S06 - Amend 0009 - Att 19 - DWG MV600 - Rvd - SPS - Sioux Falls.pdf
PDF 324 KB Posted
- Solicitation number
- 36C77624R0115
About this file
This document is a detailed Ventilation Schedules drawing (MV600) for a VA project to construct a new Sterile Processing Services (SPS) facility at the Royal C. Johnson Veterans Memorial Hospital in Sioux Falls, South Dakota. The drawing provides comprehensive technical specifications for multiple air handling units (AHU-1 and AHU-2), exhaust fans, terminal air boxes, air valves, and associated HVAC equipment.
Key technical details include two primary air handling units: AHU-1 for the Sterile Processing Area with 12,000 CFM capacity and 100% outside air, and AHU-2 for administrative areas with 5,000 CFM capacity and mixed air VAV configuration. The systems include features like fully redundant supply fans, heating and cooling coils, humidifiers, UV light treatment, and multiple stage filtration (MERV 8, 13, and 14 filters). The ventilation design supports critical spaces like scope processing, decontamination areas, clean workrooms, and various support spaces, with precise airflow control and temperature management for each zone.
View the file
Other files
Show 40 more
Latest 50 of 61 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
I O W A
S E
D
PROFESS IONA
27052
L
IC
E N
L E
N G
I N E
E R
DELLAN J.
LLEWELLYN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
B
IM
/1
.0
V A
-W a s h
D C
-V A
S io u x F a lls
N e w
S P
S /M
E P
T
.0
V A
W a s h D
C -V
A S io u x F a lls
N e w S
P S
C
.r v t
/9
/2
:2
:5
P M
MV600
VENTILATION SCHEDULES CONSTRUCT NEW SPS
Sioux Falls, SD.
438-460
02/14/2025 DAVING DELLLE16584
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE
THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG CORP. © 2025 IMEG CORP.
2882 106TH STREET
DES MOINES, IA 50322
515.334.9906 FAX: 515.334.9908
www.imegcorp.com
19004249.04
NOTES:
1.REFERENCE SPECIFICATION SECTION 23 73 00 INDOOR CENTRAL-STATION AIR-HANDLING UNITS.
2.PROVIDE SHAFT GROUNDING AS REQUIRED IN THE MOTOR SPECIFICATION 23 05 12.
3.ONE FULLY REDUNDANT (N+1) SUPPLY FAN SHALL BE PROVIDED FOR EACH FAN ARRAY. SCHEDULED RPM AND BHP REPRESENT N PERFORMANCE.
4.PROVIDE 1 VFD PER SUPPLY FAN.
5.CHILLED WATER COIL IS SELECTED WITH 100% WATER. GLYCOL HEATING WATER COIL IS SELECTED WITH 30% PROPYLENE GLYCOL.
6.TOTAL EXTERNAL STATIC PRESSURE DOES NOT INCLUDE FILTER LOADING. MANUFACTURER SHALL INCLUDE DIRTY FILTER ALLOWANCE IN TOTAL STATIC PRESSURE CALCULATION.
7.STEAM PRESSURE INDICATED IS THE PRESSURE AVAILABLE DOWNSTREAM OF THE CONTROL VALVE.
8.PROVIDE AHU WITH INTERNAL MOTOR REMOVAL RAILS FOR FAN MOTOR SERVICING.
AIR HANDLING SCHEDULE - 100% OUTSIDE AIR
TAG
NAME SERVICE
SUPPLY FAN (NOTE 2, 3, & 4)
MINIMUM
OUTSIDE
AIR CFM
HEATING COIL - GLYCOL HEATING WATER
(NOTE 5) HUMIDIFIER (NOTE 7) COOLING COIL - CHILLED WATER (NOTE 5) ULTRA-VIOLET LIGHT COMBINATION FILTER (NOTE 6) FINAL FILTER ELECTRICAL MAXIMUM DIMENSIONS
WEIGHT MANUFACTURER MODEL NOTES
NO.
OF
FANS
CFM
TOTAL
MIN.
CFM
EXT.
S.P. TYPE
RPM
(NOTE D)
BHP
EACH
(NOTE E)
MHP
EACH
(NOTE E)
EAT
°F
LAT
°F
EWT
°F
LWT
°F GPM MBH
MAX.
A.P.D.
IN.
W.C.
W.P.D
. FEET
HEAD TYPE CFM
STEAM
CAPACITY
(LBS/HR)
STEAM
PSIG MANUFACTURER
EAT
DB
°F
EAT
WB
°F
LAT
DB
°F
LAT
WB
°F
EWT
°F
LWT
°F
TOTAL
MBH GPM
W.P.D.
FEET
HEAD
MAX.
A.P.D.
IN.
W.C.
NUMBER
OF
ROWS
INTENSITY
AT COIL
SURFACE
TOTAL
POWER
(WATTS)
FIRST STAGE FILTER SECOND STAGE FILTER
TYPE
FACE
VELOCITY
PRESSURE
DROP NO. OF
POWER
CONNECTIONS VOLTAGE PHASES
DISCONNECT(S)
CONTROLLER
STATER(S)
SCCR
NO. OF
AUXILIARY
CONNECTIONS LENGTH WIDTH HEIGHTTYPE
FACE
VELOCITY
PRESSURE DROP
TYPE
FACE
VELOCITY
PRESSURE DROP
CLEAN DIRTY
BY
(NOTE A)
TYPE
(NOTE B)
BY
(NOTE A)
TYPE
(NOTE C)CLEAN DIRTY CLEAN DIRTY
AHU-1 STERILE PROCESSING
AREA
4 12000 12000 2.5 PLENUM 3420 6 6.5 12000 -20.0 65.0 175 145 73.4 1329 0.1 4.7 DISPERSION
TUBE
12,000 341 15 DRI-STEAM 95 78 46.8 46.8 40 52 1165.1 193.2 9.17 0.66 4 31.4 W/ft² 1480 MERV 8 270 .2 .74 MERV 13 270 .2 1 MERV 14 270 0.2 0.88 1 480 3 EC F MFR VFD 65000 3 351" 86" 90" 15169 TEMTROL CUSTOM NOTE 8
NOTES:
1.PROVIDE SHAFT GROUNDING AS REQUIRED IN THE MOTOR SPECIFICATION 23 05 12.
2.PROVIDE FAN WITH SOLID STATE SPEED CONTROL FOR USE BY TAB CONTRACTOR IN INITIAL BALANCING.
3.PROVIDE FAN IN A DUAL FAN CONFIGURATION WITH SHARED INLET PLENUM AND BYPASS AIR DAMPERS. DUAL FANS SHALL BE n+1 REDUNDANT SUCH THAT EACH FAN IS INDEPENDENTLY CAPABLE OF OPERATING AT THE SCHEDULED AIRFLOW. AT FULL SPEED (SCHEDULED AIRFLOW), THE BYPASS DAMPER WILL BE
COMPLETELY CLOSED. BYPASS DAMPER WILL MODULATE OPEN TO MAINTAIN A MINIMUM STACK HEIGHT OF 20 FEET AS THE EXHAUST FAN RAMPS DOWN.
4.PROVIDE EACH FAN WITH MANUFACTURER’S ISOLATION DAMPERS AND ONE MANUFACTURER’S BYPASS DAMPER. TEMPERATURE CONTROLS CONTRACTOR SHALL PROVIDE ACTUATORS AND END SWITCHES FOR ALL DAMPERS AND CONFIRM POSITION PRIOR TO START-UP SEQUENCING.
5.PROVIDE FANS WITH FINISH THAT INCLUDES AN EPOXY BASE COAT AND ELECTROSTATIC POWDER COATED HI-PRO POLYESTER TOPCOAT.
FAN SCHEDULE
TAG NAME SERVICE CFM
S.P.
IN.
W.C.
FAN
CLASS
WHEEL
DIA.
INCHES
FAN
RPM
(NOTE F)
DRIVE
TYPE
MAX.
AMCA
SONES
BACKDRAFT
DAMPER
TYPE
CURB
TYPE
(NOTE G)
ELECTRICAL (NOTE 1)
WEIGHT
VIBRATION
ISOLATION
MANUFACTURER MODEL NOTESBHP MHP VOLTAGE PHASES
DISCONNECT CONTROLLER/ STARTER
TYPE DEFL.
BY
(NOTE A)
TYPE
(NOTE B)
BY
(NOTE A)
TYPE
(NOTE C) SCCR
EF-1 CLEAN WORKROOM INSTRUMENT SET ASSEMBLY 1760 1.75 I 18 1539 DIRECT 15.6 MOD MFR 1.05 1.5 480 3 EC NF MFR VFD 5000 98 N/A 0.00" PENN BARRY DX14B NOTE 1
EF-2A/B DECONTAMINATION WORK AREA 8220 3.50 II 25.9 1170 BELT 85 MOD GC 7.88 10 480 3 EC NF MFR VFD 65000 1048 M4 0.75" MK PLASTICS AXIJET-F 3000 NOTES 1, 3, 4, & 5
EF-3 GENERAL EXHAUST 1200 1.00 I 20 1455 DIRECT 11.8 MOD MFR 0.36 0.5 120 1 EC NF MFR FV 5000 66 N/A 0.00" PENN BARRY DX16Q1GP NOTE 2
EF-4 GENERAL EXHAUST 150 0.25 I 16 1215 DIRECT 6.25 MOD MFR 0.06 0.25 120 1 EC NF MFR FV 5000 51 N/A 0.00" PENN BARRY DX13QGP NOTE 2
SF-1 PIPE BASEMENT VENTILATION 24000 0.50 I 20 515 DIRECT 13.84 MOD MFR 5.2 6 480 3 EC NF MFR VFD 5000 98 N/A 0.00" PENN BARRY LF40BC NOTE 1
NOTES:
1.MOUNT HOOD ON MANUFACTURER’S CURB. TOP OF CURB SHALL BE A MINIMUM OF 18” ABOVE TOP OF ROOF INSULATION.
2.MAXIMUM HEIGHT MEASURED FROM TOP OF CURB TO TOP OF EQUIPMENT.
HOOD SCHEDULE
TAG
NAME SERVICE CFM
THROAT SIZE
THROAT
VELOCITY
STATIC
PRESSURE
DROP
FREE
AREA
(FT ²) CONFIGURATION
MAX.
HEIGHT
(NOTE 2)
DAMPER
TYPE
CURB
TYPE
MAX. DIMENSIONS
WEIGHT MANUFACTURER MODEL NOTESWIDTH LENGTH LENGTH WIDTH HEIGHT
OAH-1 AHU-1 12000 36 54 889 0.08 13.5 GRAVITY HOOD 24 MOD MFR 92.5 68.5 17 110.6 PENN BARRY PG3654 NOTE 1
OAH-2 AHU-2 5000 20 42 833 0.07 6 GRAVITY HOOD 20 MOD MFR 62.5 50.5 13 64.1 PENN BARRY PG2436 NOTE 1
OAH-3 5-AC10 INTAKE 4750 18 24 950 0.09 5 GRAVITY HOOD 18 MOD MFR 58.5 42.5 11 53.6 PENN BARRY PG2036 NOTE 1
RAH-1 AHU-2 4000 24 30 667 0.06 6 GRAVITY HOOD 17 MOD MFR 56.5 38.5 10 50 PENN BARRY PG2436 NOTE 1
RAH-2 5-EF12 EXHAUST 625 12 18 625 0.05 1 GRAVITY HOOD 12 MOD MFR 20.5 20.5 5 18.9 PENN BARRY PG1212 NOTE 1
RAH-3 5-AC10 RELIEF 4750 18 24 543 0.04 8.75 GRAVITY HOOD 18 MOD MFR 62.5 44.5 11 63.4 PENN BARRY PG2036 NOTE 1
NOTES:
1.NEITHER RADIATED NOR DISCHARGE SOUND LEVELS SHALL EXCEED NC 35 AT 1.5" INLET STATIC PRESSURE WHEN TESTED PER AHRI STANDARD 885-2008 USING 5/8" 20-LB DENSITY MINERAL FIBER
CEILING TILE.
2.TOTAL AIR PRESSURE DROP OF TAB AND REHEAT COIL SHALL NOT EXCEED 0.50" WC. PROVIDE REHEAT COILS SEPARATE FROM BOXES IF REQUIRED TO MEET AIR PRESSURE DROP REQUIREMENTS.
3.REFER TO CONTROL DRAWINGS FOR DESCRIPTION OF CONTROL TYPE.
4.SENSOR TYPES: 1 - SENSOR ONLY, 2 - SENSOR WITH ADJUSTMENT, 3 - SENSOR WITH OVERRIDE, 4 - SENSOR WITH ADJUSTMENT AND OVERRIDE.
5.HEATING COIL IS BASED ON HEATING AIR FLOW. WATER PRESSURE DROP OF REHEAT COILS SHALL NOT EXCEED 5'. PROVIDE REHEAT COILS SEPARATE FROM BOXES IF REQUIRED TO MEET WATER
PRESSURE DROP REQUIREMENTS.
6.WHEN LAT °F, EWT °F, AND GPM VALUES ARE BLANK, HEATING COIL IS NOT REQUIRED FOR TAB.
7.HEATING COIL SELECTION SHALL BE BASED ON A FIXED LEAVING AIR TEMPERATURE AND VARIABLE FLOW (GPM). PROVIDE FINAL MAXIMUM FLOW RATE (GPM) TO TEST & BALANCE TEMPERATURE
CONTROLS CONTRACTORS.
TERMINAL AIR BOX SCHEDULE - SINGLE DUCT
TAG
NAME AREA SERVED
CFM HEATING COIL (NOTES 5, 6, & 7) MIN. INLET
SIZE (IN.)
DIA.
CONTROL
TYPE
(NOTE 3)
SENSOR
TYPE
(NOTE 4) MANUFACTURER
MODEL
(NOTES 1, 2) NOTES
COOLING
MAX.
HEATING
MAX. MIN. EAT °F LAT °F
EWT
°F
LWT
°F
MAX.
GPM
TAB-2-01 C50 CORRIDOR 400 400 400 55.0 85.0 180 150 0.9 6" TYPE B TYPE 1 TITUS DESV NOTES 1, 2
TAB-2-02 H2 CONFERENCE 350 350 175 55.0 85.0 180 150 0.8 6" TYPE B TYPE 3 TITUS DESV NOTES 1, 2
TAB-2-03 H4 OFFICE 200 200 80 55.0 85.0 180 150 0.5 6" TYPE B TYPE 4 TITUS DESV NOTES 1, 2
TAB-2-04 H5 OFFICE 125 125 80 55.0 85.0 180 150 0.5 6" TYPE B TYPE 4 TITUS DESV NOTES 1, 2
TAB-2-05 H8 STAFF LOUNGE 450 450 150 55.0 85.0 180 150 1.0 8" TYPE B TYPE 3 TITUS DESV NOTES 1, 2
TAB-2-06 H9 OFFICE 200 200 80 55.0 85.0 180 150 0.5 6" TYPE B TYPE 4 TITUS DESV NOTES 1, 2
TAB-2-07 H10 OFFICE 200 200 80 55.0 85.0 180 150 0.5 6" TYPE B TYPE 4 TITUS DESV NOTES 1, 2
TAB-2-08 H11 OFFICE 200 200 80 55.0 85.0 180 150 0.5 6" TYPE B TYPE 4 TITUS DESV NOTES 1, 2
TAB-2-09 H12 MENS LOCKER 425 425 425 55.0 85.0 180 150 0.9 8" TYPE B TYPE 2 TITUS DESV NOTES 1, 2
TAB-2-10 H13 WOMENS LOCKER 425 425 425 55.0 85.0 180 150 0.9 8" TYPE B TYPE 2 TITUS DESV NOTES 1, 2
TAB-2-11 C50 CORRIDOR 350 350 350 55.0 85.0 180 150 0.8 6" TYPE B TYPE 1 TITUS DESV NOTES 1, 2
NOTES:
1.CONTRACTOR SHALL DETERMINE PROPER BORDER TYPE TO MATCH CEILING CONSTRUCTION.
2.REFER TO DRAWINGS FOR NECK SIZE. ALL BRANCH DUCTWORK TO AIR TERMINALS SHALL BE NECK SIZE UNLESS NOTED OTHERWISE.
3.DUCTED RETURN
4.FRONT BLADES VERTICAL UNLESS OTHERWISE NOTED.
5.FLUSH FACE PANEL.
6.ALL BALANCING DAMPERS SHOWN ABOVE HARD LID CEILINGS SHALL BE ELECTRONIC REMOTELY OPERATED TYPE; GENERALLY, ALL GRILLES AND DIFFUSERS SERVED BY
AHU-1 OR EF-2A/B HAVE BALANCING DAMPERS LOCATED ABOVE HARD LID CEILINGS. MECHANICAL CONTRACTOR SHALL REVIEW ARCHITECTURAL REFLECTED CEILING PLANS AND VERIFY QUANTITY PRIOR TO BID. REFERENCE SPECIFICATION SECTION 23 31 00 FOR ADDITIONAL INFORMATION.
AIR TERMINAL SCHEDULE
TAG
NAME
FACE
SIZE (IN.)
(NOTE 2) TYPE BORDER MATERIAL FINISH
VOLUME
DAMPER
REQUIRED MANUFACTURER MODEL NOTES
EG-1 12x12 PERFORATED FACE NOTE 1 STEEL WHITE NO TITUS PAR NOTES 3 & 6
EG-2 12x12 PERFORATED FACE NOTE 1 ALUMINUM WHITE NO TITUS PAR NOTES 3 & 6
EG-3 24x24 PERFORATED FACE NOTE 1 STEEL WHITE NO TITUS PAR NOTES 3 & 6
EG-4 24x24 PERFORATED FACE NOTE 1 ALUMINUM WHITE NO TITUS PAR NOTES 3 & 6
ER-1 INLET +2 35 DEGREE DEFLECTION NOTE 1 ALUMINUM WHITE YES TITUS 350F NOTE 4 & 6
RG-3 24x24 PERFORATED FACE NOTE 1 STEEL WHITE NO TITUS PAR NOTES 3 & 6
RG-4 24x24 PERFORATED FACE NOTE 1 ALUMINUM WHITE NO TITUS PAR NOTES 3 & 6
SD-1 12x12 PANEL FACE NOTE 1 STEEL WHITE NO TITUS OMNI NOTE 5 & 6
SD-3 24x24 PANEL FACE NOTE 1 STEEL WHITE NO TITUS OMNI NOTE 5 & 6
SD-4 24x24 PANEL FACE NOTE 1 ALUMINUM WHITE NO TITUS OMNI NOTE 5 & 6
SR-1 INLET +2 35 DEGREE DEFLECTION NOTE 1 STEEL WHITE YES TITUS 350R NOTE 4 & 6
NOTES:
1.REFERENCE SPECIFICATION SECTION 23 73 00 INDOOR CENTRAL-STATION AIR-HANDLING UNITS.
2.PROVIDE SHAFT GROUNDING AS REQUIRED IN THE MOTOR SPECIFICATION 23 05 12.
3.ONE FULLY REDUNDANT (N+1) SUPPLY/RETURN FAN SHALL BE PROVIDED FOR EACH FAN ARRAY. SCHEDULED RPM AND BHP REPRESENT N PERFORMANCE.
4.PROVIDE 1 VFD PER SUPPLY/RETURN FAN.
5.CHILLED AND HEATING WATER COILS ARE SELECTED WITH 100% WATER.
6.TOTAL EXTERNAL STATIC PRESSURE DOES NOT INCLUDE FILTER LOADING. MANUFACTURER SHALL INCLUDE DIRTY FILTER ALLOWANCE IN TOTAL STATIC PRESSURE CALCULATION.
7.STEAM PRESSURE INDICATED IS THE PRESSURE AVAILABLE DOWNSTREAM OF THE CONTROL VALVE.
8.PROVIDE AHU WITH INTERNAL MOTOR REMOVAL RAILS FOR FAN MOTOR SERVICING.
AIR HANDLING SCHEDULE - MIXED AIR VAV
TAG
NAME SERVICE
SUPPLY FAN (NOTE 2, 3, & 4) RETURN FAN (NOTE 2, 3, & 4)
MINIMUM
OUTSIDE
AIR CFM
HEATING COIL - HEATING WATER (NOTE 5) HUMIDIFIER (NOTE 7) COOLING COIL - CHILLED WATER (NOTE 5) ULTRA-VIOLET LIGHT ELECTRICAL COMBINATION FILTER (NOTE 6) MAXIMUM DIMENSIONS
WEIGHT MANUFACTURER MODEL NOTES
NO.
OF
FANS
CFM
TOTAL
MIN.
CFM
EXT.
S.P. TYPE
RPM
(NOTE D)
BHP
EACH
(NOTE E)
MHP
EACH
(NOTE E)
NO.
OF
FANS
CFM
TOTAL
MIN.
CFM
EXT.
S.P. TYPE
RPM
(NOTE D)
BHP
EACH
(NOTE E)
MHP
EACH
(NOTE E)
EAT
°F
LAT
°F
EWT
°F
LWT
°F GPM MBH
MAX.
A.P.D.
IN.
W.C.
W.P.D
. FEET
HEAD TYPE CFM
STEAM
CAPACITY
(LBS/HR)
STEAM
PSIG
MANUFAC
TURER
EAT
DB
°F
EAT
WB
°F
LAT
DB
°F
LAT
WB
°F
EWT
°F
LWT
°F
TOTAL
MBH GPM
W.P.D.
FEET
HEAD
MAX.
A.P.D.
IN.
W.C.
NUMBER
OF
ROWS
INTENSITY
AT COIL
SURFACE
TOTAL
POWER
(WATTS)
NO. OF
POWER
CONNE
CTIONS VOLTAGE PHASES
DISCONNECT(S)
CONTROLLER
STATER(S)
SCCR
NO. OF
AUXILIARY
CONNECTI
ONS
FIRST STAGE FILTER SECOND STAGE FILTER
LENGTH WIDTH HEIGHT
BY
(NOTE A)
TYPE
(NOTE B)
BY
(NOTE A)
TYPE
(NOTE C) TYPE
FACE
VELOCITY
PRESSURE DROP
TYPE
FACE
VELOCITY
PRESSURE DROP
CLEAN DIRTY CLEAN DIRTY
AHU-2 STERILE
PROCESSING
ADMINISTRATIVE
AREA
2 5000 2500 1.8 PLENUM 3443 6.1 7.5 2 5000 2500 1.5 PLENUM 2254 2.7 3 1250 39.3 65.0 180 150 9.8 144 0.1 2.8 DISPERSION
TUBE
5,000 142 15 DRI-STEAM 80.9 69.4 52.3 52 40 52 261.6 43.4 9.94 0.45 4 45.6 W/ft² 248 2 480 3 EC F MFR VFD 65000 3 MERV
270 .2 .85 MERV
270 .2 1 374" 46" 77" 9969 TEMTROL CUSTOM NOTE 8
NOTES:
1.NEITHER RADIATED NOR DISCHARGE SOUND LEVELS SHALL EXCEED NC 35 AT 1.5" INLET STATIC PRESSURE WHEN TESTED PER AHRI STANDARD 885-2008 USING 5/8" 20-LB
DENSITY MINERAL FIBER CEILING TILE.
2.REFER TO SPECIFICATION SECTION 23 36 00, VENTURI VALVE AIRFLOW CONTROL SYSTEM.
3.PROVIDE ROOM INTEGRATOR TO CONNECT DIRECTLY TO FMCS VIA NETWORK.
4.FAST ACTING VALVE. REFER TO CONTROL DRAWINGS FOR DESCRIPTION OF CONTROL TYPE.
5.SENSOR TYPES: 1 - SENSOR ONLY, 2 - SENSOR WITH ADJUSTMENT, 3 - SENSOR WITH OVERRIDE, 4 - SENSOR WITH ADJUSTMENT AND OVERRIDE.
AIR VALVE SCHEDULE
TAG NAME AREA SERVED
CFM MIN. INLET
SIZE (IN.)
DIA.
CONTROL
TYPE
(NOTE 4)
SENSOR
TYPE
(NOTE 5) MANUFACTURER MODEL NOTES
COOLING
MAX. MIN.
VV1-01 C51 CORRIDOR 325 325 8" TYPE A TYPE 1 CRITICAL ROOM CLVI NOTES 1, 2, & 3
VV1-02 H17 STERILE INSTRUMENT STORAGE 875 875 8" TYPE A TYPE 1 CRITICAL ROOM CLVI NOTES 1, 2, & 3
VV1-03 H18 LOGISTICS STORAGE ROOM 125 125 8" TYPE A TYPE 1 CRITICAL ROOM CLVI NOTES 1, 2, & 3
VV1-04 H17A SCOPE STAGING ROOM 725 725 8" TYPE A TYPE 2 CRITICAL ROOM CLVI NOTES 1, 2, & 3
VV1-05 H26 SCOPE PROCESSING DECONTAMINATION AREA 550 550 8" TYPE A TYPE 2 CRITICAL ROOM CLVI NOTES 1, 2, & 3
VV1-06 H24 CART HOLDING 775 775 8" TYPE A TYPE 1 CRITICAL ROOM CLVI NOTES 1, 2, & 3
VV1-07 H20A MANUAL CARTWASH 200 200 8" TYPE A TYPE 3 CRITICAL ROOM CLVI NOTES 1, 2, & 3
VV1-08 STEAM STERILIZATION AREA 1350 1350 8" TYPE A TYPE 3 CRITICAL ROOM CLVI NOTES 1, 2, & 3
VV1-09 H25 ANTEROOM, SOILED TRANSITION/DROPOFF 175 175 8" TYPE A TYPE 1 CRITICAL ROOM CLVI NOTES 1, 2, & 3
VV1-10 H23 DETERGENT 425 425 8" TYPE A TYPE 1 CRITICAL ROOM CLVI NOTES 1, 2, & 3
VV1-11 H21 DECONTAMINATION WORK AREA 2000 2000 14" TYPE A TYPE 2 CRITICAL ROOM CLVI NOTES 1, 2, & 3
VV1-12 H15 CLEAN WORKROOM/ASSEMBLY 3035 3035 12" TYPE A TYPE 2 CRITICAL ROOM CLVI NOTES 1, 2, & 3
VV1-13 H14 ANTE-ROOM CLEAN 150 150 8" TYPE A TYPE 2 CRITICAL ROOM CLVI NOTES 1, 2, & 3
NOTES:
1.HEATING COIL SELECTION SHALL BE BASED ON A FIXED LEAVING AIR TEMPERATURE AND VARIABLE FLOW (GPM). PROVIDE FINAL MAXIMUM
FLOW RATE (GPM) TO TEST & BALANCE TEMPERATURE CONTROLS CONTRACTORS.
COIL SCHEDULE - WATER
TAG
NAME CFM
EAT LAT TOTAL
MBH
A.P.D. IN.
W.C. EWT °F LWT °F GPM
W.P.D. FT.
HEAD MANUFACTURER MODEL NOTESDB °F DB °F
HC-1-01 325 50.0 85.0 11 0.50 180 150 0.7 5.0 AAON C5 NOTE 1
HC-1-02 870 50.0 85.0 28 0.50 180 150 1.9 5.0 AAON C5 NOTE 1
HC-1-03 125 50.0 85.0 4 0.50 180 150 0.5 5.0 AAON C5 NOTE 1
HC-1-04 725 50.0 85.0 23 0.50 180 150 1.6 5.0 AAON C5 NOTE 1
HC-1-05 550 50.0 85.0 18 0.50 180 150 1.2 5.0 AAON C5 NOTE 1
HC-1-06 775 50.0 85.0 25 0.50 180 150 1.7 5.0 AAON C5 NOTE 1
HC-1-07 200 50.0 85.0 6 0.50 180 150 0.5 5.0 AAON C5 NOTE 1
HC-1-08 1350 50.0 85.0 44 0.50 180 150 2.9 5.0 AAON C5 NOTE 1
HC-1-09 175 50.0 85.0 6 0.50 180 150 0.5 5.0 AAON C5 NOTE 1
HC-1-10 425 50.0 85.0 14 0.50 180 150 0.9 5.0 AAON C5 NOTE 1
HC-1-11 2000 50.0 85.0 65 0.50 180 150 4.3 5.0 AAON C5 NOTE 1
HC-1-12 3035 50.0 85.0 98 0.50 180 150 6.6 5.0 AAON C5 NOTE 1
HC-1-13 150 50.0 85.0 5 0.50 180 150 0.5 5.0 AAON C5 NOTE 1
G. CURB TYPE:
MFR = STANDARD CURB BY MANUFACTURER
GC = BY GENERAL CONTRACTOR
F. MUST BE WITHIN +/- 10% OF SCHEDULED RPM.
E. NO EQUIPMENT SHALL BE SELECTED ABOVE 90% OF MOTOR NAME
PLATE RATING.
D. FAN RPM SHALL NOT EXCEED 110% OF SCHEDULED VALUE, WITH
THE SCHEDULED WHEEL TYPE. SUBSTITUTION OF BI OR BIA FANS
FOR FC IS ACCEPTABLE IF EFFICIENCY IS NOT LOWER.
C. CONTROLLER STARTER TYPE:
FV = FULL VOLTAGE
VFD = VARIABLE FREQUENCY DRIVE
VFD/B = VARIABLE FREQUENCY DRIVE WITH BYPASS
B. DISCONNECT TYPE:
F = FUSED
NF = NON-FUSED
A. DISCONNECT AND CONTROLLER STARTER FURNISHED AND
INSTALLED BY:
MFR = MANUFACTURER
EC = ELECTRICAL CONTRACTOR.
VENTILATION SCHEDULE
GENERAL NOTES
Revisions: Date:
Addendum 3 (AD-3) 05/12/2025
AD-3
AD-3
| Sheets |
| MV600 - VENTILATION SCHEDULES |
File details come from the government source that posted it. Updated .