This document is a detailed technical specification for a STERIS 3 Basin 120" Adjustable Height Reprocessing Sink, with comprehensive engineering drawings and utility requirements. The sink is a stainless steel (304 series) medical equipment design intended for endoscope and medical instrument processing, featuring an adjustable height range of 33"-41" with a total unit width of 120", depth of 28", and three basins.

Key technical specifications include multiple water connections (hot, cold, pure water), compressed air and water gun interfaces, electrical requirements of 120V 15A GFCI protection, and a LINAK DL2 lift system with 562 lbs weight capacity per adjustment. The sink requires specific compressed air quality meeting ISO 8573-1:2010 standards, with precise pressure (29-145 psi), flow rate, and air purity parameters. Installation demands include maintaining specific wall clearances, floor drain positioning, and seismic anchoring considerations. The shipping weight is approximately 690 lbs, with operating dimensions allowing flexibility in medical facility environments.

View the file

Other files

File Type Posted
S06 - Amend 0010 - RFP - 36C77624R0115 - SPS - Sioux Falls_rev.docx DOCX document
S06 - Amend 0010 - RFP - 36C77624R0115 - SPS - Sioux Falls.docx DOCX document
S06 - Amend 0009 - Att 12 - DWG EP111 - Rvd - SPS - Sioux Falls.pdf PDF
S06 - Amend 0009 - Att 07 - List of DWG Sheets - Rvd - SPS - Sioux Falls.pdf PDF
S06 - Amend 0009 - Att 03 - DWG AC101 - Rvd - SPS - Sioux Falls.pdf PDF
S06 - Amend 0009 - Att 10 - Ele Sch - Rvd - SPS - Sioux Falls.pdf PDF
S06 - Amend 0009 - Att 16 - DWG ES401 - Rvd - SPS - Sioux Falls.pdf PDF
S06 - Amend 0009 - Att 04 - DWG AD111 - Rvd - SPS - Sioux Falls.pdf PDF
S06 - Amend 0009 - Att 08 - DWG CD101 - Rvd - SPS - Sioux Falls.pdf PDF
S06 - Amend 0009 - Att 01 - Sign-In Sheet - Ele Site Visit- 05142025 - SPS - Sioux Falls.pdf PDF
S06 - Amend 0009 - Att 19 - DWG MV600 - Rvd - SPS - Sioux Falls.pdf PDF
S06 - Amend 0009 - Att 20 - DWG GI001 - Rvd - SPS - Sioux Falls.pdf PDF
S06 - Amend 0009 - Att 13 - DWG ES099 - Rvd - SPS - Sioux Falls.pdf PDF
S06 - Amend 0009 - Att 06 - DWG GC111 - Rvd - SPS - Sioux Falls.pdf PDF
S06 - Amend 0009 - Att 17 - DWG ES500 - Rvd - SPS - Sioux Falls.pdf PDF
S06 - Amend 0009 - Att 09 - Add Ele Questions and Responses - SPS - Sioux Falls.pdf PDF
S06 - Amend 0009 - Att 15 - DWG ES400 - Rvd - SPS - Sioux Falls.pdf PDF
S06 - Amend 0009 - Att 11 - DWG EP101 - Rvd - SPS - Sioux Falls.pdf PDF
S06 - Amend 0009 - RFP - 36C77624R0115 - SPS - Sioux Falls.pdf PDF
S06 - Amend 0009 - Att 18 - DWG ES501 - Rvd - SPS - Sioux Falls.pdf PDF
S06 - Amend 0009 - Att 02 - Narrative to KTRs - SPS - Sioux Falls.pdf PDF
S06 - Amend 0009 - Att 14 - DWG ES100 - Rvd - SPS - Sioux Falls.pdf PDF
S06 - Amend 0009 - Att 05 - DWG AE111 - Rvd - SPS - Sioux Falls.pdf PDF
S06 - Amend 0008 - RFP - 36C77624R0115 - SPS - Sioux Falls.pdf PDF
36C77624R0115 0007.pdf PDF
Amend 0007 - Att 02 - RFI QandA.pdf PDF
S06 - Amend 0006 - Att 01- RFP - Sign-In Sheet - Site Visit - 04082025 - SPS - Sioux Falls.pdf PDF
S06 - Amend 0006 - RFP - 36C77624R0115 - SPS - Sioux Falls.pdf PDF
S06 - Amend 0006 - Att 02 - Wage Rates - 03142025 - SPS - Sioux Falls.pdf PDF
S06 - Amend 0005 - RFP - 36C77624R0115 - SPS - Sioux Falls.pdf PDF
S06 - Amend 0004 - RFP - 36C77624R0115 - SPS - Sioux Falls.pdf PDF
S06 - Amend 0003 - RFP - Sign-in Sheet - Site Visit - 03252025 - SPS - Sioux Falls.pdf PDF
S06 - Amend 0003 - RFP - Site Visit Presentation - SPS - Sioux Falls.pdf PDF
S06 - Amend 0003 - RFP - 36C77624R0115 - SPS - Sioux Falls.pdf PDF
S06 - Amend 0002 - RFP - 36C77624R0115 - SPS - Sioux Falls.pdf PDF
S06 - Amend 0002 - RFP - Att 01-05 - DWG - 03242025 - SPS - Sioux Falls.pdf PDF
S06 - Amend 0002 - RFP - Att 01-02 - DWG - 03242025 - SPS - Sioux Falls.pdf PDF
S06 - Amend 0002 - RFP - Att 01-08 - DWG - 03242025 - SPS - Sioux Falls.pdf PDF
S06 - Amend 0002 - RFP - Att 01-03 - DWG - 03242025 - SPS - Sioux Falls.pdf PDF
S06 - Amend 0002 - RFP - Att 01-09 - DWG - 03242025 - SPS - Sioux Falls.pdf PDF
S06 - Amend 0002 - RFP - Att 01-07 - DWG - 03242025 - SPS - Sioux Falls.pdf PDF
S06 - Amend 0002 - RFP - Att 01-11 - DWG - 03242025 - SPS - Sioux Falls.pdf PDF
S06 - Amend 0002 - RFP - Att 01-10 - DWG - 03242025 - SPS - Sioux Falls.pdf PDF
S06 - Amend 0002 - RFP - Att 01-01 - DWG - 03242025 - SPS - Sioux Falls.pdf PDF
S06 - Amend 0002 - RFP - Att 01-06 - DWG - 03242025 - SPS - Sioux Falls.pdf PDF
S06 - Amend 0002 - RFP - Att 01-04 - DWG - 03242025 - SPS - Sioux Falls.pdf PDF
S06 - Amendment 0001 - SPS - Sioux Falls.pdf PDF
RFP - Att 02 - 02142025 - Specs - Vol I - SPS - Sioux Falls.pdf PDF
36C77624R0115_1.docx DOCX document
RFP - Att 01-01 - DWG - 02142025 - SPS - Sioux Falls.pdf PDF
Show 40 more

Latest 50 of 61 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

7/8 [22] MIN

SEE NOTE #2

28-1/16 [712]

UNIT DEPTH17 [432]

BASIN

3X 30 [762]

BASIN

23-1/16 [585]

DRAIN BOARD

13 [330]

DRAIN BOARD

120 [3048] UNIT WIDTH

33 [838]

MINIMUM

WORKING

HEIGHT

3/4 MAX

[19]

11-9/16 [293]

BACKSPLASH

4 [102]

BACKSPLASH

42 [1041]

MAXIMUM

WORKING

HEIGHT

52-17/32 [1335]

MAXIMUM

HEIGHT

T I T L E

3 BASIN 120" ADJUSTABLE HEIGHT REPROCESSING SINK

Corporation

SIZE: SCALE: DRAWN BY: DRAWING NUMBER: PART NUMBER: REVISION:

A 1.000 Kosir, Joe SINK50120 F.7 11002996 F This document contains confidential and proprietary information of STERIS Corporation. Neither this document nor the information herein are to be reproduced, either in part or in whole, except as specifically authorized by STERIS Corporation.

SHEET

REVISION: ECN #:

REVISION HISTORY DEPICTS CHANGES FROM

PRIOR REVISIONF 106432

INDEX DESCRIPTION OF CHANGE

1 SHEET 1- NOTE 2 ADDED MINIMUM. NOTE 4 CHANGED 300 TO 304

2 SHEET 3- CHANGED UTILITY REQUIREMENTS FROM 1/2" NPSM TO 3/8" COMPRESSION (2 PLACES) 3 SHEET 3- CHANGED UTILITY REQUIREMENTS FROM QUICK CONNECTOR FLEX COIL TO 3/8" COMPRESSION 4 SHEET 3- CHANGED UTILITY REQUIREMENTS FROM 1/2" NPSM WITH ...ADAPTER (INCLUDED)C TO 1/2" NPT

5 SHEET 3- CHANGED UTILITY REQUIREMENTS FROM 1/4" NPFT HOSE INCLUDED TO 1/4" NPT

6 SHEET 3- CHANGED NOTE 5 FROM "PREVENTED" TO "PREVENTION"

7 SHEET 4- CHANGED WALL AND FLOOR VIEW DRAIN DETAILS AND NOTES

8 SHEET 4- MOVED SEISMIC ANCHOR VIEW TO SHEET 6

9 SHEET 6- ADDED NOTE 2

DETAIL A

BASIN DEPTH 10" [254] DETAIL A

F

F

NOTES:

1. UNLESS OTHERWISE NOTED, ALL DIMENSIONS ARE IN INCHES [MM].

2. INSTALLER MUST MAINTAIN A MINIMUM GAP OF .875" TO ALL ADJACENT WALLS AS PINCH POINT PROTECTION.

3. UNIT TO BE INSTALLED AGAINST A WALL, FOR BACK TO BACK INSTALLATION A PONY WALL IS REQUIRED.

4. 304 SERIES STAINLESS STEEL CONSTRUCTION.

5. PONY WALL HEIGHT MUST BE 53"[1346].

6. WALL MUST BE FREE OF OBSTRUCTIONS TO 54"[1372].

ADJUSTABLE HEIGHT FEET (4)

FRONT VIEW

TOP VIEW

RIGHT SIDE VIEW

SHOWN AT

MAX HEIGHT

56-1/4 [1429]A

63-3/4 [1619]WG

[686]

13-1/2 [343]

75 [1905]

SUPPLY CONNECTIONS

TO BE IN THIS ZONE

22-3/8 [568]

29 [737]PW

40-1/2 [1029]HW

48-1/2 [1232]CW

71-1/2 [1816]HW

79-1/2 [2019]CW

91 [2311]PW

MAXIMUM

80-3/4 [2051]

MINIMUM

72-3/4 [1848]

6-3/8 [162]

T I T L

A 1.000 Kosir, Joe SINK50120 F.7 11002996 F This document contains confidential and proprietary information of STERIS Corporation. Neither this document nor the information herein are to be reproduced, either in part or in whole, except as specifically authorized by STERIS Corporation.

SHEET

FRONT VIEW

RIGHT SIDE VIEW

SHOWN AT

MAX HEIGHT

NOTE: WORKFLOW CAN BE REVERSED BY MOVING PURE WATER FAUCET

FROM RIGHT SIDE TO HOLE ON LEFT THAT IS CAPPED.

ADDITIONALLY THE COMPRESSED AIR AND WATER GUN FIXTURES SHOULD BE SWAPPED.

DB

HW HOT WATER

CW COLD WATER

PW PURE WATER

WG WATER GUN

A COMPRESSED AIR

DB DRAIN BASKET (BASIN)

D DRAIN

T L

A 1.000 Kosir, Joe SINK50120 F.7 11002996 F This document contains confidential and proprietary information of STERIS Corporation. Neither this document nor the information herein are to be reproduced, either in part or in whole, except as specifically authorized by STERIS Corporation.

SHEET

NOTES:

1. SUPPLY LINES FOR EACH CONNECTION ARE SHIPPED WITH EACH SINK.

2. STERIS RECOMMENDS THE FOLLOWING WATER QUALITY PARAMETERS:

1. 100-200 PPM (500PPM MAX) TOTAL DISOLVED SOLIDS.

2. 70-120 PPM (180PPM MAX) TOTAL ALKALINITY.

3. 6.8-7.0PH (7.5 MAX).

4. 0.1-0.5PPM (1.0PPM MAX) TOTAL SILICA.

3. STERIS DOES NOT SUPPLY A PRESSURE REGULATOR FOR USE WITH AIR GUN.

4. STERIS DOES NOT SUPPLY A PRESSURE REDUCING VALVE FOR USE WITH WATER GUN.

5. BACK FLOW PREVENTION BY CUSTOMER AGAINST BACK SIPHONAGE MAY BE REQUIRED (CHECK LOCAL PLUMBING CODE).

6. FLOOR SINK OUTLET NEEDS TO BE ABLE TO ACCOMODATE WASTE FROM ALL BAYS (CHECK LOCAL PLUMBING CODE).

7. REFERENCES FOR PARAMETERS ARE TO MANUFACTURER'S RECOMMENDATION AND SHOULD BE FOLLOWED ACCORDINGLY.

F

F

F

F

F

F

ADJ. HEIGHT PROCESSING TRIPLE SINK 120" X 28" X 33"-41"

UTILITY REQUIREMENTS CHART (PLUMBING)

UTILITY PARAMETER REQUIREMENT NOTES

HOT WATER

(HW)

CONNECTION TYPE/SIZE 3/8" COMPRESSION

PRESSURE RANGE 15 TO 125 PSI

OPERATING FLOW RATE 1.6 GPM @ MAX PSI

TEMPERATURE RANGE 40 F TO 180 F

WATER QUALITY SEE NOTE #2

COLD WATER

(CW)

CONNECTION TYPE/SIZE 3/8" COMPRESSION

PRESSURE RANGE 15 TO 125 PSI

OPERATING FLOW RATE 1.6 GPM @ MAX PSI

TEMPERATURE RANGE 70 F MAX

WATER QUALITY SEE NOTE #2

PURE WATER

(PW)

CONNECTION TYPE/SIZE 1/2" NPT

PRESSURE RANGE 20 TO 125 PSI

OPERATING FLOW RATE .25 TO 2.00 GPM 15%

TEMPERATURE RANGE 40 F TO 140 F

WATER QUALITY

WATER GUN

(WG)

CONNECTION TYPE/SIZE 3/8" COMPRESSION

PRESSURE RANGE 0 TO 44 PSI

OPERATING FLOW RATE

TEMPERATURE RANGE 40 F TO 125 F

WATER QUALITY SEE NOTE #2

AIR GUN

(A)

CONNECTION TYPE/SIZE 1/4" NPT CONNECTION MUST BE MADE

PER LOCAL CODE

PRESSURE 30 PSI MAX

TIP 1

CONSUMPTION AT 30 PSI 2 SCFM

TIP 2

TIP 3

TIP 4

TIP 5

TIPS 4 & 5 MUST BE OPERATED AT 30 PSI OR LESS TO COMPLY WITH OSHA DIRECTIVE

BASIN DRAIN

(BD) CONNECTION TYPE

1-1/2" ABS P-TRAP (INCLUDED)

2" COPPER P-TRAP (ACCESSORY)

DRAIN RATE AT 20 GPM

EACH BASIN (ESTIMATED)

17-15/16 [455]

17-15/16 [455]

[787]

CENTER TO CENTER

DRAIN LOCATION

[787]

CENTER TO CENTER

DRAIN LOCATION

9-3/8 [238]

WALL CONNECTION

HEIGHT FROM FLOOR

[152]

[152]

65-3/8 [1662]

T I T L

A 1.000 Kosir, Joe SINK50120 F.7 11002996 F This document contains confidential and proprietary information of STERIS Corporation. Neither this document nor the information herein are to be reproduced, either in part or in whole, except as specifically authorized by STERIS Corporation.

SHEET

FLOOR DRAIN CONNECTIONS

TO BE IN THIS ZONE

FRONT VIEW

FLOOR NOTES:

1. FLOOR DRAIN IS PREFERED.

2. DRAIN CANNOT BE LOCATED WITHIN 6" OF LEGS.

DRAIN

WALL NOTES:

1. EACH DRAIN INDIVIDUALLY TRAPPED.

2. WHEN TRAPS ARE NOT REQUIRED, ELBOWS CAN BE PURCHASED LOCALLY.

3. ROUGH-IN TOLERANCE 3/8"

DRAIN LOCATION, (WALL)

RIGHT SIDE VIEW

SHOWN AT

MAX HEIGHT

DRAIN

F

F

F

F

DRAIN LOCATION, (FLOOR)

FRONT VIEW RIGHT SIDE VIEW

SHOWN AT

MAX HEIGHT

[483]

[152]

1 [25]

[76]

T I T L

A 1.000 Kosir, Joe SINK50120 F.7 11002996 F This document contains confidential and proprietary information of STERIS Corporation. Neither this document nor the information herein are to be reproduced, either in part or in whole, except as specifically authorized by STERIS Corporation.

SHEET

15A 120VAC GFCI

PROTECTED OUTLET

UTILITY (ELECTRICITY)

CONNECTION POSITION

RECOMMENDED

PARTIAL FRONT VIEW

INCLUDES 10'[3048] CORD

ADJ. HEIGHT REPROCESSING TRIPLE SINK 120" X 28" X 33" TO 41"

UTILITY SPECIFICATIONS CHART (ELECTRICAL)

ELECTRICITY

UTILITY PARAMETER REQUIREMENT NOTES

ELECTRICITY 120V 15A GFCI PROTECTED OUTLET

LINAK DL2 LIFT SYSTEM

LINAK DL2

LIFT SYSTEM

WEIGHT CAPACITY 562LBS [2500 N] EACH

ADJUSTMENT RANGE 8.0" [203,2]

LIFT SPEED UP TO 3/8"[10] PER SECOND

VOLTAGE 120VAC, 3A WITH OVERLOAD

PROTECTION

14 [356]

SEE NOTE BELOW

1-1/2 [38]

4X 9/16 [14]

FOR 1/2-13

SEISMIC ANCHORS

102-7/16 [2602]

SEE NOTE BELOW

95-1/16 [2415]

[762]

6-13/16 [173]

[406]

T I T L

A 1.000 Kosir, Joe SINK50120 F.7 11002996 F This document contains confidential and proprietary information of STERIS Corporation. Neither this document nor the information herein are to be reproduced, either in part or in whole, except as specifically authorized by STERIS Corporation.

SHEET

BACK WALL

F

NOTE:

1. CONCRETE FLOOR MUST REMAIN FREE OF DEFECTS IN THESE AREAS FOR

INSTALLATION OF SEISMIC ANCHORS (NOT PROVIDED BY STERIS).

2. REFER TO EQUIPMENT SPECIFIC SEISMIC DRAWING FOR MORE INFORMATION.

SEISMIC ANCHOR HOLE POSITIONS

PHYSICAL SPECIFICATIONS

SHIPPING DIMENSIONS L X W X H 132L X 36W X 48H

SHIPPING WEIGHT 690 LBS

OPERATING DIMENSIONS L X W X H 120" X 28" X 44-9/16" TO 52-9/16"

[3048 X 711 X 1132 TO 1412]

OPERATING WEIGHT EMPTY 490 LBS

WORKING HEIGHT 33"[838] TO 41"[1041]

3X 30 [762]

BASIN

17 [432]

BASIN

97-1/2 [2477]

UNIT WIDTH

33 [838]

MINIMUM

WORKING

HEIGHT

41 [1041]

MAXIMUM

WORKING

HEIGHT

28-1/16 [712]

UNIT DEPTH

7/8 [22]MIN

SEE NOTE #2

23-1/16 [585]

DRAIN BOARD 3/4 MAX

[19]

28-15/16 [734]

MINIMUM

52-9/16 [1335]

MAXIMUM

HEIGHT

4 [102]

BACKSPLASH

11-9/16 [293]

BACKSPLASH

T I T L E

3 BASIN 97.5" ADJUSTABLE HEIGHT REPROCESS SINK

Corporation

SIZE: SCALE: DRAWN BY: DRAWING NUMBER: PART NUMBER: REVISION:

A 0.022 Kosir, Joe SINK5097 F.3 11002999 F

This document contains confidential and proprietary information of STERIS Corporation. Neither this document nor the information herein are to be reproduced, either in part or in whole, except as specifically authorized by STERIS Corporation.

SHEET

REVISION: ECN #:

REVISION HISTORY DEPICTS CHANGES FROM

PRIOR REVISIONF 106432

INDEX DESCRIPTION OF CHANGE

1 ADD 2" COPPER P-TRAP AS ACCESSORY UNDER UTILITY REQUIREMENTS ALONG WITH ESTIMATED DRAIN RATE 2 SHEET 3- CHANGED UTILITY REQUIREMENTS FROM 1/2" NPSM TO 3/8" COMPRESSION (2 PLACES) 3 SHEET 3- CHANGED UTILITY REQUIREMENTS FROM QUICK CONNECTOR FLEX COIL TO 3/8" COMPRESSION 4 SHEET 3- CHANGED UTILITY REQUIREMENTS FROM 1/2" NPSM WITH ...ADAPTER (INCLUDED)C TO 1/2" NPT

5 SHEET 3- CHANGED UTILITY REQUIREMENTS FROM 1/4" NPFT HOSE INCLUDED TO 1/4" NPT

6 SHEET 3- CHANGED NOTE 5 FROM "PREVENTED" TO "PREVENTION"

7 SHEET 4- CHANGED WALL AND FLOOR VIEW DRAIN DETAILS AND NOTES

8 SHEET 4- MOVED SEISMIC ANCHOR VIEW TO SHEET 6

9 SHEET 6- ADDED NOTE 2

DETAIL A

NOTES:

1. UNLESS OTHERWISE NOTED, ALL DIMENSIONS ARE IN INCHES [MM].

2. INSTALLER MUST MAINTAIN A MINIMUM GAP OF .875" TO ALL ADJACENT WALLS AS PINCH POINT PROTECTION.

3. UNIT TO BE INSTALLED AGAINST A WALL, FOR BACK TO BACK INSTALLATION A PONY WALL IS REQUIRED.

4. 304 SERIES STAINLESS STEEL CONSTRUCTION.

5. PONY WALL HEIGHT MUST BE 53"[1346].

6. WALL MUST BE FREE OF OBSTRUCTIONS TO 54"[1372].

TOP VIEW

BASIN DEPTH 10" [254]

ADJUSTABLE HEIGHT FEET (4)

FRONT VIEW

DETAIL A RIGHT SIDE VIEW

SHOWN AT

MAX HEIGHTF

F

17-3/4 [451]PW

29-1/4 [743]HW

37-1/4 [946]CW

45 [1143]A

52-1/2 [1334]WG

60-1/4 [1530]HW

68-1/4 [1734]CW

79-3/4 [2026]PW

27 [686]

6-3/8 [162]

13-1/2 [343]

75 [1905]

SUPPLY CONNECTIONS

TO BE IN THIS ZONE

11-1/8 [282]

MAXIMUM

80-3/4 [2051]

MINIMUM

72-3/4 [1848]

T I T L E

3 BASIN 97.5" ADJUSTABLE HEIGHT REPROCESS SINK

Corporation

SIZE: SCALE: DRAWN BY: DRAWING NUMBER: PART NUMBER: REVISION:

A 0.016 Kosir, Joe SINK5097 F.3 11002999 F

This document contains confidential and proprietary information of STERIS Corporation. Neither this document nor the information herein are to be reproduced, either in part or in whole, except as specifically authorized by STERIS Corporation.

SHEET

HW HOT WATER

CW COLD WATER

PW PURE WATER

WG WATER GUN

A COMPRESSED AIR

DB DRAIN BASKET (BASIN)

D DRAIN

NOTE: WORKFLOW CAN BE REVERSED BY MOVING PURE WATER FAUCET

FROM RIGHT SIDE TO HOLE ON LEFT THAT IS CAPPED.

ADDITIONALLY THE COMPRESSED AIR AND WATER GUN FIXTURES SHOULD BE SWAPPED.

RIGHT SIDE VIEW

SHOWN AT

MAX HEIGHT

FRONT VIEW

DB

T L E

3 BASIN 97.5" ADJUSTABLE HEIGHT REPROCESS SINK

Corporation

SIZE: SCALE: DRAWN BY: DRAWING NUMBER: PART NUMBER: REVISION:

A 0.016 Kosir, Joe SINK5097 F.3 11002999 F

This document contains confidential and proprietary information of STERIS Corporation. Neither this document nor the information herein are to be reproduced, either in part or in whole, except as specifically authorized by STERIS Corporation.

SHEET

ADJ. HEIGHT PROCESSING TRIPLE SINK 97.5" X 28" X 33"-41"

UTILITY REQUIREMENTS CHART (PLUMBING)

UTILITY PARAMETER REQUIREMENT NOTES

HOT WATER

(HW)

CONNECTION TYPE/SIZE 3/8" COMPRESSION

PRESSURE RANGE 15 TO 125 PSI

OPERATING FLOW RATE 1.6 GPM @ MAX PSI

TEMPERATURE RANGE 40 TO 180 F

WATER QUALITY SEE NOTE #2

COLD WATER

(CW)

CONNECTION TYPE/SIZE 3/8" COMPRESSION

PRESSURE RANGE 15 TO 125 PSI

OPERATING FLOW RATE 1.6 GPM @ MAX PSI

TEMPERATURE RANGE 70 F MAX

WATER QUALITY SEE NOTE #2

PURE WATER

(PW)

CONNECTION TYPE/SIZE 1/2" NPT

PRESSURE RANGE 20 TO 125 PSI

OPERATING FLOW RATE .25 TO 2.00 GPM ±15%

TEMPERATURE RANGE 40° F TO 140°F

WATER QUALITY

WATER GUN

(WG)

CONNECTION TYPE/SIZE 3/8" COMPRESSION

PRESSURE RANGE 0 TO 44 PSI

OPERATING FLOW RATE

TEMPERATURE RANGE 40° F TO 125°F

WATER QUALITY SEE NOTE #2

AIR GUN

(A)

CONNECTION TYPE/SIZE 1/4" NPT CONNECTION MUST BE MADE

PER LOCAL CODE

PRESSURE 30 PSI MAX

TIP 1

CONSUMPTION AT 30 PSI 2 SCFM

TIP 2

TIP 3

TIP 4

TIP 5

TIPS 4 & 5 MUST BE OPERATED AT 30 PSI OR LESS TO COMPLY WITH OSHA DIRECTIVE

BASIN DRAIN

(BD) CONNECTION TYPE

1-1/2" ABS P-TRAP (INCLUDED)

2" COPPER P-TRAP (ACCESSORY)

DRAIN RATE AT 20 GPM

EACH BASIN (ESTIMATED)

NOTES:

1. SUPPLY LINES FOR EACH CONNECTION ARE SHIPPED WITH EACH SINK.

2. STERIS RECOMMENDS THE FOLLOWING WATER QUALITY PARAMETERS:

1. 100-200 PPM (500PPM MAX) TOTAL DISOLVED SOLIDS.

2. 70-120 PPM (180PPM MAX) TOTAL ALKALINITY.

3. 6.8-7.0PH (7.5 MAX).

4. 0.1-0.5PPM (1.0PPM MAX) TOTAL SILICA.

3. STERIS DOES NOT SUPPLY A PRESSURE REGULATOR FOR USE WITH AIR GUN.

4. STERIS DOES NOT SUPPLY A PRESSURE REDUCING VALVE FOR USE WITH WATER GUN.

5. BACK FLOW PREVENTION BY CUSTOMER AGAINST BACK SIPHONAGE MAY BE REQUIRED (CHECK LOCAL PLUMBING CODE).

6. FLOOR SINK OUTLET NEEDS TO BE ABLE TO ACCOMODATE WASTE FROM ALL BAYS (CHECK LOCAL PLUMBING CODE).

7. REFERENCES FOR PARAMETERS ARE TO MANUFACTURER'S RECOMMENDATION AND SHOULD BE FOLLOWED ACCORDINGLY.

F

F

F

F

17-15/16 [455]

17-15/16 [455]

[787]

CENTER TO CENTER

DRAIN LOCATION

[787]

CENTER TO CENTER

DRAIN LOCATION

9-3/8 [238]

WALL CONNECTION

HEIGHT FROM FLOOR

[152]

65-3/8 [1662]

[153]

T I T L E

3 BASIN 97.5" ADJUSTABLE HEIGHT REPROCESS SINK

Corporation

SIZE: SCALE: DRAWN BY: DRAWING NUMBER: PART NUMBER: REVISION:

A 0.016 Kosir, Joe SINK5097 F.3 11002999 F

This document contains confidential and proprietary information of STERIS Corporation. Neither this document nor the information herein are to be reproduced, either in part or in whole, except as specifically authorized by STERIS Corporation.

SHEET

FLOOR NOTES:

1. FLOOR DRAIN IS PREFERED.

2. DRAIN CANNOT BE LOCATED WITHIN 6" OF LEGS.

FRONT VIEW

FRONT VIEW

DRAIN LOCATION, (FLOOR)

FLOOR DRAIN CONNECTIONS

TO BE IN THIS ZONE

DRAIN ℄

RIGHT SIDE VIEW

SHOWN AT

MAX HEIGHT

WALL NOTES:

1. EACH DRAIN INDIVIDUALLY TRAPPED.

2. WHEN TRAPS ARE NOT REQUIRED, ELBOWS CAN BE PURCHASED LOCALLY.

3. ROUGH-IN TOLERANCE ±3/8"

DRAIN LOCATION, (WALL)

RIGHT SIDE VIEW

SHOWN AT

MAX HEIGHT

DRAIN ℄

F

F

[483]

[152]

[76]

T I T L E

3 BASIN 97.5" ADJUSTABLE HEIGHT REPROCESS SINK

Corporation

SIZE: SCALE: DRAWN BY: DRAWING NUMBER: PART NUMBER: REVISION:

A 0.022 Kosir, Joe SINK5097 F.3 11002999 F

This document contains confidential and proprietary information of STERIS Corporation. Neither this document nor the information herein are to be reproduced, either in part or in whole, except as specifically authorized by STERIS Corporation.

SHEET

ADJ. HEIGHT REPROCESSING TRIPLE SINK 97.5" X 28" X 33" TO 41"

UTILITY SPECIFICATIONS CHART (ELECTRICAL)

ELECTRICITY

UTILITY PARAMETER REQUIREMENT NOTES

ELECTRICITY 120V 15A GFCI PROTECTED OUTLET

LINAK DL2 LIFT SYSTEM

LINAK DL2

LIFT SYSTEM

WEIGHT CAPACITY 562LBS [2500 N] EACH

ADJUSTMENT RANGE 8.0" [203,2]

LIFT SPEED UP TO 3/8"[10] PER SECOND

VOLTAGE 120VAC, 3A WITH OVERLOAD

PROTECTION

PARTIAL FRONT VIEW

UTILITY (ELECTRICITY)

CONNECTION POSITION

RECOMMENDED

INCLUDES 10'[3048] CORD

15A 120VAC GFCI

PROTECTED OUTLET

1-1/2 [38]

14 [356]

SEE NOTE BELOW

⌀9/16 [14]

FOR 1/2-13

SEISMIC ANCHORS

102-7/16 [2602]

SEE NOTE BELOW

95-1/16 [2415]

6-13/16 [173]

[406]

[762]

TOLERANCES: +/- INCH (MM) IF NOT INDICATED OTHERWISE MATERIAL / NOTES

DIMENSION 0-48 48+ DIMENSION 0-4 4-24 24+

NA

FINISH: NA

MACHINING FRAC.

DEC.

1/64 0.005

1/32 0.015

PLASTIC FRAC.

DEC.

1/64 0.005

1/32 0.020

1/16 N/A

SHEET METAL / SAWING 1/32 1/16 DIMENSION 0-12 12-60 60+ COMPONENT/ASSEMBLY MUST BE RoHS COMPLIANT

DIMENSION 0-1 1+ WELDED ASSEMBLY 1/32 1/16 3/32 DIMENSION 0-3/8 3/8-3/4 3/4 +

BORING 0.001 0.002 SPOT WELD 1/16 3/32 HOLE DIAMETER 0.005 0.015 1/32

SURFACE FINISH 63 machined surface (Visual) SQUARENESS 1/16 total 1/8 total ANGLE 1° WEIGHT: [.2] LBS.

T I T L E

3 BASIN 97.5" ADJUSTABLE HEIGHT REPROCESS SINK

Corporation

SIZE: SCALE: DRAWN BY: DRAWING NUMBER: PART NUMBER: REVISION:

A 0.022 Kosir, Joe SINK5097 F.3 11002999 F

This document contains confidential and proprietary information of STERIS Corporation. Neither this document nor the information herein are to be reproduced, either in part or in whole, except as specifically authorized by STERIS Corporation.

SHEET

PHYSICAL SPECIFICATIONS

SHIPPING DIMENSIONS L X W X H 132L X 36W X 48H

SHIPPING WEIGHT 580 LBS

OPERATING DIMENSIONS L X W X H 97.5" X 28" X 44-9/16" TO 52-9/16"

[2477 X 711 X 1132 TO 1412]

OPERATING WEIGHT EMPTY 380 LBS

WORKING HEIGHT 33"[838] TO 41"[1041]

NOTE:

1. CONCRETE FLOOR MUST REMAIN FREE OF DEFECTS IN THESE AREAS FOR

INSTALLATION OF SEISMIC ANCHORS (NOT PROVIDED BY STERIS).

2. REFER TO EQUIPMENT SPECIFIC SEISMIC DRAWING FOR MORE INFORMATION.

SEISMIC ANCHOR HOLE POSITIONS

SCALE 0.050

BACK WALL

ENDODRY™

Drying and Storage Cabinet | Compressed Air Requirements

The ENDODRY™ Drying and Storage Cabinet requires compressed air which must meet specific incoming air quality requirements. This ensures optimal cabinet performance with continuous air flow to safely eliminate all residual water from the endoscopes being dried, which may otherwise promote the growth of organisms.

ENDODRY Cabinet Air Requirements

1. Quality: ISO 8573-1:2010 minimum class 1.4.1, recommended class 1.2.1

• Particle Size: Incoming air filtered down to 1 micron in size

• Moisture Content: Minimum pressure dew point (PDP) of +3°C or better required and no liquid water, -40°C or better recommended

• Oil Content: < 0.01mg of oil per cubic meter of compressed air (liquid, aerosol or vapor oil)

2. Pressure: The below pressures are required at the point of cabinet connection.

Consult with the Facilities Maintenance Department or qualified air vendor to identify potential losses in air supply.

• ENDODRY Cabinet for ADVANTAGE PLUS™ Hookups: 29 – 145 psi (2 – 10 bar)

• ENDODRY Cabinet for DSD Hookups: 73-145 psi (5 – 10 bar)

3. Volume Flow: The below volume flows are required at the point of cabinet connection.

• ENDODRY Cabinet for ADVANTAGE PLUS Hookups: Max demand of 4.2 scfm (120 l/min ANR) per cabinet

• ENDODRY Cabinet for DSD Hookups: Max demand of 7 scfm (200 l/min ANR) per cabinet

Given the air volume flow demand difference, the ENDODRY Cabinet for ADVANTAGE PLUS Hookups is recommended when using or moving to the ADVANTAGE PLUS™ Automated Endoscope Reprocessor platform. This recommendation also applies to non-Medivators AER’s, due to lower air consumption and potential ADVANTAGE PLUS Endoscope Reprocessor upgrade later.

ENDODRY Cabinet Air Grade

Instrument Air (NFPA 99) is the recommended grade of air to use with the ENDODRY Cabinet. Additional particulate filtration may be required to meet the ISO class listed above. If house/facility grade air is used (or other inferior air source), additional air treatment may also be needed to achieve the moisture and oil content listed above. Medical facilities will need to consult their Facilities Maintenance Department or their qualified air vendor to identify additional filtration needs to meet the air requirements listed above.

© 2018 Cantel 50098-1660-EN / A

Air Responsibility

• The medical facility is responsible for selecting and supplying their compressed air solution.

• The facility should consult their internal Facilities Maintenance Department or a qualified air vendor.

• The facility should have an air backup plan, as air compressors require service and maintenance.

• To assist facilities, Medivators has compiled a list of compressors below that can be purchased directly from either the manufacturer or an authorized dealer. However, Medivators has not validated and does not endorse any of the listed compressors, and is not responsible for air compressor warranty, service and maintenance. The list has been compiled based on no additional air demand and supply plumbing of 100ft or less. Work with the air supply vendor or Facilities Maintenance Department for the specific application.

ADVANTAGE PLUS™ Reprocessor Hookups DSD Hookups

# of Cabinets

BeaconMedaes (w/ Additional

Dryer)

Powerex (w/ Dryer)

# of Cabinets

BeaconMedaes (w/ Additional Dryer)

Powerex (w/ Dryer)

1 LES03-145T-RD SES0308TM** 1 LES05-145T-RD SES0508TM**

2 LES05-145T-RD SES0508TM** 2 LES10-145RD LSE1504

3 LES07-145T-RD LSE1504 3 LES15-145RD LSE1504

4 LES10-145T-RD LSE1504 4 LES20-145RD LSE2005

5 LES15-145RD LSE1504 5 LES20-145RD LSE2005

Additional capacities are available. Contact Vendor for additional details.

Compressor sizes assume the inclusion of a desiccant drying solution to obtain a pressure dew point (PDP) of -40°C or better.

Systems are available with 208V/230V/460V **Single-phase systems may need additional receiver Footprint Ranges from 26”x40” to 66”x30” depending on compressor size (with heights from 46” to 62”) Powerex Contact Information: 1-888-769-7979 or http://www.powerexinc.com/ BeaconMedaes Contact Information: 1-888-463-3427 (Option 2 - Tech Support, Option 3 - customer service) or www.beaconmedaes.com (includes regional directory)

Medivators Inc.

14605 28th Avenue North Minneapolis, MN

55447-4822 USA

Tel: +1.800.444.4729 Fax: +1.763.553.3387

Medivators BV Sourethweg 11 6422 PC Heerlen The Netherlands Tel: +31.45.5.471.471 Fax: +31.45.5.429.595

ESCAD Medical GmbH Zur Ohmdwiesen 5 88633 Heiligenberg Germany Tel: +49.7554.9999.500 Fax: +49.7554.9999.558 www.cantelmedical.com

Cantel Medical Asia/Paci�c Pte. Ltd.

1A International Business Park #05-01 Singapore 609933 Tel: +65.6227.9698 Fax: +65.6225.6848

ADVANTAGE PLUS™ and ENDODRY™ are trademarks of Medivators Inc.

Medivators Headquarters 14605 28th Avenue North Minneapolis, Minnesota 55447 Tel: 1.800.444.4729 www.cantelmedical.com

E

D

C

B

A

87654321

D

C

B

A en

STATUS:DOCUMENT:

MATERIAL:

UNLESS OTHERWISE SPECIFIED

DIMENSIONS ARE IN MILLIMETERS

TOLERANCES.

DIN ISO 2768-1 class: m DIN ISO 2768-2 class: K

FINISH:

CHECKEDNAMEDATEDESCRIPTIONREV

DATE

QUALITY CONTROL

CHECKED

DRAWN

NAME

A3

DO NOT SCALE DRAWING

TITLE:

DWG NO.

SCALE:

11.08.17Stebner

30 00 20 001

Installation requirements -horizontal storage cabinet

1/11

Klein

1:10

WEIGHT: g

09.08.17

Copyright according to ISO 16016 and DIN 34 Passing on and copying of this document, utilization and communication of its contents is not permitted, unless expressly allowed.

Offenders will be liable for compensation.

All rights reserved for IP application.

ISO 128-30

Methode 1 a typing mistakes and packaging adjusted b Adjustment of the temperatures in technical data

Storage cabinet with drying function for flexible endoscopes/ Lagerungsschrank mit Trocknungsfunktion für flexible Endoskope

Cabinet with article no.: / Schränke mit Artikel Nr.:

#015120-#015125 (ENDODRY)

#015126-#015131 (ENDODRY one-click)

#015760-#015765 (endoSTORE BHT)

#015906-#015911 (endoSTORE one-click)

17.05.18 Klein Stebner

Klein Stebner11.09.18 w h d

E

D

C

B

A

87654321

D

C

B

A en

STATUS:DOCUMENT:

MATERIAL:

UNLESS OTHERWISE SPECIFIED

DIMENSIONS ARE IN MILLIMETERS

TOLERANCES.

DIN ISO 2768-1 class: m DIN ISO 2768-2 class: K

FINISH:

CHECKEDNAMEDATEDESCRIPTIONREV

DATE

QUALITY CONTROL

CHECKED

DRAWN

NAME

A3

DO NOT SCALE DRAWING

TITLE:

DWG NO.

SCALE:

11.08.17Stebner

30 00 20 001

Installation requirements -horizontal storage cabinet

2/11

Klein

WEIGHT: g

09.08.17

Copyright according to ISO 16016 and DIN 34 Passing on and copying of this document, utilization and communication of its contents is not permitted, unless expressly allowed.

Offenders will be liable for compensation.

All rights reserved for IP application.

ISO 128-30

Methode 1

Definition of the locally connections / Definition der bauseitigen Anschlüsse min. permitted floor load / minimale Nutzlast Boden: 4,4 kN/m² level and stable surface necessary / ebener und stabiler Untergrund erforderlich

Technical specifications / Technische Daten:

Dimension cabinet/ Außenmaße:

w: 600 mm h: 1900mm d: 540mm Weight/Gewicht: 145 kg

Dimension standard packaging / Maße für Standardverpackung:

w: 800 mm h: 2200 mm d: 1200 mm Weight/Gewicht: 220 kg

DL

EDV

STDPE

Notice / Hinweis Comment / Bemerkung

Electrical disconnection / Trennung vom Stromnetz

The power cable of the cabinet serves as a separation device from the power supply.

If this can not be achieved properly, a suitable device must be installed on the premise (e.g. central emergency stop): / Das Netzkabel des Schrankes dient als Trenneinrichtung vom Stromnetz. Ist dieses nicht einwandfrei zu erreichen, muss hausseitig eine geeignete Einrichtung installiert werden (bspw.

zetraler Not-Halt).

Electrical connections / Elektroanschlüsse

Electrical connections must be installed in accordance with applicable standards. / Elektroanschlüsse sind nach geltenden Vorschriften (z.B. VDE) zu installieren.

Reference / Bezug All dimensions refer to the finished floor and the finished wall. / Alle Maßangaben beziehen sich auf Fertigfußboden und Fertigwand.

Technical Data / Technische Daten Working Condition /

Betriebsbedingung Temperature/Temperatur: 50 °F-95 °F / 10 °C-35 °C Humidity / Luftfeuchtigkeit: 10 %rel.-75 %rel.

Noise level/ Geräuschpegel

55dB(A) +-5dB(A) frontal 1m distance from a single cabinet in quite environment / frontal 1m Abstand, einzelner Schrank, in ruhiger Umgebung

Waste heat/ Abwärme max. 256Btu/h /max.75W

Mark / Bezeichnung

Connection / Anschluss

Comment / Bemerkung

STD power socket / Netzsteckdose 100-240VAC, 50/60Hz,16A, max. 75W, <1kWh/d

EDV

network connection /

Netzwerkanschluss

(RJ45)

TCP-Ports: 80; 20; 21; 445; 1433; 1034; 37223 UDP-Ports: 80; 1900 LM- authentication for network logons

DL

compressed air supply / Druckluftanschluss

(DIN 13260-2,Profil Nr.2 or open end/hose barb

DN6mm (1/4"))

#015120-#015125, #015760-#015765: #015126-#015131, #015906-#015911:

2-10 bar (29-145 psi)

3.5 CFM (ANR) resp. 0.6 CFM @ 72.5 psi /

100l/min (ANR), bzw. 17 l/min @ 5bar Ø2.2CFM (ANR) / Ø63 l/min (ANR)

5-10 bar (72,5-145 psi) 7 CFM (ANR) resp. 1.2 CFM @ 72.5 psi / 200 l/min (ANR) bzw. 33 l/min @ 5 bar Ø3.3CFM (ANR) / Ø94 l/min (ANR)

ISO 8573-1:2010 min. class 1.4.1 on site supply/bauseitige Leitung min. DN10 connection tube/Anschlussschlauch DN6 max. L=2000

PE

potential earth / Potentialausgleich

(DIN 42801 6mm Plug) 4mm²

E

D

C

B

A

87654321

D

C

B

A en

STATUS:DOCUMENT:

MATERIAL:

UNLESS OTHERWISE SPECIFIED

DIMENSIONS ARE IN MILLIMETERS

TOLERANCES.

DIN ISO 2768-1 class: m DIN ISO 2768-2 class: K

FINISH:

CHECKEDNAMEDATEDESCRIPTIONREV

DATE

QUALITY CONTROL

CHECKED

DRAWN

NAME

A3

DO NOT SCALE DRAWING

TITLE:

DWG NO.

SCALE:

11.08.17Stebner

30 00 20 001

Installation requirements -horizontal storage cabinet

3/11

Klein

WEIGHT: g

09.08.17

Copyright according to ISO 16016 and DIN 34 Passing on and copying of this document, utilization and communication of its contents is not permitted, unless expressly allowed.

Offenders will be liable for compensation.

All rights reserved for IP application.

ISO 128-30

Methode 1

Overview variants / Varianten Übersicht

E

D

C

B

A

87654321

D

C

B

A en

STATUS:DOCUMENT:

MATERIAL:

UNLESS OTHERWISE SPECIFIED

DIMENSIONS ARE IN MILLIMETERS

TOLERANCES.

DIN ISO 2768-1 class: m DIN ISO 2768-2 class: K

FINISH:

CHECKEDNAMEDATEDESCRIPTIONREV

DATE

QUALITY CONTROL

CHECKED

DRAWN

NAME

A3

DO NOT SCALE DRAWING

TITLE:

DWG NO.

SCALE:

11.08.17Stebner

30 00 20 001

Installation requirements -horizontal storage cabinet

4/11

Klein

1:20

WEIGHT: g

09.08.17

Copyright according to ISO 16016 and DIN 34 Passing on and copying of this document, utilization and communication of its contents is not permitted, unless expressly allowed.

Offenders will be liable for compensation.

All rights reserved for IP application.

ISO 128-30

Methode 1

A

A shape fillet radius max. 50mm Hohlkehlen Radius max. 50mm 12

0 110

R520 R52

A-A

DL/STD/EDV/PE

E

D

C

B

A

87654321

D

C

B

A en

STATUS:DOCUMENT:

MATERIAL:

UNLESS OTHERWISE SPECIFIED

DIMENSIONS ARE IN MILLIMETERS

TOLERANCES.

DIN ISO 2768-1 class: m DIN ISO 2768-2 class: K

FINISH:

CHECKEDNAMEDATEDESCRIPTIONREV

DATE

QUALITY CONTROL

CHECKED

DRAWN

NAME

A3

DO NOT SCALE DRAWING

TITLE:

DWG NO.

SCALE:

11.08.17Stebner

30 00 20 001

Installation requirements -horizontal storage cabinet

5/11

Klein

1:20

WEIGHT: g

09.08.17

Copyright according to ISO 16016 and DIN 34 Passing on and copying of this document, utilization and communication of its contents is not permitted, unless expressly allowed.

Offenders will be liable for compensation.

All rights reserved for IP application.

ISO 128-30

Methode 1

420 600

B

B shape fillet radius max. 50mm Hohlkehlen Radius max. 50mm 4

0 110

R5

R

R520

R520

B-B

DL/STD/EDV/PE DL/STD/EDV/PE

Double wing door not possible.

Scanner module collides.

Flügeltüren nicht möglich.

Scanner Module kollidiert.

E

D

C

B

A

87654321

D

C

B

A en

STATUS:DOCUMENT:

MATERIAL:

UNLESS OTHERWISE SPECIFIED

DIMENSIONS ARE IN MILLIMETERS

TOLERANCES.

DIN ISO 2768-1 class: m DIN ISO 2768-2 class: K

FINISH:

CHECKEDNAMEDATEDESCRIPTIONREV

DATE

QUALITY CONTROL

CHECKED

DRAWN

NAME

A3

DO NOT SCALE DRAWING

TITLE:

DWG NO.

SCALE:

11.08.17Stebner

30 00 20 001

Installation requirements -horizontal storage cabinet

6/11

Klein

1:20

WEIGHT: g

09.08.17

Copyright according to ISO 16016 and DIN 34 Passing on and copying of this document, utilization and communication of its contents is not permitted, unless expressly allowed.

Offenders will be liable for compensation.

All rights reserved for IP application.

ISO 128-30

Methode 1

R520

#015120 Endodry os OL #015126 Endodry one-click os OL #015760 endoSTORE BHT os OL #015906 endoSTORE one-click os OL

E

D

C

B

A

87654321

D

C

B

A en

STATUS:DOCUMENT:

MATERIAL:

UNLESS OTHERWISE SPECIFIED

DIMENSIONS ARE IN MILLIMETERS

TOLERANCES.

DIN ISO 2768-1 class: m DIN ISO 2768-2 class: K

FINISH:

CHECKEDNAMEDATEDESCRIPTIONREV

DATE

QUALITY CONTROL

CHECKED

DRAWN

NAME

A3

DO NOT SCALE DRAWING

TITLE:

DWG NO.

SCALE:

11.08.17Stebner

30 00 20 001

Installation requirements -horizontal storage cabinet

7/11

Klein

1:20

WEIGHT: g

09.08.17

Copyright according to ISO 16016 and DIN 34 Passing on and copying of this document, utilization and communication of its contents is not permitted, unless expressly allowed.

Offenders will be liable for compensation.

All rights reserved for IP application.

ISO 128-30

Methode 1

501 49

#015121 Endodry os OR #015127 Endodry one-click os OR #015761 endoSTORE BHT os OR #015907 endoSTORE one-click os OR

E

D

C

B

A

87654321

D

C

B

A en

STATUS:DOCUMENT:

MATERIAL:

UNLESS OTHERWISE SPECIFIED

DIMENSIONS ARE IN MILLIMETERS

TOLERANCES.

DIN ISO 2768-1 class: m DIN ISO 2768-2 class: K

FINISH:

CHECKEDNAMEDATEDESCRIPTIONREV

DATE

QUALITY CONTROL

CHECKED

DRAWN

NAME

A3

DO NOT SCALE DRAWING

TITLE:

DWG NO.

SCALE:

11.08.17Stebner

30 00 20 001

Installation requirements -horizontal storage cabinet

8/11

Klein

1:20

WEIGHT: g

09.08.17

Copyright according to ISO 16016 and DIN 34 Passing on and copying of this document, utilization and communication of its contents is not permitted, unless expressly allowed.

Offenders will be liable for compensation.

All rights reserved for IP application.

ISO 128-30

Methode 1

R520

R520

501 49

#015122 Endodry pt OL/UL #015128 Endodry one-click pt OL/UL #015762 endoSTORE BHT pt OL/UL #015908 endoSTORE one-click pt OL/UL

E

D

C

B

A

87654321

D

C

B

A en

STATUS:DOCUMENT:

MATERIAL:

UNLESS OTHERWISE SPECIFIED

DIMENSIONS ARE IN MILLIMETERS

TOLERANCES.

DIN ISO 2768-1 class: m DIN ISO 2768-2 class: K

FINISH:

CHECKEDNAMEDATEDESCRIPTIONREV

DATE

QUALITY CONTROL

CHECKED

DRAWN

NAME

A3

DO NOT SCALE DRAWING

TITLE:

DWG NO.

SCALE:

11.08.17Stebner

30 00 20 001

Installation requirements -horizontal storage cabinet

9/11

Klein

1:20

WEIGHT: g

09.08.17

Copyright according to ISO 16016 and DIN 34 Passing on and copying of this document, utilization and communication of its contents is not permitted, unless expressly allowed.

Offenders will be liable for compensation.

All rights reserved for IP application.

ISO 128-30

Methode 1

R520

#015123 Endodry pt OR/UL #015129 Endodry one-click pt OR/UL #015763 endoSTORE BHT pt OR/UL #015909 endoSTORE one-click pt OR/UL

E

D

C

B

A

87654321

D

C

B

A en

STATUS:DOCUMENT:

MATERIAL:

UNLESS OTHERWISE SPECIFIED

DIMENSIONS ARE IN MILLIMETERS

TOLERANCES.

DIN ISO 2768-1 class: m DIN ISO 2768-2 class: K

FINISH:

CHECKEDNAMEDATEDESCRIPTIONREV

DATE

QUALITY CONTROL

CHECKED

DRAWN

NAME

A3

DO NOT SCALE DRAWING

TITLE:

DWG NO.

SCALE:

11.08.17Stebner

30 00 20 001

Installation requirements -horizontal storage cabinet

10/11

Klein

1:20

WEIGHT: g

09.08.17

Copyright according to ISO 16016 and DIN 34 Passing on and copying of this document, utilization and communication of its contents is not permitted, unless expressly allowed.

Offenders will be liable for compensation.

All rights reserved for IP application.

ISO 128-30

Methode 1

R520

501 49

#015124 Endodry pt OL/UR #015130 Endodry one-click pt OL/UR #015764 endoSTORE BHT pt OL/UR #015910 endoSTORE one-click pt OL/UR

E

D

C

B

A

87654321

D

C

B

A en

STATUS:DOCUMENT:

MATERIAL:

UNLESS OTHERWISE SPECIFIED

DIMENSIONS ARE IN MILLIMETERS

TOLERANCES.

DIN ISO 2768-1 class: m DIN ISO 2768-2 class: K

FINISH:

CHECKEDNAMEDATEDESCRIPTIONREV

DATE

QUALITY CONTROL

CHECKED

DRAWN

NAME

A3

DO NOT SCALE DRAWING

TITLE:

DWG NO.

SCALE:

11.08.17Stebner

30 00 20 001

Installation requirements -horizontal storage cabinet

11/11

Klein

1:20

WEIGHT: g

09.08.17

Copyright according to ISO 16016 and DIN 34 Passing on and copying of this document, utilization and communication of its contents is not permitted, unless expressly allowed.

Offenders will be liable for compensation.

All rights reserved for IP application.

ISO 128-30

Methode 1

R

#015125 Endodry pt OR/UR #015131 Endodry one-click pt OR/UR #015765 endoSTORE BHT pt OR/UR #015911 endoSTORE one-click pt OR/UR

| 1

USER MANUAL

WASHER-DISINFECTOR

CUSTOMER

REQUIREMENTS

NORTH AMERICA

ENDODRY™

Storage & Drying Sytem

2 |

50098-678-EN Rev E

© 2019 All rights reserved. This publication is protected by copyright. Copying, disclosure to others, or the use of this publication is prohibited without the express written consent of Medivators Inc.

ADVANTAGE PLUS™

is a trademark of Medivators Inc.

DSD EDGE™

is a trademark of Medivators Inc.

ENDODRY™

is a trademark of Medivators Inc.

All other company or product names referenced in this document are trademarks of their respective owner.

Medivators reserves the right to make changes in the specifications shown herein without notice or obligation. Contact your Medivators representative or Medivators customer service for more information.

| 3SITE REQUIREMENTS

This purpose of this document is to provide the facility with requirements to ensure correct installation and subsequent proper performance of the ENDODRY™ Storage and Drying System.

READ THE ENTIRE DOCUMENT.

APPLICABLE DOCUMENTS

• ENDODRY Storage and Drying System User Manual.

Any deviation from these specifications may cause operational issues that would not be covered by the Warranty.

4 |

BY SIGNING BELOW CUSTOMER ACKNOWLEDGES THAT:

1. Customer reviewed these Site Requirements for the ENDODRY™ Storage and Drying System as indicated in this document.

2. The customer assumes complete responsibility for meeting the specifications and requirements set forth in the Site Requirements documentation to ensure proper installation and performance of the ENDODRY Storage and Drying System. Failure of the customer to comply with these Site Requirements and any deviation from the specifications set forth herein may compromise the functionality of the system, and/or may cause operational issues which will not be covered by the Cantel Medical warranty, and are hereby disclaimed by Cantel Medical.

3. The customer assumes complete responsibility for meeting the specifications and requirements set forth in the Site Requirements documentation by the agreed upon installation date between the Customer and Cantel Medical. If the Cantel Medical installation team encounters any delays due to site requirements not meeting specifications and requirements, the Customer will be charged Medivators current rates for stand-by fees, until the site requirements are met and installation activity resumes; or, if it is determined that the delay results in rescheduling the installation to a later date, the Customer will be charged for all expenses at current Medivators rates (flights, lodging, and car rental, if applicable), and travel and labor time related to the return installation dispatch.

4. If installation is canceled or moved 48 hours prior to the agreed upon installation date, no fee will be charged.

5. For customers who request or accept Medivators space planning suggestions for the site prior to installation (“Space Planning Services”), Customer agrees that the Disclaimer, indicated in this document on Page 9, will apply to such Space Planning Services.

Customer Representative

Title

Signature Date Email

| 5

AIR SUPPLY

1. Quality: ISO 8573-1:2010 class 1.2.1

• Particle Size: Incoming air filtered down to <1 micron in size.

• Moisture Content: Pressure dew point (PDP) of -40°C or better required and no liquid water.

• Oil Content: < 0.01mg of oil per cubic meter of compressed air (liquid, aerosol or vapor oil).

2. Pressure: The below pressures are required at the point of cabinet connection. Facility should consult with their Maintenance Department or their qualified air vendor to identify potential issues with the air supply.

• ENDODRY™ Cabinet for ADVANTAGE PLUS™ Endoscope Reprocessor: 58-145 psi (4-10 bar).

• ENDODRY Cabinet for DSD EDGE™ Automated Endoscope Reprocessor: 72-145 psi (5-10 bar).

3. Volume: The below volumes are required at the point of cabinet connection.

• ADVANTAGE PLUS Endoscope Reprocessor/ENDODRY Cabinet: Minimum requirement of 4.2 scfm (120 l/min ANR) per cabinet.

• DSD EDGE Automated Endoscope Reprocessor/ENDODRY Cabinet: Minimum requirement of 7 scfm (200 l/min ANR) per cabinet.

4. Flexible Air Hose: A 5 foot (1.5 Meter) line is included with each cabinet.

• One end will be pre-configured to connect to ENDODRY™ Drying Cabinet.

• Open end will be ¼” or 6mm inner diameter and it is the responsibility of the facility to make that connection to their air supply line.

The compressors listed below are suggestions that the facility can purchase directly from either the compressor manufacturer or authorized dealer. Medivators is not responsible for air compressor warranty, service and maintenance.

ADVANTAGE HOOKUPS DSD HOOKUPS

# of Cabinets

BeaconMedaes (Requires Additional Dryer)

Powerex (w/ Dryer)

# of Cabinets

BeaconMedaes (Requires Additional Dryer)

Powerex (w/ Dryer)

1 LES03-145T-RD-xxx SES0308TM** 1 LES05-145T-RD-xxx SES0508TM**

2 LES05-145T-RD-xxx SES05058TM** 2 LES10-145RD LSE1504

3 LES07-145T-RD-xxx LSE1504 3 LES15-145RD LSE1504

4 LES07-145T-RD-xxx LSE1504 4 LES20-145RD LSE2005

5 LES15-145RD LSE1504 5 LES20-145RD LSE2005

6 |

ELECTRICAL SUPPLY

• 100-240 VAC ± 10%, single phase, 50/60 Hz, 15 amp circuit (120v), 10 amp circuit (230v).

• Power input: 75W

• A NEMA 5-15 power cord for the North America market and a CEE 7 power cord for the European market is included with the ENDODRY™ Storage and Drying System. The cord is approximately 6 feet (1.8 meters) in length.

• A GFI/RCD protected outlet located on the wall above the ENDODRY Storage and Drying System, see Floor & Wall Section.

• Medivators equipment must be on dedicated circuits.

NETWORKING

• The ENDODRY Storage and Drying System is a networkable piece of equipment and has the capabilities to communicate to other Medivators technologies via a LAN interface (RJ45, 10/100 Mbit).

• A 6.5 foot (2 meter) cable is included with the cabinet.

• A RJ45 wall mounted network jack located on the wall above the ENDODRY Storage and Drying System, see Floor & Wall section.

DIMENSIONS

Shipping Dimensions

• Crate Dimensions: H84”x W47”x D31”

• Crate Weight: 583 lbs.

Reprocessor Dimensions

• Dimensions: H74.8” X W23.6” X D21.3”

• Weight: 375 lbs (170 kg)

FLOOR & WALL

• The floor must be level.

• For optimal user-safety and operation, it is recommended that the ENDODRY Storage and Drying System always be placed directly on the floor, and not on an elevated platform.

• The back of the one-sided ENDODRY Storage and Drying System will be placed flush against the wall. All electrical, network and air connections must be placed a minimum of 78.7 inches (200 cm) off of the floor above the cabinet.

• The two-sided ENDODRY Storage and Drying System is designed to fit into an opening in the wall. The rough opening for a single unit is H75.2” X W24” (191cm x 61cm). All electrical, network and air connections must be placed a minimum of 78.7 inches (200 cm) off of the floor above the cabinet. The electrical, network and air connections must be located on the loading side of the ENDODRY Storage and Drying System.

| 7

.6

21.3"

41.7"

EN

D

O D

R Y

St or ag e an d

D ry in g

Sy st em

TM

El ec tri ca l C on ne ct io n

Ai r C on ne ct io n

N et w or k C on ne ct io n

2 3

O ne

-S id ed V er si on

C 3D

V ie w

M in im um fa ci lit y w al l c on ne ct io ns he ig ht is

8.

7” fr om fl oo r.

O pt io ns fo r D oo rs

O pe n Le ft -O

L O pe n

R ig ht -O

R

B To p Vi ew

A Fr on t 3

D V ie w

.6

.3

3.

9” w w w .e nd oi nf ec tio np re ve nt io n.

co m to d ow nl oa d th e R ev it fil e.

Fo r c la rif ic at io n an d/ or q ue st io ns pl ea se c on ta ct T ec hn ic al

S up po rt at

.8

.4

.4

9.

4.5”12” 4.8”

1 3

.8

8 |

62.2"

21.3"

.6

EN

D

O D

R Y

St or ag e an d

D ry in g

Sy st em

TM

El ec tri ca l C on ne ct io n

Ai r C on ne ct io n

N et w or k C on ne ct io n

2 3

Tw o-

Si de d Ve rs io n (P as s-

Th ru

O pt io ns fo r D oo rs

O pe n Le ft/ O pe n

Le ft

-O

LU

L O pe n

R ig ht /O pe n

Le ft

-O R

U L

O pe n Le ft/ O pe n

R ig ht

O

LU

R O pe n

R ig ht /O pe n

R ig ht

O R

U R

B To p Vi ew

A Fr on t 3

D V ie w

W et

S id e

D ry

S id e

W et

S id e

C 3D

V ie w

W et

S id e D ry S id e

1 3

3.

9"

M in im um fa ci lit y w al l c on ne ct io ns he ig ht is

8.

7” fr om fl oo r.

*M ea su re m en t u si ng a

” w al l.

4.5” 12”4.8”

.6

*1

5.

3"

.8 w w w .e nd oi nf ec tio np re ve nt io n.

co m to d ow nl oa d th e R ev it fil e.

Fo r c la rif ic at io n an d/ or q ue st io ns pl ea se c on ta ct T ec hn ic al

S up po rt at

.8

.4

.4

9.

| 9

SPACE-PLANNING SERVICES

For customers who request or accept Medivators space planning suggestions for the site prior to installation (“Space Planning Services”), Customer agrees that the following Disclaimer will apply to such Space Planning Services:

CUSTOMER ACKNOWLEGES AND ACCEPTS THAT SPACE PLANNING SERVICES ARE OFFERED AND

PROVIDED “AS IS” WITH NO REPRESENTATION OR WARRANTY, EXPRESS OR IMPLIED, OF ANY KIND WHATSOEVER, INCLUDING, WITHOUT LIMITATION, ANY WARRANTIES OR REPRESENTATIONS AS TO THE ADEQUACY OF ANY DESIGN, MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE, OR THAT ANY OF THE SERVICES WILL MEET CUSTOMER’S NEEDS OR REQUIREMENTS OR BE CAPABLE OF IMPLEMENTATION.

IN NO EVENT SHALL MEDIVATORS BE LIABLE TO CUSTOMER OR ANY THIRD PARTY FOR LOSS OF PROFITS, LOSS OF USE, OR ANY DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES OF ANY KIND, WHETHER OR NOT A PARTY WAS, IS, OR SHOULD BE AWARE OF SUCH LOSS OR DAMAGES.

CUSTOMER AGREES THAT IT WILL RELY ON, USE AND OR OTHERWISE EMPLOY ARCHITECTS, ENGINEERS, CONSTRUCTION PROFESSIONALS AND OTHER VENDORS OR SERVICE PROVIDERS (COLLECTIVELY, “PROJECT PROFESSIONALS”) REGARDING THE FEASIBILITY OR IMPLEMENTATION OF ANYSPACE PLANNING SERVICES PROVIDED BY MEDIVATORS. By accepting the Space Planning Services, (i) Customer agrees to hold Medivators and its affiliates entirely free from any liability, including financial responsibility, for all claims, losses, damages, suits, actions, costs, liabilities, or expenses incurred by Customer or its agents or affiliates as a result of any design defect, any requirement of corrective or other action or its use, reliance on, modification or implementation of any of the Space Planning Services; (ii) Customer acknowledges that Medivators is not a licensed architect or engineer or otherwise in the business of construction or space design and Customer accepts the risks involved in using such Space Planning Services from Medivators; and (iii) Customer agrees to communicate to the Project Professionals the content of all the Space Planning Services including, without limitation, all designs and plans, specifications and attachments, and to have such Project Professionals check, review, verify and approve such content prior to incorporating, using or otherwise implementing any Space Planning Service.

10 |

ENDODRY™ STORAGE AND DRYING SYSTEM

PRE-SITE REQUIREMENTS CHECKLIST

INITIAL AND SIGN AT THE TIME OF PRE-SITE INSPECTION

Customer Site Requirements Criteria Initials

ENDODRY™ Cabinet for ADVANTAGE PLUS™ Endoscope Reprocessor provides air supply of 58-145 psi (4-10 bar).

ENDODRY Cabinet for DSD EDGE™ Automated Endoscope Reprocessor provides air supply of 72-145 psi (5-10 bar).

Air supply provides a flow rate of 4.2 scfm (120 l/min ANR) for the Advantage and 7 scfm (200 l/min ANR) for the DSD.

Air supply maximum particle size is <1 micron, maximum dew point is -40°C, maximum oil content is 0.01 mg/m3.

Air Supply plumbed to the wall a minimum of 78.7 inches (200 cm) off of the floor above the cabinet.

GFI/RCD protected outlet located on the wall a minimum of 78.7 inches (200 cm) off of the floor above the cabinet.

RJ45 wall mounted network jack located on the wall a minimum of 78.7 inches (200 cm) off of the floor above the cabinet (ENDODRY™ Cabinet for ADVANTAGE PLUS™ Endoscope Reprocessor only).

Installation site has a level floor.

Installation site accommodates the dimensions of H74.8” x W23.6” x D21.3” (190cm x 60cm x 54cm)

Customer Site

Customer Representative

Title

Signature Date Email

Serial #

Serial #

Serial #

Serial #

Serial #

Serial #

Medivators Customer and Technical Support: Toll Free: 1-800-444-4729 · FAX: 1-866-421-7696

Medivators BV Sourethweg 11 6422PC Heerlen The Netherlands Tel: +31.45.5.471.471

Cantel Medical Asia/Pacic Pte. Ltd.

1A International Business Park #05-01 Singapore 609933 Tel: +65.6227.9698 www.medivators.com

Medivators Inc.

14605 28th Avenue North Minneapolis, MN 55447 USA Toll Free: +1.800.444.4729

ESCAD Medical GmbH Zur Ohmdwiesen 5 88633 Heiligenberg Germany Tel: +49.7554.9999.500 Fax: +49.7554.9999.558

METHOD #2

METHOD #1

41 [1041]

WALL OPENING

'A'

39-3/8 [1000]

UNIT WIDTH

89-1/16 [2263]

UNIT

HEIGHT

31-1/2 [800]

LOAD HT.

4 [102] TO 8 [203]

WALL THICKNESS

90-1/2 [2299]

WALL

OPENING

5-13/16 [148]

TRIM ZONE

TYP

5-7/16 [137]

TRIM ZONE

SERVICE AREA

SEE NOTE 4

'B'

CHAMBER LENGTH UNIT LENGTH - DIM. 'A'

MINIMUM SERVICE AND LOAD AREA - DIM. 'B'

WITHOUT ALUS WITH ALUS

39" [991] 52-1/8" [1324] 78" [1981] 147-1/16" [3735]

51" [1295] 64-1/16" [1627] 102" [2591] 182-7/8" [4645]

63" [1600] 75-9/16" [1919] 126" [3200] 218-11/16" [5555]

T I T L E

EQUIPMENT DRAWING, AMSCO 600 , 26.5" X 26.5" X 39", 51", & 63" LG.

SLIDING, SD, RECESSED WALL, FACILITY STEAM HEAT

Corporation

SIZE: SCALE: DRAWN BY: DRAWING NUMBER: PART NUMBER: REVISION:

A - Basch, Tyler 10307698 11001835 H

This document contains confidential and proprietary information of STERIS Corporation. Neither this document nor the information herein are to be reproduced, either in part or in whole, except as specifically authorized by STERIS Corporation.

SHEET

NOTES

1. THE FLOOR AREA (IN SERVICE CLEARANCE ARES) MUST BE SMOOTH AND HAVE A LEVEL TOLERANCE WITHIN ±1/2 deg OR ±1/16" PER FOOT, WITHOUT ANY OBSTRUCTIONS SUCH AS PIPING: WIRING, FLOOR SINKS, ETC.

2. SERVICE AND LOADING AREAS CLEARANCE OF UNIT SHOULD BE AT UNIT WIDTH.

3. SERVICE AREA SHOWN ARE SOLELY REPRESENTATION OF THE SPACE NEEDED TO SAFELY PERFORM PREVENTATIVE MAINTENANCE AND REPAIRS SERVICES. CUSTOMER IS RESPONSIBLE TO ENSURE CLEARANCE MEET OR EXCEED LOCAL AND NATIONAL CODE REQUIREMENTS. ADHERENCE TO LOCAL AND NATIONAL CODES AND PROCUREMENT OF PERMITS

ARE THE RESPOSIBILITY OF THE CUSTOMER UNLESS AGREED TO IN WRITING WITH STERIS.

4. PROVIDE SERVICE ACCESS FROM BACK OF UNIT IF EQUIPPED WITH FOLLOWING ACCESSORIES:

a. 30" [760] IF EQUIPPED WITH STERI-GREEN PLUS.

b. 18" [460] IF EQUIPPED WITH STERI-GREEN.

5. ZERO CLEARANCE NEEDED OUTSIDE OF SERVICE AND LOADING AREAS.

6. ALUS EQUIPMENT DRAWING P/N: 11028378.

7. LOADING EQUIPMENT CART AND TRANSFER CARRIAGE EQUIPMENT DRAWING P/N: 11012876.

8. ALL DIMENSIONS ARE INCHES AND MILLIMETERS [MM].

TOP VIEW

NO CLEARANCE

NEEDED ON SIDES

OF STERILIZER

NO CLEARANCE

NEEDED ON REAR

EXCEPT AS NOTED

ON NOTE 4

FRONT VIEW

SERVICE ACCESS

DOOR

SIDE VIEW

FINISHED

FLOOR

FINISHED

WALL

12-7/8 [327]

21-1/4 [540]

28-15/16 [735]

34-1/16 [865]

36-13/16 [935]

3-3/4 [95]

76-3/4 [1949]

2-15/16 [75]

CW COLD WATER

S STEAM

D DRAIN

A COMPRESSED AIR

T I T L E

EQUIPMENT DRAWING, AMSCO 600 , 26.5" X 26.5" X 39", 51", & 63" LG.

SLIDING, SD, RECESSED WALL, FACILITY STEAM HEAT

Corporation

SIZE: SCALE: DRAWN BY: DRAWING NUMBER: PART NUMBER: REVISION:

A - Basch, Tyler 10307698 11001835 H

This document contains confidential and proprietary information of STERIS Corporation. Neither this document nor the information herein are to be reproduced, either in part or in whole, except as specifically authorized by STERIS Corporation.

SHEET

TOP VIEW

CW

S

A

D

CW-S-A

D

FRONT VIEW

CW

D

S

A

SIDE VIEW

4-1/4 [108]

5-9/16 [142]

19-3/16 [487]

87-5/8 [2226]

17-3/4 [451]

T I T L E

EQUIPMENT DRAWING, AMSCO 600 , 26.5" X 26.5" X 39", 51", & 63" LG.

SLIDING, SD, RECESSED WALL, FACILITY STEAM HEAT

Corporation

SIZE: SCALE: DRAWN BY: DRAWING NUMBER: PART NUMBER: REVISION:

A - Basch, Tyler 10307698 11001835 H

This document contains confidential and proprietary information of STERIS Corporation. Neither this document nor the information herein are to be reproduced, either in part or in whole, except as specifically authorized by STERIS Corporation.

SHEET

E STERILIZER ELECTRIC

N NETWORK

TOP VIEW

SIDE VIEWFRONT VIEW

E N

E N

N E

25-5/16 [644]

20-5/8 [524]

26-5/8 [676,4]

T I T L E

EQUIPMENT DRAWING, AMSCO 600 , 26.5" X 26.5" X 39", 51", & 63" LG.

SLIDING, SD, RECESSED WALL, FACILITY STEAM HEAT

Corporation

SIZE: SCALE: DRAWN BY: DRAWING NUMBER: PART NUMBER: REVISION:

A 1/40 Basch, Tyler 10307698 11001835 H

This document contains confidential and proprietary information of STERIS Corporation. Neither this document nor the information herein are to be reproduced, either in part or in whole, except as specifically authorized by STERIS Corporation.

SHEET

JKR JACKET RELIEF VALVE

DISCHARGE PIPE - 1-1/8 ODT

CHR CHAMBER RELIEF VALVE

DISCHARGE PIPE - 1-1/8 ODT

IMPORTANT: FOR OPTIMAL INSTALLATION, COMPRESSED AIR,

WATER, STEAM, NETWORK, & POWER UTILITIES SHOULD BE

SUPPLIED BY CUSTOMER FROM ABOVE THE UNIT IN THE

LOCATION INDICATED ON THE DRAWING. CONSULT WITH

STERIS IF A DEVIATION IS REQUIRED.

TOP VIEW

(FRONT OF UNIT)

RIGHT SIDE VIEWLEFT SIDE VIEW

INCOMING MECHANICAL

UTILITIES LOCATIONINCOMING ELECTRICAL

UTILITIES LOCATION

JKR

CHR

JKR

CHR

MECHANICAL

UTILITY REQUIREMENTS CHART

UTILITY PARAMETER SPECIFICATIONS NOTES

STERILIZER

COLD WATER

(CW)

SEE NOTE 11

CONNECTION SIZE/TYPE 3/4" NPT

INSTALLATION SPECIFICATIONS:

1. PIPE SIZES LISTED UNDER PLUMBING REQUIREMENTS

INDICATE THE EQUIPMENT TERMINATION SIZES ONLY.

SIZE PIPING TO EQUIPMENT DEPENDING ON LENGTH OF

PIPE RUN FROM PRESSURE REGULATING STATION FOR

THE STEAM LINE AND MAIN WATER HEADERS. SUPPLY

THE SPECIFIED SERVICE PRESSURE AND FLOW RATE AT

EQUIPMENT TERMINALS, INCLUDE EFFECT OF COINCIDENT

DRAW OF MULTIPLE UNIT INSTALLATIONS.

2. DOOR OPENING DURING PRE-INSTALLATION SHALL BE AT

MINIMUM 80"x40" [2032mm x 1016mm] (HxW).

3. PROVIDE PIPING, SHUTOFF VALVE, PIPE PLUGGED TEE,

AND UNION IN STEAM AND WATER SUPPLY CONNECTIONS

BETWEEN EQUIPMENT AND STUB OUTS. PLUGGED TEE

CAN LATER BE USED FOR TEST PRESSURE GAUGE

CONNECTION. ARRANGE CONNECTION PIPING TO ALLOW

ACCESS TO MACHINE…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .