”/0.3 = 146 persons
Total = 292
Level 1 Main Entrance Stair 2
Door – 41”/0.2 = 205 persons
Door – 34”/0.2 = 170 persons
Total = 375
Level 2 Stair 1
Door – 34”/0.2 = 170 persons
Stair – 44”/0.3 = 146 persons
Total = 146
IBC Table 601: Rating
Primary Structural Frame 0 hours
Exterior Bearing Walls 0 hours
Interior Bearing Walls 0 hours
Exterior Nonbearing Walls (IBC Table 602)
FSD < 10 feet 1 hour
FSD > 30 feet 0 hours
Floor construction and secondary members 0 hours
Roof construction and secondary members 0 hours
NFPA 101 Table 8.3.4.2: Rating Fire Door
Exit Stairs 1 hour 1 hour
Shafts 1 hour 1 hour
Elevator Shaft 1 hour 1 hour
Other fire barriers 1 hour ¾ hour
IBC Section Building Height Building Area (ft2)
Table 503 3 Stories (55 feet) 23,000
Section 504.2: Automatic Sprinkler Height Increase 1 Story (20 feet) N/A
Section 506.2: Open Frontage Area Increase (76% Open) N/A 11,730
Section 506.3: Automatic Sprinkler Area Increase N/A 46,000
Maximum Permitted per IBC 4 Stories (75 feet) 80,730
Actual Height and Area 3 Stories A 6,350
Occupancy Maximum Dead-end Corridor
(ft)
Maximum Common Path of Travel
(ft)
Maximum Travel Distance
(ft)
Business 50 100 300
Floor Use Area (ft2) Occupant Load Factor
(ft2/person)
Occupants
Basement Business 4,238 100 gross 43
Waiting / Lounge 481 15 net 33
Classrooms 890 20 net 45*
Occupational Therapy 473 100 gross 5
Storage / Mechanical 268 500 gross 1
Total 127
Level 1 Business 5,156 100 gross 52
Waiting / Meeting
Room
467 15 net 32
Storage / Mechanical 240 500 gross 1
Computer Lab 487 50 net 10
Total 95
Level 2 Mechanical 1,250 500 gross 3
Total 3
*Maximum occupancy sign of 49 people to be posted
Path 1
Path 1
Path 2
Exit Capacity: 146
Exit Capacity: 146
A
B
C
D
E
F
G
765431 2
STAIR 1
ELEV 1
WATER SERVICE
CLASSROOM
STORAGE
027A
ELEV. CONTROL
ROOM
TOILET
TOILET
HAC
CORRIDOR
OFFICE
OFFICE
OT OFFICE
OCCUPATIONAL
THERAPY ROOM
OFFICE
ELECTRICAL
TELE/ DATA
ELEVATOR LOBBY
CONSULT ROOM -
EXTRA
CONSULT ROOM
CONSULT ROOM
CLASSROOM
STAFF LOUNGE
STAIR 2
STAFF TOILET
CORRIDOR
EMERG. ELECT.
018AWAITING
PRRC CUBES
CLASSROOM
STAFF TOILET
E.5
E.9
8.7
STORAGE
CLASSROOM
STORAGE
027B
F.E. F.E.
F.E.
F.E.
Dead End: 29' - 6"
D e a d E n d
/8
BUILDING INFORMATION
HEIGHT AND AREA
REQUIRED FIRE RESISTANCE RATING
ALLOWABLE TRAVEL DISTANCES
EGRESS CAPACITY
OCCUPANT LOADING
1HR FIRE SEPARATION
EGRESS PATH
LEGEND
FIRE EXTINGUISHERF.E.
1HR RATED CEILING ASSEMBLY SUPPORTED BY 1HR CONSTRUCTION
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
CONSULTANT ARCHITECT/ENGINEER OF RECORD
WBRC
A R C H I T E C T S • E N G I N E E R S
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title
Approved:
Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
TRUE NORTH
PROJECT NORTH
/1
/2
:5
:0
A
M M
F ir e
P ro te c ti o n
W
B R
C P ro v id e n c e
M e n ta l H e a lt h
\A u to C
A D
\C o n c e p ts
\W B
R C
V A
D D
.r v t
LS-101
650-332
NEW MENTAL HEALTH BUILDING -
PHASE 1
830 CHALKSTONE AVE PROVIDENCE, RI 02908
TGS GVR10 APR 2019
CONSTRUCTION
DOCUMENTS
BASEMENT LIFE SAFETY PLAN
AND ANALYSISSFC Engineering
1 Industrial Drive Windham, NH, 03087 603-647-8700
Fire Protection Engineering:
FULLY SPRINKLERED
VA RI FACILITIES MANAGEMENT
SERVICE
1/8" = 1'-0"
BASEMENT LIFE SAFETY PLAN
Travel Distances
Travel Path Travel Distance
Path 1 86' - 6"
Path 2 137' - 2"
Path 3 120' - 0"
Path 4 126' - 0"
Path 5 114' - 4"
Second 146 Persons
First 375 Persons
Basement 292 Persons
Floor Egress Capacity
Revisions: Date:
UP
UP
G-2
G-2
A1 AG-3 12
Path 4
Path 3
Exit Capacity: 205
Exit Capacity: 170
A
B
C
D
E
F
G
765431 2
TLT
TLT
TLT
HAC
CORRIDOR
100A
CORRIDOR
100B
VESTIBULE
COMMUNICATION
CENTER
RC CUBES
MEDICATION ROOM
CUBICLES
INJECTION ROOM
OFFICE
OFFICE
CONSULT ROOM
CONSULT ROOM
CONSULT ROOM
STAIR 2
COMPUTER LAB
SECURITY / WC
STORAGE
101A
WAITING
CONSULT ROOM
CONSULT ROOM -
EXTRA
CONSULT ROOM
STORAGE
OFFICE
OFFICE
TOILET
STAIR 1
ELEV 1
E.5
E.9
8.7
MAIN ELECTRICAL
ROOM
MEETING ROOM
F.E.
F.E.
F.E.
Dead End: 17' - 1"
D e a d E n d
/8
Fire Department Connection
Path 5
Exit Capacity: 146
A
B
C
D
E
F
G
765431 2
E.5
E.9
8.7
STAIR 1
ELEV 1
MECHANICAL ROOM
CIRCULATION
F.E.
F.E.
1HR FIRE SEPARATION
EGRESS PATH
LEGEND
1HR SLAB SUPPORTED BY 1HR FIREPROOFED CONSTRUCTION
FIRE EXTINGUISHERF.E.
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
CONSULTANT ARCHITECT/ENGINEER OF RECORD
WBRC
A R C H I T E C T S • E N G I N E E R S
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title
Approved:
Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
TRUE NORTH
PROJECT NORTH
/1
/2
:5
:0
A
M M
F ir e
P ro te c ti o n
W
B R
C P ro v id e n c e
M e n ta l H e a lt h
\A u to C
A D
\C o n c e p ts
\W B
R C
V A
D D
.r v t
LS-102
650-332
NEW MENTAL HEALTH BUILDING -
PHASE 1
830 CHALKSTONE AVE PROVIDENCE, RI 02908
TGS GVR10 APR 2019
CONSTRUCTION
DOCUMENTS
FIRST AND SECOND FLOOR LIFE
SAFETY PLANSSFC Engineering
1 Industrial Drive Windham, NH, 03087 603-647-8700
Fire Protection Engineering:
FULLY SPRINKLERED
VA RI FACILITIES MANAGEMENT
SERVICE
1/8" = 1'-0"
FIRST FLOOR LIFE SAFETY PLAN
1/8" = 1'-0"
SECOND FLOOR LIFE SAFETY PLAN
Travel Distances
Travel Path Travel Distance
Path 1 86' - 6"
Path 2 137' - 2"
Path 3 120' - 0"
Path 4 126' - 0"
Path 5 114' - 4"
Second 146 Persons
First 375 Persons
Basement 292 Persons
Floor Egress Capacity
Revisions: Date:
| Sheets |
| LS-101 - BASEMENT LIFE SAFETY PLAN AND ANALYSIS |
| LS-102 - FIRST AND SECOND FLOOR LIFE SAFETY PLANS |
File details come from the government source that posted it. Updated .