S06 - Amend 0009 - Att 15 - DWG ES400 - Rvd - SPS - Sioux Falls.pdf
PDF 352 KB Posted
- Solicitation number
- 36C77624R0115
About this file
This document is an electrical site detail drawing for a new electrical manhole (MH-20) at the Sioux Falls VA Health Care System project. The drawing provides technical specifications for a 36-inch diameter precast or cast-in-place concrete manhole designed to AASHTO HS-20 live load standards, with detailed section and plan views showing construction elements such as PVC-coated pulling irons, conduit routing, ground rod installation, and cable support brackets.
The drawing includes a comprehensive feeder demolition and replacement schedule detailing electrical circuit modifications across multiple buildings (Buildings 1, 5, and 24), specifying conductor sizes, quantities, and locations for various distribution panels, automatic transfer switches (ATS), and electrical rooms. The feeder schedule indicates multiple emergency and control circuit reconfigurations, with conductor specifications ranging from #10 single conductors to 600 KCMIL cables, serving different electrical systems in ground, first, and third-floor locations of the medical facility.
View the file
Other files
Show 40 more
Latest 50 of 61 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
18"Ø SUMP PIT
WITH MINIMUM 12" DRAIN
FIELD OF PEA GRAVEL
BOTTOM SECTION
PVC COATED
PULLING IRONS
LOCATED OPPOSITE
CONDUIT ENTRANCES
STANDARD PRECAST
OR CAST-IN-PLACE
CONCRETE MANHOLE
DOWEL DUCT BANK TO
MANHOLE WITH
MINIMUM (4) #4 DOWELS
CONDUITS
SLOPE TO
MANHOLE (TYP)
2500 PSI GROUT
MALLEABLE IRON
BELL END (TYP)
TOP SECTION
CAST-IN-PLACE OR
PRECAST CONCRETE TOP
PROVIDE ANCHORING FOR
CABLE SUPPORT BRACKETS
AT 2'-0" O.C. ON ALL MANHOLE
WALLS. PROVIDE NON-
METALLIC CABLE SUPPORT
ARMS AS REQUIRED
MANHOLE FRAME WITH SOLID
LID, MARKED "ELECTRICAL".
NEENAH FOUNDRY R-1640, OR
EQUAL.
5/8" x 8'-0" COPPER CLAD
GROUND ROD, IN 2" PVC
SLEEVE. BOND ALL STEEL IN
MANHOLE TO GROUND ROD
FINISH GRADE
SECTION VIEW
36" Ø 1
M
IN
IM
U
M
M
IN
IM
U
M
PLAN VIEW
GROUND ROD SLEEVE
36"Ø CLEAR OPENING
NOTES:
1. MANHOLE SHALL BE DESIGNED TO AASHTO HS-20 LIVE LOADS.
SUBMITTAL SHALL SHOW DESIGN LOADING AND MATERIAL SPECIFICATIONS
FOR SUPPLIED PRODUCTS.
1. DETAIL IS DIAGRAMMATIC AND DOES NOT SHOW EXACT NUMBER OF
CONDUITS ENTERING/EXISTING THE MANHOLE. REFER TO FLOORPLANS AND
OTHER DETAILS FOR MORE INFORMAITON.
W
ID
T
H
9'-6" LENGTH
BLDG 24 - BLDG 5 FEEDER DEMOLITION & REPLACEMENT
EMERGENCY FEEDER CIRCUITS FROM BUILDING 24 TO BUILDING 5
LOAD BLDG & ROOM LOCATION FLOOR LOCATION CONDUCTOR QTY. & SIZE
DISTRIBUTION PANEL DPIC BLDG 5 ATTIC 2 SETS OF (4) #4/0 & (1) #1/0 GND
PANEL EBB BLDG 5; 131A FIRST FLOOR (4) #1/0 & (1) #6 GND
MED GAS PANELS BLDG 5; C22 CORRIDOR, 188 CORRIDOR, 322
NURSE STATION
GROUND FLOOR, FIRST FLOOR, THIRD
FLOOR
MULTIPLE #10 SINGLE CONDUCTORS IN
1"C. EACH PANEL HAS (3) POWER
PATHWAYS FOR REDUNDANCY
MANHOLE MH-20 FEEDER DEMOLITION & REPLACEMENT SCHEDULE
EMERGENCY FEEDER CIRUITS PASSING THROUGH EXISTING ELECTRICAL MANHOLE MH-20. ALL FEEDERS ORIGINATE AT MSG-1 LOCATED IN BUILDING 50.
TAG LOAD BLDG & ROOM LOCATION FLOOR LOCATION CONDUCTOR QTY. & SIZE
A P3G-G01 (DIST. PANEL) BLDG 5 ELEC ROOM G40 GROUND FLOOR (4) 600 KCMIL & (1)#3 GND
B,C P3G-G02 (ENCL. CB) BLDG 5 ELEC ROOM G40 GROUND FLOOR 2 SETS OF (4) 600 KCMIL & (1) #1/0 GND
D PG3-G03 (DIST. PANEL) BLDG 5 ELEC ROOM G40 GROUND FLOOR (4) 600 KCMIL & (1) #3 GND
E ATS-CR (DISCON.) BLDG. 24 (4) 350 KCMIL & (1) #1/0 GND
F ATS-LS (DISCON.) BLDG 5 ELEC DISTR. E01 GROUND FLOOR (4) 350 KCMIL & (1) #1/0 GND
G,H ATS-EQ (DISCON.) BLDG 5 ELEC DISTR. E03 GROUND FLOOR 2 SETS OF (4) 350 KCMIL & (1) #3/0 GND
I ATS-1 (DISCON.) BLDG. 1 - MECH ROOM 1B GROUND FLOOR (4) 350 KCMIL & (1) #1/0 GND
J ATS-8 (ENCL. CB) BLDG. 5 MECH. ROOM 126B 1ST FLOOR (4) 600 KCMIL & (1)#1 GND
K ATS-A3S-G01 BLDG 5 ELEC ROOM G40 GROUND FLOOR CONTROL CABLING
L ATS-A3C-G01 BLDG 5 ELEC ROOM G40 GROUND FLOOR CONTROL CABLING
M ATS-A3E-G01 BLDG 5 ELEC ROOM G40 GROUND FLOOR CONTROL CABLING
N ATS-A3S-G02 BLDG 5 ELEC ROOM G40 GROUND FLOOR CONTROL CABLING
O ATS CR BLDG. 24 GEN. CONTROL - 16PR., 14 AWG
P ATS LS BLDG 5 ELEC DISTR. E01 GROUND FLOOR GEN. CONTROL - 16PR., 14 AWG
Q ATS EQ BLDG 5 ELEC DISTR. E03 GROUND FLOOR GEN. CONTROL - 16PR., 14 AWG
R ATS-1 (DISCON.) BLDG. 1 - MECH ROOM 1B GROUND FLOOR GEN. CONTROL - 16PR., 14 AWG
S ATS-8 (ENCL. CB) BLDG. 5 MECH. ROOM 126B 1ST FLOOR CONTROL CABLING
T UNKNOWN - FIELD VERIFY UNKNOWN UNKNOWN (3) #6
K I G M
J D O Q
A B C D E F
H J K
L M N
O P Q R S
I
T
C E F
H P
S LR N
A T BP
F
REFER TO MH-20 FEEDER
SCHEDULE FOR EXISTING
FEEDER INFORMATION (TYP.)
SOUTHEAST ELEVATION SOUTHWEST ELEVATION NORTHWEST ELEVATION NORTHEAST ELEVATION
= EMPTY DUCT
G
1. REFER TO MH-20 FEEDER SCHEDULE FOR EXISTING FEEDER INFORMATION
2. ALL INFORMATION IS FROM EXISTING DRAWINGS
I O W A
S E
D
PROFESS IO NA
21081
L
IC
E N
L E
N G
I N E
E R
KRISTEN L.
SPINA
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
B
IM
/1
.0
V A
-W a s h
D C
-V A
S io u x F a lls
N e w
S P
S /M
E P
T
.0
V A
W a s h D
C -V
A S io u x F a lls
N e w S
P S
C
.r v t
/2
/2
:5
:3
P
M
ES400
NEW ELECTRICAL SITE DETAILS CONSTRUCT NEW SPS
Sioux Falls, SD.
438-460
05/13/2025 KLS AWU16584
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE
THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG CORP. © 2025 IMEG CORP.
2882 106TH STREET
DES MOINES, IA 50322
515.334.9906 FAX: 515.334.9908
www.imegcorp.com
19004249.04
Revisions: Date:
Addendum 3 (AD-3) 05/20/2025
NO SCALE
NEW ELECTRICAL MANHOLE (MH-20) DETAIL
AD-3
NO SCALE
EXISTING MH-20 DETAIL
| Sheets |
| ES099 - CAMPUS SITE PLAN - ELECTRICAL |
| ES100 - NEW ELECTRICAL SITE PLANS |
| ES400 - NEW ELECTRICAL SITE DETAILS |
| ES401 - NEW ELECTRICAL SITE DETAILS |
| ES500 - ELECTRICAL ONE-LINE DIAGRAMS |
| ES501 - ELECTRICAL ONE-LINE DIAGRAMS |
File details come from the government source that posted it. Updated .