This document is an electrical one-line diagram (ES500) for a VA construction project at the Sioux Falls VA Health Care System, specifically detailing a partial demolition riser diagram for a new Sterile Processing Services (SPS) facility. The diagram depicts electrical infrastructure across multiple buildings (Buildings 24, 1, 5, and 50), including temporary generator connections with specific electrical specifications: 480V generators ranging from 400A to 800A, and various power distribution configurations.
Key technical details include requirements for new conductors with no splicing allowed, generator start-up within 10 seconds during power loss, and specific wiring configurations. The diagram provides keynotes for temporary generator provisions, including 400A, 800A, and 600A three-phase generators, and includes junction box details for medical gas alarm wiring. The electrical design is part of the project to construct approximately 8,500 square feet of new SPS space and renovate 2,300 square feet, with an interstitial mechanical space matching the SPS footprint.
View the file
Other files
Show 40 more
Latest 50 of 61 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERATOR SWITCHGEAR
MSG-1
480V,3PH,4W
ATS-LS
400A
ATS-EQ
600A
TEQ
225 KVA
DP-EL DP-EP
ATS-CR
400A
TCR
150 KVA
DP-E
BUILDING 24
BUILDING 5
BUILDING 1
ATS-1
400A
TEM
112.5 KVA
DP-EM
4#350, 1#1/0 EGC IN 4" C.
4#350, 1#1/0 EGC IN 4" C.
(2) SETS OF 4#350, 1#3/0 EGC EACH IN 4" C.
4#350, 1#1/0 EGC IN 4" C.
BUILDING 50
(16) #14 SHIELDED PAIRS IN 2" C. FOR GENERATOR START WIRING
(16) #14 SHIELDED PAIRS IN 2" C. FOR GENERATOR START WIRING
(16) #14 SHIELDED PAIRS IN 2" C. (SLEEVED THROUGH 4" C.)
GENERATOR START WIRING
(16) #14 SHIELDED PAIRS IN 2" C. (SLEEVED THROUGH 4" C.)
GENERATOR START WIRING
P3G-G01
400A
P3G-G03
400A
P3G-G02
800A
4#600, 1#3 EGC IN 4" C.
(2) SETS OF 4#600, 1#1/0 EGC EACH IN 4" C.
4#600, 1#3 EGC IN 4" C.
(4) 2" C. FOR CONTROL CABLING
ATS-A3S-G01
ATS-A3C-G01
ATS-A3E-G01
ATS-A3S-G02
ATS-8
400A
2" C. FOR CONTROL CABLING
GENERATOR START WIRING
TLS
150 KVA
SUGGESTED TEMPORARY
GENERATOR CONNECTION
SUGGESTED TEMPORARY
GENERATOR CONNECTION
SUGGESTED TEMPORARY
GENERATOR CONNECTION
SUGGESTED TEMPORARY
GENERATOR CONNECTION
SUGGESTED TEMPORARY
GENERATOR CONNECTION
SUGGESTED TEMPORARY
GENERATOR CONNECTION
SUGGESTED TEMPORARY
GENERATOR CONNECTION
1 3
L
E N
L
E N
E N
L
E N
L
E N
L
PANEL DPIC
BLDG. 5
PANEL EBB
BLDG. 5
MED GAS
BLDG. 5
DS-TCR
DS-TLS DS-TEQ
DS-ATS-8
5 5
4#600, 1#1 EGC IN 4" C.
I O W A
S E
D
PROFESS IO NA
21081
L
IC
E N
L E
N G
I N E
E R
KRISTEN L.
SPINA
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
B
IM
/1
.0
V A
-W a s h
D C
-V A
S io u x F a lls
N e w
S P
S /M
E P
T
.0
V A
W a s h D
C -V
A S io u x F a lls
N e w S
P S
C
.r v t
/2
/2
:5
:3
P
M
ES500
ELECTRICAL ONE-LINE DIAGRAMS CONSTRUCT NEW SPS
Sioux Falls, SD.
438-460
05/13/2025 KLS AWU16584
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE
THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG CORP. © 2025 IMEG CORP.
2882 106TH STREET
DES MOINES, IA 50322
515.334.9906 FAX: 515.334.9908
www.imegcorp.com
19004249.04
NO SCALE
PARTIAL DEMO RISER DIAGRAM
Revisions: Date:
Addendum 3 (AD-3) 05/20/2025
SHEET NOTES:
1. ALL NEW CONDUCTORS MUST BE RAN FOR ALL
BRANCHES OF EMERGENCY POWER. NO
SPLICING WILL BE ALLOWED.
2. ALL NEW CONDUCTORS MUST BE RAN FOR
CONTROL WIRING SERVING EQUIPMENT ON
EMERGENCY POWER. NO SPLICING WILL BE
ALLOWED.
3. TEMPORARY GENERATORS ARE REQUIRED TO
START UP WITH IN 10 SECONDS OR LESS.
GENERATORS WILL NOT BE RUNNING AT ALL
TIMES, ONLY IN THE EVENT OF A NORMAL
POWER LOSS. (STANDBY)
AD-3
KEYNOTES:
1. PROVIDE 480V, 400A, 3PH, 4W TEMPORARY
GENERATOR.
2. PROVIDE 480V, 800A, 3PH, 4W TEMPORARY
GENERATOR.
3. PROVIDE 480V, 600A, 3PH, 4W TEMPORARY
GENERATOR.
4. JUNCTION BOX FOR MED GAS ALARM WIRING.
5. TEMPORARY GENERATOR START WIRING TO
ASSOCIATED PORTABLE GENERATOR.
| Sheets |
| ES099 - CAMPUS SITE PLAN - ELECTRICAL |
| ES100 - NEW ELECTRICAL SITE PLANS |
| ES400 - NEW ELECTRICAL SITE DETAILS |
| ES401 - NEW ELECTRICAL SITE DETAILS |
| ES500 - ELECTRICAL ONE-LINE DIAGRAMS |
| ES501 - ELECTRICAL ONE-LINE DIAGRAMS |