This notice provides details for an upcoming solicitation to construct a new mental health building at the Providence VA Medical Center in Rhode Island. The Department of Veterans Affairs will issue a request for proposal on or about December 20, 2019 seeking a single firm-fixed-price contract for construction of the approximately $10-20 million project. Work includes general construction, site preparation, demolition, utilities and construction of a three-story, 15,300 square foot freestanding building to house mental health programs. The performance period is approximately 600 calendar days from notice to proceed. The solicitation will be set aside solely for Service-Disabled Veteran-Owned Small Businesses.
36E77620R0001 Attachment 8 - CD Drawings - HVAC.pdf
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CONTROL LEGEND
EQUIPMENT TAGS
ABBREVIATIONSDRAWING NOTESDUCTWORK LEGEND
AIR DEVICE LEGEND
VALVE LEGEND
PIPING LEGEND
DAMPERS
GENERAL NOTES
MECHANICAL DRAWING LIST
2. THE CONTRACTOR SHALL VISIT AND CAREFULLY EXAMINE THE SITE TO IDENTIFY EXISTING CONDITIONS AND DIFFICULTIES THAT WILL AFFECT THE WORK OF THIS SECTION. REPORT IN WRITING TO THE ARCHITECT CONDITIONS WHICH MIGHT ADVERSELY AFFECT WORK. NO EXTRA PAYMENT WILL BE PROVIDED FOR ADDITIONAL WORK CAUSED BY UNFAMILIARITY WITH SITE CONDITIONS THAT ARE VISIBLE OR READILY CONSTRUED BY AN EXPERIENCED
OBSERVER.
4. REFER TO ARCHITECTURAL PLANS FOR EXACT LOCATION OF CEILING GRID, DIFFUSERS, AND GRILLES.
5. ALL INSTALLATIONS SHALL PERMIT AND PROVIDE ACCESSIBILITY FOR SERVICE AND REPLACEMENT OF ALL NEW
EQUIPMENT AND EXISTING EQUIPMENT IMPACTED BY THIS WORK.
6. COORDINATE ALL OPENINGS IN FLOORS WITH STRUCTURAL DRAWINGS AND GENERAL CONTRACTOR.
7. COORDINATE ALL ROOF OPENINGS WITH ARCHITECT AND STRUCTURAL ENGINEER.
8. REFER TO STRUCTURAL FRAMING PLANS FOR EXACT LOCATION OF ALL ROOF MOUNTED EQUIPMENT.
9. ALL MECHANICAL EQUIPMENT, PIPING, AND DUCTWORK SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF GOVERNING LOCAL, STATE, AND FEDERAL SEISMIC CODES. PARTICULAR ATTENTION SHALL BE
MADE TO VIBRATION ISOLATION, ANCHORING, AND BALANCING REQUIREMENTS.
11. ALL DUCTWORK SHALL BE INSTALLED IN ACCORDANCE WITH CODES AND STANDARDS SET FORTH IN NFPA, SMACNA, AND ASHRAE FOR LOW PRESSURE DUCTWORK SYSTEMS.
12. ALL EXPOSED DUCTWORK SHALL BE PAINTED TO MATCH CEILING. REFER TO ARCHITECTURAL DRAWINGS.
13. PROVIDE MANUAL VOLUME DAMPERS AT ALL BRANCH DUCTS FOR AIR BALANCING.
14. ALL SHEET METAL PLENUMS AT OUTSIDE AIR LOUVERS SHALL BE INSULATED WITH RIGID INSULATION, AS PER
SPECIFICATIONS.
15. RUN-OUTS TO RETURN AND EXHAUST REGISTERS, OR GRILLES ABOVE GYP BOARD CEILINGS, SHALL BE RIGID
DUCTED. NO FLEXIBLE DUCT WORK SHALL BE ALLOWED ON RETURN OR EXHAUST REGISTERS.
16. ALL DUCTS, PIPES, AND EQUIPMENT SHALL BE INDEPENDENTLY SUPPORTED FROM THE BUILDING STRUCTURE
WITH PROPER ALLOWANCES FOR CONTRACTION, EXPANSION, AND VIBRATION ELIMINATION.
17. PROVIDE 12"x10" ACCESS PANELS AT ALL BASEBOARD CONTROL VALVES. COORDINATE EXACT LOCATIONS WITH
GENERAL CONTRACTOR.
18. PROVIDE COPPER 3/4" RUN-OUTS TO HOT WATER REHEAT COILS, CABINET HEATERS AND UNIT HEATERS UNLESS
NOTED OTHERWISE.
20. ROOM THERMOSTATS SHALL BE MOUNTED 4'-0" ABOVE FINISHED FLOOR UNLESS OTHERWISE SHOWN OR
DIRECTED. COORDINATE LOCATIONS WITH ARCHITECTURAL WALL PROTECTIONS.
22. ALL DUCT DIMENSIONS SHOWN ARE INSIDE CLEAR FREE AREA REQUIRED.
23. ALL DIFFUSER, REGISTER, AND GRILLE SIZES INDICATED ON FLOOR PLANS ARE NECK SIZE REQUIRED.
24. ALL PIPING IS TO BE SLOPED A MINIMUM OF 1/4" PER HUNDRED FEET IN THE DIRECTION OF DRAINAGE.
25. NOT ALL SYMBOLS OR ABBREVIATIONS ARE USED ON THIS PROJECT.
26. COORDINATE ENTIRE INSTALLATION WITH THE WORK OF ALL OTHER TRADES PRIOR TO ANY FABRICATION OR
INSTALLATIONS.
TD TRANSFER AIR DUCT
FINS PER INCHFPI
FA
EXH
EX. EXISTING
EXHAUST
FREE AREA
GALLONS PER MINUTE
GENERAL EXHAUST
GENERAL CONTRACTORGC
GE
GPM
KILOWATTSKW
ID
KE
IN
HVAC HEATING, VENTILATION AND AIR CONDITIONING
INCHES
INSIDE DIAMETER
KITCHEN EXHAUST
MECHANICAL CONTRACTORMEC
LD
MBH
LAT LEAVING AIR TEMPERATURE
LOUVERED DOOR
THOUSANDS OF BRITISH THERMAL UNITS PER HOUR
FEET
FEET PER MINUTEFPM
FT
GAL GALLONS
NC NORMALLY CLOSED
OUTSIDE AIR TEMPERATUREOAT
NTS
OA
NO
NIC NOT IN CONTRACT
NORMALLY OPEN
NOT TO SCALE
OUTSIDE AIR
STATIC PRESSURESP
SUPPLY AIRSA
SAT SUPPLY AIR TEMPERATURE
EACHEA
DRAWINGDWG
FACILITY MANAGEMENT SYSTEMFMS
ENTERING AIR TEMPERATURE
EXHAUST AIRE.A.
EAT
DIA.
DN
DDC
DB DRY BULB TEMPERATURE (°F)
DIRECT DIGITAL CONTROL
DIAMETER
DOWN
CONTROL VALVECV
CONNECT
CLEAN OUT
CUBIC FEET PER MINUTECFM
CONN.
CO
CAP CAPACITY
BRITISH THERMAL UNIT PER HOUR
BRITISH THERMAL UNIT
BOTTOM OF DUCTBOD
BTUH
BTU
C CLOSED
AUTOMATIC TEMPERATURE CONTROLATC
AP
ARCH.
AFF
AD ACCESS DOOR
ABOVE FINISHED FLOOR
ACCESS PANEL
ARCHITECT
CUH CABINET UNIT HEATER
CP CONDENSATE PUMP
AIR COOLED CONDENSING UNITACCU
REVISION CLOUD
REVISION NOTE
DEMOLITION WORK NOTE
NEW WORK NOTE
EQUIPMENT TAG
FIN TUBE RADIATION DESIGNATION
HEATING CAPACITY (MBH)
ELEMENT LENGTH
QUANTITY
NECK SIZE OR LENGTH IF LINEAR DIFFUSER
AIR VOLUME (CFM)
SUPPLY/RETURN/EXHAUST REGISTER OR GRILLE TAG
U UNDERCUT DOORWAY (BY G.C.)
TEMPERATURE SENSOR
HEAT/COOL THERMOSTAT
CONTROL LINE
SUPPLY AIR
RETURN OR EXHAUST AIR
SUPPLY DIFFUSER
ARROWS INDICATE BLOW PATTER
SUPPLY DIFFUSER OR REGISTER BELOW DUCT
RETURN GRILLE
RETURN REGISTER OR GRILLE BELOW DUCT
FD FIRE DAMPER
M
SMOKE DAMPER
MOTORIZED OR AUTOMATIC CONTROL DAMPER
BACK DRAFT DAMPER
VOLUME DAMPER
RECTANGULAR TO ROUND DUCTWORK TRANSITION
MITERED ELBOW WITH TURNING VANES
RECTANGULAR TRANSITION
FLEXIBLE CONNECTION
12"Ø
12"x8"
RECTANGULAR RETURN/EXHAUST DUCTWORK DOWN
ROUND DUCTWORK UP
ROUND DUCTWORK DOWN
CAPPED DUCTWORK
RECTANGULAR RETURN/EXHAUST DUCTWORK UP
RECTANGULAR SUPPLY DUCTWORK DOWN
RECTANGULAR SUPPLY DUCTWORK UP
ROUND DUCTWORK - DIMENSION IS DUCT DIAMETER (IN.)
RECTANGULAR DUCTWORK - FIRST DIMENSION IS SIDE SHOWN (IN.)
GV GATE VALVE
GLV GLOBE VALVE
BLV BALL VALVE
BFV BUTTERFLY VALVE
DV DRAIN VALVE
SCV SWING CHECK VALVE
LCV LIFT CHECK VALVE
BALANCE COCKBC
BV BALANCE VALVE
PRV PRESSURE REDUCING VALVE
SC CONTROL VALVE
UNION
FLG FLANGE
PLS PIPE LINE STRAINER
BASKET STRAINERBKS
CONCENTRIC REDUCER (ENLARGER)CRD
ECCENTRIC REDUCER (ENLARGER)ERD
PIPE ANCHORAN
PIPE GUIDEGD
EXPANSION COMPENSATOREC
PIPE FLEXIBLE CONNECTIONPFC
RV RELIEF VALVE
Ts
DRAINDR
FRESH AIR INTAKEFAI
DOOR LOUVER (BY G.C.)DL
PIPE DOWN
PIPE UP
RUN-OUT OFF BOTTOM
RUN-OUT OFF TOP
PIPE OFF TOP
PIPE OFF BOTTOM
DIRECTION OF FLOW
PIPE BREAK
PC PUMPED CONDENSATE
CD CD A.C. CONDENSATE DRAIN
RG
RG
SD/R
SD
AIR SEPARATORAS
ELECTRICAL CONTRACTOREC
ENTERING WATER TEMPERATUREEWT
SQUARE FEETSF
TE TOILET EXHAUST
EL EXPANSION LOOP
ACD
SD
BD
VD
FD
BL BOILER
SATURATED SUCTION TEMPERATURE
TRANSFER AIRTA
SST
DRAIN PIPE PITCH AND FLOW
1/2" WIRE MESH SCREEN (ON OPEN END DUCT)
BD
FS FIRE & SMOKE DAMPERFS
IS ISOLATION VALVE REFER TO DETAILS AND SPEC.
EXHAUST REGISTER OR GRILLEEG
EXHAUST REGISTER OR GRILLE BELOW DUCTEG
QUANTITY
NECK SIZE OR LENGTH IF LINEAR DIFFUSER
AIR VOLUME (CFM)
SUPPLY DIFFUSER TAG
EG EXHAUST GRILLE
SIDEWALL SUPPLY REGISTERSG
EG/RG SIDEWALL EXHAUST/RETURN REGISTER
SD-A-#
10"Ø, 12"x12"
TYP 3
SG-A, RG-A or EG-A 10"Ø, 12"x12"
TYP 3
ACCU-1
FTR-A
10'-0" 11.8
SD
FACILITY MANAGEMENT PANELFMS
THERMOMETERTRM
PRESSURE GAUGEPG
FLOW SWITCHFS
AUTOMATIC AIR VENTAAV
MANUAL AIR VENTMAV
FLOAT & THERMOSTATIC STEAM TRAPF&TT
THERMOSTATIC STEAM TRAPTT
BUCKET STEAM TRAPBT
PRESSURE/TEMPERATURE PLUGPT
PIPE CAP
STRAINER WITH DRAIN VALVE AND CAP
HWR HWR HOT WATER RETURN
HWS HWS HOT WATER SUPPLY
MUW MAKE UP WATER
PC
BRANCH CONNECTION (DIRECTION TO BE FIELD DETERMINED)
CO2 SENSOR
CO SENSORCO
CO2
AFS- AIR FLOW MEASURING STATION
VFD VARIABLE FREQUENCY DRIVE
DSD DUCT SMOKE DETECTOR
BEAM PENETRATION BY DUCTWORK
ACOUSTICALLY LINED DUCTWORK
COMPUTER ROOM AIR CONDITIONING UNITAC
SD SUPPLY DIFFUSER
HWP HOT WATER PUMP
SOUND ATTENUATORSA
VARIABLE AIR VOLUME BOXVAV
SUPPLY GRILLESG
UH UNIT HEATER
AUTOMATIC AIR VENTAAV
COMBUSTION AIR SUPPLYCAS
CA COMBUSTION AIR
COOLING COILCC
CT
CP CONTROL PANEL
CURRENT TRANSFORMER
CONTRACTORCONTR
EXISTING TO REMAINETR
EXISTING TO BE REMOVED
EXTERNAL STATIC PRESSUREESP
ETBR
ET EXPANSION TANK
FULL LOAD AMPSFLA
FLOOR DRAINFLD
HP
HE
GUH GAS FIRED UNIT HEATER
HOOD EXHAUST
HORSE POWER
HEATING COILHC
LWT LEAVING WATER TEMPERATURE
OUTSIDE DIAMETEROD
OBD OPPOSED BLADE DAMPER
PC PLUMBING CONTRACTOR
RA
PSI
PD PRESSURE DROP
POUNDS PER SQUARE INCH
RETURN AIR
RM ROOM
SPEEDSPD
STAINLESS STEELSS
TSTAT THERMOSTAT
TYP TYPICAL
UC UNDERCUT DOOR
VAV VARIABLE AIR VOLUME
VB VACUUM BREAKER
VFD VARIABLE FREQUENCY DRIVE
WB WET BULB TEMPERATURE (°F)
WMS WIRE MESH SCREEN
1. MECHANICAL WORK IS INDICATED DIAGRAMMATIC. EXACT LOCATIONS OF ALL COMPONENTS ARE TO BE DETERMINED IN THE FIELD (SPACING SUBJECT TO ARCHITECT'S REVIEW AND APPROVAL) TO AVOID
CONFLICT WITH OTHER TRADES AND EXISTING SITE CONDITIONS.
FIRE PROTECTION CONTRACTORFPC
OPEN ENDED DUCTOED
3. WORK REQUIRING INTERRUPTION OF BUILDING SERVICES SHALL BE CAREFULLY REVIEWED AND COORDINATED WITH
THE OWNER TO MINIMIZE FREQUENCY AND DURATION OF SERVICE INTERRUPTIONS.
10. PROVIDE SMOKE DETECTORS WHERE SHOWN ON THE MECHANICAL DRAWINGS. COORDINATE THE QUANTITY AND EXACT LOCATION WITH ACTUAL SHEET METAL SHOP DRAWINGS, TO BE PRODUCED BY MECHANICAL CONTRACTOR, AND APPROVED BY ENGINEER. PROVIDE SMOKE DETECTORS AND SMOKE DAMPERS IN BOTH
SUPPLY AND RETURN DUCTS ON ALL AIR HANGLERS AS SHOWN IN MECHANICAL DRAWINGS.
19. PROVIDE SWING JOINTS AT ALL BRANCH CONNECTIONS TO HYDRONIC EQUIPMENT.
21. REFER TO SPECIFICATIONS FOR TYPE OF VALVE TO BE USED. VALVES ARE SHOWN ON PLANS FOR PLACEMENT
ONLY.
PILOT OPERATED PRESSURE REDUCING VALVE
T
CLEAN OUTC.O.
CHR CHR CHILLED WATER RETURN
CHS CHS CHILLED WATER SUPPLY
CHWP CHILLED WATER PUMP
CU CONDENSING UNIT
CF CHEMICAL POT FEEDER
GF GLYCOL FEEDER
AIR SEPARATORAS
BT BUFFER TANK
ET EXPANSION TANK
CH CHILLER
ERV ENERGY RECOVERY VENTILATION UNT
H$ HOOD SWITCH
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
CONSULTANT ARCHITECT/ENGINEER OF RECORD
WBRC
A R C H I T E C T S • E N G I N E E R S
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
VA RI FACILITIES MANAGEMENT
SERVICE
Approved:
FULLY SPRINKLERED
NEW MENTAL HEALTH
BUILDING 38 - PHASE 1
830 CHALKSTONE AVE PROVIDENCE, RI 02908
650-332
Engineering Discipline:
/1
/2
:4
:4
P
M C
R e vi t P ro je ct s\
\V
A M e n ta l H e a lth
\1
.0
-V
A M
C P ro vi d e n ce
M e n ta l H e a lth B ld g
M
G R
(2 rv t
MJ.0
CW MGR10 APR 2019
CONSTRUCTION
DOCUMENTS
MECHANICAL LEGEND
DWG NO. DRAWING TITLE
MJ.0 MECHANICAL LEGEND
MH1.0 MECHANICAL BASEMENT DUCTWORK PLAN
MH1.1 MECHANICAL FIRST FLOOR DUCTWORK PLAN
MH1.2 MECHANICAL SECOND FLOOR AND ROOF DUCTWORK PLAN
MH1.3 MECHANICAL PENTHOUSE ROOF DUCTWORK PLAN
MP1.0 MECHANICAL BASEMENT PIPING PLAN
MP1.1 MECHANICAL FIRST FLOOR PIPING PLAN
MP1.2 MECHANICAL SECOND FLOOR AND ROOF PIPING PLAN
MK5.0 MECHANICAL SCHEDULES
MK5.1 MECHANICAL SCHEDULES
ML6.0 MECHANICAL DETAILS
ML6.1 MECHANICAL DETAILS
ML6.2 MECHANICAL DETAILS
MM7.0 MECHANICAL HOT WATER PIPING SCHEMATIC
MM7.1 MECHANICAL CHILLED WATER PIPING SCHEMATIC
MM7.2 MECHANICAL ROOM DATA
MI0.0 MECHANICAL CONTROLS
MI0.1 MECHANICAL CONTROLS
MI0.2 MECHANICAL CONTROLS
MI0.3 MECHANICAL CONTROLS
MI0.4 MECHANICAL CONTROLS
MI0.5 MECHANICAL CONTROLS
MI0.6 MECHANICAL CONTROLS
MI0.7 MECHANICAL CONTROLS
MI0.8 MECHANICAL CONTROLS
Revisions: Date:
S T
A
T E
O F
R H O D
E
I S L A
N D
HOP E
J
J
J
3 12"x8" E.A. DUCT UP TO FIRST FLOOR.
MECHANICAL KEYED NOTES
2 34"x18" R.A. DUCT UP TO FIRST FLOOR.
1 32"x16" S.A. DUCT UP TO FIRST FLOOR.
MECHANICAL GENERAL NOTE
1. ALL DUCTWORK SHALL BE INSTALLED SO THAT IT SHALL NOT
HINDER ANY ACCESS OR MAINTANANCE
4 8"x10" E.A. DUCT UP TO FIRST FLOOR.
5 8"x10" E.A. DUCT DN TO RANGE HOOD.
6 BROAN BW5036SS RANGE HOOD TO BE PROVIDED
AND INSTALLED BY GENERAL CONTRACTOR.
HOOD IS SIZED FOR 350 CFM. COORDINATE WITH
ARCHITECTURAL DRAWINGS.
7 OED. COVER WITH WM.
AC-38-1-02
CUH-38-0-01
FD
FD
14"x10"
VAV-38-0-10
VAV-38-0-11
V A
V -3
-0
-0
VAV-38-0-04
V A
V -3
-0
-0
V A
V -3
-0
-0
V A
V -3
-0
-0
VAV-38-0-01
LD-B
8"Ø
TYP. 2
EG-A
6"x6"
SD-A
8"Ø
STAIR 1
ELEV 1
ELEV 2
WATER SERVICE
CLASSROOM STORAGE
027A
ELEV. CONTROL ROOM
TOILET
TOILET
PRRC CUBES
OFFICE
OFFICE
014 OT OFFICE
OCCUPATIONAL THERAPY ROOM
OFFICE
ELECTRICAL
TELE/ DATA
ELEVATOR LOBBY
CONSULT ROOM - EXTRA
CONSULT ROOM
CONSULT ROOM
CLASSROOM
CLASSROOM
STAFF TOILET
EMERG. ELECT.
018A
WAITING
32"x16"
C
D
E
F
G
76543 1 2
8.7
SD-A
8"Ø
SD-A
8"Ø
SD-A
8"Ø
RG-A
12"x12"
RG-A
8"x8"
RG-A
8"x8"
RG-A
8"x8"
RG-A
12"x12"
TYP. 2
RG-C
12"x12"
RG-C
12"x12" RG-A
8"x8"
RG-A
10"x10"
RG-A
10"x10"
RG-A
10"x10"
RG-C
6"x6"
RG-A
12"x12"
RG-A
12"x12"
RG-A
12"x12"
RG-A
12"x12"
SD-A
8"Ø
SD-A
8"Ø
SD-A
8"Ø
SD-A
8"Ø
SD-A
8"Ø
LD-B
8"Ø
LD-B
8"Ø LD-B
8"Ø
TYP. 2
LD-B
8"Ø
TYP. 2
LD-B
8"Ø
LD-B
8"Ø
LD-B
8"Ø
LD-B
8"Ø
SD-A
8"Ø
TYP. 4
SG-A
12"x12"
SG-A
12"x12"
SD-A
8"Ø
EG-A
6"x6"
EG-A
6"x6"
SD-A
8"Ø
SD-A
8"Ø
EG-A
6"x6"
LD-B
8"Ø
LD-B
8"Ø
SD-A
8"Ø
TYP. 4
SD-A
8"Ø
TYP. 4
"x
"x
8"x6"
10"x10"
18"x12"
16"x10"
14"x8"
12"x8"
14"x8"
12"x8"
14"x8" 10"x8"
16"x8" 16"x10"
8"x10"
18"x10"
26"x10"
10"x6"
14"x12"
20"x14"
"x
26"x10"
"x
"x
34"x14"
34"x18"
"x
"x
20"x12"
30"x12"
"x
12"x10"10"x10"
"x
26"x14"
14"x12"
V A
V -3
-0
-0
SD-A
8"Ø
12"x8"
12"x8"
12"x8"
12"x10"
SD-A
8"Ø
SD-A
8"Ø
30"x10"
12"x8"
14"x8"
26"x12"
20"x12"
22"x10"
26"x12"
8"x6"
U
U
U
U
U
U
8"x6"
6"x8"
12"x8"
10"x6" 10"x8"
5 6
RG-A
12"x12"
TYP. 4
FD
FD
FD
FD
HAC
6"x6"
CORRIDOR
12"x8"
12"x8"
12"x8"
"x
12"x8"
12"x8"
12"x8"
8"x6" 8"x6" 8"x6"
16"x10"
SD-A
8"Ø
8"x6"
10"x6"
LD-B
8"Ø
LD-B
8"Ø
12"x12"
12"x12"12"x8"
12"x8"
12"x8"
CLASSROOM STORAGE
027B
U
10"x8"
RG-B
6"x6"
RG-B
6"x6"
8"x6"
AC-38-1-01
31"x10"
CUH-38-0-02
VAV-38-0-08
VAV-38-0-09
STAFF LOUNGE
STAIR 2
STAFF TOILET
CORRIDOR
A
B
8.7
RG-A
14"x14"
LD-B
8"Ø
SD-A
10"Ø
EG-B
6"x6"
EG-A
6"x6"
16"x10"
12"x10"
6"x8"
10"x10"
8"x8"
14"x8"
U
U
6"x8"
6"x6"
10"ø
GRAPHIC SCALE
4' 2' 0 4' 8' 12'
SCALE: 1/4" = 1' - 0"
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
CONSULTANT ARCHITECT/ENGINEER OF RECORD
WBRC
A R C H I T E C T S • E N G I N E E R S
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
TRUE NORTH
PROJECT NORTH VA RI FACILITIES MANAGEMENT
SERVICE
Approved:
FULLY SPRINKLERED
NEW MENTAL HEALTH
BUILDING 38 - PHASE 1
830 CHALKSTONE AVE PROVIDENCE, RI 02908
650-332
Engineering Discipline:
/1
/2
:4
:4
P
M C
R e v it P ro je c ts
\2
\V
A M e n ta l H e a lt h \1
.0
-V
A M
C P ro v id e n c e
M e n ta l H e a lt h
B ld g
M G
R (2 rv t
MH1.0
CW MGR10 APR 2019
CONSTRUCTION
DOCUMENTS
MECHANICAL BASEMENT
DUCTWORK PLAN
1/4" = 1'-0"MH1.0
1 MECHANICAL BASEMENT DUCTWORK PLAN - PART A
1/4" = 1'-0"MH1.0
2 MECHANICAL BASEMENT DUCTWORK PLAN - PART B
Revisions: Date:
S T
A
T E
O F
R H O D
E
I S L A
N
1 10"x14" R.A. DUCT UP TO SECOND FLOOR.
MECHANICAL KEYED NOTES
2 12"x10" S.A. DUCT UP TO SECOND FLOOR.
6 34"x18" R.A. DUCT DN TO BASEMENT FLOOR.
3 54"x22" S.A. DUCT UP TO SECOND FLOOR.
4 64"x24" R.A. DUCT UP TO SECOND FLOOR.
5 32"x16" S.A. DUCT DN TO BASEMENT FLOOR.
7 12"x8" R.A. DUCT DN TO BASEMENT FLOOR.
8 14"x10" E.A. DUCT UP THRU ROOF.
MECHANICAL GENERAL NOTE
1. ALL DUCTWORK SHALL BE INSTALLED SO THAT IT SHALL NOT
HINDER ANY ACCESS OR MAINTANANCE
9 8"x10" E.A. DUCT UP THRU ROOF.
10 8"x10" E.A. DUCT DN TO BASEMENT FLOOR.
11 DUCTWORK SHALL NOT RUN OVER ELECTRICAL PANELS PER
NEC.
GRAPHIC SCALE
4' 2' 0 4' 8' 12'
SCALE: 1/4" = 1' - 0"
VAV-38-1-09
VAV-38-1-13
VAV-38-1-08
VAV-38-1-14
VAV-38-1-07
V A
V -3
-1
-0
VAV-38-1-05
V A
V -3
-1
-0
VAV-38-1-01
V A
V -3
-1
-1
V A
V -3
-1
-0
VESTIBULE
101WAITING
SECURITY / WC STORAGE
101A
COMMUNICATION CENTER
CONSULT ROOM
CONSULT ROOM
CONSULT ROOM
OFFICE
INJECTION ROOM
MEDICATION ROOM
STORAGE
CONSULT ROOM
COMPUTER LAB
CORRIDOR
100B
RC CUBES
OFFICE
TLT
TLT
CORRIDOR
100A
TLT
HAC
ELEV 2
ELEV 1
STAIR 1
C
D
E
F
G
76543 1 2
8.7
LD-B
8"Ø
SD-A
8"Ø
SD-A
8"Ø
V A
V -3
-1
-1
V A
V -3
-1
-0
EG-A
6"x6"
EG-A
6"x6"
EG-A
6"x6"
18"x12"
SD-A
10"Ø
SD-A
10"Ø
RG-A
14"x14"
RG-A
14"x14"
RG-A
14"x14"
LD-A
8"Ø
SD-A
8"Ø
TYP. 4
LD-B
8"Ø
LD-B
8"Ø
LD-B
8"Ø
LD-B
8"Ø
RG-A
10"x10"
RG-A
10"x10"
RG-A
8"x8"
RG-A
12"x12"
RG-A
12"x12"
RG-A
12"x12"
RG-A
12"x12"
LD-B
8"Ø
LD-B
8"Ø
LD-B
8"Ø
LD-B
8"Ø
LD-B
8"Ø
LD-B
8"Ø
SD-A
8"Ø
LD-B
8"Ø
LD-B
8"Ø
EG-A
6"x6"
SD-A
8"Ø
SD-A
8"Ø
LD-B
8"Ø
LD-B
8"Ø
RG-A
10"x10"
LD-B
8"Ø
LD-B
8"Ø
LD-B
8"Ø
LD-B
8"Ø
LD-B
8"Ø
LD-B
8"Ø
LD-B
8"Ø
LD-B
8"Ø
RG-A
10"x10"
RG-A
10"x10"
RG-A
10"x10"
LD-B
8"Ø
LD-B
8"Ø
RG-A
10"x10"
RG-A
10"x10"
VAV-38-1-15
SD-A
8"Ø SD-A
8"Ø
RG-A
8"x8"
RG-A
8"x8"
CUBICLES
RG-A
12"x12"
64"x16"
32"x12"
28"x12"
10"x8" 12"x10"10"x8"
"x
"x
" 1 "x
18"x8" 12"ø
12"x10"
30"x12"
10"x14"
16"x12"
24"x12"
20"x12"
8"ø
10"ø
"x
54"x16" 24"x10"
10"x10"
30"x14"
10"x10"
8"ø
8"x8"
8"ø
10"x8"
LD-B
8"Ø
LD-B
8"Ø
20"x12"
12"x10"
8"x8"
8"ø
8"ø
12"x10"8"ø
8"ø
8"x8"
RG-C
6"x6"
34"x18"
"x
32"x16"
FD
OFFICE
38"x14"
22"x12"
8"x8"
28"x12"
RG-A
12"x12"
32"x14"
28"x12"
24"x8"
10"x6"
12"x8"
8"ø
12"x8"
18"x10"
8"x8"
"x
LD-C
LD-C
LD-C
14"x6" 14"x6" 14"x6" LD-C
LD-C
8"ø
10"x10"
8"ø
RG-B
14"x14"
14"x10"
U
U
U
U
U
MAIN ELECTRICAL ROOM
CONSULT ROOM
14"x12"
10"x8"
10"x8"
12"x8"
10"x8"
12"x8"
12"x8"
SG-A
16"x12"
RG-C
18"x12"
8"x10"
28"x12"
24"x16"
U
10"ø
10"x8"
10"x8"
14"x10"
12"x8"
"x
10"x8"
10"ø
14"x12"
12"x10"
10"x6"
12"x10"
8"x6"
12"x8"
10"ø
12"x8"
14"x14"
"x
10"x8"
8"x6"
8"x6"
FD
FD
EG-C
6"x6"
8"x8"
TOILET
LD-B
8"Ø
LD-B
8"Ø
FD
20"x10"
10"x6"
14"x10"
10"ø
SA-1 SA-2
SA-4
SA-3
12"x8"
10"x8"8"x10"
14"x8"
10"x8"
12"x8"
VAV-38-1-11
VAV-38-1-10
VAV-38-1-12
OFFICE
CONSULT ROOM - EXTRA
STAIR 2
CORRIDOR
100B
A
B
8.7
LD-B
8"Ø
LD-B
8"Ø
LD-B
8"Ø
RG-A
12"x12"
SD-A
10"Ø
LD-B
8"Ø
LD-B
8"Ø
10"x10"
8"ø
12"x8"
MEETING ROOM
LD-B
8"Ø
RG-A
12"x12"
12"x8"
SD-A
10"Ø
10"ø
12"x8"
8"ø
10"x10"
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
CONSULTANT ARCHITECT/ENGINEER OF RECORD
WBRC
A R C H I T E C T S • E N G I N E E R S
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
TRUE NORTH
PROJECT NORTH VA RI FACILITIES MANAGEMENT
SERVICE
Approved:
FULLY SPRINKLERED
NEW MENTAL HEALTH
BUILDING 38 - PHASE 1
830 CHALKSTONE AVE PROVIDENCE, RI 02908
650-332
Engineering Discipline:
/1
/2
:4
:5
P
M C
R e v it P ro je c ts
\2
\V
A M e n ta l H e a lt h \1
.0
-V
A M
C P ro v id e n c e
M e n ta l H e a lt h
B ld g
M G
R (2 rv t
MH1.1
CW MGR10 APR 2019
CONSTRUCTION
DOCUMENTS
MECHANICAL FIRST FLOOR
DUCTWORK PLAN
1/4" = 1'-0"MH1.1
1 MECHANICAL FIRST FLOOR DUCTWORK PLAN - PART A
1/4" = 1'-0"MH1.1
2 MECHANICAL FIRST FLOOR DUCTWORK PLAN - PART B
Revisions: Date:
S T
A
T E
O F
R H O D
E
I S L A
N
4 E.A. OED. FULL SIZE OF FAN E.A. INLET OPENING. COVER
WITH WM.
5 4" DOUBLE WALL STAINLESS STEEL E.A. FLUE UP THROUGH ROOF.
6 6" GALVANIZED STEEL INTAKE AIR DUCTWORK UP THROUGH ROOF.
2 10"x12" S.A. DUCT DN TO FIRST FLOOR.
1 14"x10" R.A. DUCT DN TO FIRST FLOOR.
3 14"x14" E.A. UP THROUGH MECHANICAL PENTHOUSE ROOF.
7 54"x22" S.A. DUCT DN TO FIRST FLOOR.
8 64"x24" R.A. DUCT DN TO FIRST FLOOR.
9 66"x20" INTAKE AIR DUCT DROP.
10 66"x20" RELIEF AIR DUCT RISE.
11 14"x10" E.A. DUCT DN TO FIRST FLOOR.
MECHANICAL GENERAL NOTE
1. ALL DUCTWORK SHALL BE INSTALLED SO THAT IT SHALL NOT
HINDER ANY ACCESS OR MAINTANANCE
14"x8" OPEN-ENDED DUCT w/ WMS.12
18"x10" OPEN-ENDED DUCT w/ WMS.13
EQUIPMENT SERVICE CLEARANCE (TYP).14
INSTALL BLANKOFF ON BACKSIDE OF LOUVER. BLANKOFF
SHALL BE INSULATE AS PART OF THE BUILDING ENVELOPE
INSULATION.
LOUVER PLENUM SHALL BE FULL SIZE OF LOUVER SIZE.
TYPICAL FOR ALL LOUVERS, EXCEPT EMERGENCY EXHAUST
INTAKE AIR LOUVER (REFER TO KEYED NOTE 18).
COMBINED LOUVER PLENUM. REFER TO PLANS FOR LOUVER
WIDTH AND HEIGHT SIZE. PLENUM SHALL BE 24" DEEP.
LOUVER PLENUM. PLENUM TO BE SPLIT INTO TWO
SECTIONS VIA SHEET METAL DIVIDER. TOP SECTION SHALL
BE 22" WIDE x 30" HIGH. THIS SECTION WILL SERVE THE
INTAKE AIR REQUIREMENT FOR THE EMERGENCY EXHAUST
FAN. BOTTOM SECTION SHALL BE 22" WIDE x 40" HIGH. THIS
SECTION SHALL BE CAPPED AND FULLY INSUALTED.
COMBINED LOUVER PLENUM. REFER TO PLANS FOR LOUVER
WIDTH AND HEIGHT SIZE. PLENUM SHALL BE 10" DEEP.
20 3" PVC INTAKE AIR DUCTWORK UP THROUGH ROOF.
21 3" DOUBLE WALL STAINLESS STEEL E.A. FLUE UP THROUGH ROOF.
22 3" DOUBLE WALL STAINLESS STEEL E.A. FLUE DROP TO WATER
HEATER E.A. OUTLET.
23 3" PVC INTAKE AIR DUCTWORK DROP TO WATER HEATER INTAKE AIR
INLET.
BL-38-2-01
BL-38-2-02
HWP-38-2-01
HWP-38-2-02
UH-38-2-01
UH-38-2-02
BL-38-2-03
HWP-38-2-03
CU-38-2-01
CU-38-2-02
VAV-38-2-02
VAV-38-2-01
EF-38-2-01
CIRCULATION
MECHANICAL ROOM
10"ø
A
B
C
D
E
F
G
76543 1 2
8.7
CHWP-38-2-01 CHWP-38-2-02
MD
EF-38-2-02
H-38-2-01
ERV-38-2-01
64"x24"
54"x22"
MD
LU-38-2-01
(TYP. 9)
LU-38-2-02
(TYP. 2)
66"x20"
90"x104"
72"x104"
DSD
DSD
14"x10"
14"x8"
8"ø
8"x8"
8"x8" 10"x8" 12"x10"
RG-A
14"x14"
10"x12"
MD
EF-38-2-03
FD
FD
66"x20"
LD-B
8"Ø
TYP. 4
SD-A
6"Ø
8"x8"
(FUTURE)
(FUTURE)
15 15
189"x72"
187"x61"
LU-38-2-03
(TYP. 2)
SD
SD
3"ø
3"ø
GRAPHIC SCALE
4' 2' 0 4' 8' 12'
SCALE: 1/4" = 1' - 0"
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
CONSULTANT ARCHITECT/ENGINEER OF RECORD
WBRC
A R C H I T E C T S • E N G I N E E R S
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
TRUE NORTH
PROJECT NORTH VA RI FACILITIES MANAGEMENT
SERVICE
Approved:
FULLY SPRINKLERED
NEW MENTAL HEALTH
BUILDING 38 - PHASE 1
830 CHALKSTONE AVE PROVIDENCE, RI 02908
650-332
Engineering Discipline:
/1
/2
:4
:5
P
M C
R e v it P ro je c ts
\2
\V
A M e n ta l H e a lt h \1
.0
-V
A M
C P ro v id e n c e
M e n ta l H e a lt h
B ld g
M G
R (2 rv t
MH1.2
CW MGR10 APR 2019
CONSTRUCTION
DOCUMENTS
MECHANICAL SECOND FLOOR
AND ROOF DUCTWORK PLAN
1/4" = 1'-0"MH1.2
1 MECHANICAL SECOND FLOOR DUCTWORK PLAN - PART A
Revisions: Date:
S T
A
T E
O F
R H O D
E
I S L A
N
1 14"x14" E.A. DUCT DOWN THROUGH ROOF. TERMINATE E.A.
ABOVE ROOF WITH GOOSENECK ELBOW.
3 6"Ø INTAKE AIR DUCT DN THRU ROOF. EXTEND 6"Ø INTAKE AIR
DUCT 3'-6" FT ABOVE ROOF LEVEL (TYP 3).
2 4"Ø E.A. DUCT DN THRU ROOF. EXTEND 4"Ø E.A. FLUE 7'-6" FT
ABOVE ROOF LEVEL (TYP 3).
5 3"Ø PVC INTAKE AIR DUCT DN THROUGH ROOF. EXTEND 3"Ø
INTAKE AIR DUCT 3'-6" FT ABOVE ROOF LEVEL.
4 3"Ø DOUBLE WALL STAINLESS STEEL E.A. FLUE DN THROUGH
ROOF. EXTEND 3"Ø E.A. FLUE 7'-6" FT ABOVE ROOF LEVEL.
GRAPHIC SCALE
4' 2' 0 4' 8' 12'
SCALE: 1/4" = 1' - 0"
A
B
C
D
E
F
G
76543 1 2
8.7
CU-38-2-01
CU-38-2-02
EF-38-2-01 EF-38-2-03
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
CONSULTANT ARCHITECT/ENGINEER OF RECORD
WBRC
A R C H I T E C T S • E N G I N E E R S
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
TRUE NORTH
PROJECT NORTH VA RI FACILITIES MANAGEMENT
SERVICE
Approved:
FULLY SPRINKLERED
NEW MENTAL HEALTH
BUILDING 38 - PHASE 1
830 CHALKSTONE AVE PROVIDENCE, RI 02908
650-332
Engineering Discipline:
/1
/2
:4
:2
P
M C
R e v it P ro je c ts
\2
\V
A M e n ta l H e a lt h \1
.0
-V
A M
C P ro v id e n c e
M e n ta l H e a lt h
B ld g
M G
R (2 rv t
MH1.3
CW MGR10 APR 2019
CONSTRUCTION
DOCUMENTS
MECHANICAL PENTHOUSE ROOF
DUCTWORK PLAN
1/4" = 1'-0"MH1.3
1 MECHANICAL SECOND FLOOR DUCTWORK PLAN
Revisions: Date:
S T
A
T E
O F
R H O D
E
I S L A
N
1 2" HWS/R PIPING UP TO FIRST FLOOR.
2 ROUTE 3/4" CD PIPING DN IN WALL. PIPING SHALL
TERMINATE AT OPEN END DRAIN BELOW SINK. COORDINATE
WITH PLUMBING CONTRACTOR.
MECHANICAL GENERAL NOTE
1. JOHNSON CONTROLS METASYS DDC CONTROL SYSTEM SHALL
BE PROVIDED.
2. HWS/R RUN OUTS SHALL BE 3/4" UNLESS OTHERWISE NOTED.
3 EXPANSION LOOP (TYP.)
4 CHILLER SERVICE CLEARANCE (TYP.)
5 CHILLER TO BE MOUNTED ON 3'-6" HIGH SUPPORT. INTENT IS
TO PROVIDE CHILLER WITH PROPER SERVCE CLEARANCE
ABOVE THE GUARDRAIL (INDICATED PLAN RIGHT OF
CHILLER).
6 PIPE SUPPPORT (TYP).
7 ROUTE 4" CHS/R PIPING BELOW GROUND THEN UP THRU
BASEMENT FLOOR SLAB.
8 4" CHS/R PIPING UP TO FIRST FLOOR VIA PIPE CHASE.
9 ROUTE PIPING BELOW GROUND.
10 REFRIGERANT PIPING UP TO FIRST FLOOR.
11 INSTALL ISOLATION VALVES AND DRAIN VALVES ON CHS/R
PIPING LINES WHERE THE CHS/R PIPING ENTERS THE
BUILDING. INSTLALL ACCESS PANEL TO ACCESS THESE
VALVES.
12 RANGE HOOD SWITCH.
13 CHILLER CONTROL PANEL.
GRAPHIC SCALE
4' 2' 0 4' 8' 12'
SCALE: 1/4" = 1' - 0"
CUH-38-0-01
AC-38-1-02
Ts
Ts
Ts
TsTs
Ts Ts
Ts
TsTs
Ts
CO2
CO2
CO2
CO2
VAV-38-0-01
VAV-38-0-02
VAV-38-0-03 VAV-38-0-07
V A
V -3
-0
-0
VAV-38-0-04
VAV-38-0-11
VAV-38-0-10
1" HWR
1" HWS
1 1/4" HWR
1 1/4" HWS
1" HWS
1" HWR
2" HWS
2" HWR
CO2
CLASSROOM
CORRIDOR
CLASSROOM
STAFF TOILET
CLASSROOM STORAGE
027A
ELECTRICAL
TELE/ DATA
EMERG. ELECT.
018A
OFFICE
OCCUPATIONAL THERAPY ROOM
OT OFFICE
015OFFICE
OFFICE
PRRC CUBES
CORRIDOR
WATER SERVICE
CONSULT ROOM - EXTRA
CONSULT ROOM
023CONSULT ROOM
TOILET
TOILET
ELEV. CONTROL ROOM
ELEV 2
003ELEV 1
WAITING
ELEVATOR LOBBY
STAIR 1
B
C
D
E
F
G
76543 1 2
8.7
Ts
Ts
V A
V -3
-0
-0
2" HWS
2" HWR
ANCHORS
(TYP.)
PIPE GUIDES
(TYP.)
1" HWS
1" HWR
ISOLATION
VALVE (TYP.)
STORAGE
3/4" CD
3/4" CD
CLEANOUT
(CO) (TYP.)
CO
CO
CO
H$
CUH-38-0-02
Ts
Ts
VAV-38-0-08
VAV-38-0-09
1" HWR
1" HWS
STAFF LOUNGE
CORRIDOR
STAFF TOILET
STAIR 2
A
B
8.7
CH-38-0-01
CH-38-0-02
4" CHS
4" CHR
4" CHR
4" CHS
4" CHR
4" CHS
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
CONSULTANT ARCHITECT/ENGINEER OF RECORD
WBRC
A R C H I T E C T S • E N G I N E E R S
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
TRUE NORTH
PROJECT NORTH VA RI FACILITIES MANAGEMENT
SERVICE
Approved:
FULLY SPRINKLERED
NEW MENTAL HEALTH
BUILDING 38 - PHASE 1
830 CHALKSTONE AVE PROVIDENCE, RI 02908
650-332
Engineering Discipline:
/1
/2
:4
:5
P
M C
R e vi t P ro je ct s\
\V
A M e n ta l H e a lth
\1
.0
-V
A M
C P ro vi d e n ce
M e n ta l H e a lth B ld g
M
G R
(2 rv t
MP1.0
CW MGR10 APR 2019
CONSTRUCTION
DOCUMENTS
MECHANICAL BASEMENT PIPING
PLAN
1/4" = 1'-0"MP1.0
1 MECHANICAL BASEMENT PIPING PLAN - PART A
1/4" = 1'-0"MP1.0
2 MECHANICAL BASEMENT PIPING PLAN - PART B
Revisions: Date:
S T
A
T E
O F
R H O D
E
I S L A
N
1 3" HWS/R PIPING UP TO MECHANICAL ROOM.
2 2" HWS/R PIPING DOWN TO BASEMENT.
3 2-1/2" CAPPED & VALVED. INTENT IS TO SERVE FUTURE
ADDITION.
4 2" HWS/R PIPING UP TO ERV-38-2-01.
MECHANICAL GENERAL NOTE
1. JOHNSON CONTROLS METASYS DDC CONTROL SYSTEM SHALL
BE PROVIDED.
7 PIPE ANCHOR (TYP).
5 EXPANSION LOOP (TYP.)
6 PIPE GUIDE (TYP).
8 4" CHS/R PIPING DN TO BASEMENT.
9 REFRIGERANT PIPING DN TO BASEMENT FLOOR.
10 REFRIGERANT PIPING UP THRU ROOF.
GRAPHIC SCALE
4' 2' 0 4' 8' 12'
SCALE: 1/4" = 1' - 0"
Ts
Ts
Ts
Ts
Ts
Ts
TsTs
Ts
Ts
Ts
CO2
CO2
CO2
CO2
VAV-38-1-01
VAV-38-1-16
VAV-38-1-05
V A
V -3
-1
-0
VAV-38-1-07
VAV-38-1-14
VAV-38-1-08
VAV-38-1-13
VAV-38-1-09
1" HWS
1" HWR
2 1/2" HWR
2 1/2" HWS
2 1/2" HWR
2 1/2" HWS
2 1/2" HWR
2 1/2" HWS
Ts
VAV-38-1-03
OFFICE
OFFICE
CUBICLES
MEDICATION ROOM
INJECTION ROOM
CONSULT ROOM
CONSULT ROOM
CONSULT ROOM
COMMUNICATION CENTER
SECURITY / WC STORAGE
101A
VESTIBULE
WAITING
CORRIDOR
100A
STAIR 1
ELEV 1
ELEV 2
TLT
HAC
TLT
TLT
RC CUBES
CORRIDOR
100B
TOILET
STORAGE
CONSULT ROOM
COMPUTER LAB
OFFICE
OFFICE
1" HWR
1" HWS
C
D
E
F
G
76543 1 2
8.7
2" HWS
2" HWR
VAV-38-1-02
VAV-38-1-15
Ts
2 1/2" HWR
2 1/2" HWS
VAV-38-1-17
VAV-38-1-04
Ts
MAIN ELECTRICAL ROOM
ISOLATION
VALVE (TYP.)
Ts
CUH-38-1-01
4" CHR
4" CHS
4" CHR
4" CHS
1" HWS
1" HWR
1 1/4" HWS
1 1/4" HWR
CONSULT ROOM
Ts
Ts VAV-38-1-10
VAV-38-1-11
VAV-38-1-12
Ts
CONSULT ROOM - EXTRA
OFFICE
A
B
8.7
MEETING ROOM
STAIR 2
4" CHR
4" CHS
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
CONSULTANT ARCHITECT/ENGINEER OF RECORD
WBRC
A R C H I T E C T S • E N G I N E E R S
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
TRUE NORTH
PROJECT NORTH VA RI FACILITIES MANAGEMENT
SERVICE
Approved:
FULLY SPRINKLERED
NEW MENTAL HEALTH
BUILDING 38 - PHASE 1
830 CHALKSTONE AVE PROVIDENCE, RI 02908
650-332
Engineering Discipline:
/1
/2
:4
:0
P
M C
R e v it P ro je c ts
\2
\V
A M e n ta l H e a lt h \1
.0
-V
A M
C P ro v id e n c e
M e n ta l H e a lt h
B ld g
M G
R (2 rv t
MP1.1
CW MGR10 APR 2019
CONSTRUCTION
DOCUMENTS
MECHANICAL FIRST FLOOR
PIPING PLAN
1/4" = 1'-0"MP1.1
1 MECHANICAL FIRST FLOOR PIPING PLAN - PART A
1/4" = 1'-0"MP1.1
2 MECHANICAL FIRST FLOOR PIPING PLAN - PART B
Revisions: Date:
S T
A
T E
O F
R H O D
E
I S L A
N
1 3" HWS/R PIPING DN TO FIRST FLOOR.
EXTEND CONTROL WIRING TO EF-38-2-02. WIRING SHALL
ALSO EXTEND TO EXHAUST AIR AND INTAKE AIR MOTORIZED
DAMPERS ASSOCIATED WITH THE EMERGENCY EXHAUST
SYSTEM.
REFRIGERANT PIPING (TYP).
4 ROUTE REFRIGERANT PIPING DOWN TO FIRST FLOOR. SIZE
PIPING PER MANUFACTURER'S RECOMMENDATIONS.
5 4" CHS/R PIPING DN TO FIRST FLOOR.
MECHANICAL GENERAL NOTE
1. JOHNSON CONTROLS METASYS DDC CONTROL SYSTEM SHALL
BE PROVIDED.
6 HWP-38-2-03 VFD LOCATION (TO BE INSTALLED AT FUTURE DATE).
7 HWP-38-2-01 VFD.
8 HWP-38-2-02 VFD.
9 CHWP-38-2-01 VFD.
10 CHWP-38-2-02 VFD.
11 EQUIPMENT SERVICE CLEARANCE (TYP).
12 ROOF PIPE SUPPORT (TYP).
GRAPHIC SCALE
4' 2' 0 4' 8' 12'
SCALE: 1/4" = 1' - 0"
BL-38-2-01BL-38-2-02
AS-38-2-01
ET-38-2-01
HWP-38-2-01
HWP-38-2-02
UH-38-2-01
UH-38-2-02
BL-38-2-03
HWP-38-2-03
CF-38-2-01
Ts
Ts
VAV-38-2-01
VAV-38-2-02
3" HWR
CO
CU-38-2-01
CU-38-2-02
Ts
CIRCULATION
MECHANICAL ROOM
ELEV 2
ELEV 1
STAIR 1
EF-38-2-01
3" HWS
AS-38-2-02
BT-38-2-01
CHWP-38-2-01
CHWP-38-2-02
CF-38-2-02
A
B
C
D
E
F
G
76543 1 2
8.7
EF-38-2-02
2" HWR
2" HWS
4" CHR
4" CHR2" HWS
3" HWR
H-38-2-01
4" AS
ERV-38-2-01
1" HWR
1" HWS
3" HWR
3/4" HWS
3/4" HWR
EF-38-2-03
4" CHR
4" CHS
4" CHS
GF-1
3/4"
(FUTURE)
(FUTURE)
3/4"
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
CONSULTANT ARCHITECT/ENGINEER OF RECORD
WBRC
A R C H I T E C T S • E N G I N E E R S
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
TRUE NORTH
PROJECT NORTH VA RI FACILITIES MANAGEMENT
SERVICE
Approved:
FULLY SPRINKLERED
NEW MENTAL HEALTH
BUILDING 38 - PHASE 1
830 CHALKSTONE AVE PROVIDENCE, RI 02908
650-332
Engineering Discipline:
/1
/2
:4
:0
P
M C
R e v it P ro je c ts
\2
\V
A M e n ta l H e a lt h \1
.0
-V
A M
C P ro v id e n c e
M e n ta l H e a lt h
B ld g
M G
R (2 rv t
MP1.2
CW MGR10 APR 2019
CONSTRUCTION
DOCUMENTS
MECHANICAL SECOND FLOOR
AND ROOF PIPING PLAN
1/4" = 1'-0"MP1.2
1 MECHANICAL SECOND FLOOR PIPING PLAN
Revisions: Date:
S T
A
T E
O F
R H O D
E
I S L A
N
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
CONSULTANT ARCHITECT/ENGINEER OF RECORD
WBRC
A R C H I T E C T S • E N G I N E E R S
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
VA RI FACILITIES MANAGEMENT
SERVICE
Approved:
FULLY SPRINKLERED
NEW MENTAL HEALTH
BUILDING 38 - PHASE 1
830 CHALKSTONE AVE PROVIDENCE, RI 02908
650-332
Engineering Discipline:
/1
/2
:4
:0
P
M C
R e v it P ro je c ts
\2
\V
A M e n ta l H e a lt h \1
.0
-V
A M
C P ro v id e n c e
M e n ta l H e a lt h
B ld g
M G
R (2 rv t
MK5.0
CW MGR10 APR 2019
CONSTRUCTION
DOCUMENTS
MECHANICAL SCHEDULES
7. REFER TO PROJECT SPECIFICATIONS FOR ALL REQUIRED OPTIONS AND ACCESSORIES.
6. MOUNT ON 4" CONCRETE HOUSING PAD. PAD IS BY GENERAL CONTRACTOR.
5. PROVIDE w/ DISCONNECT SWITCH.
4. REMOTE MOUNTED VFD.
3. STANDBY PUMP.
2. PUMP TO BE FURNISHED AND INSTALLED UNDER THE FUTURE BUILDING ADDITION PROJECT. PUMP SCHEDULED FOR INFORMATIONAL PURPOSES ONLY.
1. PUMP TO BE FURNISHED AND INSTALLED UNDER THIS PROJECT.
NOTES:
M - HOT WATER PUMP SCHEDULE
TAG LOCATION SERVICE TYPE
FLUID
FLOWRATE
(GPM)
HEAD
(FT WG)
SUCTION
INLET
(IN)
DISCHARGE
OUTLET
(IN)
IMPELLER
DIAMETER
(IN)
MOTOR
ELECTRICAL
DATA CONTROLS
SUCTION
DIFFUSER
TRIPLE
DUTY
VALVE STRAINER NOTES
BASIS OF DESIGN
HP RPM V PH HZ TYPE
FURNISHED
BY MANUFACTURER MODEL
HWP-38-2-01 MECHANICAL ROOM 202 BUILDING HEATING HOT WATER BASE MOUNTED END-SUCTION 40 75 1.25 1.25 8.5 3 1800 480 3 60 DDC ATC YES YES YES NOTES 1,4-7 BELL AND GOSSETT 1510
HWP-38-2-02 MECHANICAL ROOM 202 BUILDING HEATING HOT WATER BASE MOUNTED END-SUCTION 40 75 1.25 1.25 8.5 3 1800 480 3 60 DDC ATC YES YES YES NOTES 1,3-7 BELL AND GOSSETT 1510
HWP-38-2-03 MECHANICAL ROOM 202 BUILDING HEATING HOT WATER BASE MOUNTED END-SUCTION 40 75 1.25 1.26 8.5 3 1800 480 3 60 DDC ATC YES YES YES NOTE 2 BELL AND GOSSETT 1510
2. REFER TO PROJECT SPECIFICATIONS FOR ALL ADDITIONAL ACCESSORIES AND REQUIREMENTS.
1. COORDINATE FINISH WITH ARCHITECT.
NOTES:
M - CABINET UNIT HEATER SCHEDULE
TAG LOCATION TYPE
COIL DATA MOTOR DATA ELECTRICAL DATA
REMARKS
BASIS OF DESIGN
TYPE/FLUID OUTPUT (MBH)
EWT
(°F) LWT (°F)
FLUID FLOW
(GPM) HP RPM V ø Hz MANUFACTURER MODEL
CUH-38-0-01 STAIR 1 001 WALL MOUNTED, EXPOSED HOT WATER 24 140 110 1.6 1/10 1050 115 1 60 NOTES 1-2 STERLING W-06
CUH-38-0-02 STAIR 2 004 WALL MOUNTED, EXPOSED HOT WATER 24 140 110 1.6 1/10 1050 115 1 60 NOTES 1-2 STERLING W-06
CUH-38-1-01 VESTIBULE 101 WALL MOUNTED, RECESSED HOT WATER 24 140 110 1.6 1/10 1050 115 1 60 NOTES 1-2 STERLING RW-06
3. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
2. MOUNT TANK ON 4" CONCRETE HOUSING PAD. PAD IS BY GENERAL CONTRACTOR.
1. EXPANSION TANK SIZED TO SUPPORT THE NEW BUILDING AND THE FUTURE BUILDING ADDITION.
NOTES:
M - EXPANSION TANK SCHEDULE (ET)
TAG LOCATION TYPE
VOLUME
(GALLONS)
ACCEPTANCE VOLUME
(GALLONS)
DIMENSIONS
(DIA. X H) REMARKS
BASIS OF DESIGN
MFR MODEL
ET-38-2-01 MECHANICAL ROOM 202 BLADDER 86 86 24"x65" NOTES 1-3 BELL AND GOSSETT SERIES B-400
2. REFER TO PROJECT SPECIFICATIONS FOR ALL REQUIRED OPTIONS AND ACCESSORIES.
1. PROVIDE WITH DISCONNECT SWITCH.
NOTES:
M - UNIT HEATER SCHEDULE (UH)
TAG TYPE LOCATION
AIRFLOW
(CFM)
COIL DATA MOTOR DATA ELECTRICAL DATA
REMARKS
BASIS OF DESIGN
TYPE/FLUID TOTAL CAPACITY (MBH) EWT °F LWT °F GPM HP RPM V PH HZ MCA MFR MODEL
UH-38-2-01 HORIZONTAL MECHANICAL ROOM 202 750 HOT WATER 30.2 140 110 2 1/20 1000 115 1 60 1.4 NOTES 1-2 STERLING HS
UH-38-2-02 HORIZONTAL MECHANICAL ROOM 202 750 HOT WATER 30.2 140 110 2 1/20 1000 115 1 60 1.4 NOTES 1-2 STERLING HS
7. REFER TO PROJECT SPECIFICATIONS FOR ALL REQUIRED OPTIONS AND ACCESSORIES.
6. PROVIDE FLUE CONDENSATE NEUTRALIZATION EQUIPMENT.
5. PROVIDE NON-FUSED DISCONNECT SWITCH.
4. MOUNT UNIT ON 4" CONCRETE HOUSEKEEPING PAD. PAD INSTALLED BY GENERAL CONTRACTOR.
3. STANDBY BOILER.
2. BOILER TO BE FURNISHED AND INSTALLED UNDER THE FUTURE BUILDING ADDITION PROJECT. BOILER SCHEDULED FOR INFORMATIONAL PURPOSES ONLY.
1. BOILER TO BE FURNISHED AND INSTALLED UNDER THIS PROJECT.
NOTES:
M - BOILER SCHEDULE
TAG LOCATION TYPE SERVICE
OUTPUT
(MBH)
MIN.
EFF (%)
FUEL DATA ELECTRICAL
REMARKS
BASIS OF DESIGN
TYPE INPUT (SCFH) MINIMUM INLET PRESSURE (IN WC) FLA V ø Hz MANUFACTURER MODEL
BL-38-2-01 MECHANICAL ROOM 202 CONDENSING BUILDING HEATING HOT WATER 920 92 NATURAL GAS 1000 3 7 208 1 60 NOTES 1,4-7 ADVANCED THERMAL HYDRONICS KN-10
BL-38-2-02 MECHANICAL ROOM 202 CONDENSING BUILDING HEATING HOT WATER 920 92 NATURAL GAS 1000 3 7 208 1 60 NOTES 1,3-7 ADVANCED THERMAL HYDRONICS KN-10
BL-38-2-03 MECHANICAL ROOM 202 CONDENSING BUILDING HEATING HOT WATER 920 92 NATURAL GAS 1000 3 7 208 1 60 NOTE 2 ADVANCED THERMAL HYDRONICS KN-10
2. REFER TO PROJECT SPECIFICATIONS FOR ALL REQUIRED OPTIONS AND ACCESSORIES.
1. AIR SEPARATOR SIZED TO SUPPORT THE NEW BUILDING AND THE FUTURE BUILDING ADDITION.
NOTES:
M - AIR SEPARATOR SCHEDULE
TAG LOCATION TYPE
FLOWRATE
(GPM)
INLET
(IN)
OUTLET
(IN)
EFF
(%) STRAINER REMARKS
BASIS OF DESIGN
MFR MODEL
AS-38-2-01 MECHANICAL ROOM 202 TANGENTIAL CENTRIFUGAL 130 4 4 90 YES NOTES 1-2 BELL AND GOSSETT ROLAIRTROL
AS-38-2-02 MECHANICAL ROOM 202 TANGENTIAL CENTRIFUGAL 130 4 4 90 YES NOTES 1-2 BELL AND GOSSETT ROLAIRTROL
2. REFER TO PROJECT SPECIFICATIONS FOR ALL REQUIRED OPTIONS AND ACCESSORIES.
1. PROVIDE FILTER BAG KIT.
NOTES:
M - CHEMICAL POT FEEDER SCHEDULE
TAG LOCATION SERVICE REMARKS
BASIS OF DESIGN
MFR MODEL
CF-38-2-01 MECHANICAL ROOM 202 BUILDING HEATING HOT WATER NOTES 1-2 NEPTUNE DBF-5HP
CF-38-2-02 MECHANICAL ROOM 202 BUILDING COOLING CHILLED WATER NOTES 1-2 NEPTUNE DBF-5HP
5. REFER TO PROJECT SPECIFICATIONS FOR ALL REQUIRED OPTIONS AND ACCESSORIES.
4. PROVIDE WEATHERPROOF COATING.
3. PROVIDE EC MOTOR.
2. PROVIDE 24" SOUND ATTENUATING CURB. INSTALL MOTORIZED DAMPER WITHIN CURB.
1. PROVIDE EXTERIOR-MOUNTED WEATHERPROOF DISCONNECT SWITCH.
NOTES:
M - EXHAUST FAN SCHEDULE (EF)
TAG SERVES TYPE
AIRFLOW
(CFM)
ESP
(IN WG)
FAN DATA FAN MOTOR DATA HOUSING
DAMPER REMARKS
BASIS OF DESIGN
DRIVE RPM HP RPM V Ø HZ DESIGN MTL MANUFACTURER MODEL
EF-38-2-01 GENERAL EXHAUST DOWNBLAST CENTRIFUGAL 710 1 DIRECT 1712 1/4 1725 115 1 60 DOME STL MOTORIZED NOTES 1-5 GREENHECK G-VG
EF-38-2-02 MECHANICAL ROOM 202 EMERGENCY EXHAUST INLINE CENTRIFUGAL 1100 0.5 DIRECT 1602 1/4 1725 115 1 60 CABINET STL MOTORIZED NOTES 3,5 GRRENHECK SQ-VG
EF-38-2-03 RANGE HOOD EXHAUST DOWNBLAST CENTRIFUGAL 350 0.75 DIRECT 1627 1/6 1725 115 1 60 DOME STL MOTORIZED NOTES 1-5 GREENHECK G-VG
6. REFER TO PROJECT SPECIFICATIONS FOR ALL REQUIRED OPTIONS AND ACCESSORIES.
5. MOUNT ON 4" CONCRETE HOUSING PAD. PAD IS BY GENERAL CONTRACTOR.
4. RATED FOR 30% P.G. CHW.
3. PROVIDE w/ DISCONNECT SWITCH.
2. REMOTE MOUNTED VFD.
1. STANDBY PUMP.
NOTES:
M - CHILLED WATER PUMP SCHEDULE
TAG LOCATION SERVICE TYPE
FLUID
FLOWRATE
(GPM)
HEAD
(FT WG)
SUCTION
INLET
(IN)
DISCHARGE
OUTLET
(IN)
IMPELLER
DIAMETER
(IN)
MOTOR
ELECTRICAL
DATA CONTROLS
SUCTION
DIFFUSER
TRIPLE
DUTY
VALVE STRAINER NOTES
BASIS OF DESIGN
HP RPM V PH HZ TYPE
FURNISHED
BY MANUFACTURER MODEL
CHWP-38-2-01 MECHANICAL ROOM 202 BUILDING COOLING CHILLED WATER BASE MOUNTED END-SUCTION 130 115 3 2 10.625 15 1800 480 3 60 DDC ATC YES YES YES NOTES 2-6 BELL AND GOSSETT 1510
CHWP-38-2-02 MECHANICAL ROOM 202 BUILDING COOLING CHILLED WATER BASE MOUNTED END-SUCTION 130 115 3 2 10.625 15 1800 480 3 60 DDC ATC YES YES YES NOTES 1-6 BELL AND GOSSETT 1510
13. REFER TO PROJECT SPECIFICATIONS FOR ALL REQUIRED OPTIONS AND ACCESSORIES.
12. FEMP (FEDERAL ENERGY MANAGEMENT PROGRAM) CERTIFIED.
11. PROVIDE FACTORY STRAINER.
10. INSTALLED WEIGHT: APPROXIMATELY 3,200 LBS.
9. REFRIGERANT SHALL BE R-410A.
8. PROVIDE BACNET COMMUNICATION INTERFACE.
7. PROVIDE GFI CONVENIENCE OUTLET.
6. PROVIDE NON-FUSED DISCONNECT SWITCH.
5. PROVIDE SUCTION SHUT-OFF VALVES (ONE PER CIRCUIT), LIQUID LINE SHUT-OFF VALVE AND DISCHARGE SHUT-OFF VALVE.
4. PROVIDE SINGLE POINT ELECTRICAL POWER CONNECTION.
3. PROVIDE COMPRESSOR ACOUSTICAL BLANKET (SOUND INSULATION).
2. PROVIDE EPOXY COATED FINS.
1. STANDBY CHILLER.
NOTES:
M - CHILLER SCHEDULE (CH)
TAG TYPE
COOLING
REQUIRED
CAPACITY
(TONS)
EVAPORATOR DATA CONDENSER DATA COMPRESSOR DATA SOUND DATA ELECTRICAL DATA
REMARKS
BASIS OF DESIGN
FLUID
EWT
(°F)
LWT
(°F)
FLOWRATE
(GPM)
MAX. PD
(FT)
AMBIENT AIR TEMP
(°F)
CIRCUIT
QUANTITY EER
MAXIMUM
SOUND POWER
(dBA)
MAXIMUM SOUND
PRESSURE (AT 30 FT)
(dBA) VOLTS PH HZ MCA (A) MOCP (A) MANUFACTURER MODEL
CH-38-0-01 PACKAGED AIR-COOLED SCROLL 55 30% P.G. CHW 54 44 130 20 95 2 11.1 87 60 480 3 60 118 125 NOTES 2-13 DAIKIN AGZ055E
CH-38-0-02 PACKAGED AIR-COOLED SCROLL 55 30% P.G. CHW 54 44 130 20 95 2 11.1 87 60 480 3 60 118 125 NOTES 1-13 DAIKIN AGZ055E
2. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
1. MOUNT TANK ON 4" CONCRETE HOUSING PAD. PAD IS BY GENERAL CONTRACTOR.
NOTES:
M - BUFFER TANK SCHEDULE (BT)
TAG LOCATION
VOLUME
(GALLONS)
DIMENSIONS
(DIA. X H) REMARKS
BASIS OF DESIGN
MFR MODEL
BT-38-2-01 MECHANICAL ROOM 202 300 30"x72" NOTES 1-2 CEMLINE CWB
4. REFER TO PROJECT SPECIFICATIONS FOR ALL REQUIRED OPTIONS AND ACCESSORIES.
3. PROVIDE DRAIN COOLER.
2. HUMIDIFIER PACKAGE TO BE INSTALLED BY THE MECHANICAL CONTRACTOR. MECHANICAL CONTRACTOR TO ENSURE THAT HUMIDIFIER PACKAGE IS FULLY COORDINATED WITH THE ERV-38-2-01.
1. AHU VENDOR TO PROVIDE THE HUMIDIFIER EQUIPMENT PACKAGE (STEAM GENERATOR, STEAM DISPERSION GRID AND ASSOCIATED HUMIDIFIER ACCESSORIES). HUMIDIFER EQUIPMENT PACKAGE TO BE SHIPPED LOOSE.
NOTES:
M - ELECTRIC HUMIDIFIER ATMOSPHERIC STEAM GENERATOR SCHEDULE
TAG TYPE SERVES
AIRFLOW
(CFM)
EAT
(°F)
CAPACITY
(LBS/HR)
ELECTRICAL DATA CONTROLS
REMARKS
BASIS OF DESIGN
MCA V Ph HZ TYPE BY MANUFACTURER MODEL
H-38-2-01 ELECTRIC RESISTIVE ELEMENT, NON-PRESSURIZED ERV-38-2-02-01 STEAM DISPERSION GRID 16750 55 88 40.9 480 3 60 DDC ATC NOTES 1-4 PURE EC-35
7. BACKDRAFT ISOLATION DAMPER.
6. STAINLESS STEEL MOUNTING RACK.
5. REFER TO PROJECT SPECIFICATIONS FOR ALL REQUIRED OPTIONS AND ACCESSORIES. 5. STAINLESS STEEL DRAIN PAN.
4. CONTROLS PROVIDED BY ATC CONTRACTOR. 4. FILTER BANK DIFFERENTIAL PRESSURE GAUGES.
3. APPROXIMATE UNIT WEIGHT: 12,500 lbs. 3. FACTORY-MOUNTED & -WIRED DISCONNECT SWITCH.
2. DOUBLE WALL CONSTRUCTION. 2. PREMIUM EFFICIENCY MOTOR.
1. 30% O.A., VAV, ENERGY RECOVERY, SEMI-CUSTOM INDOOR AIR HANDLING UNIT. 1. SINGLE-POINT POWER CONNECTION. PROVIDE 115V CONVENIENCE OUTLET.
GENERAL NOTES: COMPONENT NOTES:
M - ENERGY RECOVERY VENTILATION UNIT SCHEDULE (ERV)
COMPONENT
TOTAL
AIRFLOW
(CFM)
MIN.
OUTDOOR
AIRFLOW
(CFM)
FAN DATA
FAN MOTOR DATA (PER
FAN) ENERGY WHEEL INFO COIL DATA FILTER DATA ELECTRICAL (PER FAN/ENERGY WHEEL)
COMPONENT
NOTESQUANTITY FAN AIRFLOW ESP (IN WC) TYPE
FAN
RPM VFD HP RPM
OUTDOOR
AIR DB
(°F)
OUTDOOR
AIR WB (°F)
EXHAUST
AIR DB
(°F)
EXHAUST
AIR WB (°F)
LDB
(°F)
LWB
(°F)
TOTAL
EXCHANGER
EFFECTIVENESS
(%) TYPE
MAXIMUM
FACE
VELOCITY
(FPM)
TOTAL
CAPACITY
(MBH)
SENSIBLE
CAPACITY
(MBH)
EDB
(°F)
EWB
(°F)
LDB
(°F)
LWB
(°F)
EWT
(°F)
LWT
(°F) GPM
MAX
WPD
(FT)
STEAM
CAPACITY
(LBS/HR) TYPE
INITIAL
PD
(IN WC)
FINAL
PD
(IN WC) V ø Hz MCA MOCP
ERV-38-2-01
DAIKIN VISION
MIXING BOX
ENERGY WHEEL - SUMMER 5025 ECM YES 1 95 75 75 62 81 66.2 54.92 115 1 60
ENERGY WHEEL - WINTER 5025 0 70 49 37.4 59.83
EXHAUST FAN ARRAY 16750 4 4188 1.75 ECM 2140 YES 6.3 2600 480 3 60 34 40 NOTES 2-3,7
ECONOMIZER
PRE-FILTER 1 (PF1) MERV 7 0.15 1 NOTE 4
PRE-FILTER 2 (PF2) MERV 11 0.37 1.5 NOTE 4
HEATING COIL HOT WATER 500 471 49 75 140 110 32 10
COOLING COIL 30% P.G. CHILLED WATER 500 650 486 81 66.2 55 54 44 54 130 10 NOTES 5-6
SUPPLY FAN ARRAY 16750 5025 4 4188 2.25 ECM 2459 YES 6.3 2600 480 3 60 34 40 NOTES 2-3
AFTER FILTER (AF) MERV 14 0.37 1.5 NOTE 4
HUMIDIFIER STEAM DISPERSION GRID 16750 5025 ATMOSPHERIC (NON-PRESSURIZED) 88
5. REFER TO PROJECT SPECIFICATIONS FOR ALL REQUIRED OPTIONS AND ACCESSORIES.
4. NEMA 4X CONTROL PANEL.
3. PROVIDE FLOAT SWITCH FOR LOW LEVEL PUMP SHUTOFF AND ALARM.
2. PROVIDE PUMP.
1. PROVIDE 55 GALLON TANK.
NOTES:
M - GLYCOL FEEDER SCHEDULE
TAG SERVICE LOCATION
PUMP DATA ELECTRICAL DATA
REMARKS
BASIS OF DESIGN
FLOWRATE
(GPM) PSI V PH HZ MFR MODEL
GF-1 BUILDING COOLING CHILLED WATER MECHANICAL ROOM 202 1.5 100 115 1 60 NOTES 1-2 NEPTUNE DBF-5HP
M - SOUND ATTENUATOR SCHEDULE
TAG TYPE SERVICE SYSTEM
AIRFLOW
(CFM)
AIR PD
(IN WG)
DIMENSIONS
LENGTH (FT)
DYNAMIC INSERTION LOSS
MANUFACTURER MODELWIDTH (IN) DEPTH (IN)
1 2 3 4 5 6 7 8
63 125 250 500 1k 2k 4k 8k
SA-1 FILM LINED AHU-1 SUPPLY 3500 0.25 24 12 5 4 4 7 14 20 21 11 5 VIBRO-ACOUSTICS RFL
SA-2 FILM LINED AHU-1 SUPPLY 13250 0.25 54 16 5 4 4 9 13 18 18 12 6 VIBRO-ACOUSTICS RFL
SA-3 FILM LINED AHU-1 RETURN 3100 0.25 32 12 3 2 4 7 11 14 21 17 8 VIBRO-ACOUSTICS RFL
SA-4 FILM LINED AHU-1 RETURN 12340 0.25 64 16 5 3 4 8 15 24 26 19 8 VIBRO-ACOUSTICS RFL
Revisions: Date:
S T
A
T E
O F
R H O D
E
I S L A
N
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
CONSULTANT ARCHITECT/ENGINEER OF RECORD
WBRC
A R C H I T E C T S • E N G I N E E R S
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
VA RI FACILITIES MANAGEMENT
SERVICE
Approved:
FULLY SPRINKLERED
NEW MENTAL HEALTH
BUILDING 38 - PHASE 1
830 CHALKSTONE AVE PROVIDENCE, RI 02908
650-332
Engineering Discipline:
/1
/2
:4
:3
P
M C
R e v it P ro je c ts
\2
\V
A M e n ta l H e a lt h \1
.0
-V
A M
C P ro v id e n c e
M e n ta l H e a lt h
B ld g
M G
R (2 rv t
MK5.1
CW MGR10 APR 2019
CONSTRUCTION
DOCUMENTS
MECHANICAL SCHEDULES
6. REFER TO PROJECT SPECIFICATIONS FOR ALL REQUIRED OPTIONS AND ACCESSORIES.
5. CONTRACTOR SHALL DETERMINE COIL HAND CONFIGURATION AMD CONTROL PANEL ACCESS.
4. PROVIDE DDC CONTROL POWER DISCONNECT.
3. PROVIDE INTEGRAL SOUND ATTENUATOR.
2. PROVIDE HOSPITAL-GRADE LINER.
1. 1- OR 2-ROW COIL AS REQUIRED TO MEET SCHEDULED CAPACITY/PERFORMANCE.
NOTES:
M - VAV TERMINAL SCHEDULE
TAG
INLET
(IN)
INLET
STATIC
PRESSURE
(IN WG)
MAXIMUM
PRESSURE
DROP
(IN WG)
MAXIMUM SOUND
RATINGS AIRFLOW DATA COIL DATA CONTROLS
REMARKS
BASIS OF DESIGN
DISCHARGE
(NC)
RADIATED
(NC)
MAXIMUM
(CFM)
HEATING
(CFM)
MINIMUM
(CFM) TYPE
TOTAL
(MBH)
EDB
(°F)
LDB
(°F)
EWT
(°F)
LWT
(°F)
FLUID FLOWRATE
(GPM)
MAX WPD
(FT) TYPE
FURNISHED
BY MANUFACTURER MODEL
VAV-38-0-01 8 1 0.25 20 20 420 235 150 HOT WATER 8.9 55 90 140 110 0.6 5 DDC ATC NOTES 1-6 TITUS DESV
VAV-38-0-02 8 1 0.25 20 20 645 550 550 HOT WATER 20.8 55 90 140 110 1.4 5 DDC ATC NOTES 1-6 TITUS DESV
VAV-38-0-03 10 1 0.25 20 20 650 350 200 HOT WATER 13.2 55 90 140 110 0.9 5 DDC ATC NOTES 1-6 TITUS DESV
VAV-38-0-04 12 1 0.25 20 20 1460 780 435 HOT WATER 29.5 55 90 140 110 2 5 DDC ATC NOTES 1-6 TITUS DESV
VAV-38-0-05 6 1 0.25 20 20 260 190 190 HOT WATER 7.2 55 90 140 110 0.5 5 DDC ATC NOTES 1-6 TITUS DESV
VAV-38-0-06 8 1 0.25 20 20 600 0 NONE DDC ATC NOTES 2-6 TITUS DESV
VAV-38-0-07 8 1 0.25 20 20 660 300 200 HOT WATER 11.3 55 90 140 110 0.8 5 DDC ATC NOTES 1-6 TITUS DESV
VAV-38-0-08 8 1 0.25 20 20 525 250 140 HOT WATER 9.5 55 90 140 110 0.7 5 DDC ATC NOTES 1-6 TITUS DESV
VAV-38-0-09 6 1 0.25 20 20 265 220 220 HOT WATER 8.3 55 90 140 110 0.6 5 DDC ATC NOTES 1-6 TITUS DESV
VAV-38-0-10 10 1 0.25 20 20 750 400 275 HOT WATER 15.1 55 90 140 110 1.1 5 DDC ATC NOTES 1-6 TITUS DESV
VAV-38-0-11 10 1 0.25 20 20 750 400 275 HOT WATER 15.1 55 90 140 110 1.1 5 DDC ATC NOTES 1-6 TITUS DESV
VAV-38-1-01 12 1 0.25 20 20 1300 605 270 HOT WATER 22.9 55 90 140 110 1.6 5 DDC ATC NOTES 1-6 TITUS DESV
VAV-38-1-02 10 1 0.25 20 20 730 400 400 HOT WATER 15.1 55 90 140 110 1.1 5 DDC ATC NOTES 1-6 TITUS DESV
VAV-38-1-03 8 1 0.25 20 20 620 350 200 HOT WATER 13.2 55 90 140 110 0.9 5 DDC ATC NOTES 1-6 TITUS DESV
VAV-38-1-04 8 1 0.25 20 20 530 300 160 HOT WATER 11.3 55 90 140 110 0.8 5 DDC ATC NOTES 1-6 TITUS DESV
VAV-38-1-05 14 1 0.25 20 20 1735 1000 525 HOT WATER 37.8 55 90 140 110 2.6 5 DDC ATC NOTES 1-6 TITUS DESV
VAV-38-1-06 6 1 0.25 20 20 135 105 105 HOT WATER 4 55 75 140 110 0.2 5 DDC ATC NOTES 1-6 TITUS DESV
VAV-38-1-07 6 1 0.25 20 20 220 200 140 HOT WATER 7.6 55 90 140 110 0.5 5 DDC ATC NOTES 1-6 TITUS DESV
VAV-38-1-08 6 1 0.25 20 20 220 200 140 HOT WATER 7.6 55 90 140 110 0.5 5 DDC ATC NOTES 1-6 TITUS DESV
VAV-38-1-09 10 1 0.25 20 20 660 400 200 HOT WATER 15.1 55 90 140 110 1 5 DDC ATC NOTES 1-6 TITUS DESV
VAV-38-1-10 8 1 0.25 20 20 410 150 250 HOT WATER 9.5 55 90 140 110 0.7 5 DDC ATC NOTES 1-6 TITUS DESV
VAV-38-1-11 6 1 0.25 20 20 305 230 115 HOT WATER 8.7 55 90 140 110 0.6 5 DDC ATC NOTES 1-6 TITUS DESV
VAV-38-1-12 6 1 0.25 20 20 320 185 320 HOT WATER 7 55 75 140 110 0.4 5 DDC ATC NOTES 1-6 TITUS DESV
VAV-38-1-13 8 1 0.25 20 20 500 325 150 HOT WATER 12.3 55 90 140 110 0.4 5 DDC ATC NOTES 1-6 TITUS DESV
VAV-38-1-14 8 1 0.25 20 20 500 325 220 HOT WATER 12.6 55 90 140 110 0.9 5 DDC ATC NOTES 1-6 TITUS DESV
VAV-38-1-15 6 1 0.25 20 20 285 200 200 HOT WATER 7.6 55 90 140 110 0.5 5 DDC ATC NOTES 1-6 TITUS DESV
VAV-38-1-16 8 1 0.25 20 20 600 350 200 HOT WATER 13.2 55 90 140 110 0.9 5 DDC ATC NOTES 1-6 TITUS DESV
VAV-38-1-17 8 1 0.25 20 20 330 330 120 HOT WATER 12.5 55 90 140 110 0.9 5 DDC ATC NOTES 1-6 TITUS DESV
VAV-38-2-01 8 1 0.25 20 20 500 500 150 HOT WATER 18.9 55 90 140 110 1.3 5 DDC ATC NOTES 1-6 TITUS DESV
VAV-38-2-02 6 1 0.25 20 20 170 170 100 HOT WATER 6.4 55 90 140 110 0.5 5 DDC ATC NOTES 1-6 TITUS DESV
9. REFER TO PROJECT SPECIFICATIONS FOR ALL REQUIRED OPTIONS AND ACCESSORIES.
8. TRIM BLANKING PLATE AS REQUIRED TO FIT GRILLE WITHIN CEILING GRID.
7. EACH SLOT SHALL HAVE INDIVIDUAL ADJUSTABLE SLOT VANE.
6. INSTALL CONTINUOUS PLENUM. PLENUM BY MECH. CONTRACTOR.
5. MFR TO PROVIDE UN-INSUALTED PLENUM (TITUS MP).
4. REFER TO HVAC PLANS FOR NECK SIZES.
3. REFER TO HVAC PLANS FOR DISCHARGE ORIENTATIONS.
2. COORDINATE FINISH WITH ARCHITECTURAL DOCUMENTS.
1. COORDINATE MOUNTING STYLE WITH ARCHITECTURAL DOCUMENTS.
NOTES:
M - REGISTER, GRILLE AND DIFFUSER SCHEDULE (R-G-D)
TAG SYSTEM TYPE MOUNTING FACE TYPE FACE BAR
SLOT DATA MFR PLENUM DATA
MATERIAL FINISH DAMPER TYPE REMARKS
BASIS OF DESIGN
QTY W (IN)
L
(IN)
DUCT CONNECTION SIZE
(" DIA.) MFR MODEL
SD-A SUPPLY DIFFUSER CEILING, NOTE 1 24"x24" SQUARE LOUVERED AL NOTE 2 NONE NOTES 3-4,9 TITUS TDC-AA
SG-A SUPPLY GRILLE WALL, NOTE 1 SQUARE OR RECT. 35° DEFLECTION AL NOTE 2 NONE NOTES 3-4,9 TITUS 272FL
LD-B SUPPLY DIFFUSER CEILING, NOTE 1 LINEAR LINEAR 4 1 48 8 AL NOTE 2 NONE NOTES 3-5,9 TITUS ML-39
LD-C SUPPLY DIFFUSER CEILING, NOTE 1 LINEAR LINEAR 2 1 48 AL NOTE 2 NONE NOTES 1-4,6-7,9 TITUS FL-TZ
RG-A RETURN GRILLE CEILING, NOTE 1 24"x24" SQUARE 35° DEFLECTION AL NOTE 2 NONE NOTES 3-4,9 TITUS 355FL
RG-B RETURN GRILLE CEILING, NOTE 1 RECT. 35° DEFLECTION AL NOTE 2 NONE NOTES 3-4,8-9 TITUS 355FL
RG-C RETURN GRILLE WALL, NOTE 1 RECT. 35° DEFLECTION AL NOTE 2 NONE NOTES 3-4,9 TITUS 355FL
EG-A EXHAUST GRILLE CEILING, NOTE 1 12"x12" SQUARE 35° DEFLECTION AL NOTE 2 NONE NOTES 3-4,9 TITUS 355FL
EG-B EXHAUST GRILLE CEILING, NOTE 1 24"x24" SQUARE 35° DEFLECTION AL NOTE 2 NONE NOTES 3-4,9 TITUS 355FL
EG-C EXHAUST GRILLE CEILING, NOTE 1 RECT. 35° DEFLECTION AL NOTE 2 NONE NOTES 3-4,8-9 TITUS 355FL
1. REFER TO PROJECT SPECIFICATIONS FOR ALL ADDITIONAL REQUIRED OPTIONS AND ACCESSORIES.
NOTE:
M - LOUVER SCHEDULE (LU)
TAG TYPE
AIRFLOW DATA DIMENSIONS
MIN. FREE AREA
(SQ. FT)
BASIS OF DESIGN
AIRFLOW
(CFM)
MAX. FACE VELOCITY
(FPM)
WIDTH
(IN)
HEIGHT
(IN)
DEPTH
(IN) MANUFACTURER MODEL
LU-38-2-01 INTAKE 2795 500 22 72 4 5.5 GREENHECK EDJ
LU-38-2-02 RELIEF 6925 750 43 61 4 9.7 GREENHECK EDJ
LU-38-2-03 RELIEF 2900 750 19 61 4 3.9 GREENHECK EDJ
7. REFER TO SPECIFICATIONS FOR ALL REQUIRED OPTIONS AND ACCESSORIES.
7. ENERGY STAR CERTIFIED.
6. PROVIDE LOW AMBIENT CONTROL (DOWN TO -4°F) WITH WIND BAFFLES.
5. PROVIDE WITH INTEGRAL CONDENSATE PUMP.
4. MOUNT OUTDOOR UNIT ON ROOF-TOP ISOLATED SPRING RAILS.
3. PROVIDE WITH DISCONNECT FOR OUTDOOR UNIT.
2. INDOOR AND OUTDOOR UNITS POWERED SEPARATELY.
1. OUTDOOR UNIT PROVIDES POWER TO THE INDOOR UNIT.
NOTES:
M -SPLIT SYSTEM SCHEDULE (AC/CU)
INDOOR UNIT OUTDOOR UNIT
REMARKSTAG TYPE
CAPACITY DATA FAN DATA
V PH HZ MCA MOCP
BASIS OF DESIGN
TAG
GENERAL DATA
V PH HZ MCA MOCP
BASIS OF DESIGN
TOTAL COOLING
(MBH)
AIR FLOW
(CFM) MANUFACTURER MODEL
MAX. AMBIENT
(°F) SEER MANUFACTURER MODEL
AC-38-1-01 CEILING CONCEALED, DUCTED 18 582 208 1 60 1.8 15 DAIKIN FBQ CU-38-2-02 95 17.5 208 1 60 16.5 20 DAIKIN RZR NOTES 2-6,8
AC-38-1-02 CEILING CONCEALED, DUCTED 18 582 208 1 60 1.8 15 DAIKIN FBQ CU-38-2-02 95 17.5 208 1 60 16.5 20 DAIKIN RZR NOTES 2-6,8
Revisions: Date:
S T
A
T E
O F
R H O D
E
I S L A
N
NO SCALE
SEISMIC
230548-01
7x19
AIRCRAFT
CABLE (TYP.)
WASHER
STEEL ANGLE
CLIP
CABLE THIMBLE
ALT. DETAIL-A
BUILDING
STEEL
LOOP SLEEVE
CABLE
RESTRAINTS
(TYP.)
LOCK WASHER (TYP.)
NUT & BOLT
ATTACHMENTS
(TYP.)
45°
DETAIL "A" - BOLTED RESTRAINTS
230548-02
NO SCALE
SEISMIC
BEAM OR TRUSS
DOUBLE SIDED BEAM CLAMP
SEISMIC CABLE
DETAIL "A" - CLAMPED TO BEAM RESTRAINTS
EQUIPMENT LEG/RAIL/BASE
230548-07
NO SCALE
BASE MOUNTED VIBRATION ISOLATOR DETAIL
EQUIPMENT SUPPORT/PAD
LEVELING BOLT WITH WASHER
SQUARE BASE PLATE ON
TWO RIBBED OR WAFFLE
PATTERN NEOPRENE
ACOUSTICAL PADS
SEPARATED BY A 16 GAUGE
STAINLESS STEEL PLATE
FREE STANDING
LATERALLY STABLE
UNHOUSED STEEL
SPRING ISOLATOR
HEIGHT SAVING
CANTILEVERED
STEEL MOUNTING
BRACKET
VIBRATION ISOLATION HANGER DETAIL
2.
NOTE:
1.
HANGER SIZE SHALL BE AS PER MANUFACTURER'S RECOMMENDATIONS
AND ACCORDING TO THE LOAD OF THE EQUIPMENT.
230548-08
NO SCALE
ALL AIR HANDLING EQUIPMENT SUSPENDED FROM STRUCTURES
AND ALL STEAM AND CHILLED WATER PIPING IN MECHANICAL
ROOMS SHALL BE HUNG WITH VIBRATION ISOLATORS.
HANGER ROD
30° MISALIGNMENT
CAPABILITY
LOCKNUT
HANGER ROD
D…