36E77620R0001-006.pdf

PDF Posted

Attached to
650-332 New Mental Health Building - Phase 1 (VA-19-00104660)
Solicitation number
36E77620R0001
Issued by

About this file

This notice provides details for an upcoming federal construction contract opportunity with the Department of Veterans Affairs. The contract is for the construction of a new mental health building located at 830 Chalkstone Ave in Providence, Rhode Island, with an estimated value between $10-20 million. The project scope includes site preparation, demolition, and construction of a three-story, approximately 15,300 square foot freestanding building along with corresponding site and utility work. The solicitation will be issued as a request for proposal on or around December 20, 2019, conducted according to FAR Parts 15, 19, and 36, and evaluated based on procedures in the solicitation. The NAICS code is 236220 with a size standard of $36.5 million. The period of performance is approximately 600 calendar days from notice to proceed. The solicitation will be a total SDVOSB set-aside with offers from other than SDVOSB concerns not considered.

36E77620R0001 Attachment 5 - CD Drawings - Electrical.pdf

View the file

Other files

File Type Posted
36E77620R0001-0007000.docx DOCX document
36E77620R0001-0007001.docx DOCX document
36E77620R0001-0006000.docx DOCX document
36E77620R0001-0005060.docx DOCX document
36E77620R0001-0005061.docx DOCX document
36E77620R0001-0005068.pdf PDF
36E77620R0001-0005064.pdf PDF
36E77620R0001-0005069.pdf PDF
36E77620R0001-0005067.pdf PDF
36E77620R0001-0005062.pdf PDF
36E77620R0001-0005070.pdf PDF
36E77620R0001-0005066.pdf PDF
36E77620R0001-0005065.pdf PDF
36E77620R0001-0005063.pdf PDF
36E77620R0001-0005071.pdf PDF
36E77620R0001-0004001.docx DOCX document
36E77620R0001-0004000.docx DOCX document
36E77620R0001-0003000.docx DOCX document
36E77620R0001-0003001.docx DOCX document
36E77620R0001-0002000.docx DOCX document
36E77620R0001-0001001.pdf PDF
36E77620R0001-0001000.docx DOCX document
36E77620R0001-008.pdf PDF
36E77620R0001-007.pdf PDF
36E77620R0001-012.pdf PDF
36E77620R0001-016.docx DOCX document
36E77620R0001-001.docx DOCX document
36E77620R0001-004.pdf PDF
36E77620R0001-005.pdf PDF
36E77620R0001-010.pdf PDF
36E77620R0001-013.pdf PDF
36E77620R0001-015.docx DOCX document
36E77620R0001-017.pdf PDF
36E77620R0001-002.pdf PDF
36E77620R0001-011.pdf PDF
36E77620R0001-014.pdf PDF
36E77620R0001-009.pdf PDF
36E77620R0001-003.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

S

S

S

S

S

S

S

EGA

TSA

VFD

ECB

PB

MANUAL MOTOR STARTER WITH INTEGRAL THERMAL PROTECTION

MOTOR - "5" INDICATES HORSEPOWER

DRY TYPE TRANSFORMER

JUNCTION BOX

POWER PLAN LEGEND

T

PULL BOX

"60AS" - DENOTES SWITCH AMPERAGE RATING

"40AF" - DENOTES FUSE AMPERAGE RATING

60AS

40AF

ENCLOSED CIRCUIT BREAKER - NEMA 1 ENCLOSURE

DISCONNECT SWITCH - NEMA 1 ENCLOSURE - UNFUSED

DISCONNECT SWITCH - NEMA 1 ENCLOSURE - FUSED

30A-3 POLE UNLESS OTHERWISE NOTED

3P

"3P" - DENOTES 3-POLE

60AT

100AF

100AF - DENOTES CIRCUIT BREAKER FRAME

60AT - DENOTES CIRCUIT BREAKER TRIP

EMERGENCY GENERATOR ANNUNCIATOR

TRANSFER SWITCH ANNUNCIATOR

"3R" - DENOTES NEMA 3R ENCLOSURE

"ADO" INDICATES CONNECTION TO AUTOMATIC DOOR OPERATOR

"ATC" INDICATES CONNECTION FOR AUTOMATIC TEMPERATURE CONTROLS

"B" INDICATES JUNCTION BOX WITH BLANK COVER

"EF" INDICATES CONNECTION TO ELECTRONIC FAUCET OR FLUSH VALVE

"EM" INDICATES CONNECTION TO EMERGENCY POWER CIRCUIT AS

INDICATED

"EWC" INDICATES CONNECTION TO ELECTRIC WATER COOLER

"GD" INDICATES CONNECTION TO GARBAGE DISPOSAL

"HM" INDICATES CONNECTION TO HUMIDIFIER

"MD" INDICATES CONNECTION TO MOTORIZED DAMPER

"NM" INDICATES CONNECTION TO NORMAL POWER CIRCUIT AS INDICATED

"PS" INDICATES CONNECTION TO MOTORIZED PROJECTION SCREEN

"SEC" INDICATES CONNECTION SECURITY DEVICES

"T/D" INDICATES TEL/DATA WIRING

SURFACE MOUNTED PANELBOARD

FLUSH MOUNTED PANELBOARD

T

VARIABLE FREQUENCY DRIVE PROVIDED BY HVAC

CONTRACTOR WIRED BY THE ELECTRICAL CONTRACTOR

3P

ELECTRICAL DRAWING LIST

THIS IS A STANDARD SYMBOL LIST. ALL DEVICE SYMBOLS AND

ABBREVIATIONS MAY NOT NECESSARILY APPEAR ON THE FLOOR PLANS

OR DETAIL SHEET. ONLY THOSE SYMBOLS INDICATED ON THE FLOORS

PLANS ARE USED AND OTHERS SHOULD BE DISREGARDED.

PC PHOTOCELL

EMERGENCY CALL SYSTEM LEGEND

EMERGENCY CALL

T

E

"T"- DENOTES TOILET/ DRESSING ROOM STATION

LOCATION, WALL, MOUNTED DEVICE WITH PUSH BUTTON ESP.

FOR MENTAL HEALTH..

"S"- DENOTES SHOWER STATION LOCATION, WALL

MOUNTED DEVICE WITH PULLCORD.

EMERGENCY CALL SYSTEM SCOPE OF WORK: THE CONTRACTOR IS

RESPONSIBLE FOR PROVIDING A COMPLETE SYSTEM, INCLUDING ALL

EQUIPMENT, DEVICES AND WIRING, AND ALL NECESSARY APPURTENANCES

FOR A COMPLETE INSTALLATION. SCOPE OF WORK TO INCLUDE THE

FOLLOWING):

CABLE PATHWAY SYSTEM, CONSISTING OF CONDUITS, CABLE PATHWAYS,

CABLE TRAYS, HANGERS, WALL PENETRATIONS, & STUB-OUTS ALL DEVICES

AND WIRING (LINE VOLTAGE).

T

N DOME LIGHT LOCATION - CEILING OR WALL AS DIRECTED BY

ARCHITECT OR HOSPITAL PERSONNEL.

PANEL DESIGNATION LEGEND

FLOOR PANEL NUMBER

"4" - 480/277V

"2" - 208/120V

4D 3 2

"D" - DISTRIBUTION PANEL

"M" - MECHANICAL PANEL

"K" - KITCHEN PANEL

"L" - LIGHTING

"P" - POWER

CONDUIT TURNING DOWN

CONDUIT STUBBED 6" ABOVE ACCESSIBLE CEILING

AT 90° ANGLE WITH BUSHED END

FLEXIBLE RACEWAY

J-HOOK CABLE MANAGEMENT TYPICALLY MOUNTED 6" ABOVE

FINISHED CEILING

L4GA-5

J

WIRING METHODS LEGEND

HOMERUN TO PANELBOARD "L4GA" ; BRANCH CIRCUIT No. 5;

NO SLASH LINES INDICATE 2#12 & 1#12G., 3/4"C. UNLESS

OTHERWISE NOTED: MINIMUM SIZE CONDUCTOR #12 AWG/

MINIMUM SIZE CONDUIT 3/4"C.

BASKET STYLE CABLE TRAY ELEVATION TRANSITION

FITTING CONDUIT TURNING UP

4P

AUTOMATIC TRANSFER SWITCH

ONE-LINE DIAGRAM LEGEND

ATS BP

LS "LS" - DENOTES LIFE SAFETY BRANCH

"ELEV" - DENOTES ELEVATOR BRANCH

- DENOTES NUMBER OF POLES; 4 POLE"4P"

- DENOTES AUTOMATIC TRANSFER SWITCH"ATS"

- DENOTES MANUAL TRANSFER SWITCH"MTS"

- DENOTES NUMBER OF POLES; 3 POLE"3P"

GROUND CONNECTION

CR43A1 PANELBOARD "CR43A1"

45 KVA DRY-TYPE TRANSFORMER

KVA

"BP" - DENOTES BYPASS ISOLATION SWITCH

- DENOTES CRITICAL BRANCH"CR"

"EQ" - DENOTES EQUIPMENT BRANCH

"X-RAY" - DENOTES X-RAY EQUIPMENT BRANCH

SPD SURGE PROTECTIVE DEVICE

a

OS

D

3D

EMERGENCY LIGHTING SUPERVISORY RELAY - UL 924 LISTED

REFER TO ELECTRICAL DETAILS FOR ADDITIONAL INFORMATION

LOCAL SWITCH, 4-WAY, DOUBLE POLE, DOUBLE THROW

LOCAL SWITCH, 3-WAY, SINGLE POLE DOUBLE THROW

LOCAL SWITCH, SINGLE POLE

SWITCHES LEGEND

"a" - DENOTES LIGHT FIXTURE CONTROL

OCCUPANCY SENSOR - WALL MOUNTED INTEGRAL, DUAL

TECHNOLOGY, DUAL RELAY SWITCH, WITH INTEGRAL

PHOTOCELL. MOUNT 48" AFF UNLESS NOTED OTHERWISE.

OCCUPANCY SENSOR - WALL MOUNTED INTEGRAL, DUAL

TECHNOLOGY, DUAL RELAY SWITCH. MOUNT 48" AFF

UNLESS NOTED OTHERWISE.

OCCUPANCY SENSOR - WALL MOUNTED INTEGRAL,

DUAL TECHNOLOGY, SINGLE POLE SWITCH. MOUNT

48" AFF UNLESS NOTED OTHERWISE.

OCCUPANCY SENSOR, CEILING MOUNTED, DUAL

TECHNOLOGY.

DIMMER SWITCH, SINGLE POLE

DIMMER SWITCH, 3-WAY

LV LOW VOLTAGE SWITCH

"MS" - DENOTES MASTER STATION OVERRIDE

"a" - DENOTES LOW VOLTAGE SWITCH CIRCUIT a

OS

D

3D

LV

OCCUPANCY SENSOR, CEILING PEDESTAL MOUNTED

CORNER UNIT, DUAL TECHNOLOGY.

OS

ER

OS

OS

OS

FOR CEILING MOUNTED AND CORNER MOUNTED OCCUPANCY SENSORS:

PROVIDE THE APPROPRIATE QUANTITY OF POWER SUPPLIES FOR SINGLE

AND MULTIPLE LEVEL SWITCHING. REFER TO FLOOR PLANS FOR

SWITCHING LAYOUTS TO DETERMINE EXACT QUANTITY OF POWER

SUPPLIES

FR 1

a

FR 1

a

FR 1

a

FR 1

a

1FR

a

REMOTE EMERGENCY LIGHTING, SINGLE HEAD MOUNT 7'-6" AFF

REMOTE EMERGENCY LIGHTING, DUAL HEAD MOUNT 7'-6" AFF

LIGHTING FIXTURE AS DESIGNATED ON LIGHTING

FIXTURE SCHEDULE

"1"

"a"

"FR"

"NL" - DENOTES NIGHT LIGHT FIXTURE

EXIT SIGN - SHADED AREA INDICATES LOCATION AND

QUANTITY OF FACES; DIRECTIONAL ARROWS AS

INDICATED

EMERGENCY BATTERY UNIT, MOUNT 7'-6" AFF; NO. OF

EMERGENCY LIGHTING HEADS AS INDICATED.

- DENOTES PANELBOARD BRANCH CIRCUIT NUMBER

- DENOTES FIXTURE CONTROLLED BY LOCAL SWITCH "a"

- DENOTES FIXTURE TYPE AS NOTED ON

FIXTURE SCHEDULE.

- DENOTES LIGHT FIXTURE ON LIFE SAFETY

BRANCH CIRCUIT

LIGHTING PLAN LEGEND

- DENOTES LIGHT FIXTURE CONNECTED TO

CRITICAL BRANCH CIRCUITRY

3/4" THICK x 8'-0" HIGH x LENGTH AS INDICATED ON THE

DRAWINGS PLYWOOD. PLYWOOD SHALL BE PAINTED GRAY

AND MOUNTED TO WALL.

TELEVISION COAX OUTLET - CEILING OR WALL MOUNTED AS

INDICATED ON ARCHITECTURAL DRAWINGS. PROVIDE WITH

3/4"C TO ABOVE ACCESIBLE CEILING WITH RG6 CABLING TO

CATV TERMINATION POINT.

REFER TO PROVIDENCE DATA AND CABLING SPECIFICATIONS FOR TELE/DATA

WIRING REQUIREMENTS, THE ELECTRICAL CONTRACTOR SHALL PROVIDE

DEVICES AND CABLING BACK TO TERMINATION EQUIPMENT.

"CAP" - DENOTES CEILING MOUNTED WIRELESS ACCESS POINT

"CCTV" - DENOTES DATA DEVICE FOR CONNECTION TO SECURITY

CAMERA. DEVICE TO BE LOCATED ABOVE ACCESSIBLE

CEILING. COORDINATE EXACT LOCATION WITH OWNER AND

SECURITY VENDOR.

AV

2-GANG BACKBOX WITH SINGLE GANG PLASTER RING AND

COVERPLATE (TYPE AND MANUFACTURE PER FACILITY

STANDARDS) WITH 1"C (EMPTY, WITH PULLSTRING)

TERMINATED IN ACCESSIBLE CEILING WITH BELL END BUSHING,

UNLESS OTHER SIZE CONDUIT IS INDICATED ON DRAWINGS.

TV TV

"H" - DENOTES MOUNTED HIGH ON WALL CORDINATE EXACT

LOCATION WITH ARCHITETURAL DRAWINGS AND ELEVATIONS

MOUNT

48" AFF

UNO

COMMUNICATIONS LEGEND (WITH WIRING)

"W" - DENOTES MOUNTED 54" AFF

"W" - DENOTES MOUNTED 48" AFF

"C" - DENOTES MOUNTED 8" ABOVE WORK SURFACE

"C" - DENOTES MOUNTED 8" ABOVE WORK SURFACE

"C" - DENOTES MOUNTED 8" ABOVE WORK SURFACE

COMBINATION VOICE/DATA QUAD OUTLET DEVICE - MOUNTED

18"AFF, UNLESS NOTED OTHERWISE. (1 VOICE, 3 DATA UNLESS

OTHERWISE NOTED) WITH 1"C (WITH PULL STRING) RUN

CONCEALED WITHIN WALL TO ABOVE FINISHED CEILING AND

TERMINATING WITHIN 6" OF CABLE MANAGEMENT SYSTEM.

PROVIDE WITH CAT6 CABLES BACK TO PATCH PANEL SERVING

THE AREA.

VOICE ONLY OUTLET DEVICE - MOUNTED 18" AFF, UNLESS

NOTED OTHERWISE, WITH 1"C (WITH PULL STRING) RUN

CONCEALED WITHIN WALL TO ABOVE FINISHED CEILING AND

TERMINATING WITHIN 6" OF CABLE MANAGEMENT SYSTEM.

PROVIDE WITH CAT6 CABLES BACK TO PATCH PANEL SERVING

THE AREA.

DATA ONLY OUTLET DEVICE (2 DATA) - MOUNTED 18" AFF,

UNLESS NOTED OTHERWISE, WITH 1"C (WITH PULL STRING) RUN

CONCEALED WITHIN WALL TO ABOVE FINISHED CEILING AND

TERMINATING WITHIN 6" OF CABLE MANAGEMENT SYSTEM.

PROVIDE WITH CAT6 CABLES BACK TO PATCH PANEL SERVING

THE AREA.

"TV" - DENOTES DEVICE MOUNTED HIGH ON WALL FOR

TELEVISION. COORDINATE EXACT LOCATION AND

MOUNTING HEIGHT WITH THE ARCHITECT PRIOR

TO INSTALLATION.

INFORMATION TECHNOLOGY (IT) OUTLET DEVICE PROVISIONS -

CEILING MOUNTED WITH 1"C (WITH PULL STRING) RUN

CONCEALED WITHIN WALL TO ABOVE FINISHED CEILING AND

TERMINATING WITHIN 6" OF CABLE MANAGEMENT SYSTEM

"C" - DENOTES MOUNTED 8" ABOVE WORK SURFACE

FLOOR MOUNTED DATA ONLY OUTLET DEVICE (2 DATA) WITH 1"C

(WITH PULL STRING) RUN CONCEALED WITHIN WALL TO ABOVE

FINISHED CEILING AND TERMINATING WITHIN 6" OF CABLE

MANAGEMENT SYSTEM. PROVIDE WITH CAT6 CABLES BACK TO

PATCH PANEL SERVING THE AREA.

J

MS

CIRCUIT BREAKER - AMPERAGE AND NO. OF POLES AS INDICATED.

M UTILITY SERVICE METER

WIRING DEVICE LEGEND

SPECIAL PURPOSE RECEPTACLE NEMA TYPE

AS INDICATED ON THE PLANS

DUPLEX RECEPTACLE GFI TYPE NEMA 5-20R

SINGLE RECEPTACLE NEMA 5-20R

DOUBLE DUPLEX RECEPTACLE NEMA 5-20R

DUPLEX RECEPTACLE NEMA 5-20R

DUPLEX RECEPTACLE NEMA 5-20R

EMERGENCY CRITICAL BRANCH CIRCUIT

DUPLEX RECEPTACLE GFI TYPE NEMA 5-20R

EMERGENCY CRITICAL BRANCH CIRCUIT

"C"-

FLOOR MOUNTED DUPLEX RECEPTACLE NEMA 5-20R. PROVIDE

RECTANGULAR METALLIC CAST IRON ADJUSTABLE FLOOR BOX

WITH ALUMINUM COVERS. PROVIDE CARPET FLANGES AS

REQUIRED.

DENOTES LISTED WEATHER RESISTANT TYPE DEVICE AND

IN-USE COVER AS DESCRIBED IN N.E.C. 2011 SECTION 406.8

CEILING MOUNTED RECEPTACLE

- DENOTES 2 HOUR FIRE RATED POKE-THROUGH

- DENOTES FLUSH FLOOR MOUNTED

"PT"

"F"

DOUBLE DUPLEX RECEPTACLE NEMA 5-20R

EMERGENCY CRITICAL BRANCH CIRCUIT

SINGLE RECEPTACLE NEMA 5-20R

EMERGENCY CRITICAL BRANCH CIRCUIT

ALL RECEPTACLES ARE MOUNTED 18" AFF UNLESS OTHERWISE

NOTED.

"TP"-

"WP"- DENOTES WEATHERPROOF TYPE: NEMA 3R MINIMUM

DENOTES TAMPER PROOF TYPE

DENOTES MOUNTED 8" ABOVE WORK

SURFACE OR COUNTER TOP

"WR"-

"MC"- DENOTES RECEPTACLE MOUNTED IN CASEWORK FOR

MICROWAVE, COORDINATE EXACT LOCATION AND

MOUNTING HEIGHT WITH THE CASEWORK VENDOR AND

ARCHITECT PRIOR TO INSTALLATION

RECEPTACLE TYPE DESIGNATIONS:

"CP"- DENOTES RECEPTACLE MOUNTED IN CEILING FOR PROJECTOR

"CM"- DENOTES RECEPTACLE MOUNTED 8" ABOVE WORK

SURFACE OR COUNTER TOP FOR COFFEE MACHINE

"IH"- DENOTES RECEPTACLE MOUNTED IN CASEWORK BELOW

SINK FOR INSTANT HOT WATER DISPENSER, COORDINATE

EXACT LOCATION AND MOUNTING HEIGHT WITH THE

CASEWORK VENDOR AND ARCHITECT PRIOR TO

INSTALLATION.

"TV"- DENOTES RECEPTACLE MOUNTED HIGH ON WALL FOR

TELEVISION. COORDINATE EXACT LOCATION AND

MOUNTING HEIGHT WITH THE ARCHITECT PRIOR TO

INSTALLATION. PROVIDE TAMPERPROOF TYPE DEVICE IN

PATIENT ACCESSIBLE AREAS

"ICE"- DENOTES RECEPTACLE MOUNTED 8" ABOVE WORK

SURFACE OR COUNTER TOP FOR ICE MACHINE

"REF"- DENOTES RECEPTACLE MOUNTED AT 48" FOR FULL HEIGHT

REFRIGERATOR

"UC"- DENOTES RECEPTACLE MOUNTED AT 18" IN CASEWORK

FOR UNDERCABINET REFRIGERATOR

"PX"- DENOTES RECEPTACLE MOUNTED AT 48"A.F.F. FOR PYXIS

MACHINE

"D"- DENOTES DEVICE FED VIA DEDICATED

BRANCH CIRCUITRY

"BW"-

DENOTES RECEPTACLE MOUNTED AT HEIGHT AS

DETERMINED BY THE ARCHITECT FOR BLANKET WARMER

TRIPLE CHANNEL, SURFACE MOUNTED, ALUMINUM RACEWAY,

DUAL COVER WIREMOLD #AL7450 SERIES OR APPROVED

EQUAL. RACEWAY TO BE MOUNTED 6" ABOVE WORK SURFACE

OR AS DIRECTED BY ARCHITECT AND HOSPITAL

REPRESENTATIVE. RACEWAY TO BE FACTORY PRE-WIRED,

WITH DUPLEX NEMA 5-20R RECEPTACLES FOR NORMAL

POWER, DUPLEX RED NEMA 5-20R RECEPTACLES FOR

EMERGENCY POWER, AND VOICE/DATA PROVISION LOCATIONS.

NORMAL POWER DEVICES 24" ON CENTER, EMERGENCY

POWER DEVICES 48" ON CENTER, AND TELE/DATA LOCATIONS

48" ON CENTER, UNLESS OTHERWISE NOTED. DEVICES WITHIN

6'-0" OF SINKS SHALL BE GFCI PROTECTED.

"TS"- DENOTES RECEPTACLE MOUNTED IN CASEWORK FOR

TOASTER

NOTE: ALL RECEPTACLES SHALL BE HOSPITAL GRADE. ALL

RECEPTACLES WITHIN PATIENT ACCESSIBLE AREAS SHALL BE

TAMPERPROOF TYPE DEVICES.

"USB"- DENOTES COMBINATION USB DEVICE

WIRING METHODS

REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION

NORMAL SYSTEM FEEDERS

EQUIPMENT SYSTEM FEEDERS

NORMAL BRANCH CIRCUITS

THHN/THWN/XHHW

CONDUCTORS IN EMT

THHN/THWN/XHHW CONDUCTORS IN

EMT OR HOSPITAL GRADE AC CABLE

TELEDATA WIRING

CAT6 WIRING IN EMT (REFER TO

COMMUNICATIONS LEGEND FOR

ADDITIONAL INFORMATION)

MECHANICAL EQUIPMENT COORDINATION

ELECTRICAL CONTRACTOR SHALL REFER TO THE MECHANICAL,

PLUMBING, AND FIRE PROTECTION DRAWINGS AND SPECIFICATIONS FOR

LOCATIONS AND QUANTITIES OF EQUIPMENT RELEASED TO EACH TRADE.

MECHANICAL EQUIPMENT COORDINATION

SL1

d

UP-1

HH

LC

TC

d

SITE LIGHTING AND POWER LEGEND

SITE LIGHTING FIXTURE

SITE LIGHTING BOLLARD

UTILITY POLE

SL2

MANHOLE

HANDHOLE

MH

LIGHTING CONTACTOR

TIME CLOCK

G

G

G

GND

GROUNDING LEGEND

GROUND ROD

GROUNDING COUNTERPOISE - (3) COPPER GROUND

RODSAT 10'-0" ON CENTER. LIGHTING PROTECTION SHALL

USE TRIAD GROUNDING SYSTEM.

GROUNDING CONDUCTOR; 1/0 CU GND MINIMUM -

UNLESS NOTED OTHERWISE

GROUND BAR - 2"H x 1/4" THICK x 18"L, MOUNTED 24"

AFF WITH 2" SPACE BETWEEN GROUND BUS AND

WALL

GROUNDING ELECTRODE CONDUCTOR OF SEPARATELY

DERIVED SYSTEM.

THHN/THWN/XHHW

CONDUCTORS IN EMT

S M

VFD

S M

VFD

PROVIDE BY EC

PROVIDE BY MC

PROJECT GENERAL NOTES

24. WHERE PANELS ARE INDICATED TO BE RELOCATED, THE ELECTRICAL

CONTRACTOR SHALL TRACE OUT EACH CIRCUIT TO DETERMINE WHAT

CIRCUITS FEED AREAS OUTSIDE THE SCOPE OF WORK. CIRCUITS WHICH

MUST BE MAINTAINED ARE TO BE RE-ROUTED TO THE NEW PANEL

LOCATION BY PROVIDING AN ADEQUATELY SIZED PULL BOX AND

SPLICING AND EXTENDING THE CONDUCTORS.

23. THE ELECTRICAL CONTRACTOR SHALL CARRY ALL COSTS ASSOCIATED

WITH DISABLING THE CONNECTIONS TO THE EXISTING MUNICIPAL LOOP

DURING FINAL CONNECTIONS AND TESTING AND SHALL CARRY COSTS FOR

RECONNECTION OF LOOP.

22. MODIFICATIONS TO THE EXISTING FIRE ALARM SYSTEM SHALL BE

COORDINATED WITH THE FIRM WHO HOLDS THE EXISTING SYSTEM

MAINTENANCE CONTRACT. THE FIRM WHO HOLDS THE EXISTING SYSTEM

MAINTENANCE CONTRACT SHALL MAKE ALL FINAL CONNECTIONS, AND

PERFORM ALL PROGRAMMING AND TESTING. ALL COSTS ASSOCIATED WITH

FINAL CONNECTIONS, PROGRAMMING AND TESTING SHALL BE INCLUDED

UNDER THIS CONTRACT AND SHALL BE THE RESPONSIBILITY OF THE

ELECTRICAL CONTRACTOR.

21. ALL GROUND CONDUCTORS SHALL BE GREEN, ISOLATED GROUND

CONDUCTORS SHALL BE GREEN/ YELLOW STRIPPED, AND NEUTRAL

CONDUCTORS SHALL BE WHITE.

20. FURNISH GROUNDING/ BONDING BUSHINGS ONTO ALL CONDUIT

ENTERING/LEAVING BOXES.

19. CURRENT CARRYING MATERIAL USED SHALL BE COPPER, INCLUDING

PANELBOARD BUS MATERIALS AND TRANSFORMER WINDINGS.

18. FOR EXACT LOCATION OF MECHANICAL EQUIPMENT (AC UNITS, FANS,

PUMPS, ETC.) REFER TO RESPECTIVE TRADES DRAWINGS. FOR ELECTRICAL

INFORMATION, REFER TO MEP COORDINATION SCHEDULE.

17. ELECTRICAL CONTRACTOR IS TO COORDINATE THE EXACT LOCATION

OF LIGHTING FIXTURES IN MECHANICAL AND STORAGE AREAS WITH

OTHER TRADES.

16. FOR EXACT LOCATION OF LIGHTING FIXTURES SEE REFLECTED

CEILING PLAN DRAWINGS. FOR MOUNTING HEIGHT OF UNDER-COUNTER

LIGHTING FIXTURES AND OTHER TASK LIGHTING, REFER TO

ARCHITECTURAL ELEVATION DRAWINGS.

15. CONTRACTOR SHALL VERIFY ALL DOORS SWINGS BEFORE INSTALLING

SWITCH BOXES.

14. MOUNTING HEIGHTS SHALL BE AS INDICATED ON MOUNTING HEIGHT

DETAIL.

1. THE CONTRACTOR SHALL FURNISH LABOR, MATERIALS, TOOLS AND OTHER

EQUIPMENT REQUIRED TO INSTALL THE WORK SHOWN AND SPECIFIED. THE

CONTRACTOR SHALL FURNISH AND INSTALL ITEMS NECESSARY FOR A

COMPLETE ELECTRICAL SYSTEM. MATERIALS SHALL BE NEW AND SHALL

BEAR THE REGISTERED UL MARK. WORK SHALL CONFORM WITH THE

NATIONAL FIRE PROTECTION ASSOCIATION STANDARD 70 (NEC), THE

NATIONAL ELECTRICAL CODE (NEC), AND APPLICABLE FEDERAL, STATE AND

LOCAL CODES. CONTRACTOR SHALL SECURE PERMITS AND PAY THE FEES

REQUIRED TO CARRY OUT HIS WORK. THE CONTRACTOR SHALL FURNISH

COPIES OF CERTIFICATES AND PERMITS TO THE ARCHITECT.

2. THE DRAWINGS AND SPECIFICATIONS INDICATE THE INTENT OF THE

DESIGN AND SHALL BE CONSIDERED AS DIAGRAMMATIC ONLY. EXACT

LOCATIONS FOR OUTLETS AND EQUIPMENT SHALL BE DETERMINED AT THE

SITE AS WORK PROGRESSES. DIMENSIONS AND CONDITIONS SHALL BE

CHECKED AND VERIFIED BY THE CONTRACTOR AT THE SITE. FINAL WORK

SHALL BE DOCUMENTED ON AS BUILT RECORD DRAWINGS.

3. PIPING, CONDUITS AND EQUIPMENT OF ALL TRADES SHALL BE

PROPERLY COORDINATED AND SET TO MAINTAIN THE CLEARANCES

REQUIRED BY APPLICABLE FEDERAL, STATE AND LOCAL CODES.

4. CONDUIT RUNS CROSSING EXPANSION JOINTS SHALL HAVE

EXPANSION OR EXPANSION DEFLECTION TYPE FITTINGS AS REQUIRED.

VERIFY EXISTING JOINTS BY FIELD MEASUREMENTS.

13. OUTDOOR ELECTRICAL EQUIPMENT SHALL BE NEMA 3R TYPE,

UNLESS OTHERWISE NOTED.

12. RECEPTACLES, SWITCHES, LIGHTING FIXTURES, SMOKE DETECTORS,

ETC. INDICATE QUANTITY, EXACT LOCATIONS OF DEVICES SHALL BE

DETERMINED IN THE FIELD AND COORDINATE WITH ARCHITECTURAL

DRAWINGS.

11. ALL BRANCH CIRCUITS (LIGHTING AND POWER) SHALL HAVE A DEDICATED

NEUTRAL CONDUCTOR. COMMON NEUTRALS WILL NOT BE ALLOWED.

10. EXIT SIGNS SHALL BE UNSWITCHED.

9. ALL RECEPTACLES INSTALLED IN UNFINISHED AREAS SHALL BE GFI

TYPE, MOUNTED 4'-0" ABOVE FINISHED FLOOR.

8. PANELBOARD SHALL BE MOUNTED SO THAT THE DISTANCE FROM THE

TOP CIRCUIT BREAKER OPERATING HANDLE TO THE FLOOR SHALL NOT

EXCEED 6'-6".

7. WIRING DEVICES SHALL BE MOUNTED IN ACCORDANCE WITH THE

LATEST REQUIREMENTS OF THE ARCHITECTURAL BARRIERS BOARD.

6. LOAD CENTERS, PANELBOARDS AND SWITCHBOARDS SHALL BE

PROVIDED WITH DEDICATED SPACE EXTENDING FROM THE FLOOR TO THE

STRUCTURAL CEILING WITH A WIDTH AND DEPTH THAT OF THE

EQUIPMENT, INCLUDING ANY ADDITIONAL SPACE DESCRIBED IN OF THE

NEC. NO PIPING, DUCTS OR EQUIPMENT FOREIGN TO THE ELECTRICAL

EQUIPMENT OR ARCHITECTURAL APPURTENANCES SHALL BE PERMITTED

TO BE INSTALLED IN, ENTER OR PASS THROUGH SUCH SPACE.

5. RACEWAYS AND CABLE SHALL BE RUN CONCEALED IN FINISHED SPACES

UNLESS OTHERWISE NOTED.

MOLDED CASE SWITCHMCSW

KAIC

INTERRUPTING CAPACITYIC

BOND BONDING JUMPER

EQUIPMENT GROUND

CONDUCTOR

EGC

AFG

ATS

AWG

CB

CKT

CT

CWS

EMT

MAX

MC METAL CLAD CABLE

MAXIMUM

ELECTRICAL METALLIC TUBING

CONDUIT WALL SEAL

CIRCUIT

CIRCUIT BREAKER

AMERICAN WIRE GAUGE

AUTOMATIC TRANSFER SWITCH

ABOVE FINISHED GRADE

ARC-FAULT CIRCUIT

INTERRUPTER

AFCI

EACHEA

A

AL

ARCH

C

CAT

BLDG

CATALOG

CONDUIT - RACEWAY

BUILDING

ARCHITECT

ALUMINUM

AMPERES

CU

COL

EM

EC

DWG

FT

FMS

HVAC

MCB

kW kVA

GC

EMS ENERGY MANAGEMENT SYSTEM

FACILITIES MANAGEMENT

SYSTEM

GENERAL CONTRACTOR

MAIN CIRCUIT BREAKER

KILOWATTS

KILOVOLT AMPERES

FEET

EMERGENCY

ELECTRICAL CONTRACTOR

DRAWING

COPPER

COLUMN

KCMIL

MCC

THOUSAND CIRCULAR MILS

MOTOR CONTROL CENTER

FA

LTG

ATC

LIGHTING

FIRE ALARM

FU

MCP MOTOR CIRCUIT PROTECTOR

FUSE

ELECTRIC WATER COOLEREWC

ABBREVIATIONS

cd CANDELA

DUAL ELEMENT TIME DELAYDETD

DIAMETERDIA

FIRE ALARM ANNUNCIATORFAA

TWISTED PAIRTP

RNC RIGID NON-METAL CONDUIT

RMC RIGID METAL CONDUIT

N

WITHW/

MLO

NEC

TSP

UL

UNO

WP WEATHERPROOF

UNLESS NOTED OTHERWISE

UNDERWRITER'S

LABORATORIES

TWISTED SHIELDED PAIR

NATIONAL ELECTRICAL CODE

MAIN LUGS ONLY

GALVANIZED RIGID STEEL

CONDUIT

RGS

SATS

PT POTENTIAL TRANSFORMER

MISC

NO

NC

MTD

NL

NTS

SP

PVC

POS

MOUNTED

SPARE

NOT TO SCALE

NIGHT LIGHT

NORMALLY OPEN

NORMALLY CLOSED

MISCELLANEOUS

SWBD

TL

UG

TEL

TWIST LOCK

UNDERGROUND OR UNDER

GRADE

TELEPHONE

SWITCHBOARD

W

TRANS

PWR

PNL

P

POWER

PANEL

WYE

DELTA

TRANSFORMER

WIRE

VOLT

RSC RIGID STEEL CONDUIT

SE SERVICE ENTRANCE

AMPERE FRAMEAF

ABOVE FINISHED FLOORAFF

AMPERE INTERRUPTING CAPACITYAIC

ACT ACOUSTICAL CEILING TILE

ANN ANNUNCIATOR

ANSI

AT AMPERE TRIP

BR BRANCH

CLG CEILING

CMS CABLE MANAGEMENT SYSTEM

CMU CONCRETE MASONRY UNIT

DP DISTRIBUTION PANEL

ELECTRICALELEC

ELEVATORELEV

EO ELECTRICALLY OPERATED

EQUIPMENTEQUIP

EXPLOSION PROOFEXP

FLUORESCENTFLUOR

GROUNDG

GAUGEGA

GENERATORGEN

GROUND FAULTGF

GROUND FAULT INTERRUPTERGFI

GFCI

GWB GYPSUM WALL BOARD

HIGH INTENSITY DISCHARGEHID

HAND-OFF-AUTOHOA

HORSE POWERHP

HERTZHZ

HEATERHTR

HOURHR

GND GROUND

KV KILOVOLTS

KILOVOLT AMPERES REACTIVEkVAR kWH KILOWATTS HOURS

INCANDESCENTINC

IMC INTERMEDIATE METAL CONDUIT

JUNCTION BOXJB

MAIN DISTRIBUTION PANELMDP

MECH MECHANICAL

MTG MOUNTING

MIN MINIMUM

MEDIUM VOLTAGEMV

NOT APPLICABLENA

NEMA

NFPA

NIC NOT IN CONTRACT

OCPD

PANEL BOARDPNLBD

PH PHASE

SW SWITCH

SWITCH GEARSWGR

KEC

STANDBY AUTOMATIC

TRANSFER SWITCH

POLYVINYL CHLORIDE,

RACEWAY

PROVIDED UNDER OTHER

SECTIONS

OVER CURRENT

PROTECTION DEVICE

NATIONAL FIRE PROTECTION

ASSOCIATION

NATIONAL ELECTRICAL

MANUFACTURERS

ASSOCIATION

NEUTRAL (GROUNDED

CONDUCTOR)

KITCHEN EQUIPMENT

CONTRACTOR

THOUSAND AMPERES

INTERRUPTING CAPACITY

HEATING, VENTILATION & AIR

CONDITIONING

GROUND FAULT CIRCUIT

INTERRUPTER

CURRENT TRANSFORMER OR

CABLE TRAY

AUTOMATIC TEMPERATURE

CONTROL

AMERICAN NATIONAL

STANDARDS INSTITUTE

V

CM

S

V

BA

SS

PA

PUBLIC ADDRESS SYSTEM LEGEND

MICROPHONE OUTLET - WALL MOUNTED 18" AFF, UNLESS

NOTED OTHERWISE

"C" - DENOTES FLUSH CEILING MOUNTED

"F" - DENOTES FLUSH FLOOR MOUNTED

SPEAKER - BI-DIRECTIONAL WALL MOUNTED

VOLUME CONTROL UNIT -WALL MOUNTED 48" AFF

PUBLIC ADDRESS SYSTEM AMPLIFIER

"BA" - DENOTES BOOSTER AMPLIFIER

SPEAKER - CEILING OR WALL MOUNTED RESPECTIVELY

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

CONSULTANT ARCHITECT/ENGINEER OF RECORD

WBRC

A R C H I T E C T S • E N G I N E E R S

WWW.WBRCAE.COM

BANGOR, MAINE 207-947-4511

PORTLAND, MAINE 207-828-4511

SARASOTA, FLORIDA 941-556-0757

STAMP

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

Project TitleDrawing Title Phase

Location

Issue Date

Project Number

Building Number

Drawing Number

Checked Drawn

TRUE NORTH

PROJECT NORTH VA RI FACILITIES MANAGEMENT

SERVICE

Approved:

FULLY SPRINKLERED

NEW MENTAL HEALTH

BUILDING 38 - PHASE 1

830 CHALKSTONE AVE PROVIDENCE, RI 02908

650-332

Engineering Discipline:

/1

/2

:5

:0

P

M C

R e v it P ro je c ts

\1

.0

-V

A M

C P ro v id e n c e

M e n ta l H e a lt h

B ld g

C e n tr a l( k p ro u ty X

J X

.r v t

EJ0.0

KT BG10 APR 2019

CONSTRUCTION

DOCUMENTS

ELECTRICAL - LEGEND

DWG NO. DRAWING TITLE

EJ0.0 ELECTRICAL - LEGEND

ES0.0 ELECTRICAL - SITE PLAN

ES0.1 ELECTRICAL - LIGHTNING PROTECTION PLAN

EL1.0 ELECTRICAL - BASEMENT - LIGHTING PLAN

EL1.1 ELECTRICAL - FIRST FLOOR - LIGHTING PLAN

EL1.2 ELECTRICAL - SECOND FLOOR - LIGHTING PLAN

EL1.3 ELECTRICAL - BASEMENT - NM PHOTOMETRIC

CALCULATION

EL1.4 ELECTRICAL - BASEMENT - EM PHOTOMETRIC

CALCULATION

EL1.5 ELECTRICAL - FIRST FLOOR - NM PHOTOMETRIC

CALCULATION

EL1.6 ELECTRICAL - FIRST FLOOR - EM PHOTOMETRIC

CALCULATION

EL1.7 ELECTRICAL - SECOND FLOOR - NM PHOTOMETRIC

CALCULATION

EL1.8 ELECTRICAL - SECOND FLOOR - EM PHOTOMETRIC

CALCULATION

EL1.9 ELECTRICAL - SITE - PHOTOMETRIC CALCULATION

EP1.0 ELECTRICAL - BASEMENT - POWER PLAN

EP1.1 ELECTRICAL - FIRST FLOOR - POWER PLAN

EP1.2 ELECTRICAL - SECOND FLOOR - POWER PLAN

EK0.0 ELECTRICAL - RISER DIAGRAMS I

EK0.1 ELECTRICAL - RISER DIAGRAMS II

EK0.2 ELECTRICAL SCHEDULES

EK1.0 ELECTRICAL - DETAILS

EK1.1 ELECTRICAL - DETAILS

Revisions: Date:

S T

A

T E

O F

R H O D

E

I S L A

N D

HOPE

04/16/2019

UP

UP

HH

HH

HH

HH

A

B

APPROXIMATE LOCATION

OF ELECTRICAL ROOM 110

APPROXIMATE LOCATION

OF MAIN ELECTRCAL

ROOM IN BASEMENT

EXISTING GENERATOR

NEW UTILITY

TRANSFORMER

D

C -

UTILITY POLE

BUILDING 14

T E

T

EXISTING TO REMAIN

UTILITY TRANSFORMER

SERVING BUILDING 32.

CONDUIT NOTES:

THE RACEWAY PROVIDED FOR THE SECONDARY FEEDERS

BETWEEN THE MAIN BUILDING TRANSFORMER AND THE

SWITCHBOARD SHALL BE AS RIGID STEEL ELBOWS WITH ONLY

STRAIGHT PORTIONS OF UNDERSLAB RACEWAY ALLOWED TO BE

PVC RACEWAY.

CONDUIT DENOTATIONS:

DUCTBANK SECTION "A"

UTILITY SECONDARIES

PP

NO SCALE

P 4" PVC CONDUIT FOR

SECONDARY FEEDERS

S4P

S4 4" PVC SPARE CONDUIT

DUCTBANK SECTION "B"

GENERATOR SECONDARIES

S4G

NO SCALE

G 4" PVC CONDUIT FOR

EMERGENCY FEEDERS

S4

D 4" PVC CONDUIT FOR

FIBER AND DATA.

S4

DUCTBANK SECTION "C"

NO SCALE

S5 S5

DUCTBANK SECTION "D"

NO SCALE

D S4

S5 5" RIGID GALVANIZED

STEEL CONDUIT

S4

CONTRACTOR SHALL COORDINATE MOUNTING HEIGHT OF

ALL DEVICES WITH ARCHITECTS DRAWINGS PRIOR TO

ROUGH IN.

CIRCUIT NUMBERS ARE FOR DESCRIPTIVE PURPOSES ONLY.

EXACT NUMBERS SHALL BE DETERMINED IN FIELD AND

SHALL BE NOTED ON THE CONTRACTORS AS-BUILT

DRAWINGS.

BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED AND

INSTALLED FOR A MAXIMUM BRANCH CIRCUIT VOLTAGE

DROP OF 3% FROM PANELBOARD. TOTAL VOLTAGE DROP

FROM SERVICE ENTRY TO LAST DEVICE ON CIRCUIT SHALL

NOT EXCEED 5%. REFER TO SPECIFICATIONS FOR

ADDITIONAL REQUIREMENTS AND OPTIONS.

SITE PLAN NOTES

1.

2.

3.

UTILITY COMPANY TO PROVIDE NEW UTILITY

TRANSFORMER. CONTRACTOR SHALL INSTALL NEW

CONDUIT FROM NEW UTILITY POLE TO TRANSFORMER.

PRIMARY WIRING BY UTILITY COMPANY. PROVIDE NEW

CONDUIT AND WIRING TO NEW MAIN ELECTRICAL

ROOM. REFER TO RISER DIAGRAM FOR WIRE SIZING.

SITE PLAN KEYED NOTES

PROVIDE NEW UNDERGROUND DUCTBANK TO

EXISTING GENERATOR PANELBOARD WITHIN BUILDING

32. REFER TO RISER DIAGRAM FOR WIRE SIZING.

ELECTRICAL CONTRACTOR SHALL PROVIDE A UL

MASTER CERTIFIED LIGHTNING PROTECTION SYSTEM

ON ROOF THAT CONNECTS TO GROUND RING. REFER TO

SPECIFICATION SECTION FOR ADDITIONAL

INFORMATION.

REFER TO RISER DIAGRAM ON CONTRACT DRAWING EK0.0

FOR ADDITIONAL DETAIL ON ELECTRIC SERVICE.

4.

CONNECT FIBER TO EXISTING SPARE FIBER PATCH

PANEL TERMINAL LOCATED IN BASEMENT OF BUILDING

14. WIRING SHALL BE ROUTED PARALLEL TO EXISTING

RACEWAY

HAND HOLES ARE SHOWN FOR REFERENCE ONLY.

COORDINATE QUANTITY AND PLACEMENT IN FIELD.

5.

26.0001

NONE

12" YELLOW WARNING TAPE SHALL

RUN THE LENGTH OF CONDUIT RUN

(TYPICAL)

REFER TO SITE PLANS FOR QUANTITIES

6" CLEAN SAND

30" (MIN) COMPACT NATIVE BACKFILL

VOID OF OBJECTS OVER

TWO INCHES IN DIAMETER

AND VOID OF DECOMPOSED

MATERIAL.

TYPICAL DIRECT BURIAL DUCT BANK SECTION

3" CONCRETE

ENCASEMENT

030' 15'

GRAPHIC SCALE

30' 60' 120'

SCALE: 1" = 30' - 0"

CONDUIT PENETRATION THROUGH EXISTING WALL

26.6507

NONE

FLANGED TYPE SEALING

BUSHING AS SPECIFIED

CONCRETE, BRICK, OR

CMU WALL

INSIDE OF

STRUCTURE

OUTSIDE OF

STRUCTURE

MEMBRANE CLAMP

CONDUIT

DUCT BANK

JUNCTION

BOX

RIGID STEEL

CONDUIT

PROVIDE

FIRESTOP

PROVIDE WATER

PROOFINGGRADE

SLEEVE OR SLEEVE OPENING

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

CONSULTANT ARCHITECT/ENGINEER OF RECORD

WBRC

A R C H I T E C T S • E N G I N E E R S

WWW.WBRCAE.COM

BANGOR, MAINE 207-947-4511

PORTLAND, MAINE 207-828-4511

SARASOTA, FLORIDA 941-556-0757

STAMP

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

Project TitleDrawing Title Phase

Location

Issue Date

Project Number

Building Number

Drawing Number

Checked Drawn

TRUE NORTH

PROJECT NORTH VA RI FACILITIES MANAGEMENT

SERVICE

Approved:

FULLY SPRINKLERED

NEW MENTAL HEALTH

BUILDING 38 - PHASE 1

830 CHALKSTONE AVE PROVIDENCE, RI 02908

650-332

Engineering Discipline:

/1

/2

:1

:5

P

M C

U s e rs

\b g ri ff in

\D o c u m e n ts \1

.0

-V

A M

C P ro v id e n c e

M e n ta l H e a lt h B ld g

C e n tr a l(

B

G R

IF

F

IN

.r v t

ES0.0

KT BG10 APR 2019

CONSTRUCTION

DOCUMENTS

ELECTRICAL - SITE PLAN

Revisions: Date:

BUILDING 32

cbellao Stamp

UP

FINISHED

GRADE

EXOTHERMIC

WELD

12" MIN

48" MIN

EXISTING

GROUND GRID

#4/0 BARE

COPPER

GROUND

BUILDING

LIGHTNING

PROTECTION

SYSTEM

#1/0 BARE COPPER DOWN

CONDUCTOR IN 1" PVC

SCHEDULE 40 CONDUIT

LIGHTING PROTECTION DOWN

CONDUCTOR (TYP)

CONNECTION TO STRUCTURAL STEEL

(TYP)

#1/0 AWG BARE COPPER GROUND

CABLE (TYP) CIRCLE AROUND

BUILDING 4'-0" FROM EXTERIOR WALL

08' 4'

GRAPHIC SCALE

8' 16' 24'

SCALE: 1/8" = 1' - 0"

SITE PLAN KEYED NOTES

1 GROUND RING SHALL ENCIRCLE ENTIRE BUILDING AND

CONSIST OF #1/0 AWG BURIED 3 FEET BELOW SURFACE.

GROUND RING SHALL CONNECT TO BUILDING STEEL AT

EVERY OTHER COLUMN. GROUND RING SHALL HAVE

ENCASED ELECTRODE, HAVING AT LEAST 20 FEET OF

EXPOSED COPPER.

LIGHTNING PROTECTION SYSTEM NOTES:

1. PROVIDE A UL MASTER LABELED LIGHTNING

PROTECTION SYSTEM IN COMPLIANCE WITH UL 96A, LP1-

175, AND NFPA 780. THE SYSTEM SHALL CONSIST OF THE

FOLLOWING:

A. COPPER CABLE, WITH SOLID AIR TERMINALS

B. AIR TERMINALS SHALL INCLUDE BASES

SPECIFICALLY DESIGNED FOR ROOF MATERIAL.

C. AIR TERMINALS SHALL BE SOLID COPPER.

2. CONTRACTOR SHALL PREPARE A COMPLETE

LIGHTNING PROTECTION SYSTEM DESIGN STAMPED BY

A REGISTERED DESIGN PROFESSIONAL FOR REVIEW

AND APPROVAL BY THE ENGINEER. DOCUMENTS SHALL

INCLUDE LAYOUT OF LIGHTING PROTECTION SYSTEM

INCLUDING AIR TERMINALS, DOWN CONDUCTORS,

MOUNTING HARDWARE, CONDUCTORS, SUPPORTS, AND

ALL NECESSARY ANCILLARY EQUIPMENT.

3. REFER TO SPECIFICATION SECTIONS 260526

(GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS)

AND 264100 (FACILITY LIGHTNING PROTECTION) FOR

ADDITIONAL DETAIL.

LIGHTNING PROTECTION SYSTEM DETAIL

NO SCALE

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

CONSULTANT ARCHITECT/ENGINEER OF RECORD

WBRC

A R C H I T E C T S • E N G I N E E R S

WWW.WBRCAE.COM

BANGOR, MAINE 207-947-4511

PORTLAND, MAINE 207-828-4511

SARASOTA, FLORIDA 941-556-0757

STAMP

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

Project TitleDrawing Title Phase

Location

Issue Date

Project Number

Building Number

Drawing Number

Checked Drawn

TRUE NORTH

PROJECT NORTH VA RI FACILITIES MANAGEMENT

SERVICE

Approved:

FULLY SPRINKLERED

NEW MENTAL HEALTH

BUILDING 38 - PHASE 1

830 CHALKSTONE AVE PROVIDENCE, RI 02908

650-332

Engineering Discipline:

/1

/2

:1

:5

P

M C

U s e rs

\b g ri ff in

\D o c u m e n ts \1

.0

-V

A M

C P ro v id e n c e

M e n ta l H e a lt h B ld g

C e n tr a l(

B

G R

IF

F

IN

.r v t

ES0.1

KT BG10 APR 2019

CONSTRUCTION

DOCUMENTS

ELECTRICAL - LIGHTNING

PROTECTION PLAN

1/8" = 1'-0"ES0.1

1 ELECTRICAL - LIGHTNING PROTECTION PLAN

Revisions: Date:

cbellao

OS

OS

OS

OSOSOSOS

OS

OSOS

OS OS

OSOS

OS

OS

OS

OS

OS

CIRCUIT NUMBERS ARE FOR DESCRIPTIVE PURPOSES ONLY.

EXACT NUMBERS SHALL BE DETERMINED IN FIELD AND

SHALL BE NOTED ON THE CONTRACTORS AS-BUILT

DRAWINGS.

EXIT SIGNS, FIXTURES DESIGNATED AS NIGHT LIGHTS, AND

EMERGENCY BATTERY UNITS SHALL BE CONNECTED TO AN

UNSWITCHED, CONSTANT "ON" SOURCE AS INDICATED.

FIXTURES SHOWN TO INCLUDE EMERGENCY BALLAST SHALL

HAVE ADDITIONAL "CONSTANT ON" SOURCE.

BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED AND

INSTALLED FOR A MAXIMUM BRANCH CIRCUIT VOLTAGE

DROP OF 3% FROM PANELBOARD. TOTAL VOLTAGE DROP

FROM SERVICE ENTRY TO LAST DEVICE ON CIRCUIT SHALL

NOT EXCEED 5%. REFER TO SPECIFICATIONS FOR

ADDITIONAL REQUIREMENTS AND OPTIONS

LIGHTING PLAN NOTES

1.

2.

3.

4.

EMERGENCY LIGHTING BYPASS RELAYS ARE NOT SHOWN

ON THE DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF

THE ELECTRICAL CONTRACTOR TO REVIEW THE LIGHTING

DRAWINGS AND PROVIDE EMERGENCY LIGHTING BYPASS

RELAYS AS REQUIRED TO MEET LOCAL AND STATE BUILDING

CODES. THE ELECTRICAL CONTRACTOR SHALL FURNISH

AND INSTALL A UL 924 LISTED EMERGENCY LIGHTING

BYPASS RELAY DEVICE IN ALL ROOMS AND AREAS

INDICATED WITH EMERGENCY LIGHTING (LIFE SAFETY OR

CRITICAL). THIS INCLUDES PROVIDING A MINIMUM OF ONE

BYPASS RELAY PER LIGHTING CONTROL DEVICE (E.G.

SWITCH, DIMMER, OCCUPANCY SENSOR, ETC.) SERVING

EMERGENCY LIGHTS TO AUTOMATICALLY BYPASS THE

LIGHTING CONTROL WHEN NORMAL POWER IS LOST AND

TURN THE EMERGENCY LIGHTING TO FULL ON. THE

ELECTRICAL CONTRACTOR SHALL COORDINATE EXACT

BYPASS RELAY TYPE WITH THE LIGHTING CONTROL SYSTEM

AND LIGHTING FIXTURES PROVIDED TO ENSURE A FULLY

FUNCTIONAL LIGHTING SYSTEM IS INSTALLED MEETING ALL

LOCAL AND STATE REGULATIONS. BYPASS RELAY SHALL BE

MODEL ELCU-100 AS MANUFACTURED BY WATTSTOPPER OR

EQUAL.

5.

THE INTENT IS TO PROVIDE LIGHTING FIXTURES, CONTROLS,

WIRING AND CONDUIT. LIFE SAFETY LIGHTING SHALL BE

ADDRESSED THROUGH INTEGRAL BATTERY BACKUP.ALL

LIGHTING FIXTURES SHALL BE CONTROLLED BY LOCAL

LIGHTING CONTROLS WITH THE EXCEPTION AS FOLLOW:

STAIRWELLS SHALL BE CONTROLLED VIA INTEGRAL

OCCUPANCY SENSING LIGHTING FIXTURES WHICH FAIL ON.

EXTERIOR LIGHTING FIXTURES SHALL BE CONTROLLED BY

COMBINATION TIME-CLOCK AND PHOTO CELL. THE TIME-

CLOCK SHALL BE AN ASTRONOMICAL TIMECLOCK CAPABLE

OF 7-DAY SCHEDULES AND PRE-SET HOURS.

6.

LR-2 LR-2E LR-2 LR-2 LR-2E

LR-2

LP-1E

LP-1E

LP-1ELP-1

LP-1E

LP-1E

LR-3E LR-3

LR-3

LR-3 LR-3 LR-3

LR-3LR-3

LR-3 LR-3E

LR-2E

LR-2

LR-2E

LR-2

LR-3

LR-3E

LR-3

LR-3E LR-3E

LR-3

LR-3 LR-3

LR-3E

LR-3LR-3LR-3

LR-3

LR-3 LR-3

LR-3

LR-3

LR-3

LR-3

LR-3

LR-3 LR-3

LR-3 LR-3

LR-3E LR-3

LR-3LR-3

LR-3 LR-3

LR-3

LR-3

LR-3

LR-3

LR-3

LR-3

LR-3

LR-3

LR-3E

LR-3

LR-3

LR-3

LR-3

LR-3

LR-3

LR-3

LR-3

LR-3E

LR-3

JJ-1JJ-1

CONSULT ROOM

CONSULT ROOM

EMERG. ELECT.

018A

CLASSROOM STORAGE

027A

CLASSROOM

ELEV 2

ELEV 1

CLASSROOM

STAFF TOILET

OCCUPATIONAL THERAPY ROOM

OFFICE

OT OFFICE

ELECTRICAL

TELE/ DATA

CORRIDOR

OFFICE

OFFICE

PRRC CUBES

WATER SERVICE

CONSULT ROOM - EXTRA

TOILET

TOILET

ELEV. CONTROL ROOM

STAIR 1

ELEVATOR LOBBY

WAITING

CORRIDOR

D D D

O S

O S

D D D D

D

O S

LR-2LR-2E

LW-1

LP-1E

LW-2E

LR-2

C

D

E

F

G

76543 1 2

8.7

/2 EL1.0

/2 EL1.0

LD-1E

LD-1E

LD-1E

EX-1

EX-1

EX-1

EX-1 LR-4

LW-3

LW-3

aD

- 2CR411

- 1NP421

1 1

1 1 2

1 1

1 1 2

1b 1a

1a1b

2b 1a

1a1b

1b 1a

1 1 2

LW-3

bD

HAC

CLASSROOM STORAGE

027B

LW-1

LW-1

LW-2E

- 7CR411

c3D aD ac ac ac ac ac ac ac ac ac c3D bD bc bc bc bc bc bc bc bc bc

LR-2E

LR-2

LR-2

LR-3E

LR-3

LR-3

LR-3

LR-3

LW-2E

CORRIDOR

STAIR 2

STAFF TOILET

STAFF LOUNGE

DOS

A

B

8.7

/1 EL1.0

/1 EL1.0

LD-1

EX-1

EX-1

LR-3

LW-3

LW-2E

GRAPHIC SCALE

4' 2' 0 4' 8' 12'

SCALE: 1/4" = 1' - 0"

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

CONSULTANT ARCHITECT/ENGINEER OF RECORD

WBRC

A R C H I T E C T S • E N G I N E E R S

WWW.WBRCAE.COM

BANGOR, MAINE 207-947-4511

PORTLAND, MAINE 207-828-4511

SARASOTA, FLORIDA 941-556-0757

STAMP

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

Project TitleDrawing Title Phase

Location

Issue Date

Project Number

Building Number

Drawing Number

Checked Drawn

TRUE NORTH

PROJECT NORTH VA RI FACILITIES MANAGEMENT

SERVICE

Approved:

FULLY SPRINKLERED

NEW MENTAL HEALTH

BUILDING 38 - PHASE 1

830 CHALKSTONE AVE PROVIDENCE, RI 02908

650-332

Engineering Discipline:

/1

/2

:5

:2

P

M C

R e v it P ro je c ts

\1

.0

-V

A M

C P ro v id e n c e

M e n ta l H e a lt h

B ld g

C e n tr a l( k p ro u ty X

J X

.r v t

EL1.0

CMB BRG10 APR 2019

CONSTRUCTION

DOCUMENTS

ELECTRICAL - BASEMENT -

LIGHTING PLAN

1/4" = 1'-0"EL1.0

1 ELECTRICAL - BASEMENT - LIGHTING PLAN - PART A

1/4" = 1'-0"EL1.0

2 ELECTRICAL - BASEMENT - LIGHTING PLAN - PART B

FULL WIDTH

OF SOFFIT

Revisions: Date:

S T

A

T E

O F

R H O D

E

I S L A

N D

OS

OS

OS OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

J

OS

CIRCUIT NUMBERS ARE FOR DESCRIPTIVE PURPOSES ONLY.

EXACT NUMBERS SHALL BE DETERMINED IN FIELD AND

SHALL BE NOTED ON THE CONTRACTORS AS-BUILT

DRAWINGS.

EXIT SIGNS, FIXTURES DESIGNATED AS NIGHT LIGHTS, AND

EMERGENCY BATTERY UNITS SHALL BE CONNECTED TO AN

UNSWITCHED, CONSTANT "ON" SOURCE AS INDICATED.

FIXTURES SHOWN TO INCLUDE EMERGENCY BALLAST SHALL

HAVE ADDITIONAL "CONSTANT ON" SOURCE.

BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED AND

INSTALLED FOR A MAXIMUM BRANCH CIRCUIT VOLTAGE

DROP OF 3% FROM PANELBOARD. TOTAL VOLTAGE DROP

FROM SERVICE ENTRY TO LAST DEVICE ON CIRCUIT SHALL

NOT EXCEED 5%. REFER TO SPECIFICATIONS FOR

ADDITIONAL REQUIREMENTS AND OPTIONS

LIGHTING PLAN NOTES

1.

2.

3.

4.

EMERGENCY LIGHTING BYPASS RELAYS ARE NOT SHOWN

ON THE DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF

THE ELECTRICAL CONTRACTOR TO REVIEW THE LIGHTING

DRAWINGS AND PROVIDE EMERGENCY LIGHTING BYPASS

RELAYS AS REQUIRED TO MEET LOCAL AND STATE BUILDING

CODES. THE ELECTRICAL CONTRACTOR SHALL FURNISH

AND INSTALL A UL 924 LISTED EMERGENCY LIGHTING

BYPASS RELAY DEVICE IN ALL ROOMS AND AREAS

INDICATED WITH EMERGENCY LIGHTING (LIFE SAFETY OR

CRITICAL). THIS INCLUDES PROVIDING A MINIMUM OF ONE

BYPASS RELAY PER LIGHTING CONTROL DEVICE (E.G.

SWITCH, DIMMER, OCCUPANCY SENSOR, ETC.) SERVING

EMERGENCY LIGHTS TO AUTOMATICALLY BYPASS THE

LIGHTING CONTROL WHEN NORMAL POWER IS LOST AND

TURN THE EMERGENCY LIGHTING TO FULL ON. THE

ELECTRICAL CONTRACTOR SHALL COORDINATE EXACT

BYPASS RELAY TYPE WITH THE LIGHTING CONTROL SYSTEM

AND LIGHTING FIXTURES PROVIDED TO ENSURE A FULLY

FUNCTIONAL LIGHTING SYSTEM IS INSTALLED MEETING ALL

LOCAL AND STATE REGULATIONS. BYPASS RELAY SHALL BE

MODEL ELCU-100 AS MANUFACTURED BY WATTSTOPPER OR

EQUAL.

5.

LIGHTING PLAN KEYED NOTES

1 LIGHT FIXTURES IN WAITING ROOM 102 SHALL BE

CONTROLLED VIA TIMECLOCK.

THE INTENT IS TO PROVIDE LIGHTING FIXTURES, CONTROLS,

WIRING AND CONDUIT. LIFE SAFETY LIGHTING SHALL BE

ADDRESSED THROUGH INTEGRAL BATTERY BACKUP. ALL

LIGHTING FIXTURES SHALL BE CONTROLLED BY LOCAL

LIGHTING CONTROLS WITH THE EXCEPTION AS FOLLOW:

STAIRWELLS SHALL BE CONTROLLED VIA INTEGRAL

OCCUPANCY SENSING LIGHTING FIXTURES WHICH FAIL ON.

EXTERIOR LIGHTING FIXTURES SHALL BE CONTROLLED BY

COMBINATION TIME-CLOCK AND PHOTO CELL. THE TIME-

CLOCK SHALL BE AN ASTRONOMICAL TIMECLOCK CAPABLE

OF 7-DAY SCHEDULES AND PRE-SET HOURS.

6.

LR-1 LR-1E LR-1 LR-1 LR-1E LR-1

LR-2

LR-2E

LR-2

LR-2

LR-1E

LR-2ELR-2 LR-2

LP-1E

LP-1E

LR-3

LR-3

LR-3 LR-3E

LR-3 LR-3

LR-3

LR-3

LR-3

LR-3

LR-3E

LR-3

LR-3

LR-3E

LR-3

LR-5

LR-3

LR-3E

LR-3

LR-3E

LR-3

LR-3

LR-3

LR-3

LR-3E

LR-3

LR-3

LR-3

LR-3

LR-3E

LR-3

LR-3E

LR-3

LR-3

LR-3E

LR-3 LR-3

LR-3

LR-3

LR-3

OFFICE

OFFICE

CUBICLES

CONSULT ROOM

CONSULT ROOM

MEDICATION ROOM

INJECTION ROOM

CONSULT ROOM

TOILET

STORAGE

CONSULT ROOM

COMPUTER LAB

COMMUNICATION CENTER

CORRIDOR

100B

OFFICE

OFFICE

RC CUBES

CONSULT ROOM

TLT

TLT

TLT

HAC

CORRIDOR

100A

VESTIBULE

SECURITY / WC STORAGE

101AWAITING

CORRIDOR

100A

STAIR 1

ELEV 1

ELEV 2

O S

O S

O S

D D D

DOS

O S

D

D

D

D

D

D

O S

D

LR-2

LR-2

LW-2E

C

D

E

F

G

76543 1 2

8.7

LS-2LS-2LS-2LS-2

/2 EL1.1

/2 EL1.1

D

LW-2E

LD-1E

LD-1E

LD-1E

LD-1E

LW-1

EX-1

EX-1

EX-1

EX-1

EX-1

LR-4

LW-3

LW-3

LD-1 LD-1 LD-1

LD-2E LD-2E LD-2E LD-2E

- 2NP421

- 4CR411

4 4 4 4

2 2 2 2

2 4 2

2 2 2

4 2 2

2 4

2a 2

24a

2a 2

22a

LW-3 2

LW-3

LD-2E

MAIN ELECTRICAL ROOM

aD bD

LR-1

SL-1

SL-1

SL-1

SL-1 SL-1 SL-1 SL-1

44 44 44

SL-1

SL-1

- 44NP211

LS-1LS-1E

LS-2LS-2

- 2NP421

LR-2

LR-2E

LR-3

LR-3E

STAIR 2

CONSULT ROOM - EXTRA

D

LW-2E

A

B

8.7

LR-3

/1 EL1.1

/1 EL1.1

LR-3

EX-1

EX-1

LR-3E

LR-3

MEETING ROOM

SL-1

SL-1

SL-1E

LW-2E

SL-1

SITE LIGHT

GRAPHIC SCALE

4' 2' 0 4' 8' 12'

SCALE: 1/4" = 1' - 0"

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

CONSULTANT ARCHITECT/ENGINEER OF RECORD

WBRC

A R C H I T E C T S • E N G I N E E R S

WWW.WBRCAE.COM

BANGOR, MAINE 207-947-4511

PORTLAND, MAINE 207-828-4511

SARASOTA, FLORIDA 941-556-0757

STAMP

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

Project TitleDrawing Title Phase

Location

Issue Date

Project Number

Building Number

Drawing Number

Checked Drawn

TRUE NORTH

PROJECT NORTH VA RI FACILITIES MANAGEMENT

SERVICE

Approved:

FULLY SPRINKLERED

NEW MENTAL HEALTH

BUILDING 38 - PHASE 1

830 CHALKSTONE AVE PROVIDENCE, RI 02908

650-332

Engineering Discipline:

/1

/2

:5

:2

P

M C

R e v it P ro je c ts

\1

.0

-V

A M

C P ro v id e n c e

M e n ta l H e a lt h

B ld g

C e n tr a l( k p ro u ty X

J X

.r v t

EL1.1

CMB BRG10 APR 2019

CONSTRUCTION

DOCUMENTS

ELECTRICAL - FIRST FLOOR -

LIGHTING PLAN

1/4" = 1'-0"EL1.1

1 ELECTRICAL - FIRST FLOOR - LIGHTING PLAN - PART A

1/4" = 1'-0"EL1.1

2 ELECTRICAL - FIRST FLOOR - LIGHTING PLAN - PART B

FULL WIDTH

OF SOFFIT

Revisions: Date:

S T

A

T E

O F

R H O D

E

I S L A

N D

CIRCUIT NUMBERS ARE FOR DESCRIPTIVE PURPOSES ONLY.

EXACT NUMBERS SHALL BE DETERMINED IN FIELD AND

SHALL BE NOTED ON THE CONTRACTORS AS-BUILT

DRAWINGS.

EXIT SIGNS, FIXTURES DESIGNATED AS NIGHT LIGHTS, AND

EMERGENCY BATTERY UNITS SHALL BE CONNECTED TO AN

UNSWITCHED, CONSTANT "ON" SOURCE AS INDICATED.

FIXTURES SHOWN TO INCLUDE EMERGENCY BALLAST SHALL

HAVE ADDITIONAL "CONSTANT ON" SOURCE.

BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED AND

INSTALLED FOR A MAXIMUM BRANCH CIRCUIT VOLTAGE

DROP OF 3% FROM PANELBOARD. TOTAL VOLTAGE DROP

FROM SERVICE ENTRY TO LAST DEVICE ON CIRCUIT SHALL

NOT EXCEED 5%. REFER TO SPECIFICATIONS FOR

ADDITIONAL REQUIREMENTS AND OPTIONS

LIGHTING PLAN NOTES

1.

2.

3.

4.

EMERGENCY LIGHTING BYPASS RELAYS ARE NOT SHOWN

ON THE DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF

THE ELECTRICAL CONTRACTOR TO REVIEW THE LIGHTING

DRAWINGS AND PROVIDE EMERGENCY LIGHTING BYPASS

RELAYS AS REQUIRED TO MEET LOCAL AND STATE BUILDING

CODES. THE ELECTRICAL CONTRACTOR SHALL FURNISH

AND INSTALL A UL 924 LISTED EMERGENCY LIGHTING

BYPASS RELAY DEVICE IN ALL ROOMS AND AREAS

INDICATED WITH EMERGENCY LIGHTING (LIFE SAFETY OR

CRITICAL). THIS INCLUDES PROVIDING A MINIMUM OF ONE

BYPASS RELAY PER LIGHTING CONTROL DEVICE (E.G.

SWITCH, DIMMER, OCCUPANCY SENSOR, ETC.) SERVING

EMERGENCY LIGHTS TO AUTOMATICALLY BYPASS THE

LIGHTING CONTROL WHEN NORMAL POWER IS LOST AND

TURN THE EMERGENCY LIGHTING TO FULL ON. THE

ELECTRICAL CONTRACTOR SHALL COORDINATE EXACT

BYPASS RELAY TYPE WITH THE LIGHTING CONTROL SYSTEM

AND LIGHTING FIXTURES PROVIDED TO ENSURE A FULLY

FUNCTIONAL LIGHTING SYSTEM IS INSTALLED MEETING ALL

LOCAL AND STATE REGULATIONS. BYPASS RELAY SHALL BE

MODEL ELCU-100 AS MANUFACTURED BY WATTSTOPPER OR

EQUAL.

5.

THE INTENT IS TO PROVIDE LIGHTING FIXTURES, CONTROLS,

WIRING AND CONDUIT. LIFE SAFETY LIGHTING SHALL BE

ADDRESSED THROUGH INTEGRAL BATTERY BACKUP. ALL

LIGHTING FIXTURES SHALL BE CONTROLLED BY LOCAL

LIGHTING CONTROLS.

6.

LR-2LR-2ELR-2

MECHANICAL ROOM

CIRCULATION

ELEV 1

ELEV 2

STAIR 1

D

E

F

G

76543 1 2

8.7

LW-2E

EX-1

EX-1

LR-4

63 3

- 6CR411

LS-1

LS-1E

LS-1

LS-1

LS-1

LS-1E

LS-1

LS-1 LS-1

LS-1E

3 6

3 3

3 3

EX-1

EX-1

a

3a

JJ-1

LW-2E

SL-2SL-2

SL-1

44 44

LS-1

GRAPHIC SCALE

4' 2' 0 4' 8' 12'

SCALE: 1/4" = 1' - 0"

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

CONSULTANT ARCHITECT/ENGINEER OF RECORD

WBRC

A R C H I T E C T S • E N G I N E E R S

WWW.WBRCAE.COM

BANGOR, MAINE 207-947-4511

PORTLAND, MAINE 207-828-4511

SARASOTA, FLORIDA 941-556-0757

STAMP

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

Project TitleDrawing Title Phase

Location

Issue Date

Project Number

Building Number

Drawing Number

Checked Drawn

TRUE NORTH

PROJECT NORTH VA RI FACILITIES MANAGEMENT

SERVICE

Approved:

FULLY SPRINKLERED

NEW MENTAL HEALTH

BUILDING 38 - PHASE 1

830 CHALKSTONE AVE PROVIDENCE, RI 02908

650-332

Engineering Discipline:

/1

/2

:5

:2

P

M C

R e v it P ro je c ts

\1

.0

-V

A M

C P ro v id e n c e

M e n ta l H e a lt h

B ld g

C e n tr a l( k p ro u ty X

J X

.r v t

EL1.2

CMB BRG10 APR 2019

CONSTRUCTION

DOCUMENTS

ELECTRICAL - SECOND FLOOR -

LIGHTING PLAN

1/4" = 1'-0"EL1.2

1 ELECTRICAL - SECOND FLOOR - LIGHTING PLAN - PART A

FULL WIDTH

OF SOFFIT

Revisions: Date:

S T

A

T E

O F

R H O D

E

I S L A

N D

J J

NT

NT

N

N

J

J J

T V

2H

M

J

J

T V

2H

N T

N

DB

N

J

J

N D

S

J

J

N

DB

08' 4'

GRAPHIC SCALE

8' 16' 24'

SCALE: 1/8" = 1' - 0"

CONTRACTOR SHALL COORDINATE MOUNTING HEIGHT OF

ALL DEVICES WITH ARCHITECTS DRAWINGS PRIOR TO

ROUGH IN.

CIRCUIT NUMBERS ARE FOR DESCRIPTIVE PURPOSES ONLY.

EXACT NUMBERS SHALL BE DETERMINED IN FIELD AND

SHALL BE NOTED ON THE CONTRACTORS AS-BUILT

DRAWINGS.

BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED AND

INSTALLED FOR A MAXIMUM BRANCH CIRCUIT VOLTAGE

DROP OF 3% FROM PANELBOARD. TOTAL VOLTAGE DROP

FROM SERVICE ENTRY TO LAST DEVICE ON CIRCUIT SHALL

NOT EXCEED 5%. REFER TO SPECIFICATIONS FOR

ADDITIONAL REQUIREMENTS AND OPTIONS.

POWER PLAN NOTES

COORDINATE EXACT LOCATIONS OF ALL MECHANICAL

EQUIPMENT WITH HVAC, PLUMBING, AND FIRE PROTECTION

DRAWINGS.

ALL RECEPTACLES WITHIN 6' OF A SINK SHALL BE PROVIDED

WITH GFCI PROTECTION.

ALL RECEPTACLES IN SPACES DESIGNATED AS "WAITING

ROOM" SHALL BE TAMPERPROOF.

1.

2.

3.

4.

5.

6.

POWER PLAN KEYED NOTES

1 PROVIDE 2#12, 1#12G FOR ELECTRIC DOOR HARDWARE.

DOOR HARDWARE FURNISHED BY OTHERS.

2 UTILITY CONDUITS TO STUB UP THROUGH CHASE. ENTIRE

INTERIOR RUN OF CONDUITS SHALL BE ENCASED IN 3" OF

CONCRETE. SEE CONDUIT ENTRANCE DETAIL ON DRAWING

EK1.0. COORDINATE ROUTING WITH STRUCTURAL ENGINEER

TO AVOID STRUCTURAL FOOTINGS.

3 PROVIDE BOGEN PA SYSTEM HEAD-END. HEAD-END UNIT

SHALL BE MOUNTED IN RACK.

4 PROVIDE 2.2KVA APC SMART UPS WITH MANAGEMENT CARD.

THE BASIS OF DESIGN FOR THE ELEVATOR IS A 20HP

THYSEENKRUPP TRACTION ELEVATOR. CONTRACTOR SHALL

NOTIFY ARCHITECT AND ENGINEER IF MOTOR HORSEPOWER

IS DIFFERENT THAN BASIS OF DESIGN.

7.

CUH-38-0-01

CR411 CR211T5

CLASSROOM

CLASSROOM

CLASSROOM STORAGE

027A

STAFF TOILET

EMERG. ELECT.

018A

TELE/ DATA

ELECTRICAL

OFFICE

OCCUPATIONAL THERAPY ROOM

016CORRIDOR

OT OFFICE

OFFICE

OFFICE

PRRC CUBES

TOILET

TOILET

ELEV. CONTROL ROOM

CONSULT ROOM

CONSULT ROOM

CONSULT ROOM - EXTRA

WATER SERVICE

ELEV 2

ELEV 1

WAITING

ELEVATOR LOBBY

STAIR 1

AC-38-1-02

C

C

REF

C

C C

C

C

C C

C

PROJECTOR

PROJECTOR

- 6,8NP211 - 5,7NP211

- 2,4NP211

- 1,3NP211

- 1CR211

ELEV-1

ELEV #2 LTS

C

C

NP211

C

D

E

F

G

76543 1 2

8.7

- 10NP211

10 10

- 11NP211

11 11

- 12NP211

- 13NP211

- 14NP211

- 15NP211

- 16NP211

- 19NP211

- 18NP211

18 18

- 20NP211

- 21NP211

- 22NP211

- 23NP211

23 23 23

- 24NP211

- 25NP211

- 26NP211

- 27NP211

-CR211 12

- 28NP211

- 29NP211

- 30NP211

-CR211 11

- 34NP211

WATER

FOUNTAIN

POWER

/2 EP1.0

/2 EP1.0

ATCATC

- 35NP211

- 37NP211

CAMERA

- 10CR211

- 39,41NP211

NEMA 6 - 40R

WP

C

C

STORAGE

- 3CR211

CAM CAM

ELEV-2

ELEV #1 LTS

CLASSROOM STORAGE

027B

OVEN

SP-1

- 42NP211

SP-1

- 9NP211

KH-1

- 45NP211

SCREEN

SCREEN

- 46NP211

WAP

WAP

MC

HAC

- 48NP211

- 38NP211

- 1,3,5CR411

- 8,10,12CR411

UPS

UPS

- 6CR211

- 4CR211

SECURITY

HEAD-END

UNIT

- 49NP211

CUH-38-0-02

STAIR 2

CORRIDOR

STAFF TOILET

STAFF LOUNGE

032C

REF

C

C

USB

USB

- 3,5,7NP221

C

A

B

8.7

- 31NP211

- 32NP211

- 33NP21133

/1 EP1.0

/1 EP1.0

- 36NP211

- 4MDP

- 5MDP

CH-38-0-02

CH-38-0-01

MC

- 47NP211

SCREEN

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

CONSULTANT ARCHITECT/ENGINEER OF RECORD

WBRC

A R C H I T E C T S • E N G I N E E R S

WWW.WBRCAE.COM

BANGOR, MAINE 207-947-4511

PORTLAND, MAINE 207-828-4511

SARASOTA, FLORIDA 941-556-0757

STAMP

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

Project TitleDrawing Title Phase

Location

Issue Date

Project Number

Building Number

Drawing Number

Checked Drawn

TRUE NORTH

PROJECT NORTH VA RI FACILITIES MANAGEMENT

SERVICE

Approved:

FULLY SPRINKLERED

NEW MENTAL HEALTH

BUILDING 38 - PHASE 1

830 CHALKSTONE AVE PROVIDENCE, RI 02908

650-332

Engineering Discipline:

/1

/2

:5

:3

P

M C

R e v it P ro je c ts

\1

.0

-V

A M

C P ro v id e n c e

M e n ta l H e a lt h

B ld g

C e n tr a l( k p ro u ty X

J X

.r v t

EP1.0

KT BG10 APR 2019

CONSTRUCTION

DOCUMENTS

ELECTRICAL - BASEMENT -

POWER PLAN

1/4" = 1'-0"EP1.0

1 ELECTRICAL - BASEMENT - POWER PLAN - PART A

1/4" = 1'-0"EP1.0

2 ELECTRICAL - BASEMENT - POWER PLAN - PART B

Revisions: Date:

S T

A

T E

O F

R H O D

E

I S L A

N D

JJ

N

N

N

N T

NT

NT

NM

S

S B

JJ

J

TV2

H

J

N T

J

N

S S

S

SSS

S

S

S

J

J

S

CONTRACTOR SHALL COORDINATE MOUNTING HEIGHT OF

ALL DEVICES WITH ARCHITECTS DRAWINGS PRIOR TO

ROUGH IN.

CIRCUIT NUMBERS ARE FOR DESCRIPTIVE PURPOSES ONLY.

EXACT NUMBERS SHALL BE DETERMINED IN FIELD AND

SHALL BE NOTED ON THE CONTRACTORS AS-BUILT

DRAWINGS.

BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED AND

INSTALLED FOR A MAXIMUM BRANCH CIRCUIT VOLTAGE

DROP OF 3% FROM PANELBOARD. TOTAL VOLTAGE DROP

FROM SERVICE ENTRY TO LAST DEVICE ON CIRCUIT SHALL

NOT EXCEED 5%. REFER TO SPECIFICATIONS FOR

ADDITIONAL REQUIREMENTS AND OPTIONS.

POWER PLAN NOTES

COORDINATE EXACT LOCATIONS OF ALL MECHANICAL

EQUIPMENT WITH HVAC, PLUMBING, AND FIRE PROTECTION

DRAWINGS.

ALL RECEPTACLES WITHIN 6' OF A SINK SHALL BE PROVIDED

WITH GFCI PROTECTION.

ALL RECEPTACLES IN SPACES DESIGNATED AS "WAITING

ROOM" SHALL BE TAMPERPROOF.

1.

2.

3.

4.

5.

6.

POWER PLAN KEYED NOTES

1 PROVIDE 2#12, 1#12G FOR ELECTRIC DOOR HARDWARE.

DOOR HARDWARE FURNISHED BY OTHERS.

OFFICE

OFFICE

CUBICLES

CONSULT ROOM

CONSULT ROOM

INJECTION ROOM

MEDICATION ROOM

CONSULT ROOM

TOILET

STORAGE

CORRIDOR

100B

COMPUTER LAB

OFFICE

OFFICE

112RC CUBES

TLT

TLT

CORRIDOR

100A

COMMUNICATION CENTER

CONSULT ROOM

SECURITY / WC STORAGE

101AVESTIBULE

WAITING

STAIR 1

ELEV 1

ELEV 2

HAC

TLT

C C

WP

C

D

E

F

G

76543 1 2

8.7

- 11NP221

- 13NP221

- 14NP221

14 14

- 16NP221 16 16

- 15NP221

- 17NP221

- 18NP221

- 19NP221

- 21NP221

- 20NP221

21 21

- 22NP221

- 23NP221

- 28NP221

- 29NP221

- 30NP221

- 31NP221

- 32NP221

- 33NP221

- 37NP221

- 38NP221

- 39NP221

- 40NP221

WATER FOUNTAIN POWER

/2 EP1.1

/2 EP1.1

ATC ATC

- 41NP221

C

C C

C C C

16 16 16

- 24NP221

24 24 24

252525

26 26 26

- 26NP221

- 25NP221

- 27NP221

CAMCAM

CAM

NP221

MAIN ELECTRICAL ROOM

NP421

T8

CONSULT ROOM

- 43NP221

- 45NP221

- 2CR211

C

- 46NP221

- 9NP221

- 48NP221

ADO

C

- 5CR211

- 7CR211

C

REF

ADO PUSH

BUTTON (TYP) CUH-38-1-01

- 1NP221

WIRELESS ADO

C

FACP

10STAIR 2

CONSULT ROOM - EXTRA

WP

A

B

8.7

- 34NP221

/1 EP1.1

/1 EP1.1

- 42NP221

- 36NP221

CAM

- 35NP221

MEETING ROOM

- 44NP221

GRAPHIC SCALE

4' 2' 0 4' 8' 12'

SCALE: 1/4" = 1' - 0"

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

CONSULTANT ARCHITECT/ENGINEER OF RECORD

WBRC

A R C H I T E C T S • E N G I N E E R S

WWW.WBRCAE.COM

BANGOR, MAINE 207-947-4511

PORTLAND, MAINE 207-828-4511

SARASOTA, FLORIDA 941-556-0757

STAMP

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

Project TitleDrawing Title Phase

Location

Issue Date

Project Number

Building Number

Drawing Number

Checked Drawn

TRUE NORTH

PROJECT NORTH VA RI FACILITIES MANAGEMENT

SERVICE

Approved:

FULLY SPRINKLERED

NEW MENTAL HEALTH

BUILDING 38 - PHASE 1

830 CHALKSTONE AVE PROVIDENCE, RI 02908

650-332

Engineering Discipline:

/1

/2

:5

:4

P

M C

R e v it P ro je c ts

\1

.0

-V

A M

C P ro v id e n c e

M e n ta l H e a lt h

B ld g

C e n tr a l( k p ro u ty X

J X

.r v t

EP1.1

KT BG10 APR 2019

CONSTRUCTION

DOCUMENTS

ELECTRICAL - FIRST FLOOR -

POWER PLAN

1/4" = 1'-0"EP1.1

1 ELECTRICAL - FIRST FLOOR - POWER PLAN - PART A

1/4" = 1'-0"EP1.1

2 ELECTRICAL - FIRST FLOOR - POWER PLAN - PART B

Revisions: Date:

S T

A

T E

O F

R H O D

E

I S L A

N D

J

M M

JJ J

M M

M

CONTRACTOR SHALL COORDINATE MOUNTING HEIGHT OF

ALL DEVICES WITH ARCHITECTS DRAWINGS PRIOR TO

ROUGH IN.

CIRCUIT NUMBERS ARE FOR DESCRIPTIVE PURPOSES ONLY.

EXACT NUMBERS SHALL BE DETERMINED IN FIELD AND

SHALL BE NOTED ON THE CONTRACTORS AS-BUILT

DRAWINGS.

BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED AND

INSTALLED FOR A MAXIMUM BRANCH CIRCUIT VOLTAGE

DROP OF 3% FROM PANELBOARD. TOTAL VOLTAGE DROP

FROM SERVICE ENTRY TO LAST DEVICE ON CIRCUIT SHALL

NOT EXCEED 5%. REFER TO SPECIFICATIONS FOR

ADDITIONAL REQUIREMENTS AND OPTIONS.

POWER PLAN NOTES

COORDINATE EXACT LOCATIONS OF ALL MECHANICAL

EQUIPMENT WITH HVAC, PLUMBING, AND FIRE PROTECTION

DRAWINGS.

1.

2.

3.

4.

NP431

CIRCULATION

MECHANICAL ROOM

ELEV 1

ELEV 2

STAIR 1

DCP-1

UH-38-2-01

HWP-38-2-01 HWP-38-2-02 HWP-38-2-03

BL-38-2-03 BL-38-2-02 BL-38-2-01

UH-38-2-02

CU-38-2-01

CU-38-2-02

EF-38-2-01

ATC

- 6,8NP231

- 7NP231

NP231

D

E

F

G

76543 1 2

8.7

- 14NP231

CHWP-38-2-01 CHWP-38-2-02

EF-38-2-02

- 15NP231

ERV-38-2-01

H-38-2-01

WH-1

CAM

- 3,5NP231- 2,4NP231- 7,9,11NP431

- 2,4,6NP431

- 1,3,5NP431

- 17NP231

- 8,10,12NP431 - 13,15,17NP431

- 14,16,18NP431

CAM

CAM

-NP231 16

EF-38-2-03

- 10,12NP231

- 9,11NP231

- 13NP231 - 18NP231

- 1NP231

- 19NP231

- 21NP231

VFD VFD

- 6MDP - 7MDP

- 20NP231

- 9CR211

WP

-NP231 22

-NP211 43

22WP

22WP

EPO EPO EPO

GRAPHIC SCALE

4' 2' 0 4' 8' 12'

SCALE: 1/4" = 1' - 0"

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

CONSULTANT ARCHITECT/ENGINEER OF RECORD

WBRC

A R C H I T E C T S • E N G I N E E R S

WWW.WBRCAE.COM

BANGOR, MAINE 207-947-4511

PORTLAND, MAINE 207-828-4511

SARASOTA, FLORIDA 941-556-0757

STAMP

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

Project TitleDrawing Title Phase

Location

Issue Date

Project Number

Building Number

Drawing Number

Checked Drawn

TRUE NORTH

PROJECT NORTH VA RI FACILITIES MANAGEMENT

SERVICE

Approved:

FULLY SPRINKLERED

NEW MENTAL HEALTH

BUILDING 38 - PHASE 1

830 CHALKSTONE AVE PROVIDENCE, RI 02908

650-332

Engineering Discipline:

/1

/2

:5

:4

P

M C

R e v it P ro je c ts

\1

.0

-V

A M

C P ro v id e n c e

M e n ta l H e a lt h

B ld g

C e n tr a l( k p ro u ty X

J X

.r v t

EP1.2

KT BG10 APR 2019

CONSTRUCTION

DOCUMENTS

ELECTRICAL - SECOND FLOOR -

POWER PLAN

1/4" = 1'-0"EP1.2

1 ELECTRICAL - SECOND FLOOR - POWER PLAN - PART A

Revisions: Date:

S T

A

T E

O F

R H O D

E

I S L A

N D

SWITCHBOARD

MDP

480/277V

3PHASE

1200A

MCB

NORM

P421 480/277V

3PHASE

100A

MCB

NORM

BASEMENT FLOOR

P211 208/120V

3PHASE

100A

MCB

NORM

T8

225KVA

NORM

P221 208/120V

3PHASE

600A

MCB

CR411

480/277V

3PHASE

100A

MCB

CR211

208/120V

3PHASE

400A

MCB

CRIT.

T5

75KVA

P431 480/277V

3PHASE

100A

MCB

NORM

FIRST FLOOR

SECOND FLOOR

3 SETS OF (3#600 KCMIL & 1#600KCMIL GSC, 4"C)

750kVA UTILITY

PAD MOUNTED

TRANSFORMER

MAIN ELECTRICAL ROOM 110

ELECTRICAL CLOSET 018A ELECTRICAL ROOM 018

MECHANICAL ROOM 202

DB

208/120V

3PHASE

1000A

MLO

EMERGENCY ELECTRICAL

ROOM

CRIT.

NORM

P231 208/120V

3PHASE

200A

MCB

CRIT.

BUILDING 32

1 PROVIDE 400A-3P ENCLOSED CIRCUIT BREAKER. TAP EXISTING SWITCHBOARD'S BUS

USING 10 FOOT TAP RULE IN ACCORDANCE WITH NEC 240.21(D).

UPON PENETRATION INTO BUILDING, CONDUIT SHALL BE CONCRETE ENCASED UNTIL

TERMINATION IN MAIN ELECTRICAL ROOM AND SWITCHBOARD. CONCRETE

ENCASEMENT SHALL CONSIST OF 3" OF CONCRETE AROUND CONDUITS. SEE

CONDUIT ENTRANCE DETAIL ON DRAWING EK1.0.

TO NEW UTILITY

POLE

STEP-UP

TRANSFORMER

SPD

ELEV-2 ELEV-1

60AF

50AT

60AF

50AT

CH-38-0-01 CH-38-0-02

100AF

60AT

100AF

60AT

TO MDPTO MDP

UTILITY METER

DATA RACK

MULTI-MODE 62.5/125 OPTICAL

FIBER CABLE, AND

50 PAIR 24 AWG TYPE 89 CAT3

CABLE TO BUILDING 14

ECB

E

3#6 & 1#10G, 3/4"C

BRANCH CIRCUIT SCHEDULE

60A-2P/2W

120 VOLT & 277 VOLT 1PH, 2W. CIRCUITS

50A-1P

40A-2P/2W

30A-2P/2W

50A-2P/2W

60A-1P

20A-2P/2W

CIRCUIT BREAKER

30A-1P

40A-1P

208 VOLT & 480 VOLT 1PH, 2W. CIRCUITS

2#4 & 1#10G - 3/4"C.

2#6 & 1#10G - 3/4"C.

2#12 & 1#12G - 3/4"C.

2#10 & 1#10G - 3/4"C.

2#8 & 1#10G - 3/4"C.

2#6 & 1#10G - 3/4"C.

2#4 & 1#10G - 3/4"C.

CONDUCTORS

2#10 & 1#10G - 3/4"C.

2#8 & 1#10G - 3/4"C.

50A-3P/3W

60A-3P/3W

40A-3P/3W

30A…