About this file

36C25219B0056 0003 S06 - FX104 - FIRE SPRINKLER SYSTEM RISER FLOOR 3 AND ATTIC PLAN.pdf

View the file

Other files

File Type Posted
36C25219C0222-000.docx DOCX document
36C25219B0056-0005000.docx DOCX document
36C25219B0056-0004002.pdf PDF
36C25219B0056-0004000.docx DOCX document
36C25219B0056-0004001.pdf PDF
36C25219B0056-0003007.pdf PDF
36C25219B0056-0003008.pdf PDF
36C25219B0056-0003001.pdf PDF
36C25219B0056-0003003.pdf PDF
36C25219B0056-0003004.pdf PDF
36C25219B0056-0003005.pdf PDF
36C25219B0056-0003020.pdf PDF
36C25219B0056-0003015.pdf PDF
36C25219B0056-0003013.pdf PDF
36C25219B0056-0003014.pdf PDF
36C25219B0056-0003019.pdf PDF
36C25219B0056-0003012.pdf PDF
36C25219B0056-0003017.pdf PDF
36C25219B0056-0003016.pdf PDF
36C25219B0056-0003011.pdf PDF
36C25219B0056-0003009.pdf PDF
36C25219B0056-0003010.pdf PDF
36C25219B0056-0003018.pdf PDF
36C25219B0056-0003002.pdf PDF
36C25219B0056-0003000.docx DOCX document
36C25219B0056-0002001.pdf PDF
36C25219B0056-0002000.docx DOCX document
36C25219B0056-0002002.pdf PDF
36C25219B0056-0001000.docx DOCX document
36C25219B0056-001.docx DOCX document
36C25219B0056-002.pdf PDF
36C25219B0056-005.pdf PDF
36C25219B0056-004.pdf PDF
36C25219B0056-003.pdf PDF
36C25219B0056-006.pdf PDF
36C25219B0056-000.docx DOCX document
36C25219B0056-000.docx DOCX document
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

WING A WING B WING C WING D

SYSTEM C

COVERAGE

SYSTEM A

COVERAGE

SYSTEM B

COVERAGE

SYSTEM B

COVERAGE

SYSTEM A

COVERAGE

SYSTEM C

COVERAGE

SYSTEM D

COVERAGE

SYSTEM D

COVERAGE

SYSTEM C

COVERAGE

SYSTEM B

COVERAGE

SYSTEM B

COVERAGE

SYSTEM C

COVERAGE

SYSTEM A

COVERAGE

SYSTEM B

COVERAGE

SYSTEM A

COVERAGE

SYSTEM B

COVERAGE

SYSTEM B

COVERAGE

SYSTEM C

COVERAGE

SYSTEM B

COVERAGE

SYSTEM C

COVERAGE

SYSTEM C

COVERAGE

SYSTEM D

COVERAGE

SYSTEM C

COVERAGE

SYSTEM D

COVERAGE

UNHEATED ATTIC TO BE

PROTECTED VIA WING A DRY

SYSTEM RISER.

UNHEATED ATTIC TO BE

PROTECTED VIA WING C DRY

SYSTEM RISER.

UNHEATED ATTIC TO BE

PROTECTED VIA WING C DRY

SYSTEM RISER.

UNHEATED ATTIC TO BE

PROTECTED VIA WING C DRY

SYSTEM RISER.

UNHEATED ATTIC ABOVE

CORRIDOR TO BE PROTECTED

VIA DRY BARREL UPRIGHT

SPRINKLERS FROM WET PIPE

BELOW

UNHEATED ATTIC ABOVE

CORRIDOR TO BE PROTECTED

VIA DRY BARREL UPRIGHT

SPRINKLERS FROM WET PIPE

BELOW

UNHEATED ATTIC ABOVE

CORRIDOR TO BE

PROTECTED VIA DRY

BARREL UPRIGHT

SPRINKLERS FROM WET PIPE

BELOW

UNHEATED ATTIC

ABOVE CORRIDOR

TO BE PROTECTED

VIA DRY BARREL

UPRIGHT

SPRINKLERS FROM

WET PIPE BELOW

UNHEATED ATTIC TO BE

PROTECTED VIA WING C DRY

SYSTEM RISER.

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked By:

Building Number

Project Number

Drawing Number

Drawn By:

Revisions: Date

ARCHITECT/ENGINEERS:

CLEMENT J. ZABLOCKI VAMC

#6 o n e e i g h t h i n c h o n e f o o t t h r e e i n c h e s o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t o n e i n c h o n e f o o t t h r e e q u a r t e r s i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number 695-16-112

FIRE SPRINKLER ENGINEER

RTM CONSULTANTS, INC

6640 Parkdale Place, Suite J, Indianapolis, IN 46254

PHONE: (317) 329-7700

905 N. CAPITOL AVE. SUITE 100 INDIANAPOLIS, IN. 46204

317.800.6388 WWW.GUIDONDESIGN.COM

SUSTAINABLE ARCHITECTURE + ENGINEERING

PROJECT LEAD

Architect, Structural Engineer, Civil Engineer

CLEMENT J. ZABLOCKI VA MEDICAL CENTER

MILWAUKEE, WISCONSIN

C :\U se rs

\k al le n\

D oc um en ts \1

4.

.0

Bl dg .S pr in kl er

R ep la ce m en t 6

-1 6-

2_ ka lle n_ ka lle n.

rv t

FX104

FDCMC

FIRE SPRINKLER SYSTEM RISER

FLOOR 3 AND ATTIC PLAN

14.1020.06BUILDING 6 FIRE

SPRINKLER REPLACEMENT

SCALE: 1/16" = 1'-0"FX104

1 FIRE SPRINKLER SYSTEM RISER ATTIC PLAN

N

SCALE: 1/16" = 1'-0"FX104

3 FIRE SPRINKLER SYSTEM RISER FLOOR 3 PLAN, SOUTH

SCALE: 1/16" = 1'-0"FX104

2 FIRE SPRINKLER SYSTEM RISER FLOOR 3 PLAN, NORTH

SEE SHEETS FX101-FX103 FOR ADDITIONAL GENERAL NOTES, REQUIREMENTS,

AND INFORMATION.

GENERAL INSTALLATION NOTES :

SEE SHEET GI204 FOR APPROXIMATE COVERAGE AREAS OF EACH PHASE.

1. PROVIDE AND INSTALL NEW WET RISER FOR EACH WING

IN STAIRWELL LANDING CORNER TIGHT TO WALLS TO

MINIMIZE OBSTRUCTION. SUPPLY STAIRWELL

SPRINKLERS FROM MAIN RISER. SUPPLY EACH FLOOR

WITH BRANCH FROM RISER.

2. PROVIDE AND INSTALL NEW DRY RISER FOR EACH WING

IN STAIRWELL LANDING CORNER TIGHT TO WALLS TO

MINIMIZE OBSTRUCTION. SUPPLY BALCONY AND ATTIC

AREAS AS INDICATED.

3. ATTIC ACCESS LOCATED IN STAIRWELL.

4. ATTIC ACCESS THROUGH CEILING SCUTTLE.

CONTRACTOR RESPONSIBLE FOR PROVIDING

SCAFFOLDING OR LADDER AS REQUIRED FOR SAFE

ACCESS.

5. PROVIDE VALVE FOR DRY SYSTEM TEST. ROUTE TO

ALLOW FULL FLOW WITH NO WATER DAMAGE OR

WETTING OF WALKING OR DRIVING SURFACES.

6. PROVIDE A SINGLE AIRVENT IN ACCORDANCE WITH

NFPA 13 (2016) NEAR A HIGH POINT IN THIS SYSTEM.

7. BUILDING EXCEEDS 2 STORIES. PROVIDE CONTROL

VALVE ASSEMBLY FOR EACH FLOOR PER NFPA 13.

FIRE SPRINKLER SYSTEM PLAN NOTES:

SPRINKLER DESIGN DENSITY

OCCUPANCY CLASSIFICATION

DESIGN

DENSITY

(GPM/FT2)

DESIGN

AREA (FT2)

HOSE STREAM

ALLOWANCE

(GPM)

DURATION OF

SUPPLY

(MINUTES)

LIGHT HAZARD 0.10 1,500 2 100 30

ORDINARY HAZARD - GROUP 1 0.15 1,500 2 250 60

ORDINARY HAZARD - GROUP

2 0.20 1,500 2 250 60

DRY PIPE SYSTEM 1 0.10 1,950 1 100 30

NOTES:

1. 30% DESIGN AREA INCREASE FOR DRY PIPE SYSTEMS.

2. DESIGN AREA REDUCTION FOR QUICK RESPONSE SPRINKLERS PERMITTED PER NFPA 13

11.2.3.2.3.1

3. DRY PIPE SYSTEMS SHALL COMPLY WITH SECTION 7.2.3.4.OF NFPA 13.

BID DOCUMENTS

* ALL AREAS SHALL BE LIGHT HAZARD UNLESS OTHERWISE NOTED.

COR : MATTHEW OSGOOD

5/20/2019

ACCOMPANYING 36C25219B0056 0003