Attachment 12 - 58.AE301.pdf

PDF 1 MB Posted

Attached to
Y1DA--EHRM Infrastructure Upgrades Construction - Danville FHCS Project 550-21-700
Solicitation number
36C77625B0011
Issued by

About this file

This document is a large-scale architectural floor plan for the EHRM Infrastructure Upgrades project at the VA Illiana Healthcare System in Danville, IL, specifically focusing on Building 58. The detailed architectural drawing provides comprehensive floor plans for multiple levels (first through fifth floors), showing proposed renovations for various rooms including telecom (TR) rooms, storage areas, waiting rooms, and corridors. Key renovation elements include installing new fire-rated walls, static-dissipative tile flooring, plywood backboards, access control devices, security film, and penetration sleeves, with specific attention to room-by-room modifications and infrastructure improvements across different floor levels.

The floor plans include extensive technical annotations and keynotes detailing construction specifications, such as wall types, door installations, ceiling treatments, and specific renovation requirements for each room. The document is part of the broader VA infrastructure upgrade project, stamped with architectural and engineering details, including the architect's professional license information and project metadata. The drawings are prepared by VCI Project Management and are dated 05/28/2024, indicating they are part of the bid documentation phase for the infrastructure upgrade project targeting various buildings within the VA Illiana Healthcare System campus.

View the file

Other files

File Type Posted
Abstract of Bids OF 1419 - CONSTRUCTION - Signed 8.11.25.pdf PDF
36C77625B0011 0006.pdf PDF
Attachment 21 - Technical Questions - Danville IL 8-5-2025.pdf PDF
36C77625B0011 0005.docx DOCX document
Attachment 21 - Technical Questions - Danville IL 7-30-2025.pdf PDF
36C77625B0011 0004.pdf PDF
Attachment 23 - A-903.pdf PDF
Attachment 3 Construction Wage Rates Vermilion 7.25.25.pdf PDF
Attachment 21 - Technical Questions - Danville IL 7-28-2025.pdf PDF
Solicitation 36C77625B0011 Amendment 0003 - Danville IL EHRM Construction.pdf PDF
Attachment 22 - Electrical Single Line.pdf PDF
Attachment 13 - 58.AE401.pdf PDF
Attachment 11 - 02 82 11_Appendix_Asbestos Containing Materials Report Crosswalk.pdf PDF
Attachment 20 - Stamped Civil Drawings.pdf PDF
Attachment 17 - FloorHeightTable.xlsx XLSX spreadsheet
Attachment 16 - FloorHeightTable.pdf PDF
Attachment 15 - 013324 - Electronic Submittals.pdf PDF
Attachment 14 -101.AE301.pdf PDF
Amendment - 0002 36C77625B0011.pdf PDF
Attachment 21 - Technical Questions - Danville IL 7-15-2025.docx DOCX document
Attachment 19 - Soil Report Danville IL - 7-15-25.pdf PDF
Attachment 18 - RFI Log_EHRM Upgrades Danville IL.xls XLS spreadsheet
Attachment 23 - Construction Wage Rates - Vermilion 7-11-25.pdf PDF
Amendment - 0001 36C77625B0011.pdf PDF
Attachment 9 Brand Name Justification Danville IL EHRM IU Construction.pdf PDF
Attachment 8 Drawings Danville IL EHRM IU Construction Volume 3 of 3.pdf PDF
Attachment 6 Drawings Danville IL EHRM IU Construction Volume 1 of 3.pdf PDF
Attachment 5 Pre Construction Risk Assessment Danville IL EHRM IU.docx DOCX document
Attachment 10 Limitations on Subcontracting Construction.pdf PDF
Attachment 7 Drawings Danville IL EHRM IU Construction Volume 2 of 3.pdf PDF
Attachment 1 Specifications Danville IL EHRM IU Construction Volume 1 of 2.pdf PDF
Attachment 4 Site Visit Instructions EHRM IU 550 21 700.docx DOCX document
Attachment 3 Construction Wage Rates Vermilion 4 18 25.pdf PDF
Attachment 2 Specifications Danville IL EHRM IU Construction Volume 2 of 2.pdf PDF
36C77625B0011_1.docx DOCX document
36C77625B0011.docx DOCX document
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

58.14

58.K

58.17

A25

IN-04.01

FE

CLOSET

100B

CR

58.2558.24

58.G

58.F

58.G'

58.D

58.AE401

F1

58.AE401

F3

TR

A9 A9

A6

A7

A10

A1

A9

A4

A21

A62

EXISTING

9' - 1" F.V.

E X

IS

T

IN

G

/2

F .V

IN-03.01 IN-04.01

A26

HAC

OFFICE

A9

58.22.458.22 58.23

EXIST. PLASTER-LATH

WALL OVER LT.GA.

FRAMING BTW ROOMS

107-108. CLOSE OFF

WALL TO B.O.

STRUCTURE W/

PLASTER-MTL LATH

OVER EXIST. FRAMING.

EXIST STRUCT. CLAY

TILE/PLASTER WALL -

CLOSE OFF WALL TO B.O.

STRUCTURE; INFILL BTW.

T.O. EXIST. WALL & B.O.

STRUCT. W/ STRUCT.

CLAY TILE W/ PLASTER

OVER STRUCT. CLAY TILE

A3

A97

A144 A144

A9

58.G

58.J'

58.J

58.I

58.H

58.G'

58.AE401

F8

58.1858.17

A25

IT

CR

58.G

58.F

58.D

58.AE401

F1

58.AE401

F5

58.AE401

F3

58.20.858.20

TR

STORAGE

208A

A9

A9 A8

A58

A9

A1

A10

A4

A59

A3

A21

A62

A61

E X

IS

T

IN

G

/8

F .V

IN-03.01 IN-04.01

A

10' - 8" F.V.

A99 FE

208 208A

A100

A100

A101

E X

IS

T

IN

G

1"

F .V

EXISTING

16' - 6 3/4" F.V.

A118

A118

A58

58.22.458.22 58.23

A1

A97

A144

A26 A26

58.J'

58.J

58.I

58.H

58.G'

58.AE401

F8

58.1858.17

IT

A25

CR

58.24

58.G

58.F

58.D

58.AE401

F1

58.AE401

F5

58.AE401

F3

58.20.8

TR

WAITING

308A

A9 A9

A9

A10

A21

A8

A4

A1

A62

E X

IS

T

IN

G

'-9

/2

F

.V

11" F.V. 10'-7" F.V.

11' - 1"

E X

IS

T

IN

G

/4

F .V

A

IN-03.01

IN-04.01

A26 A26

CORRIDOR

C3-5

F1

A98

A F1

A100

A102 7' - 1 3/8" F.V.

58.22.458.22 58.23

A97

A144

58.J'

58.J

58.I

58.H

58.G'

58.AE401

F8

58.1858.17

A25

IT

CR

58.E

58.AE401

C3

58.AE401

C1

58.18 58.1958.17

TR

PT

WAITING

ROOM

RESTROOM

437A

A1 A3

A10

A29

A29

A9

A9

A9

A8

A21

A22

A28

A28

A4

A7

A60

A61

'-7

F

.V

IN-03.01

CORRIDOR

C4-6

A

A102

EXISTING

12' - 5 3/4" F.V.

A119

A97

58.J'

58.J

58.I

58.H

58.G'

58.AE401

F8

58.1858.17

A25

IT

LARGE-SCALE PLANS & DETAILS GENERAL NOTES:

1. REFER TO DEMOLITION AND RENOVATION PLANS FOR

REQUIREMENTS RELATED TO INSTALLATION OF NEW

INTERIOR WALLS, CEILING AND ROOF MODIFICATIONS.

2. REFER TO COLOR SCHEDULE AND ROOM FINISH

SCHEDULES FOR INTERIOR AND EXTERIOR FINISH

COLORS.

A. TYPICAL FINISHES:

a. BASE-WALLS - 4"-H RESILIENT BASE W/

COVE (UNLESS NOTED OTHERWISE)

b. WALLS (GWB) - PAINT TO 6" ABOVE

FINISH CLG

c. WALLS (GWB/PLASTER) (TR ROOMS) -

PAINT FULL-HT TO B.O. STRUCTURE IN

ROOMS W/O CEILINGS

d. WALLS (CMU) - PAINT TO 6" ABOVE

FINISH CLG

e. WALLS (CMU) (TR ROOMS) - PAINT

FULL-HT TO B.O. STRUCTURE IN

ROOMS W/O CELINGS

f. FLOORS (EXCEPT TR ROOMS / DATA

CENTER) - VCT OR LVT (PER VA

GUIDELINES - SEE ROOM FINISH

SCHEDULE)

g. FLOORS (TR ROOM & DATA CENTER) -

STATIC-DISSIPATIVE VCT

h. CEILINGS (GWB) - PAINT CLG. WHITE

i. CEILINGS (SUSPENDED ACOUSTICAL

TILE) - MATCH CEILING TILES/GRID

PREVIOUSLY USED IN ROOM (UNLESS

NOTED OTHERWISE)

j. OVERHEAD STRUCTURE (TR ROOMS /

DATA CENTER) - PAINT CLG. WHITE

1. REFER TO SHEET GI004 FOR TEMPORARY

ENCLOSURE, PROTECTION OF EXISTING UTILITIES

AND PROTECTION OF THE BUILDING INTERIOR

DURING DEMOLITION AND CONSTRUCTION.

2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR

FIELD VERIFICATION OF EXISTING CONDITIONS AND

CHANGES MADE TO THE BUILDING AND SITE SINCE

THE PUBLISHED DATE OF THE CONSTRUCTION

DOCUMENTS.

3. BELOW-GRADE CONDITIONS SHOWN ARE BASED

UPON AS-BUILT DRAWINGS PROVIDED BY THE VA.

VARIATION OF EXISTING CONDITIONS WHICH DIFFER

FROM THOSE SHOWN ON THE DRAWINGS SHALL BE

REPORTED TO THE COR UPON DISCOVERY.

4. THE CONTRACTOR SHALL RETAIN THE SERVICES OF

AN UNDERGROUND UTILITY LOCATE SERVICE PRIOR

TO START OF WORK ON SITE THAT INCLUDES

EXCAVATION, DEMOLITION OF EXISTING PAVEMENT

OR OTHER WORK THAT MAY DISTURB BELOW-GRADE

UTILITIES AND IMPROVEMENTS.

5. CONTRACTOR SHALL PROTECT ALL SITE

INFRASTRUCTURE UNLESS DIRECTED OTHERWISE BY

COR.

30 MIN. SMOKE BARRIER

1 HR SMOKE BARRIER

1 HR FIRE RATED

2 HR FIRE RATED

FIRE RATED WALL LEGEND

1. REFER TO AG001 FOR ARCHITECTURAL DEMOLITION AND

RENOVATION GENERAL NOTES.

2. EXISTING STRUCTURAL GRIDS, COLUMNS, BEAMS AND

RELATED ELEMENTS ARE TYPICALLY NOT SHOWN IN THE

ARCHITECTURAL DRAWINGS. GRIDS AND COLUMNS

WHICH MAY BE SHOWN ARE FOR COORDINATION AND

ORIENTATION PURPOSES ONLY AND NOT FOR ACTUAL

LOCATIONS OR SIZE OF COMPONENTS. THE

CONTRACTOR IS TO FIELD VERIFY LOCATIONS OF

COLUMNS AND STRUCTURAL MEMBERS / ELEMENTS. THE

CONTRACTOR SHALL HAVE ACCESS TO DRAWINGS HELD

BY THE VA FOR ESTABLISHMENT OF EXISTING

STRUCTURAL COMPONENTS IF NEEDED.

3. THE AREAS OF WORK SHOWN ARE ASSOCIATED WITH AN

OPERATING FACILITY THAT HAS CERTAIN AREAS THAT

MUST REMAIN IN SERVICE 24-HOURS A DAY, 7-DAYS A

WEEK.

4. SCHEDULE WORK TO MINIMIZE DISRUPTION OF

SERVICES. COORDINATE WORK SCHEDULE WITH THE

CONTRACTING OFFICER'S REPRESENTATIVE (COR).

5. COORDINATE WORK WITH ALL OTHER TRADES. VERIFY

ALL EXISTING CONDITIONS PRIOR TO BEGINNING WORK

TO CONFIRM ACCURACY IN THE DRAWINGS. REPORT ANY

DISCREPANCIES TO THE VA COR.

6. DO NOT SCALE THE DRAWINGS. FIELD VERIFY ALL

DIMENSIONS AND EXISTING STRUCTURAL CONDITIONS.

7. PROVIDE SMOOTH, LEVEL TRANSITIONS FROM NEW

FINISH TO EXISTING FINISH TO REMAIN.

8. FINAL FINISH SELECTION TO BE MADE BY THE VA.

PROVIDE ALL MATERIAL TO VA FOR REVIEW AND

APPROVAL THOUGH COLOR BOARD SUBMITTAL FOR

BOTH MATERIAL, TYPE AND COLOR.

9. GENERAL CONTRACTOR TO PROVIDE AND INSTALL ALL

NEW FINISHES TO COMPLETE THE WORK AS NECESSARY.

10. REMOVE AND REPLACE ELECTRICAL / DATA PLATES,

BOXES, LIGHTS AND ACCESSORIES AS NECESSARY.

ADJUST ELECTRICAL / DATA COMPONENTS AS

NECESSARY.

11. PROTECT ADJACENT SURFACES - FOR EXAMPLE, BUT

NOT LIMITED TO - SILLS, DOOR JAMBS AND HEAD

FINISHES AT WINDOWS AND DOORS TO NAME A FEW.

12. THE GENERAL CONTRACTOR SHALL PROVIDE DUST

PARTITIONS AS NECESSARY TO CLOSE OFF AREA OF

WORK FROM ACTIVE AREAS OF THE BUILDING.

13. ALL WALLS ARE DIMENSIONED TO FINISH FACE, UNLESS

NOTED OTHERWISE.

14. REFER TO MECHANICAL DRAWINGS FOR NEW

MECHANICAL UNITS AND WORK IN ROOMS.

15. REFER TO ELECTRICAL DRAWINGS FOR LIGHTING

LOCATIONS AND WORK IN ROOMS.

16. REFER TO TECHNOLOGY / TELECOM DRAWINGS FOR

TELECOM AND SERVER RACKS, CABLE TRAYS, CABLE

JACK LOCATIONS AND ITEMS RELATED TO TELECOM

WORK.

17. REFER TO HAZARDOUS MATERIALS NOTES ON SHEET

GI004 AND TO ENVIRONMENTAL DRAWINGS FOR

ABATEMENT PROCEDURES OF HAZARDOUS MATERIALS.

18. EXISTING AND NEW CABLE TRAYS NOT SHOWN FOR

CLARITY OF ARCHITECTURAL SCOPE OF WORK. REFER

TO TECHNOLOGY / TELECOM DRAWINGS FOR

INFORMATION RELATED TO THESE ITEMS.

19. REFERENCE TECHNOLOGY / TELECOM DRAWINGS FOR

AREAS WHERE NEW DATA JACK WALL OUTLETS WILL BE

PROVIDED IN ROOMS OUTSIDE OF THE TELECOM ROOMS.

PATCH AND PAINT AROUND DATA JACK WALL OUTLET AS

NEEDED. COORDINATE PAINT COLOR WITH EXISTING

WALL COLOR AND VA COR.

20. FIRE- AND SMOKE-SEAL ALL THROUGH-WALL

PENETRATIONS TO COMPLY WITH FIRE-SMOKE RATING

APPLICABLE TO WALL. PROVIDE A MINIMUM OF 1-HOUR

FIRE-SMOKE RATING WHERE WALL RATING IS NOT

SHOWN.

ARCHITECTURAL FLOOR PLAN GENERAL NOTES:

GAS

STORAGE

100C

LOADING

DOCK

100A

CHUTE

STAIRS

S1

CORRIDOR

C2-2

CORRIDOR

C2-1

SOIL

CORR.

C2-4

SUPERV.

OFFICE

SOIL HOLD

CHUTE

STAIRS

S-1

CORRIDOR

C4-2

CORRIDOR

C4-1

58.2758.2658.2558.24

58.G

58.F

58.D

58.AE401

F5

CR

A27 A10

A26

A9 A9

A9

CONSULT.

ROOM

507ATR

WAITING

ROOM

507B

A21

A7

A1

507 507A

A3

A28

F.V.

9'-11"6'-6" F.V.11'-3"F.V.

58.AE401

B1

COMFORT

ROOM

506 E X

IS

T

IN

G

'-8

/2

F

.V .A

A

CAFEC1

A99

58.AE401

B4

10' - 7" F.V.

A106

IN-04.01IN-04.01IN-04.01IN-04.01

A87

58.22.458.22 58.23

A144 A144 A144

A97

A1

CORR.

C3-2

CHUTE

CORR.

C3-1

STAIRS

S1

SEE SHEET AG001 FOR ARCHITECTURAL

RENOVATION GENERAL NOTES

STAIRS

S1.

CORRIDOR

C5-2

CHUTE

ROOM

CORRIDOR

C5-1

A

R C H I T E C

T

S T

A T

E

O F N E B

R A

S K

A

05/28/2024

RICHARD

JOSEPH

ONKEN

A-5125

56 Louis Prima Dr., Suite B, Covington, LA 70433 504.684.4408

VCI

Project Management

Construction Management

Engineering

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

STAMP:

321 4 5 6 7 8 9 10

DOUG ELIA

U.S. DEPARTMENT OF VETERANS AFFAIRS - ILLIANA HEALTHCARE SYSTEM

Cell: (217) 510-5945 Email: douglas.elia@va.gov

UNITED STATES

DEPARTMENT OF

VETERANS AFFAIRS

05/28/2024

Project Number:

Building Number:

Drawing Number:

Project Title:

Location:

Issue Date: Checked: Drawn:

Drawing Title:

Approved Project Director:

Phase:

FULLY SPRINKLERED

BID DOCUMENTSARCHITECT / ENGINEER OF RECORD:CONSULTANTS:

DATE:REVISIONS: ; Sean Fitzpatrick or John Vollman

B

IM

1-

1-

V A

D a n v il le

I L

E

H R

M In fr a s tr u ct u re

U p g ra d e s

R

1-

V A

1-

.r v t

:1

:3

P

M

58.AE301

LARGE SCALE PLANS

AHT STW/TJF

550-21-700EHRM INFRASTRUCTURE UPGRADES

DANVILLE FHCS

Danville, IL

1/4" = 1'-0" B1

B58 - FIRST FLOOR - RM 100B - TIP ROOM

1/4" = 1'-0"

B3

B58 - FIRST FLOOR - RMS 106-107-107A-108 - TR ROOM (2-RACKS)

1/4" = 1'-0" B5

B58 - SECOND FLOOR - RM 200-201 - STORAGE

1/4" = 1'-0" D1

B58 - SECOND FLOOR - RMS 208-208A - NEW TR ROOM (3-RACKS)

1/4" = 1'-0"

D3

B58 - THIRD FLOOR - RM 300-301 - STORAGE

1/4" = 1'-0" D5

B58 - THIRD FLOOR - RM 308 - NEW TR WAITING RM

1/4" = 1'-0" D7

B58 - FOURTH FLOOR - RM 400-401 - EXIST TIP ROOM

1/4" = 1'-0" F1

B58 - FOURTH FLOOR - RM 438 - NEW TR ROOM (3-RACKS)

1/4" = 1'-0"

F3

B58 - FIFTH FLOOR - RM 500-501

1/4" = 1'-0" F5

B58 - FIFTH FLOOR - RMS 506 -507-507A - NEW TR / RENOVATE COMFORT-

CONSULT-WAITING RMS

KEYNOTE LEGEND - FLOOR PLAN RENOVATION

KEY VALUE KEYNOTE TEXT

A1 NEW 45-MINUTE-RATED WOOD DOOR W/ HM FRAME;

SEE DOOR SCHEDULE.

A3 INFILL OPENING TO MATCH EXISTING WALL

CONSTRUCTION.

A4 CEILING OPEN TO STRUCTURE - TYPICAL ALL TR

ROOMS FOR ACCESS (UNLESS NOTED OTHERWISE).

A6 EXISTING 6" CMU WALL; EXTEND TO BOTTOM OF

EXISTING STRUCTURE FOR WALL CLOSURE.

A7 EXTEND EXISTING WALL UP TO B.O. STRUCTURE.

A8 NEW GWB/METAL STUD WALL; EXTEND FULL-HEIGHT

FROM FLOOR TO B.O. STRUCTURE.

A9 NEW 3/4" FIRE-RETARDANT PLYWOOD BACKBOARD

FULL LENGTH OF WALL (UNLESS NOTED OR SHOWN

OTHERWISE) X 8'H MINIMUM; MOUNT PLYWOOD 12"

ABOVE FINISH FLOOR. PAINT PANELS PER ROOM

FINISH SCHEDULE GENERAL NOTE 2.

A10 ACCESS CONTROL DEVICE; SEE TECH DWGS.

A21 NEW STATIC-DISSIPATIVE TILE (SDT) FLOORING AS

SCHEDULED; SEE ROOM FINISH SCHEDULE.

A22 NEW FLOOR DRAIN; SEE MEP DWGS.

A25 SEE TELECOM-SERIES DWGS FOR WORK THIS ROOM.

A26 APPLY NEW SECURITY/BLAST & VISION-OBSCURING

FILM AND INSTALL SECURITY SCREEN; SEE DETAIL

B1/A-901.

A27 NEW DOOR/FRAME – SEE DOOR SCHEDULE.

A28 NEW WALL - EXTEND TO TO B.O. STRUCTURE / DECK

ABOVE; SEE WALL TYPES.

A29 EXISTING CHASE TO REMAIN.

A58 EXISTING RADIATOR / CONVECTOR; SEE MECH.

A59 PROVIDE & INSTALL FIRE-RATED THROUGH-FLOOR

PENETRATION SLEEVES; SEE DETAILS SHEET A-802

A60 WATERPROOF EXISTING 'WET' WALL W/ BITUMINOUS

"PEEL AND STICK" SELF-ADHESIVE MEMBRANE.

A61 EXISTING ACT CEILING TO REMAIN; REPAIR AS

NEEDED.

A62 REPAIR/REPLACE/ADD CORRIDOR GUARDRAIL AT

WALL INFILL AS NEEDED; MATCH EXISTING.

A87 NEW FIRE EXTINGUISHER CABINET (FEC); REFER TO

SPECIFICATIONS FOR TYPE LABELED & DETAILS ON

SHT A-902.

A97 EXISTING FLOOR; PREP FOR NEW (SDT)

STATIC-DISSIPATIVE TILE FLOORING; SEE ROOM

FINISH SCHEDULE.

A98 INSTALL BITUMINOUS 'PEEL & STICK' WATER

PROOFING ON WALL & LAP TO FLOOR; COVER WITH

PLYWOOD & SDT.

A99 CLEAN AGENT FIRE EXTINGUISHER (PROVIDED BY VA)

A100 COLUMN WITH CHASE; EXTEND CLOSURE TO B.O.

DECK W/ GWB/MTL STUDS.

A101 PLUMBNG CHASE; SEE MECH & PLBG DWGS FOR

WORK RELATED TO PIPING RELOCATION IN TR

ROOMS.

A102 EXISTING CHASE; EXTEND CLOSURE TO B.O.

STRUCTURE W/ GWB/MTL STUDS; SEE SHEET A-802

FOR CLOSURE DETAILS.

A106 LINE OF EXISTING CONC PAN JOIST ABOVE CEILING;

CLOSE OFF GAP BETWEEN WALL AND PAN JOIST WITH

5/8” GWB; COVER MTL STUD 'BRIDGES' THAT HOLD

WALL IN PLACE FROM F.O. WALL TO BOTTOM OF

ADJACENT PAN JOIST OVER WAITING RM. 507B FOR

FULL CLOSURE OF WALL.

A118 CLOSE TOP OF CHASE TO B.O. STRUCT W/ GWB/MTL

STUDS OVER F.O. EXISITNG CHASE WALL; INSTALL 5/8"

TYPE 'X' GWB OVER EXISITNG LT GA MTL. FRAMING IF

PRESENT, OR INSTALL LT GA FRAMING INSIDE CHASE

W/ 5/8" TYPE 'X' GWB TO CLOSE BETWEEN T.O.

PLASTER AND B.O. STRUCTURE. SEE SHEET A-802 FOR

CLOSURE DETAILS.

A119 REINSTALL EXISITNG STAINLESS STEEL COLUMN

PROTECTION.

A144 EXISTING FLOOR; PREP FOR NON-SDT FLOORING AS

SCHEDULED; SEE ROOM FINISH SCHEDULE.

EXIST ROOM 107 ABOVE CEILING

EXIST ROOM 107 ABOVE CEILING @ CORR WALL

EXIST AREA ABOVE CEILING

0' 2' 4' 8' 16'

1/4" = 1'-0"

PLAN

NORTH

TRUE

NORTH