Attachment 23 - A-903.pdf

PDF 2 MB Posted

Attached to
Y1DA--EHRM Infrastructure Upgrades Construction - Danville FHCS Project 550-21-700
Solicitation number
36C77625B0011
Issued by

About this file

The document is a roofing details drawing (A-903) for the EHRM Infrastructure Upgrades project at the VA Illiana Healthcare System in Danville, IL. The drawing provides technical specifications for deck type fasteners, pressure plates, and roof support systems, including mechanical unit supports, roof decking infill details, and pipe/conduit flashing details. The drawing is part of the bid documents for a fully sprinklered construction project, with consulting firms IMEG, Alesia, and Terracon involved, and VCI Project Management as the engineering and construction management team. The drawing is dated 8/1/2025 and includes multiple technical illustrations and photographs demonstrating roof support and installation techniques.

View the file

Other files

File Type Posted
Abstract of Bids OF 1419 - CONSTRUCTION - Signed 8.11.25.pdf PDF
36C77625B0011 0006.pdf PDF
Attachment 21 - Technical Questions - Danville IL 8-5-2025.pdf PDF
36C77625B0011 0005.docx DOCX document
Attachment 21 - Technical Questions - Danville IL 7-30-2025.pdf PDF
36C77625B0011 0004.pdf PDF
Attachment 21 - Technical Questions - Danville IL 7-28-2025.pdf PDF
Solicitation 36C77625B0011 Amendment 0003 - Danville IL EHRM Construction.pdf PDF
Attachment 3 Construction Wage Rates Vermilion 7.25.25.pdf PDF
Attachment 20 - Stamped Civil Drawings.pdf PDF
Attachment 17 - FloorHeightTable.xlsx XLSX spreadsheet
Attachment 16 - FloorHeightTable.pdf PDF
Attachment 15 - 013324 - Electronic Submittals.pdf PDF
Attachment 14 -101.AE301.pdf PDF
Attachment 12 - 58.AE301.pdf PDF
Amendment - 0002 36C77625B0011.pdf PDF
Attachment 22 - Electrical Single Line.pdf PDF
Attachment 13 - 58.AE401.pdf PDF
Attachment 11 - 02 82 11_Appendix_Asbestos Containing Materials Report Crosswalk.pdf PDF
Attachment 21 - Technical Questions - Danville IL 7-15-2025.docx DOCX document
Attachment 19 - Soil Report Danville IL - 7-15-25.pdf PDF
Attachment 18 - RFI Log_EHRM Upgrades Danville IL.xls XLS spreadsheet
Attachment 23 - Construction Wage Rates - Vermilion 7-11-25.pdf PDF
Amendment - 0001 36C77625B0011.pdf PDF
Attachment 6 Drawings Danville IL EHRM IU Construction Volume 1 of 3.pdf PDF
Attachment 5 Pre Construction Risk Assessment Danville IL EHRM IU.docx DOCX document
Attachment 9 Brand Name Justification Danville IL EHRM IU Construction.pdf PDF
Attachment 8 Drawings Danville IL EHRM IU Construction Volume 3 of 3.pdf PDF
Attachment 10 Limitations on Subcontracting Construction.pdf PDF
Attachment 7 Drawings Danville IL EHRM IU Construction Volume 2 of 3.pdf PDF
Attachment 1 Specifications Danville IL EHRM IU Construction Volume 1 of 2.pdf PDF
Attachment 4 Site Visit Instructions EHRM IU 550 21 700.docx DOCX document
Attachment 3 Construction Wage Rates Vermilion 4 18 25.pdf PDF
Attachment 2 Specifications Danville IL EHRM IU Construction Volume 2 of 2.pdf PDF
36C77625B0011_1.docx DOCX document
36C77625B0011.docx DOCX document
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

C

DECK TYPE

FASTENER & PRESSURE PLATE TYPES FOR

DIFFERENT ROOF DECKS

OPTION FASTENER PLATE

56 Louis Prima Dr., Suite B, Covington, LA 70433 504.684.4408

VCIProject Management Construction Management Engineering

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

STAMP:

321 4 5 6 7 8 9 10

DOUG ELIA

U.S. DEPARTMENT OF VETERANS AFFAIRS - ILLIANA HEALTHCARE SYSTEM

Cell: (217) 510-5945 Email: douglas.elia@va.gov

UNITED STATES

DEPARTMENT OF

VETERANS AFFAIRS

8/1/2025

Project Number:

Building Number:

Drawing Number:

Project Title:

Location:

Issue Date: Checked: Drawn:

Drawing Title:

Approved Project Director:

Phase:

FULLY SPRINKLERED

BID DOCUMENTSARCHITECT / ENGINEER OF RECORD:CONSULTANTS:

DATE:REVISIONS: ; Sean Fitzpatrick or John Vollman

BI

M

/2

1-

-2

1-

V A

D an vi lle

IL

E

HR

M In fr as tr uc tu re

U pg ra de s/ R2

0_

-1

2_ V

A

0-

-7

.r vt 5/

/2

:2

6:

P M

A-903

ROOFING DETAILS 550-21-700EHRM INFRASTRUCTURE UPGRADES

DANVILLE FHCS

Danville, IL

ALL

3" = 1'-0"B1 PREFABRICATED ROOF CURB FLASHING DETAIL

3" = 1'-0"B3 FIELD FABRICATED PIPE/CONDUIT FLASHING DETAIL

NTSD1 ROOF CADDY OR EQUAL CONDUIT SUPPORTS PER PLAN NOTES

NTSE1 ADHERED DIAGONAL BRACING PER MANUFACTURER

NTSD4 ROOF CADDY OR EQUAL MECH UNIT SUPPORTS PER PLAN NOTES

3" = 1'-0"B5 ROOF DECKING INFILL DETAIL

JV SF

AMENDMENT -1 8/1/2025

AutoCAD SHX Text NOTES: 1. APPROVED FASTENERS APPROVED FASTENERS 2. MECHANICAL SECUREMENT MAY BE MECHANICAL SECUREMENT MAY BE INSTALLED INTO THE VERTICAL SUBSTRATE. 3. WHEN USING 80 MIL THICK CURB WHEN USING 80 MIL THICK CURB FLASHING, THE INTERSECTIONS BETWEEN SPLICES MUST OVERLAID WITH A TPO "T-JOINT" COVER. 4. APPROXIMATELY 1/8" DIAMETER APPROXIMATELY 1/8" DIAMETER BEAD OF CUT-EDGE SEALANT IS REQUIRED ON CUT EDGES OF REINFORCED TPO MEMBRANE.

AutoCAD SHX Text

USE ONE CONTINUOUS SHEET OF REINFORCED TPO MEMBRANE TO WRAP AROUND CURB.

AutoCAD SHX Text

TPO REINFORCED MEMBRANE

AutoCAD SHX Text

FASTENER & SEAM FASTENING PLATE, MAX. 12" O.C.

AutoCAD SHX Text

AutoCAD SHX Text

CUT EDGE SEALANT

AutoCAD SHX Text HOT AIR WELD, 1-1/2" (4cm) MIN.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

T-JOINT COVER

AutoCAD SHX Text

AutoCAD SHX Text

TPO BONDING ADHESIVE

AutoCAD SHX Text

SEE INSET ON LEFT

AutoCAD SHX Text

COUNTER FLASHING WITH WATERPROOF JOINERY & ATTACHMENT (BY OTHERS)

AutoCAD SHX Text 3" (7.6cm) MIN.

AutoCAD SHX Text 12" (30.5cm) MIN.

AutoCAD SHX Text

EPDM GASKET

AutoCAD SHX Text

INJECT WATER CUT-OFF MASTIC THRU. PREDRILLED PILOT HOLE

AutoCAD SHX Text

MAY VARY

AutoCAD SHX Text NOTES: 1. REMOVE ALL EXISTING LEAD AND FLASHING MATERIAL REMOVE ALL EXISTING LEAD AND FLASHING MATERIAL BEFORE INSTALLING FIELD FABRICATED PIPE FLASHING. 2. TEMPERATURE OF THE PIPE PENETRATION MUST NOT TEMPERATURE OF THE PIPE PENETRATION MUST NOT EXCEED 160°F.3. TPO NON-REINFORCED FLASHING WRAPPED AROUND TPO NON-REINFORCED FLASHING WRAPPED AROUND PIPE SHALL HAVE MINIMUM 1-1/2" VERTICAL HOT AIR WELD. INSTALL A MINIMUM OF 4 SEAM FASTENING INSTALL A MINIMUM OF 4 SEAM FASTENING PLATES FOR PIPES WITH A DIAMETER UP TO 6" . ADDITIONAL SEAM FASTENING PLATES WILL BE REQUIRED FOR PIPES GREATER THAN 6" IN DIAMETER AND SHALL BE SPACED 12" ON CENTER MAXIMUM. 4. FASTENERS/PLATES ARE NOT REQUIRED ON ADHERED FASTENERS/PLATES ARE NOT REQUIRED ON ADHERED SYSTEMS UNLESS PIPE DIAMETER EXCEEDS 18" 5. APPROXIMATELY 1/8" DIAMETER BEAD OF CUT-EDGE APPROXIMATELY 1/8" DIAMETER BEAD OF CUT-EDGE SEALANT IS REQUIRED ON CUT EDGES OF REINFORCED TPO MEMBRANE.

AutoCAD SHX Text 1/2"

AutoCAD SHX Text 1.5

AutoCAD SHX Text A

AutoCAD SHX Text

MIN.

AutoCAD SHX Text cm

AutoCAD SHX Text

DIMENSIONS

AutoCAD SHX Text 1"

AutoCAD SHX Text 2.5

AutoCAD SHX Text 1-1/2"

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text

TO

AutoCAD SHX Text 2"

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text 12"

AutoCAD SHX Text

AutoCAD SHX Text D

AutoCAD SHX Text

APPROX.

AutoCAD SHX Text

MIN.

AutoCAD SHX Text

FASTENER & SEAM FASTENING PLATE, MAX. 12" O.C.

AutoCAD SHX Text

TPO NON- REINFORCED FLASHING

AutoCAD SHX Text

CUT-EDGE SEALANT

AutoCAD SHX Text

AutoCAD SHX Text D

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

XXXX

AutoCAD SHX Text

WATER CUT-OFF MASTIC

AutoCAD SHX Text

STAINLESS STEEL CLAMPING RING BY OTHERS

AutoCAD SHX Text

XXXX

AutoCAD SHX Text

HOT AIR-WELD, 1-1/2" MIN.

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text

COLD PIPE

AutoCAD SHX Text

REINFORCED TPO

AutoCAD SHX Text

STEEL OR WOOD

AutoCAD SHX Text

HP-X

AutoCAD SHX Text A

AutoCAD SHX Text

STRUCTURAL CONCRETE

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

HP-XTRA

AutoCAD SHX Text

CD-10

AutoCAD SHX Text

HD 14-10

AutoCAD SHX Text

PIRANHA

AutoCAD SHX Text

PIRANHA

AutoCAD SHX Text

PIRANHA

AutoCAD SHX Text

PIRANHA XTRA

AutoCAD SHX Text

HOT AIR-WELD, 1-1/2" MIN.

AutoCAD SHX Text

EXISTING ROOF MEMBRANE

AutoCAD SHX Text

EXISTING ROOF MEMBRANE

AutoCAD SHX Text

FASTENER & SEAM FASTENING PLATE, MAX. 12" O.C.

AutoCAD SHX Text

CUT-EDGE SEALANT

AutoCAD SHX Text

HOT AIR-WELD, 1-1/2" MIN.

AutoCAD SHX Text

REINFORCED TPO

AutoCAD SHX Text

EXISTING ROOF MEMBRANE, INSULATION AND ROOF DECKING

AutoCAD SHX Text

CUT-EDGE SEALANT

AutoCAD SHX Text

HOT AIR-WELD, 1-1/2" MIN.

AutoCAD SHX Text

REINFORCED TPO

AutoCAD SHX Text NEW ROOF DECK INFILL TO MATCH EXISTING. LAP 6" MIN. OVER EXISTING AND SCREW OR TACKWELD AT 8" O.C. MIN.

AutoCAD SHX Text

NEW RIGID INSULATION TO MATCH EXISTING

NEW ROOF MEMBRANE TO MATCH EXISTING