The document is an architectural drawing (58.AE401) depicting partial building sections for the VA Illiana Healthcare System's EHRM Infrastructure Upgrades project in Danville, IL. The detailed technical drawing shows renovation plans for Building 58, specifically focusing on treatment rooms (TR) across multiple floors, including floor levels from basement to attic. Key renovation elements include removing existing suspended acoustical ceilings, replacing finish flooring with static-dissipative vinyl composition tile (VCT), installing new fire-rated doors and frames, sealing wall joints and penetrations, and modifying existing walls and ceilings. The drawing includes specific room annotations for spaces like storage rooms, waiting areas, comfort rooms, and IT rooms, with detailed keynotes explaining precise construction and renovation specifications.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
THIRD FLOOR - B58
125' - 0"
FOURTH FLOOR - B58
137' - 0"
58.G 58.F58.D
SECOND FLOOR - B58
113' - 0"
FIRST FLOOR - B58
100' - 0"
58.AE401
F3
REMOVE EXIST FINISH FLOORING;
PREP FOR & REPLACE W/ NEW
STATIC-DISSIPATIVE VCT (TYP)
EXIST EXTERIOR MASONRY WALL
EXIST CONC STRUCT (TYP)
EXIST CONC BEAM (TYP)
NEW 45M-RATED DR/FRAME
EXIST CORRIDOR WALL - SEAL JOINTS -
PENETRATIONS FOR ENCLOSURE OF
ROOM TO B.O. STRUCTURE
(TYP)
NEW SUSP ACOUSTICAL CLG -
SEE REFL CLG PLAN
REMOVE EXIST SUSP ACOUSTICAL
CLG; REPLACE W/ NEW SUSP
ACOUSTICAL CLG - SEE REFL CLG PLAN
REMOVE EXIST SUSP ACOUSTICAL CLG
EXIST - SALVAGE GWB / MLT STUD WDW
POCKET / BULKHEAD - SEE REFL CLG PLAN
1ST FLR ARCH FFE = 100'-0" -
CIVIL FFE = 644.06' (1959 REV.)
EXIST CORRIDOR WALL - SEAL JOINTS -
PENETRATIONS FOR ENCLOSURE OF
ROOM TO B.O. STRUCTURE (TYP)
TR
STORAGE
208A
WAITING
308A
A9
A67
EXIST - SALVAGE GWB / MTL STUD
SOFFIT - SEE REFL CLG PLAN
A1
A1
A9
NEW GWB / MLT STUD WDW POCKET /
BULKHEAD - SEE F3/A-501 REFL CLG PLAN
A-501
A4 Sim A-501
F3 Sim
A-501
F3 Sim
THIRD FLOOR - B58
125' - 0"
FOURTH FLOOR - B58
137' - 0"
58.24
SECOND FLOOR - B58
113' - 0"
FIRST FLOOR - B58
100' - 0"
58.AE401
F1
58.AE401
F5
EXIST WALL - SEAL JOINTS &
PENETRATIONS FOR ENCLOSURE OF
ROOM TO B.O. STRUCTURE (TYP)
REMOVE EXIST FINISH FLOORING; PREP
FOR & REPLACE W/ NEW STATIC-
DISSIPATIVE VCT (TYP)
EXIST CONC STRUCT (TYP)
EXIST CONC BEAM (TYP)
EXIST WALL - SEAL JOINTS -
PENETRATIONS FOR ENCLOSURE OF
ROOM TO B.O. STRUCTURE (TYP)
NEW SUSP ACOUSTICAL CLG
- SEE REFL CLG PLAN
NEW GWB / MTL. STUD WALL
TO B.O. STRUCT
NEW GWB / MLT STUD WDW POCKET
/ BULKHEAD - SEE REFL CLG PLAN
NEW GWB / MTL. STUD WALL
TO B.O. STRUCT
1ST FLR ARCH FFE = 100'-0" -
CIVIL FFE = 644.06' (1959 REV.)
58.20.8
STORAGE
208A
TR
TR
WAITING
308A
HAC
TR
A9
A9
A67
A67 A67
A9
A9
A67 A67
A137
A137
D4
D4
D4
58.22.458.22 58.23
REMOVE EXIST SUSP ACOUSTICAL
CLG; REPLACE W/ NEW SUSP
ACOUSTICAL CLG - SEE REFL CLG PLAN
THIRD FLOOR - B58
125' - 0"
FOURTH FLOOR - B58
137' - 0"
FIFTH FLOOR - B58
149' - 6
ATTIC - B58
162' - 0"
58.G 58.F58.D
SECOND FLOOR - B58
113' - 0"
58.AE401
F3
REMOVE EXIST FINISH FLOORING;
PREP FOR & REPLACE W/ NEW
STATIC-DISSIPATIVE VCT (TYP)
EXIST EXTERIOR MASONRY WALL
EXIST CONC STRUCT (TYP)
EXIST CONC BEAM (TYP)
REMOVE EXIST DR/FRAME - REPL W/
NEW 45M-RATED DR/FRAME (TYP)
EXIST CORRIDOR WALL - SEAL JOINTS -
PENETRATIONS FOR ENCLOSURE OF
ROOM TO B.O. STRUCTURE (TYP)
REMOVE EXIST SUSP ACOUSTICAL CLG (TYP)
TR
TR
58.AE401
B1
COMFORT
ROOM
X-RAY
MODIFY EXIST SUSPENDED
ACOUSTICAL TILE CEILING FOR NEW
WALL - SEE REFLECTED CEILNG PLAN
A67
A9 A1
A67
A9 A1
D4
D4
A137
A137
FOURTH FLOOR - B58
137' - 0"
FIFTH FLOOR - B58
149' - 6
58.F 58.E
58.AE401
C1
REMOVE EXIST FINISH FLOORING;
PREP FOR & REPLACE W/ NEW STATIC-
DISSIPATIVE VCT (TYP)
EXIST WALL - SEAL JOINTS /
PENETRATIONS FOR ENCLOSURE
OF ROOM TO B.O. STRUCTURE (TYP)
EXIST CONC STRUCT (TYP)
EXIST CONC BEAM (TYP)
TR
D102 A9
A1
A
A118
A9
REMOVE PORTION OF EXIST SUSP.
ACOUSTICAL TILE CLG. INSIDE TR
ROOM - MODIFY REMAINING
CEILING IN WAITING ROOM TO
MEET NEW WALL
D102
A122
FOURTH FLOOR - B58
137' - 0"
FIFTH FLOOR - B58
149' - 6
58.AE401
C3
EXIST WALL - SEAL JOINTS /
PENETRATIONS FOR ENCLOSURE
OF ROOM TO B.O. STRUCTURE
(TYP)
EXIST CONC STRUCT (TYP)
EXIST CONC BEAM (TYP)
58.18
TR
RESTROOM
437A
A9
A9
D102 D102
A1
D1
A118
A122
D4
THIRD FLOOR - B58
125' - 0"
FOURTH FLOOR - B58
137' - 0"
FIFTH FLOOR - B58
149' - 6
ATTIC - B58
162' - 0"
SECOND FLOOR - B58
113' - 0"
FIRST FLOOR - B58
100' - 0"
BASEMENT - B58
87' - 0"
1ST FLR ARCH FFE = 100'-0" -
CIVIL FFE = 632.06' (1959 REV)
58.17
IT
IT
IT
IT
SOILED
LINEN
1. SEE SHEET AG001 FOR GENERAL NOTES.
2. EXISTING STRUCTURAL GRIDS, COLUMNS, BEAMS AND RELATED
ELEMENTS ARE TYPICALLY NOT SHOWN IN THE ARCHITECTURAL
DRAWINGS. GRIDS AND COLUMNS WHICH MAY BE SHOWN ARE
FOR COORDINATION AND ORIENTATION PURPOSES ONLY AND
NOT FOR ACTUAL LOCATION OR SIZE OF COMPONENTS. THE
CONTRACTOR IS TO FIELD VERIFY LOCATIONS OF COLUMNS
AND STRUCTURAL MEMBERS AND OBTAIN DRAWINGS PROVIDED
BY THE VA FOR ESTABLISHMENT OF EXISTING STRUCTURAL
CONDITIONS IF NEEDED.
3. REFER TO SHEETS PREPARED BY OTHER DISCIPLINES FOR
STRUCTURAL, MECHANICAL, ELECTRICAL AND
TELECOMMUNICATIONS WORK.
ARCHITECTURAL RENOVATION GENERAL NOTES:
FIFTH FLOOR - B58
149' - 6
ATTIC - B58
162' - 0"
58.2758.2458.AE401
F5
58.20.8 58.AE401
B4
COMFORT
ROOM
TR
CONSULT.
ROOM
507A
WAITING
ROOM
507B
MODIFY EXIST
CEILING &
SOFFITS FOR
NEW WALL
MODIFY EXIST
CEILING FOR
NEW WALL
EXIST WALL
EXIST CONC PAN JOIST
GWB CLOSURE - EXIST WALL / B.O. CONC PAN JOIST -
ATTACH TO EXIST LT.GA. MTL. FRAMING
AA
A106
A9 A9
A102
A67
58.22.458.22 58.23
FIFTH FLOOR - B58
149' - 6
ATTIC - B58
162' - 0"
58.G 58.F58.D58.AE401
B1
TR
CORRIDOR
C5-3
CLOSE EXIST WALL UP TO
B.O. STRUCTURE
VINYL BASE AS
SCHEDULED
REFINISH EXIST WALL - SEE
ROOM FINISH SCHEDULE
EXIST EXTERIOR WALL
A67
A9
A1
A102 A118
EXIST CORRIDOR WALL
A
R C H I T E C
T
S T
A T
E
O F N E B
R A
S K
A
05/28/2024
RICHARD
JOSEPH
ONKEN
A-5125
56 Louis Prima Dr., Suite B, Covington, LA 70433 504.684.4408
VCI
Project Management
Construction Management
Engineering
VA FORM 08 - 6231
A
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
STAMP:
321 4 5 6 7 8 9 10
DOUG ELIA
U.S. DEPARTMENT OF VETERANS AFFAIRS - ILLIANA HEALTHCARE SYSTEM
Cell: (217) 510-5945 Email: douglas.elia@va.gov
UNITED STATES
DEPARTMENT OF
VETERANS AFFAIRS
05/28/2024
Project Number:
Building Number:
Drawing Number:
Project Title:
Location:
Issue Date: Checked: Drawn:
Drawing Title:
Approved Project Director:
Phase:
FULLY SPRINKLERED
BID DOCUMENTS
ARCHITECT / ENGINEER OF RECORD:CONSULTANTS:
DATE:REVISIONS:
; Sean Fitzpatrick or John Vollman
B
IM
1-
1-
V A
D a n v il le
I L
E
H R
M In fr a s tr u ct u re
U p g ra d e s
R
1-
V A
1-
.r v t
:1
:5
P
M
58.AE401
PARTIAL BUILDING SECTIONS
AHT STW/AHT
550-21-700EHRM INFRASTRUCTURE UPGRADES
DANVILLE FHCS
Danville, IL
1/4" = 1'-0" F1
B58 PART SECN TR ROOMS 107-208A-308A DR-WDW
1/4" = 1'-0"
F3
B58 PART SECN TR ROOMS 107-208-208A-308-308A
1/4" = 1'-0" F5
B58 PART SECN TR ROOMS 208-308 DR-WDW
1/4" = 1'-0" C3
B58 PART SECN TR ROOM 438 DR-WALL
1/4" = 1'-0"
C1
B58 PART SECN TR ROOM 438-437A
1/4" = 1'-0" F8
B58 BLDG PART SECN EXIST TIP ROOMS
1/4" = 1'-0" B1
B58 PART SECN ROOMS 506-507-507A-507B
KEYNOTE LEGEND - FLOOR PLAN RENOVATION
KEY VALUE KEYNOTE TEXT
A1 NEW 45-MINUTE-RATED WOOD DOOR W/ HM FRAME;
SEE DOOR SCHEDULE.
A9 NEW 3/4" FIRE-RETARDANT PLYWOOD BACKBOARD
FULL LENGTH OF WALL (UNLESS NOTED OR SHOWN
OTHERWISE) X 8'H MINIMUM; MOUNT PLYWOOD 12"
ABOVE FINISH FLOOR. PAINT PANELS PER ROOM
FINISH SCHEDULE GENERAL NOTE 2.
A67 APPLY BLAST FILM WITH ADDITIONAL LAYER OF
VISION-OBSCRUING FILM; SEE WINDOW SECURITY
DETAIL B1/A-901.
A102 EXISTING CHASE; EXTEND CLOSURE TO B.O.
STRUCTURE W/ GWB/MTL STUDS; SEE SHEET A-802
FOR CLOSURE DETAILS.
A106 LINE OF EXISTING CONC PAN JOIST ABOVE CEILING;
CLOSE OFF GAP BETWEEN WALL AND PAN JOIST WITH
5/8” GWB; COVER MTL STUD 'BRIDGES' THAT HOLD
WALL IN PLACE FROM F.O. WALL TO BOTTOM OF
ADJACENT PAN JOIST OVER WAITING RM. 507B FOR
FULL CLOSURE OF WALL.
A118 CLOSE TOP OF CHASE TO B.O. STRUCT W/ GWB/MTL
STUDS OVER F.O. EXISITNG CHASE WALL; INSTALL 5/8"
TYPE 'X' GWB OVER EXISITNG LT GA MTL. FRAMING IF
PRESENT, OR INSTALL LT GA FRAMING INSIDE CHASE
W/ 5/8" TYPE 'X' GWB TO CLOSE BETWEEN T.O.
PLASTER AND B.O. STRUCTURE. SEE SHEET A-802 FOR
CLOSURE DETAILS.
A122 EXISITNG 'WET' WALL; WATERPROOF SECTION W/
PEEL-N-STICK BEHIND PLYWOOD UP FROM FLOOR;
EXTEND GWB @ EXISITNG WALL UP TO B.O.
STRUCTURE.
A137 INSTALL STATIC-DISSIPATIVE TILE (SDT) FLOORING AS
SCHEDULED.
1/4" = 1'-0" B4
B58 PART SECN TR RM 507
KEYNOTE LEGEND - FLOOR PLAN DEMOLITION
KEY VALUE KEYNOTE TEXT
D1 REMOVE EXISITNG DOOR/FRAME/HW; PREP FOR NEW
DOOR/FRAME OR INFILL TO MATCH EXISITNG WALL
CONST; SEE RENOVATION PLANS & DOOR SCHEDULE.
D4 REMOVE EXISTING SUSPENDED ACOUSTICAL CEILING
ASSEMBLY IN ITS ENTIRETY; LEAVE CEILING OPEN TO
STRUCTURE IN ALL TR ROOMS (TYPICAL UNLESS
NOTED OTHERWISE).
D102 REMOVE COUNTERTOP/BRACKETS; RETURN TO VA.