The Department of Veterans Affairs (VA) solicitation provides details for the Construction of a New Mental Health Building project located at 830 Chalkstone Ave, Providence, RI 02908. The solicitation seeks a single, Firm-Fixed-Price contract to complete construction of a new approximately 15,300 SF freestanding three-story building to house mental health programs on the Providence VAMC campus. The project includes general construction, site work including demolition and new utilities, with a period of performance of approximately 600 calendar days from notice to proceed. The solicitation will be issued as a total Service-Disabled Veteran-Owned Small Business set-aside, with offers from other than SDVOSB concerns not considered. The solicitation is expected to be released on or about December 20, 2019, with a magnitude of construction between $10-20 million. All questions must be submitted in writing by the specified deadline.
36E77620R0001 Attachment 2 - CD Drawings - General.pdf
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
CONSULTANT ARCHITECT/ENGINEER OF RECORD
WBRC
A R C H I T E C T S • E N G I N E E R S
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title
Approved:
Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
U.S. DEPARTMENT OF
VETERANS AFFAIRS
/2
/2
:4
:3
P M
C
U s e rs
\j o c e ly n
.b o o th e \D o c u m e n ts \4
V A
M H
P R
O V
ID
E
N C
E M
H C
A
R C
H jo c e ly n .b o o th e
.r v t
GI001
650-332
NEW MENTAL HEALTH BUILDING -
PHASE 1
830 CHALKSTONE AVE PROVIDENCE, RI 02908
JRB BRS10 APR 2019
CONSTRUCTION
DOCUMENTS
COVER SHEET
CONSULTANT DISCIPLINE:
FULLY SPRINKLERED
VA RI FACILITIES MANAGEMENT
SERVICE
NEW MENTAL HEALTH BUILDING - PHASE 1
830 CHALKSTONE AVE PROVIDENCE, RI 02908
PROJ. NO. 650-332
DRAWING LIST
SHEET NUMBER SHEET NAME
PLUMBING DRAWINGS
PJ0.0 PLUMBING - LEGEND
PP1.0 PLUMBING - BASEMENT - DOMESTIC WATER PLAN
PP1.1 PLUMBING - FIRST FLOOR - DOMESTIC WATER PLAN
PP1.2 PLUMBING - SECOND FLOOR - DOMESTIC WATER PLAN
PW1.0 PLUMBING - BASEMENT - DRAINAGE PLAN
PW1.1 PLUMBING - FIRST FLOOR - DRAINAGE PLAN
PW1.2 PLUMBING - SECOND FLOOR - DRAINAGE PLAN
PW1.3 PLUMBING - ROOF PLAN
PK0.0 PLUMBING DETAILS
MECHANICAL DRAWINGS
MJ.0 MECHANICAL LEGEND
MH1.0 MECHANICAL BASEMENT DUCTWORK PLAN
MH1.1 MECHANICAL FIRST FLOOR DUCTWORK PLAN
MH1.2 MECHANICAL SECOND FLOOR AND ROOF DUCTWORK PLANS
MH1.3 MECHANICAL PENTHOUSE ROOF DUCTWORK PLAN
MP1.0 MECHANICAL BASEMENT PIPING PLAN
MP1.1 MECHANICAL FIRST FLOOR PIPING PLAN
MP1.2 MECHANICAL SECOND FLOOR AND ROOF PIPING PLAN
MK5.0 MECHANICAL SCHEDULES
MK5.1 MECHANICAL SCHEDULES
ML6.0 MECHANICAL DETAILS
ML6.1 MECHANICAL DETAILS
ML6.2 MECHANICAL DETAILS
MM7.0 MECHANICAL HOT WATER PIPING SCHEMATIC
MM7.1 MECHANICAL CHILLED WATER PIPING SCHEMATIC
MM7.2 MECHANICAL ROOM DATA
MI0.0 MECHANICAL CONTROLS
MI0.1 MECHANICAL CONTROLS
MI0.2 MECHANICAL CONTROLS
MI0.3 MECHANICAL CONTROLS
MI0.4 MECHANICAL CONTROLS
MI0.5 MECHANICAL CONTROLS
MI0.6 MECHANICAL CONTROLS
MI0.7 MECHANICAL CONTROLS
MI0.8 MECHANICAL CONTROLS
ELECTRICAL DRAWINGS
EJ0.0 ELECTRICAL - LEGEND
ES0.0 ELECTRICAL - SITE PLAN
ES0.1 LIGHTNING PROTECTION PLAN
EL1.0 ELECTRICAL - BASEMENT - LIGHTING PLAN
EL1.1 ELECTRICAL - FIRST FLOOR - LIGHTING PLAN
EL1.2 ELECTRICAL - SECOND FLOOR - LIGHTING PLAN
EP1.0 ELECTRICAL - BASEMENT - POWER PLAN
EP1.1 ELECTRICAL - FIRST FLOOR - POWER PLAN
EP1.2 ELECTRICAL - SECOND FLOOR - POWER PLAN
EK0.0 ELECTRICAL - RISER DIAGRAMS I
EK0.1 ELECTRICAL - RISER DIAGRAMS II
EK0.2 ELECTRICAL SCHEDULES
EK1.0 ELECTRICAL - DETAILS
EK1.1 ELECTRICAL - DETAILS
PHYSICAL SECURITY DRAWINGS
EY101 SECURITY DEVICES - BASEMENT FLOOR PLAN
EY102 SECURITY DEVICES - FIRST FLOOR PLAN
EY103 SECURITY DEVICES - SECOND FLOOR PLAN
EY501 SECURITY DEVICES - SCHEDULES AND SCHEMATICS
DRAWING LIST
SHEET NUMBER SHEET NAME
AE201 BUILDING ELEVATIONS
AE202 BUILDING ELEVATIONS
AE203 3D VIEWS
AE204 INTERIOR ELEVATIONS
AE205 LOBBY INTERIOR ELEVATIONS
AE206 INTERIOR ELEVATIONS
AE301 BUILDING SECTIONS
AE302 BUILDING SECTIONS
AE303 WALL SECTIONS
AE304 WALL SECTIONS
AE305 WALL SECTIONS
AE306 WALL SECTIONS
AE307 WALL SECTIONS
AE401 ENLARGED RESTROOM PLANS & INTERIOR ELEVATIONS
AE402 STAIR 1 AND ELEVATORS PLANS
AE403 STAIR 1 AND ELEVATORS SECTIONS AND DETAILS
AE404 STAIR 2 SECTIONS AND PLANS
AE405 STAIR DETAILS
AE501 PLAN DETAILS
AE502 PLAN DETAILS
AE510 SECTION DETAILS
AE511 SECTION DETAILS
AE512 SECTION DETAILS
AE513 SECTION DETAILS
AE514 SECTION DETAILS
AE515 PRECAST PROFILES
AE520 INTERIOR DETAILS
AE521 INTERIOR DETAILS
AE601 PARTITION TYPES AND DETAILS
AE602 EXTERIOR WALL TYPES AND DETAILS
AE603 ROOF TYPES AND DETAILS
AE604 DOOR TYPES, DETAILS AND SCHEDULE
AE605 DOOR DETAILS
AE606 WINDOW TYPES AND DETAILS
AE607 STOREFRONT DETAILS
AE608 STOREFRONT DETAILS
AE609 CURTAIN WALL DETAILS
AF100 BASEMENT FINISH PLAN
AF101 FIRST FLOOR FINISH PLAN
AF102 SECOND FLOOR FINISH PLAN
AF103 BASEMENT SIGNAGE PLAN
AF104 FIRST FLOOR SIGNAGE PLAN
AF105 SECOND FLOOR SIGNAGE PLAN
AF600 FINISH SCHEDULE & DETAILS
AF700 BASEMENT EQUIPMENT PLAN
AF701 FIRST FLOOR EQUIPMENT PLAN
FIRE PROTECTION DRAWINGS
FP100 BASEMENT FIRE PROTECTION PLANS
FP101 FIRST FLOOR FIRE PROTECTION PLANS
FP102 SECOND FLOOR FIRE PROTECTION PLANS
FP500 FIRE PROTECTION DETAILS
FIRE ALARM DRAWINGS
FA001 FIRE ALARM GENERAL INFORMATION
FA100 BASEMENT FIRE ALARM PLANS
FA101 FIRST FLOOR FIRE ALARM PLANS
FA102 SECOND FLOOR FIRE ALARM PLANS
FA600 FIRE ALARM RISER DIAGRAM
DRAWING LIST
SHEET NUMBER SHEET NAME
GENERAL DRAWINGS
GI001 COVER SHEET
GI002 SYMBOLS, ABBREVIATIONS AND GENERAL NOTES
GI003 FIRESTOP DETAILS
LIFE SAFETY DRAWINGS
LS101 LIFE SAFETY
LS102 LIFE SAFETY
CIVIL DRAWINGS
C-001 SITE GENERAL NOTES & ABBREVIATIONS
CS101 SITE EXISTING CONDITIONS PLAN
CD101 SITE REMOVALS PLAN
CP101 SITE LAYOUT & MATERIALS PLAN
CP301 PLAZA INSET PLAN
CG101 SITE GRADING & EROSION CONTROL PLAN
CG301 SITE SECTION AA’
CG302 SITE SECTION BB'
CU101 SITE UTILITY PLAN
LP101 SITE PLANTING PLAN
C-501 SITE DETAILS
C-502 SITE DETAILS
C-503 SITE DETAILS
C-504 SITE DETAILS
C-505 SITE DETAILS
C-506 SITE DETAILS
C-601 SITE BORING LOGS
C-602 SITE BORING LOGS
C-603 SITE BORING LOGS
STRUCTURAL DRAWINGS
SS001 GENERAL NOTES
SB100 FOUNDATION PLAN
SB300 TYPICAL FOUNDATION DETAILS
SB301 FOUNDATION SECTIONS & DETAILS
SB302 FOUNDATION SECTIONS & DETAILS
SB303 CMU SECTIONS AND DETAILS
SF101 FIRST FLOOR FRAMING PLAN
SF102 SECOND FLOOR/ROOF FRAMING PLANS
SF500 TYPICAL FRAMING DETAILS
SF501 FRAMING SECTIONS & DETAILS
SF502 FRAMING SECTIONS & DETAILS
ARCHITECTURAL DRAWINGS
AE100 BASEMENT FLOOR REFERENCE PLANS
AE100A BASEMENT FLOOR PLANS
AE101 FIRST FLOOR REFERENCE PLAN
AE101A FIRST FLOOR PLANS
AE102 SECOND FLOOR REFERENCE PLAN
AE102A SECOND FLOOR PLAN
AE103 ROOF PLAN
AE110 BASEMENT REFLECTED CEILING PLANS
AE111 FIRST FLOOR REFLECTED CEILING PLANS
AE112 SECOND FLOOR REFLECTED CEILING PLAN
Revisions: Date:
NOTE: REFER TO STRUCTURAL, LIFE SAFETY, FIRE
PROTECTION, CIVIL, PSDM, MECHANICAL,
AND/OR ELECTRICAL DRAWINGS FOR
ABBREVIATIONS SPECIFIC TO EACH DISCIPLINE.
AB ANCHOR BOLT, AUGER BORING
ABI ALTERNATE BID ITEM
AC ACOUSTIC AIR CONDITIONING, ASPHALTIC CONCRETE
AD ACCESS DOOR
ADD ALT ADDITIVE ALTERNATE
ADJ ADJUSTABLE
AED AUTOMATED EXTERNAL DEFIBRILLATOR
AFF ABOVE FINISH FLOOR
AHU AIR HANDLING UNIT
ALT ALTERNATE
ALUM ALUMINUM
ANOD ANODIZE
AP ACCESS PANEL
APC ACOUSTIC PANEL CEILING
APPROX APPROXIMATE
ARCH ARCHITECTURAL
ASB ASBESTOS
ASPH ASPHALT
AUTO AUTOMATIC
AWP ACOUSTIC WALL PANEL
AVB AIR/VAPOR BARRIER
BDRM BEDROOM
BIT. CONC BITUMINOUS CONCRETE
BJ BAR JOIST
BLDG BUILDING
BLK BLOCK
BM BEAM, BENCHMARK
BOT BOTTOM
BRD BOARD
BRG BEARING
BS BOTTOM OF STEP
BSMT BASEMENT
BTWN BETWEEN
BW BOTTOM OF WALL
CAB CABINET
CAP CAPACITY
CC CENTER TO CENTER
CEM CEMENT
CFM CUBIC FEET PER MINUTE
CFS CUBIC FEET PER SECOND
CG CORNER GUARD
CI CAST IRON
CIR CIRCULATING
CJ CONSTRUCTION JOINT, CONTROL JOINT
CLG CEILING
CLO CLOSET
CLR CLEAR
CENTERLINE
CMU CONCRETE MASONRY UNITS
CMU G1 GLAZED CMU, ONE SIDE
CMU G2 GLAZED CMU, TWO SIDES
CO CLEANOUT
COL COLUMN
COMP'T COMPARTMENT
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CPT CARPET
CS/CI CONTRACTOR SUPPLIED/ CONTRACTOR INSTALLED
CS/OI CONTRACTOR SUPPLIED/OWNER INSTALLED
CSK COUNTER SINK
CT CERAMIC TILE
CTE CONNECT TO EXISTING
CTR CENTER
CUH CABINET UNIT HEATER
O DIAMETER
DF DRINKING FOUNTAIN
DFD DOOR FRAME DIMENSION
DH DOUBLE HUNG
DIA DIAMETER
DIM DIMENSION
DN DOWN
DTL DETAIL
DWG DRAWING
E EAST
EA EACH
EL, ELEV ELEVATION
ELEC ELECTRIC
EMERG EMERGENCY
EPS EXTRUDED POLYSTYRENE
EQ EQUAL
EQUIP EQUIPMENT
ETC ETCETERA
EW EACH WAY
EXIST EXISTING
EXP EXPANSION, EXPOSED
EXP JT EXPANSION JOINT
EXT EXTERIOR
FBO FURNISHED BY OTHERS
FCO FLOOR CLEAN-OUT
FD FLOOR DRAIN, FOOTING DRAIN
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISH FLOOR
FFE FINISHED FLOOR ELEVATION
FG FINISH GRADE, FIBERGLASS
FHC FIRE HOSE CABINET
FIG FIGURE
FIN FINISH
FO FUEL OIL
FOC FACE OF CMU
FOF FACE OF FOUNDATION
FOR FUEL OIL RETURN
FOS FACE OF STUD, FUEL OIL SUPPLY
FOUND FOUNDATION
FP FIREPROOF
FR FRAME, FIRE RESISTANT
FS FLOOR SINK
FT FOOT, FEET, FINNED TUBE
FTG FOOTING
FWP FABRIC WALL PANEL
GA GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GF/GI GOVT. FURNISHED/GOVT. INSTALLED
GF/CI GOVT. FURNISHED/CONTRACTOR INSTALLED
GI GALVANIZED IRON
GOV'T GOVERNMENT
GPM GALLONS PER MINUTE
GR GRADE
GRAN GRANULAR
GRD GROUND
GWB GYPSUM WALLBOARD
GYP GYPSUM
HGT HEIGHT
H&V HEATING AND VENTILATING
HB HOSE BIB
HC HANDICAPPED
HCWD HOLLOW CORE WOOD DOOR
HDC HANDICAPPED
HDW HARDWARE
HDWD HARDWOOD
HM HOLLOW METAL
HOR HORIZONTAL
HVAC HEATING, VENTILATING, AND AIR CONDITIONING
IN INSIDE DIAMETER
INCL INCLUSIVE
INFO INFORMATION
INSUL INSULATION, INSULATED
INT INTERIOR
IWP IMPACT RESISTANT WALL PROTECTION
JAN JANITOR CLOSET
JCT JUNCTION
KV KILOVOLT
KW KILOWATT
LAB LABORATORY
LAV LAVATORY
LBS POUNDS
LF LINEAR FEET
LFC LINOLEUM FLOOR COVERING
LGR LEDGER
LP LOW POINT
LR LIVING ROOM
LT LIGHT
LWC LIGHT WEIGHT CONCRETE
MACH MACHINE
MANUF MANUFACTURER
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MB MARKER BOARD
MC MEDICINE CABINET
MCB METAL CORNER BEAD
MECH MECHANICAL
MIN MINIMUM
MIR MIRROR
MISC MISCELLANEOUS
MM MILLIMETER
MO MASONRY OPENING
MR MOISTURE RESISTANT
MS METAL STRIP
MTD MOUNTED
MTL METAL
N NORTH
N.I.C. NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OA OVER ALL
OB GL OBSCURE GLASS
OC ON CENTER
OD OUTSIDE DIAMETER
OPNG OPENING
OPP OPPOSITE
OS/CI OWNER SUPPLIED/CONTRACTOR INSTALLED
OS/OI OWNER SUPPLIED/OWNER INSTALLED
OVHD, OH OVERHEAD
P-1 PLUMBING FIXTURE TYPE
PART PARTITION
PL PLATE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLAST PLASTIC
PLYWD PLYWOOD
PNL PANEL
PNTD PAINTED
POL POLISHED
PRELIM PRELIMINARY
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PAINT, POINT, PRESSURE TREATED
PT DISP PAPER TOWEL DISPENSER
PVC POLY VINYL CHLORIDE
PVMT PAVEMENT
QT QUARRY TILE
R RADIUS, RISER
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN, ROAD
RECEP RECEPTACLE
REF REFRIGERATOR
REINF REINFORCEMENT
REQ'D REQUIRED
REV REVISION
RF RESINOUS FLOOR
RL RAIN LEADER
RM ROOM
RO ROUGH OPENING
RS RESILIENT STAIR ACCESSORY
RSR RISER
RT RUBBER TILE
S SOUTH
S DISP SOAP DISPENSER
S&V STAIN AND VARNISH
SCONC SEALED CONCRETE
SCWD SOLID CORE WOOD DOOR
SCH SCHEDULE
SCR SUPPLY CEILING REGISTER
SECT SECTION
SF SQUARE FEET
SH SINGLE HUNG
SHT SHEET
SIM SIMILAR
SL SLOPE
SPECS SPECIFICATIONS
SQ SQUARE
SQ FT SQUARE FEET
SS SERVICE SINK, SANITARY SEWER, STAINLESS STEEL
SSURF SOLID SURFACE
ST STREET
STA STATION
STD STANDARD
SSTL STAINLESS STEEL
STL STEEL
STOR STORAGE
STRUCT STRUCTURAL
SUP SUPPORT
SUSP SUSPEND
SV SHEET VINYL
SYM SYMMETRICAL
T TOP, TANGENT, THERMOMETER
TB TACK BOARD
TBA TOILET BATH ACCESSORIES
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
T.O.C. TOP OF CONCRETE
T.O.M. TOP OF MASONRY
T.O.S. TOP OF STEEL
T.O.W. TOP OF WALL
TEL TELEPHONE
TEMP TEMPERATURE, TEMPORARY
TERM TERMINAL
THK THICK
THRU THROUGH
TP TOILET PARTITION
TPH TOILET PAPER HOLDER
TRAN TRANSOM
TRD TREAD
TS TOP OF STEP, TOP OF SILL
TV TELEVISION
TYP TYPICAL
TYPE "X" UL APPROVED GWB
U&D UP AND DOWN
UC UNDERCUT
UV UNIT VENTILATOR
VB VAPOR BARRIER
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
VTR VENT THROUGH ROOF
W WEST
WAIN WAINSCOT
WB RESILIENT WALL BASE
WC WALL COVERING
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WD WIDTH, WINDOW DIMENSION, WOOD
WGL WIRE GLASS
WP WATERPROOF, WEATHERPROOF
WS WEATHERSTRIPPING
WT WEIGHT
WW WELDED WIRE FABRIC
ROWS IDENTIFIED BY
LETTERS INCREASING
TOWARD THE TOP OF
SHEET
DRAWING
REFERENCED
FROM ANOTHER
SHEET
DRAWING TITLE
DRAWING COORDINATE
INDICATOR
SCALE OF DRAWING
COLUMNS IDENTIFIED BY
NUMBERS INCREASING TOWARD
THE RIGHT SIDE OF SHEET.
A
B
C
1 2 3 4
A1 1/8" = 1'-0"
VIEW NAME
R101
SCALE: 1/8" = 1'-0"
4' 8'0 16'
B3
D
C
B
A
SHEET NUMBER DETAIL
IS DRAWN ON
ROOM NAME
ROOM NUMBER
BREAK LINE
GRAPHIC SCALE
REVISION NUMBER
REVISION CLOUD
ELEVATION MARKER - SECTION
ELEVATION MARKER - PLAN
DOOR
NUMBER
REFERENCE
WINDOW TYPE REFERENCE
WALL TYPE REFERENCE
COLUMN GRID REFERENCE
SHEET NUMBER ELEVATION
IS DRAWN ON
INTERIOR ELEVATION
REFERENCE
BUILDING / WALL
SECTION
NUMBER
SHEET NUMBER BUILDING /
WALL SECTION IS DRAWN
ON
BUILDING ELEVATION
NUMBER
SHEET NUMBER
ELEVATION IS DRAWN ON
MATCH LINE
2 HOUR RATED PARTITION
1 HOUR RATED PARTITION
(PLANS & SECTIONS)
DETAIL NUMBER
SYMBOLS
LINETYPES
SMOKE PARTITION
STEEL & OTHER METAL PATTERN
CONCRETE BLOCK PATTERN
STONE CUT PATTERN
TERRA COTTA
CARPET AND PAD PATTERN
TILE,
ACOUSTICAL
CEILING
PATTERN
WOOD FLOORING PATTERN
BRICK PATTERN, GLAZED
SAND CLAY GRAVEL PATTERN
BRICK PATTERN
EROSION AND
SEDIMENTATION
CONTROL,
FILTRATION BED PATTERN
EARTHWORK GRAVEL
PATTERN, POROUS
FILL
EARTHWORK ROCK PATTERN
EARTHWORK PATTERN,
COMPACTED FILL
PATTERN
RIPRAP PATTERN
SAND PATTERN
GLASS ELEVATION PATTERN
GYPSUM BOARD FINISH PATTERN
SEALANT AND BACKER ROD
INSULATION,
RIGID
BOARD PATTERN
INSULATION,
LOOSE
FILL PATTERN
WOOD FINISH PATTERN
PARTICLE BOARD PATTERN
ORIENTED STRAND BOARD PATTERN
WOOD, GLUED-LAMINATED PATTERN
WOOD FRAMING,
CONTINUOUS
PATTERN
WOOD BLOCKING OR SHIM PATTERN
HATCH PATTERNS
EARTH, UNDISTURBED PATTERN
EARTH, CRUSHED
ROCK
GRAVEL PATTERN
EARTH, CRUSHED
ROCK
GRAVEL PATTERN
PLYWOOD PATTERN
10'-0"
Room name
B
A101
SIM
CONCRETE POURED IN
PLACE, PRECAST
ALUMINUM PATTERN
ASPHALT SHINGLE PATTERN
A101
1 1
A1
AE101
A101
SIM
BUILDING / WALL
SECTION
NUMBER
SHEET NUMBER BUILDING /
WALL SECTION IS DRAWN
ON
1 HOUR RATED PARTITION
(PLAN & SECTION DETAILS)
M2
KEY NOTE REFERENCE
FX
GENERAL NOTES:
1. ALL WALL PARTITION TYPES ARE M4 UNLESS NOTED OTHERWISE. SEE SHEETAE601 FOR PARTITION
TYPES.
2. REFER TO GI002 SHEET FOR ALL ABBREVIATIONS AND SYMBOLS.
3. REFER TO ALL DRAWINGS INCLUDING ARCHITECTURAL, CIVIL, STRUCTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR ADDITIONAL GENERAL NOTES, ABBREVIATIONS, AND SYMBOLS
4. VERIFY ALL EQUIPMENT OPENINGS & RECOMMENDATIONS. LOCATION AND SIZES SHOWN ARE FOR
INTENT PURPOSES ONLY. ADJUST ROUGH OPENINGS AND LOCATIONS AS REQUIRED PER ACTUAL
EQUIPMENT.
5. DOOR JAMBS ARE 6" FROM NEAREST ADJACENT INTERSECTING PARTITION UNLESS NOTED
OTHERWISE. SEE DOOR DETAILS FOR FURTHER INFORMATION
6. G.C. TO PROVIDE & INSTALL ALL IN-WALL OR IN-CEILING BLOCKING / BRACING AS REQUIRED FOR ALL MILLWORK ITEMS, EQUIPMENT, SHELVING, AND ACCESSORIES WHETHER ITEMS ARE BY G.C. OR
OTHERS COORDINATE WITH OWNER
7. G.C. SHALL BE RESPONSIBLE FOR LAYING OUT THE SPACE PRIOR TO COMMENCING WORK AND
SHALL NOTIFY THE ARCHITECT AND OWNER OF ANY DISCREPANCIES.
8. ALL CONCRETE MASONRY UNITS AND MORTAR TO INCLUDE AN INTEGRAL WATER REPELLENT
9. REFER TO SHEET AE604 FOR DOOR SCHEDULE AND FRAMING TYPES.
10. REFER TO SHEET AE606 WINDOW TYPES AND FRAME ELEVATIONS
11. REFER TO AF700 AND AF701 FOR EQUIPMENT AND FURNITURE INFORMATION
12. ALL EXTERIOR DIMENSIONS ARE TO FACE STUD AND / OR FACE OF FOUNDATION AND MASONRY
UNLESS SPECIFICALLY NOTED OTHERWISE.
13. ALL INTERIOR DIMENSIONS SHOWN ARE TO FACE OF FRAMING UNLESS SPECIFICALLY NOTED
OTHERWISE
14. ALL DIMENSIONS SHOWN LOCATING WINDOWS ARE TO CENTERLINE OF WINDOW, UNLESS
SPECIFICALLY NOTED OTHERWISE.
15. REFER TO SHEET GI003 FOR FIRESTOP DETAILS. ALL MECHANICAL, ELECTRICAL, AND PLUMBING PENETRATIONS THROUGH FIRE RATED CONSTRUCTION SHALL BE SLEEVED, FIRE SAFED AND / OR HAVE
FIRE DAMPERS EQUIVALENT TO THE HOURLY FIRE RATING OF THE CONSTRUCTION.
16. ALL DRAWINGS ARE OF EQUAL IMPORTANCE IN DEFINING THE WORK OF THE CONTRACT
DOCUMENTS. CONTRACTORS SHALL REVIEW ALL DRAWINGS BEFORE THE INSTALLATION OF THEIR WORK. SHOULD THERE BE A DISCREPANCY WITHIN AND BETWEEN THE DRAWINGS THAT WOULD CAUSE
AN AWKWARD OR IMPROPER INSTALLATION NOTIFY ARCHITECT FOR CLARIFICATION PRIOR TO
INSTALLATION OF SAID WORK. ANY WORK INSTALLED IN CONFLICT WITH THE ARCHITECTURAL
DRAWINGS, SHALL BE CORRECTED BY CONTRACTOR AT THEIR EXPENSE AND AT NO ADDITIONAL COST
TO THE OWNER OR ARCHITECT.
17.DO NOT SCALE DRAWINGS, THE DRAWINGS ARE NOT NECESSARILY TO SCALE - USE GIVEN
DIMENSIONS. CONTRACTOR SHALL VERIFY ALL CONDITIONS AND DIMENSIONS AT THE JOB SITE PRIOR
TO THE START OF CONSTRUCTION. IF DISCREPANCIES ARE FOUND, NOTIFY ARCHITECT FOR
CLARIFICATION BEFORE COMMENCING THE WORK.
18. DETAILS NOT SHOWN ARE SIMILAR IN CHARACTER TO THOSE SHOWN. WHERE SPECIFIC
DIMENSIONS, DETAILS, OR DESIGN INTENT CANNOT BE DETERMINED CONSULT ARCHITECT BEFORE
PROCEEDING WITH THE WORK.
19. ALL PITCHED FLOOR AREAS SHOWN WITH PITCH LINES SHALL SLOPE AT 1/4" PER FOOT UNLESS OTHERWISE NOTED, PROVIDE A SLAB DEPRESSION AT ALL FLOOR DRAINS WHERE PITCH LINES ARE
NOT SHOWN ON PLAN.
20. FINISH FLOOR ELEVATIONS ARE TO TOP OF CONCRETE, UNLESS OTHERWISE NOTED.
21. INSTALL ALL RECESSED CABINETS, PANELS, BOXES LOCATED IN FIRE-RATED PARTITIONS TO
MAINTAIN THE FIRE-RATED CONSTRUCTION
22. REFER TO MECHANICAL AND ELECTRICAL CONTRACTORS DRAWINGS AND MANUFACTURES
TEMPLATE DRAWINGS FOR ALL MECHANICAL AND ELECTRICAL EQUIPMENT SUPPORTS, BOLT SETTING
TEMPLATES, ISOLATIONS, SPRING ISOLATION, ETC. NOT SHOWN ON THE DRAWINGS
23. OWNER FURNISHED ITEMS THE G.C. SHALL COORDINATE AND PROVIDE ELECTRICAL, PLUMBING, AND MECHANICAL CONNECTIONS FOR ALL EQUIPMENT.
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
CONSULTANT ARCHITECT/ENGINEER OF RECORD
WBRC
A R C H I T E C T S • E N G I N E E R S
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title
Approved:
Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
/2
/2
:4
:3
P M
C
U s e rs
\j o c e ly n
.b o o th e \D o c u m e n ts \4
V A
M H
P R
O V
ID
E
N C
E M
H C
A
R C
H jo c e ly n .b o o th e
.r v t
GI002
650-332
NEW MENTAL HEALTH BUILDING -
PHASE 1
830 CHALKSTONE AVE PROVIDENCE, RI 02908
JRB BRS10 APR 2019
CONSTRUCTION
DOCUMENTS
SYMBOLS, ABBREVIATIONS AND
GENERAL NOTES
FULLY SPRINKLERED
VA RI FACILITIES MANAGEMENT
SERVICERevisions: Date:
ANNULAR FIRESTOPPING
THICKNESS REQUIREMENTS
TO COMPLY WITH
ANSI/UL263-DESIGN No.
FC7009 OR APPROVED
EQUIVALENT
STEEL FLANGES
DUCTWORK
ASSEMBLY VARIES SEE
ARCHITECTURAL PLANS &
DETAILS
FIRESEAL ON
FIRESAFING SYSTEM
WALL PENETRATION FIRESTOP
1HR FIRE - RATED (FD N-REQD), ANSI
\UL #263 WL7009
WP- 1
DUCTWORK
PLAN VIEW SECTION VIEW
ANNULAR FIRESTOPPING
THICKNESS REQUIREMENTS
TO COMPLY WITH
ANSI/UL263-DESIGN No.
CAJ8053 OR APPROVED
EQUIVALENT
ASSEMBLY VARIES SEE
ARCHITECTURAL PLANS &
DETAILS
METALLIC PIPE 6"
DIA OR SMALLER
FIRESEAL ON FIRESAFING
SYSTEMS SEE SPECS
FLOOR PENETRATION FIRESTOP
1HR / 2HR FIRE - RATED,
ANSI\UL #263 DESIGN FC8053
FP- 3
METALLIC PIPE 6" DIA
OR SMALLER
PLAN VIEW
SECTION VIEW
ELECTRICAL CONDUIT /
CABLE (SINGLE OR BUNDLE
UP TO 4" DIA)
ASSEMBLY VARIES SEE
ARCHITECTURAL PLANS &
DETAILS
ANNULAR FIRESTOPPING
THICKNESS REQUIREMENTS
TO COMPLY WITH
ANSI/UL263 DESIGN No.
CAJ3043 OR APPROVED
EQUIVALENT
FLOOR PENETRATION FIRESTOP
1HR FIRE - RATED,
ANSI\UL #263 DESIGN CAJ3043
FP- 5
NOTE:
ANNULUS RANGING
FROM POINT
CONTACT TO 2"
MAXIMUM
PLAN VIEW
SECTION VIEW
ANNULAR FIRESTOPPING
THICKNESS REQUIREMENTS
TO COMPLY WITH
ANSI/UL263-DESIGN No.
FC7002 OR APPROVED
EQUIVALENT
ASSEMBLY VARIES SEE
ARCHITECTURAL PLANS &
DETAILS
DUCTWORK
FIRESEAL ON FIRESAFING
SYSTEMS SEE SPECS
DUCTWORK
FLOOR PENETRATION FIRESTOP
1HR FIRE - RATED, ANSI\UL #263
FC7002
FP- 7
PLAN VIEW
SECTION VIEW
ANNULAR FIRESTOPPING
THICKNESS
REQUIREMENTS TO
COMPLY WITH ANSI/UL263-
DESIGN No. WL1049 OR
APPROVED EQUIVALENT
ASSEMBLY VARIES SEE
ARCHITECTURAL PLANS &
DETAILS
METALLIC PIPE 6"
DIA OR SMALLER
FIRESEAL ON
FIRESAFING SYSTEMS
SEE SPECS
WALL PENETRATION FIRESTOP
1HR FIRE - RATED,
ANSI\UL #263 DESIGN WL1049
WP- 3
METALLIC PIPE 6" DIA
OR SMALLER
PLAN VIEW SECTION VIEW
ELECTRICAL CONDUIT /
CABLE (SINGLE OR BUNDLE
UP TO 4 1/2" DIA)
ASSEMBLY VARIES SEE
ARCHITECTURAL PLANS &
DETAILS
ANNULAR FIRESTOPPING
THICKNESS REQUIREMENTS
TO COMPLY WITH
ANSI/UL263 DESIGN No.
WL3076 OR APPROVED
EQUIVALENT
WALL PENETRATION FIRESTOP
1HR / 2HR FIRE - RATED
ANSI\UL #263 DESIGN WL3076
WP- 5
NOTE:
ANNULUS RANGING
FROM POINT
CONTACT TO 2"
MAXIMUM
PLAN VIEW SECTION VIEW
1. EXTERIOR CONCRETE PANEL CURTAIN WALL ASSEMBLY (NON FIRE RATED.)
2. PRECAST HOLLOW-CORE CONCRETE FLOOR ASSEMBLY (MINIMUM 8" THICK) WITH CONCRETE
TOPPING (MINIMUM 2" THICK) (1-HR. OR 2-HR. FIRE RATING).
3. MINIMUM 4" THICKNESS MINERAL WOOL SAFING (MIN. 4 PCF DENSITY) COMPRESSED 33%, FLUSH
WITH FLOOR SURFACES.
4. MINIMUM 1/8" (WET) THICKNESS HILTI CFS-SP WB FIRESTOP JOINT SPRAY OR MINIMUM 2MM (WET) THICKNESS HILTI CFS-SP SIL FIRESTOP SILICONE JOINT SPRAY TO COMPLETELY COVER MINERAL
WOOL, OVERLAPPING MINIMUM 1/2" ONTO ADJACENT ASSEMBLIES.
NOTES:
- MAXIMUM WIDTH OF JOINT = 1".
- FIRE-RATING OF ASSEMBLY IS DEPENDENT UPON THE PERFORMANCE OF CURTAIN WALL
ASSEMBLY AND FLOOR ASSEMBLY UNDER FIRE CONDITIONS.
NOTE: FIRESTOPPING DETAIL BASIS OF DESIGN IS HILTI FIRESTOP SYSTEMS 1-HR. OR 2-HR.
ENGINEERING JUDGEMENT (REFERENCE: UL SYSTEM NO. CW-D-1001. DRAWING NO. 320023a).
THIS INFORMATION IS PROVIDED FOR REFERENCE ONLY, IT DOES NOT EXCLUDE OTHER
MANUFACTURERS WHICH MEET UL APPROVED FIRESTOPPING METHODS FOR THE 1-HR. OR 2-
HR. SPECIFIED CONDITIONS.
MAX. 1"
1. EXTERIOR GYP. WITH STEEL STUD FRAMING CURTAIN WALL ASSEMBLY
(NON FIRE RATED).
2. PRECAST HOLLOW-CORE CONCRETE FLOOR ASSEMBLY (MINIMUM 8"
THICK) WITH CONCRETE TOPPING (MINIMUM 2" THICK) (1-HR. OR 2-HR. FIRE
RATING).
3. STEEL DEFLECTION CLIP.
4. MINIMUM 4" THICKNESS MINERAL WOOL SAFING (MIN. 4 PCF DENSITY)
COMPRESSED 33%, FLUSH WITH FLOOR SURFACES.
5. MINIMUM 1/8" (WET) THICKNESS HILTI CFS-SP WB FIRESTOP JOINT SPRAY
OR MINIMUM 2MM (WET) THICKNESS HILTI CFS-SP SIL FIRESTOP SILICONE
JOINT SPRAY TO COMPLETELY COVER MINERAL WOOL AND DEFLECTION
CLIP, OVERLAPPING MINIMUM 1/2" ONTO ADJACENT ASSEMBLIES.
NOTES:
- MAXIMUM WIDTH OF JOINT = 8".
- FIRE-RATING OF ASSEMBLY IS DEPENDENT UPON THE PERFORMANCE OF
CURTAIN WALL ASSEMBLY AND FLOOR ASSEMBLY UNDER FIRE
CONDITIONS.
NOTE: FIRESTOPPING DETAIL BASIS OF DESIGN IS HILTI FIRESTOP
SYSTEMS 1-HR. OR 2-HR. ENGINEERING JUDGEMENT
(REFERENCE: INTERTEK SYSTEM NO. CEJ 421 P. DRAWING NO.
319890a). THIS INFORMATION IS PROVIDED FOR REFERENCE
ONLY, IT DOES NOT EXCLUDE OTHER MANUFACTURERS WHICH
MEET UL APPROVED FIRESTOPPING METHODS FOR THE 1-HR. OR
2-HR. SPECIFIED CONDITIONS.
MAX. 8"
FIRESTOPPING AT RATED FLOOR ASSEMBLY
1. EXTERIOR GYP. WITH STEEL STUD FRAMING CURTAIN WALL ASSEMBLY
(NON FIRE RATED).
2. PRECAST HOLLOW-CORE CONCRETE FLOOR ASSEMBLY (MINIMUM 8"
THICK) WITH CONCRETE TOPPING (MINIMUM 2" THICK) (NON FIRE RATING).
3. STEEL DEFLECTION CLIP.
4. MINIMUM 4" THICKNESS MINERAL WOOL SAFING (MIN. 4 PCF DENSITY)
COMPRESSED 33%, FLUSH WITH FLOOR SURFACES.
5. MINIMUM 1/8" (WET) THICKNESS HILTI CP 572 SMOKE AND ACOUSTIC
SPRAY TO COMPLETELY COVER MINERAL WOOL AND DEFLECTION CLIP,
OVERLAPPING MINIMUM 1/2" ONTO ADJACENT ASSEMBLIES.
NOTES:
- MAXIMUM WIDTH OF JOINT = 8".
- tHIS SYSTEM IS DESIGNED AS A COLD SMOKE SEAL ONLY.
NOTE: FIRESTOPPING DETAIL BASIS OF DESIGN IS HILTI FIRESTOP
SYSTEMS 1-HR. OR 2-HR. ENGINEERING JUDGEMENT
(REFERENCE: INTERTEK SYSTEM NO. CEJ 421 P. DRAWING NO.
327515a). THIS INFORMATION IS PROVIDED FOR REFERENCE
ONLY, IT DOES NOT EXCLUDE OTHER MANUFACTURERS WHICH
MEET UL APPROVED FIRESTOPPING METHODS FOR THE 1-HR. OR
2-HR. SPECIFIED CONDITIONS.
SMOKE SEAL AT NON RATED FLOOR ASSEMBLY
MAX. 3/4"
1. PRECAST HOLLOW-CORE CONCRETE FLOOR ASSEMBLY (MINIMUM 8" THICK) WITH CONCRETE
TOPPER (MINIMUM 2" THICK) (1-HR. OR 2-HR. FIRE RATING).
2. CONCRETE BLOCK WALL ASSEMBLY (UL/cUL CLASSIFIED) (MINIMUM 8" THICK) (1-HR. OR 2 HR. FIRE-
RATING)
3. MINIMUM 1" THICKNESS MINERAL WOOL SAFING ( MIN. 4 PCF DENSITY) TIGHTLY PACKED AS A
BACKER.
4. MINIMUM 1/4" DEPTH HILTI CFS-S SIL GG FIRESTOP SILICONE SEALANT.
5. MINIMUM 4" THICKNESS MINERAL WOOL FIRE SAFING (MIN. 4 PCF DENSTIY) COMPRESSED 50%, FLUSH WITH BOTTOM OF FLOOR.
NOTES:
- MAXIMUM WIDTH OF JOINT = 3/4".
- T-RATING MAY NOT EQUAL F-RATING IN ACCORDANCE WITH UL 2079.
NOTE: FIRESTOPPING DETAIL BASIS OF DESIGN IS HILTI FIRESTOP SYSTEMS 1-HR. OR 2-HR.
ENGINEERING JUDGEMENT (REFERENCE: UL/cUL SYSTEM NO. FW-D-1037. DRAWING NO.
327514a). THIS INFORMATION IS PROVIDED FOR REFERENCE ONLY, IT DOES NOT EXCLUDE
OTHER MANUFACTURERS WHICH MEET UL APPROVED FIRESTOPPING METHODS FOR THE 1-
HR. OR 2-HR. SPECIFIED CONDITIONS.
G
1HR RATED CMU SHAFT
ENCLOSURE
/4
1HR RATED PRECAST
PLANK EDGE
CONTINUOUS 1 HR.
FIRESTOPPING AT OPENING
CONTINUOUS FIRESTOPPING
AT BALLOON FRAMING
5 3/4"
5" 5 3/4"
/4
1' - 0"
/4
/8
NOTE: PROVIDE 1 HR. UL LISTED FIRESTOPPING SOLUTION.
3/4" TYP
X
Y
/4
T
Y P
PLAN VIEW SECTION VIEW
Y
1. PRECAST HOLLOW-CORE CONCRETE FLOOR ASSEMBLY (MINIMUM 8" THICK) WITH CONCRETE
TOPPER (MINIMUM 2" THICK) (1-HR. OR 2-HR. FIRE RATING).
2. STEEL COLUMN (MAXIMUM SIZE: W10 x 68) (NON FIRE-RATED)
3. MINIMUM 4" THICKNESS MINERAL WOOL SAFING ( MIN. 4 PCF DENSITY) TIGHTLY PACKED, RECESSED TO ACCOMODATE SEALANT.
4. MINIMUM 1/2" DEPTH HILTI CFS-S SIL GG FIRESTOP SILICONE SEALANT.
NOTES:
- MAXIMUM SIZE OF OPENING = 18" x 18".
- ANNULAR SPACE = MINIMUM 0", MAXIMUM 12"
- FIRE-RATING OF ASSEMBLY IS DEPENDENT UPON THE PERFORMANCE OF STEEL COLUMN AND
FLOOR ASSEMBLY UNDER FIRE CONDITIONS.
NOTE: FIRESTOPPING DETAIL BASIS OF DESIGN IS HILTI FIRESTOP SYSTEMS 1-HR. OR 2-HR.
ENGINEERING JUDGEMENT (REFERENCE: UL/cUL SYSTEM NO. F-A-8012 & W-J-7110. DRAWING NO. 327513a). THIS INFORMATION IS PROVIDED FOR REFERENCE ONLY, IT DOES NOT
EXCLUDE OTHER MANUFACTURERS WHICH MEET UL APPROVED FIRESTOPPING METHODS
FOR THE 1-HR. OR 2-HR. SPECIFIED CONDITIONS.
3 3/4" TYP.
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
CONSULTANT ARCHITECT/ENGINEER OF RECORD
WBRC
A R C H I T E C T S • E N G I N E E R S
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title
Approved:
Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
TRUE NORTH
PROJECT NORTH
/2
/2
:4
:3
P M
C
U s e rs
\j o c e ly n
.b o o th e \D o c u m e n ts \4
V A
M H
P R
O V
ID
E
N C
E M
H C
A
R C
H jo c e ly n .b o o th e
.r v t
GI003
650-332
NEW MENTAL HEALTH BUILDING -
PHASE 1
830 CHALKSTONE AVE PROVIDENCE, RI 02908
JRB BRS10 APR 2019
CONSTRUCTION
DOCUMENTS
FIRESTOP DETAILS
FULLY SPRINKLERED
VA RI FACILITIES MANAGEMENT
SERVICE
1 1/2" = 1'-0"
D4 WP-1 WALL PENETRATION FIRESTOP
1 1/2" = 1'-0"
F6 FP-3 FLOOR PENETRATION FIRESTOP
1 1/2" = 1'-0"
F8 FP-5 FLOOR PENETRATION FIRESTOP
1 1/2" = 1'-0"
F4 FP-7 FLOOR PENETRATION FIRESTOP
1 1/2" = 1'-0"
D6 WP-3 WALL PENETRATION FIRESTOP
1 1/2" = 1'-0"
D8 WP-5 WALL PENETRATION FIRESTOP
1 1/2" = 1'-0"
C1 TYPICAL FIRESTOPPING SECTION @ CONCRETE STEM WALL
1 1/2" = 1'-0"
F1 TYPICAL FIRESTOPPING SECTION @ BALLOON FRAMING
1 1/2" = 1'-0"
B9 TYPICAL FIRESTOPPING SECTION @ STAIR 1 - LEVEL 01
1 1/2" = 1'-0"
B4 FIREPROOFING PLAN DETAIL @ GRID G-3 - LEVEL 01
1 1/2" = 1'-0"
B7 TYPICAL FIRESTOPPING @ LEVEL 01 COLUMNS
Revisions: Date:
| Sheets |
| GI001 - COVER SHEET |
| GI002 - SYMBOLS, ABBREVIATIONS AND GENERAL NOTES |
| GI003 - FIRESTOP DETAILS |